HomeMy WebLinkAbout815 S. Aurora St - Electrical Issued for Permit 2021.06.22 (2)3ASPHFTVSWITCH DUPLEX RECEPTACLE HORN/STROBE / Candela STROBE / Candela PULL STATION SMOKE DETECTOR QUAD RECEPTACLE EXIT SIGN -CEILING EMERGENCY LIGHT EXIT SIGN -WALL # G:GFCI A:Above Counter W:Weatherproof P: Photoelectric NEW CONCEALED WIRING # Indicates Quantity of Jacks if More than One DATA OUTLET 3:3 Way D:Dimmer OS:Occupancy Sensor VS:Vacancy Sensor T:Timer TELEPHONE OUTLET FIRE ALARM CONTROL PANELFACP REMOTE ANNUNCIATORRA PANELBOARD-RECESSED PANELBOARD-SURFACE LEGEND OCCUPANCY SENSOR SECURITY SYSTEM REMOTE EMERGENCY HEAD WALL LIGHT KEY FOBKF 208 VOLT RECEPTACLE 75 75 CAMERA SMOKE DETECTOR F: Fixed EXIT SIGN WITH EMERGENCY LIGHT ARROW INDICATES DIRECTION OF EXIT LINEAR FIXTURE EXTERIOR WALL PACK ARROW INDICATES DIRECTION OF EXIT TV CABLE OUTLET TAMPER SWITCHTS FLOW SWITCHFS 1. ALL OCCUPANCY / VACANCY SENSORS SHALL BE MANUALLY ADJUSTED TO EXTINGUISH LIGHTS AFTER A PERIOD OF 5 MINUTES OF INACTIVITY. 2. STAIRWELL LIGHT FIXTURES HAVE INTEGRATED MOTION SENSORS. REFER TO LIGHT FIXTURE SCHEDULE FOR CONTROL SETTINGS. 3. OCCUPANCY SENSORS SHALL CONTROL ALL HALL OR ROOM LIGHTING, UNLESS OTHERWISE NOTED. WHERE FIXTURES ARE TO REMAIN CONSTANTLY ILLUMINATED, UNOCCUPIED LIGHTING LEVELS SHALL BE 20% OF OCCUPIED LEVELS. 4. ALL EMERGENCY LIGHTING AND EXIT SIGNAGE TO BE FED FROM NEAREST LIGHTING CIRCUIT. LIGHTING CONTROL NOTES 1. PROJECT DOES NOT CONTAIN ANY DAYLIGHTING SIDELIT OR TOPLIT ZONES. 2. REFER TO LIGHTING CONTROL NOTES ABOVE AND TO LIGHT FIXTURE SCHEDULE FOR INDIVIDUAL FIXTURE CONTROL DETAILS ENERGY CODE COMPLIANCE NOTES Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com 1/8" = 1'-0"6/22/2021 4:25:02 PME0.00 Notes, Schedules & Legend STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C PART 1 -GENERAL 1.1 SUBMITTALS A. Provide electronic (pdf) submittals for approval prior to ordering equipment: a. Product cut sheets: fixtures, panelboards, disconnects, devices b. Single line power diagram B.Closeout: a. Operation and Maintenance Manual. b. As-Built drawings. c. Warranty information. PART 2 -PRODUCTS 2.1 WIRING METHODS A.RACEWAYS a. Concealed dry interior locations: Romex in floor or wall cavities. THHN in EMT for circuits run in slab. b. Exposed dry interior locations: Electrical metallic tubing c. Arrange conduit to maintain headroom and present a neat appearance. d. Maintain required fire, acoustic and vapor barrier rating when penetrating walls, floors, and ceilings. e. Use conduit hangers and clamps, do not fasten with wire or perforated straps. f. Provide suitable pull string in empty raceways. g. Completely and thoroughly swab raceway system before installing conductors. B.BUILDING WIRE: a. Apartment Feeders: Armored sub-feed cable with Aluminum stranded conductors. b. Feeder and branch circuits: Copper stranded conductor, 600 V insulation, THHN/THWN, minimum #12 AWG. c. MC Cable: Armored cable, copper conductor, 600 V insulation, rated 60°C, individual conductors twisted together and covered with a PVC jacket. C.WIRING DEVICES: a. Wall switch: 15A, 120V residential grade, side wired, tamper proof b. Pilot switch: 15A, 120V red pilot handle. c. Dimmer switch: On/off and slide, 600 watt d. Duplex convenience receptacle: 15A, 120V, side wired e. Surface raceway: Wiremold or equal. f. Use recessed outlet boxes in finished areas and where indicated.Install wall plates flush and level. D. MOUNTING HEIGHTS (Above floor to center) a. Mount as indicated per plans. 2.2EQUIPMENT A. Electric service: Refer to riser diagrams B. Panelboards and load centers: Refr to riser diagrams C. Contactors: General purpose relays NEMA ICS 2, electrically held. 2.3 LUMINAIRES A. Refer to Lighting Schedule and notes on E0.00. PART 3 -EXECUTION 3.1 INSTALLATION A. Sequence rough-in of electrical connections to coordinate with installation and startup of other equipment. B. Verify field conditions are as shown on drawings; report discrepancies to engineer prior to commencement of work. C. All new wiring, except in mechanical and utility spaces, shall be concealed, unless noted otherwise. D. Neatly train and