HomeMy WebLinkAboutLL 05 of 2021 Energy Code Supplement Add Chapter 144 - ECS ONLY TOWN OF ITHACA CODE CHAPTER 144
ENERGY CODE SUPPLEMENT
Explanatory Note - Two documents work together:
• ECS
o A local energy code supplement with requirements above and beyond
the Energy Conservation Construction Code of New York State
o Town of Ithaca and City of Ithaca versions contain nearly identical local
energy code requirements and standards
• ECS Reference Manual
o Contains non-essential information to help understand and use the ECS,
such as background information and commentary
Energy Code Supplement(ECS) -Adopted 2021-06-14
Section 144-1 TITLE, PURPOSE, AND FINDINGS
SUBSECTION 144-101 TITLE, PURPOSE AND OBJECTIVES
].44 3.. 1...a.. ...itll
......................................................................................................
This Chapter 144 of the Code of the Town of Ithaca shall be known as the "Energy Code Supplement"
(ECS).
The purpose of this chapter is to promote the public health, safety, and general welfare by establishing a
local energy code supplement for all new construction, certain additions, and MAJOR RENOVATIONS, with
requirements above and beyond the state energy code that will become more stringent overtime.
The objectives of this chapter are to: (1) deliver measurable, immediate, and long-lasting reductions in
GREENHOUSE GAS(GHG)emissions from all new construction,certain additions,and MAJOR RENOVATIONS; (2)
advance best practices in the design of affordable buildings that deliver reduced GHG emissions; and (3)
provide a rapid but orderly transition to buildings that do not use FOSSIL FUELS on-site for major building
energy needs, such as space heating and hot water heating, by 2026. The requirements set forth give
priority to electrification, renewable energy, and affordability. Requirements for reductions in GHG
emissions go into effect in three steps: 2021, 2023, and 2026.
SUBSECTION 144-102 FINDINGS
The Town of Ithaca Town Board finds that:
A. Climate change is causing an increase in extreme weather events, such as storms, flooding, and
heat waves that threaten human life, healthy communities,and critical infrastructure in the TOWN,
New York State, and across the world.
B. There is a clear emerging international consensus that to avoid the most severe impacts of a
changing climate,global warming should be limited to 1.5 degrees Celsius.
C. GHG emissions related to human activity are the main cause of global warming. Buildings within
the Town of Ithaca are the most significant contributor to local GHG emissions, responsible for
more than half of all community GHG emissions.
D. The TOWN Board unanimously adopted the TOWN'S Green New Deal on March 23, 2020, which
sets forth a goal to achieve an equitable transition to carbon-neutrality community-wide by 2030.
Energy Code Supplement(ECS) -Adopted 2021-06-14 1
E. New York State,through its Climate Leadership and Community Protection Act, has set ambitious
goals to combat climate change through GHG reduction. State goals are in line with many of the
objectives of the Energy Code Supplement, including reducing emissions in buildings, electrifying
space heating, water heating, and cooking systems, increasing the use of renewable energy, and
reducing the use of FOSSIL FUELS.
F. The combustion of FOSSIL FUELS in homes and other buildings decreases internal air quality and has
adverse impacts on human health.
G. For new buildings, the most affordable and cost-effective time to reduce GREENHOUSE GAS
emissions is during the design and construction phases of a project, rather than at a time of later
retrofit.
Energy Code Supplement(ECS) -Adopted 2021-06-14 2
Section 144-2 SCOPE AND APPLICATION
SUBSECTION 144-201
.1.44 2 '1...a.3.
....................................................................
Pursuant to section 11-109 of the New York State Energy Law, and subject to the provisions and
requirements of that section, the Town of Ithaca has the power to promulgate a local energy
conservation construction code that is more stringent than the Energy Conservation Construction Code
of New York State (ECCCNYS).
..44 2 '1 d2
....................................................................
This ECS provides requirements and standards that are in addition to, and shall supplement, the
requirements and standards set forth in the ECCCNYS and in Chapter 125, Building Construction and Fire
Prevention, of the Code of the Town of Ithaca. The plans, specifications, and other materials required by
the Code Enforcement Officer relating to the ECS-related components of the building, structure, and/or
property, shall be submitted to the Code Enforcement Officer in conjunction with an application for a
building permit pursuant to said Chapter 125 and pursuant to Chapter 270, Zoning, of the Code of the
Town of Ithaca.
.I.4.4......2. .1......3.
The TOWN shall enforce this chapter in addition to the TowN's enforcement of the ECCCNYS. Chapter 125,
Building Construction and Fire Prevention, of the Code of the Town of Ithaca sets forth the method for
administration and enforcement of the ECS and establishes powers, duties and responsibilities in
connection therewith, including penalties and other remedies for violations of the ECS.
..44 2 '1 4.
....................................................................
Except as specified in this chapter,this chapter shall not be used to require the removal, alteration or
abandonment of, nor prevent the continued use and maintenance of, an existing building or building
system lawfully in existence at the time of adoption of this chapter.
SUBSECTION 144-202 APPLICABILITY
Beginning on the COMPLIANCE DATE,the requirements of this Energy Code Supplement shall apply to the
following construction:
A. All new construction, excluding additions and renovations that are not specified in this list
B. All additions 500 square feet or larger to single family dwellings or two-family dwellings
Energy Code Supplement(ECS) -Adopted 2021-06-14 3
C. All additions 1,000 square feet or larger to buildings other than single family dwellings or two-
family dwellings
D. All MAJOR RENOVATIONS, as defined in Section 144-3.
Exceptions to 144-202.1 Applicability
A. The requirements of the ECS shall not apply to construction that does not include directly
heated space.
B. The requirements of the ECS shall not apply to AGRICULTURAL BUILDINGS, including barns, sheds,
poultry houses and other buildings and equipment on the premises that are used directly and
solely for agricultural purposes.
C. The requirements of the ECS shall not apply to construction for which all necessary building
permits have been issued prior to the COMPLIANCE DATE.
D. The requirements of the ECS shall not apply to construction for which completed applications
for all necessary building permits have been submitted prior to the COMPLIANCE DATE, if such
applications are diligently prosecuted to conclusion.
1. For the purposes of this subsection only, a building permit application shall be
deemed "completed" if all other necessary approvals,including but not limited to site
plan, subdivision, special approval, special permit, and variance have been received
prior to the COMPLIANCE DATE, and if the building permit application contains all
required information, materials, and fees normally and reasonably required by the
Code Enforcement Officer to commence their building permit review process.
2. A building permit application shall be deemed "diligently prosecuted to conclusion"
if the applicant promptly responds to any inquiries and promptly supplies any
additional information reasonably required by the Code Enforcement Officer,and the
applicant otherwise cooperates so as to permit and enable the Code Enforcement
Officer to adequately and completely review the application and render a decision on
same within a reasonable period of time of its submission, and in any event within
three months of its submission.
Code compliance as applied to types of buildings:
A. COMMERCIAL BUILDINGS shall meet the provisions of Section 144-4, Commercial Building Provisions.
B. RESIDENTIAL BUILDINGS shall meet the provisions of Section 144-5, Residential Building Provisions.
C. MIXED-USE BUILDINGS where more than 50% of the heated FLOOR AREA is residential shall meet the
requirements for RESIDENTIAL BUILDINGS set forth in Section 144-5. MIXED-USE BUILDINGS where 50%
or more of the HEATED FLOOR AREA is commercial shall meet the requirements for COMMERCIAL
BUILDINGS set forth in Section 144-4. In MIXED-USE BUILDINGS, the whole building shall comply with
all applicable requirements; no portion is exempt from requirements.
D. Additions —The applicant shall demonstrate compliance for additions in either of the following
two ways:
Energy Code Supplement(ECS) -Adopted 2021-06-14 4
1. Independent of the existing building: All applicable requirements shall be met for the
addition alone, without considering the existing building. If the addition is complying
independent of the existing building, then all references to "building" in Sections 144-4,
144-5 and 144-6 shall refer to the addition.
2. Together with the existing building: All applicable requirements shall be met for the
addition and the existing building together, as a whole. If the addition is complying
together with the existing building, then all references to "building" in Sections 144-4,
144-5, and 144-6 shall refer to the addition and the existing building together.
E. In MAJOR RENOVATIONS, the whole building, including space outside of the WORK AREA, shall comply
with all applicable requirements.
Energy Code Supplement(ECS) -Adopted 2021-06-14 5
�����^���� � �� �� K����U��U-�U�����
��.."~u�... . '�~��r—.� DEFINITIONS
SUBSECTION 144-3(]1GENERAL
1.44-301.1 Terms Defined in ('.)ther Codes
Where terms are not defined in this code and are defined in the Energy Conservation Construction Code
of New York State, such terms shall have the meanings ascribed tothem as in that code. Where terms
are not defined in this code and are defined in a New York State code other than the Energy
Conservation Construction Code, and the applicable code is specifically referenced in relation to the
terms, such term shall have the meanings ascribed to them in relation to the referenced code.
SUBSECTION 144-302 GENERAL DEFINITIONS
ACCREDITED PASSIVE HOUSE CERTIFIER An organization accredited by Passive House Institute or
Passive House Institute US as a Passive House Certifier. A list of Accredited Passive House Certifiers can
be found atxvwvv.passivehouse.connand .
ADAPTIVE REUSE—The repurposing of a building for a new permitted use or change in occupancy type.
AGRICULTURAL BUILDING A structure designed and constructed to house farm equipment, farm
implements, poultry, livestock, hay,grain, or other horticultural products.This structure shall not be a
place of human habitation or a place of employment where agricultural products are processed,treated,
or packaged, nor shall itbea place used by the public.
ASHRAE8U.1 The publication entitled "ANSI/ASHRAE/IES Standard 90.1, Energy Standard for Buildings
ExceptLovv'riseResidentia| Bui|din0s" pub|ishedbyASHRAE,theAmericanSocietyofHeating,
Refrigerating and Air-Conditioning Engineers. In several provisions, a specific printing of the standard is
specified,for example, ASHRAEyO.1'2O13.
BIOMASS—Organic material that is processed and burned to provide energy, particularly for space
heating,through direct thermal energy. Biomass for space heating purposes includes cord wood, pellets,
and chips.
BUILDING THERMAL ENVELOPE—The insulated exterior walls (above and below grade),floors, ceilings,
roofs, and any other building element assemblies that enclose heated space or provide a boundary
between heated space and unheated space.
COMMERCIAL BUILDING—See also MIXED-USE BUILDING. Any building that is not included in the definition
of RESIDENTIAL BUILDING.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 6
COMMUNITY RENEWABLE ENERGY FACILITY: An off-site renewable energy system or facility that is qualified as
a community energy facility under applicable New York state and local utility statutes and rules.
COMPLIANCE DATE—The 91st day after Ithaca Town Board adoption of the local law containing the ECS.
DESIGN PROFESSIONAL—A Professional Engineer(PE) or a Registered Architect (RA) licensed to practice
in the State of New York.
DIRECTLY HEATED FLOOR AREA—The horizontal projection of the floors associated with the directly
heated space.
DIRECTLY HEATED SPACE-An area or room that is enclosed within the BUILDING THERMAL ENVELOPE and is
directly heated using FOSSIL FUEL, electricity, or BIOMASS as the energy source. Spaces are indirectly heated
(and not directly heated)where they connect through openings with heated spaces, where they are
separated from heated spaces by uninsulated walls,floors or ceilings, or where they contain uninsulated
ducts, piping or other sources of heating using FOSSIL FUEL, electricity, or BIOMASS.
DORMITORY-A multiple dwelling which provides sleeping accommodations and domestic facilities and
services for a group of college, university or secondary school students.
EASY PATH—Also known as PRESCRIPTIVE COMPLIANCE PATH. One possible compliance path for this Code,
under which a certain number of points must be earned.
ECS—The Energy Code Supplement, which is Chapter 144 of the Ithaca Town Code.
ELECTRIC VEHICLE CHARGING STATION (ELECTRIC VEHICLE SUPPLY EQUIPMENT[EVSE], EV CHARGING
STATION, CHARGING POINT) -The element in an infrastructure that supplies electric energy for the
recharging of plug-in electric vehicles.
ELECTRIC VEHICLE PARKING SPACE (EV PARKING SPACE or EV SPACE)—A parking space that includes
access to a dedicated electric vehicle charging port and supporting electrical infrastructure, collectively
referred to as Electric Vehicle Supply Equipment (EVSE).
ENERGY USE—All references to energy use in this chapter refer to site energy use, which is the heat and
electricity consumed by a building as reflected at the meter and/or in the utility bills.
ENERGY PROFESSIONAL-A professional holding a current accreditation in the energy field from BPI,
AEE, ASHRAE, RESNET, or other body approved by the Director of Code Enforcement or their designee.
FLOOR AREA—The total square footage of all levels as measured from the inside finished surface of the
walls, but excluding outside courts, unconditioned garages, and uninhabitable crawl spaces and attics.
Energy Code Supplement(ECS) -Adopted 2021-06-14 7
FOSSIL FUELS—An energy source formed in the Earth's crust from decayed organic material.The
common fossil fuels are petroleum, coal, and natural gas. For purposes of this ECS, fossil fuels shall also
include common extracts, derivatives, and products of fossil fuels, including but not limited to propane,
kerosene, and gasoline.
GREENHOUSE GAS(GHG)—Any of several gases, including carbon dioxide (CO2), methane (CH4), nitrous
oxide (N20), and fluorinated gases,that trap heat in the atmosphere.
HEATED FLOOR AREA—The horizontal projection of the floors associated with the heated space.
HEATED SPACE-An area or room that is enclosed within the BUILDING THERMAL ENVELOPE and is directly or
indirectly heated using FOSSIL FUEL, electricity, or BIOMASS as the energy source. Spaces are indirectly
heated where they connect through openings with heated spaces,where they are separated from
heated spaces by uninsulated walls,floors or ceilings, or where they contain uninsulated ducts, piping or
other sources of heating using FOSSIL FUEL, electricity, or BIOMASS.
HEAT PUMP, AIR SOURCE—Air source heat pumps extract heat from the ambient air. Water loop
boiler/tower heat pumps are not considered air source heat pumps.
HEAT PUMP, GROUND SOURCE—Ground source heat pumps, also known as geothermal heat pumps,
are heat pumps that extract heat from the earth, groundwater, a body of water, or similar sources.
Water loop boiler/tower heat pumps are not considered ground source heat pumps.
HOTEL—A building containing rooms designed and originally planned to be rented or hired out for living
or sleeping accommodations for transient occupancy.
LEADERSHIP IN ENERGY AND ENVIRONMENTAL DESIGN (LEED)—A green building rating/certification
system, developed by the U.S. Green Building Council (USGBC) and administered by Green Business
Certification, Inc. (GBCI).
LIGHTING POWER ALLOWANCE (LPA) - Maximum allowed lighting power density. Lighting Power
Allowances for use in PRESCRIPTIVE COMPLIANCE PATH/EASY PATH point A14 Right Lighting are given in Table
144-AA1 (Appendix A).
LIGHTING POWER DENSITY(LPD) - Lighting power consumption per square foot of FLOOR AREA, measured
in watts per square foot.
LIVABLE SPACE-A space in a building for living, sleeping, eating or cooking. Bathrooms,toilet rooms,
closets, halls, storage or utility spaces and similar areas are not considered livable spaces.
Energy Code Supplement(ECS) -Adopted 2021-06-14 8
MAJOR RENOVATION—Any construction or renovation to an existing structure other than a repair or
addition, where (1)the WORK AREA exceeds 75 percent of the FLOOR AREA and (2)two or more of the
following occur:
A. Replacement or new installation of a heating plant or system (e.g. boiler,furnace, or other
major system). Changes to ventilation and air conditioning systems are not considered
renovations of the heating system.
B. Construction that involves disassembly of greater than 50%of the area of the above-grade
portion(s) of the BUILDING THERMAL ENVELOPE in the building.
C. Changes to lighting, including but not limited to new installation, replacement, relocation, or
removal, of lamps, lighting, or other illumination fixtures in greater than 50%of the building
FLOOR AREA. Space within a building interior that is not currently lit, and is not proposed to be lit,
shall not count toward the 50%calculation.
MIXED-USE BUILDING—See also RESIDENTIAL BUILDING and COMMERCIAL BUILDING.Any building In which a
portion of the use is residential, and a portion of the use is commercial. For purposes of this
Supplement, any mixed-use building in which more than 50%of the HEATED FLOOR AREA is for residential
use shall be classified as a RESIDENTIAL BUILDING. Any other mixed-use building shall be classified as a
COMMERCIAL BUILDING. When determining the size of residential spaces, include all dwelling units, as well
as all shared amenity spaces (common areas)that serve only the dwelling units, including but not
limited to shared lobbies, hallways, stairways,gyms and laundry areas.
NATIONAL GREEN BUILDING STANDARD (NGBS, OR ICC/ASHRAE 700)—A green building
rating/certification system approved by the American National Standards Institute (ANSI), under which
points can be earned for energy efficiency;water efficiency; resource efficiency; lot development;
operation and maintenance; and indoor environmental quality.
OCCUPIABLE SPACE - A room or enclosed space designed for human occupancy in which individuals
congregate for amusement, educational or similar purposes or in which occupants are engaged at labor,
and which is equipped with means of egress and light and ventilation facilities meeting the requirements
of the Building Code of New York State.
ON-SITE RENEWABLE ENERGY SYSTEM: a renewable energy system located on any of the following:
A. The building
B. The property upon which the building is located
C. A property that shares a boundary with and is under the same ownership or control as the
property on which the building is located
D. A property that is under the same ownership or control as the property on which the building is
located and is separated only by a public right-of-way from the property on which the building is
located
PASSIVE HOUSE CERTIFICATION—A certification program for buildings, including COMMERCIAL BUILDINGS,
constructed to high-performance "passive building standards."
