HomeMy WebLinkAbout2018025- 238 Dryden Rd- ComCheck compliance-report-20210615
2018025 - 238 Dryden Rd- FOR PERMIT - tempered windows and doors.pdf
WH WH DW DW WH UP DW A2031 A202 1 A204 1 1 A301 1 A301 1 A302 1 A302 BEDROOM 2 B105 BATH B108 LIVING/ DINING B102 KITCHEN B101 BEDROOM 1 B103 CLO. B109 STAIR 1 STAIR 2 KITCHEN A101 MECH.
A109 BATH A108 BEDROOM 1 A102 CLO. A104 CLO. A103 BEDROOM 2 A105 BALCONY LIVING/ DINING A106 PATIO UNIT 1A UNIT 1B A201 1 10'-7 1/2" 5'-7 5/8" 5'-6 3/4" 8 1/4" 5'-1 1/4"4'-11 7/8"10'-0"
5'-4 3/4" 6'-1 3/4" 5'-2" 7'-7 1/4" 10'-0 7/8" 12'-5" 7'-6" 16'-2 3/8" 7'-3 3/4" 18'-0" 4'-11 7/8" 5'-0" 13'-10" 13'-0 1/2" 11'-10" 38'-8 1/2" 38'-8 1/2" B103 B101B B101A A101A A101B
A109 A102 A105 100 A102 A105A A106B A105B A106 A106A E3 P1 E3 E3 E3 E3 E3A E3A P2 P1 P1 P4 P4 P1 P1 P1 P1 P1 P1 P1 P1 E4A E4A E3A P1 UP UP DN 11'-1 1/4"4'-7 1/8"11'-1" 10'-7 1/2" 10'-1
1/4" MECH. B107 B105 59'-3 1/4" W/D W/D CLO. B106 B109 B102 B103 B102 A104 A103 5'-5 1/4" B108 B107 B105 B106 P1 4'-0 7/8" 5'-0" 6'-11 3/4" 3'-6" BATH A107 A107 A108 CLO. B104 A106A
2'-1 1/4" 2'-3 3/4" 5'-3 5/8" 2'-10" B104 2'-11" 5'-2 1/4" 5'-5 1/4" A401 4 A401 1 A401 6 30X48 30X48 P9 2'-9 1/4" 2'-9 3/4" P1 P1 P2 P2 P1 R @ 7"18 11" TREAD A506 C1 A506 B2 REF 30X48
AREA OF ASSISTED RESCUE R @ 7"17 11" TREAD R @ 7"18 11" TREAD E3 E3A E3A F4 F4 E2 E2 E3 101 15'-3 1/2" 3'-1 1/2" 3'-10" 102 A2031 A202 1 A204 1 1 A301 1 A301 1 A302 1 A302 CORRIDOR
001 ELECTRICAL 004 SPRINKLER 005 PACKAGE RM 006 STAIR 2 A201 1 13'-9 1/2" 24'-11" 23'-2 3/8" 15'-0 7/8" 38'-3 1/4" 54'-0" VV001B 002 B002001A F1 F1 F1 P4 P4 P9 P1 F2 STORAGE 008 BIKE
RM 003 10'-0" 001 003 004 005 006 9'-10 3/4" 6'-4 3/4" 6'-8 3/8" 8'-6 1/4"12'-8 1/2"9'-3 3/8" 7'-6" 40'-7 3/4" 109.83° 6'-6 3/4" CLEAR 5'-0" 4'-1 7/8" 5'-8 1/4" 6'-0 3/4" 10'-4" CLEAR
5'-0" CLEAR 5'-0" 10'-4 1/8"9'-5" 11'-0 1/2" 30X48 11'-8 3/8" 5'-1 1/4" KITCHEN B005 BATH B007 LIVING B001 BEDROOM B002 CLOSET B003 LIN. B006 CORRIDOR 002 001A 008 B009 W D B007 B006
B002 B003 2'-1 1/4" CLOSET B004 B004 5'-7 1/4" HALL B009 CLO. B008 B008 TRASH 007 13'-9" 8'-7 3/4" 007 16'-5 7/8" VV001C VV001D VV001E 13'-7 5/8" 2'-4 3/4" 6'-6 3/4" 1'-8" MECH 009
009 160.17° E1 E1 P2 P1 P8 P8 P1 P1P2 P2 P8 P9 P4 P1 P2 P2 P2 P2 P2 P1 P1 P1 P1 P1 F1 F1 14'-8 7/8" B001 P1 1'-7 3/4" 3'-8 1/4" P2 Project # Date STREAM Collaborative architecture +
landscape architecture dpc 108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com A 1 2 3 4 BCD 1/4" = 1'-0" 8/2/2021 2:07:42 PM C :\Users\Brandon\Documents\2018025
- 238 Dryden Rd_brandon@streamcolab.com.rvt A101 FLOOR PLANS 2018025 238 DRYDEN RD 8/2/2021 VISUM DEVELOPMENT ITHACA, NY 14850 FOR PERMIT 1/4" = 1'-0"2 1ST FLOOR PLAN 1/4" = 1'-0"1
FLOOR PLAN - BASEMENT REVISIONS Δ DESCRIPTION DATE WH WH DW DW DW WH WH DW DW A2031 A202 1 A204 1 1 A301 1 A301 1 A302 1 A302 BEDROOM 2 B205 BALCONY LIVING/ DINING B202 KITCHEN B201
BEDROOM 1 B203 STAIR 2STAIR 1 CLO. B209 BATH B208 CLO. A209 KITCHEN A201 LIVING/ DINING A206 BATH A208 BEDROOM 1 A202 CLO. A204 CLO. A203 BEDROOM 2 A205 BALCONY UNIT 2B UNIT 2A A201
1 B201B B201A A201A A201B A209 A202 B203 B208 A202 A207 A206B A205A A205B A206 A206A 200 E3 E3 P1 E3 E3 E3A P1 E3A P1 P2 P1 P1 P1 P4 P4 P1 P1 P1 P1 P1 P1 E4A E4 E3A UP DN UP DN MECH.