secure wiring inside boxes, equipment, and panelboards. E. All conduit and cables shall run parallel or perpendicular to building elements, except for short diagonal runs less than 3 feet. Support conduit and cables, including communications cables, with devices manufactured specifically for the intended use. F. Core bore masonry penetrations. G. Seal penetrations in fire rated assemblies with fire caulk to maintain fire rating of the assembly. H. Coordinate utility service outages and re-connections with utility company and owner. I. Provide power wiring to all transformers, relays, etc., required for HVAC controls. J. Install ground electrodes and conductor as required to meet regulatory requirements. K. Provide bonding to meet regulatory requirements. L. Make electrical connections to utilization equipment in accordance with equipment manufacturer's instructions. Make conduit connections to equipment using flexible conduit. Use liquidtight flexible conduit in damp or wet locations. M. Identify electrical distribution and control equipment, and loads served with secure nameplates. Install wire markers on each conductor in panelboard gutters and at load connections. Provide NEW TYPEWRITTEN circuit directories for all new panels and for existing panels that have been substantially revised. N. Make arrangements and coordinate with the utility company to obtain permanent electric service with the project. O. Install utility services in accordance with utility company instructions. P. Measure ground resistance from system neutral connection at service entrance to convenient ground reference point by passing minimum current of 10 amperes DC and measuring voltage drop. Maximum resistance: 10 ohms. Report findings to architect and engineer. Q. Clean equipment finishes to remove paint and concrete splatters. 3.2 EMERGENCY LIGHTING A. Install emergency lighting system according to NFPA 70 National Electric Code and NFPA 101 Life Safety Code. B. Ensure that no area of the means of egress will be unlighted due to the failure of one light bulb or lighting unit. C. Provide battery backup capable of maintaining required footcandle levels for a minimum period of 1 1/2 hours. D. Provide to owner three extra of each lamp provided. 3.3COMMISSIONING A. Occupant sensor controls. Where occupant sensor controls are provided, the following procedures shall be performed: A.1. Certify that the occupant sensor has been located and aimed in accordance with manufacturer recommendations. A.2. Test each sensor. For occupant sensor controls to be tested, verify the following: A.2.1. Where occupant sensor controls include status indicators, verify correct operation. A.2.2. The controlled lights turn off or down to the permitted level within the required time. A.2.3. For auto-on occupant sensor controls, the lights turn on to the permitted level when an occupant enters the space. A.2.4. For manual-on occupant sensor controls, the lights turn on only when manually activated. A.2.5. The lights are not incorrectly turned on by movement in adjacent areas or by HVAC operation. B. Documentation requirements. Documents certifying that the installed lighting controls meet documented performance shall be provided to the building owner within 90 days from the date of receipt of the certificate of occupancy. 3.4 O&M MANUALS AND AS-BUILTS A. Provide (1) hard copy and (1) digital copy of Operation & Maintenance manuals. B. Provide (1) full size hard copy and (1) digital copy of As-Built drawings. C. Provide (1) hard copy and (1) digital copy of Warranties for all electrical equipment. PART 1 -GENERAL 1.1SECTION REQUIREMENTS A. Summary: Furnish and install a complete operating addressable fire alarm system as described herein and as designed by a systems manufacturer representative with a minimum NICET level III certification, and utilize such to include installation and system cost within bid. B. Submittals a. System operating description and device address list, coordinated with final system programming. b. Product data, including all cut sheets, product numbers, and system designations c. Submit Engineer stamped