HomeMy WebLinkAbout23 05 12-1.1 Fan Submittal Rev. 2 - APPROVED AS NOTED2
Vecino Construction, LLC
(Contractor Review)
Recommend Approval
Recommend Approval as Noted
Revise and Resubmit
Reviewed for general conformance with the Contract
Documents. Subcontractor or material supplier is
responsible for: confirming and correlating all quantities
and dimensions; selecting fabrication processes and
techniques of construction; coordinating his work with
that of all other trades; and performing his work in a
safe and satisfactory manner.
Project:
Reviewed by:
Date:
Corey Olmstead
18260 Ithaca Arthaus
12/17/2020
Evan Hallas 12/28/2020
EF-2 shall be controlled by 2-hour timer
per Fan Schedule on M001. It is unclear if
controller selected has timer function.
X
D.D.1/4/21
Provide all accessories
as per schedule.
Tag:
Project:Ithaca Arthaus
Office:
Version:2014.0.487
Quantity: 1
Special:None
Dimensions Standard Construction Features
• Two (2) patented wheel designs
• Round mounting base
• Popular direct drive sizes use multi-speed motors for
maximum flexibility
• Direct drive (Open/TE) motors include overload
protection as standard
• Plug-Disconnect and pre-wired junction box (1-speed ODP
motors up to 3/4 HP)
Accessories
Application: E - Exhaust
Drive Type: D - Direct
Efficiency: G - Green Plus ECM
Motor Tap: R
Unit Size E H L Wo Controllers: 3 - Multi speed ctrlr iQ-MS (ECM only)
16 24 24.25 30.75 16 Service Switches and ITW: C - NEMA 1 - mounted and wired
Special Construction: C - Spark Resistance (AMCA C)
Weight Guard/Screen: B - Bird Screen
69 Damper Type: A1 - Alum Prllel Bld Dmpr, mtrzd 115V
Performance
800
0.5
1135
0.137
0
70
N/A
* NEC FLA - based on tables 430.248 or 430.250
of National Electrical Code 2014. Actual motor
FLA may vary depending on motor manufacturer.
+ Motor weight may vary depending on supplier
WFX16RGP
Wall Mounted Upblast Spun Aluminum Exhaust Fan
Operating Point
Volume (CFM)
Static Pressure (in. wg)
Fan RPM
Horse Power (BHP)
Elevation (ft)
Temperature (°F)
Drive Loss (%)
EF-2
Northeast HVAC Solutio
Page 1 of 2 - Edge Version 2014.0.487 - Product Information is Subject to Change without Notice
Enclosure 3 - ODP w/Overload
NEC FLA*3.6
Weight+ (lbs)C/F
Motor Information
Motor HP 0.33 - 1/3 HP
Volt/Ph/Hz 230V/1PH/60HZ
VC Note: to be
provided per notes
on previous
returned submittal.
Tag:
Project:Ithaca Arthaus
Office:
Version:2014.0.487
(continued)
63 125 250 500 1000 2000 4000 8000
63 70 70 61 58 56 49 41
LwA - Weighted sound power, based on ANSI S1.4, dBA - Weighted sound pressure, based on
65 53.9 6.9 11.5 dB attenuation per Octave band at 5 ft. Sones - calculated using AMCA 301 at 5 ft.
SOUND POWER
OCTAVE POWER CENTER FREQUENCY (hz)
Page 2 of 2 - Edge Version 2014.0.487 - Product Information is Subject to Change without Notice
LWA Dba Sones
EF-2
Northeast HVAC Solutio
Tag:
Project:Ithaca Arthaus
Office:
Version:2014.0.487
Quantity: 1
Special:None
Product Image
Motorized 115V (MD1)
•110V damper actuator for positive opening and closing.
•Square galvanized steel frame,
•Multi-leaf, roll formed aluminum blades; with
•Nylon bearings; and
•Felt Edges for quiet operation
Options or Accessories Listing
0 - Not an accessory L - Light
E - Exhaust
Schedule
ID Quantity Tag
11EF-2
EF-2
Northeast HVAC Solutions
Page 1 of 1 - Edge Version 2014.0.487 - Product Information is Subject to Change without Notice
Motorized 115V (MD1)
Motor Operated Back Draft Damper
Model Parent Duty
Application