HomeMy WebLinkAbout!Binder1_StructuralSTRUCTURAL LOADS AND CRITERIA 1. DESIGN AND CONSTRUCTION: THE 2020 BUILDING CODE OF NEW YORK STATE A.RISK CATEGORY II 2. LIVE LOADS: GROUND FLOOR = 100 PSF ELEVATED FLOORS =80 PSF (50 PSF + 30 PSF PARTITION) ROOF =20 PSF (MINIMUM ROOF LIVE LOAD) 3. DEAD LOADS: WEIGHT OF CONSTRUCTION MATERIALS PLUS ROOF = 8 PSF COLLATERAL (MEP, TYP.), 33 PSF COLLATERAL (MEP) WHERE NOTED FLOOR (TYPICAL) = 12 PSF COLLATERAL (MEP, TYP.), 27 PSF COLLATERAL (MEP) AT 4TH FLOOR 4. SNOW LOADS:Is = 1.0 SEE SNOW DRIFT MAP ON S002. Pg = 40 PSF Pf = 31 PSF Ce = 1.0, Ct = 1.1 5. WINDS LOADS:Iw = 1.0 (SEE COMPONENT AND CLADDING WIND LOADS,SHEET S003) V_ult = 115 MPH (V_asd = 90 MPH) EXPOSURE = D GCpi = (+/-)0.18 6. RAIN LOADS: d_s = 5" d_h = 3" R = 20 PSF 7. FLOOD LOADS:THE STRUCTURE IS LOCATED OUTSIDE THE 100-YEAR FLOOD HAZARD AREA BUT INSIDE THE 500-YEAR FLOOD HAZARD AREA. 8. SEISMIC LOADS:Ie = 1.0 Ss=0.119, S1= 0.045, SDs = 0.190, SD1 = 0.126 SITE CLASS = B, SEISMIC DESIGN CATEGORY = B BASIC SEISMIC-FORCE RESISTING SYSTEM: STEEL SYSTEM NOT SPECIFICALLY DETAILED (ASCE 7-16 T.12.2-1 ITEM H) BASE SHEAR = 267 KIPS, Cs=.063, R= 3, OMEGA = 3, Cd = 3 ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE CONTROLLING LFRS LOAD TYPE: WIND LOAD 9. DESIGN STAIRS, STAIR COMPONENTS, CONNECTIONS, AND RAILINGS AND INCORPORATE INTO STEEL SHOP DRAWINGS AS FOLLOWS: (LIVE LOADS SHOWN ARE IN ADDITION TO DEAD LOAD) A. MAIN STRINGERS AND LANDINGS: 100psf B. TREADS: LOAD PRODUCING GREATEST STRESS OF 100 PSF OR 300 LB ON 4 SQ IN. C. HANDRAIL ASSEMBLIES: LOAD PRODUCING GREATEST STRESS OF 200 LB OR 50 PLF. APPLIED IN ANY DIRECTION AT ANY POINT ON THE ASSEMBLY. D. MEET NYS CODE FOR ALL DETAILS AND DIMENSIONS NOT SPECIFICALLY INDICATED. E. COORDINATE FINAL DESIGN WITH ARCHITECTURAL DRAWINGS AND PROJECT SPECIFICATIONS. F. MEMBER SIZES SHOWN ON THE DRAWINGS ARE MINIMUM. G. FRAMING DETAILS SHOWN ARE SCHEMATIC. CONTRACTOR TO PROVIDE ADEQUATE SUPPLEMENTAL FRAMING AS NEEDED TO SUPPORT STAIR AND RAILING COMPONENTS. FOUNDATION NOTES 1. FOUNDATION DESIGN IS BASED ON A PRESUMPTIVE SOIL BEARING CAPACITY OF 4,000 PSF AFTER COMPLETION OF SOIL IMPROVEMENT. VERIFY SOIL CONDITIONS PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL FOLLOW THE RECOMMENDATIONS AND PROVISIONS OUTLINED IN THE PROJECT GEOTECHNICAL REPORT AND THE SOIL IMPROVEMENT REPORT FOR THE FOUNDATION TYPE EMPLOYED. 2. EXISTING CONDITIONS: VERIFY DIMENSIONS, ELEVATIONS, ETC., FOR EXISTING U/G UTILITIES. PREPARE SITE TO PROPER ELEVATIONS. PROVIDE STRUCTURAL FILL AS REQUIRED OR REUSE EXISTING SITE MATERIAL PER RECOMMENDATIONS IN THE GEOTECHNICAL EVALUATIONREPORT. 3. ENGINEERED FILL: NYSDOT ITEM 304-2 TYPE 2. 2" MAXIMUM SIZE AND NO MORE THAN 10% PARTICLES PASSING THE #200 SIEVE. PLACE IN 6" TO 9" LIFTS. COMPACT EACH LIFT TO AT LEAST 95% MAXIMUM DENSITY AS DETERMINED BY THE MODIFIED PROCTOR METHOD, WITH A MOISTURE CONTENT WITHIN TWO PERCENT OF OPTIMUM. PROVIDE BENEATH FOOTINGS AS REQUIRED, AS BACKFILL AGAINST FOUNDATION WALLS,AND BENEATH FLOOR SLAB AND SUBBASE MATERIAL. 4. GRANULAR FILL: NYSDOT 203.07 -SELECT GRANULAR FILL, MAY BE USED AS BACKFILL FILL AGAINST FOUNDATION WALLS AND BENEATH FLOOR SLAB AND SUBBASE MATERIAL. ENGINEERED FILL COMPACTION REQUIREMENTS SHALL APPLY. 5. SUBBASE MATERIAL: NYSDOT ITEM 304-2 TYPE 2. THE MATERIAL SHALL HAVE A MAXIMUM SIZE OF 2" AND NO MORE THAN 10% PARTICLES PASSING THE #200 SIEVE. PLACE IN 6" TO 9" LIFTS. ENGINEERED FILL COMPACTION REQUIREMENTS SHALL APPLY. 6. COORDINATE PIPE SLEEVES THROUGH FOUNDATION WALLS AND FOOTING STEPS TO ACCOMMODATE PIPING WITH THE MECHANICAL AND PLUMBING CONTRACTOR/DRAWINGS. 7. FOOTING BEARING ELEVATION: 4'-0" MINIMUM BELOW GRADE AT EXTERIOR WALLS. ADJUST FOR FIELD CONDITIONS. 8. PROVIDE TEMPORARY PROTECTION AS REQUIRED FOR FOUNDATIONS EXPOSED TO WATER OR FREEZING. 9. FOUNDATION WALL BACKFILL: ADEQUATELY BRACED WALLS OR BALANCE FILLING EACH SIDE. CONCRETE NOTES 1. CONCRETE DESIGN AND CONSTRUCTION: ACI 318, ACI 301, AND PROJECT SPECIFICATIONS. 2. CONCRETE PROTECTION: ACI 305 HOT WEATHER CONCRETING, ACI 306 COLD WEATHER CONCRETING. CONCRETE SHALL NOT BE PLACED ON FROZEN GROUND. PROTECT AGAINST FROST UNTIL SPECIFIED STRENGTH IS ATTAINED. 3. MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS: FOOTINGS: 4,000 PSI, MAX. W/C RATIO = 0.45 PIERS AND FOUNDATION WALLS: 4,500psi, MAX. W/C RATIO = 0.45 CONCRETE EXPOSED TO WEATHER: 4,500psi, MAX. W/C RATIO = 0.45 INTERIOR SLABS ON GRADE: 3,000 PSI, 1 1/2" MAX COURSE AGGREGATE, MAX. W/C RATIO = 0.54 ELEVATED SLABS: 3,500 PSI, MAX UNIT WEIGHT = 115 PCF; AIR ENTRAINMENT 6% 4. AIR-ENTRAINMENT FOR CONCRETE EXPOSED TO FROST OR WEATHER: (DO NOT ENTRAIN TROWEL FINISHED FLOORS) MAXIMUM AGGREGATE SIZE AIR CONTENT 2 in 4% TO 6.5% 1.5 in 4% TO 7% 1 in 4.5% TO 7% 0.75 in 4.5% TO 7% 5. LEVELING GROUT: NON-SHRINK, ASTM C1107, 5,000 PSI MINIMUM 2-DAY COMPRESSIVE STRENGTH. 6.REINFORCING STEEL: ASTM A615, GRADE 60 WELDED REINFORCING BARS: ASTM A706 AND AWS D1.4. WELDED WIRE FABRIC: ASTM A185, SUPPLIED IN SHEETS 7. REINFORCING BAR FABRICATION: ACI 318 FOR HOOKS AND BENDS UNO. 8.SECURE REINFORCEMENT: PROVIDE ACCESSORIES, CHAIRS, SPACERS, AND SUPPORTS. 9.LAP SPLICES: ACI-318 CLASS "B" TENSION LAP UNO. 10. REINFORCING BAR CLEAR COVER UNO: A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH = 3" B. FORMED CONCRETE EXPOSED TO EARTH OR WEATHER: #6 AND LARGER = 2" #5 AND SMALLER = 1 1/2" C. CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SLABS AND WALLS = 3/4" ALL OTHER = 1 1/2" 11. PROVIDE DOWELS INTO FOUNDATION ELEMENTS WITH STANDARD 90 DEGREE HOOKS OF THE SAME SIZE AND QUANTITY AS PIER AND WALL REINFORCING ABOVE THE FOUNDATION UNO. 12. PROVIDE CORNER BARS TO MATCH HORIZONTAL REINFORCING IN WALLS AND FOOTINGS. 13. CONCRETE TESTING: A.(1) COMPOSITE SAMPLE FOR EACH DAY'S POUR OF EACH CONCRETE MIX EXCEEDING 5 CY, BUT LESS THAN 25 CY, PLUS (1) SET FOR EACH ADDITIONAL 50 CY OR FRACTION THEREOF (ASTM C 172). B. OBTAIN: SLUMP (ASTM C 143), AIR CONTENT (ASTM C 231), TEMPERATURE (ASTM C 1064), AND UNIT WEIGHT (ASTM C 567) FOR EACH COMPOSITE SAMPLE. C.CAST AND FIELD CURE (1) SET OF (6) STANDARD CYLINDER COMPRESSION TEST SPECIMENS FOR EACH COMPOSITE SAMPLE (ASTM C 31). TEST (2) AT 7 DAYS, (2) AT 28 DAYS, AND HOLD (2) FOR 56 DAYS AS REQUIRED. D.CAST AND LABORATORY CURE (2) SET OF (6) STANDARD CYLINDER COMPRESSION TEST SPECIMENS FOR EACH COMPOSITE SAMPLE (ASTM C 31). TEST (2) AT 7 DAYS, (2) AT 28 DAYS AND HOLD (2) FOR 56 DAYS AS REQUIRED. 14. ELEVATED SLABS: ADJUST CONCRETE QUANTITIES TO MAINTAIN A LEVEL SLAB SURFACE AT THE REQUIRED ELEVATIONS TO ACCOMMODATE SUPPORT DEFLECTIONS. 15. ADHESIVE ANCHORS: LOCATE AWAY FROM REBAR. HILTI RE500; POWERS PE1000+; SIMPSON SET. 16. CONCRETE WALL JOINTS:(H = WALL HEIGHT) A.CONSTRUCTION JOINTS:FOUNDATION WALLS = 30 FT MAX RETAINING WALLS = 25 FT MAX WALL CORNERS = H FT FROM CORNER B.CONTRACTION JOINTS:FOUNDATION WALLS = 3H OR 15 FT MAX RETAINING WALLS = 3H OR 12'-6" FT MAX C.EXPANSION JOINTS: ALL WALLS = 100 FT MAX 17. SHOP DRAWINGS: SUBMIT PRIOR TO CONSTRUCTION FOR REINFORCING STEEL; CONCRETE MIX DESIGNS; PROPOSED CONSTRUCTION JOINT LOCATIONS FOR CONCRETE ELEMENTS INCLUDING WALLS, FOOTINGS, ELEVATED SLABS, AND TOPPING. STEEL NOTES 1. STRUCTURAL STEEL SHALL CONFORM TO THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) AISC 360 -SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS AND AISC 303 -CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES. 2.STRUCTURAL STEEL GRADES (UNLESS NOTED OTHERWISE): W-SECTIONS: ASTM A572 (ASTM A992), Fy = 50KSI ANGLES, PLATES & CHANNELS: ASTM A36, Fy = 36ksi COLUMN BASE PLATES, MOMENT CONNECTION PLATES: ASTM A572, Fy = 50KSI HOLLOW STRUCTURAL SECTIONS (HSS): ASTM A500 GRADE B, RECT 46KSI, ROUND 42KSI PIPE: ASTM A53 GRADE B, Fy = 35ksi ANCHOR RODS: 3/4" DIA. = ASTM F1554, GRADE 55 +S1, WELDABLE 1 1/4" DIA. = ASTM F1554, GRADE 105 BOLTS: ASTM A325N (A325X, A490N, A490X AND SC WHERE INDICATED) SHEAR CONNECTORS: ASTM A108 WELDS: E70xx ADHESIVE ANCHORS: ASTM F1554, GRADE 105 (OR ASTM A193 B7) GALVANIZED STRUCTURAL STEEL: ASTM A123 GALVANIZED BOLTS, FASTENERS, AND HARDWARE: ASTM A153 3.WELDING: AWS D1.1. ALL-AROUND FILLET WELDS FOR STEEL CONNECTIONS NOT INDICATED. 4. STRUCTURAL STEEL FINISH: AS INDICATED BELOW. COORDINATE WITH THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS. APPLY COATINGS IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS, INCLUDING SURFACE PREPARATIONS. AFTER ERECTION TOUCH UP AREAS WHERE PAINT OR GALVANIZING IS MISSING OR DAMAGED INCLUDING FIELD WELDS. VERIFY COMPATIBILITY BETWEEN ALL LAYERS OF COATINGS. COLORS SELECTED BY ARCHITECT. A.HOT-DIP GALVANIZE: LINTELS IN EXTERIOR WALLS, ALL EXTERIOR EXPOSED STEEL, AND ALL STEEL OUTSIDE THE STRUCTURE'S THERMAL ENVELOPE. B. STEEL TO RECEIVE SPRAY APPLIED FIRE RESISTANT MATERIALS: DO NOT PAINT. PREPARE AND CLEAN PER MANUFACTURER'S INSTRUCTIONS. C. INTUMESCENT COATINGS: WHERE INDICATED BY ARCHITECTURAL DRAWINGS. APPLY PER MANUFACTURER'S INSTRUCTIONS. D.ALL OTHER STRUCTURAL STEEL SHALL BE SHOP PAINTED WITH A MODIFIED ALKYD RUST INHIBITIVE PRIMER, 2.5 TO 3.5 MILS DFT (BASIS OF DESIGN IS TNEMEC SERIES 10). 5. BEAM CONNECTIONS: DESIGNED FOR THE LARGEST END REACTION COMPUTED FROM THE TABLE "UNIFORM LOAD CONSTANTS" IN THE AISC MANUAL, THE REACTIONS SHOWN ON THE PLANS, OR A SERVICE LOAD OF 10 KIPS. NOTE THAT REACTIONS SHOWN ON PLANS ARE STRENGTH (LRFD / ULTIMATE) LEVEL. 6. FRAMED BEAM CONNECTIONS: LENGTH EQUAL TO THE SMALLER BEAM'S "T" DIMENSION UNO. 7. PROVIDE L3X3X1/4 DECK ANGLE AT THE PERIMETER OF ALL ROOFS UNO. 8. THE GENERAL CONTRACTOR SHALL VERIFY THE SIZE AND LOCATION OF ALL ROOF DECK OPENINGS REQUIRED BY THE MECHANICAL AND ELECTRICAL CONTRACTORS AND SHALL PROVIDE SUMP PANS OR ADDITIONAL FRAMING AS REQUIRED. CUTTING HOLES IN ROOF DECKING OR SUMP PANS SHALL BE DONE BY THE MECHANICAL AND ELECTRICAL CONTRACTORS FOR THEIR OWN WORK UNDER THE SUPERVISION OF THE GENERAL CONTRACTOR. HOLES SHALL BE CUT NEATLY WITH A MAXIMUM SIZE OF PIPE OR DUCT DIMENSION PLUS 1". AN ANGLE FRAME ASSEMBLY IS REQUIRED AT ALL ROOF OPENINGS EXCEEDING 6", REFER TO TYPICAL DETAILS. 9. SHOP DRAWINGS: SUBMIT FOR REVIEW PRIOR TO FABRICATION. 10. CONNCTION DESIGN: A. AISC OPTION 2: FABRICATOR'S EXPERIENCED STEEL DETAILER SHALL SELECT OR COMPLETE CONNECTIONS IN ACCORDANCE WITH ANSI/AISC 303. i. SELECT AND COMPLETE CONNECTIONS USING SCHEMATIC DETAILS INDICATED AND ANSI/AISC 360. ii. USE LOAD AND RESISTANCE FACTOR DESIGN; DATA ARE GIVEN AT FACTORED-LOAD LEVEL. B. AISC OPTION 3 AND 3B: DESIGN CONNECTIONS AND FINAL CONFIGURATION OF MEMBER REINFORCEMENT AT CONNECTIONS IN ACCORDNACE WITH ANSI/AISC 303 BY FABRICTOR'S QUALIFIED PROFESSIONAL ENGINEER. i. USE LOAD AND RESISTANCE FACTOR DESIGN; DATA GIVEN AT FACTORED-LOAD LEVEL MASONRY NOTES 1. CONCRETE MASONRY DESIGN AND CONSTRUCTION: TMS 402 AND TMS 602. 2. CONCRETE MASONRY UNITS: ASTM C-90. F'm = 2000 PSI. 3. CMU MORTAR: ASTM C270 TYPE M OR S. TYPE M BELOW GRADE. 4. BRICK MORTAR: ASTM C270 TYPE N. TYPE S BELOW GRADE. 5. HORIZONTAL JOINT REINFORCING: ASTM A82, 9 GA, GALVANIZED LADDER-TYPE,16" O/C UNO. 6. CONCRETE MASONRY WALL CONTROL JOINTS: REFERENCE ARCHITECTURAL DRAWINGS AND PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS AND LOCATIONS. FOR CONTINUOUS EXTERIOR AND INTERIOR WALLS, REFER TO NCMA TEK NOTES 10-2B AND AS FOLLOWS: A. MAXIMUM JOINT SPACING: LESSER OF 1-1/2 TIMES THE WALL HEIGHT OR 25 FEET B. CHANGES IN WALL HEIGHT C. CHANGES IN WALL THICKNESS, SUCH AS PIPE AND DUCT CHASES AND PILASTERS D. (ABOVE) MOVEMENT JOINTS IN FOUNDATIONS AND FLOORS E. (BELOW) MOVEMENT JOINTS IN ROOFS AND FLOORS THAT BEAR ON A WALL F. NEAR ONE OR BOTH SIDES OF DOOR AND WINDOW OPENINGS. PLACE AT ONE SIDE OF AN OPENING LESS THAN 6 FT WIDE AND AT BOTH SIDES OF OPENINGS OVER 6 FT WIDE. CONTROL JOINTS CAN BE AWAY FROM THE OPENING IF ADEQUATE TENSILE REINFORCEMENT IS PLACED ABOVE, BELOW AND BESIDE WALL OPENINGS AS APPROVED BY ENGINEER. G. ADJACENT TO WALL CORNERS OR INTERSECTIONS WITHIN A DISTANCE EQUAL TO HALF THE CONTROL JOINT SPACING. H. BOND BEAM REINFORCEMENT TO BE CONTINUOUS. SCORE SHELL 3/8" EACH SIDE. 7. BLOCK CORE GROUT FILL: ASTM C476, 3,000 PSI MINIMUM 28 DAY COMPRESSIVE STRENGTH. PLACE IN LIFTS NOT EXCEEDING 7 COURSES IN HEIGHT UNLESS OTHERWISE APPROVED BY THE ENGINEER 8. PROVIDE FULL HEAD AND BED JOINTS. 9. MASONRY WALLS, PARTITIONS, AND OPENINGS: COORDINATE WITH ARCHITECTURAL DRAWINGS. 10. LAP SPLICES IN VERTICAL REINFORCING: 48 BAR DIAMETERS MINIMUM, UNO. 11. STRUCTURAL STEEL LINTELS: 8" MINIMUM BEARING AT EACH END, HOT DIP GALVANIZE EXTERIOR WALL LINTELS. LOAD BEARING LINTELS NOT INDICATED ON PLAN SHALL BE W8X21 WITH BOTTOM PLATE UP TO 5'-0". FOR LARGER OPENINGS, CONTACT STRUCTURAL ENGINEER. REFER TO LINTEL SCHEDULE ON SHEET S501 FOR ADDITIONAL INFORMATION. 12. MASONRY COURSING INDICATED ON THE STRUCTURAL DRAWINGS IS APPROXIMATE. REFER TO ARCHITECTURAL DRAWINGS FOR COURSING LAYOUT. CUT UNITS AS REQUIRED TO ACHIEVE ELEVATIONS, BEARING ELEVATIONS, AND OPENINGS INDICATED. 13. REINFORCING STEEL: A615 REINFORCING STEEL, 60 KSI TYPICAL, A706 REINFORCING STEEL, 60 KSI AT WELDED APPLICATIONS SECURE IN PLACE PRIOR TO PLACING GROUT, DO NOT WET-SET 14. GROUT MASONRY CELLS BELOW GRADE. 15. ADHESIVE ANCHORS: LOCATE AWAY FROM REBAR. A. GROUTED CMU = HILTI HY200 OR POWERS AC100+ OR SIMPSON SET B. HOLLOW CMU = HILTI HY70 OR POWERS AC100+ OR SIMPSON ACRYLIC-TIE 16. SHOP DRAWINGS: SUBMIT FOR REINFORCING STEEL, GROUT AND MORTAR MIX DESIGNS, AND CMU PRODUCT DATA TO THE ARCHITECT FOR REVIEW BEFORE CONSTRUCTION. STEEL DECK 1. STEEL DECK SHALL CONFORM TO THE STEEL DECK INSTITUTE'S CODE OF STANDARD PRACTICE,SDI C1.0 STANDARD FOR COMPOSITE STEEL FLOOR DECK, SDI-NC1.0 STANDARD FOR NON-COMPOSITE STEEL FLOOR DECK, AND SDI-RD1.0 STANDARD FOR STEEL ROOF DECK. 2. ROOF DECK: GALVANIZED FINISH (G-90). CONTINUOUS OVER 3 OR MORE SPANS. FASTEN WITH 5/8" PUDDLE WELDS OR EQUIVALENT PAF'S (PER TABLE) AT 12" O/C IN FIELD AND 6" O/C IN PERIMETER ZONES AS DEFINED BY ASCE 7, BUT NOT LESS THAN 10'-0". SIDE LAPS SHALL BE FASTENED AT 1/3 SPAN LENGTH OR 18" O/C WITH #10 SCREWS. STEEL THICKNESS POWER ACTUATED FASTENERS (PAF'S) 7/64" TO 5/32"PNEUTEK SDK61 OR HILTI XEDNK22 THQ12 5/32" TO 1/4"PNEUTEK SDK63 OR HILTI XEDNK22 THQ12 3/16" TO 5/16"PNEUTEK K64 OR HILTI XEDN19 THQ12 >= 9/32" PNEUTEK K66 OR HILTI X-ENP-19-L15 3. NON-COMPOSITE STEEL FORM DECK: FASTEN TO SUPPORTS ACCORDING TO SDI RECOMMENDATIONS. PERMANENT STEEL FORM DECK SHALL HAVE A GALVANIZED FINISH (G-60). 4. COMPOSITE STEEL DECK: FASTEN TO SUPPORTS ACCORDING TO SDI RECOMMENDATIONS. COMPOSITE STEEL DECK SHALL HAVE A GALVANIZED FINISH (G-60). 5.ROOF DECK FINISH:TOP/BOTTOM = BARE/PRIMED FORM DECK FINISH:TOP/BOTTOM = BARE/PRIMED COMP DECK FINISH:TOP/BOTTOM = BARE/PRIMED 6.SUBMIT SHOP DRAWINGS FOR STEEL DECK FOR REVIEW PRIOR TO CONSTRUCTION. SLAB ON GRADE NOTES 1. SLAB ON GRADE CONSTRUCTION: ACI 302 GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION. MOIST CURE 10 DAYS. 2. VAPOR BARRIER: ASTM 1745, CLASS A, 15 MIL MINIMUM. 3. SURFACE TREATMENT: PENETRATING LIQUID TREATMENT, STAR SEAL PS, CLEAR (VEXCON) U.N.O. 4. SLOPED FLOORS: REFERENCE ARCHITECTURAL AND PLUMBING PLANS. MAINTAIN THICKNESS. 5. REENTRANT CORNERS: PROVIDE (2) #4 X 4'-0" LONG BARS ACROSS REENTRANT CORNERS OF RECTANGULAR SLAB OPENINGS AND AROUND THE PERIMETER OF ROUND SLAB OPENINGS. 6. CONTROL JOINTS: PROVIDE AT COLUMN CENTERLINES AND 10'-0" O/C MAXIMUM. 7. MOISTURE EMISSION RATE: MAXIMUM IN 24 HOURS PRIOR TO PLACING FLOOR FINISHES OF 3 LBS PER 1000 SQ-FT OR RATE REQUIRED BY THE FLOORING MANUFACTURER. 