M6.20HVAC - SCHEDULES
HOT WATER DUCT COIL SCHEDULE HYDRONIC CONTROL VALVE SCHEDULE UNIT NO.TYPE VALVE PIPE SIZE (IN) ACTUATOR MANUFACTURER MODEL NUMBER (BASIS OF DESIGN) CV-RHC-1-8 2-WAY NON-SPRING RETURN BELIMO TR24 MAX GPM MAX PD (PSI)CV CONTROL VALVE MANUFACTURER MODEL NUMBER (BASIS OF DESIGN) BELIMO CCV-B2090.82.31.21/2 FAIL POSITION LAST CLOSE OFF RATING (PSI) 200 VALVE CHARACTERISTIC CCV VALVE TURNDOWN 30-100% REMARKS CV-RHC-1-12 CV-RHC-1-14 CV-RHC-2-12 CV-RHC-2-14 CV-FCU-1 CV-FCU-2 CV-FCU-3 CV-FCU-4 CV-FCU-5 CV-AHU-A CHW CV-EXH RECOVERY CV-RCP-1.1 (<0.6 GPM) 2-WAY NON-SPRING RETURN 3.3 3.0 1.9 BELIMO CCV-B211LAST 200 CCV 30-100% 2-WAY NON-SPRING RETURN BELIMO CCV-B211LAST 200 CCV 30-100% 2-WAY NON-SPRING RETURN BELIMO CCV-B212LAST 200 CCV 30-100% 2-WAY NON-SPRING RETURN BELIMO CCV-B212LAST 200 CCV 30-100% 3.9 4.2 1.9 1/2 5.3 3.1 3.0 1/2 6.6 4.8 3.0 1/2 BELIMO TR24 BELIMO TR24 BELIMO TR24 BELIMO TR24 1/2 2-WAY SPRING RETURN BELIMO CCV-B209CLOSED 200 CCV 30-100%1/2 1.6 4.0 0.8 BELIMO TFRX24 BELIMO CCV-B210CLOSED 200 CCV 30-100%1/2 2.6 4.7 1.2 BELIMO CCV-B211CLOSED 200 CCV 30-100%1/2 3.1 2.7 1.9 BELIMO CCV-B210CLOSED 200 CCV 30-100%1/2 2.0 2.8 1.2 BELIMO CCV-B212CLOSED 200 CCV 30-100%1/2 6.0 4 3.0 2-WAY SPRING RETURN 2-WAY SPRING RETURN 2-WAY SPRING RETURN 2-WAY SPRING RETURN BELIMO TFRX24 BELIMO TFRX24 BELIMO TFRX24 BELIMO TFRX24 2-WAY NON-SPRING RETURN 1/2 BELIMO TR240.6 4.7 0.3 BELIMO CCV-B207LAST 200 CCV 30-100% CV-RCP-1.1 (0.6-1.0 GPM) 2-WAY NON-SPRING RETURN 1/2 BELIMO TR241.0 4.7 0.46 BELIMO CCV-B208LAST 200 CCV 30-100% CV-RCP-1.1 (1.0-1.7 GPM) 2-WAY NON-SPRING RETURN 1/2 BELIMO TR241.7 4.5 0.85 BELIMO CCV-B209LAST 200 CCV 30-100% BELIMO CCV-B262CLOSED 200 CCV 30-100%2-1/2 160 4.6 75.02-WAY SPRING RETURN BELIMO ARX24-SR-T BELIMO CCV-B321BLAST 200 CCV 30-100%3/4 50 4.4 24.0 3-WAY NON-SPRING RETURN BELIMO LRB24 STEAM CONTROL VALVE SCHEDULE UNIT NO.TYPE VALVE PIPE SIZE (IN) ACTUATOR MANUFACTURER MODEL NUMBER (BASIS OF DESIGN) REMARKS CV-HX-1 2-WAY SPRING RETURN 1 FISHER 2052 MAX LBS/HR 820 MAX INLET PRESSURE (PSI) 15 CV 20 CONTROL VALVE MANUFACTURER MODEL NUMBER (BASIS OF DESIGN) FISHER V300 FAIL POSITION CLOSED CLOSE OFF RATING (PSI) 200 VALVE CHARACTERISTIC VALVE TURNDOWN 300:1MODIFIED EQUAL PERCENTAGE CV-HX-2 2-WAY SPRING RETURN 1 FISHER 20521,311 15 32 FISHER V300CLOSED 200 MODIFIED EQUAL PERCENTAGE 300:1 CV-HX-3 2-WAY SPRING RETURN 1 FISHER 20521,311 15 32 FISHER V300CLOSED 200 MODIFIED EQUAL PERCENTAGE 300:1 CV-(XR)CHILLED BEAM (<0.6 GPM) 2-WAY NON-SPRING RETURN 1/2 BELIMO TR240.6 4.7 0.3 BELIMO CCV-B207LAST 200 CCV 30-100% 2-WAY