HomeMy WebLinkAboutA002 Interior Wall & Fireproofing Systems2_
2A
2B
2C
2D
5_
5A
5B
5C
5D
1_
1A
1B
1C
1D
1E
3_
3A
3B
3C
3D
4_
4A
4B
4C
4D
7_
7A
7B
7C
7D
7E
9 FS-1RS-1RS-2EWS-1EWS-1EWS-1 EWS-1EWS-18
6_
6A
6B
6C
6D
6E
10 1211
EWS-1FS-1EWS-3
EWS-3
CEILING PLANE, SEE
REFLECTED CEILING PLANS
(2) 5/8"VARIES (2) 5/8"
6 1/8"
• EXTEND TO UNDERSIDE OF DECK
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS,
REFER TO UL DESIGN U419
• ACOUSTICAL PERFORMANCE - STC 50
• PROVIDE TILE BACKER PANEL, IN LIEU OF GYPSUM
BOARD AT LOCATIONS TO BE TILED
SEALANT, BOTH SIDES,
ENTIRE PERIMETER
UNDERSIDE OF DECK
GYPSUM BOARD
SOUND ATTENUATION
BLANKET
METAL STUDS @ 16" OC
GYPSUM BOARD
WALL BASE, SEE FINISH
SCHEDULE
SEALANT, BOTH SIDES,
ENTIRE PERIMETER
3-5/8" STUD
6" STUD
2 1/2" STUD
1 5/8" STUD
CEILING PLANE, SEE
REFLECTED CEILING PLANS
4 7/8"
VARIES (2) 5/8"SEALANT, ENTIRE
PERIMETER
UNDERSIDE OF DECK
METAL STUDS @ 16" OC
GYPSUM BOARD
WALL BASE, SEE FINISH
SCHEDULE
• EXTEND TO UNDERSIDE OF DECK
• PROVIDE TILE BACKER PANEL, IN LIEU OF GYPSUM
BOARD AT LOCATIONS TO BE TILED
SEALANT, ENTIRE
PERIMETER
3-5/8" STUD
6" STUD
2 1/2" STUD
1 5/8" STUD
• EXTEND TO UNDERSIDE OF DECK
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS,
REFER TO UL DESIGN U419
• ACOUSTICAL PERFORMANCE - STC 40
• PROVIDE TILE BACKER PANEL, IN LIEU OF GYPSUM
BOARD AT LOCATIONS TO BE TILED
5/8"VARIES 5/8"
4 7/8"
CEILING PLANE, SEE
REFLECTED CEILING PLANS
SEALANT, BOTH SIDES,
ENTIRE PERIMETER
UNDERSIDE OF DECK
GYPSUM BOARD
SOUND ATTENUATION
BLANKET
GYPSUM BOARD
SEALANT, BOTH SIDES,
ENTIRE PERIMETER
METAL STUDS @ 16" OC
WALL BASE, SEE FINISH
SCHEDULE
3-5/8" STUD
6" STUD
2 1/2" STUD
1 5/8" STUD
8" STUD
CEILING PLANE, SEE
REFLECTED CEILING PLANS
5/8"VARIES (2) 5/8"
5 1/2"
• EXTEND TO UNDERSIDE OF DECK
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS,
REFER TO UL DESIGN U419
• ACOUSTICAL PERFORMANCE -STC 45
• PROVIDE TILE BACKER PANEL, IN LIEU OF GYPSUM
BOARD AT LOCATIONS TO BE TILED
SEALANT, BOTH SIDES,
ENTIRE PERIMETER
UNDERSIDE OF DECK
GYPSUM BOARD
SOUND ATTENUATION
BLANKET
METAL STUDS @ 16" OC
GYPSUM BOARD
WALL BASE, SEE FINISH
SCHEDULE
SEALANT, BOTH SIDES,
ENTIRE PERIMETER
3-5/8" STUD
6" STUD
2 1/2" STUD
1 5/8" STUD
5/8"
CEILING PLANE, SEE
REFLECTED CEILING PLANS
VARIES
4 1/4"
SEALANT, ENTIRE
PERIMETER
UNDERSIDE OF DECK
METAL STUDS @ 16" OC
GYPSUM BOARD
WALL BASE, SEE FINISH
SCHEDULE
SEALANT, ENTIRE
PERIMETER
• EXTEND TO UNDERSIDE OF DECK
