HomeMy WebLinkAboutM8.30HVAC - CONTROLSAHU-A, EF-A.1/A.2, AND GLYCOL RUNAROUND CONTROL POINTS
POINT NAME
HARDWARE POINTS SOFTWARE POINTS
SHOW ON
GRAPHIC NOTES
BI BO AI AO AV BV SCH TREND
ALARM
BACS EMCS
STEAM LOAD SHED X(6)BINARY NETWORK INPUTS FROM EMCS
CHILLER WATER LOAD SHED X(4)X BINARY NETWORK INPUTS FROM EMCS
OUTSIDE AIR DAMPER POSITION COMMAND X X
OURSIDE AIR DAMPER STATUS X X X
OUTSIDE AIR TEMPERATURE X X X
OUTSIDE AIR RELATIVE HUMIDITY X X X
OUTSIDE AIR DEWPOINT X X
OUTSIDE AIR FILTER RACK DIFFERENTIAL PRESSURE X X X X X HIGH LIMIT X MAGNAHELIC INDICATING TRANSMITTER
HRC SUPPLY COIL ENTERING WATER TEMPERATURE X X X
HRC SUPPLY COIL LEAVING WATER TEMPERATURE X X X
HRC EXHAUST COIL ENTERING WATER TEMPERATURE X X X
HRC EXHAUST COIL LEAVING WATER TEMPERATURE X X X
HRC LOOP PUMP MOTOR START/STOP (EACH PUMP)X X X INTERLOCK WITH FA SYSTEM, IF REQUIRED
HRC LOOP PUMP MOTOR SPEED CONTROL (EACH PUMP)X X X
HRC LOOP PUMP MOTOR STATUS (EACH PUMP)X X X MOTOR FAILURE X VIA CURRENT SENSOR
HRC BYPASS CONTROL VALVE POSITION COMMAND X X X
HRC DISCHARGE AIR TEMPERATURE X X X X X
HRC DISCHARGE AIR HUMIDITY X X X X X
SUPPLY AIR FILTER RACK DIFFERENTIAL PRESSURE X X X X HIGH LIMIT X MAGNAHELIC INDICATING TRANSMITTER
PRE-HEAT COIL VALVE POSITION COMMAND X X X X 5° F ΔT ACROSS COIL WITH VALVE COMMANDED CLOSED X NORMALLY OPEN
PRE-HEAT COIL DISCHARGE AIR TEMPERATURE X X X AVERAGING SENSOR
PRE-HEAT COIL PUMP START/STOP X X
PRE-HEAT COIL PUMP STATUS X X X MOTOR FAILURE X VIA CURRENT SENSOR
LOW LIMIT AIR TEMPERATURE STATUS X X X LOW LIMIT X
LOW LIMIT WATER TEMPERATURE STATUS X X X LOW LIMIT X
COOLING COIL VALVE POSITION COMMAND X X X X 5° F ΔT ACROSS COIL WITH VALVE COMMANDED CLOSED X NORMALLY CLOSED
COOLING COIL DISCHARGE AIR TEMPERATURE X X X AVERAGING SENSOR
SUPPLY FAN AIR FLOW (EACH FAN)X X X INSTALL IN INLET CONE WHERE FEASIBLE
SUPPLY FAN FAN MOTOR START/STOP (EACH FAN)X X X X INTERLOCK WITH FA SYSTEM
SUPPLY FAN FAN SPEED COMMAND (EACH FAN)X X X
SUPPLY FAN DOWNSTREAM STATIC PRESSURE (2 SENSORS AVERAGED) X X X X 10% DEVIATION FROM SETPOINT X
SUPPLY FAN DOWNSTREAM STATIC PRESSURE SETPOINT X X X
SUPPLY FAN DUCT SMOKE DETECTOR STATUS X X
SUPPLY FAN STATUS (EACH FAN)X X X FAILURE X VIA CONTACT ON DRIVE
SUPPLY FAN POWER (kW) (EACH FAN)X X X BACnet MSTP NETWORK POINT
SUPPLY FAN SPEED (RPM) (EACH FAN)X X X BACnet MSTP NETWORK POINT
SUPPLY FAN DISCHARGE PRESSURE SWITCH STATUS X X X HIGH LIMIT X
SUPPLY FAN SUCTION PRESSURE SWITCH STATUS X X X LOW LIMIT X
AHU DISCHARGE AIR TEMPERATURE X X X X +/- 4° F FROM SETPOINT X SINGLE POINT SENSOR
AHU DISCHARGE AIR TEMPERATURE SETPOINT X X X
AHU DISCHARGE AIR HUMIDITY X X X X X
EXHAUST AIR BYPASS DAMPER POSITION COMMAND X X
EXHAUST AIR ISOLATION DAMPER POSITION COMMAND (EACH FAN) X X
EXHAUST AIR ISOLATION DAMPER STATUS (EACH FAN) X X X
EXHAUST FAN AIR FLOW (EACH FAN)X X X INSTALL IN INLET CONE WHERE FEASIBLE
EXHAUST FAN MOTOR START/STOP (EACH FAN)X X X X INTERLOCK WITH FA SYSTEM
EXHAUST FAN SPEED COMMAND (EACH FAN)X X X
EXHAUST FAN UPSTREAM STATIC PRESSURE (2 SENSORS AVERAGED) X X X X 10% DEVIATION FROM SETPOINT X
EXHAUST FAN UPSTREAM STATIC PRESSURE SETPOINT X X X
EXHUAST FAN STATUS (EACH FAN)X X X FAILURE X VIA CONTACT ON DRIVE
EXHAUST FAN POWER (kW) (EACH FAN)X X X BACnet MSTP NETWORK POINT
EXHUAST FAN SPEED (RPM) (EACH FAN)X X X BACnet MSTP NETWORK POINT
EXHAUST FAN SUCTION PRESSURE SWITCH STATUS (EACH FAN) X X X LOW LIMIT X
HRC EXHAUST AIR ENTERING HUMIDITY X X X
HRC EXHAUST AIR LEAVING HUMIDITY X X X
HRC EXHAUST AIR ENTERING TEMPERATURE X X X
HRC EXHAUST AIR LEAVING TEMPERATURE X X X
HRC EXHAUST AIR LEAVING TEMPERATURE SETPOINT X X X FOR FROST CONTROL
HRC EXHAUST AIR FILTER RACK DIFFERENTIAL PRESSURE X X X X HIGH LIMIT X MAGNAHELIC INDICATING TRANSMITTER
HEAT EXCHANGER STEAM CONTROL VALVE POSITION COMMAND (EACH HX) X X X X X FAIL CLOSED
HEAT EXCHANGER GLYCOL ISOLATION VALVE POSITION COMMAND (EACH HX) X X X X X FAIL CLOSED
HRC HEAT RECOVERY EFFECTIVENESS X X X CALCULATE BASED ON TEMPERATURE
HRC RECOVERED ENERGY (BTUH)X X X CALCULATE BASED ON TEMPERATURE
HRC TOTALIZED RECOVERED ENERGY (BTU/YR)X X X CALCULATE BASED ON TEMPERATURE
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M8.30
29313.00
11/30/18
HVAC - CONTROLS
# DATE DESCRIPTION
1 11/30/18 ISSUED FOR CONSTRUCTION
DocuSign Envelope ID: D6CBE973-BBA9-4BE0-861E-C2F6DD72B539
12/10/2018