8. CONSTRUCTION JOINT SHOP DRAWINGS: SUBMIT PROPOSED LOCATIONS FOR REVIEW. GENERAL CONDITIONS 1. THE INFORMATION SHOWN ON THESE DOCUMENTS IS THE BEST REPRESENTATION OF EXISTING CONDITIONS AVAILABLE TO THE ENGINEER. IT IS THE CONTRACTORS RESPONSIBILITY TO FIELD VERIFY THOSE FEATURES WHICH WILL AFFECT THE BID PRICE AND MAKE ALLOWANCES FOR THEM IN THEIR BID. 2. EXISTING CONSTRUCTION ADJACENT TO NEW WORK SHALL BE ADEQUATELY SUPPORTED DURING CONSTRUCTION. THE CONTRACTOR SHALL REPAIR NEW OR EXISTING CONSTRUCTION DAMAGED WHILE WORK IS IN PROGRESS. 3. THE DRAWINGS REPRESENT THE FINISHED STRUCTURE AS A COMPLETE UNIT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MEANS, METHODS, AND SEQUENCES OF DEMOLITION AND CONSTRUCTION PHASES INCLUDING TEMPORARY SHORING AND BRACING. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES AND STANDARDS THAT PERTAIN TO MEANS, METHODS, AND SEQUENCES OF CONSTRUCTION. 4. CONTRACT DRAWINGS AND SPECIFICATIONS: COORDINATE STRUCTURAL DRAWINGS WITH ALL OTHER DRAWINGS AND SPECIFICATIONS. INCORPORATE COORDINATION REQUIREMENTS INTO CONTRACTOR'S WORK. 5. DETAILS NOT SPECIFICALLY SHOWN SHALL BE SIMILAR TO THOSE SHOWN FOR THE MOST NEARLY SIMILAR CONDITION AS DETERMINED BY THE ARCHITECT OR ENGINEER. 6. SURVEY SUBMITTAL: ENGAGE A LICENSED SURVEYOR TO ESTABLISH DIMENSION AND ELEVATION CONTROL OF THE BUILDING FEATURES PRIOR TO THE START OF CONSTRUCTION. ESTABLISH CONTROL POINTS AT KEY BUILDING FEATURES, BUILDING CORNERS, COLUMN LOCATIONS, FOOTING LOCATIONS, AND OVERALL LAYOUT TO ENSURE GEOMETRIC CLOSEOUT. SUBMIT FOR RECORD A SEALED CONTROL POINT DRAWING. 7. ANCHOR ROD SURVEY AS-BUILT PLAN: ENGAGE A LICENSED SURVEYOR TO PREPARE AN AS-BUILT SURVEY OF ANCHOR RODS. SUBMIT SEALED ANCHOR ROD SURVEY PLAN FOR RECORD. 8. SHOP DRAWINGS PREPARED BY SUPPLIERS AND SUBCONTRACTORS SHALL BE REVIEWED AND SIGNED AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMISSION TO THE ARCHITECT AND ENGINEER. REPRODUCTIONS OF THE STRUCTURAL DRAWINGS SHALL NOT BE USED FOR THE PREPARATION OF SHOP DRAWINGS. MANUFACTURED COMPONENTS SHALL BE SIGNED AND SEALED BY A LICENSED PROFESSIONAL ENGINEER PRIOR TO SUBMISSION. ANCHORS AND FASTENERS 1. PROVIDE THE FOLLOWING ANCHORS UNLESS NOTED OTHERWISE ON PLANS AND DETAILS. PROVIDE GALVANIZED FASTENERS AT ALL LOCATIONS OUTSIDE THE STRUCTURE THERMAL ENVELOPE AND AS NOTED. PROVIDE STAINLESS-STEEL (SS) ANCHORS AND FASTENERS AS NOTED. PROVIDE ANCHORS AND FASTENERS NOT LISTED BELOW, AS SPECIFICALLY NOTED ON PLANS. SUBSTITUTIONS FOR ANCHORS NOTED ON PLANS SHALL BE APPROVED BY THE ENGINEER. A. POWER ACTUATED FASTENERS (PAF): HILTI XU KNURLED SHANK FASTENER, 0.157" DIAMETER, OR EQUIVALENT. PENETRATION DEPTH (MINIMUM): 1 1/2" CONCRETE, 1" MASONRY, AND 1/2" STEEL. B. GENERAL MECHANICAL EXPANSION ANCHORS (MEA): HILTI KWIK BOLT III, DeWALT POWER- STUD+SD2, OR SIMPSON WEDGE-ALL. GALVANIZED AS NOTED. C. MECHANICAL EXPANSION ANCHORS FOR USE IN CRACKED CONCRETE (MECRA): HILTI KWIK BOLT TZ, DeWALT POWER-STUD+SD1, OR SIMSPON STRONG-BOLT. GALVANIZED AS NOTED. D. STAINLESS STEEL MECHANICAL EXPANSION ANCHORS (SSMEA): HILTI KWIK BOLT III, DeWALT POWER-STUD+SD4/SD6, OR SIMPSON WEDGE-ALL. E. HEAVY DUTY SCREW ANCHOR (HDSA): HILTI KWIK HUS, DeWALT SCREW BOLT+, SIMPSON TITEN-HD. F. HEAVY DUTY SLEEVE ANCHORS (HDSLA): DeWALT POWER-BOLT+. G. SLEEVE ANCHORS (SLA) POWERS LOK-BOLT, HILTI HLC SLEEVE ANCHOR, SIMPSON SLEEVE-ALL. H. NAIL SET ANCHORS (NSA): DeWALT ZAMAC HAMMER-SCREWS. I. GENERAL ADHESIVE ANCHORS IN CONCRETE: HILTI RE500, DeWALT PE1000+, OR SIMPSON SET-XP. J. 10.)POST INSTALLED REBAR (60 BAR DIAMETER EMBEDMENT UNO): HILTI HY200 OR DeWALT AC200+. K. ADHESIVE ANCHORS IN GROUTED MASONRY: HILTI HY270, DeWALT AC100+, OR SIMPSON ET-H L. ADHESIVE ANCHORS IN HOLLOW CMU: HILTI HY270 OR POWERS AC100+ OR SIMPSON SET-XP. PROVIDE SCREEN TUBES PER MANUFACTURER'S RECOMMENDATIONS AND STAINLESS STEEEL (SS) AS NOTED. COLD-FORMED STEEL FRAMING 1. LIGHT GAGE FRAMING (CFSF) SHALL CONFORM TO THE NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS. 2. MEMBERS TO HAVE MINIMUM YIELD STRESS OF 50 KSI AND SHALL HAVE A MINIMUM FLANGE WIDTH OF 15/8" AND A RETURN LIP LENGTH OF 1/2". WHERE FLANGE WIDTHS OF 2" ARE SPECIFIED, THE RETURN LIP LENGTH SHALL BE 5/8", WHERE FLANGE WIDTHS OF 3" ARE SPECIFIED, THE RETURN LIP LENGTH SHALL BE 5/8". 3. SIZES AND GAGE (THICKNESS) SHOWN ON THE DRAWINGS ARE MINIMUM. A.TRACK GAGE: 54 MIL MINIMUM B. STUD GAGE: 54 MIL MINIMUM 4. BUILT UP MEMBERS SHALL BE FASTENED TOGETHER TO CREATE COMPOSITE MEMBERS PER AISI. 5.CFSF FINISH: ASTM A924 GALVANIZED, G60. 6.PROVIDE ALL ACCESSORIES, SUCH AS TRACKS, CLIPS, WEB STIFFENERS, AND ALL CONNECTORS REQUIRED FOR A COMPLETE INSTALLATION MEETING BUILDING CODE REQUIREMENTS AND MANUFACTURER RECOMMENDATIONS. 7.STRUCTURAL PERFORMANCE: PROVIDE COLD-FORMED STEEL MEMBERS CAPABLE OF WITHSTANDING DESIGN LOADS WITHIN LIMITS AND UNDER CONDITIONS INDICATED. A. DESIGN LOADS: AS INDICATED ON THE DRAWINGS AND LOADS REQUIRED BY THE GOVERNING BUILDING CODE FOR THE PROPOSED OCCUPANCY. B. DEFLECTION LIMITS: DESIGN FRAMING SYSTEMS TO WITHSTAND DESIGN LOADS WITH DEFLECTIONS NOT GREATER THAN THE FOLLOWING: i.) EXTERIOR LOAD-BEARING WALL FRAMING: HORIZONTAL DEFLECTION OF 1/600 OF THE WALL HEIGHT SUPPORTING BRICK VENEER. i.) EXTERIOR LOAD-BEARING WALL FRAMING: HORIZONTAL DEFLECTION OF 1/360 OF THE WALL HEIGHT SUPPORTING VENEER OTHER THAN BRICK. ii.) INTERIOR LOAD-BEARING WALL FRAMING: HORIZONTAL DEFLECTION OF 1/360 OF THE WALL HEIGHT UNDER A HORIZONTAL LOAD OF 5psf. ii.) INTERIOR NON-LOAD-BEARING WALL FRAMING: HORIZONTAL DEFLECTION OF 1/360 OF THE WALL HEIGHT UNDER A HORIZONTAL LOAD OF 5psf. iii.) EXTERIOR NON-LOAD-BEARING FRAMING: HORIZONTAL DEFLECTION OF 1/600 OF THE WALL HEIGHT SUPPORTING BRICK VENEER. iii.) EXTERIOR NON-LOAD-BEARING FRAMING: HORIZONTAL DEFLECTION OF 1/600 OF THE WALL HEIGHT SUPPORTING VENEER OTHER THAN BRICK. iv.) FLOOR AND ROOF JOISTS: VERTICAL DEFLECTION OF 1/360 (LIVE) AND 1/240 (TOTAL) OF THE SPAN. 8.WELDING: AWS D1.3 FOR WELDING SHEET STEEL IN STRUCTURES. CONSULT AWS D19.0, WELDING ZINC COATED STEEL, AND ANSI STANDARD Z49.1 FOR INFORMATION REGARDING SAFE WELDING PROCEDURES. WELDS SHALL BE TOUCHED-UP WITH A ZINC-RICH RUST-INHIBITIVE PRIMER. A. SUGGESTED METHODS FOR FIELD WELDING: 1/8" E60XX, GASLESS MIG B. WELDS SHALL BE INSPECTED BY A QUALIFIED INSPECTOR C. BURN THROUGH WILL BE CAUSE FOR REJECTION 9.SUBMIT SHOP DRAWINGS AND CALCULATIONS STAMPED BY AN ENGINEER LICENSED IN THE STATE OF NEW YORK SIGNED AND FOR COLD-FORMED STEEL FRAMING, CONNECTIONS, AND ACCESSORIES PRIOR TO CONSTRUCTION. 1.SUBMITTALS: A.PRODUCT DATA OR MANUFACTURER'S SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE UNISTRUT SYSTEM. B.SHOP DRAWINGS: INCLUDE DETAILS OF CUTS, CONNECTIONS, CAMBER, HOLES, AND OTHER PERTINENT DATA. INDICATE WELDS BY STANDARD AWS SYMBOLS AND SHOW SIZE, LENGTH, AND TYPE OF EACH WELD. C.CALCULATIONS: PROVIDE CALCULATIONS, SIGNED AND SEALED BY AN ENGINEER REGISTERED IN THE STATE OF NEW YORK, FOR ALL UNISTRUT MEMBER AND CONNECTION DESIGN. 2.QUALITY CONTROL TESTING DURING CONSTRUCTION: A.THE OWNER WILL ENGAGE AN INDEPENDENT TESTING AND INSPECTION AGENCY. THE CONTRACTOR SHALL COORDINATE TIMING AND ACCESSIBILITY WITH THE INSPECTOR. THE TESTING AGENCY ENGAGED BY THE OWNER SHALL PERFORM THE FOLLOWING SERVICES IN CONNECTION WITH UNISTRUT: B.INSPECT ALL MEMBERS FOR PROPER POSITION. C.PERFORM VISUAL INSPECTION OF ALL WELDS AND BOLTED CONNECTIONS. D.INSPECT ALL FULL PENETRATION WELDS AND 15% OF ALL FILLET WELDS, RANDOMLY SELECTED WITH MAGNETIC PARTICLE INSPECTION (ASTM E 709) 3.UPON COMPLETION, CERTIFY THAT ALL STRUCTURAL STEEL ON THE PROJECT, INCLUDING WELDING AND BOLTING OF MEMBERS, WAS DONE UNDER INSPECTION OF THE TESTING AGENCY CONCERNED AND IS IN ACCORDANCE WITH THE REQUIREMENTS OF PERTINENT CODES, AND THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. UNISTRUT NOTES MEDICAL EQUIPMENT SUPPORT 1.INSTALL MEDICAL EQUIPMENT ACCORDING TO MANUFACTURER'S INSTRUCTIONS. THE INFORMATION INDICATED ON THE STRUCTURAL DRAWINGS IS BASED ON "BASIS OF DESIGN" EQUIPMENT WITHOUT THE FINAL SELECTION AND ROOM SPECIFIC DATA FROM VENDORS/MANUFACTURERS. 2.MACHINE EQUIPMENT BASE PLATES: INSTALL WITH HIGH STRENGTH GROUT AND SIZE AND QUANTITY OF RECOMMENDED ANCHORS. CONCRETE SURFACE SHALL BE LEVEL TO WITHIN 1/32" OVER 10'-0" IN ANY DIRECTION UNLESS VENDOR SPECIFIC DATA IS LESS STRINGENT. GRIND, FILL AND/OR OTHERWISE MODIFY THE CONCRETE SURFACE TO ACHIEVE THE VENDOR SPECIFIC MINIMUM REQUIREMENTS. 3.EQUIPMENT FOUNDATION LAYOUT: PROVIDE ALL NECESSARY BOX-OUTS, RECESSES, AND HOLES REQUIRED BY VENDOR TO INSTALL THE EQUIPMENT. REFER TO THE BASIS OF DESIGN EQUIPMENT DATA SHEETS. 4. EQUIPMENT FOUNDATIONS: 4,000 PSI MINIMUM CONCRETE (FOOTING MIX). 5.UNISTRUT FRAMING: UNISTRUT FRAMING SHOWN IS CONCEPTUAL. SEE UNISTRUT NOTES THIS SHEET FOR ADDITIONAL INFORMATION. PROVIDE CHANNEL STRUT FRAMING BY UNISTRUT (R). 12 GAGE (97 MIL) MINIMUM WALL THICKNESS. PROVIDE CONNECTORS, SPRING NUTS, BRACES, THREADED ROD, ANCHORS, STANDARD MANUFACTURER'S BEAM CLAMPS, AND OTHER APPURTENANCE REQUIRED FOR A COMPLETE INSTALLATION. PROVIDE ENGINEERED DRAWINGS SEALED BY AN ENGINEER LICNESED IN THE STATE OF NEW YORK FOR EACH INSTALLATION. 6.BARIATRIC SUPPORT FRAMING: FRAMING SHOWN IS CONCEPTUAL. COORDINATE FRAMING LAYOUT WITH THE FINAL ROOM SPECIFIC BARIATRIC LIFT CONFIGURAITON. PROVIDE ENGINEERED DRAWINGS SEALED BY AN ENGINEER LICNESED IN THE STATE OF NEW YORK FOR EACH INSTALLATION. 7.MEDICAL EQUIPMENT BOOM SUPPORT FRAMING: FRAMING SHOWN IS CONCEPTUAL. COORDINATE FINAL BOOM SUPPORT FRAMING STRUCTURAL DESIGN AND LAYOUT WITH FIELD LOCATED BOOM ISO-CENTER AND FINAL EQUIPMENT SELECTION BY OWNER. PROVIDE ENGINEERED DRAWINGS SEALED BY AN ENGINEER LICNESED IN THE STATE OF NEW YORK FOR EACH INSTALLATION. DELEGATED DESIGN PROVIDE DOCUMENTS, DOCUMENTATION, AND INFORMATION INDICATED PREPARED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE THE WORK IS PERFORMED. 1. TEMPORARY SHORING 2. SOIL BEARING AND SURFACE CONDITIONS FOR STRUCTURAL WORK ON EARTH OR FILL 3. STRUCTURAL STEEL CONNECTIONS 4. STAIRS, GUARDRAILS, AND RAILINGS 5. CONCRETE FORMWORK 6. COLD-FORMED STEEL (OR METAL) FRAMING (CFSF, OR CFMF) 7. PRECAST CONCRETE ELEMENTS 8. PERFORMANCED-BASED DESIGN 9. MEDICAL EQUIPMENT SUPPORT FRAMING 10. ANCHORS AND FASTENERS IN-LIEU OF SPECIFIED FASTENERS DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:31 PMS001 GENERAL NOTES 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDINGSTRUCTURAL DRAWING LIST SHEET NO.SHEET TITLE S001 GENERAL NOTES S002 GENERAL NOTES AND SPECIAL INSPECTION S003 FOUNDATION LOADING PLAN AND C&C WIND LOADING S100 FOUNDATION PLAN S101 COLUMN AND SLAB PLAN S102 SECOND FLOOR FRAMING PLAN S103 THIRD FLOOR FRAMING PLAN S104 FOURTH FLOOR FRAMING PLAN S105 FIFTH FLOOR FRAMING PLAN S106 ROOF FRAMING PLAN S500 DETAILS AND SECTIONS S501 DETAILS AND SECTIONS S502 DETAILS AND SECTIONS S503 DETAILS AND SECTIONS S504 DETAILS AND SECTIONS S505 COLUMN SCHEDULE & BRACED FRAME ELEVATION S506 DETAILS AND SECTIONS REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 REF.RAPINSPECTOR QUALIFICATIONS CATEGORY GENERAL QUALIFICATIONS THE FOLLOWING TABLE COMPRISES THE MINIMUM QUALIFICATIONS FOR SPECIAL INSPECTORS FOR THIS PROJECT IN ACCORDANCE WITH THE UNIFORM CODE, IBC CHAPTER 17. REFER TO THE PROJECT SPECIFICATIONS AND SCHEDULE OF SPECIAL INSPECTIONS FOR ADDITIONAL INFORMATION. 1. FOR EACH CATEGORY LISTED THE FOLLOWING QUALIFICATIONS ARE ACCEPTABLE: A. ENGINEER IN TRAINING (EIT) WITH RELEVANT EXPERIENCE. B. NEW YORK STATE LICENSED PROFESSIONAL ENGINEER (PE) WITH RELEVANT EXPERIENCE. CODE REFERENCE MINIMUM QUALIFICATIONS REINFORCED CONCRETE PRESTRESSED CONCRETE WELDING HIGH STRENGTH BOLTING AND STEEL FRAME INSPECTION MASONRY SPRAYED FIRE-RESISTANT MATERIALS SOILS INSPECTION OF FABRICATORS EXTERIOR AND INTERIOR ARCHITECTURAL WALL PANELS EXTERIOR INSULATION AND FINISH SYSTEM SMOKE CONTROL SEISMIC RESISTANCE 1704.4 TABLE 1704.4 1704.3; TABLE 1704.3,ITEM 5; TABLE 1704.4,ITEM 2; 1707.2; 2208 1704.3.3; Table 1704.3 1704.5; Table 1704.5.1; Table 1704.5.3 1704.11 1704.7; 704.8; 1704.9; 704.13 1704.2 1704.10 1704.14 1707; 1708 1. CURRENT ICC REINFORCED CONCRETE SPECIAL INSPECTOR OR ACI CONCRETE CONSTRUCTION INSPECTOR. 2. CONCRETE FIELD TESTING CAN BE BY AN ACI CONCRETE FIELD TESTING TECHNICIAN WITH GRADE 1 CERTIFICATION. PRETENSION TENDONS: 1. CURRENT ICC REINFORCED CONCRETE CERTIFICATION AND ICC PRESTRESSED CONCRETE CERTIFICATION AND ACI CONCRETE FIELD TESTING TECHNICIAN WITH GRADE 1 CERTIFICATION PLUS ONE YEAR RELEVANT EXPERIENCE POST-TENSION TENDONS: 1. CURRENT POST-TENSIONING INSTITUTE (PTI) CERTIFICATION. 1. CURRENT ICC STRUCTURAL MASONRY CERTIFICATION AND ONE YEAR OF RELEVANT EXPERIENCE. 1. CURRENT ICC SPRAY-APPLIED FIRE PROOFING CERTIFICATION AND ONE YEAR OF RELEVANT EXPERIENCE. 1. CURRENT LEVEL II CERTIFICATION IN GEOTECHNICAL ENGINEERING TECHNOLOGY/CONSTRUCTION FROM THE NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET). 1. CURRENT ICC STRUCTURAL STEEL AND WELDING CERTIFICATION AND ONE YEAR OF RELEVANT EXPERIENCE. 1. CURRENT AWS CERTIFIED WELDING INSPECTOR. 2. CURRENT ICC STRUCTURAL STEEL AND WELDING CERTIFICATE PLUS ONE YEAR OF RELEVANT EXPERIENCE. 3. CURRENT LEVEL II CERTIFICATION FROM THE AMERICAN SOCIETY FOR NONDESTRUCTIVE TESTING (NDT). 4. CURRENT NDT LEVEL III PROVIDED PREVIOUSLY CERTIFIED AS NDT LEVEL II. 1. PRECAST: CURRENT ICC REINFORCED CONCRETE CERTIFICATION PLUS ONE YEAR RELEVANT EXPERIENCE. 2. BAR JOIST: SEE WELDING REQUIREMENTS. 3. METAL BUILDING: SEE WELDING REQUIREMENTS. 4. STRUCTURAL STEEL: SEE WELDING REQUIREMENTS. 1. SEE THE MASONRY REQUIREMENTS FOR THE SI OF MASONRY VENEERS SUBJECT TO BCNYS SECTION 1704.10. 1. REGISTERED DESIGN PROFESSIONAL (RDP) WITH RELEVANT EXPERIENCE. 2. EIT WITH RELEVANT EXPERIENCE. 1. SEE THE REQUIREMENTS IN BCNYS SECTION 1704.14.2 2. 2. THE RDP RESPONSIBLE FOR DESIGN. 1704.12 1. SEE THE APPLICABLE CATEGORIES IN THIS TABLE. STRUCTURAL SPECIAL INSPECTIONS 1. 2. 3. 4. 5. PERIODIC CONTINUOUS PERIODIC EARTHWORK 1705.6 1. CAST-IN-PLACE CONCRETE 2. ACI 318: CH. 20, 20.5 25.3, 26.6.1-26.6.3 1908.4 5. --AWS D1.4 ACI 318:26.6.4 7. 1908.10ASTM C172, C31 ACI 318: 26.4, 26.12 8. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING PLACEMENT AND COMPACTION OF COMPACTED FILL. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT SITE HAS BEEN PREPARED PROPERLY. INSPECT REINFORCEMENT, INCLUDING PRESTRESSING TENDONS, AND VERIFY PLACEMENT REINFORCING BAR WELDING: a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706 b. INSPECT SINGLE PASS FILLET WELDS, MAXIMUM 5/16" c. INSPECT ALL OTHER WELDS VERIFY REQUIRED CONCRETE MIX IS USED AT EACH LOCATION. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF THE CONCRETE. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES 9.INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED.ACI 318: 26.11.1.2(b) SPECIAL INSPECTION NOTES THE FOLLOWING TABLE COMPRISES THE STRUCTURAL SPECIAL INSPECTION REQUIREMENTS FOR THIS PROJECT IN ACCORDANCE WITH THE NEW YORK STATE 2017 UNIFORM CODE AND NEW YORK STATE UNIFORM CODE SUPPLEMENT, CHAPTER 17. REFER TO THE PROJECT SPECIFICATIONS FOR REQUIRED QUALIFICATIONS OF PERSONNEL PERFORMING SPECIAL INSPECTION ACTIVITIES AND ADDITIONAL INFORMATION. REFERENCE STANDARD UNIFORM CODE REFERENCEAREAS OF INSPECTION AND TESTING FREQUENCY 1908.9ACI 318: 5.11-5.13 ACI 318:26.5 1908.6, 1908.7, 1908.8 1904.1, 1904.2 1908.2, 1908.3 ACI 318: CH. 19 26.4.3, 26.12 1. SPECIAL INSPECTIONS ARE REQUIRED FOR THIS PROJECT. 2. COORDINATE WORK WITH OWNER'S TESTING AND SPECIAL INSPECTION REPRESENTATIVE. 