• PROVIDE TILE BACKER PANEL, IN LIEU OF GYPSUM
BOARD AT LOCATIONS TO BE TILED
3-5/8" STUD
6" STUD
2 1/2" STUD
1 5/8" STUD
CEILING PLANE, SEE
REFLECTED CEILING PLANS
• EXTEND TO UNDERSIDE OF DECK
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS,
REFER TO UL DESIGN U906
• ACOUSTICAL PERFORMANCE - STC 46 (HOLLOW CORE)
7 5/8"WITH STRUCTURAL1" TYPICALCOORDINATECOMPRESSIBLE FILLER
UNDERSIDE OF DECK
WALL BASE, SEE FINISH
SCHEDULE
VARIES
5/8"
METAL FURRING
GYPSUM BOARD
3-5/8" STUD
6" STUD
2 1/2" STUD
1 5/8" STUD
7/8" FURRING
CEILING PLANE, SEE
REFLECTED CEILING PLANS
3 3/4"
2 1/2"(2) 5/8"
1"
SEALANT, ENTIRE
PERIMETER
UNDERSIDE OF DECK
GYPSUM LINER
METAL CH STUD
GYPSUM BOARD
WALL BASE, SEE FINISH
SCHEDULE
SEALANT, ENTIRE
PERIMETER
• EXTEND TO UNDERSIDE OF DECK
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS,
REFER TO UL DESIGN U415, REFER TO NER-258 FOR
HORIZONTAL APPLICATIONS
• ACOUSTICAL PERFORMANCE - STC 52
• PROVIDE TILE BACKER PANEL, IN LIEU OF GYPSUM
BOARD AT LOCATIONS TO BE TILED
REFER TO FINISH PLANS
FOR FLOOR FINISH
CONCRETE SLAB
METAL DECK6 1/4"• REFER TO STRUCTURAL DRAWINGS FOR FLOOR SYSTEM
• 1-HOUR RATED PER UL DESIGN D902
• 2-HOUR RATED PER UL DESIGN D7992 5/8" MINSPRAY-APPLIED
FIREPROOFING
STEEL GIRDER/
BEAM/JOIST
REFER ALSO TO
STRUCTURAL
DRAWINGS
2 HOUR FLOOR SYSTEM,
SPRAYED FIREPROOFING
ON BEAM AND DECK
SPRAY-APPLIED
FIREPROOFING
ROOF SYSTEM
• REFER TO STRUCTURAL DRAWINGS FOR FLOOR SYSTEM
• 1-HOUR RATED PER UL DESIGN P819 (1-HOUR SPRAY-
APPLIED FIREPROOFING)
STEEL BEAM/JOIST
(W6x16 MINIMUM)SIMSPRAY-APPLIED
FIREPROOFING
5/8" GYPSUM
BOARD
8 1/2"8 1/2"1' - 5"7 1/2" 7 1/2"
1' - 3"
• 1-HOUR RATED UL DESIGN X829
2 1/2" NON-
STRUCTURAL
METAL FRAMING
2 1/2" NON-
STRUCTURAL
METAL FRAMING
STEEL COLUMN
8"8"
1 5/8" NON-STRUCTURAL
METAL FRAMING
• 1-HOUR RATED UL DESIGN X8298 1/2"6"SPRAY-APPLIED
FIREPROOFING
STEEL COLUMN
2 1/2" NON-STRUCTURAL
METAL FRAMING
5/8" GYPSUM BOARD1' - 2 1/2"1 5/8" NON-STRUCTURAL
METAL FRAMING 8"8"
1 5/8" NON-STRUCTURAL
METAL FRAMING
• 1-HOUR RATED UL DESIGN X8298 3/4"6"SPRAY-APPLIED
FIREPROOFING
STEEL COLUMN
2 1/2" NON-STRUCTURAL
METAL FRAMING
5/8" GYPSUM BOARD1' - 2 3/4"1 5/8" NON-STRUCTURAL
METAL FRAMING
CONTRACTOR OPTION TO
USE SPRAY APPLIED
FIREPROOFING AS SHOWN
OR EXTERIOR
FIREPROOFING BOARD.
CAFCO OR APPROVED
EQUAL. PROVIDE UL
ASSEMBLY OR EQUIVALENT
ENGINEERING JUDGEMENT
CONTRACTOR OPTION TO
USE SPRAY APPLIED
FIREPROOFING AS SHOWN
OR EXTERIOR
FIREPROOFING BOARD.
