CHEMICAL FUME HOOD DUCT CONNECTION DETAIL3
NTS
CHILLED BEAM DUCT CONNECTION DETAIL6
NTS
SCALE:
SCALE:
SCALE:
FULL RADIUS
ELBOW
30° TRANSITION
(MAXIMUM)
DUCT SAME SIZE AS FUME
HOOD OUTLET CONNECTION
FUME HOOD
FLOOR
REFER TO DUCT SIZE
INDICATED ON DRAWINGS
FASTEN AND SEAL PER MANUFACTURER'S
APPROVED INSTALLATION INSTRUCTIONS
NOTES:
1. COORDINATE LOCATION IN PLAN AND ELEVATION W/
ARCHITECTURAL DWGS.
2. COORDINATE SIZE AND TRANSITION REQUIRED FOR
CONNECTION TO SNORKEL.
EXHAUST DUCT TO CONSTANT
VOLUME EXHAUST VALVE;
MULTIPLE SNORKEL CONNECTIONS
MAY CONNECT TO SINGLE
EXHAUST VALVE
HATCHED AREAS PROVIDED
UNDER OTHER SECTIONS OF
THE WORK. REFER TO
ARCHITECTURAL DRAWINGS.
STRUCTURE
ABOVE
CEILING
NTS
7 WALL MOUNTED CANOPY HOOD
REMOVABLE 18 GA.
SS FACE PANEL
FACE OF WALL
DUCT CONNECTION
(SEE EACH HOOD
FOR SIZE AND
NUMBER OF
CONNECTIONS)
3/8"Ø ROD & 2" WIDE
12 GA. SS CLIP SPOT
WELD CLIP TO HOOD
(TYP)"W"A
36"
O.C.
(MAX.)
"L"
B
CANOPY HOOD PLAN VIEW
NOTES:
1. SHEET METAL SHALL BE ALL WELDED TYPE 316L STAINLESS STEEL
CONSTRUCTION.
2. ALL EXPOSED TO VIEW SURFACES SHALL HAVE A BRUSH FINISH.
GRIND AND POLISH ALL JOINTS.
3. ALL RODS, NUTS & BOLTS SHALL BE 304L STAINLESS STEEL.
CANOPY HOOD SCHEDULE
ROOM NO.CFM QTY.SIZE ("L"
x "W")
229 530 1 3'x2' X
* MOUNTING HEIGHT IS DISTANCE TO THE BOTTOM OF THE CANOPY
2" WIDE 12 GA.
SS CLIP 24" O.C.
SPOT WELD CLIP
TO HOOD (TYP)
REMOVABLE 18 GA.
SS FACE PANEL (TYP)
1/4" NUT &
BOLT 24"
O.C. (TYP)
DUCT CONNECTION
(SEE EACH HOOD
FOR SIZE AND
NUMBER OF
CONNECTIONS)
2"X2" 12 GA. SS
ANGLE FASTEN TO
CEILING (TYP)
1/4" NUT &
BOLT (TYP)3/4"X3/4" 12 GA.
ANGLE SPOT
WELD TO BAFFLE
(TYP)
18 GA. SS BAFFLE
%%UA-A
"L"
3"
1.5"
3"6"
3"
6"
2" WIDE 12 GA. SS
CLIP SPOT WELD
CLIP TO HOOD (TYP)
3/8"Ø ROD W/
HEX NUTS (TYP)
2" WIDE 12 GA.
SS CLIP FASTEN
TO STRUCTURE
(TYP)CEILING
STRUCTURE
18 GA. SS HOOD
20 DEGREES
2" WIDE 12 GA.
SS CLIP 24" O.C.
SPOT WELD CLIP
TO HOOD
2" WIDE 12 GA.
SS CLIP SPOT
WELD CLIP TO
HOOD
REMOVABLE 18 GA.
SS FACE PANEL
1/4" NUT &
BOLT 24" O.C.
2"X2" 12 GA. SS
ANGLE FASTEN TO
CEILING
2" WIDE 12 GA. SS CLIP FASTEN TO STRUCTURE
3/8"Ø ROD W/HEX NUTS
STRUCTURE
CEILING
DUCT CONNECTION
(SEE EACH HOOD
FOR SIZE AND
NUMBER OF
CONNECTIONS)
18 GA. SS HOOD
MAINTAIN BARRIER
SEAL FOR HOODS
WITHIN BSL-3 LABS
18 GA. SS BAFFLE
1/4" NUT
& BOLT
"W"
%%UB-B
20°
18"
(MAX)
3"
1.5"
A
B
MOUNTING
HEIGHT
DUCTED FAN COIL CONNECTION DETAIL2
NTS
VIBRATION
ISOLATION SEE
SPECS
FLEX CONN
REFER TO WATER COIL
DETAIL FOR PIPING AND
DRAIN REQUIREMENTS
SUPPORT FROM STRUCTURE NOTE: INSULATE ALL PIPING
COMPONENTS INCLUDING
CONTROL VALVE,
STRAINERS, VALVES, ETC.
