HomeMy WebLinkAbout12a Jerry Smith ESS_Fire Safety Compliance Plan N exa m p Energy Storage Fire Safety Compliance Plan Document Scope This document provides a reference guide describing how Nexamp's standalone battery energy storage system (BESS) projects comply with the New York State Fire Code (NYSFC) 2025,specifically Chapter 12 -Section 1207: Electrical Energy Storage Systems. The purpose of this document is to summarize how the energy storage system proposed for the following project meets the applicable requirements of NYSFC Section 1207: • Jerry Smith Energy Storage Project This document presents a structured review of the relevant code provisions and identifies how the project design, equipment specifications,operational procedures,and supporting documentation demonstrate compliance with the applicable fire code requirements. This document does not reproduce the full text of the New York State Fire Code and should be reviewed in parallel with the official NYSFC 2025 publication and other applicable codes and standards.The document is intended to support review by the Authority Having Jurisdiction (AHJ),fire departments, and other stakeholders evaluating project safety and code compliance. This document describes the fire code requirements only as they apply to the proposed outdoor,grid-scale electrochemical energy storage systems for the referenced projects. Additional requirements may apply based on local jurisdictional amendments,site-specific conditions,or determinations by the AHJ. Project design, installation,and operation will also follow applicable national standards and referenced codes including where applicable: • NFPA 855 -Standard for the Installation of Stationary Energy Storage Systems • NFPA 70-National Electrical Code • UL 9540-Energy Storage System Safety Standard • UL 9540A-Thermal Runaway Fire Propagation Testing • Applicable New York State Building and Fire Codes Supporting project documentation referenced in this compliance guide may include: • Hazard Mitigation Analysis (HMA) • Emergency Response Plan (ERP) • System commissioning documentation • Manufacturer safety and certification documentation • Site design drawings and equipment layouts • Operations and maintenance procedures This document is intended to assist regulators,fire officials,and project stakeholders in reviewing the safety design of the energy storage systems and verifying compliance with the applicable fire code requirements. References The following codes,standards,and project documents are referenced throughout this compliance guide: • New York State Fire Code (NYSFC) 2025 -Chapter 12, Section 1207 • New York State Building Code (2025) • NFPA 855 -Standard for the Installation of Stationary Energy Storage Systems • NFPA 70-National Electrical Code • UL 9540 - Energy Storage Systems • UL 9540A-Test Method for Evaluating Thermal Runaway Fire Propagation • Project Hazard Mitigation Analysis (HMA) • Project Emergency Response Plan (ERP) • Manufacturer equipment documentation Fire Safety Compliance Plan — NYS Fire Code 2025 Chapter 12 -Section 1207 Electrical Energy Storage Systems (ESS) Compliance Checklist This table is intended to document compliance with NYS Fire Code Section 1207 for Energy Storage Systems. Code Section Requirement Project Compliance Plan Supporting Summary Documents Notes 1207.1 General General application statement in code. No applicability of compliance requirement set forth. ESS fire code requirements 1207.1.1 Utilities and General application statement in code. No Industrial compliance requirement set forth. applications 1207.1.2 Mobile ESS N/A as this is not a mobile ESS 1207.1.3 Scope General application in code for applicable energy capacity. Lithium-ion set at 20 kWh and above.No compliance requirement set forth 1207.1.4 Permits Nexamp plans to work with the town of clay to Nexamp permit applications required for obtain the following permits to comply with and town/planning board installation, this section: sessions modification,or 1. Building permit removal of ESS 2. Operating ermit 1207.1.4.1 Communication N/A as this section is related to lead-acid and utilities nickel-cadmium batteries 1207.1.5 Construction Nexamp has provided the following to comply - Nexamp HMA Documents with this section: - Nexamp ERP - Location and layout diagram of area in - Megapack 2XL which ESS is to be installed. Specification - Details on the hourly fire-resistance - Megapack 2XL Fire ratings of assemblies enclosing the Protection Engineer ESS. Report - The quantities and types of ESS to be - Nexamp site layout installed. - Megapack 2XL - Manufacturer's specifications,ratings, Compliance and listings of each ESS summary - Description of energy(battery) - Megapack NFPA 855 