Energy Code Supplement(ECS) -Adopted 2021-06-14 9
PERFORMANCE-BASED COMPLIANCE PATH—Also known as WHOLE BUILDING PATH.A compliance path for
the Energy Code Supplement, under which a building must comply with specified standards of one of
several certification programs and/or use modeling to show compliance.
PLUG LOAD-A device that is powered by means of an electrical plug and matching socket or receptacle.
This excludes devices that are accounted for as part of major building end uses such as HVAC, lighting
systems, and water heating.
PRESCRIPTIVE COMPLIANCE PATH—Also known as EASY PATH.A compliance path for the Energy Code
Supplement, under which a certain number of points must be earned for the building to show
compliance.
PROCESS ENERGY(PROCESS LOAD) - Energy consumed in support of a manufacturing, industrial,
commercial, research, or educational process other than space heating,ventilating, air conditioning,
SERVICE WATER HEATING, PLUG LOADS, lighting, and appliances. Examples of process loads include
commercial cooking, commercial refrigeration, energy used by machinery in manufacturing, energy used
by medical equipment, emergency generators, and energy used for agricultural needs. Examples of
loads that are not considered process loads include electricity required for exhaust fans, heating and
cooling for ventilation makeup air for any purpose including kitchen and lab hoods, and energy used for
clothes drying.
REC: See RENEWABLE ENERGY CREDIT(REC)
RENEWABLE ENERGY CREDIT(REC):a tradable instrument that represents the environmental attributes
of one megawatt-hour of renewable electricity generation and is transacted separately from the
electricity generated by the renewable energy source. Also known as REC, renewable energy certificate,
energy attribute and energy attribute certificate.
RESIDENTIAL BUILDING—See also MIXED-USE BUILDING.Any building covered by the Residential Code of
New York State, as well as any building that is classified in accordance with Chapter 3 of the Building
Code of New York State in Group R-2, R-3, or R-4, including any RESIDENTIAL BUILDING that has more than
three stories above grade plane.
RESTAURANT—An establishment that prepares and serves meals or drinks to customers onsite or
delivers them off-site.
SERVICE WATER HEATING -Also known as domestic hot water heating. Supply of hot water for purposes
other than comfort heating.
SPANDREL PANEL-The area of a curtain wall or screen located between vision areas of windows,which
conceals structural building components such as columns, floors, HVAC equipment, and plumbing.
Energy Code Supplement(ECS) -Adopted 2021-06-14 10
SPLIT SYSTEM -A heat pump or air conditioner in which one component is located outdoors and the
other component(s) indoors, and which components are connected by refrigerant piping.
TOWN—The Town of Ithaca.
WHOLE BUILDING PATH—Also known as PERFORMANCE-BASED COMPLIANCE PATH. One possible compliance
path for the Energy Code Supplement, under which a building must comply with specified standards of
one of several certification programs and/or use modeling to show compliance.
WINDOW-TO-WALL RATIO—The total area of exterior glazing (windows) in a building divided by the
total area of the above-grade walls, expressed as a percentage.
WORK AREA—That portion or portions of a building consisting of all reconfigured spaces as indicated on
the construction documents. Work area excludes other portions of the building where incidental work
entailed by the intended work must be performed, and portions of the building where work not initially
intended by the owner is specifically required by the provisions of the New York State Existing Building
Code.
Energy Code Supplement(ECS) -Adopted 2021-06-14 11
�����^��� � ��—� ������������A � U BUILDING ������U�U��UN�
��.."~u�... . '�~��r—~� v~��o�nu�nx—nxv~o��n— PROVISIONS
SUBSECTION 144-[401GEKjER/\L
The provisions in this subsection are applicable to COMMERCIAL BUILDINGS and xx|xso'uscau|Lo|mos where
SO% or more of the HsxTso FLOOR AREA is commercial, their building sites, and associated systems and
equipment.
COMMERCIAL BUILDINGS shall comply with one of the following:
A. PRESCRIPTIVE COMPLIANCE PATH/EASY PATH:The requirements of Subsection 144-C402
1. As part of the application packet the applicant shall submit a checklist and xvorksheet
which the TOWN shall use as the basis for verifying and showing compliance with the ECS.
B. Psnronmxwcs'exssoCoxxpuAmcs Pxr*/VVHoLs Bu|Lo|wo PATH: The requirements of Subsection 144'
C4U3
1. As part of the application packet,the applicant shall submit the relevant documentation,
which is detailed in 144'C403, which the Tovvw shall use as the basis for verifying and
showing compliance with the ECS.
SUBSECTION 1z1zl-C/1[)2 PRESCRIPTIVE COMPLIANCE PATH/EASY PATH
Until January 1, 2023, to meet the requirements of this subsection 144'C402, a building must achieve a
minimum of six(6) of the points described in this subsection.A summary table is provided in 144'C402.6.
See 144'C404 for enhanced requirements beginning on and after January 1, 2023, and additional
enhanced requirements beginning on and after January 1, 2U26.
144'C4D2.2'1EE1 Heat Pumps for Space Heating
Two points shall be earned for using AIR SOURCE HEAT PUMPS or three points shall be earned for using GROUND
SOURCE HEAT Pumps, as described in 144'C402.2.1.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 12
144-C402.2.1.1
Only AIR SOURCE HEAT PUMPS or GROUND SOURCE HEAT PUMPS shall be used for all space-heating needs, with
exceptions for electric resistance heating as described in subsection 144-402.2.1.4.A heating system that
uses only GROUND SOURCE HEAT PUMPS(and electric resistance heating as allowed) shall earn three points.A
heating system that uses only AIR SOURCE HEAT PUMPS or uses a combination of air source and GROUND SOURCE
HEAT PUMPS (and electric resistance heating as allowed) shall earn two points.
144-C402.2.1.2
FOSSIL FUELS shall not be used for any space heating, space cooling or ventilation systems in the building,
including backup heating systems.Water loop boiler/tower heat pumps that use FOSSIL FUELS shall not earn
credit under this point.
144-C402.2.1.3
Except as stated in the second sentence of this provision 144-C402.2.1.3, AIR SOURCE HEAT PUMPS shall be
listed in the Northeast Energy Efficiency Partnerships (NEEP) Cold Climate AIR SOURCE HEAT PUMP Product
List, for the product types and sizes covered. For any AIR SOURCE HEAT PUMP not covered by NEEP, the heat
pump shall use a variable speed compressor(s) and the heat pump compressor(s) shall operate in
temperatures below zero (0) degrees Fahrenheit (the compressor may be supplemented by electric
resistance heat in accordance with the exceptions described in subsection 144-402.2.1.4).
144-C402.2.1.4
To allow flexibility,electric resistance heat is allowed for a portion of space heating needs.Applicants shall
submit documentation showing that at least one of the following conditions is met.
A. Stand-alone electric resistance heating (not associated with heat pumps) is used to heat 10% or
less of the buildings HEATED FLOOR AREA.
B. Stand-alone electric resistance heating (not associated with heat pumps) is used to meet 10%or
less of the building's projected annual space heating load.
144-C402.2.2 EE2 Heat Pumps for Service Water Heating
One point shall be earned for meeting the requirements of 144-C402.2.2.
Restrictions:This point may only be earned when all commercial portions of the building meet one of the
following criteria.
A. Are classified as HOTEL, RESTAURANT, or inpatient healthcare
B. Collectively use more than 40 gallons of water per square foot on an annual basis, as cited in the
latest COMMERCIAL BUILDINGS Energy Consumption Survey (CBECS)or comparable source
144-C402.2.2.1
All SERVICE WATER HEATING systems shall use heat pumps and shall not use FOSSIL FUELS.All heat pump water
heaters shall be set on heat pump-only mode.
Energy Code Supplement(ECS) -Adopted 2021-06-14 13
Exception: In commercial kitchens, booster heat units for dishwashing must be electric, but shall be
exempt from the heat pump requirement. Units used to pre-heat water for dishwashing shall use
heat pumps.
144-C402.2.3 EE3 Commercial Cooking Electrification
Three points shall be earned for meeting the requirements of 144-C402.2.3.
Restrictions:
A. Points may only be earned for buildings or portions thereof that are RESTAURANTS or other food
service establishments that use a commercial kitchen hood, and
B. Points may only be earned if the building does not use FOSSIL FUELS, except for PROCESS ENERGY. For
this point, PROCESS ENERGY shall exclude commercial cooking.
144-C402.2.3.1
All cooking equipment, including but not limited to ranges, griddles, and fryers, shall be electric.
1,44 C402..3 A.ffOrtiabiIity....!.. ..p.m° r m o . .: ...... Ql....m.....................................................................................................................................................................
144-C402.3.1 All Smaller Building/Room Size
One or two points may be earned according to the requirements below.
Restrictions:
A. This point may only be earned for HOTELS.
B. For additions,this point may only be earned if the applicant demonstrates ECS compliance for the
addition together with the existing building. This point may not be earned when considering the
addition independent of the existing building.
144-C402.3.1.1
For HOTELS, the average DIRECTLY HEATED FLOOR AREA of all guest rooms in the building shall not be greater
than the maximum average guest room size listed in Table 144-C402.3.1.1. Individual guest rooms may
exceed the maximum size.
Table 144-C402.3.1.1
Area Requirements for Hotels and Motels
Maximum average guest room size 280
allowed to receive one point(SF)
Maximum average guest room size 230
allowed to receive two points(SF)
144-C402.3.2 AI2 Heating System in Heated Space
One point may be earned according to the requirements below.
Energy Code Supplement(ECS) -Adopted 2021-06-14 14
144-C402.3.2.1
All components of heating systems shall be installed inside space that meets all the following criteria:
A. Inside the BUILDING THERMAL ENVELOPE
B. DIRECTLY HEATED SPACE
C. LIVABLE SPACE,OCCUPIABLE SPACE or contiguous to LIVABLE SPACE or OCCUPIABLE SPACE
D. On a building level where at least 50%of the FLOOR AREA Is DIRECTLY HEATED FLOOR AREA
For purposes of this subsection, heating system includes all parts of the system except for exhaust
components and dedicated air intake components, including but not limited to mechanical equipment
and the distribution network. Examples of spaces that are not allowed for heating system installation
include but are not limited to: unheated or unfinished basements and attics,crawl spaces,outdoors,roofs,
and exterior wall cavities.Rooftop systems,window-mounted systems,and"through-the wall'equipment
such as packaged terminal equipment shall not be used.
Exceptions:
A. Outdoor units of SPLIT SYSTEM heat pumps may be located outdoors.
B. There are no limitations on the location of refrigerant piping.
144-C402.3.3 AI3 Efficient Building Shape
One point may be earned according to the requirements below.
144-C402.3.3.1
The exterior surface area divided by the DIRECTLY HEATED FLOOR AREA shall be less than the maximum value
provided in Table 144-C402.3.3.1.
144-C402.3.3.2
The exterior surface area shall be measured along the above-grade portion(s) of the BUILDING THERMAL
ENVELOPE, including but not limited to walls, roofs/ceilings (depending on the location of insulation), and
exposed floors (such as those below a cantilever). The area of windows, doors, and skylights shall be
included as part of the exterior surface area.The areas of the BUILDING THERMAL ENVELOPE between DIRECTLY
HEATED SPACES and indirectly heated spaces or unheated spaces,such as the wall between a heated building
and an attached unheated garage, shall be included as part of the exterior surface area.
144-C402.3.3.3
For additions,the area of the BUILDING THERMAL ENVELOPE between DIRECTLY HEATED SPACE In the addition and
DIRECTLY HEATED SPACE in the original building(including shared walls and,if the addition is above the original
building, floors/ceilings) shall not be counted as part of the exterior surface area.
Energy Code Supplement(ECS) -Adopted 2021-06-14 15
Table 144-C402.3.3.1
Maximum Value of: Maximum Value of:
Exterior Surface Area(SF) Exterior Surface Area(SF)
Directly Heated divided by Directly Heated Directly Heated divided by Directly Heated
Floor Area(SF) Floor Area(SF) Floor Area(SF) Floor Area(SF)
199 or less 4.69 3,000 - 3,999 1.60
200 - 299 3.88 4,000 - 4,999 1.48
300 - 399 3.45 5,000 - 5,999 1.39
400 - 499 3.17 6,000 - 6,999 1.31
500 - 599 2.98 7,000 - 7,999 1.25
600 - 699 2.83 8,000 - 8,999 1.19
700 - 799 2.71 9,000 - 9,999 1.15
800 - 899 2.68 10,000 - 14,999 1.05
900 - 999 2.57 15,000 - 19,999 0.94
1,000 - 1,099 2.47 20,000 - 29,999 0.84
1,100 - 1,199 2.38 30,000 - 39,999 0.75
1,200 - 1,299 2.31 40,000 - 49,999 0.68
1,300 - 1,399 2.24 50,000 - 59,999 0.64
1,400 - 1,499 2.18 60,000 - 69,999 0.61
1,500 - 1,599 2.13 70,000 - 79,999 0.58
1,600 - 1,699 2.08 80,000 - 89,999 0.55
1,700 - 1,799 2.04 90,000 - 99,999 0.53
1,800 - 1,899 2.00 100,000 - 199,999 0.46
1,900 - 1,999 1.96 200,000 - 299,999 0.39
2,000 - 2,499 1.86 300,000 - 399,999 0.35
2,500 - 2,999 1.74 400,000 or more 0.33
144-C402.3.4 AI4 Right Lighting
One point may be earned according to the requirements below.
144-C402.3.4.1. Mixed-Use Buildings
For MIXED-USE BUILDINGS classified as Commercial, the entire commercial portion and all common areas
serving the residential portion (all areas outside of dwelling units,e.g. hallways, lobbies)shall comply with
the requirements in this subsection. Lighting inside the dwelling units does not need to comply with the
requirements in this subsection.
144-C402.3.4.2 Lighting Power Allowance
The total connected interior lighting power shall not be greater than the interior LIGHTING POWER
ALLOWANCE.The total connected interior lighting power shall be calculated using the method described in
the Energy Conservation Construction Code of NYS. (Informative note: the method can be found in the
2020 ECCCNYS in section C405.3.1 Total Connected Interior Lighting Power.) The total interior LIGHTING
POWER ALLOWANCE, in watts, shall be determined according to Table 144-AA1 (Appendix A), for all areas of
the building covered in this permit.The LIGHTING POWER ALLOWANCE shall be determined by multiplying the
Energy Code Supplement(ECS) -Adopted 2021-06-14 16
FLOOR AREA of each space times the LIGHTING POWER DENSITY(LPD)value for the space type in Table 144-AA1
that most closely represents the proposed use of the space, and then summing the LIGHTING POWER
ALLOWANCES for all spaces to calculate the total interior LIGHTING POWER ALLOWANCE.Trade-offs among spaces
are permitted.Construction documents shall include a table of space-by-space as-designed LIGHTING POWER
DENSITIES along with the LIGHTING POWER ALLOWANCES from Table 144-AA1.
144-C402.3.4.3 Additional interior lighting power.
An increase in the interior LIGHTING POWER ALLOWANCE is permitted for specific lighting functions.Additional
power shall be permitted only where the specified lighting is installed and automatically controlled
separately from the general lighting, to be turned off during non-business hours. This additional power
shall be used only for the specified luminaires and shall not be used for any other purpose.An increase in
the interior LIGHTING POWER ALLOWANCE is permitted in the following cases:
A. For lighting equipment to be installed in sales areas specifically to highlight merchandise, the
additional lighting power shall be determined in accordance with Equation 144-4-1.
Equation 144-4-1: Additional interior LIGHTING POWER ALLOWANCE = 250 watts+ (Retail Area 1 * 0.3
W/ft') +(Retail Area 2 * 0.3 W/ftz) +(Retail Area 3 * 0.7 W/ft') + (Retail Area 4 * 1.3 W/ftz)
Where:
Retail Area 1 = The FLOOR AREA for all products not listed in Retail Area 2, 3 or 4
Retail Area 2=The FLOOR AREA used for the sale of vehicles, sporting goods, and small electronics.
Retail Area 3 = The FLOOR AREA used for the sale of furniture, clothing, cosmetics, and artwork.
Retail Area 4 = The FLOOR AREA used for the sale of jewelry, crystal, and china.
Exception: Other merchandise categories are permitted to be included in Retail Areas 2
through 4, provided that justification documenting the need for additional lighting power
based on visual inspection, contrast, or other critical display is approved by the Code
Enforcement Officer.
B. For spaces in which lighting is specified to be installed in addition to the general lighting for the
purpose of decorative appearance or for highlighting art or exhibits, provided that the additional
lighting power shall be not more than 0.5 w/ftz of such spaces.
144-C402.3.4.4 Lighting Controls
Except where lighting is required to stay on by New York State or local code, motion sensors are required
for interior lighting in the following space types: office, conference room, kitchenette, corridor, stairwell,
restroom, lobby. Short off-delay (1 minute or less) is required for motion sensors. Manual control that
allows lights to be kept off shall be provided. Except where lighting is required to stay on by New York
State or local code, all exterior lighting shall be controlled by motion sensors, as well as photocells that
ensure lighting stays off during daylight hours.
Exception:
Lighting for signs is exempt from the requirements of 144-C402.3.4.4
Energy Code Supplement(ECS) -Adopted 2021-06-14 17
144-C402.3.4.5 Other Lighting Standards
All exterior lighting shall comply with the Town of Ithaca Outdoor Lighting Law,TOWN Code Chapter 173.
144-C402.3.4.6 Commissioning
Commissioning of lighting and lighting controls is required.A commissioning plan shall be developed by a
DESIGN PROFESSIONAL or an ENERGY PROFESSIONAL or approved agency (as defined in the state energy code)
and shall include the following items:
A. A narrative description of the activities that will be accomplished during each phase of
commissioning, including the personnel intended to accomplish each of the activities.
B. A listing of specific lighting and controls to be tested and a description of the tests to be
performed.
