Loading...
HomeMy WebLinkAboutOlin Hall B01 and 101_Drawings (2)UPUPUPUPUPUPDNUPUPDNUPUPDNUPDNUPDNDN101ROOM NAME1A101SIM1A101SIMA1011SIM1'-0"B1W1F1101ROOM NAMENameElevationW1A1011SIMDETAIL ENLARGEMENTWALL SECTIONBUILDING SECTIONDETAIL SECTION1INTERIOR ELEVATIONDOOR & INTERIOR WINDOW TAGWALL TAGROOM IDENTIFICATIONEXTERIOR WINDOW & LOUVER TAGROOM FINISH KEYCONTRACT LIMIT LINEEXISTING DOORNEW DOORPARTITIONS, DOORS AND ITEMS TO BE REMOVEDFULL HEIGHT PARTITION PARTIAL HEIGHT PARTITION NOTE KEYFLOOR ELEVATION1001001REVISION CLOUD & TAGPLAN ELEVATION50'-6"SITE ELEVATIONSTRUCTURAL ELEVATIONWORKING POINTWPCEILING HEIGHTEQUIPMENT TAGA101SIMA1A2A3A411iSCOPE LINEDIMENSION TO THE FACE OF FRAMING AT NEW CONSTRUCTION, TYP.DIMENSION TO THE FACE OF FINISH AT EXISTING CONSTRUCTIONDIMENSION TO THE FACE OF FINISH50'-6"50'-6"1EXISTING PARTITIONPARTIAL B01 -ALTERATION LEVEL 1FUME HOOD INSTALLATION -ALTERATION LEVEL 2101 -ALTERATION LEVEL 1SET NUMBERARCHITECTURAL SYMBOLS AND PATTERNSPROJECT INFORMATIONCrescent Building217 North Aurora StreetIthaca, New York 14850607.241.0244G0016/2/202111614/COB# 2013113 HO PLAZAOlin Hall B01, 101 Lab RenovationsCONSTRUCTION DOCUMENTSCORNELL UNIVERSITYARCHITECTURALA101 B01 - DEMO & EQUIPMENT PLANSA102 101 - DEMO & EQUIPMENT PLANSA151 B01 REFLECTED CEILING PLANA152 101 REFLECTED CEILING PLANA201 EQUIPMENT MATRIX - ROOM B01A202 EQUIPMENT MATRIX - ROOM 101A203 EXISTING PHOTOS - B01A204 EXISTING PHOTOS - 101PLUMBINGP001 DRAWING INDEX, SYMBOL LISTS & ABBREVS.P101 PARTIAL FLOOR PLAN - LAB B01P102 PARTIAL FLOOR PLANS - LAB 101MECHANICALM001 DRAWING INDEX, SYMBOLS & ABBREVS.M101 B01 FLOOR PLANSM102 101 FLOOR PLANSM601 SCHEDULES & DETAILSM701 CONTROLSELECTRICALE001 DRAWING INDEX, SCHEDULES, SYMBOL LISTS & NOTESE101 PARTIAL ELECTRICAL PLANS - LAB B01E102 PARTIAL POWER PLANS - LAB 101DATE:JOB NUMBER:BUILDING CONSTRUCTION TYPE:ALTERATION CLASSIFICATION:SPRINKLER PROTECTION:USE CLASSIFICATION:TOTAL EXISTING BUILDING AREA:AREA OF RENOVATION:AREA OF ADDITION:TOTAL AREA OF PROJECT:F|S Engineering, DPC721 East Genesee Street, Syracuse, NY 13210.1505315.471.4013 1-A LEVEL 1 &LEVEL 2SPB129,897 SF1,424 SF0 SF1,424 SF1/32" = 1'-0"1OLIN HALL BASEMENT - WORK AREA1/32" = 1'-0"2OLIN HALL FIRST FLOOR - WORK AREALOCATION PLAN WOODEN WORK BENCH WITH VICE (72" X36") -OFCILARGE HTL REACTOR WITH CASTING (80"X 42") -OFCITHERMAL SPALLATION SETUP (138"x40")OFCIELEC. CONTROL BOX -OFCITOOLBOX -NICSTEELMOVEABLETOOLBOX -OFCIMIN3'-0"ROCK SAMPLE TABLE NICMOVEABLETABLE(4'x30") -NICSTORAGE CABINET -NICEXISTING BENCH TO REMAINEXISTING BENCH TO REMAINEXISTING SINKEXISTING BENCH TO REMAINFUME HOOD RELOCATE FROM WARD HALL BASEMENT, COORDINATE WITH OWNER.ELECTRICAL OUTLET -SEE ELECTRICAL DWGS FOR MORE DETAILADJUSTABLE SNORKEL EXHAUST ABOVEMOVEABLETABLE(4'x30") -NICADJUSTABLE SNORKEL EXHAUST ABOVEFLOOR MOUNTED GAS CYLINDER RACK. COORDINATE FINAL LOCATION WITH OWNERCLEAN AND PAINT EXISTING CABINETS PROVIDE COAT HOOKS FOR LAB COATS &WALL MOUNTED LAB SAFETY GLASSES BOX, PROVIDE BLOCKED AS NEEDED, TYP. OFCIELECTRICAL OUTLET, REFER TO ELECTRICAL DWGS FOR ADDITIONAL DETAILCOMPRESSED AIR, SEE MEP DWGS FOR ADDITIONAL DETAIL B00JBB01MIN3'-0 1/4"469 SFB01TEMPORARY PARTITION DURING CONSTRUCTION -FIRE RATED POLY RELOCATE THERMAL SPALLATION SETUP WITH CONTROL BOX FROM SNEE HALL 2157, COORDINATE MOVE WITH OWNER.ALTERATION LEVEL 2EXISTING FUME HOODEXISTING BENCH TO REMAINEXISTING BENCH TO REMAINEXISTING SINKEXISTING BENCH TO REMAINB00JBB01TEMPORARY PARTITION DURING CONSTRUCTION -FIRE RATED POLY 469 SFB01REMOVE EXISTING MARKER BOARD, RELINQUISH TO OWNER. PATCH WALL AS REQUIRED TO RESTORE SURFACE TO MATCH ADJACENT EXISTING CONDITION. REMOVE EXISTING BREAKER PANEL AND ASSOCIATED WIRINGREMOVE EXISTING GAS CABINETEXISTING FUME HOODFINISH NOTES:1. ALL WALLS TO BE PAINTED W1 UNLESS OTHERWISE NOTED.2. ALL DOORS / FRAMES AND PAINTED WINDOW TRIM / FRAMES SHALL BE PAINTED P2 UNLESS OTHERWISE NOTED.3. ALL EXISTING CABINETS AND RELOCATED CABINETS IN ROOM 101 TO BE PAINTED P34. EXISTING FUME HOOD IN 101 TO BE PAINTED TO MATCH CABINETS P34. ALL EXISTING CABINETS IN B01 OUTSIDE OF WORK AREA TO REMAIN NOT TO BE PAINTED, U.O.N.5. MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, EXPOSED PIPES, CONDUIT ETC. TO BE PAINTED 6. FLOORING AND BASE IN ROOM 101 TO BE PAINTED F1A.SCRUB AND CLEAN FLOOR WITH BRISTLE BRUSH AND EMULSIFYING CLEANER & DEGREASERB. PRIME ALL SURFACES WITH EPOXY PRIMERC. PAINT ALL SURFACES WITH 100% SOLIDS EPOXY FINISH KEY:PAINTP1PAINT COLOR 1 FINISH NOTES:1. ALL WALLS TO BE PAINTED P1 UNLESS OTHERWISE NOTED.DEMOLITION NOTES:CEILINGS: REMOVE AND SALVAGE FOR REINSTALLATION CEILING AND CEILING MOUNTED EQUIPMENT TO ALLOW FOR THE WORK TO BE COMPETED.REMOVE ABANDONED CONNECTIONS, PIPING, CONDUIT, WIREMOLD, ETC. ALSO SEE MEP DRAWINGS, PATCH WALL AS REQUIRED TO RESTORE SURFACE TO MATCH ADJACENT EXISTING CONDITION. GENERAL NOTES:1. SEE EXISTING PHOTOS FOR ADDITIONAL SCOPE INFORMATION, TYPICAL2. PATCH ALL DAMAGED WALL SURFACES WITHIN ROOM B01 AND 101, TO MATCH EXISTING, TYPICAL 3. ALL EXISTING CABINETS, EQUIPMENT, AND FURNITURE TO BE PROTECTED DURING CONSTRUCTION, TYPICAL.4. RELOCATE EQUIPMENT FROM SNEE HALL AND WARD HALL AS NOTED. COORDINATE MOVE TIMING AND DETAILS WITH OWNER. 5. ALL EQUIPMENT IN ROOM B01 OUTSIDE OF THE WORK AREA TO REMAIN IN USE BY THE OWNER DURING CONSTRUCTION. ANY INTERRUPTION TO POWER, DATA, OR ACCESS TO THE EQUIPMENT IS TO BE COORDINATED WITH THE OWNER AT LEAST TWO WEEKS IN ADVANCE OF ANY INTERRUPTION.6. REINSTALL CEILING, GRID, AND CEILING MOUNTED EQUIPMENT TO MATCH PRE-RENOVATION CONDITIONS. DAMAGED CEILING PANELS TO BE REPLACED WITH MATCHING PANELS FURNISHED BY OWNER.7. AT LOCATIONS WHERE OPENINGS ARE MADE IN EXISTING CONSTRUCTION TO FACILITATE THE INSTALLATION OF MEP WORK, RESTORE TO PRE-CONSTRUCTION CONDITIONS AND MATCH ADJACENT CONSTRUCTION, U.O.N.8. OFCI: OWNER FURNISHED, CONTRACTOR INSTALLED9.PROVIDE BLOCKING AS REQUIRED AT ALL WALL-MOUNTED SHELVING, CABINETS, FURNITURE, AND ANCILLARY EQUIPMENT.10. COORDINATE ALL POWER REQUIREMENTS WITH ELECTRICAL POWER PLANS, EXISTING CONDITIONS, AND OWNER PROVIDED EQUIPMENT. 11. MOUNT ALL WALL CABINETS TO BE 2' FROM BENCHTOP TO BOTTOM OF CABINET.P2PAINT COLOR 2 P3PAINT COLOR 3F1 FLOOR FINISH ANSI -2003FIG. 308.2.1UNOBSTRUCTED FORWARD REACHFIG. 308.2.2OBSTRUCTED HIGH FORWARD REACHFIG. 308.3.1UNOBSTRUCTED SIDE REACHFIG. 308.3.2OBSTRUCTED HIGH SIDE REACHPROTRUDING OBJECTSCLEAR FLOOR SPACEUnless otherwise specified may include kneeand toe clearancesCIRCULAR TURNING SPACEMay include knee and toe clearances'T-TURN' TURNING SPACEMay include knee and toe clearances only atthe end of either the base or one arm.GENERAL -TYPICAL CLEARANCES AND REACH RANGES 48" MAX48"15" MIN.20" MAX48" MAX25" MAX44" MAX48" MAX15" MIN.46" MAX24" MAX34" MAX.48" MAX10"34" MAX.4" MAX80"27"4'-0"2'-6"5'-0"5'-0"3'-0"1'-0"3'-0"1'-0"EXCEPTIONS:(a) HANDRAILS MAY PROTRUDE 4-1/2" MAX.(b) DOOR CLOSERS & STOPS MAY BE 78" MIN. ABOVE THE FLOORFIG. 307.2WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A101B01 - DEMO &EQUIPMENTPLANS6/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho Plaza1/4" = 1'-0"F6PARTIAL PLAN B01 - FURNITURE & EQUIPMENT1/4" = 1'-0"A1PARTIAL PLAN B01 - DEMO1/4" = 1'-0"E1TYPICAL MOUNTING HEIGHTS# Description Date EXISTING BENCH AND CABINETS ABOVETO REMAINEXISTING SINK5'-0"5'-11"EXISTING FUME HOOD TO REMAINEXISTING BENCH TO REMAINCE-440NIC2'-0"REF 1OFCIREF 2OFCIADA SINK -OFCI3'-0"MOVEABLELAB TABLE(60"x30") -NICLAB BENCH -NIC(5'X5')4'-8 3/4"5'-1"EXISTING BENCH AND LOWER CABINET TO REMAIN SNORKEL EXHAUST -50" ABOVE BENCH TOP2'-6"4'-0"(1) RELOCATED 3' WALL CABINET -OFCI ADD SECOND COLD WATER LINE, SEE MEP DWGS FOR MORE DETAILADD COMPRESSED AIR LINE, SEE MEP DWGS FOR MORE DETAILTALL METAL CABINET, NIC EXISTING ELECTRICAL PANEL48"X48" PLYWOOD ABOVE SINK WITH BLOCKING AS NEEDED. MUST HOLD 300LBSADDITIONAL BENCHTOP COLD WATER SUPPLY OUTLET, SEE PLUMBING DWGS FOR DETAILS MOVEABLE TABLE FOR REACTOR PC (24"X36") NIC 602 SF101EXISTING DATA PANELBALANCE TABLE (24"X36") -NICBALANCE TABLE (24"X36") -NIC(2) RELOCATED 3' WALL CABINETS -OFCI FLEXIBLE EXHAUST DUCT TO BENCH HEIGHT (2) RELOCATED 3' WALL CABINETS -OFCI30"NEW PLASTIC LAMINATE COUNTERTOP SECURE TO EXISTING BASE AND LEGSINSTALL MORGAN MILWAUKEE BENCH VISE #45ACOORDINATE FINAL LOCATION WITH OWNER. OFCI.LOCK DOOR, PROVIDE SIGNAGEINDICATING IT IS NOT AN EXITE4A102FLOOR MOUNTED GAS CYLINDER RACK.COORDINATE FINAL LOCATION WITH OWNERFINISH NOTES:1. ALL WALLS TO BE PAINTED W1 UNLESS OTHERWISE NOTED.2. ALL DOORS / FRAMES AND PAINTED WINDOW TRIM / FRAMES SHALL BE PAINTED P2 UNLESS OTHERWISE NOTED.3. ALL EXISTING CABINETS AND RELOCATED CABINETS IN ROOM 101 TO BE PAINTED P34. EXISTING FUME HOOD IN 101 TO BE PAINTED TO MATCH CABINETS P34. ALL EXISTING CABINETS IN B01 OUTSIDE OF WORK AREA TO REMAIN NOT TO BE PAINTED, U.O.N.5. MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, EXPOSED PIPES, CONDUIT ETC. TO BE PAINTED 6. FLOORING AND BASE IN ROOM 101 TO BE PAINTED F1A.SCRUB AND CLEAN FLOOR WITH BRISTLE BRUSH AND EMULSIFYING CLEANER & DEGREASERB. PRIME ALL SURFACES WITH EPOXY PRIMERC. PAINT ALL SURFACES WITH 100% SOLIDS EPOXY FINISH KEY:PAINTP1PAINT COLOR 1 FINISH NOTES:1. ALL WALLS TO BE PAINTED P1 UNLESS OTHERWISE NOTED.DEMOLITION NOTES:CEILINGS: REMOVE AND SALVAGE FOR REINSTALLATION CEILING AND CEILING MOUNTED EQUIPMENT TO ALLOW FOR THE WORK TO BE COMPETED.REMOVE ABANDONED CONNECTIONS, PIPING, CONDUIT, WIREMOLD, ETC. ALSO SEE MEP DRAWINGS, PATCH WALL AS REQUIRED TO RESTORE SURFACE TO MATCH ADJACENT EXISTING CONDITION. GENERAL NOTES:1. SEE EXISTING PHOTOS FOR ADDITIONAL SCOPE INFORMATION, TYPICAL2. PATCH ALL DAMAGED WALL SURFACES WITHIN ROOM B01 AND 101, TO MATCH EXISTING, TYPICAL 3. ALL EXISTING CABINETS, EQUIPMENT, AND FURNITURE TO BE PROTECTED DURING CONSTRUCTION, TYPICAL.4. RELOCATE EQUIPMENT FROM SNEE HALL AND WARD HALL AS NOTED. COORDINATE MOVE TIMING AND DETAILS WITH OWNER. 