system plans, connection diagrams, battery calculations, conductor types and sizes, voltage drop calculations, and component descriptions. C. Code compliance: The system in its entirety shall comply with the requirements of the local Authority Having Jurisdiction and be in compliance with the current edition of all applicable fire and electrical codes, including (but not limited to): a. NFPA 70 National Electrical Code b. NFPA 72 National Fire Alarm Code c. NFPA 101 Life Safety Code d. Applicable State and Local Codes A. UL listed and labeled. PART 2 -PRODUCTS 2.1 FIRE ALARM CONTROL UNIT: A. General Requirements for Fire-Alarm Control Unit: Field-programmable, microprocessor-based, modular, power-limited design with electronic modules, complying with UL 864 and listed and labeled by an NRTL. B. Alphanumeric Display and System Controls: Arranged for interface between human operator at fire-alarm control unit and addressable system components including annunciation and supervision. Display alarm, supervisory, and component status messages and the programming and control menu. C. Transmission to Remote Alarm Receiving Station: Automatically transmit alarm, supervisory, and trouble signals to a remote alarm station. 2.2 ALARM-INITIATING DEVICES A. Manual Pull Stations: Double acting, metal or plastic, red in color with molded, raised-letter operating instructions in contracting color. B. Smoke Detectors: UL 268, 24-V DC, photoelectric type, plug-in arrangement. C. Thermal Detectors: Combination 135 deg F fixed-temperature and rate-of-rise unit. D. Apartment Smoke Detectors shall be installed on sounder bases. Activation of building-wide alarm will require activation of two individual apartment detectors. 2.3 ALARM-INDICATING DEVICE A. Horns: Electric-vibrating-polarized type, 90 dB at 10 feet. Visual Alarm Device: Xenon-strobe lights with the word "FIRE" engraved in 1-inch-high letters. Rated Light Output: 75 candela, unless noted otherwise. C. 2.4 WIRING A. Wire and cable shall be U.L. Listed for fire alarm use and shall be a minimum of 18 AWG or as required by local codes and Authority Having Jurisdiction. Raceways containing conductors identified as "Fire Alarm Control Panel" conductors shall not contain any other conductors. Wire in environmental air plenums not in raceway shall be plenum rated in compliance with NEC 760. No AC current carrying conductors shall be allowed in the same raceway with the emergency voice alarm communication detection and signaling conductors. All wiring shall be concealed except in utility spaces. B. Power-Limited Circuits: NFPA 70, Types FPL, FPLR, FPLP, or substitutes permitted by NFPA 70. PART 3 -EXECUTION 3.1 INSTALLATION A. Install and test systems according to NFPA 72. Comply with EIA/TIA 570 requirements for light-commercial and residential occupancies. B. Manual Pull Stations: Mount semi-flush in recessed back boxes with operating handles 48 inches above finished floor or as indicated. Water-Flow Detectors and Valve Supervisory Switches: Connect for each sprinkler valve station required to be supervised.Duct Smoke Detectors: Furnish and connect duct detectors mounted by others to fire alarm system. C. Smoke Detectors: Install ceiling-mounted detectors not less than 4 inches from a sidewall to the near edge. Install detectors located on the wall at least 4 inches but not more than 12 inches below the ceiling. For exposed solid joist construction, mount detectors on the bottoms of the joists. On smooth ceilings, install detectors not over 30 feet apart in any direction. Install detectors no closer than 5 feet from air registers. D. Audible Notification Appliances: Install not less than 80 inches above the finished floor, not more than 96 inches above finish floor, and at least 6 inches below the ceiling. Install bells and horns on flush-mounted back boxes with the device-operating mechanism concealed behind a grille or as indicated. Combine audible and visual notification appliances at the same location into a single unit. Visual Notification Appliances: Install not less than 80 inches above the finished floor; not more than 96 inches