management systems and their Compliance Guide operation - Nexamp - Location and content of required commissioning plan signage - Nexamp - Details on fire suppression,smoke or Decommissioning fire detection,thermal management, plan ventilation,exhaust and deflagration - Megapack venting systems,if provided commissioning - Support arrangement associated with protocol the installation,including any seismic restraint. - A commissioning plan - A decommissioning plan - A fire safety and evacuation plan - Peer reviewer identification and qualifications NYSERDA 1207.1.5.1 Utilities N/A as the ESS is not owned and operated by Applicabili electric utility 1207.1.6 Hazard Nexamp has developed and created site - Nexamp HMA Mitigation specific HMA's for the project it is proposing. - Megapack 2XL Fire Analysis Protection Engineer Report 1207.1.6.1 Fault condition The HMAs provided have evaluated the - Nexamp HMA consequences of the following failure modes: - Megapack 2XL Fire 1. A thermal runaway condition of single Protection Engineer electrochemical ESS unit Report 2. A mechanical failure of a nonelectro chemical ESS unit(N/A) 3. Failure of any battery(Energy) management system or fire protection system within the ESS equipment that is not covered by the product listing FMEA. 4. Failure of any required protection system external to the ESS,including but not limited to ventilation,exhaust ventilation,smoke detection,fire detection,gas detection or fire suppression system 1207.1.6.2 Analysis The HMAs will be provided to Lansing Fire - Nexamp HMA approval Department(Fire Code Official) for review - Megapack 2XL Fire and approval Protection Engineer Report 1207.1.7 Large-scale fire The Tesla Megapack 2XL has been tested to UL - Megapack 2XL Fire test 9540A at the cell,module,and installation Protection Engineer levels. Report 1207.1.8 Fire Nexamp,as the system owner shall at their - Nexamp Remediation expense mitigate the hazard or remove decommissioning damaged equipment from the premises to a plan. safe location where a fire or other event has - Nexamp HMA damaged the ESS. - Nexamp Emergency Response Plan 1207.1.8.1 Hazard Support Nexamp as the system owner is responsible - Nexamp Emergency Personnel for ensuring thar one or more hazard support Response Plan personnel is dispatched within 15 minutes - Nexamp and arrive to the premise within 4 hours. Decommissioning Nexamp itself alongside contracted hazard Plan support SMEs will attend to this responsibility.These personnel will remain on duty continuously after the fire department leaves the premise and until the damaged energy storage equipment is removed from the premises or earlier if the fire code official indicates the public safety hazard has been abated. 1207.1.8.2 Duties On-duty support personnel will be - Nexamp Emergency responsible for the following: Response Plan 1. keeping diligent watch for fires, - Nexamp obstructions to means of egress and Decommissioning other hazards. Plan 2. Immediately contact the fire department if their assistance is needed to mitigate any hazards or extinguish fires. 3. Take prompt measures for remediation hazards in accordance with decommissioning plan. 4. Take prompt measures to assist in the evacuation of the public from the structures 1207.1.8.3 Qualifications All Nexamp (employed and contracted) Nexamp to provide list of personnel will be trained in design, personnel and operations,and special hazard mitigation qualifications prior to associated with the ESS facility.All personnel construction. will be knowledgeable of the fire safety plan, pre-incident plan,emergency operations plan, and HMA.All personnel will have completed the following classes: 1. ICS-100, Introduction to the Incident Command System 2. IS-200: Basic Incident Command System for Initial Response 3. IS-700,An introduction to the National Incident Management System 1207.2 Commissioning, General section overview.Requirements decommissioni outlined in subsections below ng,operations and maintenance 1207.2.1 Commissioning The ESS being placed in service will be done in - Nexamp accordance with the commissioning plan that commissioning plan has been approved prior to initiating - Megapack commissioning. commissioning protocol - Nexamp decommissioning plan. - Nexamp ERP 1207.1.1 Initial During the commissioning process the ESS - Nexamp Acceptance shall be evaluated for proper operation in commissioning plan Testing accordance with manufacturer's instructions - Megapack and commissioning plan prior to final commissioning approval.Nexamp will commission the system protocol alongside Tesla personnel 1207.2.1.2 Commissioning A commissioning report describing the results - Nexamp Report of system commissioning will be provided to commissioning plan the fire code official prior to final inspection Megapack and approval and maintained at an approved commissioning on-site location. protocol 1207.2.2 Operations and Nexamp has provided its 0&M plan and - Tesla 0&M manual Maintenance Tesla's 0&M manual.The ESS will be operated and maintained in accordance with the manual and a copy shall be retained at an approved on-site location. 