Loading...
HomeMy WebLinkAbout01_aSelf-Pricing_Hans Bethe House Enlarged Plans and DetailsADD GREASE COLLECTION LOW POINT DRAINS ADJACENT TO EXISTING ACCESS DOORS. SEE DETAIL 6/M501. INCREASE DUCT SLOPE TO 1/4" PER FT. MODIFY EXISTING DUCT FITTINGS TO ALLOW FOR DUCT SLOPE. 14x24 10x14 36x14 36x1226x36 PROVIDE 18"x36" GREASE DUCT ACCESS DOORS IN EXHAUST PLENUM SIDEWALL ABOVE CATWALK IN CHIMNEY (TYP 3) EXG DUCT CHIMNEY DISASSEMBLE EXISTING EXHAUST FANS AND CLEAN TO BE FREE OF GREASE. REASSEMBLE WITH MANUFACTURER RECOMMENDED GASKETING TO MAKE FANS GREASE TIGHT. PROVIDE A 1-1/4" DRAIN AT THE BOTTOM SIDE OF THE FAN HOUSING PIPE TO SEALED INSULATED RESERVOIR. SEE DETAIL 10/M501. (TYP OF 3) PROVIDE 1-1/2" HIGH FIBERGLASS GRATING EQUAL TO DURADEK PULTRUDED FIBERGLASS GRATING TYPE MS 1-6515 AS MANUFACTURED BY McNICHOLS COMPANY. SIZE GRATING TO BE REMOVABLE THROUGH THE NEW ACCESS DOORS AND SAFELY COVER THE VERTICAL DUCT OPENINGS IN THE BOTTOM OF THE EXHAUST PLENUM AT THE TOP OF THE CHIMNEY. V.I.F. REMOVE WIRE MESH SCREEN AND REPLACE WITH (3) INDIVIDUAL FRAMED MESH OUTLETS. SEE DETAIL 8/M501. EXG MESH SCREEN APPROXIMATELY 5 FOOT HIGH BY 10 FOOT LONG V.I.F. CLEAN KITCHEN EXHAUST DUCT ADJACENT TO WELDED WORK, ALLOWING FOR WELDED DUCT REPAIRS WITH MINIMIZED FIRE HAZARD. REMOVE INSULATION IN ATTIC SPACE, REPAIR WELD PIN HOLES AND OTHER LEAKS IN DUCTWORK WITH A CONTINUOUS LIQUID-TIGHT WELD OR BRAZE MADE ON THE EXTERNAL SURFACE OF THE DUCT SYSTEM. INSPECT AND TEST FOR LEAKS, AND RE-INSULATE WITH FIRE RATED INSULATION COMPLETE. ASSUME REPAIR IS REQUIRED FOR 100 WELD PIN HOLES AND 30 INCHES OF CRACK. PROVIDE 22"X20" MINIMUM GREASE DUCT ACCESS DOOR AT LOCATION OF EXISTING (APPROXIMATELY) 20"X20" ACCESS PORT REPLACE DISHWASHER EXHAUST FIRE DAMPER WITH STAINLESS STEEL FIRE DAMPER AS SHOWN IN DETAIL 9/M501. ACCESS THROUGH 30"x20" ACCESS DOOR IN SHAFT. INSTALL LOW POINT DRAINS ON DUCTWORK AS SHOWN IN DETAIL 4/M501. FD 22x6 16x8 36x12 44x20 26x36 UP 5 STOREYS TO ATTIC EXISTING 18x10 DUCT ACCESS DOORS EXISTING 18x10 DUCT ACCESS DOORS EXISTING 18x18 ACCESS DOORS EXISTING DUCT MOUNTED SMOKE DETECTOR. EXISTING DUCT MOUNTED SMOKE DETECTOR. EXISTING DUCT MOUNTED SMOKE DETECTOR. FD FD FD 12X11 EXISTING 18X10 DUCT ACCESS DOOR ADD 20x20 DUCT ACCESS DOOR ON OPPOSITE SIDE OF WALL FROM CURRENT DUCT