HomeMy WebLinkAbout1979 LL 3 - Cross Connection Control LOCAL LAW #3 - (979
A LOCAL LAW FOR CROSS CONNECTION CONTROL
ARTICLE l. PURPOSE
The purpose of these regulations is to safeguard potable water supplies
by preventing backflow into public water systems.
The regulations are to be reasonably interpreted. It is the intent of these
regulations to recungnize that there are varying degrees of hazard and to
| | apply the� principle that the degree of protection should be commensurate
with the degree of h)
azard
'
ARTICLE II. DEFINITIONS
I' Cross-connections. The term "cross-connection" as used in these regulations
means any unprotected connection between any part of a water system used or
intended to supply water for drinking purposes and any source or system con-
taining water or substance that is not or cannot be approved as equally safe,
wholesome, and potable for human consumption.
2. Approved Water Supply. The term "approved water supply" means any water
supply approved by the State of New York Department of Health.
3. Auxiliary Supply. The term "auxiliary supply" means any water supply on
or available to the premises other than the approved public water supply.
4. Vacuum Breaker - Nonpressure Type. A vacuum breaker which is designed so
as not to be-subjected to static line pressure.
5' Vacuum Breaker - Pressure Type, A vacuum breaker designed to operate under
conditions of static line pressure.
b. Barometric Loop. A loop of pipe rising approximately 36 feet, at its topmost
point, above the highest fixture it supplies.
� ] 7. Approved Check Valve. The term "approve check valve" means a check valve
that seats readily and completely. It must be carefully machined to have free
moving parts and assured watertightness. The face of the closure element and valve
seat must be bronze composition, or other non-corrodible material which will
seat tightly under all prevailing conditions of field use. Pins and bushings
shall be of bronze or other non-corrodible, non-sticking material. machined
for easy, dependable operation. The closure element, e.g. clapper, shall be
internally weighted or otherwise internally equipped to promote rapid and
positive closure in all sizes where this feature is obtainable.
D. Approved Double Check Valve Assembly. The term "approved double check valve
assembly" means an assembly of at least two independently acting check valves,
including tightly closing shutoff valves on each side of the check valve assembly
and suitable leak-detector drains plus connections available for testing the
watertightness of each check valve.
This device must be approved as a complete assembly.
0. Approved Reduced Pressure Principle Backflow Prevention Device. The
term "approved reduced pressure pronciple backflow prevention device" means
a device incorporating two or more check valves and an automatically operating
differential relief valve located between the two checks, two shutoff valves"
and equipped with necessary appurtenances for testing. The device shall operate
� to maintain the pressure in the zone between the two check valves, less than the
� pressure on the public water suppply side of the device.
� ]
At cessation of normal flow. the pressure between check valves shall be less than
the supply pressure. In case of leakage of either check valve, the differential
relief valve shall operate to maintain this reduced pressure by discharging to the
atmosphere. When the inlet pressure is two pounds per square inch or less, the
relief valve shall open to the atmosphere, thereby providing an air gap in the
devioe. To be approved, these devices must be readily accessible for maintenance
and testing and installed in a location where no part of the valve will be
submerged, the enclosure must be self-draining, so that the large amount of water
which the relief valve may vent will be disposed of reliably without sub-
mergence of the relief valve.
This device must also be approved as a complete assembly.
10. Air Gap Separation. The term "air gap separation" means a physical
break between a supply pipe and a receiving vessel. The air gap shall
be at least double the diameter of the supply pipe, measured vertically
above the top rim of the vessel, in no case less than one inch.
ll. Water Supervisor. The term "water supervisor" means the consumer or
person on the premises charged with the responsibility of complete knowledge
and understanding of the water supply piping within the premises and for
maintaining the consumer's water system free from cross-connections and
other sanitary defects, as required by regulations and laws. �
|
12. Certified Backflow Prevention Device Tester - is a person who is
examined annually annuully by the water pureyor, and found competent for the testing
-�
of backflow prevention devices. He shall be provided with an appropriate
identification card which must be renewed annually. Failure to perform
his duties competently and conscientiously will result in prompt withdrawal
of his certification.
'
ARTICLE III
PROTECTION OF PUBLIC NATER SYSTEM AT SERVICE CONNECTION
Section I. Where Protection is Required.
l. Each service connection from a public water system for supplying
water to premises having an auxiliary wter supply shall be protected
against backflow of water from the premises into the public water system
unless the auxiliary water supply is approved as an additional source by
the water purveyor and is satisfactory to the public health agency
having jurisdiction with regard to quality and safety,
2. Each service connection from a public water system for supplying
water to premises, on which any substance is handled under pressure in
such fashion as to permit entry into the water system, shall be protected -
against backflow of the water from the premises into the public system, |
This shall include the handling of process waters and waters orginetiog --J
from the public water supply system which may have been subject to deter-
ioration in sanitary or chemical quality.
