NOTES:
DRAIN VALVES AT LOW POINTS OF ALL
COIL HEADERS SAME SIZE AS
COIL-OUTLET SIZES BUT NOT
LESS THAN 3/8".
AIR
FLOW
REDUCE AS
NEEDED (TYP)
WATER
COIL
SUPPLY
6" DIRT POCKET
FULL SIZE OF HEADER
DRAIN
PAN(S)
PIPING
(COOLING
ONLY)
1&1/4 0-14
1&1/2 14-21
2 21-40
2&1/2 40-65
3 65-115
4 115-240
RUNOUT SIZING
SIZE (IN) FLOW (GPM)
RETURN
SEE NOTE 4
CO
CO
TRAP SEAL
REFER TO DRAINPAN WATER SEAL DETAIL (TYP)
TO
ADD'L
COILS
W/HB
DOV
RETURN
SUPPLY
NOTE 1FZ
NOTES:
1. FOR WATER COILS ONLY (NOT
GLYCOL) THAT ARE SUBJECT TO
FREEZING, PROVIDE IMMERSION
AQUASTAT WELL. FREEZESTAT, FZ
(AN AQUASTAT) SHALL INITIATE AN
ALARM WHEN IT SENSES BELOW
38°F. (CIRCUITING IN SOME COILS
CAN ALLOW WATER TO FREEZE IN
COIL EVEN THOUGH THE LEAVING
AIR TEMPERATURE IS ABOVE
FREEZING.)
2. THIS DETAIL APPLIES TO HOT
WATER REHEAT COILS AND FAN
COIL UNITS.
PT
PT
DOV W/HB RELIEF
F & T
DRAIN
TO INDIRECT
LINE-SIZE
6" DIRT POCKET
18" MIN
HWR
HWS
STEAM
SUPPLY
MAIN
COND
RETURN
MAIN
TO
INDIRECT
DRAIN
DOV
DOV
1. PROVIDE SIMILAR PIPING FOR 3 OR MORE COILS HIGH.
2. LOCATE PIPE UNIONS (OR FLANGED BODY) AND ARRANGE PIPING TO
FACILITATE COIL REMOVAL. PROVIDE REDUCERS AS REQUIRED.
3. PROVIDE SIMILAR PIPING ARRANGEMENTS ON EACH SIDE FOR
TWO-SECTION-WIDE COIL ASSEMBLY.
4. FOR SUPPLY AND RETURN PIPES 2" AND SMALLER, USE BALL VALVES WITH
UNIONS FOR ISOLATION.
5. FOR SUPPLY AND RETURN PIPES LARGER THAN 2" USE BUTTERFLY VALVES
WITH FLANGES FOR ISOLATION.
6. REFER TO SPECIFICATIONS FOR DRAIN PAN REQUIREMENTS.
7. PROVIDE PROPER RANGE PRESSURE GAUGE OF FULL SCALE = 150% OF
MAX PRESSURE OF PUMP. MANIFOLD PIPING SHALL BE 1/2".
8. FOR WATER COILS ONLY (NOT GLYCOL) THAT ARE SUBJECT TO FREEZING.
PROVIDE IMMERSION AQUASTAT WELL. FREEZESTAT, FZ (AN AQUASTAT)
SHALL INITIATE AN ALARM WHEN IT SENSES BELOW 38°F. (CIRCUITING IN
SOME COILS CAN ALLOW WATER TO FREEZE IN COIL EVEN THOUGH THE
LEAVING AIR TEMPERATURE IS ABOVE FREEZING.
STRAINER
BLOWDOWN WITH
BRASS HOSE
CONNECTION, CAP
WITH CHAIN.
THERMOWELL
PTPT
PT PT
PT
MAV
MAV
MAV
NOTE 6
DOV
PT
PT
PT
DOV
MAV
(TYP)
SEE NOTE 5
NOTES:
DRAIN VALVES AT LOW POINTS OF ALL
COIL HEADERS SAME SIZE AS
COIL-OUTLET SIZES BUT NOT
LESS THAN 3/8".
AIR
FLOW
REDUCE AS
NEEDED (TYP)
WATER
COIL
SUPPLY
6" DIRT POCKET
FULL SIZE OF HEADER
1&1/4 0-14
1&1/2 14-21
2 21-40
2&1/2 40-65
3 65-115
4 115-240
RUNOUT SIZING
SIZE (IN) FLOW (GPM)
RETURN
SEE NOTE 4
TO
ADD'L
COILS
DOV
DOV
1. PROVIDE SIMILAR PIPING FOR 3 OR MORE COILS HIGH.
2. LOCATE PIPE UNIONS (OR FLANGED BODY) AND ARRANGE PIPING TO
FACILITATE COIL REMOVAL. PROVIDE REDUCERS AS REQUIRED.
3. PROVIDE SIMILAR PIPING ARRANGEMENTS ON EACH SIDE FOR
TWO-SECTION-WIDE COIL ASSEMBLY.
4. FOR SUPPLY AND RETURN PIPES 2" AND SMALLER, USE BALL VALVES WITH
UNIONS FOR ISOLATION.
