5
6
7
8
SP
SP
SS
BL
Location of 2003 oil spill. Exploratorytest pits or borings are recommendedin this area to determine whetherresidual contamination is present.Excess contaminated soils will needto be properly disposed of. ContactEH&S at 255-8200 for further details.
180
872
180
175
182 180
87
94
182 206
189
159
165
186
99 97
182 540
111
52
128
123
395 734
206
146
181
349
2876
148
182
106
180
55
61
75
70 83
83
181 470
258
83
87
77W129A
W129
W139
W125
W123 W121 W111
W109A
W109
W107 W105 W103 W101
W120W122
W124
W138
W144
W148 W150
W143A
W141
W143 W145
W147 W153
W153B
W153A
W100C
W100S
W142
W112A
W112B
W112 W106
W102
W106A
W117
W117C W117B
W117A
W126
W130
W146
W146A
UP
E102
177
118
222
109
50
188
182
75
E151
E150
E100TA
E100SA
E100E
E150A
E103
E100CE
DN UP
1203
82
64
77
219
856
85
104
79
72
156
34
37
8 135
234
111
1009
2744
173
43
118
A106
A106A
A100UD
A100UG
A100UC
A100UJ
A100L
A100UK
A100SB
A100UH
A100TB
A100UF
A100UE
A100SA
A100J
A101
A100CA
A100UL A100CB
A100TC
A103
A100TA
UP
DN DN
UP
UP
EXTERIOR ELEVATION
1
X-100
X-100
1
1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE
DRAWING REVISION NOTE
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
#
#
#
1
1
1
11
APPLICABLE CODES
2020 NYS BUILDING CODE
2020 NYS EXISTING BUILDING CODE
2020 NYS FIRE CODE
2020 NYS PLUMBING CODE
2020 NYS MECHANICAL CODE
2020 NYS ENERGY CONSERVATION CODE
2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2010 AMERICANS WITH DISABILITY ACT (ADA)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF APPROXIMATELY 2,250 SF
OF LABORATORY AND OFFICE SPACES ON THE FIRST FLOOR OF SEELEY
G. MUDD HALL FOR INCOMING RESEARCHERS.
ALTERATION LEVEL 2:
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE,
THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
RECONFIGURATION OR EXTENTION OF ANY SYSTEM, OR THE
INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED
SUCH THAT THE BUILDING BECOMES LESS SAFE THAN ITS EXISTING
CONDITIONS.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION: 1B
CLASSIFICATION OF HAZARDS: MAQ IN PROGRESS
HIGH-RISE BUILDING: NO
EXTINGUISHING REQUIREMENT: THE EXISTING BUILDING IS
PARTIALLY SPRINKLERED.
WORK AREA WILL BE SPRINKLERED.
OCCUPANCY OF AREA OF WORK
OCCUPANCY CLASSIFICATION: BUSINESS (B)
MECHANICAL
M-001 MECHANICAL GENERAL NOTES AND SYMBOL LEGENDS
M-101 MECHANICAL DUCTWORK & PIPING DEMOLITION PLANS
M-102 MECHANICAL NEW WORK DUCTWORK PLANS
M-103 MECHANICAL NEW WORK PIPING PLANS
M-301 CONTROLS
M-302 CONTROLS
M-303 CONTROLS
M-304 CONTROLS
M-305 CONTROLS
M-306 CONTROLS
M-307 CONTROLS
M-308 CONTROLS
M-501 SCHEDULES
M-502 SCHEDULES
ELECTRICAL
E-001 GENERAL NOTES AND SYMBOL LEGENDS
E-101 PARTIAL EXISTING POWER DISTRIBUTION KEY PLAN
E-102 PARTIAL FIRST FLOOR ELECTRICAL DEMOLITION PLAN
E-103 PARTIAL FIRST FLOOR LIGHTING & FIRE ALARM PLAN
E-104 PARTIAL FIRST FLOOR POWER & DATA PLAN
T-001 TITLE SHEET
ARCHITECTURAL
A-001 CODE COMPLIANCE PLAN, GENERAL NOTES,
SYMBOLOGY, AND ABBREVIATIONS
A-101 DEMOLITION PLAN , FLOOR PLAN, RCP
A-102 FINISH PLAN
A-103 INTERIOR ELEVATIONS, DETAILS, AND DOOR SCHEDULE
FIRE PROTECTION
FP-001 FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND
SCHEDULES
FP-101 FIRE PROTECTION DEMOLITION PLAN
FP-102 FIRE PROTECTION NEW WORK PLAN
PLUMBING
P-001 GENERAL NOTES, SYMBOL LEGENDS, & SCHEDULES
P-101 PLUMBING DEMOLITION PLAN
P-102 PLUMBING NEW WORK PLANCORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
LABORATORY
RENOVATIONS
T-001
12971596
TITLE SHEET
FE DESIGN
NH
1019W
12 MARCH 2021
SEELEY G. MUDD FIRST FLOOR LABORATORY
RENOVATIONS
BUILDING CODE SUMMARYGENERAL SYMBOLS LEGEND
DRAWING INDEX
PROJECT SCOPE
THIS PROJECT INCLUDES THE RENOVATION OF APPROXIMATELY 2,250 SF OF LABORATORY AND OFFICE SPACES ON THE FIRST FLOOR OF SEELEY G.
MUDD HALL FOR INCOMING RESEARCHERS.
PERSPECTIVE VIEWSITE LOCATION -SEELEY G. MUDD HALL
KEY PLAN -FIRST FLOOR
1019W
CAMPUS ROAD
TOWER ROAD
GARDEN AVENUEEAST AVENUE1019E
AREA OF WORK
1 01/15/2021 ISSUE FOR DD REVIEW
2 02/19/2021 ISSUE FOR 95% REVIEW
3 03/12/2021 ISSUE FOR CONSTRUCTION
180
872
180
175
182 180
87
94
182 206
189
159
165
186
99 97
182 540
111
52
128
123
395 734
206
146
181
349
2876
148
182
106
180
55
61
75
70 83
83
181 470
258
83
87
77W129A
W129
W139
W125
W123 W121 W111
W109A
W109
W107 W105 W103 W101
W120W122
W124
W138
W144
W148 W150
W143A
W141
W143 W145
W147 W153
W153B
W153A
W100C
W100S
W142
W112A
W112B
W112 W106
W102
W106A
W117
W117C W117B
W117A
W126
W130
W146
W146A
UP
E102
1018_f0g 1018_f0g
177 182 182
226
99
1720
236
302
379
118
222 195
94
78
109
50
103
103
67
34 34
188 186 185 186 159 365
171 172 172 172 172 171
455
182
349186
193
340
1386
41
114
64
196 604
137 187
75
740
75
E151 E145
E141
E139 E137
E131
E131A
E100UB
E100UA
E129
E125
E123
E150 E148 E146
E116
E100TA
E120
E100SA
E100CB
E100CA
E100SB
E100E
E141A
E118E150A
E117E115E113E111E109
E107
E105E103
E104 E108E106 E110 E112 E114
E107A E107B
E100CE E100CD E100CC
WASHER
E142
E142A
E138 E136
DN UP DN
DN
UP
1203
82
64
77
219
856
85
104
79
72
156
34
37
8
135
234
111
1009
2744
173
43
118
A106
A106A
A100UD
A100UG
A100UC
A100UJ
A100L
A100UK
A100SB
A100UH
A100TB
A100UF
A100UE
A100SA
A100J
A101
A100CA
A100UL A100CB
A100TC
A103
A100TA
UP
DN DN
UP
UP
WALL - EXISTING
WALL - METAL STUD/ GWB
WALL - CONCRETE
WALL - CMU
WALL - BRICK
ITEMS FOR DEMOLITION
DOOR/ WALL - EXISTING
DOOR/ WALL - NEW
DOOR/ WALL - DEMOLITION
TAG - DOOR
TAG - WINDOW
TAG - WALL
TAG - ROOM #
CENTER LINE
PHOTO REFERENCE
LEVEL MARKER
COLUMN GRID MARKER
ELEVATION MARKER
ELEVATION CHANGE ARROWS
BREAK LINE
SYMBOLS
0' - 0"
101
1t
X-X
X
2B00UA
CL
1
Name
Elevation
A101 1
1
1
0
DN
UP
1-HOUR FIRE SEPARATION
2-HOUR FIRE SEPARATION
ABBREVIATIONS
A
& AND
@ AT
ACT ACOUSTICAL CEILING TILE
ALT ALTERNATE
ALUM ALUMINUM
AVG AVERAGE
AFF ABOVE FINISH FLOOR
B
BD BOARD
BLDG BUILDING
BOD BOTTOM OF DECK
BSMT BASEMENT
C
CG CORNER GUARDS
CJ CONTROL JOINT
CLG CEILING
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CRS COURSE(S)
CT CERAMIC TILE
D
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DO DOOR OPENING
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC
ELEV ELEVATION/ ELEVATOR
EPDM RUBBER ROOF MEMBRANE
EQ EQUAL
EX'G EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FRP FIBER REINFORCED POLYESTER
FT FOOT/FEET
FTG FOOTING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GLASS
GWB GYPSUM WALL BOARD
H
HC HANDICAPPED
HT HEIGHT
HM HOLLOW METAL
HR HOUR
HVAC HEATING, VENTILATING & AC
J
JAN JANITOR
L
LAV LAVATORY
LB/# POUND
LGMF LIGHT GAGE METAL FRAMING
LVT LUXURY VINYL TILE
M
MFR MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NR NOT RATED
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OSB ORIENTER STRAND BOARD
P
+/- PLUS OR MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
Q
QTY QUANTITY
R
R RISER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIGERATOR
REQ REQUIRED
REV REVISION
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SHTG SHEATHING
SIM SIMILAR
SF SQUARE FOOT/ FEET
SS STAINLESS STEEL
STL STEEL
STD STANDARD
T
T TREAD
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TOS TOP OF STEEL
TV TELEVISION
TYP TYPICAL
U
UEV UNEVEN DOORS W/ VISION PANEL
UEF UNEVEN FLUSH DOOR
V
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
W
W/O WITHOUT
WD WOOD
"P1"
PLAN
3 -5/8"-20 GA. METAL STUDS
@ 16" O.C.
SOUND ATTENUATION BLANKET,
FULL STUD DEPTH, FULL HEIGHT
(1) LAYERS OF 5/8" GYPSUM BOARD,
TYPE X, EACH SIDE. FINISH LEVEL 4
(TAPE, SPACKLE, SAND). PRIME AND
PAINT (2 COATS)
SILL
SEALANT
HEAD
SEALANT
5/8"3 5/8"5/8"
4 7/8"
5/16" EXPANSION ANCHOR (POWER BOLT B
POWERS) AT 16" O.C.
MIN. 1-1/2" EMBED INTO EXISTING CONCRETE
SLIP TRACK
PROVIDE SEAL AROUND ALL STRUCTURAL OR
UTILITY PENETRATIONS (FIRE RATED SEALANT
AT ALL FIRE RATED PARTITIONS)
DECK ABOVE
ACOUSTIC CEILING
SYSTEM AS SCHEDULED
WALL BASE AS SCHEDULED
"P3"
PLAN
SILL
HEAD
3 5/8"5/8"
4 7/8"4 1/4"
SAME AS P1, BUT ONLY
(1) LAYER OF GYPSUM
BOARD ON ONE SIDE
GENERAL PARTITION NOTES
1. STEEL STUDS/GYPSUM PARTITIONS SHALL EXTEND FROM FLOOR TO UNDERSIDE OF FLOOR / ROOF DECK ABOVE.
MAINTAIN ALL REQUIRED FIRE RATINGS AND SOUND RATINGS.
2. PROVIDE CONTINUOUS SEALANT AT ALL EDGES OF PARTITIONS WHICH REQUIRE A FIRE, SMOKE OR STC. RATINGS.
3. ALL DUCTS, PIPES, CONDUIT, FRAMING MEMBERS, PASSING THROUGH NON-FIRE-RATED WALLS OR PARTITIONS SHALL
BE TIGHTLY SEALED.
4. SEE RENOVATION NOTES FOR HOLDING ROOM CONSTRUCTION
"P2" SAME AS P1, BUT WIDTH TO MATCH EXISTING PARTITION TO BE INFILLED.
VERIFY IN FIELD.
AREA OF WORK
ACTUAL MAXIMUM COMMON PATH OF EGRESS:
38 FEET
(BCNYS 1006.2.1 B, OCCUPANT LOAD <30: NOT
TO EXCEED 100' WITHOUT SPRINKLER SYSTEM)
ACTUAL MAXIMUM TRAVEL
DISTANCE TO EXIT: 172 FEET
(BCNYS 1017.2 B: NOT TO EXCEED
200' WITHOUT SPRINKLER SYSTEM)
TRAVEL DISTANCE TO EXIT: 130 FEET
FLOOR FIRE RATING BETWEEN STORIES:
2-HOUR FIRE SEPARATION
TRAVEL DISTANCE TO EXIT: 172 FEET
TRAVEL DISTANCE TO EXIT: 124 FEET
TRAVEL DISTANCE TO
EXIT: 123 FEET
1019W1019ACONTROL AREA AGP1-CA1
ESTABLISHED OCTOBER 2016,
MODIFIED MARCH 2021
PROJECT 12971596
SEELEY G. MUDD HALL (1019W)ATRIUM (1019A)DALE R. CORSON HALL (1019E)1019A1019E1019W1019A1019A1019ECORSON MUDD COMPLEX
APPLICABLE CODES
2020 NYS BUILDING CODE
2020 NYS EXISTING BUILDING CODE
2020 NYS FIRE CODE
2020 NYS PLUMBING CODE
2020 NYS MECHANICAL CODE
2020 NYS ENERGY CONSERVATION CODE
2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2010 AMERICANS WITH DISABILITY ACT (ADA)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF APPROXIMATELY 2,250 SF
OF LABORATORY AND OFFICE SPACES ON THE FIRST FLOOR OF SEELEY
G. MUDD HALL FOR INCOMING RESEARCHERS.
ALTERATION LEVEL 2:
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE,
THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
RECONFIGURATION OR EXTENTION OF ANY SYSTEM, OR THE
INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED
SUCH THAT THE BUILDING BECOMES LESS SAFE THAN ITS EXISTING
CONDITIONS.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION: 1B
CLASSIFICATION OF HAZARDS: MAQ IN PROGRESS
HIGH-RISE BUILDING: NO
EXTINGUISHING REQUIREMENT: THE EXISTING BUILDING IS
PARTIALLY SPRINKLERED.
WORK AREA WILL BE SPRINKLERED.
OCCUPANCY OF AREA OF WORK
OCCUPANCY CLASSIFICATION: BUSINESS (B)
5/8" GYPSUM WALL
BOARD (BOTH SIDES) -
CORRIDOR SIDE FINISH
TO MATCH ADJACENT
METAL BASE TRACK
WALL BASE -
MATCH ADJACENT
MATCH EXISTING CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
LABORATORY
RENOVATIONS
A-001
12971596
CODE
COMPLIANCE
PLAN, GENERAL
NOTES,
SYMBOLOGY,
AND
ABBREVIATIONS
N.HACHMANN
NH
1019W
12 MARCH 2021
GENERAL NOTES
1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND
OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE
UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101
LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND
ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS
BEING CONSTRUCTED.
2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE
AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL
MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR
NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER
PORTION OF THE DRAWINGS AND / OR NOTES.
3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE
THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST
QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING,
PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS
AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK
WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO
THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR
WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE
REPLACED AT NO COST TO THE OWNER.
4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING
CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE
ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE
PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE
ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING.
5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND /
OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF
UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED
SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED
AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS,
ROOF OR FLOOR TO BE INFILLED SOLID.
6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF
OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY
SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF
REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER
CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE
SPACES OR AREAS TO ORIGINAL CONDITION.
7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE
WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS
AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES,
LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION
NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO
INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT
LOCATION OF ALL ITEMS.
8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT
WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS
INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL
TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH
FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE
AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE
PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND
NAME OF INSTALLER.
9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO
VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE
REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A
POINT THAT A CONTAINER IS NO LONGER REQUIRED.
10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING
SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS
OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND
CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER.
PARTITION TYPES
SCALE:1" = 20'-0"1 FIRST FLOOR CODE COMPLIANCE PLAN
BUILDING CODE SUMMARY
1 01/15/2021 ISSUE FOR DD REVIEW
2 02/19/2021 ISSUE FOR 95% REVIEW
3 03/12/2021 ISSUE FOR CONSTRUCTION
WALL INFILL AT
CORRIDOR -BASE
ROOMCORRIDOR
S SSSSSS
F
CO
SSF
S
S
DS
94 SF
W154A
BEHAVIOR 1
38 SF
W154
ANTEROOM
274 SF
W154C
BEHAVIOR 3
148 SF
W154B
BEHAVIOR 2
188 SF
W156
PROCEDURE
54 SF
W162C
HOLDING 1
79 SF
W162A
BEHAVIOR 4
96 SF
W162
ANTEROOM 162 SF
W162E
IMAGING
536 SF
W161
MAIN LAB
113 SF
W162D
BEHAVIOR 5
51 SF
W162B
HOLDING 2
103 SF
W161C
OFFICE 1
105 SF
W161B
OFFICE 2
149 SF
W161A
MEETING
W162C
W162B
W162A
W162D
W162E
W156
W154A
W154B
W154C
W161C
W161A
W161C W161B
W161A
W162A
W162D
1 2
W154 8' - 2 3/4" +/-11' - 7"10'-2" +/-
CLEAR
6' - 1 1/2" +/-14'-9" +/-ALIGNALIGN5' - 10"5' - 8"8' - 3 3/4" +/-ALIGNALIGN9' - 9 3/4" +/-10' - 0"16'-1" +/-14'-8" +/-EQEQ9' - 9 3/4" +/-6' - 3 1/2" +/-11' - 0"7' - 9 1/2"10' - 0"14' - 10" +/-
P1
P1
P3
P1
P1
P1
P2
P1
P1
P1
P1
P2 P2
W161
3
4
4
5
A-103 65
A-103 24
A-1033 1' - 6"2' - 7"7' - 10"9'-10" +/-7' - 10"2' - 7"
1
6
W100C
3
P3P3
P3
NIC
NIC
7
8
7
8 8
8
9
99
9
9
9
9
10
11
11
111111
11
11
W162
12
12
11
A-103
1' - 0"4"
15
16
16
16
16
1 2 3 8
76".3' - 6"
5 6
66
6'-9".4
444
4
1 2
3 8
1 2
3 8
1 2
3 8
1 2
3 8
1 2
3 8
1 2
3 8
1 2
3 8
1 2
3 8
1 2
3 8
1 2
3 8
1 2 3 8
5
6 6
6
9
9
9
9
13
13
13
13
13
1313
11
A-103
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
14
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"8' - 6"CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
LABORATORY
RENOVATIONS
A-101
12971596
DEMOLITION
PLAN , FLOOR
PLAN, RCP
N.HACHMANN
NH
1019W
12 MARCH 2021
A-101 RENOVATION NOTES
.G1 GENERAL: ALL CHAIRS ARE NOT IN CONTRACT (N.I.C.). ALL FURNITURE SHOWN
WITH DASHED LINES IS N.I.C.
.G2 GENERAL: DIMENSIONS ARE TO CENTERLINE OF PARTITION UNLESS NOTED
OTHERWISE
.G3 GENERAL: SEE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION
DRAWINGS FOR SCOPE INFORMATION.
.G4 GENERAL: INSTALL SELF-LEVELING FLOORING UNDERLAYMENT "ARDEX FEATHER
FINISH" OR EQUIVALENT UNDERLAYMENT TO FLASH PATCH THE ENTIRE PROJECT
AREA. PREPARE FLOOR AS REQUIRED BY NEW FLOORING MANUFACTURER'S
REQUIREMENTS.
.G5 GENERAL: PATCH ALL HOLES IN EXISTING TO REMAIN WALLS TO MATCH ADJACENT
SURFACE AND PREPARE FOR PAINTING.
.G6 GENERAL: PAINT MISCELLANEOUS PIPING AND CONDUIT MOUNTED ON WALL PT-1.
.G7 GENERAL: KEY DOORS WITH CORNELL STANDARD SYSTEM (COORDINATE WITH CU
LOCKSHOP). SEE A-601 FOR DOOR AND DOOR HARDWARE INFORMATION.
1 INSPECT EXISTING FIRE RATED PARTITIONS IN WORK AREA (CORRIDORS,
STAIRWAYS, SHAFTS) TO CONFIRM ALL PENETRATIONS ARE PROPERLY
FIRE-STOPPED. USE APPROPRIATE FIRE-STOPPING MATERIAL TO FILL IN ANY OPEN
PENETRATIONS IN THE ENTIRETY OF THESE WALLS (INCLUDING UP TO DECK
ABOVE) TO CONFIRM FIRE-RATING IN WORK AREA AS INDICATED ON THE CODE
COMPLIANCE PLAN.
2 IF REMOVAL OF SUSPENDED CEILING SYSTEM WAS REQUIRED, REINSTALL
SUSPENDED CEILING SYSTEM AFTER THE COMPLETION OF MECHANICAL,
ELECTRICAL, AND PLUMBING WORK. REPLACE ANY DAMAGED PIECES WITH NEW
ACOUSTICAL CEILING PANELS AND GRID TO MATCH EXISTING.
3 FURNISH AND INSTALL BLACKOUT CURTAIN AND MOUNTING HARDWARE, FULL
HEIGHT AND WIDTH OF ROOM. PROVIDE ALL HARDWARE TO ATTACH TO GRID OF
8'-6"" ACOUSTICAL CEILING.
BASIS OF DESIGN PRODUCT: BLACKOUTCURTAINS.COM, CEILING MOUNT,
BLACK/BLACK TEXTRON, INCLUDING ALUMINUM TRACK, STANDARD VALANCE, SPLIT
WITH VELCRO OVERLAP.
4 FURNISH AND INSTALL BUMPER GUARD ON NORTH, WEST, AND EAST WALLS OF
BOTH HOLDING ROOMS AT 3'-0" AFF ON CENTER.
BASIS OF DESIGN PRODUCT: CONSTRUCTION SPECIALTIES, MODEL "BG-30", COLOR
"262 DRIFTWOOD"
5 RODENT RACK, N.I.C.
6 STEEL FRAMED TABLE 24"X48" WITH STAINLESS STEEL TOP. BASIS OF DESIGN:
MOTT, ALTUS TABLE 2248, BRIGHT WHITE
7 STEEL FRAMED TABLE 24"X48" WITH EPOXY RESIN TOP. BASIS OF DESIGN: MOTT,
ALTUS TABLE 2248, BRIGHT WHITE
8 STEEL FRAMED TABLE 30"X48" WITH EPOXY RESIN TOP. BASIS OF DESIGN: MOTT,
ALTUS TABLE 2848, BRIGHT WHITE
9 STEEL FRAMED TABLE 30"X60" WITH EPOXY RESIN TOP. BASIS OF DESIGN: MOTT,
ALTUS TABLE 2860, BRIGHT WHITE
10 STEEL LABORATORY CASEWORK. BASIS OF DESIGN: MOTT, STEEL BASE AND WALL
CABINETS, ADA HEIGHT, BRIGHT WHITE, WITH EPOXY RESIN COUNTER. SEE
INTERIOR ELEVATION FOR CONFIGURATION AND MEP DRAWINGS FOR SINK
CONNECTIONS AND FITTINGS.
11 STEEL SHELVING UNIT CONSISTING OF (4) STANDARDS, (4) SHELF BRACKETS AND
(2) STEEL SHELVES (32" WIDE, 12" DEEP +/-). ALL PAINTED WHITE. BASIS OF DESIGN:
MCMASTER-CARR OR APPROVED EQUAL
12 IN HOLDING ROOMS, USE FIBERROCK AQUA-TOUGH ON WALLS AND CEILING
CONSTRUCTION, AND SANITARY MILDEW RESISTANT SILICONE SEALANT "PECORA
898"
13 IN EACH BEHAVIOR ROOM, FURNISH AND INSTALL RAILS AS SHOWN AND SO THAT
BOTTOM OF RAIL IS FLUSH WITH BOTTOM OF ADJACENT ACOUSTICAL CEILING
PANEL. FASTEN TO DECK ABOVE. BASIS-OF DESIGN PRODUCT: "8020.NET,
ALUMINUM T-SLOTS, SQUARE 1010. FURNISH TWO ADDITIONAL 1010 PROFILE AT
7-FOOT LENGTHS AND APPROPRIATE FASTENERS TO CONNECT PERPENDICULAR
TO RAILS AT FLEXIBLE LOCATIONS
14 ACCESS PANEL18" X 18", BASIS-OF-DESIGN MODEL: NYSTROM, NT-SERIES-304
STAINLESS STEEL
15 CHASE WALL WITH 2-1/2" STUDS AND ONE LAYER OF GYPSUM DRYWALL ON ONE
SIDE FOR FAN COIL UNIT CONDENSATE LINE CONNECTION TO EXISTING DRAIN IN
THIS VICINITY. INCLUDE 8"X8" DRYWALL ACCESS DOOR WITH MUD-IN FLANGE, PAINT
TO MATCH ADJACENT FINISH. VERIFY EXACT LOCATION IN FIELD. COORDINATE
WITH MECHANICAL.
16 AT LOCATIONS OF REMOVED PARTITIONS OR NEW DOORS THAT ARE MARKED WITH
DEMOLITION NOTE 9, PROVIDE TWO 45 DEGREE KICKERS AS TOP OF WALL
BRACING OF REMAINING WALLS. PROVIDE TRACK SECURED TO UNDERSIDE OF
DECK ABOVE AND WALL STUDS FOR CONNECTIONS.
#
A-101 DEMOLITION NOTES
0A GENERAL: HAZARDOUS MATERIALS ARE EXPECTED. OWNER WILL PERFORM
REMOVAL OF ASBESTOS AND PCB CONTAINING MATERIAL PRIOR TO
CONSTRUCTION START. ALERT OWNER IF ENCOUNTERING FURTHER SUSPICIOUS
MATERIAL.
0B GENERAL: SEE MEPFP DRAWINGS FOR REMOVAL OF MEPFP EQUIPMENT AND
COORDINATE ACCORDINGLY.
1 REMOVE AND DISPOSE OF REMAINING NON-HAZARDOUS FLOOR FINISH DOWN TO
CONCRETE DECK. REMOVE ADHESIVE AND PREPARE FLOORING FOR FLASH
PATCHING AND AS REQUIRED FOR INSTALLATION OF NEW FLOOR FINISH AS PER
FLOORING MANUFACTURER'S REQUIREMENTS.
2 REMOVE AND DISPOSE OF CABINETRY AND EQUIPMENT WHERE NOTED.
3 REMOVE LOOSE EQUIPMENT, FURNITURE, AND WALL MOUNTED ITEMS.
COORDINATE WITH OWNER WHICH ITEMS TO SALVAGE.
4 REMOVE (PORTION OF) EXISTING PARTITION WHERE NOTED, INCLUDING DOORS
AND DOOR FRAMES IF APPLICABLE. PATCH ADJACENT WALL.
5 CUT OPENING IN EXISTING PARTITION FOR NEW DOOR AND FRAME WHERE NOTED.
PATCH ADJACENT WALL.
6 REMOVE DOOR AND DOOR FRAME IN ITS ENTIRETY. PATCH AND PREPARE
ADJACENT WALL TO RECEIVE NEW CONSTRUCTION AS SCHEDULED.
7 CAREFULLY REMOVE THE PORTION OF THE EXISTING SUSPENDED CEILING SYSTEM
AS REQUIRED TO PERFORM MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION WORK. SALVAGE FOR REINSTALLATION AFTER COMPLETION OF
MEPFP WORK.
8 REMOVE SUSPENDED CEILING SYSTEM IN ITS ENTIRETY. COORDINATE
PROTECTION OF REMAINING MEPFP ITEMS AND PREPARE FOR INSTALLATION IN
NEW CEILING.
9 SEE CONSTRUCTION NOTE 16
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"2 PARITAL FIRST FLOOR PLAN
SCALE:1/8" = 1'-0"1 PARTIAL FIRST FLOOR DEMOLITION PLAN
SCALE:1/8" = 1'-0"3 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN
0' 4' 8'16'
SCALE: 1/8"=1'-0"
1 01/15/2021 ISSUE FOR DD REVIEW
2 02/19/2021 ISSUE FOR 95% REVIEW
3 03/12/2021 ISSUE FOR CONSTRUCTION
GENERAL: HAZARDOUS MATERIALS ARE EXPECTED. OWNER WILL PERFORMREMOVAL OF ASBESTOS AND PCB CONTAINING MATERIAL AS WELL AS REMOVAL OFLAB CASEWORK NORTH OF THE CORRIDOR IN ORDER TO PERFORM ABATEMENT.ALERT OWNER IF ENCOUNTERING FURTHER SUSPICIOUS MATERIAL.
6
8
8
A-101 RENOVATION NOTES
.G1 GENERAL: ALL CHAIRS ARE NOT IN CONTRACT (N.I.C.). ALL FURNITURE SHOWN
WITH DASHED LINES IS N.I.C.
.G2 GENERAL: DIMENSIONS ARE TO CENTERLINE OF PARTITION UNLESS NOTED
OTHERWISE
.G3 GENERAL: SEE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION
DRAWINGS FOR SCOPE INFORMATION.
.G4 GENERAL: INSTALL SELF-LEVELING FLOORING UNDERLAYMENT "ARDEX FEATHER
FINISH" OR EQUIVALENT UNDERLAYMENT TO FLASH PATCH THE ENTIRE PROJECT
AREA. PREPARE FLOOR AS REQUIRED BY NEW FLOORING MANUFACTURER'S
REQUIREMENTS.
.G5 GENERAL: PATCH ALL HOLES IN EXISTING TO REMAIN WALLS TO MATCH ADJACENT
SURFACE AND PREPARE FOR PAINTING.
.G6 GENERAL: PAINT MISCELLANEOUS PIPING AND CONDUIT MOUNTED ON WALL PT-1.
.G7 GENERAL: KEY DOORS WITH CORNELL STANDARD SYSTEM (COORDINATE WITH CU
LOCKSHOP). SEE A-601 FOR DOOR AND DOOR HARDWARE INFORMATION.
1 INSPECT EXISTING FIRE RATED PARTITIONS IN WORK AREA (CORRIDORS,
STAIRWAYS, SHAFTS) TO CONFIRM ALL PENETRATIONS ARE PROPERLY
FIRE-STOPPED. USE APPROPRIATE FIRE-STOPPING MATERIAL TO FILL IN ANY OPEN
PENETRATIONS IN THE ENTIRETY OF THESE WALLS (INCLUDING UP TO DECK
ABOVE) TO CONFIRM FIRE-RATING IN WORK AREA AS INDICATED ON THE CODE
COMPLIANCE PLAN.
2 IF REMOVAL OF SUSPENDED CEILING SYSTEM WAS REQUIRED, REINSTALL
SUSPENDED CEILING SYSTEM AFTER THE COMPLETION OF MECHANICAL,
ELECTRICAL, AND PLUMBING WORK. REPLACE ANY DAMAGED PIECES WITH NEW
ACOUSTICAL CEILING PANELS AND GRID TO MATCH EXISTING.
3 FURNISH AND INSTALL BLACKOUT CURTAIN AND MOUNTING HARDWARE, FULL
HEIGHT AND WIDTH OF ROOM. PROVIDE ALL HARDWARE TO ATTACH TO GRID OF
8'-6"" ACOUSTICAL CEILING.
BASIS OF DESIGN PRODUCT: BLACKOUTCURTAINS.COM, CEILING MOUNT,
BLACK/BLACK TEXTRON, INCLUDING ALUMINUM TRACK, STANDARD VALANCE, SPLIT
WITH VELCRO OVERLAP.
4 FURNISH AND INSTALL BUMPER GUARD ON NORTH, WEST, AND EAST WALLS OF
BOTH HOLDING ROOMS AT 3'-0" AFF ON CENTER.
BASIS OF DESIGN PRODUCT: CONSTRUCTION SPECIALTIES, MODEL "BG-30", COLOR
"262 DRIFTWOOD"
5 RODENT RACK, N.I.C.
6 STEEL FRAMED TABLE 24"X48" WITH STAINLESS STEEL TOP. BASIS OF DESIGN:
MOTT, ALTUS TABLE 2248, BRIGHT WHITE
8 STEEL FRAMED TABLE 30"X48" WITH EPOXY RESIN TOP. BASIS OF DESIGN: MOTT,
ALTUS TABLE 2848, BRIGHT WHITE
9 STEEL FRAMED TABLE 30"X60" WITH EPOXY RESIN TOP. BASIS OF DESIGN: MOTT,
ALTUS TABLE 2860, BRIGHT WHITE
10 STEEL LABORATORY CASEWORK. BASIS OF DESIGN: MOTT, STEEL BASE AND WALL
CABINETS, ADA HEIGHT, BRIGHT WHITE, WITH EPOXY RESIN COUNTER. SEE
INTERIOR ELEVATION FOR CONFIGURATION AND MEP DRAWINGS FOR SINK
CONNECTIONS AND FITTINGS.
