E0.02ELECTRICAL GENERAL SCHEDULES
NOTES: 1-8AWG 3/4"C. 1-8AWG 3/4"C. 1-8AWG 3/4"C. 1-6AWG 3/4"C. 1-2AWG 3/4"C. 1-1/OAWG 3/4"C. 1-2/OAWG 3/4"C. 1-2/OAWG 3/4"C. 1-2/OAWG 3/4"C. 1-2/OAWG 3/4"C. 1" 60 1.25" 1.25" 70 1.5" 1.5" 100 2" 2" 125 2.5" 2" 150 2.5" 2" 175 2.5" 2" 200 2.5" LEGEND OF FEEDER SIZES COPPER CONDUCTORS 2.5" 225 2.5" 3" 250 3" 3" 300 3" 4" 350 4" 4" 400 4" (2)-3"500 (2 SETS 0F) 3-250 kcmil ; 1-250 kcmil N; 1-2 AWG GND. (2)-3.5"600 (2 SETS OF) 3-350 kcmil ; 1-350 kcmil N; 1-1 AWG GND. (2)-4"800 (2 SETS OF) 3-600 kcmil ; 1-600 kcmil N; 1-1/0 AWG GND. (3) 3.5"1000 (3 SETS OF) 3-500 kcmil; 1-500 kcmil N; 1-2/0 AWG GND. (3)-4"1200 (3 SETS OF) 3-600 kcmil; 1-600 kcmil N; 1-3/0 AWG GND. (4)-4"1600 (4 SETS OF) 3-600 kcmil; 1-600 kcmil N; 1-4/0 AWG GND. (5)-4"2000 (5 SETS OF) 3-600 kcmil; 1-600 kcmil N; 1-250 kcmil GND. NOTES: 1.ALL AMPACITIES ARE BASED ON 75 DEGREE C TEMPERATURE RATING OF CONDUCTOR AS LISTED IN THE NATIONAL ELECTRIC CODE. NOM. AMPERE RATING FEEDER TAG & MODIF. CONDUCTORS MINIMUM RACEWAY SIZE (INCHES) Y DESIGNATIONS 2.FEEDERS MAY HAVE A COMBINATION OF OVERSIZED NEUTRAL AND ISOLATED GROUND (DESIGNATION K AND G). REFER TO RISER FOR FEEDER DESIGNATIONS. Y Y Y Y Y Y 3-6 AWG; 1-6 AWG N; 1-10 AWG GND. CHANGE NEUTRAL TO 1-4 AWG ADD 1-10 AWG IG 3-4 AWG; 1-4 AWG N; 1-8 AWG GND. CHANGE NEUTRAL TO 1-1/0 AWG ADD 1-8 AWG IG 3-1 AWG; 1-1 AWG N; 1-8 AWG GND. CHANGE NEUTRAL TO 1-3/0 AWG ADD 1-8 AWG IG 3-1/0 AWG; 1-1/0 AWG N; 1-6 AWG GND. CHANGE NEUTRAL TO 2-1/0 AWG ADD 1-6 AWG IG 3-1/0 AWG; 1-1/0 AWG N; 1-6 AWG GND. CHANGE NEUTRAL TO 2-1/0 AWG ADD 1-6 AWG IG 3-2/0 AWG; 1-2/0 AWG N; 1-6 AWG GND. CHANGE NEUTRAL TO 2-2/0 AWG ADD 1-6 AWG IG 3-3/0 AWG; 1-3/0 AWG N; 1-6 AWG GND. CHANGE NEUTRAL TO 2-3/0 AWG ADD 1-6 AWG IG 3-4/0 AWG; 1-4/0 AWG N; 1-4 AWG GND. CHANGE NEUTRAL TO 2-4/0 AWG ADD 1-4 AWG IG 3-250 kcmil ; 1-250 kcmil N; 1-4 AWG GND. CHANGE NEUTRAL TO 2-250 kcmil ADD 1-4 AWG IG 3-350 kcmil ; 1-350 kcmil N; 1-4 AWG GND. CHANGE NEUTRAL TO 2-350 kcmil AWG ADD 1-4 AWG IG 3-500 kcmil ; 1-500 kcmil N; 1-3 AWG GND. CHANGE NEUTRAL TO 2-500 kcmil ADD 1-3 AWG IG 3-600 kcmil ; 1-600 kcmil N; 1-3 AWG GND. CHANGE NEUTRAL TO 2-600 kcmil ADD 1-3 AWG IG Y K G Y K G Y K G Y K G Y K G Y K G Y K G Y K G Y K G Y K G Y K G Y K G -3-6 AWG; 1-10 AWG GND. 3-4 AWG; 1-8 AWG GND.