HomeMy WebLinkAboutTC0.01TELECOM - LEGENDW
#F
TV
TV
WAP
WAP
#
#
#
1
T-501
2
T-501
20
21
23
24
OSC
WALL MOUNTED WIRELESS DATA1/DATA2 LOCATION - PROVIDE A
SINGLE GANG, 4-11/16" SQUARE, 2-1/8" DEEP, OUTLET BOX WITH A
SINGLE GANG PLASTER RING AND A 1-1/4" CONDUIT WITH
CONNECTORS, BUSHINGS AND PULL STRING TO THE NEAREST
ACCESSIBLE CEILING SPACE ON THE SAME FLOOR AS THE ROOM
BEING SERVED BY THE OUTLET LOCATION. WIRELESS DATA LOCATION
IS TO BE MOUNTED 6" FROM FINISHED CEILING TO THE TOP OF THE
OUTLET BOX UNLESS OTHERWISE NOTED.
STRUCTURED CABLING LEGEND
CEILING MOUNTED WIRELESS DATA1/DATA2 LOCATION - PROVIDE A
SINGLE GANG, 4-11/16" SQUARE, 2-1/8" DEEP, OUTLET BOX WITH A
SINGLE GANG PLASTER RING AND A 1-1/4" CONDUIT WITH
CONNECTORS, BUSHINGS AND PULL STRING TO THE NEAREST
ACCESSIBLE CEILING SPACE ON THE SAME FLOOR AS THE ROOM
BEING SERVED BY THE OUTLET LOCATION. CEILING MOUNTED
WIRELESS DATA LOCATIONS ARE TO BE CENTERED IN THE ROOM
AND MOUNTED TO THE BUILDING STRUCTURE ABOVE THE CEILING.
THE CEILING MOUNTED WIRELESS DATA DEVICE BOX ASSEMBLY IS
TO BE (UL) RATED FOR PLENUM.
WALL MOUNTED DATA# LOCATION (# DENOTES THE NUMBER OF
CABLES AT THE OUTLET LOCATION) - PROVIDE A TWO GANG, 4-11/16"
SQUARE, 2-1/8" DEEP, OUTLET BOX WITH A SINGLE GANG PLASTER RING
AND A 1-1/4" CONDUIT WITH CONNECTORS, BUSHINGS AND PULL
STRING TO THE NEAREST ACCESSIBLE CEILING SPACE ON THE SAME
FLOOR AS THE ROOM BEING SERVED BY THE OUTLET LOCATION.
DATA# LOCATION IS TO BE MOUNTED 18" FROM THE FINISHED FLOOR
TO THE CENTER OF THE OUTLET BOX UNLESS OTHERWISE NOTED.
PROVIDE ADDITIONAL 1-1/4" CONDUIT WHERE THERE ARE 6 OR MORE
CABLES AT ONE LOCATION.
FLOOR MOUNTED DATA# LOCATION (# DENOTES THE NUMBER OF
CABLES AT THE OUTLET LOCATION) - PROVIDE A 1-1/4" CONDUIT WITH
CONNECTORS, BUSHINGS AND PULL STRING TO THE NEAREST
ACCESSIBLE CEILING SPACE ON THE SAME FLOOR AS THE ROOM
BEING SERVED BY THE OUTLET LOCATION.
CEILING MOUNTED DATA# LOCATION (# DENOTES THE NUMBER OF
CABLES AT THE OUTLET LOCATION) - PROVIDE A TWO GANG, 4-11/16"
SQUARE, 2-1/8" DEEP, OUTLET BOX WITH A SINGLE GANG PLASTER
RING AND A 1-1/4" CONDUIT WITH CONNECTORS, BUSHINGS AND PULL
STRING TO THE NEAREST ACCESSIBLE CEILING SPACE ON THE SAME
FLOOR AS THE ROOM BEING SERVED BY THE OUTLET LOCATION.
