HomeMy WebLinkAboutElevator Report_Ithaca ArthausElectric Elevator
Acceptance Inspection & Witness
of Test Report
#2 MRL Tract Elev
130 Cherry St.
Ithaca, NY 13204Owner: Ithaca Arthaus
Passenger
3500
2021
Schindler
Type
Rated Load
Year Constructed
Manufacturer
9/27/2021
Winslow, Dan
E000570
QEITF
Date of Report
Inspector
QEI Certification #
QEI Cert. Issuer
210910-00-1949-T
Ithaca, City of
Workorder Designator
Authoritative Jurisdiction
Inspection & Test Items Not In Compliance Per ASME A17.1
Failure Reason
Phone monitoring not working.
Sill pours not completed.
Fire resistance rating required to
confirm to the building code.
FAIDs not tested.
Phase 1, Phase 2, Shunt and flood switches not tested.
Inspection Item
Car Emergency signal
Hoistway construction
Hoistway construction
Fire Service Operation (89-00 ed)
FSO Acceptance Checklist
Applicable Code Reference
Item 1.6
Item 3.10
Item 3.10
Item 6.4
Item 6.5
Test Results
Normal Car Operation
Empty Car Speed Up: 150 fpm
Empty Car Speed Down: 150 fpm
Full Car Speed Up: 150 fpm
Full Car Speed Down: 150 fpm
Load
Load Placed on Car: 4375 lbs
Safeties
F/L Stopping Distance (Car): 0 inches
Governor
Data Plate: 196 fpm
Buffers
Runby to CW Buffer: 6.5 inches
Miscelaneous
Top of Car Clearance: 60 inches
Notes
Inspected to ASME A17.1 - 2013 and BCNYS - 2016 with 2017 addenda.
Inspector's Signature
This conveyance inspection was performed in compliance with the applicable provisions of ASME A17.2 Guide for Inspection of Elevators, Escalators, and Moving walks. The
owner retains full responsibility to maintain this conveyance in compliance with all applicable laws, ordinances and regulations. The Authority Having Jurisdiction retains all rights and responsibilities, as defined by applicable law, regarding verification of compliance.
POSTING INSTRUCTIONS
"The most current certificate of inspection shall be on display at all times within the elevator or attached to the escalator or dumbwaiter; or the certificate shall be
available for public inspection in the office of the building operator"
- Property Maintenance Code
THIS CERTIFIES THAT AN INDEPENDENT THIRD-PARTY QEI
INSPECTION WAS PERFORMED ON:
September 27, 2021
For the following Conveyance:
#2 MRL Tract Elev
130 Cherry St.
Ithaca, NY 13204
SEE ATTACHED REPORT FOR THE
RESULTS OF THIS INSPECTION
Authority Having Jurisdiction: Ithaca, City of
This Inspection Certificate Expires in:
March 2022
This inspection certificate only indicates that a QEI certified inspector employed by CNY Elevator Inspections LLC or ATIS Elevator Inspections
LLC performed a conveyance inspection complying with the requirements of the Building Code and Property Maintenance Code on the date indicated. Where non-compliant items are indicated on the attached report and as required by the Authority Having Jurisdiction and/or as required by law, regulation, or ordinance, the Owner shall correct all deficiencies as soon as possible.
QEI Inspector: Winslow, Dan QEI # E000570 ATISNY W.O. # 210910-00-1949-T
Electric Elevator
Acceptance Inspection & Witness
of Test Report
#1 MRL Tract Elev
130 Cherry St.
Ithaca, NY 14850Owner: Ithaca Arthaus
Passenger
3500
2021
Schindler
Type
Rated Load
Year Constructed
Manufacturer
9/27/2021
Winslow, Dan
E000570
QEITF
Date of Report
Inspector
QEI Certification #
QEI Cert. Issuer
210910-00-1919-T
Ithaca, City of
Workorder Designator
Authoritative Jurisdiction
Inspection & Test Items Not In Compliance Per ASME A17.1
Failure Reason
Car flooring and finished sill grout not
completed.
Phone not working.
Standby Power not tested.
Car number ID required at bottom
and top landing.
Fire rating required to conform with
Building Code.
FAIDs not tested.
Not tested.
Inspection Item
Sills and car floor
Car Emergency signal
Standby power operation
Floor and emergency identification numbering
Hoistway enclosure
Fire Service Operation (89-00 ed)
FSO Acceptance Checklist
Applicable Code Reference
Item 1.4
Item 1.6
Item 1.17
Item 3.9
Item 4.8
Item 6.4
Item 6.5
Test Results
Normal Car Operation
Empty Car Speed Up: 150 fpm
Empty Car Speed Down: 150 fpm
Full Car Speed Up: 150 fpm
Full Car Speed Down: 150 fpm
Load
Load Placed on Car: 4375 lbs
Safeties
F/L Stopping Distance (Car): 0 inches
Governor
Data Plate: 197 fpm
Trip Speed: 176 fpm
Buffers
Runby to CW Buffer: 6.75 inches
Miscelaneous
Top of Car Clearance: 60 inches
Notes
Inspected to ASME A17.1 - 2013 and BCNYS - 2016 with 2017 addenda.
Re-acceptance of previous Acceptance test. See Previous report for additional results.continued on next page
#1 MRL Tract Elev
130 Cherry St.
Ithaca, NY 14850Owner: Ithaca Arthaus
2
9/27/2021
Winslow, Dan
210910-00-1919-T
Page
Date of Report
Inspector
Workorder Designator
Inspector's Signature
This conveyance inspection was performed in compliance with the applicable provisions of ASME A17.2 Guide for Inspection of Elevators, Escalators, and Moving walks. The
owner retains full responsibility to maintain this conveyance in compliance with all applicable laws, ordinances and regulations. The Authority Having Jurisdiction retains all rights and responsibilities, as defined by applicable law, regarding verification of compliance.
POSTING INSTRUCTIONS
"The most current certificate of inspection shall be on display at all times within the elevator or attached to the escalator or dumbwaiter; or the certificate shall be
available for public inspection in the office of the building operator"
- Property Maintenance Code
THIS CERTIFIES THAT AN INDEPENDENT THIRD-PARTY QEI
INSPECTION WAS PERFORMED ON:
September 27, 2021
For the following Conveyance:
#1 MRL Tract Elev
130 Cherry St.
Ithaca, NY 14850
SEE ATTACHED REPORT FOR THE
RESULTS OF THIS INSPECTION
Authority Having Jurisdiction: Ithaca, City of
This Inspection Certificate Expires in:
March 2022
This inspection certificate only indicates that a QEI certified inspector employed by CNY Elevator Inspections LLC or ATIS Elevator Inspections
LLC performed a conveyance inspection complying with the requirements of the Building Code and Property Maintenance Code on the date indicated. Where non-compliant items are indicated on the attached report and as required by the Authority Having Jurisdiction and/or as required by law, regulation, or ordinance, the Owner shall correct all deficiencies as soon as possible.
QEI Inspector: Winslow, Dan QEI # E000570 ATISNY W.O. # 210910-00-1919-T