ACCESS DOOR. REMOVE FIRE DAMPER'S BLADES IN THEIR ENTIRETY. FD FD FD FD FD FD FD FD FD 30x24 48x24 36x24 28x20 44x20 48x20 12x6 12x6 20x12CONNECT CONDENSATE FROM THE BOTTOM OF THE DISHWASHER EXHAUST DUCT. REPAIR DAMAGE TO SHAFTWALL BASE OF DUCT SHAFT AS REQUIRED TO RESTORE 2HR FIRE RATING. PIPE THROUGH MECHANICAL ROOM TO EXISTING GREASE DRAIN PIPING. SEE DETAIL 4/M501 FOR PIPING CONNECTIONS. FD FD FD ADD 20x20 DUCT ACCESS DOOR ON OPPOSITE SIDE OF WALL FROM CURRENT DUCT ACCESS DOOR. REMOVE FIRE DAMPER'S BLADES IN THEIR ENTIRETY. REMOVE FIRE DAMPER'S BLADES IN THEIR ENTIRETY. 8x12 10x12 10x12 28x12 REMOVE FIRE DAMPER'S BLADES IN THEIR ENTIRETY. IN ACCORDANCE WITH NFPA 110 302.1.1.1 PROVIDE WALL SIGN NEXT TO DUCT PENETRATION AS FOLLOWS: "THIS WALL AND MECHANICAL PENETRATIONS THROUGH IT ARE REQUIRED TO RESIST PASSAGE OF SMOKE BUT ARE NOT REQUIRED TO BE FIRE RATED." (TYP FOUR (4) LOCATIONS. COORDINATE LOCATIONS WITH OWNER IN FIELD) CONNECT 1 1/4" CD ABOVE TRAP V.I.F. 1 A2 43 5 6 7 8 BCD9 10 11 12 13 14 15 16 17 EFGHINNMLJIHGFEDCBADescription:Rev. No.:Date: Drawing No.:Drawn by:MLKJKTetra Tech Engineers, Architects & Landscape Architects, P.C. Hans Bethe House Enlarged Plans and Details And Code Compliance Review RHM M501 1 Attic Plan 1/16" = 1'-0" Project No.: Date: 3/23/2018 08249-15002 Key Plan NTS Remediation Work at: Alice Cook, Carl Becker, William Keeton, Flora Rose and Hans Bethe Houses Cornell University Ithaca, New York N2 Enlarged First Floor Reflected Ceiling Plan 1/8" = 1'-0"3 Enlarged Ground Floor Plan 1/8" = 1'-0" KEYED NOTES PROVIDE LEAKAGE TEST FOR ALL MODIFIED DUCTWORK. REFER TO SECTION 23 3100 - DUCTWORK FOR DETAILS. REMOVE EXISTING MESH LOUVER PROVIDE 1"x1"x1/8" STAINLESS STEEL ANGLE WELDED TO END OF EXISTING DUCT DISCHARGE. (TYP 2 SIDES) PROVIDE 1-1/2" 18 GAUGE STAINLESS STEEL SHEET METAL BENT AROUND AND SPOT WELDED TO 1/2" STAINLESS STEEL WELDED WIRE MESH. BOLT TO 1"x1"x1/8" ANGLE 12"OC MAX. TACK WELD NUT TO ANGLE. PROVIDE STAINLESS STEEL MESH LOUVER IN 3 SECTIONS FOR REMOVAL THROUGH NEW ACCESS DOORS FOR CLEANING. TO PREVENT DAMAGE TO INSULATION, PROVIDE THREE 1/2" BAND STRAPS AT EACH ACCESS DOOR TO ALLOW REPEATED INSULATION REMOVAL. PROVIDE WORM GEARS SPOT WELDED TO BANDING FOR STRAP REMOVAL REMOVE EXISTING FIRE WRAP INSULATION AND PINS SPOT WELDED TO ACCESS DOORS. PROVIDE NEW FIRE WRAP INSULATION AS SPECIFIED BY MANUFACTURER TO MAINTAIN FIRE RATING. INSULATION HELD IN PLACE BY REUSABLE BAND CLAMPS. 