28 31 11 .1 Fire Alarm Product submittal_CORRECTIONS NOTED PROCEED
SUBMITTAL TRANSMITTAL Project Name: Ithaca Arthaus Project Number : 18260 A To: Vecino Construction, LLC Date Submitted Attn:Submittal No. (per Procore) From: X Item No. Spec Paragraph / No.Submittal Type Lead Time 1 -1 4 weeks 2 3 4 5 6 7 8 9 10 11 Comments: Date 28 31 11-1 Transmittal (from SUBCONTRACTOR) 28 31 11 jorr@demcony.com (315) 715-1677 Edwards Manufacturer 7/24/2020 John Orr Dwg. And/or Specification Section Digital, Addressable Fire-Alarm System Product Info Title / Description ReSubmitted for Review & Approval REV (1) Submitted for Review & Approval REV (0) This is a FULL SUBMITTAL This is a PARTIAL Submittal Corey Olmstead corey@vecinogroup.com Phone: (315) 854-0979 Signature/Stamp of Transmitter Vecino Construction Stamp BW A&E Stamp Submittal Transmittal AEL 8/10/20 Submitted device for apartment is rejected - dwelling units must be provided with both smoke and CO detection per planset BOD device. PAGE:1 of 1 DATE:7/21/2020 ATTN: PHONE: FAX: QTY 1 1 2 1 1 1 2 12 24 3 3 106 4 110 1 18 8 2 2 27 45 6 214 6 1 344 10 Copy of NYS Alarm License is attached Battery and Line Loss Calculations are attachd 53 PIXLEY INDUSTRIAL PKWY • ROCHESTER, NY 14624 • TEL (585) 663-8530 • FAX (585) 663-8633 DESCRIPTION Special Notes; Fire Control Accessories, SPDT Auxiliary Relay, 10 Amps, 120VAC or 24VAC/DC Horn/strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 110, 135, 185, red Strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 110, 135, 185, red Low-frequency sounder/strobe, 15, 30, 75, 95,110, 135, 185 cd, wall, white Low-frequency sounder, 15, 30, 75, 95,110, 135, 185 cd, wall, white Strobe, 12/24 volt, multi-candela 15, 30, 75, 95, 110, 135, 185, white Horn/strobe, 12/24 volt, multi-candela 15, 15/75, 30, 75, 110, 115, red, outdoor, includes backbox Kidde Hardwire i12010S interconnect Ionixation Sensor Smoke Alarm with 10 Year Kidde 120VAC Interconnectable Strobe Light Addressable output signal module Sync™ circuit module, 12/24 volt, white Analog photoelectronic sensor, Velociti only, bright white color Thermal sensor 135°, Velociti only, bright white color 6" base, flanged, low profile, use with analog sensor or Velociti sensors, bright white color Addressable double action station Addressable monitor module, Class “B” Addressable output relay control module E3BB-FLUSH SLC-PM Fire Control Accessories, SPDT Auxiliary Relay, w/ Enclosure Fire alarm system equipment Smart Loop Panel addressable FACP, Black enclosure with 7A power supply, LCD-SLP display. Digital alarm communication transmitter SLP add-on SLC module, System Sensor. 1 loop-318 devices. Required for SLP panel order LCD Touch screen display unit A Size, Flush Remote LCD enclosure, black, incl keylock, LCD slot (LCD-E3, LCD-SLP) MBC MINI BATTERY CABINET BLK 12 Volt, 18 A Hr. sealed lead acid battery - PS12180F2 9 amp 24 volt UL listed fire alarm NAC expander SSU00506 SLP-BLK DACT-E3 LCD-SLP PREPARED BY: Chuck Schramm The attached CAD drawings were created specifically for the new system(s) as outlined above. PS12180 P2RK 21010407-A SL177i West Fire Systems, Inc. is the factory authorized service organization for the above system(s). HPF902ULAD ATD-L3 B300-6 MS-7AF AMM-2F AOM-2RF MR101/C PAM1 P2WL-LF HWL-LF SWL P2RL 12 Volt, 7 A Hr. sealed lead acid batteryPS1270 AOM-2SF MDL3W ASD-PL3 SRL SUBMITTAL SHIP TO:TO: MODEL PROJECT Demco Electric 6701 Manlius Center Road East Syracuse, NY 13057 same Fire alarm system Ithaca ArthausJohn Orr 315-459-6221 Project: Contractor:Standby Hours:24 Prepared By:Alarm Mins:5 DATE:Derating Factor:1.2 Total Available Nac Power:6 Voltage Drop Warning Threshold %:10 Total Standby Current (Amps):0.188 1.163 Total Alarm Current (Amps) Standby Time In Hours:24 0.208 Alarm Minutes / 24 (1.2 Mins) Total Standby AH Required:4.510 0.242 Total Alarm AH Required Total Combined AH Required: Multiply By The Derating Factor: Minimum Battery AmpHours Required: Battery Amp Size Provided: Battery cabinet required TOTAL NAC CURRENT: Device Qty Draw Standby Qty Draw Alarm Panel Information S3 FACP Control panel 1 x 0.11100 0.11100 1 x 0.24300 0.24300 Panel Add On Modules SLC-PM SLC Addressable loop card 2 x 0.01400 0.02800 2 x 0.01400 0.02800 DACT-E3 Digital communicator 1 x 0.01800 0.01800 1 x 0.01800 0.01800 0 x 0.00000 0 x 0.00000 TOTAL PANEL CURRENT 0.15700 0.28900 Remote Annunciator(s) LCD-SLP Remote Annunciator 1 x 0.03000 0.03000 1 x 0.06500 0.06500 0.065 0 x 0.00000 0 x 0.00000 REMOTE ANNUNCIATOR CURRENT 0.030 0.065 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 16 AWG Solid 4.89 200 23.94 0.26% Addressable Loop 1 Devices ASD-PL2F Addresable Smoke Detector 106 x 0.00025 0.02650 106 x 0.00000 0.00000 ATDF Series Heat Detector 4 x 0.00020 0.00080 4 x 0.00030 0.00120 MS-7A Addressable pull station 1 x 0.00030 0.00030 1 x 0.00030 0.00030 AOM-2(S or R)F Addressable supervised relay output 11 x 0.00030 0.00330 11 x 0.00030 0.00330 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.031 0 x 0.00000 0 x 0.00000 TOTAL SLC 1 CURRENT 0.031 0.005 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 16 AWG Solid 4.89 2500 23.62 1.57% Addressable Loop 2 Devices 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.000 0 x 0.00000 0 x 0.00000 TOTAL SLC 2 CURRENT 0.000 0.000 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 0 24.00 0.00% 0.38 Wire Type and AWG Rating Voltage Drop 0.00 Alarm Current Wire Type and AWG Rating Voltage Drop 0.06 Wire Type and AWG Rating Voltage Drop Standby Current 4.75 1.20 5.70 18.00 0.83 7/20/2020 System Current Draw - S3 Addressable Control Panel w/ Dialer Ithaca ArtHaus Demco Electric C Schramm NAC Circuit 1 System Sensor P2RL 95cd 1 x 0.00000 0.00000 1 x 0.14200 0.14200 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.142 0 x 0.00000 0 x 0.00000 TOTAL NAC 1 CURRENT 0.000 0.142 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 150 23.93 0.27% NAC Circuit 2 System Sensor P2RL 75cd 5 x 0.00000 0.00000 5 x 0.12100 0.60500 System Sensor SRL 15cd 2 x 0.00000 0.00000 2 x 0.04300 0.08600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.691 0 x 0.00000 0 x 0.00000 TOTAL NAC 2 CURRENT 0.000 0.691 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 400 23.15 3.54% NAC Circuit 3 System Sensor P2RL 15cd 3 x 0.00000 0.00000 3 x 0.05400 0.16200 System Sensor P2RL 75cd 1 x 0.00000 0.00000 1 x 0.12100 0.12100 System Sensor SRL 15cd 8 x 0.00000 0.00000 8 x 0.04300 0.34400 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 TOTAL NAC 3 CURRENT 0.000 0.627 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 550 22.94 4.41% NAC Circuit 4 System Sensor P2RL 15cd 1 x 0.00000 0.00000 1 x 0.05400 0.05400 System Sensor P2RL 75cd 3 x 0.00000 0.00000 3 x 0.12100 0.36300 System Sensor SRL 15cd 4 x 0.00000 0.00000 4 x 0.04300 0.17200 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 TOTAL NAC 4 CURRENT 0.000 0.589 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 600 22.92 4.52% 1.06 Wire Type and AWG Rating Voltage Drop 1.08 0.07 Wire Type and AWG Rating Voltage Drop 0.85 Wire Type and AWG Rating Voltage Drop Wire Type and AWG Rating Voltage Drop Aux Non Resettable MR-101 Relay - Powered in Alarm 2 x 0.00000 0.00000 2 x 0.01800 0.03600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.036 0 x 0.00000 0 x 0.00000 TOTAL AUX CURRENT 0.000 0.036 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 150 23.98 0.07% Aux Resettable 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.000 0 x 0.00000 0 x 0.00000 TOTAL AUX RESET CURRENT 0.000 0.000 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 0 24.00 0.00% 1 1 1.163 0.02 Wire Type and AWG Rating Voltage Drop 0.00 Total Standby Load:0.188 Total Alarm Load: Wire Type and AWG Rating Voltage Drop Project: Contractor:Standby Hours:24 Prepared By:Alarm Mins:5 DATE:Derating Factor:1.2 10 Total Standby Current (Amps):0.000 7.478 Total Alarm Current (Amps) Standby Time In Hours:24 0.208 Alarm Minutes / 24 (1.2 Mins) Total Standby AH Required:0.000 1.558 Total Alarm AH Required Total Combined AH Required: Multiply By The Derating Factor: Minimum Battery AmpHours Required: Battery Amp Size Provided: Device Qty Draw Standby Qty Draw Alarm Panel Information FCI HPF902ULADA Booster Panel 0 x 0.07500 0 x 0.17500 TOTAL PANEL CURRENT 0.00000 0.00000 NAC Circuit 1 System Sensor P2RL-LF Low Freq A/V 185cd 6 x 0.00000 0.00000 6 x 0.26600 1.59600 System Sensor SRL 15cd 6 x 0.00000 0.00000 6 x 0.04300 0.25800 System Sensor P2RL 15cd 1 x 0.00000 0.00000 1 x 0.05400 0.05400 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 1.908 0 x 0.00000 0 x 0.00000 TOTAL NAC 1 CURRENT 0.000 1.908 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 350 21.95 8.54% NAC Circuit 2 System Sensor P2RL-LF Low Freq A/V 185cd 6 x 0.00000 0.00000 6 x 0.26600 1.59600 System Sensor SRL 15cd 4 x 0.00000 0.00000 4 x 0.04300 0.17200 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 1.768 0 x 0.00000 0 x 0.00000 TOTAL NAC 2 CURRENT 0.000 1.768 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 350 22.10 7.92% 1.56 1.20 System Current Draw - HPF902ULADA BOOSTER PANEL - Typical Ithaca ArtHaus Demco Electric Voltage Drop Warning Threshold %: C Schramm 7/20/2020 1.87 Standby Current Alarm Current 1.90 7.00 Wire Type and AWG Rating Voltage Drop 2.05 Wire Type and AWG Rating Voltage Drop NAC Circuit 3 System Sensor P2RL-LF Low Freq A/V 185cd 7 x 0.00000 0.00000 7 x 0.26600 1.86200 System Sensor SRL 15cd 4 x 0.00000 0.00000 4 x 0.04300 0.17200 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 2.034 0 x 0.00000 0 x 0.00000 TOTAL NAC 3 CURRENT 0.000 2.034 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 14 AWG Solid 3.07 350 21.81 9.11% NAC Circuit 4 System Sensor P2RL-LF Low Freq A/V 185cd 6 x 0.00000 0.00000 6 x 0.26600 1.59600 System Sensor SRL 15cd 4 x 0.00000 0.00000 4 x 0.04300 0.17200 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 1.768 0 x 0.00000 0 x 0.00000 TOTAL NAC 4 CURRENT 0.000 1.768 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 0 24.00 0.00% Aux Non Resettable 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 0 x 0.00000 0 x 0.00000 TOTAL AUX CURRENT 0.000 0.000 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 0 24.00 0.00% Aux Resettable 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 0 x 0.00000 0 x 0.00000 TOTAL AUX RESET CURRENT 0.000 0.000 OHMs Per 1000FT Length of Wire Volts @ EOL % Drop LINE LOSS CALCULATIONS 0 24.00 0.00% 1 1 Total Standby Load:0.000 Total Alarm Load:7.478 Wire Type and AWG Rating Voltage Drop 2.19 Wire Type and AWG Rating Voltage Drop 0.00 0.00 Wire Type and AWG Rating Voltage Drop 0.00 Wire Type and AWG Rating Voltage Drop S3 Series S3 Series Control Panel Small Addressable Fire Alarm Control Panel Analog and Networking Systems General The Gamewell-FCI®, S3 Series Intelligent Fire Alarm Control Panel provides the latest, innovative high-end processing power. The S3 Series panel is a digital, microprocessor-based system that offers a simple, intuitive solution for the small to mid-sized fire alarm applications. In standalone or network configurations, the S3 Series complies with most fire alarm application requirements. It supports the following types of networks. • Up to 64 nodes using the 7100 Series panel. • Up to 122 nodes using the S3 Series or E3 Series® panels. Use either twisted-pair wire or fiber-optic to network panels at a high-speed 625K baud ARCNET network bus. With flexible Boolean logic, intelligent detection, and Ethernet connectivity, this system provides power and versatility that surpasses comparable, small addressable fire alarm systems. The basic S3 Series configuration consists of an SLP (Smart Loop Panel) main board, LCD-SLP touchscreen display, SLC loop personality modules, and as seven amp power supply. The SLP main board provides either one or two SLC loops in the Class A or B configuration that supports either of the following protocols: • Up to 318 devices per loop using the System Sensor® protocol. If you add a second loop module, it increases the maximum device count to 636 devices. • Up to 126 devices per loop using the Apollo protocol. If you add a second loop module, it increases the maximum device count to 252 devices. FEATURES & BENEFITS • Listed per ANSI/UL® Standard 864 9th Edition • IBC Seismic Certified • Allows one SLC loop (expandable to two loops) that supports either System Sensor or Apollo devices in Class A or Class B (Style 4, 6 or 7) • Supports a network system of up to 122 nodes (includes E3 Series® panels) or up to 64 nodes (includes 7100 Series) •System Sensor supports up to 318 intelligent devices and each SLC loop supports the following - up to 159 detectors - up to 159 modules (expandable to 636 maximum per panel) • Apollo supports up to 126 intelligent detectors and modules per SLC. (Expandable to 252 maximum per panel) • Includes a high resolution (4.3”) (10.92 cm) color touchscreen display • Provides 7.0 amp power supply (120VAC or 240VAC) • Includes four Class B or two Class A built-in Notification Appliance Circuits (NAC) • Provides selectable System Sensor, Cooper-Wheelock, or Gentex™ strobe synchronization • Supports up to 32 serial annunciators (LCD, LED-only, LED Switch) • Offers an Ethernet port for programming, a variety of system reports, and a FocalPoint® Graphic Workstation