11 STEEL SHELVING UNIT CONSISTING OF (4) STANDARDS, (4) SHELF BRACKETS AND
(2) STEEL SHELVES (32" WIDE, 12" DEEP +/-). ALL PAINTED WHITE. BASIS OF DESIGN:
MCMASTER-CARR OR APPROVED EQUAL
12 IN HOLDING ROOMS, USE FIBERROCK AQUA-TOUGH ON WALLS AND CEILING
CONSTRUCTION, AND SANITARY MILDEW RESISTANT SILICONE SEALANT "PECORA
898"
13 IN EACH BEHAVIOR ROOM, FURNISH AND INSTALL RAILS AS SHOWN AND SO THAT
BOTTOM OF RAIL IS FLUSH WITH BOTTOM OF ADJACENT ACOUSTICAL CEILING
PANEL. FASTEN TO DECK ABOVE. BASIS-OF DESIGN PRODUCT: "8020.NET,
ALUMINUM T-SLOTS, SQUARE 1010. FURNISH TWO ADDITIONAL 1010 PROFILE AT
7-FOOT LENGTHS AND APPROPRIATE FASTENERS TO CONNECT PERPENDICULAR
TO RAILS AT FLEXIBLE LOCATIONS
14 ACCESS PANEL18" X 18", BASIS-OF-DESIGN MODEL: NYSTROM, NT-SERIES-304
STAINLESS STEEL
15 CHASE WALL WITH 2-1/2" STUDS AND ONE LAYER OF GYPSUM DRYWALL ON ONE
SIDE FOR FAN COIL UNIT CONDENSATE LINE CONNECTION TO EXISTING DRAIN IN
THIS VICINITY. INCLUDE 8"X8" DRYWALL ACCESS DOOR WITH MUD-IN FLANGE, PAINT
TO MATCH ADJACENT FINISH. VERIFY EXACT LOCATION IN FIELD. COORDINATE
WITH MECHANICAL.
16 AT LOCATIONS OF REMOVED PARTITIONS OR NEW DOORS THAT ARE MARKED WITH
DEMOLITION NOTE 9, PROVIDE TWO 45 DEGREE KICKERS AS TOP OF WALL
BRACING OF REMAINING WALLS. PROVIDE TRACK SECURED TO UNDERSIDE OF
DECK ABOVE AND WALL STUDS FOR CONNECTIONS.
#
148 SF
ACP2
LIN1
W154B
LIN1
PT1
BEHAVIOR 2
94 SF
ACP2
LIN1
W154A
LIN1
PT1
BEHAVIOR 1
38 SF
ACP2
LIN1
W154
LIN1
PT1
ANTEROOM
274 SF
ACP2
LIN1
W154C
LIN1
PT1
BEHAVIOR 3
188 SF
ACP2
SRF
W156
SRF
PT1
PROCEDURE
79 SF
ACP2
LIN1
W162A
LIN1
PT1
BEHAVIOR 4
51 SF
GYP
SRF
W162B
SRF
PT2
HOLDING 2
54 SF
GYP
SRF
W162C
SRF
PT2
HOLDING 1
96 SF
ACP2
SRF
W162
SRF
PT2
ANTEROOM
113 SF
ACP2
LIN
W162D
LIN
ACP1
BEHAVIOR 5
162 SF
ACP2
LIN1
W162E
LIN1
PT1
IMAGING
536 SF
ACP1
LIN1
W161
RB1
PT1,2
MAIN LAB
149 SF
ACP1
LVT
W161A
RB1
PT1,2
MEETING
103 SF
ACP1
LVT
W161C
RB1
PT1
OFFICE 1
105 SF
ACP1
LVT
W161B
RB1
PT1
OFFICE 2
RSRSRSRS
11
A-103
ROOM
NUMBER
CEILING
FINISH
WALL
FINISH
FLOOR
FINISH
WALL
BASE
ROOM
AREA
ROOM NAME
CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
LABORATORY
RENOVATIONS
A-102
12971596
FINISH PLAN
N.HACHMANN
NH
1019W
12 MARCH 2021
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"3 PARITAL FIRST FLOOR FINISH PLAN
- - EXISTING TO REMAIN
ACP1 ACOUSTIC CEILING PANEL SYSTEM
ARMSTRONG "OPTIMA" WITH PLANT-BASED BINDER,
24"x24", 9/16" TEGULAR,
SUSPENSION SYSTEM: ARMSTRONG, 9/16" SUPRAFINE
ACP2 ACOUSTIC CEILING PANEL SYSTEM
ARMSTRONG "OPTIMA HEALTH ZONE" WITH PLANT-BASED BINDER,
24"x24", 9/16" TEGULAR,
SUSPENSION SYSTEM: ARMSTRONG, 9/16" SUPRAFINE
GYP IN HOLDING ROOMS W162B AND W162C:
SUSPENDED HARD CEILING CONSTRUCTED WITH "FIBERROCK AQUA TOUGH",
PAINTED WITH PT2
LIN LINOLEUM, SHEET
FORBO, MARMOLEUM STRIATO
PATTERN / COLOR: "3573 TRACE OF NATURE"
INSTALLED WITH "ARMOR COVE" (1-PIECE INTEGRAL ALUMINUM CAP,
BACKING, AND COVE) AND WELDED SEAMS
LVT LUXURY VINYL TILE
INTERFACE, NATURAL WOODGRAINS
COLOR: "A00207 WASHED WHEAT"
MTS METAL TRANSITION STRIP
PROVIDE AT EVERY TRANSITION FROM ONE FINISH TO ANOTHER,
SCHLUTER VINPRO (-S, -T, OR -U AS APPLICABLE)
PAINT
PT1 INTERIOR WALLS, TYPICAL
BENJAMIN MOORE, LATEX, LOW-VOC, EGGSHELL
COLOR: 912 "LINEN WHITE"
PT2 INTERIOR WALLS RODENT HOLDING ROOM
BENJAMIN MOORE, M43/M44 ACRYLIC EPOXY COATING
COLOR: 912 "LINEN WHITE"
PT3 BENJAMIN MOORE, COLOR MATCH EXISTING, SEMI-GLOSS
HM DOORS AND FRAMES (CORRIDOR SIDE)
PT4 BENJAMIN MOORE, COLOR: 912 "LINEN WHITE", SEMI-GLOSS
HM DOORS AND FRAMES (NON-CORRIDOR)
RB RUBBER BASE
JOHNSONITE, 4" COVE BASE
COLOR : "20 CHARCOAL"
RS ROLLER SHADE SYSTEM
MANUAL HORIZONTAL SINGLE ROLLER SHADE WITH FASCIA
- MECHOSHADE "MECHO/5 STANDARD BRACKET WITH WHITE
SNAPLOC FASCIA" SYSTEM INCLUDING ALL REQUIRED ACCESSORIES
- SHADECLOTH: MECHOSHADE "ECOVEIL SCREENS"
3% OPENNESS FACTOR
COLOR: 1569 SILVER BIRCH
RES EPOXY RESIN COUNTER TOP - BLACK
SRF SEAMLESS RESINOUS FLOORING
STONHARD, STONSHIELD UTR WITH COVE BASE,
COLOR: FLAGSTONE
FINISH LEGEND
(BASIS-OF-DESIGN PRODUCTS)
NOT TO SCALE23D BEHAVIOR AND HOLDING
NOT TO SCALE13D MAIN LAB AND OFFICES
1 01/15/2021 ISSUE FOR DD REVIEW
2 02/19/2021 ISSUE FOR 95% REVIEW
3 03/12/2021 ISSUE FOR CONSTRUCTION
3' - 0" 2' - 0" 3' - 0" 3' - 0" 3" FILLER2' - 0"1' - 5"2' - 10".1' - 0"1' - 0"4'-6".FRAME F1 FRAME F2
GLAZING LEGEND:
TG:1/4" FULLY TEMPERED FLOAT GLASS
FRG:45-MINUTE FIRE RESISTIVE GLAZING, SAFTI SUPERLITE II-XL 45
LG:LAMINATED GLASS WITH RED INTERLAYER (VANCEVA OC88)8"2' - 8"8"2' - 2"10"7' - 0"6" 2' - 0" 6"
DOOR D1
HOLLOW METAL DOORS AND FRAMES:
BASIS OF DESIGN FOR STILE AND RAIL DOORS -CURRIES 767 OR APPROVED EQUAL.
BASIS OF DESIGN FOR NON-RATED FLUSH DOORS -CURRIES 607 OR APPROVED EQUAL.
BASIS OF DESIGN FOR RATED FLUSH DOORS -CURRIES 727 OR APPROVED EQUAL.
•18 GAUGE MIN. DOOR
•3' WIDE AND UNDER: 16 GAUGE FRAMES
•OVER 3' WIDE: 14 GAUGE FRAMES
DOOR D2 DOOR D3 DOOR D4
TG TG
TG
FRG TG
1' - 8" 8" 8"8"2' - 10"3' - 6"7' - 0"DOOR D5
LG
1' - 0"
1' - 0"
1' - 0"
1' - 0"1' - 6"1' - 0"4' - 6"7' - 0"2' - 10"KICK PLATE1' - 0"2' - 0"4' - 0"7' - 0"INACTIVE LEAF. SEE PLAN
FOR CONFIGURATION4' - 0"2"x2" ETCHED GLASS MARKINGS
DOOR HARDWARE SETS
SET 1 -LAB ENTRY FROM CORRIDOR (WITH CARD READER):
(3) Hinges: McKinney T4A3786 x 4 1/2" x 4 1/2", NRP, US26D
(1) Mortise Lockset: Sargent M1-82271 x 24V x BIPS x B x 03 x LNL x US 26D
(1) Power Transfer Securitron EL-CEPT
(1) Cables McKinney QC-Cable x Door Width
(1) Cables QC-C1500P, 15'
(1) Closer Sargent 351 x P9 x EN
(1) Wall Bumpers DCI 3211T x US26D
(3) Silencers DCI 8S
SET 2 -LAB ENTRY FROM CORRIDOR (WITHOUT CARD READER):
(3) Hinges: McKinney T4A3786 x 4 1/2" x 4 1/2", NRP, US26D
(1) Mortise Lockset: Sargent 8205, LNL, US26D
(1) Closer Sargent 351 x P9 x EN
(1) Wall Bumpers DCI 3211T x US26D
(3) Silencers DCI 8S
SET 2A -LAB ENTRY FROM CORRIDOR (WITHOUT CARD READER, CLOSER ON PULL SIDE):
(3) Hinges: McKinney T4A3786 x 4 1/2" x 4 1/2", NRP, US26D
(1) Mortise Lockset: Sargent 8205, LNL, US26D
(1) Closer Sargent 351 x O x EN
(1) Wall Bumpers DCI 3211T x US26D
(3) Silencers DCI 8S
SET 3 -ANIMAL HOLDING ROOMS:
(6) Hinges: McKinney TA2714 x 4 1/2" x 4 1/2", NRP, US26D
(1) Mortise Lockset: Sargent 8205, LNL, US26D
(1) Sweep NGP, D608A
(2) Flush Bolt DCI 780F x US26D, incl. floor escutcheon
(2) Wall Bumper DCI 3211T x US26D
(6) Silencers DCI 8S
(1) Kickplate
SET 4 -LAB ROOMS FROM ANTEROOM:
(3) Hinges: McKinney TA2714 x 4 1/2" x 4 1/2", NRP, US26D
(1) Mortise Lockset: Sargent 8205, LNL, US26D
(1) Wall Bumpers DCI 3211T x US26D
(3) Silencers DCI 8S
SET 5 -LAB ROOMS FROM ANTEROOM (WITH OVERHEAD STOP):
(3) Hinges: McKinney TA2714 x 4 1/2" x 4 1/2", NRP, US26D
(1) Mortise Lockset: Sargent 8205, LNL, US26D
(1) Concealed Overhead Stop Sargent 1538S x US26D
(3) Silencers DCI 8S
SET 6 -OFFICES:
(3) Hinges: McKinney TA2714 x 4 1/2" x 4 1/2", NRP, US26D
(1) Mortise Lockset: Sargent 8205, LNL, US26D
(1) Wall Bumpers DCI 3211T x US26D
(3) Silencers DCI 8S
**ALTERNATE 1:
MATCH SCOPE OF WORK FOR CORRIDOR DOORS W154, W156, AND W161 TO SCOPE OF WORK
FOR DOOR W162 (NEW DOOR FRAME, NEW DOOR, NEW HARDWARE INCLUDING CARD
READER AND ASSOCIATED ELECTRICAL WORK) AS INDICATED ON DRAWINGS A-103 AND E-104
ENCLOSE EXISTING
DUCTWORK ON ATRIUM SIDE
WITH 2-HOUR FIRE-RATED
SHAFT WALL ASSEMBLY
(HORIZONTAL AND
VERTICAL) TO CONFIRM 2-
HOUR FIRE-RATED BARRIER.
COORDINATE LOCATION
WITH EXISTING DUCT AND
SUSPENDED CEILING.
REMOVE EXISTING
CEILING SYSTEM AS
REQUIRED TO INSTALL
DUCT ENCLOSURE.
REINSTALL AFTER
COMPLETION OF WORK.
5/8" GYPSUM WALL BOARD (BOTH
SIDES) -FINISH AS SCHEDULED
CONTINUOUS SEALANT
(ALL SIDES)
3 5/8" 18 GA. (DOUBLE) METAL STUDS AT JAMBS
ONLY. ALL OTHER STUDS TO BE 20 GA.
16 GA. HOLLOW METAL DOOR FRAME
FRAME ANCHOR
BORROWED LITE AS
SCHEDULED
5 7/8"2"SEE SCHEDULE
EXISTING WALL CONSTRUCTION
5/8" GYPSUM WALL BOARD (BOTH SIDES) -
FINISH AS SCHEDULED
CONTINUOUS SEALANT (ALL SIDES)
3 5/8" 20 GA. (DOUBLE) METAL STUDS
16 GA. HOLLOW METAL DOOR FRAME
FRAME ANCHOR
DOOR AND HARDWARE AS
SCHEDULED
5 7/8"2"SEE SCHEDULE
CREATE REVEAL TO MATCH ADJACENT
DOOR FRAME CONSTRUCTION
CONTINUOUS SEALANT (ALL SIDES)
16 GA. HOLLOW METAL DOOR FRAME
FRAME ANCHOR
DOOR AND HARDWARE AS
SCHEDULED
VIF.CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
LABORATORY
RENOVATIONS
A-103
12971596
INTERIOR
ELEVATIONS,
DETAILS, AND
DOOR SCHEDULE
N.HACHMANN
NH
1019W
12 MARCH 2021
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"6 INTERIOR ELEVATION - W156 EAST
SCALE:1/4" = 1'-0"5 INTERIOR ELEVATION - W156 WEST
SCALE:1/4" = 1'-0"2 INT. ELEVATION - W161 EAST
SCALE:1/4" = 1'-0"4 INT. ELEVATION - W161 ISLAND WORK STATION, TYP.
SCALE:1/4" = 1'-0"3 INT. ELEVATION - W161 WEST
SCALE:1/4" = 1'-0"1 INT. ELEVTION - W161 NORTH
SCALE:1/4" = 1'-0"
DOOR AND FRAME TYPES
DOOR / HARDWARE SCHEDULE
DOOR
To Room:
Name
DOOR
SLAB WIDTH,
ACTIVE LEAF
SLAB WIDTH,
PASSIVE LEAF
DOOR FRAME
FIRE RATINGGLAZING TYPEDOOR
HARDWA
RE SET
DETAILS
REMARKSHAND
PANEL SIZE
ELEVATION TYPEMATERIALFINISHELEVATION TYPEMATERIALFINISHJAMB (HEAD SIM.) THRESHOLDHEIGHTTHICKNESS
W154 CORRIDOR RHR 3' - 4" 0' - 0" 7' - 0" 1 3/4" D2 HM PT3/4 EXG HM PT3/4 45 Min. FRG 2 7/A-103** MTS SPLIT FINISH, **
W154A BEHAVIOR 1 RH 3' - 0" 0' - 0" 7' - 0" 1 3/4" D4 HM PT4 F1 HM PT4 - - TG 4 9/A-103 - -
W154B BEHAVIOR 2 RH 3' - 0" 0' - 0" 7' - 0" 1 3/4" D4 HM PT4 F1 HM PT4 - - TG 4 9/A-103 - -
W154C BEHAVIOR 3 LH 3' - 0" 0' - 0" 7' - 0" 1 3/4" D4 HM PT4 F1 HM PT4 - - TG 5 9/A-103 - -
W156 PROCEDURE LH 3' - 4" 0' - 0" 7' - 0" 1 3/4" D2 HM PT3/4 F1 HM PT3/4 45 Min. FRG 2A 7/A-103 MTS SPLIT FINISH, **
W161 CORRIDOR RHR 3' - 4" 0' - 0" 7' - 0" 1 3/4" D2 HM PT3/4 EXG HM PT3/4 45 Min. FRG 2 7/A-103** MTS SPLIT FINISH, **
W161A MEETING RH 3' - 0" 0' - 0" 7' - 0" 1 3/4" D3 WD CLEAR F2 HM PT4 - - TG 6 8/A-103 MTS
W161B OFFICE 2 LH 3' - 0" 0' - 0" 7' - 0" 1 3/4" D1 WD CLEAR F1 HM PT4 - - - - 6 9/A-103 - -
W161C OFFICE 1 RH 3' - 0" 0' - 0" 7' - 0" 1 3/4" D1 WD CLEAR F1 HM PT4 - - - - 6 9/A-103 - -
W162 CORRIDOR LHR 3' - 4" 0' - 0" 7' - 0" 1 3/4" D2 HM PT3/4 F1 HM PT3/4 45 Min. FRG 1 7/A-103 MTS SPLIT FINISH
W162A ANTEROOM RHR 3' - 0" 0' - 0" 7' - 0" 1 3/4" D4 HM PT4 F1 HM PT4 - - TG 4 9/A-103 MTS
W162B HOLDING 2 RH 3' - 0" 1' - 0" 7' - 0" 1 3/4" D5 HM PT4 F1 HM PT4 - - LG 3 9/A-103 MTS
W162C HOLDING 1 LH 3' - 0" 1' - 0" 7' - 0" 1 3/4" D5 HM PT4 F1 HM PT4 - - LG 3 9/A-103 MTS
W162D ANTEROOM RHR 3' - 0" 0' - 0" 7' - 0" 1 3/4" D4 HM PT4 F1 HM PT4 - - TG 4 9/A-103 MTS
W162E IMAGING LH 3' - 6" 0' - 0" 7' - 0" 1 3/4" D4 HM PT4 F1 HM PT4 - - TG 4 9/A-103 MTS
SS BEVELED FRAME, FASTEN TO
DOOR WITH SS FASTENERS
SS PANEL WITH
CONTINUOUS BOTTOM
LIP AND CONTINUOUS
TOP HINGE
HOLDING ROOM
VISION LITE PHOTOS
FOR INFORMATION ONLY
GLAZING TYPE LG
MAGNETIC HOLD AT FRAME
AND BACK OF PANEL
ANTEROOM
MAIN LAB
ANTEROOM
BEHAVIOR 4
BEHAVIOR 5
SCALE:1/2" = 1'-0"11 DUCT ENCLOSURE NEAR ATRIUM
1 01/15/2021 ISSUE FOR DD REVIEW
2 02/19/2021 ISSUE FOR 95% REVIEW
3 03/12/2021 ISSUE FOR CONSTRUCTION
SCALE:3" = 1'-0"9 HM JAMB DETAIL AT BORROWED LITE, HEAD SIMILAR
SCALE:3" = 1'-0"8 HM JAMB DETAIL, HEAD SIMILAR
SCALE:3" = 1'-0"7 HM JAMB DETAIL AT CORRIDOR, HEAD SIMILAR
SUBMITTAL REGISTRY
TITLE REQUIRED SUBMITTALS
07 84 13 - PENETRATION FIRESTOPPING PRODUCT DATA
07 92 00 - SEALANTS PAINTABLE AND MILDEW RESISTANT PRODUCT DATA
08 11 13 - HOLLOW METAL DOORS AND FRAMES PRODUCT DATA, SHOP DRAWINGS
08 14 16 - FLUSH WOOD DOORS PRODUCT DATA, SHOP DRAWINGS
08 71 00 - DOOR HARDWARE PRODUCT DATA
08 80 00 - GLAZING DOOR LITES (TEMPERED, FIRE-RESISTIVE, AND LAMINATED) PRODUCT DATA
09 22 16 - NON-STRUCTURAL METAL FRAMING PRODUCT DATA
09 29 00 - GYPSUM BOARD TYPE X AND AQUA TOUGH PRODUCT DATA
09 51 13 - ACOUSTIC PANEL CEILINGS PRODUCT DATA
09 65 13 - LINOLEUM FLOORING PRODUCT DATA, SAMPLES
09 65 13 - RESILIENT BASE AND ACCESSORIES PRODUCT DATA, SAMPLES
09 65 19 - RESILIENT TILE FLOORING LVT PRODUCT DATA, SAMPLES
09 67 23 - RESINOUS FLOORING PRODUCT DATA, SAMPLES
09 91 23 - INTERIOR PAINTING PRODUCT DATA, SAMPLES
10 20 00 - INTERIOR SPECIALTIES WALL BUMPERS, 8020 CEILING TRACK PRODUCT DATA
10 22 07 - LASER SAFETY CURTAINS PRODUCT DATA
12 24 13 - WINDOW SHADES PRODUCT DATA, SHOP DRAWINGS
12 35 53 - LABORATORY CASEWORK PRODUCT DATA, SHOP DRAWINGS
0' 1' 2' 4'
SCALE: 1/2"=1'-0"
0" 3" 6"
SCALE: 3"=1'-0"
FOR INFORMATION ONLYFOR INFORMATION ONLY
10
3' - 0" 2' - 0" 3' - 0" 3' - 0" 3" FILLER2' - 0"1' - 5"2' - 10".PROVIDE PEG BOARD
SCALE:1/4" = 1'-0"5 INTERIOR ELEVATION - W156 WEST
CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
FP-001
12971596
FIRE
PROTECTION
GENERAL
NOTES,
SYMBOLS, AND
SCHEDULES
T. JORDAN
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONFIRE PROTECTION GENERAL NOTES
1.0 IT IS THE INTENT OF THESE DRAWINGS TO PROVIDE MODIFICATIONS TO THE WET
PIPE FIRE PROTECTION SYSTEMS FOR THE PROTECTION OF THE SEELEY MUDD
FIRST FLOOR SPACES.
2.0 PRIOR TO ALTERATIONS, THE SPRINKLER CONTRACTOR SHALL FIELD VERIFY
EXTENT OF ALTERATION AND NEW WORK, WITH REGARD TO EXISTING CONDITIONS
AT PIPE PENETRATIONS THROUGH FLOORS, WALLS, CEILINGS AND SOFFITS.
3.0 ALL SPRINKLER COMPONENTS SHALL BE UNDERWRITER'S LABORATORIES (UL) AND
FACTORY MUTUAL (FM) APPROVED.
4.0 NEW SPRINKLER SYSTEM PIPING SHALL BE INSTALLED IN EXPOSED CEILING AREAS
AS SHOWN ON PLANS. PIPING AND HANGER ASSEMBLIES SHALL BE UN-PAINTED.
5.0 THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL
ARRANGEMENT OF THE ITEMS INCLUDED IN THE FIRE PROTECTION WORK. AS
SUCH, CONTRACTOR SHALL PROVIDE A COMPLETE SPRINKLER SYSTEM IN STRICT
ACCORDANCE WITH THE REQUIREMENTS OF FM GLOBAL STANDARDS, THE NFPA
13-INSTALLATION OF FIRE PROTECTION SYSTEMS, THE NEW YORK STATE BUILDING
CODES, THE NEW YORK STATE FIRE CODES, LOCAL CODES, AND GOVERNING
AUTHORITIES. THE DESIGN OF FIRE PROTECTION SYSTEMS TO WITHSTAND SEISMIC
EVENTS SHALL BE IN ACCORDANCE WITH THE CRITERIA DEVELOPED BY THE NFPA.
6.0 CONTRACTOR SHALL REQUEST SPRINKLER SYSTEM SHUTDOWNS THROUGH
CORNELL CUSTOMER SERVICE (607.255.5322) A MINIMUM OF TEN (10) DAYS PRIOR
TO THE SHUTDOWN DATE. THE CONTRACTOR SHALL BEAR THE COST OF THE
UTILITY SHUTDOWN. NOTIFY THE OWNER'S REPRESENTATIVE TO COORDINATE
BUILDING FUNCTIONS WITH THE BUILDING COORDINATOR.
7.0 COORDINATE THE EXACT LOCATION OF SPRINKLERS, EQUIPMENT, AND DEVICES
WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL AND ALL OTHER TRADES
DRAWINGS PRIOR TO ROUGH-IN AND INSTALLATION.
8.0 SPRINKLER PIPING SHALL BE ARRANGED TO DRAIN THROUGH THE MAIN DRAIN
VALVE WHENEVER PRACTICAL. ALL TRAPPED SECTIONS OF PIPE SHALL BE
PROVIDED WITH A DRAIN PER NFPA 13.
9.0 PENETRATIONS THROUGH WALL SHALL CONTAIN FIRE STOPPING WITH A FIRE
RATING EQUAL TO THAT OF THE AREA BEING PENETRATED.
10.0 SPRINKLER PIPING SHALL BE LABELED.
11.0 AFTER ALL WORK HAS BEEN COMPLETED, ACCEPTANCE TESTING SHALL BE
SCHEDULED THROUGH EH&S, AND SHALL BE WITNESSED BY EH&S AND CITY OF
ITHACA REPRESENTATIVES.
12.0 HYDROSTATIC TEST SHALL BE PERFORMED AT SYSTEM PRESSURE FOR A PERIOD
OF 2-HOURS. A REPRESENTATIVE OF ENVIRONMENTAL HEALTH AND SAFETY SHALL
WITNESS HYDROSTATIC TESTING OF THE NEW PIPING INSTALLATIONS AND
ALTERATIONS. THE AUTHORITY HAVING JURISDICTION (ITHACA FIRE DEPARTMENT)
REQUIRES THAT ONE OF THEIR REPRESENTATIVES WITNESSES HYDROSTATIC
TESTING. ADVANCE NOTICE AND SCHEDULING IS REQUIRED THROUGH EH&S.
13.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING.
14.0 IF ANY PORTION OF THE SPRINKLER SYSTEM WILL BE OUT OF SERVICE FOR MORE
THAN ONE WORKDAY, PROVIDE TEMPORARY HEAT DETECTORS IN THE AFFECTED
ROOMS. AFTER INSTALLATION AND INTEGRATION INTO EXISTING FIRE ALARM
SYSTEM, DETECTORS WILL NEED TO BE TESTED AND WITNESSED BY CORNELL
EH&S BEFORE CONSTRUCTION CAN COMMENCE. THIS DIRECTIVE IS BEING MADE
BASED ON THE UNDERSTANDING THAT THE SPRINKLER SYSTEM SERVING THE
REST OF THE ZONE (FLOOR) WILL BE PUT BACK INTO SERVICE AT THE END OF
EACH WORKDAY.
FIRE PROTECTION SCOPE OF WORK
1.0 MODIFY PORTIONS OF THE EXISTING WET-PIPE SPRINKLER SYSTEM PIPING AS
REQUIRED TO COMPLIMENT ARCHITECTURAL MODIFICATIONS
2.0 PROVIDE ACCEPTANCE TESTING OF THE NEW PIPING SYSTEM.
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
SPECS:
1.GROOVED-END COUPLING GASKETS EMPLOYED ON DRY SYSTEMS SHALL BE SPECIFIC TO DRY-PIPE SYSTEMS
2.INSTALL FIRE PROTECTION SYSTEMS TO FACILITATE SERVICE, MAINTENANCE AND REPAIR OR REPLACEMENT OF COMPONENTS.
3.ALL FIRE PROTECTION PIPING SHALL BE PITCHED BACK TOWARDS THE SOURCE AT 1/4 INCH PER 10 FOOT TO FACILITATE MAINTENANCE/DRAINING OF THE SYSTEM.
4.PROVIDE PIPE LABELS AND DIRECTIONAL ARROWS ON ALL NEW PIPING SYSTEMS. LABELS SHALL BE PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT ADHESIVE
BACKING.
5.PIPING SUPPORTS:
INSTALLATION IN ATTIC -SUPPORT PIPING FROM EXISTING STRUCTURE WITH 1/8" THREADED ROD, AND CLEVIS HANGER
FIRE PROTECTION PIPING SCHEDULE
PIPE SERVICE ABBREVIATION PIPE SIZE MATERIAL FITTINGS
WET SPRINKLER WSP ALL SIZES ASTM A 53 TYPE F STEEL, TYPE F, SCHEDULE 40 BLACK, GRADE A CAST OR MALLEABLE IRON THREADED OR DUCTILE IRON GROOVED
SPRINKLER SCHEDULE
SPRINKLER TYPE SERVES MANF BOD MODEL BOD (SIN) RESPONSE
ORIFICE
(IN)K-FACTOR
TEMPERATURE
RATING (DEG F)CONSTRUCTION FINISH ESCUTCHEON
SEMI-RECESSED PENDENT W343, W347 SUITE, W351 RELIABLE F1FR56 (RA1414) QUICK 1/2 5.6 155 BRASS CHROME F1 - CHROME
W162
W162A
W162B
W164
W154B
W154C
W154W154A
W161
W159W157
W157A
W153B
W100C
1
1
1
11
11
11
1
1 1
1
1 1
1 1
1 1
1
1
1 1
1
1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)
3" (E)3" (E)3" (E)CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
FP-101
12971596
FIRE
PROTECTION
DEMOLITION
PLAN
T. JORDAN
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONSCALE:1/4" = 1'-0"1 FIRST FLOOR - FIRE PROTECTION DEMOLITION PLAN
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
FP-101 KEYED DEMOLITION NOTES
1 REMOVE SPRINKLER AND PIPING BACK TO BRANCH TEE.
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
MAIN LAB
W161
MEETING
W161A
OFFICE 2
W161BOFFICE 1
W161C
IMAGING
W162E
ANTEROOM
W162
BEHAVIOR 5
W162D
BEHAVIOR 4
W162A
HOLDING 2
W162B
HOLDING 1
W162C
PROCEDURE
W156
BEHAVIOR 3
W154C
BEHAVIOR 2
W154B
ANTEROOM
W154BEHAVIOR 1
W154A
3" (E)3" (E)3" (E)
11
1
1
11
1
1
1
1
11
1
1
1
1
1
1
1
11
1
1
1
1 1 1
1
1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)1 1/4" (E)
1 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
FP-102
12971596
FIRE
PROTECTION
NEW WORK PLAN
T. JORDAN
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTION1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
FP-102 KEYED RENOVATION NOTES
1
PROVIDE NEW SPRINKLER WITH ARM-OVER. COORDINATE EXACT LOCATIONS WITH
NEW LAY-IN CEILING. DISASSEMBLE TEE AND INSTALL NEW TEE WITH OUTLET IN
VERTICAL POSITION.
SCALE:1/4" = 1'-0"1 FIRST FLOOR -FIRE PROTECTION NEW WORK PLAN
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
EXTERIOR ELEVATION
1
X-100
X-100
1
1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE
DRAWING REVISION NOTE
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
#
#
#
1
1
1
11 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
P-001
12971596
GENERAL
NOTES, SYMBOL
LEGENDS, &
SCHEDULES
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONPLUMBING SUBMITTAL SCHEDULE
SECTION REQUIRED MATERIAL SHOP DRAWINGSCOORDINATION DRAWINGSAS BUILT DRAWINGSPRODUCT DATAMANUFACTURER'S INSTRUCTIONSINSPECTION & TEST REPORTSOPERATION & MAINTENANCE DATAWARRANTIES & BONDS220523 GENERAL DUTY VALVES FOR PLUMBING BALL VALVES X X X
220719 PLUMBING PIPING INSULATION PIPING INSULATION X
221000 PLUMBING PIPING SYSTEMS PIPES, TUBES, FITTINGS X X X X
221000 PLUMBING PIPING SYSTEMS JOINING MATERIALS X
221000 PLUMBING PIPING SYSTEMS SPECIALTIES X X X
224500 PLUMBING FIXTURES SINKS / FAUCETS X X X X
224500 PLUMBING FIXTURES EYEWASHES X X X X X
224500 PLUMBING FIXTURES THERMOSTATIC MIXING VALVES X X X X
PLUMBING SCOPE OF WORK
1.0 SELECTIVE DEMOLITION OF EXISTING DOMESTIC HOT/COLD WATER, COMPRESSED
AIR, LAB DRAIN/VENT, AND RODI PIPING SYSTEMS.
2.0. EXTEND EXISTING DECHLORINATED WATER TO ANTE ROOM W162 SINK.
3.0 EXTEND RODI WATER TO PROCEDURE ROOM W156 SINK.
4.0 PROVIDE SINKS IN W156 AND W162. EXTEND DOMESTIC HOT/COLD WATER AND
CONNECT TO EXISTING LAB WASTE/VENT SYSTEM.
5.0 EMERGENCY FIXTURES: PROVIDE SWING-AWAY EYEWASHES WITH TEMPERING
MIXING VALVES AT SINKS IN W156 AND W162. EXISTING EMERGENCY SHOWER
LOCATED OUTSIDE W154 IS TO REMAIN.
6.0 COMPRESSED AIR SERVICE IS TO BE EXTENDED INTO BEHAVIOR ROOMS,
PROCEDURE ROOM AND IMAGING ROOM.
7.0 VACUUM IS TO BE PROVIDED BY THE RESEARCH GROUP WHERE NEEDED WITH THE
USE OF SMALL BENCHTOP VACUUM PUMPS.
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
PLUMBING FIXTURE SCHEDULE & SPEC
TAG DESCRIPTION
BASIS OF DESIGN COLD
WATER
HOT
WATER
TEMPERED
WATER RODI DCLW CA
LAB
WASTE VENT NOTESMANUFACTURZER MODEL
SK-1 SINK DURCON A07 1/2" 1/2" 1/2" 1/2" - - 1-1/4" 1-1/4" ADA, EPOXY RESIN, WITH DURCON SO3R POLYPROPYLENE SINK OUTLET AND REMOVABLE DISC STRAINER
SK-2 SINK ELKAY ELV1817 - - - - - - 1-1/4" 1-1/4" ADA, WALL MOUNT, 18 GA 304 STAINLESS STEEL, 8" CENTERS
F-1 MIXING FAUCET WATERSAVER L412-8VB-BH 1/2" 1/2" - - - - - ADA, DECK-MOUNT, 8" RIGID/SWING, SINGLE FAUCET, VACUUM BREAKER, BLADE HANDLES
F-2 PURE WATER FAUCET WATERSAVER
L7853SC-VB-8-LH-
BH - - - 1/2" - - - -
ADA, DECK-MOUNT SINGLE FAUCET, 8" RIGID GOOSENECK, VACUUM BREAKER, BLADE HANDLES, SELF CLOSING, LEFT HAND, LINED WITH
POLYPROPYLENE, SERRATED PLASTIC HOSE END
F-3 DECHLORINATED WATER
FACUCET WATERSAVER L7854SC-VB-8-LH-
BH - - - - 1/2" - - -
ADA, PANEL-MOUNT SINGLE FAUCET, 8" RIGID GOOSENECK, VACUUM BREAKER, BLADE HANDLES, SELF CLOSING, LEFT HAND, LINED WITH
POLYPROPYLENE, SERRATED PLASTIC HOSE END
CA-1 COMPRESSED AIR OUTLET WATERSAVER L4200-141FT - - - - -1/2" - - ADA, WALL-MOUNT, LABORATORY BALL VALVE ASSEMBLE, DOUBLE OUTLET AT 90 DEGREE, FLOATING ESCUTCHEON, LEVER HANDLE.
