HomeMy WebLinkAboutE0.01ELECTRICAL LEGEND & GENERAL NOTES5
J
VFD
T3
PANEL XX
X
J
J
#
F
P
SYSTEM GROUND OR EQUIPMENT GROUND
POWER TRANSFORMER - DELTA CONNECTED PRIMARY
GROUNDED WYE CONNECTED SECONDARY
SWITCH
"I" - INSTANTANEOUS PICKUP
"S" - SHORT TIME PICK UP & DELAY
"G" - GROUND FAULT PICKUP
"L" - LONG TIME PICK UP & DELAY
DRAW OUT POWER CIRCUIT BREAKER (FRAME/TRIP)
LSIG
1200
800
125E
FUSE "125E" DENOTES SIZE AND TYPE
LA LIGHTNING/SURGE ARRESTER
NOTES:
DOUBLE LUG AND FEED THRU AT PANEL BOARDS SHALL NOT BE PERMITTED1.
2.
EQUIPMENT LEGEND
JUNCTION AND/OR PULL BOX
VARIABLE FREQUENCY DRIVE
DISCONNECT SWITCH (UNFUSED)
DISCONNECT SWITCH (FUSED)
208Y/120 VOLT, 3Φ, 4 WIRE PANEL
480Y/277 VOLT, 3Φ, 4 WIRE PANEL
CONTRACTOR TO EQUIPMENT BY OTHERS.
AND CONDUCTORS BY THE ELECTRICAL
DENOTES FLEXIBLE LIQUID TIGHT CONNECTION
LSIG
**AF
**AT
PANELBOARD
TRANSFER SWITCH
MOLDED CASE CIRCUIT BREAKER
POWER ONE-LINE LEGEND
T3
E "ATS" DENOTES AUTOMATIC TRANSFER SWITCH
"MTS" DENOTES MANUAL TRANSFER SWITCH
DRY TYPE TRANSFORMER. "T3" DENOTES TRANSFORMER TYPE.
REFER TO THE "DRY TYPE TRANSFORMER SCHEDULE" FOR
FURTHER INFORMATION.
MS217-2
PLUMBING AND MECHANICAL EQUIPMENT DESIGNATION. REFER
TO SCHEDULE. DESIGNATION "MS217-2" DENOTES BRANCH
CIRCUIT DESIGNATION FOR EQUIPMENT SUCH AS UNIT
HEATERS, WHERE THERE ARE SEVERAL UNITS WITH THE SAME
EQUIPMENT DESIGNATION.
WIRING DEVICES LEGEND
NOTES:CONDUIT / CIRCUITRY TURNING UP
CONDUIT / CIRCUITRY TURNING DOWN
PS218-1,3,5
60A-3P*
PS218-1
CIRCUITRY AND FEEDERS LEGEND
HOMERUN TO PANEL "PS218", CIRCUIT #1. EACH BRANCH CIRCUIT
SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR UNLESS
OTHERWISE NOTED. PROVIDE UNSHARED GROUNDING
CONDUCTORS FOR EACH CIRCUIT IN ACCORDANCE WITH
SPECIFICATIONS AND N.E.C. UNLESS OTHERWISE NOTED.
MINIMUM SIZE CONDUIT SHALL BE 3/4" UNLESS OTHERWISE
NOTED. SEE NOTE #1 BELOW.
125 VOLT, 2 POLE, 3 WIRE, 20 AMP., DUPLEX RECEPTACLE
MOUNTED ABOVE COUNTER OR HIGHER THAN STANDARD
RECEPTACLE MOUNTING HEIGHT.
MOTOR. NUMERAL INDICATES HORSEPOWER RATING.
125 VOLT, 2 POLE, 3 WIRE, 20 AMP., DUPLEX RECEPTACLE ON
NORMAL POWER.
"2" DENOTES CIRCUIT NUMBER.
"S" - DENOTES RECEPTACLE ON STAND-BY POWER
"TV" - DENOTES RECEPTACLE FOR TV DISPLAY.
PART PLAN REFERENCE TAG. THE TOP LETTER OR NUMBER IS
THE PART PLAN REFERENCE AND THE LOWER REFERENCE
INDICATES THE DRAWING THE PART PLAN IS LOCATED.