C. Functions to be tested, including but not limited to, LIGHTING POWER DENSITY (to show compliance
with LIGHTING POWER ALLOWANCE requirements) and control settings.
D. Conditions under which the tests will be performed.
E. Measurable criteria for performance.
The DESIGN PROFESSIONAL or ENERGY PROFESSIONAL shall execute the commissioning plan. A commissioning
report, consistent with the commissioning plan, shall be submitted prior to the Certificate of Occupancy
being issued.
144-C402.3.5 AI5 Modest Window-to-Wall Ratio
One point may be earned according to the requirements below.
144-C402.3.5.1
The vertical fenestration area, not including opaque doors and opaque SPANDREL PANELS, shall be not
greater than 20 percent of the gross above-grade wall area.
144-C402.3.5.2
For additions,the area of above-grade walls that were part of the BUILDING THERMAL ENVELOPE of the original
building but are not part of the BUILDING THERMAL ENVELOPE of the new building shall be counted towards
the above-grade wall area of the addition.
144-C402.4.1 RE1 Renewable Energy Systems
Up to three points may be earned according to the requirements below.
144-C402.4.1.1 Points available
On-site and off-site renewable energy systems that meet the requirements of this subsection shall earn
up to three points based on their annual electrical or thermal energy production. Multiple renewable
Energy Code Supplement(ECS) -Adopted 2021-06-14 18
energy systems may be used to earn points, but no more than three total points may be earned for any
combination of renewable energy systems.
144-C402.4.1.2 Determining the number of points earned
The number of points earned shall be determined according to the steps below.The applicant shall submit
documentation of all related assumptions and calculations.
Step 1: Calculate Renewable Energy Production
The Renewable Energy Production (REP) is the projected annual energy production of the renewable
energy system,expressed in kilowatt-hours per year(kWh/yr). For thermal systems,the conversion 1 kWh
=3.412 kBtu shall be used.
Step 2: Calculate the Number of Points Earned
The number of points earned for a renewable energy system is based on the DIRECTLY HEATED FLOOR AREA of
the building it serves. Points shall be earned based on a weighted average related to residential and
commercial FLOOR AREA, as described in Equation 144-4-2. For purposes of this subsection 144-C402.4.1,
residential space shall include dwelling units and common areas that serve only dwelling units.
Equation 144-4-2: Minimum Renewable Energy Production needed to earn each point=
(1.2 kWh/ftZ x RA) +(2.4 kWh/ftZ x CA)
CA= DIRECTLY HEATED FLOOR AREA of Commercial space (ftZ)
RA= DIRECTLY HEATED FLOOR AREA of Residential space (ftZ)
Note:For buildings that have no residential space,set RA equal to zero.
Example Calculation-for informational purposes only
Assumptions: MIXED-USE BUILDING with 2,000 ftZ of residential DIRECTLY HEATED FLOOR AREA and 5,000 ftZ of
commercial DIRECTLY HEATED FLOOR AREA.A 25 kW solar array is being used.
Step 1: Using the PVWatts Calculator, it is projected that the 25 kW solar array will produce 30,000
kWh/year.
Renewable Energy Production is 30,000 kWh/year
Step 2: Using Equation 144-4-2:
Minimum REP needed for each point= (1.2 kWh/ftZ x RA) + (2.4 kWh/ftZ x CA)
Minimum REP needed for each point= (1.2 kWh/ftZ x 2,000 ftZ)+ (2.4 kWh/ftZ x 5,000 ftZ)
Minimum REP needed for each point= 2,400 kWh + 12,000 kWh
Minimum REP needed for each point= 14,400 kWh
Using the assumptions for this building and renewable energy system, two (2) points may be earned.
144-C402.4.1.3 Energy Sources
Renewable energy systems shall produce electricity from solar, wind, or hydropower resources, or
produce thermal energy from solar, geothermal, or hydrothermal resources. Thermal energy absorbed
Energy Code Supplement(ECS) -Adopted 2021-06-14 19
from or rejected to outdoor air/ground/water and used in conjunction with heat pumps does not count
as renewable energy for the purposes of this subsection. Hydropower shall be from new generation
capacity on a nonimpoundment or new generation capacity on an existing impoundment. Hydropower
shall meet one of the following conditions:
A. The hydropower facility complies with the Low Impact Hydropower Certification
Handbook and is certified by a nationally recognized accreditation organization.
B. The hydropower facility complies with UL 2854 and is certified by an organization that has the
standard in its ISO 17065 scope of accreditation.
C. The hydropower facility consists of a turbine in a pipeline or a turbine in an irrigation canal.
For facilities falling under condition (A) or(B), only output generated during the period of certification is
eligible for RECs sale in accordance with the provisions of this subsection. Renewables from new
impoundments of water are not eligible.
144-C402.4.1.4 Qualifying Renewable Energy Systems
Renewable energy systems producing electricity or thermal energy that is delivered to or credited to the
building to comply with Subsection 144-C402.4.1 shall meet the following requirements:
A. Renewable energy systems shall satisfy one of the following criteria:
1. ON-SITE RENEWABLE ENERGY SYSTEM
i. Self-generation
ii. Purchase Contract such as a Power Purchase Agreement
2. Off-site renewable energy system
i. Self-generation (an off-site renewable energy system owned by the building
owner)
li. COMMUNITY RENEWABLE ENERGY FACILITY
iii. Purchase Contract such as a Power Purchase Agreement
B. The renewable energy system shall be located in New York Independent System Operator
(NYISO)territory and shall be located where the energy can be delivered to the building site by
any of the following:
1. Direct connection to the renewable energy system
2. The local utility or distribution entity
3. An interconnected electrical network where energy delivery capacity between the
generator and the building site is available (Informative Note: Examples of
interconnected electrical networks include regional power pools and regions served by
Independent System Operators or Regional Transmission Organizations.)
C. The renewable energy system must have commenced operation on or after January 1, 2015 and
before the date the certificate of occupancy for the building is issued.
Energy Code Supplement(ECS) -Adopted 2021-06-14 20
Exception to 144-C402.4.1.4(C)
If the building owner can provide evidence that,for the duration of the planning
process, it has made a good faith effort to have the renewable energy system
constructed and operational by the time of certificate of occupancy, and due to
circumstances out of the control of and not otherwise due to any negligence or willful
misconduct on behalf of the building owner,the renewable energy system is not
constructed or is not operational,then the building owner shall be allowed up to one
year after the certificate of occupancy is issued to meet 144-C402.4.1.4(C).
D. Where the renewable energy system ceases operation, or the owner cannot legally claim the
associated energy or RECs for any reason,the building owner shall produce or procure
alternative qualifying renewable energy in an amount equal to or greater than the amount
needed to earn the same number of points under the requirements of 144-C402.4.1.2.
144-C402.4.1.5 Reporting and Documentation
A. The building owner shall submit documentation of renewable energy system ownership or
renewable energy procurement,which includes subscription to a community solar project.
Records on power and thermal energy produced or purchased by the building owner from the
renewable energy producer shall be retained by the building owner on behalf of the entity
demonstrating financial or operational control over the building seeking compliance to this
standard and submitted to the Code Enforcement Officer on an annual basis for no less than 15
years.Any period of non-compliance shall not count toward fulfillment of the 15-year
requirement.
B. For systems generating electricity, documentation shall be provided to the Code Enforcement
Officer that indicates an exclusive chain of custody and ownership of the RECs from the
renewable energy system to the building owner, on an annual basis for no less than 15 years.
RECs supplied from the renewable energy system shall be conveyed to and retired on behalf of
the entity who has financial or operational control over the building's electricity consumption.
The annual generation vintage date of delivered RECs shall be allocated to the same 12-month
reporting year, up to six months prior, or up to three months after the calendar year in which
the electricity is used in the building. Any period of non-compliance shall not count toward
fulfillment of the 15-year requirement.
Exceptions to 144-C402.4.1.5 (B)
1. If the total capacity of all renewable energy systems being used to earn points under
144-C402.4.1 is less than 25 kW,the requirements of 144-C402.4.1.5(B) shall be waived.
2. Where the building owner cannot provide documentation on the chain of custody or
ownership of the RECs from the renewable energy system,the building owner shall
provide documentation to the Code Enforcement Officer of an alternate supply contract
for replacement RECs from an alternate renewable energy source.The quantity of RECs
Energy Code Supplement(ECS) -Adopted 2021-06-14 21
contracted for shall be equal to or greater than the amount needed to earn the desired
number of points under the requirements of 144-C402.4.1.2.These RECs shall comply
with the Green-e®Renewable Energy Standard for Canada and the United States(latest
edition) and shall be conveyed to and retired on behalf of the entity who has financial or
operational control over the building's electricity consumption.
C. Electricity,thermal energy and RECs from renewable energy systems may not be counted more
than once for purposes of demonstrating compliance with this subsection 144-C402.4.1.The
reporting and documentation required in 144-C402.4.1.4 shall clearly state how the energy and
RECs are allocated to specific buildings.The TOWN may request additional documentation to
provide reasonable proof of ownership/procurement, and fulfillment of RECS and allocation
requirements.
D. In the case of full or partial transfer of ownership of the building,the following must be
provided: proof of transfer of ownership; a signed statement from the new owner stating they
understand the requirements of this subsection 144-C402.4.1 and the duty to fulfill them; and
contact information for the person(s) responsible for submitting annual reporting.
144-C402.4.2 RE2 Biomass Space Heating
Three points may be earned according to the requirements below.
144-C402.4.2.1
Only BIOMASS systems shall be used for all space-heating needs, with exceptions for electric resistance
heating as described in 144-C402.4.2.4.
144-C402.4.2.2
FOSSIL FUELS shall not be used for any space heating, space cooling or ventilation systems in the building,
including backup heating systems.
144-C402.4.2.3
All BIOMASS equipment must comply with the NYSERDA (New York State Energy Research and
Development Authority) Renewable Heat NY program guidelines, available at www.nyserda.ny.gov/AII-
Programs/Programs/Renewable-Heat-NY.
144-C402.4.2.4
To allow flexibility,electric resistance heat is allowed for a portion of space heating needs.Applicants shall
submit documentation showing that at least one of the following conditions is met.
A. Stand-alone electric resistance heating is used to heat 10%or less of the building's heated FLOOR
AREA.
B. Stand-alone electric resistance heating is used to meet 10% or less of the building's projected
annual space heating load.
Energy Code Supplement(ECS) -Adopted 2021-06-14 22
144'C402.5.1OP1 Development Density
One point may be earned according tothe requirements below.
Restrictions: A maximum of two points total may be earned for points OP1 Development Density, OP2
VVa|kabi|ity, and OP3 Electric Vehicle Parking Spaces combined.
144'C402.5.1.1
One point shall be earned if(DU +CA) > (7xAcnea0e),where:
DU the number of all Residential dwelling units on the entire parcel occupied by the building
CA=the FLOOR AREA of all Commercial space, measured in units of 1,000 square feet, on the entire parcel
occupied by the building
Acreage=the land area, measured in acres, of the entire parcel occupied by the building.
144'C402.5.1.2
DU shall include all dxve|Un0 units on the parcel occupied by the building, including those in existing
buildings. CA shall include all Commercial space on the parcel occupied by the building, including that in
existing buildings. [A shall not include common areas serving only dwelling units or other Residential
space.Acreage shall include all land area on the parcel occupied by the building.
Example Cbkuhotian'for informational purposes only
Mixed Use Development
Residential units: 12apartnnents 4 DU = 12
Commercial space: 1O,OOOsqft4CA= 1U
Parcel acreage: 1.5acres 4 Acreage= 1.5
DU +CA= 12+ 10=22
7x Acreage=7x1.5 = 1U.5
22 > 1U.S
1 point may be earned.
144'C402.5'2 OP2xVa|kabi|ity
One point may be earned according to the requirements below.
Restrictions: A maximum of two points total may be earned for points OP1 Development Density, DPZ
VVa|kabi|ity, and OP3 Electric Vehicle Parking Spaces combined.
144'C402.5.2.1
This point shall be earned when either of the following two conditions is met, in addition to the other
requirements in this subsection 144'C402.5.2.
A. The building is within one quarter(0.25) mile of at least five of the Neighborhood Amenity Types
listed in Table 144'C402.5.2.1.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 23
1. No single Amenity Type shall be counted more than twice, even when more than two
examples of the Amenity Type exist. For example, a building on Aurora Street's
"Restaurant Row" could count two RESTAURANTS maximum.
2. At least two Amenity Categories shall be represented.
3. The one quarter mile measurement(s) may be taken from any part(s) of the building.
B. The building is within a TOWN development priority area for which a regulating plan has been
developed and adopted.
144-C402.5.2.2
For all buildings, at the time of project completion, sidewalks, walkways and/or trails must be present on
the property or within 75 feet of the property, and connect to an existing network of pedestrian
infrastructure.
Energy Code Supplement(ECS) -Adopted 2021-06-14 24
Table 144-C402.5.2.1
Neighborhood Amenity Types and Categories
Amenity Category Amenity Type
Food retail Supermarket
Grocery with produce section
Community-serving retail Convenience store
Farmers market
Hardware store
Pharmacy
Other retail
Services Bank
Family entertainment venue (e.g., theater, sports)
Gym, health club, exercise studio
Hair care
Laundry, dry cleaner
Restaurant, cafe, diner(excluding those with only drive-
thru service)
Civic and community facilities Adult or senior care(licensed)
Child care(licensed)
Community or recreation center
Cultural arts facility(museum,performing arts)
Education facility(e.g.,K-12 school,university, adult
education center,vocational school, community college)
Government office that serves public on-site
Medical facility that treats patients
Place of worship
Post office
Public library
Public park
Social services center
144-C402.5.3 OP3 Electric Vehicle Parking Spaces
One point may be earned for installing ELECTRIC VEHICLE PARKING SPACE(s)and related infrastructure that meet
the requirements of this subsection.
Restrictions: A maximum of two points total may be earned for points OP1 Development Density, OP2
Walkability, and OP3 Electric Vehicle Parking Spaces combined.
144-C402.5.3.1 Required Number of EV Parking Spaces
The number of required EV PARKING SPACES shall be determined using Table 144-C402.5.3.1(1), based on
the number of Residential Dwelling Units (DU) and the area of Commercial space (CA).
Energy Code Supplement(ECS) -Adopted 2021-06-14 25
DU =the number of Residential dwelling units in the building.
CA=the area of all Commercial space, measured in units of 1,000 square feet, in the building.CA shall not
include common areas serving only dwelling units or other portions of Residential space.
When determining the total number of required spaces in MIXED-USE BUILDINGS, EV SPACE requirements for
Residential Dwelling Units and for Commercial space shall be calculated separately and summed.
Table 144-C402.5.3.1 (1)
Required Number of Electric Vehicle Parking Spaces
Residential Space Commercial Space
Number of EV Number of EV
Number of Area in units of 1,000 Sq.
Dwelling Units (DU) Spaces Required for Ft(CA) Spaces Required for
Residential Portion(SR) Commercial Portion(SC)
1 to 6 1 5 2
7 to 13 2 10 3
14 to 20 3 15 5
21 to 24 4 20 6
25 to 30 5 25 7
31 to 38 1 6 30 1 9
39 to 46 7 35 10
47 to 53 8 40 12
For up to 53 Dwelling Units,use table. The numbers listed above are examples.
For 54 or more Dwelling Units: For all building sizes use the equation:
SR=(0.13 x DU)+1 SC=0.28xCA
Complete Residential and Commercial calculations Complete Residential and Commercial calculations
separately, add results, and round up to nearest separately, add results, and round up to nearest
whole number: whole number.
SR+SC=ST(Total EV Parking Spaces) SR+SC=ST(Total EV Parking Spaces)
Energy Code Supplement(ECS) -Adopted 2021-06-14 26
Table 144-C402.5.3.1 (2)
Sample Calculation for required number of EV Parking Spaces
Sample Calculation
44,300 sq ft mixed-use building. 26 Dwelling Units (DU)and 6,000 sq ft Commercial Area(CA)
SR=(0.13 x 26)+ 1
SR=3.4+ 1 =4.4
4.4 EV spaces are required for Residential portion
SC=0.28x6
SC= 1.7
1.7 EV spaces are required for Commercial portion
ST= SR+ SC rounded up
ST=4.4+ 1.7=6.1,round up
7 EV spaces are required for the building to earn a point.
144-C402.5.3.2
The requirements for this point as set forth here and in Table 144-C402.6 are NOT intended to override
or supplant existing zoning code provisions regarding parking requirements. To the extent that zoning
permissible parking spaces cannot be accommodated on the building site,the building must seek off-site
spaces in accordance with the provisions of this point and applicable zoning laws.
144-C402.5.3.3
All ELECTRIC VEHICLE PARKING SPACES shall be located on the same parcel as the building, in the same parking
facilities as those used by one or more of the following target user groups:customers/clients; employees;
and fleet vehicles. If no parking facilities exist on the same parcel, and off-site parking facilities do exist
for one or more of the user groups, then EV PARKING SPACES may be installed in those off-site parking
facilities. Off-site parking must be within 0.25 miles of the building.
144-C402.5.3.4
All ELECTRIC VEHICLE PARKING SPACES shall be served by a dedicated Electric Vehicle Charging port. ELECTRIC
VEHICLE CHARGING STATIONS may have any number of ports.
144-C402.5.3.5
At least one Accessible ELECTRIC VEHICLE PARKING SPACE is required in any parking facility that includes more
than 10 ELECTRIC VEHICLE PARKING SPACES. Any parking facility with more than 50 ELECTRIC VEHICLE PARKING
SPACES must provide at least two accessible ELECTRIC VEHICLE PARKING SPACES.The associated space(s)are not
required to be designated only for accessible parking, as defined by the Building Code of NYS, but must
meet all other accessibility requirements contained in New York State law.