above finish floor, and at least 6 inches below the ceiling. E. Fire Alarm Control Unit: Surface mount with tops of cabinets not more than 6 feet above the finished floor F. Provide Digital Alarm Communicator Transmitter for connection to central monitoring agency in compliance with local code regulations. Connect to Owner's telephone lines. G. Provide sprinkler supervision. H. Ground cable shields and equipment. I. Wiring Method: a. Install wiring "fished" in concealed spaces. b. Secure to building elements. c. Run parallel and perpendicular to building elements above suspended ceilings. A. Run in metal raceways where indicated. 3.2 FINAL TEST A. The contractor's job foreman, a representative of the owner, and the fire department shall operate every building fire alarm device to ensure proper operation and correct annunciation at the control panel. B. At least one half of all tests shall be performed on battery standby power. C. Where application of heat would destroy any detector, it may be manually activated. D. The signaling line circuits and notification appliance circuits shall be opened in at least two (2) locations to check for the presence of supervision. E. When the testing has been completed to the satisfaction of both the contractor's job foreman and the representatives of the owner, a notarized letter co-signed by each attesting to the satisfactory completion of said testing shall be forwarded to the owner and the fire department. F. The contractor shall leave the fire alarm system in proper working order, and, without additional expense to the owner, shall replace any defective materials or equipment provided by him under this contract within one year (365 days) from the date of final acceptance by the awarding authority. Prior to final test, the fire department must be notified in accordance with local requirements. H. 3.3 WARRANTY A. The contractor shall warrant all equipment and wiring free from inherent mechanical and electrical defects for one year from the date of final acceptance. LIGHTING FIXTURE SCHEDULE Type Manufacturer Model Description Type Comments Wattage A1 COOPER LIGHTING - HALO OUTDOOR FE0650LPC LED ENTRY LIGHTING 9 W B Cooper Industries S23-DIW-2L30-SR-4-U-DD-SI-S9 3-W Wall Mount LED Strip light Mount at 7'-0" AFF at each stair landing. 31 W C Amex Lighting LED-SM55DL-NK Recessed LED Downlight 10 W D DRISCOLL LIGHTING - SEA GULL 6140401-962 BRUSHED NICKEL MINI PENDANT 3.5" Min.Radius 15 W EM Lithonia ELM2L SDRT LED Emergency Light, White body, Aimable optics, Self Diagnostics 2 W EX1 Lithonia LQM S W 3 R 120/277 EL N SD LED Exit Sign, White body, Red letters, Nickel cadmium battery, Self-diagnostics 5 W F Nukara VBL10LBNK Linear LED Vanity Light 12 W G Lithonia FMLRL 11 14830 Flush-mounted LED Ceiling Fixture 16 W LIGHTING CONTROL NOTES 1. OCCUPANCY SENSOR CONTROL A. ALL ENCLOSED PUBLIC ROOMS SHALL BE EQUIPPED WITH OCCUPANCY CONTROLS, OR AS INDICATED BY DRAWINGS. B. REFER TO LIGHTING PLAN NOTES FOR OCCUPANCY CONTROLS OF STAIRWELLS. 2. ALL MECHANICAL/MAINTENANCE/TRASH ROOMS SHALL BE CONTROLLED BY VACANCY SENSORS. 3. REFER TO ENCLARGED UNIT PLANS FOR LIGHTING CONTROLS WITHIN DWELLING UNITS. 4. ALL EXTERIOR LIGHTING SHALL BE ON PHOTOSENSORS, REFER TO SCHEDULE THIS SHEET. FIRE ALARM NOTES ELECTRICAL NOTES REVISIONS Δ DESCRIPTION DATE HOUSE PANEL 1 (HP-1) 225A BUS MLO 208Y/120V 3Ø-4W 30 SPACES APT 2A PANEL P-2A 150A BUS MLO 208/120V 1Ø-3W 30 SPACE GROUND FLOOR FIRST FLOOR APT 2B PANEL P-2B 150A BUS MLO 208/120V 1Ø-3W 30 SPACE TO METERSTACK ON GROUND FLOOR APT 2A PANEL P-2A 150A BUS MLO 208/120V 1Ø-3W 30 SPACE SECOND FLOOR APT 2B PANEL P-2B 150A BUS MLO 208/120V 1Ø-3W 30 SPACE APT 4A PANEL P-4A 150A BUS MLO 208/120V 1Ø-3W 30 SPACE THIRD FLOOR APT 4B PANEL P-4B 150A BUS MLO 208/120V 1Ø-3W 30 SPACE FEEDER SCHEDULE (2 SETS) 4-300 MCM AL, #1/0 AL GROUND IN 3" PVC 4-300 MCM AL, #1/0 AL GROUND IN 3" EMT 3/0-3/0-3/0-1 AL SER CABLE A PROVIDE GROUNDING IN ACCORDANCE WITH NEC 250 400A MAIN SERVICE DISCONNECT 208Y/120V 3Ø-4W (BOD: SQD EZM3400CB) 4-METER 225A METERSTACK 3Ø IN/1Ø OUT, 150A-2P BREAKER FOR EACH APARTMENT FEED (BOD: SQD EZM314225) -TYP OF (2) 1-POSITION 225A COMMERCIAL METER 3Ø IN-3Ø OUT, 225A-3P BREAKER FOR HOUSE PANEL (BOD: SQD EZMT331225) B C B UNDERGROUND TO UTILITY POLE / TRANSFORMER TYP FOR ALL APARTMENT FEEDS C A TO METERSTACK ON GROUND FLOOR TO METERSTACK ON GROUND FLOOR TO METERSTACK ON GROUND FLOOR TO METERSTACK ON GROUND FLOOR 1. 