5. ALL EQUIPMENT IN ROOM B01 OUTSIDE OF THE WORK AREA TO REMAIN IN USE BY THE OWNER DURING CONSTRUCTION. ANY INTERRUPTION TO POWER, DATA, OR ACCESS TO THE EQUIPMENT IS TO BE COORDINATED WITH THE OWNER AT LEAST TWO WEEKS IN ADVANCE OF ANY INTERRUPTION.6. REINSTALL CEILING, GRID, AND CEILING MOUNTED EQUIPMENT TO MATCH PRE-RENOVATION CONDITIONS. DAMAGED CEILING PANELS TO BE REPLACED WITH MATCHING PANELS FURNISHED BY OWNER.7. AT LOCATIONS WHERE OPENINGS ARE MADE IN EXISTING CONSTRUCTION TO FACILITATE THE INSTALLATION OF MEP WORK, RESTORE TO PRE-CONSTRUCTION CONDITIONS AND MATCH ADJACENT CONSTRUCTION, U.O.N.8. OFCI: OWNER FURNISHED, CONTRACTOR INSTALLED9.PROVIDE BLOCKING AS REQUIRED AT ALL WALL-MOUNTED SHELVING, CABINETS, FURNITURE, AND ANCILLARY EQUIPMENT.10. COORDINATE ALL POWER REQUIREMENTS WITH ELECTRICAL POWER PLANS, EXISTING CONDITIONS, AND OWNER PROVIDED EQUIPMENT. 11. MOUNT ALL WALL CABINETS TO BE 2' FROM BENCHTOP TO BOTTOM OF CABINET.P2PAINT COLOR 2 P3PAINT COLOR 3F1 FLOOR FINISH REMOVE EXISTING WALL CABINET, CLEAN, PAINT AND RE-INSTALL IN NEW LOCATION ON EAST WALL ABOVE EXISTING BENCH.EXISTING BENCH AND CABINETS ABOVE TO REMAINEXISTING SINKEXISTING FUME HOOD TO REMAINEXISTING BENCH TO REMAINREMOVE EXISTING SINK & ALL ASSOCIATED PIPINGREMOVE EXISTING BREAKER PANEL AND ASSOCIATED WIRINGCUT EXISTING COUNTERTOP AT BASE OF WIREMOLD. BACKSPLASH TO REMAIN.EXISTING BASE AND SUPPORT LEGS TO REMAIN AND BE RE-USED WITH NEW COUNTERTOP REMOVE ALL SHELVING AND SUPPORT BRACKETS, COMPLETE. PLASTIC LAMINATE COUNTERTOP, MATCH EXISTING COLORRE-USE EXISTING BASE FOR SUPPORT30"1 1/2"EXISTING BACKSPLASH & WIREMOLD TO REMAINWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A102101 - DEMO &EQUIPMENTPLANS6/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho Plaza1/4" = 1'-0"A2PARTIAL PLAN 101 - FURNITURE & EQUIPMENT1/4" = 1'-0"A1PARTIAL PLAN 101 - DEMO3/4" = 1'-0"E4COUNTERTOP# Description Date FIT PANEL AROUND SNORKEL EXHAUST DUCT AND SUPPORT. COORDINATE FINAL LOCATION WITH OWNER/ARCHITECT. FIT PANEL AROUND ADJUSTABLE FLEX CONNECTION FOR FUME HOOD FIT PANEL AROUND SNORKEL EXHAUST DUCT AND SUPPORT. COORDINATE FINAL LOCATION WITH OWNER/ARCHITECT. RETURN AIR GRILLESUPPLY AIR GRILLEEXISTING WIRE MOLDSPRINKLER HEADEXISTING LAY-IN LIGHT FIXTURES 2' X 4' EXISTING ACOUSTICAL PANEL CEILINGREFLECTED CEILING PLAN NOTES:1. REPLACE ANY DAMAGED OR DISCOLORED EXISTING CEILING TILES WITH OWNER ATTIC STOCK. DAMAGED TILES IDENTIFIED BUT NOT LIMTED TO THOSE SHOWN. 2. ALL SNORKEL EXHAUST TO BE SECURED TO STRUCTURAL DECK AND CENTER IN CEILING TILE. 3. ALL EXISTING CEILING WIREMOLD TO REMAIN.4. REPAIR CEILINGS DAMAGED BY CONCEALED SCOPE INCLUDING BUT NOT LIMITED TO MEP WORK THAT IS NOT SPECIFICALLY DETAILED ON THIS DRAWING. 5. REPAIR AND REPLACE DAMAGED GYPSUM SOFFITS AND CEILINGS IMPACTED BY NEW WORK AT EXISTING LOCATIONS AND CEILING HEIGHTS, U.O.N. 6. PAINT ALL EXPOSED DUCTWORK, CONDUIT, WIREMOLD, PIPES, ETC TO MATCH CEILING, TYPICAL. CEILING MATERIALS:LIGHT FIXTURES:OTHER:2' X 4' EXISTING ACOUSTICAL PANEL IDENTIFIED FOR REPLACEMENTEXISTING GYPSUM CEILINGWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A151B01REFLECTEDCEILING PLAN6/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho Plaza1/4" = 1'-0"A6B01 - RCP# Description Date FIT PANEL AROUND FLEXIBLE EXHAUST REPLACE GRILLE AND CEILING PANEL FIT PANEL AROUND SNORKEL EXHAUST DUCT AND SUPPORT. COORDINATE FINAL LOCATION WITH OWNER/ARCHITECT. RETURN AIR GRILLESUPPLY AIR GRILLEEXISTING WIRE MOLDSPRINKLER HEADEXISTING LAY-IN LIGHT FIXTURES 2' X 4' EXISTING ACOUSTICAL PANEL CEILINGREFLECTED CEILING PLAN NOTES:1. REPLACE ANY DAMAGED OR DISCOLORED EXISTING CEILING TILES WITH OWNER ATTIC STOCK. DAMAGED TILES IDENTIFIED BUT NOT LIMTED TO THOSE SHOWN. 2. ALL SNORKEL EXHAUST TO BE SECURED TO STRUCTURAL DECK AND CENTER IN CEILING TILE. 3. ALL EXISTING CEILING WIREMOLD TO REMAIN.4. REPAIR CEILINGS DAMAGED BY CONCEALED SCOPE INCLUDING BUT NOT LIMITED TO MEP WORK THAT IS NOT SPECIFICALLY DETAILED ON THIS DRAWING. 5. REPAIR AND REPLACE DAMAGED GYPSUM SOFFITS AND CEILINGS IMPACTED BY NEW WORK AT EXISTING LOCATIONS AND CEILING HEIGHTS, U.O.N. 6. PAINT ALL EXPOSED DUCTWORK, CONDUIT, WIREMOLD, PIPES, ETC TO MATCH CEILING, TYPICAL. CEILING MATERIALS:LIGHT FIXTURES:OTHER:2' X 4' EXISTING ACOUSTICAL PANEL IDENTIFIED FOR REPLACEMENTEXISTING GYPSUM CEILINGWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A152101REFLECTEDCEILING PLAN6/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho Plaza1/4" = 1'-0"A6FIRST FLOOR ROOM 101 - RCP# Description Date RELOCATED FROM WARD HALL NEW EQUIPMENT (FURNISHED BY OWNER):RELOCATED FROM SNEE ROOM 2157:1. 6ft PROTECTOR XL LABORATORY HOOD37.7" EXTERIOR MODEL: 111614200-24577A. WOODEN WORK BENCH WITH VICE B. HTL REACTOR WITH CASING C. HTL REACTOR CONTROLLER TABLED. THERMAL SPALLATION E. THERMAL SPALLATION CONTROL BOX F. STEEL TOOLBOX I. (2) SNORKEL EXHAUST NEW EQUIPMENT:1. (1) 2 CYLINDERS (2X1) -BARRICADE -GAS CYLINDER RACK MODEL # BR2X1FSUSA SAFETY 2" SQUARE STEEL TUBE CONTINUOUSLY SEAM WELDED, 0.125" THICKCYLINDER CAPACITY: 1-2 CYLINDER DIAMETERS SUPPORTED: UP TO 12"CYLINDER RACK DIMENSIONS: 30"W X 16"D X 30"HMEETS USGS HIGH SEISMIC HAZARD ZONE REQUIREMENTS WHEN INSTALLED PROPERLYOSHA, NFP1, NFPA 55 AND CGA COMPLIANT WHEN USED PROPERLYHOLDS TWO CYLINDERS, TWO WIDE BY ONE DEEPTWO LEVELS OF WELDED STEEL CHAINSSNAPS FOR EACH CYLINDER3 PRE-DRILLED 0.531" DIAMETER FLOOR MOUNTING HOLESANCHOR BOLTS (MODEL # ACITW5FS) AVAILABLE FOR PURCHASE SEPARATELY (NOT INCLUDED)CYLINDER RACK SEALED WITH EXTERIOR GRADE BLACK POWDER-COAT PAINTMADE IN THE USAPRODUCT WEIGHT: 91 LBSWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A201EQUIPMENTMATRIX -ROOM B016/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho Plaza# Description Date NEW EQUIPMENT (FURNISHED BY OWNER):RELOCATED FROM SNEE ROOM 3158:G. MORGAN MILWAUKEE BENCH VISE #45AII.ADA DUAL DEPTH SINK WITH BASE CABINET I. (1) SNORKEL EXHAUST NEW EQUIPMENT:1. (1) 2 CYLINDERS (2X1) -BARRICADE -GAS CYLINDER RACK MODEL # BR2X1FSUSA SAFETY 2" SQUARE STEEL TUBE CONTINUOUSLY SEAM WELDED, 0.125" THICKCYLINDER CAPACITY: 1-2 CYLINDER DIAMETERS SUPPORTED: UP TO 12"CYLINDER RACK DIMENSIONS: 30"W X 16"D X 30"HMEETS USGS HIGH SEISMIC HAZARD ZONE REQUIREMENTS WHEN INSTALLED PROPERLYOSHA, NFP1, NFPA 55 AND CGA COMPLIANT WHEN USED PROPERLYHOLDS TWO CYLINDERS, TWO WIDE BY ONE DEEPTWO LEVELS OF WELDED STEEL CHAINSSNAPS FOR EACH CYLINDER3 PRE-DRILLED 0.531" DIAMETER FLOOR MOUNTING HOLESANCHOR BOLTS (MODEL # ACITW5FS) AVAILABLE FOR PURCHASE SEPARATELY (NOT INCLUDED)CYLINDER RACK SEALED WITH EXTERIOR GRADE BLACK POWDER-COAT PAINTMADE IN THE USAPRODUCT WEIGHT: 91 LBSWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A202EQUIPMENTMATRIX -ROOM 1016/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho Plaza# Description Date WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A203EXISTINGPHOTOS - B016/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho PlazaSOUTH EAST CORNERSOUTH EAST PARTIAL WALLNORTH WALLCEILING -EAST WALL WEST WALLNORTH WALLNORTH WALLNORTH EAST CORNER CEILING -EAST WALL CEILING -SOUTH WALL CEILING -WEST WALL # Description Date WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A204EXISTINGPHOTOS - 1016/2/202111614/COB# 2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations113 Ho PlazaNORTH WEST CORNERNORTH WALLNORTH EAST CORNERNORTH COUNTER SUPPORTEAST