HomeMy WebLinkAbout23 05 12 - 11 Pipe InsulationSUBMITTAL TRANSMITTAL
Project Name: Ithaca Arthaus
Project Number : 18260
A
To: Vecino Construction, LLC Date Submitted
Attn:Submittal No. (per Procore)
X
From:
Item
No.
Spec
Paragraph /
No.Submittal Type Lead Time
1 Product Information
2
3
4
5
6
7
8
9
10
11
Comments:
Date
23 05 12 - 11
Transmittal (from SUBCONTRACTOR)
23 31 13
mcahill@suretemp.com
Streamline
Manufacturer
2/17/2021
Maura Cahill
Dwg. And/or Specification
Section
Pipe Insulation
Title / Description
ReSubmitted for Review & Approval REV (1)
Submitted for Review & Approval REV (0)
This is a FULL SUBMITTAL
This is a PARTIAL Submittal
Corey Olmstead
corey@vecinogroup.com
Phone: (315) 854-0979
Signature/Stamp of Transmitter
Vecino Construction Stamp BW A&E Stamp
Submittal Transmittal
Vecino Construction, LLC
(Contractor Review)
Recommend Approval
Recommend Approval as Noted
Revise and Resubmit
Reviewed for general conformance with the Contract Documents. Subcontractor or material supplier is
responsible for: confirming and correlating all quantities and dimensions; selecting fabrication processes and techniques of construction; coordinating his work with that of all other trades; and performing his work in a safe and satisfactory manner.
Project:
Reviewed by:
Date:
Corey Olmstead
18260 Ithaca Arthaus
2/18/21
Distributed by Mueller Streamline Co. • 150 Schilling Blvd, Suite 201, Collierville, Tennessee 38017 • 1-800-348-8464 • www.muellerstreamline.com page 1 of 4
Product Description:
Streamline® Standard and Mini Split Line Sets are available in either an elastomeric or coated elastomeric insulation for use in
HVACR applications. All line sets will be manufactured in the United States.
Material:
Streamline® Standard and Mini Split Line Sets copper tube shall be made from C12200 grade of copper. Insulation is choice of
elastomeric or coated elastomeric material. Elastomeric insulation has a UV retardant added but it is recommended to cover or
apply a coating for long term exposure. Coated elastomeric insulation utilizes a co-extruded jacket that requires no additional
cover or coating.
Key Specifications:
Streamline® Standard and Mini Split Line Sets are made to meet the requirements of ASTM B1003.
Streamline® Standard and Mini Split Line Sets are third party verified in select sizes through Underwriters Laboratories (UL)
for operating pressure of 700psi at 250°F. This rating includes fully annealed and brazed copper tubing.
Installation:
Installations and insulation material shall comply with the latest applicable building codes for the local jurisdiction. For elastomeric
insulation, it is recommended, at minimum, to coat insulation on exterior applications with 2 coats of WB Finish a (recoat every
2-4 years). For more substantial protection, place in a protective jacket or protective channel. In accordance with ASTM
instructions, insulation ends must be sealed to prevent air/moisture intrusion. Both ends of the tube should be taped with 2” wide
Polyken-936-30 tape or equivalent (high U.V. Resistant/High tack joint wrap tape). Reference local building codes for additional
details.
References:
Product Line Product Type Outer Diameter
Copper Tube Streamline® Refrigeration Service Coils
Streamline® Line Sets & Mini-Splits
Streamline® ACR - Type L (Hard Lengths)
Streamline® ACR - Type K (Hard Lengths)
1/8” – 1-1/8”
1/4” – 1-1/8”
1/4” – 1-3/8”
1/4” – 2-5/8”
STANDARD AND MINI SPLIT LINE SETS FOR HVACR APPLICATIONS
Job Name Contractor
Job Location Wholesaler
Engineer Streamline® Rep
MADE IN USA
Distributed by Mueller Streamline Co. • 150 Schilling Blvd, Suite 201, Collierville, Tennessee 38017 • 1-800-348-8464 • www.muellerstreamline.com page 2 of 4
STANDARD AND MINI SPLIT LINE SET DATA
STANDARD LINE SETS WITH ELASTOMERIC INSULATION
Copper Tube Sizes
Lengths Insulation
Thickness Optional FinishesLiquid Line Suction Line
1/4" - 1/2"3/8" - 1-1/8"10' - 50' using 5' intervals; 60' & 100' (other lengths are available upon customer request)3/8" - 1"
Flare nuts, 90-degree bends,