1
E-501
HOMERUN TO PANEL "PS218", CIRCUIT #1,3,5 VIA 60A-3P* CIRCUIT
BREAKER. ASTERISK INDICATES NEUTRAL CONDUCTOR
REQUIRED IN CIRCUIT, AS INDICATED IN THE "BRANCH CIRCUIT
SCHEDULE." SEE NOTE #1 BELOW.
MANUAL MOTOR STARTER COMPLETE WITH THERMAL
OVERLOAD PROTECTION. "P" DENOTES EQUIPPED WITH
PILOT LIGHT, PROVIDED BY ELECTRICAL CONTRACTOR.
2
125 VOLT, 2 POLE, 3 WIRE, 20 AMP., DOUBLE DUPLEX
RECEPTACLE.
125 VOLT, 2 POLE, 3 WIRE, 20 AMP., DOUBLE DUPLEX
RECEPTACLES MOUNTED ABOVE COUNTER.
125 VOLT, 2 POLE, 3 WIRE, 20 AMP., DUPLEX RECEPTACLE
EQUIPPED WITH INTEGRAL GROUND FAULT INTERRUPTER AND
MOUNTED IN CAST OUTLET BOX WITH WEATHERPROOF COVER.
125 VOLT, 2 POLE, 3 WIRE, 20 AMP., DUPLEX RECEPTACLE
EQUIPPED WITH INTEGRAL GROUND FAULT INTERRUPTER.
WP
G
ALL RECEPTACLES SHALL BE INSTALLED WITH GROUND PRONG IN THE UP
POSITION.
ALL RECEPTACLES SHALL BE SIDE WIRED.
JUNCTION AND/OR PULL BOX IN CEILING
DRY TYPE TRANSFORMER. "T3" DENOTES TRANSFORMER
TYPE. REFER TO THE "DRY TYPE TRANSFORMER SCHEDULE"
FOR FURTHER INFORMATION.
"AF" - INDICATES AMPERE FRAME SIZE
"ST"- INDICATES SHUNT TRIP BREAKER
"L" - INDICATES LONG TIME DELAY
"S"- INDICATES SHORT TIME DELAY
"I"- INDICATES INSTANTANEOUS PICKUP
"G" - INDICATES GROUND FAULT PICKUP
ST "AT"- INDICATES AMPERE TRIP SETTING
AMPERES
AMERICANS WITH DISABILITIES ACT
AMPERE INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
ALUMINUM
INSTITUTE
ARCHITECT
AMERICAN NATIONAL STANDARDS
AUTHORITY HAVING JURISDICTION
ABOVE FINISH GRADE
AIR HANDLING UNIT
ABOVE FINISH FLOOR
AMERICAN WIRE GAUGE
BELOW FINISH GRADE
AUTOMATIC TEMPERATURE CONTROL
CONDUIT
CIRCUIT
COLUMN
CONTROL POWER TRANSFORMER
CIRCUIT BREAKER
CENTERLINE
CATALOG
CURRENT LIMITING FUSE
BUILDING
DIRECT DIGITAL CONTROL
COPPER
DRAWING
CURRENT TRANSFORMER
FAN COIL UNIT
ELECTRICAL CONTRACTOR
EXHAUST FAN
EMERGENCY
FIRE ALARM
ELECTRICAL METALLIC TUBING
ELECTRIC WATER COOLER
EMERGENCY POWER OFF
GROUND FAULT INTERRUPTER
GROUND OR GROUNDING
FLEXIBLE METAL CONDUIT
FULL LOAD AMPERES
ISOLATED GROUND
HAND, OFF, AUTOMATIC SWITCH
INTERLOCK
INSTITUTE OF ELECTRICAL AND
THOUSAND CIRCULAR MILS
ELECTRONIC ENGINEERS
INTERMEDIATE METAL CONDUIT
GALVANIZED RIGID METALLIC CONDUIT
CERTIFIED BALLAST MANUFACTURERS
HOA
IG
IEEE
IMC
INT
kcmil
FLA
FT
FMC
GFI
GRMC
GND,G
FEET
EM
EPO
EMT
F
FCU
FA
EWC
FUSE
DDL
CU
CT
DWG
EC
EF
CB
CKT
CBM
CPT
CLF
COL
CL
BFG
ATC
AWG
CAT
C
BLDG
AHU
AIC
AL
ATS
ARCH
ANSI
A
ADA
AFG
AFF
AHJ
GENERAL ABBREVIATIONS
CABINET UNIT HEATERCUH
HPF HIGH POWER FACTOR
PT POTENTIAL TRANSFORMER
PHASE
ROOF TOP UNIT
TELEPHONE
SYMMETRICAL
POLYVINYL CHLORIDE
RIGID METAL CONDUIT
ROOT MEAN SQUARED
RIGID NON-METALLIC CONDUIT
BREAKER
UNIT HEATER
TRANSFORMER
WEATHERPROOF
WATER HEATER
UNLESS OTHERWISE NOTED
UNDERGROUND OR UNDERGRADE
UNDERWRITERS LABORATORIES
UNINTERRUPTABLE POWER SUPPLY
THERMAL MAGNETIC CIRCUITTMCB
WH
XFMR
WP
W
V
DELTA
WYE
WIRE
VOLT
UG
UL
UPS
UH
U.O.N.