1207.2.2.1 Ongoing All systems that monitor and protect ESS - Tesla O&M manual inspection and installation will be inspected and tested in testing accordance with manufacturer's instructions and the 0&M manual.All inspection and testing records shall be maintained in the 0&M manual.Nexamp and Tesla will conduct 24/7 monitoring of the system for planned and unplanned maintenance,with planned maintenance occurring at least once a year. 1207.2.3 Decommissioni Nexamp will notify the code official prior to - Nexamp ng the decommissioning of the ESS,with decommissioning decommissioning being performance in plan accordance with the decommissioning plan. - Nexamp ERP 1207.3 Equipment General section overview.Requirements outlined in subsections below 1207.3.1 Energy storage The ESS is listed to UL 9540 - Megapack 2XL system listings Compliance Summary - Megapack 2XL Fire Protection Engineering Report 1207.3.2 Equipment Chargers,inverters,and EMS are covered as - Megapack 2XL listings part of the UL 9540 listing Compliance Summary - Megapack 2XL Fire Protection Engineering Report 1207.3.3 Utility Inverters are listed and labeled in accordance - Megapack 2XL interactive with UL 1741 Compliance systems Summary 1207.3.4 Energy Storage The EMS will continuously monitor and - Megapack 2XL Management balance cell voltages,currents,and specification System temperatures within the manufacturer's - Megapack 2XL Fire specifications.The EMS shall disconnect Protection electrical connections to the ESS or otherwise Engineering Report place it in a safe condition if potentially - Nexamp HMA hazardous temperatures or other conditions such as short circuits,over voltage or under voltage are detected. 1207.3.4.1 Monitoring of The ESS shall be continuously(24/7) - Nexamp HMA energy storage monitored at an attended monitoring station - Nexamp ERP management by both Nexamp and Tesla's remote - Tesla 0&M Manual system operations centers.The EMS will monitor - Tesla Emergency temperature,voltage,state of charge for each Response Guide enclosure on site.The monitoring facilities will,without delay,make the following notifications in the event the ESS exceeds or appears likely to exceed thresholds at which fire,explosion or other serious adverse consequences may result: 1. Notify the local fire department through the emergency dispatch system. 2. Notify the fire code official to alter the AHJ of the unsafe condition. 3. Notify hazard support personnel to alert such individuals to be ready to provide technical assistance to the and/or respond to the incident location. 4. Notify the manufacturer of the ESS to make a qualified representative available to provide technical assistance to the responding hazard support personnel,fire code official and fire chief. 1207.3.4.1.1 Remote Nexamp and Tesla shall arrange for data Monitoring of transmissions from the ESS EMS to an energy attended remote monitoring facility staffed by management trained and knowledgeable persons retained system and by Tesla or Nexamp. re ortin 1207.3.5 Enclosures The Tesla Megapack 2XLs enclosures are - Megapack 2XL constructed with steel and are deemed Specification noncombustible construction. - Megapack 2XL Fire Protection Engineering Report 1207.3.6 Repairs Repairs of the ESS will be performed by Tesla - Tesla 0&M manual certified and qualified personnel. 1207.3.7 Retrofits N/A as Nexamp is not retrofitting an existing ESS 1203.7.1 Retrofitting N/A as Nexamp's ESS is not lead acid or nickel lead acid and cadmium nickel cadmium 1203.8 Replacements N/A as an ESS is not being replaced 1203.9 Reused or N/A as the ESS is not reused or repurposed repurposed equipment equip ment 1207.4 General ESS General section overview.Requirements installation outlined in subsections below re uirements 1207.4.1 Electrical All ESS disconnecting means that are not - Nexamp site layout Disconnects insight of the main electrical service - Nexamp single line disconnecting means,placards,or directories diagram will be installed at the location of the main electrical service disconnecting means indicating the location of stationary storage battery system disconnecting means in accordance with NFPA 70 1207.4.2 Working Access and working spaces are provided and - Nexamp site layout clearances will be maintained about all electrical - Nexamp single line equipment to permit ready and safe