HomeMy WebLinkAboutCorson Hall E136-E142A Lab Renovation Indexed DrawingsDrawing ListGeneralG-000Cover SheetG-001Code Compliance Plan & NotesG-002 Atrium Wall ImprovementsArchitecturalA-000General Notes and LegendsA-101Partial First Floor Plans -Labs E136-E142A-420 Interior ElevationsA-501Interior Details -Lab CaseworkA-601Equipment Schedule, Door Schedule & DetailsA-602Room Finish Schedule & LegendA-603SpecificationsPlumbingP-000General Notes, Symbols List, Details & Schedules -PlumbingP-100Partial First Floor Plans -PlumbingMechanicalM-000General Notes, Symbols List & Schedules -HVACM-101First Floor Plans -HVACM-200Details -HVACM-300Control Schematics & System SummariesElectricalE-000Electrical Symbols List & General NotesE-100Partial First Floor Plan -PowerE-101Partial First Floor Plan -LightingE-200Electrical Details & ScheduleFire ProtectionFP-100General Notes, Symbols List, Details & Floor Plans -Fire ProtectionThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:RevisionsSWBR Project #5/11/2021 9:30:56 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFCover SheetCWJAD/CREG-000100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 2021May 7, 2021Corson Hall RmE136-E142A LabRenovation100% Construction Documents20625.01215 Tower RdIthaca, NY 14853Architect & Structural Engineer:SWBR387 East Main StreetRochester, NY 14604585 232 8300rochester@swbr.comMechanical, Electrical, Plumbing & Fire Protection Engineer:Regional MapLocation MapCorson-Mudd HallCorson-Mudd HallPrimary Access Road EntranceLoading DockTOWER ROADGARDEN AVECAMPUS ROADTOWER ROADGARDEN AVECAMPUS ROADEnvironmental Engineer:Delta Engineers, Architects & Surveyors800 Hooper RoadEndwell, NY 13760607 231 6600M/E Engineering300 Trolley BlvdRochester, NY 14606585 288 5590 XXE1FBE1FBE1FBE1FBE2SEE2SEE2FBE2FBE151 E149 E145B E145 E145AE141E139 E137E131E131AE100UBE100UAE129E125E123E150E148E146E116E100TAE120E100SAE100CBE100CAE100SBE100EE141AE118E150AE117E115E113E111E109E107E105E103E104E108E106E110 E112 E114E107AE107BE100CEE100CDE100CCWASHERW129AW129W139W125W123W121AW115W121W111W109AW109W107W105W103W101W164W162W162AW162BW154BW154CW120W122W126W138W144W148W150W154AW143AW141W143W154W145W147W153W153BW153AW157W157AW159W161W100CW100SW142W112AW112BW112W106W102W106AA106A106AA100UDA100UGA100UCA100UJA100LA100UKA100SBA100UHA100TBA100UFA100UEA100SAA100JA101A100CAA100ULA100CBW115AW115BW115CW130W124DNUPDNDNUPUPUPDNDNUPUPCLASSIFICATIONS OF BUILDING, AS SPECIFIED IN THE 2020 EDITION OF THE BUILDING CODE OF NEW YORK STATE ARE AS FOLLOWS:BUILDING DATA AND CODE COMPLIANCEBUILDING DATA:CONSTRUCTION CLASSIFICATION:BUILDING OCCUPANCY CLASSIFICATION:FIRE PROTECTION SYSTEM:RENOVATION AREA:EXISTING FLOOR ASSEMBLY:1A (PER RECORD DRAWINGS PROVIDED BY CORNELL)B -BUSINESSPARTIALLY SPRINKLERED1,010 SF2 HR FIRE-RATEDECODE COMPLIANCE PLAN LEGENDEXIT. MAINTAIN OPERATIONAL AT ALL TIMES DURING CONSTRUCTIONINDICATES FIRE-RESISTANT WALL CONSTRUCTION OF VARIOUS TYPES AND HOURLY RATINGS. SEE FIRE-RESISTANT CONSTRUCTION WALL LEGEND.POINT OF ORIGINDECISION POINTCPET = X'-X"EATD = X'-X"COMMON PATH OF EGRESS TRAVELCPET = X'-X"EGRESS ACCESS TRAVEL DISTANCEEATD = X'-X" CODE COMPLIANCE GENERAL NOTESCODE COMPLIANCE DRAWINGS ARE INTENDED TO ASSIST IN THE PERMIT PROCESS AND TO PROVIDE GENERAL INFORMATION TO THE CONTRACTORS WITH RESPECT TO LIFE-SAFETY PROVISIONS OF THE PROJECT. THESE DRAWINGS SHOULD NOT BE USED TO DETERMINE THE SCOPE OF OTHER WORK SPECIFICALLY INDICATED ELSEWHERE IN THE DOCUMENTS. THESE DRAWINGS SHALL BE USED FOR THE LOCATIONS OF FIRE-RESISTANT RATED WALL CONSTRUCTION.THE FOLLOWING BUILDING AND ACCESSIBILITY CODES AND STANDARDS ARE APPLICABLE TO THIS PROJECT:A. 2020 BUILDING CODE OF NEW YORK STATEB. 2020 FIRE CODE OF NEW YORK STATEC. 2020 PLUMBING CODE OF NEW YORK STATED. 2020 MECHANICAL CODE OF NEW YORK STATEE. 2020 FUEL GAS CODE OF NEW YORK STATEF. 2020 ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATEG. NATIONAL ELECTRICAL CODE, NFPA 70, -2017 EDITION AS REFERENCED BY THE NYS CODES ABOVE.H. ICC A117.1, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES -2009 EDITION AS REFERENCED BY THE NYS CODES ABOVE.I. U.S. DEPARTMENT OF JUSTICE, 2010 AMERICANS WITH DISABILITIES ACT (ADA) STANDARDS FOR ACCESSIBLE DESIGN.REFERENCE FCNYS CHAPTER 33 FOR FIRE SAFETY PROVISIONS DURING CONSTRUCTION, DEMOLITION.FIRE EXTINGUISHERACCESSIBLE ENTRANCECONTROL AREA BOUNDARYFEFIRE RESISTANCE RATING SCHEDULE FOR BUILDING ELEMENTSCONSTRUCTION CLASSIFICATION TYPE 1A.DESCRIPTIONTEST REFERENCECOMMENTSFIRE RESISTANCERATINGSTRUCTURAL FRAME INCLUDING COLUMNS, GIRDERS AND TRUSSES3, EXISTING-EXISTING ASSEMBLY, CONCRETE ENCASED STRUCTURAL STEELINTERIOR AND EXTERIOR BEARING WALLS3, N/A-EXISTING ASSEMBLY, N/AFLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS2, EXISTING-EXISTING ASSEMBLY, POURED CAST-IN-PLACE CONCRETE FLOOR SLABROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS1 1/2, EXISTING-EXISTING ASSEMBLYFIRE-RESISTANT CONSTRUCTION LEGENDDESCRIPTIONPLAN DESIGNATIONFIRE WALL2FW3FWFIRE BARRIER (HORIZONTAL EXIT, INCIDENTAL USE/HAZARD, OCCUPANCY SEPARATION)1FB2FBSHAFT ENCLOSURE (FIRE BARRIER AT ELEVATOR, STAIR OR MECHANICAL SHAFT)1SE2SEFIRE PARTITION (ELEV LOBBY, CORRIDOR WALL, TENANT & DWELLING UNIT SEPARATION)1FPPRESUMED EXISTING FIRE-RATED ASSEMBLIESPREFIX E. SEE NOTE 1WHEN THE PREFIX "E" IS INDICATED ON THE CODE COMPLIANCE FLOOR PLAN, IT DENOTES EXISTING WALL CONSTRUCTION WITH A PRESUMED FIRE-RESISTANCE RATING OF THE TYPE INDICATED AS INDICATED ON RECORD DRAWINGS PROVIDED BY THE OWNER. THE ACTUAL CONDITIONS IN THE FIELD HAVE NOT BEEN VERIFIED TO CONFIRM COMPLIANCE. NEW PENETRATIONS SHALL BE CONSTRUCTED IN ACCORDANCE WITH UL LISTED THROUGH-PENETRATION FIRE STOP SYSTEMS FOR THE RATING INDICATED. NEW OPENINGS TO BE PROTECTED WITH OPENING PROTECTIVES FOR RATING INDICATED.2FW3FW1FB2FB1SE2SE1FPNOTES:1.EE2. PENETRATIONS THROUGH FIRE-RESISTANT CONSTRUCTION SHALL BE BUILT IN ACCORDANCE WITH U.L. LISTED THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE CODE COMPLIANCE PLAN FOR FIRE-RATED PARTITIONS LOCATIONS.596 SFWET LABE142136 SFMICROSCOPY/MICROINJECTIONE13864 SFPREPE142A189 SFANIMAL ROOME136CORRIDOREXISTING NON-RATED PARTITIONE146E148E150E1FBE1FBE1FBE1FBE1FBE1FBEXISTING 45 MIN FIRE-RATED DOORS IN EXISTING FIRE-RATED FRAMESEXISTING 90 MIN FIRE-RATED DOOR IN EXISTING FULLY-WELDED FRAME IN MASONRY CONSTRUCTION - EQUIVALENT CONSTRUCTION TO FIRE-RATED FRAME45 MIN FIRE-RATED DOOR IN EXISTING FULLY-WELDED FRAME IN MASONRY CONSTRUCTION - EQUIVALENT CONSTRUCTION TO FIRE-RATED FRAME45 MIN FIRE-RATED DOOR IN EXISTING FULLY-WELDED FRAME IN MASONRY CONSTRUCTION -EQUIVALENT CONSTRUCTION TO FIRE-RATED FRAMEACCESSIBLE SINKADJUSTABLE HEIGHT FUME HOODACCESSIBLE WORKSTATION, POWER, DATA AND NG WITHIN REACH RANGESLIDING DOOR PERMITTED PER BC1010.1.2 EXCEPTION 9ANSI A117.1-2009 §304DOOR COMPLIES WITH ACCESSIBLE OPERATING CLEARANCES, BUT THE EXISTING THRESHOLD DOES NOT COMPLY WITH ANSI A117.1-2009 §303EXISTING CONTROL AREA 1PROJECT WORK AREA, SEE PLAN 2/G-001 FOR ROOM INFORMATIONEXISTING EMERGENCY SHOWERTEMPORARY CONSTRUCTION PARTITION AS ALLOWED IN BC603.1. CONSTRUCT AROUND EXISTING LIGHT FIXTURES.EXISTING CONTROL AREA 2FECPET = 34'-6"EATD = 128'-2"E2FBE2FBE2FBE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2FBE2FBE2FBE2SEE2SEE2SEE2FBE2FBE2SEE2FBE2FBE1FBE2FBE2FBE2FBE2FBE2FBE2FBE2FBE2FBE2FBCPET = 49'-0"CPET = 55'-0" (ALONG ACCESSIBLE PATH)These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:58 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFCode Compliance