ACOUSTICAL LINING
DUCTED
RETURN AIR
FLEX
CONNECTION
(TYP)
FILTER (MODIFY FRAME
FOR SIDE OR BOTTOM PULL
IF NECESSARY TO ALLOW
COORDINATION OF OTHER
CEILING SERVICES WITH
FILTER REMOVAL)
BASEMENT FCU SHALL HAVE SECONDARY
DRAIN PAN AND PIPED DRAIN CONNECTION.
EXTEND THIS DRAIN TO ENSURE CONTROL
VALVE IS ALSO ABOVE DRAIN PAN. ALL
OTHER FCUS WILL BE SENSIBLE ONLY AND
SHALL NOT HAVE DRAIN CONNECTIONS
LOUVER CONNECTION4
NTS
CAULK ALL AROUND
REFER TO
ARCHITECT'S PLANS
AND SPECS FOR
LOUVER DETAILS
1/2" BIRDSCREEN
PLENUM INSULATE ALL EXPOSED
PARTS W/ 2" RIGID BOARD
INSULATION (ALSO INSULATE
UNUSED LOUVER AREA)
ACCESS DOOR HALF HEIGHT
OF DUCT, 12" X 12" MIN
(UNLESS SHOWN OTHERWISE
ON PLANS)
DN
SEE NOTE
"D"
NOTE:
WHEN "D" IS OVER 24" PROVIDE 3/4" DRAIN IN CENTER OF PLENUM
AND AT 5'-0" CENTERS WHERE DEPTH INTO PAPER IS GREATER
THAN 5'-0". LOCATE 6" FROM LOUVER WITH TRAP
SEAL AND CAULK
ALL AROUND
PITCH TO DRAIN WATER OUTSIDE
SOLDER BOTTOM JOINT
AND UP 12" ALL AROUND
EXTERNALLY MOUNTED
U.L. RATED ACTUATOR
HEAT ACTUATED
RELEASE DEVICE
S
SMOKE DETECTOR
60" MAX
SMOKE AND SMOKE/FIRE DAMPER12
NTS
NOTES:
1. ANY CLEARANCE BETWEEN FIRE-RATED WALL OR SMOKE PARTITION AND DAMPER SLEEVE OR DAMPER SHALL
BE FILLED WITH FIRE-RESISTANT PACKING ON ALL SIDES TO MAINTAIN FIRE RATING.
2. WHEN DUCTWORK IS INSULATED OR LINED, PROVIDE INSULATED ACCESS DOOR.
3. ACCESS DOOR SHALL BE 12" X 12" OR LARGER IF REQUIRED FOR HEAT ACTUATED RELEASE DEVICE
REPLACEMENT.
4. INSTALLATION SHOWN AS AN EXAMPLE. SPECIFIC INSTALLATION SHALL CONFORM WITH MANUFACTURER'S, UL
APPROVED INSTRUCTIONS.
5. DUCT MOUNTED SMOKE DETECTOR SHALL BE PROVIDED BY DIVISION 28, INSTALLED BY DIVISION 23 AND WIRED
TO FIRE ALARM SYSTEM UNDER DIVISION 28.
6. INSTALLATION SHOWN AS AN EXAMPLE. SPECIFIC INSTALLATION SHALL CONFORM WITH MANUFACTURER, UL
APPROVED INSTRUCTIONS.
7. PROVIDE REMOTE DAMPER TEST SWITCH AND ANNUNCIATION FOR EH&S TESTING. THESE SHALL BE LOCATED IN
CORRIDORS INSTEAD OF LABS WHERE POSSIBLE.
FIRE-RATED WALL OR SMOKE
PARTITION (TYPE AND SIZE VARIES).
SUPPLY AIR FLOW
DUCT
ACCESS
DOOR
(EITHER SIDE
OR BOTTOM)
CHEMICAL STORAGE
CABINET
EXHAUST DUCT
CONNECTION
CONNECT EXHAUST
DUCT TO CHEMICAL
STORAGE CABINET
CONNECTION. PROVIDE
TRANSITION TO MATCH
CABINET CONNECTION
SIZE. SEAL
CONNECTION TO
CABINET.
