MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
DIMENSIONAL LETTER SIGNAGE 101419 - 1
SECTION 101419 - DIMENSIONAL LETTER SIGNAGE
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Dimensional characters.
a. Fabricated channel dimensional characters.
1.2 DEFINITIONS
A. Illuminated: Illuminated by lighting source integrally constructed as part of the sign unit.
1.3 COORDINATION
A. Furnish templates for placement of electrical service embedded in permanent construction by
other installers.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Sustainable Design Submittals:
1. Product Data: For adhesives, indicating VOC content.
2. Laboratory Test Reports: For adhesives, indicating compliance with requirements for
low-emitting materials.
C. Shop Drawings: For signs.
1. Include fabrication and installation details and attachments to other work.
2. Show sign mounting heights, locations of supplementary supports to be provided by other
installers, and accessories.
3. Show message list, typestyles, graphic elements, and layout for each sign at least half
size.
4. Show locations of electrical service connections.
5. Include diagrams for power, signal, and control wiring.
D. Samples for Verification: For each type of sign assembly showing all components and with the
required finish(es), in manufacturer's standard size unless otherwise indicated and as follows:
1. Dimensional Characters: Half-size Sample of dimensional character.
E. Product Schedule: For dimensional letter signs. Use same designations indicated on Drawings
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
DIMENSIONAL LETTER SIGNAGE 101419 - 2
or specified.
F. Delegated Design Submittal: For signs indicated in "Performance Requirements" Article.
1. Include structural analysis calculations for signs indicated to comply with design loads;
signed and sealed by the qualified professional engineer responsible for their preparation.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: For signs to include in maintenance manuals.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and
approved by manufacturer.
1.7 FIELD CONDITIONS
A. Field Measurements: Verify locations of electrical service embedded in permanent construction
by other installers by field measurements before fabrication, and indicate measurements on
Shop Drawings.
1.8 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of signs that fail in
materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Deterioration of finishes beyond normal weathering.
b. Separation or delamination of sheet materials and components.
2. Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000
"Quality Requirements," to design sign structure and anchorage of dimensional character sign
type(s) according to structural performance requirements.
B. Structural Performance: Signs and supporting elements shall withstand the effects of gravity
and other loads within limits and under conditions indicated.
1. Uniform Wind Load: As indicated on Drawings.
2. Concentrated Horizontal Load: As indicated on Drawings.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
DIMENSIONAL LETTER SIGNAGE 101419 - 3
3. Other Design Load: As indicated on Drawings
4. Uniform and concentrated loads need not be assumed to act concurrently.
C. Thermal Movements: For exterior fabricated channel dimensional characters, allow for thermal
movements from ambient and surface temperature changes.
1. Temperature Change: 120 deg F, ambient; 180 deg F, material surfaces.
D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
2.2 DIMENSIONAL CHARACTERS
A. Fabricated Channel Characters : Translucent face with metal side returns, formed free from
warp and distortion; with uniform faces, sharp corners, and precisely formed lines and profiles;
internally braced for stability, to meet structural performance loading without oil-canning or
other surface deformation, and for securing fasteners; and as follows.
1. Manufacturers: Subject to compliance with requirements, provide products by the
following:
a. Takeform.
2. Illuminated Characters: Backlighted character construction with LED lighting, including
transformers, insulators, and other accessories for operability, with provision for
servicing and concealing connections to building electrical system. Use tight or sealed
joint construction to prevent unintentional light leakage. Space lamps apart from each
other and away from character surfaces as needed to illuminate evenly.
a. Power: 120 V, 60 Hz, 1 phase, 15 A.
b. Weeps: Provide weep holes to drain water at lowest part of exterior characters.
Equip weeps with permanent baffles to block light leakage without inhibiting
drainage.
3. Character Material: Sheet or plate aluminum.
4. Material Thickness: Manufacturer's standard for size and design of character.
5. Translucent Face Sheet: Acrylic sheet with integral color matching Architect's sample.
a. Sheet Thickness: 0.1875 inch.
6. Character Height: As indicated on Drawings.
7. Character Depth: As indicated on Drawings.
8. Mounting: Concealed, painted aluminum back bar or bracket assembly.
a. Hold characters at distance as selected by Architect from wall surface.
9. Typeface: As selected by Architect.
2.3 DIMENSIONAL CHARACTER MATERIALS
A. Aluminum Castings: ASTM B26/B26M, alloy and temper recommended by sign manufacturer
for casting process used and for type of use and finish indicated.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
DIMENSIONAL LETTER SIGNAGE 101419 - 4
B. Acrylic Sheet: ASTM D4802, category as standard with manufacturer for each sign, Type UVF
(UV filtering).
2.4 ACCESSORIES
A. Fasteners and Anchors: Manufacturer's standard as required for secure anchorage of signs,
noncorrosive and compatible with each material joined, and complying with the following:
1. Use concealed fasteners and anchors unless indicated to be exposed.
2. For exterior exposure, furnish stainless steel devices unless otherwise indicated.
3. Exposed Metal-Fastener Components, General:
a. Fabricated from same basic metal and finish of fastened metal unless otherwise
indicated.
b. Fastener Heads: For nonstructural connections, use flathead screws and bolts with
tamper-resistant Allen-head slots unless otherwise indicated.
4. Sign Mounting Fasteners:
a. Concealed Studs: Concealed (blind), threaded studs welded or brazed to back of
sign material, screwed into back of sign assembly, or screwed into tapped lugs cast
integrally into back of cast sign material, unless otherwise indicated.
2.5 FABRICATION
A. General: Provide manufacturer's standard sign assemblies according to requirements indicated.
1. Preassemble signs and assemblies in the shop to greatest extent possible. Disassemble
signs and assemblies only as necessary for shipping and handling limitations. Clearly
mark units for reassembly and installation; apply markings in locations concealed from
view after final assembly.
2. Mill joints to a tight, hairline fit. Form assemblies and joints exposed to weather to resist
water penetration and retention.
3. Comply with AWS for recommended practices in welding and brazing. Provide welds
and brazes behind finished surfaces without distorting or discoloring exposed side. Clean
exposed welded and brazed connections of flux, and dress exposed and contact surfaces.
4. Conceal connections if possible; otherwise, locate connections where they are
inconspicuous.
5. Internally brace dimensional characters for stability, to meet structural performance
loading without oil-canning or other surface deformation, and for securing fasteners.
6. Provide rabbets, lugs, and tabs necessary to assemble components and to attach to
existing work. Drill and tap for required fasteners. Use concealed fasteners where
possible; use exposed fasteners that match sign finish.
7. Castings: Fabricate castings free of warp, cracks, blowholes, pits, scale, sand holes, and
other defects that impair appearance or strength. Grind, wire brush, sandblast, and buff
castings to remove seams, gate marks, casting flash, and other casting marks before
finishing.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
DIMENSIONAL LETTER SIGNAGE 101419 - 5
2.6 GENERAL FINISH REQUIREMENTS
A. Protect mechanical finishes on exposed surfaces from damage by applying a strippable,
temporary protective covering before shipping.
B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of
approved Samples and are assembled or installed to minimize contrast.
C. Organic, Anodic, and Chemically Produced Finishes: Apply to formed metal after fabrication
but before applying contrasting polished finishes on raised features unless otherwise indicated.
2.7 ALUMINUM FINISHES
A. Clear Anodic Finish: AAMA 611, Class I, 0.018 mm or thicker.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance.
B. Verify that sign-support surfaces are within tolerances to accommodate signs without gaps or
irregularities between backs of signs and support surfaces unless otherwise indicated.
C. Verify that electrical service is correctly sized and located to accommodate signs.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION OF DIMENSIONAL CHARACTERS
A. General: Install signs using mounting methods indicated and according to manufacturer's
written instructions.
1. Install signs level, plumb, true to line, and at locations and heights indicated, with sign
surfaces free of distortion and other defects in appearance.
2. Before installation, verify that sign surfaces are clean and free of materials or debris that
would impair installation.
3. Corrosion Protection: Coat concealed surfaces of exterior aluminum in contact with
grout, concrete, masonry, wood, or dissimilar metals, with a heavy coat of bituminous
paint.
B. Mounting Methods:
1. Concealed Studs: Using a template, drill holes in substrate aligning with studs on back of
sign. Remove loose debris from hole and substrate surface.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
DIMENSIONAL LETTER SIGNAGE 101419 - 6
a. Masonry Substrates: Fill holes with adhesive. Leave recess space in hole for
displaced adhesive. Place sign in position and push until flush to surface, embedding
studs in holes. Temporarily support sign in position until adhesive fully sets.
b. Thin or Hollow Surfaces: Place sign in position and flush to surface, install
washers and nuts on studs projecting through opposite side of surface, and tighten.
2. Back Bar and Brackets: Remove loose debris from substrate surface and install backbar
or bracket supports in position, so that signage is correctly located and aligned.
3.3 ADJUSTING AND CLEANING
A. Remove and replace damaged or deformed characters and signs that do not comply with
specified requirements. Replace characters with damaged or deteriorated finishes or
components that cannot be successfully repaired by finish touchup or similar minor repair
procedures.
B. Remove temporary protective coverings and strippable films as signs are installed.
C. On completion of installation, clean exposed surfaces of signs according to manufacturer's
written instructions, and touch up minor nicks and abrasions in finish. Maintain signs in a clean
condition during construction and protect from damage until acceptance by Owner.
3.4 SIGN SCHEDULE
A. See attached drawings and details by takeform, Inc. for the project "Cayuga Health - Carpenter
Park, Park Grove MOB - Exterior" for additional design information for signage.
