HomeMy WebLinkAboutM8.60HVAC - CONTROLSC
C
LOW HOOD DENSITY LAB CONTROLS
POINT NAME
HARDWARE POINTS SOFTWARE POINTS
SHOW ON
GRAPHIC NOTES
BI BO AI AO AV BV SCH TREND
ALARM
BACS EMCS
STEAM LOAD SHED X(6)BINARY NETWORK INPUTS FROM EMCS
CHILLED WATER LOAD SHED X(4)BINARY NETWORK INPUTS FROM EMCS
TOTAL EXHAUST AIRFLOW (CFM)X X X
TOTAL EXHAUST AIR SETPOINT (CFM)X X X
LABORATORY AIR CHANGE RATE (ACPH)X X X
FLOW OFFSET SETPOINT (CFM)X X
FLOW OFFSET ACTUAL (CFM)X X
FUME HOOD EXHAUST VALVE FLOW FEEDBACK (CFM)X X X
FUME HOOD EXHAUST AIR VALVE STATUS X X
X
VALVE COMMAND ≠ FEEDBACK (JAM)
LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X TRI-STATE ALARM
FUME HOOD SASH POSITION X X X SASH OPEN (18") FOR 24 CONTINUOUS HOURS OR MORE X
FUME HOOD EXHAUST AIR VALVE OCC/UNOCC COMMAND X X TRI-STATE OUTPUT POINT
SUPPLY AIR VALVE FLOW FEEDBACK (CFM)X X X
SUPPLY AIR VALVE STATUS X
X
X
X
10% FLOW DEVIATION FROM SETPOINT
VALVE COMMAND ≠ FEEDBACK (JAM)
LOW DIFFERENTIAL PRESSURE (VIA SWITCH)
X TRI-STATE ALARM
SUPPLY AIR VALVE POSITION COMMAND (CFM)X X X
SUPPLY AIR VALVE MINIMUM AIRFLOW SETPOINT (CFM)X X
SUPPLY AIR VALVE MAXIMUM AIRFLOW SETPOINT (CFM)X X
RE-HEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR
RE-HEAT COIL VALVE POSITION COMMAND (%)X X X 5° F ΔT ACROSS COIL WITH VALVE COMMANDED CLOSED X FAIL LAST
SPACE TEMPERATURE SETPOINT, HEATING X X X
SPACE TEMPERATURE SETPOINT, COOLING X X X
SPACE TEMPERATURE X X X +/- 4 ° FROM SETPOINT X
SPACE SETPOINT ADJUSTMENT X X
SPACE OCCUPANCY X X X X
SPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINT X
GENERAL EXHAUST AIR VALVE POSITION COMMAND (CFM)X X X
GENERAL EXHAUST AIR VALVE MINIMUM AIRFLOW SETPOINT (CFM)X X
GENERAL EXHAUST AIR VALVE MAXIMUM AIRFLOW SETPOINT (CFM)X X
GENERAL EXHAUST AIR VALVE FLOW FEEDBACK (CFM)X X X
GENERAL EXHAUST AIR VALVE STATUS X
X
X
X
10% FLOW DEVIATION FROM SETPOINT
VALVE COMMAND ≠ FEEDBACK (JAM)
LOW DIFFERENTIAL PRESSURE (VIA SWITCH)
X TRI-STATE ALARM
RADIANT CEILING PANEL CONTROL VALVE POSITION COMMAND (%)X X X FAIL LAST
COOLING COIL CONTROL VALVE POSITION COMMAND (%)X X X NORMALLY CLOSED
FAN COIL UNIT FAN MOTOR START/STOP X X X
FUME HOOD
DI
AO
AI
AI DIAI AI
C
YA
01
FCV
01
ZS
01
TT
01
YI
01
MT
01
CO2
01
SYSTEM DESCRIPTION
FUME HOOD WITH EXHAUST AIR VALVE
GENERAL EXHAUST AIR VALVE
SUPPLY AIR VALVE
DUCT MOUNTED RE-HEAT COIL
SUPPLEMENTAL COOLING FAN COIL UNIT
RADIANT CEILING PANEL HEATER
GENERAL
REFER TO COMMON INDIVIDUAL DEVICE SEQUENCES/DIAGRAMS FOR REQUIRED
POINTS. ALL POINTS WITHIN EACH ZONE MUST BE CONNECTED DIRECTLY TO A LOCAL
CONTROLLER. TO ENSURE ZONES CAN OPERATE INDEPENDENTLY, DEVICES SHALL
NOT RELY ON NETWORK TO COMMUNICATE ACROSS ZONES.
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND
CONTROL SYSTEM (BACS).
