HomeMy WebLinkAboutApp w Not - 283100 IC-PAP FP 031 Submittal ROTHCHILD Feb 10-2021SUBMITTAL COVER SHEET
JOB: ITHACA COLLEGE PHYSICIAN’S ASSISTANT ROTHSCHILD RENOVATION SUBMITTAL NUMBER: 31 DATE: 10 FEBRUARY 2021 SUBCONTRACTOR NAME: ARCHITECTURAL CONCRETE PLUS, LLC
ARCHITECTURAL CONCRETE PLUS, LLC 69 HOLLISTER STREET
DUNDEE, NY 14837
PHONE: 607-243-7113
FAX 315-423-0054
ACP PROJECT NO: 21-105
ARCHITECT: QPK 450 S SALINA ST STE 500, SYRACUSE, NY 13202
ARCHITECT PROJECT NO: 220157.00 (12/18/2020)
TYPE OF SUBMITTAL:
X PRODUCT DATA TEST REPORT X SHOP DRAWING RECORD DOCUMENT
SAMPLE CERTIFICATION MFGR COMPLIANCE CE CLOSEOUT DOCUMENT
COLOR SELECTION MFGR DWG SUBSTITUTION MSDS
SUBMITTAL DESCRIPTION FIRE PROTECTION
SUPPLIER ABJ
MANUFACTURER VARIOUS
SPEC SECTION NUMBER & TITLE 283100
SUB-PARAGRAPH DRAWING NO 1ST TIME SUBMISSION X REVISION
PRIME CONTRACTOR’S STAMP/CERTIFICATION : I HEREBY CERTIFY THAT I HAVE REVIEWED THIS SUBMITTAL, VERIFIED THE PRODUCTS, VERIFIED FIELD MEASUREMENTS WHERE APPROPRIATE AND HAVE COORDINATED THE INFORMATION WITHIN THE SUBMITTAL WITH THE REQUIREMENTS OF CONTRACT DOCUMENTS. THE SUBMITTED ITEMS COMPLY IN EVERY RESPECT WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS AND SPECIFICATIONS
ARCHITECT/ENGINEER REVIEW STAMP:
PRIME CONTRACTOR/CONTRACT/BID PKG NO.
SIGNED:
POSITION:
DATE:
COMMENTS:
Received MCE 2/10/21
SCHEDULE 40 PIPE FROM POINT OF CONNECTION TO SUPPLY
4.026"
6.065"
U/G PIPE MAY BE DOUBLE CEMENT LINED DUCTILE 8.04" ID
UNLINED DI
ARCHITECT & COLLEGE PROPOSED "VIRTUAL CEILING" PANELS ABOVE STAIRWAY.SPRINKLER LOCATIONS MAY REQUIRE ALTERATION THATREPRESENTED ON BID DRAWINGS.CEILING IN AREAS 240 TO 242 MAY REQUIRE SPRINKLER ALTERATION.MODIFY AS NECESSARY. INSTALL G5-56 CONCEALED SPRINKLERS.VERIFY WITH GC.IDENTIFY METHOD OF SUSPENSION OF CROSS MAINS. TRAPEZE CONSTRUCTION, IF USED.ALL EXISTING 4" PIPING IS SCHEDULE 40(4.026" ID). 4" & 6" FITTINGS ARE THREADED.PROVIDED CORRECTIONS ON HYDRAULIC CALCULATIONS FOR ARCHIVAL.1. COORDINATE INSTALLATION AND LOCATION OF SPRINKLERS WITH FINAL CEILING LAYOUT, HVAC, AND LIGHTING CONFIGURATIONS AND OBSTRUCTIONS.2. CORRECT PIPE DIAMETER AND FITTING "TYPE" ENTRIES ON HYDRAULIC CALCULATION FOR ARCHIVAL PURPOSES, TO REFLECT EXACT INFRASTRUCTURE. ALL FITTINGS ARE THREADED CAST IRON.3. ADD SPRINKLER PROTECTION TO ENTRY VESTIBULE OF NEW STAIR ENTRY. 4. ADVISE OWNER OF HEAT REQUIREMENT TO PROTECT SYSTEM IN ENTRY VESTIBULE.5. CONNECT EXISTING 1st FLOOR 1 1/4" AUXILIARY DRAIN NEAR COLUMN LNES 18 AND C, INTO NEW 3" MAIN TO SERVE AS AN AUTOMATIC DRAIN TO TRAPPED 4".6. IF TRAPEZE ARE USED, SHOW DETAIL OF CONSTRUCTION.7. SEE SELECT NOTATIONS ON HYDRAULIC CALCULATIONS, TO ALTER INPUT DATA. SAMPLE INFORMATION APPLIES TO BOTH CALCULATIONS.8. CHECK WITH OWNERS AGENTS REGARDING POSSIBLE "VIRTUAL CEILING" IN STAIRWAY BETWEEN FLOORS, COL. 17-18, AND D-E.9. ADD FULL HEIGHT CROSS SECTION DIAGRAM TO DRAWING. SEE ELABORATIONS IN OTHER NOTES.BUILDING OWNER MUST ARRANGE TAMPER SWITCH INSTALLATION AND CONNECTION TO FIRE ALARM SYSTEM FOR SUPERVISION AT EACH FLOORCONTROL VALVE.FP CONTRACTOR TO PROVIDE CHAINAND BREAKABLE LOCK TO CONTROL VALVES. 1ST & 2ND FLOORS
PROVIDE SPRINKLER PROTECTION IN THE ENTRY VESTIBULE, AND UNDERSTAIRS IF STORAGE CAPABLE.HEAT MUST BE PROVIDED TO ENTRY VESTIBULE.TIE IN EXISTING 1 1/4" AUXILIARY DRAININTO NEW 3" MAIN TO ALLOW FOR ADEQUATE DRAINING OF EXISTING TRAPPED MAIN.ALL EXISTING PIPE SCHEDULE 40UP TO TO CONNECTION AT UNDERGROUND.ALL FITTINGS ARE THREADED CAST IRON.