Evan Hallas 10/13/2020
As requested in original submittal review, thefollowing wills till need to be provided. Seesubsequent submittal request by Vecino:-Provide wall mounted speed controller for EF-2-Provide motorized make-up air damper for EF-2 thatmeets IECC air leakage requirements, installed atexterior wall, and linked to EF-2 operation
Installation notes:-Radiation damper to be air sealed to EF-1 exhaustfan. EF-1/radiation damper to be air sealed to drywall.