ALL SETPOINTS SHALL BE ADJUSTABLE
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING
DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
SETPOINTS
SPACE COOLING TEMPERATURE SETPOINTS:
OCCUPIED: 75 °F +/- 1.5 °F
OCCUPIED SETBACK: 75 °F + 3 °F
UNOCCUPIED: 75 °F + 6 °F
SPACE HEATING TEMPERATURE SETPOINTS:
OCCUPIED: 75 °F +/- 1.5 °F
OCCUPIED SETBACK: 75 °F - 3 °F
UNOCCUPIED: 75 °F - 6 °F
TOTAL EXHAUST AIR CHANGE RATE (ACPH):
TYPICALLY = 8 ACPH OCC / 4 ACPH UNOCC
ACPH = TOTAL EXHAUST CFM x 60 / ROOM VOLUME
TOTAL EXHAUST AIRFLOW RATE: (CFM):
REFER TO AIRFLOW SCHEDULE
SUPPLY AIRFLOW RATE (CFM):
REFER TO AIRFLOW SCHEDULE
TYPICALLY = TOTAL EXHAUST RATE + OFFSET
FUME HOOD EXHAUST AIRFLOW RATE:
NOT CONTROLLED BY BACS. VALVE IS CONTROLLED BY FUME HOOD MONITOR TO
MAINTAIN FACE VELOCITY SETPOINT.
GENERAL EXHAUST AIRFLOW RATE (CFM):
REFER TO AIRFLOW SCHEDULE
TOTAL EXHAUST CFM - FUME HOOD EXHAUST CFM
SPACE AIR DIFFERENTIAL OFFSET (CFM):
REFER TO AIRFLOW SCHEDULE
TYPICALLY = - 100 CFM FOR NEGATIVE PRESSURE LABS
TYPICALLY = + 100 CFM FOR POSITIVE PRESSURE LABS
FUME HOOD FACE VELOCITY:
NOT CONTROLLED BY BACS. FACE VELOCITY SETPOINTS ARE PROGRAMMED INTO
FUME HOOF MONITOR. TYPICALLY 100 FPM OCC / 65 FPM UNOCC
MINIMUM LABORATORY OCCUPANCY INDEX TIME: 30 MINUTES
ZONE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRI
FACE VELOCITY CONTROL
THE FUME HOOD SHALL BE EQUIPPED WITH A FUME HOOD MONITOR AND SASH
POSITION INDICATOR.
THE MONITOR SHALL, AS A MINIMUM, HAVE THE FOLLOWING CAPABILITIES:
- SASH POSITION INPUT
- STANDBY MODE INPUT TO ALLOW ADJUSTMENT OF FACE VELOCITY.
- HOOD DECOMMISSION MODE.
LABORATORY AIRFLOW CONTROL
AIR VALVE POSITIONS SHALL BE BASED ON MODE. UNDER NORMAL CONTROL, ROOM
OCCUPANCY SHALL BE DETERMINED VIA ROOM OCCUPANCY SENSORS (MINIMUM 2
PER LAB USING LIGHTING OCCUPANCY SENSOR AUXILIARY CONTACTS). IF THE
LABORATORY IS VACANT, THE ROOM SHALL BE PLACED IN VACANT MODE BY THE
BACS.
WHEN THE ROOM IS OCCUPIED, THE BACS SHALL SEND AN OCCUPIED COMMAND TO
THE FUME HOOD EXHAUST AIR VALVE. THE FUME HOOD MONITOR SHALL INDEX THE
FUME HOOD EXHAUST AIR VALVE AS NEEDED TO MAINTAIN THE 100 FPM FACE
VELOCITY SETPOINT BASED ON THE SASH POSITION. THE GENERAL EXHAUST AIR
VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE OCCUPIED AIR CHANGE
RATE. THE SUPPLY AIR VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE
SPECIFIED AIRFLOW DIFFERENTIAL.
WHEN THE ROOM IS UNOCCUPIED, AND THE SASH IS AT OR BELOW 18-INCHES, THE
BACS SHALL SEND AN UNOCCUPIED COMMAND TO THE FUME HOOD EXHAUST AIR
VALVE. THE FUME HOOD MONITOR SHALL INDEX THE FUME HOOD EXHAUST AIR
VALVE AS NEEDED TO MAINTAIN THE 65 FPM FACE VELOCITY SETPOINT BASED ON
THE SASH POSITION. THE GENERAL EXHAUST AIR VALVE SHALL MODULATE AS
NEEDED TO MAINTAIN THE UNOCCUPIED AIR CHANGE RATE. THE SUPPLY AIR VALVE
SHALL MODULATE AS NEEDED TO MAINTAIN THE SPECIFIED AIRFLOW DIFFERENTIAL
WHEN THE ROOM IS UNOCCUPIED AND THE SASH IS ABOVE 18-INCHES BASED ON
SASH POSITION, THE BACS SHALL NOT SEND THE SPACE UNOCCUPIED COMMAND TO
THE FUME HOOD EXHAUST AIR VALVE. THE FUME HOOD MONITOR SHALL INDEX THE
FUME HOOD EXHAUST AIR VALVE TO MAINTAIN THE UNOCCUPIED AIR CHANGE RATE.
THE SUPPLY AIR VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN THE SPECIFIED
AIRFLOW DIFFERENTIAL.