3. PREFABRICATED ITEMS SHALL BE MANUFACTURED BY APPROVED AND CERTIFIED SHOPS. 4. REFERENCE IBC CHAPTER 17 FOR DEFINITION OF "CONTINUOUS" AND "PERIODIC". 5. REFERENCE AISC 360 CHAPTER N FOR DEFINITION OF " PERFORM" AND "OBSERVE". 6. REFERENCE ACI 530 FOR DEFINITION OF "CONTINUOUS" AND "PERIODIC". 7. REFERENCE SDI QA/QC FOR DEFINITION OF "PERFORM AND "OBSERVE". PERIODIC PERIODIC CONTINUOUS CONTINUOUS PERIODIC PERIODIC CONTINUOUS PERIODIC PERIODIC PERIODIC PERIODIC 1. 4. 5. 6. INSPECTION TASKS AFTER BOLTING: STEEL CONSTRUCTION 7. INSPECTION TASKS PRIOR TO WELDING: A. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE. B. MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE. C. MATERIAL IDENTIFICATION (TYPE/GRADE) D. WELDER IDENTIFICATION SYSTEM E. FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY) F. CONFIGURATION AND FINISH OF ACCESS HOLES G. FIT-UP OF FILLET WELDS INSPECTION TASKS PRIOR TO BOLTING: A. MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS B. FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS. C. PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE) D. PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL E. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS. F. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED G. PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER FASTENER COMPONENTS A. FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED. B. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING OPERATION C. FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING D. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION, PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE EDGES A. PLACEMENT AND INSTALLATION OF STEEL DECK B. PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS C. DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS INSPECTION OF STEEL ELEMENTS OF COMPOSITE CONSTRUCTION PRIOR TO CONCRETE PLACEMENT PERFORM PERFORM PERFORM PERFORM PERFORM OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE 2.INSPECTION TASKS DURING WELDING: A. USE OF QUALIFIED WELDERS B. CONTROL AND HANDLING OF WELDING CONSUMABLES C. NO WELDING OVER CRACKED TACK WELDS D. ENVIRONMENTAL CONDITIONS E. WPS FOLLOWED F. WELDING TECHNIQUES OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE 3.INSPECTION TASKS AFTER WELDING: A. WELDS CLEANED B. SIZE, LENGTH AND LOCATION OF WELDS C. WELDS MEET VISUAL ACCEPTANCE CRITERIA D. ARC STRIKES E. K-AREA F. BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) G. REPAIR ACTIVITIES H. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT / MEMBER NONDESTRUCTIVE TESTING OF WELDED JOINTS: AISC 360 STRUCTURAL STEEL SPECIFICATION CHAPTER N, 5.5 OBSERVE PERFORM PERFORM PERFORM PERFORM PERFORM PERFORM PERFORM AWS D1.1 PERFORM OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE A. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS PERFORM 1705.2 3.1 INSPECTION TASKS DURING BOLTING: POST INSTALLED ANCHORS IN MASONRY AND CONCRETE 1. ANCHOR SIZE AND EMBEDMENT AND HOLE CLEANING (ALL) 2. HOLE CLEANING AND PREPARATION (ADHESIVE) 3. OVERHEAD APPLICATIONS (ALL) 4. HORIZONTAL ANCHORS SUPPORTING SUSTAINED TENSION (ADHESIVE) 5. ADDITIONAL INSPECTION PER MANUFACTURER'S ESR REPORT PERIODIC CONTINUOUS CONTINUOUS CONTINUOUS CONTINUOUS MANUFACTURER'S INSTALLATION INSTRUCTIONS ACI318 AND ESR REPORT MASONRY CONSTRUCTION 1. 2. ART. 1.5 530.1: ART. 2.1,2.6A 530.1: ART. 3.3B 3. 4. 5. 530.1: ART. 2.4B,2.4H 530.1: ART. 3.4,3.6A VERIFY COMPLIANCE WITH APPROVED SUBMITTALS: VERIFY THE FOLLOWING DURING CONSTRUCTION: VERIFY THE FOLLOWING PRIOR TO GROUTING: VERIFY THE FOLLOWING DURING CONSTRUCTION: A. SIZE AND LOCATION OF STRUCTURAL ELEMENTS B. TYPE, SIZE, AND LOCATION OF ANCHORS, INCLUDING OTHER DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS, FRAMES OR OTHER CONSTRUCTION C. WELDING OF REINFORCEMENT D. PREPARATION, CONSTRUCTION, AND PROTECTION OF MASONRY DURING COLD WEATHER (BELOW 40) OR HOT WEATHER (ABOVE 90) E. APPLICATION AND MEASUREMENT OF PRESTRESSING FORCE F. PLACEMENT OF GROUT G. PLACEMENT OF ACC MASONRY UNITS AND CONSTRUCTION OF THIN- BED MORTAR JOINTS OBSERVE GROUT SPECIMEN PREPARATION. ACI 530.1: 530.1: ART. 2.1C ACI 530.1: ART. 1.4 1705.4 A. GROUT SPACE B. GRADE, TYPE, AND SIZE OF REINFORCEMENT AND ANCHOR BOLTS, AND PRESTRESSING TENDONS AND ANCHORAGE C. PLACEMENT OF REINFORCEMENT, CONNECTORS AND ANCHORAGES D. PROPORTIONS OF SITE-PREPARED GROUT E. PROPER CONSTRUCTION OF MORTAR JOINTS ACI REFERENCE: A. PROPORTIONS OF SITE PREPARED MORTAR. B. CONSTRUCTION OF MORTAR JOINTS C. GRADE AND SIZE OF PRESTRESSING TENDONS AND ANCHORAGES D. LOCATION OF REINFORCEMENT, CONNECTORS, AND PRESTRESSING TENDONS AND ANCHORAGES E. PROPERTIES OF THIN-BED MORTAR FOR ACC MASONRY (PERIODIC AFTER FIRST 5,000 SF OF AAC) ACI REFERENCE PERIODIC REQUIREMENTS FOR LEVEL B SPECIAL INSPECTION & TESTING PERIODIC PERIODIC PERIODIC PERIODIC PERIODIC CONTINUOUS PERIODIC PERIODIC PERIODIC PERIODIC PERIODIC 530.1: ART. 3.2D,3.2F 530.1: ART. 2.4,3.4 530.1: ART. 3.2E,3.4,3.6A 530.1: 2.6B,2.4G.1.B 530.1: ART. 3.3B ACI REFERENCE ACI530.1: ART. 3.3F ACI530: SEC 1.2.1(E), 6.1.4.3, 6.2.1 ACI530: SEC 8.1.6.72 ACI530.1: ART. 1.8C ACI530.1: ART. 3.6B ACI530.1: ART. 3.5, 3.6C ACI530.1: ART. 1.4B.2.A-C.3, 1.4B.3-4 (REFERENCE AISC 360 CHAPTER N) 3.--INSPECT ANCHORS IN CONCRETE PERIODIC ACI 318: 17.8.2 4 -- INSPECT ANCHORS POST -INSTALLED IN HARDENED CONCRETE MEMBERS a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS. b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.A. CONTINUOUS PERIODIC ACI 318:17.8.2.4 ACI 318: 17.8.2 6. AISC 360 CHAPTER N 1. COLD FORMED STEEL FRAMING 2. 3. AISI S100-2004 FRAMING MEMBERS: SIZE, SPACING, STITCH CONNECTORS, ORIENTATION, AND ALIGNMENT SELF-TAPPING SCREWS FOR BEARING AND SHEAR WALLS: SHOP AND FIELD WELDED CONNECTIONS (BURN THROUGH WILL BE CAUSE FOR REJECTION) A. SIZE, QUANTITY, SPACING, EDGE DISTANCE, AND LOCATION PERIODIC PERIODIC PERIODIC (SEE STRUCTURAL STEEL FOR GENERAL REQUIREMENTS) AISI S100-2004 AWS D1.3 -- -- -- -- -- -- STEEL DECK INSTALLATION 1. INSPECTION OR EXECUTION TASKS PRIOR TO DECK PLACEMENT A. VERIFY COMPLIANCE OF MATERIALS (DECK AND ALL DECK ACCESSORIES) WITH CONSTRUCTION DOCUMENTS, INCLUDING PROFILES, MATERIAL PROPERTIES, AND BASE METAL THICKNESS B. DOCUMENT ACCEPTANCE OR REJECTION OF DECK AND DECK ACCESSORIES 2. INSPECTION OR EXECUTION TASKS AFTER DECK PLACEMENT A. VERIFY COMPLIANCE OF DECK AND ALL DECK ACCESSORIES INSTALLATION WITH CONSTRUCTION DOCUMENTS B. VERIFY DECK MATERIALS ARE REPRESENTED BY MILL CERTIFICATIONS THAT COMPLY WITH THE CONSTRUCTION DOCUMENTS C. DOCUMENT ACCEPTANCE OR REJECTION OF INSTALLATION OF DECK AND DECK ACCESSORIES 3. INSPECTION OR EXECUTION TASKS PRIOR TO WELDING A. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE B. MANUFACTURER CERTIFICATION FOR WELDING CONSUMABLES AVAILABLE C. MATERIAL IDENTIFICATION (TYPE/GRADE) D. CHECK WELDING EQUIPMENT 4. INSPECTION OR EXECUTION TASKS DURING WELDING A. USE OF QUALIFIED WELDERS B. CONTROL AND HANDLING OF WELDING CONSUMABLES C. ENVIRONMENTAL CONDITIONS (WIND SPEED, MOISTURE, TEMP) D. WPS FOLLOWED 5. INSPECTION TASKS AFTER WELDING A. VERIFY SIZE AND LOCATION OF WELDS, INCLUDING SUPPORT, SIDELAP, AND PERIMETER WELDS B. WELDS MEET VISUAL ACCEPTANCE CRITERIA C. VERIFY REPAIR ACTIVITIES D. DOCUMENT ACCEPTANCE OR REJECTION OF WELDS 6. INSPECTION OR EXECUTION TASKS PRIOR TO MECHANICAL FASTENING A. MANUFACTURER INSTALLATION INSTRUCTIONS AVAILABLE FOR MECHANICAL FASTENERS B. PROPER TOOLS AVAILABLE FOR FASTENER INSTALLATION C. PROPER STORAGE FOR MECHANICAL FASTENERS 7. INSPECTION OR EXECUTION TASKS DURING MECHANICAL FASTENING A. FASTENERS ARE POSITIONED AS REQUIRED B. FASTENERS ARE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS 8. INSPECTION OR EXECUTION TASKS AFTER MECHANICAL FASTENING A. CHECK SPACING, TYPE, AND INSTALLATION OF SUPPORT FASTENERS B. CHECK SPACING, TYPE, AND INSTALLATION OF SIDELAP FASTENERS C. CHECK SPACING, TYPE, AND INSTALLATION OF PERIMETER FASTENERS D. VERIFY REPAIR ACTIVITIES E. DOCUMENT ACCEPTANCE OR REJECTION OF MECHANICAL FASTENERS PERFORM PERFORM PERFORM PERFORM PERFORM OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE PERFORM PERFORM PERFORM PERFORM OBSERVE OBSERVE OBSERVE OBSERVE OBSERVE PERFORM PERFORM PERFORM PERFORM PERFORM SDI QA/QC QUALITY CONTROL AND QUALITY ASSURANCE FOR INSTALLATION OF STEEL DECK 1705.2.2 PERIODIC PERIODIC CONTINUOUS PERIODIC CONTINUOUS CONTINUOUS PERIODIC A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 5.6 A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.3 6'-0" BALANCED SNOW = 31 PSF ON LOW ROOF - DRIFT = 71 PSF AT BUILDING FACE ON LOW ROOF BALANCED SNOW = 31PSF6'-0"6'-0"6 '-0" ON LOW ROOF - BALANCED SNOW = 31PSFON LOW ROOF - DRIFT = 71 PSF AT BUILDING FACE 13'-0" 13'-0"13'-0"13'-0"13'-0"13'-0" ON MAIN ROOF - DRIFT = 93 PSF AT PARAPET FACE ON MAIN ROOF - DRIFT = 93 PSF AT PARAPET FACE ON MAIN ROOF - DRIFT = 93 PSF AT PARAPET FACE ON MAIN ROOF - DRIFT = 93 PSF AT PARAPET FACE BALANCED SNOW = 31PSF BALANCED SNOW = 31PSF BALANCED SNOW = 31PSF BALANCED SNOW = 31PSF DN DN DN DN DN DNDNDNDNDRIFT = 93 PSF AT WALL FACE 1 0' - 0 " MI N1 3 ' - 1 1 7 /8 "1 1 ' - 1 1 7 /8 "1 0' - 0 " MI Nø 5 ' - 0 "ø 4' - 0"ø 2' - 0"2' - 0"2' - 0"2' - 0"2' - 0" 2' - 8" ± 3' - 0" ± VIF 2' - 0" ±VIF2' - 0" ±VIF2' - 0" ±B.5 B.5 DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:37 PMS002 GENERAL NOTES AND SPECIAL INSPECTION 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/32" = 1'-0" SNOW DRIFT MAP REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 REF.RAPA A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 6 6 F 3.9 E 5.5 5.5 5.6 5.6 A.5 A.5 B.3 B.3 2.7 2.7 D.3 E.1 E.1 DEAD = 59 KIPS LIVE = 24 KIPS SNOW = 3 KIPS WIND = +2 KIPS / -2 KIPS EQ = +1 KIP / -2 KIPS DEAD = 130 KIPS LIVE = 55 KIPS SNOW = 49 KIPS WIND = +3 KIPS / -23 KIPS EQ = +2 KIPS / -2 KIPS DEAD = 15 KIPS LIVE = 6 KIPS SNOW = 7 KIPS WIND = +2 KIPS / -6 KIPS EQ = 0 DEAD = 15 KIPS LIVE = 8 KIPS SNOW = 3 KIPS WIND = +2 KIPS / -5 KIPS EQ = 0 DEAD = 161 KIPS LIVE = 110 KIPS SNOW = 49 KIPS WIND = +171 KIPS / -176 KIPS EQ = +96 KIPS / -140 KIPS DEAD = 305 KIPS LIVE = 120 KIPS SNOW = 57 KIPS WIND = +10 KIPS / -35 KIPS EQ = +5 KIPS / -8 KIPS DEAD = 170 KIPS LIVE = 95 KIPS SNOW = 49 KIPS WIND = +35 KIPS / -55 KIPS EQ = +5 KIPS / -40 KIPS DEAD = 20 KIPS LIVE = 10 KIPS SNOW = 6 KIPS WIND = +4 KIPS / -10 KIPS EQ = +1 KIP / -1 KIP DEAD = 127 KIPS LIVE = 62 KIPS SNOW = 24 KIPS WIND = +290 KIPS / -258 KIPS EQ = +0 KIPS / -260 KIPS DEAD = 182 KIPS LIVE = 96 KIPS SNOW = 44 KIPS WIND = +135 KIPS / -135 KIPS EQ = +96 KIPS / -0 KIPS DEAD = 180 KIPS LIVE = 118 KIPS SNOW = 55 KIPS WIND = +173 KIPS / -183 KIPS EQ = +140 KIPS / -0 KIPS DEAD = 236 KIPS LIVE = 72 KIPS SNOW = 39 KIPS WIND = +123 KIPS / -188 KIPS EQ = +158 KIPS / -23 KIPS DEAD = 364 KIPS LIVE = 116 KIPS SNOW = 72 KIPS WIND = +5 KIPS / -32 KIPS EQ = +2 KIPS / -0 KIPS DEAD = 328 KIPS LIVE = 121 KIPS SNOW = 88 KIPS WIND = +0 KIPS / -32 KIPS EQ = 0 KIPS DEAD = 122 KIPS LIVE = 65 KIPS SNOW = 44 KIPS WIND = +18 KIPS / -39 KIPS EQ = +21 KIPS / -5 KIPS DEAD = 250 KIPS LIVE = 89 KIPS SNOW = 42 KIPS WIND = +245 KIPS / -200 KIPS EQ = +0 KIPS / -230 KIPS DEAD = 430 KIPS LIVE = 130 KIPS SNOW = 88 KIPS WIND = +85 KIPS / -80 KIPS EQ = +77 KIPS / -44 KIPS DEAD = 35 KIPS LIVE = 20 KIPS SNOW = 10 KIPS WIND = +2 KIPS / -10 KIPS EQ = +3 KIPS / -1 KIPS DEAD = 415 KIPS LIVE = 130 KIPS SNOW = 100 KIPS WIND = +8 KIPS / -50 KIPS EQ = +8 KIPS / -2 KIPS DEAD = 185 KIPS LIVE = 90 KIPS SNOW = 70 KIPS WIND = +15 KIPS / -44 KIPS EQ = +18 KIPS / -2 KIPS DEAD = 136 KIPS LIVE = 73 KIPS SNOW = 23 KIPS WIND = +420 KIPS / -487 KIPS EQ = +417 KIPS / -145 KIPS DEAD = 248 KIPS LIVE = 110 KIPS SNOW = 52 KIPS WIND = +256 KIPS / -270 KIPS EQ = +165 KIPS / -185 KIPS DEAD = 122 KIPS LIVE = 52 KIPS SNOW = 50 KIPS WIND = +7 KIPS / -18 KIPS EQ = +4 KIPS / -6 KIPS DEAD = 175 KIPS LIVE = 95 KIPS SNOW = 64 KIPS WIND = +2 KIPS / -22 KIPS EQ = +2 KIPS / -2 KIPS DEAD = 68 KIPS LIVE = 42 KIPS SNOW = 9 KIPS WIND = +2 KIPS / -4 KIPS EQ = +1 KIP / -1 KIPS DEAD = 12 KIPS LIVE = 10 KIPS SNOW = 10 KIPS WIND = +1 KIP / -8 KIPS EQ = +1 KIP / -1 KIP DEAD = 430 KIPS LIVE = 132 KIPS SNOW = 89 KIPS WIND = +85 KIPS / -80 KIPS EQ = +77 KIPS / -45 KIPS NOTES: 1. LOADING INFORMATION IS PROVIDED FOR THE PURPOSES OF SOIL IMPROVEMENT DESIGN ONLY. 2. LOADS SHOWN IN GREEN BOXES ARE NOMINAL (UNFACTORED) LOADS CALCULATED PER ASCE 7-16 AND HAVE BEEN ROUNDED UP TO THE NEAREST KIP. 3. LOADS DESIGNATED AS "WIND" ARE THE VERTICAL COMPONENTS RESULTING FROM LATERAL WIND LOADS APPLIED TO THE BUILDING CALCULATED IN ACCORDANCE WITH ASCE 7-16. 4. LOADS DESIGNATED AS "EQ" ARE THER VERTICAL COMPONENTS RESULTING FROM SEISMIC LOADS CALCULATED IN ACCORDANCE WITH ASCE 7-16. 5. LOADS SHOWN DO NOT INCLUDE LIVE LOAD REDUCTION. 6. LOADS SHOWN EXCLUDE SELF-WEIGHT OF FOOTING AND WEIGHT OF SLAB-ON GRADE. 7. FOOTINGS HAVE BEEN SIZED ASSUMING A DESIGN ALLOWABLE BEARING PRESSURE OF 4000 PSF. NOTIFY STRUCTURAL ENGINEER IF THIS VALUE IS NOT ACHIEVED. 8. SLAB-ON-GRADE IS TO BE 5" THICK ON 12" OF COMPACTED SUBBASE MATERIAL. PROVIDE SUPPORT AS REQUIRED TO CONTROL SLAB DEFLECTION IN ACCORDANCE WITH PROJECT SPCIFICATIONS. SLAB-ON-GRADE LIVE LOAD = 100 PSF. 9. EXTERIOR PERIMETER FOUNDATION WALL LOAD = 3000 PLF (DEAD). 10. ELEVATOR SHAFT PERIMETER FOUNDATION WALL LOAD = 2500 PLF (DEAD). ELEVATOR PIT ESTIMATED LIVE LOAD = 50 KIPS. SEE NOTES FOR DEAD. PRECAST STAIR SUPPORT FOOTING DEAD = 7 KIPS LIVE = 4 KIPSSTAIR LANDING FOUNDATION WALL DEAD = 3 KLF LIVE = 3 KLF B.5 B.5 N A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 5.6 A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.310 ' - 0" MI N1 3 ' - 1 1 7 /8 "1 1 ' - 1 1 7 /8 "10 ' - 0" MI Nø 5 ' - 0 "ø 4' - 0"ø 2' - 0"2' - 0"2' - 0"2' - 0"2' - 0" 2' - 8" ± 3' - 0" ± VIF 2' - 0" ±VIF2' - 0" ±VIF2' - 0" ±2'-1 5/8"10'-0"2'-1 7/8"2'-7 1/2" ZONE 1 ZONE 2 ZONE 2 ZONE 2 ZONE 2 ZONE 3 ZONE 3 ZONE 3ZONE 3 ZONE 3 ZONE 2 ZONE 2 ZONE 1 1 0 '-0 "10 '-0" ZONE 3 ZONE 2 ZONE 2 ZONE 1 1 0 '-0 "1 0'- 0 " NOTES: 1. SEE TABLE ABOVE FOR LOAD VALUES. 2. FOR WALLS: EDGE DISTANCE (WIDTH OF ZONE 5) = 10'-0" FROM EACH CORNER, EACH WAY. BALANCE OF WALL FALLS IN ZONE 4. B.5 B.5 N GENERAL NOTES: 1. ULTIMATE COMPONENTS AND CLADDING PRESSURES PER ASCE 7. 2. USE ASCE 7 LOAD CASES TO CONVERT ULTIMATE VALUES TO SERVICE LOADS. 3. END ZONE DISTANCE (a) = 10'-0", 4. MEAN ROOF HEIGHT = 74'-0" 5. MINIMUM PRESSURE = +/- 16 PSF (ASCE 7 30.2) VERTICAL PRESSURE (PSF) - ROOF WITHOUT OVERHANG HORIZONTAL PRESSURE (PSF) - WALL VERTICAL PRESSURE (PSF) - ROOF WITH OVERHANG COMPONENT AND CLADDING WIND LOADS WALL AREA 10 ZONE 4 41.4 ZONE 5 ROOF AREA 10 ZONE 1 ZONE 2 ZONE 3 16.0 20 50 100 (+ ve)(- ve) 16.0 16.0 16.0 60.6 57.2 52.7 49.3 16.0 (+ ve)(- ve) 16.0 16.0 16.0 95.1 90.3 84.0 79.3 16.0 (+ ve)(- ve) 16.0 16.0 16.0 95.1 90.3 84.0 79.3 ROOF AREA 10 ZONE 1 ZONE 2 ZONE 3 16.0 20 50 100 (+ ve)(- ve) 16.0 16.0 16.0 58.2 56.3 54.8 54.4 16.0 (+ ve)(- ve) 16.0 16.0 16.0 81.2 73.5 62.0 54.4 16.0 (+ ve)(- ve) 16.0 16.0 16.0 115.7 100.3 81.2 69.7 50 100 >500 (+ ve, WINDWARD) (- ve, LEEWARD, SIDE) 38.1 35.6 29.9 41.4 39.2 37.6 33.7 41.4 38.1 35.6 29.9 75.9 67.2 60.6 45.2 20 41.4 41.4 41.4 75.9 >500 16.0 31.4 16.0 35.2 16.0 35.2 HORIZONTAL PRESSURE (PSF) - PARAPET WALL AREA 10 ZONE 4 42.2 ZONE 5 50 100 >500 WINDWARD LEEWARD WINDWARD LEEWARD 20 (+ ve, WINDWARD) (- ve, LEEWARD, SIDE) 42.2 38.9 36.4 30.5 (+ ve) 97.0 92.1 85.7 80.8 69.6 (- ve) (+ ve) 42.2 42.2 40.0 38.3 34.4 (- ve) (+ ve) 132.1 125.9 117.7 111.4 97.0 (- ve) (+ ve) 77.4 77.4 68.5 61.8 46.1 (- ve) 42.2 42.2 38.9 36.4 30.5 42.2 42.2 38.9 36.4 30.5 42.2 42.2 38.9 36.4 30.5 >500 16.0 41.4 16.0 68.2 16.0 68.2 DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:42 PMS003 FOUNDATION LOADING PLAN AND C&C WIND LOADING 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/32" = 1'-0"1 FOUNDATION LOADING PLAN 3/32" = 1'-0"2 ROOF C&C WIND ZONE MAP REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 TOP OF FOOTING ELEV UNO (WHERE SHOWN) LEGEND = TOP OF FOOTING ELEVATION UNLESS NOTED OTHERWISE = STEP FOOTING (REFER TO TYPICAL DETAILS) = CONSTRUCTION JOINT = SAWCUT GROOVE JOINT (CONTROL JOINT) = NO PIER = NO FOOTING = MATCH EXISTING SF CJ SJ NP NF ME -5'-0" FOOTING MARK (SEE FOOTING SCHEDULE)FX -96'-0" PIER MARK (SEE PIER SCHEDULE) PX TOF ELEV NOTES 1. DATUM ELEVATION = FINISHED GROUND FLOOR = 0'-0" (100' -0"). 