Energy Code Supplement(ECS) -Adopted 2021-06-14 27
144-C402.5.3.6
All buildings must install Level 2 EV CHARGING STATIONS that operate on a 240-volt AC circuit and/or Direct
Current Fast Chargers.
144-C402.5.3.7
ELECTRIC VEHICLE PARKING SPACES shall be provided with a dedicated branch circuit, raceways, and all other
electric vehicle charging equipment. The branch circuit shall be identified for electric vehicle service in
the service panel or subpanel directory. Electrical room(s) serving areas with EV PARKING SPACES shall be
designed to accommodate the electrical equipment and distribution required to serve all of the ELECTRIC
VEHICLE CHARGING STATIONS.
144-C402.5.3.8
ELECTRIC VEHICLE CHARGING STATION equipment shall be maintained in all respects, including the functioning
of the charging equipment. A phone number or other contact information shall be provided on the
charging station equipment for reporting when the equipment is not functioning, or other problems are
encountered.
144-C402.5.3.9
The ELECTRIC VEHICLE CHARGING STATION, including the charging cord, shall be installed so as to not interfere
with pedestrian walkways at anytime.
144-C402.5.3.10
Except for Accessible EV PARKING SPACES, each EV PARKING SPACE shall be posted with signage indicating that
the space is only to be used for electric vehicle charging purposes. Days and hours of operations and any
other restrictions on use of the parking space shall be included if time limits or tow-away provisions are
to be enforced.
144-C402.5.4 OP4 Adaptive Reuse
One point may be earned according to the requirements below.
144-C402.5.4.1
The building must maintain 50%or more of the existing building structure and BUILDING THERMAL ENVELOPE,
based on measurement of the surface area.The existing building structure must be retained in place and
re-purposed for a different permitted use (for example, when an old school is adapted for use as
apartments). A MAJOR RENOVATION of a building and re-use for the same purpose shall not be eligible for
this point.
144-C402.5.5 OP5 NY Stretch Code
One point may be earned according to the requirements below.
Energy Code Supplement(ECS) -Adopted 2021-06-14 28
144-C402.5.5.1
The building shall comply with all requirements of the NYStretch Energy Code-2020 Version 1.0,which is
available at:
www.nyserda.ny.gov/AI I-Progra ms/Progra ms/Energy-Code-Tra i n i ng/NYStretch-Energy-Code-2020
144-C402.5.6 OP6 Custom Energy Improvement
Up to two points may be earned according to the requirements below.
144-C402.5.6.1
To earn one point, both of the following conditions must be met:
A. Reduce ENERGY USE by 1.2 kWh/SF/year or 4.1 kbtu/SF/year for all residential HEATED FLOOR AREA in
the building.
B. Reduce ENERGY USE by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all commercial HEATED FLOOR AREA in
the building.
144-C402.5.6.2
To earn two points, both of the following conditions must be met:
A. Reduce ENERGY USE by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all residential HEATED FLOOR AREA in
the building.
B. Reduce ENERGY USE by 4.8 kWh/SF/year or 16.4 kbtu/SF/year for all commercial HEATED FLOOR AREA
in the building.
144-C402.5.6.3
Multiple improvements may be combined to achieve each point under this improvement. Improvements
may be made anywhere in the building as long as they meet the thresholds of ENERGY USE reduction. The
proposed energy improvement(s) shall be submitted to the Code Enforcement Officer in writing, signed
by the DESIGN PROFESSIONAL or ENERGY PROFESSIONAL. Energy reduction must be shown through energy
analysis performed by a DESIGN PROFESSIONAL or ENERGY PROFESSIONAL. Simplified calculations (e.g.,
spreadsheet) are acceptable.
144-C402.5.6.4
For a baseline, use the 2016 Energy Conservation Construction Code of New York State. If the baseline
condition is not addressed by the ECCCNYS, use baseline conditions as defined in Appendix G of ASHRAE
Standard 90.1-2013.
144-C402.5.6.5
Production of renewable energy shall not count toward energy reduction. Energy reduction must be
calculated after applying all other proposed energy improvements to the proposed design. In other words,
interactive energy savings must be performed. Savings cannot be taken for improvements made with
other points, such as right-lighting or the NY Stretch Energy Code.
Energy Code Supplement(ECS) -Adopted 2021-06-14 29
The following Table 144'C402.6 is a summary of the PnsscmpT|vc Coxxpuxwcc PATH/EASY PATH for
COMMERCIAL BUILDINGS. This is a summary for informational purposes only. To earn points, all applicable
requirements insubsections 144'C402.1, 144'C4022, 144'C40I3, 144'C402.4and 144'C402.5 must be
met. In case of discrepancies between Table 144-C402.6 and the requirements in subsections 144-C402.1,
144'C4O22, 144'C4UI3, 144'C4OZ.4 and 144'C4OZ.S,the latter shall hold precedence.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 30
Table 144-C402.6
Commercial Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least six points
Cate- Improvement Points Details
or
EFFICIENT ELECTRIFICATION
EE1 Heat pumps for space 2 -3 2 points for air source heat pumps.
heating 3 points for ground source heat pumps.
EE2 Heat pumps for domestic hot I 1 point for water heating systems that use heat pumps.Available
water heating to hotels and restaurants only.
Commercial cooking 3 points for electric cooking equipment in restaurants and other
EE3 3 food service buildings.Prerequisite: no fossil fuel use in the
electrification building.
AFFORDABILITY IMPROVEMENTS
All Smaller building/room size 1 -2 Up to 2 points for smaller room sizes.Available for Hotel and
Residential portions only.
Heating systems in heated
AI2 1 1 point for installing heating systems in directly heated spaces.
space
AI3 Efficient building shape 1 1 point if exterior surface area divided by directly heated floor
area is less than the maximum allowed value.
AI4 Right-lighting 1 1 point for reducing overlighting and implementing other
lighting improvements.
AI5 Modest window-to-wall I 1 point for overall window-to-wall ratio less than 20%
ratio (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE Renewable energy systems 1 -3 Up to 3 points for on-site or off-site renewable electric systems
or on-site renewable thermal systems.
RE2 Biomass systems 3 3 points for biomass space heating systems.
OTHER POINTS
1 point for achieving sufficient development density on the
OP 1 Development density 1 building parcel.A maximum of two points total may be earned
for points OP I,OP2,and OP3 combined.
1 point if the building meets the walkability criteria.A
OP2 Walkability 1 maximum of two points total may be earned for points OP 1,
OP2,and OP3 combined.
Electric Vehicle Parking 1 point for installing electric vehicle parking spaces and related
OP3 1 infrastructure.A maximum of two points total may be earned for
Spaces points OP1,OP2,and OP3 combined.
OP4 Adaptive reuse 1 1 point for substantial re-purpose of existing building.
OP5 Meet NY Stretch Code 1 1 point for complying with NYStretch Energy Code
OP6 Custom energy improvement 1 -2 Up to 2 points for reduction in energy use.
Energy Code Supplement(ECS) -Adopted 2021-06-14 31
SUBSECTION 144-C403 PERFORMANCE-BASED COMPLIANCE PATH/WHOLE
BUILDING PATH
1.44-•C40 .1 Generall
.......................................................................................................................................
Until January 1,2023,to meet the requirements of this subsection 144-C403,a building must comply with
any one of the high-performance building approaches described in 144-C403.2, 144-C403.3, 144-C403.4,
and 144-C403.5. See 144-C404 for enhanced requirements beginning on and after January 1, 2023, and
additional enhanced requirements beginning on and after January 1, 2026.
1.44-•C40 .2 DI...EE;D-base and �:�.n m,,,�, C I ! .!21 on-�� n Cony Di n
................................................................................................................................................................................................................................... ................................................................................................................................................................... ..........................................
144-C403.2.1
Buildings shall comply with one of the following:
A. Using LEED v4 for Building Design + Construction, the building shall earn no less than 17 LEED
points total in the Optimize Energy Performance credit and the Renewable Energy Production
credit of the Energy and Atmosphere section.
1. LEED certification is not necessary.
2. Renewable energy generation that meets all applicable requirements for renewable
energy systems described in 144-C402.4.1 may be used to meet the requirements of the
Renewable Energy Production credit.
B. Demonstrate 40% savings relative to ASHRAE Standard 90.1-2013, using the energy cost budget
method OR Demonstrate 46% savings relative to ASHRAE Standard 90.1-2010, using the energy
cost budget method.
1. Renewable energy generation may be used. All applicable requirements for renewable
energy systems described in 144-C402.4.1 must be met. Renewable energy generation
used to achieve the 40%/46%savings is capped at 25%of the baseline energy use.
2. The energy cost reduction assessment and requirement shall exclude ENERGY USE by
PROCESS LOADS. However,the energy model shall include the energy used for PROCESS LOADS
because energy used by heating, cooling, and ventilation (including exhaust fans/hoods,
makeup air fans, and heating/cooling for makeup air) is subject to the energy cost
reduction requirement. After the baseline and proposed energy models are run, for the
energy cost reduction calculation, subtract out the PROCESS ENERGY use from both the
baseline and the proposed building energy model results, and use the resulting without-
process-energy results for the energy cost calculations.
Energy Code Supplement(ECS) -Adopted 2021-06-14 32
144-C403.2.2
Documentation shall include either:
A. Design approval by Green Business Certification Inc.TM (GBCI), through the Split Review process,
that shows the building is eligible to receive no less than 17 LEED points as described in 144-
C403.2.1 (A).
OR both of the following:
B. Complete input and output reports of the energy model showing that the energy model meets
the requirements of this subsection 144-C403
C. Approval of the energy model by NYSERDA, U.S. Department of Energy, Energize NY, or another
agency approved by the Code Enforcement Officer.
1,44-•C403.3 Passive Illousa.,.based Cone. .. n iianc
................................................................................................................................................................................................................................................................... .......................................
144-C403.3.1
Buildings shall meet the design requirements of one of the following.
A. PHIUS+ Passive Building Standard from Passive House Institute US
B. Passive House Classic Standard from Passive House Institute
Actual certification is not required. The most recent version of the chosen standard in effect at the time
of building permit application shall be used.
144-C403.3.2
Documentation shall include at least one of the following:
A. Pre-certification letter (or other formal communication) from an ACCREDITED PASSIVE HOUSE
CERTIFIER, stating that Design Review has been completed and the building is designed to meet all
requirements of the chosen Standard. All documentation used to show achievement of the
requirements must be submitted to the Code Enforcement Officer.
B. Documentation of PASSIVE HOUSE CERTIFICATION. All documentation used to achieve certification
must be submitted to the Code Enforcement Officer.
144-•C403.4 Greenhouse Gas Emissions Calculation-based Co.m iiancm
........................................................................................................................................................................................................................................................................................................................................................................................................................................... .........................................
The building shall demonstrate a reduction in GREENHOUSE GAS (GHG) emissions of not less than 40% as
compared to the baseline building.
144-C403.4.1 Energy Modeling Standards
GHG emissions reductions shall be shown through energy modeling that complies with Appendix G of
ASHRAE Standard 90.1-2013.
144-C403.4.2 Process Loads
The GHG emissions reduction assessment and requirement shall exclude ENERGY USE by PROCESS LOADS.
However, the energy model shall include the energy used for PROCESS LOADS because energy used by
heating, cooling, and ventilation (including exhaust fans/hoods, makeup air fans,and heating/cooling for
Energy Code Supplement(ECS) -Adopted 2021-06-14 33
makeup air) is subject to the GHG emissions reduction requirement. After the baseline and proposed
energy models are run, for the GHG emissions reduction calculation, subtract out the PROCESS ENERGY use
from both the baseline and the proposed building energy model results, and use the resulting without-
process-energy results for the GHG emissions calculations.
144-C403.4.3 Renewable Energy
Renewable energy generation may be used. All applicable requirements for renewable energy systems
described in 144-C402.4.1 must be met. Renewable energy generation used to achieve the 40%reduction
in GHG emissions is capped at 25% of the baseline energy use. The GHG emissions factor for electricity
produced by renewable energy systems shall be 0 (zero) lb CO2e/MWh.
144-C403.4.4 GHG Emissions Factor for Electricity
For buildings not served by combined heat and power plants,the GHG emissions factor for electricity used
for all calculations shall be 548.37 lb CO2e/MWh.
144-C403.4.5 GHG Emissions Factor for Electricity for Buildings Served by Combined Heat and Power
Plants
For buildings using electricity generated by combined heat and power (CHP) plants, the GHG emissions
factor for electricity shall be determined in one of the following ways:
A. The most recent heat rate data available at the time of building permit application shall be used
from www.eia.gov/electricity/annual/html/epa_08_02.html, for the specific type of generation
plant used,for electricity to be used in the proposed building,and the heat rate shall be multiplied
by the EPA emissions factor for the fuel used at the CHP plant.The result shall be used as the GHG
emissions factor for electricity from CHP plants.
B. Data gathered from actual operation of the CHP plant and its distribution network shall be used
to determine the site-specific GHG emissions factor for electricity to be used in the building. All
data used shall be made publicly available before the time of building permit application.
For buildings served by CHP plants, the baseline (reference building) electricity use GHG emissions factor
shall be the same as for buildings not served by a CHP plant.
144-C403.4.6
If a facility uses electricity from a combination of sources (e.g., utility, off-site renewable energy system,
and CHP plant), a weighted average of GHG emissions factors shall be used.
144-C403.4.7 Documentation
The following documentation shall be submitted to show compliance with 144-C403.4 in sufficient clarity
and detail:
1. A report, signed and stamped by an accredited third-party ENERGY PROFESSIONAL, showing the
results of all calculations, assumptions, inputs, and outputs for the energy model
Energy Code Supplement(ECS) -Adopted 2021-06-14 34
2. A letter, signed and stamped by an accredited third-party ENERGY PROFESSIONAL, stating that
proposed total GHG emissions for the building are at least 40% less than the GHG emissions of
the baseline building.
3. The TOWN reserves the right to require additional documentation and/or additional third-party
review and analysis by a consultant selected by the TOWN,at the expense of the applicant.All such
documentation shall be submitted and fee shall be paid prior to issuance of a building permit.
1.44-C403.5 Greenhouse Gas Emissions Caicuiation- ase CO.m. .fiance for Additions
.........................................................................................................................................................................................................................................................................................................................................................................................................................................I ...............................................................................................................................
Compliance using the requirements of this provision 144-C403.5 may only be used for additions that are
showing compliance together with the existing building. See also 144-202.2.
144-C403.5.1
The addition and the existing building, together as a whole, shall be shown to have lower total GHG
emissions than the original existing building.
144-C403.5.2
Current and proposed GHG emissions shall be calculated following the requirements of the GHG Emissions
Calculation Method (144-C403.4).
144-C403.5.3 Documentation
The following documentation shall be submitted to show compliance with 144-C403.5 in sufficient clarity
and detail:
A. An energy study of the existing building that includes ENERGY USE from at least 12 consecutive
months of the most recent 24 months at the time of building permit application.
B. An energy study that shows anticipated ENERGY USE for the new addition and modified existing
building.
C. A report, signed and stamped by an accredited ENERGY PROFESSIONAL, showing the results of all
calculations, assumptions, inputs, and outputs for the energy model, and
D. A letter, signed and stamped by an accredited third-party ENERGY PROFESSIONAL, stating that
proposed total GHG emissions for the building and addition together are less than the GHG
emissions for the existing building.
E. The TOWN reserves the right to require additional documentation and/or additional third-party
review and analysis by a consultant selected by the TOWN,at the expense of the applicant.All such
documentation shall be submitted and fee shall be paid prior to issuance of a building permit.
Energy Code Supplement(ECS) -Adopted 2021-06-14 35
SUBSECTION 144-C404FUTURE REQUIREMENTS
1,44-C404.1 General
On January 1, 2023, the requirements ofSubsections 144'C402 and 144'C403 shall change as described
in 144'C404.2, 144'C404.3, 144'C404.4, and 144'C404.6. Where no changes are listed, the requirements
shall remain as described in Subsections 144'C4O2 and 144'C4O3.
On January 1, ZOZG, the requirements of Subsections 144'C401, 144'C402 and 144'C403 shall change as
described in 144'C404.7. Where no changes are listed, the requirements shall remain as described in
Subsections 144'C4O1, 144'C4O2 and 144'C4O3.
Path
Effective January 1, 2023, to meet the requirements of subsection 144'C402, a building must achieve a
minimum of twelve (12) of the points described in subsection 144-C402. A summary table is provided in
144'C4O4.5
Effective January 1, 2023, all points awarded from 144'C402.2 Efficient Electrification shall be doubled.
144'C404.3'1
Fourpointssha|| beearnedforusin0mnsouncs*sxTpumpsandmeetingtherequirementsof144'C4O2.Z.1
Heat Pumps for Space Heating. Six points shall be earned for using GROUND SOURCE HEAT Pumps and
meeting the requirements of144'C4O2.2.1 Heat Pumps for Space Heating.
144'C404.3'2
Two points shall be earned for meeting the requirements of 144'C402.2.2 EEZ Heat Pumps for SERVICE
WATER HEATING.
144'C404.3'3
Six points shall be earned for meeting the requirements of144'C4OZ.2.3 EE3 Commercial Cooking
Electrification.
Effective January 1, 2023, the maximum number of points allowed under 144'402.4.1 RE1 Renewable
Energy Systems shall increase to six/G\ points.The criteria for earning points shall remain as described in
144'C402.4.1.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 36
144--C404,5 Ch n ,,�.es in 2023to Summ r laWefor Prescrip.l.ive Co.nip iance F. a h Eas Path
.............................................................................................2 P...................................................................................................................................2 y................................................................................................................... ... .......................................................!.............................................I..........It I........................y....................................
Commercial Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least 12 points
Cate-
gory � Improvement Points Details
EFFICIENT ELECTRIFICATION
EEI Heat pumps for space 4 -6 4 points for air source heat pumps.
heating 6 points for ground source heat pumps.