operation diagram and maintenance of such equipment in - Tesla 0&M Manual accordance with NFPA 70 and the - Tesla design manual manufacturer's instructions 1207.4.3 Fire-resistance- N/A as the ESS is not in a room or other rated indoor area separation 1207.4.4 Seismic and The ESS will comply with the seismic design - Tesla site design structural requirements in Chapter 16 of the Building manual design Code of New York State.This will be shown on - Nexamp site layout Nexamp's construction set drawings - Megapack 2XL specification 1207.4.5 Vehicle Impact ESS area is be surrounded by fences and noise - Nexamp Site Layout protection barriers.Each Megapack 2XL is IK09 impact - Megapack 2XL rated. specification 1207.4.6 Combustible No combustible materials are storage in the - Nexamp site layout storage ESS area or enclosures.Any combustible material is sited at least 10ft from any ESS enclosure/cabinet despite the requirement being 3ft 1207.4.7 Toxic and Each Megapack 2XL is equipped with - Megapack 2XL highly toxic deflagration vents at the top of the enclosure specification gases and equipped with 12 sparkers for gas - Megapack 2XL Fire management Protection Engineering Report 1207.4.8 Signage Nexamp will provide signs on or adjacent to the Megapack 2XL units. Signs are designed to meet both requirements outlined below and NFPA 70: 1. "Energy Storage System"and"Battery Storage System" 2. The identification of electrical ESS technology present(lithium-ion 3. "Energized Electrical Circuits" 4. "Apply no water' 5. Current contact information,including phone numbers,for personnel authorized to service the equipment and for fire mitigation personnel. 6. Relevant hazard warnings,maps of the site,ESS enclosures,and associated equipment and isolation distances that response personnel should maintain from ESS involved in fire or where there may be a risk of explosion or deflagration. 7. Most recent date the sign was produced or updated. 8. Identification of multiple power sources 1207.4.8.1 Sign Features All signs installed by Nexamp will: 1. Be a minimum size of 18 inches by 24 inches. 2. The letters providing warnings identified in 1,3,and 4 of section 1207.4.8 at least 5 inches in height. 3. The number designating all other required information of at least 1 inch in height. 4. Characters and their background will have a non-glare finish. Characters will contrast with their background,with either light characters on dark background or dark characters on a light background 1207.4.9 Security of The ESS area will be fenced and secured - Nexamp site layout installations against unauthorized entry. 1207.4.9.1 Video The ESS area will be monitored by camera monitoring 24/7 and will provide the following: 1. A minimum look back period of 72 hours. 2. Surveillance coverage of the ESS enclosures and the entry points of the facility 3. In the case of an incident,the video surveillance will be made available to the fire department and fire code official for viewing 1207.4.10 Occupied work N/A as the ESS is not an occupied work center centers 1207.4.11 Open rack N/A as there are no open rack installations installations 1207.4.12 Walk in units N/A as the Megapack 2XLs are not walk in units 1207.5 Electrochemical General section overview.Requirements ESS protection outlined in subsections below 1207.5.1 Size and Large-scale fire testing demonstrates the - Tesla site design separation ability for larger than 50 kWh groupings and manual smaller than 3ft separation distances between - Megapack 2XL Fire Megapack 2XL enclosures Protection Engineering Report 1207.5.2 Maximum N/A as there are no fire areas within rooms allowable and walk-in units uantities 1207.5.2.1 Mixed N/A as this ESS only uses one type of electrochemical electrochemical system (lithium-ion) energy systems 1207.5.3 Elevation The ESS is not installed on a floor located - Nexamp site layout more than 75 feet above the lowest level of fire department vehicle access-it is on grade with such access. 1207.5.4 Fire Detection Not applicable as the ESS is not in a room, - Megapack NFPA 855 indoor area or walk-in unit.However,BMS Compliance guide and video cameras will be capable of detecting - Nexamp site layout fires. - Megapack 2XL Fire Protection Engineering Report 1207.5.4.1 System status N/A as the ESS is not a lead-acid or nickel- cadmium battery system 1207.5.4.2 Alarm criteria In accordance with Tesla's instructions and - Nexamp ERP registered design professional's specifications for the ESS,alarm activation criteria will be set to minimize non-emergency alarm activations for all fire detection,temperature, other emergency system sensors 1207.5.5 Fire N/A as the ESS is not in a room,building, or Suppression walk-in unit. Systems 1207.5.6 Maximum ESS The Tesla Megapack does not exceed the - Megapack enclosure size maximum size and has dimensions of specifications approximately 28.5 ft x 6 ft x 9 feet high. 1207.5.7 Vegetation All areas within 10ft from the ESS will be - Nexamp site layout control cleared of vegetation and managed such that - Tesla site design no vegetation growth occurs.Gravel will be manual installed on all sides of each ESS enclosure and within the BESS area. 1207.5.8 Means of Egress All means of egress on site ensure safe egress - Nexamp site layout Separation under fire conditions and allow for at least 10ft of separation. 