2. REFER TO S001 AND S002 FOR GENERAL NOTES. REFER TO S101 FOR COLUMN AND SLAB PLAN. REFER TO S502 FOR FOUNDATION WALL AND FOOTING SCHEDULE. 3. TOP OF PIER IS (-0'-8") UNLESS OTHERWISE NOTED. 4. (+/-) X'-XX" DENOTES TOP OF FOOTING ELEVATION WITH RESPECT TO DATUM ELEVATION. 5. COLUMN PIERS AND GRADEWALLS SHALL BE CAST INTEGRAL. WALL REINFORCING SHALL BE CONTINUOUS THROUGH PIERS. REFER TO TYPICAL DETAILS. 6. COORDINATE LOCATION OF PIPES PENETRATING FOUNDATION WALLS WITH MECH. DRAWINGS. PROVIDE PIPE SLEEVES AT PENETRATIONS, REFER TO TYPICAL DETAILS. A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 6 6 F 3.9 E 5'-1 3/4"33'-3"14'-11 1/4"10'-5 5/8"5'-1 1/8"12'-6 5/8"16'-6 5/8"31'-6"23'-8 1/2"6'-9 1/2"24'-6 1/4"6'-11 3/4"31'-10"10'-7 7/8"16'-6" 1 8 '-8 "33.00°96'-0" F12 96'-0" F15.1 96'-0" F20 96'-0" F15.1 96'-0" F6 96'-0" F12 96'-0" F15 96'-0" F14 96'-0" F10 96'-0" F5 96'-0" F8 96'-0" F14 96'-0" F14 96'-0" F14 96'-0" F10 96'-0" F5 96'-0" F4 96'-0" F4 96'-0" F10 96'-0" F15.1 96'-0" F8 96'-0" F6 96'-0" F8 96'-0" F6 96'-0" F15 95'-0" F15 95'-0" F14F12F12F12F12 F15 F15F15 F15 F15F15F 1 5 96'-0" SF1 96'-0" SF1 96'-0" SF1 96'-0" SF1 96'-0" SF1 96'-0" SF1 96'-0" SF1 SUMP. COORDINATE WITH ELEVATOR SUPPLIER. 95'-0"F15F 1 5 F 1 5 96'-0" SF1 5.5 5.513'-8 3/4"18'-8 3/4"15 7/8"9"5.6 5.6 33.00°0'-3" 2 '-1" 4 '-1 "1'-3"1'-3"8'-0"1'-3"6'-8 1/2" P6 P5 P3 P5 P3 P1 P1 P1 P5 P3P3P6P6 P3 P6 P3 P4 P3 P6P6 P6P7 A.5 A.5 B.3 B.3 2.7 2.7 D.3 99'-7" F6 LOCATE FOOTING AT LANDING OF PRECAST STAIR 8'-8"+/- STRIP FOOTING. COORDINATE WITH STAIR LANDING.78.00°5 S501 TYP. 3 6 S500 96'-0" SF1 2 '-1 "5 '-1 "1 S501 1 S501 1 S501 1 S501 1 S501 4 S501 3 S501 12.00°90.00° E.1 E.1 2 '-1 "18 '-9 5 /8"13'- 5 1/4" 8 '-0 1 /8"61 '-11 1 /4" 1 '-3" 7" BRICK LEDGE (TYP) 7" BRICK LEDGE (TYP) 7" BRICK LEDGE (TYP) 7" BRICK LEDGE (TYP) 7" BRICK LEDGE (TYP) 7" BRICK LEDGE (TYP)2'-4"2'-4" 1 '-10"1'-10" 1 '-1 0 "1 '-4"2'-4"2'-4" 1'-4" 1'-4" 96'-0" SF1 1'-4" 1'-0"1'-4"11 S501 1 '-1 0 "1'- 4 "1'-4"1'-0"1'-4"1'-0"1'-4"1'-0"1'-0"1'-0"P7 11 S501 2 S501 2 S501 2 S501 2 S501 COORD. DIMS WITH FINAL ELEVATOR SELECTION 4'-5 3/4" 152'-5 7/8" B.5 B.5 12 S501 N 1 0 "SIM. SIM. 2 '-1 "0'-10"2'- 1 " 2 S501 SIM. 1 S501 SIM. 1'-0"1'-0" P6 P3 P3 P3 PROVIDE ENGINEERED SHORING FOR EXCAVATION TO ENSURE EXCAVATION WILL COMPLY WITH OSHA REQUIREMENTS AND TO ENSURE PROTECTION OF THE ADJACENT BUILDING. COORDINATE EXTENTS REQUIRED WITH FIELD CONDITIONS. SUBMIT PLANS SIGNED AND SEALED BY A REGISTERED NEW YORK STATE PROFESSIONAL ENGINEER. 7 5/8" ANTICIPATED CLOSEST POINT TO PROPERTY LINE. COORD. WITH SITE AND ARCH. APPROXIMATE LOCATION OF PROPERTY LINE. COORDINATE WITH SITE, ARCH. AND SURVEY INFORMATION.DO NOT LOCATE BUILDING BASED ON STRUCTURAL DRAWINGS. LINE IS PROVIDED HERE FOR INFORMATION ONLY. 20'-0" 8'-0" 1'-3" 10'-9"9'-3"10'-9"DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:42 PMS100 FOUNDATION PLAN 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"1 FOUNDATION PLAN PIER SCHEDULE PIER DESCRIPTION REINFORCING P1 18" DIAMETER (6)-#7 BARS WITH #3 TIES AT 12" o/c P3 24" X 24"(8)-#6 BARS WITH #3 TIES AT 12" o/c P4 24" X 30"(8)-#6 BARS WITH #3 TIES AT 12" o/c P5 30" X 30"(8)-#7 BARS WITH #3 TIES AT 12" o/c P6 24" X 36"(8)-#7 BARS WITH #3 TIES AT 12" o/c P7 36" X 36"FULL DEPTH ANCHOR RODS W/ #4 TIES AT 4" O/C STRIP FOOTING SCHEDULE MARK DESCRIPTION WIDTH DEPTH REINFORCING SF1 CONTINUOUS STRIP FOOTING 2'-0" 1'-0" (2)-#5 BARS, CONTINUOUS FOUNDATION WALL SCHEDULE MARK DESCRIPTION THICKNESS LAYERS VERTICAL DOWELS W/HOOK VERTICAL BARS HORIZONTAL BARS F12 12" C.I.P. FOUNDATION WALL 12" 2 #5 AT 12" O/C #5 AT 12" O/C #5 AT 12" O/C F15 15" C.I.P. FOUNDATION WALL 15" 2 #5 AT 12" O/C #5 AT 12" O/C #5 AT 12" O/C RECTANGULAR COLUMN FOOTING SCHEDULE MARK LENGTH WIDTH THICKNESS REINFORCING F4 4'-0"4'-0"16" (5)-#5 BARS EA. WAY F5 5'-0"5'-0"16" (6)-#5 BARS EA. WAY F6 6'-0"6'-0"16" (7)-#5 BARS EA. WAY F8 8'-0"8'-0"20" (9)-#7 BARS EA. WAY F10 10'-0"10'-0"24" (11)-#7 BARS EA. WAY F12 12'-0"12'-0"24" (13)-#7 BARS EA. WAY TOP AND BOTTOM F14 14'-0"14'-0"28" (19)-#7 BARS EA. WAY F15 15'-0"15'-0"30" (18)-#7 BARS EA. WAY TOP AND BOTTOM F15.1 15'-0"15'-0"54" (22)-#8 BARS EA. WAY TOP AND BOTTOM F20 20'-0"20'-0"72" (40)-#8 BARS EA. WAY TOP AND BOTTOM REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 RAPNOTES 1. DATUM ELEVATION = FINISHED GROUND FLOOR = 100'-0" (XXX' -X") 2. REFER TO S001 AND S002 FOR GENERAL NOTES. REFER TO S100 FOR FOUNDATION PLAN. 3. SEE S502 FOR STEEL COLUMN SCHEDULE. 4. PROVIDE HSS6X4X3/8 ELEVATOR DIVIDER BEAM AT (0'-0") AND AT 12'-0" O/C MAX. VERTICALLY. 5. BRACE FORCES SHOWN ARE ULTIMATE (FACTORED) LOADS. POSITIVE (+) FORCES INDICATE COMPRESSION, NEGATIVE (-) FORCES INDICATE TENSION. A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 6 6 F 3.9 E HSS8X6X5/8 BRACE (+205K/-140K) 5.5 5.5 5.6 5.6 A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.3 HSS8X6X5/8 BRACE(+175K/-160K)HSS6X6X1/2 BRACE(+90K/-80K)HSS6X6X5/8 BRACE (+125K/-75K) HSS6X6X1/2 BRACE (+140/-100K) HSS6X6X1/2 BRACE (+140K/-100K) HSS6X6X5/8 BRACE (+130K/-30K)HSS6X4X3/87 S500 1 S501 1 S501 1 S501 1 S501 1 S501 THICKENED SLAB 5" SLAB-ON-GRADE. SEE NOTES. SEE DETAILS. 4 S500 4 S500 4 S500 4 S500 4 S500 4 S500 SJ SJ SJ SJ SJ SJ SJ SJ SJ SJ SJ SJSJSJSJSJSJSJSJSJSJSJSJSJSJ SJ SJ SJ SJ SJ SJ SJ SJ SJ SJ SJ SJ SJ SJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJSJ SJ 1 S501 E.1 6 S500 HSS6X6X1/2W10X112HSS6X6X1/2W10X33HSS7X7X5/8W10X49W10X45W10X77W10X54HSS8X8X5/8W10X77W10X112W10X49W10X49W10X68W10X49W10X68HSS6X6X5/8W10X88W10X45W10X60W12X210W12X136W10X77W10X68W10X68BP-1BP-2BP-3BP-3W10X33BP-3BP-4BP-3ABP-5BP-2BP-5BP-6BP-7BP-4ABP-8BP-9ABP-9ABP-9ABP-9ABP-9BP-9BP-9BP-9BP-10BP-10PRECAST STAIR (SEE ARCH) RE-ENTRANT CORNER BARS (SEE TYP DETAILS) COLD-FORMED EXTERIOR WALLS (SEE ARCH & NOTES) B.5 B.5 12 S501 HSS8X6X5/8 BRACE (+205K/-140K)HSS8X6X5/8 BRACE(+175K/-160K)HSS6X6X1/2 BRACE(+90K/-80K)HSS6X6X5/8 BRACE (+125K/-75K) HSS6X6X5/8 BRACE (+130K/-30K) N SIM. SIM. 1 S501 HSS4X4X5/161 '-1 "2 4'-6"BP-11LEGEND = STEP FOOTING (REFER TO TYPICAL DETAILS) = CONSTRUCTION JOINT = SAWCUT GROOVE JOINT (CONTROL JOINT) SF CJ SJ DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:46 PMS101 COLUMN AND SLAB PLAN 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"1 COLUMN AND SLAB PLAN REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 -DENOTES TOP OF STEEL ELEVATION WITH RESPECT TO DATUM ELEVATION -DENOTES THE NUMBER OF 3/4" DIA. x 5" (LONG) SHEAR STUDS. -DENOTES MOMENT CONNECTION SEE SHEET S-504 -DENOTES FRAMED OPENING. COORDINATE SIZE AND LOCATION w/ ARCH. & MECH. DRAWINGS -BEAM MOMENT SPLICE. SEE DETAILS. (+/-x'-xx") [X] LEGENDNOTES 1. DATUM ELEVATION = 100'-0" = F.F.E. 2. T.O. 2ND FLOOR STEEL ELEVATION = 113'-5 3/4" 3. D6 = COMPOSITE SLAB, 6 1/4" TOTAL THICKNESS LIGHTWEIGHT CONCRETE SLAB ON 3", 20 GA, GALVANIZED COMPOSITE METAL DECK -BASIS OF DESIGN: VULCRAFT 3.0VL. REINFORCE WITH 4 LBS/CY STRUX90/40 (GRACE) MACRO-FIBER REINFORCING. 4. BEAMS ARE EQUALLY SPACED UNLESS NOTED OTHERWISE. 5. PROVIDE A MINIMUM 1/4" BENT PLATE AT FLOOR PERIMETERS U.N.O. 6. "E.O.S." INDICATES EDGE OF COMPOSITE DECK. 7. BRACE FORCES SHOWN ARE ULTIMATE (FACTORED) LOADS. POSITIVE (+) FORCES INDICATE COMPRESSION, NEGATIVE (-) FORCES INDICATE TENSION. 8. COORDINATE ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. OPENINGS NOT INDICATED ON PLANS SHALL CONFORM TO TYPICAL DETAIL REQUIREMENTS. 9. PROVIDE (1)-3/4" DIA. X 5" (LONG) SHEAR STUD PER FOOT OF LENGTH U.O.N. A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 6 6 F 3.9 E HSS6X6X5/8 BRACE (+140K/-75K) D6 D6 D6 D6 D6 5.5 5.5 5.6 5.6 A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.3 0'-6" E.O.S.0'-6" E.O.S.0'-6" E.O.S. 1 '-4 " E .O .S .1 '-4 " E .O .S .1 '-4" E.O.S. HSS6X6X5/8 BRACE (+140K/-75K)HSS6X6X5/8 BRACE(+130K/-90K)HSS6X6X3/8 BRACE(+100K/-65K)HSS6X6X3/8 BRACE (+100K/-50K) HSS6X6X3/8 BRACE (+105K/-50K) HSS6X6X1/2 BRACE (+145K/-40K) HSS6X6X1/2 BRACE (+145K/-40K) 3 S503 TOP OF EXTERIOR COLUMN W/ THERMALLY BROKEN SPLICE, TYP. AT 3 3 S503 3 S503 13 S503 3 S503 HSS4X4X5/16 (UP) COORD. W/ ARCH AND GLASS WALL SUPPLIER 12 K W18X50 20 K W18X76 3 4 K W 2 1 X 4 8 5 6 K66 KW24 X55 23 K66 K-FT12 KW14 X38 75 K-FT1 4 K32 KW18X11934 K27 KW18X35[17]27 K18 K W24X84 11 KW16X31 87 K W24X62 [28] 83 K 70 K W30X90 [122]105 K 73 K W24X55 [25] 74 K 1 3 3 K -F T27 K W 1 2 X 5 8 2 4 0 K -F T46 K 70 K W24X55 [25] 66 K 23 KW16X26 [15]23 K74 K W24X103 76 K 73 K W24X55 [24] 73 K25 KW16X31 [15]25 K25 KW16X31 [15]25 KW16X3124 KW16X31 [15]24 K19 KW16X26 [17]19 K23 KW16X31 [17]23 K27 KW18X35 [17]27 K27 KW18X35 [17]27 K31 KW21X4426 K24 KW16X31 [15]24 K24 KW16X31 [15]24 K25 KW16X26 [15]25 K26 KW16X31 [15]26 K26 KW16X31 [15]26 K20 KW16X26 [15]20 K14 KW12X19 [13]14 K23 KW16X26 [15]23 K24 KW16X26 [14]20 K23 KW18X35 [18]25 K11 KW12X19 [16]12 KW16X31 27 KW18X35 [17]27 K25 KW16X31 [15]25 K24 KW16X26 [15]24 K25 KW16X31 [15]25 K23 KW16X26 [14]22 KW12X19[6]21 KW16X26 [15]21 K8 KW12X19 [8]8 K7 KW12X19 [8]7 K21 K W18X40 31 K 13 KW14 X2221 KW16X312 5 K W 1 8 X 3 5 2 5 K 13 KW12X1412 K6 KW10X12W 8 X 1 3 W 16X31 1 0 K 21 KW16X26 [15]17 KW12X19 [6] W 1 0 X 3 3 W8X13W8X13W8X1337 K W21X44 [20] 37 K10 K W16X45 44 KW27X14658 K91 K-FT21 KW14X3892 K-FT22 K20 KW14X22 [13]21 K23 KW16X26 [14]21 K19 KW12X22 [11]17 K15 KW12X19 [17]13 K10 KW12X19 [16]12 K18 KW12X19 [11]17 K10 K W16X4526 KW16X31 [15]26 K23 KW16X26 [15]23 KW 8 X 1 3 8 K W16X31 7 K W12X19 [12]6 KW8X106 K123 K-FT25 KW14X38103 K-FT23 KHSS18X6X1/220 K W1 0 X30 12 K15 KW12X1913 KW8X13W16X31W12X19 [6] 2 3 K W 1 8 X 3 5 [3 2 ]4 1 K27 KW18X35 [17]27 K24 KW16X31 [15]24 K23 KW16X26 [15]23 K16 K W12X19 [11] 14 K 26 KW16X31 [15]26 K18 KW16X26 [17]18 K13 KW12X1413 KW12X19 [9]25 KW18X40 [20]23 K25 KW16X26 [15]25 K24 KW16X26 [15]24 K23 KW16X26 [15]23 K24 KW16X26 [15]24 KHSS6X4X3/8W16X3174 K W24X55 [25] 78 K 1'-10 3/4"W16X31E.1 E.1 9" E.O.S.HSS6X6X5/82 5 K -F T9 K 2 5 K -F T3 K SUPPLEMENTARY STRUCUTRAL SUPPORT BELOW: UNISTRUT SYSTEM FOR MEDICAL EQUIPMENT SUPPORT BY OTHERS. COORDINATE WITH EQUIPMENT MNFR. 1 S503 5 3 /4 " E .O.S. 6" E.O.S. 1'-3 7/8" +/- COLD-FORMED EXTERIOR WALLS (SEE ARCH & NOTES) #4'S AT 16" O/C (SEE TYP DETAILS) #4'S AT 16" O/C (SEE TYP DETAILS) 1'-0" E.O.S.3'-6"4" E.O.S.13'-2 3/4" +/-1'-5 7/8" E.O.S.1 1/8" E.O.S.7 5/8" E.O.S.2 1/2" E.O.S.10" E.O.S.UP12'-0 1/4" +/-5'-1 7/8" +/- SIMCOORD. W/ ARCH13'-1"6" E.O.S.1'-0" E.O.S.1'-0" E.O.S.7 1/8" E.O.S.8 1/4" E.O.S. 8 1 /4 " E .O .S .6 1/4" E.O.S.B.5 B.5 13 S502 15 S502 14 S502 14 S502 16 S502 HSS6X6X5/8 BRACE(+130K/-90K)HSS6X6X3/8 BRACE(+100K/-65K)HSS6X6X3/8 BRACE (+100K/-50K) HSS6X6X3/8 BRACE (+105K/-50K) 5 S506 5 S506 N 6" E.O.S. 6" E.O.S. 7 1/2" E.O.S.18 '-9 5 /8"HSS1 4X6 X5/89 S506 -1'- 4 1/ 4 " -1'-4 1/4" -1'-8 1/ 4 "HSS1 0X6 X1/2-1'-8 1/4"-1 '-8 1 /4 "-1 '-8 1 /4 "4 '-0 "16 K16 KL3X3X1/4 KICKER FROM TOP OF POST TO TOP FLANGE OF BEAM 10 S506 2 S503 H S S 1 0 X 6 X 1 /2 2 S503 2 S503 DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:47 PMS102 SECOND FLOOR FRAMING PLAN 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"1 SECOND FLOOR FRAMING PLAN REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 6 6W16X31 [15] W24X103 W16X45 W16X26 [15]W16X26 [15] W18X50 W16X26 [15] W18X50 W30X90 [22] W 8 X 2 1 W8 X10W 8 X 2 1 W8X2 1W8X21W8 X28 W 1 0 X 3 3W8X10W8X10 W8X10 W8X10 W8X10 W8X10W8X10W8X10W8X10W8X10W8X21W8X10W8X10 W16X26 [15]W16X31 [15]W24X68W8X10W8X10F 3.9 E W8X10HSS6X6X5/8 BRACE (+150K/-80K)W16X31 [15]W12X19 [17]W8 X15W8X1 0W12X19 [6] W 1 6X31 W8X18 LOW W21X5 5LOWW8X18 LOWW8 X18 LOWW8X18 LOWW12X19 LOWW 1 2X19 LOW W8X10 LOW D6 D6 D6 R1R 1 R1 R1 5.5 5.5 W8X10 W8X10 W8X10 W8X10 W8X10 W8X10 W8X10 W8X10 W8X48W8 X18 LOWW8X18 LOW 5.6 5.6 W8X10'S AT UNSUPPORTED ROOF HATCH OPENINGS W16X26 [15] A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.3 W10X12W10X121'-4" E.O.S.1'-7 1/2" E.O.S.1'-7 1/2" E.O.S. 1'-7 1/2" E.O.S.1'-7 1/2" E.O.S.11" E.O.S. 0'-11" E.O.S.HSS6X6X5/8 BRACE(+120K/-70K)HSS6X6X5/16 BRACE(+75K/-40K)HSS6X6X5/16 BRACE (+65K/-15K) HSS6X6X5/8 BRACE (+120K/-55K)W12X19W12X30 W12X19W12X19 W12X19W12X19 W12X19W12X19 W12X19 W12X19 W12X19 W12X19W12X19 W12X19W12X19 W12X19 W12X19HANGING COL., HSS3X3X1/4 HANGING COL., HSS3X3X1/4 HANGING COL., HSS3X3X1/4 4 S503 4 S503 15 S503 15 S503 W8X10'S AT UNSUPPORTED ROOF HATCH OPENINGS PROVIDE COLD FORMED HEADERS AND HANGING WALLS AS REQUIRED TO SUPPORT FIRE-RATED GLAZING (SEE ARCH) 1 8 '-8 "21 K W18X76 32 K W12X58 HSS14X6X5/812 K65 K W24X62 [19] 75 K 27 KW18X40 [33]27 K19 K W21X62 13 K 81 K W24X62 [29] 79 K26 KW18X35 [17]26 K25 KW16X31 [15]25 K126 K-FT25 KW12X40106 K-FT23 K73 K W24X55 [24] 73 K HSS14X6X3/840 K W21X44 [20] 40 K 70 K W24X55 [25] 66 K 3 1 K W 2 1 X 4 4 4 8 K23 KW16X31 [17]23 K27 KW18X40 [33]27 K27 KW18X40 [33]27 K28 KW18X35 [17]28 K26 KW16X31 [15]26 K25 KW16X31 [15]25 K24 KW16X31 [15]24 K24 KW16X31 [15]24 K20 KW16X26 [15]20 K23 KW16X26 [15]23 K27 KW16X31 [15]27 K28 KW18X35 [30]28 K19 KW12X22 [11]17 K23 KW16X26 [14]21 KW12X19 [11]27 KW16X31 [15]27 K26 KW12X19 [32]11 K28 KW18X35 [17]28 KW12X19 [6]21 KW16X26 [15]25 K28 KW18X35 [17]28 K25 KW16X31 [15]25 K24 KW16X26 [15]24 K32 KW30X9033 K47 KW30X9062 K14 KW16X3110 KW16X31 [13]W12X19 [6]21 KW16X26 [15]21 KW12X19 [8]W12X19 [8] 22 K W18X40 26 K W12X19 [25]10 K18 KW16X26 [15]17 K24 KW16X31 [15]24 K23 KW16X26 [15]23 K11 KW12X1910 KHSS18X6X1/248 K W21X44 24 K W12X30 W16X31 W12X30 W16X31 [17]27 KW18X40 [33]27 K24 KW16X31 [15]24 K79 K W24X55 [26] 78 K18 KW16X26 [17]18 KW12X19 [6]HSS6X4X3/8W12X19 W12X19 W16X31W16X3111 KW24X6823 K23 K24 K24 K23 K23 K22 K22 K25 K25 K23 K23 K15 K26 K13 K26 K11 K 10 K 53 K 68 K 69 K 92 K 23 K23 K10 K W12X199'-6 3/4"3'-6"6'-6 1/2"6'-7 1/2"12'-5 1/4"5'-8"W12X19W12X19 W12X19W12X19W12X19W8X10 W8X10 HANGING COL., HSS5X4X1/2 3 5 K-FT5 K6 1 K -F T9 K71 K-FT21 K6 1 K -F T9 K48 K-FT11 KE.1 E.1 9" E.O.S.W12X19 W12X19 W12X19 W12X30 W12X19 W12X19 HSS6X6X5/8W10X33 W10X33 W10X33 18'-7 1/2"[LOW][LOW][LOW] 4 S506 HSS4X4X5/16UPW16X31 W 8 X 1 8 2 5 K -F T 2 5 K -F T 6" E.O.S.4 S503 4 S503 6 " E.O.S . 