5. FOR SUPPLY AND RETURN PIPES LARGER THEN 2" USE BUTTERFLY VALVES
WITH FLANGES FOR ISOLATION.
6. PROVIDE PROPER RANGE PRESSURE GAUGE OF FULL SCALE = 150% OF
MAX PRESSURE OF PUMP. MANIFOLD PIPING SHALL BE 1/2".
MAV
MAV
MAV
NOTE 6
DOV
PT
PT
PT
DOV
MAV
(TYP)
SEE NOTE 5
NOTES:
DRAIN VALVES AT LOW POINTS OF ALL
COIL HEADERS SAME SIZE AS
COIL-OUTLET SIZES BUT NOT
LESS THAN 3/8".
AIR
FLOW
REDUCE AS
NEEDED (TYP)
WATER
COIL
SUPPLY
6" DIRT POCKET
FULL SIZE OF HEADER
1&1/4 0-14
1&1/2 14-21
2 21-40
2&1/2 40-65
3 65-115
4 115-240
RUNOUT SIZING
SIZE (IN) FLOW (GPM)
RETURN
SEE NOTE 4
TO
ADD'L
COILS
DOV
DOV
1. PROVIDE SIMILAR PIPING FOR 3 OR MORE COILS HIGH.
2. LOCATE PIPE UNIONS (OR FLANGED BODY) AND ARRANGE PIPING TO
FACILITATE COIL REMOVAL. PROVIDE REDUCERS AS REQUIRED.
3. PROVIDE SIMILAR PIPING ARRANGEMENTS ON EACH SIDE FOR
TWO-SECTION-WIDE COIL ASSEMBLY.
4. FOR SUPPLY AND RETURN PIPES 2" AND SMALLER, USE BALL VALVES WITH
UNIONS FOR ISOLATION.
5. FOR SUPPLY AND RETURN PIPES LARGER THEN 2" USE BUTTERFLY VALVES
WITH FLANGES FOR ISOLATION.
6. PROVIDE PROPER RANGE PRESSURE GAUGE OF FULL SCALE = 150% OF
MAX PRESSURE OF PUMP. MANIFOLD PIPING SHALL BE 1/2".
CO
(TYP)
DRAIN
NEAREST
TO
EXTEND
DRAIN LINES
INDEPENDENT
CO
CO
TRAP SEAL
REFER TO DRAINPAN WATER SEAL DETAIL (TYP)
AHU-A CHILLED WATER COIL5
NTS
STEAM TO LIQUID HEAT EXCHANGER; STEAM FLOW; 15 PSIG OR LESS9
NONE
GLYCOL CHARGING7
NTS
STEAM PIPING DRIP TRAP ASSEMBLY13
NTS
MAKE-UP WATER, DIAPHRAGM EXPANSION TANK & AIR SEPARATOR FOR CLOSED LOOP
CHILLED WATER SYSTEM (EQUAL TO OR LESS THAN 4" SUPPLY)8
NTS
AHU-A GLYCOL PREHEAT COIL4
NTS
EXHAUST GLYCOL ENERGY RECOVERY COIL3
NTS
MANUAL AIR VENT ASSEMBLY12
NTS
CHEMICAL FEED (SHOT FEEDER)11
NTS
WATER COIL W/ 2-WAY CONTROL VALVE1
NTS
RADIANT PANEL PIPING DETAIL2
NTS
CHILLED BEAM PIPING DETAIL6
NTS
INLINE PUMP PIPING (EACH PUMP)10
NTS
SCALE:
SCALE:
SCALE:
SCALE:
PT
PT
PT
CHWR CHWS
PT
AAV
COMPRESSION TANK
DIAPHRAGM EXPANSION/
FLOOR MOUNTED
PUMP SUCTION
TO CHILLED WATER
12"
VALVES FOR 2" PIPES AND SMALLER (SEE SPECS).
AND LARGER; FULL PORT LOCKING HANDLE BALL
3. PROVIDE BUTTERFLY VALVES FOR 2-1/2" PIPES
PREVENT GRAVITY HEATING OF TANK.
2. PROVIDE ANTI-THERMOSYPHON LOOP TO
BOTTOM CONNECTION NOT PERMITTED.
DEBRIS FROM ENTERING PIPE TO TANK. TOP OR
1. CONNECT TO SIDE OF MAIN TO PREVENT AIR OR
NOTES:
SEE NOTE 1
SEE NOTE 2
FLOOR
MAKE-UP SIZE (d)
TOTAL SYSTEM
PUMP FLOW (GPM)
UP TO 200
201-500
501-1,200
1,201-3,000
3,001-5,000
5,001-12,000
d
(INCHES)
1/2
3/4
1
1 1/4
1 1/2
2
3
5
10
20
30
60
PRV MIN.
FLOW (GPM)
RETURN
WITH HOSE BIBB
DRAIN OUT VALVE
(TYP)
SEE NOTE 3
WATER SYSTEM
FROM CHILLED
AAV (LARGE CAPACITY)
AIR SEPARATOR
3/8"
RELIEF VALVE (TYP.)