WALL SINK EAST WALL CENTRAL BENCH WEST WALL CENTRAL BENCH CENTRAL BENCH CENTRAL BENCH CENTRAL BENCH SOUTH WALL SOUTH WALL -BASE CABINET SOUTH WALL -FUME HOODSOUTH WALL -FUME HOOD# Description Date ISSUE:DATE:DRAWN BY:CHECKED BY:SCALE:PROJECT NO.SHEET TITLESHEETDRAWING NO.ALTERATION OF THIS DOCUMENTEXCEPT BY A LICENSED DESIGN PROFESSIONAL, IS A VIOLATION OFNEW YORK STATE EDUCATIONAL LAW.OFFS ENGINEERING,DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044Enter address hereR:\Revit MEP 2012\Templates\S&A_Mechanical.rte10/5/2011 4:16:29 PMOwnerProject NameSK-M201/01/2019AuthorCheckerProject NumberUnnamedMARK DATE DESCRIPTIONPLUMBING SYMBOLS AND ABBREVIATIONSSYMBOLDESCRIPTION (ABBREVIATION)BALANCING VALVEBACKFLOW PREVENTER (BFP)CHECK VALVEPRESSURE REDUCING VALVE (PRV)STRAINER WITH BLOWDOWNUNIONREMOVE TO POINT AND CAPREMOVE TO POINT FOR RECONNECTIONSHOWER HEADCLEANOUT IN FLOOR (FPCO)CLEANOUT IN SUSPENDED PIPE (CO)FLOOR DRAINPIPE BRANCH TAKE-OFF FROM BOTTOMPIPE DROPPIPE RISEROOF DRAIN/SANITARY VENTROOF DRAIN ABOVEVENT THRU ROOF (VTR)HOSE BIBB (HB)ANTIFREEZE WALL HYDRANT (AFWH)COMPRESSED AIR PIPINGFPCOCOCACWHW (__)PIPE BRANCH TAKE-OFF FROM TOPSHUT OFF VALVEOSTPDRHWSANSANSTSTVCOLD WATER PIPINGHOT WATER PIPING (____°F)OVERFLOW STORM PIPINGPUMP DISCHARGE PIPINGHOT WATER RETURN PIPINGSANITARY SEWER (ABOVE GROUND)SANITARY SEWER (UNDERGROUND/UNDERFLOOR)STORM SEWER (ABOVE GROUND)STORM SEWER (UNDERGROUND/UNDERFLOOR)VENT PIPINGEMERGENCY SHOWERESES/EEWEMERGENCY SHOWERCDCONDENSATE DRAIN PIPINGGRADE CLEANOUT (GCO)GCOWALL PLATE CLEANOUT (WPCO)WPCOEMERGENCY SHOWER/ EMERGENCY EYE WASHPIPING TO BE DEMOLISHEDTYPE (D)AAVAIR ADMITTANCE VALVESHOCK ABSORBER (SA-_)SWSOFTENED WATER PIPINGPOINT OF CONNECTION -NEW TO EXISTINGP-TRAPCWCOLD WATER PIPING (UNDERGROUND/UNDERFLOOR)EEWEMERGENCY EYE WASHUPPITCH OF PIPEDNTEMPERATURE WELLTHERMOMETERPRESSURE GAUGE (WITH VALVE)PIPING EXISTING TO REMAINTYPE (E)POINT OF REMOVAL -DEMOLITION TO EXISTINGACID WASTE PIPINGAW??PLAN DETAILBUILDING SECTIONDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDEXTENT OF DETAILEXTENT OF DETAILA1B1C1D1E1A2B2C2D2E2A3B3C3D3E3A4B4C4D4E4A5B5C5D5E5A6B6C6D6E6DETAIL NUMBERDETAIL SCALEDETAIL NAMEDETAIL NUMBERPLAN SETUPSHEET NUMBER WHERE DETAIL IS LOCATEDCAUTION: THESE DOCUMENTS WERE DIGITALLY PRODUCED AND/OR REPRODUCED. CONFIRM REDUCTION OR MAGNIFICATION USING DIMENSIONAL 3"-LONG LINE IN TITLE BARS. IF SCALING DRAWINGS FOR APPROXIMATE DIMENSIONS, ALTERNATE ARCHITECTURAL SCALES MAY BE USED AS FOLLOWS:DOCUMENT REDUCTION/MAGNIFICATION SCALEIF LINE MEASURES 2”(67% COPY):USE 3/16th SCALE ON 1/8”=1’-0”DWGUSE 3/8th SCALE ON 1/4”=1’-0”DWGIF LINE MEASURES 1.5”(50% COPY):USE 1/16th SCALE ON 1/8”=1’-0”DWGUSE 1/8th SCALE ON 1/4”=1’-0”DWG3"3"????XXXX" = X"1.PLUMBING DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ALL RISERS AND DROPS ARENOT SHOWN. CONTRACTORS SHOULD INCLUDE THESE IN THE BID. ADJUSTINSTALLATION OF PIPING TO ACCOMMODATE WORK WITH OBSTACLES ANDINTERFERENCES ENCOUNTERED AS PART OF THE CONTRACT.2.ALL FIXTURES SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERSPUBLISHED INSTRUCTIONS.3.MATERIALS AND INSTALLATION SHALL COMPLY WITH THE MOST RECENT PLUMBINGCODE OF NEW YORK STATE. APPLICABLE PROVISIONS OF THE EDITION OF NFPA,AND LOCAL UTILITY REGULATIONS.4.SEAL ALL WALL AND FLOOR PENETRATIONS AIR TIGHT. ALL PENETRATIONS THROUGHFIRE RATED WALLS TO BE SEALED PER UL DETAILS.5.PIPING SHALL NOT BE INSTALLED ABOVE ELECTRICAL PANELS. COORDINATE LOCATIONOF PIPING WITH ELECTRICAL CONTRACT WHEN SHOWN NEAR PANELS OR OVERELECTRICAL ROOMS.6.EQUIPMENT, MATERIALS AND LABOR REQUIRED BY THESE CONTRACT DRAWINGS SHALLBE GUARANTEED TO BE FREE OF DEFECTIVE MATERIALS OR WORKMANSHIP FOR ONEYEAR AFTER ACCEPTANCE OF THE PROJECT UNLESS SPECIFIED OTHERWISE.DEFECTIVE MATERIALS OR WORKMANSHIP OCCURRING DURING THIS PERIOD SHALL BECORRECTED AT NO ADDITIONAL COST.7.PROVIDE SHUTOFF VALVES IN A READILY ACCESSIBLE LOCATION IN ALL PIPINGSYSTEMS IN ALL BRANCH PIPING SERVING MORE THAN ONE FIXTURE.8.SCHEDULE NEW CONSTRUCTION WORK WITH THE OWNERS REPRESENTATIVE WELL INADVANCE. CONSTRUCTION WORK AND DEMOLITION SHALL BE PERFORMED AT SUCHTIMES AND UNDER SUCH CONDITIONS AS SUITS THE OWNER, AT NO ADDITIONAL COSTFOR PREMIUM TIME.9.ALL FINISHES AND SURFACES TO REMAIN WHICH ARE DAMAGED DURING THE WORK OFTHIS CONTRACT SHALL BE REPAIRED OR REPLACED. FINISHES FINISHES TO MATCHEXISTING TO THE SATISFACTION OF THE OWNER.10.EXISTING SYSTEMS SHOWN ON DRAWINGS ARE BASED ON AVAILABLE RECORDDRAWINGS. THIS INFORMATION IS PARTIALLY VERIFIED. THE CONTRACTOR ISRESPONSIBLE TO FIELD VERIFY AND INVESTIGATE ALL CONDITIONS THAT AFFECT THEWORK PRIOR TO SUBMITTING THE BID.PLUMBING GENERAL NOTESFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910P001DRAWINGINDEX,SYMBOL LIST &ABBREVS.6/2/202111614/COB# 2013DDD113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab RenovationsPLUMBING DRAWING INDEXNUMBER NAMEREVISIONS# DATEP001 DRAWING INDEX, SYMBOL LIST & ABBREVS.P101 PARTIAL FLOOR PLAN - LAB B01P102 PARTIAL FLOOR PLANS -LAB 101TO THE BEST OF THE ENGINEER'S PROFESSIONAL JUDGEMENT, THE DESIGN OF THIS PROJECT CONFORMS TO ALL APPLICABLE PORTIONS OF THE FOLLOWING:THE 2020 NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODETHE 2020 NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, 2016 ASHRAE 90.1, AND 2007 ASHRAE 183; FOLLOWING THE COMPLIANCE PATH MARKED BELOW:ANSI / ASHRAE / IESNA 90.1, AS AMENDED BY 19 NYCRR PART 1240.IECC CHAPTER 4 [CE] PRESCRIPTIVE PROVISIONS (SECTIONS C402, C403, C404, C405, C408 AND ONE OF THE SIX OPTIONS IN SECTION C406 AS NOTED BELOW:MORE EFFICIENT HVAC PERFORMANCE IN ACCORDANCE WITH SECTION C406.2.REDUCED LIGHTING POWER DENSITY SYSTEM IN ACCORDANCE WITH SECTION C406.3.ENHANCED LIGHTING CONTROL IN ACCORDANCE WITH SECTION C406.4.ON-SITE SUPPLY OF RENEWABLE ENERGY IN ACCORDANCE WITH SECTION C406.5.PROVISION OF A DEDICATED OUTDOOR AIR SYSTEM FOR CERTAIN HVAC EQUIPMENT IN ACCORDANCE WITH SECTION C406.6.HIGH-EFFICIENCY SERVICE WATER HEATING IN ACCORDANCE WITH SECTION C406.7.ENHANCED ENVELOPE PERFORMANCE IN ACCORDANCE WITH SECTION C406.8.REDUCED AIR INFILATRATION IN ACCORDANCE WITH SECTION C406.9.TOTAL BUILDING PERFORMANCE PROVISIONS (SECTION C407)THE NEW YORK STATE EDUCATION DEPARTMENT ("SED") MANUAL OF PLANNING STANDARDSTHE 2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIESTHE 2018 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF:HOSPITALSOUTPATIENT FACILITIESRESIDENTIAL HEALTH, CARE, AND SUPPORT FACILITIESALL SYMBOLS SHOWN ARE NOT NECESSARILY USEDPLUMBING FIXTURE SCHEDULE 'BASIN FIXTURES'FIXTURE TAG TYPEFIXTURE OUTSIDEDIMENSIONS (INCHES)FIXTURE INSIDEDIMENSIONS (INCHES)BASIN DEPTH(INCHES)ADA COMPLIANT(YES/NO)MANUFACTURER MODELFAUCETOPERATIONFAUCET SPREAD(INCHES)SPOUT TYPESPOUTLENGTHHANDLE TYPE OUTLET T YPE GPM DRAIN TYPEFAUCETMANUFACTURERFAUCET MODEL REMARKSSK-A SINK 26.70 x 16.69 25 x 15 5" Yes --- --- MANUAL SINGLE HOLE GOOSENECK 5 3/4 4" WRISTBLADE AERATOR 2.2 GRID T&S BL-5704-05 FAUCET ONLY, INTEGRAL SINK BY OTHERSPLUMBING FIXTURE ROUGH IN SCHEDULEFIXTURE WASTE VENT CW HW REMARKSSK-A 1 1/2" 24" 1/2" 1/2" PD (E)CA (E)ST (E)PD (E)CWCA1/2" CW1/2" CA1/2" CWB01EXISTING SINKP3P4P5P6P7B00JBPD (E)AWCA1 1/2" AV (E)1 1/2" AV (E)1 1/2" AV (E)3" AV (E)1 1/2" AVP11EXISTING HOODNEW FUME HOODFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910P101PARTIALFLOOR PLAN -LAB B016/2/202111614/COB# 2013DDD113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations3"SCALE: 1/4" = 1'-0"P101A3PARTIAL PLAN - LAB B01PLUMBING KEYED NOTESP3 CONNECT 1/2"CA TO EXISTING 1/2"CA ON SERVICE SIDE OF REGULATOR.P4 CONNECT 1/2"CW TO EXISTING 1"CW WITH VALVE.P5 PROVIDE 1/2"CW WITH VALVE AND THREADED OUTLET.P6 CONNECT 2"AW TO EXISTING IN WALL.P7 CONNECT 2"AW, 1/2"CW, & 1/2"CA TO RELOCATED HOOD. PROVIDE ADDITIONAL CONTROLSAND OUTLETS TO MATCH EXISTING. CONNECT AW TO EXISTING TRAP OUTLET.P11 CONNECT 1 1/2"AV TO EXISTING ABOVE CEILING. DISCONNECT AW, CW & HW PIPING TO SINK. CAP PIPING FOR RECONNECTION.CA (E)HW (E)CW (E)CA (E)AW (E)AW (E)CW (E)HW (E)RHW (E)CA (D)CA (D)CA (D)REMOVE CA OUTLET AND PIPINGPIPING LOCATED BELOW CABINETRYEXISTING 1 1/2"AW DNEXISTING FUME HOODEXISTING 2"AW DNEXISTING FDHW (E)CW (E)SK-AHW (E)CW (E)CA (E)CA (E)CA (E)CACWHW (E)CW (E)RHW (E)AW (E)AW (E)EXISTING FDP2P9P4P8CWEXISTING SINKEXISTING PIPING BELOW BENCH2" AW (E)1011 1/2" AV1 1/2" AV1 1/2" AVP12P10P1HW (E)CW (E)FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910P102PARTIALFLOOR PLANS-LAB 1016/2/202111614/COB# 2013DDD113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations3"SCALE: 1/4" = 1'-0"P102A2PARTIAL PLAN 101 - DEMO3"SCALE: 1/4" = 1'-0"P102A6PARTAIL PLAN - 101PLUMBING KEYED NOTESP1 