2. 3. NOTES: FOR 3 PHASE, 4 WIRE POWER PANEL FEEDERS, PROVIDE FULLY RATED NEUTRAL WIRE IN ADDITION TO CONDUCTORS SHOWN ABOVE. 120V & 208V CIRCUITS OVER 75', CONTRACTOR TO INCREASE CONDUIT AND WIRE SIZE ACCORDING TO VOLTAGE DROP. PROVIDE VOLTAGE DROP CALC TO ENGINEER OF RECORD. 480V CIRCUITS OVER 125', CONTRACTOR TO INCREASE CONDUIT AND WIRE SIZE, SIMILAR TO NOTE #2 ABOVE. CONDUIT AND AL CONDUCTOR TABLE CIRCUIT RATING PHASE CONDUCTORS CONDUIT 15 1 2-#12, 1-#12 G 3/4" 3 3-#12, 1-#12 G 3/4" 20 2-#12, 1-#12 G 3/4" 3/4" 30 2-#10, 1-#10 G 3/4" 3-#10, 1-#10 G 3/4" 40 2-#8, 1-#10 G 3/4" 3-#8, 1-#10 G 1" 50 2-#6, 1-#10 G 1" 3-#6, 1-#10 G 1" 60 2-#4, 1-#10 G 1" 3-#4, 1-#10 G 1 1/2" 70 2-#3, 1-#6 G 3-#3, 1-#6 G 80 2-#2, 1-#6 G 3-#2, 1-#6 G 90 2-#2, 1-#6 G 3-#2, 1-#6 G 100 3-#12, 1-#12 G 2-#1, 1-#6 G 3-#1, 1-#6 G 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 110 2-#1/0, 1-#4 G 2" 125 150 2-#3/0, 1-#4 G 2" 3-#3/0, 1-#4 G 2" 175 2-#4/0, 1-#4 G 3-#4/0, 1-#4 G 200 2-#250MCM, 1-#4 G 3-#250MCM, 1-#4 G 2 1/2" 225 2-#300MCM, 1-#2 G 3-#300MCM, 1-#2 G 250 2-#350MCM, 1-#2 G 3-#350MCM, 1-#2 G 300 2-#500MCM, 1-#2 G 3-#500MCM, 1-#2 G 350 3-#1/0, 1-#4 G (2 SETS) 2-#4/0, 1-#1 G (2 SETS) 3-#4/0, 1-#1 G 4" 4" 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 400 (2 SETS) 2-#250MCM, 1-#1 G (2 SETS) 3-#250MCM, 1-#1 G 1 3 2-#2/0, 1-#4 G 3-#2/0, 1-#4 G 1 3 2" 1 1/2" 2" 2" 2 1/2" 2 1/2" 2 1/2" 3" 3" 3" 3" 2 1/2" 2 1/2" 2 1/2" 2 1/2" Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com As indicated6/22/2021 4:25:03 PME0.01 Building C Riser Diagram STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C 1/2" = 1'-0"1 Electrical Riser Diagram - Building C REVISIONS Δ DESCRIPTION DATE TVTV T TVGSee 4/ E3.00 HP-1 4 See 5/ E3.00 FACP Stair 1 FC-3 HP-1 1 See 2/ E3.00 See 3/ E3.00 Mechanical Stair 0 HP-1 4 E1.00 3 FC-2 HP-1 1 HP-1 SERVICE DISCONNECT AND METERING EQUIPMENT HP-1 16 DP-1 HP-1 18,20,22 Mechanical 1 HP-1 6 EBH-1 HP-1 8,10 Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com As indicated6/22/2021 4:25:05 PME1.00 Building C Ground & First Floor - Power & Data STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C 1/8" = 1'-0"2 FIRST FLOOR POWER & DATA 1/8" = 1'-0"1 GROUND FLOOR POWER &DATA 1/2" = 1'-0"3 MECHANICAL ROOM ENLARGED PLAN - POWER & DATA Keynote Legend Key Value Keynote Text 1 REFER TO FIRE PUMP RISER DIAGRAM ON SHEET EA0.00 FOR DETAILS ON FIRE PUMP SERVICE. E1.00 GENERAL NOTES 1. MECHANICAL CONTRACTOR TO FURNISH AC DISCONNECT FOR ALL HVAC EQUIPMENT. ELECTRICAL CONTRACTOR TO INSTALL AND COMPLETE ELECTRICAL CONNECTIONS TO DISCONNECTS AND EQUIPMENT, TYPICAL OF ALL. 2. EC TO PROVIDE PATHWAYS TO SECURITY DEVICE LOCATIONS FROM HEAD END LOCATION IN MECHANICAL ROOM. COORDINATE MOUNTING HEIGHTS WITH OWNER. HARDWARE, WIRING, TERMINATIONS, AND TESTING BY OTHERS. REVISIONS Δ DESCRIPTION DATE G WTV HP-1 4 Stair 2 See 4/ E3.00 See 5/ E3.00 See 1/ E3.00 HP-1 4 Stair 3 See 4/ E3.00 FC-2 HP-1 1 1A 6,8 <unnamed> 2B 6,8 4A 9,11 HP-1 12,14 1B 6,8 HP-1 13 HP-1 HP-1 HP-1 HP-1 APT 1A APT 3BAPT 4B APT3A APT 2A APT 1B APT 2B HP-1 APT 4A HP-1 HP-2 STUDY STAIR HP-1 HP-1 Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com 1/8" = 1'-0"6/22/2021 4:25:07 PME1.01 Building C Second, Third & Roof - Power & Data STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C 1/8" = 1'-0"1 SECOND FLOOR PWER & DATA 1/8" = 1'-0"2 THIRD FLOOR POWER & DATA 1/8" = 1'-0"3 ROOF POWER & DATA E1.01 GENERAL NOTES 1. MECHANICAL CONTRACTOR TO FURNISH AC DISCONNECT FOR ALL HVAC EQUIPMENT. ELECTRICAL CONTRACTOR TO INSTALL AND COMPLETE ELECTRICAL CONNECTIONS TO DISCONNECTS AND EQUIPMENT, TYPICAL OF ALL. 2. EC TO PROVIDE PATHWAYS TO SECURITY DEVICE LOCATIONS FROM HEAD END LOCATION IN MECHANICAL ROOM. COORDINATE MOUNTING HEIGHTS WITH OWNER. HARDWARE, WIRING, TERMINATIONS, AND TESTING BY OTHERS. REVISIONS Δ DESCRIPTION DATE SPSPSP T