B207 CLO. B206 B202 B202 B205 B209 B203 B205 B206 B207B208 BATH A207 A203 A204 A205 A207 A208 CLO. B204 B204 A206A 30X48 P9 R @ 7"18 11" TREAD R @ 7"18 11" TREAD P9 R @ 7" 18 11" TREAD
R @ 7"18 11" TREAD 2'-8" 2'-10" A2031 A202 1 A204 1 1 A301 1 A301 1 A302 1 A302 UNIT 3A UNIT 3B LIVING/ DINING B302 KITCHEN B301 BEDROOM 1 B303 CLO. B309 BATH B308 BEDROOM 2 B305 BALCONY
STAIR 1 STAIR 2 KITCHEN A301 LIVING/ DINING A306 BEDROOM 1 A302 CLO. A304 CLO. A303 BEDROOM 2 A305 BATH A307 CLO. A309 BALCONY BATH A308 A201 1 W/D B303 B301B B301A A301A A301B B309
A309 A302 B303 B308 A302 A307 A305A A305B A306 A306A 300 E3 E3 P1 E3 E3 P1 E3A P1 P2 P1 P1 P4 P4 P1 P1 P1 P1 P1 P1 P1 E4A E4 E3A UP DN UP DN W/D MECH. B307 B302 B302 B305 CLO. B304
CLO. B306 B305 B306 B307 B308 A308 A307 A303 A304 A305 A306B A306A B304 30X48 P9R @ 7"18 11" TREAD R @ 7"18 11" TREAD R @ 7"18 11" TREAD R @ 7"18 11" TREAD P9 Project # Date STREAM
Collaborative architecture + landscape architecture dpc 108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com A 1 2 3 4 BCD 1/4" = 1'-0" 8/2/2021 2:07:44
PM C :\Users\Brandon\Documents\2018025 - 238 Dryden Rd_brandon@streamcolab.com.rvt A102 FLOOR PLANS 2018025 238 DRYDEN RD 8/2/2021 VISUM DEVELOPMENT ITHACA, NY 14850 FOR PERMIT 1/4"
= 1'-0"1 2ND FLOOR PLAN 1/4" = 1'-0"2 FLOOR PLAN - 3RD FLOOR REVISIONS Δ DESCRIPTION DATE WH WH DW DW A2031 A202 1 A204 1 1 A301 1 A301 1 A302 1 A302 BALCONY BEDROOM 2 B405 BATH B408
LIVING/ DINING B402 KITCHEN B401 BEDROOM 1 B403 CLO. B409 STAIR 1 STAIR 2 CLO. A409 LIVING/ DINING A406 KITCHEN A401 BEDROOM 1 A402 CLO. A403 BEDROOM 2 A405 BATH A407 BALCONY UNIT 4A
UNIT 4B A201 1 B403 B401B B401A A401A A401B A409 A402 B403 B408 A402 A407 A406B A405A A406 A406A 400 E4 E4 E4 E4 E4 E4A P1 E4A P1 P2 P1 P1 P1 P4 P4 P1 P1 P1 P1 P1 P1 P1 E4A E4 DNDN
CLO. A404 MECH. B407 A405B B402 B402 B405 B409 W/D CLO. B406 BATH A408 B405 B406 B407 B408 A408 A407 A405 A404 A403 CLO. B404 A406A B404 30X48 P9 P2 R @ 7"18 11" TREAD E4A R @ 7"18
11" TREADP9 P1 P1 1 A301 1 A301 1 A302 1 A302 DOWNSPOUT DOWNSPOUT DOWNSPOUT DOWNSPOUT 6FT TALL WOOD SCREENING Project # Date STREAM Collaborative architecture + landscape architecture
dpc 108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com A 1 2 3 4 BCD 1/4" = 1'-0" 8/2/2021 2:07:45 PM C :\Users\Brandon\Documents\2018025 - 238 Dryden
Rd_brandon@streamcolab.com.rvt A103 FLOOR PLANS 2018025 238 DRYDEN RD 8/2/2021 VISUM DEVELOPMENT ITHACA, NY 14850 FOR PERMIT 1/4" = 1'-0"1 FLOOR PLAN - 4TH FLOOR 1/4" = 1'-0"2 ROOF
PLAN REVISIONS Δ DESCRIPTION DATE G1A L Z F LOUVER SAFETY GLAZING NG GLAZING NOT TO EXCEED 100 SQ. IN. NOTE: SOME DOORS MAY BE TWO LEAF PER PLANS Project # Date STREAM Collaborative
architecture + landscape architecture dpc 108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com A 1 2 3 4 BCD 1/4" = 1'-0" 8/2/2021 2:09:28 PM C :\Users\Brandon\Documents
\2018025 - 238 Dryden Rd_brandon@streamcolab.com.rvt A601 DOOR SCHEDULE 2018025 238 DRYDEN RD 8/2/2021 VISUM DEVELOPMENT ITHACA, NY 14850 FOR PERMIT DOOR SCHEDULE MARK TYPE ROOM # ROOM
NAME DESCRIPTION WIDTH HEIGHT FIRE RATING COMMENTS LIGHT VENT B207 A B207 MECH. 2-PANEL MASONITE 5' - 0" 6' - 8" B208 A B202 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" B209 A B209
CLO. 2-PANEL MASONITE 4' - 0" 6' - 8" 3RD SUB FLOOR A301A F STAIR 1 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. A301B F STAIR 2 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6'
- 8" 90 MIN. A302 A A306 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A303 A A303 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" A304 A A304 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" A305 A A306
LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A306 G1 A306 LIVING/ DINING HALF LITE SINGLE INSULATED FIBERGLASS 3' - 0" 8' - 0" A306A A A306 LIVING/ DINING 2-PANEL MASONITE 2' - 2"
6' - 8" A307 A A307 BATH 2-PANEL MASONITE 3' - 0" 6' - 8" A308 A A308 BATH 2-PANEL MASONITE 3' - 0" 6' - 8" A309 A A309 CLO. 2-PANEL MASONITE 5' - 0" 6' - 8" B301A F STAIR 1 FLUSH PANEL-
METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B301B F STAIR 2 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B302 G1 B302 LIVING/ DINING HALF LITE SINGLE INSULATED FIBERGLASS
3' - 0" 8' - 0" B303 A B301 KITCHEN 2-PANEL MASONITE 3' - 0" 6' - 8" B304 A B303 BEDROOM 1 2-PANEL MASONITE 4' - 0" 6' - 8" B305 A B302 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' -
8" B306 A B306 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" B307 A B307 MECH. 2-PANEL MASONITE 5' - 0" 6' - 8" B308 A B302 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" B309 A B309 CLO.
2-PANEL MASONITE 4' - 0" 6' - 8" 4TH SUB FLOOR A401A F STAIR 1 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. A401B F STAIR 2 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8"
90 MIN. A402 A A406 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A403 A A403 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" A404 A A404 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" A405 A A406 LIVING/
DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A406 G1 A406 LIVING/ DINING HALF LITE SINGLE INSULATED FIBERGLASS 3' - 0" 7' - 0" A406A A A406 LIVING/ DINING 2-PANEL MASONITE 2' - 2" 6' - 8"
A407 A A407 BATH 2-PANEL MASONITE 3' - 0" 6' - 8" A408 A A401 KITCHEN 2-PANEL MASONITE 3' - 0" 6' - 8" A409 A A409 CLO. 2-PANEL MASONITE 5' - 0" 6' - 8" B401A F STAIR 1 FLUSH PANEL-
METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B401B F STAIR 2 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B402 G1 B402 LIVING/ DINING HALF LITE SINGLE INSULATED FIBERGLASS
3' - 0" 7' - 0" B403 A B401 KITCHEN 2-PANEL MASONITE 3' - 0" 6' - 8" B404 A B403 BEDROOM 1 2-PANEL MASONITE 4' - 0" 6' - 8" B405 A B402 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' -
8" B406 A B406 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" B407 A B407 MECH. 2-PANEL MASONITE 5' - 0" 6' - 8" B408 A B402 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" B409 A B409 CLO.