connectivity • Provides two fully- programmable Form-C contacts for Fire, Trouble, and Supervisory •TimeCap - Saves time and date up to 48 hours without any power or battery • Automatically adjusts to any NAC End-of- Line Resistor (EOL) value (1k-55k ohm) for legacy audible/visual appliances •Removable display can be used as a remote annunciator • Suitable for pre-action deluge applications 2 General Four Class B or two Class A NACs can be wired and synchronized using the System Sensor, Cooper- Wheelock®, or Gentex™ strobes. To retrofit the SLP on the existing audible/visual appliances, the on-board Electronic EOL (EEOL) automatically adjusts to the EOL resistor in the field. A 4.3" (10.92 cm) color touchscreen display screen shows the following: • Events on the system • Status of analog addressable devices • Complete diagnostic fault codes/messages • Five programmable function buttons with LED status for accessibility to the following functions: Application The S3 Series Fire Alarm and Life Safety System is an easy-to-use intelligent fire alarm solution designed for the small to mid-sized buildings. Analog technology delivers the benefits of a simple system installation, while a user-friendly interface makes panel operation and system maintenance quick and intuitive. Smart Panel Programming Using Boolean logic programming, the installer may customize the system to precisely suit the needs of the building owner. Auto-programming allows the installer to instantly locate all the devices on the SLC loop. Simple, Intuitive Display The front panel display provides a user-friendly interface for the operator's control. A 4.3” (10.922 cm) color touchscreen displays system status, event details and service modes. On the front of the panel, six LEDs show the following conditions. Five custom programmable switches allow the user quick access to common functions specific to the building like device disable, output bypass and device status. Perfect for Retrofits The S3 Series is well-suited for retrofit applications. The SLP provides a simple way to upgrade your fire protection system. It is designed to be an upgrade solution for the legacy FCI, 7100 and Gamewell, 602 Series panels. An added feature is the SLP's EEOL. Using EEOL, the installers can automatically identify the EOL for existing audible/visual appliances. Flexibility for Future Growth The S3 Series can be expanded to add a second SLC loop without replacing the entire system. Using the RPT-E3-UTP Network Repeater, you can network up to 64 nodes (122 nodes with the ANX node expander) using either twisted-pair or fiber-optic. The built-in Ethernet port allows the connection to the Gamewell- FCI’s FocalPoint Graphical Workstation. Figure 1 LCD-SLP Display Optional Accessories DACT-E3 - Dialer The Digital Alarm Communication Transmitter sends digital signals over telephone lines to the central station. It connects to the SLP through an RS-485 bus. Using the Contact ID format, the DACT-E3 provides a four-digit account code followed by the code/numbers listed below: • Three-digit Event Code • Two-digit Group Number • Three-digit Contact Number All codes are used to provide specific point identification. The DACT-E3 is compatible with digital alarm communicator receivers (DACRs) that receive the following signaling formats: For more information, refer to the following data sheets: • DACT-E3 Data Sheet, P/N: 9020-0610 RPT-E3-UTP - Network Repeater Card The Network Repeater allows the SLP fire control panels to connect to the broadband network from remote locations. It connects to other networked units using unshielded, twisted-pair wiring. The RPT-E3- UTP is available with two add-on fiber modules: • FML-E3 connects to the network using either 62.5/125 micron multi-mode fiber. • FSL-E3 connects to the network using 9/125 micron single-mode fiber. Refer to the following data sheets: • RPT-E3-UTP Data Sheet, P/N: 9020-0609. • FML-E3/FSL-E3 Data Sheet, P/N: 9021-60783 - Disable/Enable - Trouble Acknowledge - Bypass Output - Alarm Acknowledge - Lamp Test - Custom-defined • Fire • Silenced • Hazard (Gas or CO) • AC Power •Supervisory •Trouble •Contact ID •SIA •3+1 •4+2 3 LCD-7100 - Remote Annunciator The Remote serial display features an 80-character display. The LCD-7100 can be surface or flush- mounted on a standard 4-gang electrical box. You can use up to five LCD-7100 remote annunciators per SLP panel. For more information, refer to the LCD-7100 Data Sheet, P/N: 9020-0486. ASM-16 - Addressable Switch/LED Module There are 16 programmable switches available to perform any function the application requires. Each ASM-16 switch has 3 LEDs fully programmable in red, yellow, and green. These LEDs can be programmed to operate with a certain button press or operate independently as a status signal (e.g. ON, OFF, Activated, etc). Up to 16 ASM-16 modules can be connected to the SLP panel. For more information, refer to the ASM-16 Data Sheet, P/N: 9020-0554. ANU-48 - 48 LED Driver Unit The ANU-48 provides output for eight remote panel switches and 48 remote LEDs for use in a remotely located UL® Listed annunciator enclosure. Up to 16 ANU-48 modules can be connected to the SLP panel. For more information, refer to the ANU-48 Data Sheet, P/N: 9020-0596. Figure 2 illustrates the S3, SLP-BB Cabinet Enclosure. Figure 2 S3, SLP Enclosure Ordering Information SLP-BLK: SLP addressable FACP in black S3, SLP-BB enclosure. Requires either an SLC-PM or an SLC95- PM for SLC loops. SLP-RED: SLP addressable FACP with red door and black S3, SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops. SLP-RED-G: SLP addressable FACP 240VAC power supply with red door and black S3, SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops. SLC-PM: System Sensor Loop Card - 1 loop used for 159 sensors and 159 modules. For use with the S3 panels only. SLC95-PM: Apollo Loop Card-1 loop used for 126 sensors and modules. For use with the S3 panels only. Accessories DACT-E3: Digital Dialer Communicator Transmitter for the S3 or E3 Series. LCD-SLP: LCD Color Touchscreen display with five programmable switches. For use with the S3 Series panels. Remote annunciation requires the E3 Series A2 cabinet. (E3BB-BA2, E3BB-RA2) RPT-E3-UTP: Network repeater card with twisted-pair, fiber connections. Requires either an FML-E3 or an FSL-E3 card. FML-E3: Multi-mode fiber-optic card for one channel on the RPT-E3-UTP. FSL-E3: Single-mode fiber-optic card for one channel on the RPT-E3-UTP. SLP-RB: SLP motherboard For use with the replacement or the retrofit solutions. FLPS-7-RB: SLP 120VAC 7A power supply. For use with the replacement or the retrofit solutions. SLP-RETROFIT: SLP Retrofit Kit for the 7100 B-Slim and IF602 panels. Includes the new door and the mounting plate. Requires the following: S3BB-RB: SLP red cabinet with an inner door for the mounting display behind the locked, plexi-glass door. Requires the following: LCD-7100: Remote Serial LCD Annunciator ASM-16: Remote Programmable Addressable Switch/ LED Module ANU-48: Remote LED Driver Module S3, SLP-BB CABINET OUTER DOOR S3, SLP-BB CABINET BACKBOX 1 2 3 4 141/2"W 20 1/8"H 4 1/2" D •SLP-RB •FLPS-7-RB •SLC95-PM •LCD-SLP •SLC-PM •SLP-RB •FLPS-7-RB •SLC95-PM •LCD-SLP •SLC-PM 4 Figure 3 illustrates the various S3 Series configuration options that are available. Figure 3 S3 Series Panel Configuration Options Networked up to 122 panels using twisted- pair wire or fiber optics. FocalPoint Workstation LCD-E3 Remote Annunicator LCD-SLP Color Touchscreen Annunicator LCD-7100 Remote Annunicator ASM-16 LED Switch Control ANU-48 LED Display Driver RS485DACTRS232EthernetRelay: 3 Form CS3 Series Fire Alarm Control Panel MCS-COF Fire/Carbon Monoxide Detector MS-7AF Pull Station AMM-2RIF Dual Input/Output Module Supports up to 636 Velociti devices or 252 XP95 devices DNR Intelligent Duct Detector ASD-PL2F Photo Detector AOM-2RF Relay Module AMM-2IF Mini Monitor Module ASD-LS Laser Detector Local Energy Trip E3 Series Panel Laptop Programming S3 Series Control Panel Technical Specifications 9021-60730 | H | 09/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, FocalPoint®, Gamewell-FCI®, and System Sensor® are registered trademarks of Honeywell International Inc. Cooper-Wheelock® is a registered trademark of Cooper-Wheelock Corporation. Gentex™ is a trademark of Gentex Corporation. UL® is a registered trademark of Underwriters Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s S3 Series Control Panel and other products available by visiting www.Gamewell-FCI.com SYSTEM Device Loops: Up to two Class A or B, System Sensor units, each loop supports up to 318 device addresses. OR- Apollo units, each loop supports up to 126 device addresses per loop. NAC Circuits: Four Class B or 2 Class A (2.0 A each circuit), 6.0 A total NAC Operating Voltage: 24 VDC NAC Minimum Voltage: 19.5 VDC @ 20.4 V battery voltage SLC Loop Circuit Operating Voltage: 24 V peak-to-peak Input Voltage: 120 VAC, 60 Hz 240 VAC 50-60 Hz Input Current: 120 VAC, 2.75 amps max. 240 VAC, 1.4 amps max. Aux Power (Resettable): Two Auxiliary circuits, 24 VDC, 1.75 A Aux Power Supervised Class 2 Power-Limited (Non-Resettable): (maximum current of 1.75 is shared between two circuits). Base Panel Current Draw: Standby: 0.111 amps Alarm: 0.243 amps Operating Temperature: 32°-120° F (0°-49° C) Relative Humidity: 93% (non-condensing) Battery Charger Voltage: +24 VDC Battery Charger Capacity: 55 A/H batteries (cabinet accommodates 12 A/H batteries) Alarm, Trouble & Supervisory Relay Contacts: Form-C, 2 amps @ 24VDC (resistive) Cabinet Dimensions: S3, SLP-BB Dimensions: 14 1/2”Wx20 1/8”Hx4 1/2” D (36.83W x 51.18 H x 11.43 D cm) S3BB-RB Dimensions: 19 3/8”Wx19 3/8”Hx4.5” D (49.22 W x 49.22 H x 11.43 D) TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The S3 Series Control Panel is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult the factory for the latest listing status. UL Listed: S1869 FM Approved MEA FDNY: COA 6162 CSFM: 7165-1703:0176 City of Chicago Approved: Class 1 Reference Certificate of Compliance: VMA 45894-02C ISO 9001 Certification LCD-SLP LCD Touchscreen Annunciator Display GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60782 Rev. B page 1 of 1 Description The Gamewell-FCI, Liquid Crystal Display, Smart Loop Panel (LCD-SLP) is a touchscreen annunciator display used with the S3 Series System. The LCD-SLP provides an easy-to-use, intuitive interface for the operator’s control. The 4.3” (10.92 cm) color touchscreen display shows the following: • System Status • Service modes • Event details The following identify the LED Indicators that display on the panel. • AC (green) • Supervisory (yellow) • Fire Alarm (red) • Trouble (yellow) • Hazard (blue) • Silenced (yellow) The five fully-programmable front panel switch/LED combi- nations provide a direct access to perform the following tasks: • Device Bypass • Lamp Test • Enable/Disable Groups or Devices The display features the following physical switches. •Menu •System Reset • Five Programmable Switches •Drift Walk Test Installation The LCD-SLP is adaptable for installation in either the S3 or E3® Series cabinets. • S3 Series Cabinets - SLP-BB basic system enclosure - S3BB-BB/S3BB-RB system enclosure • E3 Series ® Cabinets- A2 size cabinet (E3BB-BA2, E3BB-RA2)- A size flush cabinet (E3BB-FLUSH-LCD) Specifications Operating Voltage:24 VDC FWR Operating Current:0.030 amp Alarm Current:0.065 amp Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity:0 to 93%,non-condensing at 90° F (32° C) E3 Series® is a registered trademark of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. Features LCD-SLP • Listed per ANSI/UL ® Standard 864 9th Edition. • Provides 4.3” (10.92 cm) color touchscreen display of System Events. • Includes five custom function buttons with LEDs for direct access to system controls. • Offers the following installation options: - Locally mounted in the S3 Series panels. - Remotely mounted in the E3 Series, A2 cabinet or LCD Flush enclosure. • Displays the following six LED indicators: - Alarm - Hazard - Trouble - NAC Silence - Supervisory - AC Power • Shows the Hazard LED to indicate gas, carbon monoxide or other toxic gases. • S3 Series (SLP) supports up to 15 LCD-SLP displays via the RS-485 serial interface. Ordering Information Part Number Description LCD-SLP LCD Touchscreen display unit E3BB-BA2 Remote enclosure with inner door, black, one LCD slot E3BB-RA2 Remote enclosure with inner door, red, one LCD slot E3BB-FLUSH-LCD Remote flush mounting enclosure, black, LCD slot S1869 SIGNALING 7165-1703:0176 Space Age Electronics, Inc. 2007 ED0247 LT10247 Rev.C 1/2 NFPA®Made In U.S.A. MBC Mini Battery Cabinet The MBC “BATTERY CABINET” is designed for the profes- sional installation of systems requiring battery storage and meets the requirement of NFPA 72 (1-5.2.9) stand-by battery storage for battery backup. The MBC allows for easy access and maintenance of the bat- teries while also assisting against unnecessary power drain, interference or degeneration of the battery. The unit can be mounted securely to a wall, preventing mechanical injury or damage to other equipment. Standard Features: 16 Gauge (.062 thk.) cold rolled steel White 2” lettering “BATTERY CABINET” Green ground screw with threaded insert Formed lift-a-way hinge Red or Black textured ¿nish CAT 30 keyed door lock Dimensions: 17” wide x 8” high x 4” deep Six 1/2” and 3/4” EMT conduit knockouts located on both sides, top and back NFPA 72 National Electric Code The door of the MBC lifts away for worry free wiring and battery change-out. Space Age Electronics, Inc. www.1sae.com 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax Space Age Electronics, Inc. 2007 ED0247 LT10247 Rev.C 2/2 Ordering Information: Part # Description SSU00505 MBC Mini Battery Cabinet - Red SSU00506 MBC Mini Battery Cabinet - Black 6SHFL¿ cations: The MBC Mini Battery Cabinet is constructed of 16 gauge (.062 thk.) cold rolled steel and ¿nished with a durable red or black textured, heat-resistant baked-on enamel ¿nish. The front cover is engi- neered with a removable formed lift-a-way hinge, displays “BATTERY CABINET” in 2” white screened lettering and includes a high security CAT 30 keyed door lock. The unit comes with a green ground screw with threaded insert. Overall dimensions measure 17” wide by 8” high by 4” deep. Six 1/2” and 3/4” EMT conduit knockouts are located on both sides, top and back. The battery cabinet meets NFPA 72 National Electric Code requirements. Batteries not included. Removable formedlift-a-way hinge 17” 8” 4 ” Space Age Electronics, Inc. www.1sae.com 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax This document is subject to change without notice, see doc # ED0479 for legal disclaimer Agency Approvals: UOXX.S2580 UL Listed Control Unit Accessories PS SERIESTERMINALS: (mm) DIMENSIONS: inch (mm)PERFORMANCE SPECIFICATIONS Nominal Voltage 12 volts (6 cells) Nominal Capacity 20-hr. (900mA to 10.50 volts) 10-hr. (1.70A to 10.50 volts) 5-hr. (3.20A to 10.20 volts) 1-hr. (11.1A to 9.00 volts) 18.00 AH 17.00 AH 16.00 AH 11.1 AH Approximate Weight 12.60 lbs. (5.72 kg) Internal Resistance (approx.) 