- 3-1 AWG; 1-8 AWG GND.- 3-1/0 AWG; 1-6 AWG GND.- 3-1/0 AWG; 1-6 AWG GND.- 3-2/0 AWG; 1-6 AWG GND.- 3-3/0 AWG; 1-6 AWG GND.- 3-4/0 AWG; 1-4 AWG GND.- 3-250 kcmil; 1-4 AWG GND.- 3-350 kcmil; 1-4 AWG GND.- 3-500 kcmil; 1-3 AWG GND.- 3-600 kcmil ; 1-3 AWG GND.- 2000* 1600* 1200* 1000* 800* 600* 500* 400* 350* 300* 250* 225* 200* 175* 150* 125* 100* 70* 60* THE ASTERISK ABOVE IS FILLED IN WITH ONE OR MORE OF THE FOLLOWING DESIGNATIONS ON THE RISER. Y - THREE PHASE FOUR WIRE FEEDER. K - THREE PHASE FEEDER WITH OVERSIZED NEUTRAL. G - THREE PHASE FEEDER WITH ISOLATED GROUND. VD - FEEDER SIZED FOR VOLTAGE DROP (6)-4"2500 (6 SETS OF) 3-600 kcmil; 1-600 kcmil N; 1-350 kcmil GND.Y2500* (8)-4"3000 (8 SETS OF) 3-500 kcmil; 1-500 kcmil N; 1-400 kcmil GND.Y3000* (10)-4"4000 (10 SETS OF) 3-600 kcmil; 1-600 kcmil N; 1-500 kcmil GND.Y4000* SYMBOL NOTE: 1. COORDINATE EXACT NEMA CONFIGURATION WITH EQUIPMENT MANUFACTURER/PROVIDER. - 3/4" 3#6 & 1#10 GND 3#6 & 1#10 GND 2#10 & 1#10 GND 2#12 & 1#12 GND 250V., 3Φ, 3P., 4W. 250V., 3Φ, 3P., 4W. 60A., 20A., 50A., 30A., 15-60R L5-20R 15-50R L5-30R 16 14 15 13 125V., 2P., 3W. 125V., 2P., 3W. TWIST-LOCK TWIST-LOCK 30A - 1P 50A - 3P 60A - 3P 20A - 1P C. C. C. C.- 3/4" - 3/4" - 3/4" 2#10 & 1#10 GND 2#6 & 1#10 GND 2#12 & 1#12 GND 2#12 & 1#12 GND 2#6 & 1#10 GND 3#6 & 1#10 GND 3#6 & 1#10 GND 3#12 & 1#12 GND 2#10 & 1#10 GND 3#10 & 1#10 GND 3#10 & 1#10 GND 3#12 & 1#12 GND DEVICE RATINGS 125/250V., 3P., 4W. 250V., 3Φ, 3P., 4W. 125/250V., 3P., 4W. 125/250V., 3P., 4W. 250V., 3Φ, 3P., 4W. 125/250V., 3P., 4W. 20A., 50A., 20A., 30A., 50A., 50A., 30A., 20A., 30A., 60A., 14-50R 14-60R 15-30R 15-20R 14-30R11 12 9 8 10 6-20R 5-50R 6-50R 6-30R 14-20R 5 7 6 4 3 250V., 2P., 3W. 125V., 2P., 3W. 250V., 2P., 3W. 250V., 2P., 3W. 30A., 20A., NEMA NO. 5-20R 5-30R 2 125V., 2P., 3W. 125V., 2P., 3W. 60A - 2P 20A - 3P 30A - 3P 50A - 2P 30A - 2P 30A - 2P 20A - 2P 50A - 2P 20A - 2P 50A - 1P CIRCUIT BREAKER 20A - 1P 30A - 1P C. C. C. C. C. C. C. C. C. C.