END OF SECTION 101419
Received by DiMarco 02/25/2021
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 1 of 9
Type 1-n
Face Lit Channel Letters on a Raceway
LED Illumination
Mechanically Fasten to Curtain Wall
Mounting Hardware to Suit Wall Construction
QTY: 1 set
Notes:
Coordinate with Electrical
and refer to A160 - Roof
Plan for Roof Power
Supply Access Panel
locations.
Coordinate with Curtain
Wall manufacturer for
mounting specifications.
120V Electrical Service
Scale:
1/2” = 1’-0”
LET TERS & LOGOS
24.00"
36.00"
50.91"
292.00"
(24’-4”)
A
3/16” Translucent Acrylic with First Surface Applied Translucent Vinyl
Graphic / Font: Customer Supplied Artwork
printed to match PMS 3015 C Blue / printed to match PMS 3115 Light Blue / 230-156 Vivid Green / 7328 White
Faces
B 1” Trimcap
5687 White
Face Trim
C Painted, 5” Deep .040 Aluminum Channel Coil
CO104 White
Returns
D
Painted, 3 1/2” Deep Extruded Aluminum w/ Cover
SC-1970N / SC-1976N
Finish: TBD - Color Match Required
Mounting
A
B
C
Translucent Polycarbonate
Mounting Detail
Scale: 1 1/2” = 1’-0”Mounting Detail
Scale: 3” = 1’-0”
Curtain Wall Knife Plate
(by Others)
D
2” X 2” X 1/4” Aluminum Angle Mounting Brackets
Welded to Raceway Mounting Clip
Remote LED Power Supply
Resides in Soffit above Curtain Wall
- Refer to North Elevation
12.00"
7.25"
9.25"
12.00"5.00"
3.50"
Ø 0.56"
Ø1/2” 18-8 Stainless Steel Hardware
1.13"
2.50"
72.00" Typ.
Mullion
Mullion
Knife Plate Projection
1/2” Flexible Conduit
- Feed through Mullion
Low Voltage Wire
35 lbs
Raceway - 80 lbs
6 lbs 8 lbs 8 lbs 6 lbs 6 lbs 6 lbs6 lbs
8 lbs 8 lbs 8 lbs9 lbs 4 lbs
Received by DiMarco 02/25/2021
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 2 of 9
Notes:
Recommended path for power
feed to be coordinated with
curtain wall manufacturer and
installer.
Scale:
3/32” = 1’-0”
LET TERS & LOGOS
North Elevation - partial
Type 1-n
176’-4”
T/O Curtain Wall
158’-0”
Fifth Floor
144’-0”
Forth Floor
128’-6”
Third Floor
Access Panel to Power Supplies
on Back Side of Soffit Wall
Low Voltage Wire
PS
Received by DiMarco 02/25/2021
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 3 of 9
Type 1-e
Face Lit Channel Letters
LED Illumination
Mechanically Fasten thru Metal Composite Wall Panels into Substrate
Mounting Hardware to Suit Wall Construction
QTY: 1 set
Notes:
Coordinate with Electrical
and refer to A160 - Roof
Plan for Roof Power
Supply Access Panel
locations.
120V Electrical Service
Required
All penetrations to be sealed
Scale:
1/2” = 1’-0”
LET TERS & LOGOS
288.00"
(24’-0”)
A
3/16” Translucent Acrylic with First Surface Applied Translucent Vinyl
Graphic / Font: Customer Supplied Artwork
printed to match PMS 3015 C Blue / printed to match PMS 3115 Light Blue / 230-156 Vivid Green / 7328 White
Faces
B 1” Trimcap
5687 White
Face Trim
C Painted, 5” Deep .040 Aluminum Channel Coil
CO104 White
Returns
24.00"
36.00"
50.91"
A
Translucent Polycarbonate
Mounting Detail
Scale: 1 1/2” = 1’-0”
Remote
LED
Power
Supply
Architectural Panel Seams
B
C
5.00"
1.88"0.63"
Composite Metal Panel
Composite Polyisocyanurate Board
Insulation
Glass-mat Gypsum Sheathing
0.50"
6.50"
Low
Voltage
Wire
35 lbs
6 lbs 8 lbs 8 lbs 6 lbs 6 lbs 6 lbs6 lbs
8 lbs 8 lbs 8 lbs9 lbs 4 lbs
18-8 SS 1/4” X 3 1/2” Lag Bolt
Received by DiMarco 02/25/2021
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 4 of 9
Notes:
Scale:
3/32” = 1’-0”
LET TERS & LOGOS
East Elevation - partial
176’-4”
T/O Curtain Wall
158’-0”
Fifth Floor
144’-0”
Forth Floor
128’-6”
Third Floor
15.00"31.88"
Type 1-e Access Panel to Power Supplies
on Back Side of Soffit Wall
Wall Penetrations
Scale 3/8” = 1’-0”
Electrical Penetrations in Red
Type 1-e
Type 1-s
Received by DiMarco 02/25/2021
South Elevation - partial
Scale 1/4” = 1’-0”
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 5 of 9
Type 1-s
Face Lit Channel Letters
LED Illumination
Mechanically Fasten thru Metal Composite Wall Panels into Substrate
Mounting Hardware to Suit Wall Construction
QTY: 1 set
Notes:
Coordinate with Electrical
and refer to A160 - Roof
Plan for Roof Power
Supply Access Panel
locations.
Refer to page 3 of 9 for wall
section
120V Electrical Service
Required
Scale:
1/2” = 1’-0”
LET TERS & LOGOS
288.00"
(24’-0”)
Composite Metal Panel
A
3/16” Translucent Acrylic with First Surface Applied Translucent Vinyl
Graphic / Font: Customer Supplied Artwork
printed to match PMS 3015 C Blue / printed to match PMS 3115 Light Blue / 230-156 Vivid Green / 7328 White
Faces
B 1” Trimcap
5687 White
Face Trim
C Painted, 5” Deep .040 Aluminum Channel Coil
CO104 White
Returns
24.00"
36.00"
50.91"
A
B
C
Mounting Detail
Scale: 1 1/2” = 1’-0”
Remote LED Power Supply
5.00"54.00"
113.00"120.00"55.00"
Use Brake Formed Aluminum C Channel
as rigid mounting template
Dow 790 Silicone Building Sealant
1/4” Sch40 PVC Spacer (.54 OD)
2.97"
3.00"
18-8 SS 1/4” X 5” Lag Bolt
3.68"
3.71"
14.00"
35 lbs
6 lbs 8 lbs 8 lbs 6 lbs 6 lbs 6 lbs6 lbs
8 lbs 8 lbs 8 lbs9 lbs 4 lbs
Translucent Polycarbonate Architectural Panel Seams
Received by DiMarco 02/25/2021
Types 1-n, 1-e, 1-s
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 6 of 9
Notes:
Scale:
NTS
LET TERS & LOGOS
Received by DiMarco 02/25/2021
Profile
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 7 of 9
Notes:
Scale:
1/2” = 1’-0”
LET TERS & LOGOS
Type 1-w
Dimensional Logo
Stud Mount Flush to Brick
QTY: 1 set
A
Painted 1” Deep Fabricated Aluminum
Graphic: Customer Supplied Artwork
to match PMS 3015 C Blue / to match PMS 3115 Light Blue / to match PMS 347 C Green
Logo
B
1” Deep Fabricated Aluminum
Font: Customer Supplied Artwork
CO104 White
Logo Copy
24.00"
68.00"
36.00"
172.50"
1.00"Wall
B
A
Received by DiMarco 02/25/2021
West Elevation
Profile
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 8 of 9
Notes:
Site Survey Required
Refer to Customer Approved
Message Schedule for final
copy.
Scale:
3/4” = 1’-0”
LET TERS & LOGOS
Type Q-w
Dimensional Logo
Stud Mount to Brick
Stand Off - 1/2” to clear Decorative CMU
QTY: 1 set
Type Q-n
Dimensional Logo
Stand Off - 1/2” to clear Decorative CMU
QTY: 1 set
A Not Used
Not Used
B
1” Deep Fabricated Aluminum
Font: Customer Supplied Artwork
Clear Anodized - Vertical Grain
Copy
1.00"
Wall
1/2”
14.00"
North Elevation
BUILDING SIGNAGE14.00"
TBD Based on Message
BUILDING SIGNAGETBD Based on Message
B
Received by DiMarco 02/25/2021
Project:
Cayuga Health - Carpenter Park
Park Grove MOB - Exterior
Date:
04.16.20
Revisions:
01.04.21 JB
01.11.21 JB
01.26.21 JB
01.28.21 JB
Drawn By:
JB
Filename:
CAY0001_181614_EXT_Rev4
Rendering 9 of 9
Notes:
Scale:
1/4” = 1’-0”
LET TERS & LOGOS42.00"
West Elevation - partial
center above door
North Elevation - partial
EQ
EQ
23.00"
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
CUBICLE CURTAINS AND TRACK 102123 - 1
SECTION 102123 - CUBICLE CURTAINS AND TRACK
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Curtain tracks and carriers.
2. Cubicle curtains.
B. Related Requirements:
1. Section 061053 "Miscellaneous Rough Carpentry" for supplementary wood framing and
blocking for mounting items requiring anchorage.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include durability, laundry temperature limits, fade resistance, applied curtain treatment,
and fire-test-response characteristics for each type of curtain fabric indicated.
2. Include data for each type of track.
B. Shop Drawings:
1. Show layout and types of cubicles, sizes of curtains, number of carriers, anchorage
details, and conditions requiring accessories. Indicate dimensions taken from field
measurements.
