1 NO. 1 OF 3NO. 2 OF 3NO. 3 OF 3NO. 2 OF 2NO. 1 OF 2NO. 1 OF 1OUTSIDE RADIUS IN INCHESINSIDE RADIUS OF ELBOW IN INCHESNUMBER OF SPLITTERS
SCALE:
SCALE:
SCALE:
SCALE:
NO & SPACING OF DUCT SPLITTER VANES2
NTS
SCALE:
SCALE:
SCALE:
h = DUCT HEIGHT
w = DUCT WIDTH
h
w
NO. OF VANES
EQUIVALENT DIAMETER = (w+h)/2
1
2
3
3
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
WITHIN 2 EQUIV. DIA.:
WHEN 2 ELBOWS ARE
NO. OF VANES
DEPICTED HERE:
EXAMPLE AT LEFT IS
OF 3 VANES.
NO. 2 VANE OF A TOTAL
"NO. 2 OF 3" =
OF 3 VANES.
NO. 1 VANE OF A TOTAL
"NO. 1 OF 3" =
TERMINOLOGY:
= INSIDE RADIUS
= CENTERLINE RADIUS
R
r
rR
r/w = 0.5 IS A SQUARE THROAT ELBOW!
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
3
2
1
0
FOR 1 ELBOW:
r/w >= 1.50
1.5 > r/w >= 0.70
0.7 > r/w >= 0.60
0.6 > r/w >= 0.55
HOWEVER, MINIMUM INSIDE RADIUS R SHOULD BE 2".
NOTE:
r/w RATIO:
RADIUS ELBOW AND SPLITTER VANE REQUIREMENTS
R=20"
R=2"
R=4-1/4"
R=9-1/4"
D = DUCT DIAMETER
= INSIDE BEND RADIUS
= CENTERLINE BEND RADIUS
R
rRr
D
D
D
SUPPLY OR EXHAUST VENTURI VALVE INSTALLATION DETAIL8
NTS
FLANGE CONNECTION FOR
EASY REMOVAL. SLIP
CONNECTION ALLOWED IF
DUCTWORK IS TRANSLATABLE
TO ALLOW FOR REMOVAL
DUCT
SS SHEETMETAL SCREWS
(4 PER CONNECTION)
SUPPORT VALVE
INDEPENDENTLY
SEAL AIR
TIGHT
CLEANOUT &
INSPECTION
TEE SECTION:
REFER TO
DETAIL
4" MAX
AIR
EXHAUST
VALVE
SEAL AIR
TIGHT
(REFER TO
SPECS)
AIR FLOW
NOTES:
1. WHERE DUCT SIZES ARE NOT INDICATED ON PLANS, SELECT SIZE FROM TABLE BASED ON THE CFM
REQUIRED; SIZES BASED ON MAXIMUM STATIC PRESSURE DROP OF 0.05 INCHES PER 100 FEET OF DUCT.
EQUIVALENT RECTANGULAR DUCT SIZE (IN)
DUCT ARRANGEMENT
60
75
110
160
220
300
380
500
600
700
850
1000
1400
1800
2100
2500
3000 26
24
22
20
18
16
16
14
14
14
12
10
10
8
8
6
6 4x8
4x8
4x12
6x10
6x12
6x16
6x18
6x24
8x20
8x22
8x26
8x30
10x30
10x38
12x34
12x42
12x50 14x42
14x36
14x28
12x30
12x24
10x22
10x20
10x18
10x16
8x16
8x14
8x12
8x10
8x8
6x8
6x6
18x32
18x26
18x22
16x22
16x18
14x16
14x14
16x36
16x30
16x24
14x26
14x20
12x18
12x16
12x14
12x12
10x14
10x10
10x10
AIR INLET WITH
FLOW SENSOR
(TYP)
NOTES:
1. CONNECTIONS APPLY TO ALL TERMINAL BOXES INCLUDING THOSE WITHOUT REHEAT COILS OR WITHOUT SOUND ATTENUATORS. REFER
TO PLANS AND SCHEDULES FOR REHEAT COIL AND SOUND ATTENUATOR REQUIREMENTS.
2. PROVIDE RECTANGULAR OR ROUND TO OVAL TRANSITIONS WHEN BOX INLET IS OVAL.
3. FOR CONTROLLERS WITH INSULATED ELECTRICAL CONNECTORS (NO EXPOSED LIVE PARTS), ACCESS DEPTH SHALL BE 24 INCHES
MINIMUM. FOR CONTROLLERS WITH EXPOSED CONNECTORS/TERMINAL STRIPS, ACCESS DEPTH SHALL BE 36 INCHES MINIMUM PER THE
NEC. WIDTH OF ACCESS ZONE SHALL MATCH WIDTH OF CONTROLLER PANEL COVER OR 24 INCH MINIMUM.