WALL MOUNTED TV LOCATION - PROVIDE A TWO GANG, 4-11/16"
SQUARE, 2-1/8" DEEP, OUTLET BOX WITH A SINGLE GANG PLASTER
RING AND A 1-1/4" CONDUIT WITH CONNECTORS, BUSHINGS AND
PULL STRING TO THE NEAREST ACCESSIBLE CEILING SPACE ON THE
SAME FLOOR AS THE ROOM BEING SERVED BY THE OUTLET
LOCATION. TV VIDEO LOCATION IS TO BE MOUNTED 18" FROM THE
FINISHED FLOOR TO THE CENTER OF THE OUTLET BOX UNLESS
OTHERWISE NOTED. PROVIDE TWO DATA CABLES.
FLOOR MOUNTED TV VIDEO LOCATION - PROVIDE A 1-1/4" CONDUIT
WITH CONNECTORS, BUSHINGS AND PULL STRING TO THE NEAREST
ACCESSIBLE CEILING SPACE ON THE SAME FLOOR AS THE ROOM
BEING SERVED BY THE OUTLET LOCATION.
WALL MOUNTED WALL PHONE VOICE LOCATION - PROVIDE A SINGLE
GANG, 4-11/16" SQUARE, 2-1/8" DEEP, OUTLET BOX WITH A SINGLE
GANG PLASTER RING AND A 1-1/4" CONDUIT WITH CONNECTORS,
BUSHINGS AND PULL STRING TO THE NEAREST ACCESSIBLE CEILING
SPACE ON THE SAME FLOOR AS THE ROOM BEING SERVED BY THE
OUTLET LOCATION. WALL PHONE VOICE LOCATION IS TO BE MOUNTED
48" FROM THE FINISHED FLOOR TO THE CENTER OF THE OUTLET BOX
UNLESS OTHERWISE NOTED.
FEED LOCATION (# DENOTES THE NUMBER OF CABLES AT THE FEED
LOCATION) PROVIDE A 2-GANG MUDRING WITH GROMMET FACEPLATE
AT FEED LOCATIONS AS IDENTIFIED ON PLANS. PROVIDE
POLYETHYLENE SLEEVE FROM GROMMET TO MODULAR FURNITURE
ENTRY POINT.
1. THE WORK REQUIREMENTS DESCRIBED WITHIN DIVISION 20 SPECIFICATION
SECTION "COMMON MECHANICAL / ELECTRICAL REQUIREMENTS" FORM
COMPLIMENTARY REQUIREMENTS TO THE SCOPE OF WORK CONTAINED WITHIN
DIVISION 27 AND 28.
2. CONDITIONS OF THE CONTRACT AND DIVISION 1, GENERAL REQUIREMENTS APPLY
TO WORK OF THIS SECTION. EXAMINE DRAWINGS AND OTHER SPECIFICATIONS
FOR REQUIREMENTS THAT AFFECT WORK OF THIS SECTION.
3. PROVIDE ITEMS REFERRED TO IN SINGULAR OR PLURAL NUMBERS IN CONTRACT
DOCUMENTS IN QUANTITIES NECESSARY TO COMPLETE WORK.
4. PERFORM WORK AS REQUIRED BY CODES, REGULATIONS AND LAWS OF LOCAL,
STATE AND FEDERAL GOVERNMENTS AND OTHER AUTHORITIES WITH LAWFUL
JURISDICTION.
5. MATERIAL AND EQUIPMENT SHALL BE UL, NEMA, ANSI, IEEE, ADA & CBM
APPROVED FOR INTENDED SERVICE. MATERIAL AND INSTALLATION SHALL MEET
REQUIREMENTS OF NATIONAL AND STATE ELECTRICAL CODE.
6. MAINTAIN RECORD DRAWINGS ON SITE. RECORD SET MUST BE COMPLETE AND
CURRENT AND AVAILABLE FOR INSPECTION WHEN REQUISITIONS FOR PAYMENT
ARE SUBMITTED.
7. GUARANTEE WORK IN WRITING FOR ONE YEAR FROM DATE OF FINAL
ACCEPTANCE. REPAIR OR REPLACE DEFECTIVE MATERIALS OR INSTALLATION AT
NO COST TO OWNER. CORRECT DAMAGE CAUSED IN MAKING NECESSARY
REPAIRS AND REPLACEMENTS UNDER GUARANTEE AT NO COST TO OWNER.