VACANT MODE: THE BACS SHALL SEND A DECOMMISSION COMMAND TO THE FUME
HOOD EXHAUST AIR VALVE. THE FUME HOOD MONITOR SHALL INDEX THE FUME
HOOD EXHAUST AIR VALVE TO CLOSE. THE GENERAL EXHAUST AIR VALVE SHALL
MODULATE AS NEEDED TO MAINTAIN THE VACANT AIR CHANGE RATE. THE SUPPLY
AIR VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN THE SPECIFIED AIRFLOW
DIFFERENTIAL.
ZONE TEMPERATURE CONTROL
TEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OF
PROGRAMED SCHEDULE AND SPACE OCCUPANCY SENSORS.
OCCUPIED HEATING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED
PERIOD AND THE SPACE TEMPERATURE FALLS BELOW THE OCCUPIED HEATING
TEMPERATURE SETPOINT, THE REHEAT AND RADIANT PANEL CONTROL VALVES
SHALL MODULATE IN PARALLEL TO MAINTAIN THE SPACE TEMPERATURE SETPOINT.
WHEN THE SPACE TEMPERATURE IS AT SETPOINT, THE RADIANT PANEL AND REHEAT
COIL CONTROL VALVES SHALL BE CLOSED.
OCCUPIED COOLING: THE SPACE SHALL HAVE A FAN COIL UNIT TO PROVIDE
SUPPLEMENTAL SPACE COOLING. IF THE SPACE IS OCCUPIED DURING THE
SCHEDULED OCCUPIED PERIOD AND THE SPACE TEMPERATURE RISES ABOVE THE
OCCUPIED COOLING TEMPERATURE SETPOINT, THE FAN COIL UNIT FAN SHALL
START, AND THE COOLING COIL CONTROL VALVE SHALL MODULATE TO MAINTAIN
SETPOINT. WHEN THE SPACE TEMPERATURE IS AT SETPOINT, THE FAN COIL UNIT
SHALL SHUT OFF AND THE CHILLED WATER CONTROL VALVE SHALL CLOSE.
OCCUPIED SETBACK: IF THE SPACE BECOMES UNOCCUPIED DURING THE
SCHEDULED OCCUPIED PERIOD, THE ABOVE OCCUPIED HEATING/COOLING
SEQUENCES SHALL APPLY. BUT THE SPACE SHALL BE MAINTAINED AT THE OCCUPIED
SETBACK TEMPERATURE SETPOINTS.
UNOCCUPIED HEATING: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED
UNOCCUPIED PERIOD AND THE SPACE TEMPERATURE FALLS BELOW THE
UNOCCUPIED HEATING TEMPERATURE SETPOINT, THE REHEAT AND RADIANT PANEL
CONTROL VALVES SHALL MODULATE IN PARALLEL TO MAINTAIN THE SPACE
TEMPERATURE SETPOINT.
UNOCCUPIED COOLING: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED
UNOCCUPIED PERIOD AND THE ZONE TEMPERATURE RISES ABOVE THE UNOCCUPIED
COOLING TEMPERATURE SETPOINT, THE FAN COIL UNIT SHALL START, AND THE FAN
COIL UNIT COOLING CONTROL VALVE SHALL MODULATE TO MAINTAIN SETPOINT.
IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD,
THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY.
WHEN THE SPACE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULED
UNOCCUPIED PERIOD, THE SPACE SHALL INDEX BACK TO UNOCCUPIED MODE.
VACANT MODE: THE ABOVE UNOCCUPIED HEATING/COOLING SEQUENCES SHALL
APPLY. THE SPACE SHALL BE MAINTAINED AT THE UNOCCUPIED TEMPERATURE
SETPOINTS.
THE COOLING COIL CONTROL VALVE SHALL BE CLOSED WHENEVER THE HEATING
COIL CONTROL VALVE IS OPEN TO PREVENT SIMULTANEOUS HEATING AND COOLING.
THE COOLING CONTROL VALVE SHALL BE CLOSED WHEN THE FAN COIL UNIT FAN IS
OFF.
LOW HOOD DENSITY TRACKING LABORATORY ZONE CONTROL
GENERAL EXHAUST
LOCAL FUME HOOD
ALARM WITH
REMOTE ALARM
CONTACTS
FUME HOOD EXHAUST
TYPICAL FOR EACH FUME HOOD
(WHERE APPLICABLE)
RADIANT CEILING PANELS
HWS
HWR
ONLY APPLICABLE FOR SPACES
WITH RADIANT HEATING PANELS
SV
FUME HOOD SASH
POSITION SENSOR
SEQUENCE OF OPERATION
FCU
SPACE
OCCUPANCY
SENSOR
OCCUPANCY SENSORS PROVIDED
BY DIVISION 26. PROVIDE BMS
INTERFACE MODULE AND
COORDINATE WITH LIGHTING
CONTROL MANUFACTURER.
COMBINATION SPACE
TEMPERATURE/HUMIDITY/CO2
TRANSMITTER
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M8.60
29313.00
11/30/18
HVAC - CONTROLS