6" E.O.S. #4'S AT 16" O/C (SEE TYP DETAILS) #4'S AT 16" O/C (SEE TYP DETAILS) COLD-FORMED EXTERIOR WALLS (SEE ARCH & NOTES) 3'-0" 3'-0" 1'-0" E.O.S.COORD. W/ ARCH12'-1 7/8"12'-0 1/4" +/-HSS4X4X5/16DOWNHSS4X4X5/16DOWN1 1/8" E.O.S.1'-5 7/8" E.O.S.13'-2 3/4" +/-1'-3 7/8" +/-5'-1 7/8" +/-1'-0" E.O.S.1'-0" E.O.S.7 1/8" E.O.S.6" E.O.S.4 1/4" E.O.S.8 1/8" E.O.S. 7 1/2" E.O.S. B.5 B.5 12 S502TYP15 S502 14 S502 14 S502 16 S502 6 S506 6 S506 SIM. 6 S506 6 S506 SIM.1'-7 1/2" E.O.S.HSS6X6X5/8 BRACE (+150K/-80K)HSS6X6X5/8 BRACE(+120K/-70K)HSS6X6X5/16 BRACE(+75K/-40K)HSS6X6X5/16 BRACE (+65K/-15K) HSS6X6X5/8 BRACE (+120K/-55K) 4 S503 N 3" E.O.S.1'-6" E.O.S.W12X19W12X195'-5 1/8"6'-7 1/2"6'-7 1/2"6'-7 1/2"6'-7 1/2"5'-1 3/4"0'-6 1/4"3'-0"5" E.O.S.3'-0" 3'-0" 11 S506 PROVIDE ANGLES TO SUPPORT CURTAIN WALL JAMB. COORD. WITH ARCH. 4" E.O.S.FALL PROTECTION ANCHOR ATTACHED TO W8. SEE ARCH. THRU-ROOF FALL PROTECTION STANCHIONS (NOT SHOWN) ATTACHED TO W8 AT LOCATIONS INDICATED ON ARCH DRAWINGS. SEE ARCH AND SPECS FOR LOACTIONS AND REQUIREMENTS. SUPPLEMENTAL W8X10'S MAY BE REQUIRED. PROVIDE FULL-DEPTH 3/8" WEB STIFFENERS AT FINAL LOCATIONS. FALL PROTECTION ANCHOR ATTACHED TO W8. SEE ARCH. THRU-ROOF FALL PROTECTION STANCHIONS (NOT SHOWN) ATTACHED TO W8 AT LOCATIONS INDICATED ON ARCH DRAWINGS. SEE ARCH AND SPECS FOR LOACTIONS AND REQUIREMENTS. SUPPLEMENTAL W8X10'S MAY BE REQUIRED. PROVIDE FULL-DEPTH 3/8" WEB STIFFENERS AT FINAL LOCATIONS. -DENOTES TOP OF STEEL ELEVATION WITH RESPECT TO DATUM ELEVATION -DENOTES THE NUMBER OF 3/4" DIA. x 5" (LONG) SHEAR STUDS. -DENOTES MOMENT CONNECTION SEE SHT. S-504 -DENOTES FRAMED OPENING. COORDINATE SIZE AND LOCATION w/ ARCH. & MECH. DRAWINGS -BEAM MOMENT SPLICE. SEE DETAILS. -ROOF STEP DOWN (+/-x'-xx") [X] LEGENDNOTES 1. DATUM ELEVATION = 100'-0" = F.F.E. 2. T.O. 3RD FLOOR STEEL ELEVATION = 127'-5 3/4" 3. T.O. LOW ROOF STEEL ELEVATION = 124'-6" 4. D6 = COMPOSITE SLAB, 6 1/4" TOTAL THICKNESS LIGHTWEIGHT CONCRETE SLAB ON 3", 20 GA, GALVANIZED COMPOSITE METAL DECK -BASIS OF DESIGN: VULCRAFT 3.0VL. REINFORCE WITH 4 LBS/CY STRUX90/40 (GRACE) MACRO-FIBER REINFORCING. 5. R1 = 1 1/2", 20 GA., TYPE B, GALVANIZED METAL ROOF DECK. MINIMUM 2-SPAN CONDITION. 6. BEAMS ARE EQUALLY SPACED UNLESS NOTED OTHERWISE. 7. PROVIDE A MINIMUM 1/4" BENT PLATE AT FLOOR PERIMETERS U.N.O. 8. "E.O.S." INDICATES EDGE OF COMPOSITE DECK. 9. BRACE FORCES SHOWN ARE ULTIMATE (FACTORED) LOADS. POSITIVE (+) FORCES INDICATE COMPRESSION, NEGATIVE (-) FORCES INDICATE TENSION. 10. COORDINATE ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. OPENINGS NOT INDICATED ON PLANS SHALL CONFORM TO TYPICAL DETAIL REQUIREMENTS. 11. PROVIDE (1)-3/4" DIA. X 5" (LONG) SHEAR STUD PER FOOT OF LENGTH U.N.O. 12. FOURTH FLOOR FRAMING (ABOVE) HAS BEEN DESIGNED FOR AN ADDITIONAL DL ALLOWANCE TO SUPPORT FUTURE 3RD FLOOR USES. SEE S001. DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:49 PMS103 THIRD FLOOR FRAMING PLAN 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"1 THIRD FLOOR FRAMING PLAN REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 HSS6X6X5/16 BRACE (+60K/-10K) D6 D6 D6 5.6 5.6 A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.3 1'-4" E.O.S.1'-4" E.O.S.1'-4" E.O.S. 1'-4" E.O.S.1'-4" E.O.S.1'-4" E.O.S.HSS6X6X5/16 BRACE (+60K/-10K) HSS6X6X5/16 BRACE (+65K/-15K) HSS6X6X5/16 BRACE (+65K/-15K)HSS6X6X5/16 BRACE(+75K/-30K)HSS6X6X5/8 BRACE. (+100K/-30K) 1 S503 1 S503 15 S503 15 S503 1 S503 11 K W18X50 11 K 48 K W18X76 [22] 48 K 34 K W18X65 20 KW16X31 [17]20 K10 KHSS14X6X5/810 K86 K W24X76 [19] 87 K 29 KW18X35 [17]29 K517 K-FT 90 K W24X84 360 K-FT 79 K 90 K W30X99 [31] 117 K 28 KW18X35 [17]28 K89 K W24X68 [31] 88 K 27 KW16X31 [15]27 K85 K W24X103 78 K 79 K W24X55 [24] 79 K 27 KW16X31 [15]27 K81 K W24X62 [30] 85 K 107 K-FT25 KW12X40139 K-FT27 K77 K W24X62 [29] 71 K 52 K W18X40 [46] 25 K 3 3 K W 2 1 X 4 4 5 2 K 12 K W18X50 10 K43 K W21X44 [20] 43 K11 K W16X45 11 K 26 KW16X31 [15]26 K26 KW16X31 [15]26 K25 KW21X50 [15]25 K27 KW16X31 [15]27 K25 KW18X35 [17]25 K13 KW16X31 [17]13 K29 KW18X35 [17]29 K29 KW18X35 [17]29 K30 KW18X35 [17]30 K30 KW18X35 [17]30 K28 KW16X31 [15]28 K28 KW16X31 [15]28 K25 KW16X31 [15]25 K26 KW16X31 [15]26 K27 KW16X31 [15]27 K27 KW16X31 [15]27 K22 KW16X26 [15]22 K25 KW16X31 [15]25 K29 KW18X40 [15]29 K21 KW12X22 [11]19 K25 KW21X50 [14]23 KW12X19 [3]W24X6852 K-FT19 K27 KW16X31 [15]27 K16 KW12X19 [9]14 K26 KW16X31 [15]26 K30 KW18X35 [17]30 K10 KW12X19 [6]28 KW16X31 [15]28 K30 KW18X35 [17]30 K42 KW27X8450 K59 KW30X9967 K28 KW21X4837 KW16X31 [13]W12X19 [6]23 KW16X31 [15]23 K28 KW16X31 [15]28 KW12X19 [5]W12X19 [5] 36 K W21X48 42 K W 16X3 1 10 KW16X31 [13]11 K24 KW16X26 [15]18 KW12X19 [10]23 KW12X1423 K10 KHSS18X6X1/210 K25 KW16X31 [15]25 K20 KW16X31 [17]20 K29 KW18X35 [17]29 K29 KW18X40 [15]29 K21 KW12X1421 K27 KW16X31 [15]27 KW12X19 [6]25 KW16X31 [15]25 KW12X19W16X31W16X31W12X19W12X19W12X19W12X30 W12X19 W12X19 W12X19 W12X19 W12X19W12X19 W12X19W12X19 W12X19 W12X19W12X19 W12X30 W12X19W12X19 W12X19 W12X19W12X19W12X19 W12X19W12X19 W12X19W12X30 W12X19W12X19W12X30 W8X10 W8X10 5" E.O.S.W12X19 W12X30 W12X19 W12X19 W12X19 HSS14X6X5/8HSS6X6X5/8HSS4X4X5/16UPW12X19 W12X19 W16X31 W16X31 3'-9 5/8" 3'-9 5/8"9" E.O.S. COORD. W/ ARCH11'-3"1'-0" E.O.S.4" E.O.S.9'-6 3/4"3'-6"6'-6 1/2"6'-7 1/2"6'-7 1/2"5'-9 3/4"5'-8"#4'S AT 16" O/C (SEE TYP DETAILS) #4'S AT 16" O/C (SEE TYP DETAILS) COLD-FORMED EXTERIOR WALLS (SEE ARCH & NOTES)6" E.O.S.6" E.O .S . 6" E.O.S.12'-0 1/4"4 1/4" E.O.S.8 1/8" E.O.S. PROVIDE COLD FORMED HEADERS AND HANGING WALLS AS REQUIRED TO SUPPORT FIRE-RATED GLAZING (SEE ARCH) 5'-1 7/8" +/-13'-2 3/4" +/-1'-3 7/8" +/- 1'-0" E.O.S.6" E.O.S.1 1/8" E.O.S.1'-5 7/8" E.O.S.7 1/8" E.O.S.RADIAL STAIR BY OTHERS. PROVIDE HSS14X4X5/16 STAIR STRINGERS (MIN.)1'-0" E.O.S.B.5 B.5 15 S502 14 S502 14 S502 16 S502 HSS6X6X5/8 BRACE. (+100K/-30K)HSS6X6X5/16 BRACE(+75K/-30K)HSS6X6X5/16 BRACE(+75K/-30K)HSS6X6X5/16 BRACE(+75K/-30K)N 3" E.O.S.1'-6" E.O.S.5'-5 1/8"6'-7 1/2"6'-7 1/2"6'-7 1/2"6'-7 1/2"5'-1 3/4"0'-6 1/4"0'-10 7/8" E.O.S.3'-9 5/8" 0'-10 7/8" E.O.S.3'-9 5/8" PROVIDE ANGLES TO SUPPORT CURTAIN WALL JAMB. COORD. WITH ARCH. 7 1/2" E.O.S. SLAB OPENING (TYP.) SEE DETAILS. SEE ARCH. -DENOTES TOP OF STEEL ELEVATION WITH RESPECT TO DATUM ELEVATION -DENOTES THE NUMBER OF 3/4" DIA. x 5" (LONG) SHEAR STUDS. -DENOTES MOMENT CONNECTION SEE SHT. S-504 -DENOTES FRAMED OPENING. COORDINATE SIZE AND LOCATION w/ ARCH. & MECH. DRAWINGS -BEAM MOMENT SPLICE. SEE DETAILS. (+/-x'-xx") [X] LEGENDNOTES 1. DATUM ELEVATION = 100'-0" = F.F.E. 2. T.O. 4TH FLOOR STEEL ELEVATION = 143'-5 3/4" 3. D6 = COMPOSITE SLAB, 6 1/4" TOTAL THICKNESS LIGHTWEIGHT CONCRETE SLAB ON 3", 20 GA, GALVANIZED COMPOSITE METAL DECK -BASIS OF DESIGN: VULCRAFT 3.0VL. REINFORCE WITH 4 LBS/CY STRUX90/40 (GRACE) MACRO-FIBER REINFORCING. 4. BEAMS ARE EQUALLY SPACED UNLESS NOTED OTHERWISE. 5. PROVIDE A MINIMUM 1/4" BENT PLATE AT FLOOR PERIMETERS U.N.O. 6. "E.O.S." INDICATES EDGE OF COMPOSITE DECK. 7. BRACE FORCES SHOWN ARE ULTIMATE (FACTORED) LOADS. POSITIVE (+) FORCES INDICATE COMPRESSION, NEGATIVE (-) FORCES INDICATE TENSION. 8. COORDINATE ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. OPENINGS NOT INDICATED ON PLANS SHALL CONFORM TO TYPICAL DETAIL REQUIREMENTS. 9. PROVIDE (1)-3/4" DIA. X 5" (LONG) SHEAR STUD PER FOOT OF LENGTH U.N.O. 10. FOURTH FLOOR DESIGNED WITH ADDITIONAL DEAD LOAD ALLOWANCE TO SUPPORT FUTURE USE OF THIRD FLOOR. SEE S001. DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:51 PMS104 FOURTH FLOOR FRAMING PLAN 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"1 FOURTH FLOOR FRAMING PLAN REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5HSS14X6X5/8W21X44 W16X31 [15] W18X50W16X26 [15]W16X26 [15]W16X26 [15] W30X90 [39]W24X62W16X31 [15]W16X31 [15]W12X19 [7]W16X26 [15]W16X26 [15]W16X26 [15]W18X35 [17]W16X31 [15]W16X31 [9]W16X26 [15]W16X26 [15] D6 D6 D6 5.6 5.6 W16X31W10X12 W16X26 [15] A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.3 W10X121'-4" E.O.S.1'-4" E.O.S.1'-4" E.O.S. 1'-4"E.O.S.1'-4" E.O.S.HSS6X6X5/8 BRACE (+100K/-10K)HSS6X6X5/16 BRACE(+35K/-15K)HSS6X6X3/8 BRACE(+60K/-35K)HSS6X6X3/8 BRACE (+70K/-15K) HSS6X6X5/16 BRACE (+55K/-10K) 1 S503 1 S503 15 S503 15 S503 1 S503W16X31W12X19W12X30 W12X19 W12X30W12X19 W12X19 W12X19 W12X19 W12X30 W12X1912 K W18X50 12 K 45 K W18X76 [20] 45 K 32 K W18X65 19 KW16X31 [17]19 K71 K W24X62 [19] 76 K 27 KW18X35 [17]27 K507 K-FT 82 K W24X84 382 K-FT 74 K 22 KW16X31 [17]22 K88 K W24X62 [31] 81 K 25 KW16X31 [15]25 K73 K W24X55 [24] 73 K 91 K-FT20 KW14X38111 K-FT21 K66 K W21X55 [26] 57 K 32 K W18X35 [17] 20 K 2 0 K W 1 8 X 3 5 1 5 K 40 K W21X44 [20] 40 K11 K W16X45 11 KHSS14X6X5/825 KW16X26 [15]25 K28 KW18X35 [17]28 K12 KW16X31 [17]12 K27 KW18X35 [17]27 K27 KW18X35 [17]27 K31 KW18X35 [17]31 K26 KW18X35 [17]26 K29 KW18X35 [30]29 K24 KW16X31 [15]24 K24 KW16X31 [15]24 K24 KW16X31 [15]24 K18 KW16X31 [15]13 KW12X19 [4]W12X19 [11]25 KW16X31 [15]25 K23 KW16X31 [17]23 K33 KW24X8434 K48 KW30X9059 K14 KW16X3110 KW12X19 [9]W12X19 [9] W16X31 [13]W12X19 [6]21 KW16X26 [15]21 K24 K W21X44 28 K W 16X31 9 KW12X19 [13]10 KW12X19 [6]25 KW16X26 [15]25 KHSS18X6X1/2W16X31 W16X3127 KW18X35 [17]27 K24 KW16X31 [15]24 K26 KW16X31 [15]26 K18 KW16X26 [17]18 KW12X19 [6]W12X19 [7]23 KW16X26 [15]23 KHSS6X4X3/8?W16X3174 K W24X55 [25] 78 K W12X30 W12X30 W12X19 W12X19 W12X19 W12X19 W12X19W12X19W12X19W12X19W12X19W12X19W12X19 W12X19W12X19W12X19W12X19 W12X19 W12X19 W12X19W12X19 W12X30 W12X19W12X19W12X19W8X10 W8X10 23 K24 K24 K20 K17 K23 K24 K23 K20 K23 K24 K23 K23 K24 K24 K20 K18 K20 K27 K26 K25 K24 K17 K30 K30 K27 K26 K25 K24 K10" E.O.S.5" E.O.S.69 K53 K W12X30 HSS6X6X5/8W16X31 W16X31 HSS6X6X5/8W16X31 HSS4X4X5/16DOWN50 K-FTSUPPLEMENTARY STRUCUTRAL SUPPORT BELOW: UNISTRUT SYSTEM FOR MEDICAL EQUIPMENT SUPPORT BY OTHERS. COORDINATE WITH EQUIPMENT MNFR. COLD-FORMED EXTERIOR WALLS (SEE ARCH & NOTES) RADIAL STAIR BY OTHERS. PROVIDE HSS14X4X5/16 STAIR STRINGERS (MIN.) 4'-7" 4'-7" #4'S AT 16" O/C (SEE TYP DETAILS) #4'S AT 16" O/C (SEE TYP DETAILS)6" E.O.S.6" E.O .S .12'-0 1/4"6" E.O.S. PROVIDE COLD FORMED HEADERS AND HANGING WALLS AS REQUIRED TO SUPPORT FIRE-RATED GLAZING (SEE ARCH) 8 1/8" E.O.S.4 1/4" E.O.S.5'-1 7/8" +/-13'-2 3/4" +/-1'-3 7/8" +/- 1'-0" E.O.S.6" E.O.S.1 1/8" E.O.S.1'-5 7/8" E.O.S.7 1/8" E.O.S.1'-0" E.O.S.9" E.O.S.COORD. W/ ARCH12'-2"5'-3"5'-1 1/8"3'-6"6'-6 1/2"6'-7 1/2"6'-7 1/2"5'-9 3/4"5'-8"4" E.O.S.7 1/2" E.O.S. 1'-0" E.O.S. B.5 B.51'-6" E.O.S.15 S502 14 S502 14 S502 16 S502 HSS6X6X5/8 BRACE (+100K/-10K)HSS6X6X5/16 BRACE(+35K/-15K)HSS6X6X3/8 BRACE(+60K/-35K)HSS6X6X3/8 BRACE (+70K/-15K) HSS6X6X5/16 BRACE (+55K/-10K) N 3" E.O.S.5'-5 1/8"6'-7 1/2"6'-7 1/2"6'-7 1/2"6'-7 1/2"5'-1 3/4"0'-6 1/4"4'-7" 10" E.O.S.4'-7" PROVIDE ANGLES TO SUPPORT CURTAIN WALL JAMB. COORD. WITH ARCH. SLAB OPENING (TYP.) SEE DETAILS. SEE ARCH. -DENOTES TOP OF STEEL ELEVATION WITH RESPECT TO DATUM ELEVATION -DENOTES THE NUMBER OF 3/4" DIA. x 5" (LONG) SHEAR STUDS. -DENOTES MOMENT CONNECTION SEE SHT. S-504 -DENOTES FRAMED OPENING. COORDINATE SIZE AND LOCATION w/ ARCH. & MECH. DRAWINGS -BEAM MOMENT SPLICE. SEE DETAILS. (+/-x'-xx") [X] LEGENDNOTES 1. DATUM ELEVATION = 100'-0" = F.F.E. 2. T.O. 5TH FLOOR STEEL ELEVATION = 157'-5 3/4" 3. D6 = COMPOSITE SLAB, 6 1/4" TOTAL THICKNESS LIGHTWEIGHT CONCRETE SLAB ON 3", 20 GA, GALVANIZED COMPOSITE METAL DECK -BASIS OF DESIGN: VULCRAFT 3.0VL. REINFORCE WITH 4 LBS/CY STRUX90/40 (GRACE) MACRO-FIBER REINFORCING. 4. BEAMS ARE EQUALLY SPACED UNLESS NOTED OTHERWISE. 5. PROVIDE A MINIMUM 1/4" BENT PLATE AT FLOOR PERIMETERS U.N.O. 6. "E.O.S." INDICATES EDGE OF COMPOSITE DECK. 7. BRACE FORCES SHOWN ARE ULTIMATE (FACTORED) LOADS. POSITIVE (+) FORCES INDICATE COMPRESSION, NEGATIVE (-) FORCES INDICATE TENSION. 8. COORDINATE ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. OPENINGS NOT INDICATED ON PLANS SHALL CONFORM TO TYPICAL DETAIL REQUIREMENTS. 9. PROVIDE (1)-3/4" DIA. X 5" (LONG) SHEAR STUD PER FOOT OF LENGTH U.O.N. DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:46:56 PMS105 FIFTH FLOOR FRAMING PLAN 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"1 FIFTH FLOOR FRAMING PLAN REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 S D S D S DFFREF.RAPSD SD -DENOTES TOP OF STEEL ELEVATION WITH RESPECT TO DATUM ELEVATION -DENOTES THE NUMBER OF 3/4" DIA. x 5" (LONG) SHEAR STUDS. -DENOTES MOMENT CONNECTION SEE SHT. S-XXX -DENOTES FRAMED OPENING. COORDINATE SIZE AND LOCATION w/ ARCH. & MECH. DRAWINGS -BEAM MOMENT SPLICE CONNECTION. SEE DETAILS. (+/-x'-xx") [X] LEGENDNOTES 1. DATUM ELEVATION = 100'-0" = F.F.E. 2. T.O. ROOF STEEL ELEVATION = 172'-10 3/8" 3. T.O. PENTHOUSE STEEL ELEVATION = 182'-9" 4. D6 = COMPOSITE SLAB, 6 1/4" TOTAL THICKNESS LIGHTWEIGHT CONCRETE SLAB ON 3", 20 GA, GALVANIZED COMPOSITE METAL DECK -BASIS OF DESIGN: VULCRAFT 3.0VL. REINFORCE WITH 4 LBS/CY STRUX90/40 (GRACE) MACRO-FIBER REINFORCING. 5. PENTHOUSE ROOF DECK TO BE MIN. 1/2" WOOD STRUCTURAL SHEATHING PANEL. FASTEN AT 6" O.C., PERIMETER, 12" O.C. FIELD. SEE ARCH. 6. R1 = 1 1/2", 20 GA., TYPE B, GALVANIZED METAL ROOF DECK. MINIMUM 2-SPAN CONDITION. 7. PROVIDE A L3x3x1/4 EDGE-OF-DECK ANGLE OR 1/4" BENT-PLATE, EDGE-OF-DECK PLATE AT ROOF PERIMETERS U.N.O. COORDINATE OVERHANGS WITH ARCHITECTURAL DRAWINGS. 8. SEE S103 FOR LOW ROOF FRAMING. 9. MECHANICAL UNITS TO BE SUPPORTED OFF ROOF STRUCTURE WITH THERMALLY BROKEN STANCHION (BASIS OF DESIGN: THALER) OR AS SHOWN ON . /8 S504 A A B B C C D D 1 1 2 2 3 3 3.8 3.8 4 4 5 5 R1 R1 R1 S106 2 5.6 5.6 HATCHED REGION INDICATES ALLOWANCE FOR ADDITIONAL MECHANICAL LOAD OF 25PSF A.5 A.5 B.3 B.3 2.7 2.7 D.3 D.3 1/4" PER FOOT (UP) 1/4" PER FOOT (UP) 9 S504 9 S504 W8X4018 KW18X35W18X3512 KW21X4838 KW14X26W16X31W16X26W10X22W14X22W14X22W12X2220 KW18X4018 K20 KW18X4018 K19 KW18X4018 K16 KW18X3514 K17 KW21X4815 K18 KW16X40W18X35W18X35W18X35W18X35W14X26W14X2215 KW21X4813 K10 KW16X26W16X26W16X26W16X2611 KW21X4411 KW14X22W14X22W14X22W14X22W12X19W14X22W14X22W14X22W12X19W16X31W16X31W16X31W16X31W16X31W18X35W18X35W18X3539 KW21X6244 KW14X2610 KW14X2610 KW14X2610 K30 KW16X3115 KW14X22W14X22W14X22W14X22W14X22W12X22W14X22W12X19W12X19W14X22W12X22W14X22W8X13W6X9W10X12W16X31 W8X1312 KW18X3514 K14 K W16X26 14 K W10X12W12X14W8X13W8X24W8X24W8X24W14X22W14X22W14X22W8X13W8X13W8X13W8X13W14X26-0'-5 1/8"0'-2 5/8"0'-2 5/8"0'-10 1/4"0'-10 1/4 " 1 '-4 3/8" 1'-4 3/8"2'-2 1/4" -0'-5 1/8"0'-2 5/8"0'-2 5/8"0'-10 1/4"0'-10 1/4"1'-6 1/8"1'-6 1/8"2'-2 1/8"2'-2 1/8"2'-2 1/4"0'-0"0'-2 5/8"0'-2 5/8"0'-10 1/4"0'-10 1/4"1'-6 1/8"1'-6 1/8"2'-2 1/8"-0'-5 1/8"-0'-5 1/8"-0'-5 1/8"0'-2 5/8"0'-2 5/8"0'-10 1/4"0'-10 1/4"1'-6 1/8"1 '-7 3 /4 "2 '-2 "1'-6 1/8"2'-2 1/4"2'-2 1/4"2'-2 1/8"1'-4 3/8" W18X60W8X35 W24X62 W18X50 W24X68 W33X118W 1 8 X 4 0 W33X118W21X55W21X55W24X62W21X44 W33X118 W18X76 W24X55 W24X62 W24X62W30X99 W 2 1X44 W18X35 W24X76W12X53 LOWLOWLOW ELEVATOR HOIST BEAMS - COORDINATE LOCATIONS AND ELEVATIONS WITH ELEVATOR SUPPLIER 14 K14 K16 K14 K14 K16 K13 K16 K16 K16 K16 K14 K16 K16 K16 K14 K13 K13 K13 K13 K15 K11 K16 K16 K16 K14 K33 K13 K13 K13 K13 K15 K11 K38 K38 K 38 K84 K 43 K 44 K91 K 217 K-FT 63 K 398 K-FT 79 K 23 K-FT8 K31 K-FT6 K25 K-FT5 K11 K 15 K 43 K 41 K 18 K18 K 17 K 79 K 51 K 34 K 33 K77 K 48 K 36 K 35 K EQUIPMENT SUPPORT RAILS. SEE DETAILS. COORDINATE EXTENTS AND POSITION WITH MECH. PROVIDE ADDITIONAL INTERMEDIATE FRAMING AS REQUIRED BY UNITS. MIN. SIZE: GALV. L4X4X5/16. W8X13 W8X13 W8X13 4'-0" MAX.12'-0" MAX.ACCU, 750 LBS. (TYP., SEE MECH.) CU, 150 LBS. (TYP., SEE MECH.) DOAS, 3500 LBS. (SEE MECH.) DOAS, 3500 LBS. (SEE MECH.) DOAS, 3000 LBS. (SEE MECH.) ACCU, 750 LBS. (TYP., SEE MECH.) ROOF DRAIN. COORD. WITH MEP. ROOF DRAIN. COORD. WITH MEP. E.1 E.1 EQUIPMENT SUPPORT RAILS. SEE DETAILS. COORDINATE EXTENTS AND POSITION WITH MECH. PROVIDE ADDITIONAL INTERMEDIATE FRAMING AS REQUIRED BY UNITS. MIN. SIZE: GALV. L4X4X5/16. 