SP
RTU
RNMC
SW
TEL
SYM
SWITCH
SPARE
PWR
PVC
RMC
RMS
POWER
KILOWATTS
CONDUIT
LIGHTING
MAIN LUGS ONLY
KILOVOLT AMPERES
NORMALLY CLOSED
METAL CLAD CABLE
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
LIQUIDTIGHT FLEXIBLE METAL
ASSOCIATION
NOT TO SCALE
PUSHBUTTON
NOT IN CONTRACT
NATIONAL ELECTRICAL
NATIONAL ELECTRIC CODE
MANUFACTURES ASSOCIATION
NATIONAL FIRE PROTECTION
PROVIDED UNDER OTHER SECTIONS
NORMALLY OPEN OR NUMBERNO
NTS
POS
PNL
P
PB
PANEL
POLE
NEC
NEMA
N.I.C.
NFPA
MC
MCB
MCC
MCP
MLO
NC
kW
kVA
LTG
LFMC
Φ
Y
BAS
EHD
ES
ESD
EWC
OPS
OVP
SEC
TP
SPECIAL PURPOSE RECEPTACLE. "#" DENOTES RECEPTACLE
TYPE. REFER TO "SPECIAL PURPOSE RECEPTACLE SCHEDULE"
ON DRAWING E0.01 FOR FURTHER INFORMATION.
CEILING MOUNTED 125 VOLT, 2 POLE, 3 WIRE, 20 AMP, DUPLEX
RECEPTACLE. COORDINATE EXACT LOCATIONS WITH
ARCHITECT.
"OVP" DENOTES RECEPTACLE FOR OVERHEAD VIDEO
PROJECTOR.
AUDIO VISUAL CONTRACTORAVC
PS218-1,2 MULTIPLE HOMERUNS TO PANEL "PS218", CIRCUIT #1 AND #2.
PROVIDE DEDICATED NEUTRAL AND GROUND FOR EACH CIRCUIT
NUMBER SHOWN UNLESS OTHERWISE NOTED. SEE NOTE #1
BELOW.
NOTES:
1.REFER TO PANEL SCHEDULES FOR BREAKER SIZE OF EACH CIRCUIT
HOMERUN. REFER TO THE "BRANCH CIRCUIT SCHEDULE" ON DRAWING E002
FOR CONDUCTOR QUANTITIES, CONDUIT SIZES, AND CIRCUIT LENGTH TABLE
FOR WIRE SIZE INCREASES DUE TO VOLTAGE DROP. REFER TO GENERAL
NOTES ON THIS DRAWING FOR ADDITIONAL INFORMATION.
VI VACUUM INTERRUPTER
S
PS218-1,3,5 HOMERUN TO PANEL "PS218", CIRCUIT #1,3,5 VIA 3-POLE CIRCUIT
BREAKER. SEE NOTE #1 BELOW.
OVP
AUTOMATIC TRANSFER SWITCH WITH BYPASS ISOLATION
N
TV
SIDE GUTTERS SHALL BE PROVIDED ON ALL PANELBOARDS WITH
MORE THAN 60 POLES.
PULL BOX (SIZE AS REQUIRED)PB
DISTRIBUTION PANELBOARD
"BAS" - DENOTES CONNECTION TO BAS PANELS.