8 Mesh Louver Detail 7 Access Door Straps Detail EXTERNAL FIRE WRAP INSULATION ACCESS DOOR UNDER INSULATION GREASE EXHAUST DUCT, REFER TO CONTRACT DWGS FOR SIZES AND ARRANGEMENT DOOR BOTH SIDES OPENING IN FIRE RATED WALL REQUIRING OUT OF WALL FIRE DAMPER. FIRE RATED WALL DUCT SIZE DUCTWORK, REFER TO DRAWINGS FOR 14 GAUGE MINIMUM TO WALL 6" OC ALL 4 SIDES. RETAINING "ZEE", SECURE EXTEND FIRE RATED INSULATION PAST PLANE OF DAMPER. INSULATION TO BE 3M CS-195+ COMPOSITE OR EQUAL. PROVIDE ACCESS AWAY JOINT ALL LISTED BREAK- SIDES (TYP.) 9 Out of Wall Fire Damper TO SPEC. SECTION 23 3300. EQUAL TO DUCT SIZE SHOWN. REFER TYPE "C" FIRE DAMPER WITH FREE AREA TEE WITH FULL SIZE CLEAN OUT (TYP OF 2) UNION DRAIN RESERVOIR CONNECTION ‘'5$,1 75$3 ASSEMBLY 2" NOTES: 2" CASING (-) 1. DRAIN PAN AT NEGATIVE STATIC PRESSURE 3/4" HOSE THREAD CONNECTION WITH BRASS CAP 5 Condensate Trap Detail PROVIDE 3/4" DRAIN WITH BALL VALVE AND CAPPED HOSE THREAD CONNECTION. PROPERLY CLEAN EXISTING GREASE DUCT TO ALLOW FOR WELDING OF GREASE COLLECTION RESERVOIR TO THE BOTTOM OF DUCT WHERE INDICATED 12" LONG X 1-1/2" MIN DEEP GREASE COLLECTION RESERVOIR. SLOPE TO ACCESSIBLE SIDE OF DUCT WITH A LOW POINT DRAIN.1-1/2" MINFULLY WELD GREASE COLLECTION RESERVOIR TO BOTTOM OF GREASE DUCT. FIRE WRAP DUCT AND GREASE COLLECTION RESERVOIR. 6 Grease Duct Drain Detail EXTERNAL FIRE WRAP INSULATION GREASE EXHAUST DUCT, REFER TO CONTRACT DWGS FOR SIZES AND ARRANGEMENT 1 IS WATERTIGHT VERIFY EXHAUST DUCTWORK PIPE TO GREASE INTERCEPTOR DRAIN LOCATED IN THE BASEMENT SEE DETAIL 9/M101 PROVIDE 12" WIDE X 1-1/2" MIN DEEP CONDENSATE COLLECTION RESERVOIR AND LOW POINT DRAIN ON WELDED STAINLESS STEEL DISHWASHER DUCTWORK DRAIN VALVE ON BOTTOM OF DUCT EXISTING 2HR RATED WALL 1 1/4" STAINLESS STEEL FIRE DAMPER AT 2HR RATED WALL 12" (TYP) CONDENSATE TRAP (TYP). SEE DETAIL 6/M101 4 Bottom of Dishwasher Duct Drain Detail EXTERNAL INSULATION EXHAUST DUCT, REFER TO CONTRACT DWGS FOR SIZES AND ARRANGEMENTS 1.THE FOLLOWING GENERAL NOTES APPLY TO ALL "H" SERIES DRAWINGS. 2.REFER TO ALL CONTRACT DOCUMENTS; DRAWINGS AND SPECIFICATIONS, FOR DETAILED STANDARDS AND REQUIREMENTS. 