J. Each service connection from a public water system for supplying
water to premises on which a substance of unusually toxic concentration
or danger to health is handled in liquid form, even though it is not under
pressure, shall be protected against backflow of the water from premises
into the public system. Examples are plating factories, using cyanide and
hospitals. This is not intended to apply to normal household installations.
4. Backflow prevention devices shall �e installed on the service connection
to any premises that have internal cross connections, unless such cross-
connections are abated to the satisfaction of the water purveyor.
It shall be the responsibility of the water user to provide and maintain
these protective devices, and each one must be of a type acceptable to the
State Health Department.
Section l[. Type of Protection. The protective device required shall depend on
the degree of hazard as tabulated below:
l. At the service connection to any premises where there ia an auxiliary
water supply handled in a separate piping system with no known cross-
connection, the public water supply shall be protected by an approved |
double check valve assembly. �
2. At the service connection to any premises on which theere is an
auxiliary water supply where cross-connections are know to exist which
cannot be presently eliminated, the public water supply system shall be
protected by an air gap separation or an approved reduced pressure principle
backflow prevention device.
3. At the service connection to any premise on which a substance that would
be objectionable (but not necessarily hazardous to health if introduced into
the public water supply) is handled so as to constitute a cross-connection. the
public water supply shall be protected by an approved double check valve
assembly.
4. At the service connection to any premise on which a substance of
unusual toxic concentration or danger to health is or may be handled;
but not under pressure, the public water supply shall be protected by an
air gap separation or an approved reduced pressure principle backflow
prevention device. This device shall be located as close as practicable
to the water meter, and all piping between the water meter and receiving
tanks shall be entirely visible.
S. At the service connection to any premise on which any material
dangerous to health, or toxic substance in toxic concentration, is or
may be handled under pressure, the public water supply shall be protected
| � by an air gap separation. The air gap shall be located as close as pract-
icable to the water meter" and piping between the water meter and receiving
tanks shall be entirely visible. If these conditions cannot reasonably be
met, the public water supply shall be protected with an approved reduced
'
pressure principle backflow prevention device, providing the alternative
is acceptable to the water purveyor.
h. At the service connection ao any sewage treatment plant or sewage
pumping station, the public water supply shall be protected by an air
gap separation. The air gap shall be located as close as practicable
to the water meter and all piping between the water meter and receiving
tanks shall be entirely visible. If these conditions cannot be
reasonably metm the public water supply shall be protected with an
approved reduced pressure principle backflow prevention device.
Section III. Frequency of Inspection of Protective Devices.
It shall be the duty of the water user on any premises on account of
which backflow protective devices are installed, to have competent
inspections made at least once a year, or more often in those instances
where successive inspections indicate repeated failure. These devices
shall be repaired, overhauled or replaced at the expense of water
user whenever they are found to be defective. These tests shall be performed
by a qualified backflow prevention device tester, and all test results will
be provided to the water purveyor within 72 hours after the test is made.
\ J
Records of such tests, repairs and overhaul shall also be kept and made
available to the water purveyor and the local health department upon request.
ARTICLE IV
PROTECTION OF POTABLE WATER SYSTEM WITHIN PREMISES
Section I. Separate Drinking Water Systems.
Whenever the plumbing inspector determines that it is not practical to
protect drinking water systems on premises against entry of water from
a source or piping system or equipment that cannot be approved as safe
or potable for human use, an entirely separate drinking water system
shall be installed to supply water at points convenient for consumers.
Section TI. Fire Systems.
Water systems for fighting fire, derived form a supply that cannot be
approved as safe or potable for human use shall, wherever practicable,
�- be kept wholly separate from drinking water pipelines and equipment. In
cases where the domestic water system is used for both drinking and
firefighting purposes, approved backflow prevention devices shall be
installed to protect such individual drinking water lines as are not
� | used for fire-fighting purposes. Any auxiliary fire-fighting water supply
� ] which is not approve for potable purposes, but which is so connected that
it may be introduced into potable water piping furing an emergency
shall be equipped with an approved automatic chlorination machine. It
is hereby declared that is is the responsibility of the person or persons
causing the introduction of said unapproved or unsafe water into the
pipelines to see: (l) that a procedure be developed and carried out to
notify and protect users of this piping system during the emergency (2)
that special precautions be taken to disinfect thoroughly and flush
out all pipelines which may become contaminated before they are again
used to furnish drinking water. In the event the means of protection of
water consumers is by disinfection of the auxiliary fire-fighting supply,
the installation and its use shall be thoroughly reliable.