2. Include details on blocking above ceiling.
C. Samples: For each exposed product and for each color and texture specified, 10 inches in size.
D. Curtain and Track Schedule: Use same designations indicated on Drawings.
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For curtains, track, and hardware to include in operation
and maintenance manuals.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
CUBICLE CURTAINS AND TRACK 102123 - 2
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials described below, before installation begins, that match products
installed and that are packaged with protective covering for storage and identified with labels
describing contents.
1. Curtain Carriers and Track End Caps: Full-size units equal to 3 percent of amount
installed, but no fewer than 10 units.
2. Curtains: Full-size units equal to 10 percent of amount installed, but no fewer than two
units.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Curtains: Provide curtain fabrics with the following characteristics:
1. Launderable to a temperature of not less than 160 deg F.
2. Flame resistant and identical to those that have passed NFPA 701 when tested by a
testing and inspecting agency acceptable to authorities having jurisdiction.
a. Identify fabrics with appropriate markings of a qualified testing agency.
2.2 CURTAIN SUPPORT SYSTEMS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. C/S General Cubicle.
2. InPro Corporation.
B. Extruded-Aluminum Curtain Track: Not less than 1-1/4 inches wide by 3/4 inch high;
manufacturer's standard wall thickness.
1. Curved Track: Factory-fabricated, 12-inch-radius bends.
2. Finish: Baked enamel, acrylic, or epoxy.
C. Curtain Track Accessories: Fabricate splices, end caps, connectors, end stops, coupling and
joining sleeves, wall flanges, brackets, ceiling clips, and other accessories from same material
and with same finish as track.
1. Suspended-Track Support: Not less than 5/8-inch- square tube.
2. End Stop: Removable with carrier hook.
D. Curtain Carriers: Two nylon rollers and nylon axle with chrome-plated steel hook.
E. Exposed Fasteners: Stainless steel.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
CUBICLE CURTAINS AND TRACK 102123 - 3
F. Concealed Fasteners: Stainless steel.
2.3 CURTAINS
A. Cubicle Curtain Fabric: Curtain manufacturer's standard, 100 percent polyester; inherently and
permanently flame resistant, stain resistant, and antimicrobial.
1. Products: Subject to compliance with requirements, provide the following:
a. Knoll Textiles.
2. Color: As indicated on Drawings.
B. Curtain Grommets: Two-piece, rolled-edge, rustproof, nickel-plated brass; spaced not more
than 6 inches o.c.; machined into top hem.
C. Mesh Top: Not less than 22-inch-high mesh top of No. 50 nylon mesh.
D. Curtain Tieback: Nickel-plated brass chain; one at each curtain termination.
2.4 CURTAIN FABRICATION
A. Fabricate curtains as follows:
1. Width: Equal to track length from which curtain is hung plus 10 percent added fullness,
but not less than 12 inches added fullness.
2. Length: Equal to floor-to-ceiling height, minus depth of track and carrier at top, and
minus clearance above the finished floor as follows:
a. Cubicle Curtains: 12 inches.
3. Mesh Top: Top hem of mesh not less than 1 inch and not more than 1-1/2 inches wide,
triple thickness, reinforced with integral web, and double lockstitched. Double
lockstitch bottom of mesh directly to 1/2-inch triple thickness, top hem of curtain fabric.
4. Bottom Hem: Not less than 1 inch and not more than 1-1/2 inches wide, double
thickness and double lock stitched.
5. Side Hems: Not less than 1/2 inch and not more than 1-1/4 inches wide, with double
turned edges, and single lockstitched.
B. Vertical Seams: Not less than 1/2 inch wide, double turned and double stitched.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance of the Work.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
CUBICLE CURTAINS AND TRACK 102123 - 4
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. General: Install tracks level and plumb, according to manufacturer's written instructions.
B. Up to 20 feet in length, provide track fabricated from single, continuous length.
1. Curtain Track Mounting: Suspended.
C. Suspended-Track Mounting: Install track with manufacturer's standard tubular aluminum
suspended supports at intervals and with fasteners recommended by manufacturer. Fasten
supports to structure. Provide supports at each splice and tangent point of each corner.
Secure ends of track to wall with flanged fittings or brackets.
D. Track Accessories: Install splices, end caps, connectors, end stops, coupling and joining
sleeves, and other accessories as required for a secure and operational installation.
E. Curtain Carriers: Provide curtain carriers adequate for 6-inch spacing along full length of
curtain plus an additional carrier.
F. Curtains: Hang curtains on each curtain track. Secure with curtain tieback.
END OF SECTION 102123
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FOLDING PANEL PARTITIONS 102239 - 1
SECTION 102239 - FOLDING PANEL PARTITIONS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Manually operated, acoustical panel partitions.
B. Related Requirements:
1. Section 055000 "Metal Fabrications" for supports that attach supporting tracks to
overhead structural system.
2. Section 092900 "Gypsum Board" for fire-rated assemblies and sound barrier construction
above the ceiling at track.
1.3 DEFINITIONS
A. NIC: Noise Isolation Class.
B. NRC: Noise Reduction Coefficient.
C. STC: Sound Transmission Class.
1.4 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.5 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Sustainable Design Submittals:
1. Chain-of-Custody Qualification Data: For manufacturer and vendor.
2. Laboratory Test Reports: For composite wood products, indicating compliance with
requirements for low-emitting materials.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FOLDING PANEL PARTITIONS 102239 - 2
C. Shop Drawings: For operable panel partitions.
1. Include plans, elevations, sections, attachment details.
2. Indicate stacking and operating clearances. Indicate location and installation requirements
for hardware and track, blocking, and direction of travel.
D. Samples for Initial Selection: For each type of exposed material, finish, covering, or facing.
E. Samples for Verification: For each type of exposed material, finish, covering, or facing,
prepared on Samples of size indicated below:
1. Textile Facing Material: Full width by not less than 36-inch- long section of fabric from
dye lot to be used for the Work, with specified treatments applied. Show complete pattern
repeat.
F. Delegated-Design Submittal: For operable panel partitions.
1. Include design calculations for seismic restraints that brace tracks to structure above.
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For operable panel partitions to include in maintenance
manuals.
1. In addition to items specified in Section 017823 "Operation and Maintenance Data,"
include the following:
a. Panel finish facings and finishes for exposed trim and accessories. Include
precautions for cleaning materials and methods that could be detrimental to finishes
and performance.
b. Seals, hardware, track, track switches, carriers, and other operating components.
1.7 QUALITY ASSURANCE
A. Certified Wood: Provide an invoice including vendor's chain-of-custody number, product cost,
and entity being invoiced.
B. Vendor Qualifications: A vendor that is certified for chain of custody by an FSC-accredited
certification body.
C. Installer Qualifications: An entity that employs installers and supervisors who are trained and
approved by manufacturer.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Protectively package and sequence panels in order for installation. Clearly mark packages and
panels with numbering system used on Shop Drawings. Do not use permanent markings on panels.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FOLDING PANEL PARTITIONS 102239 - 3
1.9 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of operable panel
partitions that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Faulty operation of operable panel partitions.
b. Deterioration of metals, metal finishes, and other materials beyond normal use.
2. Warranty Period: Two years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000
"Quality Requirements," to design seismic bracing of tracks to structure above.
B. Seismic Performance: Operable panel partitions shall withstand the effects of earthquake
motions determined according to ASCE/SEI 7.
1. The term "withstand" means "the partition panels will remain in place without separation
of any parts when subjected to the seismic forces specified."
C. Acoustical Performance: Provide operable panel partitions tested by a qualified testing agency
for the following acoustical properties according to test methods indicated:
1. Sound-Transmission Requirements: Operable panel partition assembly tested for
laboratory sound-transmission loss performance according to ASTM E 90, determined by
ASTM E 413, and rated for not less than the STC indicated.
D. Fire-Test-Response Characteristics: Provide panels with finishes complying with one of the
following as determined by testing identical products by a testing and inspecting agency
acceptable to authorities having jurisdiction:
1. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing
agency. Identify products with appropriate markings of applicable testing agency.
a. Flame-Spread Index: 25 or less.
b. Smoke-Developed Index: 450 or less.
2. Fire Growth Contribution: Complying with acceptance criteria of local code and
authorities having jurisdiction when tested according to NFPA 286.
2.2 OPERABLE ACOUSTICAL PANELS
A. Operable Acoustical Panels: Partition system, including panels, seals, finish facing, suspension
system, operators, and accessories.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FOLDING PANEL PARTITIONS 102239 - 4
1. Manufacturers: Subject to compliance with requirements, provide products by the
following:
a. Hufcor, Inc; Series 601.
B. Panel Operation: Manually operated, individual panels.
C. Panel Construction: As required to support panel from suspension components and with
reinforcement for hardware attachment. Fabricate panels with tight hairline joints and
concealed fasteners. Fabricate panels so finished in-place partition is rigid; level; plumb;
aligned, with tight joints and uniform appearance; and free of bow, warp, twist, deformation,
and surface and finish irregularities.
D. Dimensions: Fabricate operable acoustical panel partitions to form an assembled system of
dimensions indicated and verified by field measurements.
1. Panel Width: As indicated.
E. STC: Not less than 56.
F. Panel Weight: 12 lb/sq. ft. Insert value maximum.
G. Panel Thickness: Nominal dimension of 3 inches.
H. Panel Materials:
1. Recycled Content: Postconsumer recycled content plus one-half of preconsumer recycled
content.
2. Certified Wood: Wood products shall be certified as "FSC Pure" or "FSC Mixed Credit"
according to FSC STD-01-001 and FSC STD-40-004.
3. Adhesives: Use adhesives that meet the testing and product requirements of the
California Department of Public Health's "Standard Method for the Testing and
Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using
Environmental Chambers."