EW-1 EYE WASH WITH
THERMOSTATIC MIXING VALVE WATERSAVER EW805 + AP3600 1/2" 1/2" 1/2" - - - - -
ANSI Z358.1, CHROME-PLATED DECK-MOUNT SWING-OUT EYEWASH, AUTO-FLOW; SWEAT FEMALE HOT AND COLD WATER INLETS, EACH
WITH A CHECK VALVE AND SUPPLY STOP
EW-2 EYE WASH WITH
THERMOSTATIC MIXING VALVE WATERSAVER EW891-T + AP3600 1/2" 1/2" 1/2" - - - 1-1/4" 1-1/4"ANSI Z358.1, STAINLESS STEEL WALL-MOUNT EYEWASH WITH CHROME PLATED BARASS TAILPIECE AND TRAP. MIXING VALVE - SWEAT
FEMALE HOT AND COLD WATER INLETS, EACH WITH A CHECK VALVE AND SUPPLY STOP
NOTES
1) FOR VALVES INSTALLED IN INSULATED PIPING SYSTEMS, PROVIDE EXTENDED HANDLE
2) PROVIDE VALVES WITH UNIONS AT EACH PIECE OF EQUIPMENT ARRANGED TO ALLOW SERVICE, MAINTENANCE AND EQUIPMENT REMOVAL WITHOUT SYSTEM
SHUTDOWN
3) PROVIDE PRESSURE/TEMPERATURE TEST PORTS AT ALL COILS, AND WHERE INDICATED
4) PROVIDE UNIONS ADJACENT TO VALVES AND AT FINAL EQUIPMENT CONNECTIONS.
5) BEFORE PLACING SYSTEM IN SERVICE, REMOVE MESH FROM ALL STRAINERS, CLEAN MESH AND FLUSH SYSTEM, RE-INSTALL AFTER FINAL FLUSHING.
6) PROVIDE STRAINERS AT INLET OF CONTROL VALVES, AND WHERE INDICATED. INSTALL NIPPLE AND BALL VALVE IN BLOWDOWN CONNECTION.
7) PROVIDE MANUAL AIR VENTS AT HIGH POINTS IN PIPING SYSTEM, HEAT TRANSFER COILS, AND ELSEWHERE AS REQUIRED FOR SYSTEM AIR VENTING.
8) PROVIDE DRAIN VALVES AT MAIN SHUT-OFF VALVES, LOW POINTS OF PIPING SYSTEM, AND ELSEWHERE AS REQUIRED FOR SYSTEM DRAINING.
PLUMBING PIPING ACCESSORIES SCHEDULE
TAG COMPONENT
BASIS OF DESIGN PRESSURE
RATING SPECIFICATIONMANF MODEL
PV-1 BALL VALVE, COMPRESSED AIR
WATTS
APOLLO
NIBCO
B6000-SS or B6001-SS
70-140 or 70-240
T-580-70-66 or S-580-70-66
300 PSIG @ 250 ˚F
300 PSIG WOG
150 PSIG SWP
MSS SP-110, 2-PIECE, STANDARD PORT, BRONZE BODY, 316
SS BALL & STEM, PTFE OR TFE SEAT
PV-2 BALL VALVE, DCW/DHW/DCLW
NPS 1/2 - 2 INCH
WATTS
APOLLO
NIBCO
LFB6000-SS or LFB6001-SS
70LF-140 or 70LF-240
T-580-66-LF or S-580-66-LF
300 PSIG @ 250 ˚F
300 PSIG WOG
150 PSIG SWP
MSS SP-110, NSF 61 FOR POTABLE WATER SERVICE,
2-PIECE, STANDARD PORT, BRONZE BODY, 316 SS BALL &
STEM, PTFE OR TFE SEAT
PV-3 BALL VALVE, PURE WATER HAYWARD TB SERIES 125 PSIG @ 73 ˚F ASTM D1784, MSS SP-122, UNION TYPE WITH SOCKET ENDS
FCO LAB WASTE FLOOR CLEANOUT ZURN C01-PB - ADJUSTABLE CLEANOUT, PVC
TP-1 TRAP PRIMER WATTS LFTP300 125 PSIG ASTM D1784, MSS SP-122, UNION TYPE WITH SOCKET ENDS
SPECS
1) DIELECTRIC FITTINGS: USE FLANGES OR COUPLINGS. UNIONS ARE UNACCEPTABLE
2) INSTALL ESCUTCHEONS FOR PENETRATIONS OF WALLS, CEILING, AND FLOORS
3) INSTALL SLEEVES FOR PIPES PASSING THROUGH CONCRETE AND MASONRY WALLS, GYPSUM-BOARD PARTITIONS, AND CONCRETE FLOOR AND ROOF SLABS.
4) INSTALL PLUMBING SYSTEMS TO FACILITATE SERVICE, MAINTENANCE AND REPAIR OR REPLACEMENT OF COMPONENTS.
5) ALL WASTE PIPING SHALL BE PITCHED AT 1/8" PER FOOT. ALL SUPPLY PIPING SHALL BE PITCHED BACK TOWARDS CONNECTION TO THE ROOM ENTRANCE
6) PROVIDE VAPOR RETARDER ON PIPING INSULATION SYSTEMS CARRYING FLUIDS WITH AN OPERATING TEMPERATURE LOWER THAN 60 DEGREES F
7) POLYPROPYLENE PIPING SHALL BE FLAME RETARDANT
8) ALL PIPING AND INSULATION SYSTEM EXPOSED TO VIEW SHALL BE PAINTED TO MATCH SURROUNDING SURFACES
JACKETING IN HIGH TRAFFIC AREAS AND ALL EXPOSED PIPING BELOW 8 FEET SHALL BE ALUMINUM OR PVC
9) MAINTAIN INDICATED FIRE RATING OF WALLS, PARITIONS, CEILINGS, AND FLOORS AT PIPE PENETRATIONS. SEAL PIPE PENETRATIONS WITH FM APPROVED FIRESTOP MATERIALS
10) DO NOT ENCLOSE, COVER OR PUT PLUMBING PIPING SYSTEMS INTO OPERATION UNTIL IT HAS BEEN INSPECTED AND APPROVED BY THE AUTHORITIES HAVING JURISDICTION.
11) LEAVE NEW, ALTERED, EXTENDED, OR REPLACED DOMESTIC WATER PIPING UNCOVERED AND UNCONCEALED UNTIL IT HAS BEEN TESTED.
EXPOSE WORK THAT WAS COVERED OR CONCEALED BEFORE IT WAS TESTED.
12) ROVIDE PIPE LABLES AND DIRECTIONAL ARROWS ON ALL NEW PIPING SYSTEMS. LABELS SHALL BE PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT ADHESIVE BACKING.
13) ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
TYPE A INSULATION: PRE-FORMED MINERAL FIBERGLASS, ASTM C547 TYPE I, ASTM C1136 FACTORY APPLIED SELF-SEALING ALL SERVICE JACKET.
14) TESTING OF DOMESTIC WATER PIPING:
CAP AND SUBJECT DOMESTIC WATER PIPING TO STATIC WATER PRESSURE OF 50 PSIG ABOVE OPERATING PRESSURE, WITHOUT EXCEEDING PRESSURE RATING OF PIPING SYSTEM MATERIALS
ISOLATE TEST SOURCE AND ALLOW TO STAND FOR FOUR HOURS. LEAKS AND LOSS IN TEST PRESSURE CONSTITUTE DEFECTS THAT MUST BE REPAIRED
REPAIR LEAKS AND DEFECTS WITH NEW MATERIALS AND RETEST PIPING UNTIL SATISFACTORY RESULTS ARE OBTAINED.
15) TESTING OF DOMESTIC WASTE AND VENT PIPING:
CAP AND SUBJECT DOMESTIC WATER PIPING TO STATIC WATER PRESSURE OF 10 FEET HEAD PRESSURE ABOVE HIGHEST POINT OF SYSTEM UNDERGOING TEST
ISOLATE TEST SOURCE AND ALLOW TO STAND UNTIL SYSTEM CAN BE VISUALLY INSPECTED BY AUTHORITY HAVING JURISDICTION. LEAKS CONSTITUTE DEFECTS THAT MUST BE REPAIRED
REPAIR LEAKS AND DEFECTS WITH NEW MATERIALS AND RETEST PIPING UNTIL SATISFACTORY RESULTS ARE OBTAINED.
16) CLEANING AND DISINFECTION OF POTABLE WATER SYSTEMS:
FLUSH PIPING SYSTEM WITH CLEAN, POTABLE WATER UNTIL DIRTY WATER DOES NOT APPEAR AT OUTLETS
FILL SYSTEM WITH WATER/CHLORINE SOLUTION WITH AT LEAST 50 PPM OF CHLORINE. ISOLATE WITH VALVES AND ALLOW TO STAND FOR 24 HOURS. DRAIN TO SANITARY.
FLUSH SYSTEM WITH CLEAN, POTABLE WATER UNTIL NO TSP REMAINS IN WATER COMING FROM SYSTEM.
SUBMIT WATER SAMPLES IN STERILE BOTTLES TO AUTHORITIES HAVING JURISDICTION. REPEAT PROCEDURE IF BIOLOGICAL EXAMINATION SHOWS EVIDENCE OF CONTAMINATION.
17) CLEANING AND DISINFECTION OF PURE WATER SYSTEMS:
PIPING SHALL BE DISINFECTED PRIOR TO INSTALLATION. PIPING SHALL BE INSTALLED WITHIN ONE WEEK OF DISINFECTION, OTHERWISE PROCEDURE SHALL BE REPEATED.
MIX 1 PART HYDROGEN PEROXIDE (30% CONCENTRATION) WITH 6 PARTS RODI WATER IN 55 GALLON DRUM. THIS SHOULD YIELD A 5% HYROGEN PEROXIDE SOLUTION.
PREPARE SUFFICIENT QUANTITY TO FILL ADDITIONS TO THE PIPING SYSTEM.
FILL THE PIPING WITH THE HYDROGEN PEROXIDE SOLUTION USING SMALL PUMP. KEEP SOLUTION IN PIPING SYSTEM FOR FOUR HOURS. DRAIN TO SANITARY.
BLOW DRY PIPING SYSTEM WITH HIGH PURITY NITROGEN AND WIPE WITH LINT FREE WIPES.
ONE PIPING IS INSTALLED, FLUSH PIPING SYSTEM WITH RODI WATER.
18) CLEANING AND PROTECTION OF DOMESTIC WASTE AND VENT PIPING
CLEAN INTERIOR OF PIPING SYSTEM. REMOVE DIRT AND DEBRIS AS WORK PROGRESSES
PROTECT DRAINS DURING CONSTRUCTION PERIOD TO AVOID CLOGGING WITH DIRT AND DEBRIS AND TO PREVENT DAMAGE FROM TRAFFIC AND CONSTRUCTION WORK
PLACE PLUGS IN ENDS OF UNCOMPLETED PIPING AT END OF DAY AND WHEN WORK STOPS
PLUMBING PIPING SCHEDULE
PIPE SERVICE ABBREVIATION PIPE SIZE MATERIAL FITTING JOINT
INSULATION
THICKNESS
(IN)
CONDUCTIVITY
(BTU-IN/HR-FT²-˚F)
MEAN TEMP
(°F)MATERIAL
DOMESTIC COLD WATER DCW 1-1/4" & BELOW
ASTM B88
TYPE L COPPER
ASTM B16.22 STD
WROUGHT COPPER
ASTM B32 SOLDER,
LEAD FREE 1 0.21 - 0.27 75 A
DOMESTIC HOT WATER DHW 1-1/4" & BELOW
ASTM B88
TYPE L COPPER
ASTM B16.22 STD
WROUGHT COPPER
ASTM B32 SOLDER,
LEAD FREE 1 0.22 - 0.28 100 A
LAB WASTE & VENT LW / LWV ALL SIZES
ASTM D4101 ASTM D635
POLYPROPYLENE,
SCH 40
ASTM D4101
POLYPROPYLENE MECHANICAL N/A N/A N/A N/A
PURE WATER RO, DI, RODI ALL SIZES
ASTM F441, CPVC, SCH
80 ASTM F439 SOCKET TYPE SOCKET N/A N/A N/A N/A
COMPRESSED AIR CA 2" & SMALLER
ASTM B88
TYPE L COPPER
ASTM B16.22 STD
WROUGHT COPPER
ASTM B32 SOLDER,
LEAD FREE N/A N/A N/A N/A
DECHLORINATED WATER DCLW 1-1/4" & BELOW
ASTM B88
TYPE L COPPER
ASTM B16.22 STD
WROUGHT COPPER
ASTM B32 SOLDER,
LEAD FREE 1 0.21 - 0.27 75 A
PLUMBING GENERAL NOTES
1.0 FIRESTOPPING: THE CONTRACTOR IS TO PROVIDE THROUGH FIRESTOP SYSTEMS
WITH A FIRE RATING OF 1-HOUR AT ALL EXISTING AND NEW CORRIDOR WALL
PIPING PENETRATIONS WITHIN THE PROJECT AREA, WHETHER OR NOT SAID
PENETRATIONS WERE MADE BY THE PROJECT CONSTRUCTION TEAM.
2.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN REQUIRED FIRE RATING.
3.0 DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT
OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. CONTRACTOR SHALL
FIELD VERIFY ALL DIMENSIONS. IF DIMENSIONS OR CONDITIONS ARE FOUND
TO BE IN CONFLICT WITH THE DRAWINGS, THE CONTRACTOR SHALL
IMMEDIATELY REFER THE CONFLICT TO THE ENGINEER.
4.0 UTILITY SHUTDOWNS: SHUTDOWN OF ANY BUILDING UTILITY SYSTEM SHALL BE
COORDINATED WITH CORNELL’S PROJECT MANAGER. THE CONTRACTOR SHALL
BEAR THE COST OF THE UTILITY SHUTDOWN. SCHEDULE WORK TEN DAYS IN
ADVANCE AND NOTIFY THE OWNER'S REPRESENTATIVE TO COORDINATE BUILDING
FUNCTIONS WITH THE BUILDING COORDINATOR.
5.0 ALL PENETRATIONS THROUGH FULL HEIGHT WALLS ARE TO BE FIRESTOPPED
IN ACCORDANCE WITH UL STANDARDS. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS ARE TO BE FIRE AND SMOKE STOPPED. CAPS
AND JOINTS INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR
ROOF DECK, WALL TO BEAMS, AND CONTROL OR EXPANSION JOINTS.
FIRESTOPPING INCLUDES BOTH FORM OR PACKING MATERIAL AND THE FILL,
VOID OR CAVITY MATERIAL.
6.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS AND WITH SUFFICIENT SPACE TO
PERFORM ROUTINE MAINTENANCE AND
REPAIR. EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN
MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL
DEFICIENCIES ARE CORRECTED.
7.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION,
FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK
REQUIRED AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER
TO ACCESS SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE
UNIVERSITY.
8.0 VERIFY FINAL EQUIPMENT/FIXTURE LOCATIONS FOR ROUGHING-IN.
9.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING.
10.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING
CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR
DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH
MATERIALS TO MATCH FINISHED AREAS.
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
W162
W162A
W162B
W164
W154B
W154C
W154
W154A
W161
W159
W157
W157A
W153B
W100C
1
3
1
1
1
2" DCW
1 1/4" DHW
3/4" DHWR
1" CA
3/4" G
1 1/2" DI
1" DIR
EXISTING
EMERGENCY
EYEWASH
2" DCW
1 1/4" DHW
3/4" DHWR
1" CA
3/4" G
1 1/2" DI
1" DIR
2" DCW
1 1/4" DHW
3/4" DHWR
1" CA
3/4" G
1 1/2" DI
1" DIR
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"3/4"3/4"3/4"
3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"
3/4"2 1/2" DCW
1 1/4" DHW
3/4" DHWR2" DCW2" DHW3/4" DHWR1" CA3/4" G1 1/2" DI1" DIR5
5
1
1
1
2
4
2
LAB WASTE
CLEAN OUT
(TYPICAL)
LAB WASTE
CLEAN OUT
(TYPICAL)
6" LW
4" LWV
6" ROOF DRAIN
6" LW
4" LWV
6" ROOF DRAIN CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
P-101
12971596
PLUMBING
DEMOLITION
PLAN
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONSCALE:1/4" = 1'-0"1 FIRST FLOOR - PLUMBING DEMOLITION PLAN
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
P-101 KEYED DEMOLITION NOTES
1 REMOVE ALL PLUMING AND LAB GAS PIPING SERVING SINKS AND LAB BENCHES.
REMOVE SINKS IF NOT INTEGRAL WITH COUNTER.
2 REMOVE ALL PLUMING PIPING SERVING SINK. REMOVE SANITARY WASTE PIPING
BACK TO RISER AND PREPARE TO SERVE AS INDIRECT WASTE.
3 REMOVE ALL PLUMING SERVING SINK. PREPARE LAB WASTE PIPING FOR
RECONNECTION.
4 REMOVE ALL PLUMING AND LAB GAS PIPING SERVING FUME HOOD.
5 TERMINATE WITH ISOLATION VALVE AND CAP.
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
GENERAL NOTES
1.0 ALL EXISTING PLUMBING SERVICES IN THE RENOVATION AREA WILL BE REMOVED
BACK TO MAIN AND CAPPED OR EXTENDED AS NEEDED.
-DOMESTIC COLD WATER
-DOMESTIC HOT WATER
-COMPRESSED AIR
-GAS
-DEIONIZED WATER
-LAB DRAIN
-LAB VENT
2.0 NOTIFY THE CORNELL PROJECT MANAGER IF ANY UTILITIES EXIT OUT OF THE
RENOVATION AREA TO SERVE OTHER LAB SPACES.
3.0 LAB WASTE PIPING PASSING THROUGH THE FLOOR SHALL BE TERMINATED WITH
CLEANOUTS, UNLESS NOTED OTHERWISE.
MAIN LAB
W161
MEETING
W161A
OFFICE 2
W161BOFFICE 1
W161C
IMAGING
W162E
ANTEROOM
W162
BEHAVIOR 5
W162D
BEHAVIOR 4
W162A
HOLDING 2
W162B
HOLDING 1
W162C
PROCEDURE
W156
BEHAVIOR 3
W154C
BEHAVIOR 2
W154B
ANTEROOM
W154
BEHAVIOR 1
W154A
1
1/2" DE-CL W
2" DCW2" DHW3/4" DHWR1" CA3/4" G1 1/2" DI1" DIR2" DCW
1 1/4" DHW
3/4" DHWR
1" CA
3/4" G
1 1/2" DI
1" DIR
2" DCW 1 1/4" DHW
3/4" DHWR
1" CA
3/4" G
1 1/2" DI
1" DIR
W102
SK-2
F-1
F-3
CA-1
CA-1
1/2" CA1/2" CA
CA-1
SK-1
F-1
EW-1
F-2
CA-1
CA-11/2" CACA-1
CA-1
1/2" CA
CA-1
CA-1
EYEWASH
MIXING VALVE
ABOVE CEILING
EXISTING
EMERGENCY
EYEWASH
FCO
(TYP OF 6)
FCO
(TYP OF 3)
FCO
FCO
FCO
(TYP OF 3)FCO
FCO
6" LW
4" LWV
6" ROOF DRAIN
6" LW
4" LWV
6" ROOF DRAIN
EW-2
2" LW
RUN IN WALL
2 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
P-102
12971596
PLUMBING NEW
WORK PLAN
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONSCALE:1/4" = 1'-0"1 FIRST FLOOR - PLUMBING NEW WORK PLAN
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
P-102 KEYED RENOVATION NOTES
1 NEW 3/4” DECHLORINATED WATER LINE. TIE INTO 3/4” DECHLORINATED MAIN
LOCATE ABOVE THE CEILING IN ROOM W102. APPROXIMATELY 25'-0" AWAY.
2 PROVIDE INDIRECT DRAIN FUNNEL WITH P-TRAP AND TRAP PRIMER. COORDINATE
LOCATION WITH MECHANICAL CONTRACTOR. LOCATE WITHING SINK CASEWORK.
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
COMPRESSED AIR
GENERAL NOTES
1.0 COORDINATE WALL MOUNTED COMPRESSED AIR TURRETS (CA-1) LOCATIONS
WITH LAB OWNER.
EXTERIOR ELEVATION
1
X-100
X-100
1
1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE
DRAWING REVISION NOTE
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
#
#
#
1
1
1
11 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-001
12971596
MECHANICAL
GENERAL NOTES
AND SYMBOL
LEGENDS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONMECHANICAL ABBREVIATIONS
BCU BLOWER COIL UNIT
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CC CLEAN CONDENSATE
CO CLEAN OUT
CS CLEAN STEAM
CD CONDENSATE DRAIN
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
FD FIRE DAMPER
GWR GLYCOL HEATING RETURN
GWS GLYCOL HEATING SUPPLY
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HWR HOT WATER HEATING RETURN
HWS HOT WATER HEATING SUPPLY
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
MU MAKE UP WATER
MPC MEDIUM PRESSURE CONDENSATE
MPS MEDIUM PRESSURE STEAM
NG NATURAL GAS
PCWR PROCESS CHILLED WATER RETURN
PCWS PROCESS CHILLED WATER SUPPLY
HG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RAG RETURN AIR GRILLE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
VD VOLUME DAMPER
MECHANICAL SYMBOLOGY
AIRFLOW
BACKFLOW PREVENTER
BALANCE VALVE
BALL VALVE
BOTTOM PIPE CONNECTION
BUTTERFLY VALVE
CAP OR PLUG
CHECK VALVE
CIRCULATING PUMP
DIRECTION OF FLOW
DUCT AIRFLOW
DUCT DOWN (EXHAUST OR RETURN)
DUCT DOWN (SUPPLY)
FIRE AND SMOKE DAMPER IN DUCT
FIRE DAMPER IN DUCT
FLANGE CONNECTION
FLEX CONNECTOR
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FLOW METER
FLOW SWITCH
FUSIBLE LINK VALVE
GLOBE VALVE
MANUAL AIRVENT
ORIFICE METER
PIPE DOWN
PIPE UP
PIPING REDUCER (CONCENTRIC)
PIPING REDUCER (ECCENTRIC)
PRESSURE GAUGE
PRESSURE OR TEMPERATURE PETES PLUG
PRESSURE REDUCING VALVE
PRESSURE SWITCH
RECTANGULAR ELBOW
RECTANGULAR ELBOW WITH TURNING VANES
RELIEF VALVE
SMOKE DAMPER IN DUCT
SOLENOID VALVE
STANDARD BRANCH DUCT
STEAM TRAP
STRAINER (DUPLEX)
STRAINER WITH BLOWDOWN VALVE AND CAP
SUPPLY THROUGH NEXT FLOOR OR ROOF
TEMPERATURE WELL
THERMOMETER
THERMOMETER (DIAL)
TOP PIPE CONNECTION
TRIPLE DUTY VALVE
UNION CONNECTION
VACUUM BREAKER
VOLUME DAMPER IN DUCT
CONTROL SYMBOLOGY
2-WAY CONTROL VALVE, DIGITAL
2-WAY CONTROL VALVE, PNEUMATIC
3-WAY CONTROL VALVE, DIGITAL
3-WAY CONTROL VALVE, PNEUMATIC
ADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE)
AIRFLOW CONTROL VALVE (VENTURI OR VORTEX SHEDDING)
AVERAGING SENSOR
BINARY POINT
BUTTERFLY CONTROL DAMPER
CARBON DIOXIDE SENSOR
CONDENSATE SENSOR
CURRENT SENSOR
DEW-POINT SENSOR
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
ELECTRIC TO PNEUMATIC SWITCH
ELECTRIC TO PNEUMATIC TRANSDUCER
END SWITCH
FLOW ELEMENT (METER)
FLOW SENSOR
HIGH LEVEL SWITCH
HUMIDSTAT SENSOR
LIQUID IMERSION TEMPERATURE SENSOR
LOW LEVEL SWITCH
MODULATING
MOTOR
MOTOR STARTER
NETWORK COMMUNICATION POINT, BACnet MSTP
OCCUPANCY SENSOR
OPEN/CLOSE
OPPOSED BLADE CONTROL DAMPER
PARALLEL BLADE CONTROL DAMPER
PNEUMATIC THERMOSTAT
PRESSURE SENSOR
PRESSURE SWITCH
RELATIVE HUMIDITY SENSOR
RELAY
ROOM TEMPERATURE SENSOR WITH ADJUSTABLE
THERMOSTAT
ROOM TEMPERATURE SENSOR WITH OCCUPANCY
OVERRIDE
ROOM TEMPERATURE SENSOR WITH ON/OFF SWITCH
ROOM TEMPERATURE SENSOR WITH VISUAL DISPLAY
ROTATION DETECTOR
SINGLE POINT SENSOR
SMOKE DETECTOR
SPEED COMMAND
START/STOP
STATIC PRESSURE SENSOR
SWITCH
TEMPERATURE SENSOR
TEMPERATURE SENSOR
TEMPERATURE SENSOR WITH ADJUSTABLE SETPOINT
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
CONTROL ABBREVIATIONS
AI ANALOG INPUT
AO ANALOG OUTPUT
AV ANALOG VALUE
BI BINARY INPUT
BO BINARY OUTPUT
BV BINARY VALUE
F.L. FAIL LAST
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
VFD VARIABLE FREQUENCY DRIVE
MECHANICAL SCOPE OF WORK
1.0 SELECTIVE DEMOLITION OF MECHANICAL SYSTEMS
2.0 DUCT SYSTEMS: PROVIDE NEW ZONE DUCTWORK, AIRFLOW CONTROL AND
TERMINAL DEVICES
3.0 HEATING SYSTEMS: PROVIDE NEW ELECTRIC DUCT HEATERS, EXISTING
BASEBOARD RADIATION ELEMENTS ARE TO REMAIN AND INTEGRATED WITH THE
NEW DDC CONTROL SYSTEM
4.0 COOLING SYSTEMS: EXTEND EXISTING CHILLED WATER TO NEW FAN COIL UNITS.
5.0 CONTROL SYSTEMS: EXTEND EXISTING ALC DDC CONTROL SYSTEM. INTEGRATE
HVAC AND LIGHTING CONTROLS.
6.0 INSULATION OF ALL NEW DUCT AND PIPING SYSTEMS
7.0 FIRE WRAP INSULATION SHALL BE PROVIDED ON THE EXHAUST DUCT AS
INDICATED.
8.0 FIRE/SMOKE DAMPERS SHALL BE PROVIDED ON ALL SUPPLY AIR PENETRATIONS OF
THE CORRIDOR WALL.
MECHANICAL GENERAL NOTES
1.0 FIRESTOPPING: THE CONTRACTOR IS TO PROVIDE THROUGH FIRESTOP SYSTEMS
WITH A FIRE RATING OF 1-HOUR AT ALL EXISTING AND NEW CORRIDOR WALL DUCT
AND PIPING PENETRATIONS WITHIN THE PROJECT AREA, WHETHER OR NOT SAID
PENETRATIONS WERE MADE BY THE PROJECT CONSTRUCTION TEAM.
2.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN REQUIRED FIRE RATING.
3.0 PNEUMATIC TERMINATIONS: DO NOT BEND/CRIMP OR USE SHEETMETAL SCREWS
TO TERMINATE PNEUMATIC CONTROL LINES. IF THE PNEUMATIC AIR LINE IS
COPPER, REMOVE THE TUBING BACK TO THE MAIN AND PROVIDE A SOLDERED END
CAP; IF THE PNEUMATIC AIR LINE IS POLY, REMOVE THE TUBING BACK TO THE MAIN
AND PROVIDE A BRASS PLUG.
4.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND
CLEAR DIMENSIONS.
5.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND
WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR.
EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE
RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE
CORRECTED.
6.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION,
FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK REQUIRED
AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER TO ACCESS
SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE UNIVERSITY.
7.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING
CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR
DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH
MATERIALS TO MATCH FINISHED AREAS.
8.0 TESTING AND BALANCING: THE CONTRACTOR SHALL BALANCE ALL AIR SYSTEMS
AS INDICATED. SUBMIT RESULTS OF TESTING AND BALANCING ON STANDARD TAB
CONTRACTOR'S FORMS TO THE ENGINEER FOR REVIEW. SYSTEMS SHALL BE
BALANCED TO WITHIN +/- 10% OF DESIGN VALUES. FINAL BALANCING SHALL OCCUR
AFTER ALL LEAKS IN THE BUILDING ENVELOPE HAVE BEEN IDENTIFIED AND
SEALED.
MECHANICAL SUBMITTAL SCHEDULE
SECTION DESCRIPTION MATERIAL SHOP DRAWINGSCOORDINATION DRAWINGSAS BUILT DRAWINGSPRODUCT DATASCHEDULESWIRING DIAGRAMSSTANDARDSQUALIFICATIONSCERTIFICATIONSMANUFACTURER'S INSTRUCTIONSINSPECTION & TEST REPORTSOPERATION & MAINTENANCE DATAWARRANTIES & BONDS230500 COMMON WORK RESULTS FOR HVAC WELDING CERTIFICATES X
230500 COMMON WORK RESULTS FOR HVAC THROUGH-PENETRATION FIRESTOP SYSTEMS X X X
230519 METERS AND GAGES FOR HVAC EQUIPMENT TEMPERATURE/PRESSURE TEST PORTS X
230523 GENERAL DUTY VALVES FOR HVAC PIPING BALL VALVES X
230593 TESTING, ADJUSTING & BALANCING FOR HVAC CERTIFIED TEST REPORT X X
230593 TESTING, ADJUSTING & BALANCING FOR HVAC EQUIPMENT CALIBRATION X
230700 HVAC INSULATION PIPING INSULATION X
230700 HVAC INSULATION DUCTWORK INSULATION X
230700 HVAC INSULATION FIRE-RATED INSULATION X X
230900 INSTRUMENTATION & CONTROL FOR HVAC CONTROLLERS & ENCLOSURES X X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC POINTS / ALARM LIST X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC SCHEMATIC CONTROL DIAGRAMS X X
230900 INSTRUMENTATION & CONTROL FOR HVAC ARCHITECTURE DIAGRAM X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC SEQUENCES OF OPERATION X X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC BILL OF MATERIALS X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC TEMPERATURE/HUMIDITY SENSORS X X
230900 INSTRUMENTATION & CONTROL FOR HVAC OCCUPANCY/VACANCY SENSORS X X
230900 INSTRUMENTATION & CONTROL FOR HVAC CONTROL VALVES AND ACTUATORS X X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC LABORATORY AIRFLOW DEVICES X X X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC LIGHTING CONTROLS X X X X
230900 INSTRUMENTATION & CONTROL FOR HVAC CABLING X
232113 HYDRONIC PIPING SYSTEMS PIPES, TUBES, FITTINGS X X X X
232113 HYDRONIC PIPING SYSTEMS JOINING MATERIALS X
232113 HYDRONIC PIPING SYSTEMS DIELECTRIC FITTINGS X
232113 HYDRONIC PIPING SYSTEMS BALANCING VALVES X
232113 HYDRONIC PIPING SYSTEMS AIR CONTROL DEVICES X
232113 HYDRONIC PIPING SYSTEMS STRAINERS X
232213 STEAM AND CONDENSATE PIPING SYSTEMS PIPE AND FITTINGS X X X X X
232213 STEAM AND CONDENSATE PIPING SYSTEMS JOINING MATERIALS X
232213 STEAM AND CONDENSATE PIPING SYSTEMS STRAINERS X
232213 STEAM AND CONDENSATE PIPING SYSTEMS STEAM TRAPS X
233113 METAL DUCTS RECTANGULAR DUCTWORK X X X X
233113 METAL DUCTS ROUND DUCTWORK X X X X
233113 METAL DUCTS DUCT LINER X X X X
233113 METAL DUCTS SEALING & GASKETING MATERIALS X
233113 METAL DUCTS SHOP CONSTRUCTION STANDARDS X
233300 AIR DUCT ACCESSORIES VOLUME DAMPERS X X X X
233300 AIR DUCT ACCESSORIES COMBINATION FIRE/SMOKE DAMPERS X X X X X X X X X
233300 AIR DUCT ACCESSORIES FLANGE CONNECTORS X
233300 AIR DUCT ACCESSORIES TURNING VANES X
233300 AIR DUCT ACCESSORIES ACCESS DOORS X X X X
233300 AIR DUCT ACCESSORIES FLEXIBLE CONNECTORS X X X X
233300 AIR DUCT ACCESSORIES FLEXIBLE DUCTS X X X X
233600 AIR TERMINAL UNITS AIR VALVES X X X X X X X
233713 DIFFUSERS, REGISTERS AND GRILLES CEILING DIFFUSERS AND GRILLES X X X X X
233713 DIFFUSERS, REGISTERS AND GRILLES ZONE AIRFLOW REGULATING TERMINALS X X X X X X
238216 AIR COILS ELECTRIC COILS X X X X X X X X X
238219 FAN COIL COOLING UNITS FAN COIL UNITS X X X X X X X X X
238413 HUMIDIFIERS HUMIDIFIERS X X X X X X X X X X
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
18x1016x1016x1018x10
18x1016x1016x1016x1018x1018x1016x1016x1010ø
16x1018x10
12x8
16x1048x18
(BOD=10' -8 1/2")
30x18
(BOD=10' -2 1/2")30x1830x18
16x1016x1016x1016x10
12x612x612x612x612x830x18 10ø12x1010ø10x610x1010x1010x10
10x1010x812x814x10
42x1842x16
W162
W162A
W162B W164
W154B
W154C
W154W154A
W161
W159W157
W157A
W153B
W100C
1 1 1
1 1
1
2
2
222
2 2
2
222 2
2
48x18
(BOD=10' -8 1/2")
34x18
(BOD=10' -8 1/2")12x62
555 444
3 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-101
12971596
MECHANICAL
DUCTWORK &
PIPING
DEMOLITION
PLANS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTION#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
M-101 KEYED DEMOLITION NOTES
1 REMOVE ELECTRIC REHEAT COILS. COORDINATE THE REMOVAL OF ELECTRIC
REHEAT COILS WITH ELECTRICAL CONTRACTOR.