Plan& NotesCWJAD/CREG-001100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 20211/8" = 1'-0"2First Floor Code Compliance Plan1/16" = 1'-0"1First Floor Code Compliance Plan - East WingN E151E150E100TAE100SAE100EE150AE103E100CEA106A100UDA100UGA100UCA100UJA100LA100SBA100JA100CAA100ULA100CBDNUPUPDNEXISTING DUCT W/ FIRE-WRAPUL-LISTED THRU-PENETRATION, FIRESTOP SYSTEM AT PENETRATIONSC-H STUD (BEYOND)2-HR SHAFT WALL CONSTRUCTION, "S2". ANCHOR TO DECK ABOVE.EXISTING ELECTRICALEXISTING FIRE-RATED PARTITION AND DOORVIF+/- 1' - 0"VIF+/- 1' - 3"EXISTING SUSPENDED ACOUSTICAL TILE CEILING, REMOVE AND REINSTALL ACOUSTICAL CEILING TILES AS REQUIRED TO ACCOMMODATE SOFFIT AND THRU-PENETRATION FIRESTOPPING WORK. PROVIDE NEW MATERIAL AS NECESSARY TO REPLACE DAMAGED COMPONENTSVIF+/- 4"VIF+/- 4"LINE OF STRUCTUREEXISTING DOOR TRANSOM PANELEXISTING CONTROL AREA BOUNDARYE2FBE2FBE1FBE2FBE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2SEE2FBE2FBRELOCATE WIRES TO NOT IMPEDE TRANSFER GRILLE, PHOTO AINSTALL FIRESTOPPING AT APPROXIMATE 1”X 12”VOID BETWEEN MULTI-DUCT ASSEMBLY AND ADJACENT WALL. (PHOTO D)E2FBE2FBE2FBE2FBE2FBE2FBG-0022E2FBE2FBE2SEE2SEE2SEE2SEPROVIDE 2-HR RATED SOFFIT ABOVE, SEE DETAIL 3/G-002FIRESTOP EXISTING OPEN JUNCTION BOX (PHOTO C)FIRESTOP EXISTING PENETRATION IN CONCRETE WALLINSTALL FIRESTOPPING AT GAP BETWEEN (2) EXISTING CONDUITS ABOVE DOOR (PHOTO E)E2FBPROVIDE (2) LAYERS OF GYPSUM BOARD AT VOID IN GYPSUM BOARD FURRING ABOVE ACT CEILING (PHOTO B)INSTALL FIRESTOPPING AT (2) EXISTING PNEUMATIC TUBES (PHOTO F)INSTALL FIRESTOPPING AT EXISTING MC CABLE (PHOTO F)INSTALL THROUGH PENETRATION FIRESTOPPING AT (4) EXISTING PIPE PENETRATIONS (UL WL-5028 SIM.) (PHOTO F)EXISTING DUCTVIF+/- 3' - 9"These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:59 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFAtrium WallImprovementsCWJCREG-002100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 20211 1/2" = 1'-0"3Fire-Rated Soffit Detail1/8" = 1'-0"1First Floor Code Compliance Plan - East Atrium WallN1/4" = 1'-0"2First Floor Code Compliance Plan - East Atrium WallPHOTO A: WIRES IMPEDING TRANSFER GRILLEPHOTO D: VOID AT MULTIDUCT ASSEMBLYPHOTO B: VOID IN GYPSUM BOARD FURRINGPHOTO C: OPEN JUNCTION BOXPHOTO E: DUCTWORK AND GAP BETWEEN CONDUITPHOTO F: PIPING AND CABLE PENETRATIONS GENERAL NOTES:ALL GENERAL NOTES PERTAIN TO ALL ARCHITECTURAL (A-SERIES) DRAWINGS IN THIS SETWHERE DIFFERENT FLOORING MATERIALS MEET, AND A SPECIFIC TRANSITION DETAIL IS NOT INDICATED, PREPARE SUBSTRATE WITH A TRANSITION HEIGHT BUILD UP USING TROWELABLE LEVELING AND PATCHING COMPOUND TO PRODUCE A FLUSH SMOOTH CONDITION. TROWEL MATERIAL FOR A MINIMUM DISTANCE OF 2 FEET FROM A FEATHER EDGE CONDITION UP TO A MAXIMUM SINGLE LAYER APPLICATION THICKNESS OF 1/2". FOR APPLICATIONS THICKER THAN 1/2", PLACE MATERIAL IN SUCCESSIVE LAYERS, SCORING PREVIOUS LAYER, UP TO A MAXIMUM THICKNESS OF 1".PROVIDE CONCEALED STEEL STUD BLOCKING, FRT WOOD BLOCKING OR 4" x 18 GA CONTINUOUS STEEL STRAPPING ATTACHED TO FACE OF STUDS BEHIND ALL WALL MOUNTED ITEMS SUCH AS: WALL CABINETS, SHELVING, COAT RODS, GRAB BARS, HANDRAILS, TOILET ACCESSORIES, ETC. SEE INTERIOR ELEVATIONS & FURNITURE PLANS FOR ADDITIONAL INFORMATION AND SCOPE.FLOOR FINISH TRANSITIONS/CHANGES SHALL OCCUR BELOW THE DOORDIMENSIONS LOCATING INTERIOR PARTITIONS ARE TO THE FACE OF WALL (EXCLUDING FINISHMATERIALS SUCH AS -BUT NOT LIMITED TO: CERAMIC TILE, AND WOOD PANELING) UNLESS NOTED OTHERWISE. SEE PARTITION SCHEDULE FOR WALL THICKNESSALL EXISTING DIMENSIONS ARE APPROXIMATE AND FOR CONTRACTORS VERIFICATIONS. IFDISCREPANCIES ARISE, NOTIFY THE ARCHITECT (AND/OR CONSTRUCTION MANAGER) PRIOR TO PROCEEDING WITH THE WORK THAT MAY BE EFFECTED BY THE DIMENSION CHANGEEVERY ATTEMPT HAS BEEN MADE TO INDICATE PERTINENT EXISTING UTILITIES AND CONDITIONS AS ACCURATELY AS POSSIBLE FROM EXISTING SURVEYS, DRAWINGS AND OTHER DATA. PRIOR TO THE BID OPENING, CONTRACTORS SHALL WALK THE JOB SITE AND SATISFY THEMSELVES TO EXISTING CONDITIONS. THE ARCHITECT SHALL BE CONSULTED WHEN ANY QUESTION ARISES RELATIVE TO MATERIALS NOT SPECIFICALLY SHOWN OR SPECIFIEDALL EXISTING WORK (CEILINGS, FLOORS, WALLS, PARTITIONS, FINISHES, ETC.) DISTURBED BY NEW CONSTRUCTION, INCLUDING MECHANICAL, PLUMBING, AND ELECTRICAL, SHALL BE PATCHED AND REPAIRED TO RESTORE SURFACES TO THE ORIGINAL CONDITION AFTER INSTALLATION OF OTHER WORKPENETRATIONS THROUGH FIRE-RESISTANT CONSTRUCTION SHALL BE BUILT IN ACCORDANCE WITH U.L. LISTED THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE CODE COMPLIANCE PLAN FOR PARTITION LOCATIONS. PENETRATIONS THROUGH NON FIRE-RESISTANT RATED HORIZONTAL ASSEMBLIES, NOT PROTECTED BY A SHAFT ENCLOSURE, SHALL HAVE ITS ANNULAR SPACE FILLED WITH NON-COMBUSTIBLE MATERIAL TO PREVENT THE PASSAGE OF FLAME, SMOKE FUMES, AND HOT GASES. NON-COMBUSTIBLE PENETRATING ITEMS SHALL NOT PENETRATE MORE THAN 3 FLOOR ASSEMBLIES. COMBUSTIBLE PENETRATING ITEMS SHALL NOT PENETRATE MORE THAN 1 FLOOR ASSEMBLY.1.2.3.4.5.6.7.8.9.(1) LAYER 5/8" GYPSUM BOARD LAMINATED TO SUBSTRATE INDICATED.6" METAL STUDS AT 16" O.C.(1) LAYER 5/8" GYPSUM BOARD AT ROOM SIDE ONLY.3 5/8" METAL STUDS AT 16" O.C.(1) LAYER 5/8" GYPSUM BOARD AT ROOM SIDE ONLY.UNBALANCED SERIES PARTITIONS5/8"U14 1/4"U86 5/8"U10LEGENDINDICATES PARTITION TYPEINDICATES PARTITION HEIGHT ABOVEFINISHED FLOOR:"X" AFCPARTITION TO X" ABOVEFINISHED CEILINGUFCPARTITION TO UNDERSIDE OF FINISHED CEILINGX'-X"WHERE HEIGHT IS NOTED,CONSTRUCT WALL TO THATHEIGHT INCLUDING TOP OFWALL CAPXX**GYPSUM BOARD TO BE "TYPE X" UNLESS OTHERWISE NOTEDALL PARTITIONS ARE TO BE TO THE UNDERSIDE OF DECK UNLESS OTHERWISE NOTEDDIMENSIONS SHOWN FOR EACH PARTITION DESCRIPTION INDICATE FACE-TO-FACETHICKNESS OF MATERIALS LISTED FOR THAT PARTITIONPROVIDE LISTED U.L. FIRE-RESISTANT JOINT ASSEMBLIES @ TOP OFALL WALLS INDICATED TO BE FIRE-RESISTANT RATEDTHE TOP OF ALL PARTITIONS FRAMED AGAINST THE UNDERSIDE OFSTRUCTURES SHALL HAVE PROVISIONS FOR DEFLECTION & RESTRAINTREFER TO CODE COMPLIANCE PLANS FOR PARTITION FIRE RESISTANCE RATINGS.GYPSUM BOARD JOINT TREATMENT IN CONCEALED SPACES SHALL BE FIRE TAPED. UNLESS OTHERWISE INDICATED IN A SPECIFIC UL DESIGN, JOINTS SHALL BE FIRE TAPED, AND JOINTS AND FASTENER HEADS COVERED WITH (1) COAT OF JOINT COMPOUND. BASE LAYERS IN MULTI-LAYER SYSTEMS ARE NOT REQUIRED TO HAVE JOINTS OR FASTENER HEADS TAPED OR COVERED WITH JOINT COMPOUND. FOR PARTITIONS SCHEDULED WITH BOARD ON (1) SIDE ONLY, PROVIDE 20 GA. MINIMUM PRE-NOTCHED BRIDGING/SPACING BARS (SIMILAR TO SPAZZER 9200 BY CLARK DIETRICH) AT 4'-0" O.C. HORIZONTALLY. AT CONTRACTORS' OPTION, 1-1/2" x 12GA. C.R. CHANNEL BRIDGING WITH 16 GA. CLIP ATTACHMENT TO EACH STUD CAN BE UTILIZED.PARTITIONS WITH SOUND ATTENUATION BLANKETS:GENERAL PARTITION NOTES:A.B.C.D.E.F.G.H.J.BALANCED SERIES PARTITIONSA3A3INDICATES PARTITION TYPEINDICATES ADDITIONAL SOUND ATTENUATIONBLANKETS FOR ACOUSTICAL PURPOSES(REFER TO GENERAL PARTITION NOTES)AREFER TO CODE COMPLIANCE PLAN(S) FOR PARTITIONS REQUIRED TO BE FIRE-RESISTANT-RATED CONSTRUCTION.PROVIDE SOUND ATTENUATION BLANKETS IN ALL CAVITY SPACES IN WALL FULL HEIGHTTHICKNESS OF BLANKETS IN STUD WALLS SHALL BE EQUAL TO THICKNESS OF CAVITY TO NEAREST 1/2", UNLESS INDICATED OTHERWISEPARTITIONS TO BE SEALED @ THE PERIMETER, BEHIND CONTROL JOINTS, AROUND OPENINGS AND AT ALL PENETRATIONS WITH EACH LAYER OF BOARD TO RECEIVE A BEAD OF NON-HARDENING SEALANTSEE WALL TYPE DESCRIPTIONS FOR CONDITIONS REQUIRING MINERAL FIBER SAFING INSULATION BATTS1.2.3.4.2-HOUR RATED SHAFT WALL.2 1/2" METAL C-H STUDS AT 24" O.C.(2) LAYERS 5/8" GYPSUM BOARD AT ROOM SIDE ONLY.