CONNECTION TO MAIN DUCT AS
INDICATED IN ABOVE DETAIL
RECTANGULAR MAIN SUPPLY OR
BRANCH: TAPERED 45° ANGLE
CONNECTION, L = MAX 0.25 x W OR 4"
MINIMUM; FOR ROUND MAIN SUPPLY
OR BRANCH: CONICAL OR
BELLMOUTH TAKEOFF (TYPICAL)
TERMINAL
BOX INLET
SIZE
(INCHES)
RUNOUT DUCT
RUNOUT DUCT SIZE -
BOX TO MAIN DISTANCE
LESS THAN 10 FEET
ROUND DIAMETER
(INCHES)
RUNOUT DUCT
RUNOUT DUCT SIZE - BOX TO MAIN
DISTANCE GREATER THAN 10 FEET
(INCHES)
RUNOUT DUCT SIZING SCHEDULE UNLESS LARGER SIZE INDICATED ON PLANS
NTS
5 SUPPLY AIR TERMINAL BOX AND VALVE - DUCT CONNECTIONS
15 DEG MAX DUCT
TRANSITION (TYP)
ACTUATOR AND
CONTROLLER
(TYPICAL)
SUPPLY AIR MAIN
SERVICE SPACE. DO NOT
BLOCK WITH PIPING,
CONDUIT, EQUIPMENT OR
WALLS (TYPICAL) - SEE
NOTES FOR CLEARANCES
REQUIRED.
SUPPLY AIR
TERMINAL
BOX OR VALVE
SUPPLY AIR
TERMINAL
BOX OR VALVE
REHEAT COIL INLET ACCESS DOOR IN
BOTTOM OF DUCT. TERMINAL BOX
MANUFACTURER OPTIONAL ACCESS
DOOR IN HOUSING IS ACCEPTABLE IN
LIEU OF DUCT ACCESS DOOR (TYP)
FOR REHEAT COILS MOUNTED
IMMEDIATELY ADJACENT TO BOX
(TYPICAL).
PROVIDE AIRFLOW SENSOR
AT AIR INLET (TYP)
NOTES:
1. DUCT AND SOUND ATTENUATOR SIZE SHALL BE AS INDICATED ON DRAWINGS AND SCHEDULES. TRANSITION AFTER SATT TO SIZE
MATCHING BOX INLET SIZE.
2. DUCT CONNECTION REQUIREMENTS INDICATED APPLY TO ALL TERMINAL BOXES INCLUDING THOSE WITHOUT SOUND ATTENUATORS.
REFER TO PLANS AND SCHEDULES FOR SOUND ATTENUATOR REQUIREMENTS.
3. PROVIDE RECTANGULAR OR ROUND TO OVAL TRANSITIONS WHEN BOX INLET IS OVAL.
4. FOR CONTROLLERS WITH INSULATED ELECTRICAL CONNECTORS (NO EXPOSED LIVE PARTS), ACCESS DEPTH SHALL BE 24 INCHES
MINIMUM. FOR CONTROLLERS WITH EXPOSED CONNECTORS/TERMINAL STRIPS, ACCESS DEPTH SHALL BE 36 INCHES MINIMUM PER
THE NEC. WIDTH OF ACCESS ZONE SHALL MATCH WIDTH OF CONTROLLER PANEL COVER OR 24 INCH MINIMUM.
RECTANGULAR MAIN SUPPLY OR
BRANCH: TAPERED 45° ANGLE
CONNECTION, L = MAX 0.25 x W OR 4"
MINIMUM; FOR ROUND MAIN SUPPLY
OR BRANCH: CONICAL OR
BELLMOUTH TAKEOFF (TYPICAL)
INLET DUCT
(TYP)
15 DEG MAX DUCT
TRANSITION (TYP)
ACTUATOR AND
CONTROLLER
(TYPICAL)
EXHAUST
OR
RETURN
AIR MAIN
EXHAUST OR
RETURN AIR
TERMINAL
BOX OR
VALVE
EXHAUST OR
RETURN AIR
TERMINAL
BOX OR
VALVE
EXHAUST OR RETURN
FROM SPACE OR
EQUIPMENT
EXHAUST OR RETURN
FROM SPACE OR
EQUIPMENT
SERVICE SPACE. DO NOT
BLOCK WITH PIPING,
CONDUIT, EQUIPMENT OR
WALLS (TYPICAL) - SEE
NOTES FOR CLEARANCES
REQUIRED.
