HomeMy WebLinkAboutM5.50HVAC - DETAILSSCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
DRAW THROUGH UNIT CONDENSATE TRAP9
N.T.S.
ROOF PIPING SUPPORT5
NTS
DETAIL OF PIPE THRU ROOF (EXCLUDING STEAM RELIEFS)3
NTS
PIPE RISER SUPPORT6
NTS
PIPE PENETRATION OF FULL HEIGHT PARTITIONS7
NTS
TYPICAL PIPE INSULATION & VALVE HANDLE EXTENSION11
NTS
TYPICAL FREEZESTAT LAYOUTS FOR AHU COOLING COILS1
NTSSCALE:
SCALE:
SCALE:
PITCH
1" WATER SEAL.
WC (WITH DIRTY FILTERS, COILS,
GREATER THAN THE MAXIMUM FAN
THIS DIMENSION IN INCHES MUST BE
SUCTION STATIC PRESSURE IN INCHES
AND MAXIMUM AIR FLOW).
MAXIMUM FAN SUCTION STATIC
GREATER THAN 1/2 OF THE SAME
THIS DIMENSION IN INCHES MUST BE
PRESSURE IN INCHES WC.
DRAIN PAN
NOTES:1. ALLOW SUFFICIENT SPACE BELOW DRAIN PAN FOR TRAP.
2. PITCH DRAIN FOR PROPER RUNOFF.
3. MANUALLY PRIME FILL TRAP BEFORE START-UP TO FORM
INITIAL DRAIN SEAL.
4. SUPPORT LENGTHY DRAIN LINES TO PREVENT SAG AND
CONDENSATE OVERFLOW.
PITCH
DRAIN PIPE
TO MATCH DRAIN
OUTLET SIZE.
CLEANOUT (TYP.)
(a)
(c)
(b)
(a)
(b)
(c)
3"
1.5"
1"
AND ACCEPTANCE BY ROOFING CONTRACTOR.
REGISTERED STRUCTURAL ENGINEER.
4. THE SUPPORTS SHALL BE SUBMITTED AS SHOP DRAWINGS AND SHALL BE REVIEWED BY THE
18" MAX.
SEE NOTE 1
W
3. FOR DISTANCE BETWEEN SUPPORTS REFER TO SPECIFICATIONS.
CENTER SUPPORTPLATE SEE NOTE 2
AVOID ROOF MEMBRANE DAMAGE. OBTAIN WRITTEN, APPROVED DRAWINGS OF COORDINATION
2. SIZE PLATE SUFFICIENT TO AVOID ROOF DAMAGE, BUT NO LESS THAN 8"x8". BRAKE EDGES TO
1. FOR W >= 24" AND PIPES >= 6" PROVIDE 3/4"∅ CENTER SUPPORT WITH NUT AND NUT LOCK.
NOTES:
SADDLE
COVERING PROTECTION
ROLLER SUPPORT WITH
5.4 #/FT
AND TO PLATE
ROOF
TO C-SECTION
2" PIPE WELDED
4" C-SECTION;
WELD 5" MIN.
2" MIN.
1/4" MIN
1"
OR OTHER APPROVED MATERIAL
FIREPROOF MINERAL WOOL
SCHEDULE 80 PIPE ONE
SIZE LARGER THAN RISER
SLEEVE ONE NOMINAL
THAN SLEEVE
NOMINAL SIZE LARGER
RISER CLAMP
CONTINUOUS WELD
FIREPROOF CAULK
(TOP & BOTTOM)
FLASHING POS
COUNTER
ROOF
BUILT UP
PIPE SLEEVE AROUND
ALL
SEAL
DRAWINGS
SEE ARCHITECTS
ROOF CONSTRUCTION
FLASHING POS
16 OUNCE COPPER
JOSAM #26450
SIMILAR TO
FLASHING SLEEVE
FOR SIZE
PIPING SEE PLANS
NOTES:
1. AT FIRE RATED PARTITIONS, REPLACE PACKING AND SILICONE SEALANT WITH UL LISTED FIRE
STOP SYSTEM. INSTALL IN ACCORDANCE WITH UL LISTING.