PROVIDE 1/2"CW WITH THREADED OUTLET, VALVE AND ESCUTCHEON LOCATED ABOVE COUNTERTOP.P2 PROVIDE 1/2"CW WITH VALVE AND CAP ON WALL ADJACENT TO COUNTERTOP FOR CONNECTION TOCOUNTERTOP EQUIPMENT.P4 CONNECT 1/2"CW TO EXISTING 1"CW WITH VALVE.P8 CONNECT 1/2"CW, & 1/2"CA TO EXISTING HOOD. PROVIDE ADDITIONAL CONTROLS AND OUTLETS TOMATCH EXISTING.P9 CONNECT 1/2"CA TO EXISTING 1/2"CA.P10 CONNECT SINK TO EXISTING 1 1/2"AW, 1/2"CW & 1/2"HW LOCATED BELOW SINK.P12 CONNECT 1 1/2"AV TO EXISTING 3"AV RISER. ISSUE:DATE:DRAWN BY:CHECKED BY:SCALE:PROJECT NO.SHEET TITLESHEETDRAWING NO.ALTERATION OF THIS DOCUMENTEXCEPT BY A LICENSED DESIGNPROFESSIONAL, IS A VIOLATION OFNEW YORK STATE EDUCATIONAL LAW.OFFS ENGINEERING,DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044Enter address hereR:\Revit MEP 2012\Templates\S&A_Mechanical.rte10/5/2011 4:16:29 PMOwnerProject NameSK-M201/01/2019AuthorCheckerProject NumberUnnamedMARK DATE DESCRIPTION14/10RECTANGULAR DUCT (SIZE IN INCHES)ROUND DUCT (DIAMETER IN INCHES)14ØAUTOMATIC AIR DAMPERVOLUME DAMPERSMOKE DAMPERFIRE DAMPERSDVDFDSYMBOLDESCRIPTIONAADDUCTWORK SYMBOLS & ABBREVIATIONSFIRE SMOKE DAMPERFSDDUCT SMOKE DETECTOR (FURNISHED & WIRED BY DIV 28, MOUNTED BY DIV 23. INSTALL PER MANUFACTURER'S INSTRUCTIONS)DSDOVAL DUCT (SIZE IN INCHES)14/10ØLOW VELOCITY DUCTWORK SYMBOLSSINGLE LINEDOUBLE LINEDESCRIPTIONDIRECTION OF FLOWDUCT SIZE, FIRST FIGURE IS SIZE SHOWN12/2012/20SUPPLY DUCT SECTION (POSITIVE) PRESSURE, FIRST FIGURE IS TOP20/1220/12RETURN / EXHAUST DUCT SECTION20/1220/12ROUND SIDE TAP WITHVOLUME DAMPER (UNLESSOTHERWISE NOTED)90° BRANCHTAKE OFF(45° ENTRY TYPE FORRECTANGULAR DUCT)1-1/4A)XB (MIN)VDVDAxB4" (MIN)45°VDVDVDDUAL 90°BRANCH TAKEOFF(45° ENTRY TYPE)FLEXIBLE DUCTFLEX CONNECTIONACCESS DOORADADGRILLE REGISTEROR DIFFUSER INBOTTOM OF DUCTDUCTELBOW UPOR DOWNTURN UPTURN DOWN12x6TURN DOWN12x6TURN UPORLONG RADIUS 90DEGREE ELBOWOR TURNINGVANESTRANSITION: LOCATION OF TRANS. IS DIAGRAMMATICAL CONTRACTOR MAY EXTEND LENGTH OF LARGER DUCT TO ACCOMMODATE STD. LENGTH DUCT SECTIONS.CONTRACTOR'S OPTIONAS SHOWN90 DEGREE BRANCHTAKEOFF FROMVERTICAL DUCT-45DEGREE ENTRY TYPEELEV.PLANPLANELEV.DUCT RISE / DROP TOAVOID OBSTRUCTIONARROW INDICATES AIRFLOW DIRECTION90° BRANCH TAKE OFF(TEE TYPEFOR ROUND DUCT)RISERDDROPRISEUPDNDROPVDVDRETURN / EXHAUST DUCT PENETRATION OF FLOOR OR ROOF ABOVE. SEE PLANS FOR DAMPER REQUIREMENTSSUPPLY DUCT PENETRATION OF FLOOR OR ROOF ABOVE. SEE PLANS FOR DAMPER REQUIREMENTSMECHANICAL PIPING SYMBOLS & ABBREVIATIONSSHUTOFF VALVE (REFER TO SPECIFICATIONS FOR SPECIFIC TYPE)CHECK VALVEBUTTERFLY VALVEBALL VALVEPETCOCKCALIBRATED BALANCING VALVEUNIONPRESSURE GAUGE (WITH VALVE)TEMPERATURE SENSORDRAIN VALVE WITH CAPPED AND CHAINED HOSE ENDPIPE UP / PIPE DOWN (ELBOW)BRANCH CONNECTION -UP / DOWNCONCENTRIC REDUCERPIPING (ARROW INDICATES DIRECTION OF FLOW)PIPE ANCHOR PIPE GUIDEGLOBE VALVEPIPE CAPPITCH OF PIPESTRAINER W/ BLOW OFFSTRAINERMVAVPRESSURE RELIEF VALVETEMPERATURE WELLTHERMOMETERTRIPLE DUTY VALVECONDENSATE "P"-TRAPDNUPPSFSPRESSURE SWITCHFLOW SWITCHEXPANSION JOINTPRESSURE REDUCING REGULATOR VALVETGATE VALVE2-WAY CONTROL VALVE3-WAY CONTROL VALVEMANUAL AIR VENT / AUTOMATIC AIR VENTSYMBOLDESCRIPTIONSPECIFIC SHUTOFF VALVE TYPES:SUPPLY DIFFUSER PLAN SYMBOL EXPLANATION:CFMSUPPLY AIR DIFFUSER (NOMINAL 2' x 2')SUPPLY DIFFUSER TYPE (SEE SCHEDULE)RETURN / EXHAUST AIR REGISTERCFMSL8REGISTER/GRILLE PLAN SYMBOL EXPLANATION:CFM (E = EXHAUST / R = RETURN)REGISTER/GRILLE TYPE (SEE SCHEDULE)CFMRE10SYMBOLDESCRIPTIONGRILLE, REGISTER & DIFFUSER SYMBOLSLINEAR SLOT DIFFUSER WITH DISTRIBUTION PLENUMREGISTER AND DIFFUSER AIR FLOW PATTERNS4-WAY BLOW3-WAY BLOW2-WAY BLOWDUCTWORK EXISTING TO REMAIN IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTDUCTWORK REMOVED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTPOINT OF CONNECTION -NEW TO EXISTINGPOINT OF REMOVAL -DEMOLITION TO EXISTINGDEDICATED ELECTRICAL AREA -NO MECHANICAL WORK ALLOWED IN OR ABOVE HIGHLIGHTED AREA UNLESS SPECIFICALLY NOTED OTHERWISEPIPE REMOVED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTPIPE EXISTING TO REMAIN IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTSYS (E)SYSTEM NAME(E) = EXIST TO REMAIN, (D) = EXIST TO BE REMOVEDDUCTWORK PROVIDED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTPIPE PROVIDED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTSYS (D)SYSSYS (D)SYS(10x6) SYS (E)(10) SYS (E)DEMOLITION KEYED NOTEKEYED NOTESYSTEM PHASING SYMBOLSM#MD#??PLAN DETAILBUILDING SECTIONDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDEXTENT OF DETAILEXTENT OF DETAILA1B1C1D1E1A2B2C2D2E2A3B3C3D3E3A4B4C4D4E4A5B5C5D5E5A6B6C6D6E6DETAIL NUMBERDETAIL SCALEDETAIL NAMEDETAIL NUMBERPLAN SETUPSHEET NUMBER WHERE DETAIL IS LOCATEDCAUTION: THESE DOCUMENTS WERE DIGITALLY PRODUCED AND/OR REPRODUCED. CONFIRM REDUCTION OR MAGNIFICATION USING DIMENSIONAL 3"-LONG LINE IN TITLE BARS. IF SCALING DRAWINGS FOR APPROXIMATE DIMENSIONS, ALTERNATE ARCHITECTURAL SCALES MAY BE USED AS FOLLOWS:DOCUMENT REDUCTION/MAGNIFICATION SCALEIF LINE MEASURES 2”(67% COPY):USE 3/16th SCALE ON 1/8”=1’-0”DWGUSE 3/8th SCALE ON 1/4”=1’-0”DWGIF LINE MEASURES 1.5”(50% COPY):USE 1/16th SCALE ON 1/8”=1’-0”DWGUSE 1/8th SCALE ON 1/4”=1’-0”DWG3"3"????XXXX" = X"FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M001DRAWINGINDEX,SYMBOLS &ABBREVS.6/2/202111614/COB# 2013TAM113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab RenovationsMECHANICAL DRAWING INDEXNUMBERNAMEREVISIONS# DATEM001 DRAWING INDEX, SYMBOLS & ABBREVS.M101 B01 FLOOR PLANSM102 101 FLOOR PLANSM601 SCHEDULES & DETAILSM701 CONTROLSHVAC DESIGN CRITERIAINTERIOR DESIGN CONDITIONSHEATING70 deg F DBCOOLING75 deg F DB / 63 deg F WBOUTDOOR DESIGN CONDITIONSSUMMER88 deg F DB / 75 deg F WBWINTER-5 deg F DBCLIMATE ZONE6HVAC DESIGN REQUIREMENTSITEMYES NODUCT SMOKE DETECTORSXFIRE DAMPERSXSMOKE DAMPERSXFIRE RATED ENCLOSUREXFIRE RATED ROOF / FLOOR / CEILING ASSEMBLYXFIRE STOPPING (REFER TO DIVISION 7)XSMOKE CONTROLXECONOMIZER CONTROLN/ADUCT SEALINGXGENERAL MECHANICAL NOTESA REFER TO ARCHITECTURAL DRAWINGS FOR CEILING GRID WORKPREFORMED BY OTHERS. IF NOT SHOWN ELSEWHERE INCLUDE IN THISDIVISIONS WORK AS REQUIRED.B WHERE WORK ISN'T SHOWN BY OTHERS, HVAC CONTRACTOR SHALLREMOVE, STORE, AND REINSTALL EXISTING LAY-IN CEILING TILES & TEESAS REQUIRED FOR ALL WORK SHOWN.C HVAC CONTRACTOR SHALL COORDINATE LEFT OR RIGHT UNITCONNECTION ORIENTATION.D HVAC CONTRACTOR SHALL INSTALL UNIT TO ALLOW FOR MAINTENANCEACCESS TO FILTERS, VALVES, CONTROLS, LUBRICATION POINTS,INCLUDING MOVING EXISTING INTERERENCES SUCH AS CONDUITS,WIRINGS AND PIPING.F CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, AND REPORTDISCREPANCIES TO THE ARCHITECT / ENGINEER AND AWAIT CLARIFICATIONPRIOR TO PROCEEDING WITH REMOVAL AND RENOVATION WORK.LAT LEAVING AIR TEMPERATURELWT LEAVING WATERTEMPERATUREMAX. MAXIMUMMBH 1,000 BTUHMCA MINIMUM CIRCUIT AMPACITYMGAP MEDICAL GAS ALARM PANELMIN. MINIMUMMOCP MAXIMUM OVERCURRENTPROTECTIONMTD MOUNTEDNC NORMALLY CLOSEDNIC NOT IN CONTRACTNO NORMALLY OPENNOM. NOMINALNTS NOT TO SCALEOA OUTSIDE AIROAI OUTDOOR AIR INTAKEOED OPEN-END DUCTPD PRESSURE DROPPH PHASEPLBG. CONTRACTOR FOR PLUMBINGDIVISIONPRV PRESSURE REDUCING VALVEPS PRESSURE SWITCH / SENSORPSI POUNDS PER SQUARE INCHRA RETURN AIRRH RELATIVE HUMIDITYRV RELIEF VALVESA SUPPLY AIRSENS. SENSIBLESPL SOUND PRESSURE LEVELSWL SOUND POWER LEVELTA TRANSFER AIRTC TEMPERATURE CONTROLSCONTRACTORTDV TRIPLE DUTY VALVETOS TOP OF STEELTS TAMPER SWITCHUH UNIT HEATERUNO UNLESS NOTED OTHERWISEVRA VENTILATION RELIEF AIRVRS VENTILATION SUPPLY AIRWB WET BULBZVB ZONE VALVE BOXAAV AIR ADMITTANCE VALVEAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEBFF BELOW FINISHED FLOORBFG BELOW FINISHED GRADEBOS BOTTOM OF STEELBTUH BRITISH THERMAL UNIT PERHOURCFM CUBIC FEET PER MINUTECO CLEANOUTCOP COEFFICIENT OFPERFORMANCEDB DRY BULBDIA. DIAMETER°F DEGREES FARENHEITEA EXHAUST AIREAT ENTERING AIR TEMPERATUREEFF. EFFICIENCYELEC. CONTRACTOR FOR ELECTRICALDIVISIONEWT ENTERING WATERTEMPERATUREEXT EXISTINGEXT. PD EXTERNAL PRESSURE DROPFF FINISHED FLOORFL FAIL LASTFLA FULL LOAD AMPACITYFLR FLOORFP CONTRACTOR FOR FIREPROTECTIONFPM FEET PER MINUTEFS FLOW SWITCHFSD FIRE / SMOKE DAMPERFT FEETFT-HD FEET OF HEAD (PRESSURE)GC CONTRACTOR FOR GENERALCONSTRUCTION DIVISIONGPM GALLONS PER MINUTEGRD GRILLES, REGISTERS,DIFFUSERSHGT HEIGHTHP HORSEPOWERHVAC CONTRACTOR FOR HEATING,VENTILATING & AIRCONDITIONING DIVISIONIN-WC INCHES OF WATER COLUMN(PRESSURE)IN. INCHHVAC DUCT SYSTEM ABBREVIATIONSABBREV.DESCRIPTIONEA EXHAUST AIROA OUTDOOR AIRHVAC PIPE SYSTEM ABBREVIATIONSABBREV.DESCRIPTIONHWR HOT WATER RETURNHWS HOT WATER SUPPLYHVAC EQUIPMENT ABBREVIATIONSABBREV.DESCRIPTIONFTR-A FINNED TUBE