NON-SPRING RETURN 1/2 BELIMO TR241.0 4.7 0.46 BELIMO CCV-B208LAST 200 CCV 30-100% 2-WAY NON-SPRING RETURN 1/2 BELIMO TR241.7 4.5 0.85 BELIMO CCV-B209LAST 200 CCV 30-100% CV-(XR)CHILLED BEAM (0.6-1.0 GPM) CV-(XR)CHILLED BEAM (1.0-1.7 GPM) MANUFACTURER MODEL NUMBER (AS STANDARD) SERVICEUNIT NO.CFM OUTPUT (MBH) SIZE W X H (IN.) FACE VELOC. (FPM) ROWS EAT (°F) LAT (°F) AIR DATA P.D. (IN.WG)GPM WATER DATA EWT (°F) LWT (°F) P.D. (FT.) REMARKS RHC-1-8 SUPPLY AIR 450 12.2 10x10 620 2 55 80 0.22 1.2 130 109.4 0.7 AEROFIN HWP-12.0AF-10.5 X 10.0-2-11 RHC-1-12 SUPPLY AIR 1,000 27.0 18x12 670 2 55 80 0.24 3.3 130 113.3 0.5 AEROFIN HW-12.0AF-12.0 X 18.0-2-0.333 RHC-1-14 SUPPLY AIR 1,300 35.1 20x14 700 2 55 80 0.26 3.9 130 111.6 0.8 AEROFIN HW-12.0AF-13.5 X 20.0-2-0.333 RHC-2-12 SUPPLY AIR 2,000 54.0 26x16 700 2 55 80 0.25 5.3 130 109.2 0.9 AEROFIN HW-12.0AF-16.5 X 26.0-2-0.333 RHC-2-14 SUPPLY AIR 2,800 75.6 32x18 700 2 55 80 0.26 6.6 130 106.6 1.5 AEROFIN HW-12.0AF-18.0 X 32.0-2-0.333 FLOOR PLAN LAYOUT UTILIZES BOTH LEFT AND RIGHT HAND COIL CONNECTIONS. CONTRACTOR SHALL COORDINATE LOCATION AND ORIENTATION OF EACH COIL.1 LABORATORY VARIABLE AIR VOLUME TERMINAL BOX AND AIR BALANCE SCHEDULE ROOM NUM ROOM NAME ROOM DIMENSIONS CODE MINIMUM VENTILATION EXHAUST AIR SUPPLY AIR XFER AREA (SF) HEIGHT (FT) NYS OUTDOOR AIRFLOW (NOTE 2) NYS EXHAUST AIRFLOW (NOTE 3) EXHAUST POINT EXHAUST TYPE VALVE SIZE SOUND ATTENUATOR VALVE RANGE OCCUPIED SASH OPEN (NOTE 4) OCCUPIED SASH CLOSED COOLING PEAK (NOTE 5) OCCUPIED SASH CLOSED MINIMUM (NOTE 5) UNOCCUPIED SASH FULL (NOTE 6) UNOCCUPIED SASH OPEN (NOTE 7) UNOCCUPIED SASH CLOSED (NOTE 8) SUPPLY POINT VALVE SIZE REHEAT COIL SOUND ATTENUATOR VALVE RANGE OCC SASH OPEN (NOTE 4) OCC SASH CLOSED COOLING PEAK (CFM) OCC SASH CLOSED MINIMUM (CFM) UNOCC SASH FULL (CFM) UNOCC SASH OPEN (CFM) UNOCC SASH CLOSED (CFM) ALL MODES (CFM)MAX MIN 100 FPM 80 FPM MAX MIN 100 FPM 80 FPM (CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (CFM) 276A GLASSWASH 111 10 65 3.5 115 6 EV-2.4 CANOPY HOOD 1-12 SATT-EV3 1005 100 530 28.6 530 28.6 530 28.6 530 28.6 530 28.6 530 28.6 265 14.3 SV-2.4 1-12 RHC-1-12 SATT-SV2 1005 100 485 485 485 485 485 485 220 -45 TOTAL 530 530 530 530 530 530 265 276B TISSUE CULTURE (MAMMALIAN)170 10 105 3.7 170 6 EV-2.13 GEN EXH 1-8 SATT-EV1 450 50 230 8.1 230 8.1 130 4.5 130 4.5 230 8.1 215 7.5 215 7.5 SV-2.3 1-8 RHC-1-8 SATT-SV1 450 50 130 130 750 130 130 130 115 -100 TOTAL 230 230 130 130 230 215 215 276C TISSUE CULTURE (BACTERIAL)158 10 90 3.4 160 6 EV-2.12 GEN EXH 1-8 SATT-EV1 450 50 215 8.1 215 8.1 115 4.3 115 4.3 215 8.1 215 8.1 