2 PATCH DUCTWORK AS REQUIRED WHERE DUCTWORK HAS BEEN REMOVED FROM
THE MAIN. MAINTAIN SEAL CLASS A @ (+/-) 4 IN. WG.
3 REMOVE FUME HOOD.
4 REMOVE BOTH PNEUMATIC CONTROL AND ISOLATION VALVES SERVING EXISTING
BASEBOARD HEATER.
5 REMOVE BOTH ISOLATION AND BALANCING VALVES SERVING BASEBOARD HEATER.
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
SCALE:1/4" = 1'-0"1 FIRST FLOOR - DUCTWORK DEMOLITION PLAN
MAIN LAB
W161
MEETING
W161A
OFFICE 2
W161B
OFFICE 1
W161C
IMAGING
W162E
ANTEROOM
W162
BEHAVIOR 5
W162D
BEHAVIOR 4
W162A
HOLDING 2
W162B
HOLDING 1
W162C
PROCEDURE
W156BEHAVIOR 3
W154C
BEHAVIOR 2
W154B
ANTEROOM
W154
BEHAVIOR 1
W154A
12x12
10x86ø 20x1816x16 12ø12ø
12x12
16x126ø12ø
12ø6ø
8ø
8x820x1420x1414x1410x10
10x10
10ø8ø8ø10ø
8ø
8ø
6ø
10x10
6ø
10x106ø
48x18
(BOD=10' -8 1/2")
34x18
(BOD=10' -8 1/2")
12x8 SA(E)10x8 EA(E)12x12 12x1218x1410x810ø8ø8ø 8ø8ø6ø6ø6ø
10ø10ø
12x10
12x10
16x14
6ø
8x8
4ø
10x10
8ø 10x10 10x108x6
8x6
20x12
14x8 14x8
16x12 10ø
10ø
10x10
22x10 22x10
EDH-161-1FCU-161-1 FCU-161-2
FCU-161-3
FCU-161-4
H-3
FCU-162-1
EAV-162-5
42x18 EA(E)42x16 EA(E)
EDH-162-3
EDH-162-4
EAV-162-4
EDH-162-5
10ø
22x14
SAV-156-1
12x12
FSD-3
4ø4ø
EAV-162-3EAV-162-2
EAV-162-1
EAV-156-1
EAV-154-3
SAV-162-3
SAV-162-2
SAV-162-1
EDH-162-2
EDH-162-1
EDH-156-1
H-2
EDH-154-3
H-1
FSD-2
EDH-154-1
SAV-154-1
EAV-154-2
EAV-154-1
EDH-154-2
SAV-154-2
SAV-154-3
FSD-4
FSD-1
10x10ZRT-1
ZRT-2
ZRT-3
EDH-161-2
SAV-161-1
EAV-161-1
DAD-2
DAD-3
DAD-1
DAD-3
SAD-2
265 CFM
EAG-3
370 CFM
SAD-3
410 CFM
SAD-3
345 CFM
RAG-1
410 CFM
SAV-162-5
SAV-162-4
EAG-3
315 CFM
SAD-3
280 CFM
EAG-3
300 CFM
SAD-3
430 CFM
EAG-4
530 CFM
EAG-4
515 CFM
EAG-4
515 CFM
SAD-4
480 CFM
SAD-4
480 CFM
SAD-2
270 CFM
SAD-1
50 CFM
EAG-5
305 CFM
SAD-3
290 CFM
EAG-3
325 CFM
SAD-1
50 CFM
SAD-4
445 CFM
SAD-4
445 CFM
SAD-4
445 CFM
RAG-2
753 CFM
20x128ø
SAD-4
445 CFM
RAG-2
752 CFM
EAG-2
175 CFM
(50 CFM)
(50 CFM)
(50 CFM)
SAD-3
280 CFM
SAD-3
280 CFM
SAD-2
175 CFM
RAG-2
280 CFM
RAG-2
280 CFM
48x18
(BOD=10' -8 1/2")
30x18
(BOD=10' -2 1/2")
30x18
(BOD=10' -2 1/2")
30x18
(BOD=10' -2 1/2")20x14
(BOD=10' -2 1/2")
12x10
12ø
VDVD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VDVD
VD VD VD
VDVD VDVD
VD
VD
VD
VD
VD
VDVD
VDVD
VD
VD
VD VD VD VD
VD
VDVD VD
1
1
1
22x10
22x10
VDVD 6ø
6ø
2
3 4
10X10 TO 10"ø
TRANSITION
10X10 TO 10"ø
TRANSITION
5
8x8 TRANSITION TO 8"ø 10ø12x12
RAG-2
175 CFM
66
6
EAG-1
110 CFM
SAD-5
85 CFM
EAG-1
110 CFM
SAD-5
85 CFM
7
7
VOLUME DAMPER
CEILING
WALL MOUNTED
DUCT SUPPORT
6" FLEXIBLE EXHAUST
DUCT CONNECTED TO
GALVANIZED DUCT
BASIS OF DESIGN:
FLEXIBLE R-2 LIGHT
WEIGHT BLUE PVC HOSE
REINFORCED WITH A
SPRING STEEL WIRE
HELIX, UL 94V-0 FLAME
RETARDANT
TERMINATE
HOSE END WITH
ALUMINUM
CONNECTOR
6" GALVANIZED
EXHAUST AIR
DUCT
EXTEND DUCT 1'-0"
BELOW CEILING
PROVIDE ESCUTCHEON
AT CEILING PENETRATION
ELECTRIC REHEAT COIL
HINGED CONTROL CABINET.
MAINTAIN MANUFACTURERS
RECOMMENDED SERVICE
CLEARANCES.
HEATER ELEMENT
4'-0" (MIN) STRAIGHT RUN
OF DUCTWORK, SAME
SIZE AS REHEAT COIL
A
IR
F
L
OW2'-0" (MIN) STRAIGHT RUN
OF DUCTWORK, SAME
SIZE AS REHEAT COIL
AIR VALVE
AIR FLOW
GYPSUM WALL
WALL SLEEVE GAGE
EQUAL TO DUCT GAGE
JUNCTION BOX
MOUNTED ON SLEEVE
FIRE/SMOKE
DAMPER BLADES
ACTUATOR
METAL STUD (ALL FOUR SIDES)
RETAINING ANGLE (SEE NOTES)
NOTES
1. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS
2. RETAINING ANGEL GAGE PER UL 555 AND UL555S
20 GAGE MINIMUM: 1-1/2 HOUR COMBINATION FIRE/SMOKE DAMPERS WITH DUCT HEIGHT 48" OR LESS.
3. RETAINING ANGLE SIZE:
1-1/2" x 1-1/4" FOR DAMPERS 48" OR LESS
4. RETAINING ANGLE ATTACHMENT TO SLEEVE:
DAMPERS ≤48" W x 36" H = 12" OC MAX, ALL SIDES (MINIMUM OF TWO CONNECTIONS PER SIDE)
ATTACHMENT METHODS:
-TACK OR SPOT WELDS
-#10 (3/4" MAX LENGTH) SHEET METAL SCREWS
-1/4" BOLT & NUTS
-3/16" STEEL POP RIVETS
5. PROVIDE RETAINING ANGELS ON BOTH SIDES OF THE WALL, ANGLES SHALL NOT BE ATTACHED TO WALL.
(MAX)
0' - 6"
(MAX)
-
DUCT ACCESS DOOR OF SUFFICIENT
SIZE TO INSPECT/SERVICE DAMPER.
ACCESS DOOR WIDTH SHALL BE 2"
SMALLER THAN THE DUCT WIDTH
16" MAX WHEN EQUIPPED WITH FACTORY
ACTUATOR AND/OR ACCESS DOOR
BREAKAWAY DUCT CONNECTION
(REFER TO MANUFACTURER FOR
APPROVED TYPES)
(MIN)
0' - 8"
DSD
RL /
OCIDTS
SD-
TS
SD-
LED
120 VAC
DUCT SMOKE DETECTOR, SAMPLING TYPE (DSD),
REMOTE DETECTOR STATUS (SD-LED),
ANNUNCIATOR (LED),
AND TEST/RESET STATION (SD-TS)
BY ELECTRICAL CONTRACTOR.
WIRE PER MANUFACTURER'S INSTRUCTIONS.
DAMPER TEST SWITCH (DTS) AND RESETTABLE
LINK/OPEN-CLOSED INDICATOR (RL/OCI):
LOCATE IN CORRIDOR ADJACENT TO SMOKE
DETECTOR REMOTE LED ANNUNCIATOR AND
TEST/RESET STATION, REVIEW LOCATION WITH
CORNELL PRIOR TO INSTALLATION. WIRE PER
MANUFACTURERS INSTRUCTIONS.
HANG ACOUSTICALLY
LINED TRANSFER
DUCT INDEPENDENT
OF CEILING
1" ACOUSTICAL LINING
1'-0"
(MIN)
CEILING
RETURN AIR GRILLE
MOUNTED IN CEILING
1'-0" (MIN)
RETURN AIR
STAINLESS
STEEL BAND
DIFFUSER
INSULATED FLEXIBLE DUCT
3'-0" MAXIMUM LENGTH
RIGID DUCT
VOLUME
DAMPER
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-102
12971596
MECHANICAL
NEW WORK
DUCTWORK
PLANS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONM-102 KEYED RENOVATION NOTES
1 PROVIDE STAINLESS STEEL DUCTWORK 6” UPSTREAM OF AND 5’-0” DOWNSTREAM
OF HUMIDIFIER.
2 6” EXHAUST DROP THROUGH CEILING TO SERVE SOLDERING STATION. REFER TO
DETAIL B, THIS SHEET FOR FURTHER INFORMATION.
3 FIRE WRAP EXISTING EXHAUST DUCT.
4 FIRE ENCLOSURE, REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION
AND DETAILS.
5
LOCATE SUPPLY DUCT AT A LOWER ELEVATION THAN THE 10X10 SA DUCT IN FRONT
OF THE ELECTRIC REHEAT COIL CONTROL CABINET TO PROVIDE ADEQUATE
SERVICE CLEARANCE.
6 SEMI RECESSED CONTROL PANEL 16”W x 20”H x 6”D. COORDINATE EXACT LOCATION
WITH ELECTRICAL CONTRACTOR.
7 COORDINATE ELECTRIC DUCT HEATER CEILING ACCESS DOOR LOCATION WITH
GENERAL CONTRACTOR.
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
SCALE:1/4" = 1'-0"1 FIRST FLOOR - NEW DUCTWORK PLAN
NOT TO SCALEBSOLDERING EXHAUST DROP DETAIL
NOT TO SCALEAELECTRIC REHEAT COIL DETAIL
NOT TO SCALEECOMBINATION VERTICAL FIRE / SMOKE DAMPER DETAIL
NOT TO SCALECRETURN PLENUM DETAIL
NOT TO SCALEDFLEX DUCT CONNECTION TO DIFFUSER
MAIN LAB
W161
MEETING
W161A
OFFICE 2
W161B
OFFICE 1
W161C
IMAGING
W162E
ANTEROOM
W162
BEHAVIOR 5
W162D
BEHAVIOR 4
W162A
HOLDING 2
W162B
HOLDING 1
W162C
PROCEDURE
W156
BEHAVIOR 3
W154C
BEHAVIOR 2
W154B
ANTEROOM
W154
BEHAVIOR 1
W154A
FCU-161-1 FCU-161-2
FCU-161-3
FCU-161-4
H-3
FCU-162-1
H-2
H-1
1" CHWS
1" CHWR
3/4" CHWS
3/4" CHWR
3/4" CHWS
3/4" CHWR
3/4" CHWS3/4" CHWR1 1/2" CHWR1 1/2" CHWS1 1/4" CHWS1 1/4" CHWRTIE INTO CHILLED WATER
MAINS LOCATED IN CORRIDOR
W100. PROVIDE ISOLATION
VALVES AT MAIN CONNECTION.
(APPROXIMATELY 25'-0")
TIE INTO 2-1/2" LPCS AND 2" LPCC
MAINS LOCATED IN W100 CORRIDOR.
PROVIDE ISOLATION VALVES AT MAIN
CONNECTION. (APPROXIMATELY 25'-0")3/4" LPCC1" LPCS1
3/4" CHWS
3/4" CHWR
3/4" CHWS
3/4" CHWR
3/4" LPCC
3/4" LPCS3/4" LPCC1" LPCS1" LPCS
3/4" LPCC
TIE INTO 2-1/2" LPCS AND 2" LPCC
MAINS LOCATED IN W100 CORRIDOR.
PROVIDE ISOLATION VALVES AT MAIN
CONNECTION. (APPROXIMATELY 25'-0")
222333
CLEAN OUT WITH
THREADED CAP
(TYP)
3/4" CD 3/4" CD 3/4" CD3/4" CD
3/4" CD
3/4" CD
CLEAN OUT WITH
THREADED CAP
(TYP)
4
3/4" CD3/4" CD3/4" CD3/4" CD
3/4" CD1
3/4" CD
SUPPLY RETURN
ISOLATION VALVE
BALANCING
VALVE
P R E S S U R E /T E M P E R A T U R E
T E S T P O R T (T Y P . O F 2 )M A N U A L
A IR V E N T
C O IL
STRAINER BLOWDOWN
WITH BRASS HOSE
CONNECTION, CAP WITH CHAIN
COIL DRAIN WITH BRASS HOSE
CONNECTION, CAP AND CHAIN (TYP.)
STAINLESS STEEL
DRAIN PAN
CONDENSATE DRAIN WITH
P-TRAP TO INDIRECT WASTE
C O N T R O L V A L V E
U N IO N
STAINLESS STEEL DUCTWORK
0'-6" UPSTREAM & 5'-0"
DOWNSTREAM OF HUMIDIFIER
TERMINATE JUST BELOW
TOP OF THE FUNNEL WITH
A MINIMUM 1" AIR GAP.
STEAM
TUBES
INDIRECT WASTE FUNNEL
STEAM HEADER BRACKET.
INSTALL PER MANUFACTURE'S
RECOMMENDATIONS. USE CAULKING TO
SEAL ALL DUCT HOLES AIR/WATER TIGHT.(MIN)0' - 6"CONDENSATE
RETURN
CLEAN STEAM
SUPPLY
***STRAINER***
***CONTROL VALVE***
ISOLATION
VALVE (TYP)(MIN)0' - 6"***F&T STEAM TRAP***
***SEPARATOR***
NOTE
***STEAM COMPONENTS IN GRAY ARE PROVIDED BY HUMIDIFIER
MANUFACTURER AND INSTALLED BY CONTRACTOR***
TAP FROM TOP
OF STEAM MAIN
0' - 1" (MIN)
1" + CASING STATIC PRESSURE
TEE WITH
THREADED CAP
TO INDIRECT WASTE.
REFER TO PLUMBING PLANS
FOR TERMINATION POINT
UNION
(3" MINIMUM DISTANCE)
COOLING EQUIPMENT
COOLING COIL DRAIN SIZING
CONNECTED COOLING
CAPACITY (TONS)MINIMUM PIPE DIAMETER
UP TO 20 3/4"
> 20 AND ≤40 1"
1-1/4"
1-1/2"
2"
> 40 AND ≤90
> 90 AND ≤125
> 125 AND ≤250
NOTES:
1) 1 TON = 12,000 BTU/H
2) COOLING COIL DRAIN LINES SHALL SLOPE AWAY
FROM EQUIPMENT CONNECTION AT A MINIMUM
SLOPE OF 0.125" / FOOT CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-103
12971596
MECHANICAL
NEW WORK
PIPING PLANS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONSCALE:1/4" = 1'-0"1 FIRST FLOOR - NEW MECHANCIAL PIPING PLAN
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
NOT TO SCALEBFAN COIL UNIT PIPING DETAIL
NOT TO SCALEADUCT HUMIDIFIER DETAIL
M-103 KEYED RENOVATION NOTES
1 REFER TO PLUMBING DRAWINGS FOR INDIRECT WASTE FUNNEL LOCATION.
2 PROVIDE DIGITAL CONTROL VALVE AND ISOLATION VALVE SERVING EXISTING
BASEBOARD HEATER.
3 PROVIDE NEW ISOLATION AND BALANCING VALVE SERVING EXISTING BASEBOARD
HEATER.
4 3/4” CONDENSATE DRAIN (COOLING) DOWN IN WALL, OPEN SITE TO LAB WASTE
FUNNEL, LOCATED APPROXIMATELY @ 4’-0” AFF.
#
NOT TO SCALECCOOLING CONDENSATE DRAIN DETAIL
MAIN LAB
W161
MEETING
W161A
OFFICE 2
W161B
OFFICE 1
W161C
IMAGING
W162E
ANTEROOM
W162
BEHAVIOR 5
W162D
BEHAVIOR 4
W162A
HOLDING 2
W162B
HOLDING 1
W162C
PROCEDURE
W156BEHAVIOR 3
W154C
BEHAVIOR 2
W154B
ANTEROOM
W154
BEHAVIOR 1
W154A
SAV-162-3
SAV-162-2
SAV-162-1
EDH-162-3
EDH-162-2
SAD-1
50 CFM
SAV-162-4
SAV-162-5
EDH-162-4
EAV-162-4 EAV-162-5
SAD-3
280 CFM
EAG-3
315 CFM
EDH-162-5
SAD-3
345 CFM
SAD-3
410 CFM
FCU-162-1
RAG-1
410 CFM
EDH-162-1
SAD-2
265 CFM
EAG-3
300 CFM
EAG-3
370 CFM
25
CFM
35
CFM
25
CFM
25
CFM
35
CFM
95CFMEAV-162-3
EAV-162-2
EAV-162-1
EAV-156-1
EAV-154-3
EAG-4
530 CFM
EAG-4
515 CFM
SAD-4
480 CFM
EAG-4
515 CFM
SAD-3
430 CFM
SAD-4
480 CFM
H-2
H-3
EDH-156-1SAV-156-1
SAV-154-3
SAV-154-2
EDH-154-3
EDH-154-2
EAV-154-2
EAV-154-1
EDH-154-1
SAV-154-1
EAG-3
325 CFM
SAD-3
290 CFM
EAG-5
305 CFM
SAD-2
270 CFM
SAD-1
50 CFM
H-1
100CFM90CFM70
CFM35
CFM 35CFMSAV-161-1
EDH-161-1
EAV-161-1
0 CFM
ZRT-20 CFM
ZRT-3
EDH-161-2
FCU-161-3
FCU-161-4
RAG-2
175 CFM SAD-2
175 CFM
SAD-3
280 CFM
SAD-3
280 CFM
RAG-2
280 CFM
RAG-2
280 CFM
SAD-4
445 CFM
SAD-4
445 CFM
SAD-4
445 CFM
SAD-4
445 CFM
RAG-2
752 CFM
EAG-2
175 CFM
RAG-2
753 CFM
FCU-161-2FCU-161-1
0 CFM
ZRT-1
50 CFM
50 CFM50 CFM
137 CFM FROM
SAV-161-1
138 CFM FROM
SAV-161-1
50CFM50CFM100
CFM
100CFMCOMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH / CO2
SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
SEMI-RECESS
CONTROL PANEL
SEMI-RECESS
CONTROL PANEL
SEMI-RECESS
CONTROL PANEL
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR
COMBINATION
TEMP / RH SENSOR CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-301
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTION1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
SCALE:3/8" = 1'-0"1 FIRST FLOOR - PRESSURIZATION AND TEMPERATURE CONTROL PLAN
POSITION
FLOW
N.C.
ECM
F.L.
MODCOOLING COILT
POINTS TYPICAL FOR
FCU-161-1 AND FCU-161-2
FTR
EAV-161-1 TO
EF-1
POSITION
FLOW
MOD
SAV-161-1FROM
AC-1
EDH-161-1CV-6
CV-1
CV-2
P T
LS
MOD CS
1
2 4
6
9
11
12
14
15
7
8
10
13
16
WS
22
D
23
DS OS
20
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
24
26
25277 VAC
LINE VOLTAGE
FSD-1R
120 VAC
LINE VOLTAGE R
AOM
TO FIRE
ALARM
CIRCUIT
3
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
T sa
d
H
17 18
C
19
MOD
5
VS
21 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-302
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONNOT TO SCALE1W161 CONTROLS
SEQUENCE OF OPERATION
THE HVAC AND LIGHTING IN THE ZONE SHALL BE CONTROLLED BY THE BUILDING
AUTOMATION AND CONTROL SYSTEM (BACS). THE PROJECT SHALL EXTEND THE
EXISTING AUTOMATED LOGIC CONTROL SYSTEM TO SERVE THIS ZONE.
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE LIGHTING CONTROLS ARE TO BE TIED TO THE BACS FOR HVAC TEMPERATURE
SETBACKS WITH THE USE OF OCCUPANCY/VACANCY SENSING.
HVAC SYSTEM COMMISSIONING: THE CONTRACTOR SHALL DEMONSTRATE TO THE
OWNER’S REPRESENTATIVE THAT THE HVAC CONTROL SYSTEMS ARE CALIBRATED,
ADJUSTED, AND ARE WORKING PER THE PRESCRIBED SEQUENCE OF OPERATION.
FUNCTIONAL TESTING OF THE LIGHTING CONTROL SYSTEM: THE CONTRACTOR SHALL
DEMONSTRATE TO THE OWNER’S REPRESENTATIVE THAT THE CONTROL HARDWARE
AND SOFTWARE IS CALIBRATED, ADJUSTED, PROGRAMMED AND CONTROLLING IN
ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTIONS AND
SEQUENCE OF OPERATION.
DESIGN INTENT: W161 MAIN LAB
FRESH AIR IS CONNECTED TO AC-1 WITH A SUPPLY AIR TEMPERATURE RESET
SCHEDULE AS FOLLOWS:
OAT = 55 °F=>SAT = 60 °F
OAT = 75 °F=>SAT = 55 °F
EXHAUST AIR IS CONNECTED TO EF-1
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE VENTILATION AIR FOR A MAXIMUM OF 15
SPACE OCCUPANTS. BASEBOARD RADIATION PROVIDES STAGE 1 HEATING, AN
ELECTRIC DUCT HEATER PROVIDES STAGE 2 HEATING. FAN COILS PROVIDE
SUPPLEMENTAL COOLING.
LOAD SHED: THE ZONE SHALL REMAIN UNDER CONTROL UNDER ALL STEAM AND
CHILLED WATER LOAD SHED LEVELS.
OCCUPANCY MODES
ZONE OCCUPANCY SCHEDULE: 6 AM TO 6 PM, MONDAY -FRIDAY
ZONE OCCUPANCY IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE ZONE SHALL INDEX TO OCCUPIED
MODE AND OPERATE FOR A MINIMUM OF 30 MINUTES.
OCCUPIED/OCCUPIED SETBACK MODE: THE ZONE SHALL INDEX BETWEEN OCCUPIED
AND OCCUPIED SETBACK MODES DURING THE SCHEDULED OCCUPANCY PERIOD
BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE ZONE
OCCUPANCY/VACANCY SENSOR. THE ZONE SHALL INDEX TO OCCUPIED SETBACK
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 30 MINUTES.
UNOCCUPIED MODE: THE ZONE SHALL INDEX TO UNOCCUPIED MODE OUTSIDE OF THE
TIME OF DAY SCHEDULE. IF THE ZONE BECOMES OCCUPIED DURING THE SCHEDULED
UNOCCUPIED PERIOD BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE
ZONE OCCUPANCY/VACANCY SENSOR, THE ZONE SHALL INDEX TO OCCUPIED MODE
FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO UNOCCUPIED
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 15 MINUTES.
VENTILATION CONTROL
ZONE CO2 SETPOINT: 900 PPM
VENTILATION RATE IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR VALVES
SHALL INDEX TO MAXIMUM AIRFLOW POSITION AND OPERATE FOR A MINIMUM OF 30
MINUTES.
OCCUPIED/OCCUPIED SETBACK OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR
VALVES SHALL MODULATE BETWEEN MINIMUM AND MAXIMUM POSITIONS TO MAINTAIN
THE ZONE CARBON DIOXIDE LEVEL AT SETPOINT.
UNOCCUPIED MODE: WHEN THE ZONE IS UNOCCUPIED, THE SUPPLY AND EXHAUST AIR
VALVES SHALL CLOSE.
TEMPERATURE CONTROL
TEMPERATURE SETPOINTS:COOLING HEATING
OCCUPIED:75 °F ± 1.5 °F 70 °F ± 1.5 °F
OCCUPIED SETBACK:75 °F + 3 °F 70 °F -3 °F
UNOCCUPIED:75 °F + 6 °F 70 °F -6 °F
TEMPERATURE SETPOINTS ARE DETERMINED BY A COMBINATION OF A TIME OF DAY
SCHEDULE AND A SPACE OCCUPANCY/VACANCY SENSOR.
THE CHILLED WATER CONTROL VALVES SHALL BE CLOSED WHENEVER THE FAN COIL
UNITS ARE OFF.
OCCUPIED/OCCUPIED SETBACK MODES:
• DURING THE OCCUPIED/OCCUPIED SETBACK MODES, THE FAN COIL UNITS SHALL
INDEX ON AND OPERATE AT MINIMUM SPEED.
• HEATING CONTROL: IF THE ZONE FALLS BELOW THE OCCUPIED/OCCUPIED
SETBACK HEATING SETPOINT, THE FAN COIL UNIT CHILLED WATER CONTROL
VALVES SHALL CLOSE. THE BASEBOARD RADIATION CONTROL VALVE SHALL
MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT. IF THE ZONE
IS NOT AT SETPOINT WITH THE BASEBOARD RADIATION CONTROL VALVE FULLY
OPEN, THE SUPPLY AIR VALVE SHALL MAINTAIN CO2 CONTROL AND THE ELECTRIC
REHEAT COIL SHALL INDEX ON AND MODULATE AS NEEDED TO MAINTAIN SETPOINT.
IF THE ZONE IS STILL NOT AT SETPOINT, CO2 CONTROL SHALL BE OVERRIDEN AND
THE SUPPLY AIR VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN
SETPOINT.
• COOLING CONTROL: IF THE ZONE RISES ABOVE THE OCCUPIED/OCCUPIED
SETBACK COOLING SETPOINT, THE SUPPLY AIR VALVE SHALL INDEX TO CO2
CONTROL, THE ELECTRIC REHEAT COIL SHALL INDEX OFF AND THE BASEBOARD
RADIATION VALVE SHALL CLOSE. THE CHILLED WATER CONTROL VALVES SHALL
MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT. IF THE ZONE
IS NOT AT SETPOINT WITH THE CHILLED WATER CONTROL VALVES FULLY OPEN,
THE FAN COIL UNIT SPEED SHALL INCREASE AS NEEDED TO MAINTAIN SETPOINT.
UNOCCUPIED MODE:
• THE FAN COIL UNITS SHALL BE OFF.
• HEATING CONTROL: IF THE ZONE FALL BELOW THE UNOCCUPIED HEATING
SETPOINT, THE CHILLED WATER CONTROL VALVES SHALL CLOSE. THE BASEBOARD
RADIATION CONTROL VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN THE
ZONE AT SETPOINT.
• COOLING CONTROL: IF THE ZONE RISES ABOVE THE UNOCCUPIED COOLING
SETPOINT, THE ELECTRIC DUCT COIL SHALL INDEX OFF AND THE BASEBOARD
RADIATION CONTROL VALVES SHALL CLOSE. THE FAN COIL UNITS SHALL INDEX ON
AND OPERATE AT MINIMUM SPEED. THE CHILLED WATER CONTROL VALVES SHALL
MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT. IF THE ZONE
IS NOT AT SETPOINT WITH THE CHILLED WATER CONTROL VALVES FULLY OPEN,
THE FAN COIL UNIT SPEED SHALL INCREASE AS NEEDED TO MAINTAIN SETPOINT.
SAFETIES
THE FAN COIL SHALL INDEX OFF AND THE CHILLED WATER CONTROL VALVE SHALL
CLOSE UPON ACTIVATION OF THE DRAIN PAN OVERFLOW SWITCH.
THE ELECTRIC DUCT COIL SHALL INDEX OFF WHENEVER THE INTEGRAL AIR PROVING
SWITCH DOES NOT SENSE AIRFLOW
THE BACS SHALL MONITOR THE STATUS OF THE FIRE/SMOKE DAMPER. THE DAMPER
SHALL CLOSE WHENEVER AC-1 IS OFF VIA COORDINATION WITH THE FIRE ALARM
SYSTEM.
LIGHTING
THE FOLLOWING LIGHTING CONTROLS ARE REQUIRED TO BE PROVIDED FOR THIS
ZONE:
• MANUAL ON/OFF/DIMMING CONTROL
• VACANCY SENSING –MANUAL ON/AUTOMATIC OFF
• DAYLIGHT RESPONSIVE CONTROLS
W161 CONTROL POINTS LIST SCHEDULE
POINT
#CONTROL POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW
ON
GRAPHIC NOTESBI BO AI AO AV BV SCH TREND
ALARM
ALARM DESCRIPTIONBACS EMCS
1 SUPPLY AIR VALVE FLOW FEEDBACK/SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X
2 SUPPLY AIR VALVE POSITION FEEDBACK (%)X X X
3 FIRE/SMOKE DAMPER STATUS (OPEN/CLOSED) X X X
4 SUPPLY AIR VALVE COMMAND X X X
5 ELECTRIC HEATING COIL COMMAND X X X
6 ELECTRIC HEATING COIL AIR PROVING SWITCH X X X LOSS OF AIRFLOW X
7 ELECTRIC HEATING COIL DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X
8 FCU ECM FAN START/STOP/SPEED X X X TYPICAL FOR 2 FCUS
9 FCU ECM STATUS (ON/OFF)X X X FAN FAILURE X TYPICAL FOR 2 FCUS
10 FCU COOLING COIL CONTROL VALVE POSITION COMMAND X X X TYPICAL FOR 2 FCUS
11 FCU OVERFLOW SWITCH STATUS X X X OVERFLOW X TYPICAL FOR 2 FCUS
12 FCU DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X TYPICAL FOR 2 FCUS
13 BASEBOARD RADIATION CONTROL VALVE POSITION COMMAND (%)X X X
14 EXHAUST AIR VALVE FLOW FEEDBACK /SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X
15 EXHAUST AIR VALVE POSITION FEEDBACK (%)X X X
16 EXHAUST AIR VALVE FLOW COMMAND (CFM)X X X
17 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X
18 SPACE HUMIDITY X X X
19 SPACE CO2/SETPOINT X X X X DEVIATION FROM SETPOINT X
20 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X
21 LIGHTING VACANCY SENSING (ON/OFF)X X X
22 LIGHTING MANUAL WALL SWITCH (ON/OFF)X X X
23 LIGHTING MANUAL DIMMING (%)X X X
24 AUTOMATIC DIMMING CONTROL DAYLIGHT SENSOR (FOOT-CANDLES) X X X X SENSOR FAILURE X
25 DIMMING LIGHT FIXTURE COMMAND X X X
26 LIGHTING CONTACT RELAY (OPEN/CLOSED)X X X
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
POSITION
FLOW
N.C.
ECM
MODCOOLING COILT
T sa
FCU-162-1
EAV-162-5 TO EF-1
d
H
POSITION
FLOW MOD
SAV-162-5
EDH-162-5CV-5
P T
LS
MOD CS
6
7
8
10
13
15
16
17
18
20 21
11
12
14
19
WS
23
D
24
OS
22
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
26
277 VAC
LINE VOLTAGE R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
POSITION
FLOW MOD
T
TO EF-1
POSITION
FLOW MOD
SAV-162-1
SAV-162-4
EDH-162-1EDH-162-4P
27
28
29
31
33
34
32
35
WS
39
D
40
OS
38
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
42
R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
POSITION
FLOW MOD
T
TO EF-1
POSITION
FLOW MOD
P
47
48
49
51
53
54
52
55
RED LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
62
R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
FROM AC-1
FSD-4120 VAC
LINE VOLTAGE R
AOM
TO
FIRE ALARM
CIRCUIT
1
N.C.
H-3
2
TP
3 4
H
5
W162E
277 VAC
LINE VOLTAGE
W162A & W162D
EAV-162-1
EAV-162-4
WS
43
D
44
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
46
R277 VAC
LINE VOLTAGE
W162
FROM
SAV-162-1
W162B & W162C
SAV-162-2
SAV-162-3
EAV-162-2
EAV-162-3EDH-162-2EDH-162-3WHITE LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
61
63R
277 VAC
LINE
VOLTAGE
LS
64
6665
T sa
d
H
36 37
WS
58
D
59
T sa
d
H
56 57
277 VAC
LINE
VOLTAGE
MOD
9
MOD
30
MOD
50 VS
60
VS
41
VS
25
VS
45 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-303
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONNOT TO SCALE1W162 CONTROLS
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-304
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONSEQUENCE OF OPERATION
THE HVAC AND LIGHTING IN THE ZONE SHALL BE CONTROLLED BY THE BUILDING
AUTOMATION AND CONTROL SYSTEM (BACS). THE PROJECT SHALL EXTEND THE
EXISTING AUTOMATED LOGIC CONTROL SYSTEM TO SERVE THIS ZONE.
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE LIGHTING CONTROLS ARE TO BE TIED TO THE BACS FOR HVAC TEMPERATURE
SETBACKS WITH THE USE OF OCCUPANCY/VACANCY SENSING.
