HomeMy WebLinkAboutFP001 Legend & General NotesGENERAL NOTES:1. THE FIRE PROTECTION SYSTEM DESIGN, INSTALLATION AND MATERIALSSHALL CONFORM TO THE FIRE CODE AND AUTHORITIES HAVINGJURISDICTION. IN CASE OF CONFLICTS WITH CODES, DRAWINGS, ORSPECIFICATIONS, THE MOST STRINGENT SHALL PREVAIL.2. BEFORE COMMENCEMENT OF WORK, THE CONTRACTOR SHALL VERIFYTHE EXACT LOCATIONS, ELEVATIONS AND CHARACTERISTICS OF ALLUTILITIES AND PIPING, AND SHALL IMMEDIATELY NOTIFY THE ARCHITECTOF ANY DISCREPANCIES.3. THE DRAWINGS WERE PREPARED WITH THE BEST STRUCTURAL ANDARCHITECTURAL INFORMATION AVAILABLE. IT IS UNDERSTOOD THATEQUIPMENT LOCATIONS AND ROUTING OF PIPING MAY VARY FROM THATSHOWN ON THE PLANS AS CONSTRUCTION PROCEEDS.4. THESE DRAWINGS DO NOT INCLUDE ALL NECESSARY SAFETYREQUIREMENTS. CONTRACTOR TO COMPLY TO THE SAFETYREQUIREMENTS SET FORTH BY THE LOCAL AUTHORITIES HAVINGJURISDICTION.5. THESE DRAWINGS ARE FOR BIDDING PURPOSES ONLY. THEY AREESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT MANY OFFSETS,BENDS, UNIONS, SPECIFIC FITTINGS AND EXACT LOCATIONS ARE NOTINDICATED.6. ALL FIRE PROTECTION WORK SHALL BE INSTALLED SO AS TO AVOIDINTERFERENCE WITH ELECTRICAL EQUIPMENT, MECHANICALEQUIPMENTAND STRUCTURAL FRAMING, SKYLIGHTS, ETC.7. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILINGACCESS PANELS WITH THE ARCHITECTURAL REFLECTED CEILING PLANAND ELECTRICAL LIGHTING PLAN.8. COORDINATE ALL LOCATIONS, SIZES AND ELEVATIONS OF ALL SLEEVESTHROUGH WALLS, BEAMS, SLABS AND FOOTING WITH STRUCTURAL ANDARCHITECTURAL DRAWINGS. ALL PIPES SLEEVING THROUGH BEAMS ORFOOTINGS SHALL HAVE A SLEEVE DIAMETER OF TWO PIPE SIZES OVERTHE PIPE PASSING THROUGH THE FOOTING OR PER STRUCTURALDRAWING. THE MOST STRINGENT SHALL PREVAIL.9. PIPING SUPPORTS. ALL PIPING TO BE SUPPORTED WITH HANGERS ANDBRACKETS WHICH PROVIDE ISOLATION FROM FRAMING. CONTACTBETWEEN PIPE AND SUPPORT TO BE LINED WITH PLASTIC OR FELT.10.ALL FLOOR AND WALL PENETRATIONS MUST BE SEALED WATERTIGHTAND VERMIN PROOF.11.FIRE PROTECTION CONTRACTOR SHALL COORDINATE COMPLETE FIREPROTECTION INSTALLATION AND REQUIREMENTS PRIOR TO SUBMITTINGBID WITH ALL LOCAL DISTRICTS AND GOVERNING AUTHORITIES. INCLUDEALL FINDINGS WITHIN THE BASE BID.12.PROVIDE ALL WORK IN COMPLIANCE WITH ALL LOCAL, STATE ANDFEDERAL CODES. OBTAIN ALL REQUIRED PERMITS. COORDINATE ALLWORK WITH LOCAL FIRE MARSHAL.13. PROVIDE CUTTING, CORING AND PATCHING OF ALL WALLS, SLABS ANDDECKS AS REQUIRED FOR WORK SHOWN. COORDINATE ALL WORK WITHOWNER AND GENERAL CONTRACTOR.14. REFER TO ARCHITECTURAL DRAWINGS AND THE PROJECTSPECIFICATIONS FOR PROJECT PHASING REQUIREMENTS.15.PROVIDE FULL SPRINKLER COVERAGE FOR ALL SPACES WITHIN THEPROJECT AREA IN COMPLIANCE WITH LOCAL, STATE AND FEDERALCODES, NFPA-13 AND OWNER'S INSURANCE CARRIER/UNDERWRITER.16.PROVIDE FULL SPRINKLER COVERAGE FOR ALL SPACES WITHIN THEPROJECT AREA IN COMPLIANCE WITH LOCAL, STATE AND FEDERALCODES, NFPA-13 AND OWNER'S INSURANCE CARRIER/UNDERWRITER.17. PROVIDE SPRINKLER SHOP DRAWINGS AND HYDRAULIC CALCULATIONSWITH ALL