215 8.1 SV-2.8 1-8 RHC-1-8 SATT-SV1 450 50 115 115 685 115 115 115 115 -100 TOTAL 215 215 115 115 215 215 215 276 OPEN RESEARCH LAB 2358 10 1275 3.2 2360 6 EV-2.2 POINT EXHAUST 1-8 SATT-EV1 450 50 400 15.6 400 12.1 400 12.8 400 7.6 400 15.6 400 8.3 400 7.6 SV-2.1 1-14 RHC-1-14 SATT-SV3 1300 200 1180 955 930 605 1180 535 605 150 EV-2.5 FUME HOOD 1-12 SATT-EV3 1005 100 825 660 300 300 825 345 300 SV-2.2 1-14 RHC-1-14 SATT-SV3 1300 200 1180 955 930 605 1180 535 605 EV-2.6 FUME HOOD 1-12 SATT-EV2 1005 100 825 660 300 300 825 345 300 SV-2.5 1-12 RHC-1-12 SATT-SV6 1005 100 1000 810 790 510 1000 450 510 EV-2.7 FUME HOOD 1-12 SATT-EV2 1005 100 825 660 300 300 825 345 300 SV-2.6 2-12 RHC-2-12 SATT-SV7 2005 200 2000 1615 1575 1020 2000 900 1020 EV-2.8 FUME HOOD 1-12 SATT-EV3 1005 100 825 660 300 300 825 345 300 SV-2.7 2-12 RHC-2-12 SATT-SV8 2005 200 2000 1615 1575 1020 2000 900 1020 EV-2.9 FUME HOOD 1-12 SATT-EV2 1005 100 825 660 300 300 825 345 300 EV-2.10 FUME HOOD 1-12 SATT-EV3 1005 100 825 660 300 300 825 345 300 EV-2.1 GEN EXH 1-12 SATT-EV3 1005 100 267 133 947 267 267 267 267 EV-2.3 GEN EXH 1-12 SATT-EV3 1005 100 267 133 947 267 267 267 267 EV-2.11 GEN EXH 1-12 SATT-EV3 1005 100 267 133 947 267 267 267 267 TOTAL 6,150 4,760 5,040 3,000 6,150 3,270 3,000 276D ICVD ROOM 395 10 215 3.3 395 6 EV-2.17 GEN EXH 1-14 SATT-EV4 1300 200 400 35.6 200 27.6 1,065 29.8 400 19.7 400 35.6 400 21.1 400 19.7 SV-2.9 1-14 RHC-1-14 SATT-SV3 1300 200 1145 1065 885 550 1145 395 550 -200 EV-2.16 FUME HOOD 1-12 SATT-EV3 1005 100 825 660 300 300 825 345 300 SV-2.10 1-14 RHC-1-14 SATT-SV3 1300 200 1145 1065 885 550 1145 395 550 EV-2.15 FUME HOOD 1-12 SATT-EV3 1005 100 825 660 300 300 825 345 300 EV-2.14 POINT EXHAUST 1-8 SATT-EV1 450 50 300 300 300 300 300 300 300 TOTAL 2,350 1,820 1,965 1,300 2,350 1,390 1,300 367B LIGHT SCATTERING 57 10 50 5.3 60 6 EV-3.10 GEN EXH 1-8 SATT-EV1 450 50 170 11.5 170 11.5 370 38.9 70 4.7 170 11.5 170 11.5 170 11.5 SV-3.8 1-8 RHC-1-8 SATT-SV1 450 50 70 70 270 70 70 70 70 -100 TOTAL 170 170 370 70 170 170 170 367A FLUORESCENCE MICROSCOPE 66 10 50 4.5 70 6 EV-3.16 GEN EXH 1-8 SATT-EV1 450 50 150 11.2 150 11.2 410 37.2 50 3.7 150 11.2 150 11.2 150 11.2 SV-3.9 1-8 RHC-1-8 SATT-SV1 450 50 50 50 310 50 50 50 50 -100 TOTAL 150 150 410 50 150 150 150 367 OPEN RESEARCH LAB 2323 10 1265 3.3 2325 6 EV-3.8 VENT ENCLOSURE 1-8 SATT-EV1 450 50 340 15.2 340 12.6 340 15.3 340 8.4 340 15.2 340 9.0 340 8.4 SV-3.1 1-12 RHC-1-12 SATT-SV2 1005 100 580 495 580 315 580 295 315 -200 EV-3.9 VENT ENCLOSURE 1-8 SATT-EV1 450 50 340 340 340 340 340 340 340 SV-3.3 1-12 RHC-1-12 