WxH FOR RECT
CONCENTRIC TRANSITIONS (TYPICAL)
1.5 D
3D
TRANSITION (TYP)
SOUND ATTENUATOR
SUPPLY TO SPACESUPPLY TO SPACESOUND ATTENUATOR
REHEAT COIL (TYP)
R=D
1.5 D
WxH ROUND DIAMETER
4
5
6
8
10
12
14
16
18
4
5
6
8
10
12
14
16
18
6x6
8x6
8x8
10X10
14X10
14X12
16X14
18X16
20X18 20
18
16
14
12
10
8
7
6
L
TRANSITION (TYP)
1.5 D
R=D
1.5 D
SOUND ATTENUATORTRANSITION
L
SOUND ATTENUATOR
3D
D
DISCHARGE
DUCT WxH
FOR RECT
DISCHARGE
DUCT WxH
FOR RECTD
AIRFLOW MAX
(CFM)ROUND DUCT
SIZE (IN)
RECTANGULAR DUCT
WHEN HEIGHT DOES NOT ALLOW FLEX CONN,
HARD-DUCT BUT BE SURE BRANCH IS 4" WIDER
THAN COLLAR TO ALLOW ALIGNMENT OF
TERMINAL WITHIN GRID WITHOUT FISHMOUTHING.
FLEX CONN. REFER
TO SPECS FOR
INSULATED TYPE
DIFFUSER
REGISTER (TYP.)MAX. OFFSET = D/8"
NOTES:
1. DETAIL ALLOWS DUCTWORK TO BE INSTALLED BEFORE CEILING GRID THEN ALLOWS DIFFUSERS AND
REGISTERS TO BE POSITIONED INTO GRID.
2. PROVIDE INSULATED TRANSITION ROUND TO SQUARE INLET DIFFUSERS.
7. SECURE FLEXIBLE DUCT TO METAL DUCT WITH (2) STAINLESS STEEL CLAMPS OR NYLON TY-WRAPS TO
INDIVIDUALLY SECURE FLEXIBLE DUCT INNER SLEEVE AND OUTER SLEEVE. WHEN INSTALLED ON
INSULATED SYSTEM SEAL INSULATION JOINT WITH VAPOR BARRIER MASTIC. PROVIDE NYLON TY-WRAP
TOOL OR REUSABLE SS DRAW BANDS.
8. PROVIDE DUCT MOUNTED VOLUME DAMPER. AVOID NECK DAMPERS.
9. FLEXIBLE DUCTS SHALL BEND IN ONE DIRECTION ONLY WITH A MAXIMUM CHANGE IN DIFFERENCE OF 90
DEGREES.
10. UNLESS SHOWN OTHERWISE FLEXIBLE DUCT SIZE AND COLLAR OF TAP OFF SHALL BE SAME SIZE AS
DIFFUSER NECK.
11. IF RUN-OUT LENGTH REQUIRES SEGMENT OF HARD DUCT, SIZE SHALL BE SAME AS DIFFUSER NECK.
RUN-OUT TO DIFFUSER SHALL BE AS STRAIGHT AS POSSIBLE.
12. CENTERLINE RADIUS r OF FLEXIBLE DUCT BEND SHALL BE MINIMUM 1.5 DUCT DIAMETERS r >= 1.5 x D
13. LENGTH OF FLEX DUCT SHALL NOT EXCEED 6'-0" AS RECOMMENDED IN THE 2017 ASHRAE FUNDAMENTALS
HANDBOOK. FLEX DUCT SHALL NOT HAVE MORE THAN 1/2" SAG PER FOOT.
NTS
3 DIFFUSER/REGISTER DUCTWORK CONNECTIONS
SUPPORT ELBOW WITH TIE
SCREW AND
CLAMP
(TYPICAL)
AIR DEVICE
NECK AIR DEVICE
SIZE AS NOTED
ON PLANS
PROVIDE DURABLE
ELBOW SUPPORT
DRAW BANDS SNUG
WITHOUT CRUSHING
FLEXIBLE DUCT
FLEXIBLE DUCT
3D PREFERRED
1D MINIMUM
PROVIDE EQUALIZING GRID IF LESS THAN 3D
RETURN/EXHAUST AIR
SUPPLY AIR
BRANCH DUCTL
W
VD
TAPERED CONNECTION 45° ANGLE(IF MAIN
DUCT IS RECTANGULAR) OR CONICAL
CONNECTION (IF MAIN DUCT IS ROUND) L=1/4 W;
4"MIN
MAIN DUCT
A
SUPPLY OR EXHAUST VENTURI VALVE CLEANOUT & INSPECTION DETAIL7
NTS
PVC
THREADED
CLEANOUT
FLANGE CONNECTION
EXHAUST DUCT2dFLANGE
AIR
FLOWd
SECTION A
LOW PRESSURE DUCT SIZING TABLE1
NTS
NTS
4 EXHAUST AND RETURN AIR TERMINAL BOX AND VALVE - DUCT CONNECTIONS
LOW PRESSURE BRANCH TAKE-OFFS6
NTS
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
NTS
M5.20
29313.00
11/30/18
HVAC - DETAILS