(1) LAYER 1" TYPE "X" GYPSUM LINER PANELS AT SHAFT SIDE.FULL HEIGHT PARTITION TO UNDERSIDE OF DECK.2-HOUR RATED PER ASSEMBLY U.L. #U438.SHAFT WALL SERIES PARTITIONS3 3/4"S23 5/8" METAL STUDS AT 16" O.C.(1) LAYER 5/8 " GYPSUM BOARD EACH SIDE.1 HOUR FIRE RESISTANT RATED WHEN INDICATED(WITH OR WITHOUT INSULATION) PER UL U4194 7/8"EXISTING CONCRETE DECKSCREW FASTENER TO STUDS ONLY2" x 20 GA. MIN DEEP LEG DEFLECTION TRACKCONT. LATERAL BRACE WITHIN 12" OF TOP TRACK 1 1/2 C.R. CHANNEL W/ 16 GA. CLIP ANGLE OR CONT. STRAPPING ON EA. SIDESTEEL STUDCUT STUDS 1" SHORT OF DECK OR BEAMGYPSUM BOARD -EXTEND TO TOP OF STUD ELEVATIONAT FIRE -RATED PARTITIONS:CONSTRUCT DETAIL IN ACCORDANCE WITH U.L. LISTED FIRE-RESISTANT JOINT SYSTEMS (HW-D). PROVIDE DEFLECTION TRACK ASSEMBLIES, FORMING/ FILL MATERIALS AS REQUIRED BY APPROVED JOINT SYSTEMAT NON-RATED PARTITIONS & SMOKE PARTITIONS: FOR PARTITIONS CONTAINING SOUND BATT INSULATIONPACKING MATERIALFILL MATERIAL/SEALANTBOND BREAKER TAPEFINISH FLOORCOORDINATE EXTINGUISHER TYPE WITH SPECIFICATIONSWALL HUNG BRACKET COORDINATE WITH SPECIFICATIONSWALL HUNG/BRACKETMOUNTED EXTINGUISHER(40 LB OR LESS)4'-0" AFF MAX.4" MIN.(40 LB OR LESS)4'-0" AFF MAX.(40 LB OR LESS)4'-0" AFF MAX.(GREATER THAN 40 LB)3'-6" AFF MAX.These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:47 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFGeneral Notes andLegendsCWJAD/CREA-000100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 2021AB Anchor boltA/C Air condition(ing) (ed)ACC AccessibleACCU Air cooled condensing unitACI American Concrete InstituteACT Acoustical ceiling tileACM Asbestos containing materialACOUS PNL Acoustical panelACS PNL Access panelADDL AdditionalADJ Adjustable, adjacentADH AdhesiveAFF Above finished floorAGGR AggregateAHU Air handling unitAISC American Institute of Steel ConstructionAISI American Iron and Steel InstituteALT AlternateALUM AluminumANOD AnodizedAPPROX ApproximateARCH Architect(ural)ARD Auxillary roof drainASD Allowable stress designASTM American Society for Testing and MaterialsAWP Acoustical wall panelAWS American Welding SocietyBAT BattenB/B Back to backB BD Base boardBCNYS Building Code of New York StateBITUM BituminousBD BoardBLDG BuildingBLKG BlockingBM Beam, BenchmarkBOT BottomBR BedroomBRG BearingBRZ BronzeBSMT BasementBTWN BetweenBUR Built up roofingBW Both waysCCTV Closed circuit televisionCAB CabinetCB Catch basin, Corner beadCH BD ChalkboardCEM CementCF Contractor furnishedCFMF Cold-formed metal framingCF/CI Contractor furnished/ Contractor installedCF/OI Contractor furnished/ Owner installedCG Corner guardCH Coat hookCI Cast ironCIP Cast in place, Cast iron pipeCJ Control jointCL CenterlineCLG CeilingCLO ClosetCLR Clear, ColorCMT Ceramic mosaic tileCMU Concrete masonry unitCNTR CounterCO Cleanout, Cased opening, CompanyCOL ColumnCONC ConcreteCONF ConferenceCONN Connect(ion)CONSTR ConstructionCONT Continue(ous)CONTR Contract(or)COORD CoordinateCPT CarpetCSJ Construction jointCSK Counter sunkCT Ceramic tile, Count, Current transformerCTR CenterCW Cold water piping, Casement windowCU CubicCUH Cabinet unit heaterCU YD Cubic yardD Deep, DepthD Penny (nail)db Bar diameterDBL DoubleDEFS Direct-applied exterior finish systemDEG DegreeDEMO DemolitionDEPT DepartmentDET DetailDF Drinking fountainDIA OR ø DiameterDIAG Diagonal, DiagramDIM DimensionDIFF DiffuserDIR DirectionDISP DispenserDIV DivisionDMPF Damp proofingDL Dead loadDN DownDO DittoDR Door, DriveDS DownspoutDW DishwasherDWVDrainage waste & ventDWGDrawingDWLDowelEEastEAEachEBCNYSExisting Building Code of New York StateECElectrical contractorEFEach faceEIFSExterior insulation and finish systemEJExpansion jointELASElastomericELElevationELECElectric(al)ELEVElevatorEMEntry mat, Expanded metalEMEREmergencyENCLEnclosureENGREngineerEOSEdge of slabEPElectric panelEQEqualEQUIPEquipmentESEmergency showerETCEt ceteraETRExisting to remainEWEach wayEWCElectric water coolerEXISTExistingEXCExcavation, ExcavateEXPExpand, ExpansionEXTExterior, External, ExtinguisherF/FFace to faceFAAPFire alarm annunciator panelFACPFire alarm control panelFDFloor drainFDTNFoundationFEFire extinguisherFECFire extinguisher cabinetFHCFire hose cabinetFINFinish(ed)FIXTFixtureFLASHFlashingFLEXFlexibleFLOURFluorescentFLGFlooring, flangeFOFinished openingFPFire protection, FireproofFRTWFire retardant treated woodFTFoot, FeetFTGFootingFTRFinned tube radiationFURNFurnace, Furniture, FurnishFUTFutureFWCFabric wall coveringGAGageGALGallonGALVGalvanizedGBGrab barGCGeneral contract(or)GFRCGlass fiber reinforced concreteGFRGGlass fiber reinforced gypsumGLGlass, Ground levelGL BLKGlass blockGLU LAMGlued laminated beamGRGrade, GrossGWTGlazed wall tileGYPGypsumGYP BDGypsum boardGYP PLASGypsum plasterHBHose bibbHCHollow core, Hose cabinetHCPHandicappedHDWHardwareHDWDHardwoodHMHollow metalHOHold openHORIZHorizontalHPHigh point, HorsepowerHRHourHSSHollow structural sectionHTHeightHTGHeatingHTRHeaterHVACHeating, ventilating and air conditioningHWHot waterHYDHydrantIDInside diameterINInchesINCLIncludedINCANDIncandescentINFOInformationINSULInsulationINTERMIntermediateINTInteriorJANJanitorJSTJoistJTJointKIP1000 PoundsKITKitchenKOKnockoutKPLKick plateLLiter, AngleLAMLaminate(d)LAULaundryLAVLavatoryLBPoundLBLLabelLDLoadLFLinear feet (foot)LHLeft hand, Latent heatLINLinearLKRLockerLLLive loadLLHLong leg horizontalLLVLong leg verticalLOCLocationLRFDLoad & resistance factor designLTLightLTGLightingLWCLight-weight concreteMACHMachineMAINTMaintenanceMASMasonryMATLMaterialMAXMaximumMCMechanical contractorMCBMetal corner beadMDOMedium density overlayMDFMedium density fiberboardMECHMechanicalMEPMechanical, electrical, plumbing and fire protectionMEZZMezzanineMFRManufacturerMHManholeMMMillimeterMIFRCMastic/intumescent fire-resistive coatingMINMinimumMISCMiscellaneousMLWKMillworkMOMasonry openingMRK BDMarker boardMTDMountedMTLMetalMULLMullionNNorthNATNaturalNCOMBLNoncombustibleNICNot in contractNO OR #NumberNOMNominalNORMNormalNRCNoise reduction coefficientNTSNot to scaleNWCNormal weight concreteO/OOut to outOAOverall, Outside airOCOn centerODOutside diameterOF/CIOwner furnished, Contactor installedOF/OIOwner furnished, Owner installedOFDOverflow drainOFFOfficeOHOpposite handOH DROverhead (coiling) doorOPNGOpeningOPPOppositeOPTOptional, OptimumOZOuncePAPublic addressPBDParticleboardPCPlumbing contractor, Portland cementPCCPrecast concretePCTPorcelain ceramic tilePEDPedestalPENDPendantPERPeriodPERFPerforatedPGBDPeg boardPLPlate, Property linePLFPonds per linear footPLAMPlastic laminatePLASPlasterPLBPlumbingPLYWDPlywoodPNLPanelPOLPolishedPORCPorcelainPOSPositive, PositionPPTPressure-preservative treatedPRPairPREFABPrefabricatePREFINPrefinishPREPPreparationPROJProjectPROJ SCRN Projection screenPSFPounds per square footPSIPounds per square inchPTPaint, Post tensionPTNPartitionPVCPolyvinyl chloride (plastic)PVGPavingQTQuarry tileQTRQuarterQTYQuantityRRiser, Radius, Thermal resistanceRBRubber base, Resilient baseRCPReinforced concrete pipe, Reflected ceiling planRDRoof drain, RoadRECRecessedREFRefrigeratorREFLReflectREGRegister, RegulationREINFReinforcedREQDRequiredRESILResilientREVRevisionRFResilient flooringRFGRoofingRHRight hand, Roof hatchRMRoomRORough openingROWRight of wayRTURoof top unitRVRoof ventRWBRubber wall baseSSouthSABSound attenuation battsSANSanitarySCSolid core, Shading coefficientSCHEDScheduleSEALSealer on floor (finish)SECTSectionSFSquare foot, Safety factorSFRMSprayed fire-resistiveMaterialSGTStructural glazed tileSHTSheetSHRShowerSIMSimilarSOGSlab on