SATT-SV6 1005 100 1000 850 1000 540 1000 510 540 EV-3.9 GAS CABINET 1-8 SATT-EV1 450 50 200 200 200 200 200 200 200 SV-3.4 2-12 RHC-2-12 SATT-SV8 2005 200 1500 1275 1500 805 1500 760 805 EV-3.2 FUME HOOD 1-12 SATT-EV2 1005 100 825 660 300 300 825 345 300 SV-3.5 2-12 RHC-2-12 SATT-SV8 2005 200 1500 1275 1500 805 1500 760 805 EV-3.4 FUME HOOD 1-12 SATT-EV3 1005 100 825 660 300 300 825 345 300 SV-3.6 1-12 RHC-1-12 SATT-SV2 1005 100 580 495 580 315 580 295 315 EV-3.13 FUME HOOD 1-12 SATT-EV2 1005 100 825 660 300 300 825 345 300 SV-3.7 1-12 RHC-1-12 SATT-SV2 1005 100 580 495 580 315 580 295 315 EV-3.14 FUME HOOD 1-12 SATT-EV2 1005 100 825 660 300 300 825 345 300 EV-3.7 FUME HOOD 1-12 SATT-EV3 1005 100 825 660 300 300 825 345 300 EV-3.1 GEN EXH 1-14 SATT-EV4 1300 200 318 255 1,256 318 318 318 318 EV-3.15 GEN EXH 1-14 SATT-EV3 1300 200 263 210 1,038 263 263 263 263 EV-3.11 GEN EXH 1-14 SATT-EV4 1300 200 318 255 1,256 318 318 318 318 TOTAL 5,905 4,900 5,930 3,280 5,905 3,505 3,280 367F E-BEAM DEPOSITION ROOM 173 10 105 3.6 175 6 EV-3.3 FUME HOOD 1-12 SATT-EV3 1005 100 525 18.2 420 14.5 190 6.5 190 6.5 525 18.2 345 11.9 190 6.5 SV-3.2 1-12 RHC-1-12 SATT-SV2 1005 100 475 370 1125 190 475 295 190 -100 TOTAL 525 420 190 190 525 345 190 1 1 1 SUPPLY AIRFLOWS SHOWN FOR OPEN LABS ARE BASED ON FUTURE FUME HOODS. UNTIL THESE HOODS ARE INSTALLED SUPPLY AIRFLOWS WILL BE LOWER THAN SCHEDULED VALUES. PER CONTROL SEQUENCES SUPPLY VALVES WILL MODULATE TO MAINTAIN ROOM DIFFERENTIAL AIRFLOW SETPOINT. 2 2 2 2 Architect Payette Associates Architects, P.C. 290 Congress Street, Fifth Floor Boston, MA 02210-1005 Tel: 617-895-1000 Fax: 617-895-1002 MEP/FP Engineer Vanderweil 274 Summer Street Boston, MA 02210 Tel: 617-423-7423 Structural Engineer SGH 41 Seyong Street Building 1, Suite 500 Waltham, MA 02453 Tel: 781-907-9000 Fax: 781-907-9009 Drawing Scale Project Number Date Issued Renovation of Olin Hall for Chemical and Biomolecular Engineering - Phase 1 Code Consultant Hastings Consulting Inc 142 Hanlon Road Hollister, MA 01746 Tel: 508-397-8417 Lighting Designer Available Light 10 Derby Square #3 Salem, MA 01970 Tel: 978-744-6800 N Cost Consultant Dharam Consulting 745 Atlantic Ave Fl 8 Boston, MA 02111 Tel: 617-913-4345 Abatement Specialist Delta 860 Hooper Rd Endwell, NY 13760 Tel: 607-231-6600 Civil Engineer T.G. Miller, P.C. 203 N. Aurora Street Ithaca, NY 14850 Tel: 607-272-6477 NTS M6.20 29313.00 11/30/18 HVAC - SCHEDULES # DATE DESCRIPTION 1 11/30/18 ISSUED FOR CONSTRUCTION 2 12/18/18 ADDENDUM 01 DocuSign Envelope ID: 934A8599-03FD-4A73-BE43-DDC4ED06E6FA 12/18/2018