14.0 milliohms Max Short-Duration Discharge Current (10 Sec.)180.0 amperes Shelf Life (% of nominal capacity at 68°F (20°C) 1 Month 3 Month 6 Month 97% 91% 83% Operating Temperature Range Charge Discharge 5°F (-15°C) to 122°F (50°C) -4°F (-20°C) to 140°F (60°C) Case ABS Plastic Power Sonic Chargers PSC-122000A-C PSC-122000-PC PSC-124000-PC PSC-124000A-C www.power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. © 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.All data subject to change without notice. E&O.E CORPORATE HEADQUARTERS (USA AND INTERNATIONAL EXCLUDING EMEA) Power-Sonic Corporation 7550 Panasonic Way, San Diego, California 92154 T: +1 (619) 661 2020 F: +1 (619) 661 3650 E: customer-service@power-sonic.com POWER-SONIC EUROPE LIMITED (EMEA – EUROPE, MIDDLE EAST AND AFRICA) 3 Buckingham Square, Hurricane Way, Wickford, Essex SS11 8YQ T: +44 (0)1268 560686 F: +44 (0)1268 560902 E: salesEMEA@power-sonic.com General Purpose Fire & SecurityEmergency Lighting Warning: Risk of fire, explosion, or burns.Do not disassemble,heat above 60 C, or incinerate. Rechargeable Sealed Lead-Acid BatteryDC power, constant voltage chargeCycle use: 14.4 - 15.0V(20 C)Standby use: 13.5 - 13.8V(20 C)Initial current: 5.4A MAX 8313340 01054 MODEL PS-12180 NB 12 Volt 18.0 Amp. Hr. Sealed RechargeableBattery 120180400208 L HT H W L: 7.13 (181) W: 3.00 (76) H: 6.59 (167) HT: 6.59 (167) Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice. FEATURES •10 – 12 year design life •Absorbent Glass Mat (AGM) technology for superior performance •Valve regulated, maintenance free spill proof construction •Power/volume ratio yielding excellent energy density •Rugged vibration and impact resistant ABS case and cover •Gas recombination technology APPROVALS •Approved for transport by air. D.O.T., I.A.T.A., F.A.A. ERH'%&GIVXMƼIH •U.L. recognized •ISO9001:2015 – Quality management systems Medical Rev1: 11/18PS-12180S 12V 18.0 AH @ 20-hr.12V 17.0 AH @ 10-hr. Rechargeable Sealed Lead Acid Battery PS – General Purpose Series Torque – Not Applicable 6.351.57.95 3.4 2.5 0.8F2: Quick disconnect tabs, 0.250" x 0.032" – Mate with AMP. INC FASTON “250” series NB2: Tin plated brass post with ‘Nut & Bolt’ fasteners Torque: 3.9~5.4 Nxm T12: Threaded insert with 5mm stud fastener Torque: 2.0~3.0 Nxm 14mm 4.5mm6mm12mm2mm 12mm M5 6mm PS SERIESwww.power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. © 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.All data subject to change without notice. E&O.E CORPORATE HEADQUARTERS (USA AND INTERNATIONAL EXCLUDING EMEA) Power-Sonic Corporation 7550 Panasonic Way, San Diego, California 92154 T: +1 (619) 661 2020 F: +1 (619) 661 3650 E: customer-service@power-sonic.com POWER-SONIC EUROPE LIMITED (EMEA – EUROPE, MIDDLE EAST AND AFRICA) 3 Buckingham Square, Hurricane Way, Wickford, Essex SS11 8YQ T: +44 (0)1268 560686 F: +44 (0)1268 560902 E: salesEMEA@power-sonic.com SHELF LIFE & STORAGE LIFE CHARACTERISTICS IN STAND-BY USE Capacity Retention Ratio (%)Standing Period (Months) 100 80 60 40 00 2 4 6 8 10 12 14 16 18 20 40oC (104oF) 30oC (86oF)20oC (68oF) 5oC (41oF) Charging is not necessary unless 100% of capacity is required. Charging beforeuse is necessaryto help recoverfull capacity. 100 80 60 40 20 0 012345 Ambient THPSHUDWXUHÛ&Û) Float Charging Voltage 2.25 - 2.30 V/Cell Years CHARGING Cycle Applications: Apply constant voltage charge at 2.35v/c – 2.45v/c (14.1 – 14.7v for 12v Monobloc) at 20°C. Initial charging current should be set at less than 0.25C %QTW7[MXGLXSƽSEXGLEVKIXSEZSMHSZIVGLEVKMRK “Float” or “Stand-By” Service: Apply constant voltage charge of 2.25v/c – 2.30v/c (13.5 to 13.8 volts for 12v Monobloc at 20°C. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. Temperature Compensation: Charging Voltage for both Cyclic and Standby applications should be regulated in relation to ambient temperature. As temperature rises charging voltage should be reduced to prevent overcharge and increased as temperature falls to avoid undercharge. For further charging information including temperature compensation factors, see Power Sonic Technical Manual/ 4S[IV7SRMG'LEVKIVWTIGMƼGEXMSRW CHARGERS Power Sonic offers a wide range of chargers suitable for batteries with a variety of capacities. Please refer to our website for more information on our switch mode and transformer type chargers. Please contact our technical department for advice if ]SYLEZIHMƾGYPX]MRPSGEXMRKEWYMXEFPIGLEVKIV FURTHER INFORMATION Please refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), -73GIVXMƼGEXMSRIXG APPLICATIONS •General purpose •Emergency lighting •Medical •Fire and security PS-12180S 12V 18.0 AH @ 20-hr.12V 17.0 AH @ 10-hr. Rechargeable Sealed Lead Acid Battery PS – General Purpose Series Rev1: 11/18 PS SERIESTERMINALS: (mm) DIMENSIONS: inch (mm)PERFORMANCE SPECIFICATIONS Nominal Voltage 12 volts (6 cells) Nominal Capacity 20-hr. (350mA to 10.50 volts) 10-hr. (650mA to 10.50 volts) 5-hr. (1.2A to 10.20 volts) 1-hr. (4.5A to 9.00 volts) 7.00 AH 6.50 AH 6.00 AH 4.50 AH Approximate Weight 4.80 lbs. (2.18 kg) Internal Resistance (approx.) 23.0 milliohms Max Short-Duration Discharge Current (10 Sec.)70.0 amperes Shelf Life (% of nominal capacity at 68°F (20°C) 1 Month 3 Month 6 Month 97% 91% 83% Operating Temperature Range Charge Discharge 5°F (-15°C) to 122°F (50°C) -4°F (-20°C) to 140°F (60°C) Case ABS Plastic Power Sonic Chargers PSC-12800A-C PSC-121000-PC www.power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. © 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.All data subject to change without notice. E&O.E CORPORATE HEADQUARTERS (USA AND INTERNATIONAL EXCLUDING EMEA) Power-Sonic Corporation 7550 Panasonic Way, San Diego, California 92154 T: +1 (619) 661 2020 F: +1 (619) 661 3650 E: customer-service@power-sonic.com POWER-SONIC EUROPE LIMITED (EMEA – EUROPE, MIDDLE EAST AND AFRICA) 3 Buckingham Square, Hurricane Way, Wickford, Essex SS11 8YQ T: +44 (0)1268 560686 F: +44 (0)1268 560902 E: salesEMEA@power-sonic.com General Purpose Fire & SecurityEmergency Lighting MODEL PS-1270 F1 12 Volt 7.0 Amp. Hr. Warning: Risk of fire, explosion, or burns.Do not disassemble, heat above 60 C, or incinerate. Rechargeable Sealed Lead-Acid BatteryDC power, constant voltage chargeCycle use: 14.4 - 15.0V(20 C)Standby use: 13.5 - 13.8V(20 C)Initial current: 2.1A MAX 8013340 01000Sealed Rechargeable Battery 120070260211 L HT H W L: 5.95 (151) W: 2.56 (65) H: 3.70 (94) HT: 3.86 (98) Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice. FEATURES •Absorbent Glass Mat (AGM) technology for superior performance •Valve regulated, maintenance free spill proof construction •Power/volume ratio yielding excellent energy density •Rugged vibration and impact resistant ABS case and cover •Gas recombination technology •5 year design life APPROVALS •Approved for transport by air. D.O.T., I.A.T.A., F.A.A. ERH'%&GIVXMƼIH •U.L. recognized •ISO9001:2015 – Quality management systems Medical Rev1: 11/18PS-1270 12V 7.0 AH @ 20-hr.12V 6.5 AH @ 10-hr. Rechargeable Sealed Lead Acid Battery PS – General Purpose Series OR Torque – Not Applicable 4.751.56.35 3.2 2.5 0.8F1: Quick disconnect tabs, 0.187" x 0.032" – Mate with AMP. INC. FASTON “187” series Torque – Not Applicable 6.351.57.95 3.4 2.5 0.8F2: Quick disconnect tabs, 0.250" x 0.032" – Mate with AMP. INC FASTON “250” series PS SERIESwww.power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. © 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.All data subject to change without notice. E&O.E CORPORATE HEADQUARTERS (USA AND INTERNATIONAL EXCLUDING EMEA) Power-Sonic Corporation 7550 Panasonic Way, San Diego, California 92154 T: +1 (619) 661 2020 F: +1 (619) 661 3650 E: customer-service@power-sonic.com POWER-SONIC EUROPE LIMITED (EMEA – EUROPE, MIDDLE EAST AND AFRICA) 3 Buckingham Square, Hurricane Way, Wickford, Essex SS11 8YQ T: +44 (0)1268 560686 F: +44 (0)1268 560902 E: salesEMEA@power-sonic.com SHELF LIFE & STORAGE LIFE CHARACTERISTICS IN STAND-BY USE Capacity Retention Ratio (%)Standing Period (Months) 100 80 60 40 00 2 4 6 8 10 12 14 16 18 20 40oC (104oF) 30oC (86oF)20oC (68oF) 5oC (41oF) Charging is not necessary unless 100% of capacity is required. Charging beforeuse is necessaryto help recoverfull capacity. 100 80 60 40 20 0 012345 Ambient THPSHUDWXUHÛ&Û) Float Charging Voltage 2.25 - 2.30 V/Cell Years CHARGING Cycle Applications: Apply constant voltage charge at 2.35v/c – 2.45v/c (14.1 – 14.7v for 12v Monobloc) at 20°C. Initial charging current should be set at less than 0.25C %QTW7[MXGLXSƽSEXGLEVKIXSEZSMHSZIVGLEVKMRK “Float” or “Stand-By” Service: Apply constant voltage charge of 2.25v/c – 2.30v/c (13.5 to 13.8 volts for 12v Monobloc at 20°C. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. Temperature Compensation: Charging Voltage for both Cyclic and Standby applications should be regulated in relation to ambient temperature. As temperature rises charging voltage should be reduced to prevent overcharge and increased as temperature falls to avoid undercharge. For further charging information including temperature compensation factors, see Power Sonic Technical Manual/ 4S[IV7SRMG'LEVKIVWTIGMƼGEXMSRW CHARGERS Power Sonic offers a wide range of chargers suitable for batteries with a variety of capacities. Please refer to our website for more information on our switch mode and transformer type chargers. Please contact our technical department for advice if ]SYLEZIHMƾGYPX]MRPSGEXMRKEWYMXEFPIGLEVKIV FURTHER INFORMATION Please refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), -73GIVXMƼGEXMSRIXG APPLICATIONS •General purpose •Emergency lighting •Medical •Fire and security PS-1270 12V 7.0 AH @ 20-hr.12V 6.5 AH @ 10-hr. Rechargeable Sealed Lead Acid Battery PS – General Purpose Series Rev1: 11/18 HPF902ULADA Fire Alarm Power Supply h1012cov.jpgDescription The HPF902ULADA Fire Alarm Power Supply from Honeywell Power Products offers the highest value among power sup- plies available today. It delivers 9.0 A of notification appliance circuit power and built-in synchronization for appliances from System Sensor, Gentex, Wheelock, and Faraday. Our design represents the state-of-the-art in fire alarm supplies. Yet for all its sophistication, it is an extremely cost-effective notification power supply. The HPF902ULADA is a 9.0 A notification power expander that provides its own AC power connection, battery charging circuit, and backup battery space, for use with fire and security controls. It is ideal for powering notification appliances required by the Americans with Disabilities Act (ADA). It con- tains a built-in ANSI cadence pattern, which can upgrade older control panels that lack cadence capability. Benefits • Extends and supports power for additional fire alarm devices. • Instantaneous switchover to standby battery (if equipped) when AC fails, maintaining power to all attached devices without intervention. • Strobe signal "passes through" allowing syncing of large systems. • LED lights for quick and easy diagnosis, troubleshooting, and status indication. Features • 9.0 A of notification power. • 24 VDC filtered output voltage. • DIP switches for easy reconfiguration. • Power supply has advanced switch-mode design. • Four power-limited notification outputs: two Class A, or four Class B, or one Class A and two Class B. • Additional continuous auxiliary output. • 3.0 A per output circuit. • Two inputs; two Class B or two Class A. • Ground fault detector/indicator. • Independent