CEILING
4"Ø WELDED SS AUXILIARY
EXHAUST DUCT. EXTEND DOWN
TO 9FT AFF AND TERMINATE
WITH WIRE MESH SCREEN.
COPPER PIPE SIZED TO MATCH
VACUUM PUMP DISCHARGE SIZE.
CONNECT ONE END TO VACUUM PUMP.
TERMINATE OTHER END NEAR
EXHAUST DUCT SO THE DISCHARGE IS
2" BELOW THE WIRE MESH SCREEN.
COORDINATE LOCATION WITH OWNER.
LABORATORY
EXHAUST BRANCH
DUCT
SUPPORT FROM STRUCTURE INLET DUCT CONNECTION
FLEX DUCT
NOTES:
1. PROVIDE NYLON TY-WRAP TOOL OR REUSABLE SS DRAW BAND.
2. FLEX DUCT SHALL NOT HAVE MORE THAN 0.5 INCH SAG PER FOOT. LENGTH OF FLEX DUCT SHALL
NOT EXCEED 5 FEET. MAXIMUM SUPPORT SPACING SHALL BE 3 FEET. FLEX DUCT SHALL NOT BE
COMPRESSED PER SMACNA DUCT CONSTRUCTION MANUAL.
3. SUPPORT QUANTITIES AND DETAILS SHALL MEET MANUFACTURER REQUIREMENTS.
MAXIMUM (1) 90
DEGREE BEND IN
FLEX DUCT. CENTER
LINE RADIUS OF
BEND SHALL NOT BE
LESS THAN (1) TIMES
THE DUCT DIAMETER
PER SMACNA DUCT
CONSTRUCTION
MANUAL.
DUCT HANGER SUPPORT9
NTS
NOTES:
1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORE
THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.
2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.
3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA.
UNISTRUT
OR ANGLE
IRON
HANGER
STRAP
THREADED
HANGER ROD
GALV. HANGER
SEE NOTE 3MAX. 60"OVER 60"
1"
TYPICAL DUCT INSULATION & SUPPORTS NEAR VOLUME DAMPERS10
NTS
PROVIDE
LOCKING
QUADRANT ARM
STANDOFF
BUTT ENDS
& SEAL
FOR HANGING DUCT:
TRAPEZE DUCT OR STRAP
HANGER AROUND DUCT
COMPLETELY. DO NOT
USE ANY SCREWS,
BECAUSE THEY
INTERFERE WITH DAMPER
BLADE(S).
PROVIDE EXTRA
LENGTH TO AVOID
"PINCHING" OF
INSULATION AT
CORNERS.
LABORATORY SNORKEL ARM EXHAUST CONNECTION1
NTS
LABORATORY AUXILIARY EXHAUST HOSE CONNECTION5
NTS
VACUUM PUMP (POS)
VENTILATED CABINET EXHAUST CONNECTION8
NTS
ACCESS
DOOR
(EITHER SIDE
OR BOTTOM)
FIRE DAMPER PENETRATION11
NTS
NOTES:
1. DAMPER BLADES SHALL BE OUT OF AIRSTREAM TYPE "3A,3B,7 OR 8" (SEE SMACNA FIRE DAMPER AND HEAT STOP
GUIDE - 2ND EDITION PAGE 9 OR NEWER VERSION IF APPLICABLE) WHEN OPEN 100% FREE AREA IS REQUIRED.
WHEN DUCT DIMENSIONS REQUIRE MULTIPLE DAMPER SECTIONS, TYPE "2" MAY BE USED.
2. PROVIDE SPRING LOADED CLOSURE FOR ALL FIRE DAMPERS.
3. WHEN DUCTWORK IS INSULATED OR LINED, PROVIDE INSULATED ACCESS DOOR.
4. ACCESS DOOR SHALL BE 12" X 12" OR LARGER IF REQUIRED FOR FUSIBLE LINK REPLACEMENT.
5. TYPE "1" FIRE DAMPERS (BLADES IN AIR STREAM) MAY BE SUBSTITUTED FOR TYPE "3A OR 3B" WHERE VELOCITIES
ARE UNDER 500 FPM IN LOW PRESSURE DUCT SYSTEMS ONLY.
6. INSTALLATION SHOWN AS AN EXAMPLE. SPECIFIC INSTALLATION SHALL CONFORM WITH MANUFACTURER, UL
APPROVED INSTRUCTIONS.
FIRE-RATED WALL OR
PARTITION (TYPE AND
SIZE VARIES).
FLOW
AIR
DUCT
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M5.40
29313.00
11/30/18
HVAC - DETAILS