4. Composite Wood Products: Products shall be made using ultra-low-emitting
formaldehyde resins as defined in the California Air Resources Board's "Airborne Toxic
Control Measure to Reduce Formaldehyde Emissions from Composite Wood Products"
or shall be made with no added formaldehyde.
5. Steel Frame: Steel sheet, manufacturer's standard nominal minimum thickness for
uncoated steel.
6. Medium-Density Fiberboard: ANSI A208.2.
I. Panel Closure: Manufacturer's standard unless otherwise indicated.
J. Hardware: Manufacturer's standard as required to operate operable panel partition and
accessories; with decorative, protective finish.
1. Hinges: Concealed (invisible).
K. Finish Facing: Fabric wall covering.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FOLDING PANEL PARTITIONS 102239 - 5
2.3 SEALS
A. Description: Seals that produce operable panel partitions complying with performance
requirements and the following:
1. Manufacturer's standard seals unless otherwise indicated.
2. Seals made from materials and in profiles that minimize sound leakage.
3. Seals fitting tight at contact surfaces and sealing continuously between adjacent panels
and between operable panel partition perimeter and adjacent surfaces, when operable
panel partition is extended and closed.
B. Vertical Seals: Deep-nesting, interlocking astragals mounted on each edge of panel, with
continuous, resilient acoustical seal.
C. Horizontal Top Seals: Continuous-contact, resilient seal exerting uniform constant pressure on
track.
D. Horizontal Bottom Seals: Resilient, mechanical, retractable, constant-force-contact seal
exerting uniform constant pressure on floor when extended, ensuring horizontal and vertical
sealing and resisting panel movement.
1. Mechanically Operated for Acoustical Panels: Extension and retraction of bottom seal by
operating handle or built-in operating mechanism, with operating range not less than 2
inches between retracted seal and floor finish.
2.4 PANEL FINISH FACINGS
A. Description: Finish facings for panels that comply with indicated fire-test-response
characteristics and that are factory applied to operable panel partitions with appropriate
backing, using mildew-resistant nonstaining adhesive as recommended by facing
manufacturer's written instructions.
1. Apply one-piece, seamless facings free of air bubbles, wrinkles, blisters, and other
defects, with edges tightly butted, and with invisible seams complying with Shop
Drawings for location, and with no gaps or overlaps. Horizontal seams are not permitted.
Tightly secure and conceal raw and selvage edges of facing for finished appearance.
2. Where facings with directional or repeating patterns or directional weave are indicated,
mark facing top and attach facing in same direction.
3. Match facing pattern 72 inches above finished floor.
B. Fabric Wall Covering: 100 percent polyolefin woven fabric, from same dye lot, treated to resist
stains.
1. Color/Pattern: As scheduled on Drawings.
C. Trimless Edges: Fabricate exposed panel edges so finish facing wraps uninterrupted around
panel, covering edge and resulting in an installed partition with facing visible on vertical panel
edges, without trim, for minimal sightlines at panel-to-panel joints.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FOLDING PANEL PARTITIONS 102239 - 6
2.5 SUSPENSION SYSTEMS
A. Tracks: Steel or aluminum mounted directly to overhead structural support, designed for
operation, size, and weight of operable panel partition indicated. Size track to support partition
operation and storage without damage to suspension system, operable panel partitions, or
adjacent construction. Limit track deflection to no more than 0.10 inch between bracket
supports. Provide a continuous system of track sections and accessories to accommodate
configuration and layout indicated for partition operation and storage.
1. Panel Guide: Aluminum guide on both sides of the track to facilitate straightening of the
panels; finished with factory-applied, decorative, protective finish.
2. Head Closure Trim: As required for acoustical performance; with factory-applied,
decorative, protective finish.
B. Carriers: Trolley system as required for configuration type, size, and weight of partition and for
easy operation; with ball-bearing wheels.
C. Track Intersections, Switches, and Accessories: As required for operation, storage, track
configuration, and layout indicated for operable panel partitions, and compatible with partition
assembly specified. Fabricate track intersections and switches from steel or aluminum.
D. Steel Finish: Manufacturer's standard, factory-applied, corrosion-resistant, protective coating
unless otherwise indicated.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine flooring, floor levelness, structural support, and opening, with Installer present, for
compliance with requirements for installation tolerances and other conditions affecting
performance of operable panel partitions.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install operable panel partitions and accessories after other finishing operations, including
painting, have been completed in area of partition installation.
B. Install panels in numbered sequence indicated on Shop Drawings.
C. Broken, cracked, chipped, deformed, or unmatched panels are not acceptable.
D. Broken, cracked, deformed, or unmatched gasketing or gasketing with gaps at butted ends is
not acceptable.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FOLDING PANEL PARTITIONS 102239 - 7
E. Light-Leakage Test: Illuminate one side of partition installation and observe vertical joints and
top and bottom seals for voids. Adjust partitions for alignment and full closure of vertical joints
and full closure along top and bottom seals.
3.3 ADJUSTING
A. Adjust operable panel partitions, hardware, and other moving parts to function smoothly, and
lubricate as recommended by manufacturer.
3.4 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to
adjust, operate, and maintain operable panel partitions.
END OF SECTION 102239
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
WALL AND DOOR PROTECTION 102600 - 1
SECTION 102600 - WALL AND DOOR PROTECTION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Wall guards.
2. Corner guards.
3. Abuse-resistant wall coverings.
B. Related Requirements:
1. Section 087100 "Door Hardware" for metal protective trim units, according to
BHMA A156.6, used for armor, kick, mop, and push plates.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, impact strength, dimensions of
individual components and profiles, and finishes.
2. Include fire ratings of units recessed in fire-rated walls and listings for door-protection
items attached to fire-rated doors.
B. Sustainable Design Submittals:
1. Chain-of-Custody Certificates: For certified wood products. Include statement of costs.
2. Chain-of-Custody Qualification Data: For manufacturer and vendor.
3. Product Data: For adhesives, indicating VOC content.
4. Laboratory Test Reports: For adhesives, indicating compliance with requirements for
low-emitting materials.
5. Laboratory Test Reports: For composite wood products, indicating compliance with
requirements for low-emitting materials.
C. Shop Drawings: For each type of wall and door protection showing locations and extent.
1. Include plans, elevations, sections, and attachment details.
D. Samples for Verification: For each type of exposed finish on the following products, prepared
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
WALL AND DOOR PROTECTION 102600 - 2
on Samples of size indicated below:
1. Wall Guards: 12 inches long. Include examples of joinery, corners, end caps, and field
splices.
2. Corner Guards: 12 inches long. Include example top caps.
3. Abuse-Resistant Wall Covering: 6 by 6 inches square.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For each type of wall and door protection product to include in maintenance
manuals.
1. Include recommended methods and frequency of maintenance for maintaining best
condition of plastic covers under anticipated traffic and use conditions. Include
precautions against using cleaning materials and methods that may be detrimental to
finishes and performance.
1.5 QUALITY ASSURANCE
A. Certified Wood: Provide an invoice including vendor's chain-of-custody number, product cost,
and entity being invoiced.
B. Vendor Qualifications: A vendor that is certified for chain of custody by an FSC-accredited
certification body.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Store wall and door protection in original undamaged packages and containers inside
well-ventilated area protected from weather, moisture, soiling, extreme temperatures, and
humidity.
1. Maintain room temperature within storage area at not less than 70 deg F during the period
plastic materials are stored.
2. Keep plastic materials out of direct sunlight.
3. Store plastic wall- and door-protection components for a minimum of 72 hours, or until
plastic material attains a minimum room temperature of 70 deg F.
a. Store corner-guard covers in a vertical position.
b. Store wall-guard covers in a horizontal position.
1.7 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of wall- and
door-protection units that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
WALL AND DOOR PROTECTION 102600 - 3
a. Structural failures including detachment of components from each other or from
the substrates, delamination, and permanent deformation beyond normal use.
b. Deterioration of metals, metal finishes, plastics, and other materials beyond normal
use.
2. Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain wall- and door-protection products from single source from single
manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Surface Burning Characteristics: Comply with ASTM E 84 or UL 723; testing by a qualified
testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: 25 or less.
2. Smoke-Developed Index: 450 or less.
B. Regulatory Requirements: Comply with applicable provisions in ICC A117.1.
2.3 WALL GUARDS [TYPE: WP2]
A. Rub Rail : Standard-duty, PVC-free assembly consisting of continuous snap-on cover installed
over concealed, continuous retainer.
1. Manufacturers: Subject to compliance with requirements, provide products by the
following:
a. InPro Corporation (IPC); Palladium G2 BioBlend R4.
2. Cover: Extruded plastic, minimum 0.040-inch wall thickness; as follows:
a. Color and Texture: As indicated on Drawings.
3. Accessories: Concealed splices and mounting hardware.
4. Mounting: Surface mounted directly to wall.
2.4 CORNER GUARDS [TYPE: CG1, CG2]
A. Surface-Mounted, Plastic-Cover Corner Guards : Manufacturer's standard, PVC-free assembly
consisting of snap-on, resilient plastic cover installed over retainer; including mounting
hardware; fabricated with 90- or 135-degree turn to match wall condition.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
WALL AND DOOR PROTECTION 102600 - 4
1. Manufacturers: Subject to compliance with requirements, provide products by the
following:
a. InPro Corporation (IPC); Low Profile G2 BioBlend.
2. Cover: Extruded rigid plastic, minimum 0.100-inch wall thickness; as follows:
a. Profile: Nominal 1-1/2-inch- long leg and 1/4-inch corner radius.
b. Height: 8 feet .
c. Color and Texture: As indicated on Drawings.