- 3/4" - 3/4" - 3/4" - 3/4" - 3/4" - 3/4" - 3/4" - 3/4" - 3/4" - 3/4" C. C. BRANCH CIRCUIT - 3/4" - 3/4" 17 18 19 21 22 23 24 25 27 26 28 29 20 L16-20R 20A., 480V., 3Φ, 3P., 4W. TWIST-LOCK 20A - 3P 3#12 & 1#12 GND - 3/4" L16-30R - 3/4"480V., 3Φ, 3P., 4W.30A.,TWIST-LOCK 3#10 & 1#10 GND30A - 3P C. C. L15-30R TWIST-LOCK L6-30R - 3/4"250V., 2P., 3W.30A.,TWIST-LOCK 2#10 & 1#10 GND30A - 2P C. L6-20R - 3/4"250V., 2P., 3W.20A.,TWIST-LOCK 2#12 & 1#12 GND20A - 2P C. L15-20R - 3/4"250V., 3Φ, 3P., 4W.20A.,TWIST-LOCK 3#12 & 1#12 GND20A - 3P C. L14-20R L14-30R L6-15R 15A., 3#10 & 1#10 GND250V., 3Φ, 3P., 4W.30A.,30A - 3P C.- 3/4" C.2#10 & 1#12 GND250V., 2P., 3W.20A - 2P - 3/4"TWIST-LOCK 3#12 & 1#12 GND 3#10 & 1#10 GND 125/250V., 3P., 4W. 125/250V., 3P., 4W. 20A., 30A.,30A - 2P 20A - 2P C. C.- 3/4" - 3/4" TWIST-LOCK TWIST-LOCK L22-30R TWIST-LOCK L22-20R - 3/4"277/480V., 3Φ, 4P., 5W.20A.,TWIST-LOCK 4#12 & 1#12 GND20A - 3P C. L21-20R L21-30R 4#10 & 1#10 GND277/480V., 3Φ, 4P., 5W.30A.,30A - 3P C.- 3/4" 4#12 & 1#12 GND 4#10 & 1#10 GND 125/208V., 3Φ, 4P., 5W. 125/208V., 3Φ, 4P., 5W. 20A., 30A.,30A - 2P 20A - 2P C. C.- 3/4" - 3/4" TWIST-LOCK TWIST-LOCK 2#12 & 1#12 GND15A.,5-15R1 125V., 2P., 3W.15A - 1P C.- 3/4" 2#12 & 1#12 GND15A.,6-15R 250V., 2P., 3W.15A - 2P C.- 3/4" 3#12 & 1#12 GND125/250V., 3P., 4W.15A.,14-15R 15A - 2P C.- 3/4" 3#12 & 1#12 GND250V., 3Φ, 3P., 4W.15A.,15-15R 15A - 3P C.- 3/4" 2#12 & 1#12 GND15A.,L5-15R 125V., 2P., 3W. TWIST-LOCK 15A - 1P C.- 3/4" 30 31 32 33 34 2. 50A - 2P 2 #6 & 1 #10 GND. - 3/4"C. 208/120 VOLT, 1Φ, 3W. CIRCUITS 208 OR 480 VOLTS, 3Φ, 3W. CIRCUITS 3 #10 & 1 #10 GND. - 3/4"C. 3 #12 & 1 #12 GND. - 3/4"C. 3 #8 & 1 #10 GND. - 3/4"C. 3 #6 & 1 #10 GND. - 3/4"C. 3 #6 & 1 #10 GND. - 3/4"C. 3 #12 & 1 #12 GND. - 3/4"C. 3 #10 & 1 #10 GND. - 3/4"C. 2 #6 & 1 #10 GND. - 3/4"C. 120 FT. TO 180 FT. 65 FT. TO 120 FT. CIRCUIT LENGTH 4 #6 & 1 #10 GND. - 1"C. 4 #6 & 1 #10 GND. - 1"C. 208Y/120 & 480Y/277 VOLT, 3Φ, 4W. CIRCUITS 4 #8 & 1 #10 GND. - 3/4"C. 3 #6 & 1 #10 GND. - 3/4"C. 3 #6 & 1 #10 GND. - 3/4"C. 4 #12 & 1 #12 GND. - 3/4"C. 4 #10 & 1 #10 GND. - 3/4"C. ALL BRANCH CIRCUIT SIZES ARE BASED ON RACEWAY LENGTH OF 65 FEET FOR 120 VOLT BRANCH CIRCUITS AND 150 FEET FOR 277 VOLT BRANCH CIRCUITS. IF LENGTH EXCEEDS 65 FEET (120 VOLT CIRCUITS) OR 150 FEET (277 VOLT CIRCUITS) THEN USE WIRE SIZE DENOTED BELOW AND INCREASE RACEWAY ACCORDINGLY. REDUCE LARGE CABLE SIZES IN JUNCTION BOX PRIOR TO DEVICE TERMINATION. PROVIDE WIRE REDUCERS AT BREAKERS WHEN REQUIRED. 3 #8 & 1 #10 GND. - 3/4"C. #10 #8 #6 180 FT. TO 250 FT. NOTES: 1. WIRE SIZE 120V CIRCUIT 20A - 3P* 30A - 3P* 40A - 3P* 60A - 3P* 50A - 3P* 30A - 3P 20A - 3P 50A - 3P 60A - 3P 40A - 3P 60A - 2P 20A - 2P* 50A - 2P* 60A - 2P* 30A - 2P* 40A - 2P* 150 FT. TO 240 FT. 240 FT. TO 400 FT. 400 FT. TO 640 FT. 277V CIRCUIT 2 #8 & 1 #10 GND. - 3/4"C. 208 VOLT, 1Φ, 2W. CIRCUITS 2 #8 & 1 #10 GND. - 3/4"C. 2 #12 & 1 #12 GND. - 3/4"C. 2 #10 & 1 #10 GND. - 3/4"C. 2 #6 & 1 #10 GND. - 3/4"C. 2 #6 & 1 #10 GND. - 3/4"C. 120 OR 277 VOLT, 1Φ, 2W. CIRCUITS 2 #10 & 1 #10 GND. - 3/4"C. 50A - 1P 60A - 1P 40A - 2P 30A - 2P 20A - 2P CIRCUIT BREAKER 40A - 1P 30A - 1P CONDUCTOR 20A - 1P 2 #12 & 1 #12 GND. - 3/4"C. #4 #2 375 FT. TO 560 FT. 250 FT. TO 375 FT.- - EACH BRANCH CIRCUIT SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR. SHARED NEUTRALS ARE NOT ACCEPTABLE. 150A-3P 20A-3P 30A-3P TRANSFORMER SCHEDULE 90A-3P 200A-3P 300A-3P 400A-3P 60A-3P ALL CONDUCTOR SIZES ARE FOR COPPER CONDUCTORS. 5. 6. 4. 3. 181 271225 150 135112/12 75 90 T1 5445 30 36 15 9 18 11 25 40A-3P TAG kVA PRIMARY (480V - 3Φ) AMPS (120/208V. - 3Φ) SECONDARY T1K T1G 3-12 AWG, & 1-12 AWG GND.-3/4"C FEEDER SIZE FEEDER SIZE 4-8 AWG, & 1-10 AWG GND.-3/4"C. 42 50A-3P3-10 AWG, & 1-10 AWG GND.-3/4"C 4-6 AWG, & 1-10 AWG GND.-1"C. 83 100A-3P3-6 AWG, & 1-10 AWG GND-3/4"C. 4-1 AWG, & 1-8 AWG GND.-2"C. 125 150A-3P3-3 AWG, & 1-8 AWG GND-1 1/4"C. 4-1/O AWG, & 1-6 AWG GND.