8. SUBMIT GUARANTEE TO ARCHITECT BEFORE APPLICATION FOR FINAL PAYMENT.
9. STATEMENT OF GUARANTEE REQUIREMENTS SHALL NOT BE INTERPRETED TO
LIMIT OWNER'S RIGHTS UNDER LAW AND THIS CONTRACT.
10. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF
SYSTEMS. PROVIDE INFORMATION AND COMPONENTS SHOWN ON RISER
DIAGRAMS BUT NOT SHOWN ON PLANS, AND VICE VERSA, AS IF EXPRESSLY
REQUIRED ON BOTH.
11. ALL WIRING SHALL BE RUN CONCEALED UNLESS SPECIFIED OTHERWISE.
12. ALL RACEWAYS RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE
EQUIPPED WITH EXPANSION FITTINGS.
13. CONTRACTOR SHALL REVIEW ALL TRADES' CONTRACT DOCUMENTS TO
DETERMINE SPECIFIC MOUNTING HEIGHTS AND LOCATIONS FOR TELECOM
EQUIPMENT. COORDINATE EXACT MOUNTING LOCATIONS WITH THE ARCHITECT.
14. ALL GROUNDING SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL
AND STATE ELECTRICAL CODES.
15. REFER TO SPECIFICATION FOR CABLE COLORS
16. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, JUNCTION BOXES,
CABLE TRAYS, PANELS, PULL STRINGS, ENCLOSURES, FLOOR BOXES, POWER
CIRCUITS, TELCOM GROUNDING SYSTEM, POWER CABLE AND POWER
CONNECTIONS UNDER THIS SECTION.
17. CONDUIT SHALL NOT EXCEED 100'-0" OR A TOTAL OF 180 DEGREES IN BENDS
BETWEEN PULL BOXES FOR DISTRIBUTION OF TELE/DATA CABLE.
18. VERIFY ALL DEVICE PLATE FINISHES WITH ARCHITECT AND/OR OWNER.
19. LABEL ALL CABLE, CONDUIT AND BACK BOXES FOR EASE OF IDENTIFICATION.
20. ALL CABLE RUNS MUST BE CONTINUOUS FROM SOURCE TO DESTINATION. NO
EXCEPTIONS.
21. PROVIDE A SERVICE LOOP OF 15'-0" MINIMUM AT ALL BACKBONE TERMINATION
LOCATIONS AND SPLICE POINTS.
22. INTERBUILDING AND INTRABUILDING OPTICAL FIBER CABLING SHALL BE CLEARLY
AND VISIBLY IDENTIFIED BY THE CONTRACTOR IN ALL MANHOLES, PULL BOXES,
ENTRANCE POINTS, SERVICE ENTRENCES AND 3'-0" BEFORE ENTERING A FREE
STANDING RACK, WALL MOUNTED ENCLOSURE OR SURFACE MOUNT FIBER
CABINET UTILIZING AN OPTICAL FIBER CABLE MARKER TAG SYSTEM.
23. WHEN ROUTING COMMUNICATIONS CABLES USING OPEN CABLING METHODS,
MAINTAIN A MINIMUM SPACING OF 1'-0" FROM ELECTRICAL FEEDERS, BRANCH
CIRCUIT WIRING AND AUXILIARY SYSTEM CABLING.
24. WHEN ROUTING COMMUNICATIONS CABLES USING OPEN CABLING METHODS,
MINIMUM SPACING FROM ELECTRICAL APPARATUS SUCH AS MOTOR DRIVEN
EQUIPMENT AND TRANSFORMERS SHALL BE 4'-0". SPACING REQUIREMENTS
SHALL APPLY TO OPEN CABLE PATHS WHERE EQUIPMENT IS LOCATED ON THE
SAME FLOOR, FLOOR ABOVE, FLOOR BELOW OR IN ROOMS ADJACENT TO SUCH
EQUIPMENT AS THOUGH WALLS AND FLOORS DID NOT EXIST. EXCEPTION:
BUILDING CONSTRUCTION THAT RESULTS IN METALLIC BARRIER BETWEEN
ELECTRICAL APPARATUS AND CABLE PATHWAYS SHALL BE CONSIDERED
SUITABLE SEPARATION.C - MOUNT 6" ABOVE COUNTER TOP BACK SPLASH
ETR - EXISTING TO REMAIN
N - NEW
R - RELOCATE
X - REMOVE
GENERAL NOTES
OUTLET LOCATION DESIGNATORS
1. THIS SHEET IS A GENERAL LIST OF SYMBOLS AND SHALL BE USED AS
A REFERENCE TO DEFINE ITEMS INDICATED ON THE DRAWINGS. NOT
ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT.