INFORMATION NOTED BY NFPA-13. DO NOT START ANY WORKUNTIL DRAWINGS AND CALCULATIONS HAVE BEEN APPROVED BY THEPROJECT ENGINEER, OWNER'S AGENTS AND LOCAL FIRE MARSHAL.18.OBTAIN WATER FLOW TEST DATA (PRESSURES AND FLOWS) ASREQUIRED. PROVIDE ALL FLOW TESTS REQUIRED IF CURRENT TESTDATA IS UNAVAILABLE.19.COORDINATE SPRINKLER SYSTEM WITH ALL OTHER TRADES, BUILDINGCONDITIONS, ETC. OFFSET SPRINKLER SYSTEM PIPING AS REQUIRED(PROVIDE ALL FITTINGS, CONNECTIONS, ETC.)20.FOR ALL AREAS WITH LAY-IN CEILINGS, PROVIDE SPRINKLERS IN THECENTER OF CEILING TILES (2x2 PATTERN). REFER TO ARCHITECTURALPLAN FOR CEILING GRID LAYOUT.21. THE SPRINKLER/FIRE PROTECTION CONTRACTOR SHALL HYDRAULICALLYCALCULATE ALL SPRINKLER SYSTEMS SHOWN ON THE DRAWING ANDSHALL SIZE PIPING ACCORDINGLY.22.SUBMITTALS AND SHOP DRAWINGS: AS SOON AS POSSIBLE AND WITHIN21 DAYS AFTER AWARD OF THE CONTRACT, AND BEFORE THEIRPURCHASE, THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT 6BOUND BOOKLETS FOR APPROVAL AND CONTAINING A COMPLETE LISTOF MATERIALS, SPECIALTIES AND EQUIPMENT HE IS TO FURNISH FORTHE INSTALLATION. ALL SUBMITTALS SHALL BE MADE AT ONE TIME. NODEVIATION OF PLUMBING FIXTURES WILL BE ACCEPTED. BASED ONAPPROVAL OF ALTERNATE PRIOR TO BID.23. COORDINATE FIRE PROTECTION SYSTEMS WITH WORK OF ALL OTHERTRADES PRIOR TO ANY FABRICATION OR INSTALLATION.24.ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THEEQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND APPLICABLECODES, PROVIDE ALL FITTINGS, VALVES, AND OTHER DEVICES REQUIREDFOR A COMPLETE WORKABLE INSTALLATION.25. MAINTENANCE LABEL SHALL BE AFFIXED TO ALL FIRE PROTECTIONEQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TOOWNER'S REPRESENTATIVE.26.FIRE PROTECTION CONTRACTOR SHALL LAYOUT SPRINKLER SYSTEM.COORDINATE WITH ALL OTHER TRADES, AND SHALL PROVIDE SPRINKLERSHOP DRAWINGS AND HYDRAULIC CALCULATIONS. SPRINKLER PIPINGSHALL BE SIZED HYDRAULICALLY.27. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS OVER 4FEET WIDE SUCH AS DUCTS, OPEN GRATE FLOORING AND OVERHEADDOORS.28. COORDINATE WITH ELECTRICAL TRADE PRIOR TO ORDERINGELECTRICALLY OPERATED EQUIPMENT FOR AVAILABLE VOLTAGES ATEQUIPMENT LOCATIONS.29.PIPE SIZE DISCREPANCIES BETWEEN FLOOR PLANS AND RISERDIAGRAMS LARGER PIPE SIZE INDICATED WILL TAKE PRECEDENCE.30.THESE PLANS INDICATE APPROXIMATE ROUGH-INS ONLY FOREQUIPMENT NOT IN THIS SECTION (N.I.T.S.) EXACT ROUGH-INDIMENSIONS MUST BE OBTAINED FROM THE EQUIPMENTMANUFACTURER.31. THE FIRE PROTECTION CONTRACTOR SHALL COORDINATE ALLREQUIREMENTS FOR ALL POINTS OF CONNECTION WITH THE GENERALCONTRACTOR AND OTHER TRADES PRIOR TO BID.32.FIRE PROTECTION CONTRACTOR SHALL LAYOUT SPRINKLER SYSTEM,COORDINATE WITH ALL OTHER TRADES, AND SHALL PROVIDE SPRINKLERSHOP DRAWINGS AND HYDRAULIC CALCULATIONS. SPRINKLER PIPINGSHALL BE SIZED HYDRAULICALLY.33.CONTRACTOR SHALL PROVIDE ALL VALVES AND BACKFLOW PREVENTIONDEVICES AS REQUIRED BY STATE AND LOCAL CODES.34.SPRINKLER HEADS WITHIN ATTIC SPACE SHALL BE 212 F.35. PROVIDE CORROSIVE COATING ON SPRINKLER