-2"C. 208 250A-3P 4-250kcmil, & 1-4 AWG GND.-3"C. 313 400A-3P3-3/O AWG, & 1-6 AWG GND-2"C. 2 SETS (4-4/0 AWG, 1-3 AWG GND.-2 1/2"C). 417 500A-3P3-350kcmil, & 1-4 AWG GND-3"C. 2 SETS (4-250kcmil, & 1-2 AWG GND.-3"C). 625 800A-3P3-500kcmil, & 1-3 AWG GND-3"C. 3 SETS (4-300kcmil, & 1-1/O AWG GND.-4"C). AMPS ASTERISK "*" DENOTES TRAPEZE MOUNTED.7. BOND NEUTRAL OF TRANSFORMER SECONDARY TO THE TRANSFORMER CASE WITH BONDING JUMPER AS PER NATIONAL ELECTRIC CODE. SECONDARY OVERCURRENT PROTECTION SHALL BE LOCATED WITH TEN (10) FEET OF THE TRANSFORMER SECONDARY TERMINALS EITHER IN A PANELBOARD (MAIN BREAKER) OR AN INDIVIDUALLY MOUNTED CIRCUIT BREAKER. WHERE ISOLATED GROUND PANELBOARDS & GROUND WIRES ARE REQUIRED REFER TO ISOLATED GROUNDING DETAIL FOR ADDITIONAL INFORMATION. OCP OCPCOND. BONDING 3-6 AWG, 1-3 AWG N., & 1-10 AWG GND.-1 1/4"C. 3-4 AWG, 1-1 AWG N., & 1-10 AWG GND.-1 1/2"C. T2 T2K T2G T8 T1 TAG T8K T1K T8G T1G T2 T2K T2G 3-1 AWG, 2-1/O AWG N., & 1-8 AWG GND.-2"C. T3 T3K T3G T3 T3K T3G 5-3/O AWG, & 1-6 AWG GND.-2 1/2"C. T4 T4K T4G T4 T4K T4G T5 T5K T5G T5 T5K T5G T6 T6K T6G T6 T6K T6G 3-300kcmil, 2-300kcmil N, & 1-4 AWG GND.-3 1/2"C. 2 SETS (3-250kcmil, 2-250kcmil N, & 1-3 AWG GND.-3"C). 3-1/O AWG, & 1-6 AWG GND-1 1/2"C. 2 SETS (3-300kcmil, 2-300kcmil N, & 1-2 AWG GND.-3 1/2"C). T7 T7K T7G T7 T7K T7G 3 SETS (3-350kcmil, 2-350kcmil N, 1-1/O AWG IG & 1-1/O AWG GND.-4"C). 3 SETS (3-350kcmil, 2-350kcmil N, & 1-1/O AWG GND.-4"C). T8 T8K T8G 1.TAG DESIGNATIONS ARE AS FOLLOWS: T# IS NEMA TP1 TRANSFORMER , T#K IS MINIMUM K13 RATED TRANSFORMER AND T#G IS MINIMUM K13 RATED TRANSFORMER WITH ISOLATED GROUND ON SECONDARY. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 2.PROVIDE NEUTRAL TO GROUND BONDING JUMPER ON SECONDARY OF TRANSFORMER. PROVIDE GROUNDING ELECTRODE CONDUCTOR FROM GROUNDED NEUTRAL TO THE NEAREST EFFECTIVELY GROUNDED METAL MEMBER OF STRUCTURE, WATER PIPE AND/OR ONE OF THE METHODS LISTED IN NEC 250. BONDING AND ELECTRODE CONDUCTOR SHALL BE SIZED AS LISTED ABOVE 3-6 AWG, 1-3 AWG N., 1-10 AWG IG & 1-10 AWG GND.