trouble relay. • AC loss delay option shuts off power to nonessential high current accessories, such as magnetic door holders. • Built-in synchronization for appliances from System Sensor, Gentex, Wheelock and Faraday. • Stand-alone operation. • Lightweight design adds to ease of installation and reduces shipping costs. • Operates with most polarized, UL-Listed notification devices. • Complies with UL 864, UL 1481, and NFPA 72. • Built-in ANSI cadence pattern output capability. • Connection to local fire control: – May be connected to a local fire control which utilizes Class A or Class B type notification circuits operating between 9 and 32 VDC. – One unit can be connected to each notification circuit on the control panel and still provide full supervision of the notification circuits all the way to the control panel. • Supervision for a variety of functions, including: –Low AC power. – Low battery condition. – Earth ground fault. – Auxiliary output power limit condition. – EOL supervision trouble or power-limited condition at an output. – Form-C trouble relay. Electrical Specifications • AC input: 120 VAC @ 3.6 A. • Output: 24 VDC @ 9.0 A (9.0 A total from all notification circuits and auxiliary circuit). • Amps per output circuit: 3.0 A. • Current draw of unit on battery: 75 mA standby, 175 mA in alarm. • Auxiliary power circuits: 1. • Notification circuits: 4. • Output configuration options: 2 Class A (Style Z); 4 Class B (Style Y); or 1 Class A and 2 Class B. • Notification circuit output: 20.4 to 27.3 VDC @ 3.0 A each. • Inputs: 2, with configuration 2 Class B or 2 Class A. • Input voltage range: 9 – 32 VDC. • Battery charging capacity: 33.0 AH. • Ambient temperature rating: 32°F to 120°F (0°C to 49°C). • Relative humidity: 85% non-condensing maximum. Mechanical Specifications • Dimensions: 16.0" H x 12.25" W x 3.0" D (cm: 40.64 H x 30.88 W x 7.62 D). • Indicator lights: AC Power On (green), Battery Trouble (yellow), Ground Fault (yellow), Aux Trouble (yellow), Output Troubles (1 – 4, yellow). Automation and Control Solutions Honeywell 12 Clintonville Road 1(877) HPP-POWR Northford, CT 06472-1610 hpp_techserv@honeywell.com www.honeywellpower.com This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. DH-1012:B May 2010 Made in the U.S.A. ® U.S. Registered Trademark © 2010 Honeywell International Inc. Page 2 of 2 Listings Listings and approvals below apply to the basic HPF902ULADA panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL Listed: file S6677 • CSFM: 7300-1637 AOM-2SF Velociti® Series AOM-2SF Addressable Output Relay Supervised Control Module Addressable Devices General The Gamewell-FCI Velociti® Series addressable output supervised control module (AOM-2SF) allows a Gamewell-FCI analog addressable fire alarm control panel to switch an external power supply, such as a DC supply or audio amplifier (up to 80 VRMS) to notification appliances. The AOM-2SF notification appliance circuit can be wired either Class A (Style Z) or Class B (Style Y). It also supervises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN or SHORT CIRCUIT. The module contains a panel controlled LED. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the SLC devices and certain Gamewell-FCI analog addressable fire alarm control panels. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net result is a superior response speed up to five times greater than the earlier designs. The AOM-2SF module is designed for installation in the signaling line circuit of any Gamewell-FCI analog addressable fire alarm control panel. The signaling line circuits of Gamewell-FCI analog addressable fire alarm control panels are designed to accommodate up to 159 modules per circuit. The AOM-2SF is designed to mount in a 4” (10.16 cm) square junction box 2 1/8” (5.5 cm) deep. Table 1 lists the relay contact ratings. Ordering Information AOM-2SF: Addressable output supervised control module FEATURES & BENEFITS • Listed under UL ® Standard 864 and UL2572 for Mass Notification • Designed as a compact size to allow easy installation • Includes Class A, Style Z, or Class B, Style Y notification appliance circuit • Accommodates audio amplifiers up to 80 VRMS • FM Listed as suitable for a releasing device service • Includes a bi-color LED that flashes green whenever the module is addressed, and lights steady red upon activation* *Note: Only the red LED is operative in panels that do not operate in Velociti® mode Current Rating Maximum Voltage Load Description Application 3A 30 VDC Resistive Non-Coded 2A 30 VDC Resistive Coded 0.9A 110 VDC Resistive Non-Coded 0.5A 125 VAC Resistive Non-Coded 0.5A 30 VDC Inductive (L/R=5ms) Coded 1A 30 VDC Inductive (L/R=2ms) Coded 0.5A 125 VAC Inductive (PF=.35) Non-Coded 0.7A 75 VAC Inductive Non-Coded Table 1: Relay Contact Ratings Velociti® Series AOM-2SF Technical Specifications 9020-0627 | H | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series AOM-2SF and other products available by visiting www.Gamewell-FCI.com SYSTEM Supervisory Current: .000375 amps Alarm Current: .0065 amps Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 10 to 93% relative humidity (non-condensing) Dimensions: 4 1/2” H x 4” W x 1 1/4” D (11.4 H x 10.2 W x 3.2 D cm) TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The Velociti Series AOM-2SF are designed to comply with the following standard: UL Standards: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1949 FM: 3023594 MEA FDNY: 227-03-E Vol. IV CSFM: 7300-1703:0102 ISO 9001 Certification Agency Listings S4011 S5512 7300-1653:202 3032010 4ZODt$JSDVJU™.PEVMF 5IF4ZODt$JSDVJUNPEVMFTZODISPOJ[FT4QFDUS"MFSU¥ "EWBODFTUSPCFTBU)[BOEIPSOTBOEDIJNFTBU UFNQPSBMPWFSBTJOHMFQBJSPGXJSFT1BUFOUFENPEVMF UFDIOPMPHZBMTPBMMPXTUIFTJMFODJOHPGIPSOTPS DIJNFTPOIPSOTUSPCFBOEDIJNFTUSPCFNPEFMTPWFS BQBJSPGXJSFT 'FBUVSFT tTwo-wire operation from module to the devices tSilences horns and chimes over a two-wire loop tSynchronizes strobes at 1 Hz tSynchronizes horns and chimes to temporal 3 pattern tPatented technology tInterconnects modules for multiple zone synchronization tModule controls two Style Y (Class B) circuits or one Style Z (Class A) circuit tNew NAC slave feature enables the interconnection of slave modules over a supervised NAC loop 5IF.%-.PEVMF is designed to work with the SpectrAlert and SpectrAlert Advance series of notification appliances to provide a means of synchronizing the temporal-coded horns and chimes, synchronizing the one-second flash timing of the strobe, and silencing the horns and chimes of the horn/strobe and chime/ strobes combination over a two-wire circuit while leaving the strobes active. "QQMJDBUJPO'MFYJCJMJUZ5IF4ZODt$JSDVJUNPEVMFJTEFTJHOFEUP power and synchronize either two 3-amp circuits wired in Class B, or one 3-amp circuit powered as Class A. Should more than two zones require synchronization, additional modules can be added by interconnecting the “slave” input and output terminals between modules. 0IJP"WFOVFt4U$IBSMFT *- 1IPOF4&/403t'BY ª4ZTUFN4FOTPS Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. "tt )PSOTBOE$IJNFT4JMFODFE0WFS5XP8JSF $JSDVJU "OZNJYPG)PSO4USPCFT $IJNF4USPCFTPS4USPCFPOMZEFWJDFTJT acceptable 2. Horn and chime control connects to interruptible power source $VSSFOU%SBXBOE0SEFSJOH*OGPSNBUJPO Red White Voltage Average Current (mA) Peak Current (mA) In-rush Current (mA) NAC Slave Input (mA) DC FWR DC FWR DC FWR DC FWR .%-3 .%-3" $BOBEJBO .%-8 .%-8" $BOBEJBO 12 10 12 50 60 100 120 3.5 4 24 12 15 60 75 120 150 4.5 5 4ZODt$JSDVJU™.PEVMF4QFDJGJDBUJPOT Architectural/Engineering Specifications 4ZODISPOJ[BUJPO$JSDVJU.PEVMFTIBMMCFB4ZTUFN4FOTPS4ZODt$JSDVJU.PEFM @@@@@@@@@MJTUFEUP6-BOE6-BOETIBMMCFBQQSPWFEGPSmSF protective service. The module shall synchronize SpectrAlert® or SpectrAlert Advance strobes at 1 Hz and horns at temporal 3. Also, the module shall be capable of silencing the horns on horn/strobe models, while operating the strobes, over a single pair of wires. The module shall be capable of mounting UPBʔʔcʃʈ¨ʔʔcʃʈ¨ʔcʊCBDLCPYBOETIBMMDPOUSPMUXP4UZMF: DMBTT# PS one Style Z (class A) circuit. The module shall be capable of multiple zone synchronization by connecting multiple modules (slaves) together. Slaves DBOCFESJWFOGSPNFJUIFSUIFTMBWFPVUQVUPGBQSJPS.%-PSGSPNUIF/"$ output of the master. Using the NAC enables all wiring to be supervised, whereas the slave-out terminals are not supervised, so their use is confined to specific applications. Note: The module shall not operate on a coded power supply. Physical Specifications Dimensions -¨8 Mounting ʔʔcʃʈ¨ʔʔcʃʈ¨ʔcʊCBDLCPY Indoor Operating Temperature ¡UP¡' ¡UP¡$ Electrical/Operating Specifications Operating Voltage PS7%$BOE'83VOmMUFSFE Operating Voltage Range (12 V)8.5 to 17.5 VDC Operating Voltage Range (24 V)16.5 to 33 VDC Maximum Load on Loop 3 Amps/zone U.S. Patent Nos. 5,850,178 FACP #1 + – + – + – + – + – + – + – EOL FACP #2 NAC 1 + – + – } } } } HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN +–+–+–+–}}}}ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF + – + – + – + – } } } } HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN +–+–+–+–}}}}ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF}B+ B– NAC 1 }B+ B– NAC 2 }B+ B– NAC 3 }B+ B–}A+ A– TO NEXT SPECTRALERT ADVANCE DEVICE OR EOL TO NEXT SPECTRALERT ADVANCE DEVICE OR EOL TO NEXT SPECTRALERT ADVANCE DEVICE TO NEXT SPECTRALERT ADVANCE DEVICE WIRING MUST BE CONTAINED WITH EITHER THE COMMON ENCLOSURE OF MODULES OR ENCLOSURES WITHIN 20 FEET OF EACH OTHER WITH WIRING INSIDE CONDUIT STYLE Z ZONES (CLASS A) 2 STYLE Y ZONES (CLASS B)MASTER SLAVE FACP + – + – + – + – + – + – NAC 3 + – + – } } } } HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN +–+–+–+–}}}}ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF + – + – + – + – } } } } HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN +–+–+–+–}}}}ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF}B+ B– NAC 1 NAC 2 }B+ B–}B+ B–}A+ A– TO NEXT SPECTRALERT ADVANCE DEVICE OR EOL TO NEXT SPECTRALERT ADVANCE DEVICE OR EOL TO NEXT SPECTRALERT ADVANCE DEVICE TO NEXT SPECTRALERT ADVANCE DEVICE WIRING MUST BE CONTAINED WITH EITHER THE COMMON ENCLOSURE OF MODULES OR ENCLOSURES WITHIN 20 FEET OF EACH OTHER WITH WIRING INSIDE CONDUIT STYLE Z ZONES (CLASS A) 2 STYLE Y ZONES (CLASS B) (STYLE Z CLASS A) MASTER SLAVE FACP + – + – + – + – + – + – FACP NAC 1 NAC 2 + – + – } } } } HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN +–+–+–+–}}}}ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF + – + – + – + – } } } } HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN +–+–+–+–}}}}ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF}B+ B– NAC 1 NAC 2 }B+ B–}B+ B–}B+ B– TO NEXT SPECTRALERT ADVANCE DEVICE OR EOL TO NEXT SPECTRALERT ADVANCE DEVICE OR EOL TO NEXT SPECTRALERT ADVANCE DEVICE OR EOL 2 STYLE Y ZONES (CLASS B) TO NEXT MDL3 NAC SLAVE IN OR EOL MASTER SLAVE .BTUFS4MBWF.PEF .BTUFS4MBWF6TJOH/"$4MBWF*OQVU ASD-PL2F/ASD-PTL2F ASD-PL2FR Velociti® Series 3 Detectors Photoelectric Detectors Addressable Devices Photoelectric Detector Description The Gamewell-FCI, Velociti® Series 3 intelligent photoelectric detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 smoke detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The photoelectric detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. The Gamewell-FCI, ASD-PL3 photoelectric detector's re-designed optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The sensitivity of Velociti series detectors can be programmed using the control panel software to suit the environment. The ASD-PL3R photoelectric detector is also remote test capable that may be used with a DNR (DNRW) duct smoke detector housing. The ASD-PTL3 multi- sensor detector offers either photoelectric detection or thermal detection through dual electronic thermistors at 135°F fixed temperature thermal sensing. For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number after the detector model. Note: Although the E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, the GWF-7075 panel does not support the CLIP protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL® Standard 268 7th Edition • Designed with a new profile to offer modern and improved aesthetics • Contains a built-in functional test switch activated by external magnet • Supports a low standby current • Provides rotary address switches (01-159) • Supplies optional relay, isolator, or sounder bases (standard or low frequency) • Includes dual LEDs for 360° visibility • Offers expanded color options 2 Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. NOTE: “WH” suffix indicates Bright White color model. ASD-PL3: Photoelectric smoke detector, bright white, Velociti ASD-PL3R: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, bright white, Velociti ASD-PTL3: Photoelectric smoke detector with thermal sensing, bright white, Velociti ASD-PL3-IV : Photoelectric smoke detector, ivory, Velociti/ CLIP ASD-PL3R-IV: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, ivory, Velociti/CLIP ASD-PTL3-IV : Photoelectric smoke detector with thermal sensing, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. Note: “IV” suffix indicates Flashscan and CLIP devices. “WH” suffix indicates bright white B501-WHITE: 4” Flangeless mounting base, bright white B501-WHITE-BP: 4” Flangeless mounting base bulk pack, bright