gradeSPStandpipe, Sump pitSPASpacesSPKRSpeakerSPECSpecificationSQSquareSRDSecondary roof drainSSService sinkSSMSolid surface materialSSPStainless steel pipeSSTStainless steelSTStainSTAStationSTCSound transmission classSTDStandardSTIFFStiffenerSTLSteelSTORStorageSTRStraight, StringersSTRUCTStructuralSUSPSuspendedSVSheet vinylSYSquare yardTTreadT/Top ofT&BTop and bottomT&GTongue and grooveTELTelephoneTHRESThresholdTEMPTemporaryTERTerrazzoTHKThick(ness)TK BDTack boardTMPDTemperedTOCTop of concreteTOMTop of masonryTOPOTopography, TopographicTOSTop of steelTOWTop of wallTPDToilet paper dispenserTSTATThermostatTVTelevisionTYPTypicalUHeat transfer coefficientUCUndercutUCLUnder cabinet lightingUGNDUndergroundUHUnit heaterULUnderwriter's laboratoriesUNEXUnexcavatedUNFINUnfinishedUONUnless otherwise notedUTILUtilityUVUnit ventilatorVARNVarnish(ed)VBVinyl baseVCTVinyl composition tileVENTVentilationVERTVerticalVESTVestibuleVIFVerify in fieldVINVinylVOLVolumeVRVapor retarderVTVinyl tileV SHTVinyl sheetVWCVinyl wall coveringWWestW/WithWCWater closet, Wall coveringW/OWithoutWDWoodWDWWindowWFWide flangeWD GDWood guardWHWater heaterWIWrought ironWMWire meshWPWaterproofing, Working pointWRWater repellent, weather resistantW RECPTWaste receptacleWSCTWainscotWTWeight, Watertight, Water tableWWFWelded wire fabricXByYDYardC12AC12A-XXX1432XSCALE: X"=1'-0"Title112BA18'-0" AFF1Batt insulationRigid insulationWood blocking (intermittent) StoneGravel or crushed stoneWood framing (continuous)Finish woodSteel - large scaleSteel - small scalePlywoodConcreteConcrete masonry unitBrick(Other metals as noted)View titleBuilding / wall section cutDetail - blow upExterior elevationInterior elevations1011Partition typeRoom numberDoor numbersWindow typeRevisionORORUndisturbed earth001100A001Structural gridViewing directionDetail no.Drawing no.Detail no.Drawing no.Drawing no.Elevation no.Plan key noteDemolition key noteCeiling type and heightDrawing symbols(Other metals as noted)A-XXXXA-XXXXGypsum, sand, mortarA-XXXXDrawing no.Elevation no.Detail no.Detail section cutDetail no.DRAWING NO.A-XXXXViewing directionAccessibilityAccessible unitV/HAUVisual / hearing accommodation unitMaterial symbolsArchitectural / Structural abbreviations3" = 1'-0"1Typical Deflection Head Detail3/4" = 1'-0"2Fire Extinguisher Mounting Detail EVERY ATTEMPT HAS BEEN MADE TO DOCUMENT PERTINENT EXISTING CONDITIONS FROM EXISTING SURVEYS, DRAWINGS AND LIMITED FIELD INSPECTION. PRIOR TO THE SUBMISSION OF BIDS, CONTRACTORS SHALL WALK THE SITE AND SATISFY THEMSELVES TO EXISTING VISUAL CONDITIONS. THE ARCHITECT SHALL BE CONSULTED WHEN ANY QUESTION ARISES RELATIVE TO MATERIALS AND CONDITIONS NOT SPECIFICALLY SHOWN OR SPECIFIED.ALL EXISTING WORK (CEILING, FLOORS, WALLS, FINISHES, ETC.) DISTURBED BY NEW CONSTRUCTION SHALL BE PATCHED AND REFINISHED. PATCHING AND FINISH WORK IS THE REPAIR WORK REQUIRED TO RESTORE SURFACES TO THE ORIGINAL CONDITION AND/ OR MATCHING THE ADJACENT SURFACES. MISCELLANEOUS FINISH REQUIREMENTS TO WALL, FLOOR AND CEILING IN AREAS AFFECTED BY DEMOLITION HAVE NOT BEEN TOTALLY INCORPORATED INTO THE ROOM FINISH SCHEDULE. REFER TO THE DEMOLITION , FLOOR AND REFLECTED CEILING PLANS FOR ADDITIONAL CUTTING , PATCHING AND REFINISHING WORK SCOPE.CONTRACTOR(S) SHALL COORDINATE ALL WORK WITH HAZARDOUS MATERIALS ABATEMENT WORK. SOME ITEMS ON DEMOLITION PLAN WILL REQUIRE REMOVAL PRIOR TO START OF ABATEMENT WORK.THE EXISTING FIRE-RESISTANT CONSTRUCTION MUST BE MAINTAINED OR MADE TO COMPLY WITH THE REQUIREMENTS AS ESTABLISHED BY THIS CONTRACT. SEE THE CODE COMPLIANCE PLANS FOR THE FIRE RESISTANT RATINGS OF EXISTING AND NEW CONSTRUCTION.CARE SHALL BE TAKEN TO LIMIT IMPACT OF CONSTRUCTION ON THE SURROUNDING OCCUPANTS AND OPERATIONS DURING THE PROJECT. SAFE LEGAL PASSAGES SHALL BE PROVIDED FOR ALL BUILDING OCCUPANTS DURING ALL THE PHASES OF THIS PROJECT.WHEN EXISTING CONSTRUCTION WHICH IS TO REMAIN IS DAMAGED DURING THE COURSE OF CONSTRUCTION AS A RESULT OF CONTRACTOR'S WORK, IT SHALL BE REPAIRED AND/OR REPLACED WITH SIMILAR OR LIKE MATERIALS, SUBJECT TO ARCHITECT'S APPROVAL AND WITHOUT COMPENSATION.'REMOVE' IS DEFINED AS DETACH FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF OFF-SITE UNLESS INDICATED TO BE SALVAGED OR REINSTALLED1.2.3.4.5.6.7.GENERAL DEMOLITION NOTES:GENERAL NOTES:ALL FLOORS, WALLS, CEILINGS, AND OTHER SURFACES THAT ARE TO REMAIN ARE TO BE PATCHED, REPAIRED, AND REFINISHED PRIOR TO FINISH INSTALLATION. ALL SURFACES ARE TO BE RESTORED TO THEIR ORIGINAL CONDITION AND/OR MATCH THE ADJACENT SURFACES.FIRESTOP ALL FLOOR PENETRATIONS (USED/UNUSED/ABANDONED) WITH 2 HR UL LISTED PENETRATION FIRESTOPPING." " INDICATES LAB EQUIPMENT, REFER TO A-601 FOR 'LAB EQUIPMENT SCHEDULE'DIMENSIONS WITHIN PARENTHESES, (X'-X"), HAVE BEEN PROVIDED FOR REFERENCE ONLY1.2.3.4.RCP LEGENDGYP BD CLG AND SOFFITCEILING GRIDEXIT LIGHT2'X4' LED FIXTURE1'X4' LED FIXTURESPRINKLER HEADSUPPLY DIFFUSER, REFER TO MECHANICAL DRAWINGS RETURN AIR GRILLE, REFER TO MECHANICAL DRAWINGS EETR 2X4 SUSPENDED ACOUSTICAL TILECEILING TYPESACT-1, 2X2 SUSPENDED ACOUSTICAL TILE1F141516E142E138E142AE13641312781111127444456TEMPORARY PARTITION (METAL STUD W/GYP BOARD OR FRT WOOD) FASTENED INTO CEILING TILES, DO NOT FASTEN BOTTOM TRACK INTO FLOORING. REPLACE AFFECTED ACOUSTICAL CEILING TILES AFTER TEMPORARY PARTITION REMOVAL. PATCH EXISTING FIBER LITE LINER PANELS ADHERED TO 1/2" PLYWOOD SET IN CEILING GRID.109+/- 23' - 1"+/- 4' - 2"1312121415161711REMOVE "E140" ROOM SIGNAGE619ELECTRICAL PANEL, SEE ELECTRICAL DRAWINGS202122+/- 13' - 8"F141516WET LABE142MICROSCOPY/MICROINJECTIONE138PREPE142AANIMAL ROOME136111341171711022CBAE138AA-42048' - 0"FGEJEEFG12A-4205A-42038' - 0"2' - 6"4' - 10"5' - 0"5' - 0"4' - 10"2' - 6"4' - 0"2' - 6"10' - 8"556A-420101177777121189821515156A-4207A-4202114VIF+/- 8' - 8"( 9' - 11" )18A-420915153( 29' - 5" )( 20' - 2" )ELECTRICAL PANEL, SEE ELECTRICAL DRAWINGS17E142E136( 20' - 7" )U10U82' - 6"2' - 6"2' - 6"U1U1U1A-4206A-4207OPPOPPALIGN BENCHES AND ISLANDS, TYP4EEE7181812' - 6"2' - 7"NG4"1' - 8"FUTURE CONFOCAL MICROSCOPE LOCATIONE138E142BE142CE142DDHMLNK11U8NGE142A164' - 7"FUTURE DOOR PANEL AND OPERATING CLEARANCESVIF+/- 6 3/4"VIF1' - 8 3/4"3' - 8"3' - 2"19E138B10 5/8"WET LABE142MICROSCOPY/MICROINJECTIONE138PREPE142AANIMAL ROOME136REPLACE AFFECTED CEILING TILES AFTER TEMPORARY PARTITION REMOVALE8' -7"NOTE: REMOVE AND REINSTALL ACOUSTICAL CEILING TILES AS REQUIRED TO ACCOMMODATE MECHANICAL, ELECTRICAL AND PLUMBING WORK. PROVIDE NEW MATERIAL AS NECESSARY TO REPLACE DAMAGED COMPONENTS.SERVICE DROP ENCLOSURESERVICE DROP ENCLOSURE18' -6"ISLAND WORKSTATION BELOWWORKSTATION BELOWWORKSTATION BELOWEQEQVIF1' - 7"CEILING GRID2"FUME HOOD EXHAUST DUCTE8' -6"E8' -6"+/-+/-These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:50 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFPartial First Floor Plans- Labs E136-E142CWJAD/CREA-101100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 2021DEMOLITION KEY NOTESNO.DESCRIPTION1 REMOVE ALL LAB CASEWORK IN ITS ENTIRETY. PATCH, REPAIR AND PREP WALLS AND FLOORS TOMATCH ADJACENT SURFACES AND/OR TO RECEIVE SCHEDULED FINISHES2 REMOVE WALL MOUNTED SHELVING ON WALL STANDARDS & ASSOCIATED COMPONENTS IN THEIRENTIRETY. PATCH, REPAIR AND PREP PARTITION TO RECEIVE SCHEDULED FINISH.3 REMOVE DOOR, FRAME & HARDWARE. TURN OVER LOCK CYLINDERS TO OWNER.4 REMOVE UPPER WALL CABINET & ASSOCIATED COMPONENTS IN THEIR ENTIRETY. PATCH, REPAIRAND PREP PARTITION TO RECIEVE SCHEDULED FINISH.5 DISCONNECT AND SALVAGE FUME HOOD AND ADJUSTABLE BASE FOR REINSTALLATION6 REMOVE METAL STUD