2.5 ABUSE-RESISTANT WALL COVERINGS [TYPE: WP1]
A. Abuse-Resistant Sheet Wall Covering : Fabricated from semirigid, plastic sheet wall-covering
material.
1. Manufacturers: Subject to compliance with requirements, provide products by the
following:
a. InPro Corporation (IPC); Palladium G2 BioBlend.
2. Size: 48 by 96 inches for sheet.
3. Sheet Thickness: 0.040 inch .
4. Color and Texture: As indicated on Drawings.
5. Height: As indicated.
6. Trim and Joint Moldings: Extruded rigid plastic that matches wall-covering color.
7. Mounting: Adhesive.
2.6 MATERIALS
A. Fasteners: Aluminum, nonmagnetic stainless-steel, or other noncorrosive metal screws, bolts,
and other fasteners compatible with items being fastened. Use security-type fasteners where
exposed to view.
B. Adhesive: As recommended by protection product manufacturer.
1. Adhesives shall have a VOC content of 70 g/L or less.
2. Adhesive shall comply with the testing and product requirements of the California
Department of Public Health's "Standard Method for the Testing and Evaluation of
Volatile Organic Chemical Emissions from Indoor Sources Using Environmental
Chambers."
2.7 FABRICATION
A. Fabricate wall and door protection according to requirements indicated for design,
performance, dimensions, and member sizes, including thicknesses of components.
B. Factory Assembly: Assemble components in factory to greatest extent possible to minimize
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
WALL AND DOOR PROTECTION 102600 - 5
field assembly. Disassemble only as necessary for shipping and handling.
C. Quality: Fabricate components with uniformly tight seams and joints and with exposed edges
rolled. Provide surfaces free of wrinkles, chips, dents, uneven coloration, and other
imperfections. Fabricate members and fittings to produce flush, smooth, and rigid hairline joints.
2.8 FINISHES
A. Protect finishes on exposed surfaces from damage by applying a strippable, temporary
protective covering before shipping.
B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of
approved Samples and are assembled or installed to minimize contrast.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and wall areas, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance of the Work.
B. Examine walls to which wall and door protection will be attached for blocking, grounds, and
other solid backing that have been installed in the locations required for secure attachment of
support fasteners.
1. For wall and door protection attached with adhesive, verify compatibility with and
suitability of substrates, including compatibility with existing finishes or primers.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Complete finishing operations, including painting, before installing wall and door protection.
B. Before installation, clean substrate to remove dust, debris, and loose particles.
3.3 INSTALLATION
A. Installation Quality: Install wall and door protection according to manufacturer's written
instructions, level, plumb, and true to line without distortions. Do not use materials with chips,
cracks, voids, stains, or other defects that might be visible in the finished Work.
B. Mounting Heights: Install wall and door protection in locations and at mounting heights
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
WALL AND DOOR PROTECTION 102600 - 6
indicated on Drawings.
C. Accessories: Provide splices, mounting hardware, anchors, trim, joint moldings, and other
accessories required for a complete installation.
1. Provide anchoring devices and suitable locations to withstand imposed loads.
2. Where splices occur in horizontal runs of more than 20 feet, splice aluminum retainers
and plastic covers at different locations along the run, but no closer than 12 inches apart.
3. Adjust end caps as required to ensure tight seams.
D. Abuse-Resistant Wall Covering: Install top and edge moldings, corners, and divider bars as
required for a complete installation.
3.4 CLEANING
A. Immediately after completion of installation, clean plastic covers and accessories using a
standard ammonia-based household cleaning agent.
B. Remove excess adhesive using methods and materials recommended in writing by
manufacturer.
END OF SECTION 102600
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
TOILET, BATH, AND LAUNDRY ACCESSORIES 102800 - 1
SECTION 102800 - TOILET, BATH, AND LAUNDRY ACCESSORIES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Public-use washroom accessories.
2. Healthcare accessories.
3. Childcare accessories.
4. Custodial accessories.
1.3 COORDINATION
A. Coordinate accessory locations with other work to prevent interference with clearances required
for access by people with disabilities, and for proper installation, adjustment, operation,
cleaning, and servicing of accessories.
B. Deliver inserts and anchoring devices set into concrete or masonry as required to prevent
delaying the Work.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components
and profiles, and finishes.
2. Include anchoring and mounting requirements, including requirements for cutouts in
other work and substrate preparation.
3. Include electrical characteristics.
B. Product Schedule: Indicating types, quantities, sizes, and installation locations by room of each
accessory required.
1. Identify locations using room designations indicated.
2. Identify accessories using designations indicated.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
TOILET, BATH, AND LAUNDRY ACCESSORIES 102800 - 2
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: For accessories to include in maintenance manuals.
1.6 WARRANTY
A. Manufacturer's Special Warranty for Mirrors: Manufacturer agrees to repair or replace mirrors
that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, visible silver spoilage defects.
2. Warranty Period: 15 years from date of Substantial Completion.
B. Manufacturer's Special Warranty for Hand Dryers: Manufacturer agrees to repair or replace
hand dryers that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Seven years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 OWNER-FURNISHED MATERIALS
A. Owner-Furnished Materials: As indicated on Drawings.
2.2 PERFORMANCE REQUIREMENTS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
B. Structural Performance: Design accessories and fasteners to comply with the following
requirements:
1. Grab Bars: Installed units are able to resist 250 lbfconcentrated load applied in any
direction and at any point.
2. Heavy Duty Grab Bars: Installed units are able to resist 900 lbf concreted load applied in
any direction and at any point.
3. Shower Seats: Installed units are able to resist 250 lbf applied in any direction and at any
point.
2.3 PUBLIC-USE WASHROOM ACCESSORIES
A. Source Limitations: Obtain public-use washroom accessories from single source from single
manufacturer.
B. Manufacturers: Subject to compliance with requirements, provide Basis-of-Design products as
indicated in this Section or comparable products by one of the following:
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
TOILET, BATH, AND LAUNDRY ACCESSORIES 102800 - 3
1. AJW Architectural Products.
2. American Specialties, Inc.
3. Bobrick Washroom Equipment, Inc.
4. Bradley Corporation.
C. Toilet Tissue (Roll) Dispenser:
1. Description: Single-roll dispenser .
2. Mounting: Surface mounted.
3. Capacity: Designed for 4-1/2- or 5-inch- diameter tissue rolls.
4. Material and Finish: Chrome-plated zinc alloy (zamac) or steel.
D. Paper Towel (Folded) Dispenser:
1. Mounting: Surface mounted.
2. Minimum Capacity: 400 C-fold or 525 multifold towels.
3. Material and Finish: Stainless steel, ASTM A480/A480M No. 4 finish (satin).
4. Lockset: Tumbler type.
E. Automatic Soap Dispenser:
1. Description: Automatic dispenser with infrared sensor to detect presence of hands;
battery powered; designed for dispensing soap in liquid or lotion form.
2. Mounting: Surface mounted.
3. Capacity: 16 oz.
4. Refill Indicator: LED indicator.
5. Low-Battery Indicator: LED indicator.
F. Grab Bar:
1. Mounting: Flanges with concealed fasteners.
2. Material: Stainless steel, 0.05 inch thick.
a. Finish: Smooth, ASTM A480/A480M No. 4 finish (satin) on ends and slip-resistant
texture in grip area.
3. Outside Diameter: 1-1/2 inches.
4. Configuration and Length: As indicated on Drawings.
G. Mirror Unit:
1. Frame: Stainless steel angle, 0.05 inch thick.
a. Corners: Welded and ground smooth.
2. Size: As indicated on Drawings.
3. Hangers: Manufacturer's standard rigid, tamper and theft resistant.
H. Hook:
1. Description: Single-prong unit.
2. Mounting: Concealed.
3. Material and Finish: Polished chrome-plated zinc alloy (zamac).
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
TOILET, BATH, AND LAUNDRY ACCESSORIES 102800 - 4
2.4 HEALTHCARE ACCESSORIES
A. Specimen Pass-Through Cabinet:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
a. AJW Architectural Products.
b. American Specialties, Inc.
c. Bobrick Washroom Equipment, Inc.
d. Bradley Corporation.
2. Description: Two-sided type, with self-closing, interlocking doors on both sides, that
prevent both from being open at same time, and removable stainless steel tray .
3. Nominal Wall Opening: Insert dimensions, width by height.
4. Material and Finish: Stainless steel, ASTM A480/A480M No. 4 finish (satin).
5. Lockset: Tumbler type.
B. Glove Box Holders:
1. Products: Subject to compliance with requirements, provide Health Care Logistics, Inc.
MODEL #17896.
2. Triple box holder with dividers.
3. Keyhole slots for mounting vertically.
2.5 CHILDCARE ACCESSORIES
A. Diaper-Changing Station:
1. Manufacturers: Subject to compliance with requirements, provide products by the
following:
a. Koala Kare Products; a Division of Bobrick.
2. Description: Horizontal unit that opens by folding down from stored position and with
child-protection strap.
a. Engineered to support minimum of 250-lb static load when opened.
3. Mounting: Surface mounted, with unit projecting not more than 4 inches from wall when
closed.
4. Operation: By pneumatic shock-absorbing mechanism.
5. Material and Finish: HDPE in manufacturer's standard color.
6. Liner Dispenser: Provide built-in dispenser for disposable sanitary liners.
2.6 CUSTODIAL ACCESSORIES
A. Custodial Mop and Broom Holder:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
TOILET, BATH, AND LAUNDRY ACCESSORIES 102800 - 5
following:
a. AJW Architectural Products.
b. American Specialties, Inc.
c. Bobrick Washroom Equipment, Inc.
d. Bradley Corporation.