white B501-IV: 4” Flangeless mounting base, ivory B300-6: 6” Flanged mounting base, bright white B300-6-IV: 6” Flanged mounting base, ivory B300-6-BP: 6” Flanged mounting base bulk (Pack of 10) B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B200S-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, bright white B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory DNR: Intelligent duct detector housing, non-relay DNRW: Intelligent duct detector housing, non-relay, watertight Ordering Information Accessories SMB600: Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6” Base, bright white TR300-IV: Accessory Flange Ring for B300 6” Base, ivory RA100Z: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single-gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCSCOF Series detectors. (Pack of 10) CK300-BL: Black detector kit. (Pack of 10) CK300-IR-Bl: Black, detector color kit for use with MCSCOF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows the installation and/ or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR2B. Shipped with three, 5-foot (1.524,m) sections. Velociti® Series 3 Detectors Technical Specifications 9020-0617 | K | 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com SYSTEMS Photoelectric Intelligent Detector: Physical Specifications Height: 2.0 inches (51 mm) installed in B300-6 base Diameter: 6.1 inches (15.49 cm) installed in B300-6 base 4 inches (10.16 cm) installed in B501 base Shipping Weight: 3.4 oz (96.4 g) Operating Temperature Range: Photo: 32° F to 122° F (0° C to 50° C) Photo in Duct Applications: -4° F to 158° F (-20° C to 70° C) Photo with Thermal: 32° F to 100° F (0° C to 38° C) Operating Humidity Range: 10% to 93% non-condensing Rate-of-Rise Detection: Responds to greater than 15°F/minute or 135°F (8.3° C/minute or 57°C Air Velocity Range: 0 to 4,000 ft/min (0 to 1219.2 m/min) Electrical Specifications Voltage Range: 15 to 32 VDC Standby Current (@ 24 VDC): 200 UA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): 2 mA @ 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: 0.0063 STANDARDS The Velociti® Series 3 Photoelectric Detectors are designed to comply with the following standard: UL Standard: UL 268 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA FDNY: COA-219-02-E Vol. VI CSFM: 7272-1703:0501 ISO 9001 Certification Thermal Detector Velociti® Series 3 Detectors Thermal Detectors Addressable Devices Description The Gamewell-FCI, Velociti® Series 3 intelligent thermal detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 heat detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The thermal detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. Velociti Series 3 thermal detectors provide cost-effective, intelligent property protection using the following single thermistor: • ATD-L3 offers 135°F fixed thermal detection. • ATD-L3R offers 135°F fixed and rate-of-rise thermal detection. • ATD-L3H provides fixed high-temperature detection at 190°F . For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number that appears after the detector model. Note: The E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, and the GWF-7075 panel supports only the Velociti® protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL® 268 7th Edition • Designed with a new profile to offer modern and improved aesthetics • Contains a built-in functional test switch activated by an external magnet • Supports a low standby current • Provides rotary address switches (01-159) • Supplies optional relay, isolator, or sounder bases (standard or low frequency) •Includes dual LEDs used for 360° visibility • Offers expanded color options 2 Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. NOTE: “WH” suffix indicates Bright White color model. ATD-L3: Thermal heat detector, 135°F fixed, bright white, Velociti ATD-L3-IV: Thermal heat detector, 135°F fixed, ivory, Velociti/CLIP ATD-L3R: Thermal heat detector, 135°F rate of rise, bright white, Velociti ATD-L3R-IV: Thermal heat detector, 135°F rate of rise, ivory, Velociti/CLIP ATD-L3H: Thermal heat detector, 190°F high temp, bright white, Velociti ATD-L3H-IV: Thermal heat detector, 190°F high temp, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. B501-White: 4" Flangeless mounting base, bright white B501-White-BP: 4" Flangeless mounting base bulk pack, bright white B501-IV: 4" Flangeless mounting base, ivory B501-BL 4" Flangeless mounting base, B300-6: 6" Flanged mounting base, bright white B300-6-IV: 6" Flanged mounting base, ivory B300-6-BP: 6" Flanged mounting base bulk pack B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B200S-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, bright white B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory Ordering Information Accessories SMB600: Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6" Base, bright white TR300-IV: Accessory Flange Ring for B300 6" Base, ivory RA100Z: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single-gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCS- COF Series detectors. (Pack of 10) CK300-BL: Black detector kit (Pack of 10) CK300-IR-Bl: Black, detector color kit for use with MCS- COF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows the installation and/or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR2B. Shipped with three, 5- foot (1.524,m) sections. Velociti® Series 3 Detectors Technical Specifications 9020-0620 | G | 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks and CLIP™ is a trademark of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com SYSTEMS Thermal Intelligent Detector Physical Specifications Height: 2.0 inches (51 mm) installed in B300-6 base Diameter: 6.1 inches (15.6 cm) installed in B300-6 base 4 inches (10.2 cm) installed in B501 base Shipping Weight: 3.4 oz (95 g) Operating Temperature Range: Thermal 135° F fixed: -4° F to 100° F (-20° C to 38° C) Thermal 135° F rate-of-rise: -4° F to 100° F (-20° C to 38° C) Thermal 190° F rate-of-rise: -4° F to 135° F (-20° C to 57° C) Operating Humidity Range: 10% to 93% non- condensing Rate-of-Rise Detection: : Responds to greater than 15°F/minute or 135°F (8.3° C/minute or 57°C Electrical Specifications Voltage Range: : 15 to 32 VDC Standby Current (@ 24 VDC): 200 uA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): : 2 mA @ 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): : 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: : 0.0063 STANDARDS The Velociti® Series 3 Thermal Detectors are designed to comply with the following standard: UL Standard: UL 268 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA-FDNY: 219-02-E Vol. VI CSFM: 7270-1703-0502 ISO 9001 Certification MS-7 Series MS-7 Series Manual Fire Alarm Pull Stations Addressable Devices General The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide variety of configurations. The pull stations comply with the Americans with Disabilities Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle. All pull stations include a key lock/reset which is keyed alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull stations. MS-7AF Velociti Addressable Station The MS-7AF Velociti® Series addressable station is a double action pull station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the pull station causes its assigned address to register at the fire alarm control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The station features screw terminals. MS-7ASF Velociti Addressable Station The MS-7ASF Velociti® Series addressable pull station is a single action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is activated.* The station features screw terminals. The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response speed up to five times greater than earlier designs. MS-7 Double Action Station The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. FEATURES & BENEFITS • Addressable stations compatible with all Gamewell-FCI analog addressable fire alarm controls • Conventional stations suitable for use with any UL® Listed control panel • The pull stations (MS- 7LOB) are Listed for outdoor applications • Complies with ADA pull force requirements • Offers surface or semi- flush mounting • Shock and vibration resistant • Both single and double action pull stations available • Includes a tumbler lock for test and reset keyed alike with analog addressable fire alarm controls *Only the red LED is operative in panels that do not operate in Velociti mode 2 MS-7S Single Action Station The MS-7S single action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and wire leads for connection to an initiating circuit. MS-7SP Double Action Station The MS-7SP is a double action pull station similar to the MS-7 station, with the additional feature of including both English and Spanish instructions molded into the unit. MS-7LR Dual-action Agent Release Station The MS-7LR is designed for use with the Gamewell-FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems. It features a set of single pole contacts and screw terminals used to connect to an initiating circuit. MS-7LRA Agent Release Station with Abort The MS-7LRA is designed for use with the Gamewell- FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabilities are required. It consists of the following: • An MS-7LR mounted on a plate with an abort switch • LED indicators that signal system normal and system activated status MS-7LOB Double Action Station (Listed for Outdoor Applications) The MS-7LOB station must be mounted on a Model SB-I/O backbox. In retrofit applications, the pull station is UL Listed for use with the WP-10 backbox. It is intended for use with conventional control panels and has a set of single pole contacts and screw terminals. Mounting The MS-7 interior pull stations may be surface mounted or semi-flush mounted on a standard double-gang, or 4-inch (10.2 cm) square electrical box. An optional trim ring (BG12TR) may also be used for semi-flush mounting. NYC-Plate The NYC-Plate provides the backplate for the manual pull station. (See Figure 1). Figure 1 NYC-Plate Ordering Information MS-7: Double action station MS-7AF**: Velociti addressable double action station MS-7ASF**: Velociti addressable single action station MS-7S: Single action station, wire leads MS-7SP: Double action station, English and Spanish instructions MS-7LR: Agent release station, dual-action MS-7LRA: Agent release station with abort switch, LED indicators, dual- action MS-7LOB: Double action station, outdoor use (Includes SB-I/O - Indoor/outdoor use backbox) SB-I/O: Indoor/outdoor use backbackbox SB-10: Surface backbox BG12TR: Trim ring for semi-flush mount, plastic NY-PLATE: NYC backplate for manual pull station **For use with the Gamewell-FCI analog addressable control panels only. MS-7 Series Technical Specifications 9020-0616 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Velociti® and Gamewell-FCI are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s MS-7 Series and other products available by visiting www.Gamewell-FCI.com SYSTEMS Material: Lexan® Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive) Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D (14 x 10.1 x 3.2 cm) Operating Temperature: (MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C) (MS-7LOB): -30° to 150° F (-35° to 66° C) Relative Humidity : (MS-7AF, MS-7ASF): 10 to 93% (non-condensing) (MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C) Alarm Current: .0030 amp. 0.007 for LED Supervisory Current: (MS-7AF, MS-7ASF): .00030 amps. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The MS-7 Series is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2465 FM: 3023594 MEA FDNY: 67-02-E Vol. VII CSFM: 7160-1703:0119 7160-1703:0170 7160-1703:0109 ISO 9001 Certification AMM-2F AMM-2F Addressable Monitor Module Addressable Devices General The Gamewell-FCI Velociti®Series, addressable monitor module AMM-2F is a single Style B, Class B initiating device circuit (IDC) with a 47KW end-of-line resistor. This module provides an address for any device or group of devices connected to this circuit on the signaling line circuit (SLC) of the Gamewell-FCI addressable series fire alarm control panel. Any initiating device with normally open (N.O.) dry contacts may be made addressable when connected to the AMM-2F module. The Velociti®Seriems use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The AMM-2F module can be programmed to provide a wide variety of input functions to the Gamewell-FCI addressable series fire alarm control panels. It can be identified as a manual station, heat detector, plenum detector, waterflow switch, tamper switch, N.O. contact, smoke detector, projected beam smoke detector, sub loop, remote zone, etc. It can also serve as a remote system silence, system reset, system acknowledge or drill switch. It is even possible to customize its device type to meet specific job requirements. The initiating device circuit of the AMM-2F can support a maximum line resistance of up to 40 ohms allowing the use of linear heat detection devices. The compact size facilitates the installation of the module inside manual stations, or mounting boxes of various types of alarm initiating devices. Ordering Information AMM-2F: Addressable monitor module, single circuit, Style B, Class B FEATURES & BENEFITS •Compact size allows easy installation • Class B, Style B, initiating circuit • 40 Ohm line resistance for each initiating device circuit • Connects to any normally open dry contact device AMM-2F Technical Specifications 9020-0626 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s AMM-2F and other products available by visiting www.Gamewell-FCI.com System Supervisory Current: .000375 amps Alarm Current: .00060 amps Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 10 to 93% (non-condensing) End-of-Line Resistance: 47K ohms Dimensions: 1.3” L x 2.5” W x 0.5” D (3.3 x 6.4 x 1.3 cm) TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The E3 Series Control Panel is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1949 FM: 3023594 MEA FDNY: 227-03-E VOL. IV CSFM: 7300-1703:0102 ISO 9001 Certification AOM-2RF Velociti® Series AOM-2RF Addressable Output Relay Control Module Addressable Devices General The Gamewell-FCI Velociti® Series, addressable output relay control module (AOM- 2RF) allows a Gamewell-FCI analog addressable fire alarm control panel to switch discrete relay contacts by code command. The relay provides two isolated sets of Form-C contacts which transfer simultaneously. Circuit connections to the relay contacts are not supervised by the module. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the SLC devices and certain Gamewell-FCI analog addressable fire alarm control panels. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net result produces a superior response speed up to five times greater than earlier designs. The AOM-2RF Module is designed for installation in the signaling line circuit of any Gamewell-FCI analog addressable fire alarm control panel. The module contains a panel controlled LED. The AOM-2RF is designed to mount in a 4” (10.16 cm) square junction box 2 1/8” (5.53 cm) deep. Ordering Information AOM-2RF: Addressable output relay control module Table 1 lists the relay contact ratings. FEATURES & BENEFITS • Listed under UL ® Standard 864 • Offers two sets of Form “C” contacts • Provides visual rotary, decimal switch addressing (01-159) •Includes a bi-color LED that flashes green whenever the module is addressed, and lights steady red upon activation* • Designed as a compact size to allow easy installation Note: Only the red LED is operative in panels that do not operate in Velociti® mode CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION 3A 30 VDC Resistive Non-Coded 2A 30 VDC Resistive Coded 0.9A 110 VDC Resistive Non-Coded 0.5A 125 VAC Resistive Non-Coded 0.5A 30 VDC Inductive (L/R=5ms) Coded 1A 30 VDC Inductive (L/R=2ms) Coded 0.5A 125 VAC Inductive (PF=.35) Non-Coded 0.7A 75 VAC Inductive Non-Coded Table 1: Relay Contact Ratings Velociti® Series AOM-2RF Technical Specifications 9020-0625 | G | 11/17 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Velociti® Series and Gamewell- FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series AOM-2RF and other products available by visiting www.Gamewell-FCI.com SYSTEMS Supervisory Current: .000375 amps. Alarm Current: .0065 amps. Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 10 to 93% relative humidity (non- condensing) Dimensions: 4 1/2” H x 4” W x 1 1/4” (11.4 x 10.2 x 3.2 cm) TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The Velociti Series® AOM-2RF is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1913 FM: 3023594 MEA FDNY: 219-02-E Vol. VI CSFM: 7300-1703:0102 ISO 9001 Certification GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.©2016 by Honeywell International Inc. All rights reserved www.gamewell-fci.com CS-2481 Rev. B page 1 of 2 MR and PAM Series Multi-Voltage Control RelaysDescription The Gamewell-FCI, MR and PAM Series both offer multi-voltage control relays with SPDT or DPDT 10.0 amp (7.0amp with PAM-2) contacts which may be operated by oneof four input control voltages. A single relay may be ener-gized from any of the following voltage sources when you wire to the appropriate input terminals. • 24 VDC • 115 VAC • 24 VAC • 230 VAC Each relay position contains a red LED which indicatesthat the relay coil is energized. The relays are available ina four-module assembly and the relays may be snappedapart and used independently. The PAM relays are encapsulated multi-voltage devices, providing 10.0 amp Form-C contacts (7.0 amp with PAM-2). The relay may be energized by any one of the following three voltages. • 24 VDC • 115 VAC •24 VAC The relay is supplied with a red LED which indicates thatthe coil is energized. Standard Application The MR and PAM Series are ideal when remote relays arerequired for control, general purpose switching, or statusfeedback. They are suitable for use in the following appli-cations. • fire alarm • HVAC • security • energy management • lighting control Installation The MR Series relays may be mounted in a control panelor supplied with either a four-position or single-positionmetal enclosure. To mount the PAM relays, you can use any of the following: • Double-sided adhesive tape • Self-drilling screw • Loosely installed in a backbox Features MR and PAM Series • Complies with the UL-Listed Standard for a Control Unit Accessory. • Available in dust-proof metal enclosure with an LED viewing port. • Includes the track-mounting hardware to facilitate ease of installation. • Suitable for use with fire alarm, HVAC, energy manage- ment and lighting control systems. • Contains a red LED annunciation when the relay coil is energized. SIGNALING S281 GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118CS-2481 Rev. B page 2 of 2 www.gamewell-fci.com Specifications Input Power MR-101 MR-210 PAM-1 24 VDC 24 VDC 24 VDC 24 VAC 24 VAC 24 VAC 115 VAC 115 VAC 115 VAC 230 VAC 230 VAC Contact Rating MR Series PAM-1 PAM-2 10.0 A @ 115 VAC 10.0 A @ 115 VAC 7.0 A @ 115 VAC 7.0 A @ 28 VDC 7.0 A @ 28 VDC 250 NA @ 5 VDC 250 NA @ 5 VDC Temperature Rating:-50°C to 85°C (-58°F to 185°F) Dimensions: MR-101/T, MR201/T 2.125" W x 3.0 H x 1.5" D (cm: 7.62 H x 5.398 W x 3.81 D) MR-104/T, MR-204/T:3.0" H x 8.5" W x1.5" D (cm: 7.62 H x 21.59 W x 3.81 D) MR-101/CR, MR-210/CR:6.125" H x 3.25" W X 2.5" D (cm: 15.556 H x 16.51 W x 6.35 D) MR-104/CR, MR-204/CR:6.125" H x 6.5" W x 2.5" D (cm: 15.556 H x 16.51 W x 6.35 D) PAM-1:1.15" H x 1.0" W x 5.75" D (cm:3.0 H x 2.54 W x 14.605 D). Ordering Information Part Number MR-101/T Single SPDT relay with LED and track- mounting hardware. MR-101/CR Single SPDT relay with LED mounted in metal enclosure. MR-104/T Four-position SPDT relay with LEDs and track-mounting hardware. MR104/CR Four-position SPDT relay with LEDs mounted in metal enclosure. MR-201/T Single DPDT relay with LED and track- mounting hardware. MR-201/CR Single DPDT relay with LED mounted in metal enclosure. MR-204/T Four-position DPDT relay with LEDs mounted in track-mounting hardware. MR-204/CR Four-position DPDT relay with LEDs mounted in metal enclosure. PAM-1 Single SPDT relay with LED, double-sided adhesive, mounting screw, 12" (30.48 cm) leads and 6 wire nuts. PAM-2 Single SPDT relay with LED, double-sided adhesive, mounting screws, 12" (30.48 cm) leads and six wire nuts. Wall Horn, Horn Strobe L-Series, Indoor Strobes and Horn Strobes Indoor Selectable-Output Horns, Strobes and Horn Strobes for Wall Applications Notification Appliances General The L-Series audible visible notification products offer the most versatile and easy-to- use line of horns, strobes, and horn strobes in the industry. In addition, this product includes lower current draws and a modern aesthetic design which reduce installation times and maximize profits. The following devices offer a variety of design options, so that the L-Series can be used for any application requirement. • White and red plastic housings • Standard and small footprint devices • Plain, FIRE, and FUEGO-printed devices Similar to the entire L-Series product line, the wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying the installation. All devices offer a plug-in design so that there is minimal intrusion into the backbox. These features make installations fast and foolproof while eliminating costly and time-consuming ground faults. To further simplify the installation and protect devices from construction damage, the L-Series uses a mounting plate for all standard and compact models that include an onboard shorting spring. This feature allows Installers to test wiring continuity before the device is installed. Installers can also easily adapt devices to suit a wide range of application requirements using the following features: • Field-selectable candela settings • Automatic selection of 12- or 24-volt operation • Rotary switch for horn tones with two volume selections FEATURES & BENEFITS • Listed for wall mounting only • Offers small profile devices for horns and horn strobes • Provides an automatic selection of 12- or 24- volt operation at 15 and 30 candela • Produces horn rated at 88+ dBA at 16 volts • Uses field-selectable candela settings on wall units: - 15 - 30 - 75 - 95 - 110 - 135 - 185 • Includes a mounting plate for all standard and all compact wall units • Contains a mounting plate with a shorting spring that checks the wiring continuity before device installation • Features a plug-in design with minimal intrusion into the backbox •Designed with a tamper-resistant construction • Supports a rotary switch for horn tone and two volume selections 2 Architect/Engineer Specifications General When it is used with the Sync•Circuit Module, the following occur: • 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts • 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts The Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have the following field-selectable candela settings: Strobe The strobe shall be an L-Series Model _______ listed to UL Standard 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/ reflector system. Horn Strobe Combination The horn strobe shall be an L-Series Model _______ listed to UL Standard 1971 and UL Standard 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audible options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch backbox. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy-chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply UL Current Draw Table 1 lists the UL maximum strobe current draw. 7DEOHOLVWVWKH8/PD[LPXP+RUQFXUUHQWGUDZ•15 •30 •75 •95 • 115 • 150 • 177 &DQGHOD 9ROWV 9ROWV ):5'& '& &DQGHOD 5DQJH 1$ 1$ 1$ 1$ 1$ Table 1: UL Maximum Strobe Current Draw (mA RMS) 6RXQG3DWWHUQ G% 9ROWV 9ROWV '& '& ):5 7HPSRUDO +LJK 7HPSRUDO /RZ 1RQ7HPSRUDO +LJK 1RQ7HPSRUDO /RZ .+]7HPSRUDO +LJK .+]7HPSRUDO /RZ .+]1RQ7HPSRUDO +LJK .+]1RQ7HPSRUDO /RZ &RGHG +LJK .+]&RGHG +LJK Table 2: UL Max. Horn Current Draw (mA RMS) 3 UL Current Draw Data Table 3 lists the maximum UL Current Draw (mA RMS) allowed for Wall Horn Strobes. Horn Strobe Tones and Sound Output Data Table 4 lists the horn strobe tones and sound output date. DC 8-17.5 Volts 16-33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd EM Temp Hi 98 158 54 74 121 142 162 196 245 EM Temp Low 93 154 44 65 111 133 157 164 235 EM Cont Hi 106 166 73 94 139 160 182 21 262 EM Cont Low 93 156 51 71 119 139 162 190 239 3.1K Temp Hi 93 156 53 73 119 140 164 190 242 3.1K Temp Low 91 154 45 66 112 133 160 185 235 3.1K Cont Hi 99 162 69 90 135 157 175 208 261 3.1K Cont Low 93 156 52 72 119 138 162 192 242 16V FWR FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd EM Temp Hi 83 107 156 177 198 234 287 EM Temp Low 68 91 145 165 185 223 271 EM Cont Hi 111 135 185 207 230 264 316 EM Cont Low 79 104 157 175 197 235 283 3.1K Temp Hi 81 105 155 177 196 234 284 3.1K Temp Low 68 90 145 166 186 222 276 3.1K Cont Hi 104 131 177 204 230 264 326 3.1K Cont Low 77 102 156 177 199 234 291 Table 3 UL Max. Current Draw (mA RMS), Wall Horn Strobe, Horn Strobe, Candela Range (15-115 cd) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts FWR DC DC 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9* (See Note)Coded High 85 90 90 10* (See Note)3.1 KHz Coded High 84 89 89 Note: Settings 9 and 10 are not available on 2-Wire horns and strobes. Temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output remains constantly on. Table 4: Horn Strobe Tones and Sound Output Data 4 L-Series Ordering Information Wall Strobes: SRL: Strobe, Red SWL: Strobe, White SGRL: Compact Strobe, Red SGWL: Compact Strobe, White SRL-P: Strobe, Red, Plain SWL-P: Strobe, White, Plain SWL-CLR-ALERT: Strobe, White, ALERT Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -SP models have “FUEGO” marking on cover. All -ALERT models have “ALERT” marking on cover. L-Series Ordering Information HRL*: Horn, Red HWL*: Horn, White HGRL*: Compact Horn, Red HGWL*: Compact Horn, White Note: Horn-only models are listed for wall or ceiling use. Accessories: TR-2: Universal Wall Trim Ring Red TR-2W: Universal Wall Trim Ring White SBBRL: Wall Surface Mount Back Box, Red SBBWL: Wall Surface Mount Back Box, White SBBGRL: Compact Wall Surface Mount Backbox, Red SBBGWL: Compact Wall Surface Mount Backbox, White L-Series Dimensions Figure 1 Compact Strobe, Horn Strobe Figure 2 Compact Horn Figure 3 Compact Wall Surface Mount Backbox (SBBGRL, SBBGWL) Figure 4 Strobe, Horn Strobe Figure 5 Horn Figure 6 Wall Surface Mount Backbox (SBBRL/SBBWL) PP PP PP PP PP PP PP FP FP FP FP FP PP FP PP PP PP FP FP FP