AND GYP BD PARTITION TO RECEIVE SCHEDULED DOOR.7 REMOVE COAT RACK AND ASSOCIATED COMPONENTS. PATCH, REPAIR AND PREP PARTITION TORECEIVE SCHEDULED FINISH.8 REMOVE GYP BOARD CHASE BELOW SST SINK. REFER TO PLUMBING DRAWINGS FOR SINKREMOVAL. PATCH RESINOUS FLOORING AT CHASE REMOVAL TO MATCH ADJACENT FLOORING.PROVIDE INTEGRAL COVE BASE. PATCH WALLS AND PREP FOR FINISH.9 SALVAGE PEGBOARD AND ASSOCIATED COMPONENTS FOR REINSTALLATION.10 REMOVE BOTTOM ROW OF UNISTRUT, COORDINATE WITH PLUMBING WORK. PATCH AND REPAIRCMU PARTITION TO MATCH ADJACENT SURFACE11 REMOVE SHEET VINYL FLOORING, FLOOR BASE AND MASTIC IN THEIR ENTIRETY. PREP CONCRETESLAB ON GRADE TO RECEIVE SCHEDULED FINISH.12 REMOVE DOOR PANEL AND ASSOCIATED HARDWARE. TURN OVER LOCK CYLINDERS TO OWNER.FULLY-WELDED FRAME IN MASONRY CONSTRUCTION - EQUIVALENT CONSTRUCTION TOFIRE-RATED FRAME TO REMAIN. MARBLE THRESHOLD TO REMAIN. PREP FRAME TO RECEIVESCHEDULED DOOR AND FINISH.13 REMOVE AND SALVAGE FIRE EXTINGUISHER AND WALL BRACKET FOR REINSTALLATION. PREPAND PATCH CMU PARTITION TO RECEIVE SCHEDULED FINISH,14 REMOVE LAYER OF GYPSUM BOARD TO ACCOMMODATE PLUMBING WORK. REFER TO PLUMBINGDRAWINGS.15 REMOVE LAYER OF GYPSUM BOARD TO ACCOMMODATE MECHANICAL AND PLUMBING WORK.REFER TO MECHANICAL AND PLUMBING DRAWINGS.16 REMOVE GYPSUM BOARD AND FURRING AT COLUMN17 TRENCH CONCRETE SLAB ON GRADE TO ACCOMMODATE PLUMBING WORK. REFER TO PLUMBINGDRAWINGS. SCAN CONCRETE SLAB AND MAP SUBSURFACE OBJECTS INCLUDING REBAR,CONDUIT AND PIPING. MARK LOCATIONS OF FOUND ELEMENTS ON FLOOR AND SUBMIT REPORTTO OWNER FOR REVIEW PRIOR TO CUTTING. EMPLOY REMOVAL METHODS AT LOCATIONSWHERE PIPES OR CONDUITS ARE SUSPECTED TO EXIST TO AVOID DAMAGE TO THOSE ELEMENTS.TAKE CARE TO NOT DAMAGE VAPOR RETARDER19 REMOVE SHEET VINYL FLOORING, RUBBER BASE AND MASTIC. RESINOUS FLOOR TO REMAIN.PATCH AND PREP FLOOR TO RECEIVE SCHEDULED FLOORING.20 REMOVE ACT CEILING AND ASSOCIATED COMPONENTS IN THEIR ENTIRETY.21 REMOVE MARBLE THRESHOLD22 REMOVE LAYER OF GYPSUM BOARD TO ACCOMMODATE BLOCKING FOR COUNTERTOP SUPPORTBRACKETS. VERIFY METAL STUD GAUGE. REINSTALL GYPSUM BOARD, TAPE AND FINISH TOMATCH ADJACENT WALL SURFACES ONCE BLOCKING HAS BEEN INSTALLED.PLAN KEY NOTESNO.DESCRIPTION1 PROVIDE PAINTED STEEL BASE CABINETS, WALL CABINETS (WHERE SHOWN) & EPOXYCOUNTERTOP. SEE INTERIOR ELEVATIONS FOR DETAILS.2 EXISTING DOOR TO BE CONSIDERED INOPERABLE. OWNER TO MODIFY HARDWARE TO RENDER ITINOPERABLE.3 REINSTALL SALVAGED FIRE EXTINGUISHER. CONFIRM LOCATION WITH OWNER.4 PROVIDE ADJUSTABLE REAGENT SHELVING MOUNTED TO PAINTED STEEL UPRIGHTS. SEEINTERIOR ELEVATIONS FOR DETAILS5 PROVIDE 30"W X 30"H PEGBOARD WITH SST DRIP TRAY AT 42" AFF TO BOTTOM6 INSTALL SALVAGED PEGBOARD AT 42" AFF TO BOTTOM7 PROVIDE WALL MOUNTED ADJUSTABLE REAGENT SHELVING. SEE INTERIOR ELEVATIONS FORDETAILS.8 PROVIDE DROP-IN EPOXY RESIN SINK, SK-A, 18"L X 15"W X 7.9"D9 PROVIDE DROP-IN EPOXY RESIN SINK, SK-B, 18" L X 15" W X 5" D10 PROVIDE SST SCULLERY SINK, SK-C, 74" L X 27" W X 36"H WITH 8" H BACKSPLASH11 PROVIDE DECK-MOUNTED NATURAL GAS CONNECTION, SEE PLUMBING DRAWINGS.12 INSTALL SALVAGED FUME HOOD AND ADJUSTABLE BASE. REFER TO MECHANICAL, PLUMBING,AND ELECTRICAL DRAWINGS.13 LAMINATE 5/8" GYPSUM BOARD AT SIDES AND TOP OF EXISTING OPENING. INSTALL (4) CORNERGUARDS.14 INFILL TRENCH PER DETAIL 3/A-601. PREP CONCRETE SLAB TO RECEIVE SCHEDULED FINISH.15 COMPUTER WORKSTATION (OF/OI)16 PROVIDE MARBLE THRESHOLD WITH FLASH PATCHING, SEE DETAIL 5/A-601.17 PROVIDE EPOXY COUNTERTOP WITH CUSTOM FABRICATED STEEL BRACKET, PAINT BRACKETSBLACK. SEE INTERIOR ELEVATIONS FOR DETAILS.18 PROVIDE BLACKOUT SHADE MOUNTED TO DOOR PANEL. SHADE TO COVER DOOR LITE, VIF DOORLITE DIMENSIONS.19 PROVIDE GYPSUM BOARD FRAMED OPENING. INSTALL (4) CORNER GUARDS.#PLAN KEY NOTE#DEMO KEY NOTEN1/4" = 1'-0"1Partial First Floor Demolition Plan1/4" = 1'-0"2Partial First Floor Plan1/4" = 1'-0"3Partial First Floor Reflected Ceiling Plan 3' - 0"3' - 0"3' - 0"CUSTOM FABRICATED COUNTER SUPPORT BRACKETS AT 32" OC MAXPAINTED STL CABINETS W/ SLIDING GLASS DOORSEPOXY COUNTERTOP, BACK AND SIDE SPLASH AT PARTITION, TYPSCHEDULED FLOOR BASE2' - 7"EQ3A-501ACCESSIBLE RACEWAY ALONG EAST SIDE OF COUNTERTOP, SEE ELECTRICAL DRAWINGSMAX3' - 8"4"2' - 6"4"3' - 0"4"3' - 0"10' - 8"12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLYSCHEDULED BASE AT ALL EXPOSED FINISH WALLS AND EXPOSED CABINET BASE FRONTS AND SIDE PANELSEPOXY COUNTERTOP, BACK AND SIDE SPLASH AT PARTITION, TYPPAINTED STEEL CABINETS & DRAWERS24"W X 30"H PEG BOARD W/ SST DRIP TROUGHEPOXY COUNTERTOP, BACK AND SIDE SPLASH AT PARTITION, TYPPAINTED STEEL CABINETS & DRAWERS12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLY3' - 6"3' - 6"RELOCATED SALVAGED FUME HOOD AND ADJUSTABLE BASE8' - 8"EQ2' - 0"2' - 6"4' - 0"EQ3' - 0"NGFLAMMABLE CABINETPREFINISHED STEEL ACCESS PANEL AT BACK OF KNEESPACE2' - 6"3' - 0"3' - 0"2' - 0"3' - 6"3' - 6"5A-5016A-5013' - 6"3' - 6"RACEWAY. SEE ELECTRICAL DRAWINGS.7A-5017' - 1"EQEQ3' - 0"4"2' - 0"4' - 3"1' - 6"12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLY, CENTER OVER CASEWORKEPOXY COUNTERTOP AND BACKSPLASH, TYPSCHEDULED BASE AT ALL EXPOSED FINISH WALLS AND EXPOSED CABINET BASE FRONTS AND SIDE PANELSPAINTED STEEL CABINETS & DRAWERS3' - 6"3' - 6"7' - 1"3' - 0"8' - 0"PREFINISHED STEEL ACCESS PANEL AT BACK OF KNEESPACECOAT RACK. SEE DETAIL 10/A-5015A-5016A-5013' - 6"RACEWAY. SEE ELECTRICAL DRAWINGSSIM2' - 0"3' - 6"2' - 5"3' - 0"4' - 1"12"D OUTER LIP W/ 12"D INNER REAGENT SHELVING ON PAINTED STEEL UPRIGHTSPAINTED STEEL CABINETS & DRAWERS8' - 0"6" PIPE SHROUDPEGBOARDEPOXY COUNTERTOPSCHEDULED BASE AT EXPOSED CABINET BASE FRONTS, SIDE PANELS, AND KNEE SPACESTEEL CLOSURE PANEL AT KNEESPACE2' - 6"2' - 6"DUAL CHANNEL RACEWAY, SEE ELECTRICAL DWGS2A-5011A-5013' - 6"SIM4' - 1"3' - 0"2' - 10"8' - 0"2' - 4"12"D OUTER LIP W/ 12"D INNER REAGENT SHELVING ON PAINTED STEEL UPRIGHTSPAINTED STEEL CABINETS & DRAWERS6" PIPE SHROUDPEGBOARDEPOXY COUNTERTOPSCHEDULED BASE AT EXPOSED CABINET BASE FRONTS, SIDE PANELS, AND KNEE SPACESTEEL CLOSURE PANEL AT KNEESPACE2' - 6"2' - 6"DUAL CHANNEL RACEWAY, SEE ELECTRICAL DWGS2' - 0"3' - 6"2' - 4"2A-5011A-5013' - 6"SIM2' - 9"PREFINISHED STEEL ACCESS PANEL AT BACK OF KNEESPACE12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLY, CENTER OVER CASEWORK3' - 6"3' - 6"EQ2' - 0"2' - 9"3' - 0"EQ3' - 0"4"8' - 0"7' - 1"EPOXY COUNTERTOP, BACKSPLASH, TYPPAINTED STEEL CABINETS & DRAWERSSCHEDULED BASE AT ALL EXPOSED FINISH WALLS AND EXPOSED CABINET BASE FRONTS AND SIDE PANELSFIXED PANEL WITH RECEPTACLES AND DATA JACKS (POWER AND DATA TO BE IN ACCESSIBLE REACH RANGE)DECK-MOUNTED NATURAL GAS SERVICE FITTINGCOAT RACK. SEE DETAIL 10/A-5015A-5016A-5013' - 6"RACEWAY. SEE ELECTRICAL DRAWINGS.2' - 6"4"CUSTOM FABRICATED COUNTER SUPPORT BRACKETS LOCATED AT 32" OC MAX12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLYEPOXY COUNTERTOP, BACK AND SIDE SPLASH AT PARTITION, TYPEXISTING RUBBER FLOOR BASEEQ3' - 6"3' - 0"3' - 0"3' - 6"3' - 0"7' - 1"4A-501ACCESSIBLE RACEWAY ALONG NORTH SIDE OF COUNTERTOP, SEE ELECTRICAL DRAWINGSMAX3' - 8"2' - 6"4"8' - 0"CUSTOM FABRICATED COUNTER SUPPORT BRACKETS AT 32" OC MAXEPOXY COUNTERTOP, BACK AND SIDE SPLASH AT PARTITION, TYPEXISTING RUBBER FLOOR BASE12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLY3' - 0"3' - 0"3' - 0"4A-501ACCESSIBLE RACEWAY ALONG NORTH SIDE OF COUNTERTOP, SEE ELECTRICAL DRAWINGSBLACKOUT SHADEHEMBAR HOLD DOWN7' - 1"3' - 0"MAX3' - 8"VIF1' - 3"VIF1' - 11"SLIDING WD DOORWALL MOUNTED TRACK SCHEDULED FLOOR BASEPROVIDE SCHEDULED FLOOR BASE AT INSIDE FACE OF OPENINGBLACKOUT