9 S504 9 S504 2 0 K 1 8 K COLD-FORMED FRAMING TO CREATE PARAPET. SITE OR PREFAB ELEMENTS. SEE ARCH FOR FINAL PROFILE. MAX SPACING 24" O.C. COLD-FORMED FRAMING TO CREATE PARAPET. SITE OR PREFAB ELEMENTS. SEE ARCH FOR FINAL PROFILE. MAX SPACING 24" O.C. HSS6X6X5/16 (HIGH) HSS6X6X5/16 (HIGH) HSS6X6X5/16 (HIGH) HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH) HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)HSS6X6X5/16 (HIGH)4" SCHEDULE 40 POSTS. SEE DETAILS. (TYP.) 4" SCHEDULE 40 POSTS. SEE DETAILS. (TYP.)W27X841 S506 5'-8 1/8"4'-1 3/8" 5'-2" W16X31 W16X31 W14X26W14X261 0' - 0" MI N1 3 ' - 1 1 7 /8 "1 1 ' - 1 1 7 /8 "1 0' - 0" MI Nø 5 ' - 0 "ø 4' - 0"ø 2' - 0"2' - 0"2' - 0"2' - 0"2' - 0" 2' - 8" ± 3' - 0" ± VIF 2' - 0" ±VIF2' - 0" ±VIF2' - 0" ±10 S504 5'-3 5/8"5'-0"ROOF FRAMES AS REQUIRED FOR MECH EQUIP. B.5 B.5 PROVIDE (2) 3'X4' KNOCK OUT PANELS IN COLD- FORMED FRAMING AT ROOF LEVEL (SEE ARCH) T.O.S. = 173'-5 3/4" +/- (COORD. W/ STAIR MNF) 7 S506 7 S506 15 S502 SIM. 15 S502 SIM.7'-8 1/2"7'-8 1/2"8'-2"9" E.O.S.SLAB D6. COORD. WITH ARCH AND TYP. DETAILS B 1 B.3 600S162-54 AT 24" O/C 1 S506 7'-8 1/2"7'-8 1/2"8'-2"W12X26 W12X26 W12X26 W12X26 W12X19W12X19W12X19W12X19W12X19W12X19W12X26 W12X26 W12X26 W12X26 W12X19W12X19W12X19W8X21W8X21W8X21HSS6X6X5/8HSS6X6X5/8HSS6X6X5/8HSS6X6X5/8HSS6X6X5/8HSS6X6X5/8HSS6X6X5/8HSS6X6X5/8214 SF S600 STAIR 2 B.5 3/16" = 1'-0"1 ROOF FRAMING PLAN DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:08 PMS106 ROOF FRAMING PLAN 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"2 PENTHOUSE FRAMING PLAN REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 SUBBASE: SELECT STRUCTURAL FILL, MIXED #` AND #2 CRUSHED STONE. PROVIDE UNDERSLAB DRAIN PER GEOTECHNICAL REPORT. GEOTEXTILE FABRIC UNDERLAY (MIRAFI 500X OR EQUIVALENT) VAPOR BARRIER: 15 MIL CLASS A REINFORCING: W2.9XW2.9 6"X6" WWF OR 5 LBS/CY STRUX/90 (GRACE) OR FORTA- FERRO (FORTA) MACRO-FIBER REINFORCEMENT. SEE NOTE, LEFT. SAWCUT GROOVE JOINT (SJ): 1 1/4" X 1/8", FILL WITH EPOXY 1 3/4"5" 1'-0" MIN. CONSTRUCTION JOINTS (CJ) SAWN JOINT W/ EPOXY FILLER FIRST POUR LIGHTLY GREASE (BOND BREAKER) OR PROVIDE PLASTIC DOWEL SLEEVE 3/4" DIAMETER SMOOTH DOWEL, ASTM A36, 12" O/C SLAB FORM SECOND POUR SUBGRADE: SELECT IMPORTED STRUCTURAL FILL (COMPACTED AND PROOF- ROLLED) OR BEDROCK NOTE: AT THE CONTRACTOR'S OPTION - THE "DIAMOND DOWEL SYSTEM" BY PNA CONSTRUCTION TECHNOLOGIES MAY BE USED IN LIEU OF ROUND DOWELS. PROVIDE 1/4" x 4 1/2" x4 1/2" DOWELS AT 18" o.c. INSTALL IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. NOTE: TYPICAL AT ALL SLAB AND FOUNDATION RE- ENTRANT CORNERS RE-ENTRANT CORNER4'-0"RECTANGULAR SLAB OPENING (2) #4 BARS, 2 LAYERS WHEN T > = 8" 1/2" JOINT FILLER WITH SEALANT AT WALL OR OBSTRUCTION 2 " 2 "COORDINATEWITH ARCH.1 5 REFER TO PLAN FOR SLAB INFORMATION CONTRACTOR OPTION: CONSTRUCTION JOINT LOCATION SEE PLANTT#3 BAR, PROVIDE CORNER BARS D #3 X 36" AT 12" O/C WHEN "D" GREATER THAN 4"2"REFER TO SITE FOR SIDEWALK LOCATIONS AND DETAILS TOP OF SLAB SEE PLAN FOUNDATION WALL SEE PLAN #4's AT 12" O.C. MAX 36" 24" WALL BEYOND CONCRETE SLAB SEE PLAN FOR SLAB REINFORCEMENT (4) #4 BARS 3/4" DIA SMOOTH DOWEL X 18" AT 12" O/C, WITH PLASTIC DOWEL SLEEVE OR COAT 1/2 WITH BOND BREAK INSULATION, REFER TO ARCH. PROVIDE AT DOOR OPENINGS WITH THRESHOLD TJOINT FILLER WITH EPOXY SEALANT DOOR AND THRESHOLD REFER TO ARCHITECTURAL TOP OF SLAB SEE PLAN PROVIDE AT DOOR OPENINGS WITHOUT THRESHOLD TFILL WITH EPOXY SEALANT REFER TO OPENING WITH THRESHOLD FOR BALANCE OF REQUIREMENTS 1.5 X T1" BOX OUT TO CLEAR BASEPLATE (TYP.) EXTERIOR WF COLUMN, SIMILAR AT HSS COLUMN PIER ISOLATION JOINT BASEPLATE, GEOMETRY VARIES CONSTRUCTION JOINT OR CONTROL JOINT MAX. JOINT SPACING IN EITHER DIRECTION 10'-0", U.N.O. CONSTRUCTION OR CONTROL JOINT INTERIOR COLUMN PIER WF-COLUMN, SIMILAR AT HSS ISOLATION JOINT AROUND COLUMN WITH 1/2" EXPANSION MATERIAL AND SEALANT 2" MIN 2" M I N #5 AT12" O/C #5 AT12" VERT. EACH FACE #5 AT12" HORIZ. EACH FACE 12"12"12"6"6"8"SLAB PER PLAN0'-6"PROVIDE (2) CORNER BARS ELEVATOR SUMP PIT TYP. REINFORCING NOT SHOWN (VERIFY) 2'-0"SQ. #4 BARS AT 6" O/C EA WAY COORD. SUMP PIT SIZE AND LOCATION WITH ELEVATOR SUPPLIER #5 AT12" O/C DWL'S TO MATCH VERT. REINF. BY SIZE AND LOCATION WATERPROOFING (SEE ARCH) #5 CONT. COORD. W/ ELEVATOR CONTRACTOR TOP OF SLAB 2X4 KEYWAY 2X4 KEYWAY 0'-0" TOP OF SLAB SLAB PER PLAN #5 CONT. 8" CMU W/ #5 VERT'S AT 32" O/C. DRILL AND GROUT INTO CONCRETE WALL (EMBED 8")24"X24" #4 BAR AT 12" O/C POUR SLAB OVER WALL AT DOOR OPENINGS TYP FNDN WALL REINF AT INTERSECTION TYP FNDN WALL REINF AT SKEWED CORNERTYP FNDN WALL REINF AT CONSTRUCTION JOINT TYP FNDN WALL REINF AT CORNER AND END TYP FNDN WALL REINF AT INTERSECTION TYP FNDN WALL REINF AT SKEWED CORNERTYP FNDN WALL REINF AT CONSTRUCTION JOINT TYP FNDN WALL REINF AT CORNER AND END SEE PLAN FOR ANGLE SEE PLAN FOR ANGLE CONSTRUCTION JOINT -SEE GENERAL NOTES FOR SPACING WALL REINF PROVIDE CORNER BARS AS SHOWN. MATCH SIZE AND SPACING OF HORIZONTAL WALL REINFORCING. VERTICAL REINFORCING HORIZONTAL REINFORCING STANDARD HOOK CONTINUOUS KEY, 1/3 WALL THICKNESS DOWELS TO MATCH HORIZ. REINFORCEMENT SIZE AND SPACING OR HOOK HORIZ. BARSHORIZONTAL REINFORCING PROVIDE CORNER BARS AS SHOWN. MATCH SIZE & SPACING OF HORIZONTAL WALL REINFORCING. CONSTRUCTION JOINT WALL REINF "U"-BARS @ OPENINGS AND DISCONTINUOUS ENDS. MATCH SIZE AND SPACING OF HORIZ. WALL REINFORCING. LAP OUTSIDE HORIZONTAL BARS OR PROVIDE CORNER BARS AS SHOWN. MATCH SIZE AND SPACING OF HORIZONTAL WALL REINFORCING. VERTICAL REINFORCING SEE PLAN HORIZONTAL REINFORCING SEE PLAN STANDARD HOOK DOWELS TO MATCH HZ REINF SIZE AND SPACING OR HOOK HORIZONTAL BARS LAP OUTSIDE HZ BARS OR PROVIDE CORNER BARS AS SHOWN; MATCH SIZE AND SPACING OF HZ WALL REINF CONTINUOUS KEY, 1/3 WALL THICKNESS 2" CLEAR 2" VERTICAL REINFORCING 2" SMOOTH DOWELS: MATCH WALL REINF DIA, SLEEVE ONE END OR COAT WITH BOND BREAKER PER ACI LAP SPLICE T TTT TT TTTT T TPER ACILAP SPLICEP ER AC ILAP S PLIC E PER ACILAP SPLICEPER ACILAP SPLICEPER ACILAP SPLICEPROVIDE CONSTRUCTION JOINT WITHIN 3'-0" OF CORNER SMOOTH DOWELS: MATCH WALL BAR DIA; SLEEVE ONE END OR COAT WITH BOND BREAKER CONSTRUCTION JOINT PER ACI LAP SPLICE 0" (TYP)0" (TYP)CONSTRUCTION JOINT -SEE GENERAL NOTES FOR SPACING CONT. REINFORCING SEE FOUNDATION SECTION FOR SIZE AND NUMBER OF BARS.SLEEVED PIPE w/ 1 1/2" COMPRESSIBLE MATERIAL AROUND PIPE REFER TO PLAN AND SCHEDULES IF PIPE FALLS IN THESE LOCATIONS BACKFILL AND COMPACT TRENCH SEE SPEC. FOR COMPACTION REQUIREMENTS SEE DETAIL EXTEND FOOTING SEE DETAIL 5/S502 SEE DETAIL SLEEVE PIPE EXTEND FOOTING: SLEEVE PIPE & CAST FOOTING TO BOTTOM OF TRENCH DEPRESS FOOTING AND SLEEVE PIPE SLEEVE PIPE (4) #4 BARS x 4'-0" LONG, DIAGONALLY PLACED. PROVIDE ONE LAYER EACH FACE FOR WALL >/=8" THICK LINK-SEAL OR APPROVED EQUIVALENT. COORDINATE w/MECHANICAL DWGS. INSTALL PER MANUFACTURER'S INSTRUCTIONS, FOR OPENINGS > OR EQUAL TO 8" FOUNDATION WALL CORE HOLE AS REQUIRED (LESS THAN 12"). DO NOT CUT THROUGH REINFORCEMENT. GROUT HOLE WITH NON-SHRINK, NON-METALLIC GROUT (5 STAR OR EQUAL) TO FORM A WATERTIGHT CONDITION. SLEEVE OPENING GREATER THAN OR EQUAL TO 8" SCHED. 40, GALV. OR APPROVED EQUAL PIPE PENETRATION DETAILS AT CONTINUOUS WALL FOOTINGS EXTEND FOOTING SECTION ELEVATION 0'-6"TD SLEEVE DIA 1.5 X W0'-2"WT COLD JOINT SLEEVE PIPE 1.5 X W6" MIN 6" MINTOP OF FOOTING 3" MINCOVERUSE THIS DETAIL TO: 1. CHANGE FOOTING ELEVATION 2. LOWER FOOTING TO FIRM BEARING 3. AVOID PIPE PASSING THROUGH FOOTING 1'-6" MAXSEE PLANSLEEVE PIPE w/ 1 1/2" COMPRESSIBLE MATERIAL AROUND PIPE CONT. REINFORCING (SEE FOUNDATION SECTION FOR SIZE AND NUMBER OF BARS) 6" MIN 3" MIN 1.5 X A ATTT MI NP E R A C IL A P S P L IC E (2)-#4's CONT. SLAB-ON-GRADE REFER TO PLAN 1 1 2'-0"1'-0"TCOLD FORMED WALL, SEE NOTES CONT. TRACK AT BOTTOM DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:09 PMS500 DETAILS AND SECTIONS 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/4" = 1'-0"1 SLAB ON GRADE 3/4" = 1'-0"2 RE-ENTRANT CORNER 3/4" = 1'-0"3 DEPRESSED SLAB 3/4" = 1'-0"4 SLAB POUR OUT 3/4" = 1'-0"5 ISOLATION JOINT 3/4" = 1'-0"6 SECTION AT ELEVATOR 3/4" = 1'-0"9 FOUNDATION WALL JUNCTIONS 3/4" = 1'-0"10 PIPE PENETRATION 3/4" = 1'-0"8 STEP FOOTING - CONCRETE WALL 3/4" = 1'-0"7 THICKENED SLAB REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 F.F.E. = SEE PLAN PIER = SEE PLAN -8" BELOW FFE UNO FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING APPROVED BEARING GRADE REFER TO PIER SCHEDULE FOR PIER SIZE AND REINFORCING COLUMN (SEE PLAN.) INFILL w/ CONCRETE BASE PLATE AND ANCHOR RODS REF SCHEDULE 1/2 " ISOLATION JOINT WITH EPOXY SEALANT (TYP) CONCRETE SLAB (TYP) REFER TO PLAN TOF = SEE PLAN 2"(3) SPA AT 2" #3 TIES AT 12" O/C EQ UNO EQ UNOREF PLANT3" CLR3" CLR GL COLD FORMED METAL STUDS (SEE ARCH.) FIRST FLOOR EL. (+) 0'-0" FOOTING EL. REFER TO PLAN SLAB ON GRADE (SEE PLAN.) BRICK (SEE ARCH.) #5 CONT. AT TOP OF WALL 3'-0" MIN. (SEE PLAN)1'-0"CAST IN PLACE FOUNDATION WALL CONT. FOOTING (2)-#5 CONT. PERIMETER DRAIN SYSTEM, COORD. W/ SITE PLAN REINFORCING (SEE SCHEDULE) INSULATION, SEE ARCH. GL 1'-3"2'-8"8"7" 1'-3" GL "SIM." 10" AT "SIM." OCCURS AT COL. LINES 3.9 AND E ONLY. F.F.E. = SEE PLAN FOOTING, SEE SCHEDULE FOR SIZE AND REINFORCING APPROVED BEARING GRADE CONCRETE SLAB (TYP.) REFER TO PLAN 1/2 " ISOLATION JOINT WITH EPOXY SEALANT (TYP) INFILL w/ CONCRETE AFTER SLAB IS CURED BASE PL. AND ANCHOR BOLTS (SEE DETAILS.) COLUMN (SEE PLAN.) B.O.F. = SEE PLAN TGL ROUND CAST-IN-PLACE PIER (SEE SCHEDULE) C.I.P. FOOTING (SEE SCHEDULE) DOWELS TO MATCH VERTS. GALV. BASEPLATE COLUMN (SEE PLAN) (4) 3/4" DIA. GALV. ANCHOR BOLTS 1'-6"1'-6"T.O.F. SEE PLAN T.O. PIER +2'-0" 5/16 (3) SPA. AT 2" #3 TIES AT 12" O/C 8"3"3"W10: 1-1/4"X16" DIA. BASE PLATE HSS: 3/4"X14" DIA. BASE PLATE LEVELING PL. AND GROUT PAD GL BP-1 BP-9/9A CJP1'-6"1'-6" 9/16 (4) 3/4" ANCHOR RODS 2'-5"2'-5" 6 1/2"6 1/2"2 1/2"2 1/2" 2 1/2"2 1/2"4"4"BP-1 GL GL GL GL 2'-4" 19"9"1'-6"BP-2 GL GL 1'-6" 9"9"1'-6"6 1/2"11 1/2"BP-3/3A THICKNESS = 2 1/4"THICKNESS = 2 1/4" THICKNESS AT BP-3 = 1" THICKNESS AT BP-3A = 1 1/2" GL GL 1'-4" 8"8"1'-4"6 1/2"9 1/2"BP-4/4A THICKNESS AT 4 = 3/4" THICKNESS AT 4A = 1 1/4"11 1/2"6 1/2"2" TYP. BP-5 THICKNESS = 2 1/4" GL GL 2'-4" 19"9"1'-6"6 1/2"11 1/2"2" TYP. BP-6 THICKNESS = 2 1/4"2'-5"2'-5" 6 1/2"6 1/2"2 1/2"2 1/2" 2 1/2"2 1/2"4"4"GL GL GL GL 2'-7" 22"9"1'-6"BP-7 THICKNESS = 2 1/4"11 1/2"6 1/2"2" TYP. BP-8 THICKNESS = 2 1/4" GL GL 2'-7" 22"9"1'-6"11 1/2"6 1/2"2" TYP. THICKNESS AT BP-9 = 1 1/2" THICKNESS AT BP-9A = 2" (12)-1 1/4" ANCHOR RODS, EMBED FULL DEPTH (SEE D/1 PIER DETAIL) 1/2" GUSSET PLATE (TYP) 3"x7" SHEAR LUG 12" LONG, EA. WAY TYP 6" (4)-3/4" ANCHOR RODS 2 1/4"x7 1/2" SHEAR LUG 16" LONG 1/2" GUSSET PLATE (4)-3/4" ANCHOR RODS CJP 1/4 (4)-3/4" ANCHOR RODS 1/4 CJP (4)-3/4" ANCHOR RODS 2 1/4"x7 1/2" SHEAR LUG 16" LONG 1/2" GUSSET PLATE (4)-1 1/4" ANCHOR RODS. EMBED FULL DEPTH (SEE PIER DETAIL) 1/2" GUSSET PLATE (TYP) 3"x7" SHEAR LUG 12" LONG, EA. WAY CJP (4)-3/4" ANCHOR RODS 2 1/4"x7 1/2" SHEAR LUG 16" LONG, EA. WAY 1/2" GUSSET PLATE (4)-3/4" ANCHOR RODS 2 1/4"x7 1/2" SHEAR LUG 16" LONG, EA. WAY 1/2" GUSSET PLATE CJP CJP 2" TYP CJP GL 2'-6" 10"20"1'-8"BP-10 THICKNESS = 2 1/4"10"10"(4)-3/4" ANCHOR RODS 2 1/4"x7 1/2" SHEAR LUG 16" LONG, EA. WAY 1/2" GUSSET PLATE GL 2" TYP BP-11 HSS 4X4 POST BASE THICKNESS = 5/8" INSTALL ALIGNED WITH CENTER OF CFMF WALL RUNNER TRACK 8" 3"10"5" TOP OF CONCRETE FOUND. WALL (2) 5/8" DIA. X 6" LONG HEAVY DUTY SCREW ANCHORS. ANCHOR RODS PLATE WASHER SIZE AND BASE PLATE HOLE DIAMETER SCHEDULE ANCHOR BOLT SEE SCHEDULE FOR SIZE 1/4" LEVELING PLATE -MATCH BASE PL. SIZE (OMIT AT BASE PLATES WITH SHEAR LUGS) FINISH END OF COLUMN AND BASE PLATE SURFACE ACCORDING TO AISC 360 M2.4 AND M4.4 REQUIREMENTS 3/4" NON-SHRINK GROUT - SEE SPECIFICATIONS BASE PLATE EMBEDMENT UNOA36 WASHER PLATE - (TYP.) WELD TO BASE PLATE NOTES: 1. PLATE WASHERS: ASTM A36, ROUND OR SQUARE 2. WELD WASHERS TO BASE PLATES WITH MIN FILLET WELD. 3. INCREASE EDGE DISTANCE FOR WASHER PLATE SIZE GREATER THAN 3 1/2" FOR WELD. 4. DIA WASHER PLATE HOLE = DIA ANCHOR ROD + 1/16" ANCHOR ROD DIAMETER MAXIMUM HOLE DIAMETER WASHER PLATE ROUND/SQUARE MINIMUM WASHER THICKNESS WASHER PLATE REFER TO TABLE BASE PLATE3/4" DIA...............1-1/4" DIA..................= 16"= FULL DEPTHWASHER PLATE DETAIL BASE PLATE HOLE DIA REFER TO TABLE 1/4" MIN(TYP)1-1/4"3"1/2"2-1/16" 3/4"2"1/4"1-5/16" DOUBLE NUT OR TACK WELD AT COLUMNS WITH SHEAR LUGS PROVIDE LEVELING NUT. NOTE THAT ADDITIONAL GROUT WILL BE REQUIRED. SEE DETAILS. GL 10'-6" 9'-0" 7'-6" 6'-6" 5'-6" 4'-6" 4" WALL 8" WALL WALL TYPES L3 1/2x 3 1/2x 5/16 (LLV) TYPICAL LINTEL SCHEDULE L4x 3 1/2x 5/16 (LLV) L5x 3 1/2x 5/16 (LLV) L6x 3 1/2x 5/16 (LLV) (2) - L3 1/2x 3 1/2x 5/16 (LLV) (2) - L4x 3 1/2x 5/16 (LLV) (2) - L5x 3 1/2x 5/16 (LLV) (2) - L6x 3 1/2x 5/16 (LLV) W8x10 + PL. 5/16"x 7 1/2" W8x15 + PL. 5/16"x 7 1/2" NOTES: MAXIMUM MASONRY OPENING 9) ALL COMPONENT PARTS OF EXTERIOR LINTELS SHALL BE HOT-DIP GALVANIZED AND PAINTED. 1) UNLESS OTHERWISE SPECIFIED ON THE DRAWINGS, PROVIDE LINTELS FOR EXTERIOR MASONRY OPENINGS IN ACCORDANCE WITH THE SCHEDULE ABOVE. 2) PROVIDE 8" MIN. BEARING EACH END ONTO SOLID GROUTED CMU. 3) BLOCK WALLS SHALL BE GROUTED SOLID 3 COURSES BELOW BEARING x 24" LONG, MINIMUM. PROVIDE REINFORCING EACH SIDE OF DOOR OPENINGS AND GROUT FULL HEIGHT. REFER TO TYPICAL MASONRY WALL ELEVATION. 4) SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF MASONRY OPENINGS NOT SHOWN. 5) ALL WF LINTELS SHALL HAVE 1/2" DIA. x 6" LONG STUD ANCHORS WELDED TO THEIR TOP FLANGE @ 16" O.C. WALL REINFORCING SHALL BE WELDED TO LINTEL AT SPACING INDICATED. GROUT REINFORCED CELLS. 6) INSTALL ANGLES WITH LONG LEG VERTICAL. 7)SEE DETAILS FOR OPENINGS GREATER THAN SHOWN. 8) FOLLOW B.I.A. RECOMMENDATIONS WHERE LINTELS INTERSECT VERTICAL RELIEF JOINTS. FIRST FLOOR EL. (+) 0'-0" FOOTING EL. REFER TO PLAN3'-0" MIN. (SEE PLAN)GL SEE 1/S501 FOR ADDITIONAL INFORMATION 2'-1" AT "SIM." 1'-3" TYP.2'-8"CONCRETE FOOTING (SEE SCHEDULE) CONCRETE PIER (SEE SCHEDULE) (3) SPA AT 2" BASE PLATE (SEE BASE PLATE DETAILS) STEEL COLUMN (SEE PLAN) 1/2 " ISOLATION JOINT WITH EPOXY SEALANT (TYP) INFILL WITH CONCRETE AFTER SLAB CURES 0'-8"INSIDE FACE OF WALL STUDS ALIGNS WITH GRIDLINE (SEE PLAN). EXCEPT AT "SIM" - INSIDE FACE OF STUD IS 10" FROM GRIDLINE. 1'-2 1/2"1'-6 1/2"1 3 1 /2 "8"3/8 1'-8 3/4"1'-4 3/4"8 "3/8 1/2" MIN. GUSSET PLATE 1/2" MIN. GUSSET PLATE BEAM FLANGE CONNECTION BEAM WEB CONNECTION BASE PLATE AND ANCHOR RODS (SEE BASE PLATE DETAILS) BASE PLATE AND ANCHOR RODS (SEE BASE PLATE DETAILS) FIRST FLOOR EL. (+) 0'-0" FOOTING EL. REFER TO PLAN3'-0" MIN. (SEE PLAN)GL SEE 1/S501 FOR ADDITIONAL INFORMATION 1'-3"2'-8"#4 TIES AT 4" O/C EXTEND ALL ANCHOR RODS TO BOTTOM LAYER OF FOOTING REINFORCMENT (EMBEDMENT = 8'-9") BASE PLATE (SEE BASE PLATE DETAILS) STEEL COLUMN (SEE PLAN) 1/2 " ISOLATION JOINT WITH EPOXY SEALANT (TYP) INFILL WITH CONCRETE AFTER SLAB CURES 1'-0"TOP OF PIER CONCRETE FOOTING (SEE SCHEDULE) 0'-7" 3'-0"X3'-0" CONCRETE PIER INSIDE FACE OF WALL STUDS ALIGNS WITH GRIDLINE (SEE PLAN). BASE PLATE W/ SHEAR LUGS (SEE BASE PLATE DETAILS)2"PROVIDE LEVELING NUTS AT ALL SHEAR LUG BASE PLATES BOX OUT TOP OF PIERS TO ALLOW FOR INSTALLATION OF SHEAR LUGS. GROUT AREA SOLID WITH NON-SHRINK GROUT FIRST FLOOR EL. (+) 0'-0" TOP OF PIER 1'-0"CONCRETE PIER (SEE SCHEDULE) *REINFORCING NOT SHOWN FOR CLARITY* 9/16 FOOTING EL. REFER TO PLAN CONCRETE FOOTING (SEE PLAN) DOWELS TO MATCH VERTS 8" CMU W/ #5 BARS AT 32" O/C (GROUT SOLID)STRUCTURAL FILL (SEE NOTES) STRUCTURAL FILL (SEE NOTES) 5" SLAB-ON-GRADE W/ #4 BARS AT 12" O/C (TOP) AND 6" O/C (BOT) #4 DOWELS AT 32" O/C 24" 24" CHAMFER EXPOSED SLAB CORNERS DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:12 PMS501 DETAILS AND SECTIONS 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/4" = 1'-0"3 INTERIOR FOOTING WITH PIER 3/4" = 1'-0"1 FOUNDATION WALL W/ BRICK 3/4" = 1'-0"4 INTERIOR COLUMN FOOTING 3/4" = 1'-0"5 EXTERIOR FOOTING WITH PIER 3/4" = 1'-0"8 BASE PLATE DETAILS 3/4" = 1'-0"6 BASE PLATE ANCHOR BOLTS 12" = 1'-0"7 LOOSE LINTEL SCHEDULES 3/4" = 1'-0"2 COLUMN PIER W/ BRICK 3/4" = 1'-0"9 TYPCIAL GUSSET PLATE DETAILS 3/4" = 1'-0"11 PIERS AT D/1 AND A/1 3/4" = 1'-0"10 TYPCIAL SHEAR LUG DETAILS 3/4" = 1'-0"12 CMU STAIR LANDING REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 BLOCK & STRAP FOR WALL STUDS CONTINUOUS STRAP EACH SIDE FASTEN AT EACH INTERSECTION w/ (1)-#10-16 SCREW. FASTEN AT EACH BLOCK with (3)-#10-16 SCREWS USE (2)-TRACKS SOLID BLOCKS AT 8'-0"C-C BETWEEN STRAPS, CUT FLANGES & BEND WEB TO FORM A 4" OVERLAP. USE (2)-#10-16 SCREWS, EACH SIDE PROVIDE BRIDGING AT 48" O/C 6"x11/4 54 MIL x 6"Lg. RUNNER TRACK, SCREW ATTACHED TO FULL HEIGHT STUD w/ (6)-#10-16 SCREWS & TO HEADER w/ (3)-#10-16 SCREWS EACH FLANGE FULL HEIGHT JAMB STUDS SEE ELEVATION FOR MEMBER SIZE & QUANTITY (JACK STUDS NOT SHOWN) (2)-UNPUNCHED STUDS SEE ELEVATION FOR MEMBER SIZES (1)-#10-16 SCREW TYP. EACH FLANGE (2)-2"x2"x16ga. CLIP ANGLES, ONE TOP & BOTTOM OF HEADER.1/2" LESS THAN STUD WIDTH, USE: (3)-#10-16 SCREWS ON EACH LEG AS SHOWN ABOVE. CRIPPLE STUDS ATTACH TOP & BOTTOM TRACK USING: (2)-#10-16 SCREWS AT 16"O.C. (2)-2"x2"x54 MIL. CLIP ANGLES, ONE TOP & BOTTOM OF HEADER. 