L-Series, Indoor Strobes and Horn Strobes Technical Specifications 9021-60929 | D | 02/19 ©2019 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s L-Series, Indoor Strobes and Horn Strobes and other products available by visiting www.Gamewell-FCI.com SYSTEMS Temperature Ranges: Standard Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity Range: 10 to 93% non-condensing Voltages: Strobe Flash Rate: 1 flash per second Nominal Voltage: Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2: 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3): 8.5 to 17.5V(12 V nominal) or 16.5 to 33 V(24V nominal) Wire Gage: Input Terminal Wire Gauge: 12 to 18 AWG Dimensions: Wall-Mount Dimensions (including lens): 5.6”L x 4.7”W x 1.91”D (143 mm L x 119 mm W x 49 mm D) Compact Wall-Mount Dimensions (including lens): 5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions: 5.6” L x 4.7” W x 1.25” D (143 mm L x 119 mm W x 32 mm D) Compact Horn Dimensions: 5.25” L x 3.45” W x 1.25” D (133 mm L x 88 mm W x 32 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non- regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The L-Series, Ceiling Strobes and Horn Strobes are designed to comply with the following standard: UL Standard: UL 1971 and UL 464 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S5512, S4011 CSFM: 7135-1653:0503 7125-1653:0504 ISO 9001 Certification AVDS910-01 • 10/1/2019 • Page 1 Horns only: 7135-1653:0516 Horn/Strobes: 7125-1653:0517 PR452768 S4011 Features • 520 Hz ± 10% square wave tone, NFPA compliance • Full candela range plus High/Low tone options to optimize current draw for a wide variety of applications • Compact, standard, and round ceiling options • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Rotary switch for High and Low, Temp3 and Temp4 settings • Plug-in design with minimal intrusion into the back box • Mounting plate shorting spring checks wiring continuity before device installation • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices (Direct replacement for HW/R-LF and P2R/WH-LF) • Compatible with MDL3 sync module • Sounders listed for ceiling and wall mounting • Sounder Strobe listed for wall mounting • Updated modern aesthetics The L-Series offers the most versatile and easy-to-use line of low frequency sounder and low frequency sounder strobes in the industry. With white and red plastic housings, listed for wall and ceiling mounting, L-Series Low Frequency can meet virtually any application requirement. The low frequency sounder and low frequency sounder strobes were designed to address the NFPA 72 sleeping space requirements that require a low frequency notification appliance that operates within frequency range of 520 Hz ± 10% and is of a square wave tone. Like the entire L-Series product line they include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, L-Series uses a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, 24- volt operation, and a rotary switch for 520 Hz low frequency sounder tones. Indoor Selectable- Output Low Frequency Sounders and Low Frequency Sounder Strobes System Sensor L-Series audible visible notification products are rich with features guaranteed to maximize profits with lower current draw and modern aesthetics. Agency Listings AVDS910-01 • 10/1/2019 • Page 2 L-Series Specifications Architect/Engineer Specifications General L-Series low frequency sounder and low frequency sounder strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit (0°C to 49°C) from a regulated DC or full-wave rectified unfiltered power supply. Low Frequency Sounder strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, 185. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone and have a permanent marking on the housing that reads “low frequency sounder”. Low Frequency Sounder The low frequency sounder shall be a System Sensor L-Series Model _______ listed to UL 464 and shall be approved for fire protective service. The low frequency sounder and the Sync•Circuit™ MDL3 Module accessory, if used, shall be powered from a notification appliance circuit output and shall operate on a nominal 24 volts (includes fire alarm panels with built-in sync). When used with the Sync•Circuit Module MDL3, 24-volt rated notification appliance circuit outputs shall operate between 16.5 to 33 volts. If the notification appliances are not UL 9th edition listed with the corresponding panel or power supply being used, then refer to the compatibility listing of the panel to determine maximum devices on a circuit. The low frequency sounder has an option to switch between temporal three or temporal four pattern, non- temporal (continuous) pattern and coded supply within the frequency range of 520Hz ± 10% square wave tone. The low frequency sounder shall operate on a coded or non-coded power supply with high and low volume settings. Low Frequency Sounder Strobe Combination The low frequency sounder strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The low frequency sounder strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The sounder shall have an option to switch between a temporal three or temporal four pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The low frequency sounder on low frequency sounder strobe models shall operate on a non-coded power supply with high and low volume settings. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the strobes, the module shall silence the low frequency sounder on low frequency sounder strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Class B circuits or one Class A circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Frequency Range 520 Hz ± 10% Strobe Flash Rate 1 flash per second Nominal Voltage Low Frequency Sounder Regulated 24 DC/FWR1 Nominal Voltage Range Low Frequency Sounder Strobe Regulated 24 VDC/FWR1 Operating Voltage Range 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Dimensions Wall Sounder Strobe (including lens)5.6" L x 4.7" W x 1.9" D (142 mm L x 119 mm W x 49 mm D) Standard Wall Sounder 5.6" L × 4.7" W × 1.5" D (142 mm L × 119 mm W × 38 mm D) Compact Wall Sounder 5.25" L x 3.46" W x 1.5" D (133mm L x 88mm W x 38mm D) Ceiling Sounder 6.8" diameter x 1.4" high (173mm diameter x 36mm high) Standard Wall Sounder with SBBRL/SBBWL Surface Mount Back Box 5.7” L x 4.8” W x 3.3” D (145 mm L x 120 mm W x 87 mm D) Compact Wall Sounder with SBBGRL/SBBGWL Surface Mount Back Box 5.4” L x 3.6” W x 3.0” D (137 mmL x 91mm W x 76 mm D) Low Frequency Ceiling Sounder with SBBCRL/SBBCWL Surface Mount Back Box 6.9" diameter x 3.9" high (175mm diameter x 99mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. AVDS910-01 • 10/1/2019 • Page 3 UL Current Draw and Sound Output Data Low Frequency Wall Sounder Strobe Current Draw (mA) and Sound Output (dBA) Current Draw (mA) Sound Output (dBA) Pos Tone Volume Setting 16-33 VDC 16-33 FWR 16-33 V 15cd 30cd 75cd 95cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd DC FWR 1 Temporal 3 High 98 115 158 173 182 212 266 136 153 188 206 228 258 304 80 80 2 Temporal 3 Low 98 102 141 162 173 202 255 150 150 176 194 216 242 280 76 76 3 Temporal 4 High 98 108 137 151 178 202 252 200 198 169 188 212 242 290 80 80 4 Temporal 4 Low 102 104 122 136 163 187 237 176 174 154 173 197 227 275 76 76 5 Continuous High 141 158 198 216 234 264 305 190 207 249 268 289 321 368 80 80 6 Continuous Low 120 128 179 196 215 244 285 165 182 226 244 266 297 342 76 76 UL Max. Low Frequency Sounder Current Draw (mA RMS) Volume Setting Current Draw (mA) Sound Output (dBA) Reverberant 16–33 Volts 16–33 Volts Pos Tone DC FWR DC FWR 1 Temporal 3 High 108 150 80 80 2 Temporal 3 Low 78 76 76 76 3 Temporal 4 High 111 151 80 80 4 Temporal 4 Low 80 76 76 76 5 Continuous High 111 151 80 80 6 Continuous Low 80 76 76 76 7 Coded High 111 151 80 80 8 Coded Low 80 76 76 76 *NOTE: For coded tones, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the sounder output will remain constantly on. Coded ratings provided are for continuous voltage. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2019 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS910-01 • 10/1/2019 Part No. Description Red White Low Frequency Sounder Strobes P2RL-LF P2WL-LF LF Sounder Strobe, Wall Low Frequency Sounders HRL-LF HWL-LF LF Sounder, Wall HGRL-LF HGWL-LF Compact LF Sounder, Wall HCRL-LF HCWL-LF LF Sounder, Ceiling Accessories MDL3R MDL3W Sync•Circuit™ Module, UL-listed SBBRL SBBWL Surface Mount Back Box, Wall SBBCRL SBBCWL Surface Mount Back Box, Ceiling SBBGRL SBBGWL Surface Mount Back Box, Wall, Compact L-Series Dimensions Wall LF Sounder Strobe Wall LF Sounder Compact Wall LF Sounder 3.455 1.453 5.265 Ceiling LF Sounder 6.830 1.438 System Sensor® is a registered trademark and Sync•Circuit™ is a trademark of Honeywell International, Inc. 4.700 1.453 5.670 GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2008 by Honeywell International Inc. All rights reserved.www.gamewell-fci.com 9021-60345 Rev. A page 1 of 3 SpectrAlert® Advance Outdoor Notification Appliances Outdoor Selectable Output Speaker Strobes and Dual Voltage Evacuation Speakers An ISO 9000-2000 Company SIGNALING S4048Vol. 1, Sec. 2 MEA Approved 10-08-E 7300-1653:201 Description SpectrAlert® is a registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. The SpectrAlert® Advance series offers the broadest line of outdoor speakers and speaker strobes in the industry. From metal and plastic outdoor back boxes, to white and red plastic housings, to wall and ceiling mounting options, virtually every application is covered. SpectrAlert Advance outdoor speakers and speaker strobes offer reliable opera- tion over the entire temperature range of -40°F to 151°F. They may be used indoors or outdoors in wet or dry appli- cations. In addition, these speakers provide a broad fre- quency response range and low harmonic distortion to provide an accurate and intelligible broadcast of evacua- tion messages. High sound pressure level at all tap set- tings ensures that messages are clearly heard. The plug-in design allows the installer to pre-wire mounting plates and dress the wires before plugging in the speakers to help reduce ground faults. This design also allows faster installations with instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and field selectable candela settings for wall and ceiling speaker strobes. The weatherproof back boxes have plastic and metal ver- sions. They are designed to accommodate in-and-out wir- ing for daisy chaining outdoor devices. The plastic weatherproof back boxes are shipped with the product fea- ture removable side flanges and have improved resistance to salt water corrosion. The screw hole knockouts, located on the back of the weatherproof back box, eliminate the need to drill holes for screw-in mounting. Both weather- proof back boxes are available with 3/4 inch top and bot- tom conduit entries and 3/4 inch knock-outs at the back. Included with each back box is a screw-in NPT plug with an O-ring gasket for a watertight seal. Metal back boxes are available separately. Features • Plug-in design • Electrical compatibility with existing SpectrAlert products • Shorting spring on mounting plate tests continuity before installation • Rotary switch simplifies field selection of speaker voltage and power settings • Universal mounting plate for wall- and ceiling-mount units • Weatherproof per NEMA 4x, IP56 • Compatible with System Sensor synchronization protocol • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Field selectable candela settings on wall and ceiling units • Ceiling and wall mount application SpectrAlert Advance GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189021-60345 Rev. A page 2 of 3 www.gamewell-fci.com Architectural/Engineering Specifications General SpectrAlert Advance outdoor speaker and speaker strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Out- door SpectrAlert Advance products shall operate between –40°F and 151°F from a regulated DC, or full-wave recti- fied, unfiltered power supply. Speaker The Speaker shall be a System Sensor SpectrAlert Advance Model ______ dual voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. Speaker shall be Listed to UL® Standard S4048 for out- door fire protective signaling systems. Speaker shall have a frequency range of 400 to 4000 Hz and shall have an operating temperature from –40°F to 150.8°F. Speaker shall have power taps and wattage settings which are selected by rotary switches. The speaker must be installed with its weatherproof backbox in order to remain outdoor approved per UL listing S4048. The speaker shall be suit- able for use in air handling spaces, as well as wet environ- ments. Speaker Strobe Combination The Speaker Strobe shall be a System Sensor Model _____listed to UL 1638 and UL 1480 and be approved for fire protective signaling systems. Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms, and shall have a frequency range of 400 to 4000 Hz. Speaker shall have power taps that are selected by rotary switch. The strobe shall consist of a xenon flash tube with associated lens/ reflector system and operate on either 12V or 24V. The strobe shall also feature selectable candela output, provid- ing options for 15 or 15/75 candela when operating on 12V and 15, 15/75, 30, 75, 110, 115, 135, 150, 177 or 185 when operating on 24V. The strobe shall comply with the Americans with Disabilities Act requirement for visible sig- naling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The speaker strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The speaker strobe shall be suitable for use in wet environments. Sound Output UL Reverberant (dBA@10 ft) 2 W 1 W 1/2 W 1/4 W Outdoor Speaker 90 87 84 81 Outdoor Speaker/Speaker Strobe 89 86 83 80 UL Maximum Strobe Current Draw (mA RMS) Candela 8 to 17.5 Volts 16 to 33 Volts DC FWR DC FWR StandardCandelaRange 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 vmvm95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 HighCandelaRange 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 Candela Derating NOTE: For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela Rating at -40 F 15 Do not use below 32 F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118www.gamewell-fci.com 9021-60345 Rev. A page 3 of 3 Specifications Physical Specifications Operting Temperature:-40°F to 151°F (-40°C to 66°C) Wall-Mount Dimensions: SPS Speaker Strobe:6.0”L x 5.0”W x 4.9”D(including lens and speaker) SP Speaker:6.0”L x 5.0”W x 2.9”D Ceiling Mount Dimensions: SPS Speaker Strobe:6.8”Dia x 4.8”D(including lens and speaker) SP Speaker:6.8”L x 2.9”D Wall-Mount Weatherproof Backbox: Dimensions:6.5”L x 5.5”H x 2.9”D Ceiling-Mount Weatherproof Backbox: Dimensions:7.2”Dia x 2.9”D Electrical/Operating Specifications: Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage (speakers):50VDC Strobe Flash Rate:1 flash per second Nominal Voltage (Strobes):Regulated 12VDC/FWR or 24VDC/FWR Operating Voltage Range (includes fire panels with built-in sync):8 to 17.5V (12V nominal) or 16 to 33V (24 nominal) Operating Voltage with MDL Sync Module: 9 to 17.5V (12V nominal) or 17 to 33V (24V nominal) Frequency Range:400 to 4000Hz Power:¼, ½, 1, 2 watts Ordering Information Part Number Description SPWK:Wall mount outdoor speaker; white SPRK:Wall mount outdoor speaker; red SPSWK:Wall mount outdoor speaker strobe, selectable candela(15, 15/75, 30, 75, 95, 100, 115); white SPSRK:Wall mount outdoor speaker strobe, selectable candela (15, 15/75, 30, 75, 95, 100, 115); red SPCWK:Ceiling mount outdoor speaker; white. SPSCWK:Ceiling mount outdoor speaker strobe, selectable candela (15, 15/75, 30, 50, 75, 95, 110, 115); white SPSCWHK:Ceiling mount outdoor speaker strobe, selectable candela, high cd(135, 150, 177, 185); white Accessories MWBB:Wall, metal weatherproof backbox; red MWBBW:Wall, metal weatherproof backbox; white MWBBCW:Ceiling, metal weatherproof backbox; white PWBB:Wall, plastic weatherproof backbox; red PWBBW:Wall, plastic weatherproof backbox; white PWBBCW:Ceiling, plastic weatherproof backbox; white Worry-Free 120V AC Wire-in Smoke Alarm Sealed Lithium Battery Backup Model i12010S Description The Kidde i12010S is an AC/DC powered, ionization smoke alarm that operates on a 120V power source with sealed-in lithium battery backup. This alarm uses ionization sensing technology. Ionization sensing alarms may detect invisible fire particles (associated with flaming fires) sooner than photoelectric alarms. Photoelectric sensing alarms may detect visible particles (associated with smoldering fires) sooner than ionization alarms. Leading authorities recommend that both ionization and photoelectric smoke alarms be installed to help insure maximum detection of the various types of fires that can occur within the home. The i12010S contains a 10-year tamper proof battery that eliminates the need for battery replacement, and ends worry over unauthorized battery removal. The alarm provides continuous protection from smoke and fire, even during power outages. At the end of alarm life, the unit will chirp, indicating the alarm is in need of replacement. The customer can use a simple tool such as a screwdriver to deactivate the unit, stopping the chirp and making it safe for disposal. The end of life signal can be temporarily silenced to allow for replacement at a more convenient time. Install Confidence: Easy Installation • Battery backup automatically activates when the alarm is attached to mounting bracket • Large mounting base makes mounting easier, protects surface paint from dirt and covers imperfections. • Pre-stripped wiring harness with easy off cap does not require stripper tool. Tinned strands increase conductivity and wire nut grip. Fewer Callbacks • 10-year sealed battery substitutes need for routine 9V replacement • Large centrally located Test/Hush® alarm control button silences nuisance alarms for approximately 9 minutes. • Dust cover protects sensor from contaminates during construction, reducing nuisance alarms. User-Friendly Features • Red LED indicates alarm mode, Green LED indicates AC power is present. • Interconnectable with up to 24 devices (of which 18 can be initiating) including smoke, CO and heat alarms. See user guide for complete instructions. • End of Life Hush feature allows user to temporarily silence end of life chirp 3 days at a time for a maximum of 30 day life extension. — Ionization Sensing Technology — Sealed-In 10-Year* Lithium Battery Backup — Hush® Button — Alarm Memory Indicator — 360° Mounting Plate with Tamper Resistance — 2 LED Indicators Backup Install Confidence: Easy Installation B ttery backup automatically activates when the alarm k t p ance Install Confidence: 10 * Architectural and Engineering Specifications The smoke alarm shall be Kidde Model i12010S or approved equal. It shall be powered by a 120VAC, 60Hz source along with a 3V sealed lithium battery backup. The unit shall incorporate an ionization sensor with nominal sensitivity of 0.50 to 1.04%/ ft. The temperature operating range shall be between 40°and 100°F (4°C and 38°C) and the humidity operating range shall be up 95% relative humidity, non-condensing. The smoke alarm can be installed on any standard single gang electrical box, up to a 4” octagon junction box. The electrical connection (to the alarm) shall be made with a plug-in connec- tor. A maximum of 24 Kidde devices can be interconnected in a multiple station arrangement. The interconnect system must not exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices, of which 12 can be smoke alarms. With 18 initiating devices (Smoke, heat, CO, etc), interconnected, it is still possible to interconnect 6 strobe lights and/or relay modules. The alarm shall provide optional tamper resistance that deters removal of the unit from the wall or ceiling. No additional pieces shall be required to activate this feature. The alarm shall include a test button that will electronically simu- late the presence of smoke and cause the unit to go into alarm. This sequence tests the unit’s electronics, battery and horn to ensure proper operation. The unit shall include a piezoelectric horn that is rated at 85 decibels at 10 feet. The unit shall include the Smart Hush™ feature that silences the unit for approximately 9 minutes if a nuisance condition occurs. The unit shall indicate a low battery condition with a brief alarm chirp and red LED flash once every 60 seconds. In standby con- dition, the green LED will be constantly on when powered by AC, and flash every 60 seconds when powered by only battery backup. The green LED will also flash every 2 seconds when in Hush mode, and every 16 seconds in Memory Condition. The smoke alarm shall include an End of Life Alert, where ten years after initial power-up the unit shall chirp two times every 30 seconds to indicate the alarm needs to be replaced. The End of Life signal can be silenced three days at a time for a maxi- mum of 30 days. The unit shall have a deactivation switch to disable it and make it safe for disposal. The unit shall at a minimum meet the requirements of UL217, NFPA72, and (chapter 11), The State of California Fire Marshall, NFPA101 (0ne and two family dwellings), Federal Housing Authority (FHA), Housing and Urban Development (HUD). It shall also include a 10-year manufacturer’s limited warranty. FUSE OR CIRCUIT BREAKER BLACK WHITE RED L N First Alarm Additional Alarms Worry-Free 120V AC Wire-In Smoke Alarm Sealed Lithium Battery Backup Model i12010S Technical Specifications Model: i12010S Power Source: 120VAC (60 Hz, 45mA Max) Sensor: Ionization Audio Alarm: 85dB at 10ft Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C) Humidity Range: Up to 95% relative humidity (RH), non-condensing Size: 5.5” in diameter x 1.75” depth Weight: .45lbs Interconnects: Up to 24 Kidde devices Warranty: 10 year limited Installation of Smoke Alarm The smoke alarm should be installed to comply with all local codes having jurisdic- tion in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in the interconnect system. Use standard UL listed household wire as required by code. 1016 Corporate Park Drive Mebane NC 27302 1-800-880-6788 www.Kidde.com Distributed by: P/N: KL-i12010S-sheet rev. 08-2014 Ordering Information Ordering Pack Pack Dimensions Cartons/Number UPC I2F5 Config. Quantity (w x d x h inches) Weight Pallet 21010407-A 0-47871-11407-8 100-47871-11407-5 BOX Master Pack (6 Units) 6.0 x 13.0 x 6.0 2.7 126 Not for sale by individual unit 5.5”1.75” Units needs to be provided with both smoke and CO detection, per planset. BOD device is combination CO/smoke detector (BRK SC9120LBL). 120VAC Dual Mode Strobe Light for the Hearing Impaired Model SL177i Bright Strobe Light Flashes to warn of a smoke, heat or carbon monoxide hazard. Green LED Indicates AC power is being delivered to unit. Description The Kidde SL177i is a 120VAC wire in unit that provides a visual warning when part of an interconnected system. This unit can be directly interconnected with Kidde smoke alarms, heat alarms and carbon monoxide alarms (a maximum of 24 devices of which 18 can by initiating). When triggered by a smoke alarm or heat alarm, it will produce a steady flash warning. When triggered by a carbon monoxide alarm it will produce an intermittent flash warning. The SL177i has a 5 year limited warranty and is UL Listed. ATTENTION! The model SL177 and SL177I strobe lights are designed to notify hearing impaired individuals of impending danger, they have no detection means and MUST be used in conjunction with operating Smoke, Heat, or Carbon Monoxide Alarms. Consumer Benefits The Kidde SL177i, used in conjunction with a smoke, heat or carbon monoxide alarm, provides a bright visual signal to warn of a smoke, heat or CO hazard. The Kidde Strobe light benefits the hearing impaired, allowing a visual alert of a danger. This unit also includes a tamper resist pin that helps to deter thief and tampering. Architectural and Engineering Specifications The strobe light shall be Kidde Unit SL177i or approved equal. It shall be powered by a 120VAC, 60Hz source. The temperature operation range shall be between 40°F and 100°F (4°C and 38°C). The strobe light can be installed on any standard single gang electrical box, up to a 4” octagon junction box. The electrical connection (to the device) shall be made with a plug-in connector. A maximum of 24 Kidde devices can be interconnected in a multiple station arrange- ment. The interconnect system must not exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices (Smoke, heat, CO, etc) interconnected, it is still possible to interconnect 6 strobe lights and or relay modules. The device shall provide optional tamper resistance that deters removal of the unit from the wall or ceiling. This unit shall include a bright candela strobe light with a flash rate of one (1) flash per second. This unit shall be interconnected with Kidde smoke alarms, heat detectors and/or carbon monoxide alarms. The unit shall at a minimum meet the requirements of UL217, NFPA72, (chapter 10 & 11 2002 edition) The State of California Fire Marshall, NFPA101 (One and two family dwellings, Federal Housing Authority (FHA), Housing and Urban Development (HUD), Americans with Disabilities Act (ADA). Installation of Strobe Light The strobe light should be installed to comply with all local codes having jurisdiction in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all devices are wired to a single, continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in the interconnect system. Light output gradually decreases as viewing angle is increased. Consult chart in users guide to determine the best location for the strobe light installation. 120VAC Dual Mode Strobe Light for the Hearing Impaired Model Number SL177i Technical Specifications Model: SL177i UPC: 0-25417-19129-5 Power Source: 120VAC, 60HZ Electrical Rating: 100 - 130 VAC, 60HZ, 80 mA standby, 44 mA inrush, 1.5 A peak, 390 mA when operating. Temperature Range: 40˚F to 100˚F (4˚C to 38˚C) Flash Rate: 1 flash per second Light Output 177 Candela Size: 5.6” in diameter x 3” depth Weight: 1lb Interconnects: Up to 24 Kidde devices of which 18 can be initiating devices. Warranty: 5 year limited warranty Ordering Information Gift Box UPC: 0-25417-19129-5 Part Dimensions Case/ Layers/ Skid Number I 2 of 5 Pack Quantity (w x d x h inches) Weight Skid Skid Weight SL177i* N/A Individual 5.75 x 3.25 x 6.75 1lb N/A N/A N/A SL177i 200 25417 19129 9 3 units 6.5 x 10.5 x 6.5 3lbs 120 5 360lbs * Not for sale by individual unit 1016 Corporate Park Drive Mebane NC 27302 1-800-880-6788 www.Kidde.com Distributed by: P/N: KL-SL177i sheet rev. 01-2009