EE2 Heat pumps for service 2 2 points for water heating systems that use heat pumps.
water heating Available to hotels and restaurants only.
Commercial cooking 6 points for electric cooking equipment in restaurants and other
EE3 electrification 6 food service buildings.Prerequisite: no fossil fuel use in the
building.
AFFORDABILITY IMPROVEMENTS
All Smaller building/room size 1 -2 Up to 2 points for smaller room sizes.Available for Hotel and
Residential portions only.
Al2 Heating systems in heated I I point for installing heating systems in directly heated spaces.
- space
A13 Efficient building shape I I point if exterior surface area divided by directly heated floor
I area is less than the maximum allowed value.
A14 Right-lighting I I point for reducing overlighting and implementing other
lighting improvements.
A15 Modest window-to-wall I I point for overall window-to-wall ratio less than 20%
ratio (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE I Renewable energy systems 1 -6 Up to 6 points for on-site or off-site renewable electric systems
or on-site renewable thermal systems.
RE2 Biomass systems 3 3 points for biomass space heating systems.
OTHER POINTS
I point for achieving sufficient development density on the
OPI Development density I building parcel.A maximum of two points total may be earned
for points OP I,OP2,and OP3 combined.
I point if the building meets the walkability criteria.A
OP2 Walkability I maximum of two points total may be earned for points OP 1,
OP2,and OP3 combined.
Electric Vehicle Parking I point for installing electric vehicle parking spaces and related
OP3 Spaces I infrastructure.A maximum of two points total may be earned for
points CIP1,OP2,and OP3 combined.
OP4 Adaptive reuse I I point for substantial re-purpose of existing building.
OP5 Meet NY Stretch Code I I point for complying with NYStretch Energy Code
OP6 Custom energy improvement 1 -2 Up to 2 points for reduction in energy use.
Energy Code Supplement(ECS) -Adopted 2021-06-14 37
Effective January 1, 2023, the requirements of Subsection 144'C403 Psnponwmmcs'BxscoCoxxpumvcc
PATH/WHOLE Buuo|ws PATH shall change as described in 144'C404.6.1, and 144'C404.62. Where no
changes are listed,the requirements shall remain as described in Subsection 144-C403.
144'C4O4.G'1 Changes toLEEQ-based and Energy Ca|cu|ation'basedcmmmp|imnce
Effective January 1, ZOZ3:
A. Compliance method 1 (LEEDpoints): |n addition to all existing requirements, seven ECS points
from Subsection C402 PRESCRIPTIVE COMPLIANCE PATH/EASY PATH must be earned. Points from A14
Right-Lighting and OP5 Meet NY Stretch Code may not be counted toward the seven ECS points.
B. Compliance method Z (savings relative toASHRAE 90.1'2013): An 8OY6savings relative to
ASHRAE Standard QU.1'ZU13 shall berequired.
1. Renewable energy generation used to achieve the savings shall be capped at 50%of the
baseline energy use.
C. Compliance method 3 (savings relative to ASH RAE 90.1'2010):A8Z%savings relative to ASH RAE
Standard yO.1'2O1O shall berequired.
1. Renewable energy generation used to achieve the savings shall be capped at 50%of the
baseline energy use.
144'C404.6'2 Changes tgGreenhouse Gas Emissions Ca|cu|mtimn-based Compliance
Effective January 1, 2023,the building shall demonstrate a reduction in GREENHOUSE GAS (GHG) emissions
of not less than 8OY6as compared to the baseline building.
144'C404.6.2.1
Renewable energy generation used to achieve the 80Y6 reduction in GHG emissions is capped at 50Y6 of
the baseline energy use.
144'C404.6.2.2
For buildings not served by combined heat and power plants or renewable energy systems, the GHG
emissions factor for electricity used for all calculations shall be 285.8 |bCO2e/MVVh.
Effective January 1, 2026, all buildings shall be built to have net-zero GHG emissions and shall not use
FOSSIL FUELS for space heating, water heating, or clothes drying.
144'C404.7'1
The language in144'C4O1.2 Application shall be replaced with:
COMMERCIAL BUILDINGS shall comply with the requirements of the ZERO Code, using the most recent version
of the ZERO Code available at the time of permit application. The ZERO Code, an Architecture 2030
initiative, is available at .
Energy Code Supplement(ECS) AdoptedZU21'OG'14 38
An ECS Compliance Plan shall be the basis for evaluating compliance.
144-C404.7.2
FOSSIL FUELS shall not be used for space heating, water heating or clothes drying. FOSSIL FUELS may be used
for PROCESS ENERGY and for cooking.
Energy Code Supplement(ECS) -Adopted 2021-06-14 39
Section 144_5 RESIDENTIAL BUILDING PROVISIONS
SUBSECTION 144-R5[)1GENERAL
The provisions in this section are applicable to RESIDENTIAL BUILDINGS and xxmzo'uss au|u)|mos where more
than 50% of the heated FLOOR AREA is residential, their building sites, and associated systems and
equipment.
RESIDENTIAL BUILDINGS shall comply with one of the following:
A. PRESCRIPTIVE COMPLIANCE PATH/EASY PATH:The requirements of Subsection 144-R502
1. As part of the application packet the applicant shall submit a checklist and xvorksheet
which the TOWN shall use as the basis for verifying and showing compliance with the ECS.
B. Psnronmxwcs'exssoCoxxpuAmcs Pxr*/VVHoLs Bu|Lo|ws PATH: The requirements of Subsection 144'
RSO3
1. As part of the application packet,the applicant shall submit the relevant documentation,
which is detailed in 144'R503, which the Tovvw shall use as the basis for verifying and
showing compliance with the ECS.
SUBSECTION 1z1zl-11 [)� 2 PRESCRIPTIVE COMPLIANCE PATH/EASY PATH
Until January 1, 2023, to meet the requirements of this Subsection 144-R502, A building must achieve a
minimum of six(6) of the points described in this subsection.A summary table is provided in 144'R502.6.
See 144'R504 for enhanced requirements beginning on and after January 1, 2023, and additional
enhanced requirements beginning on and after January 1, 2U26.
1.44-11502.2 Efficient Electrification
144'R5Q2'2'1EE1 Heat Pumps for Space Heating
Three points shall be earned for using AIR SOURCE HEAT PUMPS or five points shall be earned for using GROUND
SOURCE HEAT Pumps, as described in 144'R502I1.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 40
144-R502.2.1.1
Only AIR SOURCE HEAT PUMPS or GROUND SOURCE HEAT PUMPS shall be used for all space-heating needs, with
exceptions for electric resistance heating as described in 144-R502.2.1.4.A heating system that uses only
GROUND SOURCE HEAT PUMPS (and electric resistance heating as allowed) shall earn five points. A heating
system that uses only AIR SOURCE HEAT PUMPS or uses a combination of air source and GROUND SOURCE HEAT
Pumps(and electric resistance heating as allowed) shall earn three points.
144-R502.2.1.2
FOSSIL FUELS shall not be used for any space heating, space cooling or ventilation systems in the building,
including backup heating systems.Water loop boiler/tower heat pumps that use FOSSIL FUELS shall not earn
credit under this point.
144-R502.2.1.3
Except as stated in the second sentence of this provision 144-R502.2.1.3, AIR SOURCE HEAT PUMPS shall be
listed in the Northeast Energy Efficiency Partnerships (NEEP) Cold Climate AIR SOURCE HEAT PUMP Product
List, for the product types and sizes covered. For any AIR SOURCE HEAT PUMP not covered by NEEP,the heat
pump shall use a variable speed compressor(s) and the heat pump compressor(s) shall operate in
temperatures below zero (0) degrees Fahrenheit (the compressor may be supplemented by electric
resistance heat in accordance with the exceptions described in 144-R502.2.1.4).
144-R502.2.1.4
To allow flexibility,electric resistance heat is allowed for a portion of space heating needs.Applicants shall
submit documentation showing that at least one of the following conditions is met.
A. Stand-alone electric resistance heating (not associated with heat pumps) is used to heat 10% or
less of the building HEATED FLOOR AREA.
B. Stand-alone electric resistance heating (not associated with heat pumps) is used to meet 10%or
less of the building's projected annual space heating load.
144-R502.2.2 EE2 Heat Pumps for Service Water Heating
One point shall be earned for meeting the requirements of 144-R502.2.2.
144-R502.2.2.1
All SERVICE WATER HEATING systems shall use heat pumps and shall not use FOSSIL FUELS.All heat pump water
heaters shall be set on heat pump-only mode.
Exception: In commercial kitchens, booster heat units for dishwashing must be electric, but shall be
exempt from the heat pump requirement. Units used to pre-heat water for dishwashing shall use
heat pumps.
144-R502.2.3 EE3 Commercial Cooking Electrification
Three points shall be earned for meeting the requirements of 144-R502.2.3.
Restrictions:
Energy Code Supplement(ECS) -Adopted 2021-06-14 41
A. Points may only be earned for portions of buildings that are RESTAURANTS or other food service
establishments that use a commercial kitchen hood, and
B. Points may only be earned if the building does not use FOSSIL FUELS, except for PROCESS ENERGY. For
this point, PROCESS ENERGY shall exclude commercial cooking.
144-R502.2.3.1
All commercial cooking equipment in the building, including but not limited to ranges, ovens, griddles,
and fryers, shall be electric.
144-R502.2.4 EE4 Residential Cooking and Clothes Drying Electrification
One point shall be earned for meeting the requirements of 144-R502.2.4
Restrictions: Point may only be earned if the building does not use FOSSIL FUELS except for PROCESS ENERGY.
144-R502.2.4.1
All residential cooking equipment in the building, including but not limited to ranges,cooktops and ovens,
shall be electric.
144-R502.2.4.2
All clothes drying equipment in the building shall be ventless heat pump clothes dryers.
144-1,15 2. Af orda illt'y....Dlor l!. .:: u m o u . ......(A!..)
....................................................................................................................................................................
144-R502.3.1 All Smaller building/room size
One or two points may be earned according to the requirements below.
Restrictions:
A. For MIXED-USE BUILDINGS, this point may only be earned when all portions of the building are
classified as Residential or HOTEL.
B. DORMITORIES are not eligible for this point.
C. For additions,this point may only be earned if the applicant demonstrates ECS compliance for the
addition together with the existing building. This point may not be earned when considering the
addition independent of the existing building.
144-R502.3.1.1
For single family dwellings, the DIRECTLY HEATED FLOOR AREA of the building shall not be greater than the
maximum home size listed in Table 144-R502.3.1.1 relating to the number of bedrooms in the dwelling.
For two-family dwellings and townhouses,the total DIRECTLY HEATED FLOOR AREA of the building Shall not be
greater than the Total Building Size Allowance.The Total Building Size Allowance, in square feet, shall be
determined by multiplying the quantity of each type of dwelling unit(1-BR,2-BR etc.)times the'maximum
home size' value for that dwelling unit type in Table 144-R502.3.1.1, and then summing the home size
allowances for all unit types to calculate the Total Building Size Allowance.This method is summarized in
Equation 144-5-1.
Energy Code Supplement(ECS) -Adopted 2021-06-14 42
Equation 144-5-1:
Total Building Size Allowance =
[(Number of 1-BR units in the building) x (Maximum home size for 1-BR units listed in Table 144-
R502.3.1.1)] + [(#of 2-BR units in the building)x(Maximum home size for 2-BR units)] + ... +
[(#of 6-BR units in the building)x(Maximum home size for 6-BR units)]
Individual dwelling units may exceed the maximum home size allowance for that unit type given in Table
144-R502.3.1.1.
Table 144-R502.3.1.1
Size Allowances for Single Family Dwellings,Two-family Dwellings, and Townhouses
Number of Bedrooms 1 2 3 4 5 6 7 or more
Maximum home size allowed to +510 for each
850 1,360 1,870 2,380 2,890 3,400
receive one point(SF) additional bedroom
Maximum home size allowed to +420 for each
700 1,120 1,540 1,960 2,380 2,800
receive two points (SF) additional bedroom
Example Calculation-for informational purposes only
Duplex, building contains 3,100 sq ft Of DIRECTLY HEATED FLOOR AREA,two dwelling units (3 bedrooms each)
From Table 144-R502.3.1.1
Maximum home size allowed to receive one point for 3-BR units: 1,870 sq ft
Total Building Size Allowance = (2 x 1,870 sq ft) =3,740 sq ft
Building size of 3,100 sq ft does not exceed size allowance,so one point can be earned.
From Table 144-R502.3.1.1
Maximum home size allowed to receive two points for 3-BR units: 1,540 sq ft
Total Building Size Allowance = (2 x 1,540 sq ft) =3,080 sq ft
Building size of 3,100 sq ft exceeds size allowance, so two points cannot be earned.
144-R502.3.1.2
For RESIDENTIAL BUILDINGS other than single family dwellings, two-family dwellings, and townhouses, the
total DIRECTLY HEATED FLOOR AREA of all dwelling units in the building shall not be greater than the Total Unit
Size Allowance. The DIRECTLY HEATED FLOOR AREA of dwelling units refers to in-unit areas only and shall not
include common areas. The Total Unit Size Allowance, in square feet, shall be determined by multiplying
the quantity of each type of dwelling unit(studio, 1-BR,etc.)times the'Dwelling unit size allowance'value
for that dwelling unit type in Table 144-R502.3.1.2,and then summing the unit size allowances for all unit
types to calculate the Total Unit Size Allowance.This method is summarized in Equation 144-5-2.
Equation 144-5-2:
Total Unit Size Allowance =
[(Number of studio units in the building) x (Dwelling unit size allowance for studio units listed in Table
144-R502.3.1.2)] +
Energy Code Supplement(ECS) -Adopted 2021-06-14 43
[(#of 1-13R units in the building)x (Dwelling unit size allowance for 1-1311 units)] +
[(#of 2-13R units in the building)x(Dwelling unit size allowance for 2-1311 units)] + ... +
[(#of 7-13R units in the building)x(Dwelling unit size allowance for 7-1311 units)]
Individual dwelling units may exceed the allowance for that unit type given in Table 144-R502.3.1.2.
Table 144-R502.3.1.2
Dwelling Unit Size Allowances for RESIDENTIAL BUILDINGS other than Single Family Dwellings, Two-family
Dwellings, and Townhouses
Number of Bedrooms Studio 1 2 3 4 5 6 7
Dwelling unit size allowance to
408 600 842 986 1,156 1,326 1,496 1,666
receive one point(sq ft)
Dwelling unit size allowance to 336 490 693 812 952 1,092 1,232 1,372
receive two points (sq ft)
144-R502.3.1.3
For HOTELS, the average DIRECTLY HEATED FLOOR AREA of all guest rooms in the building shall not be greater
than the maximum average guest room size listed in Table 144-R502.3.1.3. Individual guest rooms may
exceed the maximum size.
Table 144-R502.3.1.3
Area Requirements for Hotels and Motels
Maximum average guest room size 280
allowed to receive one point(SF)
Maximum average guest room size 230
allowed to receive two points(SF)
144-R502.3.2 AI2 Heating System in Heated Space
One point may be earned according to the requirements below.
144-R502.3.2.1
All components of heating systems shall be installed inside space that meets all the following criteria:
A. Inside the BUILDING THERMAL ENVELOPE
B. DIRECTLY HEATED SPACE
C. LIVABLE SPACE,OCCUPIABLE SPACE or contiguous to LIVABLE SPACE or OCCUPIABLE SPACE
D. On a building level where at least 50%of the FLOOR AREA Is DIRECTLY HEATED FLOOR AREA
For purposes of this subsection, heating system includes all parts of the system except for exhaust
components and dedicated air intake components, including but not limited to mechanical equipment
and the distribution network. Examples of spaces that are not allowed for heating system installation
Energy Code Supplement(ECS) -Adopted 2021-06-14 44
include but are not limited to: unheated or unfinished basements and attics,crawl spaces,outdoors,roofs,
and exterior wall cavities.Rooftop systems,window-mounted systems,and"through-the wall'equipment
such as packaged terminal equipment shall not be used.
Exceptions:
A. Outdoor units of SPLIT SYSTEM heat pumps may be located outdoors.
B. There are no limitations on the location of refrigerant piping.
144-R502.3.3 AI3 Efficient Building Shape
One point may be earned according to the requirements below.
144-R502.3.3.1
The exterior surface area divided by the DIRECTLY HEATED FLOOR AREA shall be less than the maximum value
provided in Table 144-R502.3.3.1.
144-R502.3.3.2
The exterior surface area shall be measured along the above-grade portions of the BUILDING THERMAL
ENVELOPE, including but not limited to walls, roofs/ceilings (depending on the location of insulation), and
exposed floors (such as those below a cantilever). The area of windows, doors, and skylights shall be
included as part of the exterior surface area.The areas of the BUILDING THERMAL ENVELOPE between directly
heated spaces and indirectly heated spaces or unheated spaces, such as the wall between a heated
building and an attached unheated garage, shall be included as part of the exterior surface area.
144-R502.3.3.3
For additions,the area of the BUILDING THERMAL ENVELOPE between DIRECTLY HEATED SPACE In the addition and
DIRECTLY HEATED SPACE in the original building(including shared walls and,if the addition is above the original
building, floors/ceilings) shall not be counted as part of the exterior surface area.
