HomeMy WebLinkAboutFP2.20FIRE PROTECTION LEVEL 2FFFFF FFFFF FFF FF FF FHOSE ALLOWANCE(GPM)(SQ FT)MAX AREA PER SPRINKLER(SQ FT)CALCULATION AREADESIGN DENSITY(GPM/SQ FT)OCCUPANCY CLASSIFICATIONAREA DESCRIPTIONSPRINKLER SYSTEM DESIGN CRITERIA - NFPA 13ORDINARY HAZARD II/HC-2 LABORATORIES (USING CHEMICALS) - CLASS A AND B 0.20 2500 130 25021346785QPRSTOU9S1R14AQ15.121346785QPRSTOU9S1R14AQ15.1EXISTING TO REMAIN STANDPIPE, FEED AND VALVESPROVIDE NEW ZONECHECK ASSEMBLY AT EXISTING SPRINKLER CONTROL VALVE ASSEMBLYWORK AREA1PLBG2PLBG? ??TISSUE CULTURE(MAMMALIAN)276BTISSUE CULTURE(BACTERIAL)276CGLASSWASH276ALAB WRITE-UP260LAB WRITE-UP269OPEN RESEARCHLAB276? ??? ??? ??iCVD ROOM276DRoom200SDRoom255ARoom252Room254Room256Room267CO2 CLOSET200JAELECTRICAL200UAPLUMBING200UBACCESSIBLERESTROOM200TC? ??4" WSP2 1/2" WSP2 1/2" WSP4" WSP11112ArchitectPayette Associates Architects, P.C.290 Congress Street, Fifth FloorBoston, MA 02210-1005Tel: 617-895-1000Fax: 617-895-1002MEP/FP EngineerVanderweil274 Summer StreetBoston, MA 02210Tel: 617-423-7423Structural EngineerSGH41 Seyong StreetBuilding 1, Suite 500Waltham, MA 02453Tel: 781-907-9000Fax: 781-907-9009Drawing ScaleProject NumberDate IssuedRenovation of Olin Hall for Chemical and Biomolecular Engineering - Phase 1 Code ConsultantHastings Consulting Inc142 Hanlon RoadHollister, MA 01746Tel: 508-397-8417Lighting DesignerAvailable Light10 Derby Square #3Salem, MA 01970Tel: 978-744-6800NCost ConsultantDharam Consulting745 Atlantic Ave Fl 8Boston, MA 02111Tel: 617-913-4345Abatement SpecialistDelta860 Hooper RdEndwell, NY 13760Tel: 607-231-6600Civil EngineerT.G. Miller, P.C.203 N. Aurora StreetIthaca, NY 14850Tel: 607-272-6477As indicatedFP2.2029313.0011/30/18FIRE PROTECTION -LEVEL 2GENERAL NOTES:1.PROVIDE SPRINKLER PROTECTION THROUGHOUT IN ACCORDANCE WITH NFPA 13. IN AREAS WHERE FIRE SUPPRESSION OR ARCHITECTURAL DRAWINGS INDICATE SPRINKLER LOCATIONS, COMPLY WITH THE DESIGN INTENT INDICATED BY THE DRAWINGS AND NFPA 13. IN AREAS WHERE FIRE SUPPRESSION OR ARCHITECTURAL DRAWINGS DO NOT INDICATE SPRINKLER LOCATIONS, COMPLY WITH NFPA 13.2.REFER TO ARCHITECTURAL & STRUCTURAL SERIES DRAWINGS FOR STRUCTURAL FRAMING PLANS, DETAILED REFLECTED CEILING PLANS, ELEVATIONS, AND SECTIONS. 3.IN AREAS WITH FINISHED CEILINGS, LOCATE SPRINKLERS IN THE CENTER OF SUSPENDED CEILING TILES, ALONG THE CENTER-LINE OF CEILING FEATURES AND IN-LINE WITH ADJACENT CEILING FIXTURES. 4.IN AREAS OPEN TO STRUCTURE ABOVE, LOCATE SPRINKLERS WITHIN BEAM POCKETS AND MAINTAIN SPRINKLER CLEARANCE FROM STRUCTURAL MEMBERS IN ACCORDANCE WITH NFPA 13.5.LOCATE SPRINKLERS WITH RESPECT TO CEILING AND FLOOR MOUNTED OBSTRUCTIONS SIMILAR TO (BUT NOT LIMITED TO) SHELVING, ROOM DIVIDERS, LIGHT FIXTURES, EXIT SIGNS, SOFFITS AND CHANGES IN CEILING ELEVATION AND MAINTAIN CLEARANCE IN ACCORDANCE WITH NFPA 13.6.SHOP DRAWINGS INCLUSIVE OF SPRINKLER AND BRANCH PIPING LAYOUTS AND CORRESPONDING HYDRAULIC CALCULATIONS SHALL BE PREPARED BY THE INSTALLER'S QUALIFIED DESIGNER. SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW AND SHALL BE USED FOR FIRE PROTECTION SYSTEM INSTALLATION PERMITS. 7. PROVIDE ALL NECESSARY FLUSHING VALVES IN ACCORDANCE WITH CORNELL UNIVERSITY FIRE PROTECTION SPECIFICATIONS. SHEET NOTES:COORDINATE EXACT BEAM PENATRATION LOCATIONS FOR SPRINKLER BRANCH LINES WITH STRUCTURAL ENGINEER. 1# DATE DESCRIPTION1 11/30/18 ISSUED FOR CONSTRUCTION2 12/18/18 ADDENDUM 01DocuSign Envelope ID: A198E6BC-80F0-4574-909E-457FA59E132F12/18/2018