VFD
END OF MAIN BYPASS
P-3
OUTDOOR AIR TEMPERATURE
SENSOR - COMMON
LPS
TO HWS/R180
SYSTEMSYSTEM
FROM HWS/R180
P-3A
HX-1.1
HX-1.2
HWR
HWSHWS180 HWS180
180 DEG. HW SYSTEM SERVES
AHU PREHEAT AND PERIMETER
HEAT
LPC
LPC
DI
DI
DI
DI
DI
DI
DI
AI
AI
AI
AO
DO
AI
AI
DATA
DATA
DATA
DATA
DATA
DATA
DI
DI
DI
DI
DI
DIDATA
DATA
DI
DI DI
DIDATA
DIDATA
DIDATA
DATAZI
ZI
ZI
ZI
ZI
ZI
ZI
GI
01
TT
02
TT
01
TT
03
ZI
ZI
ZI
ZI
ZI
ZI
ZI
ZI ZI
ZI
ZI
ZI
CA-DD-1A CONTROL PANEL:
TROUBLE ALARM & DATA
DROP
PURE WATER SYSTEM
CONTROL PANEL:
TROUBLE ALARM & DATA
DROP
CA-C-1A CONTROL PANEL:
TROUBLE ALARM & DATA
DROP
REMOTE
"TROUBLE ALARM"
CONTACTS
REMOTE
"TROUBLE ALARM"
CONTACTS
PLUMBING SYSTEMS MONITOR/ALARMS
VACUUM SYSTEM CONTROL
PANEL:
TROUBLE ALARM & DATA
DROP
SAFETY STATIONS:
PROVIDE TROUBLE
CONTACT WITH
DISCRETE ADDRESS
FOR EACH SAFETY
EQUIPMENT
CA-C-1B CONTROL PANEL:
TROUBLE ALARM & DATA
DROP
CA-DD-1B CONTROL PANEL:
TROUBLE ALARM & DATA
DROP
GENERAL
1. REFER TO SEQUENCE OF OPERATION - GENERAL, CONTROL SYSTEM NOTES AND SEQUENCE OF OPERATION - STANDBY POWER
ON CONTROLS LEGEND SHEET M8.01 FOR ADDITIONAL REQUIREMENTS.
2. CONNECT TO EXISTING GAS DETECTION SYSTEM.
ALARMS
1. THE FOLLOWING SHALL INITIATE SPECIFIC ALARM NOTICES AT THE BAS:
a. CABINET SENSOR DETECTS GAS LEVELS ABOVE ACCEPTABLE LEVELS.
AIRFLOW CONTROL
1. EXHAUST AIRFLOW SHALL NORMALLY BE CONSTANT VOLUME IF GAS DETECTION SYSTEM INDICATES UNACCEPTABLE LEVELS
OF CONCENTRATION, AIRFLOW SHALL INCREASE TO PURGE AIRFLOW RATE DICTATED BY CABINET MANUFACTURER..
GENERAL
1. HEATING SYSTEM SHALL BE OPERATIONAL 24 HOURS PER DAY, 7 DAYS PER WEEK.
2. REFER TO SEQUENCE OF OPERATION - GENERAL, CONTROL SYSTEM NOTES AND SEQUENCE OF OPERATION - STANDBY POWER ON CONTROLS LEGEND
SHEET M8.01 FOR ADDITIONAL REQUIREMENTS.
3. EXISTING RE-HEAT LOOP IS BEING MODIFIED TO ADD CAPACITY FOR THIS PROJECT. EXISTING LOOP HAS 1 HEAT EXCHANGER AND 1 PUMP. THIS PROJECT
IS ADDING 1 HEAT EXCHANGER AND 1 PUMP. ASSOCIATED CONTROL POINTS FOR NEW EQUIPMENT SHALL BE PROVIDED. EXISTING TO REMAIN
COMPONENTS ARE LISTED.
SAFETIES
1. THE FOLLOWING SAFETIES, EACH WITH INDIVIDUAL MANUAL RESETS, SHALL SHUT DOWN EXHAUST FAN(S) AND INITIATE A SPECIFIC ALARM NOTICE AT
THE BAS:
a. DIFFERENTIAL PRESSURE AT PDT-01 INDICATES PUMP IS IN DEADHEAD CONDITION. DEADHEAD SETPOINT SHALL BE DETERMINED FROM APPROVED
SHOP DRAWING PUMP CURVE.