2. Description: Unit with shelf, hooks, holders, and rod suspended beneath shelf.
3. Length: 36 inches.
4. Hooks: Four.
5. Mop/Broom Holders: Three, spring-loaded, rubber hat, cam type.
6. Material and Finish: Stainless steel, ASTM A480/A480M No. 4 finish (satin).
a. Shelf: Not less than nominal 0.05-inch- thick stainless steel.
b. Rod: Approximately 1/4-inch- diameter stainless steel.
2.7 MATERIALS
A. Steel Sheet: ASTM A1008/A1008M, Designation CS (cold rolled, commercial steel),
0.036-inch- minimum nominal thickness.
B. Galvanized-Steel Sheet: ASTM A653/A653M, with G60 hot-dip zinc coating.
C. Galvanized-Steel Mounting Devices: ASTM A153/A153M, hot-dip galvanized after
fabrication.
D. Fasteners: Screws, bolts, and other devices of same material as accessory unit, unless otherwise
recommended by manufacturer or specified in this Section, and tamper and theft resistant where
exposed, and of stainless or galvanized steel where concealed.
E. Mirrors: ASTM C1503, Mirror Glazing Quality, clear-glass mirrors, nominal 6.0 mm thick.
2.8 FABRICATION
A. General: Fabricate units with tight seams and joints, and exposed edges rolled. Hang doors and
access panels with full-length, continuous hinges. Equip units for concealed anchorage and with
corrosion-resistant backing plates.
B. Keys: Provide universal keys for internal access to accessories for servicing and resupplying.
Provide minimum of six keys to Owner's representative.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install accessories according to manufacturers' written instructions, using fasteners appropriate
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
TOILET, BATH, AND LAUNDRY ACCESSORIES 102800 - 6
to substrate indicated and recommended by unit manufacturer. Install units level, plumb, and
firmly anchored in locations and at heights indicated.
1. Remove temporary labels and protective coatings.
B. Grab Bars: Install to comply with specified structural-performance requirements.
3.2 ADJUSTING AND CLEANING
A. Adjust accessories for unencumbered, smooth operation. Replace damaged or defective items.
B. Clean and polish exposed surfaces according to manufacturer's written instructions.
END OF SECTION 102800
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
MANUFACTURED FIREPLACES 103100 - 1
SECTION 103100 - MANUFACTURED FIREPLACES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Manufactured electric fireplaces.
2. Fireplace accessories.
B. Related Requirements:
1. Section 061053 "Miscellaneous Rough Carpentry."
1.3 REFERENCES
A. UL 127 - Standard for Factory-Built Fireplaces.
B. NFPA - 70 - National Electric Code.
1.4 PREINSTALLATION MEEINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.5 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: Provide large-scale drawings of required clearances, rough-in of enclosure,
limits of non-combustible and combustible materials, and utilities.
1.6 CLOSEOUT SUBMITTALS
A. Closeout Submittals: Provide manufacturer's maintenance instructions that include
recommendations for periodic checking and adjustment and periodic cleaning and maintenance
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
MANUFACTURED FIREPLACES 103100 - 2
of all components.
1.7 QUALITY ASSURANCE
A. Manufacturer Qualifications: Manufacturer with a minimum of 5 years experience
manufacturing similar products.
B. Installer Qualifications: Installer with a minimum 2 years experience with the type of products
specified and approved by the manufacturer or Certified by the National Fireplace Institute.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Store products in manufacturer's unopened packaging until ready for installation.
1.9 SEQUENCING
A. Ensure that locating templates and other information required for installation of products of this
section are furnished to affected trades in time to prevent interruption of construction progress.
B. Ensure that products of this section are supplied to affected trades in time to prevent
interruption of construction progress.
1.10 PROJECT CONDITIONS
A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits
recommended by manufacturer for optimum results. Do not install products under
environmental conditions outside manufacturer's absolute limits.
1.11 WARRANTY
A. Provide manufacturer's limited lifetime warranty covering combustion chamber heat exchanger,
stainless steel burner, logs, ceramic glass against thermal breakage, gold plated parts against
tarnishing, porcelain enameled surfaces and aluminum extrusion trim.
PART 2 - PRODUCTS
2.1 MANUFACTURED ELECTRIC FIREPLACES
A. General:
1. Comply with applicable building codes.
2. UL Listed.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
MANUFACTURED FIREPLACES 103100 - 3
B. Basis-of-Design Product: Provide Regency Fireplace Products, Inc.; Skope E110 43-Inch
Multi-Sided Fireplace.
C. Unit Information:
1. Front width: 45-7/16 inches.
2. Height: 22-3/8 inches.
3. Depth: 10-7/8 inches.
4. BTU/Hour Input: 5,000 BTU/Hour.
D. Flame Color and Fuel Bed Color: As selected by Architect from manufacturer's full range of
options.
E. Fuel Effects: As selected by Architect from manufacturer's full range.
2.2 FIREPLACE MANTELS
A. Mantle Surround and Base Finishing Trims: As selected by Architect from manufacturer's full
range.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Do not begin installation until substrates have been properly prepared.
B. If substrate preparation is the responsibility of another installer, notify Contractor of
unsatisfactory preparation before proceeding.
C. Verify proper power supply and fuel source are available.
3.2 PREPARATION
A. Clean surfaces thoroughly prior to installation.
B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best
result for the substrate under the project conditions.
3.3 INSTALLATION
A. Install in accordance with manufacturer's instructions, ANSI Z21.44 and the requirements of
authorities having jurisdiction.
B. Use manufacturer's guidelines for minimum clearances to combustibles, walls, and finishes.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
MANUFACTURED FIREPLACES 103100 - 4
C. Set fireplace units plumb, level, and rigid
D. Anchor all components firmly in position.
E. Connect to power supply and control wiring in accordance with NFPA 70.
F. Upon completion of installation, visually inspect all exposed surfaces. Touch up scratches and
abrasions with touch up paint recommended by the manufacturer; make imperfections invisible
to the unaided eye from a distance of 5 feet.
3.4 PROTECTION
A. Protect installed products until completion of project.
B. Touch-up, repair or replace damaged products before Substantial Completion.
END OF SECTION 103100
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FIRE PROTECTION CABINETS 104413 - 1
SECTION 104413 - FIRE PROTECTION CABINETS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Fire-protection cabinets for the following:
a. Portable fire extinguishers.
B. Related Requirements:
1. Section 104416 "Fire Extinguishers."
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product. Show door hardware, cabinet type, trim style, and
panel style. Include roughing-in dimensions and details showing recessed-, semirecessed-, or
surface-mounting method and relationships of box and trim to surrounding construction.
B. Product Schedule: For fire-protection cabinets. Indicate whether recessed, semirecessed, or
surface mounted. Coordinate final fire-protection cabinet schedule with fire-extinguisher
schedule to ensure proper fit and function. Use same designations indicated on Drawings.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For fire-protection cabinets to include in maintenance manuals.
1.5 COORDINATION
A. Coordinate size of fire-protection cabinets to ensure that type and capacity of fire extinguishers
indicated are accommodated.
B. Coordinate sizes and locations of fire-protection cabinets with wall depths.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FIRE PROTECTION CABINETS 104413 - 2
PART 2 - PRODUCTS
2.1 FIRE-PROTECTION CABINET
A. Cabinet Type: Suitable for fire extinguisher.
1. Products: Subject to compliance with requirements, provide one of the following:
a. Guardian Fire Equipment, Inc.; 1800 SERIES.
b. JL Industries, Inc.; a division of the Activar Construction Products Group;
AMBASSADOR.
c. Larsens Manufacturing Company; Architectural.
B. Cabinet Construction: Nonrated.
C. Recessed Cabinet:
1. Trimless with Hidden Flange: Flange of same metal and finish as box overlaps
surrounding wall finish and is concealed from view by an overlapping door.
D. Cabinet Trim Material: Steel sheet.
E. Door Material: Steel sheet.
F. Door Style: Vertical duo panel with frame.
G. Door Glazing: Fully-tempered glass.
H. Door Hardware: Manufacturer's standard door-operating hardware of proper type for cabinet
type, trim style, and door material and style indicated.
1. Provide manufacturer's standard.
I. Accessories:
1. Mounting Bracket: Manufacturer's standard steel, designed to secure fire extinguisher to
fire-protection cabinet, of sizes required for types and capacities of fire extinguishers
indicated, with plated or baked-enamel finish.
2. Lettered Door Handle: One-piece, cast-iron door handle with the word "FIRE" embossed
into face.
3. Identification: Lettering complying with authorities having jurisdiction for letter style,
size, spacing, and location. Locate as directed by Architect.
a. Identify fire extinguisher in fire-protection cabinet with the words "FIRE
EXTINGUISHER."
1) Location: Applied to cabinet door.
2) Application Process: Pressure-sensitive vinyl letters.
3) Lettering Color: Red.
4) Orientation: Vertical.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FIRE PROTECTION CABINETS 104413 - 3
4. Wall-Mounted Signage: Rigid plastic identification signs visible from a distance on either
side of cabinet.
J. Materials:
1. Cold-Rolled Steel: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B.
a. Finish: Baked enamel or powder coat.
b. Color: White.
2.2 FABRICATION
A. Fire-Protection Cabinets: Provide manufacturer's standard box (tub) with trim, frame, door, and
hardware to suit cabinet type, trim style, and door style indicated.
1. Weld joints and grind smooth.
2. Provide factory-drilled mounting holes.
B. Cabinet Doors: Fabricate doors according to manufacturer's standards, from materials indicated
and coordinated with cabinet types and trim styles.
1. Fabricate door frames with tubular stiles and rails and hollow-metal design, minimum 1/2
inch thick.