HVAC SYSTEM COMMISSIONING: THE CONTRACTOR SHALL DEMONSTRATE TO THE
OWNER’S REPRESENTATIVE THAT THE HVAC CONTROL SYSTEMS ARE CALIBRATED,
ADJUSTED, AND ARE WORKING PER THE PRESCRIBED SEQUENCE OF OPERATION.
FUNCTIONAL TESTING OF THE LIGHTING CONTROL SYSTEM: THE CONTRACTOR SHALL
DEMONSTRATE TO THE OWNER’S REPRESENTATIVE THAT THE CONTROL HARDWARE
AND SOFTWARE IS CALIBRATED, ADJUSTED, PROGRAMMED AND CONTROLLING IN
ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTIONS AND
SEQUENCE OF OPERATION.
DESIGN INTENT: GENERAL
FRESH AIR IS CONNECTED TO AC-1 WITH A SUPPLY AIR TEMPERATURE RESET
SCHEDULE AS FOLLOWS:
OAT = 55 °F=>SAT = 60 °F
OAT = 75 °F=>SAT = 55 °F
EXHAUST AIR IS CONNECTED TO EF-1
DESIGN INTENT: W162A/W162D BEHAVIOR ROOMS
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE VENTILATION AND COOLING AIR. AN
ELECTRIC DUCT HEATER PROVIDES HEATING. OCCUPIED/UNOCCUPIED CONTROL
STRATEGY SHALL BE IMPLEMENTED. ROOMS ARE TO BE NEGATIVELY PRESSURIZED
WITH RESPECT TO THE ANTE ROOM.
LOAD SHED: THE ZONE SHALL REMAIN UNDER CONTROL UNDER ALL STEAM AND
CHILLED WATER LOAD SHED LEVELS.
DESIGN INTENT: W162E BEHAVIOR ROOM
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE VENTILATION AND COOLING AIR. AN
ELECTRIC DUCT HEATER PROVIDES HEATING. OCCUPIED/UNOCCUPIED CONTROL
STRATEGY SHALL BE IMPLEMENTED. ROOMS ARE TO BE NEGATIVELY PRESSURIZED
WITH RESPECT TO THE ANTE ROOM. A SUPPLEMENTAL COOLING ONLY FAN COIL IS
PROVIDED FOR FUTURE CONVERSION TO AN IMAGING SPACE.
LOAD SHED: THE ZONE SHALL REMAIN UNDER CONTROL UNDER ALL STEAM AND
CHILLED WATER LOAD SHED LEVELS.
DESIGN INTENT: W162B/W162C HOLDING ROOMS
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE A CONSTANT VOLUME OF 10-15 AIR
CHANGES PER HOUR OF VENTILATION AIR. AN ELECTRIC DUCT HEATER PROVIDES
HEATING. COOLING IS PROVIDED VIA THE VENTILATION AIR. CONSTANT VOLUME
CONTROL STRATEGY SHALL BE IMPLEMENTED. ROOMS ARE TO BE NEGATIVELY
PRESSURIZED WITH RESPECT TO THE ANTE ROOM.
LOAD SHED: THE ZONE SHALL REMAIN UNDER CONTROL UNDER ALL STEAM AND
CHILLED WATER LOAD SHED LEVELS.
DESIGN INTENT: W154 ANTE ROOM
FRESH AIR IS PROVIDED VIA ONE OF THE ADJACENT BEHAVIOR ROOMS
FRESH AIR FROM AC-1 IS SIZED TO MAINTAIN POSITIVE PRESSURE TO THE BEHAVIOR
AND/OR HOLDING ROOMS, AND A NEGATIVE PRESSURE TO THE CORRIDOR.
HUMIDITY CONTROL
SETPOINT:45% ± 5% RH
DUCT HUMIDITY HIGH LIMIT:95%
THE BACS SHALL POLL EACH SPACE HUMIDITY LEVEL. THE HUMIDIFIER CONTROL
VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE SPACE WITH THE LOWEST
HUMIDITY LEVEL AT SETPOINT.
SAFETIES
THE BACS SHALL MONITOR THE STATUS OF THE FIRE/SMOKE DAMPER. THE DAMPER
SHALL CLOSE WHENEVER AC-1 IS OFF VIA COORDINATION WITH THE FIRE ALARM
SYSTEM.
THE HUMIDIFIER SHALL BE INDEXED OFF UPON LOSS OF AIRFLOW AS DETERMINED BY
THE AIR PROVING SWITCH AS WELL AS WHEN THE DUCT HUMIDITY LIMIT IS EXCEEDED.
THE ELECTRIC DUCT COIL SHALL INDEX OFF WHENEVER THE INTEGRAL AIR PROVING
SWITCH DOES NOT SENSE AIRFLOW
LIGHTING
THE FOLLOWING LIGHTING CONTROLS ARE REQUIRED TO BE PROVIDED FOR THIS
ZONE:
• MANUAL ON/OFF/DIMMING CONTROL
• VACANCY SENSING –MANUAL ON/AUTOMATIC OFF
SEQUENCE OF OPERATION FOR BEHAVIOR ROOMS W162A/W162D/W162E
OCCUPANCY MODES
ZONE OCCUPANCY SCHEDULE: 6 AM TO 6 PM, MONDAY -FRIDAY
ZONE OCCUPANCY IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE ZONE SHALL INDEX TO OCCUPIED
MODE AND OPERATE FOR A MINIMUM OF 30 MINUTES.
OCCUPIED/OCCUPIED SETBACK MODE: THE ZONE SHALL INDEX BETWEEN OCCUPIED
AND OCCUPIED SETBACK MODES DURING THE SCHEDULED OCCUPANCY PERIOD BASED
ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE ZONE OCCUPANCY/VACANCY
SENSOR. THE ZONE SHALL INDEX TO OCCUPIED SETBACK MODE WHEN OCCUPANCY IS
NOT SENSED FOR A PERIOD OF 30 MINUTES.
UNOCCUPIED MODE: THE ZONE SHALL INDEX TO UNOCCUPIED MODE OUTSIDE OF THE
TIME OF DAY SCHEDULE. IF THE ZONE BECOMES OCCUPIED DURING THE SCHEDULED
UNOCCUPIED PERIOD BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE
ZONE OCCUPANCY/VACANCY SENSOR, THE ZONE SHALL INDEX TO OCCUPIED MODE
FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO UNOCCUPIED
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 15 MINUTES.
VENTILATION CONTROL
VENTILATION RATE IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR VALVES
SHALL INDEX TO MAXIMUM AIRFLOW POSITION AND OPERATE FOR A MINIMUM OF 30
MINUTES.
OCCUPIED/OCCUPIED SETBACK OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR
VALVES SHALL INDEX BETWEEN UNOCCUPIED AND OCCUPIED MINIMUM POSITIONS
BASED ON SPACE OCCUPANCY AS DETERMINED BY THE SPACE OCCUPANCY SENSOR.
UNOCCUPIED MODE: WHEN THE ZONE IS UNOCCUPIED, THE SUPPLY AND EXHAUST AIR
VALVES SHALL BE AT MINIMUM POSITIONS.
TEMPERATURE CONTROL
OCCUPIED SETPOINT: 72 °F ± 2.0 °F
UNOCCUPIED HEATING SETPOINT:72 °F -6.0 °F
UNOCCUPIED COOLING SETPOINT:72 °F + 6.0 °F
W162A/W162B: OCCUPIED/UNOCCUPIED CONTROL:
• HEATING CONTROL: IF THE ZONE TEMPERATURE FALLS BELOW SETPOINT, THE
ELECTRIC REHEAT COIL SHALL INDEX ON AND MODULATE AS NEEDED TO MAINTAIN
SETPOINT.
• COOLING CONTROL: IF THE ZONE TEMPERATURE RISES ABOVE SETPOINT WHEN
THE SPACE IS OCCUPIED, THE ELECTRIC REHEAT COIL SHALL INDEX OFF AND THE
SUPPLY AND EXHAUST AIR VALVES SHALL MODULATE AS NEEDED BETWEEN
OCCUPIED MINIMUM AND OCCUPIED MAXIMUM POSITIONS TO MAINTAIN SETPOINT.
IF THE ZONE TEMPERATURE RISES ABOVE SETPOINT WHEN THE SPACE IS IN
OCCUPIED SETBACK OR UNOCCUPIED MODES, THE THE SUPPLY AND EXHAUST AIR
VALVES SHALL MODULATE AS NEEDED TO MAINTAIN SETPOINT.
W162E TEMPERATURE CONTROL
OCCUPIED CONTROL:
• HEATING CONTROL: IF THE ZONE TEMPERATURE FALLS BELOW SETPOINT, THE FAN
COIL UNIT SHALL BE OFF AND THE CHILLED WATER CONTROL VALVE SHALL CLOSE.
THE ELECTRIC REHEAT COIL SHALL INDEX ON AND MODULATE AS NEEDED TO
MAINTAIN SETPOINT.
• COOLING CONTROL: IF THE ZONE TEMPERATURE RISES ABOVE SETPOINT, THE
ELECTRIC REHEAT COIL SHALL INDEX OFF. THE FAN COIL UNIT SHALL INDEX ON AND
OPERATE AT MINIMUM SPEED. THE CHILLED WATER CONTROL VALVE SHALL
MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT. IF THE ZONE IS
NOT AT SETPOINT WITH THE CHILLED WATER CONTROL VALVE FULLY OPEN, THE
FAN COIL UNIT SPEED SHALL INCREASE AS NEEDED TO MAINTAIN SETPOINT.
UNOCCUPIED COOLING CONTROL:
• HEATING CONTROL: IF THE ZONE FALL BELOW THE UNOCCUPIED HEATING
SETPOINT, THE FAN COIL UNIT SHALL BE OFF AND THE CHILLED WATER CONTROL
VALVES SHALL CLOSE. THE ELECTRIC REHEAT COIL SHALL INDEX ON AND
MODULATE AS NEEDED TO MAINTAIN SETPOINT.
• COOLING CONTROL: IF THE ZONE RISES ABOVE THE UNOCCUPIED COOLING
SETPOINT, THE ELECTRIC DUCT COIL SHALL INDEX OFF. THE FAN COIL UNIT SHALL
INDEX ON AND OPERATE AT MINIMUM SPEED. THE CHILLED WATER CONTROL
VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT.
IF THE ZONE IS NOT AT SETPOINT WITH THE CHILLED WATER CONTROL VALVES
FULLY OPEN, THE FAN COIL UNIT SPEED SHALL INCREASE AS NEEDED TO MAINTAIN
SETPOINT.
THE CHILLED WATER CONTROL VALVE SHALL BE CLOSED WHENEVER THE FAN COIL
UNITS ARE OFF.
LIGHTING
THE FOLLOWING LIGHTING CONTROLS ARE REQUIRED TO BE PROVIDED FOR THIS
ZONE:
• MANUAL ON/OFF/DIMMING CONTROL
• VACANCY SENSING –MANUAL ON/AUTOMATIC OFF
SEQUENCE OF OPERATION FOR HOLDING ROOM W162B/W162C
OCCUPANCY MODES
ZONE OCCUPANCY SCHEDULE: DAY/NIGHT SCHEDULE COORDINATED WITH THE
RESEARCH GROUP
VENTILATION CONTROL
THE SUPPLY AND EXHAUST AIR VALVES SHALL MODULATE TO MAINTAIN THE CONSTANT
VOLUME AIRFLOW SETPOINT.
TEMPERATURE CONTROL
SETPOINT: 72 °F ± 2.0 °F
HEATING CONTROL: IF THE ZONE TEMPERATURE FALLS BELOW SETPOINT, THE
ELECTRIC REHEAT COIL SHALL INDEX ON AND MODULATE AS NEEDED TO MAINTAIN
SETPOINT.
COOLING CONTROL: IF THE ZONE TEMPERATURE RISES ABOVE SETPOINT, THE
ELECTRIC REHEAT COIL SHALL INDEX OFF.
LIGHTING
TWO LIGHTING CIRCUITS SHALL BE PROVIDED. ONE CIRCUITED TO WHITE DAY LIGHTS
AND ONE CIRCUITED TO RED NIGHT LIGHTS. WHEN THE DAY LIGHTS ARE SCHEDULED
ON, THEY SHALL GRADUALLY TURN ON UNTIL THE LIGHT LEVEL REACHES SETPOINT AS
MEASURED BY A CEILING MOUNTED LIGHTING SENSOR. LOCAL SWITCHES SHALL BE
PROVIDED TO PERMIT STAFF TO BYPASS THE LIGHTS FOR CLEANING AND ANIMAL CARE.
IF THE LIGHTS ARE SCHEDULED TO BE IN DAY MODE AND A LOCAL OVERRIDE SWITCH IS
ENGAGED, THE WHITE LIGHTS WILL INDEX TO FULL POWER AND REMAIN ON UNTIL
EITHER THE SWITCH IS RETURNED TO AUTO OR A PREDETERMINED AMOUNT OF TIME
HAS PASSED, AT WHICH POINT THE LIGHTS RETURN TO THE SCHEDULED DAY STATE
AND MAINTAIN SETPOINT.
IF THE LIGHTS ARE SCHEDULED TO BE IN NIGHT MODE AND A LOCAL OVERRIDE SWITCH
IS ENGAGED, THE RED LIGHTS WILL INDEX ON AND REMAIN ON UNTIL EITHER THE
SWITCH IS RETURNED TO AUTO OR A PREDETERMINED AMOUNT OF TIME HAS PASSED.
IF THE LIGHTING IS MANUALLY OVERRIDEN USING THE LOCAL SWITCHES AND THE
ROOM SCHEDULE INDEXES FROM DAY TO NIGHT (OR VICE/VERSA), THE LIGHTS IN
OVERRIDE SHALL CHANGE ACCORDINGLY.
W162 CONTROL POINTS LIST SCHEDULE
POINT
#CONTROL POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW
ON
GRAPHIC NOTESBI BO AI AO AV BV SCH TREND
ALARM
ALARM DESCRIPTIONBACS EMCS
1 FIRE/SMOKE DAMPER STATUS (OPEN/CLOSED) X X X
2 HUMIDIFIER CONTROL VALVE POSITION COMMAND X X X
3 HUMIDIFIER AIR PROVING SWITCH X X X LOSS OF AIRFLOW X
4 HUMIDIFIER DISCHARGE AIR TEMPERATURE X X X TEMPERATURE ALARM / SENSOR FAILURE X
5 HUMIDIFIER DISCHARGE HIGH LIMIT (%RH)X X X X EXCEEDS 95% RELATIVE HUMIDITY X
6 SUPPLY AIR VALVE FLOW FEEDBACK/SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X
7 SUPPLY AIR VALVE POSITION FEEDBACK (%)X X X
8 SUPPLY AIR VALVE COMMAND X X X
9 ELECTRIC HEATING COIL COMMAND X X X
10 ELECTRIC HEATING COIL AIR PROVING SWITCH X X X LOSS OF AIRFLOW X
11 ELECTRIC HEATING COIL DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X
12 FCU ECM FAN START/STOP/SPEED X X X
13 FCU ECM STATUS (ON/OFF)X X X FAN FAILURE X
14 FCU COOLING COIL CONTROL VALVE POSITION COMMAND X X X
15 FCU OVERFLOW SWITCH STATUS X X X OVERFLOW X
16 FCU DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X
17 EXHAUST AIR VALVE FLOW FEEDBACK /SETPOINT (CFM)X X X DEVIATION FROM SETPOINT X
18 EXHAUST AIR VALVE POSITION FEEDBACK (%)X X X
19 EXHAUST AIR VALVE FLOW COMMAND (CFM)X X X
20 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X
21 SPACE HUMIDITY/SETPOINT X X X X DEVIATION FROM SETPOINT X
22 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X
23 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X
24 LIGHTING MANUAL DIMMING (%)X X X
25 LIGHTING VACANCY SENSING (ON/OFF)X X X
26 LIGHTING CONTACT RELAY (OPEN/CLOSED)X X X
27 SUPPLY AIR VALVE FLOW FEEDBACK/SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162A, W162D
28 SUPPLY AIR VALVE POSITION FEEDBACK (%)X X X TYPICAL FOR W162A, W162D
29 SUPPLY AIR VALVE COMMAND X X X TYPICAL FOR W162A, W162D
30 ELECTRIC HEATING COIL COMMAND X X X TYPICAL FOR W162A, W162D
31 ELECTRIC HEATING COIL AIR PROVING SWITCH X X X LOSS OF AIRFLOW X TYPICAL FOR W162A, W162D
32 ELECTRIC HEATING COIL DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X
33 EXHAUST AIR VALVE FLOW FEEDBACK /SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162A, W162D
34 EXHAUST AIR VALVE POSITION FEEDBACK (%)X X X TYPICAL FOR W162A, W162D
35 EXHAUST AIR VALVE FLOW COMMAND (CFM)X X X TYPICAL FOR W162A, W162D
36 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162A, W162D
37 SPACE HUMIDITY/SETPOINT X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162A, W162D
38 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X TYPICAL FOR W162A, W162D
39 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X TYPICAL FOR W162A, W162D
40 LIGHTING MANUAL DIMMING (%)X X X TYPICAL FOR W162A, W162D
41 LIGHTING CONTACT RELAY (OPEN/CLOSED) X X X TYPICAL FOR W162A, W162D
42 LIGHTING CONTACT RELAY (OPEN/CLOSED)X X X TYPICAL FOR W162A, W162D
43 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X
44 LIGHTING MANUAL DIMMING (%)X X X
45 LIGHTING VACANCY SENSING (ON/OFF)X X X
46 LIGHTING CONTACT RELAY (OPEN/CLOSED)X X X
47 SUPPLY AIR VALVE FLOW FEEDBACK/SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162B, W162C
48 SUPPLY AIR VALVE POSITION FEEDBACK (%)X X X TYPICAL FOR W162B, W162C
49 SUPPLY AIR VALVE COMMAND X X X TYPICAL FOR W162B, W162C
50 ELECTRIC HEATING COIL COMMAND X X X TYPICAL FOR W162B, W162C
51 ELECTRIC HEATING COIL AIR PROVING SWITCH X X X LOSS OF AIRFLOW X TYPICAL FOR W162B, W162C
52 ELECTRIC HEATING COIL DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X TYPICAL FOR W162B, W162C
53 EXHAUST AIR VALVE FLOW FEEDBACK /SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162B, W162C
54 EXHAUST AIR VALVE POSITION FEEDBACK (%)X X X TYPICAL FOR W162B, W162C
55 EXHAUST AIR VALVE FLOW COMMAND (CFM)X X X TYPICAL FOR W162B, W162C
56 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162B, W162C
57 SPACE HUMIDITY/SETPOINT X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W162B, W162C
58 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X X TYPICAL FOR W162B, W162C
59 LIGHTING MANUAL DIMMING (%)X X X X TYPICAL FOR W162B, W162C
60 LIGHTING VACANCY SENSING (ON/OFF)X X X TYPICAL FOR W162B, W162C
61 WHITE LIGHT CONTACT RELAY (OPEN/CLOSED)X X X X TYPICAL FOR W162B, W162C
62 RED LIGHT CONTACT RELAY (OPEN/CLOSED)X X X X TYPICAL FOR W162B, W162C
63 DIMMING WHITE LIGHT FIXTURE COMMAND X X X TYPICAL FOR W162B, W162C
64 AUTOMATIC DIMMING CONTROL LIGHT SENSOR (FOOT-CANDLES) X X X X SENSOR FAILURE X TYPICAL FOR W162B, W162C
65 WHITE LIGHT STATUS (ON/OFF)X X X TYPICAL FOR W162B, W162C
66 RED LIGHT STATUS (ON/OFF)X X X TYPICAL FOR W162B, W162C
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
POSITION
FLOW MOD
T
TO EF-1
POSITION
FLOW MOD
SAV-154-1
SAV-154-2
SAV-154-3
EDH-154-1EDH-154-2EDH-154-3P
6
7
8
10
15
16
11
17
WS
18
D
19
OS
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
21
R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
FROM
AC-1 FSD-2120 VAC
LINE VOLTAGE R
AOM
TO
FIRE ALARM
CIRCUIT
1
N.C.
H-1
2
TP
3 4
H
5
277 VAC
LINE VOLTAGE
W154A, W154B, W154C
EAV-154-1
EAV-154-2
EAV-154-3
WS
22
D
23
14
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
25
R277 VA
LINE VOLTAGE
W154
FROM
SAV-154-1
T sa
d
H
12 13
MOD
9 VS
20
VS
24 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-305
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONNOT TO SCALE1W154 CONTROLS
SEQUENCE OF OPERATION
THE HVAC AND LIGHTING IN THE ZONE SHALL BE CONTROLLED BY THE BUILDING
AUTOMATION AND CONTROL SYSTEM (BACS). THE PROJECT SHALL EXTEND THE
EXISTING AUTOMATED LOGIC CONTROL SYSTEM TO SERVE THIS ZONE.
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE LIGHTING CONTROLS ARE TO BE TIED TO THE BACS FOR HVAC TEMPERATURE
SETBACKS WITH THE USE OF OCCUPANCY/VACANCY SENSING.
HVAC SYSTEM COMMISSIONING: THE CONTRACTOR SHALL DEMONSTRATE TO THE
OWNER’S REPRESENTATIVE THAT THE HVAC CONTROL SYSTEMS ARE CALIBRATED,
ADJUSTED, AND ARE WORKING PER THE PRESCRIBED SEQUENCE OF OPERATION.
FUNCTIONAL TESTING OF THE LIGHTING CONTROL SYSTEM: THE CONTRACTOR SHALL
DEMONSTRATE TO THE OWNER’S REPRESENTATIVE THAT THE CONTROL HARDWARE
AND SOFTWARE IS CALIBRATED, ADJUSTED, PROGRAMMED AND CONTROLLING IN
ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTIONS AND
SEQUENCE OF OPERATION.
DESIGN INTENT: W154A/W154B/W154C BEHAVIOR ROOMS
FRESH AIR IS CONNECTED TO AC-1 WITH A SUPPLY AIR TEMPERATURE RESET
SCHEDULE AS FOLLOWS:
OAT = 55 °F=>SAT = 60 °F
OAT = 75 °F=>SAT = 55 °F
EXHAUST AIR IS CONNECTED TO EF-1
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE VENTILATION AND COOLING AIR. AN
ELECTRIC DUCT HEATER PROVIDES HEATING. OCCUPIED/UNOCCUPIED CONTROL
STRATEGY SHALL BE IMPLEMENTED. ROOMS ARE TO BE NEGATIVELY PRESSURIZED
WITH RESPECT TO THE ANTE ROOM.
LOAD SHED: THE ZONE SHALL REMAIN UNDER CONTROL UNDER ALL STEAM AND
CHILLED WATER LOAD SHED LEVELS.
DESIGN INTENT: W154 ANTE ROOM
FRESH AIR IS PROVIDED VIA ONE OF THE ADJACENT BEHAVIOR ROOMS
FRESH AIR FROM AC-1 IS SIZED TO MAINTAIN POSITIVE PRESSURE TO THE BEHAVIOR
AND/OR HOLDING ROOMS, AND A NEGATIVE PRESSURE TO THE CORRIDOR.
OCCUPANCY MODES
ZONE OCCUPANCY SCHEDULE: 6 AM TO 6 PM, MONDAY -FRIDAY
ZONE OCCUPANCY IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE ZONE SHALL INDEX TO OCCUPIED
MODE AND OPERATE FOR A MINIMUM OF 30 MINUTES.
OCCUPIED/OCCUPIED SETBACK MODE: THE ZONE SHALL INDEX BETWEEN OCCUPIED
AND OCCUPIED SETBACK MODES DURING THE SCHEDULED OCCUPANCY PERIOD BASED
ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE ZONE OCCUPANCY/VACANCY
SENSOR. THE ZONE SHALL INDEX TO OCCUPIED SETBACK MODE WHEN OCCUPANCY IS
NOT SENSED FOR A PERIOD OF 30 MINUTES.
UNOCCUPIED MODE: THE ZONE SHALL INDEX TO UNOCCUPIED MODE OUTSIDE OF THE
TIME OF DAY SCHEDULE. IF THE ZONE BECOMES OCCUPIED DURING THE SCHEDULED
UNOCCUPIED PERIOD BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE
ZONE OCCUPANCY/VACANCY SENSOR, THE ZONE SHALL INDEX TO OCCUPIED MODE
FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO UNOCCUPIED
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 15 MINUTES.
VENTILATION CONTROL
VENTILATION RATE IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR VALVES
SHALL INDEX TO MAXIMUM AIRFLOW POSITION AND OPERATE FOR A MINIMUM OF 30
MINUTES.
OCCUPIED/OCCUPIED SETBACK OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR
VALVES SHALL INDEX BETWEEN UNOCCUPIED AND OCCUPIED MINIMUM POSITIONS
BASED ON SPACE OCCUPANCY AS DETERMINED BY THE SPACE OCCUPANCY SENSOR.
UNOCCUPIED MODE: WHEN THE ZONE IS UNOCCUPIED, THE SUPPLY AND EXHAUST AIR
VALVES SHALL BE AT MINIMUM POSITIONS.
TEMPERATURE CONTROL
OCCUPIED SETPOINT: 72 °F ± 2.0 °F
UNOCCUPIED HEATING SETPOINT:72 °F -6.0 °F
UNOCCUPIED COOLING SETPOINT:72 °F + 6.0 °F
OCCUPIED/UNOCCUPIED CONTROL:
• HEATING CONTROL: IF THE ZONE TEMPERATURE FALLS BELOW SETPOINT, THE
ELECTRIC REHEAT COIL SHALL INDEX ON AND MODULATE AS NEEDED TO MAINTAIN
SETPOINT.
• COOLING CONTROL: IF THE ZONE TEMPERATURE RISES ABOVE SETPOINT WHEN
THE SPACE IS OCCUPIED, THE ELECTRIC REHEAT COIL SHALL INDEX OFF AND THE
SUPPLY AND EXHAUST AIR VALVES SHALL MODULATE AS NEEDED BETWEEN
OCCUPIED MINIMUM AND OCCUPIED MAXIMUM POSITIONS TO MAINTAIN SETPOINT.
IF THE ZONE TEMPERATURE RISES ABOVE SETPOINT WHEN THE SPACE IS IN
OCCUPIED SETBACK OR UNOCCUPIED MODES, THE THE SUPPLY AND EXHAUST AIR
VALVES SHALL MODULATE AS NEEDED TO MAINTAIN SETPOINT.
HUMIDITY CONTROL
SETPOINT:45% ± 5% RH
DUCT HUMIDITY HIGH LIMIT:95%
THE BACS SHALL POLL EACH SPACE HUMIDITY LEVEL. THE HUMIDIFIER CONTROL
VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE SPACE WITH THE LOWEST
HUMIDITY LEVEL AT SETPOINT.
SAFETIES
THE BACS SHALL MONITOR THE STATUS OF THE FIRE/SMOKE DAMPER. THE DAMPER
SHALL CLOSE WHENEVER AC-1 IS OFF VIA COORDINATION WITH THE FIRE ALARM
SYSTEM.
THE HUMIDIFIER SHALL BE INDEXED OFF UPON LOSS OF AIRFLOW AS DETERMINED BY
THE AIR PROVING SWITCH AS WELL AS WHEN THE DUCT HUMIDITY LIMIT IS EXCEEDED.
THE ELECTRIC DUCT COIL SHALL INDEX OFF WHENEVER THE INTEGRAL AIR PROVING
SWITCH DOES NOT SENSE AIRFLOW
LIGHTING
THE FOLLOWING LIGHTING CONTROLS ARE REQUIRED TO BE PROVIDED FOR THIS
ZONE:
• MANUAL ON/OFF/DIMMING CONTROL
• VACANCY SENSING –MANUAL ON/AUTOMATIC OFF
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
W154 SUITE CONTROL POINTS LIST SCHEDULE
POINT
#CONTROL POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW
ON
GRAPHIC NOTESBI BO AI AO AV BV SCH TREND
ALARM
ALARM DESCRIPTIONBACS EMCS
1 FIRE/SMOKE DAMPER STATUS (OPEN/CLOSED) X X X
2 HUMIDIFIER CONTROL VALVE POSITION COMMAND X X X
3 HUMIDIFIER AIR PROVING SWITCH X X X LOSS OF AIRFLOW X
4 HUMIDIFIER DISCHARGE AIR TEMPERATURE X X X TEMPERATURE ALARM / SENSOR FAILURE X
5 HUMIDIFIER DISCHARGE HIGH LIMIT (%RH)X X X X EXCEEDS 95% RELATIVE HUMIDITY X
6 SUPPLY AIR VALVE FLOW FEEDBACK/SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W154A, W154B, W154C
7 SUPPLY AIR VALVE POSITION FEEDBACK (%)X X X TYPICAL FOR W154A, W154B, W154C
8 SUPPLY AIR VALVE COMMAND X X X TYPICAL FOR W154A, W154B, W154C
9 ELECTRIC HEATING COIL COMMAND X X X TYPICAL FOR W154A, W154B, W154C
10 ELECTRIC HEATING COIL AIR PROVING SWITCH X X X LOSS OF AIRFLOW X TYPICAL FOR W154A, W154B, W154C
11 ELECTRIC HEATING COIL DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X TYPICAL FOR W154A, W154B, W154C
12 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W154A, W154B, W154C
13 SPACE HUMIDITY/SETPOINT X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W154A, W154B, W154C
14 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X TYPICAL FOR W154A, W154B, W154C
15 EXHAUST AIR VALVE FLOW FEEDBACK /SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X TYPICAL FOR W154A, W154B, W154C
16 EXHAUST AIR VALVE POSITION FEEDBACK (%)X X X TYPICAL FOR W154A, W154B, W154C
17 EXHAUST AIR VALVE FLOW COMMAND (CFM)X X X TYPICAL FOR W154A, W154B, W154C
18 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X TYPICAL FOR W154A, W154B, W154C
19 LIGHTING MANUAL DIMMING (%)X X X TYPICAL FOR W154A, W154B, W154C
20 LIGHTING VACANCY SENSING (ON/OFF)X X X TYPICAL FOR W154A, W154B, W154C
21 LIGHTING CONTACT RELAY (OPEN/CLOSED)X X X TYPICAL FOR W154A, W154B, W154C
22 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X
23 LIGHTING MANUAL DIMMING (%)X X X
24 LIGHTING VACANCY SENSING (ON/OFF)X X X
25 LIGHTING CONTACT RELAY (OPEN/CLOSED)X X X
POSITION
FLOW MOD
T
TO EF-1
POSITION
FLOW MOD
SAV-156-1
EDH-156-1P
6
7
8
10
12
13
11
14
WS
18
D
19
OS
17
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
21
R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
FROM AC-1
FSD-3120 VAC LINE VOLTAGE R
AOM
TO FIRE ALARM CIRCUIT
1
N.C.
H-2
2
TP
3 4
H
5
277 VAC LINE VOLTAGE
W156
EAV-156-1
T sa
d
H
15 16
MOD
9
VS
20 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-306
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONNOT TO SCALE1W156 CONTROLS
SEQUENCE OF OPERATION
THE HVAC AND LIGHTING IN THE ZONE SHALL BE CONTROLLED BY THE BUILDING
AUTOMATION AND CONTROL SYSTEM (BACS). THE PROJECT SHALL EXTEND THE
EXISTING AUTOMATED LOGIC CONTROL SYSTEM TO SERVE THIS ZONE.
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE LIGHTING CONTROLS ARE TO BE TIED TO THE BACS FOR HVAC TEMPERATURE
SETBACKS WITH THE USE OF OCCUPANCY/VACANCY SENSING.
HVAC SYSTEM COMMISSIONING: THE CONTRACTOR SHALL DEMONSTRATE TO THE
OWNER’S REPRESENTATIVE THAT THE HVAC CONTROL SYSTEMS ARE CALIBRATED,
ADJUSTED, AND ARE WORKING PER THE PRESCRIBED SEQUENCE OF OPERATION.
FUNCTIONAL TESTING OF THE LIGHTING CONTROL SYSTEM: THE CONTRACTOR
SHALL DEMONSTRATE TO THE OWNER’S REPRESENTATIVE THAT THE CONTROL
HARDWARE AND SOFTWARE IS CALIBRATED, ADJUSTED, PROGRAMMED AND
CONTROLLING IN ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION
INSTRUCTIONS AND SEQUENCE OF OPERATION.
DESIGN INTENT: W156 PROCEDURE ROOM
FRESH AIR IS CONNECTED TO AC-1 WITH A SUPPLY AIR TEMPERATURE RESET
SCHEDULE AS FOLLOWS:
OAT = 55 °F=>SAT = 60 °F
OAT = 75 °F=>SAT = 55 °F
EXHAUST AIR IS CONNECTED TO EF-1
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE VENTILATION AND COOLING AIR. AN
ELECTRIC DUCT HEATER PROVIDES HEATING. OCCUPIED/UNOCCUPIED CONTROL
STRATEGY SHALL BE IMPLEMENTED. ROOM IS TO BE NEGATIVELY PRESSURIZED
WITH RESPECT TO THE CORRIDOR.
LOAD SHED: THE ZONE SHALL REMAIN UNDER CONTROL UNDER ALL STEAM AND
CHILLED WATER LOAD SHED LEVELS.
OCCUPANCY MODES
ZONE OCCUPANCY SCHEDULE: 6 AM TO 6 PM, MONDAY -FRIDAY
ZONE OCCUPANCY IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE ZONE SHALL INDEX TO
OCCUPIED MODE AND OPERATE FOR A MINIMUM OF 30 MINUTES.
OCCUPIED/OCCUPIED SETBACK MODE: THE ZONE SHALL INDEX BETWEEN
OCCUPIED AND OCCUPIED SETBACK MODES DURING THE SCHEDULED OCCUPANCY
PERIOD BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE ZONE
OCCUPANCY/VACANCY SENSOR. THE ZONE SHALL INDEX TO OCCUPIED SETBACK
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 30 MINUTES.