G G B See 3/ E4.00 See 2/ E4.00 HP-1 3 HP-1 2 G HP-1 EMEMEX1 HP-1 3 FC-2 TS FS TS FS 2 2EX1 EX1 1 TS FS 2 B G See 4/ E4.00 FACP HP-1 3 HP-1 3 EMEMSee 5/ E4.00 EX1 A1 FC-3 Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com 1/8" = 1'-0"6/22/2021 4:25:09 PME2.00 Building C Ground & First Floor - Lighting & Fire Alarm STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C 1/8" = 1'-0"1 GROUND FLOOR - LIGHTING & FIRE ALARM 1/8" = 1'-0"2 FIRST FLOOR - LIGHTING & FIRE ALARM Keynote Legend Key Value Keynote Text 1 PROVIDE WEATHERPROOF HORN-STROBE ON BUILDING EXTERIOR. COORDINATE LOCATION WITH LOCAL FIRE DEPARTMENT REQUIREMENTS. 2 PROVIDE FIRE ALARM CONNECTION TO SPRINKLER SYSTEM TAMPER AND FLOW SWITCHES. COORDINATE CONNECTION TYPE AND NUMBER WITH SPRINKLER CONTRACTOR. E2.00 GENERAL NOTES 1. OCCUPANCY SENSOR SHALL BE PROVIDED AT EACH FLOOR LANDING IN EACH STAIRWELL AND SHALL BRING LIGHTS UP TO FULL POWER WHEN TRIGGERED. STAIR OCCUPANCY SENSORS SHALL REDUCE LIGHT LEVELS TO MAX 50% OUTPUT DURING PERIODS OF INACTIVITY. 2. ALL OCCUPANCY/VACANCY SENSORS SHALL BE MANUALLY ADJUSTED TO EXTINGUISH LIGHTS AFTER A PERIOD OF 5 MINUTES OF INACTIVITY. REVISIONS Δ DESCRIPTION DATE SP S P TS FS 1 B G See 4/ E4.00 EMEMSee 5/ E4.00 EX1 HP-1 3 HP-1 3 TS FS G B See 4/ E4.00 See 1/ E4.00 HP-1 3 EMEMEX1 FC-2 1 HP-1 3 Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com 1/8" = 1'-0"6/22/2021 4:25:10 PME2.01 Building C Second, Third & Roof - Lighting & Fire Alarm STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C 1/8" = 1'-0"1 SECOND FLOOR - LIGHITING & FIRE ALARM 1/8" = 1'-0"2 THIRD FLOOR - LIGHTING & FIRE ALARM E2.01 GENERAL NOTES 1. OCCUPANCY SENSOR SHALL BE PROVIDED AT EACH FLOOR LANDING IN EACH STAIRWELL AND SHALL BRING LIGHTS UP TO FULL POWER WHEN TRIGGERED. STAIR OCCUPANCY SENSORS SHALL REDUCE LIGHT LEVELS TO MAX 50% OUTPUT DURING PERIODS OF INACTIVITY. 2. ALL OCCUPANCY/VACANCY SENSORS SHALL BE MANUALLY ADJUSTED TO EXTINGUISH LIGHTS AFTER A PERIOD OF 5 MINUTES OF INACTIVITY. Keynote Legend Key Value Keynote Text 1 PROVIDE FIRE ALARM CONNECTION TO SPRINKLER SYSTEM TAMPER AND FLOW SWITCHES. COORDINATE CONNECTION TYPE AND NUMBER WITH SPRINKLER CONTRACTOR. REVISIONS Δ DESCRIPTION DATE GAG AGAGAAGAGGAT TVTVG A G A G A G A GAA G A TT TVG A G A G A G A A A G A GT TVTV AGAGAGAGAGAG ATVTV GAG A A G A G A G A G A TVTV 1B 1B 16 1B 4 1B 17 1B 14 1B 2 1B 13,15 1 2 1B 10,12 1B 9,11 1B 5,7 1B 3 3 FC-1 1B 18 1B 21 WH-1 76"AFF 76"AFF 4 1B 19 4A 4A 3 4A 19 4A 18 4A 4 4A 13,15 4A 5 4A 14,164A 2 4A 22 4A 17 4A 6,8 4A 10,12 1 4A 7 2 3 FC-1 WH-1 76" AFF 4A 20 76" AFF 4 4A 21 1A 1A 4 1A 17 1A 20 1A 3 1A 16 1A 10,12 1A 181A 14 1A 22 1A 13,15 WH-1 1A 5,7 1A 9,11 1A 19 1A 21 2 FC-1 76"AFF 31A 21 76"AFF 1A 17 4 2B 2B 4 2B 14 2B 20 2B 18 2B 21 2B 10,12 2B 16 2B 22 2B 13,15 2B 21 2B 3 2B 9,11 2B 5,7 2B 19 2B 2 2 1 WH-1 3 76"AFF FC-1 2B 17 2B 14 76"AFF 4 2B 21 76" AFF 76" AFF WH-1 FC-1 2A 2A 9 2A 4 2A 3,5 2A 6 2A 2 2A 12A 7 2A 8 2A 11 2A 12 2A 13,15 2A 14 2A 16,18 2A 10 2A 9 2A 17,19 Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com 1/4" = 1'-0"6/22/2021 4:25:14 PME3.00 Enlarged Unit Plans - Power & Data STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C 1/4" = 1'-0"3 ENLARGED UNIT PLAN 1.1 - POWER & DATA Keynote Legend Key Value Keynote Text 1 RECEPTACLE FOR MICROWAVE/VENT HOOD TO MOUNTED AT 76" AFF, TYP OF ALL. COORDINATE MOUNTING OF RECEPTACLE WITH UPPER CABINETRY INSTALLATION. 2 VERTICAL AIR HANDLER UNIT IS POWERED DIRECTLY FROM OUTDOOR CONDENSING UNIT. WIRING BY MECHANICAL CONTRACTOR. 3 PROVIDE SEPARATE CIRCUIT FOR DUCT HEATING ELEMENT IN APARTMENT UNITS. 4 EC TO RUN COAX CABLE FROM ELECTRIC ROOM TO TV CABLE LOCATIONS IN CLOSETS IN ALL APARTMENTS. TERMINATE CABLE NEXT TO DUPLEX RECEPTACLE. CABLE FURNISHED BY OTHERS. COORDINATE LOCATIONS WITH OWNER. 1/4" = 1'-0"1 ENLARGED UNIT 3.5 - POWER & DATA 1/4" = 1'-0"2 ENLARGED UNIT PLAN 3.2 - POWER & DATA 1/4" = 1'-0"4 ENLARGED UNIT3.3 1. MECHANICAL CONTRACTOR TO FURNISH AC DISCONNECT FOR ALL HVAC EQUIPMENT. ELECTRICAL CONTRACTOR TO INSTALL AND COMPLETE ELECTRICAL CONNECTIONS TO DISCONNECTS AND EQUIPMENT, TYPICAL OF ALL. 2. ELECTRICAL PANELS SHALL BE MOUNTED SUCH THAT THE MIDLINE OF THE HIGHEST BREAKER SHALL BE NO MORE THAN 48" ABOVE FIXED FLOOR, TYPICAL FOR ALL APARTMENTS. 