2-PANEL MASONITE 4' - 0" 6' - 8" DOOR SCHEDULE MARK TYPE ROOM # ROOM NAME DESCRIPTION WIDTH HEIGHT FIRE RATING COMMENTS LIGHT VENT BASEMENT SLAB 001 G 001 CORRIDOR FULL LITE STEEL DOOR
3' - 0" 7' - 0" 001A N 001 CORRIDOR FLUSH PANEL NARROW LITE- METAL HOLLOW FRAME 3' - 0" 6' - 8" 002 N 002 CORRIDOR FLUSH PANEL NARROW LITE- METAL HOLLOW FRAME 3' - 0" 6' - 8" 003 F
002 CORRIDOR FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 20 MIN. 004 F 005 SPRINKLER FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 20 MIN. 005 F 005 SPRINKLER FLUSH PANEL- METAL
HOLLOW FRAME 3' - 0" 6' - 8" 20 MIN. 006 F 002 CORRIDOR FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 20 MIN. 007 F 002 CORRIDOR FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 20
MIN. 008 F 002 CORRIDOR FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 20 MIN. 009 L 009 MECH FLUSH PANEL HALF LOUVER- METAL HOLLOW FRAME 3' - 0" 6' - 8" B001 G B001 LIVING FULL LITE
STEEL DOOR 3' - 0" 7' - 0" B002 A B001 LIVING 2-PANEL MASONITE 3' - 0" 6' - 8" B003 A B002 BEDROOM 2-PANEL MASONITE 3' - 0" 6' - 8" B004 A B004 CLOSET 2-PANEL MASONITE 3' - 0" 6' -
8" B006 A B006 LIN. 2-PANEL MASONITE 4' - 0" 6' - 8" B007 A B009 HALL 2-PANEL MASONITE 3' - 0" 6' - 8" B008 A B008 CLO. 2-PANEL MASONITE 4' - 0" 6' - 8" B009 F 002 CORRIDOR FLUSH PANEL-
METAL HOLLOW FRAME 3' - 0" 6' - 8" 20 MIN. 1ST SUB FLOOR 100 G1 STAIR 1 HALF LITE SINGLE INSULATED FIBERGLASS 3' - 0" 8' - 0" 101 G1 STAIR 2 HALF LITE SINGLE INSULATED FIBERGLASS 3'
- 0" 8' - 0" 102 Z STAIR 2 STAIRWAY INTERRUPTION GATE 3' - 6" 2' - 10" A101A F STAIR 1 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. A101B F STAIR 2 FLUSH PANEL- METAL HOLLOW
FRAME 3' - 0" 6' - 8" 90 MIN. A102 A A106 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A103 A A103 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" A104 A A104 CLO. 2-PANEL MASONITE 2' - 8"
6' - 8" A105 A A106 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A106 G1 A106 LIVING/ DINING HALF LITE SINGLE INSULATED FIBERGLASS 3' - 0" 8' - 0" A106A A B410 WH 2-PANEL MASONITE
2' - 2" 6' - 8" A107 A A107 BATH 2-PANEL MASONITE 3' - 0" 6' - 8" A108 A A101 KITCHEN 2-PANEL MASONITE 3' - 0" 6' - 8" A109 A A109 MECH. 2-PANEL MASONITE 5' - 0" 6' - 8" B101A F STAIR
1 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B101B F STAIR 2 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B102 G1 B102 LIVING/ DINING HALF LITE SINGLE INSULATED
FIBERGLASS 3' - 0" 8' - 0" B103 A B102 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" B104 A B103 BEDROOM 1 2-PANEL MASONITE 4' - 0" 6' - 8" B105 A B102 LIVING/ DINING 2-PANEL MASONITE
3' - 0" 6' - 8" B106 A B106 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" B107 A B107 MECH. 2-PANEL MASONITE 5' - 0" 6' - 8" B108 A B102 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" B109
A B109 CLO. 2-PANEL MASONITE 4' - 0" 6' - 8" 2ND SUB FLOOR A201A F STAIR 1 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. A201B F STAIR 2 FLUSH PANEL- METAL HOLLOW FRAME 3'
- 0" 6' - 8" 90 MIN. A202 A A206 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A203 A A203 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" A204 A A204 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8"
A205 A A206 LIVING/ DINING 2-PANEL MASONITE 3' - 0" 6' - 8" A206 G1 A206 LIVING/ DINING HALF LITE SINGLE INSULATED FIBERGLASS 3' - 0" 8' - 0" A206A A A206 LIVING/ DINING 2-PANEL MASONITE
2' - 2" 6' - 8" A207 A A207 BATH 2-PANEL MASONITE 3' - 0" 6' - 8" A208 A A201 KITCHEN 2-PANEL MASONITE 3' - 0" 6' - 8" A209 A A209 CLO. 2-PANEL MASONITE 5' - 0" 6' - 8" B201A F STAIR
1 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B201B F STAIR 2 FLUSH PANEL- METAL HOLLOW FRAME 3' - 0" 6' - 8" 90 MIN. B202 G1 B202 LIVING/ DINING HALF LITE SINGLE INSULATED
FIBERGLASS 3' - 0" 8' - 0" B203 A B201 KITCHEN 2-PANEL MASONITE 3' - 0" 6' - 8" B204 A B203 BEDROOM 1 2-PANEL MASONITE 4' - 0" 6' - 8" B205 A B202 LIVING/ DINING 2-PANEL MASONITE 3'
- 0" 6' - 8" B206 A B206 CLO. 2-PANEL MASONITE 2' - 8" 6' - 8" REVISIONS Δ DESCRIPTION DATE 1/4" = 1'-0" DOOR TYPES Project # Date STREAM Collaborative architecture + landscape architecture
dpc 108 W. State St. Fl 2 Ithaca, New York 14850 ph: 607.216.8802 www.streamcolab.com A 1 2 3 4 BCD 11/8/2021 9:28:52 AMC:\Users\Brandon\Documents\2018025 - 238 Dryden Rd_brandon@streamcolab.com.rvt
A602 WINDOW SCHEDULE 2018025 238 DRYDEN RD 8/2/2021 VISUM DEVELOPMENT ITHACA, NY 14850 FOR PERMIT WINDOW SCHEDULE MARK ROOM NUMBER ROOM NAME UNIT WIDTH UNIT HEIGHT SILL HEIGHT HEAD
HEIGHT OPERATION COMMENTS FALL PROTECTION TEMPERED B105 B105 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No Yes BASEMENT SLAB 001A B001 LIVING 2' - 6" 5' - 0" 2' - 0" 7' - 0"
CASEMENT No Yes 001B B001 LIVING 2' - 6" 5' - 0" 2' - 0" 7' - 0" FIXED No 001C B001 LIVING 2' - 6" 5' - 0" 2' - 0" 7' - 0" FIXED No 001D B001 LIVING 2' - 6" 5' - 0" 2' - 0" 7' - 0"
FIXED No 001E B001 LIVING 2' - 6" 5' - 0" 2' - 0" 7' - 0" FIXED No B002 B002 BEDROOM 2' - 6" 5' - 0" 2' - 0" 7' - 0" CASEMENT No 1ST SUB FLOOR A102 A102 BEDROOM 1 2' - 8" 5' - 0" 3'
- 0" 8' - 0" CASEMENT No Yes A105A A105 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A105B A105 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A106A A106 LIVING/ DINING
3' - 0" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A106B A106 LIVING/ DINING 3' - 0" 5' - 0" 3' - 0" 8' - 0" CASEMENT No B102 B102 LIVING/ DINING 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No
Yes B103 B103 BEDROOM 1 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No 2ND SUB FLOOR 200 STAIR 1 2' - 0" 4' - 0" 4' - 0" 8' - 0" FIXED No Yes A202 A202 BEDROOM 1 2' - 8" 5' - 0" 3' - 0"
8' - 0" CASEMENT No Yes A205A A205 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A205B A205 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A206A A206 LIVING/ DINING 3'
- 0" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A206B A206 LIVING/ DINING 3' - 0" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A207 A207 BATH 2' - 0" 4' - 0" 4' - 0" 8' - 0" FIXED No B202 B202 LIVING/
DINING 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No Yes B203 B203 BEDROOM 1 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No B205 B205 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No
Yes B208 B208 BATH 2' - 0" 4' - 0" 4' - 0" 8' - 0" FIXED No 3RD SUB FLOOR 300 STAIR 1 2' - 0" 4' - 0" 4' - 0" 8' - 0" FIXED No Yes A302 A302 BEDROOM 1 2' - 8" 5' - 0" 3' - 0" 8' - 0"