HEADS IN POOL.APPLICABLE CODES:THE INTERNATIONAL FIRE CODE.NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.NFPA 14: STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS.NFPA 25: RECOMMENDED PRACTICE FOR THE INSPECTION, TESTING ANDMAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS.SPRINKLER SYSTEM DESCRIPTION:THE FIRE PROTECTION SYSTEM SHALL BE A WETPIPE AUTOMATICSPRINKLER SYSTEM ARRANGED TO PROPERLY PROTECT ALL SPACESAS INDICATED.STANDPIPE SYSTEM DESCRIPTION:THE STANDPIPE SYSTEM SHALL BE A WET MANUAL CLASS I STANDPIPESYSTEM.FLOW TEST DATA:STATIC PRESSURE94PSIRESIDUAL PRESSURE62PSIFLOW1900GPMCLASSIFICATION OF OCCUPANCIES:1.LIGHT HAZARD:WATER DENSITY:0.10 GPM/SQ. FT.HYDRAULIC REMOTE AREA:1500 SQ. FT.COMBINED HOSE DEMAND:100 GPMWATER DENSITY:0.15 GPM/SQ. FT.HYDRAULIC REMOTE AREA:1500 SQ. FT.COMBINED HOSE DEMAND:250 GPM2. ORDINARY GROUP I:SYSTEM PROTECTION AREA LIMITATIONS:LIGHT HAZARD:52,000 SQ. FT.ORDINARY HAZARD: 52,000 SQ. FT.TSSYMBOLDESCRIPTIONSHUT OFF VALVE WITH TAMPER SWITCH (TS)FLOW SWITCH (FS)FIRE PROTECTION SYMBOLS LISTREMOVE TO THIS POINTNEW TO EXISTING CONNECTIONEXISTING PIPINGPIPING TO BE REMOVEDDROP CONNECTIONELBOW UPDIRECTION OF FLOWCAP OR PLUGCHECK VALVEPRESSURE GAGEBACKFLOW PREVENTERDRY PIPE VALVEALARM CHECK VALVESIDEWALL SPRINKLER HEADPENDENT SPRINKLER HEADSEMI-RECESSED SPRINKLER HEADUPRIGHT SPRINKLER HEADCONCEALED SPRINKLER HEADFIRE DEPARTMENT CONNECTION (FDC)PIPE CONTINUATION (SINGLE LINE)PIPE CONTINUATION (DOUBLE LINE)BREAKBUTTERFLY VALVEPUMPFIRE HYDRANTELBOW DOWNFSNOTE: NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECTNEW PIPINGEXHIBIT "B" - PIPING MATERIALS (FIRE PROTECTION)(NOTES AT END OF EXHIBIT "B")SERVICEPIPE MATERIALFITTINGSCONNECTIONSSPRINKLER(WET)SCHEDULE 40, BLACK STEEL2" AND SMALLERMALLEABLEORDUCTILE IRONTHREADEDSCHEDULE 10, BLACK STEEL 2 1/2" AND LARGERMALLEABLEORDUCTILE IRONROLL GROOVED MECHANICAL TYPE COUPLINGSFIRE STANDPIPESCHEDULE 40, BLACK STEEL2-1/2" AND SMALLERMALLEABLE IRONTHREADEDSCHEDULE 10, BLACK STEEL3" AND LARGERMALLEABLEORDUCTILE IRONROLL GROOVED MECHANICAL TYPE RIGID COUPLINGSFIRE SERVICEDUCTILE IRONW/CEMENT LININGBELL & SPIGOTMECHANICAL OR GROOVED RUBBER GASKETUSE GALVANIZED STEEL PIPE AND FITTINGS FOR ALL ABOVEGROUND EXTERIOR LOCATIONS PASSING THROUGH EXTERIOR WALLS AND WHERE CALLED FOR.NOTES FOR EXHIBIT BNOTE 1:ALL EXPOSED PIPING WITHIN FINISHED AREAS SHALL BE PAINTED WITH A PRIMER COAT AND TWO FINISH COATS. COLOR PER THE ARCHITECT/OWNER.NOTE 2:803573SNSEWYORKOFETAT SSOIANLEOFPRLI C E N S E DREENIGN ETRASS N EJ.CIRER EXCELSIOR°°°°°°°°DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEFG1234567891012345678910ArchitecturePlanningInterior Design1112HI1112HI619 West State StreetIthaca, New York 14850132 E. Jefferson StreetSyracuse, New York 13202p 607 273 7600 www.holt.com2/10/2021 1:59:41 PMFP001LEGEND &GENERALNOTES02/05/20212018089AuthorCayuga Park, Ithaca, New York 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDINGREVISION SCHEDULENAME DATEReceived by DiMarco 2/15/2021