SHADEHEMBAR HOLD DOWN3' - 1"2' - 8"FILLER PANEL24"W X 30"H PEG BOARD W/ SST DRIP TROUGH12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLY4' - 10"3' - 0"3' - 0"3' - 0"2' - 10"2' - 9"FILLER PANEL5' - 0"4' - 10"5' - 0"2' - 6"EPOXY COUNTERTOP, EPOXY TRANSITION TO STANDING HEIGHT COUNTERTOPSCHEDULED BASE AT ALL EXPOSED FINISH WALLS AND EXPOSED CABINET BASE FRONTS AND SIDE PANELSPAINTED STEEL APRONSTEEL CLOSURE PANEL AT KNEE SPACEPAINTED STEEL END PANELSPAINTED STEEL SINK BASE CABINET6" PIPE SHROUD8A-5017A-501SIM12"D OUTER LIP REAGENT SHELVING ON WALL RAIL ASSEMBLYEPOXY COUNTERTOP, BACK AND SIDE SPLASH AT PARTITION, TYP3' - 0"3' - 0"3' - 0"2' - 9"FILLER PANELFILLER PANELFILLER PANEL5' - 0"5' - 0"12"D OUTER LIP W/ 12"D INNER REAGENT SHELVING ON PAINTED STEEL UPRIGHTSSCHEDULED BASE AT ALL EXPOSED FINISH WALLS AND EXPOSED CABINET BASE FRONTS AND SIDE PANELSThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:53 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFInterior ElevationsCWJAD/CREA-420100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 20211/4" = 1'-0"1Interior Elevation E142A North1/4" = 1'-0"3Interior Elevation - Rm E142 North A1/4" = 1'-0"5Interior Elevation - Rm E142 West1/4" = 1'-0"6Interior Elevation - Rm E142 - Island Casework A1/4" = 1'-0"7Interior Elevation - Rm E142 - Island Casework B1/4" = 1'-0"4Interior Elevation - Rm E142 East1/4" = 1'-0"10Interior Elevation - Rm E138 East1/4" = 1'-0"11Interior Elevation - Rm E138 West1/4" = 1'-0"2Interior Elevation E142A South1/4" = 1'-0"9Interior Elevation - Rm E142 North B1/4" = 1'-0"8Interior Elevation - Rm E142 South STEEL BASE CABINET PER ELEVATIONSEPOXY RESIN COUNTER W/ BACKSPLASHFINISHED FLOORWIRE PULLADJUSTABLE REAGENT SHELVES W/ LIPS7' - 1"4' - 1"3' - 0"1' - 9 5/8"1' - 2 3/4"1' - 0"1' - 0"ISLAND UPRIGHTINNER & OUTERREAGENT SHELFW/ LIP BEYOND3' - 0"5' - 0"1"OPEN UTILITY CHASEEPOXY RESIN COUNTER W/ BACKSPLASHFINISHED FLOORWIRE PULLBASE CABINET BEYONDMETAL APRON W/ DRAWER3' - 0"1' - 0"1' - 0"4' - 1"3' - 0"7' - 1"ADJUSTABLE REAGENT SHELVES W/ LIPSISLAND UPRIGHTINNER & OUTERREAGENT SHELFW/ LIP BEYONDREMOVABLE METAL PANEL -TYPICAL AT KNEE SPACES5' - 0"1' - 9 5/8"1' - 2 3/4"1' - 9 5/8"1"1"OPEN UTILITY CHASEEPOXY RESIN COUNTER W/ BACKSPLASHFINISHED FLOORDUAL-CHANNEL WIREMOLD WITHIN ACCESSIBLE REACH RANGE, REFER TO ELECTRICAL DRAWINGSPROVIDE BLOCKING PER 2/A-000, TYPICALSTEEL WALL CABINET, REFER TO ELEVATIONS2' - 7"4"2' - 6"2' - 6"7' - 0"CUSTOM FABRICATED COUNTER SUPPORT BRACKET -SIMILAR TO CENTERLINE FRONT-MOUNTING PLUS. MFR: ACCUFAB, MICHAEL MASTERS, 607.273.3706, MIKE@ACCUFABINC.COMMAX3' - 8"STEEL BASE CABINET PER ELEVATIONSEPOXY RESIN COUNTER W/ BACKSPLASHFINISHED FLOORDUAL-CHANNEL WIREMOLD, REFER TO ELECTRICAL DRAWINGSWIRE PULLOPEN UTILITY CHASEREFER TO ELEVATIONS2' - 6" TO 3' - 0"4"2' - 6"PROVIDE BLOCKING PER 2/A-000, TYPICALADJUSTABLE REAGENT SHELVES W/ LIPS7' - 1"3' - 6"3' - 0"1' - 0"7 3/8"REFER TO ELEVATIONS FOR INVERTED TOP SHELF LOCATIONSEPOXY RESIN COUNTER W/ BACKSPLASHDUAL-CHANNEL WIREMOLD, REFER TO ELECTRICAL DRAWINGSREFER TO ELEVATIONS2' - 6" TO 3' - 0"4"2' - 6"PROVIDE BLOCKING PER 2/A-000, TYPICALADJUSTABLE REAGENT SHELVES W/ LIPS7' - 1"3' - 6"3' - 0"1' - 0"FINISHED FLOOROPEN UTILITY CHASEWIRE PULLBASE CABINET BEYONDREMOVABLE METAL PANEL -TYPICAL AT KNEE SPACES, FINISH TO MATCH CABINETS METAL APRON W/ DRAWER7 3/8"REFER TO ELEVATIONS FOR INVERTED TOP SHELF LOCATIONSSTEEL BASE CABINET PER ELEVATIONSEPOXY RESIN COUNTER W/ BACKSPLASHFINISHED FLOORWIRE PULL4"2' - 6"3' - 0"FALSE FRONTEPOXY PAINTED STEELFIXED SINK SUPPORTSHELF7 3/8"PEG BOARD W/ SST DRIP TROUGH3' - 6"8"EPOXY RESIN COUNTER W/ BACKSPLASHFINISHED FLOORDUAL-CHANNEL WIREMOLD WITHIN ACCESSIBLE REACH RANGE, REFER TO ELECTRICAL DRAWINGS4"2' - 6"2' - 6"CUSTOM FABRICATED COUNTER SUPPORT BRACKET -SIMILAR TO CENTERLINE FRONT-MOUNTING PLUS. MFR: ACCUFAB, MICHAEL MASTERS, 607.273.3706, MIKE@ACCUFABINC.COMPROVIDE BLOCKING PER 2/A-000, TYPICALADJUSTABLE REAGENT SHELVES W/ LIPS3' - 0"1' - 0"REFER TO ELEVATIONS FOR INVERTED TOP SHELF LOCATIONS7' - 1"MAX3' - 8"STANDING OR ADA HEIGHTADA HEIGHT OR SITTING HEIGHTALIGN FRONT OF SIDESPLASH FLUSH WITH FRONT OF ADJACENT WORKSURFACES WHEN TRANSITIONING HEIGHTSEPOXY RESIN COUNTER W/ BACKSPLASHFINISHED FLOOREND PANEL BEYONDMETAL APRON3' - 0"ISLAND UPRIGHTREMOVABLE METAL PANEL, FINISH TO MATCH CABINETS OPEN UTILITY CHASESERVICE DROP ENCLOSURE2' - 10"3' - 6"PEG BOARD W/ SST DRIP TROUGH2' - 4"INNER SHELVING5' - 2"5/4 X 6 HARDWOOD, OAK, STAIN TO MATCH ARCHITECT'S SAMPLE.(4) STAINLESS STEEL BOBRICK B-6827 HOOKSSectionElevationTYP8"2' - 0"EQEQEQWD BLOCKING BETWEEN STUDSEQ1/2" CW1/2" HW1/2" DI2" LAB VENTELECTRICAL CONDUITDATA CONDUITSERVICE DROP ENCLOSURE BY LAB CASEWORK MFR6"1' - 0""LIFT-OFF" CENTER PANELNOTE: SEE ELECTRICAL AND PLUMBING DRAWINGS FOR SERVICES INCLUDED IN SERVICE DROPThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:53 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFInterior Details - LabCaseworkCWJCREA-501100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 20213/4" = 1'-0"1Section at Bench, Typ3/4" = 1'-0"2Section at Bench Knee Spaces3/4" = 1'-0"3Section at Casework - A3/4" = 1'-0"5Section at Casework - C3/4" = 1'-0"6Section at Casework - D3/4" = 1'-0"7Section at Casework - E3/4" = 1'-0"4Section at Casework - B1 1/2" = 1'-0"9Worksurface Transition Detail3/4" = 1'-0"8Section at Accessible Sink3/4" = 1'-0"10Coat Rack Detail3" = 1'-0"11Service Drop Enclosure, Typ. DOOR ELEVATIONSFRAME ELEVATIONSGLAZING TYPES:S-11/4" SAFETY GLASSS-21/4" FIRE-RATED SAFETY GLASSD1F1SCHEDSEE DOORSEE DOOR SCHEDULED2SCHEDSEE DOOR8"MAX3' - 7"SEE DOOR SCHEDULEMAX3' - 7"8"5"8"SEE DOOR SCHEDULESCHEDSEE DOOR6"6"SEE DOOR SCHED FOR GLAZING TYPE, TYP.SEE DOOR SCHED FOR GLAZING TYPE, TYP.DOUBLE MTL STUD AT JAMBS, TYPICALDOORHM WRAPPED FRAME W/ GYP BD RETURNS AND MTL STUD ANCHORS2"PLANSEE FLRPARTITION TYPE AS SCHED.J1TYP.5/8"MIN.1/2"4"WALL WHERE APPLICABLE5/8" TYPDOUBLE MTL STUD AT JAMBS, TYPICALDOORPLANSEE FLRPARTITION TYPE AS SCHED.J2STAINLESS STEEL CORNER GUARD34" MIN CLEAR4"TYP.60" TO TOP OF SIGNSINGLE DOOR9"LOCATE ON LATCH SIDE OF DOOR3 1/2"3 1/2"0003/8"1/2"3/4"3/4'' LETTERING (WHITE)CENTER ON SIGNBRAILLECOLOR: TBDEQEQEQEQMARBLE THRESHOLDEXISTING RESINOUS FLOORSHEET VINYL ON EXISTING RESINOUS FLOORFRAME BEYONDFUTURE DOOR E136E142A1/4" VIF7 1/4"CAREFULLY CUT EXISTING FLOORING TO STRAIGHT AND NEAT EDGE TO ACCOMMODATE THRESHOLDNOTE: VERIFY FLOORING TRANSITIONS AND THRESHOLD DIMENSIONS IN FIELD.SET SCREW200WM FASCIA2"FLOOR MOUNTED GUIDEKERF WOOD DOOR TO RECEIVE BOTTOM TRACKJOHNSON HARDWARE 200WF WALL MOUNT SLIDING DOOR HARDWARE W/ FASCIAE142AE138METAL STUD AND GYPSUM BOARD PARTITION. EXISTING SHEET VINYL ON RESINOUS FLOORCORNER BEAD AND GYP BDSTAINLESS STEEL CORNER GUARD BEYONDSHEET VINYL ON EXISTING RESINOUS FLOORMARBLE THRESHOLD1/2"2 1/2"2 1/2"CAREFULLY CUT EXISTING FLOORING TO STRAIGHT AND NEAT EDGE TO ACCOMMODATE THRESHOLDNOTE: VERIFY FLOORING TRANSITIONS AND THRESHOLD DIMENSIONS IN FIELD.BOX HEADER:• 3 5/8" METAL TRACK TOP & BOTTOM• 8" METAL JOISTS• PROVIDE 8" BEARING AT EACH END OF OPENINGDOOR SCHEDULE REMARKS:1. NEW DOOR PANEL IN EXISTING FULLY-WELDED FRAME IN MASONRY CONSTRUCTION -EQUIVALENT CONSTRUCTION TO FIRE-RATED FRAME2. SLIDING DOOR, SEE 2/A-101. PROVIDE DOOR PULL W/ PLATE EACH SIDE OF DOOR (BOD: ROCKWOOD RM5200 PLANTEK STRAIGHT CAST PULL, SST, 12"L). CENTER OF DOOR PULL TO BE 4" FROM OUTSIDE EDGE OF DOOR STILE.3. OWNER WILL PERFORM “GAP TESTING”TO CONFIRM COMPLIANCE WITH NFPA 80 FOR RATED DOORS. COORDINATE WITH OWNER FOR TESTING AND CORRECT DEFICIENCIES NOTED.4. PREP FRAME FOR HINGES AND DOOR STRIKE. PROVIDE HINGE BLANKS AND BLANK STRIKE PLATE. PAINT FRAME AND BLANKS.