LEGEND NOTES
DETAIL CALL-OUT - PLAN VIEW.
DENOTES DETAIL "1" ON DRAWING "T-501".
KEY LEGEND
VANDERWEIL PROJECT INFO
PROJECT NUMBER
PROJECT NAME
29313
CORNELL OLIN HALL
125 VOLT, 2 POLE, 3 WIRE, 20 AMP, DUPLEX
RECEPTACLE.
D - DEDICATED CIRCUIT
GF - CONNECTED TO GROUND FAULT CIRCUIT BREAKER
GFI - WITH INTEGRAL GROUND FAULT INTERRUPTER
IG - ISOLATED GROUND
ELECTRICAL LOCATION DESIGNATORS
ELECTRICAL LEGEND
DETAIL CALL-OUT - ELEVATION VIEW.
DENOTES DETAIL "2" ON DRAWING "T-501".
DRAWING NUMBERING SYSTEM
T-0## - GENERAL (SYMBOLS LEGEND, NOTES, SPECIFICATION, ETC.)
T-1## - PLANS (HORIZONTAL VIEWS)
T-2## - ELEVATIONS (VERTICAL VIEWS
T-3## - SECTIONS (SECTIONAL VIEWS)
T-4## - LARGE SCALE DRAWINGS (PLANS, ELEVATIONS OR SECTIONS THAT ARE
NOT DETAILS)
T-5## - DETAILS
T-6## - RISERS, SCHEDULES AND DIAGRAMS
125 VOLT, 2 POLE, 3 WIRE, 20 AMP, DOUBLE DUPLEX
RECEPTACLE.
GROUND BAR WITH INSULATED #6 CONNECTED TO GROUND IN
ELECTRICAL ENTRANCE ROOM
L5-20R - 20 AMP, 125 VOLT, 2 POLE, 3 WIRE TWIST
LOCK RECEPTACLE
L5-30R - 30 AMP, 125 VOLT, 2 POLE, 3 WIRE TWIST
LOCK RECEPTACLE
L6-20R - 20 AMP, 250 VOLT, 2 POLE, 3 WIRE TWIST
LOCK RECEPTACLE
L6-30R - 30 AMP, 250 VOLT, 2 POLE, 3 WIRE TWIST
LOCK RECEPTACLE
125 VOLT, 2 POLE, 3 WIRE, 20 AMP, DUPLEX
RECEPTACLE FLUSH FLOOR MOUNTED
125 VOLT, 2 POLE, 3 WIRE, 20 AMP, DOUBLE
DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED
1. THIS EXISTING FLOOR PLAN HAS BEEN DEVELOPED UTILIZING EXISTING DOCUMENTS AND READILY
OBSERVABLE SITE CONDITIONS. ALL DEVICES, CONDUITS,TELECOMMUNICATIONS EQUIPMENT, ETC.
SHOWN ARE FOR REFERENCE ONLY AND MAY NOT INDICATE CORRECT IDENTIFICATION, AND SIZE; AND
TOTAL QUANTITIES OF ITEMS SCHEDULED FOR DEMOLITION. VISIT SITE AND FIELD VERIFY THE
NUMBER OF DEVICES WITHIN THE CONSTRUCTION PHASE AREA PRIOR TO THE BID AND REMOVAL. THE
DRAWINGS DO NOT LIMIT THE AMOUNT OF DEMOLITION WORK REQUIRED. THE TELECOMMUNICATIONS
CONTRACTOR MUST PERFORM THE DEMOLITION WORK AS INDICATED ON THE DEMOLITION DRAWINGS
AND AS REQUIRED FOR THE NEW WORK.