3.REPORT UNSAFE OR UNSATISFACTORY CONDITIONS IN WRITING TO OWNER AND ARCHITECT AND RESOLVE ISSUES BEFORE PROCEEDING. 4.WORK INCLUDES ALL LABOR AND MATERIALS REQUIRED TO PROVIDE COMPLETE WORKING SYSTEMS. 5.COORDINATE PHASING REQUIREMENTS AT JOB MEETINGS AND ON WORK SCHEDULES. 6.DO NOT SCALE DRAWINGS. PIPING AND DUCTWORK ARE SHOWN DIAGRAMMATICALLY. IT IS NOT POSSIBLE TO SHOW EVERY TRANSITION, FITTING, ASPECT RATIO CHANGE, ETC..; PROVIDE AS REQUIRED TO FIT WITHIN STRUCTURAL CONSTRAINTS. EXAMINE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED AND VERIFY ALL ACCESS, LOCATIONS, DIMENSIONS, ARRANGEMENTS, ELECTRICAL CHARACTERISTICS, AND INTERFERENCE IN THE FIELD PRIOR TO BID. 7.VERIFY EXTENT OF CEILING WORK SHOWN ELSEWHERE IN THE CONTRACT DOCUMENTS. PROVIDE FOR ADDITIONAL CEILING SYSTEM REMOVAL, PROTECTION, AND REINSTALLATION AS REQUIRED FOR CONTRACT WORK. 8.DEMOLITION DRAWINGS SHOW THE GENERAL SCOPE OF ITEMS AND SYSTEMS TO BE REMOVED. IT IS NOT THE INTENT TO SHOW ALL ITEMS TO BE REMOVED. FIELD VERIFY AND REMOVE ALL ASSOCIATED ITEMS BACK TO POINT OF CONTINUED SERVICE, UNLESS OTHERWISE NOTED. VERIFY WHAT ALL EQUIPMENT SERVES PRIOR TO REMOVAL. 9.GIVE ALL REMOVED EQUIPMENT TO THE OWNER. DELIVER ON SITE WHERE DESIGNATED BY THE OWNER. PROMPTLY REMOVE FROM THE SITE AND LEGALLY DISPOSE OF ANY SUCH ITEMS DECLINED BY OWNER. 10.IF UNANTICIPATED MECHANICAL, ELECTRICAL, OR STRUCTURAL CONFLICTS ARE ENCOUNTERED, INVESTIGATE AND REPORT BOTH NATURE AND EXTENT OF THE CONFLICT. RE-ROUTE WORK OR EXISTING ELECTRICAL OR PLUMBING AS REQUIRED. 11.CUT, DRILL, OR OTHERWISE CREATE OPENINGS AS NEATLY AS POSSIBLE, AS REQUIRED FOR THE INDICATED CONTRACT WORK. PROVIDE SUPPORT AS REQUIRED FOR AND USE METHODS LEAST LIKELY TO DAMAGE ELEMENTS TO REMAIN. PRIOR TO WORK, VERIFY LOCATIONS OF ALL STRUCTURAL MEMBERS INCLUDING CROSS BRACING, ELECTRICAL WIRING, PLUMBING, ETC. PROMPTLY NOTIFY ARCHITECT OF ANY CONFLICTS. DO NOT CUT ANY STRUCTURAL MEMBERS OR OTHER SERVICES UNTIL SPECIFICALLY DIRECTED TO DO SO. PENDING RECEIPT OF DIRECTIVE, REARRANGE SCHEDULE AS NECESSARY TO CONTINUE OVERALL JOB PROGRESS WITHOUT DELAY. 12.PATCH ALL DISTURBANCES RESULTING FROM DEMOLITION OR NEW WORK TO MATCH SURROUNDING SURFACES. PATCH FOLLOWING DEMOLITION, AND AGAIN FOLLOWING CONTRACT WORK. WHERE HOLES REMAIN FROM REMOVALS, INFILL AND PATCH TO MATCH UNLESS HOLE IS TO BE REUSED. 