Energy Code Supplement(ECS) -Adopted 2021-06-14 45
Table 144-R502.3.3.1
Maximum Value of: Maximum Value of:
Exterior Surface Area(SF) Exterior Surface Area(SF)
Directly Heated divided by Directly Heated Directly Heated divided by Directly Heated
Floor Area(SF) Floor Area(SF) Floor Area(SF) Floor Area(SF)
199 or less 4.69 3,000 - 3,999 1.60
200 - 299 3.88 4,000 - 4,999 1.48
300 - 399 3.45 5,000 - 5,999 1.39
400 - 499 3.17 6,000 - 6,999 1.31
500 - 599 2.98 7,000 - 7,999 1.25
600 - 699 2.83 8,000 - 8,999 1.19
700 - 799 2.71 9,000 - 9,999 1.15
800 - 899 2.68 10,000 - 14,999 1.05
900 - 999 2.57 15,000 - 19,999 0.94
1,000 - 1,099 2.47 20,000 - 29,999 0.84
1,100 - 1,199 2.38 30,000 - 39,999 0.75
1,200 - 1,299 2.31 40,000 - 49,999 0.68
1,300 - 1,399 2.24 50,000 - 59,999 0.64
1,400 - 1,499 2.18 60,000 - 69,999 0.61
1,500 - 1,599 2.13 70,000 - 79,999 0.58
1,600 - 1,699 2.08 80,000 - 89,999 0.55
1,700 - 1,799 2.04 90,000 - 99,999 0.53
1,800 - 1,899 2.00 100,000 - 199,999 0.46
1,900 - 1,999 1.96 200,000 - 299,999 0.39
2,000 - 2,499 1.86 300,000 - 399,999 0.35
2,500 - 2,999 1 1.74 1400,000 or more 1 0.33
144-11502.3.4 AI5 Modest Window-to-Wall Ratio
One point may be earned according to the requirements below.
144-R502.3.4.1
The vertical fenestration area, not including opaque doors and opaque SPANDREL PANELS, shall be not
greater than 20 percent of the gross above-grade wall area.
144-R502.3.4.2
For additions,the area of above-grade walls that were part of the BUILDING THERMAL ENVELOPE of the original
building but are not part of the BUILDING THERMAL ENVELOPE of the new building shall be counted towards
the above-grade wall area of the addition.
144-11502.4.1 RE1 Renewable Energy Systems
Up to three points may be earned according to the requirements below.
Energy Code Supplement(ECS) -Adopted 2021-06-14 46
144-R502.4.1.1 Points available
On-site and off-site renewable energy systems that meet the requirements of this subsection shall earn
up to three points based on their annual electrical or thermal energy production. Multiple renewable
energy systems may be used to earn points, but no more than three total points may be earned for any
combination of renewable energy systems.
144-R502.4.1.2 Determining the number of points earned
The number of points earned shall be determined according to the steps below.The applicant shall submit
documentation of all related assumptions and calculations.
Step 1: Calculate Renewable Energy Production
The Renewable Energy Production (REP) is the projected annual energy production of the renewable
energy system,expressed in kilowatt-hours per year(kWh/yr). For thermal systems,the conversion 1 kWh
=3.412 kBtu shall be used.
Step 2: Calculate the Number of Points Earned
The number of points earned for a renewable energy system is based on the DIRECTLY HEATED FLOOR AREA of
the building it serves. Points shall be earned based on a weighted average related to residential and
commercial FLOOR AREA, as described in Equation 144-5-2. For purposes of this subsection 144-R502.4.1,
residential space shall include dwelling units and common areas that serve only dwelling units.
Equation 144-5-2: Minimum Renewable Energy Production needed to earn each point=
(1.2 kWh/ftZ x RA) +(2.4 kWh/ftZ x CA)
CA= DIRECTLY HEATED FLOOR AREA of Commercial space (ftZ)
RA= DIRECTLY HEATED FLOOR AREA of Residential space (ftZ)
Note:For buildings that have no commercial space, set CA equal to zero.
Example Calculation-for informational purposes only
Assumptions: MIXED-USE BUILDING with 2,000 ftZ of residential DIRECTLY HEATED FLOOR AREA and 5,000 ftZ of
commercial DIRECTLY HEATED FLOOR AREA.A 25 kW solar array is being used.
Step 1: Using the PVWatts Calculator, it is projected that the 25 kW solar array will produce 30,000
kWh/year.
Renewable Energy Production is 30,000 kWh/year
Step 2: Using Equation 144-5-2:
Minimum REP needed for each point= (1.2 kWh/ftZ x RA) + (2.4 kWh/ftZ x CA)
Minimum REP needed for each point= (1.2 kWh/ftZ x 2,000 ftZ)+ (2.4 kWh/ftZ x 5,000 ftZ)
Minimum REP needed for each point= 2,400 kWh + 12,000 kWh
Minimum REP needed for each point= 14,400 kWh
Using the assumptions for this building and renewable energy system, two (2) points may be earned.
Energy Code Supplement(ECS) -Adopted 2021-06-14 47
144-R502.4.1.3 Energy Sources
Renewable energy systems shall produce electricity from solar, wind, or hydropower resources, or
produce thermal energy from solar, geothermal, or hydrothermal resources. Thermal energy absorbed
from or rejected to outdoor air/ground/water and used in conjunction with heat pumps does not count
as renewable energy for the purposes of this subsection. Hydropower shall be from new generation
capacity on a nonimpoundment or new generation capacity on an existing impoundment. Hydropower
shall meet one of the following conditions:
A. The hydropower facility complies with the Low Impact Hydropower Certification
Handbook and is certified by a nationally recognized accreditation organization.
B. The hydropower facility complies with UL 2854 and is certified by an organization that has the
standard in its ISO 17065 scope of accreditation.
C. The hydropower facility consists of a turbine in a pipeline or a turbine in an irrigation canal.
For facilities falling under condition (a) or(b), only output generated during the period of certification is
eligible for RECs sale in accordance with the provisions of this subsection. Renewables from new
impoundments of water are not eligible.
144-R502.4.1.4 Qualifying Renewable Energy Systems
Renewable energy systems producing electricity or thermal energy that is delivered to or credited to the
building to comply with Subsection 144-R502.4.1 shall meet the following requirements:
A. Renewable energy systems shall satisfy one of the following criteria:
1. ON-SITE RENEWABLE ENERGY SYSTEM
i. Self-generation
ii. Purchase Contract such as a Power Purchase Agreement
2. Off-site renewable energy system
i. Self-generation (an off-site renewable energy system owned by the building
owner)
li. COMMUNITY RENEWABLE ENERGY FACILITY
iii. Purchase Contract such as a Power Purchase Agreement
B. The renewable energy system shall be located in New York Independent System Operator
(NYISO)territory and shall be located where the energy can be delivered to the building site by
any of the following:
1. Direct connection to the renewable energy system
2. The local utility or distribution entity
3. An interconnected electrical network where energy delivery capacity between the
generator and the building site is available (informative Note: Examples of
interconnected electrical networks include regional power pools and regions served by
Independent System Operators or Regional Transmission Organizations.)
C. The renewable energy system must have commenced operation on or after January 1, 2015 and
before the date the certificate of occupancy for the building is issued.
Energy Code Supplement(ECS) -Adopted 2021-06-14 48
Exception to 144-R502.4.1.4(C)
If the building owner can provide evidence that,for the duration of the planning
process, it has made a good faith effort to have the renewable energy system
constructed and operational by the time of certificate of occupancy, and due to
circumstances out of the control of and not otherwise due to the negligence or willful
misconduct on behalf of the building owner,the renewable energy system is not
constructed or is not operational,then the building owner shall be allowed up to one
year after the certificate of occupancy is issued to meet 144-R502.4.1.4 (C).
D. Where the renewable energy system ceases operation, or the owner cannot legally claim the
associated energy or RECs for any reason,the building owner shall produce or procure
alternative qualifying renewable energy in an amount equal to or greater than the amount
needed to earn the same number of points under the requirements of 144-R502.4.1.2.
144-R502.4.1.5 Reporting and Documentation
A. The building owner shall submit documentation of renewable energy system ownership or
renewable energy procurement,which includes subscription to a community solar project.
Records on power and thermal energy produced or purchased by the building owner from the
renewable energy producer shall be retained by the building owner on behalf of the entity
demonstrating financial or operational control over the building seeking compliance to this
standard and submitted to the Code Enforcement Officer on an annual basis for no less than 15
years.Any period of non-compliance shall not count toward fulfillment of the 15-year
requirement.
B. For systems generating electricity, documentation shall be provided to the Code Enforcement
Officer that indicates an exclusive chain of custody and ownership of the RECs from the
renewable energy system to the building owner, on an annual basis for no less than 15 years.
RECs supplied from the renewable energy system shall be conveyed to and retired on behalf of
the entity who has financial or operational control over the building's electricity consumption.
The annual generation vintage date of delivered RECs shall be allocated to the same 12-month
reporting year, up to six months prior, or up to three months after the calendar year in which
the electricity is used in the building. Any period of non-compliance shall not count toward
fulfillment of the 15-year requirement.
Exceptions to 144-R502.4.1.5 (B)
1. If the total capacity of all renewable energy systems being used to earn points under
144-R502.4.1 is less than 25 kW,the requirements of 144-R502.4.1.5(B) shall be waived.
2. Where the building owner cannot provide documentation on the chain of custody or
ownership of the RECs from the renewable energy system,the building owner shall
provide documentation to the Code Enforcement Officer of an alternate supply contract
for replacement RECs from an alternate renewable energy source.The quantity of RECs
Energy Code Supplement(ECS) -Adopted 2021-06-14 49
contracted for shall be equal to or greater than the amount needed to earn the desired
number of points under the requirements of 144-R502.4.1.2.These RECs shall comply
with the Green-e®Renewable Energy Standard for Canada and the United States(latest
edition) and shall be conveyed to and retired on behalf of the entity who has financial or
operational control over the building's electricity consumption.
C. Electricity,thermal energy and RECs from renewable energy systems may not be counted more
than once for purposes of demonstrating compliance with this subsection 144-R502.4.1.The
reporting and documentation required in 144-R502.4.1.4 shall clearly state how the energy and
RECs are allocated to specific buildings.The TOWN may request additional documentation to
provide reasonable proof of ownership/procurement, and fulfillment of RECS and allocation
requirements.
D. In the case of full or partial transfer of ownership of the building,the following must be
provided: proof of transfer of ownership; a signed statement from the new owner stating they
understand the requirements of this subsection 144-R502.4.1 and the duty to fulfill them; and
contact information for the person(s) responsible for submitting annual reporting.
144-R502.4.2 RE2 Biomass Space Heating
Five points may be earned according to the requirements below.
144-R502.4.2.1
Only BIOMASS systems shall be used for all space-heating needs, with exceptions for electric resistance
heating as described in 144-R502.4.2.4.
144-R502.4.2.2
FOSSIL FUELS shall not be used for any space heating, space cooling or ventilation systems in the building,
including backup heating systems.
144-R502.4.2.3
All BIOMASS equipment must comply with the NYSERDA Renewable Heat NY program guidelines,
available at www.nvserda.nv.gov/All-Programs/Programs/Renewable-Heat-NY.
144-R502.4.2.4
To allow flexibility,electric resistance heat is allowed for a portion of space heating needs.Applicants shall
submit documentation showing that at least one of the following conditions is met.
A. Stand-alone electric resistance heating is used to heat 10% or less of the building heated FLOOR
AREA.
B. Stand-alone electric resistance heating is used to meet 10% or less of the building's projected
annual space heating load.
Energy Code Supplement(ECS) -Adopted 2021-06-14 50
3.44-1:1502. (."hh r Points .�w�..��..�..m..............................................................................................................................................................................
144-11502.5.1 OP1 Development Density
One point may be earned according to the requirements below.
Restrictions: A maximum of two points total may be earned for points OP1 Development Density, OP2
Walkability, and OP3 Electric Vehicle Parking Spaces combined.
144-R502.5.1.1
One point shall be earned if(DU +CA) > (7 x Acreage),where:
DU =the number of all Residential dwelling units on the entire parcel occupied by the building
CA=the FLOOR AREA of all Commercial space, measured in units of 1,000 square feet, on the entire parcel
occupied by the building
Acreage=the land area, measured in acres, of the entire parcel occupied by the building.
144-R502.5.1.2
DU shall include all dwelling units on the parcel occupied by the building, including those in existing
buildings. CA shall include all Commercial space on the parcel occupied by the building, including that in
existing buildings. CA shall not include common areas serving only dwelling units or other Residential
space.Acreage shall include all land area on the parcel occupied by the building.
Example Calculation-for informational purposes only
Mixed Use Development
Residential units: 12 apartments 4 DU = 12
Commercial space: 10,000 sq ft 4 CA= 10
Parcel acreage: 1.5 acres 4 Acreage= 1.5
DU +CA= 12+ 10=22
7 x Acreage=7 x 1.5 = 10.5
22 > 10.5
1 point may be earned.
144-11502.5.2 OP2 Walkability
One point may be earned according to the requirements below.
Restrictions: A maximum of two points total may be earned for points OP1 Development Density, OP2
Walkability, and OP3 Electric Vehicle Parking Spaces combined.
144-R502.5.2.1
This point shall be earned when either of the following two conditions is met, in addition to the other
requirements in this subsection 144-R502.5.2.
A. The building is within one quarter(0.25) mile of at least five of the Neighborhood Amenity Types
listed in Table 144-R502.5.2.1.
Energy Code Supplement(ECS) -Adopted 2021-06-14 51
1. No single Amenity Type shall be counted more than twice, even when more than two
examples of the Amenity Type exist. For example, a building on Aurora Street's
"Restaurant Row" could count two RESTAURANTS maximum.
2. At least two Amenity Categories shall be represented.
3. The one quarter mile measurement(s) may be taken from any part(s) of the building.
B. The building is within a TOWN development priority area for which a regulating plan has been
developed and adopted.
144-R502.5.2.2
For all buildings, at the time of project completion, sidewalks, walkways and/or trails must be present on
the property or within 75 feet of the property, and connect to an existing network of pedestrian
infrastructure.
Energy Code Supplement(ECS) -Adopted 2021-06-14 52
Table 144-R502.5.2.1
Neighborhood Amenity Types and Categories
Amenity Category Amenity Type
Food retail Supermarket
Grocery with produce section
Community-serving retail Convenience store
Farmers market
Hardware store
Pharmacy
Other retail
Services Bank
Family entertainment venue (e.g., theater, sports)
Gym, health club, exercise studio
Hair care
Laundry, dry cleaner
Restaurant, cafe, diner(excluding those with only drive-
thru service)
Civic and community facilities Adult or senior care(licensed)
Child care(licensed)
Community or recreation center
Cultural arts facility(museum,performing arts)
Education facility(e.g.,K-12 school,university, adult
education center,vocational school, community college)
Government office that serves public on-site
Medical facility that treats patients
Place of worship
Post office
Public library
Public park
Social services center
144-R502.5.3 OP3 Electric Vehicle Parking Spaces
One point may be earned for installing ELECTRIC VEHICLE PARKING SPACE(s)and related infrastructure that meet
the requirements of this subsection.
Restrictions: A maximum of two points total may be earned for points OP1 Development Density, OP2
Walkability, and OP3 Electric Vehicle Parking Spaces combined.
144-R502.5.3.1 Required Number of EV Parking Spaces
The number of required EV PARKING SPACES shall be determined using Table 144-R502.5.3.1(1), based on
the number of Residential Dwelling Units (DU) and the area of Commercial space (CA).
Energy Code Supplement(ECS) -Adopted 2021-06-14 53
DU =the number of Residential dwelling units in the building.
CA=the area of all Commercial space, measured in units of 1,000 square feet, in the building.CA shall not
include common areas serving only dwelling units or other portions of Residential space.
When determining the total number of required spaces in MIXED-USE BUILDINGS, EV SPACE requirements for
Residential Dwelling Units and for Commercial space shall be calculated separately and summed.
Table 144-R502.5.3.1 (1)
Required Number of Electric Vehicle Parking Spaces
Residential Space Commercial Space
Number of EV Number of EV
Number of Area in units of 1,000 Sq.
Dwelling Units (DU) Spaces Required for Ft(CA) Spaces Required for
Residential Portion(SR) Commercial Portion(SC)
1 to 6 1 5 2
7 to 13 2 10 3
14 to 20 3 15 5
21 to 24 4 20 6
25 to 30 5 25 7
31 to 38 1 6 30 1 9
39 to 46 7 35 10
47 to 53 8 40 12
For up to 53 Dwelling Units,use table. The numbers listed above are examples.
For 54 or more Dwelling Units: For all building sizes use the equation:
SR=(0.13 x DU)+1 SC=0.28xCA
Complete Residential and Commercial calculations Complete Residential and Commercial calculations
separately, add results, and round up to nearest separately, add results, and round up to nearest
whole number: whole number.
SR+SC=ST(Total EV Parking Spaces) SR+SC=ST(Total EV Parking Spaces)
Energy Code Supplement(ECS) -Adopted 2021-06-14 54
Table 144-R502.5.3.1 (2)
Sample Calculation for required
number of EV Parking Spaces
Sample Calculation
44,300 sq ft mixed-use building. 26 Dwelling Units (DU)and 6,000 sq ft Commercial Area(CA)
SR=(0.13 x 26)+ 1
SR=3.4+ 1 =4.4
4.4 EV spaces are required for Residential portion
SC=0.28x6
SC= 1.7
1.7 EV spaces are required for Commercial portion
ST= SR+ SC rounded up
ST=4.4+ 1.7=6.1,round up
7 EV spaces are required for the building to earn a point.
144-R502.5.3.2
The requirements for this point as set forth here and in Table 144-R502.6 are NOT intended to override
or supplant existing zoning code provisions regarding parking requirements. To the extent that zoning
permissible parking spaces cannot be accommodated on the building site,the building must seek off-site
spaces in accordance with the provisions of this point and applicable zoning laws, where zoning allows
off-site parking spaces.
144-R502.5.3.3
All ELECTRIC VEHICLE PARKING SPACES shall be located on the same parcel as the building, in the same parking
facilities as those used by one or more of the following target user groups:customers/clients; employees;
and fleet vehicles. If no parking facilities exist on the same parcel, and off-site parking facilities do exist
for one or more of the user groups, then EV PARKING SPACES may be installed in those off-site parking
facilities. Off-site parking must be within 0.25 miles of the building.