UNOCCUPIED MODE: THE ZONE SHALL INDEX TO UNOCCUPIED MODE OUTSIDE OF
THE TIME OF DAY SCHEDULE. IF THE ZONE BECOMES OCCUPIED DURING THE
SCHEDULED UNOCCUPIED PERIOD BASED ON A MANUAL INPUT OR AUTOMATIC
INPUT FROM THE ZONE OCCUPANCY/VACANCY SENSOR, THE ZONE SHALL INDEX TO
OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX
BACK TO UNOCCUPIED MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF
15 MINUTES.
VENTILATION CONTROL
VENTILATION RATE IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR
VALVES SHALL INDEX TO MAXIMUM AIRFLOW POSITION AND OPERATE FOR A
MINIMUM OF 30 MINUTES.
OCCUPIED/OCCUPIED SETBACK OCCUPANCY MODE: THE SUPPLY AND EXHAUST AIR
VALVES SHALL INDEX BETWEEN MINIMUM AND MAXIMUM POSITIONS BASED ON
SPACE OCCUPANCY AS DETERMINED BY THE SPACE OCCUPANCY SENSOR.
UNOCCUPIED MODE: WHEN THE ZONE IS UNOCCUPIED, THE SUPPLY AND EXHAUST
AIR VALVES SHALL BE AT MINIMUM POSITIONS.
TEMPERATURE CONTROL
OCCUPIED SETPOINT: 72 °F ± 2.0 °F
UNOCCUPIED HEATING SETPOINT:72 °F -6.0 °F
UNOCCUPIED COOLING SETPOINT:72 °F + 6.0 °F
OCCUPIED/UNOCCUPIED CONTROL:
• HEATING CONTROL: IF THE ZONE TEMPERATURE FALLS BELOW SETPOINT, THE
ELECTRIC REHEAT COIL SHALL INDEX ON AND MODULATE AS NEEDED TO
MAINTAIN SETPOINT.
• COOLING CONTROL: IF THE ZONE TEMPERATURE RISES ABOVE SETPOINT, THE
ELECTRIC REHEAT COIL SHALL INDEX OFF.
HUMIDITY CONTROL
SETPOINT:45% ± 5% RH
DUCT HUMIDITY HIGH LIMIT:95%
THE HUMIDIFIER CONTROL VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE
SPACE HUMIDITY AT SETPOINT.
SAFETIES
THE FAN COIL SHALL INDEX OFF AND THE CHILLED WATER CONTROL VALVE SHALL
CLOSE UPON ACTIVATION OF THE DRAIN PAN OVERFLOW SWITCH.
THE ELECTRIC DUCT COIL SHALL INDEX OFF WHENEVER THE INTEGRAL AIR PROVING
SWITCH DOES NOT SENSE AIRFLOW
THE BACS SHALL MONITOR THE STATUS OF THE FIRE/SMOKE DAMPER. THE DAMPER
SHALL CLOSE WHENEVER AC-1 IS OFF VIA COORDINATION WITH THE FIRE ALARM
SYSTEM.
THE HUMIDIFIER SHALL BE INDEXED OFF UPON LOSS OF AIRFLOW AS DETERMINED
BY THE AIR PROVING SWITCH AS WELL AS WHEN THE DUCT HUMIDITY LIMIT IS
EXCEEDED.
LIGHTING
THE FOLLOWING LIGHTING CONTROLS ARE REQUIRED TO BE PROVIDED FOR THIS
ZONE:
• MANUAL ON/OFF/DIMMING CONTROL
• VACANCY SENSING –MANUAL ON/AUTOMATIC OFF
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
W156 CONTROL POINTS LIST SCHEDULE
POINT
#CONTROL POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW
ON
GRAPHIC NOTESBI BO AI AO AV BV SCH TREND
ALARM
ALARM DESCRIPTIONBACS EMCS
1 FIRE/SMOKE DAMPER STATUS (OPEN/CLOSED) X X X
2 HUMIDIFIER CONTROL VALVE POSITION COMMAND X X X
3 HUMIDIFIER AIR PROVING SWITCH X X X LOSS OF AIRFLOW X
4 HUMIDIFIER DISCHARGE AIR TEMPERATURE X X X
5 HUMIDIFIER DISCHARGE HIGH LIMIT (%RH)X X X X EXCEEDS 95% RELATIVE HUMIDITY X
6 SUPPLY AIR VALVE FLOW FEEDBACK/SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X
7 SUPPLY AIR VALVE POSITION FEEDBACK (%)X X X
8 SUPPLY AIR VALVE COMMAND X X X
9 ELECTRIC HEATING COIL COMMAND X X X
10 ELECTRIC HEATING COIL AIR PROVING SWITCH X X X LOSS OF AIRFLOW X
11 ELECTRIC HEATING COIL DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X
12 EXHAUST AIR VALVE FLOW FEEDBACK /SETPOINT (CFM)X X X X DEVIATION FROM SETPOINT X
13 EXHAUST AIR VALVE POSITION FEEDBACK (%)X X X
14 EXHAUST AIR VALVE FLOW COMMAND (CFM)X X X
15 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X
16 SPACE HUMIDITY/SETPOINT X X X X DEVIATION FROM SETPOINT X
17 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X
18 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X
19 LIGHTING MANUAL DIMMING (%)X X X
20 LIGHTING VACANCY SENSING (ON/OFF)X X X
21 LIGHTING CONTACT RELAY (OPEN/CLOSED)X X X
N.C.
ECM
COOLING COILFCU-161-4 FROM AC-1
CV-4
T
LS
MOD CS 2
4
5
1
3
WS
9
D
10
T sa
d
H
6 7
OS
8
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
12
277 VAC LINE VOLTAGE R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
W161A
ZRT
VS
11 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-307
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONNOT TO SCALE1W161A CONTROLS
SEQUENCE OF OPERATION
THE HVAC AND LIGHTING IN THE ZONE SHALL BE CONTROLLED BY THE BUILDING
AUTOMATION AND CONTROL SYSTEM (BACS). THE PROJECT SHALL EXTEND THE
EXISTING AUTOMATED LOGIC CONTROL SYSTEM TO SERVE THIS ZONE.
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE LIGHTING CONTROLS ARE TO BE TIED TO THE BACS FOR HVAC TEMPERATURE
SETBACKS WITH THE USE OF OCCUPANCY/VACANCY SENSING.
HVAC SYSTEM COMMISSIONING: THE CONTRACTOR SHALL DEMONSTRATE TO THE
OWNER’S REPRESENTATIVE THAT THE HVAC CONTROL SYSTEMS ARE CALIBRATED,
ADJUSTED, AND ARE WORKING PER THE PRESCRIBED SEQUENCE OF OPERATION.
FUNCTIONAL TESTING OF THE LIGHTING CONTROL SYSTEM: THE CONTRACTOR SHALL
DEMONSTRATE TO THE OWNER’S REPRESENTATIVE THAT THE CONTROL HARDWARE
AND SOFTWARE IS CALIBRATED, ADJUSTED, PROGRAMMED AND CONTROLLING IN
ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTIONS AND
SEQUENCE OF OPERATION.
DESIGN INTENT: W161A MEETING ROOM
FRESH AIR IS CONNECTED TO AC-1 WITH A SUPPLY AIR TEMPERATURE RESET
SCHEDULE AS FOLLOWS:
OAT = 55 °F=>SAT = 60 °F
OAT = 75 °F=>SAT = 55 °F
EXHAUST AIR IS CONNECTED TO EF-1
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE VENTILATION AIR VIA CONSTANT VOLUME
ZONE TERMINAL DIFFUSERS (ZRT) FOR A MAXIMUM OF 4 SPACE OCCUPANTS. THE FAN
COIL PROVIDES COOLING.
LOAD SHED:
• ZONE SHALL BE INDEXED TO UNOCCUPIED MODE DURING STEAM LOAD SHED 1, 2, 3,
4. THE SPACE TEMPERATURE SETPOINT SHALL BE INDEXED TO 60 °F DURING STEAM
LOAD SHED 5, 6
• ZONE SHALL BE INDEXED TO UNOCCUPIED MODE DURING CHILLED WTAER LOAD
SHED 1, 2, 3, 4.
OCCUPANCY MODES
ZONE OCCUPANCY SCHEDULE: 6 AM TO 6 PM, MONDAY -FRIDAY
ZONE OCCUPANCY IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
OCCUPIED/OCCUPIED SETBACK MODE: THE ZONE SHALL INDEX BETWEEN OCCUPIED
AND OCCUPIED SETBACK MODES DURING THE SCHEDULED OCCUPANCY PERIOD BASED
ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE ZONE OCCUPANCY/VACANCY
SENSOR. THE ZONE SHALL INDEX TO OCCUPIED SETBACK MODE WHEN OCCUPANCY IS
NOT SENSED FOR A PERIOD OF 30 MINUTES.
UNOCCUPIED MODE: THE ZONE SHALL INDEX TO UNOCCUPIED MODE OUTSIDE OF THE
TIME OF DAY SCHEDULE. IF THE ZONE BECOMES OCCUPIED DURING THE SCHEDULED
UNOCCUPIED PERIOD BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE
ZONE OCCUPANCY/VACANCY SENSOR, THE ZONE SHALL INDEX TO OCCUPIED MODE
FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO UNOCCUPIED
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 15 MINUTES.
TEMPERATURE CONTROL
TEMPERATURE SETPOINTS:COOLING HEATING
OCCUPIED:75 °F ± 1.5 °F 70 °F ± 1.5 °F
OCCUPIED SETBACK:75 °F + 3 °F 70 °F -3 °F
UNOCCUPIED:75 °F + 6 °F 70 °F -6 °F
TEMPERATURE SETPOINTS ARE DETERMINED BY A COMBINATION OF A TIME OF DAY
SCHEDULE AND A SPACE OCCUPANCY/VACANCY SENSOR.
THE CHILLED WATER CONTROL VALVE SHALL BE CLOSED WHENEVER THE FAN COIL
UNITS ARE OFF.
OCCUPIED/OCCUPIED SETBACK MODES:
• INITIAL SCHEDULED ZONE OCCUPANCY: THE FAN COIL SHALL INDEX ON AND
OPERATE FOR A MINIMUM OF 30 MINUTES. AFTER 30 MINUTES, IF THERE IS NO CALL
FOR COOLING THE FAN COIL UNIT SHALL INDEX OFF.
• HEATING CONTROL: IF THE ZONE FALLS BELOW THE OCCUPIED/OCCUPIED
SETBACK HEATING SETPOINT, THE FAN COIL UNIT CHILLED WATER SHALL BE OFF
AND THE CONTROL VALVE SHALL CLOSE.
• COOLING CONTROL: IF THE ZONE RISES ABOVE THE OCCUPIED/OCCUPIED SETBACK
COOLING SETPOINT, THE FAN COIL SHALL INDEX ON AN OPERATE AT MINIMUM
SPEED. THE CHILLED WATER CONTROL VALVE SHALL MODULATE OPEN AS NEEDED
TO MAINTAIN THE ZONE AT SETPOINT. IF THE ZONE IS NOT AT SETPOINT WITH THE
CHILLED WATER CONTROL VALVE FULLY OPEN, THE FAN COIL UNIT SPEED SHALL
INCREASE AS NEEDED TO MAINTAIN SETPOINT.
UNOCCUPIED MODE:
• THE FAN COIL UNITS SHALL BE OFF.
• COOLING CONTROL: IF THE ZONE RISES ABOVE THE UNOCCUPIED COOLING
SETPOINT, THE FAN COIL UNIT SHALL INDEX ON AND OPERATE AT MINIMUM SPEED.
THE CHILLED WATER CONTROL VALVES SHALL MODULATE OPEN AS NEEDED TO
MAINTAIN THE ZONE AT SETPOINT. IF THE ZONE IS NOT AT SETPOINT WITH THE
CHILLED WATER CONTROL VALVES FULLY OPEN, THE FAN COIL UNIT SPEED SHALL
INCREASE AS NEEDED TO MAINTAIN SETPOINT.
SAFETIES
THE FAN COIL SHALL INDEX OFF AND THE CHILLED WATER CONTROL VALVE SHALL
CLOSE UPON ACTIVATION OF THE DRAIN PAN OVERFLOW SWITCH.
LIGHTING
THE FOLLOWING LIGHTING CONTROLS ARE REQUIRED TO BE PROVIDED FOR THIS ZONE:
• MANUAL ON/OFF/DIMMING CONTROL
• VACANCY SENSING –MANUAL ON/AUTOMATIC OFF
W161A CONTROL POINTS LIST SCHEDULE
POINT
#CONTROL POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW
ON
GRAPHIC NOTESBI BO AI AO AV BV SCH TREND
ALARM
ALARM DESCRIPTIONBACS EMCS
1 FCU ECM FAN START/STOP/SPEED X X X
2 FCU ECM STATUS (ON/OFF) X X X FAN FAILURE X
3 FCU COOLING COIL CONTROL VALVE POSITION
COMMAND
X X X
4 FCU OVERFLOW SWITCH STATUS X X X OVERFLOW X
5 FCU DISCHARGE AIR TEMPERATURE/SETPOINT X X X TEMPERATURE ALARM / SENSOR FAILURE X
6 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X
7 SPACE HUMIDITY X X X
8 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X
9 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X
10 LIGHTING MANUAL DIMMING (%)X X X
11 LIGHTING VACANCY SENSING (ON/OFF) X X X
12 LIGHTING CONTACT RELAY (OPEN/CLOSED) X X X
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
N.C.
ECM
F.L.COOLING COILFCU-161-3
FROM AC-1
CV-7
CV-3
T
LS
MOD CS 2
4
5
1
3
10
WS
17
D
18
OS
16
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
24
277 VA
LINE VOLTAGE R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
T sa
d
H
11 12EDH-161-2MOD
6
OS
15
LIGHT FIXTURES WITH
0-10 VDC CONTROL
REFER TO ELECTRICAL
DRAWINGS FOR QUANTITY
20
277 VAC
LINE VOLTAGE R
PROVIDE QUANTITY NEEDED FOR
COVERAGE PER MANUFACTURER'S
RECOMMENDATIONS
W161CW161B
WS
21
D
22
T sa
d
H
13 14
F.L.
CV-8
9
ZRT ZRT
FTR FTR
T
8
P
7
VS
19
VS
23 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-308
12971596
CONTROLS
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTIONNOT TO SCALE1W161B&C CONTROLS
SEQUENCE OF OPERATION
THE HVAC AND LIGHTING IN THE ZONE SHALL BE CONTROLLED BY THE BUILDING
AUTOMATION AND CONTROL SYSTEM (BACS). THE PROJECT SHALL EXTEND THE
EXISTING AUTOMATED LOGIC CONTROL SYSTEM TO SERVE THIS ZONE.
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE LIGHTING CONTROLS ARE TO BE TIED TO THE BACS FOR HVAC TEMPERATURE
SETBACKS WITH THE USE OF OCCUPANCY/VACANCY SENSING.
HVAC SYSTEM COMMISSIONING: THE CONTRACTOR SHALL DEMONSTRATE TO THE
OWNER’S REPRESENTATIVE THAT THE HVAC CONTROL SYSTEMS ARE CALIBRATED,
ADJUSTED, AND ARE WORKING PER THE PRESCRIBED SEQUENCE OF OPERATION.
FUNCTIONAL TESTING OF THE LIGHTING CONTROL SYSTEM: THE CONTRACTOR SHALL
DEMONSTRATE TO THE OWNER’S REPRESENTATIVE THAT THE CONTROL HARDWARE
AND SOFTWARE IS CALIBRATED, ADJUSTED, PROGRAMMED AND CONTROLLING IN
ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTIONS AND
SEQUENCE OF OPERATION.
DESIGN INTENT: W161B AND W161C OFFICES
FRESH AIR IS CONNECTED TO AC-1 WITH A SUPPLY AIR TEMPERATURE RESET
SCHEDULE AS FOLLOWS:
OAT = 55 °F=>SAT = 60 °F
OAT = 75 °F=>SAT = 55 °F
EXHAUST AIR IS CONNECTED TO EF-1
FRESH AIR FROM AC-1 IS SIZED TO PROVIDE VENTILATION AIR VIA CONSTANT VOLUME
ZONE TERMINAL DIFFUSERS (ZRT) FOR A MAXIMUM OF 2 OCCUPANTS IN EACH SPACE.
BASEBOARD RADIATION PROVIDES HEATING. A FAN COIL PROVIDES COOLING.
LOAD SHED:
• ZONE SHALL BE INDEXED TO UNOCCUPIED MODE DURING STEAM LOAD SHED 1, 2,
3, 4. THE SPACE TEMPERATURE SETPOINT SHALL BE INDEXED TO 60 °F DURING
STEAM LOAD SHED 5, 6
• ZONE SHALL BE INDEXED TO UNOCCUPIED MODE DURING CHILLED WTAER LOAD
SHED 1, 2, 3, 4.
OCCUPANCY MODES
ZONE OCCUPANCY SCHEDULE: 6 AM TO 6 PM, MONDAY -FRIDAY
ZONE OCCUPANCY IS DETERMINED BY A COMBINATION OF A TIME OF DAY SCHEDULE
AND A SPACE OCCUPANCY/VACANCY SENSOR
INITIAL SCHEDULED ZONE OCCUPANCY MODE: THE ZONE SHALL INDEX TO OCCUPIED
MODE AND OPERATE FOR A MINIMUM OF 30 MINUTES.
OCCUPIED/OCCUPIED SETBACK MODE: THE ZONE SHALL INDEX BETWEEN OCCUPIED
AND OCCUPIED SETBACK MODES DURING THE SCHEDULED OCCUPANCY PERIOD
BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE ZONE
OCCUPANCY/VACANCY SENSOR. THE ZONE SHALL INDEX TO OCCUPIED SETBACK
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 30 MINUTES.
UNOCCUPIED MODE: THE ZONE SHALL INDEX TO UNOCCUPIED MODE OUTSIDE OF THE
TIME OF DAY SCHEDULE. IF THE ZONE BECOMES OCCUPIED DURING THE SCHEDULED
UNOCCUPIED PERIOD BASED ON A MANUAL INPUT OR AUTOMATIC INPUT FROM THE
ZONE OCCUPANCY/VACANCY SENSOR, THE ZONE SHALL INDEX TO OCCUPIED MODE
FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO UNOCCUPIED
MODE WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 15 MINUTES.
TEMPERATURE CONTROL
TEMPERATURE SETPOINTS:COOLING HEATING
OCCUPIED:75 °F ± 1.5 °F 70 °F ± 1.5 °F
OCCUPIED SETBACK:75 °F + 3 °F 70 °F -3 °F
UNOCCUPIED:75 °F + 6 °F 70 °F -6 °F
TEMPERATURE SETPOINTS ARE DETERMINED BY A COMBINATION OF A TIME OF DAY
SCHEDULE AND A SPACE OCCUPANCY/VACANCY SENSOR.
THE CHILLED WATER CONTROL VALVES SHALL BE CLOSED WHENEVER THE FAN COIL
UNITS ARE OFF.
EACH SPACE IN THE ZONE SHALL BE PROVIDED WITH A COMBINATION SPACE
TEMPERATURE/HUMIDITY SENSOR. SYSTEM SHALL BE CONTROLLED BASED ON AN
AVERAGE OF THE TEMPERATURE IN BOTH SPACES.
OCCUPIED/OCCUPIED SETBACK MODES:
• INITIAL SCHEDULED ZONE OCCUPANCY: THE FAN COIL SHALL INDEX ON AND
OPERATE FOR A MINIMUM OF 30 MINUTES. AFTER 30 MINUTES, IF THERE IS NO
CALL FOR COOLING THE FAN COIL UNIT SHALL INDEX OFF.
• HEATING CONTROL: IF THE ZONE FALLS BELOW THE OCCUPIED/OCCUPIED
SETBACK HEATING SETPOINT, THE FAN COIL UNIT SHALL BE OFF AND THE CHILLED
WATER CONTROL VALVE SHALL CLOSE. THE BASEBOARD RADIATION CONTROL
VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT.
IF THE ZONE IS NOT AT SETPOINT WITH THE BASEBOARD RADIATION CONTROL
VALVE FULLY OPEN, THE ELECTRIC REHEAT COIL SHALL INDEX ON AND MODULATE
AS NEEDED TO MAINTAIN SETPOINT.
• COOLING CONTROL: IF THE ZONE RISES ABOVE THE OCCUPIED/OCCUPIED
SETBACK COOLING SETPOINT, THE ELECTRIC REHEAT COIL SHALL INDEX OFF AND
THE BASEBOARD RADIATION VALVES SHALL CLOSE. THE FAN COIL UNIT SHALL
INDEX ON AND OPERATE AT MINIMUM SPEED. THE CHILLED WATER CONTROL
VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT.
IF THE ZONE IS NOT AT SETPOINT WITH THE CHILLED WATER CONTROL VALVE
FULLY OPEN, THE FAN COIL UNIT SPEED SHALL INCREASE AS NEEDED TO MAINTAIN
SETPOINT.
UNOCCUPIED MODE:
• HEATING CONTROL: IF THE ZONE FALL BELOW THE UNOCCUPIED HEATING
SETPOINT, THE FAN COIL UNIT SHALL BE OFF AND THE CHILLED WATER CONTROL
VALVE SHALL CLOSE. THE BASEBOARD RADIATION CONTROL VALVE SHALL
MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT.
• COOLING CONTROL: IF THE ZONE RISES ABOVE THE UNOCCUPIED COOLING
SETPOINT, THE ELECTRIC DUCT COIL SHALL INDEX OFF AND THE BASEBOARD
RADIATION CONTROL VALVES SHALL CLOSE. THE FAN COIL UNITS SHALL INDEX ON
AND OPERATE AT MINIMUM SPEED. THE CHILLED WATER CONTROL VALVES SHALL
MODULATE OPEN AS NEEDED TO MAINTAIN THE ZONE AT SETPOINT. IF THE ZONE
IS NOT AT SETPOINT WITH THE CHILLED WATER CONTROL VALVES FULLY OPEN,
THE FAN COIL UNIT SPEED SHALL INCREASE AS NEEDED TO MAINTAIN SETPOINT.
SAFETIES
THE FAN COIL SHALL INDEX OFF AND THE CHILLED WATER CONTROL VALVE SHALL
CLOSE UPON ACTIVATION OF THE DRAIN PAN OVERFLOW SWITCH.
LIGHTING
THE FOLLOWING LIGHTING CONTROLS ARE REQUIRED TO BE PROVIDED FOR THIS
ZONE:
• MANUAL ON/OFF/DIMMING CONTROL
• VACANCY SENSING –MANUAL ON/AUTOMATIC OFF
• DAYLIGHT RESPONSIVE CONTROLS
W161B & C CONTROL POINTS LIST SCHEDULE
POINT
#CONTROL POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOW
ON
GRAPHIC NOTESBI BO AI AO AV BV SCH TREND
ALARM
ALARM DESCRIPTIONBACS EMCS
1 FCU ECM FAN START/STOP/SPEED X X X
2 FCU ECM STATUS (ON/OFF) X X X FAN FAILURE X
3 FCU COOLING COIL CONTROL VALVE POSITION
COMMAND
X X X
4 FCU OVERFLOW SWITCH STATUS X X X OVERFLOW X
5 FCU DISCHARGE AIR TEMPERATURE/SETPOINT X X X X TEMPERATURE ALARM / SENSOR FAILURE X
6 ELECTRIC HEATING COIL COMMAND X X X
7 ELECTRIC HEATING COIL AIR PROVING SWITCH X X X LOSS OF AIRFLOW X
8 ELECTRIC HEATING COIL DISCHARGE AIR
TEMPERATURE/SETPOINT
X X X X TEMPERATURE ALARM / SENSOR FAILURE X
9 BASEBOARD RADIATION CONTROL VALVE POSITION
COMMAND (%)
X X X
10 BASEBOARD RADIATION CONTROL VALVE POSITION
COMMAND (%)
X X X
11 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X
12 SPACE HUMIDITY X X X
13 SPACE TEMPERATURE/SETPOINT X X X X DEVIATION FROM SETPOINT X
14 SPACE HUMIDITY X X X
15 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X
16 HVAC SPACE OCCUPANCY SENSING X X X X SENSOR FAILURE X
17 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X
18 LIGHTING MANUAL DIMMING (%)X X X
19 LIGHTING VACANCY SENSING (ON/OFF) X X X
20 LIGHTING CONTACT RELAY (OPEN/CLOSED) X X X
21 LIGHTING MANUAL WALL SWITCH (ON/OFF) X X X
22 LIGHTING MANUAL DIMMING (%)X X X
23 LIGHTING VACANCY SENSING (ON/OFF) X X X
24 LIGHTING CONTACT RELAY (OPEN/CLOSED) X X X
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-501
12971596
SCHEDULES
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTION1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
NOTES:
1) PRESSURE IN THE DUCT NEEDS TO BE A MINIMUM OF 0.07" WC TO KEEP THE HEATER ON.
SPECS
1) ACCEPTABLE MANUFACTURERS: INDEECO, GREENHECK, PRICE
2) RATINGS: NFPA 70, UL 1996
3) HOUSING: HEAVY GAUGE GALVANIZED STEEL, SLIP IN
4) HEATING ELEMENTS: 80/20 NICKEL/CHROMIUM RESISTANCE WIRE
5) CONTROL PANEL: UNIT MOUNTED WITH DISCONNECTING MEANS AND OVERCURRENT PROTECTION
6) ACCESSORIES: AIR PROVING SWITCH, DISCONNECT SWITCH
ELECTRIC DUCT HEATER
TAG SERVICE
BASIS OF DESIGN AIRFLOW
(CFM)
EAT
DB
(F)
LAT
DB
(F)
ELECTRICAL CONTROL
DUCT DIMENSION
(IN)
NOTESMANF MODEL KW AMPS V/PH/HZ TYPE VOLTAGE WIDTH HEIGHT
EDH-154-1 W154 ANTE / W154A BEHAVIOR 1 GREENHECK IDHE 320 60 75 1.5 1.8 480/3/60 SCR 24 12 12 -
EDH-154-2 W154B BEHAVIOR 2 GREENHECK IDHE 290 60 75 1.4 1.7 480/3/60 SCR 24 12 12 -
EDH-154-3 W154C BEHAVIOR 3 GREENHECK IDHE 960 60 75 4.6 5.5 480/3/60 SCR 24 16 16 -
EDH-156-1 WI56 PROCEDURE GREENHECK IDHE 430 60 75 2.0 2.4 480/3/60 SCR 24 12 12 -
EDH-161-1 W161 MAIN LAB GREENHECK IDHE 275 60 85 2.2 2.6 480/3/60 SCR 24 10 10 -
EDH-161-2 W161B/W161C OFFICES GREENHECK IDHE 100 60 95 1.1 1.3 480/3/60 SCR 24 8 8 -
EDH-162-1 W162 ANTE / W162A BEHAVIOR 4 GREENHECK IDHE 315 60 75 1.5 1.8 480/3/60 SCR 24 8 8 -
EDH-162-2 W162B HOLDING 2 GREENHECK IDHE 85 60 75 0.5 0.6 480/3/60 SCR 24 10 10 -
EDH-162-3 W162C HOLDING 1 GREENHECK IDHE 85 60 75 0.5 0.6 480/3/60 SCR 24 10 10 -
EDH-162-4 W162C HOLDING 5 GREENHECK IDHE 280 60 75 1.3 1.6 480/3/60 SCR 24 10 10 -
EDH-162-5 W162E IMAGING GREENHECK IDHE 345 60 75 1.6 1.9 480/3/60 SCR 24 10 10 -
DIFFUSER/GRILLE SCHEDULE
TAG #
BASIS OF DESIGN
FACE SIZE
NECK SIZE
WXH OR DIA.TYPE MOUNTING NOTESMANF MODEL
EAG-1 PRICE 535 10"X8" 8"X6" LOUVERED SURFACE -
EAG-2 PRICE SPD 24"X24" 8" PLAQUE FACE LAY-IN -
EAG-3 PRICE SPD 24"X24" 10" PLAQUE FACE LAY-IN -
EAG-4 PRICE SPD 24"X24" 12" PLAQUE FACE LAY-IN -
EAG-5 PRICE 85 12"X24" 10"X22" EGG CRATE LAY-IN -
RAG-1 PRICE 85 12"X24" 10"X22" EGG CRATE LAY-IN -
RAG-2 PRICE 85 24"X24" 22"X22" EGG CRATE LAY-IN -
SAD-1 PRICE SPD 24"X24" 6" PLAQUE FACE LAY-IN -
SAD-2 PRICE SPD 24"X24" 8" PLAQUE FACE LAY-IN -
SAD-3 PRICE SPD 24"X24" 10" PLAQUE FACE LAY-IN -
SAD-4 PRICE SPD 24"X24" 12" PLAQUE FACE LAY-IN -
SAD-5 PRICE 535 10"X8" 8"X6" LOUVERED SURFACE -
SPECS
1) ACCEPTABLE MANUFACTURERS: ENVIRO-TEC, IEC, JOHNSON CONTROLS, McQUAY, TRANE
2) CONSTRUCTION: GALVANIZED STEEL CONSTRUCTION, 1/2" THICK FIBERGLASS INSULATION, INTEGRAL REAR DUCTED RETURN
3) COIL: 3/8-IN OD COPPER TUBE, 0.012-IN TUBE WALL THICKNESS, ALUMINUM FINS, MANUAL AIR VENT.
4) FAN ASSEMBLY: DOUBLE WIDTH, DOUBLE INLET, FORWARD CURVED, CENTRIFUGAL, EC MOTOR
5) DRAIN PAN: STAINLESS STEEL WITH EXTERNAL INSULATION
6) FILTERS: INTEGRAL RACK WITH 1-IN THROWAWAY FILTER
7) ELECTRICAL: CONDENSATE OVERFLOW SWITCH, TOGGLE DISCONNECT SWITCH, MAIN FUSING
NOTES
1) FAN COILS ARE PURPOSELY OVERSIZED TO MEET THE SCHEDULED COOLING CAPACITY AT A REDUCED FAN SPEED.
FAN COIL UNIT SCHEDULE
TAG # SERVICE
BASIS OF DESIGN AIRFLOW (CFM)
ESP
(IN WG)
COOLING COIL ELECTRICAL
WEIGHT
(LBS)NOTESMANF MODEL SUPPLY VENT
CAPACITY (BTUH)
ROWS FPI
AIR SIDE WATER SIDE
WATTS V/PH/HZTOTAL SENSIBLE
EAT
DB
(F)
LAT
DB
(F)
EWT
DB
(F)
LWT
DB
(F)GPM
WPD
(FT)TYPE
FCU-161-1 W161 MAIN LAB JOHNSON CONTROLS FNP 12 890 140 0.25 17800 13385 4 10 72 58 47 62 2.5 5 MAX WATER 494 115/1/60 - 1
FCU-161-2 W161 MAIN LAB JOHNSON CONTROLS FNP 12 890 140 0.25 17800 13385 4 10 72 58 47 62 2.5 5 MAX WATER 494 115/1/60 - 1
FCU-161-3 W161B/W161C OFFICES JOHNSON CONTROLS FNP 10 565 0 0.25 14000 10300 4 10 75 58 47 62 2.0 5 MAX WATER 457 115/1/60 - 1
FCU-161-4 W161A MEETING JOHNSON CONTROLS FNP 06 175 0 0.25 4180 3215 4 10 75 58 47 62 1.0 5 MAX WATER 247 115/1/60 - 1
FCU-162-1 W162E BEHAVIOR JOHNSON CONTROLS FNP 08 410 0 0.25 8060 6200 4 10 72 58 47 62 1.5 5 MAX WATER 375 115/1/60 - 1
SPECS
1) ACCEPTABLE MANUFACTURERS: ACCUTROL, PHOENIX
2) ALL AIR VALVES ARE TO BE ALUMINUM WITH HIGH SPEED ACTUATORS AND FULL SHUTOFF.
3) ALL SUPPLY AIR VALVES ARE TO BE INSULATED.