2. FIRE STOP PIPE PENETRATIONS THRU CORRIDOR WALLS ABOVE CEILINGS.
MINERAL
FIBER
PACKING
PIPE
SLEEVE 1/2" MAX (TYP)
SILICONE ACOUSTICAL
AND AIRFLOW SEALANT
NON-RATED
PARTITION
BUTT & SEAL
JOINTS
CAP INSULATION. LEAVE
NO EXPOSED INSULATION
ANYWHERE
PROVIDE VALVE
EXTENSION KIT
TO ALLOW PROPER
INSULATION COVERAGE
END CAP
ALUMINUM
CROSSBRACE
180°
CORNER
SECTION
NON-HARDENING HEAT
PASTE BETWEEN TUBING
& ALUMINUM
INSULATION
BY DIV 23
HANGING
DEVICE
SCALE:
RADIANT PANEL INSTALLATION DETAILS8
NONE
OF FREEZESTAT
REFER TO SPEC. FOR LENGTH
FZ
FZFZ
FZ
COOLING COIL
(TYP)
PREFABRICATED
EQUIPMENT
SUPPORT.
EXTERIOR DUCTWORK SUPPORT AND INSULATION1
NTS
ROOF
ANCHOR CURB TO DECK IN
ACCORDANCE WITH CURB
MANUFACTURER
INSTRUCTIONS
A
A
ROOFING INSULATION
ROOFING MEMBRANE
WOOD BLOCKING
ALUMINUM METAL CAP
S.S. BOLT
6x6x3/8 GALV. PLATES SUPPORT
8" WIDE CONTINUOUS
GALVANIZED SHEET
METAL SADDLE
RIGID EXTRUDED
BOARD WITH FOIL FACE
6" OVERLAP MIN.
VENTURECLAD
VAPOR BARRIER
JACKETING SYSTEM.
PITCH DN
SECTION A-A
UNISTRUT DUCTWORK
SUPPORT W/
ADJUSTABLE HEIGHT
FIRST VAPOR JACKET SEAM
SHALL BE A MIN. OF 12 INCHES
FROM THE SADDLE SUPPORT
(BOTH SIDES)
INSULATION PIN
AS
RECOMMENDED
BY MANUFACTURE
DUCT BASE BOARD THICKNESS
TO MATCH EXISTING
6lb DENSITY RIGID
FIBER BOARD
INSULATION
8" WIDTH GALVANIZED
SHEET METAL SADDLE
SADDLE TO BE
DE-BURRED TO AVOID
DAMAGE TO THE VAPOR
BARRIER JACKETED
ASSEMBLY
8"
DUCT PENETRATION THROUGH ROOF2
NTS
PREFABRICATED,
INSULATED CURB WITH
WOOD NAILOR (THYCURB
OR EQUAL)
COMPLETELY SEAL &
COVER JOINT WITH
OUTDOOR, UV RESISTANT
SEALANT
SS SHEETMETAL SCREW
S-SLIP CONNECTION
FLASHING
ROOF MEMBRANE
ROOF DECK INSULATION
ANCHOR CURB TO DECK
CONCRETE DECK
STEEL DECK
TACK WELD
CURB TO DECK
DUCT PENETRATION OF FULL HEIGHT PARTITIONS10
NTS
STEEL FRAME, ANGLE
1.25"X1.25"X0.125" ONLY
AT PENETRATIONS
EXPOSED TO VIEW IN
NON-MECHANICAL OR
ELECTRICAL SPACES
SILICONE
ACOUSTICAL
AND AIRFLOW
SEALANT (TYP)
FRAMED OPENING
OR SHEETMETAL
SLEEVE
SHEETMETAL SLEEVE
MINERAL
FIBER
PACKING
SILICONE
ACOUSTICAL
AND AIRFLOW
SEALANT (TYP)
NON-RATED PARTITION
1/2"
MAX
(TYP)
1/2"
MAX
(TYP)
NON-RATED PARTITION
NOTES:
1. AT FIRE RATED PARTITIONS WITHOUT FIRE DAMPER, REPLACE PACKING AND SILICONE SEALANT
WITH UL LISTED FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH UL LISTING.
2. FIRE STOP DUCT PENETRATIONS THRU RATED AND NON-RATED CORRIDOR WALLS ABOVE CEILINGS.
NOTES:
1. INSTALLATION SHALL BE IN FULL COMPLIANCE WITH MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
2
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M5.50
29313.00
11/30/18
HVAC - DETAILS
# DATE DESCRIPTION
1 11/30/18 ISSUED FOR CONSTRUCTION
2 1/7/18 ADDENDUM 02