CASEMENT No Yes A305A A305 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A305B A305 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A306A A306 LIVING/ DINING 3' - 0" 5'
- 0" 3' - 0" 8' - 0" CASEMENT No A306B A306 LIVING/ DINING 3' - 0" 5' - 0" 3' - 0" 8' - 0" CASEMENT No A307 A307 BATH 2' - 0" 4' - 0" 4' - 0" 8' - 0" FIXED No B302 B302 LIVING/ DINING
2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No Yes B303 B303 BEDROOM 1 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No B305 B305 BEDROOM 2 2' - 8" 5' - 0" 3' - 0" 8' - 0" CASEMENT No Yes B308
B308 BATH 2' - 0" 4' - 0" 4' - 0" 8' - 0" FIXED No 4TH SUB FLOOR 400 STAIR 1 2' - 0" 4' - 0" 4' - 0" 8' - 0" FIXED No Yes A402 A402 BEDROOM 1 2' - 8" 4' - 10" 3' - 0" 7' - 10" CASEMENT
No Yes A405A A405 BEDROOM 2 2' - 8" 4' - 10" 3' - 0" 7' - 10" CASEMENT No A405B A405 BEDROOM 2 2' - 8" 4' - 10" 3' - 0" 7' - 10" CASEMENT No A406A A406 LIVING/ DINING 2' - 8" 4' - 10"
3' - 0" 7' - 10" CASEMENT No A406B A406 LIVING/ DINING 2' - 8" 4' - 10" 3' - 0" 7' - 10" CASEMENT No A407 A407 BATH 2' - 0" 4' - 0" 3' - 10" 7' - 10" FIXED No B402 B402 LIVING/ DINING
2' - 8" 4' - 10" 3' - 0" 7' - 10" CASEMENT No Yes B403 B403 BEDROOM 1 2' - 8" 4' - 10" 3' - 0" 7' - 10" CASEMENT No Yes B405 B405 BEDROOM 2 2' - 8" 4' - 10" 3' - 0" 7' - 10" CASEMENT
No Yes B408 B408 BATH 2' - 0" 4' - 0" 3' - 10" 7' - 10" FIXED No REVISIONS Δ DESCRIPTION DATE
2018025 - 238 Dryden Rd SITE - SPR-FIRE APPARATUS ACCESS-2019.12.03.pdf U:\2018025 - 238 Dryden Rd - Visum\06.0 DRAWINGS\06.1 REVIT\2018025 - 232-236-238 Dryden Rd SITE - SPR_brandon@streamcolab.pdf
S 83°39'27" E 25.00' N 06°25'17" E 120.03' N 83°15'47" W 25.00' N 06°25'17" E 66.40' 6 " C . I . 1 " C O P P E R 6 " C . I . 6 " C . I . 2" COPPER 4" C.I. 4" C.I. 12" CT 4 " C T 8" TRANS
12" C.I. P O R C H B L D G . N o . 3 2 0 A P M T . HOUSE BUILDING BUILDING No. 116 BUILDING HOUSE No. 228 DRYDEN ROAD AVENUE S U M M I T A V E N U E PIN FOUND PIN SET NAIL SET PIPE
FOUND 1'± NLY OF COR. 1 0 . 0 0 ' COR. CONC. WALL ON P L 4.74' L FOUND BENT PIPE 2 0 1 4 0 0 2 3 1 S E E I n s t . N o . T I E = N 0 6 ° 3 7 ' 1 2 ' ' E 1 4 3 . 6 9 ' N 62°15'09'' W
53.60' S 0 7 ° 0 0 ' 1 5 ' ' W 9 6 . 4 3 ' S 06°40'32" W 120.75' N 06°40'32" E 242.09' S 83°15'47" E 158.54' S 06°25'17" W 120.20' N 83°39'27" W 89.74'R&M S 06°25'17" W 66.26' S 83°19'14"
E 25.00' S 76°28'40" E 25.18' S 06°40'46" W 85.80' N 63°44'45" W 132.19' N 06°07'38" E 110.32' R&M 4.74' F O R I N G R E S S & E G R E S S 1 0 ' W I D E R . O . W . AREA "A" AREA=0.069
ACRES P I P E F O U N D 0 . 6 ' ± W L Y O F P L 65.05' (P TO P) AREA "B"AR EA=0.038 ACRES E L E C T R I C T R A N S F O R M E R N Y S E G E A S E M E N T S E E 2 0 1 8 0 4 8 6 5 E.E.=781.03
E.E.=793.86 E.E.=793.86 E.E.=795.00 E.E.=795.00 HH H H C.O. C.O. C.O. C.O. M B E E DRYDEN ROAD 114 SUMMIT 112 SUMMIT FIRE LANE DUMPSTER ENCLOSURE P-2 P-2 P-2 P-2 20.00' P-2 P-2 N 5109.77'
E 4701.92' W1 CONC. LAWN LAWN CONC. ASPHALT LAWN PLANT PLANT PLANT CONC. LAWN LAWN LAWN L1 L1 L201 A2 LAWN 24"X42" INTERPRETIVE SIGN PANEL / C1L502 L1 5.00' L201 L201 L201 238 DRYDEN
793.25 C1 A3 A1 788.44 781.4 15'-0 1/4" 2 0 ' 0 " RETAINING WALL RETAINING WALL RETAINING WALL BIKE RACKS TERRACE, RECESSED IN WELL 5'-0" 1 0 ' 0 " RAMP RAMP EXISTING BUILDING EXISTING
BUILDING PROPOSED BUILDING LAWN Project # Date PRELIMINARY NOT FOR CONSTRUCTION STREAM Collaborative architecture + landscape architecture dpc 108 W. State St. Fl 2 Ithaca, New York
14850 ph: 607.216.8802 www.streamcolab.com A 1 2 3 4 B C D 1" = 20'-0" 12/3/2019 10:40:23 AMC:\Users\Brandon\Documents\2018025 - 232-236-238 Dryden Rd SITE - SPR_brandon@streamcolab.com.rvt
L101 SITE LAYOUT PLAN 2018025 238 DRYDEN ROAD DEC. 3, 2019 VISUM DEVELOPMENT CITY OF ITHACA, NY SCHEMATIC DESIGN 1" = 20'-0" C1 LAYOUT PLAN 0'20' 10' GENERAL SHEET NOTES - LAYOUT 1.
GENERAL CONTRACTOR SHALL NOTIFY ALL UTILITY OWNERS HAVING UNDERGROUND UTILITIES ON SITE PRIOR TO EXCAVATION. CONTRACTOR SHALL CONTACT UTILITY LOCATING COMPANY AND LOCATE ALL UTILITIES
PRIOR TO ANY EXCAVATION. 2. SEE CIVIL DRAWINGS FOR LAYOUT OF UNDERGROUND UTILITIES. 3. SEE ELECTRICAL DRAWINGS FOR LAYOUT OF UNDERGROUND ELECTRICAL AND LIGHTING. 4. ALL WALKS ARE 4"
MEDIUM DUTY CONCRETE UNLESS NOTED OTHERWISE. 5. INSTALL EXPANSION JOINTS EVERY 30' IN CONCRETE AND IN AREAS WHERE CONCRETE ABUTS CURBS AND OTHER FIXED OBJECTS. 6. VERIFY DIMENTIONS
AND ACCEPT CONDITIONS BEFORE PROCEEDING WITH WORK. REPORT DISCREPANCIES TO LANDSCAPE ARCHITECT BEFORE PROCEEDING. 7. DO NOT SCALE FROM MEASURING DRAWINGS. 8. WALKS, DRIVES, CURBS,
PARKING, & BUILDING LOCATIONS TO BE LAID OUT IN THE FIELD BY A LICENSED SURVEYOR. 9. DIMENSIONS TO CURBS ARE TO EXPOSED FACES UNLESS OTHERWISE NOTED. REVISIONS ΔDESCRIPTIONDATE 92'-4"
46'-1" 14'-5" 24'-6" 10'-5" PROPERTY LINE
2018025- 238 Dryden Rd- ComCheck compliance-report-20210615.pdf
COMcheck Software Version 4.1.5.1 Envelope Compliance Certificate Project Title: 2018 IECC Project Type: New Construction Permit No. 38763 Vertical Glazing / Wall Area: 6% Location:
Ithaca, New York Climate Zone: 6a Construction Site: 238 Dryden Rd Ithaca, NY 14850 Owner/Agent: Todd Fox Visum Development 119 S. Cayuga St 3rd floor Ithaca, NY 14850 607-269-7300
todd@visumdevelopment.com Designer/Contractor: Noah Demarest STREAM Collaborative 108 W. State St 2nd floor Ithaca, NY 14850 607-216-8802 noah@streamcolab.com Project Information Energy
Code: 238 Dryden Rd Enhanced Interior Lighting Controls Additional Efficiency Package(s) Building Area Floor Area 1-Multifamily : Residential 9657 Envelope Assemblies Assembly Cavity
R-Value Cont. R-Value Proposed U-Factor Budget UFactor(a) Gross Area or Perimeter basement slab: Slab-On-Grade:Heated Fully Insulated (user specified perimeter R-value + R-10.0 under
slab), [Bldg. Use 1 - Multifamily] (d) 180 --- 12.5 0.530 0.602 NORTH basement north icf: Solid Concrete:8" Thickness, Normal Density, Furring: None, [Bldg. Use 1 - Multifamily] 401
--- 22.0 0.042 0.071 wood framed north wall: Wood-Framed, 16" o.c., [Bldg. Use 1 Multifamily] 1613 30.0 0.0 0.053 0.051 Window 1 copy 1: Vinyl/Fiberglass Frame:Operable, Perf. Specs.:
Product ID INTERTEK LPB/WPPS-60-01, SHGC 0.28, VT 0.48, [Bldg. Use 1 - Multifamily] (c) 106 --- --- 0.270 0.430 Door 4: Other Door, Swinging, [Bldg. Use 1 - Multifamily] 93 --- ---
0.230 0.370 EAST basement east icf: Solid Concrete:8" Thickness, Normal Density, Furring: None, [Bldg. Use 1 - Multifamily] 554 --- 22.0 0.042 0.071 Door 3: Other Door, Swinging, [Bldg.