"EHD" - DENOTES CONNECTION TO ELECTRIC HAND/HAIR DRYER.
"ESD" - DENOTES CONNECTION TO ELECTRIC SOAP DISPENSER.
"EWC" - DENOTES CONNECTION TO ELECTRIC WATER COOLER.
PROVIDE GFCI PROTECTION; HUBBELL "GFBF20ILA" OR EQUAL.
"OPS" - DENOTES CONNECTION TO OPERABLE PROJECTOR SCREEN
MOTOR.
"OVP" - DENOTES TO CONNECT TO OVERHEAD VIDEO PROJECTOR.
"SEC" - DENOTES TO CONNECT TO SECURITY PANELS.
"TP" - DENOTES CONNECTION TO TRAP PRIMERS
"ES" - DENOTES CONNECTION TO EMERGENCY SHOWER.
WALL MOUNTED POWER CONNECTION TO ELECTRIFIED
FURNITURE PARTITION WITH 3/4" LIQUIDTIGHT FLEX
WITH CONDUCTORS AS INDICATED.
11.
1.
2.
7.
6.
5.
4.
3.
8.
9.
10.
GENERAL NOTES
ALL WIRING SHALL BE RUN CONCEALED UNLESS SPECIFIED OTHERWISE.
12.ALL RECEPTACLES LOCATED WITHIN 6'-0" OF A SINK SHALL BE OF THE GFI TYPE.
ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER,RECTILINEAR TO
BUILDING STRUCTURE.
ALL COMPONENTS SHOWN ON THE RISER DIAGRAMS, BUT NOT ON THE PLAN OR VICE VERSA, SHALL
BE INCLUDED AS IF SHOWN ON BOTH.
EXACT LOCATION OF MECHANICAL EQUIPMENT THAT REQUIRES ELECTRICAL CONNECTION IS SHOWN
ON THE MECHANICAL DRAWINGS.
ALL RACEWAYS CROSSING BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH EXPANSION
FITTINGS.
CONDUIT HOMERUNS SHOWN ON THE DRAWING WITH MORE THAN 3 CURRENT CARRYING
CONDUCTORS ARE SHOWN DIAGRAMATICALLY. THE CONTRACTOR SHALL NOT INSTALL MORE THAN 3
CURRENT CARRYING CONDUCTORS IN A RACEWAY.
ALL FLUSH MOUNTED PANELS SHALL HAVE AN EMPTY 1-1/2" CONDUIT & (2) 3/4" CONDUIT STUBBED
ABOVE ACCESSIBLE CEILING FOR FUTURE SPARE CIRCUITS.
CONTRACTOR SHALL REVIEW ALL TRADES' CONTRACT DOCUMENTS TO DETERMINE SPECIFIC
MOUNTING LOCATIONS FOR ELECTRICAL EQUIPMENT. COORDINATE EXACT MOUNTING LOCATIONS
WITH THE ARCHITECT.
ELEMENTS OF THE ELECTRICAL WORK SHALL BE INSTALLED SUCH THAT AT COMPLETION THE
ELEMENT SHALL BE "FULLY AND REASONABLY ACCESSIBLE". ELEMENTS OF THE ELECTRICAL WORK
INCLUDE, BUT ARE NOT LIMITED TO PANELS, SWITCHBOARDS, MOTOR CONTROLS, TRANSFORMER,
DISCONNECTS, JUNCTION BOXES, AND ALL MAINTENANCE ACCESS POINTS INCLUDING CABLE PULL
SPACE. "FULLY AND REASONABLE ACCESSIBLE" SHALL BE DEFINED AS; CAPABLE OF BEING
ACCESSED FOR SERVICE, REPAIR OR REPLACEMENT BY AN AVERAGE SPEED INDIVIDUAL, ON A
LADDER ID NECESSARY, AND CAPABLE OF BEING SERVICED OR REMOVED WITHOUT REMOVING,
MODIFYING OR DISTORTING OTHER COMPONENTS OF THE WORK OF OTHER TRADES. CONFLICTS
WITH MEETING THIS REQUIREMENT SHALL BE BROUGHT TO THE ATTENTION OF THE OWNERS
REPRESENTATIVE IN A TIMELY MANNER.