ALARMS
1. THE FOLLOWING SHALL INITIATE SPECIFIC ALARM NOTICES AT THE BAS ONLY WHEN THE UNIT IS STATUS ON:
a. ANY PUMP IS COMMANDED TO RUN AND THE BAS SENSES NO STATUS AT CURRENT TRANSMITTER CONTINUOUSLY FOR 10 SECONDS.
b. SUPPLY HOT WATER IS AT LEAST 10°F ABOVE OR BELOW SETPOINT CONTINUOUSLY FOR 30 SECONDS.
ACTIVE/STANDBY DESIGNATION
1. EVERY WEEK, THE BAS WILL SWITCH THE STANDBY/ACTIVE HEAT EXCHANGER DESIGNATIONS AND THE FOLLOWING SHALL OCCUR:
a. NEWLY ACTIVE HEAT EXCHANGER HOT WATER ISOLATION VALVE SHALL FULLY OPEN.
b. AFTER HOT WATER VALVE IS OPEN, NEWLY ACTIVE HEAT EXCHANGER STEAM CONTROL VALVES SHALL MODULATE IN ACCORDANCE WITH
TEMPERATURE CONTROL PARAGRAPH BELOW.
c. AFTER A 30 SECOND DELAY, PREVIOUSLY ACTIVE HEAT EXCHANGER STEAM CONTROL VALVES AND HOT WATER ISOLATION VALVE SHALL FULLY
CLOSE.
2. EVERY WEEK, THE BAS WILL SWITCH THE STANDBY/ACTIVE PUMP DESIGNATIONS.
TEMPERATURE CONTROL
1. EXISTING SUPPLY TEMPERATURE CONTROL SHALL REMAIN. MODIFICATIONS SHALL ONLY BE DONE TO ADD NEW COMPONENTS TO SYSTEM WITHOUT
EFFECTING SYSTEM PERFORMANCE.
2. IF TEMPERATURE IS BELOW SETPOINT AND STEAM CONTROL VALVE IS FULLY OPEN ON ACTIVE HEAT EXCHANGERS, BOTH HEAT EXCHANGERS SHALL
OPERATE TO MAINTAIN HYDRONIC TEMPERATURE.
PUMP SPEED CONTROL
1. ACTIVE PUMP VFD SHALL MODULATE TO MAINTAIN STATIC PRESSURE SETPOINT AT EXISTING SENSOR.
2. THE INITIAL DIFFERENTIAL PRESSURE SETPOINT SHALL BE 15 PSI. THIS VALUE SHALL BE ADJUSTED TO THE REQUIRED SETPOINT TO ACHIEVE THE
PROPER FLOW RATE AS DETERMINED DURING BALANCING.
3. IF VFD OF OPERATING PUMP IS AT MAXIMUM SPEED AND PRESSURE SETPOINT IS NOT MAINTAINED, BOTH PUMPS SHALL RUN TO MAINTAIN SYSTEM
PRESSURE.
BACNET DATA DROP
CONNECTION
CA-F-1A:
REMOTE TROUBLE
ALARM
CA-F-1B:
REMOTE TROUBLE
ALARM
CA-F-2A:
REMOTE TROUBLE
ALARM
CA-F-2B:
REMOTE TROUBLE
ALARM
SAN-SP-1A CONTROL
PANEL: TROUBLE
ALARM & DATA DROP
SAN-SP-1B CONTROL
PANEL: TROUBLE
ALARM & DATA DROP
CA-DEWPOINT
ANALYZER: LOOP
POWERED W/ DATA
DROP 4-20 AMP
LHWR-CP-1: REMOTE
TROUBLE ALARM
N2-OXYGEN
ANALYZER: LOOP
POWERED W/ DATA
DROP 4-20 AMP
N2-PRESSURE
TRANSMITTER: LOOP
POWERED W/ DATA
DROP 4-20 AMP
N2-FLOW METER :
LOOP POWERED W/
DATA DROP 4-20 AMP
LHWR-EWH-1:
REMOTE TROUBLE
ALARM
BACNET DATA DROP
CONNECTION
REMOTE
"TROUBLE ALARM"
CONTACTS
GAS CABINET
CO SENSOR
GAS CABINET
EXHAUST VALVE
RE-HEAT HOT WATER SYSTEM CONTROLS
TYPICAL FOR EACH
HEAT EXCHANGER
(XM)
(XM)
(XM)
(XM)
(XM)
(XM)
(XM)
(XM)
CYLINDER STORAGE GAS DETECTION
TCV
01
PDT
01
LEAD HX
LAG HX
FCV
01
2
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M8.80
29313.00
11/30/18
HVAC - CONTROLS