1/2" LESS THAN STUD WIDTH, USE: (3)-#10-16 SCREWS ON EACH LEG AS SHOWN ABOVE. CRIPPLE STUDS JACK STUD(S) 1/2" 1/2" EQUIVALENT HEADER ATTACHMENT 1"1" 1 /2 "1 /2 " E Q U IV A L E N T 1 "1 "ALTERNATE BOX HEADER CONNECTION 6"x1 1/4 54 MIL x 6"Lg. RUNNER TRACK, SCREW ATTACHED TO FULL HEIGHT STUD WITH (6)-#10-16 SCREWS & TO HEADER WITH (3)-# 10-16 SCREWS EACH FLANGE FULL HEIGHT JAMB STUDS SEE ELEVATION FOR MEMBER SIZE & QUANTITY (2)-UNPUNCHED STUDS SEE ELEVATION FOR MEMBER SIZES (1)-#10-16 SCREW TYP. EACH FLANGE (2)-2"x2"x54 MIL. CLIP ANGLES, ONE TOP & BOTTOM OF HEADER. 1/2" LESS THAN STUD WIDTH, USE: (3)-#10-16 SCREWS ON EACH LEG AS SHOWN ABOVE. CRIPPLE STUDS ATTACH TOP & BOTTOM TRACK USING: (2)-#10-16 SCREWS AT 16"O.C.. 1/2" 1" 1/2" EQUIVALENT 1" HEADER ATTACHMENT POST BUILT-UP WITH TRACK EACH SIDE TRACK TRACK RUNNER ATTACH EACH SIDE STUD NOTE: FASTEN BUILT-UP MEMBERS TOGETHER AT 12" O.C. Max. (2)-JAMB ANCHORAGE TO STRUCTURAL WITH STUD STIFFENER 1"3"3"ATTACH TO SLAB USING: (4)-0.143" DIA. P.D.F.'s w/ 1 1/4" Min. EMBED., LOCATED AS SHOWN IN DETAILS SEE DETAILS FOR JAMB ASSEMBLY METHOD. TRACK RUNNER 6" Lg. SECTION OF STUD TO STIFFEN TRACK. USE (2)-#10-16 SCREWS ON BOTH SIDES. (1)-#10-16 SCREW AT EACH FLANGE TOPVIE W TOP VIEW O P E N IN G Min.SPACING(OPTION #1) JAMB STUDS WITH TRACK BLOCKS (OPTION #2) BACK TO BACK JAMB STUDS WITH TRACK COVER 68 MIL STUDS AT JOIST OR BEAM BEARING HEADERS, 54 MIL STUDS AT BEARING WALLS (U.N.O.), MATCH WALL STUDS OTHERWISE PROVIDE OPTION #2 AT JOIST OR BEAM BEARING HEADER LOCATIONS. PROVIDE 54-MIL TRACK AND FASTENERS FOR 100% COMPOSITE PROPERTIES PER NAS-2012 (2)-JAMB STUDS ATTACH JAMB MEMBERS USING 6" SECTION OF RUNNER TRACK, Min. USE (8)-#10-16 SCREWS AS SHOWN 24" O.C. Max.ATTACH JAMB STUD TO TRACK (NOT SHOWN) WITH (2)-# 10-16 SCREWS AT 16"O.C. (2)-JAMB STUDS CAP JAMB w/ TRACK FOR WINDOW ATTACHMENT. EXTEND 6" ABOVE HEADER AND 6" BELOW SILL CONN. PARTIAL-HEIGHT WALL BASE CONNECTION DIETRICH EASY CLIP T975 W/ 1/2" DIA. HILTI KWIK BOLT ANCHOR (TYP. AT SLAB ON GRADE) OR 1/2" DIA. THRU-BOLT AT ELEVATED SLAB SIMPSON H10 TIE-DOWN ANCHOR WITH 1/2" HILTI KWIK BOLT (SLAB ON GRADE) OR 1/2" THRU- BOLT (ELVATED SLAB) AT KNEE WALL ENDS 600S200-54 STUDS AT 16" O/C MAX, SEE PLAN FOR STUD DEPTH 600T200-68 TRACK TOP AND BOTTOM CONCRETE SLAB REFER TO PLAN DOUBLE STUD AT KNEE WALL END (2) BAYS OF SOLID BLOCKING AT 8' O.C. (VERT.) MAX. AT EACH END OF WALL TYPICAL STUDS. SEE SCHEDULE. SLIP TRACK (43 MIL MIN.), WIDTH AS REQUIRED W/ 3" MIN. LEGS (2) POWER ACTUATED FASTENERS TO DECK ABOVE AT EACH STUD BRIDGING PER DETAIL 1/S502 WITHIN 12" OF TOP OF STUD "1 1/2" MAX. BLOCKING END CONNECTION PER1/S500.2 NOTES: ALTERNATE 1 - PROVIDE CLARKDIETRICH MAXTRACK NON- STRUCTURAL 2 1/2" LEG SYSTEM OR EQUIVALENT. FASTEN TO DECK AS SHOWN. ALTERNATE 2 -PROVIDE CLARKDIETRICH FAST TOP CLIP (OR EQUIVALENT) AT EACH STUD IN LIEU OF SLIP TRACK. 12ga FRAMING ANGLE MIN. (3) POWDER ACTUATED FASTENERS (SEE NOTES) BRACES AT 48" o.c. (3) #12 SELF DRILLING SCREWS EACH END NON-BEARING WALL STUDS. SEE SCHEDULE. SEE ARCH. EX. SLAB ON DECK. (ORIENTATION VARIES) CEILING LINE SEE ARCH.+/ - 45°12ga FRAMING ANGLE MIN. (3) POWDER ACTUATED FASTENERS (SEE NOTES) BRACES AT 48" o.c. (3) #12 SELF DRILLING SCREWS EACH END NON-BEARING WALL STUDS. SEE SCHEDULE. SEE ARCH. EX. SLAB ON DECK. (ORIENTATION VARIES) CEILING LINE SEE ARCH.+/- 45°12ga FRAMING ANGLE ANCHORED TO TOP TRACK WITH (3) #12 SELF DRILLING SCREWS. FASTENER/CONNECTOR SCHEDULE SCREWS CONNECTOR METAL TRACK STUD-TO-STUD WOOD FRAMING or PLYWOOD SUBSTRATE #10-16 x 5/8" PAN HEAD DESCRIPTION BUILDEX "TEKS" COMPASS "DARTS" GRABBER SELF-DRILLING PRODUCT #10-16 x 5/8" HEX HEAD BUILDEX "TEKS" COMPASS "DARTS" GRABBER SELF-DRILLING METAL-TO- STRUCTURAL STEEL #12-24 x 11/4" HEX HEAD, #5 TIP BUILDEX "TEKS" HILTI KWIK-PRO #14-20 x 2 3/4" PHILLIPS FLAT HEAD, #4 WINGS BUILDEX "TEKS" HILTI KWIK-PRO CONCRETE or GROUTED C.M.U. P.D.F.'s (Powder Driven Fasteners)STRUCTURAL STEEL 0.143" DIA. (Min. Shank) 11/4" Embedment POWERS .300 HEAD DRIVE PAN HILTI 0.145" DIA. X-DNI 0.143" DIA. (Min. Shank) 5/8" (Min. Length) POWERS .300 HEAD DRIVE PAN HILTI X-DNI ** PRODUCTS BY OTHER MANUFACTURERS MAY BE ACCEPTABLE, PLEASE CONTACT OUR OFFICE OR SUBMIT PRODUCT DATA. COLD FORMED STUDS, BEYOND (SEE ARCH.) CL STEEL BEAM, SEE PLAN T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) MC6X18 EACH END OF WINDOW OPENING. PROVIDE VERT. SLIP CONN. TO BEAM. HSS6X4X1/2. MAY BE BROKEN BACK AT ANGLED STOREFRONT. THERMAL BREAK MATERIAL AT EACH CONNECTION (BASIS OF DESIGN: FABREEKA TIM) 3/4" A325 BOLTS AT 4'-0" O.C. MAX. GALV. L8X8X1/2 LINTEL, 1/2" SHORTER THAN OPENING, EA. END. ANCHOR MC6'S TO SLAB WITH (2) 3/8"X 5" HEAVY DUTY SCREW ANCHORS WITHIN CONT. BOTTOM TRACK. PROVIDE 1/2" THICK BASEPLATE. 1 1/2" MIN. PROVIDE BLOCKING AROUND OPENING PER ARCH. L3X3X1/4 KICKER TO SLAB AT EACH MC6 AND AT VERTEX IN HSS T.O. SLAB (SEE PLAN) NOTE: DETAIL APPLIES AT BRICK MASONRY OPENINGS GREATER THAN 7'-6", OR WHERE THE WALL CHANGES DIRECTION WITHIN THE OPENING. WT6X8 AT 4'-0" O.C. CL STEEL BEAM, SEE PLAN T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) (2) 3/4" A325 BOLTS AT EACH WT PROVIDE BLOCKING AROUND OPENING PER ARCH. (NOT SHOWN) L3X3X1/4 KICKER TO SLAB AT EACH WT NOTE: DETAIL APPLIES AT BRICK MASONRY OPENINGS GREATER THAN 7'-6", OR WHERE THE WALL CHANGES DIRECTION WITHIN THE OPENING. GALV. L8X8X1/2 LINTEL, 1/2" SHORTER THAN OPENING, EA. END. THERMAL BREAK MATERIAL AT EACH CONNECTION (BASIS OF DESIGN: FABREEKA TIM) SHEATHING -COORD. WITH ARCH. T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) CL SEE PLAN E.O.S. FIRE CAULK GAP (SEE ARCH) CONCRETE SLAB ON METAL DECK (SEE PLAN) SLAB EDGE REINFORCING (SEE SLAB EDGE DETAIL) 8" CMU W/ #5 BARS AT 48" O/C, DRILL AND GROUT INTO SLAB (EMBED 5") 8" CMU W/ #5 BARS AT 48" O/C STEEL BEAM (SEE PLAN) T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) CL SEE PLAN E.O.S. CONCRETE SLAB ON METAL DECK (SEE PLAN) SLAB EDGE REINFORCING (SEE SLAB EDGE DETAIL) STEEL BEAM (SEE PLAN) FIRE CAULK GAP (SEE ARCH) STEEL TO BE COATED IN INTUMESCENT PAINT. REFER TO ARCH FOR FIRE RATING REQUIREMENTS AND DETAILS 8" CMU W/ #5 BARS AT 48" O/C, DRILL AND GROUT INTO SLAB (EMBED 5") 8" CMU W/ #5 BARS AT 48" O/C T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) CL SEE PLAN E.O.S. SEE 14/S502 FOR ADDITIONAL INFORMATION FIRE CAULK GAP (SEE ARCH) SHAFT WALL (SEE ARCH) STEEL BEAM (SEE PLAN) 8" CMU W/ #5 BARS AT 48" O/C (WELD TO TOP OF BEAM) 3/8" CLOSURE PLATE CL DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:12 PMS502 DETAILS AND SECTIONS 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/4" = 1'-0"1 BRIDGING DETAILS 3/4" = 1'-0"2 HEADER AND JAMB STUD 3/4" = 1'-0"3 BOX HEADER CONN. - ALT 3/4" = 1'-0"4 BUILT-UP POST 3/4" = 1'-0"5 DOOR JAMB ANCHORAGE 3/4" = 1'-0"6 TIED JAMB STUD 3/4" = 1'-0"7 KNEE WALL BASE CONNECTION 3/4" = 1'-0"8 TOP OF WALL - FULL HEIGHT PARTITION 3/4" = 1'-0"9 TOP OF CFMF WALL - ABOVE CEILING 3/4" = 1'-0"10 TOP OF CFMF WALL - BELOW CEILING 3/4" = 1'-0"11 FASTENER AND CONNECTOR SCHEDULE 3/4" = 1'-0"12 LONG SPAN OR BENT LINTEL 3/4" = 1'-0"13 LONG SPAN OR BENT LINTEL - HIGH WINDOW 3/4" = 1'-0"14 ELEVATOR SHAFT 1 3/4" = 1'-0"15 ELEVATOR SHAFT 2 3/4" = 1'-0"16 ELEVATOR SHAFT 3 REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 ACOLD FORMED STUDS (SEE ARCH.) SLAB EDGE (SEE DETAILS.) SHEAR STUDS (SEE PLAN.) CL SEE PLAN E.O.S. STEEL BEAM (SEE PLAN.) 6-1/4" COMPOSITE SLAB (SEE PLAN.) T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) DECK DIRECTION VARIES AT "SIM". SLIP CONNECTION AT EACH STUD PROVIDE CURTAIN WALL ATTACHMENTS AS REQUIRED. (BY OTHERS, U.N.O.) POURSTOP SCHEDULE (t </= 7") 0" - 5" 1/4" BENT PL. 12 GA. 14 GA. 16 GA. 5" - 7" 7" - 9" 9" - 14" 14" - 17" 5/16" BENT PL. " L " POURSTOP GAGE FOR DIM. "L" -SEE SCHEDULE BELOW FOR DIM. "L" -SEE SCHEDULE BELOW #3 BARS, 3'-0" EXT., WITH STANDARD HOOKS, AT16" O.C. (REQUIRED WHERE "L" IS GREATER THAN 4"). #3 BARS x 3'-0" EXT., w/ STANDARD HOOKS, @ 9" O.C. (REQUIRED WHERE "L" IS GREATER THAN 12") CONCRETE SLAB METAL DECK WIDE FLANGE BEAM SEE PLAN FOR SIZE POUR STOP -SEE SCHEDULE BELOW #3 BARS, 3'-0" EXT., WITH STANDARD HOOKS, @ 16" O.C. (REQUIRED WHERE "L" IS GREATER THAN 4"). #3 BARS x 3'-0" EXT., w/ STANDARD HOOKS, @ 9" O.C. (REQUIRED WHERE "L" IS GREATER THAN 12") CONCRETE SLAB METAL DECK WIDE FLANGE BEAM SEE PLAN FOR SIZE CELL CLOSURE AND POUR STOP DECK PARALLEL TO SLAB EDGE DECK PERPENDICULAR TO SLAB EDGE NOTE: NOTE: "L" IS TYPICALLY 1" FOR INTERIOR MECHANICAL SHAFTS (UNLESS NOTED OTHERWISE ON PLAN) NOTE: "L" IS TYPICALLY 1" FOR INTERIOR MECHANICAL SHAFTS (UNLESS NOTED OTHERWISE ON PLAN) SEE PLAN FOR SHEAR STUDS 17" - 18" 3/8" BENT PL. EXT.SEE PLANS EXT.SEE PLANS 1" (TYP) EDGE OF OPENING NOTE: USE L3X3X1/4 FRAMING WHERE WF SIZES ARE NOT SHOWNPROVIDE 2 -#4 BARS ALONG EACH SIDE OF OPENING. EXTEND BARS 24" BEYOND LIMITS OF OPENING PROVIDE 1 -#4 BAR x 3'-0" LONG DIAG. @ EACH CORNER OF OPENING (TYP.) L4x3 1/2X5/16 (LLH) END CLIPS X 4" LG.SEE ARCH. OR MECHDWGS. FOR SIZEWF BEAM SLAB OPENINGS GREATER THAN 12" x 12" SLAB OPENINGS 12" x 12" OR LESS OPENINGS GREATER THAN 24" x 24" SHALL BE REINFORCED WITH THE ANGLE FRAME INDICATED IN "TYPICAL DETAIL AT FRAMED SLAB OPENINGS" SEE ARCH. AND/OR MECH. DWGS. FOR EXACT NUMBER,SIZE & LOCATION OF ALL SLAB OPENINGS. THIS DETAIL APPLIES TO ALL SLAB OPENINGS GREATER THAN 24" x24". TYPICAL DETAIL AT FRAMED SLAB OPENINGS NOTE: ALL OPENINGS SHALL BE FORMED BY CONSTRUCTION OF A SLEEVE OR "BOX-OUT" SET DIRECTLY ON THE METAL DECK. UNDER NO CIRCUMSTANCES SHALL THE METAL DECK BE CUT UNTIL THE CONCRETE HAS BEEN IN PLACE FOR A MINIMUM OF THREE DAYS. THESE REQUIREMENTS ARE TYPICAL FOR ALL OPENINGS, REGARDLESS OF SIZE. DWGS. FOR SIZES SEE ARCH. OR MECH. L3X3X1/4 L3X3X1/4L3X3X1/4L3X3X1/4 NOTE: NO REINFORCEMENT REQUIRED WHERE "L" IS 6" OR LESS, IN DIRECTION PERPENDICULAR TO DECK. CONCRETE STOP RQD. @ OPENINGS. REFER TO TYPICAL DETAILS FOR CONCRETE DECK REINFORCING. 68 MIL SHEET 6" MIN. (TYP.)13" MAX13" MAX L 1/8"1-4 1/8 2 1/2 EA. RIB 1'-0" MAX. OPENING C4x5.4, TOE UP, (EACH SIDE) NOTE: POUR STOP REQUIRED AT ALL OPENINGS. REFER TO TYPICAL DETAIL FOR REINFORCING. FOR OPENINGS GREATER THAN 1'-0" x 2'-0" MAX. REFER TO TYPICAL DETAIL. 2'-0" MAX. OPENING 24" MIN. (TYP.) 1/8 0'-1" EA. RIBL3X3X1/4 @ L<4'-0"L5X3X1/4 @ L<6'-0"LBEAM, SEE PLAN (TYP.) COLUMN, SEE PLAN ROOF DRAIN / SANITARY, REFER TO MECHANICAL DWGS. EDGE OF DECK BENT PL., REFER TO SCHEDULE CMU, REFER TO ARCHITECTURAL SEAT ANGLE (TYP.) L3X3X5/16 -WELDED TO FACE OF COLUMN OR TOE OF FLANGES COLUMN REFER TO PLAN EDGE OF DECK, REFER TO SCHEDULE BEAM REFER TO PLAN L2 1/2X2 1/2X1/4" (TYP.) BETWEEN BEAMS BEAM REFER TO PLAN L2 1/2X2 1/2X1/4 WELDED TO EDGE OF BEAM FLANGE FACE OF COLUMN 1/4" BENT PLATE L3X3X1/4" - WELDED TO FACE OF COLUMN OR TOE OF FLANGE SPECIAL DETAIL @ MOMENT CONNECTIONS A 12ga BENT PL., LAP 3" WITH MAIN POUR STOP #5 REBAR, 3'-0" LG. 12ga BENT PL., LAP 3" WITH MAIN POUR STOP 12ga PL., CUT TO FIT COL. 0'-3"0'-3" #5 REBAR, 3'-0" LG. 0'-3"0'-3" FLOOR BEAM (SEE PLAN) #4 X 6'-0" AT 16" O.C. OVER FLOOR GIRDERS FLOOR GIRDER (SEE PLAN FOR LOCATION) (2)-#5x6'-0" LONG EACH SIDE OF COLUMN @ MID-DEPTH OF SLAB SHEAR STUDS (TYP). BREAK METAL DECK OVER GIRDER AS REQUIRED TO INSTALL STUDS #4 AT 16" o/c, 6'-0" LG. OVER GIRDERS WWF, SEE PLAN GALV. COMPOSITE DECK, SEE PLAN STEEL FABRICATOR NOTE: PROVIDE DOUBLE ANGLE SHEAR CONNECTIONS OR EXTENDED SHEAR TAB CONNECTIONS AS INDICATED IN TYPICAL DETAILS. BEAM SEE PLAN CONCRETE SLAB, SEE PLAN 3/4" COVER ADD #4 @ 12" O.C. DOWEL x 4'-0" LONG FORMED BULKHEAD CONSTRUCTION JOINTS SHALL BE PLACED AT ONE THIRD OF THE DISTANCE BETWEEN BEAMS WHEN PARALLEL TO BEAMS AND AT ONE THIRD THE SPAN LENGTH WHEN PERPENDICULAR TO THE BEAM. SAW-CUT JOINTS ARE PROHIBITED. 2`-0"2`-0" 3/4" DIA STUDS PROVIDE PAIRS AS RQD., SEE NOTE 3/4" DIA. STUD, WELD PER AWS RQMTS. NOTE: NUMBER OF EQUALLY SPACED STUDS NOTED [NN] ON PLANS. PLACE STUD IN EACH RIB OF DECK AT EQ. SPA. IF # STUDS > # RIBS, ADD EQ. NUMBER OF STUDS AT EACH END IN PAIRS TO ACHIEVE TOTAL BREAK DECK AS REQUIRED GIRDER BEAM ELEVATION 1" CLEAR 3/4" DIA. STUDS PROVIDE PAIRS AS RQD. SEE NOTE COLD FORMED STUDS OR CURTAIN WALL WINDOW SYSTEM (SEE ARCH.) CLOSURE PLATE. SEE DETAILS. CL STEEL BEAM (SEE PLAN.) 6-1/4" COMPOSITE SLAB (SEE PLAN.) T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) PROVIDE SLIP CONNECTION AT TOP OF STUDS. COLD FORMED STUDS (SEE ARCH.) SLIP CONNECTION AT EACH STUD SLAB EDGE (SEE DETAILS.) SHEAR STUDS (SEE PLAN.) CL SEE PLAN E.O.S. STEEL BEAM (SEE PLAN.) 6-1/4" COMPOSITE SLAB (SEE PLAN.) T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) DECK DIRECTION VARIES AT "SIM". BUILD-OUT EDGE PER ARCH. PROVIDE CURTAIN WALL ATTACHMENTS AS REQUIRED. (BY OTHERS, U.N.O.) SEE S503 FOR ADDITIONAL INFORMATION 5/16" MIN. SLAB EDGE CL SEE PLAN E.O.S. 6-1/4" COMPOSITE SLAB (SEE PLAN.) T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) DECK DIRECTION VARIES AT "SIM". 