2. Miter and weld perimeter door frames.
C. Cabinet Trim: Fabricate cabinet trim in one piece with corners mitered, welded, and ground smooth.
2.3 GENERAL FINISH REQUIREMENTS
A. Comply with NAAMM's AMP 500, "Metal Finishes Manual for Architectural and Metal
Products," for recommendations for applying and designating finishes.
B. Protect mechanical finishes on exposed surfaces of fire-protection cabinets from damage by
applying a strippable, temporary protective covering before shipping.
C. Finish fire-protection cabinets after assembly.
D. Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of
approved Samples and are assembled or installed to minimize contrast.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine walls and partitions for suitable framing depth and blocking where recessed cabinets
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FIRE PROTECTION CABINETS 104413 - 4
will be installed.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Prepare recesses for recessed fire-protection cabinets as required by type and size of cabinet
and trim style.
3.3 INSTALLATION
A. General: Install fire-protection cabinets in locations and at mounting heights indicated or, if not
indicated, at heights indicated below:
1. Fire-Protection Cabinets: 54 inches above finished floor to top of cabinet.
B. Fire-Protection Cabinets: Fasten cabinets to structure, square and plumb.
1. Unless otherwise indicated, provide recessed fire-protection cabinets. If wall thickness is
inadequate for recessed cabinets, provide semirecessed fire-protection cabinets.
2. Fasten mounting brackets to inside surface of fire-protection cabinets, square and plumb.
C. Identification: Apply vinyl lettering at locations indicated.
3.4 ADJUSTING AND CLEANING
A. Remove temporary protective coverings and strippable films, if any, as fire-protection cabinets
are installed unless otherwise indicated in manufacturer's written installation instructions.
B. Adjust fire-protection cabinet doors to operate easily without binding.
C. On completion of fire-protection cabinet installation, clean interior and exterior surfaces as
recommended by manufacturer.
D. Touch up marred finishes, or replace fire-protection cabinets that cannot be restored to
factory-finished appearance. Use only materials and procedures recommended or furnished by
fire-protection cabinet and mounting bracket manufacturers.
E. Replace fire-protection cabinets that have been damaged or have deteriorated beyond
successful repair by finish touchup or similar minor repair procedures.
END OF SECTION 104413
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FIRE EXTINGUISHERS 104416 - 1
SECTION 104416 - FIRE EXTINGUISHERS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes portable, hand-carried fire extinguishers.
B. Related Requirements:
1. Section 104413 "Fire Protection Cabinets."
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product. Include rating and classification, material descriptions,
dimensions of individual components and profiles, and finishes for fire extinguisher.
B. Product Schedule: For fire extinguishers. Coordinate final fire-extinguisher schedule with
fire-protection cabinet schedule to ensure proper fit and function. Use same designations
indicated on Drawings.
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For fire extinguishers to include in maintenance manuals.
1.5 COORDINATION
A. Coordinate type and capacity of fire extinguishers with fire-protection cabinets to ensure fit and
function.
1.6 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or
replace fire extinguishers that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FIRE EXTINGUISHERS 104416 - 2
a. Failure of hydrostatic test according to NFPA 10.
b. Faulty operation of valves or release levers.
2. Warranty Period: Six years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. NFPA Compliance: Fabricate and label fire extinguishers to comply with NFPA 10, "Portable
Fire Extinguishers."
B. Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent
testing agency acceptable to authorities having jurisdiction.
1. Provide fire extinguishers approved, listed, and labeled by FM Global.
2.2 PORTABLE, HAND-CARRIED FIRE EXTINGUISHERS
A. Fire Extinguishers: Type, size, and capacity for each fire-protection cabinet indicated.
1. Products: Subject to compliance with requirements, provide the following:
a. Guardian Fire Equipment, Inc; 4000 SERIES.
b. JL Industries, Inc.; a division of the Activar Construction Products Group;
COSMIC SERIES.
c. Larsens Manufacturing Company; MP SERIES.
2. Valves: Manufacturer's standard.
3. Handles and Levers: Manufacturer's standard.
4. Instruction Labels: Include pictorial marking system complying with NFPA 10,
Appendix B, and bar coding for documenting fire-extinguisher location, inspections,
maintenance, and recharging.
B. Multipurpose Dry-Chemical Type in Steel Container: UL-rated 4-A:60-B:C, 10-lb nominal
capacity, with monoammonium phosphate-based dry chemical in enameled-steel container.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine fire extinguishers for proper charging and tagging.
1. Remove and replace damaged, defective, or undercharged fire extinguishers.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
FIRE EXTINGUISHERS 104416 - 3
3.2 INSTALLATION
A. General: Install fire extinguishers and mounting brackets in locations indicated and in
compliance with requirements of authorities having jurisdiction.
END OF SECTION 104416
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
PHENOLIC LOCKERS 105100 - 1
SECTION 105100 PHENOLIC LOCKERS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Solid phenolic lockers.
B. Related Requirements:
1. Section 061053 "Miscellaneous Rough Carpentry" for blocking.
1.3 ACTION SUBMITTALS
A. Product Data: Manufacturer's data sheets for each type of product indicated include
fabrication details, description of materials and finishes.
B. Shop Drawings: Include overall locker dimensions, floor plan, elevations, sections, details,
and attachments to other work. Include choice of options with details.
C. Samples for Approval: Furnish a physical sample of the material in the selected color.
1. Size: 6 by 6 inch in type of finish specified.
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications: Manufacturer with minimum 5 years experience in the
manufacture of phenolic lockers.
B. Installers Qualifications: An experienced Installer regularly engaged in the installation of
lockers for a minimum of 3 years.
C. Source Limitations: Obtain phenolic lockers and trim accessories from single manufacturer.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
PHENOLIC LOCKERS 105100 - 2
D. Accessibility Requirements: Comply with requirements of ADA/ABA and with requirements of
authorities having jurisdiction.
E. Surface-Burning Characteristics: As determined by testing identical products according to
ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of
applicable testing agency.
1. Flame-Spread Index: 25 or less.
2. Smoke-Developed Index: 450 or less.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Do not deliver phenolic lockers to the site until the building is enclosed and HVAC systems are
in operation. Deliver phenolic lockers in manufacturer's original packaging. Store in an
upright condition. Protect phenolic lockers from exposure to direct sunlight.
B. Ship phenolic lockers fully assembled.
C. Lift and handle phenolic lockers from the base not the sides.
1.7 WARRANTY
A. Special Manufacturer’s Warranty: 20 year against defects in materials.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire Ratings: Core of panel shall meet fire Class B resistance per ASTM E84.
2.2 MANUFACTURERS
A. Basis-of-Design Product: Subject to compliance with requirements, provide Summit Lockers,
Inc.; Phenolic Lockers, or comparable product by one of the following:
1. American Specialities, Inc,. ASI Group Storage Solutions
2. Hadrian Manufacturing Inc.
B. Materials:
1. Panels: Decorative papers impregnated with a melamine resin on faces with a clear
protective overcoat and integrally compression molded within a core consisting of solid
phenolic impregnated kraft papers.
2. Stainless-Steel: ASTM A 666, Type 304.
3. Fasteners: Tamper-Resistant Fasteners: Stainless steel torx-head screws.
a. Locker Connectors: No. 10-24 sex bolts.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
PHENOLIC LOCKERS 105100 - 3
b. Anchors: Type and size required for secure anchorage.
c. Drilled-in-place Masonry Anchors: Minimum 1/4 by 1-3/4 inch screws.
2.3 MULTI-HEIGHT LOCKERS
A. Locker Configurations: Multiple height two tier units with full-height garment and half-height
accessory storage compartments.
B. “Z" Locker Dimensions
1. Height, Nominal: 72 inches.
2. Width: 12 inches.
3. Depth: 12 inches.
C. Sides, Tops, Bottoms, Dividers, and Shelves: 3/8 inch thick phenolic with smooth finish.
D. Locker Tops: Slope top.
E. Doors: Fabricate from a single piece 1/2 inch phenolic.
1. Handle: ADA/ABA-compliant handle fabricated from injection molded plastic.
2. Locks: Stainless steep hasp for combination padlocks by Owner.
3. Hinges: Include three (3) hinges for doors greater than 36-inches tall or two (2) hinges
for all other heights.
a. Standard Lockers: Opens 90-degrees.
b. ADA Lockers: Continuous 180-degree swing type 304 stainless steel and attached
with stainless steel tamper-resistant screws.
F. Color: As indicated on Drawings.
G. Accessories:
1. End Panels: 1/2 inch (13mm) thick, with color and finish matching locker body.
2. Filler Panels: 1/2 inch phenolic filler panel, with color and finish matching locker body.
3. Wall Hooks: Stainless steel hook, two per locker.
4. Number Plate: Black plastic with reverse engraved characters, surface mounted with
permanent adhesive. Provide one per locker.
a. Numbering sequence to be provided by Owner.
5. Adjustable Locker Base: Adjustable locker feet with 1/2-inch solid phenolic kick plate,
color matched with lockers.
6. Coat Rod: Stainless steel coat rod.
2.4 LOCKER FABRICATION
A. Hardware Attachment: All hinges, handles, hasps, hooks, latch bars, and locks attached with
tamper-resistant screws.
B. Provide manufacturer's optional additional ventilated panels.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
PHENOLIC LOCKERS 105100 - 4
C. Continuous Base: Set toe clearance 3 inch from locker front. Notch end caps for ease of
installation.
D. Continuous Sloping Tops: Fabricated in lengths indicated, without visible fasteners at splice
locations; and finished to match lockers.