LABORATORY AIRFLOW CONTROL DEVICE SCHEDULE
TAG # SERVES SUP EXH
BASIS OF DESIGN
SIZE
BACS
SETPOINTS
FACTORY
RANGE
ΔPT
(IN WC)
REHEAT
COIL TAG
DAMPER
POSITION NOTESMANF MODEL
MAX
(CFM)
MIN
(CFM)
MAX
(CFM)
MIN
(CFM)
SAV-154-1 W154/W154A ANTE/BEHAVIOR 1 X ACCUTROL AVC6408-05-ISW 08 320 65 650 0 0.3 EDH-154-1 N.O. -
EAV-154-1 W154/W154A ANTE/BEHAVIOR 1 X ACCUTROL AVC6408-05-SW 08 305 85 650 0 0.3 - N.O. -
SAV-154-2 W154B BEHAVIOR 2 X ACCUTROL AVC6408-05-ISW 08 290 50 650 0 0.3 EDH-154-2 N.O. -
EAV-154-2 W154B BEHAVIOR 2 X ACCUTROL AVC6408-05-SW 08 325 85 650 0 0.3 - N.O. -
SAV-154-3 W154C BEHAVIOR 3 X ACCUTROL AVC6410-05-ISW 10 960 100 1056 0 0.3 EDH-154-3 N.O. -
EAV-154-3 W154C BEHAVIOR 3 X ACCUTROL AVC6410-05-SW 10 1030 170 1056 0 0.3 - N.O. -
SAV-156-1 W156 PROCEDURE X ACCUTROL AVC6408-05-ISW 08 430 50 650 0 0.3 EDH-156-1 N.O. -
EAV-156-1 W156 PROCEDURE X ACCUTROL AVC6408-05-SW 08 530 150 650 0 0.3 - N.O. -
SAV-161-1 W161 MAIN LAB X ACCUTROL AVC6408-05-ISW 08 275 80 650 0 0.3 EDH-161-1 N.O. -
EAV-161-1 W161 MAIN LAB X ACCUTROL AVC6408-05-SW 08 275 80 650 0 0.3 - N.O. -
SAV-162-1 W162/W162A ANTE/BEHAVIOR 4 X ACCUTROL AVC6408-05-ISW 08 315 53 650 0 0.3 EDH-162-1 N.O. -
EAV-162-1 W162/W162A ANTE/BEHAVIOR 4 X ACCUTROL AVC6408-05-SW 08 300 85 650 0 0.3 - N.O. -
SAV-162-2 W162B HOLDING 2 X ACCUTROL AVC6406-05-ISW 06 85 85 254 0 0.3 EDH-162-2 N.O. -
EAV-162-2 W162B HOLDING 2 X ACCUTROL AVC6406-05-SW 06 110 110 254 0 0.3 - N.O. -
SAV-162-3 W162C HOLDING 1 X ACCUTROL AVC6406-05-ISW 06 85 85 254 0 0.3 EDH-162-3 N.O. -
EAV-162-3 W162C HOLDING 1 X ACCUTROL AVC6406-05-SW 06 110 110 254 0 0.3 - N.O. -
SAV-162-4 W162D BEHAVIOR 5 X ACCUTROL AVC6408-05-ISW 08 280 50 650 0 0.3 EDH-162-4 N.O. -
EAV-162-4 W162D BEHAVIOR 5 X ACCUTROL AVC6408-05-SW 08 315 85 650 0 0.3 - N.O. -
SAV-162-5 W162E IMAGING X ACCUTROL AVC6408-05-ISW 08 345 60 650 0 0.3 EDH-162-5 N.O. -
EAV-162-5 W162E IMAGING X ACCUTROL AVC6408-05-SW 08 370 85 650 0 0.3 - N.O. -
SPECS
1) ACCEPTABLE MANUFACTURERS: GREENHECK, NAILOR, RUSKIN, POTTORFF
2) FRAME: 16 GA GALVANIZED STEEL
3) BLADES: 14 GA GALVANIZED STEEL AIRFOIL, WITH SILICONE BLADE SEALS
4) ACCESSORIES: TEST SWITCH, OPEN CLOSED INDICATION SWITCHES, SMOKE DETECTOR
FIRE / SMOKE DAMPER SCHEDULE
TAG # SERVES
BASIS OF DESIGN
DUCT
SIZE
(IN)TEMP
RATING
(°F)
FIRE RATING SMOKE RATING ACCESSORIES
POWER NOTESMANF MODEL W H HOURS UL CLASS UL #1 #2
FSD-1 W161 SUITE GREENHECK FSD-312 10 10 165 1.5 555 II 555S GTS-3 RRL/OCI 120 VAC -
FSD-2 W154 SUITE GREENHECK FSD-312 20 18 165 1.5 555 II 555S GTS-3 RRL/OCI 120 VAC -
FSD-3 W156 PROCEDURE GREENHECK FSD-312 12 12 165 1.5 555 II 555S GTS-3 RRL/OCI 120 VAC -
FSD-4 W162 SUITE GREENHECK FSD-312 20 14 165 1.5 555 II 555S GTS-3 RRL/OCI 120 VAC -
SPECS
1) ACCEPTABLE MANUFACTURERS: ARMSTRONG, CONDAIR, DRISTEEM
2) CONTROL VALVE: BRONZE BODY WITH STAINLESS STEEL SEAT, STEM AND PLUG; 24VAC; 0-10 VDC; NORMALLY CLOSED SPRING RETURN
3) HEADER: SHORT ABSORPTION, STAINLESS STEEL WITH RUBBER SEALS, 304 SS SHIELDING WITH SYNTHETIC FOAM INSULATION
4) DISTRIBUTOR: 304 STAINLESS STEEL WITH STAINLESS STEEL NOZZLES, 304 STAINLESS STEEL SHIELDS, WITH SYNTHEIC FOAM INSULATION
5) ACCESSORIES: STAINLESS STEEL SEPARATOR, F&T STEAM TRAPS, WYE STRAINER, DUCT MOUNTED HIGH LIMIT DIGITAL HUMIDISTAT CONTROLLER; AIR PROVING SWITCH
NOTES
1) CONDITIONS IN THE SPACE ARE TO BE MAINTAINED AT A MINIMUM OF 72 °F DB, 40% RH...
DUCT HUMIDIFIER SCHEDULE
TAG # SERVES
BASIS OF DESIGN
AIRFLOW
(CFM)
DUCT SIZE
WXH (IN)
AIR CONDITIONS
STEAM
PSIG
CONTROL
VALVE
STEAM
PPH
INJECTION
TUBES MAX
ABSORPTION
DISTANCE NOTESMANF MODEL MANIFOLD DISTRIBUTOR
ENTERING AIR LEAVING AIR
QTY
LENGTH
(IN)(°F DB) (% RH) (°F DB) (% RH)
H-1 W154 SUITE CONDAIR LIVESTEAM 1594314 MINI SAM-e 2577698 MB 1509800 1570 20 x 18 55 5 55 91 10 Cv=2.2 53 5 15 5 FT 1
H-2 W156 PROCEDURE CONDAIR LIVESTEAM 1594314 MINI SAM-e 2577686 MA 1509790 430 12x12 55 5 55 91 10 Cv=0.75 15 5 9 5 FT 1
H-3 W162 SUITE CONDAIR LIVESTEAM 1594314 MINI SAM-e 2577698 MA 1509791 1110 20 x 14 55 5 55 91 10 Cv=1.30 38 5 11 5 FT 1
NOTES:
1) PROVIDE SECONDARY VOLUME DAMPER, UPSTREAM OF TERMINAL TO ENSURE THE MAX DELTA P (IN WG) ACROSS
THE REGISTER VALVE IS LESS THAN 1.0 IIN WG.
ZONE REGISTER TERMINAL
TAG # SERVES
BASIS OF DESIGN
AIRFLOW
GRILLE
(L X W)
INLET
SIZE
(IN)ELECTRICAL NOTESMANF MODEL
ZRT-1 161A MEETING ALDES ZRT-2-4-24MAX 50 CFM 10" x 10" 4 24V / 60HZ 1
ZRT-2 161B OFFICE 2 ALDES ZRT-2-4-24MAX 50 CFM 10" x 10"4 24V / 60HZ 1
ZRT-3 W161C OFFICE 1 ALDES ZRT-2-4-24MAX 50 CFM 10" x 10" 4 24V / 60HZ 1
SPECS
1) ACCEPTABLE MANUFACTURERS: BELIMO
2) ELECTRIC INPUT: 4-20mA OR 0-10VDC
3) 2-WAY VALVES: EQUAL PERCENTAGE FLOW CHARACTERISTIC
4) CONSTRUCTION: CHARACTERIZING DISK, FORGED BRASS, NICKEL PLATED BODY, STAINLESS STEEL BALL AND STEM, FIBERGLASS REINFORCED PTFE SEAT
5) RATINGS: 400 PSI PRESSURE, 0-212 F MEDIA TEMPERATURE RANGE
6) CONTROL WIRING SHALL BE INSTALLED IN ELECTROMETALLIC TUBING WITH COMPRESSION FITTINGS.
7) CONTROL WIRING SHALL BE COLOR CODED AND LABELED AT ALL POINTS OF TERMINATION.
CONTROL VALVE SCHEDULE & SPEC
TAG
BASIS OF DESIGN
SERVICE
VALVE
TYPE CONTROL
CAPACITY
(GPM)
VALVE
SIZE (IN)CV
MAX PD
(PSIG)FAIL POSMANF
VALVE
MODEL
ACTUATOR
MODEL
CV-1 BELIMO CCV-B211 TF-24-SR US FCU-161-1 2-WAY MOD 2.5 1/2 1.9 1.7 N.C.
CV-2 BELIMO CCV-B211 TF-24-SR US FCU-161-2 2-WAY MOD 2.5 1/2 1.9 1.7 N.C.
CV-3 BELIMO CCV-B211 TF-24-SR US FCU-161-3 2-WAY MOD 2.0 1/2 1.9 1.1 N.C.
CV-4 BELIMO CCV-B211 TF-24-SR US FCU-161-4 2-WAY MOD 1.0 1/2 1.9 0.3 N.C.
CV-5 BELIMO CCV-B211 TF-24-SR US FCU-162-1 2-WAY MOD 1.5 1/2 1.9 0.6 N.C.
CV-6 BELIMO CCV-B211 TR24-SR-T US MAIN LAB 161 2-WAY MOD 1.5 1/2 1.9 0.6 F.L.
CV-7 BELIMO CCV-B211 TR24-SR-T US OFFICE W161B / MAIN LAB 161 2-WAY MOD 1.5 1/2 1.9 0.6 F.L.
CV-8 BELIMO CCV-B211 TR24-SR-T US OFFICES W161C / W153A 2-WAY MOD 1.5 1/2 1.9 0.6 F.L.
DUCT ACCESS DOOR SCHEDULE
TYPE
BASIS OF DESIGN
SIZE
(IN)
MATERIAL
FRAME
GAGE
DOOR
GAGE FASTENER
HINGE
(Y/N)
GASKET
MATERIAL
INSULATION
MAX
WORKING
STATIC
PRESSURE
(IN WG)
LEAKAGE @
6 IN WG
(CFM/SF)NOTESMANF MODEL W H TYPE
THICKENSS
(IN)
DAD-1 RUSKIN ADH24 8 8 GALVANIZED 22 24 CAM LOCK N NEOPRENE FIBERGLASS 1 6 7.8 -
DAD-2 RUSKIN ADH24 10 10 GALVANIZED 22 24 CAM LOCK N NEOPRENE FIBERGLASS 1 6 7.8 -
DAD-3 RUSKIN ADH24 14 14 GALVANIZED 22 24 CAM LOCK N NEOPRENE FIBERGLASS 1 6 7.8 -
AIRFLOW SCHEDULE
ROOM DESCRIPTION
ROOM DIMENSIONS EXHAUST AIR SUPPLY AIR
XFER
ALL
MODES
(CFM)NOTES
AREA
(SF)
HEIGHT
(FT)
EXHAUST
POINT
OCCUPIED
MAX
OCCUPIED
MIN UNOCCUPIED
SUPPLY
POINT
OCCUPIED
UNOCCUPIED
(CFM)(CFM) (ACH) (CFM) (ACH) (CFM) (ACF)
MAX
(CFM)
MIN
(CFM)
W154 ANTEROOM 38 8.5 - - - - - - - SAV-154-1 50 - - - PRESSURIZATION
W154A BEHAVIOR 1 94 8.5 EAV-154-1 305 22.9 160 12.0 85 6.4 SAV-154-1 270 125 50 -35 COOLING / VENTILATION
W154B BEHAVIOR 2 148 8.5 EAV-154-2 325 15.5 255 12.2 85 4.1 SAV-154-2 290 220 50 -35 COOLING / VENTILATION
W154C BEHAVIOR 3 274 8.5 EAV-154-3 1030 26.5 465 12.0 170 4.4 SAV-154-3 960 395 100 -70 COOLING / VENTILATION
W156 PROCEDURE 188 8.5 EAV-156-1 530 19.9 335 12.6 150 5.6 SAV-156-1 430 235 50 -100 COOLING/AIR CHANGE LAB
W161 MAIN LAB (COMPUTATIONAL) 536 8.5 EAV-161-1 275 3.6 80 1.1 80 1.1 SAV-161-1 275 80 80 0 VENTILATION
W161A MEETING 149 8.5 - - - - - - - ZRT 50 - - - VENTILATION
W161B OFFICE 2 106 8.5 - - - - - - - ZRT 50 - - - VENTILATION
W161C OFFICE 1 103 8.5 - - - - - - - ZRT 50 - - - VENTILATION
W162 ANTEROOM 96 8.5 - - - - - - - SAV-162-1 50 - - 50 PRESSURIZATION
W162A BEHAVIOR 4 79 8.5 EAV-162-1 300 26.8 135 12.1 85 7.6 SAV-162-1 265 100 50 -35 COOLING / VENTILATION
W162B HOLDING 2 51 8.5 EAV-162-2 110 15.2 110 15.2 110 15.2 SAV-162-2 85 85 85 -25 AIR CHANGE LAB
W162C HOLDING 1 54 8.5 EAV-162-3 110 14.4 110 14.4 110 14.4 SAV-162-3 85 85 85 -25 AIR CHANGE LAB
W162D BEHAVIOR 5 113 8.5 EAV-162-4 315 19.7 195 12.2 85 5.3 SAV-162-4 280 160 50 -35 COOLING / VENTILATION
W162E IMAGING 162 8.5 EAV-162-5 370 16.1 275 12.0 85 3.7 SAV-162-5 345 250 60 -25 COOLING / VENTILATION
CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
M-502
12971596
SCHEDULES
E. KOLACKI
PCO
1019W
MARCH 12, 2021REVIEWPURPOSESONLY NOTFORCONSTRUCTION1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
SPECS
1) SOLDER FILLER METALS: ASTM B32, LEAD-FREE ALLOYS. INCLUDE WATER FLUSHABLE FLUX ACCORDING TO ASTM B813.
2) DIELECTRIC FITTINGS: USE FLANGES OR COUPLINGS. UNIONS ARE UNACCEPTABLE
3) INSTALL ESCUTCHEONS FOR PENETRATIONS OF WALLS, CEILING, AND FLOORS
4) INSTALL SLEEVES FOR PIPES PASSING THROUGH CONCRETE AND MASONRY WALLS, GYPSUM-BOARD PARTITIONS, AND CONCRETE FLOOR AND ROOF SLABS.
5) INSTALL PIPING SYSTEMS TO FACILITATE SERVICE, MAINTENANCE AND REPAIR OR REPLACEMENT OF COMPONENTS.
6) ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
TYPE A INSULATION: PRE-FORMED MINERAL FIBERGLASS, ASTM C547 TYPE I, ASTM C1136 FACTORY APPLIED SELF-SEALING ALL SERVICE JACKET.
7) ALL PIPING AND INSULATION SYSTEM EXPOSED TO VIEW SHALL BE PAINTED TO MATCH SURROUNDING SURFACES
8) PROVIDE ALUMINUM OR PVC FIELD APPLIED JACKETING IN HIGH TRAFFIC AREAS AND ALL EXPOSED PIPING BELOW 8 FEET.
9) MAINTAIN INDICATED FIRE RATING OF WALLS, PARITIONS, CEILINGS, AND FLOORS AT PIPE PENETRATIONS. SEAL PIPE PENETRATIONS WITH FM APPROVED FIRESTOP MATERIALS
10) INSTALL DRAINS, CONSISTING OF A TEE FITTING, NPS 3/4 BALL VALVE, AND SHORT NPS 3/4 THREADED NIPPLE AT LOW POINTS IN PIPING SYSTEM AS REQUIRED FOR DRAINAGE.
11) INSTALL MANUAL AIR VENT AT HIGH POINT IN PIPING SYSTEM AS REQUIRED FOR BLEEDING SYSTEM OF AIR.
12) INSTALL UNIONS IN PIPING, NPS 2 AND SMALLER, ADJACENT TO VALVES, AT FINAL CONNECTIONS OF EQUIPMENT, AND ELSEWHERE AS INDICATED
13) INSTALL STRAINERS ON INLET SIDE OF CONTROL VALVES AND ELSEWHERE AS INDICATED. INSTALL NIPPLE AND BALL VALVE IN BLOWDOWN CONNECTION.
14) INSTALL PORTS FOR PRESSURE GAGES AND THERMOMETERS AT COIL INLET AND OUTLET CONNECTIONS.
15) INSTALL STEAM SUPPLY PIPING AT A MINIMUM UNIFORM GRADE OF 0.2 PERCENT DOWNWARD IN DIRECTION OF STEAM FLOW.
INSTALL CONDENSATE RETURN PIPING AT A MINIMUM UNIFORM GRADE OF 0.4 PERCENT DOWNWARD IN DIRECTION OF CONDENSATE FLOW.
REDUCE STEAM PIPE SIZES USING ECCENTRIC REDUCER FITTINGS INSTALLED WITH LEVEL SIDE DOWN.
16) PROVIDE PIPE LABLES AND DIRECTIONAL ARROWS ON ALL NEW PIPING SYSTEMS. LABELS SHALL BE PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT ADHESIVE BACKING.
17) TESTING:
FILL SYSTEM WITH AMBIENT TEMPERATURE WATER. USE VENTS INSTALLED AT HIGH POINTS OF SYSTEM TO RELEASE AIR. USE DRAINS INSTALLED AT LOW POINTS FOR COMPLETE DRAINING OF TEST LIQUID.
ISOLATE EXPANSION TANKS AND DETERMINE THAT HYDRONIC SYSTEM IS FULL OF WATER
SUBJECT PIPING SYSTEM TO HYDROSTATIC TEST PRESSURE THAT IS NOT LESS THAN 1.5 TIMES THE SYSTEM WORKING PRESSURE. TEST PRESSURE SHALL NOT EXCEED MAXIMUM PRESSURE FOR DEVICE IN THE SYSTEM UNDER TEST.
AFTER HYDROSTATIC TEST PRESSURE HAS BEEN APPLIED FOR AT LEAST 10 MINUTES, EXAMINE PIPING, JOINTS, AND CONNECTIONS FOR LEAKAGE.
ELIMINATE LEAKS BY TIGHTENING, REPAIRING, OR REPLACING COMPONENTS, AND REPEAT HYDROSTATIC TEST UNTIL THERE ARE NO LEAKS.
ARRANGE FOR INSPECTION BY FACILITIES MANAGEMENT PIPE SHOP.
18) CHILLED WATER SYSTEMS: CHEMICALS SHALL NOT BE USED TO TREAT CHILLED WATER SYSTEMS CONNECTED TO THE CAMPUS CHILLED WATER LOOP.
FILL SYSTEM WITH POTABLE WATER. NOTIFY THE CENTRAL ENERGY PLANT FOR PERMISSION TO BEGIN CIRCULATING WATER INTO THE CAMPUS CHILLED WATER LOOP.
19) CHEMICAL TREATMENT OF NON-GLYCOL HYDRONIC HEATING SYSTEMS:
AFTER CLEANING AND INSPECTION, ADD A MOLYBDATE BASED CORROSION INHIBITOR. ACCEPTABLE CORROSION INHIBITORS SHALL INCLUDE A COMBINATION OF SODIUM MOLYBDATE AND TOLYTRIAZOLE.
TEST FOR RESIDUAL CONCENTRATION AS FOLLOWS: 150 PPM MOLYBDATE; 8.3-9 PH; 10-20 PPM TOLYTRIAZOLE.
ARRANGE FOR INSPECTION BY FACILITIES MANAGEMENT WATER TREATMENT LAB BEFORE FINAL ACCEPTANCE.
HVAC PIPE AND FITTING SCHEDULE AND SPECIFICATIONS
PIPE SERVICE ABBREVIATION PIPE SIZE MATERIAL FITTINGS JOINT
INSULATION
THICKNESS
(IN)
CONDUCTIVITY
(BTU-IN/HR-FT²-˚F)
MEAN TEMP
(°F)MATERIAL
VAPOR
RETARDER
HEATING HOT WATER HWS&R 1-1/4" & BELOW ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER 1.5 0.25 - 0.29 125 A NO
CHILLED WATER CHWS&R 1-1/2" & BELOW ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER 1 0.21 - 0.27 75 A YES
LOW PRESSURE CLEAN STEAM LPCS 1-1/2" & BELOW ASTM A312 SCH 40 STAINLESS STEEL ANSI B16.11 FORGED STEEL SOCKET WELD 2.5 0.27 - 0.30 150 A NO
LOW PRESSURE CLEAN CONDENSATE LPCC 1-1/2" & BELOW ASTM A312 SCH 80 STAINLESS STEEL ANSI B16.11 FORGED STEEL SOCKET WELD 2.5 0.27 - 0.30 150 A NO
CONDENSATE DRAIN (COOLING / HUMIDIFIER DRAIN) CD ALL SIZES ASTM B88 TYPE M HARD TEMPER COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER 1 0.22 - 0.27 75 A YES
NOTES
1) FOR VALVES INSTALLED IN INSULATED PIPING SYSTEMS, PROVIDE EXTENDED HANDLE
2) PROVIDE VALVES WITH UNIONS AT EACH PIECE OF EQUIPMENT ARRANGED TO ALLOW SERVICE, MAINTENANCE AND EQUIPMENT REMOVAL WITHOUT SYSTEM SHUTDOWN
3) PROVIDE PRESSURE/TEMPERATURE TEST PORTS AT ALL COILS, AND WHERE INDICATED
4) PROVIDE UNIONS ADJACENT TO VALVES AND AT FINAL EQUIPMENT CONNECTIONS.
5) BEFORE PLACING SYSTEM IN SERVICE, REMOVE MESH FROM ALL STRAINERS, CLEAN MESH AND FLUSH SYSTEM, RE-INSTALL AFTER FINAL FLUSHING.
6) PROVIDE STRAINERS AT INLET OF CONTROL VALVES, AND WHERE INDICATED. INSTALL NIPPLE AND BALL VALVE IN BLOWDOWN CONNECTION.
7) PROVIDE MANUAL AIR VENTS AT HIGH POINTS IN PIPING SYSTEM, HEAT TRANSFER COILS, AND ELSEWHERE AS REQUIRED FOR SYSTEM AIR VENTING.
8) PROVIDE DRAIN VALVES AT MAIN SHUT-OFF VALVES, LOW POINTS OF PIPING SYSTEM, AND ELSEWHERE AS REQUIRED FOR SYSTEM DRAINING.
PIPING ACCESSORIES SCHEDULE AND SPECIFICATIONS
TAG DEVICE BOD MANUFACTURER MODEL PRESSURE RATING SPECIFICATIONS
BV-1 BALANCE VALVE NPS 1/2 - 2 INCH BELL & GOSSETT CB SERIES, CB 3/4S 200 PSIG @ 250 DEGF
1.5 - 6.0 GPM RANGE, BRONZE, BALL 1.0 - 8.0 GPM RANGE, BRONZE, BALL OR PLUG TYPE BODY WITH CALIBRATED ORIFICE OR
VENTURI; GLASS AND CARBON FILLED TFE OR EPDM SEAT RINGS, EPDM STEM O-RING, WITH INTEGRAL SEALS FOR PORTABLE
DIFFERENTIAL PRESSURE METER, WITH LEVEL HANDLE AND MEMORY STOP TO RETAIN SET POSITION.OR PLUG TYPE BODY WITH
CALIBRATED ORIFICE OR VENTURI; GLASS AND CARBON FILLED TFE OR EPDM SEAT RINGS, EPDM STEM O-RING, WITH INTEGRAL
SEALS FOR PORTABLE DIFFERENTIAL PRESSURE METER, WITH LEVEL HANDLE AND MEMORY STOP TO RETAIN SET POSITION.
V-1 BALL VALVE, CHILLED WATER SERVICE NPS 1/2 - 2 INCH
WATTS
APOLLO
NIBCO
B6000-SS or B6001-SS
70-140 or 70-240
T-580-70-66 or S-580-70-66
300 PSIG @ 250 ˚F
300 PSIG WOG
150 PSIG SWP
MSS SP-110, 2-PIECE, STANDARD PORT, BRONZE BODY, 316 SS BALL & STEM, PTFE OR TFE SEAT
V-2 BALL VALVE, CLEAN STEAM SERVICE NPS 1/2 - 2 INCH
METSO JAMESBURY
SVF FLOW CONTROLS
JFLOW CONTROLS
SERIES 4000
SERIES N8
SERIES 4600
100 PSIG @ 450 °F SWP
400 PSIG WOG ASTM A351 CR8M 316 SS BODY, SOCKET WELD, 316 SS BALL AND STEM, HIGH TEMPERATURE RTFE SEAT
PT-1 PRESSURE/TEMPERATURE TEST PORT TRERICE D3770 500 PSIG @ 200 ˚F HOT WATER / GLYCOL SERVICE: BRASS BODY & CAP, 1/2 NPT CONNECTION, EPDM (NORDEL) SEAT, GASKETED AND THREADED CAP
WITH RETENTION CHAIN
S-1 STRAINERS, WYE PATTERN NPS 1/2 - 2 INCH WATTS SERIES 777 200 PSIG @ 210 ˚F WOG
125 PSIG @ 353 ˚F WSP BRONZE BODY, #20 MESH 304 STAINLESS STEEL SCREEN, THREAD OR SWEAT CONNECTION.
AV-1 AIR VENT BELL & GOSSETT MODEL 4V 150 PSIG BRASS BODY, NON-FERROUS INTERNALS
SPECS
1) ALL DUCTWORK AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN COMPLIANCE WITH THE LATEST ISSUE OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE.
2) CONSTRUCT TEES, BENDS, AND ELBOWS WITH RADIUS OF NOT LESS THAN 1.0 TIMES THE WIDTH OF DUCT ON CENTER LINES.
3) WHERE RECTANGULAR ELBOWS ARE USED, PROVIDE AIR FOIL TYPE TURNING VANES.
4) INCREASE DUCT SIZES GRADUALLY, AND IN COMPLIANCE WITH FIGURE 4-7 OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE.
5) BRANCH CONNECTIONS SHALL BE MADE WITH A 45 DEGREE ENTRY. STRAIGHT TEES ARE NOT ACCEPTABLE.
6) SEALANTS AND GASKETS: SURFACE BURNING CHARACTERISTICS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25, AND MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED TO UL 723.
7) ALL MANUAL BALANCING DAMPERS SHALL BE PROVIDED WITH LOCKING HAND QUADRANT.
8) ACCESS DOORS SHALL BE GALVANIZED SHEETMETAL WITH INSULATION FILL AND THICKNESS AS INDICATED FOR DUCT PRESSURE CLASS. INSTALL ADJACENT TO FIRE/SMOKE DAMPERS AND ELSEWHERE AS INDICATED.
9) INSTALL FIRE/SMOKE DAMPERS ACCORDING TO UL LISTING.
10) CONNECT DIFFUSERS TO SUPPLY DUCTS WITH MAXIMUM OF 36-INCHES OF FLEXIBLE DUCT CLAMPED OR STRAPPED IN PLACE.
11) PROVIDE FLEXIBLE CONNECTORS TO CONNECT DUCTS TO EQUIPMENT.
12) INSTALL VOLUME DAMPERS AT POINTS ON SUPPLY, RETURN, AND EXHAUST SYSTEMS WHERE BRANCHES EXTEND FROM LARGER DUCTS.
13) REMOVE SURFACE CONTAMINANTS AND DEPOSITS FROM DUCTWORK AND EQUIPMENT PRIOR TO TESTING AND BALANCING.
14) ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
TYPE A INSULATION: MINERAL FIBERGLASS BLANKET, ASTM C553 TYPE I, ASTM C1136 TYPE I FACTORY APPLIED FSK JACKET, K-VALUE BETWEEN 0.22 - 0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 0.75 PCF
TYPE E INSULATION: ACOUSTICAL DUCT LAGGING, STC 29, 1.5 PCF
TYPE F INSULATION: FIREPROOFING DUCT WRAP, VENTILATION AIR DUCT ENCLOSURE, 2 HOUR
DUCT SCHEDULE AND SPECIFICATIONS
SYSTEM LOCATION SERVICE
PRESSURE
CLASS
SEAL
CLASS
LEAKAGE CLASS
DUCT MATERIAL LINING
INSULATION
DUCT
FINISHRECT ROUND
MIN
R-VALUE MATERIAL FIELD JACKET
VAPOR
RETARDER
SUPPLY CONCEALED CONNECTION TO MAIN - AIR VALVE INLET 4" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
SUPPLY CONCEALED CONNECTION TO MAIN - AIR VALVE INLET 4" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
SUPPLY CONCEALED AIR VALVE DISCHARGE - SUPPLY OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
SUPPLY CONCEALED AIR VALVE DISCHARGE - SUPPLY OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
SUPPLY CONCEALED FAN COIL DISCHARGE - SUPPLY OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
SUPPLY CONCEALED FAN COIL DISCHARGE - SUPPLY OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
SUPPLY CONCEALED CONNECTION TO MAIN - ZRT OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
SUPPLY CONCEALED HUMIDIFIER DISCHARGE 2" POS A 6 3 316 STAINLESS STEEL, WELDED NONE R-6 A NONE YES NONE
RETURN CONCEALED FAN COIL 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE
TRANSFER CONCEALED RETURN AIR TRANSFER 1" NEG N/A N/A N/A G90 GALVANIZED 1-INCH N/A E NONE N/A NONE
EXHAUST CONCEALED EXHAUST INLET - AIR VALVE INLET 4" NEG A 6 3 G90 GALVANIZED NONE N/A N/A NONE N/A NONE
EXHAUST EXPOSED EXHAUST INLET - AIR VALVE INLET 4" NEG A 6 3 G90 GALVANIZED NONE N/A N/A NONE N/A PAINT
EXHAUST CONCEALED AIR VALVE DISCHARGE - CONNECTION TO MAIN 4" NEG A 6 3 G90 GALVANIZED NONE N/A N/A NONE N/A NONE
EXHAUST CONCEALED EXISTING - WHERE INDICATED N/A N/A N/A N/A N/A NONE N/A F NONE NO NONE
WORK ALSO TO PROVIDE REMOTE TEST
STATION AND DAMPER STATUS ANNUNCIATION.MA
G
NE
T
T
ES
T
TAMPER R B
+ -YY
TEST COIL +
TEST COIL -M/N DNR
1 2 3
54
DUCT SMOKE DETECTOR
M/N DNR W/RTS 151 REMOTE TEST STATION
RTS-151
REMOTE TEST
STATION
JUMPER MUST BE
INSTALLED BETWEEN
TERMINALS 2 & 5
DCOIL REMOTE TEST COIL ASSEMBLY
IS NOT REQUIRED WHEN THE
ASD-PL2FR SENSOR HEAD IS USED.
0 24 110 220
N/C COM N/O
RELAY WILL BE POWERED ALL
THE TIME. WIRE RELAY
OUTPUT ACCORDINGLY.
SEE NOTE 1
USE RELAYS
CONTACTS FOR
INTERFACE WITH
FIRE SMOKE DAMPER
120VAC POWER
0 24 110 220
N/C COM N/O
MR101/C
MR101/C
FIRE/ SMOKE DAMPER CONTROL CIRCUIT WIRING
M/N AOM-2RF W/MR101/C RELAY
LOCATE RELAY ARRAY WITHIN
3' OF CONTROLLED DEVICE
AOM-2RF ADDRESSABLE RELAY
MODULE
FORM "C" RELAY RATED AT
2 A @ 30 VDC,
.5 A @ 120 VAC
TOP
T11
T10 2 COM
T9 2 N/C
T8 2 N/O
T7 1 COM
T6 1 N/C
LOOP ADDRESS
SLC- T1
SLC+ T2
N/A T3
N/A T4
1 N/O T5
TENS ONES
THE MR-101C/R RELAY'S CONTACTS ARE LABELED IN THEIR
NON-ENERGIZED STATE. THE RELAYS ARE SHOWN WIRED SO THAT
THEY WILL IN FACT BE ENERGIZED AT ALL TIMES AS NOTED.
THIS BEING THE CASE, THE ACTUAL CONTACTS WILL
FUNCTION OPPOSITE OF THEIR LABELED STATE ENERGIZED.
NOTE 1
N/O COM N/C ACTUAL ENERGIZED STATE=
FAN DRIVE STATUS MONITORING
M/N AMM-2F
TENS ONES
IN/ OUT COMM +
AMM-2F
MONITOR MODULE
BLACKPURPLE
YELLOW
MONITORED DEVICE
N/O CIRCUIT
EOL FROM
AMM-2F MODULE
OUT (CONV ONLY) +
IN/OUT COMM -
RA/RTS -
RA +
RTS +
SLC INITIATING CIRCUIT (-) NEG
WIRING FROM FACP (+) POS{
2 #16AWG 2 #16AWG 2 #16AWG
NEG (-) SLC INITIATING CIRCUIT TO NEXT DEVICE OR
POS (+) RETURN TO ORIGINATING DEVICE TO MAINTAIN
CIRCUIT SUPERVISION
}
3 #16AWG
2 #12AWG
2 #12AWG
MR-101CR RELAY
24VDC AUXILIARY PANEL (+) POS
FIRE CONTROL PANEL OR (-) NEG {
OR BOOSTER
1 0 15
14213
123
114
1059687
1 0
2
3
4
5 9687
RED CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
E-001
12971596
GENERAL NOTES
AND SYMBOL
LEGENDS
H. TRAN
EWK
1019W
MARCH 12, 2021
GENERAL ELECTRICAL NOTES
1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT
ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY
CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALL
BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORK
PROCEEDS.
2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREAS
FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OF
WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROM
THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND
OPERABLE.
3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR
FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE
MATERIAL PENETRATED.
4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT
DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF
INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL
PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK.
5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE
EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON
CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED
WITH ASSOCIATED PHASE CONDUCTORS.
6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABEL
ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE
PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE AND
INVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH
CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667.
7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90
DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WET
AREAS.
9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE
ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTED
OTHERWISE.
10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE
PANELBOARD. SIZE AS INDICATED.
11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT
HANGERS FOR CONDUIT AS NEEDED.
12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND
DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND
REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MIND
SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES
ARE CORRECTED.
ELECTRICAL LEGEND
LIGHTING LEGEND
MOTOR
1'x4' LUMINAIRE
HARDWIRED EQUIPMENT CONNECTION
P-1A
12
HOMERUN TO PANEL P-1A, CIRCUIT #12. FED
FROM 20A -1P BREAKER IS INTENDED UNLESS
NOTED OTHERWISE. RUN GREEN WIRE GROUND
FOR ALL CIRCUITS. PROVIDE ONE GROUND PER
CIRCUIT.