RADIATIONVAVGENERAL ABBREVIATIONSTO THE BEST OF THE ENGINEER'S PROFESSIONAL JUDGEMENT, THE DESIGN OF THIS PROJECT CONFORMS TO ALL APPLICABLE PORTIONS OF THE FOLLOWING:THE 2020 NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODETHE 2020 NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, 2016 ASHRAE 90.1, AND 2007 ASHRAE 183; FOLLOWING THE COMPLIANCE PATH MARKED BELOW:ANSI / ASHRAE / IESNA 90.1, AS AMENDED BY 19 NYCRR PART 1240.IECC CHAPTER 4 [CE] PRESCRIPTIVE PROVISIONS (SECTIONS C402, C403, C404, C405, C408 AND ONE OF THE SIX OPTIONS IN SECTION C406 AS NOTED BELOW:MORE EFFICIENT HVAC PERFORMANCE IN ACCORDANCE WITH SECTION C406.2.REDUCED LIGHTING POWER DENSITY SYSTEM IN ACCORDANCE WITH SECTION C406.3.ENHANCED LIGHTING CONTROL IN ACCORDANCE WITH SECTION C406.4.ON-SITE SUPPLY OF RENEWABLE ENERGY IN ACCORDANCE WITH SECTION C406.5.PROVISION OF A DEDICATED OUTDOOR AIR SYSTEM FOR CERTAIN HVAC EQUIPMENT IN ACCORDANCE WITH SECTION C406.6.HIGH-EFFICIENCY SERVICE WATER HEATING IN ACCORDANCE WITH SECTION C406.7.ENHANCED ENVELOPE PERFORMANCE IN ACCORDANCE WITH SECTION C406.8.REDUCED AIR INFILATRATION IN ACCORDANCE WITH SECTION C406.9.TOTAL BUILDING PERFORMANCE PROVISIONS (SECTION C407)THE NEW YORK STATE EDUCATION DEPARTMENT ("SED") MANUAL OF PLANNING STANDARDSTHE 2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIESTHE 2018 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF:HOSPITALSOUTPATIENT FACILITIESRESIDENTIAL HEALTH, CARE, AND SUPPORT FACILITIESALL SYMBOLS SHOWN ARE NOT NECESSARILY USED TTTT469 SFB01CONNECT TO EXST. CAPPED 12" DIA SS LAB EXHAUST RISER12" DIA SS EXH DUCT UP TO EXISTING TWIN CITY 911 RBA UTILITY SET EF-15 IN PENTHOUSE ABOVE. BALANCE AS INDICATED. 12" DIA EA DUCT DN TO FUME HOOD. PROVIDE SS FLEX CONNECTION AS REQUIRED FOR ADA ADJUSTABLE HOOD.10"4"4"VD TYPCEILING MOUNTED SNORKEL HOOD. BALANCE TO 200 CFMRA-14/10200EXST. TO REMAIN SUPPLY TU-9.RUN DUCT EXPOSED AND MOUNT HIGH AS POSSIBLE. TRANSITION AND CONNECT TO SNORKEL HOOD CONNECTION AS REQURED.RUN DUCT IN CEILING SOFFITDUCT BETWEEN HOOD AND EXISTING RISER CONNECTION TO BE WELDED 304 S.S. REST OF DUCT TO BE GALVANIZED. 3M10112/10VAV-E1VAV-E2EXST. TO REMAIN SUPPLY TU-7.EXST. TO REMAIN FUME HOOD EXH. VALVE.EXST. TO REMAIN GEX TU-8.DISCONNECT AND REMOVE EXST. 6" DIA EA DUCT AND CAP AT MAIN3M101EXST. SUPPLY TU-9 AND ASSOCIATED DUCTWORK AND CONTROLS TO REMAIN.EXST. 26x12 OA INTAKE DUCT TO REMAINEXST. 12" DIA SS EXHAUST RISER TO EXST. EF-15 IN PENTHOUSE TO REMAINEXST. SUPPLY TU-7 AND ASSOCIATED DUCTWORK AND CONTROLS TO REMAIN.EXST. GEX TU-8 AND ASSOCIATED DUCTWORK AND CONTROLS TO REMAIN.EXST. FUME HOOD EXH VALVE AND ASSOCIATED DUCTWORK AND CONTROLS TO REMAIN.EXST. GEX TU-10 AND ASSOCIATED DUCTWORK AND CONTROLS BE REMOVED FROM SPACE IF STILL LOCATED THERE. REMOVE FROM CONTROLS GRAPHIC AS WELL.EXST. 12" DIA SS EXHAUST RISER TO EXST. EF-11 IN PENTHOUSE TO REMAINVAV-E1VAV-E2FUME HOODFLOOREXST. SHAFTCONNECT TO EXST. 12" DIA SS EXHAUST RISER12"12"12"12"10/12CEILING SOFFITCEILINGEXST. 26x12 OA INTAKE8" DIA DUCT TO SNORKEL HOODS12" SS REINFORCED FLEX DUCT CONNECTIONTRANSITION TO GALVANIZED DUCTSS DUCTGALVANIZED DUCTSS DUCTFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M101B01 FLOORPLANS6/2/202111614/COB# 2013TAM113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations3"SCALE: 1/4" = 1'-0"M1011B01 PLAN - ALTERATION3"SCALE: 1/4" = 1'-0"M1012B01 PLAN - DEMOLITIONSCALE: NOT TO SCALEM1013B01 FUME HOOD AND EXHAUST TERMINAL UNIT SECTIONNOTES:1) PROVIDE PRE-BALANCE REPORT FOR ALL SYSTEMS AND COMPONENTSAFFECTED BY WORK AND NOTED TO BE BALANCED. THIS INCLUDES EXST. EF-15 & 11 EXST. TU-9, EXST. DUCT FLOW SENSOR AND EXST. FAN EF-15 & 11 OA MAKE-UP CONTROL DAMPER, GEX TU-8, FUME HOOD EXHAUST VALVE AND SUPPLY TU-7.NOTES:1) REMOVE EXISTING ACCUTROL FUME HOOD ALARM AND MONITOR AND ALL ACCESSORIES. PROVIDE AND INSTALL NEW LOCAL ALARM. PRODUCT: DWYER #670.2) PROVIDE UPDATED CONTROLS GRAPHIC FOR ENTIRE ROOM INCLUDING WEST SIDE AND EAST SIDE COMPONENTS. TTVD TYPWALL MOUNTED SNORKEL HOOD. BALANCE TO 200 CFM.CONNECT TO EXST. 16x15 EXHAUST DUCT8" DIA EXHAUST DUCT DN TO TABLE HEIGHT FOR CONNECTION TO HOOD BY OTHERS. PROVIDE 18" FLEXIBLE DUCT W/ DRAWBAND FOR OWNER CONNECTION. BALANCE TO 200 CFM.RE-BALANCE EXST EXHAUST TU-27 TO 1000 CFM MAX AND 200 CFM MIN. BOX TO CYCLE WITH EXISTING TO REMAIN SUPPLY TERMINAL UNIT.RE-BALANCE EXIST SUPPLY TERMINAL UNIT TU-26 TO 1350 CFM MAX AND 300 CFM MIN (UNOCC.).8"8"RE-BALANCE EXST EA GRILLE TO 600 CFMRE-BALANCE EXST FUME HOOD TO 450 CFMEXISTING TO REMAIN SUPPLY TERMINAL UNIT TU-26.EXISTING TO REMAIN EXHAUST TERMINAL UNIT TU-27.EXST. 12" DIA SS RISER TO EXST. EF-14 IN PENTHOUSE ABOVE.EXST. 12" DIA SS RISER TO EXST. EF-15 IN PENTHOUSE ABOVE.EXISTING TO REMAIN FTR.FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M102101 FLOORPLANS6/2/202111614/COB# 2013TAM113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations3"SCALE: 1/4" = 1'-0"M1021101 PLAN - ALTERATION3"SCALE: 1/4" = 1'-0"M1022101 PLAN - DEMOLITIONNOTES:1) PROVIDE PRE-BALANCE REPORT FOR ALL SYSTEMS AND COMPONENTSAFFECTED BY WORK AND NOTED TO BE BALANCED. THIS INCLUDES EXST. EF-14, EXST. TU-26 AND TU-27, EXST. DUCT FLOW SENSORS, EXST. FAN OA MAKE-UP CONTROL DAMPER AND ROOM 201 EXH DUCT. FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M601SCHEDULES &DETAILS6/2/202111614/COB# 2013TAM113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab RenovationsGRILLE AND DIFFUSER SCHEDULEMARK LOCATION MANUFACTURER MODEL FRAME/BORDER MODULE SIZE DAMPER MODEL FINISH REMARKSRA SEE PLANS PRICE 530 LAY IN24/24 OPP. BLADE WHITEVAV TERMINAL UNIT SCHEDULEMARKINLET SIZE (IN)CFMMAX DISCHARGE NC MANUFACTURER MODEL REMARKSMAX MINVAV E1 12 600 20025ANEMOSTAT EZT-121VAV E2 12 850 55025ANEMOSTAT XAFT-12 1,2SCALE: NOT TO SCALEM6012EXISTING LAB AIRFLOWNOTES:1. EXHAUST AIR CONTROL BOX. NO HEATING COIL REQUIRED.2. LAB HOOD EXHAUST BOX INSTALLED IN STAINLESS STEEL DUCT. PROVIDE COMPATIBLE CONNECTIONSAND SS LINING.SCALE: NOT TO SCALEM6013EXISTING PNEUMATIC LAB CONTROL SYSTEMNOTE:1. SYSTEM IS PNEUMATIC WITH CONNECTION TO BUILDING DDC BACKBONE. SYSTEM IS EXISTING TO REMAIN FOR ROOM 101. ROOM B01 WILL BE PROVIDING AND INTEGRATING A NEW GENERAL EXHAUST AND A NEW FUME HOOD EXHAUST VALVE WITH THE EXISTING SYSTEM. PROVIDE ALL NEW DDC CONTROLS FOR NEW SYSTEMS. INTERFACE WITH EXISTING BUILDING PNEUMATIC CONTROLS AND BACS SYSTEM AS REQUIRED.NOTE:1. SYSTEM IS PNEUMATIC WITH CONNECTION TO BUILDING DDC BACKBONE. SYSTEM IS EXISTING TO REMAIN FOR ROOM 101. ROOM B01 WILL BE PROVIDING AND INTEGRATING A NEW GENERAL EXHAUST AND A NEW FUME HOOD EXHAUST VALVE WITH THE EXISTING SYSTEM. PROVIDE ALL NEW DDC CONTROLS FOR NEW SYSTEMS. INTERFACE WITH EXISTING BUILDING PNEUMATIC CONTROLS AND BACS SYSTEM AS REQUIRED.EXST. EF-15 IN PENTHOUSE TO RUN CONTINUOUSLY WHENEVER ASSOCIATED EXST. AHU-1 AND AHU-2 ARE RUNNING.EXST. EF-15 IN PENTHOUSE TO RUN CONTINUOUSLY WHENEVER ASSOCIATED EXST. AHU-1 AND AHU-2 ARE RUNNING.EXST. EXH VALVE, FUME HOOD, FLOW SENSOR AND ASSOCIATED CONTROLS HAVE BEEN DELETED FOR ROOM B01 SYSTEM. REFER TO NEW CONTROL DRAWING M701 FOR CONTROLS FOR NEW SYSTEM.EXST. EXH VALVE, FUME HOOD, FLOW SENSOR AND ASSOCIATED CONTROLS HAVE BEEN DELETED FOR ROOM B01 SYSTEM. REFER TO NEW CONTROL DRAWING M701 FOR CONTROLS FOR NEW SYSTEM.EXST. MAKE UP AIR DAMPER ASSOCIATED WITH EXST. FAN EF-15 TO MODULATE BASED ON ROOM OCC./UNOCC. SETTING. DAMPER TO BE CLOSED DURING OCCUPIED MODE. PROVIDE NEW ACTUATOR AND CONTROLS AND BALANCE DAMPER TO OPEN AS REQUIRED TO PROVIDE 700 CFM MAKE-UP AIRFLOW DURING UNOCCUPIED MODE.EXST. MAKE UP AIR DAMPER ASSOCIATED WITH EXST. FAN EF-15 TO MODULATE BASED ON ROOM OCC./UNOCC. SETTING. DAMPER TO BE CLOSED DURING OCCUPIED MODE. PROVIDE NEW ACTUATOR AND CONTROLS AND BALANCE DAMPER TO OPEN AS REQUIRED TO PROVIDE 700 CFM MAKE-UP AIRFLOW DURING UNOCCUPIED MODE.SCALE: NOT TO SCALEM6011EXISTING FUME HOOD SPECSNOTES:1) FUME HOOD IS EXISTING HOOD TO BE RELOCATED BY OTHERS. PROVIDE ALL DUCT AND CONTROLS CONNECTIONS AS REQUIRED. REMOVE EXISTING ACCUTROL FLOW ALARM AND MONITOR AND REPLACE WITH LOCAL ALARM DWYER #670. SASH STOP TO REMAIN AT 18". AOAV: MIN. SETPOINTAOAIAV: SETPOINT : HEATINGBIAIAOAV: MIN. SETPOINTAV: MAX. SETPOINTAV: SETPOINT: COOLINGAV: MAX. SETPOINTAV: SETPOINT : MINIMUMOCCUPANCYAV: FLOW FEEDBACK (CFM)AV: POSITION FEEDBACK(%)AV: FLOW FEEDBACK (CFM)AV: POSITION FEEDBACK(%)AOAV: FLOW SETPOINT (CFM)AV: FLOW FEEDBACK (CFM)AV: POSITION FEEDBACK(%)BIAV: SETPOINT : MINIMUMOCCUPANCYSEQUENCE OF OPERATIONSYSTEM DESCRIPTIONFUME HOOD WITH EXHAUST AIR VALVE (FEV)SUPPLY AIR VALVE (SAV)GENERAL EXHAUST AIR VALVE (GEX)DUCT MOUNTED REHEAT COIL (RHC)BASEBOARD RADIATION HEATING (FTR) -WHERE SHOWN ON PLANSGENERALSYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND CONTROL SYSTEM (BACS).ALL SETPOINTS SHALL BE ADJUSTABLE.THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.LABORATORY AIR CHANGE RATES ARE BASED ON TOTAL EXHAUST AIR FLOW FROM THE SPACE.THE SPACE SHALL BE CONTROLLED TO AN AIR CHANGE RATE. THE BACS SHALL CALCULATE THE REQUIRED CFM USING THE ROOM GROSS VOLUME (AREA X CEILING HEIGHT).IF THE ZONE BECOMESOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF THE OCCUPANCY, WHEN THE SPACE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX BACK TO UNOCCUPIED MODE.AIR VALVE POSITIONS SHALL BE BASED ON SPACE OCCUPANCY. ROOM OCCUPANCY SHALL BE DETERMINED VIA ROOM OCCUPANCY SENSOR. IF THE LABORATORY IS VACANT, THE ROOM SHALL BE PLACED IN VACANT MODE BY BACS.SETPOINTSSPACE COOLING TEMPERATURE SETPOINTS:OCCUPIED:75°F +/-1.5 °FOCCUPIED SETBACK:75°F + 3°FUNOCCUPIED:75°F + 6°FSPACE HEATING TEMPERATURE SETPOINTS:OCCUPIED:70°F +/-1.5°FOCCUPIED SETBACK:70°F -3°FUNOCCUPIED:70°F -6°FTOTAL EXHAUST AIR CHANGE RATE (ACPH): REFER TO AIRFLOW SCHEDULE ACPH = TOTAL EXHAUST CFM X 60 / ROOM VOLUMETOTAL EXHAUST AIRFLOW RATE: (CFM): REFER TO AIRFLOW SCHEDULESUPPLY AIRFLOW RATE (CFM): REFER TO AIRFLOW SCHEDULE TYPICAL = TOTAL EXHAUST AIRFLOW RATE + OFFSETFUME HOOD EXHAUST AIRFLOW RATE: REFER TO AIRFLOW SCHEDULEGENERAL EXHAUST AIRFLOW RATE (CFM) REFER TO AIRFLOW SCHEDULE TOTAL EXHAUST CFM –FUME HOOD EXHAUST CFMSPACE AIR DIFFERENTIAL OFFSET (CFM): REFER TO AIRFLOW SCHEDULE -100 CFM FOR NEGATIVE PRESSURE LABSFUME HOOD FACE VELOCITY: 100 FPM OCC / 65 FPM UNOCC. REFER TO SCHEDULEMINIMUM LABORATORY OCCUPANCY INDEX TIME: 30 MINUTESZONE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRIFACE VELOCITY CONTROLFACE VELOCITY WILL BE CONTROLLED BY MONITORING TERMINAL UNIT FLOW. TERMINAL UNIT ALARM TO NOTIFY BACS UPON LOSS OF FLOW.FLOW DETECTOR AT EACH HOOD OR CABINET TO PROVIDE LOCAL ALARM UPON LOSS OF FLOW. MONITOR IS EXISTING TO REMAIN WITH EXISTING HOOD.LABORATORY AIRFLOW CONTROLHOOD EXHAUST TERMINAL UNIT DAMPER POSITIONS SHALL BE AS REQUIRED TO MAINTAIN REQUIRED AIRFLOW AT HOOD OPENING. HEATING MODE:GEX TERMINAL UNIT DAMPER SHALL CLOSE AND SUPPLY TERMINAL UNIT DAMPER SHALL REDUCE FLOW TO MINIMUM SHOWN ON SCHEDULE BEFORE ANY REHEATING TAKES PLACE.COOLING MODE:GEX TERMINAL UNIT DAMPER SHALL OPEN AND SUPPLY TERMINAL UNIT DAMPER SHALL OPEN TO PROVIDE AIRFLOWS AS SHOWN ON SCHEDULE. UPON A REDUCED NEED FOR COOLING GEX TERMINAL UNIT DAMPER AND SUPPLY TERMINAL UNIT DAMPER WILL MODULATE SIMULTANEOUSLY TOWARD MINIMUM POSITION BEFORE ANY REHEAT TAKES PLACE.ZONE TEMPERATURE CONTROLTEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OF PROGRAMMED SCHEDULE AND SPACE OCCUPANCY SENSORS.OCCUPIED HEATING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD AND THE SPACE TEMPERATURE FALLS BELOW THE OCCUPIED HEATING TEMPERATURE SETPOINT, THE REHEAT CONTROL VALVE AND THE PERIMETER FIN RADIATION CONREOL VALVE SHALL MODULATE TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. WHEN THE SPACE TEMPERATURE IS AT SETPOINT, THE CONTROL VALVES SHALL BE CLOSED.OCCUPIED COOLING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD AND THE SPACE TEMPERATURE RISES ABOVE THE OCCUPIED COOLING TEMPERATURE SETPOINT, THE HEATING CONTROL VALVES SHALL BE CLOSED.OCCUPIED SETBACK: IF THE SPACE BECOMES UNOCCUPIED DURING THE SCHEDULED OCCUPANCY PERIOD, THE ABOVE OCCUPIED HEATING/COOLING SEQUENCES SHALL APPLY, BUT THE SPACE SHALL BE MAINTAINED AT THE OCCUPIED SETBACK TEMPERATURE SETPOINTS.UNOCCUPIED HEATING: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD AND THE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED COOLING TEMPERATURE SETPOINT, THE HEATING CONTROL VALVES SHALL BE CLOSED.IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. WHEN THE SPACE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX BACK TO UNOCCUPIED MODE.REHEAT COILTU-2-S9FUME HOODVAV-E2VAV-E1FROM EXST. AHU-1/2DAT -55°FF.L.N.C.MODdTsaOSTMODMICROBIOLOGY 206ACOMHOT WIRE MANOMETER FLOW DETECTOR WITH LOCAL ALARM.DWYER #670COMMODCOMOSPROVIDE (2) OCC SENSORS FOR EACH LAB. IF ANY SENSOR IS IN OCC MODE THEN THE LAB IS IN OCC MODE.EXST SUPPLY TU AND CONTROLS TO REMAINEXST T-STAT AND CONTROLS TO REMAINEXST FUME HOOD RELOCATED BY OTHERSTO EXST. EF-15TO EXST. EF-15FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M701CONTROLS6/2/202111614/COB# 2013TAM113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab RenovationsSCALE: NOT TO SCALEM7011Tracking Laboratory Zone Control System - B01DESCRIPTIONHARDWARE POINTS SOFTWARE POINTSSHOW ONGRAPHICNOTESBI BO AI AO AV BV SCH TRENDALARMBACS/DDC DESCRIPTIONSUPPLY TERMINAL UNIT VAV AIR FLOW FEEDBACK (CFM) X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORKPOINTFUME HOOD EXHAUST TERMINAL UNIT VAV AIR FLOWFEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORKPOINTGENERAL EXHAUST TERMINAL UNIT VAV AIR FLOWFEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORKPOINTFUME HOOD EXHAUST TERMINAL UNIT VAV AIRFLOWSETPOINT (CFM)XXX BACnet MSTP NETWORKPOINTSUPPLY TERMINAL UNIT VAV POSITION FEEDBACK (%) X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORKPOINTFUME HOOD EXHAUST TERMINAL UNIT VAV POSITIONFEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACKX BACnet MSTP NETWORKPOINTGENERAL EXHAUST TERMINAL UNIT VAV POSITIONFEEDBACK (%)XXXVALVE COMMAND ≠ FEEDBACKX BACnet MSTP NETWORKPOINTSUPPLY TERMINAL UNIT POSITION COMMANDXXXSUPPLY TERMINAL UNIT MINIMUM AIRFLOW SETPOINT (CFM)XXSUPPLY TERMINAL UNIT MAXIMUM AIRFLOW SETPOINT (CFM)XXREHEAT COIL LEAVING AIR TEMPERATUREXXX SINGLE POINT SENSORREHEAT COIL CONTROL VALVE POSITION COMMAND (%)XXX 5°F ΔT ACROSS COIL WITH VALVE COMMANDEDCLOSEDX FAIL LASTSPACE TEMPERATURE SETPOINT: HEATINGXXXSPACE TEMPERATURE SETPOINT: COOLINGXXXSPACE TEMPERATURE & SETPOINT ADJUSTMENTXXX± 4°F FROM SETPOINTXSPACE OCCUPANCYXXXXSPACE OCCUPANCYXXXXSPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINTXXSPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINTXXGENERAL EXHAUST TERMINAL UNIT POSITION COMMANDXXXFUME HOOD EXHAUST TERMINAL UNIT POSITION COMMANDXXXGENERAL EXHAUST TERMINAL UNIT MINIMUM AIRFLOWSETPOINT (CFM)XXGENERAL EXHAUST TERMINAL UNIT MAXIMUM AIRFLOWSETPOINT (CFM)XXSCALE: NOT TO SCALEM7013B01 LAB AIRFLOW ISSUE:DATE:DRAWN BY:CHECKED BY:SCALE:PROJECT NO.SHEET TITLESHEETDRAWING NO.ALTERATION OF THIS DOCUMENTEXCEPT BY A LICENSED DESIGNPROFESSIONAL, IS A VIOLATION OFNEW YORK STATE EDUCATIONAL LAW.OFFS ENGINEERING,DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044Enter address hereR:\Revit MEP 2012\Templates\S&A_Mechanical.rte10/5/2011 4:16:29 PMOwnerProject NameSK-M201/01/2019AuthorCheckerProject NumberUnnamedMARK DATE DESCRIPTION??PLAN DETAILBUILDING SECTIONDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDEXTENT OF DETAILEXTENT OF DETAILA1B1C1D1E1A2B2C2D2E2A3B3C3D3E3A4B4C4D4E4A5B5C5D5E5A6B6C6D6E6DETAIL NUMBERDETAIL SCALEDETAIL NAMEDETAIL NUMBERPLAN SETUPSHEET NUMBER WHERE DETAIL IS LOCATEDCAUTION: THESE DOCUMENTS WERE DIGITALLY PRODUCED AND/OR REPRODUCED. CONFIRM REDUCTION OR MAGNIFICATION USING DIMENSIONAL 3"-LONG LINE IN TITLE BARS. IF SCALING DRAWINGS FOR APPROXIMATE DIMENSIONS, ALTERNATE ARCHITECTURAL SCALES MAY BE USED AS FOLLOWS:DOCUMENT REDUCTION/MAGNIFICATION SCALEIF LINE MEASURES 2”(67% COPY):USE 3/16th SCALE ON 1/8”=1’-0”DWGUSE 3/8th SCALE ON 1/4”=1’-0”DWGIF LINE MEASURES 1.5”(50% COPY):USE 1/16th SCALE ON 1/8”=1’-0”DWGUSE 1/8th SCALE ON 1/4”=1’-0”DWG3"3"????XXXX" = X"NOTES:FSCFINISHED FLOOR1'-6"1'-6"1'-6"DUPLEX RECEPTACLEDESK TOPTELEPHONEDATA OUTLET2'-0"EXTERIOR DUPLEXRECEPTACLE4'-0"DUPLEX RECEPTACLEMECH RMLIGHT SWITCH4'-0"PBGYM DOOR PUSHBUTTONFSEE NOTE 3FIRE ALARMPULLSTATIONWALL MOUNTEDTELEPHONE/INTERCOM PHONESEE NOTE 3F5'-0"DISCONNECTSWITCH6'-0"PANELBOARDFIRE ALARMA/V DEVICEFIRE ALARMVISUAL DEVICESEE NOTE 4EMERGENCYLIGHTCLOCKINTERCOMSPEAKERSEE NOTE 51. IN LOCATIONS WHERE SIMILAR DEVICES ARE MOUNTED AT THE SAME HEIGHT DEVICES SHALL BE PROPERLY "GANGED" AND SHALL HAVE ASINGLE COVER PLATE.2. IN LOCATIONS WHERE DIFFERENT DEVICES ARE MOUNTED AT DIFFERENT HEIGHTS WITHIN FOUR FEET OF ONE ANOTHER. DEVICES SHALL BE MOUNTED SUCH THAT THEY HAVE A COMMON CENTER LINE. IF THERE ARE THREE OR MORE DEVICES THE CONTRACTOR SHALL REQUEST A DETAIL FROM THE ARCHITECT.3. 42" MINIMUM TO 48" MAXIMUM AND WITHIN 5FT FROM DOOR. 4. 80" OR, AT SHALLOW CEILING INSTALLATIONS, WITHIN 6" OF FINISHED CEILING. VERIFY WITH ENGINEER.5. 