EACH LIGHTING AND RECEPTACLE BRANCH CIRCUIT SHALL INCLUDE A SEPARATE NEUTRAL
CONDUCTOR FOR EACH AND EVERY CIRCUIT, UNLESS SPECIFICALLY NOTED OTHERWISE.
THE ELECTRICAL CONTRACTORS SHALL VERIFY EXISTING CONDITIONS TO INSURE THAT THE NEW
WORK WILL FIT TO THE EXISTING STRUCTURE IN THE MANNER INTENDED AND SHOWN ON THE
DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/OWNER REPRESENTATIVE PRIOR TO
ANY ROUGH-INS, FABRICATION, OR PERFORMING ANY WORK IN THE AREA INVOLVING DIFFERENCES.
NOTIFICATION SHALL BE IN THE FORM OF A DRAWING OR SKETCH INDICATING FIELD MEASUREMENTS
AND NOTES RELATED TO THE AREA.
13.COORDINATE LOCATION OF ALL ELECTRICAL EQUIPMENT WITH THE HVAC, PLUMBING AND FIRE
PROTECTION CONTRACTORS. THE ELECTRICAL CONTRACTOR SHALL NOT ALLOW ANY EQUIPMENT,
DUCTWORK, OR PIPING FOREIGN TO THE ELECTRICAL INSTALLATION TO BE INSTALLED IN OR PASS
THROUGH ANY ROOM IN WHICH ELECTRICAL SYSTEMS OR EQUIPMENT IS LOCATED, SUCH AS
ELECTRICAL ROOM, ELECTRIC CLOSETS TELEPHONE OR DATA CLOSETS. WHEN SERVING AN
ELECTRICAL SPACE, NO PIPING, DUCTWORK OR OTHER MECHANICAL EQUIPMENT SHALL BE ALLOWED
TO PASS THROUGH THE AREA OF THE ELECTRICAL EQUIPMENT EQUAL TO THE WIDTH AND DEPTH OF
THE ELECTRICAL EQUIPMENT EXTENDING FROM FLOOR TO STRUCTURAL CEILING ABOVE.
(REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION)
LIGHTING FIXTURES INDICATED WITH SHADING DENOTES
CIRCUITED TO NORMAL/EMERGENCY SUPPLY.
MOUNTED OR WALL MOUNTED PROVIDE DIRECTIONAL
ILLUMINATED "EXIT" SIGN LIGHTING FIXTURE. CEILING
ARROWS AS INDICATED ON FLOOR PLANS. DOT " "
LIGHT FIXTURE
DENOTES SIDE WITH FACE.
"a" INDICATES SWITCH CONTROL
"13" INDICATES CIRCUIT NUMBER
"A" INDICATES FIXTURE TYPE
a
A 13
LIGHTING EQUIPMENT LEGEND
A INTENT SCHEDULE.
LIGHTING CONTROL INTENT TAG. REFER TO LIGHTING CONTROL
LOW VOLTAGE SYSTEM NOTES
1.
2.
3.
INCLUDE FIRE STOPPING OF ALL PENETRATIONS ASSOCIATED WITH THE ABOVE SYSTEMS.
THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SYSTEM OF BOXES AND PATHWAYS
FOR THE TEL/DATA DEVICES SHOWN ON THE TEL/DATA DRAWINGS. REFER TO THE
TEL/DATA DRAWINGS FOR DEVICE QUANTITY, PATHWAY SIZING, AND LOCATIONS. ALL CONDUITS
SHALL BE PROVIDED WITH BUSHINGS ON BOTH ENDS AND A PULL STRING.
THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SYSTEM OF BOXES AND PATHWAYS
FOR THE SECURITY DEVICES AS DESCRIBED IN THE SECURITY DRAWINGS. REFER TO THE
SECURITY DRAWINGS FOR DEVICE QUANTITY, PATHWAY SIZING, AND LOCATIONS. ALL CONDUITS
THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SYSTEM OF BOXES AND PATHWAYS
FOR THE A/V DEVICES AS DESCRIBED IN THE A/V DRAWINGS. REFER TO THE A/V
DRAWINGS FOR DEVICE QUANTITY, PATHWAY SIZING, AND LOCATIONS. ALL CONDUITS SHALL BE
4.