3. MOUNTING HEIGHTS OF DEVICES SHALL BE AS FOLLOWS IN ALL APARTMENTS, UNLESS OTHERWISE NOTED. MEASUREMENTS ARE TO CENTERLINE OF DEVICES: A. CONVENIENCE RECEPTACLES: 18" ABOVE FINISHED FLOOR B. ABOVE COUNTER CONVENIENCE RECEPTACLES: 42" ABOVE FINISHED FLOOR C. ABOVE DESK CONVENIENCE RECEPTACLES: 42" ABOVE FINISHED FLOOR D. LIGHT SWITCHES: MAXIMUM 48" ABOVE FINISHED FLOOR E. DEDICATED EQUIPMENT RECEPTACLES: a. ABOVE COUNTER: 44" ABOVE FINISHED FLOOR b. STANDARD: 18" ABOVE FINISHED FLOOR c. RANGE RECEPTACLE: 6" ABOVE FINISHED FLOOR E3.00 GENERAL NOTES REVISIONS Δ DESCRIPTION DATE 1/4" = 1'-0"5 ENLARGED UNIT 3.4 SP SP J J SP T SP SP SP SP SP J J J 3 TT 3SPJ SP SP SP SP SP SP J JJ J T 33SP SP SP SP SP J J J J SP3 33SP SP SP SP SP SP SP J J J J J EF-1 G G G F G 1 1 G G 1B 1 FC-1 WH-1 G G D G 1B 1 1B 1 4A 1 EF-1 G G F G GG 11 1 G D G 4A G G 1 G 4A 1 4A 1 A1 4A 1 4A 1 1A 1 EF-1 D G G GGG F 111 1 G G G 1A G 2B 1 EF-1 1 G D G G GG G F 1 1 1 G G GGGGGG 2B 1 G 2B 1 2B 1 TO EF-1 2A 20 2A 20 2A 20 2A 20 2A 20 2A 20 2A 20 2A 20 2A 20 1 1 1 1 1 2A Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com 1/4" = 1'-0"6/22/2021 4:25:17 PME4.00 Enlarged Unit Plans - Lighting & Fire Alarm STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C 1/4" = 1'-0"3 ENLARGED UNIT PLAN 1.1 - LIGHTING & FIRE ALARM 1/4" = 1'-0"1 ENLARGED UNIT PLAN 3.5 - LIGHTING & FIRE ALARM 1/4" = 1'-0"2 ENLARGED UNIT PLAN 3.2- LIGHTING & FIRE ALARM 1/4" = 1'-0"4 ENLARGED UNIT PLAN 3.3 - LIGHTING & FIRE ALARM Keynote Legend Key Value Keynote Text 1 PROVIDE WIRING AND BLANK COVER PLATE TO J-BOX LOCATIONS IN ALL BEDROOMS AND BATHROOMS TO ALLOW FOR FUTURE INSTALLATION OF NOTIFICATION DEVICES TO MEET ADA REQUIREMENTS. TYPICAL FOR ALL BEDROOMS. 1. NOTIFICATION DEVICES IN APARTMENTS SHALL TIE INTO BUILDING FIRE ALARM SYSTEM TO ALERT RESIDENTS UPON INITIATIION OF BUILDING FIRE ALARM. 2. MULTISTATION SMOKE ALARMS IN APARTMENTS SHALL BE INDEPENDENT OF BUILDING FIRE ALARM SYSTEM AND ONLY SOUND UPON DETECTION OF SMOKE. 3. ALL LIGHT FIXTURES SHALL BE CENTERED IN THEIR RESPECTIVE ROOMS. 4. COORINATE LOCATION OF SMOKE ALARMS IN MECHANICAL AND PLUMBING CLOSETS WITH OTHER TRADES. E4.00 GENERAL NOTES REVISIONS Δ DESCRIPTION DATE 1/4" = 1'-0"5 ENLARGED UNIT PLAN 3.4 - LIGHTING & FIRE ALARM Project # Date PRICING SETNOT FOR CONSTRUCTION108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com COPYRIGHT STREAM COLLABORATIVE/ TAITEM. ALL RIGHTS RESERVEDA 1 2 3 4 BCD 110 South Albany St. Ithaca, New York 14850 ph: 607.277.1118 www.taitem.com 6/22/2021 4:25:18 PME5.00 Panel Schedules STRM01OVERLOOK 6/22/21Visum Development Group815 South Aurora StreetIthaca, New York 14850Permit Set BUILDING C TYPICAL FOR ALL ELECTRICAL PANELS IN UNIT TYPE 3.2 Notes: Total Amps:142 A 142 A Total Load:14,793 14,810 23 24 21 REC. KITCHEN ABOVE COUNTER (AFCI) 20 A 1 180 360 1 20 A Power - Above Counter (AFCI) 22 19 Power - Fridge (AFCI) 20 A 1 180 180 1 20 A Power - Bedroom (AFCI) 20 17 Power - Entry (AFCI) 20 A 1 720 180 1 20 A Power - Bedroom (AFCI) 18 15 ---- -- 4000 180 1 20 A Power - Washer (AFCI) 16 13 Range 50 A 2 4000 180 1 20 A Power - Bedroom (AFCI) 14 11 ---- -- 2250 3000 -- -- --12 9 Water Heater 30 A 2 2250 3000 2 30 A Dryer 10 7 ---- -- 1500 2080 -- -- --8 5 Duct Heater 20 A 2 1500 2080 2 30 A Heat Pump (Roof) 6 3 Power - Bathroom 20 A 1 180 1260 1 20 A Power - Living Room (AFCI) 4 1 Lighting (AFCI)20 A 1 170 180 1 20 A Power - Microwave (AFCI) 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:1 A Mounting:Recessed Wires:3 Mains Rating:150 A Supply From:A Phases:1 Mains Type:MLO Location:K/L/D 214 Volts:120/208 Single A.I.C. Rating:22K Branch Panel: 1A Notes: Total Amps:136 A 139 A Total Load:14,107 14,450 23 24 21 REC. KITCHEN ABOVE COUNTER (AFCI) 20 A 1 360 22 19 REC. KITCHEN ABOVE COUNTER (AFCI) 20 A 1 180 20 17 Power - Microwave (AFCI) 20 A 1 180 180 1 20 A REC. FRIDGE (AFCI) 18 15 ---- -- 4000 180 1 20 A Power - Washer (AFCI) 16 13 Range 50 A 2 4000 180 1 20 A Power - bedroom (AFCI) 14 11 ---- -- 2250 3000 -- -- --12 