90" AFF, OR, AT SHALLOW CEILING INSTALLATIONS, TOP OF UNIT WITHIN 6" OF FINISHED CEILING.SEE NOTE 3X1X2EXIT SIGN LIGHT FIXTURE WITH CONNECTION TO EMERGENCY POWER. COORDINATE TYPE AND MOUNTING. PROVIDE ARROWS WHERE INDICATED. DESCRIPTIONSYMBOLLIGHTING SYMBOLSDLED LIGHT FIXTURE, SUBSCRIPT D = FIXTURE TYPE, REFER TOSPECIFICATIONS AND LIGHT FIXTURE SCHEDULE.EMTVFCAFFACGNFGFGROUND FAULT INTERUPT DEVICENON-FUSEDGROUNDABOVE FINISHED FLOORVARIABLE FREQUENCY CONTROLLERABOVE COUNTER - 6"ABOVE COUNTERTOP OR BACKSPLASHELECTRIC METALLIC TUBINGEWCELECTRIC WATER COOLER3aSNIGHT LIGHTNLAT UNITAUFIRE SMOKE DAMPER. PROVIDE CONNECTIONS AS INDICATEDFSOS1PCPANELBOARD, 208/120V - SURFACE MOUNTEDBRANCH CIRCUIT HOMERUN: 2 #12, 1 #12G, 1/2"C TO PANELBOARD CIRCUIT NUMBER AS INDICATED UNLESS OTHERWISE NOTED.B1 / 12 = PANEL NAME / CIRCUIT NUMBERDESCRIPTIONSYMBOLABBREVIATIONSPHOTOCELL.WALL MOUNTED OCCUPANCY SENSOR, 1 = TYPE, REFER TOSPECIFICATIONS.WALL SWITCH, 3 = THREEWAY, a = FOR LIGHTING FIXTUREMARKED SAME.CEILING MOUNTED OCCUPANCY SENSOR, 3 = TYPE, REFER TOSPECIFICATIONS.SYMBOLGENERAL SYMBOLSDESCRIPTIONDESCRIPTIONCOMBINATION MAGNETIC STARTERFUSED DISCONNECT SWITCHNON-FUSED DISCONNECT SWITCHSYMBOLSECONDARY SERVICE SYMBOLSPANELBOARD, 208/120V - RECESSED MOUNTEDMOTOR CONNECTION. EQUIPMENT AND CIRCUITRY AS INDICATED ON PLANS AND KEYED TO ELECTRICAL EQUIPMENT AND CONTROL SCHEDULE OR AS OTHERWISE NOTED.SFFFFIRE ALARM CONNECTION. SUBSCRIPT IDENTIFIES TYPE:FS - FIRE SMOKE DAMPER CONNECTIONFA - FIRE ALARM SHUTDOWN OF EQUIPMENTFIRE ALARM SYSTEM ANNUNCIATOR PANELSYMBOLFIRE ALARM SYSTEM CONTROL PANEL (FACP)FIRE ALARM SYMBOLSDESCRIPTIONFIRE ALARM SYSTEM THERMAL DETECTORFIRE ALARM SYSTEM MANUAL PULL STATIONFIRE ALARM SYSTEM SMOKE DETECTORFIRE ALARM SYSTEM SMOKE DETECTOR, DUCT MOUNTFIRE ALARM SYSTEM COMBINATION VISUAL AND AUDIBLEINDICATING DEVICE, WALL MOUNTED. STROBE INTENSITY 75CANDELAS, UNLESS INDICATED OTHERWISE. SUBSCRIPTS: WP - WEATHERPROOF, WG - WIREGUARDFIRE ALARM SYSTEM VISUAL (ONLY) INDICATING APPLIANCE, WALL MOUNTED, INTENSITY 75 CANDELA UNLESS INDICATED OTHERWISEFACPFAAFSWPFIRE ALARM SYSTEM - BEAM DETECTOR TYPE, TRANSMITTERTRBRDUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDACG.F.C.I. DUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDGF/ACGFDOUBLE DUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDACWEATHERPROOF DUPLEX RECEPTACLE OUTLETWPFLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE OUTLETISOLATED GROUND DUPLEX RECEPTACLE OUTLETIGSPECIAL PURPOSE RECEPTACLE OUTLET, NEMA CONFIGURATION TO MATCH PLUGBRANCH CIRCUITRY: 2 #12, 1 #12G, 1/2"C UNLESS OTHERWISE NOTEDB1/12FFIRE ALARM SYSTEM COMBINATION VISUAL AND AUDIBLEINDICATING DEVICE, CEILING MOUNTED. STROBE INTENSITY 75CANDELAS, UNLESS INDICATED OTHERWISE. SUBSCRIPTS: WP - WEATHERPROOF, WG - WIREGUARDFIRE ALARM SYSTEM VISUAL (ONLY) INDICATING APPLIANCE, CEILING MOUNTED, INTENSITY 75 CANDELA UNLESS INDICATED OTHERWISEFDUPLEX RECEPTACLE OUTLET, SURACE MOUNTED FIRE ALARM SYSTEM - BEAM DETECTOR TYPE, RECEIVERSSDEVICE SYMBOLSDESCRIPTIONSYMBOLFIRE ALARM SYSTEM - SPRINKLER FLOW SWITCHFSFIRE ALARM SYSTEM - SPRINKLER TAMPER SWITCHTSDSD4 PORT (QUAD) USB CHARGER OUTLET WAPDESCRIPTIONSYMBOLVOICE/DATA SYMBOLSDATA OUTLET, WALL MOUNTED(2) CAT 6 CABLES / (2) RJ-45 JACKS UNLESS NOTED OTHERWISETYPE WAP (WIRELESS ACESS POINT) DATA OUTLET, CEILING MOUNTED UNLESS NOTED OTHERWISE. WALL MOUNTED UNITS AT 90"AFF WITH 12" CLEARANCE TO CEILING.(1) CAT 6A CABLE / (1) RJ-45 JACKWALL PHONE - (1) CAT 6 CABLE / (1) RJ-45 JACKE1REFERS TO KEYED NOTE ON RESPECTIVE DRAWINGHP-012FIRE ALARM SYSTEM MAGNETIC DOOR HOLD OPENETREXISTING TO REMAIN3OSSFIRE ALARM SYSTEM SMOKE DETECTOR, ELEVATOR RECALLRJJUNCTION BOXAUTOMATIC TRANSFER SWITCHATSPANELBOARD, 480/277V - SURFACE MOUNTEDPANELBOARD, 480/277V - RECESSED MOUNTEDDIMMER SWITCHJCEILING MOUNTED, FLUSH, DOUBLE-GANG JUNCTION BOX FOR MOTORIZED SCREEN. COORDINATE LOCATION WITH AV CONTRACTOR AND ARCHITECT. MSDATA OUTLET FOR AV EQUIPMENT, WALL MOUNTED AT 18" AFF, UNLESS NOTED OTHERWISE(4) CAT 6 CABLES / (4) RJ-45 JACKS UNLESS NOTED OTHERWISEAV/4JWALL MOUNTED, FLUSH, SINGLE-GANG JUNCTION BOX FOR PROJECTOR SCREEN SWITCH. MOUNT AT 45" AFF COORDINATE LOCATION WITH AV CONTRACTOR AND ARCHITECT. SSDATA OUTLET FOR AV EQUIPMENT, WALL MOUNTED AT 78" AFF UNLESS NOTED OTHERWISE(2) CAT 6 CABLES / (2) RJ-45 JACKS UNLESS NOTED OTHERWISEAV/2A.REFER TO ARCHITECTURAL DRAWINGS FOR EXTENT OF BASE BID NEW CONSTRUCTION AND RENOVATED AREAS, PHASING REQUIREMENTS AND ALTERNATES.PROVIDE MATERIALS AND LABOR FOR COMPLETE, FUNCTIONAL SYSTEMS. COORDINATE WIRING AND CONNECTION REQUIREMENTS FOR EQUIPMENT. MATERIALS, EQUIPMENT, CONDUCTORS, WIRING DEVICES, ETC. SHALL BE NEW AND UL-LISTED, SUITABLE FOR LOCATION AND FUNCTION.COORDINATE EXACT LOCATION OF ELECTRICAL BOXES AND RACEWAY PRIOR TO ROUGH-IN. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS.PROVIDE TEMPORARY POWER AND LIGHTING. PROVIDE TEMPORARY ELECTRICAL CIRCUITRY AND CONNECTIONS AS REQUIRED TO MAINTAIN SERVICES.CONTACT CIT OPERATIONS SUPPORT AT 255-5500 TO DISCONNECT ACTIVE SERVICES AND REMOVE IT HARDWARE PRIOR TO DEMOLITION OF WALLS AND PARTITIONS. VERIFY SCOPE AND PHASING OF DEMOLITION WORK FOR AREAS TO BE ABATED AND RENOVATED. PROTECT EXISTING CIRCUITRY SERVING ADJACENT AREA/EQUIPMENT WHICH WILL REMAIN IN USE. PROVIDE SUPPORT AND TEMPORARY CONNECTIONS/RE-ROUTING AS REQUIRED. REFER TO ARCHITECTURAL DRAWINGS INDICATING REMOVAL SCOPE OF WORK. CONTRACTOR FOR DIVISION 26 SHALL DISCONNECT AND REMOVE BRANCH CIRCUITRY, LIGHT FIXTURES, WIRING DEVICES, CLOCKS, SPEAKERS, TELEPHONES AND RESPECTIVE SYSTEM WIRING/CABLING COMPLETE. REMOVALS SHALL INCLUDE ALL ELECTRICAL COMPONENTS IN/ON WALLS THAT ARE TO BE REMOVED. MAINTAIN CIRCUITRY TO EQUIPMENT AND DEVICES THAT ARE TO REMAIN.FIRE STOP PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS WITH FIRE STOP MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF WHICH IT IS PENETRATING. SOUND TRANSFERENCE: FLUSH WALL MOUNTED ELECTRICAL BOXES MOUNTED IN COMMON WALLS BETWEEN ADJACENT ROOMS, SHALL BE INSTALLED INDEPENDENT OF EACH OTHER; EACH WITH SEPARATE CONDUIT RISER(S). NIPPLING OF FLUSH WALL MOUNTED ELECTRICAL BOXES NOT ALLOWED. WHERE ELECTRICAL BOXES ARE MOUNTED BACK TO BACK, PROVIDE INSULATION BETWEEN BOXES. GROUNDING REQUIREMENTS1. ALL GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLES 250.2. ALL INSULATED GROUND CONDUCTORS SHALL BE GREEN. PROVIDE EQUIPMENT GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT.3. PROVIDE GROUNDING PER EQUIPMENT MANUFACTURER REQUIREMENTS.CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS:1. VARIOUS PIECES OF EQUIPMENT WILL BE FURNISHED TO THE PROJECT SITE AND INSTALLED BY OTHER DIVISIONS.2. PROVIDE ROUGHING-IN AND FINAL CONNECTIONS AS REQUIRED IN ACCORDANCE WITH EQUIPMENT INSTALLATION INSTRUCTIONS.3. BEFORE PROCEEDING WITH THE WORK, OBTAIN FULL INFORMATION REGARDING ROUGH-IN MEASUREMENTS, EQUIPMENT LAYOUTS, ELEVATIONS, TRIM BEING FURNISHED, AND OTHER NECESSARY DATA.4. UPON REQUEST, CONSTRUCTION MANAGER WILL PROVIDE THIS DIVISION WITH DIAGRAMS, PHOTOGRAPHS, DRAWINGS, AND/OR SPECIFICATIONS AND OTHER COMPLETE DESCRIPTIVE DATA. DO NOT ROUGH WITHOUT APPROVED LAYOUT FROM CONSTRUCTION MANAGER.5. PROVIDE ACCESSORIES SO THAT CONNECTIONS MAY BE MADE IN A MANNER THAT SHALL MEET ALL REGULATIONS AND CODES.6. SEE APPROPRIATE SECTIONS OF THIS DIVISION'S SPECIFICATIONS FOR MATERIALS AND METHODS.USE OF SHALLOW FLUSH MOUNT ELECTRICAL BOXES SHALL BE PERMITTED WHERE DEPTH OF WALL CAVITY/FURRING IS LESS THAN 2 1/2" AS INDICATED ON ARCHITECTURAL DRAWINGS.CONCEAL ALL ADDED CONDUITS, EXPOSED CONDUIT INSTALLATION IS UNACCEPTABLE UNLESS PRIOR APPROVAL IS GIVEN BY ARCHITECT. ANY EXPOSED CONDUIT INSTALLATION SHALL BE PAINTED TO MATCH ADJACENT WALL FINISH.B.GENERAL NOTESC.D.E.F.G.H.I.J.K.L.FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E001DRAWINGINDEX,SCHEDULES,SYMBOL LISTS& NOTES6/2/202111614/COB# 2013ASC/JLR113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab RenovationsELECTRICAL DRAWING INDEXNUMBERNAMEREVISIONS# DATEE001 DRAWING INDEX, SCHEDULES, SYMBOL LISTS & NOTESE101 PARTIAL ELECTRICAL PLANS - LAB B01E102 PARTIAL ELECTRICAL PLAN - LAB 101SCALE: NOT TO SCALEE001A3DEVICE MOUNTING HEIGHTSTO THE BEST OF THE ENGINEER'S PROFESSIONAL JUDGEMENT, THE DESIGN OF THIS PROJECT CONFORMS TO ALL APPLICABLE PORTIONS OF THE FOLLOWING:THE 2020 NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODETHE 2020 NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, 2016 ASHRAE 90.1, AND 2007 ASHRAE 183; FOLLOWING THE COMPLIANCE PATH MARKED BELOW:ANSI / ASHRAE / IESNA 90.1, AS AMENDED BY 19 NYCRR PART 1240.IECC CHAPTER 4 [CE] PRESCRIPTIVE PROVISIONS (SECTIONS C402, C403, C404, C405, C408 AND ONE OF THE SIX OPTIONS IN SECTION C406 AS NOTED BELOW:MORE EFFICIENT HVAC PERFORMANCE IN ACCORDANCE WITH SECTION C406.2.REDUCED LIGHTING POWER DENSITY SYSTEM IN ACCORDANCE WITH