-1 1/2"C. 3-4 AWG, 1-1 AWG N., 1-10 AWG IG & 1-10 AWG GND.-1 1/4"C. 3-1 AWG, 2-1/0 AWG N., 1-8 AWG IG & 1-8 AWG GND.-2"C. 5-3/0 AWG, 1-6 AWG IG & 1-6 AWG GND.-2 1/2"C. 3-250kcmil, 2-300kcmil N, 1-4 AWG IG & 1-4 AWG GND.-3 1/2"C. 2 SETS (3-250kcmil, 2-250kcmil N, & 1-3 AWG IG & 1-3 AWG GND.-3"C). 2 SETS (3-300kcmil, 2-300kcmil N, 1-2 AWG IG & 1-2 AWG GND.-3 1/2"C). 500A-3P 800A-3P 361 602500 300 833 1000A-3P 3 SETS (4-400kcmil, & 1-2/0 AWG GND.-3 1/2"C). 1388 1600A-3P 5 SETS (4-500kcmil, & 1-4/O AWG GND.-4"C). 3 SETS (3-400kcmil, 2-400kcmil N, & 1-2/0 AWG GND.-3 1/2"C). T9 T9K T9G 5 SETS (3-500kcmil, 2-500kcmil N, 1-4/O AWG IG & 1-4/O AWG GND.-4"C). 5 SETS (3-500kcmil, 2-500kcmil N, & 1-4/O AWG GND.-4"C). T10 T10K T10G 3 SETS (3-400kcmil, 2-400kcmil N, 1-2/0 AWG IG & 1-2/0 AWG GND.-4"C). 2 SETS (3-250kcmil, & 1-2 AWG GND-2 1/2"C.) 3 SETS (3-300kcmil, & 1-1/0 AWG GND-4"C.) T9 T9K T9G T10 T10K T10G BRANCH CIRCUIT SCHEDULE SPECIAL PURPOSE RECEPTACLE SCHEDULE Architect Payette Associates Architects, P.C. 290 Congress Street, Fifth Floor Boston, MA 02210-1005 Tel: 617-895-1000 Fax: 617-895-1002 MEP/FP Engineer Vanderweil 274 Summer Street Boston, MA 02210 Tel: 617-423-7423 Structural Engineer SGH 41 Seyong Street Building 1, Suite 500 Waltham, MA 02453 Tel: 781-907-9000 Fax: 781-907-9009 Drawing Scale Project Number Date Issued Renovation of Olin Hall for Chemical and Biomolecular Engineering - Phase 1 Code Consultant Hastings Consulting Inc 142 Hanlon Road Hollister, MA 01746 Tel: 508-397-8417 Lighting Designer Available Light 10 Derby Square #3 Salem, MA 01970 Tel: 978-744-6800 N Cost Consultant Dharam Consulting 745 Atlantic Ave Fl 8 Boston, MA 02111 Tel: 617-913-4345 Abatement Specialist Delta 860 Hooper Rd Endwell, NY 13760 Tel: 607-231-6600 Civil Engineer T.G. Miller, P.C. 203 N. Aurora Street Ithaca, NY 14850 Tel: 607-272-6477 12" = 1'-0" E0.02 29313.00 11/30/18 ELECTRICAL GENERAL SCHEDULES # DATE DESCRIPTION 1 11/30/18 ISSUED FOR CONSTRUCTION DocuSign Envelope ID: DAB23A5A-6B4E-4542-874F-F48E2BF76454 12/10/2018