CAFCO OR APPROVED
EQUAL. PROVIDE UL
ASSEMBLY OR EQUIVALENT
ENGINEERING JUDGEMENT
6"8"
1 5/8" NON-STRUCTURAL
METAL FRAMING8 1/2"6"SPRAY-APPLIED
FIREPROOFING
STEEL COLUMN
5/8" GYPSUM BOARD
2 1/2" NON-STRUCTURAL
METAL FRAMING1' - 2 1/2"1' - 2"
• 1-HOUR RATED UL DESIGN X829
8"8"
• 1-HOUR RATED UL DESIGN X8278 1/2"6"1 5/8" NON-STRUCTURAL
METAL FRAMING
SPRAY-APPLIED
FIREPROOFING
HSS STEEL
TUBE COLUMN
2 1/2" NON-STRUCTURAL
METAL FRAMING
5/8" GYPSUM BOARD1' - 2 1/2"1' - 4"
1 5/8"
NON-STRUCTURAL
METAL FRAMING
CEILING PLANE, SEE
REFLECTED CEILING PLANS
SEALANT, ENTIRE
PERIMETER
UNDERSIDE OF DECK
GYPSUM LINER
METAL CH STUD
WALL BASE, SEE FINISH
SCHEDULE
• EXTEND TO UNDERSIDE OF DECK
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS,
REFER TO UL DESIGN U415, REFER TO NER-258 FOR
HORIZONTAL APPLICATIONS
• ACOUSTICAL PERFORMANCE - STC 37
• PROVIDE TILE BACKER PANEL, IN LIEU OF GYPSUM
BOARD AT LOCATIONS TO BE TILED
GYPSUM BOARD
SEALANT, ENTIRE
PERIMETER
1"5/8"
2 1/2"
3 1/8"
CEILING PLANE, SEE
REFLECTED CEILING PLANS
• EXTEND TO UNDERSIDE OF DECK
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS,
REFER TO UL DESIGN U906
• ACOUSTICAL PERFORMANCE - STC 46 (HOLLOW CORE)
7 5/8"WITH STRUCTURAL1" TYPICALCOORDINATECOMPRESSIBLE FILLER
UNDERSIDE OF DECK
WALL BASE, SEE FINISH
SCHEDULE
VARIES
5/8"
METAL FURRING
GYPSUM BOARD
3-5/8" STUD
6" STUD
2 1/2" STUD
1 5/8" STUD
7/8" FURRING
CEILING PLANE, SEE
REFLECTED CEILING PLANS
• EXTEND TO UNDERSIDE OF SOFFITS AS NOTED PER
PLANS
• BASIS-OF-DESIGN: PILKINGTON PROFILIT; SURFACE
TEXTURES: CLEAR, MACRO, SLIMLINE, STANDARD
2 23/64"
ALUMINUM BASE
CHANNEL
STRUCTURAL GLASS
CHANNEL
ALUMINUM TOP
CHANNEL
STEEL-FRAMED FIRE-RATED
GLASS AND FRAMING SYSTEM
FIRE-RESISTIVE GLAZING
(120 MIN)
• EXTEND TO UNDERSIDE OF DECK, UON
• RATED AS REQUIRED BY CODE CONFORMANCE PLANS
• ACOUSTICAL PERFORMANCE - STC 44
• BASIS-OF-DESIGN:
1. CONTACT: MIKE AUGUSTINE | 415.230.6708
maugustine@safti.com
1. FRAMING SYSTEM: SAFTI FIRST GPX ARCHITECTURAL
SERIES; FINISH CLEAR ANODIZED
2. GLAZING
A. BASE BID: SUPERLITE II-XLB (CLEAR TEMPERED)
B. ALTERNATE: SUPERLITE II-XL 120 (CLEAR TEMPERED)
SEALANT, BOTH SIDES,
ENTIRE PERIMETER
ALUMINUM STOREFRONT
FRAMING
GLAZING
• EXTEND TO UNDERSIDE OF SOFFITS, TYPICAL, UNO
• BASIS-OF-DESIGN:
1. CONTACT: MJD ASSOCIATES OF CNY
MARC DONAHUE AND PHIL DONAHUE | 315.432.8401
mdonahue@mjdcorp.com | pdonahue@mjdcorp.com
1. FRAMING SYSTEM: EFCO SERIES 403X 2" X 4 1/2" ALUMINUM
STOREFRONT FRAMING; FINISH CLEAR ANODIZED
2. GLAZING
A. 1/4" CLEAR TEMPERED, UON
