HomeMy WebLinkAboutM8.70HVAC - CONTROLSCCCZONE CONTROL: RADIANT CEILING HEATING AND ACTIVE CHILLED BEAM COOLING ZONE CONTROL
POINT NAME
HARDWARE POINTS SOFTWARE POINTS
SHOW ON
GRAPHIC NOTES
BI BO AI AO AV BV SCH TREND
ALARM
BACS EMCS DESCRIPTION
STEAM LOAD SHED X(6)BINARY NETWORK INPUTS FROM EMCS
CHILLED WATER LOAD SHED X(4)BINARY NETWORK INPUTS FROM EMCS
SPACE TEMPERATURE SETPOINT X X X
SPACE TEMPERATURE X X X +/- 4 °F FROM SETPOINT X
SPACE OCCUPANCY OVERRIDE X X
SPACE SETPOINT ADJUSTMENT X X
CHILLED BEAM CONTROL VALVE POSITION COMMAND X X X FAILS CLOSED
CONDENSATE SENSOR STATUS X X X MOISTURE SENSED X
SPACE DEWPOINT X X X
RADIANT CEILING PANEL CONTROL VALVE POSITION COMMAND X X X FAIL LAST
SPACE OCCUPANCY X X X
PRIMARY AIR BOX DAMPER POSITION COMMAND X X X
PRIMARY AIR BOX AIRFLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT
PRIMARY AIR SUPLY BOX AIRFLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT
PRIMARY AIR BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT
EXHAUST BOX DAMPER POSITION COMMAND X X X
EXHAUST BOX AIRFLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT
EXHAUST BOX AIRFLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT
EXHAUST BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT
AO
AI DIAI AI
FCV
01
TT
01
YI
01
MT
01
CO2
01
SYSTEM DESCRIPTION
ACTIVE CHILLED BEAM CEILING COOLING
RADIANT HEATING PANEL(S)
PRIMARY SUPPLY AIR BOX
DUCT MOUNTED RE-HEAT COIL
EXHAUST AIR BOX
GENERAL
REFER TO COMMON INDIVIDUAL DEVICE SEQUENCES/DIAGRAMS FOR REQUIRED
POINTS. ALL POINTS WITHIN EACH ZONE MUST BE CONNECTED DIRECTLY TO A LOCAL
CONTROLLER. TO ENSURE ZONES CAN OPERATE INDEPENDENTLY, DEVICES SHALL
NOT RELY ON NETWORK TO COMMUNICATE ACROSS ZONES.
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND
CONTROL SYSTEM (BACS).
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE BACS SHALL BE CAPABLE OF STARTING AND STOPPIING THE SYSTEM FOR
SEVEN DIFFERENT DAILY SCHEDULES PER WEEK.
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING
DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
SETPOINTS
SPACE COOLING TEMPERATURE SETPOINTS:
OCCUPIED: 75 °F +/- 1.5 °F
OCCUPIED SETBACK: 75 °F +/- 3 °F
UNOCCUPIED: 75 °F +/- 6 °F
SPACE HEATING TEMPERATURE SETPOINTS:
OCCUPIED: 70 °F +/- 1.5 °F
OCCUPIED SETBACK: 70 °F +/- 3 °F
UNOCCUPIED: 70 °F +/- 6 °F
ZONE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRI
SPACE OCCUPANCY
ZONE OCCUPANCY SHALL BE DETERMINED BASED ON A COMBINATION OF A TIME OF
DAY SCHEDULE AND A SPACE OCCUPANCY SENSOR.
DURING THE SCHEDULED OCCUPANCY PERIOD, THE ZONE SHALL BE INITIALLY
INDEXED TO OCCUPIED AND OPERATE FOR A MINIMUM OF 30 MINUTES, AT WHICH
TIME THE SPACE OCCUPANT SENSOR SHALL INDEX THE SPACE BETWEEN OCCUPIED
AND OCCUPIED SETBACK MODE.
IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD,
AS DETERMINED VIA THE OCCUPANCY SENSOR, THE ZONE SHALL BE INDEXED TO
OCCUPIED FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO
UNOCCUPIED WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 30 MINUTES.
SPACE VENTILATION CONTROL
IF THE ZONE IS OCCUPIED, THE SUPPLY AND EXHAUST AIR BOXES SHALL INDEX TO
THE OCCUPIED AIRFLOW SETPOINT.
IF THE SPACE IS UNOCCUPIED, THE SUPPLY AND EXHAUST AIR BOXES SHALL CLOSE.
ZONE TEMPERATURE CONTROL
TEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OF
PROGRAMMED SCHEDULE AND A SPACE OCCUPANCY SENSOR.