144-R502.5.3.4
All ELECTRIC VEHICLE PARKING SPACES shall be served by a dedicated Electric Vehicle Charging port. ELECTRIC
VEHICLE CHARGING STATIONS may have any number of ports.
144-R502.5.3.5
At least one Accessible ELECTRIC VEHICLE PARKING SPACE is required in any parking facility that includes more
than 10 ELECTRIC VEHICLE PARKING SPACES. Any parking facility with more than 50 ELECTRIC VEHICLE PARKING
SPACES must provide at least two Accessible ELECTRIC VEHICLE PARKING SPACES.The associated space(s)are not
required to be designated only for accessible parking, as defined by the Building Code of NYS, but must
meet all other accessibility requirements contained in New York State law.
Energy Code Supplement(ECS) -Adopted 2021-06-14 55
144-R502.5.3.6
All buildings must install Level 2 EV charging stations that operate on a 240-volt AC circuit and/or Direct
Current Fast Chargers.
144-R502.5.3.7
ELECTRIC VEHICLE PARKING SPACES shall be provided with a dedicated branch circuit, raceways, and all other
electric vehicle charging equipment. The branch circuit shall be identified for electric vehicle service in
the service panel or subpanel directory. Electrical room(s) serving areas with EV PARKING SPACES shall be
designed to accommodate the electrical equipment and distribution required to serve all of the ELECTRIC
VEHICLE CHARGING STATIONS.
144-R502.5.3.8
ELECTRIC VEHICLE CHARGING STATION equipment shall be maintained in all respects, including the functioning
of the charging equipment. A phone number or other contact information shall be provided on the
charging station equipment for reporting when the equipment is not functioning, or other problems are
encountered.
144-R502.5.3.9
The ELECTRIC VEHICLE CHARGING STATION, including the charging cord, shall be installed so as to not interfere
with pedestrian walkways at anytime.
144-R502.5.3.10
Except for Accessible EV PARKING SPACES, each EV PARKING SPACE shall be posted with signage indicating that
the space is only to be used for electric vehicle charging purposes. Days and hours of operations and any
other restrictions on use of the parking space shall be included if time limits or tow-away provisions are
to be enforced.
144-R502.5.4 OP4 Adaptive Reuse
One point may be earned according to the requirements below.
144-R502.5.4.1
The building must maintain 50%or more of the existing building structure and BUILDING THERMAL ENVELOPE.
The existing building structure must be re-purposed for a different permitted use (for example, when an
old school is adapted for use as apartments). A MAJOR RENOVATION of a building and re-use for the same
purpose shall not be eligible for this point.
144-R502.5.5 OP5 NY Stretch Code
Two points may be earned according to the requirements below.
144-R502.5.5.1
The building shall comply with all requirements of the NYStretch Energy Code-2020 Version 1.0,which is
available at:
Energy Code Supplement(ECS) -Adopted 2021-06-14 56
www.nyserda.ny.gov/AI I-Progra ms/Progra ms/Energy-Code-Tra i n i ng/NYStretch-Energy-Code-2020
144-11502.5.6 OP6 Custom Energy Improvement
Up to two points may be earned according to the requirements below.
144-R502.5.6.1
To earn one point, both of the following conditions must be met:
A. Reduce ENERGY USE by 1.2 kWh/SF/year or 4.1 kbtu/SF/year for all residential HEATED FLOOR AREA in
the building.
B. Reduce ENERGY USE by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all commercial HEATED FLOOR AREA in
the building.
144-R502.5.6.2
To earn two points, both of the following conditions must be met:
A. Reduce ENERGY USE by 2.4 kWh/SF/year or 8.2 kbtu/SF/year for all residential HEATED FLOOR AREA in
the building.
B. Reduce ENERGY USE by 4.8 kWh/SF/year or 16.4 kbtu/SF/year for all commercial HEATED FLOOR AREA
in the building.
144-R502.5.6.3
Multiple improvements may be combined to achieve each point under this improvement. Improvements
may be made anywhere in the building as long as they meet the thresholds of ENERGY USE reduction. The
proposed energy improvement(s) shall be submitted to the Code Enforcement Officer in writing, signed
by the DESIGN PROFESSIONAL or ENERGY PROFESSIONAL. Energy reduction must be shown through energy
analysis performed by a DESIGN PROFESSIONAL or ENERGY PROFESSIONAL. Simplified calculations (e.g.
spreadsheet) are acceptable.
144-R502.5.6.4
For a baseline, use the 2016 Energy Conservation Construction Code of New York State. If the baseline
condition is not addressed by the ECCCNYS, use baseline conditions as defined in Appendix G of ASHRAE
Standard 90.1-2013, or RESNET HERS (latest edition).
144-R502.5.6.5
Production of renewable energy shall not count toward energy reduction. Energy reduction must be
calculated after applying all other proposed energy improvements to the proposed design. In other words,
interactive energy savings must be performed. Savings cannot be taken for improvements made with
other points, such as right-lighting or the NY Stretch Energy Code.
1,44-1:1 2.6 Jnnnn r „I" be for PresCrl pflve Comp� De
..... .o cD.. tO � .s
................................................................................................................... ........................................................... ........... .. ........ .............. .... .... . . ....D..I..............t.......O........
The following Table 144-R502.6 is a summary of the PRESCRIPTIVE COMPLIANCE PATH / EASY PATH for
RESIDENTIAL BUILDINGS. This is a summary for informational purposes only. To earn points, all applicable
Energy Code Supplement(ECS) -Adopted 2021-06-14 57
requirements in subsections 144-R502.1, 144-R502.2, 144-R502.3, 144-R502.4 and 144-R502.5 must be
met. In case of discrepancies between Table 144-R502.6 and the requirements in subsections 144-R502.1,
144-R502.2, 144-R502.3, 144-R502.4 and 144-R502.5,the latter shall hold precedence.
Energy Code Supplement(ECS) -Adopted 2021-06-14 58
Table 144-11502.6
Residential Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least six points
Cate- Improvement Points Details
gory I
EFFICIENT ELECTRIFICATION
EE1 Heat pumps for space 3 -5 3 points for air source heat pumps.
heating 5 points for ground source heat pumps.
Heat pumps for domestic hot
EE2 1 1 point for water heating systems that use heat pumps.
water heating
Commercial cooking 3 points for electric cooking equipment in restaurants and other
EE3 3 food service buildings.Prerequisite: no fossil fuel use in the
electrification building.
EE4 Residential cooking and I 1 point for electric stoves and ventless heat pump clothes dryers.
clothes drying electrification Prerequisite: no fossil fuel use in the building.
AFFORDABILITY IMPROVEMENTS
All Smaller building/room size 1 -2 Up to 2 points for smaller room sizes.Available for Hotel and
Residential portions only.
Heating systems in heated
AI2 1 1 point for installing heating systems in directly heated spaces.
space
AI3 Efficient building shape 1 1 point if exterior surface area divided by directly heated floor
area is less than the maximum allowed value.
AI5 Modest window-to-wall 1 1 point for overall window-to-wall ratio less than 20%
ratio (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE Renewable energy systems 1 -3 Up to 3 points for on-site or off-site renewable electric systems
or on-site renewable thermal systems.
RE2 Biomass systems 5 5 points for biomass space heating systems.
OTHER POINTS
1 point for achieving sufficient development density on the
OP 1 Development density 1 building parcel.A maximum of two points total may be earned
for points OP I,OP2,and OP3 combined.
1 point if the building meets the walkability criteria.A
OP2 Walkability 1 maximum of two points total may be earned for points OP 1,
OP2,and OP3 combined.
Electric Vehicle Parking 1 point for installing electric vehicle parking spaces and related
OP3 1 infrastructure.A maximum of two points total may be earned for
Spaces points OP1,OP2,and OP3 combined.
OP4 Adaptive reuse 1 1 point for substantial re-purpose of existing building.
OP5 Meet NY Stretch Code 2 2 points for complying with NYStretch Energy Code
OP6 Custom energy improvement 1 -2 Up to 2 points for reduction in energy use.
Energy Code Supplement(ECS) -Adopted 2021-06-14 59
SUBSECTION 144-R503 PERFORMANCE-BASED COMPLIANCE PATH/WHOLE
BUILDING PATH
.1,44 [1.503,1 Generai
.......................................................................................................................................
Until January 1,2023,to meet the requirements of this subsection 144-11503,a building must comply with
any one of the high-performance building approaches described in 144-R503.2, 144-R503.3, 144-R503.4,
144-R503.5 and 144-R503.6. See 144-R504 for enhanced requirements beginning on and after January 1,
2023, and additional enhanced requirements beginning on and after January 1, 2026.
1,44-1:1 3.2 i:�,n�%,r l3atin.1 Ilncje..x,.bas n Comp iian� n
........................................... ' ......................................... ............................................................................................................................ .........................................
Restrictions: This compliance method may only be used for RESIDENTIAL BUILDINGS of not more than three
stories.
144-R503.2.1
The building shall comply with all requirements of Subsection R406 Energy Rating Index Compliance
Alternative of the 2020 Energy Conservation Construction Code of NYS (ECCCNYS R406). Where the
requirements of this Energy Code Supplement are more stringent than the requirements of ECCCNYS
R406, ECS requirements shall prevail.
144-R503.2.2
The rated design shall be shown to have an Energy Rating Index (ERI) less than or equal to 40 when
compared to the ERI reference design.
144-R503.2.3
Renewable energy generation that meets all applicable requirements for renewable energy systems
described in 144-R502.4.1 may be used to meet the requirements.
144-R503.2.4 Documentation
Compliance documentation shall be submitted as detailed in ECCCNYS R406.
1:15 3.3 Nationai Gree B ildin,; Standard Eased co.w ...han
.................................................................................................................................................... . ............................... ......................................................................................................................................... .................................
144-R503.3.1
Using the NATIONAL GREEN BUILDING STANDARD ("NGBS", also known as ICC/ASHRAE 700-2015),the building
shall earn no less than 80 NGBS Energy Efficiency points. NGBS certification is not necessary.
144-R503.3.2
Renewable energy generation that meets all applicable requirements for renewable energy systems
described in R502.4.1 may be used to meet the requirements.
Energy Code Supplement(ECS) -Adopted 2021-06-14 60
144'RS03'3'30gcurnentation
The DESIGN PROFESSIONAL or ENERGY PROFESSIONAL documenting compliance will provide a signed statement
that the design meets the requirements of this subsection, and documentation showing compliance.
144'R503'4'1
Buildings shall meet the design requirements of one of the following.
A. PH|US+ Passive Building Standard from Passive House Institute US
B. Passive House Classic Standard from Passive House Institute
Actual certification is not required. The most recent version of the chosen standard in effect at the time
of building permit application shall beused.
Documentation shall include at least one of the following:
A. Pre-certification letter (or other formal communication) from an Accnso|Tco PAss|vs Houss
Ccnrmcn, statin0thatDesi0nReviexvhasbeencomp|etedandthebui|din0isdesi0nedtomeetaU
requirements of the chosen Standard. All documentation used to show achievement of the
requirements must be submitted to the Code Enforcement Officer.
B. Documentation of PAss|vs HOUSE CERTIFICATION. All documentation used to achieve certification
must be submitted to the Code Enforcement Officer.
The building shall demonstrate a reduction in GREENHOUSE GAS (GHG) emissions of not less than 40Y6 as
compared to the baseline building.
144'R5Q3'5'1 Energy Modeling Standards
GHG emissions reductions shall be shown through energy modeling.
A. For Rcs|osmnxL Bu|Lo|wss four stories and greater and for xx|xso'usc au|Lo|mss classified as
residential, energy modeling shall comply with Appendix G of ASHRAE Standard 90.1-2013.
B. For RESIDENTIAL BUILDINGS of not more than three stories, energy modeling shall comply with
RESNET'HERS.
144'RSQ3'5'2 Process Loads
The GHG emissions reduction assessment and requirement shall exclude ENERGY USE by PROCESS LOADS.
However, the energy model shall include the energy used for PROCESS LOADS because energy used by
heating, cooling, and ventilation (including exhaust fans/hoods, makeup air fans, and heating/cooling for
makeup air) is subject tothe GHG emissions reduction requirement. After the baseline and proposed
energy models are run, for the GHG emissions reduction calculation, subtract out the PROCESS ENERGY use
from both the baseline and the proposed building energy model results, and use the resulting without-
process-energy results for the GHG emissions calculations.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 61
144-11503.5.3 Renewable Energy
Renewable energy generation may be used. All applicable requirements for renewable energy systems
described in 144-R502.4.1 must be met. Renewable energy generation used to achieve the 40%reduction
in GHG emissions is capped at 25% of the baseline energy use. The GHG emissions factor for electricity
produced by renewable energy systems shall be 0(zero) lb CO2e/MWh.
144-11503.5.4 GHG Emissions Factor for Electricity
For buildings not served by combined heat and power plants,the GHG emissions factor for electricity used
for all calculations shall be 548.37 lb CO2e/MWh
144-11503.5.5 GHG Emissions Factor for Electricity for Buildings Served by Combined Heat and Power
Plants
For buildings using electricity generated by combined heat and power (CHP) plants, the GHG emissions
factor for electricity shall be determined in one of the following ways:
A. The most recent heat rate data available at the time of building application shall be used from
www.eia.gov/electricity/annual/html/epa_08_02.html, for the specific type of generation plant
used, for electricity to be used in the proposed building, and the heat rate shall be multiplied by
the EPA emissions factor for the fuel used at the CHP plant. The result shall be used as the GHG
emissions factor for electricity from CHP plants.
B. Data gathered from actual operation of the CHP plant and its distribution network shall be used
to determine the site-specific GHG emissions factor for electricity to be used in the building. All
data used shall be made publicly available before the time of building permit application.
For buildings served by CHP plants, the baseline (reference building) electricity use GHG emissions shall
be the same as for buildings not served by a CHP plant.
144-11503.5.6
If a facility uses electricity from a combination of sources (e.g., utility, off-site renewable energy system,
and CHP plants), a weighted average of GHG emissions factors shall be used.
144-11503.5.7 Documentation
The following documentation shall be submitted to show compliance with 144-R503.5 in sufficient clarity
and detail:
A. A report, signed and stamped by an accredited third-party ENERGY PROFESSIONAL, showing the
results of all calculations, assumptions, inputs, and outputs for the energy model
B. A letter, signed and stamped by an accredited third-party ENERGY PROFESSIONAL, stating that
proposed total GHG emissions for the building are at least 40% less than the GHG emissions of
the baseline building.
C. The TOWN reserves the right to require additional documentation and/or additional third-party
review and analysis by a consultant selected by the TOWN,at the expense of the applicant.All such
documentation shall be submitted and fee shall be paid prior to issuance of a building permit.
Energy Code Supplement(ECS) -Adopted 2021-06-14 62
3.44-1:1503.6 Greenhouse Gas Ennissions Calculation-based Co.mip.j.jancefor Additions
Compliance using the requirements of this provision 144-R503.6 may only be used for additions that are
showing compliance together with the existing building. See also 144-202.2.
144'R503'6'1
The addition and the existing building, together as a whole, shall be shown to have lower total GHG
emissions than the original existing building.
144'R503'6'2
Current and proposed GHG emissions shall be calculated following the requirements of the GHG emissions
Calculation Method (R5O35).
144'R503'6'30gcurnentation
The following documentation shall besubmitted:
A. An energy study of the existing building that includes smcnGY USE from at least 12 consecutive
months of the most recent 24 months at the time of building permit application.
B. An energy study that shows anticipated ENERGY USE for the new addition and modified existing
building.
C. A report signed and stamped by an accredited ENERGY PROFESSIONAL, showing the results of all
calculations, assumptions, inputs, and outputs for the energy model.
D. A letter, signed and stamped by an accredited third-party ENERGY PROFESSIONAL, stating that
proposed total GHG emissions for the building and addition together are less than the GHG
emissions for the existing building.
E. The TOWN reserves the right to require additional documentation and/or additional third-party
review and analysis by a consultant selected by the TOWN, at the expense of the applicant.All
such documentation shall be submitted and fee shall be paid prior to issuance of a building
permit.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 63
SUBSECTION 144-11504FUTURE REQUIREMENTS
On January 1, 2023, the requirements of Subsections 144-11502 and 144-R503 shall change as described
in144'RSO4.2, 144'RSU4.3, 144'R5O4.4, and 144'RSO4.6. Where no changes are listed,the requirements
shall remain as described in Subsections 144'R5OZ and 144'RSO3.
Dn January 1, 2O2G, the requirements of Subsections 144'RSO1, 144'R5O2 and 144'RSU3 shall change as
described in 144'R504IVVhene no changes are listed, the requirements shall remain as described in
Subsections 144'RSU1, 144'RSO2 and 144'RSUI
Path
Effective January 1, 2023, to meet the requirements of subsection 144'11502, a building must achieve a
minimum of twelve (12) of the points described in subsection 144-R502. A summary table is provided in
144'R5O45
Effective January 1, 2023, all points awarded from 144'R5022 Efficient Electrification shall be doubled.
144'R504'3'1
SixpointsshaUbeearnedforusingmnsouncsHcArpuxxpsandmeetingtherequinementsof144'RSOII1
Heat Pumps for Space Heating. Ten (10) points shall be earned for using GROUND SOURCE HEAT Pumps and
meeting the requirements of144'R5OZ.2.1 Heat Pumps for Space Heating.
144'R504'3'2
Two points shall be earned for meeting the requirements of 144'R50I22 EE2 Heat Pumps for SERVICE
WATER HEATING.
144'R504'3'3
Six points shall be earned for meeting the requirements of 144'R502.2.3 EE3 Commercial Cooking
Electrification.
144'R504'3'4
Two points shall be earned for meeting the requirements of 144'R50I2.4 EE4 Residential Cooking and
Clothes Drying Electrification.