2. DEMOLITION WORK MUST FOLLOW THE CONSTRUCTION PHASING SEQUENCE AND MUST BE
COORDINATED WITH THE CONSTRUCTION DRAWINGS AND CONTRACTORS.
3. REMOVE ALL DEVICES, EQUIPMENT, MATERIAL, AND ASSOCIATED CABLING IN THEIR ENTIRETY, WHICH
INTERFERE WITH THE NEW CONSTRUCTION AS DIRECTED BY THE CONSTRUCTION MANAGER. ALWAYS
FIELD VERIFY SYSTEM PRIOR TO STARTING WORK AT SITE. THE TERM ASSOCIATED CABLING SHALL
MEAN CONDUIT, FITTINGS, SUPPORTS, JUNCTION BOXES, CABLES, ETC. BACK TO THE RESPECTIVE
EQUIPMENT ROOM.
4. MAINTAIN AND RESTORE, IF INTERRUPTED BY REMOVALS OR IN PATH OF NEW CONSTRUCTION, ALL
CABLES AND CONDUITS PASSING THROUGH AND SERVING UNDISTURBED AREAS (SHOWN OR NOT
SHOWN). VERIFY CABLES, DEVICES, AND EQUIPMENT SCHEDULED FOR REMOVAL TO ASSURE THAT
THEIR REMOVAL WILL NOT ADVERSELY AFFECT ADJACENT AREAS NOT BEING RENOVATED.
5. IN ANY AREA REQUIRING THE PERFORMANCE OF ANY TRADE'S WORK, THIS CONTRACTOR SHALL
CAREFULLY REMOVE AND STORE ANY OR ALL TELECOMMUNICATIONS ITEMS IN PATH Of WORK,
REINSTALLING AND RECONNECTING SAME AS REQUIRED, AFTER COMPLETION OF OTHER TRADE'S
WORK IN THAT AREA, IN ACCORDANCE WITH THE PLANS AND/OR AS DIRECTED.
6. IN ALL EXISTING OR NEW AREAS SPECIFIED OR SHOWN TO BE PAINTED, THIS CONTRACTOR SHALL
REMOVE BAG AND PROTECT DURING WORK ALL TELECOMMUNICATIONS ITEMS AS REQUIRED
INCLUDING BUT NOT LIMITED TO DEVICE PLATES, DEVICES, ETC., REINSTALLING SAME AFTER
COMPLETION OF PAINTING. ANY ITEM NOT REMOVED AND PAINTED OVER SHALL BE SUITABLY CLEANED
OR REPLACED WITH NEW ITEM BY THIS CONTRACTOR.
7. INVENTORY MAJOR TELECOMMUNICATIONS ITEMS THAT ARE REMOVED AND PROVIDE A LIST TO THE
OWNER FOR THEIR SELECTION OF ITEMS TO BE RETAINED. ALL ITEMS REJECTED BY THE OWNER
SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE.
8. DISCONNECT, MAKE SAFE AND REMOVE ALL TEMPORARY AND ABANDONED WIRE WITHIN THE SPACE.
SPECIFICALLY BUT NOT LIMITED TO LOW VOLTAGE CABLING SERVING THE MAILBOX DISTRIBUTION
SYSTEM.
9. FLAG, LABEL AND CLEARLY IDENTIFY CABLES AND ITEMS TO REMAIN IN PLACE, AND OR SERVICE,
THROUGHOUT THE PROJECT OR ANY PORTION OF THE PROJECT. REPAIR AND/OR REPLACE ANY
CABLE OR DEVICE DAMAGED DURING THE PROJECT, WITHIN 24 HOURS OF NOTIFICATION OF DAMAGES
OR DISRUPTION.
GENERAL DEMOLITION NOTES
OVERHEAD SERVICE CARRIER. SEE SHEET TC4.01 FOR DETAILS.
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
1/8" = 1'-0"
TC0.01
29313.00
11/30/18
TELECOM - LEGEND
# DATE DESCRIPTION
1 11/30/18 ISSUED FOR CONSTRUCTION