TO 6" AFF
TO 6" AFF
OPERATING PRESSURE.
1. ALL PIPING & EQUIPMENT SHALL BE RATED FOR INSTALLED
(55 GALLON
MINIMUM)
FLOW METER.
DISPLACEMENT
OUT. POSITIVE
OR DIGITAL READ-
RESETTABLE DIAL
FM
HB
MAKE-UP
COLD WATER
PUMP SUCTION
TO MAIN SYSTEM
RETURN
MAIN SYSTEM
PREVENTER
BACK-FLOW
PREMIX DRUM
GLYCOL & WATER
FLOOR
NOTES:
3/4"
3. SUBSTITUTE BUTTERFLY VALVES FOR BALL VALVES FOR PIPING GREATER THAN 2".
INLINE PUMP
HAVE SPRING-ISOLATOR SUPPORTS
PUMP & PIPE WITHIN 20' SHALL
2. FOR PUMPS OVER 1 HP:
1. VALVES SHALL BE SAME SIZE AS PIPE, REDUCE AS REQUIRED TO PUMP CONNECTIONS.
NOTES:6" MINPIPE RISE
STEAM TRAP APPLICATIONS
APPLICATION TRAP TYPE
STEAM LESS THAN OR EQUAL TO 15 PSIG F&T
1" DRAIN W/
HOSE CONNECT
WELDED CAP W/
DRAIN
CONNECTION
INSTALL STRAINER WITH
BLOW DOWN ON SIDE
STEAM
PIPNG
DIRT LEG-FULL
LINE SIZE NOT
LARGER THAN 6"
CONDENSATE
RETURN
1" DRAIN W/
HOSE CONNECT
4 PIPE DIAMETERS (WITH 18"MAX)
USE TFE TAPE ON ALL THREADED JOINTS.
NOTE:
HIGHEST POINT IN SYSTEM
REDUCER
1/4" BRASS NIPPLE
1/4" GAGE COCK
1/4" TYPE "L" COPPER TUBE
SHUNT
WITH MEMORY STOP
BALANCING VALVE
SHUT OFF/
RETURN
SUPPLY
NC
5 GALLON SHOT
FEEDER TANK OR
OTHER SIZE AS
SPECIFIED ASME
RATED
TO CHILLED OR
HOT WATER RETURN
3/4"
FROM CHILLED
OR HOT WATER
SUPPLY
3/4"HBNOTES:
1. BYPASS PIPING AROUND F&T TRAP LEG SHALL BE SAME SIZE AS TRAP.
2. PROVIDE PIPE UNIONS, FLANGES, AND ARRANGE WATER PIPING TO FACILITATE TUBE
BUNDLE REMOVAL WITH MINIMUM DISTURBANCE TO PIPING.
3. VACUUM BREAKERS ARE REQUIRED ON ALL SYSTEMS.
4. FOR LIQUID PIPE SIZE 2" AND UNDER, REPLACE BUTTERFLY VALVES WITH BALL
VALVES,
5. COORDINATE FINAL LOCATION OF CONNECTIONS WITH APPROVED EQUIPMENT
SUBMITTALS (E.G. EXTENDED SHELL HEAT EXCHANGER STEAM AND CONDENSATE
CONNECTIONS ON OPPOSITE ENDS FROM THOSE SHOWN)
NOTES:
TYPICAL COMPONENTS
REQUIRED FOR EACH
CHILLED BEAM IN ZONE
PROVIDE ONE CONTROL
VALVE PER CHILLED BEAM
ZONE
1. FOR TWO-PIPE CHILLED BEAMS PROVIDE ONLY CHILLED WATER PIPING SHOWN. REFER TO PLANS
FOR REQUIRED CONNECTIONS IN EACH ZONE.
2. RELOCATE MANUAL AIR VENT TO COIL IF CONNECTION IS PROVIDED BY THE MANUFACTURER.
3. REMOVE STRAINER BASKETS AFTER INITIAL STARTUP AND SYSTEM FLUSH IS COMPLETE.
4. WHERE COIL CONNECTIONS ARE NOT IN SAME VERTICAL PLANE, SUPPLY SHALL BE THROUGH
THE BOTTOM CONNECTION.
CHILLED BEAM
12" INSULATED SS
BRAIDED HOSE
CONNECTION
PT
PHWR
PHWS
TYPICAL COMPONENTS
REQUIRED FOR EACH
RADIANT PANEL IN ZONE
PROVIDE ONE CONTROL
VALVE PER ZONE
RADIANT PANEL
PT
TO ADDITIONAL RADIANT
PANELS IN ZONE
TO ADDITIONAL
BEAMS IN ZONE
PROVIDE ISOLATION
VALVE AND CAP FOR
MANUAL FILL AND 55
GALLON DRUM TO
RECEIVE RELIEF VALVE
DISCHARGE.
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M5.30
29313.00
11/30/18
HVAC - DETAILS
# DATE DESCRIPTION
1 11/30/18 ISSUED FOR CONSTRUCTION
DocuSign Envelope ID: D6CBE973-BBA9-4BE0-861E-C2F6DD72B539
12/10/2018