B. 3/8" CLEAR TEMPERED IF ONE DIMENSION IS GREATER
THAN 5 FEET
C. 1/2" CLEAR TEMPERED, IF ONE DIMENSION IS GREATER
THAN 7 FEET OR BOTH DIMENSIONS ARE GREATER THAN 5
FEET
4 1/2"2"2"STEEL COLUMN
INTUMESCENT COATING
• 1-HOUR RATED UL DESIGN AS INDICATED
• STEEL SHALL BE FREE OF DIRT, LOOSE SCALE AND OIL
• PRIME WITH COMPATIBLE PRIMER PER MANUFACTURER'S RECOMMENDATION
• INTUMESCENT COATING
• TOPSEAL COATING
• SCHEDULED PAINT COATING
UL DESIGN Y615 (EXTERIOR)
HSS TUBE STEEL COLUMN
UL DESIGN Y616 (INTERIOR)
UL DESIGN Y614 (EXTERIOR)
STEEL BEAM
INTUMESCENT
COATING
• 1-HOUR RATED UL DESIGN N634
• STEEL SHALL BE FREE OF DIRT, LOOSE SCALE AND OIL
• PRIME WITH COMPATIBLE PRIMER PER
MANUFACTURER'S RECOMMENDATION
• INTUMESCENT COATING
• TOPSEAL COATING
• SCHEDULED PAINT COATING
1-5/8" STEEL STUDS, TYP
STEEL COLUMN, REFER
TO STRUCTURAL
DRAWINGS
5/8" FIRE-RATED
GYPSUM BOARD, TYP
UL DESIGN X528 1 HR RATING
SEE UL FIRE RESISTANCE DIRECTORY VOLUME 1
FOR SPECIFIC CONSTRUCTION INFORMATION
NO. 28 MSG GALVANIZED
STEEL CORNER BEAD
STEEL COLUMN
PREFINISHED
ALUMINUM
COLUMN COVER
SPRAY-APPLIED
FIREPROOFING
• 1-HOUR RATED UL DESIGN X764
• BASIS-OF-DESIGN EXTERIOR FIREPROOFING SYSTEM:
ISOLATEK CAFCO FENDOLITE M-II
A. BASIS-OF-DESIGN COLUMN COVER SYSTEM: SEE
EXTERIOR FINISH SCHEDULE
STEEL BASE
PLATE BELOW
9" RADIUSSTEEL TUBE
PREFINISHED
ALUMINUM
COLUMN COVER
SPRAY-APPLIED
FIREPROOFING
• 1-HOUR RATED UL DESIGN X768
• BASIS-OF-DESIGN EXTERIOR FIREPROOFING SYSTEM: ISOLATEK
CAFCO FENDOLITE M-II
• BASIS-OF-DESIGN COLUMN COVER SYSTEM: PAC-CLAD PAC-1000F
FLUSH JOINT COLUMN COVER
1. MATERIAL: .125" ALUMINUM
2. FINISH: KYNAR 500
A. COLOR: MANUFACTURER'S PREMIUM COLORS; TBD
STEEL BASE
PLATE BELOW
9" RADIUS
• 1-HOUR RATED UL DESIGN Y616
• STEEL SHALL BE FREE OF DIRT, LOOSE SCALE AND OIL
• PRIME WITH COMPATIBLE PRIMER PER
MANUFACTURER'S RECOMMENDATION
• INTUMESCENT COATING
• TOPSEAL COATING
• SCHEDULED PAINT COATING6"INTUMESCENT COATING
HSS STEEL TUBE COLUMN
CONTINUOUS FIRE-
RATED SEALANT, BOTH
SIDES OF COLUMN
MINERAL-WOOL BLANKET
INSULATION
MINERAL-WOOL BOARD
INSULATION
IMPALING PINS @ 12" OC
STEEL BACKPAN, 22 GA
FIRESTOP SEALANT
FIRESAFING INSULATION
MIN
3"
UL DESIGN CW-D-1044 OR APPROVED EQUAL
2 1/2" @ SIM
3 1/2"
1-5/8" STEEL STUDS, TYP
5/8" FIRE-RATED
GYPSUM BOARD, TYP
UL DESIGN N873 1 HR RATING
SEE UL FIRE RESISTANCE DIRECTORY VOLUME 1
FOR SPECIFIC CONSTRUCTION INFORMATION
STEEL BEAM, REFER TO
STRUCTURAL
DRAWINGS
NO. 28 MSG GALVANIZED
STEEL CORNER BEAD
SPRAY-APPLIED
FIREPROOFING
Z-CLIPS WELDED TO
STEEL BEAM