Use 1 - Multifamily] 15 --- --- 0.230 0.370 wood framed east wall: Wood-Framed, 16" o.c., [Bldg. Use 1 Multifamily] 2465 30.0 0.0 0.053 0.051 Window 1 copy 2: Vinyl/Fiberglass Frame:Operable,
Perf. Specs.: Product ID INTERTEK LPB/WPPS-60-01, SHGC 0.28, VT 0.48, [Bldg. Use 1 - Multifamily] (c) 159 --- --- 0.270 0.430 Door 4 copy 1: Other Door, Swinging, [Bldg. Use 1 - Multifamily]
8 --- --- 0.230 0.370 Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 201 ofPage Assembly Cavity
R-Value Cont. R-Value Proposed U-Factor Budget UFactor(a) Gross Area or Perimeter SOUTH basement south wood framed: Wood-Framed, 16" o.c., [Bldg. Use 1 Multifamily] 130 30.0 0.0 0.053
0.051 Window 2: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID INTERTEK LPB/WPPS-60-01, SHGC 0.28, VT 0.48, [Bldg. Use 1 Multifamily] (c) 25 --- --- 0.270 0.430 Door 1: Other
Door, Swinging, [Bldg. Use 1 - Multifamily] 21 --- --- 0.230 0.370 Door 2: Other Door, Swinging, [Bldg. Use 1 - Multifamily] 21 --- --- 0.230 0.370 basement southwest wood framed: Wood-Framed,
16" o.c., [Bldg. Use 1 - Multifamily] 96 30.0 0.0 0.053 0.051 Window 1: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID INTERTEK LPB/WPPS-60-01, SHGC 0.28, VT 0.48, [Bldg.
Use 1 Multifamily] (c) 50 --- --- 0.270 0.430 wood framed south wall: Wood-Framed, 16" o.c., [Bldg. Use 1 Multifamily] 1662 30.0 0.0 0.053 0.051 Window 1 copy 4: Vinyl/Fiberglass Frame:Operable,
Perf. Specs.: Product ID INTERTEK LPB/WPPS-60-01, SHGC 0.28, VT 0.48, [Bldg. Use 1 - Multifamily] (c) 169 --- --- 0.270 0.430 Door 7: Other Door, Swinging, [Bldg. Use 1 - Multifamily]
72 --- --- 0.230 0.370 WEST basement west icf: Solid Concrete:8" Thickness, Normal Density, Furring: None, [Bldg. Use 1 - Multifamily] 488 --- 22.0 0.042 0.071 wood framed west wall:
Wood-Framed, 16" o.c., [Bldg. Use 1 Multifamily] 2280 30.0 0.0 0.053 0.051 Window 1 copy 3: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID INTERTEK LPB/WPPS-60-01, SHGC 0.28,
VT 0.48, [Bldg. Use 1 - Multifamily] (c) 72 --- --- 0.270 0.430 Door 4 copy 2: Other Door, Swinging, [Bldg. Use 1 - Multifamily] 24 --- --- 0.230 0.370 (a) Budget U-factors are used
for software baseline calculations ONLY, and are not code requirements. (b) 'Other' components require supporting documentation for proposed U-factors. (c) Fenestration product performance
must be certified in accordance with NFRC and requires supporting documentation. (d) Slab-On-Grade proposed and budget U-factors shown in table are F-factors. Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit
application. The proposed envelope systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any applicable mandatory requirements
listed in the Inspection Checklist. Name - Title Signature Date Envelope PASSES: Design 18% better than code Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd -
Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 202 ofPage COMcheck Software Version 4.1.5.1 Interior Lighting Compliance Certificate Project Title: 2018 IECC Project
Type: New Construction Permit No. 38763 Construction Site: 238 Dryden Rd Ithaca, NY 14850 Owner/Agent: Todd Fox Visum Development 119 S. Cayuga St 3rd floor Ithaca, NY 14850 607-269-7300
todd@visumdevelopment.com Designer/Contractor: Noah Demarest STREAM Collaborative 108 W. State St 2nd floor Ithaca, NY 14850 607-216-8802 noah@streamcolab.com Project Information Energy
Code: 238 Dryden Rd Enhanced Interior Lighting Controls Additional Efficiency Package(s) Allowed Interior Lighting Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed
Watts (B X C) 1-Multifamily 9657 0.68 6567 6567Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp
/ Ballast B Lamps/ Fixture C # of Fixtures 1-Multifamily LED 1: B: WALL MOUNT STRIP LIGHT: LED Linear 10W: 1 17 10 170 LED 2: H: DOWN LIGHT: LED MR 10W: 1 12 10 120 LED 3: D: PENDANT:
LED Other Fixture Unit 60W: 1 4 60 240 LED 4: F: VANITY LIGHT: LED Linear 11W: 1 13 12 156 LED 5: G: ROUND FLUSH MOUNT: LED Panel 60W: 1 64 60 3840 LED 6: J: WALL STRIP: LED Linear
10W: 1 7 10 70 LED 7: EM1: EMERGENCY LIGHT: LED A Lamp 2.5W: 1 18 2 36 LED 8: EM2: EMERGENCY EXIT LIGHT/SIGN: LED A Lamp 2.5W: 1 3 2 6 4638Total Proposed Watts = Interior Lighting Compliance
Statement Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted
with this permit application. The proposed interior lighting systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist. Interior Lighting PASSES: Design 29% better than code Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden
Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 203 ofPage Name - Title Signature Date Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0
APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 204 ofPage COMcheck Software Version 4.1.5.1 Exterior Lighting Compliance Certificate Project Title: 2018 IECC Project Type: New
Construction Permit No. 38763 Construction Site: 238 Dryden Rd Ithaca, NY 14850 Owner/Agent: Todd Fox Visum Development 119 S. Cayuga St 3rd floor Ithaca, NY 14850 607-269-7300 todd@visumdevelopment
.com Designer/Contractor: Noah Demarest STREAM Collaborative 108 W. State St 2nd floor Ithaca, NY 14850 607-216-8802 noah@streamcolab.com Project Information Energy Code: 238 Dryden
Rd 2 (Residential mixed use area)Exterior Lighting Zone Allowed Exterior Lighting Power A Area/Surface Category B Quantity C Allowed Watts / Unit D Tradable Wattage E Allowed Watts
(B X C) EM EGRESS (Pedestrian and vehicular entrances and exits) 6 ft of door 14 Yes 84 PATIOS/BALCONY (Pedestrian and vehicular entrances and exits) 9 ft of door 14 Yes 126 Total Tradable
Watts (a) = Total Allowed Watts = Total Allowed Supplemental Watts (b) = 210 210 400 (a) Wattage tradeoffs are only allowed between tradable areas/surfaces. (b) A supplemental allowance
equal to 400 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. Proposed Exterior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description
/ Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures EM EGRESS ( Pedestrian and vehicular entrances and exits 6 ft of door width): Tradable Wattage LED 1: K: EM EGRESS:
LED Other Fixture Unit 16W: 1 6 14 84 PATIOS/BALCONY ( Pedestrian and vehicular entrances and exits 9 ft of door width): Tradable Wattage LED 2: L1: BALCONY: LED Other Fixture Unit
13W: 1 9 9 81 165Total Tradable Proposed Watts = Exterior Lighting Compliance Statement Compliance Statement: The proposed exterior lighting design represented in this document is
consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been designed to meet
the 2018 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Exterior
Lighting PASSES: Design 73% better than code Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date:
205 ofPage COMcheck Software Version 4.1.5.1 Mechanical Compliance Certificate Project Title: 2018 IECC Project Type: New Construction Permit No. 38763 Location: Ithaca, New York Climate
Zone: 6a Construction Site: 238 Dryden Rd Ithaca, NY 14850 Owner/Agent: Todd Fox Visum Development 119 S. Cayuga St 3rd floor Ithaca, NY 14850 607-269-7300 todd@visumdevelopment.com
Designer/Contractor: Noah Demarest STREAM Collaborative 108 W. State St 2nd floor Ithaca, NY 14850 607-216-8802 noah@streamcolab.com Project Information Energy Code: 238 Dryden Rd Enhanced
Interior Lighting Controls Additional Efficiency Package(s) Mechanical Systems List Quantity System Type & Description Split System Heat Pump Heating Mode: Capacity = 15 kBtu/h,
Proposed Efficiency = 11.40 HSPF, Required Efficiency = 8.20 HSPF Cooling Mode: Capacity = 13 kBtu/h, Proposed Efficiency = 22.00 SEER, Required Efficiency: 14.00 SEER Fan System:
Ducted Unit -- Compliance (Motor nameplate HP method) : Passes Fans: FAN 1 Supply, Constant Volume, 445 CFM, 1.0 motor nameplate hp, 50.0 fan efficiency grade 9 HVAC System 1 (Single
Zone): Mechanical Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications, and
other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.1 and to comply
with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0
APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 206 ofPage Inspection Checklist Requirements: 100.0% were addressed directly in the COMcheck software COMcheck Software Version 4.1.5.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and
how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2018 IECC Section
# & Req.ID Plan Review Complies? Comments/Assumptions C103.2 [PR1]1 Plans and/or specifications provide all information with which compliance can be determined for the building envelope
and document where exceptions to the standard are claimed. Complies Does Not Not Observable Not Applicable Requirement will be met. C103.2 [PR2]1 Plans, specifications, and/or calculations
provide all information with which compliance can be determined for the mechanical systems and equipment and document where exceptions to the standard are claimed. Load calculations
per acceptable engineering standards and handbooks. Complies Does Not Not Observable Not Applicable Requirement will be met. C103.2 [PR4]1 Plans, specifications, and/or calculations
provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and document where exceptions to the standard are claimed.
Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Complies Does Not Not Observable Not Applicable
Requirement will be met. C103.2 [PR8]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the exterior lighting and electrical
systems and equipment and document where exceptions to the standard are claimed. Information provided should include exterior lighting power calculations, wattage of bulbs and ballasts,
transformers and control devices. Complies Does Not Not Observable Not Applicable Requirement will be met. C402.4.1 [PR10]1 The vertical fenestration area <= 30 percent of the gross
above-grade wall area. Complies Does Not Not Observable Not Applicable Requirement will be met. C402.4.1 [PR11]1 The skylight area <= 3 percent of the gross roof area. Complies Does
Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025
- 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 207 ofPage Section # & Req.ID Plan Review Complies? Comments/Assumptions C405.5 [PR16]1 Group R-2 dwelling
units have separate electrical meters. Complies Does Not Not Observable Not Applicable Requirement will be met. C406 [PR9]1 Plans, specifications, and/or calculations provide all information
with which compliance can be determined for the additional energy efficiency package options. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions
: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck
06/15/21Report date: 208 ofPage Section # & Req.ID Footing / Foundation Inspection Complies? Comments/Assumptions C303.2 [FO4]2 Slab edge insulation installed per manufacturer’s instructions.
Complies Does Not Not Observable Not Applicable Requirement will be met. C303.2.1 [FO6]1 Exterior insulation protected against damage, sunlight, moisture, wind, landscaping and equipment
maintenance activities. Complies Does Not Not Observable Not Applicable Requirement will be met. C105 [FO3]2 Installed slab-on-grade insulation type and R-value consistent with insulation
specifications reported in plans and COMcheck reports. Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.2.4 [FO7]2 Slab edge insulation
depth/length. Slab insulation extending away from building is covered by pavement or >= 10 inches of soil. Complies Does Not Not Observable Not Applicable Requirement will be met. See
the Envelope Assemblies table for values. C402.2.6 [FO12]3 Radiant heating systems panels insulated to >=R-3.5 on face opposite space being heated. Complies Does Not Not Observable
Not Applicable Exception: Requirement does not apply. See the Envelope Assemblies table for values. C403.12.2 , C403.12.3 [FO9]3 Snow/ice melting system and freeze protection systems
have sensors and controls configured to limit service for pavement temperature and outdoor temperature. future connection to controls. Complies Does Not Not Observable Not Applicable
Exception: Requirement does not apply. Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden
Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 209 ofPage Section # & Req.ID Framing / Rough-In Inspection Complies? Comments/Assumptions
C303.1.3 [FR12]2 Fenestration products rated in accordance with NFRC. Complies Does Not Not Observable Not Applicable Requirement will be met. C303.1.3 [FR13]1 Fenestration products
are certified as to performance labels or certificates provided. Complies Does Not Not Observable Not Applicable Requirement will be met. C402.4.3 [FR10]1 Vertical fenestration SHGC
value. Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.4.3, C402.4.3. 4 [FR8]1 Vertical fenestration U-Factor. Complies Does Not Not
Observable Not Applicable See the Envelope Assemblies table for values. C402.4.4 [FR14]2 U-factor of opaque doors associated with the building thermal envelope meets requirements. Complies
Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.5.1. 2.1 [FR19]1 The building envelope contains a continuous air barrier that is sealed in
an approved manner and material permeability <= 0.004 dfm/ft2. Air barrier penetrations are sealed in an approved manner. Complies Does Not Not Observable Not Applicable Requirement
will be met. C402.5.2, C402.5.4 [FR18]3 Factory-built fenestration and doors are labeled as meeting air leakage requirements. Complies Does Not Not Observable Not Applicable Requirement
will be met. C402.5.7 [FR17]3 Vestibules are installed on all building entrances. Doors have self-closing devices. Complies Does Not Not Observable Not Applicable Exception: Doors that
open directly from a space =3000 ft2. Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden
Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 2010 ofPage Section # & Req.ID Plumbing Rough-In Inspection Complies? Comments/Assumptions
C404.5, C404.5.1, C404.5.2 [PL6]3 Heated water supply piping conforms to pipe length and volume requirements. Refer to section details. Complies Does Not Not Observable Not Applicable
Exception: Requirement does not apply. C404.6.3 [PL7]3 Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after
end of heating cycle. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C404.7 [PL8]3 Demand recirculation water systems have controls that start
the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F. Complies Does Not
Not Observable Not Applicable Exception: Requirement does not apply. Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title:
Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 2011 ofPage Section # & Req.ID Mechanical Rough-In Inspection
Complies? Comments/Assumptions C402.2.6 [ME41]3 Thermally ineffective panel surfaces of sensible heating panels have insulation >= R-3.5. Complies Does Not Not Observable Not Applicable
Exception: Requirement does not apply. C402.5.5, C403.2.4. 3 [ME3]3 Stair and elevator shaft vents have motorized dampers that automatically close. Refernece section C403.7.7 for operational
details. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.11.3 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.11.3.
Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met.
C403.8.4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors
have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.8.5 [ME143]2 Each DX cooling system > 65 kBtu and chiller
water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies
Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.12.1 [ME71]2 Systems that heat outside the building envelope are radiant heat systems controlled by
an occupancy sensing device or timer switch. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.2.3 [ME55]2 HVAC equipment efficiency verified.
Complies Does Not Not Observable Not Applicable See the Mechanical Systems list for values. C403.2.2 [ME59]1 Natural or mechanical ventilation is provided in accordance with International
Mechanical Code Chapter 4. Mechanical ventilation has capability to reduce outdoor air supply to minimum per IMC Chapter 4. Complies Does Not Not Observable Not Applicable Requirement
will be met. C403.7.1 [ME59]1 Demand control ventilation provided for spaces >500 ft2 and >25 people/1000 ft2 occupant density and served by systems with air side economizer, auto modulating
outside air damper control, or design airflow >3,000 cfm. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.7.2 [ME115]3 Enclosed parking garage
ventilation has automatic contaminant detection and capacity to stage or modulate fans to 50% or less of design capacity. Complies Does Not Not Observable Not Applicable Exception:
Requirement does not apply. C403.7.6 [ME141]3 HVAC systems serving guestrooms in Group R-1 buildings with > 50 guestrooms: Each guestroom is provided with controls that automatically
manage temperature setpoint and ventilation (see sections C403.7.6.1 and C403.7.6.2). Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. 1 High Impact
(Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report
date: 2012 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions C403.7.4 [ME57]1 Exhaust air energy recovery on systems meeting Table C403.7.4(1)
and C403.7.4(2). Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.7.5 [ME116]3 Kitchen exhaust systems comply with replacement air and conditioned
supply air limitations, and satisfy hood rating requirements and maximum exhaust rate criteria. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply.
C403.11.1 , C403.11.2 [ME60]2 HVAC ducts and plenums insulated in accordance with C403.11.1 and constructed in accordance with C403.11.2, verification may need to occur during Foundation
Inspection. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.4.3. 3.2 [ME121]3 Closed-circuit cooling tower within heat pump loop have either
automatic bypass valve or lower leakage positive closure dampers. Open-circuit tower within heat pump loop have automatic valve to bypass all heat pump water flow around the tower.
Open- or closed-circuit cooling towers used in conjunction with a separate heat exchanger have heat loss by shutting down the circulation pump on the cooling tower loop. Open- or closed
circuit cooling towers have a separate heat exchanger to isolate the cooling tower from the heat pump loop, and heat loss is controlled by shutting down the circulation pump on the
cooling tower loop. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.4.1. 4 [ME63]2 Heating for vestibules and air curtains with integral
heating include automatic controls that shut off the heating system when outdoor air temperatures > 45F. Vestibule heating and cooling systems controlled by a thermostat in the vestibule
with heating setpoint <= 60F and cooling setpoint >= 80F. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C408.2.2. 1 [ME53]3 Air outlets and
zone terminal devices have means for air balancing. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.5, C403.5.1, C403.5.2 [ME123]3 Refrigerated display
cases, walk-in coolers or walk-in freezers served by remote compressors and remote condensers not located in a condensing unit, have fan-powered condensers that comply with Sections
C403.5.1 and refrigeration compressor systems that comply with C403.5.2.. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck
06/15/21Report date: 2013 ofPage Section # & Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions C405.2.2. 2 [EL22]1 Spaces required to have lightreduction controls
have a manual control that allows the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern >= 50 percent. Complies Does Not Not Observable Not
Applicable Requirement will be met. C405.2.1, C405.2.1. 1 [EL18]1 Occupancy sensors installed in classrooms/lecture/training rooms, conference/meeting/multipurpose rooms, copy/print
rooms, lounges/breakrooms, enclosed offices, open plan office areas, restrooms, storage rooms, locker rooms, warehouse storage areas, and other spaces <= 300 sqft that are enclosed
by floor-to-ceiling height partitions. Reference section language C405.2.1.2 for control function in warehouses and section C405.2.1.3 for open plan office spaces. Complies Does Not
Not Observable Not Applicable Requirement will be met. C405.2.1. 2 [EL19]1 Occupancy sensors control function in warehouses: In warehouses, the lighting in aisleways and open areas
is controlled with occupant sensors that automatically reduce lighting power by 50% or more when the areas are unoccupied. The occupant sensors control lighting in each aisleway independently
and do not control lighting beyond the aisleway being controlled by the sensor. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C405.2.1. 3 [EL20]1
Occupant sensor control function in open plan office areas: Occupant sensor controls in open office spaces >= 300 sq.ft. have controls 1) configured so that general lighting can be
controlled separately in control zones with floor areas <= 600 sq.ft. within the space, 2) automatically turn off general lighting in all control zones within 20 minutes after all occupants
have left the space, 3) are configured so that general lighting power in each control zone is reduced by >= 80% of the full zone general lighting power within 20 minutes of all occupants
leaving that control zone, and 4) are configured such that any daylight responsive control will activate space general lighting or control zone general lighting only when occupancy
for the same area is detected. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C405.2.2, C405.2.2. 1, C405.2.2. 2 [EL21]2 Each area not served
by occupancy sensors (per C405.2.1) have timeswitch controls and functions detailed in sections C405.2.2.1 and C405.2.2.2. Complies Does Not Not Observable Not Applicable Requirement
will be met. 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238
ComCheck (1).cck 06/15/21Report date: 2014 ofPage Section # & Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions C405.2.3, C405.2.3. 1, C405.2.3. 2 [EL23]2 Daylight
zones provided with individual controls that control the lights independent of general area lighting. See code section C405.2.3 Daylight-responsive controls for applicable spaces, C405.2.3.1
Daylight responsive control function and section C405.2.3.2 Sidelit zone. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C405.2.4 [EL26]1 Separate
lighting control devices for specific uses installed per approved lighting plans. Complies Does Not Not Observable Not Applicable Requirement will be met. C405.2.4 [EL27]1 Additional
interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting. Complies Does Not Not Observable
Not Applicable Requirement will be met. C405.2.5 [EL28]null Automatic lighting controls for exterior lighting installed. Controls will be daylight controlled, set based on business
operation time-of-day, or reduce connected lighting > 30%. Complies Does Not Not Observable Not Applicable Requirement will be met. C405.3 [EL6]1 Exit signs do not exceed 5 watts per
face. Complies Does Not Not Observable Not Applicable Requirement will be met. C405.6 [EL26]2 Low-voltage dry-type distribution electric transformers meet the minimum efficiency requirements
of Table C405.6. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C405.7 [EL27]2 Electric motors meet the minimum efficiency requirements of Tables
C405.7(1) through C405.7(4). Efficiency verified through certification under an approved certification program or the equipment efficiency ratings shall be provided by motor manufacturer
(where certification programs do not exist). Complies Does Not Not Observable Not Applicable Requirement will be met. C405.8.2, C405.8.2. 1 [EL28]2 Escalators and moving walks comply
with ASME A17.1/CSA B44 and have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME A17.1/CSA B44 or applicable local code when not
conveying passengers. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C405.9 [EL29]2 Total voltage drop across the combination of feeders and
branch circuits <= 5%. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low
Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 2015 ofPage Section # & Req.ID