custom connections, thermostat
wire and taping
MINI SPLIT LINE SETS WITH ELASTOMERIC INSULATION
Copper Tube Sizes
Lengths Insulation
Thickness Optional FinishesLiquid Line Suction
Line
1/4" - 3/8"3/8" - 3/4"
15' - 50' using 5' intervals; 100'
(other lengths are available upon
customer request)
3/8" - 1"
Insulated liquid and suction lines and
twin tube system, flare nuts, 90-degree
bends, custom connections, mini-split
wire or control cable and taping
DURAGUARD UV™ LINE SETS WITH COATED ELASTOMERIC INSULATION
Copper Tube Sizes
Lengths Insulation
Thickness Optional FinishesLiquid
Line
Suction
Line
1/4" - 1/2"3/8" - 7/8"25', 35' & 50'1/2" - 1"
Insulated liquid and suction lines,
flare nuts, 90-degree bends, mini-split
wire or control cable and taping
Distributed by Mueller Streamline Co. • 150 Schilling Blvd, Suite 201, Collierville, Tennessee 38017 • 1-800-348-8464 • www.muellerstreamline.com page 3 of 4
ELASTOMERIC INSULATION SPECIFICATION*
INSULATION:
"R" Values
Pipe Insulation ID Size Nom. 3/8"Nom. 1/2"Nom. 3/4"Nom. 1"
1/4"2.8 3.8 6.4 8.3
3/8"2.8 3.3 5.9 7.2
1/2"2.6 3.3 5.5 7.2
5/8"2.6 3.4 5.6 7.0
3/4"2.4 3.3 5.5 7.0
7/8"2.4 3.3 5.4 7.0
1-1/8"2.2 3.3 5.4 7.2
SPECIFICATION COMPLIANCE
•ASTM B1003
•ASTM C 534, Type II —
Sheet Grade 1
•ASTM C 1534
•ASTM E 84, NFPA 255, UL 723
•CAN/ULC S102
•NFPA 90A, 90B
•ASTM G21/C1338
•ASTM G22
•ASTM D 1056, 2B1
•MIL-P-15280J, FORM S
•MIL-C-3133C (MIL STD 670B),
•Grade SBE 3
•MEA 107-89M
•UL 181
•UL 94 5V-A, V-0, File E 55798
•City of Los Angeles – RR 7642
•ASTM D 1149
PHYSICAL PROPERTIES
Specifications Values Test Method
Thermal Conductivity,
Btu • in./h • ft2 • °F (W/mK)
75°F Mean Temperature (24°C)
90°F Mean Temperature (32°C)
0.245 (0.035)
0.254 (0.037)ASTM C 177 or C 518
Water Vapor Permeability,
Perm-in. [Kg/(s•m•Pa)]0.05 (0.725 x 10–13)ASTM E 96, Procedure A
Flame Spread and Smoke
Developed Index through
1” (25mm)*25/50*
ASTM E 84
CAN/ULC S102
Mold Growth
Fungi Resistance
Bacterial Resistance
UL181
ASTM G21/C1338
ASTM G22
Meets requirements
Meets requirements
Meets requirements
Water Absorption, % by Volume 0.2%ASTM C 209
Upper Use Limit 220°F (105°C)**ASTM C 534
Lower Use Limit -297°F (-183°C)**ASTM C 534
Ozone Resistance GOOD Ozone Chamber Test
*Mueller Streamline does not independently verify the following information provided by its vendors and makes no representation to the accuracy or completeness of information.
Distributed by Mueller Streamline Co. • 150 Schilling Blvd, Suite 201, Collierville, Tennessee 38017 • 1-800-348-8464 • www.muellerstreamline.com page 4 of 4
COATED ELASTOMERIC INSULATION SPECIFICATION*
INSULATION:
"R" Values
Pipe Insulation ID Size Nom. 1/2"Nom. 3/4"Nom. 1"
1/4"4.0 6.1 9.6
3/8"3.6 5.6 8.5
1/2"3.4 5.4 7.9
5/8"3.3 5.4 7.5
3/4"3.1 5.4 7.5
7/8"3.2 5.4 7.2
1-1/8"3.1 5.5 7.1
SPECIFICATION COMPLIANCE
•ASTM B1003
•ASTM C 534, Type I —
Tubular, Grade 1
•ASTM E 84, NFPA 255, UL 723
•NFPA 90A, 90B
•ASTM G21/C1338
•ASTM G22
•ASTM D 1056, 2B1
•MIL-P-15280J, FORM S
•MIL-C-3133C (MIL STD 670B),
•UL 94 5V-A, V-0, HF-I (File E
300774)
•2012, 2015, 2018 IECC, IMC, IRC
•2016 CA Title 24, Part 6,
Subchapter 3, Section 120.3
•RoHS Compliant
PHYSICAL PROPERTIES
Specifications Values Test Method
Thermal Conductivity,
Btu • in./h • ft2 • °F (W/mK)
75°F Mean Temperature (24°C)0.242 (0.035)ASTM C 177 or C 518
Water Vapor Permeability,<0.01 perm-in. insulation
≤0.05 perms jacket ASTM E 96
Flame Spread and Smoke
Developed Index through
1-1/2” (37.5mm)25/50 ASTM E 84
Mold Growth
Fungi Resistance
Bacterial Resistance
UL181
ASTM G21/C1338
ASTM G22
Meets requirements
Meets requirements
Meets requirements
Water Absorption, % by Volume 0%ASTM C 209
Upper Use Limit 220°F (104°C)**ASTM C 534
Lower Use Limit -297°F (-183°C)**ASTM C 534
Hot Surface Performance 250°F ASTM C411, NFPA 90A Meets requirements
UV Resistance (Artificial Aging) ASTM G153 Meets requirements
*Mueller Streamline does not independently verify the following information provided by its vendors and makes no representation to the accuracy or completeness of information.