1207.6 Technology- General section overview.Requirements s ecific ESS outlined in subsections below protection re uirements 1207.6.1 Exhaust N/A for lithium-ion technology as per Table ventilation 1207.6 1207.6.2 Spill control N/A for lithium-ion technology as per Table and 1207.6 neutralization 1207.6.3 Explosion Each Megapack 2XL consists of deflagration - Megapack 2XL Fire Control vents on the roof as a means of explosion Protection control. In addition, 12 sparkers are fitted Engineering Report within each Megapack to reduce the potential - Nexamp ERP of built-up flammable/explosive gas to protect - Nexamp HMA against a deflagration 1207.6.4 Safety caps N/A for lithium-ion technology as per Table 1207.6 1207.6.5 Thermal ESS is listed to UL 9540 and has conducted - Megapack 2XL Fire Runaway large-scale fire testing under UL 9540A Protection Engineering Report - Megapack 2XL compliance summary - Megapack NFPA 855 Compliance guide 1207.7 Indoor This section is N/A as this ESS is an outdoor - Nexamp site layout installations installation 1207.8 Outdoor ESS General section overview. Requirements installation outlined in subsections below. 1207.8.1 Remote The ESS is considered a remote outdoor - Nexamp site layout outdoor installation as the ESS is located more than installations 100ft from lot lines and public ways 1207.8.2 Installations The ESS is not considered an installation near - Nexamp site layout near exposures exposures as it is classified as a remote outdoor installation as per 1207.8.1 1207.8.3 Clearance to The ESS located outdoors is separated by a - Nexamp site layout exposures minimum of 10 feet from the following exposures: 1. Lot lines 2. Public ways 3. Buildings 4. Stored combustible materials (N/A) 5. Hazardous materials (N/A) 6. High-piled stock(N/A) 7. Other exposure hazards 1207.8.4 Exterior wall N/A as the ESS in not installed on the exterior installations walls of any buildings. Each ESS unit is ground mounted to a concrete pad 1207.9 Special Section is N/A as the ESS is not located on a Installations rooftop or open parking garage 1207.10 Mobile ESS Section is N/A as the ESS is not a mobile ESS. requirements ESS is stationary. 1207.11 ESS in Group R- Section is N/A as the ESS is not located in a 3 and R-4 Group R-3 or R-4 occupancy occupancies 1207.12, Peer review Nexamp will be responsible for retaining and 1207.12.1, furnishing the services of a registered 1207.12.1.1, professional engineer or special expert to 1207.12.1.2, perform a peer review,subject to the approval 1207.12.2 of the fire code official.This will either be facilitated by NYSERDA's Peer Review Process or Nexamp will directly contract ESRG for this service.A peer review report will be commissioned and provided to all AHJs 1207.13 First responder Nexamp has developed an ERP for the facility, - Nexamp ERP pre-incident with a draft plan included in its permit - Megapack 2XL Fire plan application and provided to the fire code Protection official/fire department.The plan will be Engineering Report further developed in consultation with the - Nexamp HMA Lansing Fire Department and will adhere to the requirements in Section 11 of Annex G of NFPA 855. 1207.13.1 First responder Nexamp will provide an annual visit and - Nexamp ERP site review of the pre-incident plan developed to familiarization the Lansing Fire Department 1207.14, ESS third party Nexamp will facilitate a third-party fire safety 1207.14.1 fire safety inspection performed every 3 years or more inspection frequently as requested by the fire code official.The inspection will be performed by a registered profession engineer or special expert.The ESS third-party fire safety inspection shall cover the following: 1. Structural integrity and weather tightness of enclosures 2. Operation and maintenance of the ESS 3. Emergency operations plan 4. Hazard mitigation analysis 5. Electrical inspection 6. Explosion control verification 7. Monitoring procedures and history 8. Alarm activation criteria and history. 9. System performance concerns 10. Fire protection system (s) and testing records. 11. Ventilation system 12. Other items requested by the AHJ