Insulation Inspection Complies? Comments/Assumptions C303.1 [IN10]2 Building envelope insulation is labeled with R-value or insulation certificate providing R-value and other relevant
data. Complies Does Not Not Observable Not Applicable Requirement will be met. C303.2 [IN7]1 Above-grade wall insulation installed per manufacturer’s instructions. Complies Does Not
Not Observable Not Applicable Requirement will be met. C303.2.1 [IN14]2 Exterior insulation is protected from damage with a protective material. Verification for exposed foundation
insulation may need to occur during Foundation Inspection. Complies Does Not Not Observable Not Applicable Requirement will be met. C105 [IN6]1 Installed above-grade wall insulation
type and R-value consistent with insulation specifications reported in plans and COMcheck reports. Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table
for values. C402.2.3 [IN8]2 Installed floor insulation type and Rvalue consistent with insulation specifications reported in plans and COMcheck reports. Complies Does Not Not Observable
Not Applicable See the Envelope Assemblies table for values. C402.2.6 [IN18]3 Radiant panels and associated components, designed for heat transfer from the panel surfaces to the occupants
or indoor space are insulated with a minimum of R-3.5. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C402.5.1. 1 [IN1]1 All sources of air leakage
in the building thermal envelope are sealed, caulked, gasketed, weather stripped or wrapped with moisture vaporpermeable wrapping material to minimize air leakage. Complies Does Not
Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename:
238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 2016 ofPage Section # & Req.ID Final Inspection Complies? Comments/Assumptions
C303.3, C408.2.5. 2 [FI17]3 Furnished O&M instructions for systems and equipment to the building owner or designated representative. Complies Does Not Not Observable Not Applicable
Requirement will be met. C303.3, C408.2.5. 3 [FI8]3 Furnished O&M manuals for HVAC systems within 90 days of system acceptance. Complies Does Not Not Observable Not Applicable Requirement
will be met. C402.5.6 [FI37]1 Weatherseals installed on all loading dock cargo door openings and provide direct contact along the top and sides of vehicles parked in the doorway. Complies
Does Not Not Observable Not Applicable Exception: Requirement does not apply. C402.5.6 [FI37]1 Weatherseals installed on all loading dock cargo door openings and provide direct contact
along the top and sides of vehicles parked in the doorway. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C402.5.6 [FI37]1 Weatherseals installed
on all loading dock cargo door openings and provide direct contact along the top and sides of vehicles parked in the doorway. Complies Does Not Not Observable Not Applicable Exception:
Requirement does not apply. C402.5.6 [FI37]1 Weatherseals installed on all loading dock cargo door openings and provide direct contact along the top and sides of vehicles parked in
the doorway. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C402.5.8 [FI26]3 Recessed luminaires in thermal envelope to limit infiltration and
be IC rated and labeled. Seal between interior finish and luminaire housing. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. C403.2.2 [FI27]3
HVAC systems and equipment capacity does not exceed calculated loads. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling
to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable
Requirement will be met. C403.2.4. 1.1 [FI42]3 Heat pump controls prevent supplemental electric resistance heat from coming on when not needed. Complies Does Not Not Observable Not
Applicable Requirement will be met. C403.4.1. 2 [FI38]3 Thermostatic controls have a 5 °F deadband. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4.
1.3 [FI20]3 Temperature controls have setpoint overlap restrictions. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1) 2 Medium Impact
(Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 2017 ofPage Section
# & Req.ID Final Inspection Complies? Comments/Assumptions C403.2.4. 2 [FI39]3 Each zone equipped with setback controls using automatic time clock or programmable control system. Complies
Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.1, C403.2.4. 2.2 [FI40]3 Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2hour occupant
override, 10-hour backup Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls. Complies Does Not Not
Observable Not Applicable Requirement will be met. C405.4.1 [FI18]1 Interior installed lamp and fixture lighting power is consistent with what is shown on the approved lighting plans,
demonstrating proposed watts are less than or equal to allowed watts. Complies Does Not Not Observable Not Applicable See the Interior Lighting fixture schedule for values. C405.5.1
[FI19]1 Exterior lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts. Complies Does
Not Not Observable Not Applicable See the Exterior Lighting fixture schedule for values. C408.1.1 [FI57]1 Building operations and maintenance documents will be provided to the owner.
Documents will cover manufacturers' information, specifications, programming procedures and means of illustrating to owner how building, equipment and systems are intended to be installed,
maintained, and operated. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.1 [FI28]1 Commissioning plan developed by registered design professional or
approved agency. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.3. 1 [FI31]1 HVAC equipment has been tested to ensure proper operation. Complies Does
Not Not Observable Not Applicable Requirement will be met. C408.2.3. 2 [FI10]1 HVAC control systems have been tested to ensure proper operation, calibration and adjustment of controls.
Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.4 [FI29]1 Preliminary commissioning report completed and certified by registered design professional
or approved agency. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.5. 1 [FI7]3 Furnished HVAC as-built drawings submitted within 90 days of system acceptance.
Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden
Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date: 2018 ofPage Section # & Req.ID Final Inspection Complies? Comments/Assumptions C408.2.5.
1 [FI16]3 Furnished as-built drawings for electric power systems within 90 days of system acceptance. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.5.
3 [FI43]1 An air and/or hydronic system balancing report is provided for HVAC systems. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.5. 4 [FI30]1 Final
commissioning report due to building owner within 90 days of receipt of certificate of occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.3 [FI33]1
Lighting systems have been tested to ensure proper calibration, adjustment, programming, and operation. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional
Comments/Assumptions: 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238
ComCheck (1).cck 06/15/21Report date: 2019 ofPage Project Title: Data filename: 238 Dryden Rd U:\2018025 - 238 Dryden Rd - Visum\02.0 APPROVALS\238 ComCheck (1).cck 06/15/21Report date:
2020 ofPage
Compliance with TC Energy Recommendations.pdf
238 Dryden Rd Conformance with Tompkins County Energy Recommendations for New Construction (2018) 1. Energy Star. The project will include water fixtures that meet EPA’s Water Sense
requirements. All permanent appliances will be Energy Star rated. 2. Heat Pumps. Air sourced heat pumps will be used throughout the building. Electric water heaters will be used
3. Renewables. Roof surfaces are solar receptive to the extent possible, however, we are not providing solar panels as part of this project due to cost constraints. 4. Energy-efficient
building design. The building has been designed with a window-to-wall ratio of less than 25%. The overall building shape is simple. The final R-value of the insulation has not
been determined at this time, but it is our intent to achieve an increase in R-value over code. Best practices will be used for air sealing to minimize infiltration and stack effects.
For buildings over 20 units: (Though only 8 units are proposed there are some items we intend to meet.) 5. Lighting controls and high-efficient lighting technology LED lighting
will be used throughout the project Occupancy sensors will be used in common areas and photo sensors will be used for exterior lighting. 6. High-efficiency heating and cooling systems
Heating and cooling systems will be located in conditioned space. Energy recovery ventilation will be used where required. If ductwork is used for the heating/cooling system,
it will be leak-tested and sealed as necessary. 7. Whole building energy modeling Whole building modeling will not be completed. However, ComCheck will be performed to show code compliance
with code energy requirements.