1/2" DIA. x 8" LONG HEADED STUDS AT 8" O.C. #3, 6'-0" EXT. WITH STD-HOOK AT 8" O.C. TIED TO HEADED STUDS THERMALLY BROKEN (BASIS OF DESIGN FABREEKA TIM), GALV. CURTAIN WALL SUPPORT ANGLE. COORDINATE WITH CURTAIN WALL REQUIREMENTS. ASSUME L5X5X3/8 MIN. PROVIDE POST-INSTALLED ANCHORS AT 8" O.C. LOCATED BETWEEN HEADED STUDS SECOND FLOOR T.O.S. 113'-5 3/4" HALFEN ADJUSTABLE BRICK SUPPORT SYSTEM AND CONCEALED LINTEL (BY OTHERS) THERMAL BREAK MATERIAL (BASIS OF DESIGN "FABREEKA TIM"), 1/2" THICKNESS ASSUMED OPENING TO BE SHORED UNTIL MORTAR IS CURED AND SHORING REMOVAL APPROVED BY LINTEL SUPPLIER. HSS BRICK SUPPORT. SEE PLAN WT9X17.5 AT 6'-0" O.C. MAX. TYP. CFMF WALL STUDS. PROVIDE TOP SLIP CONN. SEE DETAILS. (BEYOND) FLOOR SLAB. SEE PLAN. STOREFRONT OR SECOND COURSE OF BRICK. SEE ARCH. PER ARCH. C6X8.2 AT EACH WT L3x3x1/4 KICKER AT EA. C6 W/ 1/4" GUSSET CL BEAM. SEE PLAN. BLOCKING AND SEALANT. SEE ARCH. NOTE: WHERE HSS PASSES COLUMN, LOWER KICKER TO BE HORIZONTALLY CONNECTED TO COLUMN DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:13 PMS503 DETAILS AND SECTIONS 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/4" = 1'-0"1 TYP. PERIMETER SECTION 3/4" = 1'-0"16 SLAB EDGE DETAILS 3/4" = 1'-0"5 CONCRETE DECK OPENING FRAME 3/4" = 1'-0"6 FLOOR DECK OPENING - 13" SQ. MAX 3/4" = 1'-0"7 TYPICAL FLOOR DECK OPENING - 2'-0" MAX 3/4" = 1'-0"8 DECK SUPPORT AT COLUMNS 3/4" = 1'-0"9 DECK SUPPORT AT CORNER COLUMNS 3/4" = 1'-0"10 DECK SUPPORT AT PERIMETER COLUMNS 3/4" = 1'-0"11 TYPICAL SLAB REINFORCING AT COLUMNS 3/4" = 1'-0"12 FLOOR BEAM TO GIRDER CONNECTION 3/4" = 1'-0"13 CONSTR. JOINT - SLAB ON METAL DECK 1" = 1'-0"14 STUDS ON BEAMS / GIRDERS 3/4" = 1'-0"15 SECTION AT WRAP 3/4" = 1'-0"3 EDGE DETAIL - LOW CLEARANCE 3/4" = 1'-0"4 SLAB EDGE AT CURTAIN WALL SUPPORT 3/4" = 1'-0"2 HSS BRICK SUPPORT REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 A A A MOMENT CONNECTION TO FLANGE TOP OF COLUMN WF COLUMN, SEE PLAN BEAM SEE PLAN BEAMS FRAMING FROM OTHER SIDES NOT SHOWN (N) SC BOLTS TOP AND BOTTOM FLANGE STIFFENER PLATE WELDED 3 SIDES (TYP.) MATCH FLANGE PLATE THICKNESS EXTENDED PLATE SHEAR CONNECTION TYPICAL WELDED FLANGE PLATE BEAM SEE PLAN (N) SC BOLTS TOP AND BOTTOM FLANGE BEAM SEE PLAN WELDED FLANGE PLATE BEAM-SEE PLAN FOR SIZE STANDARD SHEAR CONNECTION TYPICAL BEAMS FRAMING FROM OTHER SIDE NOT SHOWN (N) SC BOLTS TOP AND BOTTOM FLANGE STIFFENER PLATE WELDED 3 SIDES (TYP.) MATCH FLANGE PLATE THICKNESS WF COLUMN SEE PLAN (N) SC BOLTS TOP AND BOTTOM FLANGE (N) SC BOLTS TOP AND BOT. FLANGE EXTENDED PLATE SHEAR CONN. BEAM FRAMING FROM OTHER SIDE NOT SHOWN (N) SC BOLTS TYP. TOP AND BOTTOM FLANGE EXTENDED PLATE SHEAR CONN. (TYP.) WELDED FLANGE PLATE BEAM SEE PLAN WF COLUMN SEE PLAN SECTION A X CJP AS NOTED X CJP AS NOTED X CJP AS NOTED MOMENT CONNECTION TO FLANGE INTERMEDIATE BEAM MOMENT (K-FT)NPLATE (t) (IN) NOTES: 1. N = ROWS OF (2) 7/8" DIAMETER A490 SLIP CRITICAL (SC) BOLTS U.N.O. 2. PLATE WIDTH TO MATCH COLUMN WIDTH 3. CJP = COMPLETE JOINT PENETRATION WELD TYPE TC-U4a 4. FLANGE STIFFENER: Y = PROVIDE STIFFENER, N = NOT REQUIRED 5. WEB STIFFENER: PLATE R" THICK X Y" EXTENSION (N = NOT REQUIRED), Z = R, 2S = PROVIDE ON TWO SIDES OF WEB WELD (X) FLANGE STIFFENER MOMENT CONNECTION TO WEB WEB STIFF. R X Y WF COLUMN, SEE PLAN BEAM SEE PLAN FLANGE STIFFENER WEB STIFFENER, R" THICK (2S) TWO SIDES AS NOTED WELDED FLANGE PLATE BEAM SEE PLAN Z Y" TOP AND BOTTOMt t WEB STIFFENER WEB STIFFENER, R" THICK (2S) TWO SIDES AS NOTED W14X38 125 3/4"3/8"3 Y N W10 62 3/4"1/4"2 Y N W8 48 3/4"1/4"2 Y N W12X40 139 3/4"3/8"5 Y N W12X58 240 1"CJP 8 Y N W24X68 W24X62 71 3/4"5/16"3 N N W24X84 517 1"CJP 8 N N W18 398 3/4"3/8"8 N N W33 23 1/2"1/4"2 N N 25 1/2"1/4"2 N NW12X26 STANDARD SHEAR CONNECTION NUMBER OF BOLTS SHALL BE DESIGNED USING BEAM UNIFORM LOAD CAPACITIES, UNLESS BEAM REACTION IS NOTED. 3/4"DIA. A325 BOLTS, LARGER DIA. MAY BE REQ. (TYPICAL) REFER TO PLAN FOR BEAM SIZE STANDARD SHEAR CONNECTION REFER TO PLAN FOR BEAM SIZE 3/4" DIA. A325 BOLT PAIRS TO MATCH FLANGE STRENGTH WELD OPTIONAL CONTINUOUS CONNECTION SIMPLE CONNECTION PLATE =FLANGE WIDTH + 1" FLANGE THICKNESS + 1/8" PLATE =FLANGE WIDTH -1" FLANGE THICKNESS + 1/4" PL. ASTM A572 Gr.50 (TYP.) EXTENDED ENDPLATE SHEAR CONNECTION AT CONTRACTOR'S OPTION. BOLTS SHALL CARRY 100% OF ECCENTRIC MOMENT L BOLTS IN STD. HOLES EXTENDED SINGLE PLATE SHEAR CONNECTION OR DOUBLE ANGLE AT WEB REFER TO PLAN FOR BEAM SIZE 3/4" DIA. A325 BOLTS LARGER DIAMETER MAY BE REQUIRED WIDE FLANGE OR HSS COLUMN (REFER TO COLUMN SCHEDULE) STANDARD DOUBLE ANGLE SHEAR CONNECTION. DESIGN WITH BEAM UNIFORM LOAD CAPACITIES, UNLESS BEAM REACTIONS NOTED SEAL WELD CAP PLATE HSS COLUMN, REFER TO PLAN5/8" CAP PLATE CL 1/2" STIFFENER PLATE EA. SIDE OF BEAM WEB REFER TO PLAN FOR BEAM SIZE (4)-3/4" DIA. A325 BOLTS COLUMN, REFER TO PLAN 1" CAP PLATE CL (N) ROWS SC BOLTS TOP AND BOTTOM FLANGE DBL ANGLE OR EXTENDED PLATE SHEAR CONN. BEAM FRAMING FROM OTHER SIDE NOT SHOWN (N) ROWS BOLTS TOP AND BOTTOM FLANGE DBL ANGLE OR EXTENDED PLATE SHEAR CONN. (TYP.) WELDED FLANGE PLATE BEAM SEE PLAN HSS COLUMN SEE PLAN SECTION A 1/4" BEAM MOMENT (K-FT)NPLATE (t) (IN) NOTES: 1. N = ROWS OF (2) 3/4" DIAMETER A325 PRETENSIONED BOLTS U.N.O. 2. PLATE TO BE 50 KSI STEEL U.N.O. 3. EXTENDED SHEAR CONNECTION DESIGNED BY FABRICATOR'S ENGINEER MAY BE PROVIDED IN LIEU OF DBL ANGLE SHEAR CONNECTION. WELD (X) MOMENT CONNECTION TO HSS t CLIP CORNER AT 90 DEG. CONN. DOUBLE MOMENT CONNECTIONS: TIGHTEN BOLTS IN BOTTOM FLANGES AFTER DEAD LOADS APPLIED (TYP.) CJP TO COLUMN AT MOMENT CONNECTIONS t W8X28 35 1/2 1/4 3 W10X33 61 1/2 3 W12X58 133 3/4 4 W14X38 75 3/4 3 2" MIN. 6" MIN. 1/4 1/4 1/4 2" MIN. BEAM PER PLAN DOUBLE ANGLE SHEAR CONNECTION: CONNECTION DEPTH = BEAM "T" DIMENSION WITH 3/4" A325-N CJP TYP. 3 SIDES FOR OPENINGS 2'-0" SQUARE MAX SPAN OF DECK FOR OPENINGS 2'-0" TO 6'-0" SQ. MAXREFER TOPLANCL BEAM L4x4x1/4L4x4x1/4SPAN OF DECK L4x4x1/4 L4x4x1/4 L4x4x3/8L4x4x3/8 L4x4x3/8 L4x4x3/8SEAT ANGLE L4x4x3/8 x 6" CL BEAM NOTES: 1. COORDINATE EXACT OPENING SIZE AND LOCATION WITH ACTUAL EQUIPMENT USED AND WITH ARCHITECTURAL AND M.E.P. DRAWINGS. A B 2'-0" MAX 2'-0" MAX6'-0" MAX 6'-0" MAX 6'-0" MAXCOORD. WITH MECH.MAX. 4'-0"STEEL DECK ROOF BEAM, SEE PLAN THERMALLY BROKEN SPLICE (BASIS OF DESIGN: FABREEKA TIM) PIPE 4STD AT 12'-0" MAX. 1/2" STIFFENER PLATE AT EA. POST, EACH WAY W8X18 MECHANICAL UNIT SUPPORT RAIL *NOTE: ALL EXTERIOR EXPOSED STEEL TO BE HOT-DIP GALVANIZED 3/16 3/16 PROVIDE ADDITIONAL INTERMEDIATE SUPPORTS AS REQUIRED BY UNITS TO BE INSTALLED. MIN. SIZE L4X4X5/16. (NOT SHOWN)0'-10"0'-10" L3X3X1/4 KICKER AT EA. BRACE W/ 1/4" GUSSET (OMIT AT GRIDLINES "A" AND "D")BEAM, SEE PLAN PIPE 4" STD. AT 12' o.c. MAX COLD FORMED FRAMING BY OTHERS AT 24" O.C. MAX. SEE ARCH FOR PROFILES. MAY BE SITE-BUILT OR PRE-FAB TRUSSES. CLAD PER ARCH. THERMALLY BROKEN SPLICE (BASIS OF DESIGN: FABREEKA TIM) LOCATE IN APPROX. CENTER OF INSULATION. T.O. STEEL (VARIES - SEE PLAN) T.O. PARAPET (VARIES - SEE ARCH.) BEARING ELEV. (CONSTANT, SEE ARCH.) PIPE 4" STD. AT 12' o.c. MAX HSS6X6X5/16, CONT. PROVIDE ACCESS PANELS AS REQURIED FOR FALL PROTECTION ATTACHMENT POINTS. PROVIDE ATTACHEMENT LUG DIRECTLY WELDED TO HSS. OR ATTACH AROUND HORIZ HSS. STEEL FRAMING. SEE PLAN. MIN. 5'-0" COORDINATE WITH PROVIDE HURRICANE TIES AT EACH BEARING POINT. FIRE RETARDANT TREATED WOOD SHEATHING (1/2" PERFORMANCE CATEGORY). FASTEN TO COLD- FORMED FRAMING WITH COMPATIBLE FASTENERS AT 4" O.C. (EDGE) AND 12" O.C. FIELD. ROOF MEMBRANE, SEE ARCH. COLD-FORMED EXTERIOR WALL FRAMING AND/OR CURTAIN WALL SYSTEM PROVIDE DEFLECTION CLIP TO BEAM AT EACH STUD .2" TYP.L3X3X1/4 KICKER AT EA. BRACE W/ 1/4" GUSSET (OMIT AT GRIDLINES "A" AND "D") BEAM, SEE PLAN PIPE 4" STD. AT 12' o.c. MAX COLD FORMED FRAMING BY OTHERS AT 24" O.C. MAX. SEE ARCH FOR PROFILES. MAY BE SITE-BUILT OR PRE-FAB TRUSSES. CLAD PER ARCH. THERMALLY BROKEN SPLICE (BASIS OF DESIGN: FABREEKA TIM) LOCATE IN APPROX. CENTER OF INSULATION. T.O. STEEL (VARIES - SEE PLAN) T.O. PARAPET (VARIES - SEE ARCH.) BEARING ELEV. (CONSTANT, SEE ARCH.) PIPE 4" STD. AT 12' o.c. MAX HSS6X6X5/16, CONT. PROVIDE ACCESS PANELS AS REQURIED FOR FALL PROTECTION ATTACHMENT POINTS. PROVIDE ATTACHEMENT LUG DIRECTLY WELDED TO HSS. OR ATTACH AROUND HORIZ HSS. STEEL FRAMING. SEE PLAN. MIN. 5'-0" COORDINATE WITH PROVIDE HURRICANE TIES AT EACH BEARING POINT. FIRE RETARDANT TREATED WOOD SHEATHING (1/2" PERFORMANCE CATEGORY). FASTEN TO COLD- FORMED FRAMING WITH COMPATIBLE FASTENERS AT 4" O.C. (EDGE) AND 12" O.C. FIELD. ROOF MEMBRANE, SEE ARCH. COLD-FORMED EXTERIOR WALL FRAMING AND/OR CURTAIN WALL SYSTEM PROVIDE DEFLECTION CLIP TO BEAM AT EACH STUD . TOP MOUNT JOIST HANGER AT EACH JOIST 8" X 54 MIL MIN. CFMF ROOF JOISTS AT 24" O.C. MAX. INFILL CFMF MIN. (1) LAYER FIRE RETARDANT SHEATHING (3/4" PERFORMANCE CATEGORY) FASTEN TO COLD-FORMED FRAMING WITH COMPATIBLE FASTENERS AT 4" O.C. (EDGE) AND 12" O.C. FIELD. MAKE UP ELEV. WITH ADDITIONAL LAYERS OR HAT CHANNELS TO PRODUCE SURFACE FLUSH WITH TOP OF DECK. DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:16 PMS504 DETAILS AND SECTIONS 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/4" = 1'-0"5 TYPICAL MOMENT CONNECTIONS AT W-COL. 3/4" = 1'-0"1 BEAM TO BEAM CONN. 3/4" = 1'-0"2 BEAM TO COLUMN CONNECTION 3/4" = 1'-0"3 BEAM OVER COLUMN CONNECTION 3/4" = 1'-0"4 TYPICAL MOMENT CONNECTIONS AT HSS 3/4" = 1'-0"6 FR MOMENT SPLICE 3/4" = 1'-0"7 TYPICAL FRAMING AT OPENINGS 3/4" = 1'-0"8 MECHANICAL UNIT RAILS 3/4" = 1'-0"9 PARAPET FRAMING - BEAMS PARALLEL 3/4" = 1'-0"10 PARAPET FRAMING - BEAMS PARALLEL AT GRID 1 REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 FIRST FLOOR 100'-0" SECOND FLOOR T.O.S. 113'-5 3/4" THIRD FLOOR T.O.S. 127'-11 3/4" ROOF T.O.S. SLOPES, SEE PLAN COLUMN LOCATIONS A-1 A-2 A-3 A-4 B-1 B-2 B-3 B-4 B-5 B.3-6 B.5-1 C-1 C-2 C-3 C-4 C-5 C-5.5 D-1 D-2 D-2.7 D-3 D-3.9 D.3-3.8 E.1-3.9 E-F E-3.9W10X49W10X68W10X49W10X112W10X68W10X77W10X68W10X68 COLUMN LOCATIONS FOURTH FLOOR T.O.S. 143'-5 3/4" FIFTH FLOOR T.O.S.157'-5 3/4" LOW ROOF T.O.S.124'-6" T.O.F.96'-0" FIRST FLOOR 100'-0" SECOND FLOOR T.O.S. 113'-5 3/4" THIRD FLOOR T.O.S. 127'-11 3/4" ROOF T.O.S. SLOPES, SEE PLAN FOURTH FLOOR T.O.S. 143'-5 3/4" FIFTH FLOOR T.O.S.157'-5 3/4" LOW ROOF T.O.S.124'-6" T.O.F.96'-0" A.5-5W10X49 W10X77HSS8X8X5/8HSS6X6X5/8W10X88W12X210W12X136W10X77W10X54W10X33W10X45W10X60W10X49W10X45W10X112HSS7X7X5/8HSS6X6X1/2W10X33HSS6X6X1/2W10X68T.O. PIER - SHEAR LUG T.O. PIER - STANDARD 99'-4" 99'-0" FIRST/GROUND F.F.E. 100'-0" SECOND FLOOR T.O.S. 113'-5 3/4" ROOF T.O.S. 172'-10 3/8" THIRD FLOOR T.O.S. 127'-11 3/4" FOURTH FLOOR T.O.S. 143'-5 3/4" FIFTH FLOOR T.O.S. 157'-5 3/4" VARIES S501 9S501 9 SEE S101 FOR BRACE SIZES SEE S102 FOR BRACE SIZES SEE S103 FOR BRACE SIZES SEE S104 FOR BRACE SIZES SEE S105 FOR BRACE SIZES S506 2 S506 2 S506 2 S506 2 S506 2 S506 3 S506 3 OPP. HAND S506 3 S506 3 OPP. HAND S506 3 S506 3 OPP. HAND S506 3 S506 3 OPP. HAND DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:17 PMS505 COLUMN SCHEDULE & BRACED FRAME ELEVATION 02/05/2021 2018089 NH Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING1/4" = 1'-0" STEEL COLUMN SCHEDULE 1/4" = 1'-0" TYPICAL BRACE ELEVATION REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021 ROOF T.O.S. 172'-10 3/8" ROOF T.O.S. 172'-10 3/8" 1 MEP Roof 175' -9 25/64" MEP PENTHOUSE 183' -4"PENTHOUSE FRAMING PLAN 182'-9" PENTHOUSE FRAMING PLAN 182'-9" ROOF JOISTS. SEE PLAN. AT GRIDLINE 1, BEAR JOISTS ON CFMF WALL. AT OPP. END, PROVIDE JOIST HANGERS. 1/2" MIN. WOOD STRUCTURAL PANEL. SEE NOTES. SEE ARCH. CANTILEVERED STEEL BEAMS. MOMENT CONNECT THRU COLUMNS. SEE PLAN. SEE DETAILS. SEE NOTES ROOF DECK. SEE PLAN. SEE NOTES. COLD FORMED METAL FRAMING AT 24" O.C. MAX. SEE ARCH FOR FINISHED PROFILE. SEE NOTES. RIGIDLY CONNECT CFMF TO STRUCTURAL STEEL AS REQUIRED TO PRODUCE ARCH. REQUIRED SHAPE. THERMALLY BROKEN MOMENT SPLICE CFMF WALL. NOTE - WALL IS NOT ALIGNED WITH COLUMN ON SOUTH SIDE OF ENCLOSURE STEEL COLUMN. SEE PLAN ROOF BEAM. SEE PLAN. SEE DETAILS FOR MOMENT CONNECTIONS. CONDITIONED SPACE UNCONDITIONED SPACE POST BASES WELDED OR BOLTED TO TOP FLANGE OF BEAMS. CURTAIN WALL CAPTURE BRACKETS (BY OTHERS) ROOF DECK. SEE PLAN. SEE NOTES. 0.17:12 -1'-7" -1'-8 5/8" CFMF KNEE WALL (SEE ARCH.) TYP 4 PLACES TYP 4 PLACES HSS BRACE (SEE PLAN) HSS BRACE (SEE PLAN) 1/2" MIN. GUSSET PLATE STEEL BEAM (SEE PLAN)WORK POINT CL STEEL BEAM (SEE PLAN) CONCRETE SLAB ON METAL DECK (SEE PLAN) HSS BRACE (SEE PLAN) STEEL COLUMN (SEE PLAN) 1/2" MIN. GUSSET PLATE WORK POINT T.O. SLAB (SEE PLAN) T.O. STEEL (SEE PLAN) CL 6 1/4" COMPOSITE SLAB (SEE PLAN) B.O. SUPPORT COORD. W/ MNFR2'-3 3/4"3/8" DIA. HANGER RODS AT 30" O/C BY MNFR (COORD W/ DOOR MNFR FOR HOLE LOCATIONS) W10X33 STEEL BEAM (SEE PLAN)1'-9"1 1/2"9"1 1/2"1 1/2"1 1/2"6 1/2"5"6 1/2"12" W10X112 COLUMN. SEE PLAN 1 1/4" THICK COLUMN BASE AND CAP PLATES. SEE SECTION. STRUCTURAL THERMAL BREAK MATERIAL (BASIS OF DESIGN FABREEKA TIM). ALIGN TOP OF THERMAL BREAK WITH TOP OF INSULATION. SEE ARCH. (8) 3/4" DIA. A325, THERMALLY ISOLATED BOLTS. EXTERIOR FINISH ASSEMBLY WITH INSULATION. SEE ARCH. HSS6X6 COLUMN. SEE PLAN 3/4" THICK COLUMN BASE AND CAP PLATES. SEE SECTION. (4) 3/4" DIA. A325, THERMALLY ISOLATED BOLTS.1 1/2"1 1/2"9"1 1/2" 12" SECTION - HSS6X6SECTION - W10 CL COLD-FORMED METAL STUDS. SEE NOTES, SEE ARCH. ROOF MEMBRANE. SEE ARCH. ROOF DECK. SEE PLAN INSULATION. SEE ARCH. 5/16" BENT PLATE STEEL BEAM. SEE PLAN DEFLECTION CONNECTION AT EACH STUD INSULATION AND BRICK. SEE ARCH. NOTE: AT "SIM." DECK RUNS OPPOSITE DIRECTION VARIES. SEE ARCH. 1/4" CLEAR ROOF DECK (SEE PLAN) ROOFING MEMBRANE (SEE ARCH) 8" CMU W/ #5 BARS AT 48" O/C 1/4" BENT PLATE W/ VERT. SLOTTED HOLES. FASTEN TO UNDERSIDE OF ROOF DECK 3/8" DIA. MASONRY SCREW ANCHOR AT 2'-0" O/C FIRE CAULK GAP (SEE ARCH) HSS3X3X1/4 DOOR FRAME. SEE ARCH FOR LOCATIONS AND DIMENSIONS. 1/2" THICK X 10" X 3" BASE PLATE AT EACH POST (2) 3/8" X 3 1/4" HEAVY DUTY SCREW ANCHORS AT EACH POST 1/2" GUSSET WITH (2) VLSSL HOLES. (SLIP CONNECTION)1 1/2"6"10"4"L6X4X5/16 BY 16" LONG (MIN.) AT EACH POST. IF FIELD CONDITIONS PERMIT, ANGLE MAY BE CONT. OVER DOOR. PROVIDE (2) 3/8" X 3 1/4" HEAVY DUTY SCREW ANCHORS FOR EACH POST. SEE NOTE. COORDINATE WITH FIELD CONDITIONS. NOTE: TOP CONNECTION MAY BE TO STEEL IF REQUIRED. WELD TOP ANGLE TO STEEL BEAM WITH MIN (4) 1/4" FILLET WELD OR PROVIDE (2) 3/4" A325 BOLTS AT EACH VERTICAL POST. (2) 5/8" A307 BOLTS TOP OF SLAB (SEE PLAN) BOTTOM OF DECK ABOVE (SEE PLAN) 1 THIRD FLOOR T.O.S. 127'-11 3/4" COMPOSITE SLAB. SEE PLAN FOR EXTENTS. HEADED STUDS. SEE NOTES. SUPPORT ANGLE FOR CURTAIN WALL. L6X6X3/8" ASSUMED. COORD WITH CURTAIN WALL SUPPLIER. 3/4" DIA. HOLLOW-BOLT OR APPROVED EQUIVALENT AT 12" O.C. THERMAL BREAK MATERIAL. BASIS OF DESIGN: FABREEKA TIM. CURTAIN WALL. SEE ARCH. SECOND FLOOR T.O.S. 113'-5 3/4" 3.9 HALFEN ADJUSTABLE BRICK SUPPORT SYSTEM AND CONCEALED LINTEL (BY OTHERS) THERMAL BREAK MATERIAL (BASIS OF DESIGN "FABREEKA TIM"), 1/2" THICKNESS ASSUMED OPENING TO BE SHORED UNTIL MORTAR IS CURED AND SHORING REMOVAL APPROVED BY LINTEL SUPPLIER. HSS BRICK SUPPORT. SEE PLAN L3X3X1/4 KICKERS AT 6'-0" O.C. (MAX.) TYP. CFMF WALL STUDS. PROVIDE TOP SLIP CONN. SEE DETAILS. FLOOR SLAB. SEE PLAN. AT AREAS NOT ENCLOSED BY STOREFRONT, PROVIDE (2) BRICK REVEAL AT BOTTOM OF WALL. COORD. WITH ARCH. STOREFRONT. SEE ARCH. PER ARCH.BLOCKING AND SEALANT. SEE ARCH. SECOND FLOOR T.O.S. 113'-5 3/4" 3.9 HALFEN ADJUSTABLE BRICK SUPPORT SYSTEM AND CONCEALED LINTEL (BY OTHERS) THERMAL BREAK MATERIAL (BASIS OF DESIGN "FABREEKA TIM"), 1/2" THICKNESS ASSUMED OPENING TO BE SHORED UNTIL MORTAR IS CURED AND SHORING REMOVAL APPROVED BY LINTEL SUPPLIER. HSS BRICK SUPPORT. SEE PLAN MIN. 3/4" GUSSET. AND SHEAR CONNECTION TO HSS BRICK SUPPORT. DESIGN LOAD = 15 KIPS TYP. CFMF WALL STUDS. PROVIDE TOP SLIP CONN. SEE DETAILS. FLOOR SLAB. SEE PLAN. THERMALLY BROKEN COLUMN SPLICE. SEE 5/S506. DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F G 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Architecture Planning Interior Design 11 12 H I 11 12 H I 619 West State Street Ithaca, New York 14850 132 E. Jefferson Street Syracuse, New York 13202 p 607 273 7600 www.holt.com phone: (585) 482-8130 www.jensenbrv.com ROCHESTER, NEW YORK 14609 1653 EAST MAIN STREET Structural Engineering Consultants2/10/2021 4:47:21 PMS506 DETAILS AND SECTIONS 02/05/2021 2018089 RF Carpenter Park, Ithaca, NY 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/4" = 1'-0"1 SECTION THRU PENTHOUSE 3/4" = 1'-0"2 BRACE FRAME 1 3/4" = 1'-0"3 BRACE FRAME 2 3/4" = 1'-0"4 FOLDING PARTITION SUPPORT 3/4" = 1'-0"5 THERMALLY BROKEN COLUMN SPLICE 3/4" = 1'-0"6 LOW ROOF EDGE DETAIL 3/4" = 1'-0"7 TOP OF ELEVATOR SHAFT 3/4" = 1'-0"8 REINFORCED DOOR FRAME 3/4" = 1'-0"11 SECTION AT CURTAIN WALL AND STAIR 2 3/4" = 1'-0"9 BRICK SUPPORT AT 3.9 LINE 3/4" = 1'-0"10 BRICK SUPPORT AT W-SHAPE COL. REVISION SCHEDULE NAME DATE 02/10/2021 Received by DiMarco 2/15/2021