SHALL BE PROVIDED WITH BUSHINGS ON BOTH ENDS AND A PULL STRING.
SHALL BE PROVIDED WITH BUSHINGS ON BOTH ENDS AND A PULL STRING.
1.
2.
1.
LEGEND NOTES
THIS SHEET IS A GENERAL LIST OF SYMBOLS AND SHALL BE USED AS A
REFERENCE TO DEFINE ITEMS INDICATED ON THE DRAWINGS. NOT ALL
SYMBOLS ARE NECESSARILY USED ON THIS PROJECT.
MULTI - OUTLET ASSEMBLY WITH DEVICES AS SHOWN.
EXISTING TO REMAINETR
CEILING MOUNTED, OCCUPANCY/ VACANCY SENSOR.
XL
XD
XN
XR
XM
RESPONSIBLE FOR MAINTAINING CIRCUITRY TO DEVICES
TO POWER SOURCE AND LABEL BREAKER IN
PANELBOARD AS SPARE. CONTRACTOR SHALL BE
CONDUIT AS REQUIRED SO AS TO PROVIDE A
COMPLETE OPERATIONAL INSTALLATION.
TO BE REMOVED. CUT BACK AND MAKE SAFE ALL
ASSOCIATED BRANCH CIRCUIT WIRING CONDUIT BACK
EQUIPMENT TO BE REMOVED AND REPLACED WITH NEW.
"XL" ADJACENT TO EQUIPMENT DENOTES RELOCATED
EXISTING AT NEW LOCATION
UNAFFECTED BY DEMOLITION.
"XD" ADJACENT TO EQUIPMENT DENOTES EXISTING
"XR" ADJACENT TO EQUIPMENT DENOTES EXISTING
"XN" ADJACENT TO EQUIPMENT DENOTES EXISTING
"XM" ADJACENT TO EQUIPMENT DENOTES EXISTING
SYMBOLS OUT OF FUNCTION DENOTES EXISTING
TO BE RELOCATED AS SHOWN. CUT BACK AND/OR
EXTEND EXISTING BRANCH CIRCUIT WIRING AND
EQUIPMENT TO REMAIN.
EXISTING EQUIPMENT LEGEND
IN EXISTING LOCATION.
TO BE REMOVED, STORED, CLEANED AND REINSTALLED
"XS" ADJACENT TO EQUIPMENT DENOTES EXISTINGXS
S1
WALL MOUNTED, OCCUPANCY/VACANCY SENSOR. S2
P1 CEILING MOUNTED PHOTOCELL "b" DENOTES DIMMING CONTROL.
LVD LOW VOLTAGE DIMMER SWITCH 0-10 V.
SINGLE POLE LOW VOLTAGE TOGGLE SWITCH "B" DENOTES
SWITCH CONTROL.
b
b
Architect
Payette Associates Architects, P.C.
290 Congress Street, Fifth Floor
Boston, MA 02210-1005
Tel: 617-895-1000
Fax: 617-895-1002
MEP/FP Engineer
Vanderweil
274 Summer Street
Boston, MA 02210
Tel: 617-423-7423
Structural Engineer
SGH
41 Seyong Street
Building 1, Suite 500
Waltham, MA 02453
Tel: 781-907-9000
Fax: 781-907-9009
Drawing Scale
Project Number
Date Issued
Renovation of Olin Hall for
Chemical and Biomolecular
Engineering - Phase 1
Code Consultant
Hastings Consulting Inc
142 Hanlon Road
Hollister, MA 01746
Tel: 508-397-8417
Lighting Designer
Available Light
10 Derby Square #3
Salem, MA 01970
Tel: 978-744-6800
N
Cost Consultant
Dharam Consulting
745 Atlantic Ave Fl 8
Boston, MA 02111
Tel: 617-913-4345
Abatement Specialist
Delta
860 Hooper Rd
Endwell, NY 13760
Tel: 607-231-6600
Civil Engineer
T.G. Miller, P.C.
203 N. Aurora Street
Ithaca, NY 14850
Tel: 607-272-6477
12" = 1'-0"
E0.01
29313.00
11/30/18
ELECTRICAL LEGEND &
GENERAL NOTES
# DATE DESCRIPTION
1 11/30/18 ISSUED FOR CONSTRUCTION