SECTION C406.3.ENHANCED LIGHTING CONTROL IN ACCORDANCE WITH SECTION C406.4.ON-SITE SUPPLY OF RENEWABLE ENERGY IN ACCORDANCE WITH SECTION C406.5.PROVISION OF A DEDICATED OUTDOOR AIR SYSTEM FOR CERTAIN HVAC EQUIPMENT IN ACCORDANCE WITH SECTION C406.6.HIGH-EFFICIENCY SERVICE WATER HEATING IN ACCORDANCE WITH SECTION C406.7.ENHANCED ENVELOPE PERFORMANCE IN ACCORDANCE WITH SECTION C406.8.REDUCED AIR INFILATRATION IN ACCORDANCE WITH SECTION C406.9.TOTAL BUILDING PERFORMANCE PROVISIONS (SECTION C407)THE NEW YORK STATE EDUCATION DEPARTMENT ("SED") MANUAL OF PLANNING STANDARDSTHE 2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIESTHE 2018 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF:HOSPITALSOUTPATIENT FACILITIESRESIDENTIAL HEALTH, CARE, AND SUPPORT FACILITIESALL SYMBOLS SHOWN ARE NOT NECESSARILY USED 469 SFB0136" CODE CLEARANCEE1E2E3WAPE7EX. PANELLPB3469 SFB01EX. PANELLPB336" CODE CLEARANCEED2A. VERIFY EXACT LOCATION OF RECEPTACLES & DATA OUTLETS WITH ARCHITECT, ARCHITECT'S ELEVATION DRAWINGS, AV CONSULTANT AND TA-SERIES DRAWINGS PRIOR TO ROUGH-IN.B. PROVIDE SEPARATE NEUTRAL AND GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT INDICATED.C. VERIFY EXACT LOCATION OF LIGHT FIXTURES WITH ARCHITECT AND ARCHITECT'S REFLECTED CEILING PLANS AND ELEVATION DRAWINGS PRIOR TO ROUGH-IN.D. CIRCUIT LIGHT FIXTURES TOGETHER WITH 2#10, #10E.G. - 1/2" CONDUIT, UNLESS NOTED OTHERWISE.E. UNLESS OTHERWISE INDICATED, AT ROOMS/LOCATIONS WHERE DIMMING SWITCHES ARE INDICATED PROVIDE 0-10V DIMMING / LIGHTING CONTROL. COORDINATE THE 0-10V DIMMING CONTROL WITH THE 0-10V LED DRIVERS AT LIGHT FIXTURES.GENERAL NOTESA. COORDINATE SCHEDULING OF REMOVAL WORK WITH OWNER OR OWNER'S REPRESENTATIVE, PHASING DRAWINGS AND REQUIREMENTS.B. VERIFY LOCATIONS AND SCHEDULE OF REMOVAL WORK IN ALL AREAS PRIOR TO STARTING WORK. REFER TO OTHER TRADES DRAWINGS AND COORDINATE REMOVAL WORK WITH OTHER TRADES DIVISION CONTRACTORS PRIOR TO STARTING.C. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES WITHIN SPACES INDICATED. D. PROVIDE ALL REQUIRED WIRING AND TEMPORARY CONNECTIONS NECESSARY TO MAINTAIN ELECTRICAL CONTINUITY OF ALL EXISTING ELECTRICAL EQUIPMENT, RECEPTACLES, DEVICES, LIGHTING FIXTURES AND DEVICES, FIRE ALARM EQUIPMENT AND DEVICES THAT ARE TO REMAIN DURING ALL STAGES OF WORK.E. PROVIDE TEMPORARY SUPPORT FOR ALL EXISTING RACEWAYS AND BRANCH CIRCUITRY TO REMAIN DURING ALL STAGES OF WORK.F. PROTECT ALL EXISTING ELECTRICAL EQUIPMENT, RECEPTACLES, DEVICES, LIGHTING FIXTURES AND DEVICES, FIRE ALARM EQUIPMENT AND DEVICES, TELECOMMUNICATIONS EQUIPMENT AND DEVICES, SECURITY (CCTV) EQUIPMENT AND DEVICES AND ALL ASSOCIATED RACEWAYS AND BRANCH CIRCUITRY TO REMAIN FROM DAMAGE AND DEBRIS DURING ALL STAGES OF WORK.G. ALL ELECTRICAL DEVICES AND EQUIPMENT SHOWN ON FLOOR PLANS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.H. OBTAIN A LIST FROM THE OWNER, OR THE OWNER’S REPRESENTATIVE, OF ANY ITEMS THEY WISH TO RETAIN. DISCONNECT, REMOVE, INVENTORY AND DELIVER ALL ITEMS TO OWNER DESIGNATED ON-SITE LOCATION IN GOOD OPERATING ORDER. PROVIDE A TRANSMITTAL OF THE ITEMS INVENTORIED TO THE OWNER OR OWNER'S REPRESENTAIVE. ALL OTHER ITEMS SHALL BE REMOVED FROM THE PROJECT SITE COMPLETE AND DISPOSED OF IN THE APPROPRIATE MANNER.I. EXISTING CONDUIT AND BRANCH CIRCUTRY LOCATED IN NON-ACCESSIBLE WALLS/FLOORS, JUNCTION BOXES SHALL BE ABANDON IN PLACE AS FOLLOWS:• DISCONNECT BRANCH CIRCUIT AT SOURCE.• REMOVE SURFACE AND FLOOR BOX(ES).• PROVIDE PRIMED STEEL BLANK PLATE ON ANY FLUSH OUTLET BOX(ES) TO REMAIN.• CUT BACK RACEWAY SUBS SO AS TO BE RECESSED INTO FLOOR/WALL.• PATCH ALL ANCHOR HOLES FROM REMOVED EQUIPMENT. BOXES, AND RACEWAYS.GENERAL DEMOLITION NOTESEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXEXE6E6E5FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E101PARTIALELECTRICALPLANS - LABB016/2/202111614/COB# 2013ASC/JLR113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations3"SCALE: 1/4" = 1'-0"E1014BASEMENT PLAN B013"SCALE: 1/4" = 1'-0"E1018BASEMENT DEMO PLAN B01ELECTRICAL KEYED NOTESE1 208V 50A, 3 PHASE TWIST LOCK RECEPTACLE. CONNECT TO EXISTING PANEL LPB3. PROVIDE50A/3P CIRCUIT BREAKER IN EXISTING PANEL LPB3. PROVIDE 3#6 #10G - 3/4"CE2 208V 40A, 3 PHASE TWIST LOCK RECEPTACLE. CONNECT TO EXISITNG PANEL LPB3. PROVIDE40A/3P CIRCUIT BREAKER IN EXISTING PANEL LPB3. PROVIDE 3#8 #10G - 3/4"CE3 208V NEMA - 6 - 15 OUTLET. CONNECT TO EXISTING PANEL LPB3. PROVIDE 15A/2P CIRCUITBREAKER IN EXISTING PANEL LPB3. PROVIDE 3#12 #12G - 1/2"CE5 LIGHTING FIXTURES ARE EXISTING TO REMAIN.E6 CEILING MOUNTED WIRE MOLD IS EXISTING TO REMAIN.E7 CONNECT WIRELESS ACCESS POINT TO EXISTING UNIVERSITY SYSTEM.ED2 REMOVE 208V 30A, 3 PHASE TWIST LOCK RECEPTACLE. REMOVE ALL ASSOCIATEDCIRCUITING AND RACEWAY BACK TO SOURCE CONTRACTOR SHALL VERIFY EXACTQUANTITIES IN THE FIELD.3"SCALE: 1/4" = 1'-0"E1011BASEMENT REFLECTED CEILING PLAN B01 101EX. PANELLP1A436" CODE CLEARANCEWAPE710136" CODE CLEARANCEEX. PANELLP1A4ED1A. COORDINATE SCHEDULING OF REMOVAL WORK WITH OWNER OR OWNER'S REPRESENTATIVE, PHASING DRAWINGS AND REQUIREMENTS.B. VERIFY LOCATIONS AND SCHEDULE OF REMOVAL WORK IN ALL AREAS PRIOR TO STARTING WORK. REFER TO OTHER TRADES DRAWINGS AND COORDINATE REMOVAL WORK WITH OTHER TRADES DIVISION CONTRACTORS PRIOR TO STARTING.C. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES WITHIN SPACES INDICATED. D. PROVIDE ALL REQUIRED WIRING AND TEMPORARY CONNECTIONS NECESSARY TO MAINTAIN ELECTRICAL CONTINUITY OF ALL EXISTING ELECTRICAL EQUIPMENT, RECEPTACLES, DEVICES, LIGHTING FIXTURES AND DEVICES, FIRE ALARM EQUIPMENT AND DEVICES THAT ARE TO REMAIN DURING ALL STAGES OF WORK.E. PROVIDE TEMPORARY SUPPORT FOR ALL EXISTING RACEWAYS AND BRANCH CIRCUITRY TO REMAIN DURING ALL STAGES OF WORK.F. PROTECT ALL EXISTING ELECTRICAL EQUIPMENT, RECEPTACLES, DEVICES, LIGHTING FIXTURES AND DEVICES, FIRE ALARM EQUIPMENT AND DEVICES, TELECOMMUNICATIONS EQUIPMENT AND DEVICES, SECURITY (CCTV) EQUIPMENT AND DEVICES AND ALL ASSOCIATED RACEWAYS AND BRANCH CIRCUITRY TO REMAIN FROM DAMAGE AND DEBRIS DURING ALL STAGES OF WORK.G. ALL ELECTRICAL DEVICES AND EQUIPMENT SHOWN ON FLOOR PLANS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.H. OBTAIN A LIST FROM THE OWNER, OR THE OWNER’S REPRESENTATIVE, OF ANY ITEMS THEY WISH TO RETAIN. DISCONNECT, REMOVE, INVENTORY AND DELIVER ALL ITEMS TO OWNER DESIGNATED ON-SITE LOCATION IN GOOD OPERATING ORDER. PROVIDE A TRANSMITTAL OF THE ITEMS INVENTORIED TO THE OWNER OR OWNER'S REPRESENTAIVE. ALL OTHER ITEMS SHALL BE REMOVED FROM THE PROJECT SITE COMPLETE AND DISPOSED OF IN THE APPROPRIATE MANNER.I. EXISTING CONDUIT AND BRANCH CIRCUTRY LOCATED IN NON-ACCESSIBLE WALLS/FLOORS, JUNCTION BOXES SHALL BE ABANDON IN PLACE AS FOLLOWS:• DISCONNECT BRANCH CIRCUIT AT SOURCE.• REMOVE SURFACE AND FLOOR BOX(ES).• PROVIDE PRIMED STEEL BLANK PLATE ON ANY FLUSH OUTLET BOX(ES) TO REMAIN.• CUT BACK RACEWAY SUBS SO AS TO BE RECESSED INTO FLOOR/WALL.• PATCH ALL ANCHOR HOLES FROM REMOVED EQUIPMENT. BOXES, AND RACEWAYS.GENERAL DEMOLITION NOTESA. VERIFY EXACT LOCATION OF RECEPTACLES & DATA OUTLETS WITH ARCHITECT, ARCHITECT'S ELEVATION DRAWINGS, AV CONSULTANT AND TA-SERIES DRAWINGS PRIOR TO ROUGH-IN.B. PROVIDE SEPARATE NEUTRAL AND GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT INDICATED.C. VERIFY EXACT LOCATION OF LIGHT FIXTURES WITH ARCHITECT AND ARCHITECT'S REFLECTED CEILING PLANS AND ELEVATION DRAWINGS PRIOR TO ROUGH-IN.D. CIRCUIT LIGHT FIXTURES TOGETHER WITH 2#10, #10E.G. - 1/2" CONDUIT, UNLESS NOTED OTHERWISE.E. UNLESS OTHERWISE INDICATED, AT ROOMS/LOCATIONS WHERE DIMMING SWITCHES ARE INDICATED PROVIDE 0-10V DIMMING / LIGHTING CONTROL. COORDINATE THE 0-10V DIMMING CONTROL WITH THE 0-10V LED DRIVERS AT LIGHT FIXTURES.GENERAL NOTESEXEXEXEXEX EXEXEXEXEXE5E6E4FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E102PARTIALELECTRICALPLANS - LAB1016/2/202111614/COB# 2013ASC/JLR113 Ho PlazaCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSOlin Hall B01, 101 Lab Renovations3"SCALE: 1/4" = 1'-0"E1021FIRST FLOOR POWER PLAN 1013"SCALE: 1/4" = 1'-0"E1022FIRST FLOOR DEMO PLAN 101ELECTRICAL KEYED NOTESE4 PROVIDE 120V, 20A TWIST LOCK PLUG WITH QUAD RECEPTACLE POWER BOX DOWN TOTABLE. CONNECT TO EXISTING CEILING MOUNTED WIRE MOLD. COORDINATE WITH CORNELLFACULTY REPRESENTATIVE.E5 LIGHTING FIXTURES ARE EXISTING TO REMAIN.E6 CEILING MOUNTED WIRE MOLD IS EXISTING TO REMAIN.E7 CONNECT WIRELESS ACCESS POINT TO EXISTING UNIVERSITY SYSTEM.ED1 DISCONNECT AND REMOVE EXISTING ELECTRICAL PANEL. REMOVE ALL ASSOCIATEDCIRCUITING AND RACEWAY BACK TO SOURCE. CONTRACTOR SHALL VERIFY EXACTQUANTITIES IN THE FIELD.3"SCALE: 1/4" = 1'-0"E1023FIRST FLOOR REFLECTED CEILING PLAN 101