HomeMy WebLinkAboutM106 Roof Plan12345ABCE3.8F3.9DOAS-1DOAS-3DOAS-23500 lbs.3500 lbs.3000 lbs.ACCU-1ESERVES 5TH FLOOR ONLYSERVES FLOORS 1 THRU 4SERVES FLOORS 1 THRU 4ACCU-1NACCU-2EACCU-2NACCU-3EACCU-3NACCU-4EACCU-4N750 lbs. (TYP. 15)ACCU-5EACCU-5NACCU-1WACCU-2WACCU-3WACCU-4WSTRUCTURAL ENGINEER TO PROVIDE 24" HIGH STANDS TO MOUNT ACCU'S TOACCU-5WACCU-5SACCU-4SACCU-3SACCU-2SACCU-1S750 lbs. (TYP. 5)PROVIDE CONDENSING UNITS ON STANDS, STANDS BY OTHERS. INSTALL PER MANUFACTURER'S WRITTEN INSTRUCTIONS, MAINTAIN ALL REQUIRED CLEARANCES.VRF PIPING FROM 1ST THRU 4TH FLOOR ACCU'S DOWN THRU CHASE TO FLOORS BELOW, (TYP.12)VRF PIPING FROM 5TH FLOOR ACCU'S DOWN TO FLOOR BELOW, (TYP.3)VRF PIPING FROM 1ST THRU 4TH FLOOR ACCU'S DOWN THRU CHASE TO FLOORS BELOW, (TYP.4)X26"x20"24"x20"XX20"x12"CU-18ACU-18B150 lbs. (TYP. 11)CU-18CCU-18DCU-18ECU-18FCU-18GCU-18HCU-18IPROVIDE PIPE SUPPORTS EVERY 24", SECURE PIPE SUPPORT TO ROOF DECK. MAINTAIN A MINIMUM OF 24" FROM THE BOTTOM OF THE PIPE TO THE TOP OF ROOF, REFER TO ARCH PLANS FOR ROOF THICKNESS.PROVIDE PIPE SUPPORTS EVERY 24", SECURE PIPE SUPPORT TO ROOF DECK. MAINTAIN A MINIMUM OF 24" FROM THE BOTTOM OF THE PIPE TO THE TOP OF ROOF, REFER TO ARCH PLANS FOR ROOF THICKNESS.PROVIDE DUCY SUPPORTS EVERY 48", SECURE DUCT SUPPORT TO ROOF DECK. MAINTAIN A MINIMUM OF 24" FROM THE BOTTOM OF THE DUCT TO THE TOP OF ROOF, REFER TO ARCH PLANS FOR ROOF THICKNESS.PROVIDE DUCY SUPPORTS EVERY 48", SECURE DUCT SUPPORT TO ROOF DECK. MAINTAIN A MINIMUM OF 24" FROM THE BOTTOM OF THE DUCT TO THE TOP OF ROOF, REFER TO ARCH PLANS FOR ROOF THICKNESS.PROVIDE DUCY SUPPORTS EVERY 48", SECURE DUCT SUPPORT TO ROOF DECK. MAINTAIN A MINIMUM OF 24" FROM THE BOTTOM OF THE DUCT TO THE TOP OF ROOF, REFER TO ARCH PLANS FOR ROOF THICKNESS.VRF PIPING FROM ACCU-5S DOWN TO FLOOR BELOW, (TYP.3)EF-1560150 lbs.CU-24ACU-48AAC-24A803573SNSEWYORKOFETAT SSOIANLEOFPRLI C E N S E DREENIGN ETRASS N EJ.CIRER EXCELSIOR°°°°°°°°DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEFG1234567891012345678910ArchitecturePlanningInterior Design1112HI1112HI619 West State StreetIthaca, New York 14850132 E. Jefferson StreetSyracuse, New York 13202p 607 273 7600 www.holt.com2/10/2021 2:03:36 PMM106ROOF PLAN02/05/20212018089JCC, CTLCayuga Park, Ithaca, New York 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING3/16" = 1'-0"1ROOF PLANNGENERAL NOTES:A. PROVIDE AEROSEAL COMMERCIAL DUCT SEALING OR APPROVED ALTERNATE TO ALL OUTSIDE AIR AND EXHAUST DUCTWORK SERVING ALL THREE DOAS UNITS.INSTALL PER MANUFACTURER’S WRITTEN INSTRUCTIONS.REVISION SCHEDULENAME DATEReceived by DiMarco 2/15/2021