EMERGENCY POWER OFF (EPO)
GROUND ROD ELECTRODE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH AFCI PROTECTION
QUAD RECEPTACLE
LINETYPES LEGEND
SPECIAL RECEPTACLE5-30R
PANELBOARD
JUNCTION BOX
B = INSTALLED IN BASEBOARD
TR = INSTALLED IN WOOD TRIM/ CASEWORK/ WAINSCOTT
SR = SURFACE RACEWAY
WP = WEATHERPROOF
AC = AIR CONDITIONER
EM = EMERGENCY
DUPLEX RECEPTACLE:
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
J
2'x4' LUMINAIRE
CEILING MOUNTED LUMINAIRE
EM LIGHTING BATTERY UNIT
COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT
SINGLE FACE, WALL MOUNT EXIT SIGN
DOUBLE FACE, WALL MOUNT EXIT SIGN
SINGLE FACE, CEILING MOUNT EXIT SIGN
DOUBLE FACE, CEILING MOUNT EXIT SIGN
LIGHT SWITCH:
SAFETY SWITCH (NON-FUSED)
SAFETY SWITCH (FUSED)
3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
D = DIMMER SWITCH
O = WALL SWITCH OCCUPANCY SENSOR
V = WALL SWITCH VACANCY SENSOR
W = WIRELESS SWITCH
S = WIRELESS SCENE SWITCH
WIRELESS OCCUPANCY SENSOR
WIRELESS DAYLIGHT SENSOR
OS
DS
1'x2' LUMINAIRE
FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
BATTERY CABINET
WATER FLOW SWITCH
MUXPAD
REMOTE ANNUNCIATOR
D = DUCT SMOKE DETECTOR
R = RELAY BASE
BR = BEAM RECEIVER
BT = BEAM TRANSMITTER
SB = SOUNDER BASE
SMOKE DETECTOR:
TAMPER SWITCH
AUDIBLE NOTIFICATION APPLIANCE
FACP
BATT
MUX
FAA
NAC PANELNAC
MANUAL PULL STATIONF
S X
F = FIXED TEMPERATURE
R = RATE OF RISE
R/F = COMBINATION RISE/FIXED TEMPERATURE
HEAT DETECTOR:
H X
CARBON MONOXIDE DETECTORCO
AM
F
XXcd
C
FS
F
S
XXcd
C
TS
ADDRESSABLE MODULE
XXcd = CANDELA
C = CEILING
COMBO A/V NOTIFICATION APPLIANCE:
XXcd = CANDELA
C = CEILING
VISUAL NOTIFICATION APPLIANCE:
SUPPRESSION SYSTEM
UNDERGROUND ELECTRICUE
UNDERGROUND LIGHTINGUL
OVERHEAD ELECTRICOE
TO BE PROVIDED
DEMOLITION / TO BE RELOCATED
EXISTING TO REMAIN
UNDERGROUND TELCOUC
MOUNTING HEIGHTS
CARD READER 48" TOP OF BOX
LIGHT SWITCH 48" TOP OF BOX
RECEPTACLE 18" TOP OF BOX
DATA OUTLET 18" TOP OF BOX
TV OUTLET 84" TOP OF BOX
PHONE OUTLET 48" TOP OF BOX
SAFETY SWITCH 60" CENTERLINE OF HANDLE
MOTOR STARTER 60" CENTERLINE OF HANDLE
PANELBOARD 72" TOP OF PANELBOARD
MANUAL PULL STATION 48" OPERABLE HANDLE
NOTIFICATION APPLIANCE 80" BOTTOM OF LENS
DOOR HOLD OPEN COORDINATE IN FIELD
EM BATTERY UNIT 96" BOTTOM OF UNIT
EM REMOTE UNIT 102" BOTTOM OF UNIT
EXIT SIGN 96" BOTTOM OF UNIT
LIGHT POLE WITH LED LUMINAIRES, REFER TO
PLANS FOR NUMBER AND CONFIGURATION OF
HEADS
GENERAL ELECTRICAL DEMOLITION NOTES
1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING
ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER
APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED.
REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED
OTHERWISE.
2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEW
WORK SHALL BE REUSED WHERE POSSIBLE.
3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTING
SYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWN
TO BE DEMOLISHED.
4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH
THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE
RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH
SURROUNDING MATERIALS, FINISHES, AND COLORS.
5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM
DEMOLITION NOT SPECIFIED TO BE INFILLED.
6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING
CONSTRUCTION.
MAGNETIC DOOR HOLDERDH
CARD READERCR
IT/ COMMUNICATIONS LEGEND
DATA RECEPTACLE
X = NUMBER OF CABLES TO BE PROVIDED
WIRELESS ACCESS POINT OUTLET-CEILING MTD.
WIRELESS ACCESS POINT OUTLET-WALL MTD.WLS
x
EM EMERGENCY LIGHT FIXTURE
ELECTRICAL ABBREVIATIONS
PC PHOTOCELL
PM PLUGMOLD
PP POWER PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RGS RIGID GALVANIZED STEEL CONDUIT
SR SURFACE RACEWAY
ST SHUNT TRIP
TM THERMAL MAGNETIC
TR TRIM/CASEWORK/WAINSCOTT
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UE UNDERGROUND ELECTRIC
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPS
WP WATERPROOF
ELECTRICAL ABBREVIATIONS
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
GAA GENERATOR ALARM ANNUNCIATOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSEPOWER
KW KILOWATT
LC LIGHTING CONTACTOR
LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUG ONLY
MTS MANUAL TRANSFER SWITCH
NAC NOTIFICATION APPLIANCE CIRCUIT
NIC NOT IN CONTRACT
OE OVERHEAD ELECTRIC
ELECTRICAL ABBREVIATIONS
AC AIR CONDITIONER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT INTERRUPTER
AMM ADDRESSABLE MONITOR MODULE
AOM ADDRESSABLE OUTPUT MODULE
ARB AUXILIARY RELAY BOARD
ATS AUTOMATIC TRANSFER SWITCH
B BASEBOARD
BKR BREAKER
C CONDUIT
CD CANDELA
CKT CIRCUIT
CR CONTROL RELAY
EC ELECTRICAL CONTRACTOR
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF STATION
ELECTRICAL SUBMITTAL SCHEDULE
MATERIAL
SCHEDULE/
SHOP
DWGS.
PRODUCT
DATA SAMPLES INSPECTIONS & TESTS O&M DATA WARRANTIES
LUMINAIRES X
PHONE/ DATA (TELECOMMUNICATIONS)X
LIGHTING CONTROLS X
WIRING DEVICES X
PANELBOARDS X
FIRE ALARM X
CARD ACCESS X
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING SIZE MANUFACTURER CATALOG NO. VOLTAGE BALLAST LAMPS WATTAGE FINISH
L1 RED LED FIXTURE RECESSED/ PLASTER FRAME 2'x2' KENALL CSEFL22-23R-DIM1-5F-2H-SM-PF 120-277V LED 23W
L2 WHITE LED FIXTURE RECESSED/ PLASTER FRAME 2'x2' KENALL M4SEDI-22-75L-35K8-DCC-277-2F-2H-SYM 120-277V LED 55W
L3 GENERAL LED FIXTURE RECESSED/ CEILING 2'x2' DAY-BRITE SIGNIFY-2-EV-G-45L-835-2-D-UNV-DIM 120-277V LED 23W
L4 SURGERY LED FIXTURE CEILING BURTON ALED070SC (SINGLE CEILING) 100-240V LED 70W
L5 BEAM IN USE FIXTURE SURFACE/ WALL 10" H x 15" W KENALL METMSU-MW-R-BIU-DT 120-277V LED 2W
L6 EXIT/ EMERGENCY SURFACE/ CEILING 9" H x 11" W DAY-BRITE SIGNIFY-VLLCR-3.6V-RED-WHITE-2(1W) 120-277V LED 2W
SCALE:12" = 1'-0"2 FIRE/ SMOKE DAMPER FIRE ALARM WIRING DIAGRAM
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% CD REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
W129A
W129
W139
W125
W123 W121 W111
W109A
W109
W107 W105 W103 W101
W164W162
W162A
W162B
W154B
W154C
W120W122
W124
W138
W144
W148 W150 W154A
W143A
W141
W143
W154
W145
W147 W153
W153B
W153A
W157
W157A
W159 W161
W100C
W100S
W142
W112A
W112B
W112 W106
W102
W106A
W117
W117C W117B
W117A
W126
W130
W146
W146A
UP
A106
A106A
A100UD
A100UG
A100UC
A100UJ
A100L
A100UK
A100SB
A100UH
A100TB
A100UF
A100UE
A100SA
A100J
A101
A100CA
A100UL A100CB
A100TC
A103
A100TA
UP
DN
DN
UP
UP
109
50
182
E100TA
E100SA
E100E
DN UP
W129A
W129
W139
W125
W123 W121 W111
W109A
W109
W107 W105 W103 W101
W164W162
W162A
W162B
W154B
W154C
W120W122
W124
W138
W144
W148 W150 W154A
W143A
W141
W143
W154
W145
W147 W153
W153B
W153A
W157
W157A
W159 W161
W100C
W100S
W142
W112A
W112B
W112 W106
W102
W106A
W117
W117C W117B
W117A
W126
W130
W146
W146A
UP
A106
A106A
A100UD
A100UG
A100UC
A100UJ
A100L
A100UK
A100SB
A100UH
A100TB
A100UF
A100UE
A100SA
A100J
A101
A100CA
A100UL
A100CB
A100TC
A103
A100TA1019W1019A 1019E1019A1019W1019A1019E1019ADFLW1-4
400A, 208Y/120V
FED FROM DPLW4-4
FLW1-5
100A, 208Y/120V
EPLW1-4
(EMERGENCY)
800A, 208Y/120V
FED FROM EPLW1-1
PLW1-3
100A, 208Y/120V
FED FROM DPLW1-2
EPLW1-2
(EMERGENCY)
100A, 208Y/120V
FED FROM EPLW1-1
DPLW1-2
400A, 208Y/120V
FED FROM DPLW1-1
PLW1-2
100A, 208Y/120V
FED FROM DPLW1-2
LCW1-1
100A, 240/120V
FED FROM DPLW1-2
PLW4-4
100A, 208Y/120V
FED FROM DPLW1-2
LCW1-2
100A, 240/120V
FED FROM DPLW1-2
LCW1-3
100A, 240/120V
FED FROM DPLW1-2
PLW1-10
100A, 208Y0/120V
FED FROM DPLW1-2
LCW1-11
100A, 240/120V
FED FROM DPLW1-4
EPLW1-1
400A MCB
208Y/120V
DPLW1-1
1000A MCB
208Y/120V
LHW1-1
100A, 480Y/277V
(LIGHTING)
DPHW1-1
225A, 480Y/277V
(HVAC)
PLW1-1
GFCI E3
FIRE ALARM
CONTROL PANEL CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
E-101
12971596
PARTIAL
EXISTING POWER
DISTRIBUTION
KEY PLAN
H. TRAN
EWK
1019W
MARCH 12, 2021
SCALE:1/8" = 1'-0"1 PARTIAL EXISTING POWER DISTRIBUTION KEY PLAN
0' 4' 8'16'
SCALE: 1/8"=1'-0"
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% CD REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
3
22
2 EM
222222EM22
EM
2
22
EM2EM
EM EMEM
2SSSS
EMEMEMEMEMEMEMEM S
F
CO
F F
S
W161W159
W157A
W157
W100C
W154A
W154C
W154B
W162B
W162A
W162 W164
1
3
5
6
7
8
9
10
7
4
4
3
6
3
55
PANEL PLW1-2
208Y/120V
5
3
5
4
3
3
55
3
5
3
5
5
W154
6
6
3
3 3
33
4
1
5
J
5
3
PANEL LCW1-11
100A, 240/120V
PANEL PLW1-10
100A, 208Y/120V
PANEL LCW1-1
100A, 240/120V
PANEL LCW1-2
100A, 240/120V
PANEL LCW1-3
100A, 208Y/120V
PANEL PLW1-4
100A, 208Y/120V
2 2EMEMEM EMEMEMEM
8
EM
7
A100TA
A103
A100UF
A100UE
11
FWL
11
11
11
1111
11
1111
11
1111
EPLW1-1
400A MCB
208Y/120V
DPLW1-1
1000A MCB
208Y/120V
LHW1-1
100A, 480Y/277V
(LIGHTING)
DPHW1-1
225A, 480Y/277V
(HVAC)
PLW1-1
GFCI E3
FIRE ALARM
CONTROL PANEL
EPLW1-2
(EMERGENCY)
100A, 208Y/120V
FED FROM EPLW1-1 DPLW1-2
400A, 208Y/120V
FED FROM DPLW1-1
7
7EXISTING CABLE
TRAY ABOVE TO REMAIN
(4) 4" CONDUITS UP
TO CIT ROOM ABOVE
12
12
12
12
12
12
13
131313 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
E-102
12971596
PARTIAL FIRST
FLOOR
ELECTRICAL
DEMOLITION
PLAN
H. TRAN
EWK
1019W
MARCH 12, 2021
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
E-102 KEYED DEMOLITION NOTES
1 HOOD TO BE REMOVED BY OTHERS. ELECTRICAL CONTRACTOR TO REMOVE THE
SWITCH CONNECTED TO THE HOOD AND ALL ASSOCIATED POWER WIRING AND
CONDUIT TO THE HOOD COMPLETELY BACK TO SOURCE.
2 REMOVE EXISTING EMERGENCY LIGHT, ASSOCIATED WIRING, AND CONDUIT
COMPLETELY BACK TO SOURCE. TYPICAL ON DRAWING.
3 REMOVE EXISTING LUMINAIRE. EXISTING LIGHTING CIRCUIT SHALL BE REUSED TO
FEED THE NEW LIGHTING. TYPICAL IN ROOM. TYPICAL ON DRAWING.
4 EXISTING PHONE/ DATA BOX AND CABLES TO BE REMOVED. NUMBER INDICATES
CABLE QUANTITY. SEE GENERAL NOTE FOR ADDITIONAL INFORMATION. TYPICAL
ON DRAWING.
5 REMOVE EXISTING WM 3000, ASSOCIATED RECEPTACLES, CONDUIT, AND WIRING
COMPLETELY BACK TO SOURCE. TYPICAL ON DRAWING.
6 ABATEMENT CONTRACTOR TO COORDINATE WITH CORNELL ELECTRIC SHOP TO
REMOVE LAB BENCH SURFACE MOUNTED RECEPTACLES, ASSOCIATED CONDUIT,
AND POWER WIRING COMPLETELY BACK TO SOURCE.
7 REMOVE EXISTING POWER PANEL, ASSOCIATED CONDUIT, FEEDER CONDUCTORS,
AND BRANCH CIRCUITS COMPLETELY BACK TO SOURCE. SAVE CIRCUIT BREAKERS
FOR REUSE TO FILL IN OTHER EXISTING POWER PANELS.
8 REMOVE DARK ROOM LIGHT FIXTURE, ASSOCIATED CONDUIT, AND WIRING
COMPLETELY BACK TO SOURCE.
9 REMOVE IN-USE LIGHT FIXTURE, ASSOCIATED CONDUIT, AND WIRING COMPLETELY
BACK TO SOURCE.
10 REMOVE OLD TELEPHONE BOX, ASSOCIATED CONDUIT, AND WIRING COMPLETELY
BACK TO SOURCE.
11 PROVIDE TEMPORARY HEAT DETECTOR DURING THE CONSTRUCTION. CIRCUIT
TEMPORARY HEAT DETECTOR TO NEAREST INITIATION CIRCUITRY. COORDINATE
WITH CORNELL EH&S FOR THE TESTING OF THE DETECTOR.
12 EXISTING ELECTRIC REHEAT TO BE REMOVED BY MECHANICAL CONTRACTOR.
ELECTRICAL CONTRACTOR TO DISCONNECT POWER TO THE UNIT. TAG AND SAVE
THE EXISTING POWER CIRCUIT. CIRCUIT TO BE REUSED TO FEED THE NEW UNIT.
EXISTING PANEL DPHW1-1 LOCATED IN ROOM 100UF IS CURRENTLY FEEDING THE
EXISTING ELECTRIC REHEAT.
13 EXISTING EMERGENCY RECEPTACLE TO REMAIN.
SCALE:1/4" = 1'-0"1 PARTIAL FIRST FLOOR ELECTRICAL DEMOLITION PLAN
E-102 GENERAL DEMOLITION NOTES
1.0 REMOVE ALL SURFACE RACEWAYS RELATE TO THE REMOVE WORK COMPLETELY.
RACEWAYS LOCATED IN EXISTING WALL TO REMAIN SHALL BE ABANDONED IN
PLACE. REMOVE ALL ASSOCIATED WIRING AS REQUIRED.
2.0 PHONE/ DATA CABLES SHALL BE REMOVED IN THEIR ENTIRETY BACK TO THE CIT
TELECOMMUNICATIONS ROOM LOCATED ON THE SECOND FLOOR ABOVE ROOM
A100UE.
3.0 AFTER THE REMOVAL OF EXISTING RECESS MOUNTED ELECTRICAL DEVICES AND
PHONE/DATA BOXES, COORDINATE WITH GENERAL CONTRACTORS TO PATCH
EXISTING WALLS.
4.0 DRAWING MAY NOT REPRESENT ALL WORK REQUIRED FOR ELECTRICAL
DEMOLITION. IT IS THE CONTRACTOR’S RESPONSIBILITY TO FIELD VERIFY ALL
DEMOLITION REQUIREMENTS PRIOR TO BID SUBMISSION.
5.0 CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE DISPOSAL OF DEBRIS AND
MATERIALS GENERATED FROM THE SCOPE OF WORK AS A RESULT OF THE
DEMOLITION PROCESS UNLESS OTHERWISE COORDINATED WITH G.C..
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% CD REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
S D
DD DSSD DDS D
D DD
DSS
SD
F
CO
SSD
F F
S
D
DDD
D
SD
DS
W161
W161BW161A
W100C
W154B
W154A
W154
W154C
W156
PANEL LCW1-1
100A, 240/120V
PANEL PLW1-4
100A, 208Y/120V
A100TA
A103
A100UF
A100UEW162CW162D
W162W162B
W162A
W162E
W161C
EPLW1-2
(EMERGENCY)
100A, 208Y/120V
FED FROM EPLW1-1 DPLW1-2
400A, 208Y/120V
FED FROM DPLW1-1
EPLW1-1
400A MCB
208Y/120V
LHW1-1
100A, 480Y/277V
(LIGHTING)
GFCI E3
FIRE ALARM
CONTROL PANEL
DPLW1-1
1000A MCB
208Y/120V
DPHW1-1
225A, 480Y/277V
(HVAC)
PLW1-1
1
EXISTING CABLE
TRAY ABOVE TO REMAIN
L3L3
L3 L3L3
L3L3
L3 L3
L3 L3 L3
L3
L3
L3
L3
L3 L3L3
L3
L3L3
L3
L3 L3
L3
L3
L3
L2L1
L1 L2
L3
L3
L3
L3L3
L3L3
L3
L3 L3
L3L3
L3
L3
L3
L3
L3 L3
L3
L3
(4) 4" CONDUITS UP
TO CIT ROOM ABOVE
L5
3
5
3
L6
4
2
2
2
2
6
2
2
22
2
2
2
22
2
3
6
2
7
L4
8
9
FSD-4
PLW1-2, #9
FSD-1
9
PLW1-2, #9
FSD-3
9
PLW1-2, #9
FSD-2 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
E-103
12971596
PARTIAL FIRST
FLOOR LIGHTING
& FIRE ALARM
PLAN
H. TRAN
EWK
1019W
MARCH 12, 2021
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
E-103 KEYED RENOVATION NOTES
1 PROVIDE NEW FIRE ALARM NOTIFICATION DEVICE AND ASSOCIATED WIRING AS
INDICATED. NEW DEVICE SHALL BE COMPATIBLE WITH THE EXISTING GFCI E3 FIRE
ALARM CONTROL PANEL. CONTACT TIM McGEE (1-585-202-3602) FROM WEST FIRE
SYSTEMS INC. FOR PRODUCT INFORMATION. TYPICAL ON DRAWING.
2 AT LOCATION SHOWN, PROVIDE A RECESS MOUNT 0-10V DIMMING WALL SWITCH
OCCUPANCY SENSOR, WATTSTOPPER PW-311-W-U (120/277V), INCLUDING
WATTSTOPPER WHITE WALL PLATE. CIRCUIT TO NEW LIGHTING AND TO EXISTING
LIGHTING CIRCUITRY SERVING THIS AREA. LIGHTING SHALL BE CONTROLLED VIA
ALC. REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
3 AT LOCATION SHOWN, PROVIDE A SURFACE MOUNT 0-10V DIMMING WALL SWITCH
OCCUPANCY SENSOR, WATTSTOPPER PW-311-W-U (120/277V), INCLUDING
WATTSTOPPER WHITE WALL PLATE. CIRCUIT TO NEW LIGHTING AND TO EXISTING
LIGHTING CIRCUITRY SERVING THIS AREA. SURFACE BOX SHALL BE A WHITE
SINGLE GANG, AND SURFACE RACEWAY SHALL BE WIREMOLD 700 (IVORY).
LIGHTING SHALL BE CONTROLLED VIA ALC. REFER TO MECHANICAL DRAWINGS
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
4 AT LOCATION SHOWN, PROVIDE A RECESS MOUNT TOGGLE LIGHT SWITCH TO
CONTROL THE BEAM IN USE LUMINAIRE LOCATED OUTSIDE OF ROOM. CIRCUIT TO
NEW LIGHTING AND TO EXISTING LIGHTING CIRCUITRY SERVING THIS AREA.
5 CIRCUIT CEILING MOUNT COMBO EXIT/ EMERGENCY LIGHT TO NEAREST EXIT
LIGHTING CIRCUITRY.
6 PROVIDE WEATHERPROOF COVERS FOR THE LIGHT SWITCHES.
7 PROVIDE A CEILING MOUNT WATTSTOPPER LIGHTSAVER LS-102 SWITCHING
PHOTOSENSOR (DAY LIGHTING HARVESTING SENSOR) AND POWER PACK TO
CONTROL THE LIGHTING IN THIS ROOM. WIRING PER MANUFACTURING
RECOMMENDATION.
8 CEILING MOUNT SURGERY LIGHT. SEE LUMINAIRE SCHEDULE FOR THE PRODUCT
INFORMATION AND CIRCUIT TO A SPARE 20A/1P CIRCUIT BREAKER LOCATED IN
EXISTING PANEL LCW1-1.
9 PROVIDE 120V POWER CONNECTION TO FIRE/ SMOKE DAMPER AS INDICATED.
REFER TO FIRE/ SMOKE DAMPER FIRE ALARM WIRING DIAGRAM ON E-001 FOR
ADDITIONAL WORK.
#
SCALE:1/4" = 1'-0"1 PARTIAL FIRST FLOOR LIGHTING & FIRE ALARM PLAN
E-103 GENERAL NOTES
1.0 CIRCUIT ALL NEW LIGHTING TO EXISTING 277V LIGHTING CIRCUITS SERVING THE
AREA UNLESS OTHERWISE INDICATED. THE 480Y/277V LIGHTING PANEL LHW1-1 IS
LOCATED IN ELECTRIC ROOM A100UF.
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% CD REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION
EM
EMEMEM
2222 2 22 2222
22 32
2
222222 2
2
4 232
3
3
22
2
2
2
222222CR
CR
CR
CR 222
W161
W161BW161A
W100C
W162C
W162A
W162
W154B
W154A
W154
W154C
W156
PANEL LCW1-1
100A, 240/120V
PANEL PLW1-4
100A, 208Y/120V
A100TA
A103
A100UF
A100UE
W162B
W161C
EPLW1-1
400A MCB
208Y/120V
LHW1-1
100A, 480Y/277V
(LIGHTING)
GFCI E3
FIRE ALARM
CONTROL PANEL
DPLW1-1
1000A MCB
208Y/120V
DPHW1-1
225A, 480Y/277V
(HVAC)
PLW1-1
EPLW1-2
(EMERGENCY)
100A, 208Y/120V
FED FROM EPLW1-1 DPLW1-2
400A, 208Y/120V
FED FROM DPLW1-1
PLW1-2
100A, MLO
208Y/120V
W162D
W162E
(4) 4" CONDUITS UP
TO CIT ROOM ABOVE
EXISTING CABLE
TRAY ABOVE TO REMAIN
1
1
1
1
11
1
1
11
1
1
1 1
1
1
2
18" AFF
42" AFF
PLW1-2, #8
PLW1-2, #4
18" AFF
PLW1-2, #5 PLW1-2, #6 PLW1-2, #7
42" AFF
18" AFF
18" AFF 18" AFF
PLW1-2, #1
PLW1-2, #2 PLW1-2, #3
WL
42" AFF
3
4 4
4
4
4
42" AFF
4
4
3
4
4
42" AFF
442" AFF
3
3
3
3
3
3
3
3
3
3
5
6
7
9
WL
7
WL
8 WL42" AFF7
WL
9
SERVER
RACK EM9
42" AFF
42" AFF
6
WL
10
11
12
12
10
1
42" AFF
3
3
1
18" AFF
42" AFF
13 FCU-161-214FCU-161-1
PLW1-2, #11
EDH-161-1
14
PLW1-2, #11
13
EDH-161-214FCU-161-4
PLW1-2, #10
FCU-161-3
PLW1-2, #10
14
FCU-162-1 14
PLW1-2. #11
13
EDH-162-5
13
EDH-162-4
13
EDH-162-1
13
EDH-162-2
13
EDH-162-3
13
EDH-154-3
13
EDH-156-1
13
EDH-154-1
13
EDH-154-2
13
EDH-154-2
151515
OFFSET DATA OUTLETS
FROM POWER OUTLETS
UTILIZE RADIUS
CONTROLLED FITTINGS
CEILING
FLOOR PER PLANHEIGHT AFFPANEL PLW1-2
LOCATION:
FED FROM:
MOUNTING:
ENCLOSURE:
VOLTS:
PHASE:
WIRES:
AIC RATING:
MAINS TYPE:
MAINS RATING:
W161C
DPLW1-2
RECESSED
NEMA 1
208Y/120V
3
4
10 KA
MLO
100A
CKT CKTDESCRIPTIONTRIPPOLESABCPOLESTRIPDESCRIPTION
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
RECEPT. W161C
RECEPT. W161B
RECEPT. W161
RECEPT. W161
FIRE/ SMOKE DAMPERS
FCU 161-1, 161-2, 162-1
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20A 1
20A 1
20A 1
20A 1
20A 1
20A 1
20A 1
20A 1
20A 1
20A 1
20A 1
20A 2
30A 2
1
1
1
1
1
1
1
1
1
1
1
2
2
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
30A
FCU 161-4, 161-3
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
RECEPT. W161
RECEPT. W161
RECEPT. W161A
RECEPT. W161
NOTES:
THE FOLLOWING CABLES ARE FOR EACH DOOR'S CORRESPONDING DEVICES:
(6) #22AWG STANLEY 2S22062B5 READER POWER & COMM.
(4) #18AWG STANLEY 2U18042BK5 STRIKE POWER & REQUEST TO EXIT
(2) #18AWG STANLEY 2S18022RD5 DOOR CONTACT
PROVIDE A COMPLETE ACCESS CONTROL SYSTEM, INCLUDING ACCESS CONTROL
MODULES, CONDUIT AND WIRE, AND PROGRAMMING. REFER TO AND COMPLY
WITH CORNELL DESIGN STANDARD 281316.
CEILING
W260D
EXISTING CARD READER PANEL
1" EMT 22 AWG/ 2 PAIR TWISTED/ SHEILDED,
18 AWG/ 1 PAIR TWISTED
BASE
BID
NEW BAS-CTX CABINET (1-4A, 12/24V PS; LNL 1320)
W162 (ABOVE CEILING)
1" EMT 22 AWG/ 2 PAIR TWISTED/ SHEILDED,
18 AWG/ 1 PAIR TWISTED
DOOR W162 (BASE BID)
DOOR W161 (ALTERNATE 1)
ALT 1
NEW BAS-CTX CABINET (1-4A, 12/24V PS; LNL 1320)
W156 (ABOVE CEILING)
DOOR W156 (ALTERNATE 1)
DOOR W154 (ALTERNATE 1)CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
215 TOWER ROAD
ITHACA, NEW YORK 14853
SEELEY G. MUDD
FIRST FLOOR
A&A LAB
RENOVATION
E-104
12971596
PARTIAL FIRST
FLOOR POWER &
DATA PLAN
H. TRAN
EWK
1019W
MARCH 12, 2021
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"1 PARTIAL FIRST FLOOR POWER & DATA PLAN
#E-104 KEYED RENOVATION NOTES
1 AT THIS LOCATION, FROM A POINT ABOVE CEILING, PROVIDE A VERTICAL SECTION
OF WIREMOLD 4000 (TWO PIECE-STEEL MULTIPLE CHANNEL LARGE RACEWAY WITH
A DIVIDER) DOWN WALL. TRANSITION THE VERTICAL WIREMOLD 4000 TO RUN
HORIZONTALLY AS INDICATED. THE TOP CHANNEL TO HOUSE THE DATA OUTLET(S),
THE BOTTOM CHANNEL TO HOUSE DUPLEX RECEPTACLE(S). PROVIDE 1" FROM THE
POWER PANEL TO THE TOP OF THE VERTICAL SECTION OF WIREMOLD FOR POWER.
PROVIDE 3/4" CONDUIT FOR EVERY 2 DATA CABLES AND 1" CONDUIT FOR EVERY 3
DATA CABLES FROM THE EXISTING CABLE TRAY TO THE TOP OF THE VERTICAL
SECTION OF THE WIREMOLD.
2 UTILIZE EXISTING CABLE TRAY AND CONDUITS TO PULL NEW DATA CABLES UP TO
THE CIT TELECOMMUNICATIONS CLOSET ABOVE THIS ROOM. DO NOT PROVIDE
TOO MUCH SLACK ON THE CABLES. COORDINATE THE LENGTH OF THE CABLES
INSIDE OF ROOM WITH JOSEPH L. BLASZ.
3 CIRCUIT TO A SPARE 20A/1P CIRCUIT BREAKER LOCATED IN EXISTING PANEL
PLW1-4. UPDATE PANEL DIRECTORY AS REQUIRED.
4 CIRCUIT TO A SPARE 20A/1P CIRCUIT BREAKER LOCATED IN EXISTING PANEL
LCW1-1. UPDATE PANEL DIRECTORY AS REQUIRED.
5 ELECTRICAL CONTRACTOR TO PROVIDE UNINTERRUPTED POWER SUPPLY (UPS),
APC SMART-UPS C SMC1500C UPS AC 120V 900W WITH APC SMARTCONNECT
OUTPUT CONNECTORS: 8-BLACK.
6 AT 12" BELOW NEW CEILING, PROVIDE A RECESS BOX WITH A 1" EMT TO THE
EXISTING CABLE TRAY. PROVIDE ONE CAT 6A CABLE RUNNING FROM BOX TO THE
CIT ROOM. REFER TO GENERAL NOTES ON THIS DRAWING FOR ADDITIONAL
INFORMATION. ACCESS POINT (WIRELESS DEVICE TO BE PROVIDED BY CIT).
7 AT 12" BELOW NEW CEILING, PROVIDE A SUFACE BOX WITH A 1" EMT TO THE
EXISTING CABLE TRAY (SURFACE RACEWAY ON WALL SHALL BE A WM 2300).
PROVIDE ONE CAT 6A CABLE RUNNING FROM BOX TO THE CIT ROOM. REFER TO
GENERAL NOTES ON THIS DRAWING FOR ADDITIONAL INFORMATION. ACCESS
POINT (WIRELESS DEVICE TO BE PROVIDED BY CIT).
8 BASE BID, PROVIDE CARD READER. REFER TO DETAIL ON THIS SHEET FOR
ADDITIONAL INFORMATION.
9 ALTERNATE 1, PROVIDE CARD READER. REFER TO DETAIL ON THIS SHEET FOR
ADDITIONAL INFORMATION.
10 REPLACE ALL EXISTING 2 POLE AND 3 POLE CIRCUIT BREAKERS WITH 20A/1P
CIRCUIT BREAKERS. UTILIZE THE EXISTING 20A/1P CIRCUIT BREAKERS FROM THE
REMOVED POWER PANELS IN OTHER ROOMS.
11 SEE PANEL SCHEDULE ON THIS SHEET FOR ADDITIONAL INFORMATION. CIRCUIT TO
THE EXISTING 100A/3P CIRCUIT BREAKER LOCATED IN PANEL DPLW1-2. PROVIDE (4)
2 AWG & (1) 8 AWG GROUND IN 1-1/4" EMT BETWEEN THE TWO PANELS AS
REQUIRED.
12 PROVIDE ALL ELECTRICAL DEVICES WITH WEATHERPROOF COVERS.
13 480V ELECTRIC DUCT HEATER. CIRCUIT TO EXISTING 480V CIRCUITRY THAT
ORIGINALLY FED THE EXISTING ELECTRIC REHEAT UNIT. MODIFY AND EXTEND
EXISTING POWER WIRING AND CONDUIT AS REQUIRED. SEE DRAWING E-102.
14 120V FAN COIL UNIT. CIRCUIT AS INDICATED.
15 CIRCUIT NEW CONTROL PANEL TO A SPARE 20A/1P CIRCUIT BREAKER LOCATED IN
EXISTING PANEL PLW1-4.
E-104 GENERAL NOTES
1.0 REFER TO CORNELL UNIVERSITY STANDARD DIVISION 2700 FOR DATA WORK
REQUIREMENTS AND INFORMATION ON THE CABLES, JACKS, FACEPLATES,
TESTING, AND LABELING. CONTACT CIT ENGINEER JOSEPH L. BLASZ
(JLB222@CORNELL.EDU/607-255-0770) FOR ASSISTANCE.
2.0 PROVIDE 3/4" CONDUIT FOR EVERY 2 DATA CABLES AND 1" CONDUIT FOR EVERY 3
DATA CABLES.
3.0 ALL NEW DATA CABLES SHALL BE CAT 6A.
4.0 TELE/ DATA CONTRACTOR TO PROVIDE A CABLE SCHEDULE WITH OUTLET CABLE
ID's TO CIT BEFORE SERVICES CAN BE ACTIVATED.
5.0 UNLESS OTHERWISE INDICATED, MOUNT NEW RECEPTACLE AND DATA BOXES AT
18" AFF.
NOT TO SCALE2WIREMOLD 4000 DETAIL
SCALE:12" = 1'-0"3 ACCESS CONTROL SCHEMATIC DIAGRAM
1 01/15/21 ISSUE FOR DD REVIEW
2 02/19/21 ISSUE FOR 95% CD REVIEW
3 03/12/21 ISSUE FOR CONSTRUCTION