OCCUPIED HEATING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED
PERIOD AND THE ZONE TEMPERATURE FALLS BELOW THE OCCUPIED HEATING
TEMPERATURE SETPOINT, THE REHEAT COIL AND RADIANT CEILING PANEL CONTROL
VALVES SHALL MODULATE IN PARALLEL TO MAINTAIN THE OCCUPIED HEATING
TEMPERATURE SETPOINT.
OCCUPIED COOLING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED
OCCUPIED PERIOD AND THE ZONE TEMPERATURE RISES ABOVE THE OCCUPIED
COOLING TEMPERATURE SETPOINT, THE CHILLED BEAM CONTROL VALVE SHALL
MODULATE TO MAINTAIN THE OCCUPIED COOLING TEMPERATURE.
OCCUPIED HEATING SETBACK: IF THE SPACE IS UNOCCUPIED DURING THE
SCHEDULED PERIOD, AND THE ZONE TEMPERATURE FALLS BELOW THE OCCUPIED
HEATING SETBACK TEMPERATURE SETPOINT, THE REHEAT COIL AND RADIANT
CEILING PANEL CONTROL VALVES SHALL MODULATE IN PARALLEL TO MAINTAIN THE
OCCUPIED HEATING TEMPERATURE SETPOINT.
OCCUPIED COOLING SETBACK: IF THE SPACE IS UNOCCUPIED DURING THE
SCHEDULED OCCUPIED PERIOD, AND THE ZONE TEMPERATURE RISES ABOVE THE
OCCUPIED COOLING SETBACK TEMPERATURE SETPOINT, THE PRIMARY AIR BOX AND
EXHAUST AIR BOX SHALL OPEN, AND THE CHILLED BEAM CONTROL VALVE SHALL
MODULATE TO MAINTAIN THE OCCUPIED COOLING SETBACK TEMPERATURE
SETPOINT.
UNOCCUPIED HEATING SETBACK: IF THE SPACE IS UNOCCUPIED DURING THE
SCHEDULED UNOCCUPIED PERIOD AND THE ZONE TEMPERATURE FALLS BELOW THE
UNOCCUPIED HEATING TEMPERATURE SETPOINT, THE RADIANT CEILING PANEL
CONTROL VALVE SHALL MODULATE TO MAINTAIN THE UNOCCUPIED HEATING
TEMPERATURE SETPOINT.
UNOCCUPIED COOLING SETBACK: IF THE SPACE IS UNOCCUPIED DURING THE
SCHEDULED UNOCCUPIED PERIOD AND THE ZONE TEMPERATURE RISES ABOVE THE
UNOCCUPIED COOLING TEMPERATURE SETPOINT, THE PRIMARY AIR BOX AND THE
EXHAUST BOX SHALL OPEN, AND THE CHILLED BEAM COOLING CONTROL VALVE
SHALL MODULATE TO MAINTAIN THE UNOCCUPIED COOLING TEMPERATURE
SETPOINT.
THE COOLING COIL CONTROL VALVE SHALL BE CLOSED WHENEVER THE HEATING
COIL CONTROL VALVE IS OPEN TO PREVENT SIMULTANEOUS HEATING AND COOLING.
CONDENSATION CONTROL
IF MOISTURE IS SENSED ON THE CHILLED WATER SUPPLY PIPING BY THE
CONDENSATION SENSOR, THE CHILLED WATER ZONE VALVE SHALL CLOSE UNTIL
MOISTURE IS NO LONGER SENSED, AT WHICH TIME NORMAL SEQUENCE SHALL
RESUME.
RADIANT CEILING HEATING AND ACTIVE CHILLED BEAM COOLING ZONE CONTROL
GENERAL EXHAUST
RADIANT CEILING PANELS
HWS
HWR
ONLY APPLICABLE FOR SPACES
WITH RADIANT HEATING PANELS SEQUENCE OF OPERATION
SA MAIN
VV TERMINAL BOX WITH
REHEAT COIL
CHILLED
BEAM
PROVIDE 1 CONTROL VALVE
FOR CHILLED BEAM COOLING
PER ZONE.
TO OTHER CHILLED
BEAMS IN SPACE
TO CHILLED BEAMS
WITHIN ZONE
SPACE
OCCUPANCY
SENSOR
OCCUPANCY SENSORS PROVIDED
BY DIVISION 26. PROVIDE BMS
INTERFACE MODULE AND
COORDINATE WITH LIGHTING
CONTROL MANUFACTURER.
COMBINATION SPACE
TEMPERATURE/HUMIDITY/CO2
TRANSMITTER
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M8.70
29313.00
11/30/18
HVAC - CONTROLS
# DATE DESCRIPTION
1 11/30/18 ISSUED FOR CONSTRUCTION
DocuSign Envelope ID: D6CBE973-BBA9-4BE0-861E-C2F6DD72B539
12/10/2018