The public water supply must be protected against backflow from
such dual domestic systems, as setailed in Article III.
Section III. Process Waters.
Potable water pipelines connected to equipment for industrial
processes or operations shall be protected by a suitable backflow
prevention device located beyond the lost point from which
drinking water may be taken, which device shall be provided
on the feed line to process piping or equipment.
In the event the particular process liquid is especially corrosive ! |
or apt to prevent reliable action of the backflow prevention device, |- �
air gap separation shall be provided. These devices shall he tested
by the water user at least once a year; or more often in those instances
where successive inspections indicate repeated failure. The devices
shall be repaired, overhauled or replaced whenever they are found to
be defective. These tests must be performed by a qualified backflow
prevention device tester and records of tests, repairs, and replacement
shall be kept and made available to the water purveyor and the health
departmentupon request.
Section IV. Sewage Treatment Plants and Pumping Stations.
Sewage pumps shall not have priming connections directly off
any drinking water systems. No connections shall exist between
the drinking water system and any other piping" equipment, or
tank in any sewage treatment plant or sewage pumping station.
Section V. Plumbing Connections.
Where the circumstances are such that there is special danger .
to health by the backflow of sewage, as from sewers, toilets,
hospital bedpans and the like, into a drinking water system,
a dependable device or devices shall be installed to prevent
such backflow. ' l
' ' |
�
The purpose of these regulations is not to transcend local —�
plumbing regulations but only to deal with these extraordinary
situations where sewage may be force or drawn into the drinking
water pining. These regulations do not attempt to eliminate at
this time the hazards of back-siphonage through flushometer
valves on all toilets, but deal with those situations where
the likelihood of vacuum conditions inthe drinking water system -
is definite and there is special danger to health. Devices suited
to the purpose of avoiding back-siphonage from plumbing fixtures
are roof tanks" barometric loops or separate pressure systems separately
piped to supply such foxtures, recognized approved vacuum or siphon
breaker and other backflow protective devices which have been
proved by appropriate tests to be dependable for destroying
the vacuum.
Inasmuch as many of serious hazards of this kind are due to water
supply piping which is too small. thereby causing vacuum conditions
when fixtures are flushed or water is drawn from the system in other
ways, it is recommended that water supply piping that is too small
be enlarged whenever possible.
Section VI. Pier and Dock Hydrants. ^
Backflow protection by a suitable backflow Prevention device shall be �
provided oneach drinking water pierhead outlet used for supplying vessels �
at piers or waterfronts. THese assemblies must be located where they
will prevent the return of any water from the vessel into the drinking
water pipeline or into another adjacent vessel. This will prevent such
practices as connecting the ship fire-pumping or sanitary pumping system
with a dock hydrant and therby pumping contaminated water into the drinking
water system, and thence to adjacent vessels or back into the pudic mains.
Section VII. Marking Safe and Unsafe Nater Lines.
Where the premises contain dual or multiple water systems and piping,
the exposed portions of pipelines shall be painted, nanded or marked
at sufficient intervals to distinguish clearly which water is safe
and which isnot safe. All outlets from secondary or other potentially
contaminated systems shall be posted as being contaminated and unsafe
for drinking purposes. All outlets intended for drinking purposes
shall be plainly marked to indicate that fact.
Nater Supervisor. The health department and the water purveyor shall
be kept informed of the identity of the responsible for the
water piping on all premises concerned with these regulations. At
eacb Promixe where it is necessary in thempininn of the water purveyor
�
y | a wer supervisor shall be designated. This water supervisor
shall be responsible for the installation and use of pipelines and
equipment and for the avoidance of cross-connections.
�-�
In the event of contamination or pollution of the drinking water
system due to a cross-connection on the premises, the local health
officer and water purveyor shall be promptly advised by the person
responsible for the water system so that appropriate measures may
be taken to overcome the contamination.
ARTICLE V
RECOURSE FOR NON-COMPLIANCE
Section l, No water service connection to any premises shall be installed
or maintained by the water purveyor, unless the water supply is
protected as required by state regulations and this rule.
Section II, Service of water to any premises may be discontinued by the
water purveyor, if a backflow preventive device required by
this rule and regulation isnot installed, tested, and maintained;
if any defect is found in a installed backflow preventive device;
if it is found that a backflow preventive device has been removed or
bypassedl if unprotected cross-connections exist on the premises,
and service will not be restores until such conditions or defects
are corrected.
ARTICLE VI
EFFECTIVE DATE
This local law shall take effect immediately-
'