E. Filler Panels: Fabricated in unequal leg angle shape; finished to match lockers.
F. Finished End Panels: Fabricated with wide edge dimension, configured to conceal fasteners
and holes at exposed ends of phenolic lockers.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install lockers in climate controlled environment, shielded from direct sunlight.
B. General: Install on floor or other firm support. Install level, plumb, and true.
1. Position locker base per approved shop drawing. Using fasteners provided by
manufacturer, anchor base sections to the floor.
2. Attach filler pieces to lockers with male-female sex bolts.
3. Position first locker according to submittal layout. Square and plumb the locker using
concealed shims. Secure the locker to the wall at the top and bottom of the locker.
Position second locker next to first, square and plumb to align the tops and bottoms; and
temporarily clamp lockers together. Drill four holes through the sides of the lockers and
connect lockers using sex bolts provided by manufacturer.
C. Accessories: Fit exposed connections of trim, fillers, and closures together to form tight,
hairline joints, with concealed fasteners and splice plates furnished by locker manufacturer.
Install as indicated on approved shop drawings.
1. Coat Hooks: Attach with at least two fasteners.
2. Coat Rods: Attach at height indicated.
3. Identification Plates: Identify phenolic lockers with approved identification numbers.
Attach plates to each locker door.
4. Filler Panels: Attach with concealed fasteners.
5. Sloping Tops: Attach sloping-tops to phenolic lockers, with closures at exposed ends.
6. Finished End Panels: Attach at ends indicated.
3.2 FINAL CLEANING
A. Clean locker interior and exterior surfaces.
B. Remove packaging and construction debris and legally dispose of off-site.
END OF SECTION 105100
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
ALUMINUM EXTERIOR SUN CONTROL DEVICES 107100 - 1
SECTION 107100 – ALUMINUM EXTERIOR SUN CONTROL DEVICES
PART 1 - GENERAL
1.1 SUMMARY
A. This section includes vertical aluminum sunshades.
1.2 REFERENCES
A. Products and executions are specified in this section by reference to the following industry
and/or tradeA 2605 – High Performance Organic Coatings on Architectural Extrusion and
Panels.
1. ASCE 7 – Minimum Design Loads for Buildings and Other Structures
2. ASTM B 209 – Standard Specification for Aluminum and Aluminum-Alloy Sheet and
Plate.
3. ASTM B 221 – Standard Specification for Aluminum and Aluminum-Alloy Extruded
Bars, Rods, Wire, Profiles and Tubes.
4. ASTM D 822 – Standard Practice for Filtered Open-Flame Carbon-Arc Exposures of
Paint and Related Coatings.
5. ASTM D 4214 – Standard Test Methods for Evaluating the Degree of Chalking of
Exterior Paint Films.
1.3 PERFORMANCE REQUIREMENTS
A. Sunshades shall be manufactured to withstand wind loads, acting inwards and outwards.
1. Minimum design loads shall be calculated to comply with ASCE – 7 and CBC
requirements.
B. Sunshades shall be manufactured to withstand the specified seismic loads.
1. Minimum design loads shall be calculated to comply with ASCE – 7 and CBC
requirements.
C. Sunshades shall be manufactured to withstand the thermal stress to which the sunshades will be
subjected to.
1. Base engineering on a surface design temperature change of 180 degrees F (82 degrees C).
D. Sunshades shall be designed to perform under conditions specified herein or required by site
conditions with no permanent damage to or deforming of the sunshade blades or assembly or
noise to metal fatigue caused by sunshade blade rattle or flutter or permanent damage to
fasteners and anchors.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
ALUMINUM EXTERIOR SUN CONTROL DEVICES 107100 - 2
1.4 ACTION SUBMITTALS
A. Product data: Manufacturers technical and descriptive data on each product to be used.
B. Shop Drawings:
1. Submit for architect’s approval prior to commencement of any work or fabrication under
this section, detailed shop drawings showing all areas of work profiles and sections of all
components, finishes and fastening details.
C. Structural Calculations: Submit comprehensive analysis of design loads, dead, live, snow, wind
and thermal movements. Calculations shall be stamped and signed by a professional engineer
registered in the jurisdiction where the project is located.
D. Samples: For each finish product specified, submit sample of grid screen to show blades,
fasteners, accessories, finish and color.
1.5 QUALITY ASSURANCE
A. Structural Requirements: Design and fabricate so installed sunshades support gravity loads and
loads of related components as required for proper support and rigidity of configurations
indicated, including provisions for deflection, expansion and contraction forces.
B. AWS D1.2M: Certify that each welder employed in fabrication of work of this section has
satisfactorily passed all AWS qualification tests for welding processes involved and, if
pertinent, has undergone recertification.
C. Installer Qualifications: As determined by contractor, experienced installer to perform work of
this section to have not less than five (5) years experience in product installation.
D. Obtain sunshade devices from one source of a single manufacturer.
1.6 PROJECT CONDITIONS
A. Field Measurements: Verify actual measurements/openings by field measurements before
fabrication; show recorded measurements on shop drawings. Coordinate field measurements,
fabrication schedule with construction progress to avoid delays.
B. Deliver materials to the job site ready for erection. Assembled units to be packaged and shipped
to prevent damage during freight and storage on site.
1.7 WARRANTY
A. Warranty Period: The work in this section shall be guaranteed against defects in material and
workmanship for a period of one (1) year from date of substantial completion. Contractor shall
replace and repair any defects at no cost to the owner.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
ALUMINUM EXTERIOR SUN CONTROL DEVICES 107100 - 3
B. Finish Warranty: Refer to “Conditions of the Contract” for finish warranty provisions.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products as indicated on
Drawings by Architectural Grilles and Sunshades, Inc. (AGS, Inc.); 22442 Fey Drive,
Frankfort, IL 60423. Phone: (708) 479-9458, Fax: (708) 479-9478. Contact: Eric Niemeyer
(eric@agsshade.com).
1. Distributor: JHC Sales Corp. Contact: Jim Crane, Phone: (914)388-3655,
jim@jhcsales.com.
2.2 SUNSHADES
A. Basis-of-Design Product: Subject to compliance with requirements, provide Architectural
Grilles & Sunshades, Inc. (AGS, INC); Custom Vertical Sunshades 1-1/2" thick x 14 inches
deep by length as indicated on Drawings.
B. Attachment Brackets to be AGS Inc. 6” knife Plate – Extruded Aluminum “T” 6063-T6
C. Fasteners – Unless otherwise noted, fasteners devices shall be 300 series non-magnetic stainless
steel. ASTM A-304, grade A or better.
D. Components to be shop assembled in large practical sections to allow for immediate erection.
2.3 FINISHES
A. General: Finish on exposed aluminum shall be compliant with the performance standards set
forth in AAMA Specifications 2605-98 "Superior Performing Organic Coatings on Aluminum."
B. Type: Factory-applied, high performance, 70% Polyvinylidene Fluoride (PVDF) coating
based on Elf Atochem Inc. Kynar 500 or Ausimont USA Inc. Hylar 5000 resin, formulated by a
licensed paint manufacturer, and applied by paint manufacturer’s warranty-approved applicator
complying with performance standards as outlined in AAMA Specifications 2605.
C. Pretreatment: Applicator to pretreat the aluminum with solutions to remove organic and
inorganic surface soils, remove residual oxides, followed by a chrome phosphate conversion
coating - at minimum 40 mg/square foot – to ensure adhesion of paint to the aluminum.
D. Application: Kynar 3 Coat: One primer coat, one metallic color coat, and one clear top coat.
1. Dry Film Thickness: Minimum of 1.6 mils.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
ALUMINUM EXTERIOR SUN CONTROL DEVICES 107100 - 4
E. Color: Selected by Architect from the following:
1. Architect to submit custom color sample for matching.
PART 3 - EXECUTION
3.1 FIELD DIMENSIONS
A. Verify conditions: Examine areas where work is to be performed and identify any conditions
that could be detrimental to proper or timely completion.
B. General Contractor Shall field confirm openings and elevations as shown on shop drawings
prior to fabrication.
C. Installation should not proceed until all conditions are satisfactory.
3.2 ERECTION
A. Preparation
1. Surface preparation: Clear sunshade to remove all dirt, debris, and loose particles prior to
installation.
2. Protection: Take all necessary steps to prevent damage to material during installation as
required in manufacturer’s installation instruction.
B. Installation
1. Qualified installer needs to comply with manufacturer’s installation instructions.
2. Verify all dimensions and the supporting structure and provide accurate field
measurements, so that the sunshades will be properly designed, fabricated and fitted to
the structure.
3. Anchor sunshade to the building per the architectural drawings.
4. Erection Tolerances:
a. A maximum of +/- 1/8” (non cumulative) tolerance between any column to column
spacing is acceptable.
b. Offsets in end-to-end or edge-to-edge alignment of consecutive members: 1/32”.
5. Do not cut or trim any sunshade components without written approval by AGS, Inc.
6. Do not erect any damaged or deformed members. Remove or replace any damaged
members in the erection process as directed by AGS, Inc.
7. Set sunshade units level, plumb, with uniform joints.
8. Qualified installer to erect after all adjacent painting, roofing and masonry has been
completed.
Received by DiMarco 02/25/2021
Park Grove - Cayuga Medical Center
MEDICAL OFFICE BUILDING
Cayuga Park, Ithaca, NY 14850
HOLT Project No. 2018089
ALUMINUM EXTERIOR SUN CONTROL DEVICES 107100 - 5
3.3 CLEANING
A. Clean exterior sunshades surfaces to prevent buildup of dust and debris, refer to AGS, Inc.
cleaning instructions based on the finish of the material.
3.4 PROTECTION
A. Protect sunshade materials after installation to prevent damage by other tradespersons.
END OF SECTION 107100