9 Water Heater 30 A 2 2250 3000 2 30 A Dryer 10 7 ---- -- 1500 2080 -- -- --8 5 Duct Heater 20 A 2 1500 2080 2 30 A Heat Pump (roof) 6 3 Power - living room (AFCI) 20 A 1 1080 180 1 20 A Power - entry (AFCI) 4 1 Lighting (AFCI)20 A 1 202 180 1 20 A Power (AFCI)2 CKT Circuit Description Trip Poles A C Poles Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:1 A Mounting:Recessed Wires:3 Mains Rating:150 A Supply From:B Phases:1 Mains Type:MLO Location:K/L/D 208 Volts:120/208 Single A.I.C. Rating:22K Branch Panel: 1B TYPICAL FOR AALL ELECTRICAL PANELS IN UNIT TYPE 3.4 Notes: Total Amps:142 A 142 A Total Load:14,781 14,810 23 24 21 REC. HALL (AFCI) 20 A 1 720 360 1 20 A Power - Above Counter (AFCI) 22 19 REC.- Fridge (AFCI) 20 A 1 180 180 1 20 A Power - Bedroom (AFCI) 20 17 REC. KITCHEN ABOVE COUNTER (AFCI) 20 A 1 180 180 1 20 A Power - Bedroom (AFCI) 18 15 ---- -- 4000 180 1 20 A Power - Washer (AFCI) 16 13 Range 50 A 2 4000 180 1 20 A Power - Bedroom (AFCI) 14 11 ---- -- 2250 3000 -- -- --12 9 Water Heater 30 A 2 2250 3000 2 30 A Dryer 10 7 ---- -- 1500 2080 -- -- --8 5 Duct Heater 20 A 2 1500 2080 2 30 A Heat Pump (roof) 6 3 Power - Bathroom 20 A 1 180 1260 1 20 A Power - Living Room (AFCI) 4 1 Lighting (AFCI)20 A 1 159 180 1 20 A Power - Microwave (AFCI) 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:1 A Mounting:Recessed Wires:3 Mains Rating:150 A Supply From:B Phases:1 Mains Type:MLO Location:K/L/D 231 Volts:120/208 Single A.I.C. Rating:22K Branch Panel: 2B Notes: Total Amps:150 A 141 A Total Load:15,726 14,630 23 24 21 REC. BEDROOM, HALL (AFCI) 20 A 1 1080 180 1 20 A Power - Bathroom (AFCI) 22 19 Power - Bedroom (AFCI) 20 A 1 180 180 1 20 A REC. KITCHEN ABOVE COUNTER (AFCI) 20 17 Power - Microwave (AFCI) 20 A 1 180 180 1 20 A Power - Entry (AFCI) 18 15 ---- -- 3000 4000 -- -- --16 13 Dryer 30 A 2 3000 4000 2 50 A Range 14 11 ---- -- 2080 2250 -- -- --12 9 Heat Pump (roof) 30 A 2 2080 2250 2 30 A Water Heater 10 7 Power - Fridge (AFCI) 20 A 1 180 1500 -- -- --8 5 Power - Bedroom (AFCI) 20 A 1 720 1500 2 20 A Duct Heater 6 3 Power - Living Room (AFCI) 20 A 1 1080 180 1 20 A Power - Washer (AFCI) 4 1 Lighting (AFCI)20 A 1 205 360 1 20 A REC. - Above Counter (AFCI) 2 CKT Circuit Description Trip Poles A C Poles Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:1 A Mounting:Recessed Wires:3 Mains Rating:150 A Supply From:A Phases:1 Mains Type:MLO Location:K/L/D 209 Volts:120/208 Single A.I.C. Rating:22K Branch Panel: 4A Notes: Total Amps:42 A 32 A 37 A Total Load:4,981 3,859 4,380 41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26 23 24 21 1981 -- -- --22 19 1981 -- -- --20 17 1981 3 30 A Booster Pump 18 15 180 1 20 A Power - Mech Room 16 13 Power - Roof 20 A 1 180 2039 -- -- --14 11 2039 2 30 A Heat Pump (HP-3) 12 9 375 -- -- --10 7 ERV-1 20 A 1 156 375 2 20 A Electric Baseboard - Mech Room 8 5 Site Lighting 20 A 1 180 180 1 20 A Power - Mech Room 6 3 Lighting (AFCI) 20 A 1 606 720 1 20 A Power - Cooridor 4 1 Fan Coils 20 A 1 60 191 1 20 A Lighting 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:1 A Mounting:Surface Wires:4 Mains Rating:225 A Supply From:Phases:3 Mains Type:MLO Location:Mechanical 101 Volts:120/208 Wye A.I.C. Rating:22K Branch Panel: HP-1 REVISIONS Δ DESCRIPTION DATE Notes: Total Amps:155 A 190 A Total Load:16,098 20,372 23 24 21 22 19 ---- -- 2250 203 1 20 A LIGHTING (AFCI) 20 17 WATER HEATER WH-1 30 A 2 2250 5408 -- -- --18 15 ---- -- 2500 5408 2 30 A FC-1 16 13 DRYER 30 A 2 2500 180 1 20 A REC. WASHING MACHINE (AFCI) 14 11 REC. BED RM, HALL (AFCI) 20 A 1 1260 1440 1 20 A REC. BEDRMS (AFCI) 12 9 REC. CATV / WIFI (AFCI) 20 A 1 360 180 1 20 A REC. BATHROOM (AFCI) 10 7 REC. DINING RM (AFCI) 20 A 1 360 1260 1 20 A REC. LIVING RM, STUDY (AFCI) 8 5 ---- -- 4500 360 1 20 A REC. ABOVE COUNTER (AFCI) 6 3 RANGE 50 A 2 4500 1200 1 20 A REC. MICROWAVE / FAN (AFCI) 4 1 FRIDGE (AFCI) 20 A 1 180 180 1 20 A REC. ABOVE COUNTER (AFCI) 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:1 A Mounting:Recessed Wires:3 Mains Rating:150 A Supply From:Phases:1 Mains Type:MLO Location:K/L/D 232 Volts:120/208 Single A.I.C. Rating:22K Branch Panel: 2A