1-5/8" STEEL STUDS, TYP
5/8" FIRE-RATED
GYPSUM BOARD, TYP
NO. 28 MSG GALVANIZED
STEEL CORNER BEAD
SPRAY-APPLIED
FIREPROOFING
STEEL GIRDER/
BEAM/JOIST
REFER ALSO TO
STRUCTURAL
DRAWINGS
1 1/2" = 1'-0"F2 INTERIOR WALL SYSTEM TYPE 2 (IWS-2)
1 1/2" = 1'-0"F7 INTERIOR WALL SYSTEM TYPE 5 (IWS-5)
1 1/2" = 1'-0"F1 INTERIOR WALL SYSTEM TYPE 1 (IWS-1)
1 1/2" = 1'-0"F4 INTERIOR WALL SYSTEM TYPE 3 (IWS-3)
1 1/2" = 1'-0"F5 INTERIOR WALL SYSTEM TYPE 4 (IWS-4)
1 1/2" = 1'-0"F9 INTERIOR WALL SYSTEM TYPE 7 (IWS-7)
1 1/2" = 1'-0"D1 INTERIOR WALL SYSTEM TYPE 9 (IWS-9)
1 1/2" = 1'-0"E7 FLOOR SYSTEM 1 (FS-1)
1 1/2" = 1'-0"D9 TYPICAL ROOF FIREPROOFING
1 1/2" = 1'-0"A1 COLUMN ENCLOSURE DETAIL, TYPICAL
1 1/2" = 1'-0"A7 COLUMN ENCLOSURE DETAIL
1 1/2" = 1'-0"A11 COLUMN ENCLOSURE W10X39 EXTERIOR
1 1/2" = 1'-0"A3 COLUMN ENCLOSURE DETAIL
1 1/2" = 1'-0"F11 INTERIOR WALL SYSTEM TYPE 8 (IWS-8)
1 1/2" = 1'-0"F8 INTERIOR WALL SYSTEM TYPE 6 (IWS-6)
1 1/2" = 1'-0"D2 INTERIOR WALL SYSTEM TYPE 10 (IWS-10)
1 1/2" = 1'-0"D5 INTERIOR WALL SYSTEM TYPE 12 (IWS-12)
1 1/2" = 1'-0"D4 INTERIOR WALL SYSTEM TYPE 11 (IWS-11)
1 1/2" = 1'-0"B1 TYPICAL COLUMN - INTUMESCENT
1 1/2" = 1'-0"B3 TYPICAL BEAM/JOIST/GIRDER - INTUMESCENT
1 1/2" = 1'-0"B9 1 HOUR FIRE-RATED COLUMN WRAP DETAIL
DATE:
PROJECT:
OTHER:
DRAWN BY:
A
B
C
D
E
F
G
A
B
C
D
E
F
G
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
Architecture
Planning
Interior Design
11 12
H
I
11 12
H
I
619 West State Street
Ithaca, New York 14850
132 E. Jefferson Street
Syracuse, New York 13202
p 607 273 7600 www.holt.com
WARNING: It is a violation of New
York State Law for any person,
unless acting under the direction of
a licensed Architect, to alter this
document in any way. If a document
bearing the seal of an Architect is
altered, the altering Architect shall
affix to such document his seal and
the notation "altered by" followed by
his signature, the date of such
alteration, and a specific description
of the alteration.2/5/2021 4:44:27 PMA002
INTERIOR
WALL &
FIREPROOFING
SYSTEMS
02/05/2021
2018089
CRB/GLM Cayuga Park, Ithaca, New York 14850Park Grove - Cayuga Medical CenterMEDICAL OFFICE BUILDING1 1/2" = 1'-0"B7 COLUMN - W10 SPRAY FIREPROOFING WITH COLUMN COVER
1 1/2" = 1'-0"B5 COLUMN - HSS6X6 SPRAY FIREPROOFING WITH COLUMN COVER
1 1/2" = 1'-0"A5 COLUMN ENCLOSURE DETAIL
1 1/2" = 1'-0"D11 FLOOR SLAB FIRESTOPPING@CURTAIN WALL
REVISION SCHEDULE
NAME DATE
1 1/2" = 1'-0"B10 1 HOUR FIRE-RATED HSS BEAM WRAP DETAIL
1 1/2" = 1'-0"B11 1 HOUR FIRE-RATED BEAM WRAP DETAIL
Received by DiMarco 2/15/2021