HomeMy WebLinkAboutE503 DetailsFINISHED FLOORCEILINGAAB12AAB134" MINIMUMPROVIDE 1 1/4" CONDUITINSIDE NEW WALL TURNEDUP INTO CEILING SPACEWITH PULL STRINGPROVIDE 4 11/16" SQUARE x 2 1/8" MINIMUMDEPTH BACKBOX WITH SINGLE GANG DEVICERING TO MATCH WALL THICKNESS AND TYPEPROVIDE SINGLE GANG BACKBOXWITH DOUBLE DUPLEXRECEPTACLE, FLUSH MOUNTEDPROVIDE 1/2" CONDUIT INSIDE NEW WALL TURNEDUP INTO CEILING SPACENOTE:ONLY APPLIES FOR SITUATIONS WHERE DEVICE IS LOCATED ON EXISTING BLOCK WALLSA.FINISHED FLOORCEILINGAAB12AAB134" MINIMUMPROVIDE 1 1/4" CONDUITINSIDE NEW WALL TURNEDUP INTO CEILING SPACEWITH PULL STRINGPROVIDE 4 11/16" SQUARE x 2 1/8" MINIMUMDEPTH BACKBOX WITH SINGLE GANG DEVICERING TO MATCH WALL THICKNESS AND TYPEPROVIDE 2-GANG BACKBOXWITH DOUBLE DUPLEXRECEPTACLE, FLUSH MOUNTEDPROVIDE 1/2" CONDUIT INSIDE NEW WALL TURNEDUP INTO CEILING SPACENOTE:ONLY APPLIES FOR SITUATIONS WHERE DEVICE IS LOCATED ON EXISTING BLOCK WALLSA.GENERAL NOTES:FLASH AND SEAL ROOF PENETRATIONAS REQUIRED TO MAINTAIN ANYROOF WARRENTEE. PROVIDE THESERVICES OF A QUALIFIED ROOFINGCONTRACTOR.GALVANIZED CONDUIT(SIZE AS REQUIRED)SEALTIGHTCONNECTORWEATHERPROOF DUPLEX RECEPTACLEWITH SPRING LOADED CAP. KEY LOCKABLE,WEATHER-PROOF ENCLOSURE SHALLBE MARKED "SUITABLE FOR WETLOCATIONS WHILE IN-USE."WPGFICONTROL OUTPUTCOMMON+24V dcPOWER PACKLINENEUTRAL277VCEILING MOUNTEDOCCUPANCY SENSORCONTROL OUTPUTCOMMON+24V dcCONTROL OUTPUTCOMMON+24V dcADDITIONAL CEILINGMOUNTED OCCUPANCY SENSORAS REQUIRED3-WAYSWITCH3-WAYSWITCHLOAD-aLOAD-bWALLSWITCHaWALLSWITCHbPROVIDE 3-WAY AND/ORDUAL LEVEL SWITCHING ASCALLED FOR ON PLANSADDITIONAL CEILINGMOUNTED OCCUPANCY SENSORAS REQUIREDNORMAL CIRCUITNORMAL CONTROLSNORMAL LIGHTING LOADUL 924ALCRNORMAL SWITCH SIGNALEMERGENCY LIGHTING LOADEMERGENCY ONNORMAL POWER ON/OFFNORMAL SENSING SIGNALEMERGENCY CIRCUITNORMAL CIRCUITUL 924ALCREMERGENCY LIGHTING LOADEMERGENCY POWER ONNORMAL SENSING SIGNALEMERGENCY CIRCUITCONTROLSTANDEM NORMAL/EMERGENCY SWITCHINGSEPARATELY SWITCHED EMERGENCYNOTE: EMERGENCY LIGHTING LOAD TO BE POWERED VIA EMERGENCY CIRCUIT AND CONTROLLED VIA SWITCHING SHOWN ON PLANS. UPON LOSS OF NORMAL SENSING SIGNAL ALCR SHALL BYPASS SWITCHING AND PROVIDE UNINTERRUPTED POWER TO EMERGENCY LOAD.NOTE: EMERGENCY LIGHTING LOAD TO BE POWERED VIA EMERGENCY CIRCUIT AND CONTROLLED VIA SWITCHING FROM LOCAL ROOM NORMAL LIGHTING CONTROLS/SWITCHING SHOWN ON PLANS. UPON LOSS OF NORMAL SENSING SIGNAL ALCR SHALL BYPASS SWITCHING AND PROVIDE UNINTERRUPTED POWER TO EMERGENCY LOAD.ELECTRIC STRIKECEILINGFLOOR6"MAGNET SWITCHMAGNETCARD READER - SINGLEGANG BOX FLUSHMOUNTED (UNSECURE SIDE)3/4 " CONDUIT TO SECURITY PANELPASSIVE INFRARED DETECTOR (REX) (SECURESIDE) (MOUNTED TO DOOR FRAME HEADER ORCEILING)8"x8"x4" JUNCTION BOX LOCATEON SECURE SIDE OF DOOR3/4 " CONDUITGENERAL NOTES:120VAC POWER REQUIRED AT SECURITYPANEL. EXACT LOCATION TO BE DETERMINED.ALL POWER AND CONDUIT TO BE SUPPLIEDAND INSTALLED BY ELECTRICAL CONTRACTOR.A.B.803573SNSEWYORKOFETAT SSOIANLEOFPRLI C E N S E DREENIGN ETRASS N EJ.CIRER EXCELSIOR°°°°°°°°DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEFG1234567891012345678910ArchitecturePlanningInterior Design1112HI1112HI619 West State StreetIthaca, New York 14850132 E. Jefferson StreetSyracuse, New York 13202p 607 273 7600 www.holt.com2/10/2021 1:59:08 PME503DETAILS02/05/20212018089RSCayuga Park, Ithaca, New York 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING1TYPICAL NEW CONSTRUCTION FLUSH DATA OUTLET DETAIL2TYPICAL NEW CONSTRUCTION FLUSH DATA/QUAD OUTLET DETAIL3ROOF/EXTERIOR RECEPTACLE DETAIL4MULTIPLE OCCUPANCY SENSOR DETAIL5AUTOMATIC LOAD CONTROL RELAY WIRING DIAGRAM6DOOR SECURITY DETAILREVISION SCHEDULENAME DATEReceived by DiMarco 2/15/2021