Energy Code Supplement(ECS) AdoptedZU21'OG'14 64
Effective January 1, 2U23 the maximum number of points allowed under 144'R5UZ.4.1RE1Renewable
Energy Systems shall increase to six(G) points.The criteria for earning points shall remain as described in
144'R502.41
3.44-1:1504.5 Ch n ,,�.es in 2023 to Sum.ri'i N FaWe fw� PN-�es.qjlpfive Co.m.lp rice ..........a............../
..... .....!Jar.ce P th E��as 1:)ath
............................................................................................... ..................................................................................................................................ii y................................................................................................................. ........................................................ .................... ......... ..........................y...................................
Residential Compliance Summary for Easy Path/Prescriptive Path
Projects must earn at least 12 points
Cate-
� Improvement Points Details
or
EFFICIENT ELECTRIFICATION
EEI Heat pumps for space 6 - 10 6 points for air source heat pumps.
heating 10 points for ground source heat pumps.
EE2 Heat pumps for domestic hot 2 2 points for water heating systems that use heat pumps.
water heating
Commercial cooking 6 points for electric cooking equipment in restaurants and other
EE3 electrification 6 food service buildings.Prerequisite: no fossil fuel use in the
building.
EE4 Residential cooking and 2 2 points for electric stoves and ventless heat pump clothes
clothes drying electrification dryers.Prerequisite:no fossil fuel use in the building.
AFFORDABILITY IMPROVEMENTS
All Smaller building/room size 1 -2 Up to 2 points for smaller room sizes.Available for Hotel and
Residential portions only.
Al2 Heating systems in heated I I point for installing heating systems in directly heated spaces.
space
A13 Efficient building shape I I point if exterior surface area divided by directly heated floor
area is less than the maximum allowed value.
A15 Modest window-to-wall 1 I point for overall window-to-wall ratio less than 20%
ratio (individual spaces may exceed 20%).
RENEWABLE ENERGY
RE I Renewable energy systems 1 -6 Up to 6 points for on-site or off-site renewable electric systems
or on-site renewable thermal systems.
RE2 Biomass systems 5 5 points for biomass space heating systems.
OTHER POINTS
I point for achieving sufficient development density on the
OP Development density I building parcel.A maximum of two points total may be earned
for points OP I,OP2,and OP3 combined.
I point if the building meets the walkability criteria.A
OP2 Walkability I maximum of two points total may be earned for points OP 1,
OP2,and OP3 combined.
Electric Vehicle Parking I point for installing electric vehicle parking spaces and related
OP3 Spaces I infrastructure.A maximum of two points total may be earned for
points OP1,OP2,and OP3 combined.
OP4 Adaptive reuse I I point for substantial re-purpose of existing building.
OP5 Meet NY Stretch Code 2 2 points for complying with NYStretch Energy Code
OP6 Custom energy improvement 1 -2 Up to 2 points for reduction in energy use.
Energy Code Supplement(ECS) -Adopted 2021-06-14 66
Effective January 1, 2023, the requirements of Subsection 144'R503 PcnponMxwcs'BxscoCoxxpuxmcz
PATH/WHOLE BUILDING PATH shall change as described in 144'R504.6.1, 144'R504.6.2, and 144'R504.63.
Where no changes are listed,the requirements shall remain as described in Subsection 144-R503.
144'115Q4'G'1 Changes tmEnergy Rating |ndem+based Compliance
Effective January 1, ZOZ3,the language of144'R5O3.2.Z shall be replaced with the following language:
The building must satisfy one of the following criteria:
A. The rated design shall be shown to have an Energy Rating Index (ER|) less than or equal to 20
when compared to the ER| reference design.
B. The rated design shall be shown to have an Energy Rating Index (ER|) less than or equal to 40
when compared to the ER| reference design AND seven ECS points from Subsection 144'11502
PRESCRIPTIVE COMPLIANCE PxT*/EAsYPxTH shall be earned. Points from A14 Ri0ht'Lightingand OPS
Meet NY Stretch Code may not be counted toward the seven ECSpoints.
144'R504'6'2 Changes tm National Green Building Standard'basedcmmmpUance
In addition to all existing requirements, seven ECS points from Subsection 144-R502 PRESCRIPTIVE
COMPLIANCE PATH/EASY PATH must be earned. Points from A14 Right-Lighting and OP5 Meet NY Stretch
Code may not be counted toward the seven ECSpoints.
144'11504'6'3 Changes tmGreenhouse Gas Emissions Calculation-based Compliance
Effective January 1, 2023,the building shall demonstrate a reduction in GREENHOUSE GAS (GHG) emissions
of not less than 8OY6as compared to the baseline building.
144'R504.6.3.1
Renewable energy generation used to achieve the 80% reduction in GHG emissions is capped at 50% of
the baseline energy use.
144'R504.6.3.2
For buildings not served by combined heat and power plants or renewable energy systems, the GHG
emissions factor for electricity used for all calculations shall be 285.8 |bCO2e/MVVh.
1.44-11504.7 Changes in 2026
Effective January 1, 2026, all buildings shall be built to have net-zero GHG emissions and shall not use
FOSSIL FUELS for space heating, water heating, or clothes drying.
144'11504'7'1
The language in144'R5O1.2 Application shall be replaced with:
Energy Code Supplement (ECS) AdoptedZU21'OG'14 67
RESIDENTIAL BUILDINGS of not more than three stories shall comply with all requirements of 144-R503.2
Energy Rating Index-based Compliance except 144-R503.2.2.The rated design shall be shown to have an
Energy Rating Index (ERI) less than or equal to 5 when compared to the ERI reference design.
RESIDENTIAL BUILDINGS four stories and greater shall comply with the requirements of the ZERO Code, using
the most recent version of the ZERO Code available at the time of permit application.The ZERO Code, an
Architecture 2030 initiative, is available at httRs j zero-code.org.
An ECS Compliance Plan shall be the basis for evaluating compliance.
144-R504.7.2
FOSSIL FUELS shall not be used for space heating, water heating or clothes drying. FOSSIL FUELS may be used
for PROCESS ENERGY and for cooking.
Energy Code Supplement(ECS) -Adopted 2021-06-14 68
Section 144-6 COMPLIANCE DOCUMENTATION AND
VARIANCES
SUBSECTION 144-601 Compliance Documentation
...1....4.4......f. .1.............3..
144-601.1.1
The following compliance documentation shall be submitted:
A. For the proposed point system, a checklist that shows which points are sought, and support for
each point. For example, if a developer is seeking the size credit for a house design, the checklist
would show the house area (square feet), number of bedrooms, required house size, and
proposed house size,to show that the house meets the size requirement.
B. For the proposed whole-building compliance, a report by a DESIGN PROFESSIONAL or ENERGY
PROFESSIONAL, at the time of planning review and again when applying for a building permit.
144-601.1.2
Compliance documents are available from the Town of Ithaca website and from the Town Code
Enforcement Department.
144-601.1.3
At the planning review phase, a preliminary green building checklist shall be submitted, indicating which
green compliance items are proposed/planned. A checklist shall be submitted with the construction
documents, prior to the building department issuing the building permit.
SUBSECTION 144-602 Variances
].44 6 2 d].
....................................................................
144-602.1.1
Any person aggrieved by an order, interpretation, or decision of a Code Enforcement Officer concerning
the application or requirements of the provisions of this chapter may take an appeal to the Zoning Board
of Appeals.
144-602.1.2
An application for an interpretation or variance shall be submitted to the Building and Code Enforcement
Department in a form substantially indicating the name and owner of the real property,the nature of the
condition for which an interpretation or variance waiver is sought, and the reasons for which an
interpretation or variance is sought.
Energy Code Supplement(ECS) -Adopted 2021-06-14 69
144-602.1.3
The applicant shall pay the TOWN the same fee as that set from time to time by Town Board resolution for
appeals to the Zoning Board of Appeals for area variances from zoning requirements.
144-602.1.4
The Zoning Board of Appeals shall, in accordance with the provisions of this chapter, review any order,
interpretation,or decision (including refusals of a building permit or certificate of occupancy or certificate
of compliance) of said Code Enforcement Officer where such order, interpretation, or decision is based
upon the requirements of this chapter.
144-602.1.5
The Zoning Board of Appeals, in hearing an appeal from the order, interpretation, or decision of the Code
Enforcement Officer, shall have the power to make its own interpretation (where an interpretation is
requested), and to grant variances from the standards and requirements of this chapter. Any standard or
requirement of this chapter may be varied, in whole or part, with regard to specific construction upon
application made by or on behalf of an owner, where the applicant meets its burden of demonstrating
strict compliance with such standard or requirement would entail practical difficulty or cause any
unnecessary hardship in relation to such construction, provided, however, that any such variance shall
provide for alternative energy conservation standards or requirements to achieve to the extent
practicable the purpose of this chapter to reduce GREENHOUSE GAS emissions.
144-602.1.6
In determining whether to grant a variance from a standard or requirement of this chapter, the Zoning
Board of Appeals shall take into consideration the benefit to the applicant if the variance is granted, as
weighed against the detriment to the health, safety and welfare of the community that would result by
such grant. In making such determination, the Zoning Board of Appeals shall also consider and make
findings on the following:
A. Whether the benefits sought by the applicant can be achieved by some method, feasible for the
applicant to pursue, other than a variance;
B. Whether the applicant has proposed to implement other energy or construction options, in place
of the standard or requirement that is the subject of the variance request, that will result in the
least amount practicable of additional GREENHOUSE GAS emissions.
C. Whether the variance request will result in a substantial amount of GREENHOUSE GAS emissions if
the request is granted.
D. Whether the variance request is unique to the building, project, or site and does not apply to a
substantial portion of the neighborhood or community.
E. Whether the requested variance is the minimum necessary.
F. Whether the alleged difficulty was self-created, which consideration shall be relevant to the
decision of the Zoning Board of Appeals but shall not necessarily preclude the granting of the
variance.
Energy Code Supplement(ECS) -Adopted 2021-06-14 70
144-602.1.7
If the Zoning Board of Appeals grants a variance, it shall grant the minimum variance necessary,condition
such grant on the imposition of alternative energy conservation standards or requirements to achieve to
the extent practicable the purpose of this chapter to reduce GREENHOUSE GAS emissions, and impose other
conditions as such Board may reasonably determine necessary to mitigate the consequences of the grant
of the variance.
144-602.1.8
The procedures relating to variances in Chapter 270, Zoning, of the Town of Ithaca Code, and the
procedures set forth in New York Town Law §267-a(5)-(9) and (11)-(13) shall apply, except to the extent
expressly provided otherwise herein or superseded hereby. Those subsections contain procedures and
requirements for the filing of administrative decisions;the time for appeal to the Zoning Board of Appeals;
stays upon appeal; hearings of appeals; time, filing and notice of Zoning Board of Appeals decisions;
compliance with the New York State Environmental Quality Review Act; rehearings; and voting
requirements. In addition to publication of the public hearing notice, the Zoning Board of Appeals notice
of the application shall also be given to all landowners owning property adjoining the property for which
an interpretation or variance is sought. The Zoning Board of Appeals notice shall also be posted on the
property in accordance with the posting provisions of§ 270-237 of the Town of Ithaca Code. To the extent
a procedure is not provided herein, the Zoning Board of Appeals may administratively adopt procedures
that are approved by the Town Board and published in the official Minutes of the Town Board of the Town
of Ithaca.
144-602.1.9
The actions and determinations of the Town of Ithaca,the Zoning Board of Appeals,the Town Board,and
the Code Enforcement Officer, as referenced in this chapter, shall be deemed final determinations for
purposes of Article 78 of the New York Civil Practice Laws and Rules(CPLR). Notwithstanding this,standing
under said Article 78 of the CPLR shall only be appropriate after the exhaustion of any administrative
reviews and/or appeals as provided for in this chapter.
144-602.1.10
Unless work has commenced in accordance with the variance granted by the Zoning Board of Appeals
within one year from the issuance of the building permit authorizing such work, or within 18 months of
the granting of such variance, whichever is earlier, not only the building permit but the variance shall
expire and the construction on the property shall revert to those ECS standards and requirements in effect
at the time of variance expiration.
144-602.1.11
If the building permit expires,the variance shall also expire at the same time.
Energy Code Supplement(ECS) -Adopted 2021-06-14 71
Appendix A - Lighting Power Allowances
Table 144-AA1 below provides the LIGHTING POWER ALLOWANCES (LPA), by space type, that are used to
determine compliance with EASY PATH point A14, Right Lighting.
Table 144-AA1. Interior Lighting Power Allowances
COMMON SPACE TYPESa LPA(watts/sq.ft)
Atrium
Less than 40 feet in height 0.015 per foot in
total height
Greater than 40 feet in height 0.2+0.01 per ft in
total height
Audience seating area
In an auditorium 0.32
In a convention center 0.41
In a gymnasium 0.33
In a motion picture theater 0.57
In a penitentiary 0.14
In a performing arts theater 1.22
In a religious building 0.77
In a sports arena 0.22
Otherwise 0.22
Banking activity area 0.51
Breakroom (See Lounge/Breakroom)
Classroom/lecture hall/training room
In a penitentiary 0.67
Otherwise 0.62
Conference/meeting/multipurpose room 0.62
Copy/print room 0.36
Corridor
In a facility for the visually impaired (and not used primarily by the staff)b 0.46
In a hospital 0.40
In a manufacturing facility 0.21
Otherwise 0.33
Courtroom 0.86
Computer room 0.86
Dining area
In a penitentiary 0.48
In a facility for the visually impaired (and not used primarily by the staff)b 0.95
In bar/lounge or leisure dining 0.54
Energy Code Supplement(ECS) -Adopted 2021-06-14 72
In a cafeteria or fast food dining 0.33
In family dining 0.45
Otherwise 0.33
Electrical/mechanical room 0.48
Emergency vehicle garage 0.28
Food preparation area 0.61
Guest room 0.24
Laboratory
In or as a classroom 0.72
Otherwise 0.91
Laundry/washing area 0.30
Loading dock; interior 0.24
Lobby
In a facility for the visually impaired (and not used primarily by the staff)b 0.90
For an elevator 0.32
In a hotel 0.53
In a motion picture theater 0.30
In a performing arts theater 1.00
Otherwise 0.45
Locker room 0.38
Lounge/Breakroom
In a healthcare facility 0.46
Otherwise 0.37
Office
Enclosed 0.56
Open plan 0.49
Parking area 0.10
Pharmacy area 0.84
Restroom
In a facility for the visually impaired (and not used primarily by the staff)b 0.61
Otherwise 0.49
Sales area 0.80
Seating area,general 0.27
Stairway(See space containing stairway)
Stairwell 0.35
Storage room 0.32
Vehicular maintenance area 0.34
Workshop
0.80
Energy Code Supplement(ECS) -Adopted 2021-06-14 73
BUILDING TYPE SPECIFIC SPACE TYPESa LPA(watts/sq.ft)
Facility for the visually impaired
In a chapel (and not used primarily by the staff) 1.11
In a recreation room (and not used primarily by the staff) 1.21
Automotive (See Vehicular Maintenance Area above)
Convention Center-exhibit space 0.73
Dormitory-living quarters 0.19
Fire Station-sleeping quarters 0.11
Gymnasium/fitness center
In an exercise area 0.36
In a playing area 0.60
Healthcare facility
In an exam/treatment room 0.83
In an imaging room 0.76
In a medical supply room 0.37
In a nursery 0.44
In a nurse's station 0.36
In an operating room 1.24
In a patient room 0.31
In a physical therapy room 0.46
In a recovery room 0.58
Library
In a reading area 0.53
In the stacks 0.86
Manufacturing facility
In a detailed manufacturing area 0.65
In an equipment room 0.37
In an extra high bay area (greater than 50'floor-to-ceiling height) 0.53
In a high bay area (25-50' floor-to-ceiling height) 0.62
In a low bay area (less than 25'floor-to-ceiling height) 0.60
Museum
In a general exhibition area 0.53
In a restoration room 0.51
Performing arts theater-dressing room 0.31
Post Office-Sorting Area 0.47
Religious buildings
In a fellowship hall 0.32
In a worship/pulpit/choir area 0.77
Retail facilities
In dressing/fitting room 0.36
Energy Code Supplement(ECS) -Adopted 2021-06-14 74
In a mall concourse 0.55
Sports arena-playing area
For a Class I facility° 1.84
For a Class II facilityd 1.20
For a Class III facilitye 0.90
For a Class IV facilityf 0.60
Transportation facility
In a baggage/carousel area 0.27
In an airport concourse 0.18
At a terminal ticket counter 0.40
Warehouse-storage area
For medium to bulky, palletized items 0.29
For smaller, hand-carried items 0.48
a) In cases where both a common space type and a building area specific space type are listed, the
building area specific space type shall apply.
b) A 'Facility for the Visually Impaired' is a facility that is licensed or will be licensed by local or state
authorities for senior long-term care, adult daycare, senior support or people with special visual
needs.
c) Class 1 facilities consist of professional facilities;and semiprofessional,collegiate,or club facilities with
seating for 5,000 or more spectators.
d) Class 11 facilities consist of collegiate and semiprofessional facilities with seating for fewer than 5,000
spectators; club facilities with seating for between 2,000 and 5,000 spectators; and amateur league
and high-school facilities with seating for more than 2,000 spectators.
e) Class III facilities consist of club, amateur league and high-school facilities with seating for 2,000 or
fewer spectators.
f) Class IV facilities consist of elementary school and recreational facilities;and amateur league and high-
school facilities without provision for spectators.
Informative Note: Table 144-AA1 is based on one from the Energy Conservation Code of NYS; the
LIGHTING POWER ALLOWANCES were reduced from the NYS Code to meet the needs of the ECS.
Energy Code Supplement(ECS) -Adopted 2021-06-14 75