Loading...
HomeMy WebLinkAboutP106 Roof Plan1235ABCEF3.94" RD-A4" RD-A6" RD-A6" RD-A4" VTR4" VTR4" VTR4" VTR123803573SNSEWYORKOFETAT SSOIANLEOFPRLI C E N S E DREENIGN ETRASS N EJ.CIRER EXCELSIOR°°°°°°°°DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEFG1234567891012345678910ArchitecturePlanningInterior Design1112HI1112HI619 West State StreetIthaca, New York 14850132 E. Jefferson StreetSyracuse, New York 13202p 607 273 7600 www.holt.com2/10/2021 2:07:14 PMP106ROOF PLAN02/05/20212018089WABCayuga Park, Ithaca, New York 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDINGN3/16" = 1'-0"1ROOF PLANDRAWING NOTES:1PROVIDE NON-FREEZE ROOF HYDRANT WITH GALVANIZED CASING AND ADJUSTABLE FLOW WHEEL LOCK HANDLE WITH DECK FLANGE AND UNDER DECK CLAMP EQUAL TO JAY R SMITH MODEL 5906-H. PROVIDE VACUUM BREAKER. 1/8”DRAIN HOLE MUST BE PIPED AND DISCHARGED TO AN ACCEPTABLE DISCHARGE POINT. REFER TO DETAIL DRAWING(S).2CONNECT 3/4" INDIRECT WASTE TO HEAT PUMP (BY MECHANICAL CONTRACTOR). REFER TO DETAIL DRAWING(S).3TERMINATE 3/4" INDIRECT WASTE 6" ABOVE FINISHED ROOF. SLEEVE AND SEAL THROUGH EXTERIOR WALL.1. COORDINATE ALL VENT THROUGH ROOF (VTR) WITH HVACCONTRACTOR. ALL VENT TERMINATIONS ABOVE ROOF SHALL BE A MINIMUM 25'-0" (HEALTHCARE) AWAY FROM ANY HVAC OUTSIDE AIR INTAKE (ROOFTOP UNIT, LOUVER, ETC). OR AT LEAST 3 FEET ABOVE WINDOW, DOOR, OPENING, AIR INTAKE OR VENT SHAFT.GENERAL NOTES:REVISION SCHEDULENAME DATEReceived by DiMarco 2/15/2021