#4 BAR X 8" LONG DOWEL DRILLED AND EPOXY GROUTED INTO EXISTING CONCRETE SLAB ON GRADE AT 24" O.C. MAX. EMBED 4" INTO EXISTING CONCRETE SLAB ON GRADE.6" THICK CONCRETE SLAB ON GRADE WITH 6X6 - W2.1XW2.1 WWFSAW CUT SLABCOMPACTED GRAVEL FILLEXISTING CONCRETE SLAB ON GRADE2' - 0"EXISTING VAPOR BARRIER10 MIL PLASTIC SHEET VAPOR RETARDER, INCLUDE MANUFACTURER'S RECOMMENDED PRESSURE-SENSITIVE TAPE. OVERLAP EXISTING VAPOR RETARDER A MINIMUM OF 3" AND TAPE SEAMS. VAPOR RETARDER SHALL COMPLY WITH ASTM E1745, CLASS A.SPRING-ROLLER SHADE W/ FASCIABLACKOUT SHADEHEMBAR HOLD DOWNDOOR LITESCHEDULED/EXISTING DOOR1"LAB EQUIPMENT SCHEDULE NOTES:1. ALL PLUGS TO BE NEMA 5-15/5-20 UNLESS OTHERWISE NOTED.VIF+/- 1' - 0 1/4"112VIF1 5/8"FLASH PATCHMARBLE THRESHOLDSHEET VINYL FLOORING ON EXISTING RESINOUS FLOORNOTE: VERIFY FLOORING TRANSITIONS AND THRESHOLD DIMENSIONS IN FIELD.VIF+/- 7 5/8"GYP BD CHASE BEYONDSTAINLESS STEEL CORNER GUARD BEYONDSHEET VINYL FLOORING2"1/2"1/4"1/4"1/2" MAXThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 12:56:58 PMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFEquipment Schedule,Door Schedule &DetailsCWJAD/CREA-601100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 2021DOOR SCHEDULEDOOR #DOORFRAMEHARDWARE LABEL THRESHOLD REMARKS DOOR #LEAFSSIZETYPE MATERIAL FINISH GLASS ELEVATION JAMB MATERIAL FINISHWIDTH HEIGHT THICKLEVEL 1E136(1)3' - 4" 7' - 0" 1 3/4" D1WD PT-2/PT-3S-2ETRJ1 EXIST HM PT-2/PT-3 SEE HARDWARESCHED45 MIN ETR MARBLE 1, 3E136E138(1)3' - 0" 6' - 11" 1 3/4" ETR ETR WD PT-2/PT-3-ETRETR ETR HM PT-2/PT-3ETR EXISTING 90MINETRE138E138A (1)3' - 6" 7' - 1" 1 3/4" D2WD PT-2S-1SEE A-420J2-- SEE HARDWARESCHED-Y, MARBLE 2E138AE138B (1)3' - 0" 7' - 0" 1 3/4" ETR ETR WD PT-2ETRETRETR ETR HM PT-2ETR-ETRE138BE142(1)3' - 4" 7' - 0" 1 3/4" D1WD PT-2/PT-3S-2ETRJ1 EXIST HM PT-2/PT-3 SEE HARDWARESCHED45 MIN ETR MARBLE 1, 3E142E142A NO DOOR 3' - 0" 7' - 0" 1 3/4" -- --D2J1HMPT-2 SEE HARDWARESCHED-Y, MARBLE 4E142AE142B (1)3' - 4" 7' - 0" 1 3/4" ETR ETR WD PT-2/PT-3ETRETRETRETR PT-2/PT-3ETR EXISTING 45MIN-E142BE142C (1)3' - 4" 7' - 0" 1 3/4" ETR ETR WD PT-2/PT-3-ETRETR ETR HM PT-2/PT-3ETR EXISTING 45MIN-E142CE142D (1)3' - 0" 7' - 0" 1 3/4" ETR ETR WD PT-2-ETRETR ETR HM PT-2ETR--E142DJAMB DETAILSSIGNAGE MOUNTING TYPESTYPICAL ROOM SIGNAGE TYPELAB EQUIPMENT SCHEDULE - 136-142ALETTER QTY EQUIPMENT NAME MANUFACTURER MODEL NO. LOCATIONDIMENSIONSELECTRICALHOUSE LABORATORY PLUMBING SYSTEMSCYLINDERGASESOWNERFURNISHEDOWNERINSTALLEDCONTRACTORFURNISHEDCONTRACTORINSTALLEDCOMMENTSLETTERHEIGHT(IN)WIDTH(IN)DEPTH(IN)WEIGHT(LBS)NORMALVOLTAGE (VAC)PHASE HzPOWER DRAWEMERGENCYPOWERPLUG TYPE(SEE NOTE 1)DCW DHW PCWLABDRAINLABVENTRO/DIGASPROPANECA85PSICALPAMPS HP WATTSA 1 -80 FREEZERREVCO SCIENTIFIC DUPONT SUVA ULT 1490D-N-RFLOOR 42 74 32 833 208/230 1/3 60 11Y NEMA 6-15 - - - - - - - - - -XX--AB 1 -20 BIOMEDICALFREEZERPANASONICMDF-U5312FLOOR 80 31.6 30.4 751201 60 5275 Y- - - - - - - - - -XX--BC 1 REFRIGERATOR PANASONICMPR1411PAFLOOR 74.25 56.75 32.87 632.7 1201 60 4.2380 Y- - - - - - - - - -XX--CD 1 AIR TABLEZEISSFLOOR 33.9 36 48 366.8 N/A- - - - -N- - - - - - - - - - ----- (FUTURE), SEE AIRCOMPRESSOR BELOW FORPOWER REQUIREMENTSDE 6 DISSECTING SCOPE ZEISSSTEMI 508BENCH 17.1 8.8 14.6 13.7 1201 60 2N- - - - - - - - - -XX--EF 2 CENTRIFUGE EPPENDORF54040001385424RBENCH 10 11.4 18.9 43.6 1201 60 3.2N- - - - - - - - - -XX--FG 2 PCR MACHINE EPPENDORF MASTERCYCLER NEXUSGX2EBENCH 13 9.8 16.2 23.1 1201 60700 N- - - - - - - - - -XX--GH 1 CONFOCALMICROSCOPESCANHEADZEISSLSM980ON AIRTABLE8.6 17.7 21.7 59.5 1201 60 13 1500 N NEMA L5-15 - - - - - - - - - ----- (FUTURE)HJ 1 MICROSCOPE ZEISSAXIO IMAGER 2BENCH 19.8 15.3 26.91201 60 4N- - - - - - - - - -XX--JK 1 LASER AND POWERSUPPLY MODULEZEISSFLOOR 22 23.6 19.7 154.3 1201 60N- - - - - - - - - ----- (FUTURE)KL 1 MICROSCOPE ZEISSAXIO IMAGER Z2ON AIRTABLE19.9 11.8 28.4 88.1 1201 60N- - - - - - - - - ----- (FUTURE)LM 1 LASER SCANZEISSAIRYSCAN 2ON AIRTABLE9.4 15.7 7.9 26.5 1201 60 4N- - - - - - - - - ----- (FUTURE)MN 1 AIR COMPRESSOR NEWPORTACGPFLOOR 13 11 13.5 37.5 1201 60N- - - - - - - - - ----- (FUTURE)N6" = 1'-0"1Detail - Marble Threshold at Frame 142A3" = 1'-0"2Sliding Door Detail1/2" = 1'-0"3Detail - Trench Infill3" = 1'-0"4Detail - Shade at Door Lite3" = 1'-0"5Detail - Marble Threshold MISCELLANEOUS FINISH REQUIREMENTS TO WALLS, FLOORS & CEILINGS IN AREAS AFFECTED BY DEMO HAVE NOT BEEN TOTALLY INCORPORATED INTO THE ROOM FINISH SCHEDULE. REFER TO DEMOLITION, FLOOR & REFLECTED CEILING PLANS FOR EXTENT OF "CUTTING & PATCHING". PATCHING SHALL BE THE REPAIR WORK REQUIRED TO RESTORE SURFACES TO THE ORIGINAL CONDITION AND/OR MATCHING THE ADJACENT SURFACES.FLOORING TO RUN BENEATH ANY OPEN SPACES IN ROOMS, INCLUDING ADA CABINETS & APPLIANCES IN THE ROOM FINISH SCHEDULE -IN ANY ROW OR COLUMN "-" or "ETR" INDICATES THERE ARE NO CHANGES OR NEW FINISHES, EXISTING TO REMAINPAINT ALL EXPOSED HVAC, PLUMBING & ELECTRICAL CONSTRUCTION TO MATCH ADJACENT OR BACKGROUND SURFACES UNLESS OTHERWISE NOTED, INCLUDING BUT NOT LIMITED TO STEEL ACCESS DOORS & FRAME, STEEL GRILLES, DIFFUSERS, REGISTERS, AND LOUVERS. DO NOT PAINT OPERATIONAL COMPONENTS OF SYSTEMS INCLUDING BUT NOT LIMITED TO SPRINKLER HEADS, FIRE, SMOKE, OR HEAT DETECTORS.WHERE TRANSITIONS OCCUR AT DOORWAYS, CENTER TRANSITION BENEATH DOOR.PAINT DOOR FRAMES & DOORS UNLESS OTHERWISE INDICATED. FINISH FRAMES & DOORS THE SAME ON BOTH SIDES UNLESS INDICATED AS A SPLIT FINISH IN THE DOOR SCHEDULE.ALL PAINTED VERTICAL SURFACES (WALLS, SOFFITS, COLUMNS, ETC ) TO BE AN EGGSHELL FINISH UNLESS OTHERWISE NOTED.GENERAL NOTES -FINISHESA.B.C.D.E.F.G.H.FINISH LEGENDSECTION 07 92 00 -JOINT SEALANTJOINT SEALANTAT COUNTERTOP TO WALL TRANSITIONS, MATCH JOINT SEALANT TO COUNTERTOPSECTION 09 51 13 -ACOUSTICAL PANEL CEILINGSACOUSTICAL CEILING TILE (ACT)ACT-1CERTAINTEED PERFORM TILE, SQUARE LAY IN MINERAL FIBER TILE, STYLE: FINE FISSURED, TYPE: HHF-197, SIZE: 24" X 24", COLOR: WHITE, INCLUDE COORDINATING 15/16" SUSPENSION GRID, COLOR: WHITE(E142 CEILING REPLACEMENT)ACT-2ARMSTRONG CERMAGUARD TILE, SQUARE LAY IN MINERAL FIBER TILE, STYLE: UNPERFORATED, TYPE: #605, SIZE: 24" X 48" X 5/8", COLOR WHITE(ANIMAL ROOM E136 AT TEMPORARY PARTITION REMOVAL. PRODUCT PER RECORD DRAWINGS PROVIDED BY CORNELL. CONFIRM PRODUCT IN FIELD AND MATCH)SECTION 09 65 00 -RESILIENT FLOORINGSHEET VINYL (SV)SV-1MANNINGTON, BIOSPEC MD, THICKNESS: .080", COLOR: OYSTER WHITE 15201 (LABS E142 AND E142A)SECTION 09 65 13 -RESILIENT BASE AND ACCESSORIESRUBBER BASE (RB)RB-1JOHNSONITE, RUBBER BASE, 4" H, COVE TOE BASE, COLOR: MATCH EXISTINGRB-2JOHNSONITE, RUBBER BASE, 4" H, COVE TOE BASE, COLOR: AS SELECTED FROM MANUFACTURER'S FULL LINE (LABS E142 AND E142A)SECTION 09 91 23 -INTERIOR PAINTINGPAINT (PT)-ALL DOORS, FRAMES AND TRIM –SEMI-GLOSS-CEILINGS –FLAT-ALL PAINTED VERTICAL SURFACES (WALLS, SOFFITS, COLUMNS, ETC) TO BE AN EGGSHELL FINISH.