13.PROTECT ALL CONTRACT EQUIPMENT, ELEMENTS TO REMAIN, OWNER'S BELONGINGS, AND EQUIPMENT TO BE REUSED OR RETAINED BY OWNER DURING ALL CONTRACT WORK. AT NO ADDITIONAL COST TO OWNER REPAIR OR REPLACE ITEMS WHICH ARE DAMAGED. 14.THOROUGHLY CLEAN FOLLOWING DEMOLITION AND BEFORE BEGINNING CONTRACT INSTALLATIONS. THOROUGHLY CLEAN AGAIN DURING AND FOLLOWING CONTRACT WORK AS REQUIRED. LEAVE ALL WORK AREAS CLEANER THAN FOUND. LEGALLY DISPOSE OF ALL CONSTRUCTION DEBRIS. 15.PROVIDE TEMPORARY PIPING, DUCT, HEAT, WEATHERPROOFING ETC.. TO SERVICES TO REMAIN UNTIL PERMANENT INSTALLATIONS CAN BE MADE. 16.ALL EXCESS MATERIALS AND SCRAPS ARE CONTRACTOR'S PROPERTY. PROMPTLY REMOVE FROM SITE UNLESS SPECIFICALLY DIRECTED OTHERWISE. GENERAL NOTES: VALVE TAG VALVE NORMALLY OPEN (N.O.) FORMED OR WELDED STAINLESS STEEL FLANGED RESERVOIR TO FIT DOOR FLANGES BOLTED AND GASKETED RESERVOIR TOP EQUAL TO DUCTMATE ULTIMATE DOOR II 12"x10" MINIMUM 10 GREASE RESERVOIR EXTERNAL FIRE WRAP INSULATION TANK INLET COUPLING WELDED TO RESERVOIR 6" MIN 8" MIN FAN HOUSING THREADED 1 1/4" PIPE 1 1 CODE COMPLIANCE REVIEW HANS BETHE HOUSE - 3033 314 WEST AVE, ITHACA, NY PROJECT DESCRIPTION: THIS PROJECT CONSISTS OF THE REMEDIATION OF NON-CODE COMPLIANT CONDITIONS FOR GREASE DUCT AND SHAFTS LOCATED IN THE BUILDINGS WHICH IS CONSIDERED ALTERATIONS - LEVEL 1 APPLICABLE CODES AND STANDARDS: BASED ON THE NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODE INCLUDING APPLICABLE 2015 ICC CODES AND 2017 NYS SUPPLEMENTS, AND 2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDING AND FACILITIES. BUILDING DATA: YEAR BUILT:2007 (KIERAN-TIMBERLAKE ASSOCIATES LLP) CODE DATA SUMMARY: BUILDINGS ARE BELIEVED TO HAVE BEEN CONSTRUCTED AND SUBSEQUENT ALTERATIONS MADE IN COMPLIANCE WITH CODES IN EXISTENCE AT THAT TIME. USE GROUP:R-2 - RESIDENTIAL, A-2 - ASSEMBLY, B - BUSINESS CONSTRUCTION TYPE IB FIRE SAFETY:BUILDING IS PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. PATH OF CODE COMPLIANCE: 2015 INTERNATIONAL EXISTING BUILDING CODE AND 2017 NYS SUPPLEMENTS 301.1.2 WORK AREA COMPLIANCE METHOD CHAPTER 5 - CLASSIFICATION OF WORK 503 ALTERATION - LEVEL 1 (CHAPTER 7) NEW CONSTRUCTION WILL COMPLY WITH REQUIREMENTS OF 2015 INTERNATIONAL BUILDING CODE AND 2017 NYS SUPPLEMENTS