-AT EXPOSED CEILING USE DRYFALL PAINT.PT-1BENJAMIN MOORE, COLOR: LINEN WHITE 912, FINISH: INTERIOR SATIN (GENERAL)PT-2BENJAMIN MOORE, COLOR: LINEN WHITE, FINISH: SEMI-GLOSS (DOOR &FRAMES, WHERE INDICATED TO BE SPLIT FINISH USE AT DOORS AND FRAME ROOM SIDE)PT-3BENJAMIN MOORE, COLOR: MATCH EXISTING, FINISH: SEMI-GLOSS (DOOR & FRAMES, CORRIDOR SIDE)SECTION 10 14 00 -SIGNSPANEL SIGNAGEINTEGRAL ACRYLIC SHEET COLOR:AS SELECTED BY ARCHITECT FROM FULL RANGE OF INDUSTRY COLORS RAISED TEXT AND TYPEFACE COLOR:AS SELECTED BY ARCHITECT FROM FULL RANGE OF INDUSTRY COLORSSECTION 12 24 13 –ROLLER WINDOW SHADESWINDOW TREATMENTS (WT)WT-1DRAPER INC. -STYLE: DRAPER SUNBLOC SB9000 -FLEXSHADE WITH FASCIA, SPRING-ROLLER CONTROLLED, FLAT EXPOSED HEM BAR, HEM BAR CLIPS, SHADE COLOR: SB9050 BLACK, HARDWARE COLOR: AS SELECTED FROM MANUFACTURER'S FULL LINE (DOOR LITE)SECTION 12 35 51 -LABORATORY CASEWORKMETAL CASEWORKMOTT MANUFACTURING, SCIENCE LABORATORY FURNITURE, COLOR: WHITE.SECTION 12 36 53 -LABORATORY WORK SURFACESEPOXY COUNTERTOP (EC)EC-1 DURCON, EPOXY RESIN WORKS, COLOR: BLACKROOM FINISH SCHEDULE REMARKS1. PAINT EXISTING CORRIDOR DOOR AND FRAME PT-2 AND PT-3 AS INDICATED ON THE FINISH LEGEND2.PAINT EXISTING INTERIOR ROOM DOORS AND FRAMES PT-2 AS INDICATED ON THE FINISH LEGEND3.RESILIENT BASE AT NEW CASEWORKThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:55 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFRoom Finish Schedule& LegendCWJCREA-602100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 2021ROOM FINISH SCHEDULEROOM NUMBERROOM NAMEFLOORBASEWALLCEILINGFINISHREMARKS ROOM NUMBERMATERIAL/ FINISH MATERIAL/ FINISHNORTHSOUTHEASTWESTMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISHLEVEL 1E136 ANIMAL ROOMETR RESETR RES ETR CMU PT-1 ETR CMU PT-1 ETR CMU PT-1 ETR GWB PT-1ETRACT/ACT-2E136E138 MICROSCOPY/ MICROINJECTION ETR SVETR RB/RB-1 ETR GWB PT-1 ETR CMU PT-1 ETR GWB PT-1 ETR CMU PT-1 ETR ACT 1 AND 2E138E142 WET LABSV-1RB-2 ETR CMU/ETRGWBPT-1 ETRCMU/ETRGWBPT-1ETRCMU/GWBPT-1 ETR GWB PT-1ACT-1 1, 2 AND 3E142E142A PREPSV-1RB-2ETR CMU PT-1 ETR GWB PT-1 ETR GWB PT-1 ETR CMU PT-1 ETR ACTE142A SECTION 07 92 00 JOINT SEALANTS1. PRODUCT: MILDEW RESISTANT SILICONE SEALANTA. MANUFACTURER: DOW CORNINGB. PRODUCT: 786 MILDEW RESISTANTC. COLOR: TO BE SELECTED FROM MANUFACTURER'S FULL RANGESPECIFICATIONS:SECTION 09 29 00 GYPSUM BOARD1. GYPSUM BOARD, TYPE X: ASTM C1396/C1396M.1. LONG EDGES:TAPERED.2. SOUND-ATTENUATION BLANKETS: ASTM C665, TYPE I (BLANKETS WITHOUT MEMBRANE FACING) PRODUCED BY COMBINING THERMOSETTING RESINS WITHMINERAL FIBERS MANUFACTURED FROM GLASS, SLAG WOOL, OR ROCK WOOL.1. FIRE-RESISTANCE-RATED ASSEMBLIES: COMPLY WITH MINERAL-FIBER REQUIREMENTS OF ASSEMBLY.3. ACOUSTICAL SEALANT: MANUFACTURER'S STANDARD NONSAG, PAINTABLE, NONSTAINING LATEX SEALANT COMPLYING WITH ASTM C834. PRODUCT EFFECTIVELY REDUCES AIRBORNE SOUND TRANSMISSION THROUGH PERIMETER JOINTS AND OPENINGS IN BUILDING CONSTRUCTION AS DEMONSTRATED BY TESTING REPRESENTATIVE ASSEMBLIES ACCORDING TO ASTM E90.4. GYPSUM BOARD FINISH LEVELS: FINISH PANELS TO LEVELS INDICATED BELOW AND ACCORDING TO ASTM C840:1. LEVEL 1: CEILING PLENUM AREAS, CONCEALED AREAS, AND WHERE INDICATED.2. LEVEL 4:AT PANEL SURFACES THAT WILL BE EXPOSED TO VIEW UNLESS OTHERWISE INDICATED.SECTION 09 22 16 NON-STRUCTURAL METAL FRAMING1.STUDS AND RUNNERS: ASTM C 645A. MIN BASE-METAL THICKNESS: 0.027"1. EQUIVALENT COATINGS AND METAL THICKNESS (DIMPLED STEEL) STUDS WILL NOT BE ALLOWED.B. DEPTH: AS INDICATED ON DRAWINGSC. PROTECTIVE COATING: ASTM A 653/A 653M, G40, HOT-DIP GALVANIZEDSECTION 02 70 00 SELECTIVE DEMOLITION1.SUMMARYA. DEMOLISH AND REMOVE SELECTED PORTIONS OF BUILDING.B. DISCONNECT AND CAP OR SEAL UTILITIES PRIOR TO DEMOLITION.C. MAINTAIN AND PROTECT ALL EXISTING UTILITY SERVICES.2.DEFINITIONSA. REMOVE: DETACH ITEMS FROM EXISTING CONSTRUCTION AND DISPOSE OF THEM OFF-SITE UNLESS INDICATED TO BE SALVAGED OR REINSTALLED.B. REMOVE AND SALVAGE: DETACH ITEMS FROM EXISTING CONSTRUCTION, IN A MANNER TO PREVENT DAMAGE, AND DELIVER TO OWNER READY FOR REUSE.C.REMOVE AND REINSTALL: DETACH ITEMS FROM EXISTING CONSTRUCTION, IN A MANNER TO PREVENT DAMAGE, PREPARE FOR REUSE, AND REINSTALL WHEREINDICATED.D.EXISTING TO REMAIN: LEAVE EXISTING ITEMS THAT ARE NOT TO BE REMOVED AND THAT ARE NOT OTHERWISE INDICATED TO BE SALVAGED OR REINSTALLED.3. DEMOLITIONA. INSTALL TEMPORARY DUSTPROOF PARTITIONS AND ENCLOSURES.B. PATCH AND REPAIR DAMAGED SURFACES CAUSED BY SELECTIVE DEMOLITION OPERATIONS.C. DEMOLISHED MATERIALS BECOME CONTRACTOR'S PROPERTY, UNLESS OTHERWISE INDICATED.D. REFER TO DRAWINGS FOR ITEMS TO BE SALVAGED. ITEMS INCLUDED, BUT ARE NOT LIMITED TO, LOCK CYLINDERS, FIRE EXTINGUISHERS, FIRE EXTINGUISHER MOUNTING BRACKETS, PEGBOARDS, AND FUME HOOD.4. DISPOSAL OF DEMOLISHED MATERIALS:A. BURNING: NOT PERMITTED.B. DISPOSAL: OFF OWNER'S PROPERTY.5. SELECTIVE DEMOLITION SCHEDULEA. COORDINATE WITH OWNER'S REPRESENTATIVE FOR UTILITY SHUTDOWNS6. OCCUPANCYA. AREAS ADJACENT TO THE AREAS OF DEMOLITION MAY BE OCCUPIED. WORK IS TO BE CONDUCTED IN SUCH A MANNER AS TO MINIMIZE THE DISRUPTION OF NORMAL OPERATIONS.7. CONDITIONS OF STRUCTURESA. THE OWNER ASSUMES NO RESPONSIBILITY FOR ACTUAL CONDITIONS OF ITEMS OR STRUCTURES TO BE DEMOLISHED. CONDITIONS EXISTING AT THE TIME OF COMMENCEMENT OF CONTRACT WILL BE MAINTAINED BY THE OWNER INSOFAR AS IS PRACTICAL. HOWEVER, VARIATIONS WITHIN THE STRUCTURE MAY OCCUR BY THE OWNER'S REMOVAL AND SALVAGE OPERATIONS PRIOR TO START OF SELECTIVE DEMOLITION WORK.8. DAMAGESA. THE CONTRACTOR IS TO PROMPTLY REPAIR ALL DAMAGES CAUSED TO ADJACENT FACILITIES AND EQUIPMENT BY DEMOLITION WORK AT NO ADDITIONAL COST TO OWNER.SECTION 09 91 23 INTERIOR PAINTING1. PRODUCTS: A. GENERAL:a. MATERIALS FOR USE WITHIN EACH PAINT SYSTEM SHALL BE COMPATIBLE WITH ONE ANOTHER AND SUBSTRATES INDICATED, UNDER CONDITIONS OF SERVICE AND APPLICATION AS DEMONSTRATED BY MANUFACTURER, BASED ON TESTING AND FIELD EXPERIENCEb. FOR EACH COAT IN A PAINT SYSTEM, PRODUCTS SHALL BE RECOMMENDED IN WRITING BY TOPCOAT MANUFACTURERS FOR USE IN PAINT SYSTEM AND ON SUBSTRATE INDICATED.B. INTERIOR PRIMERS:a. INTERIOR GYPSUM BOARD PRIMER: FACTORY-FORMULATED LATEX-BASED PRIMER FOR INTERIOR APPLICATION• BENJAMIN MOORE; MOORCRAFT SUPER SPEC LATEX ENAMEL UNDERCOATER & PRIMER SEALER 253; APPLIED AT A DRY FILM THICKNESS OF NOT LESS THAN 1.2 MILS.b. INTERIOR FERROUS-METAL PRIMER: FACTORY-FORMULATED QUICK-DRYING RUST-INHIBITIVE ALKYD-BASED METAL PRIMER• BENJAMIN MOORE; MOORCRAFT SUPER SPEC ALKYD ENAMEL UNDERBODY AND PRIMER SEALER C245; APPLIED AT A DRY FILM THICKNESS OF NOT LESS THAN 1.5 MILS. C. INTERIOR FINISH COATS:a. INTERIOR FLAT ACRYLIC PAINT: FACTORY-FORMULATED FLAT LATEX PAINT FOR INTERIOR APPLICATION• BENJAMIN MOORE: MOORCRAFT SUPER SPEC LATEX FLAT 275: APPLIED AT A DRY FILM THICKNESS OF NOT LESS THAN 1.2 MILS.b. INTERIOR SEMIGLOSS ACRYLIC ENAMEL: FACTORY-FORMULATED SEMIGLOSS LATEX ENAMEL FOR INTERIOR APPLICATION:• BENJAMIN MOORE: MOORCRAFT SUPER SPEC LATEX SEMI-GLOSS ENAMEL 276: APPLIED AT A DRY FILM THICKNESS OF NOT LESS THAN 1.2 MILS.2. SUBMITTALSA. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INCLUDE PREPARATION REQUIREMENTS AND APPLICATION INSTRUCTIONS.3. EXAMINATION:A. EXAMINE SUBSTRATES AND CONDITIONS, WITH APPLICATOR PRESENT, FOR COMPLIANCE WITH REQUIREMENTS FOR MAXIMUM MOISTURE CONTENT AND OTHER CONDITIONS AFFECTING PERFORMANCE OF THE WORK.B. GYPSUM BOARD SUBSTRATES: VERIFY THAT FINISHING COMPOUND IS SANDED SMOOTHC. VERIFY SUITABILITY OF SUBSTRATES, INCLUDING SURFACE CONDITIONS AND COMPATIBILITY, WITH EXISTING FINISHES AND PRIMERS.D. PROCEED WITH COATING APPLICATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTEDa. APPLICATION OF COATING INDICATES ACCEPTANCE OF SURFACES AND CONDITIONS4. PREPARATION:A. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS IN "MPI ARCHITECTURAL PAINTING SPECIFICATION MANUAL" APPLICABLE TO SUBSTRATES AND PAINT SYSTEMS INDICATED.B. REMOVE HARDWARE, COVERS, PLATES, AND SIMILAR ITEMS ALREADY IN PLACE THAT ARE REMOVABLE AND RE NOT TO BE PAINTED. IF REMOVAL IS IMPRACTICAL OR IMPOSSIBLE BECAUSE OF SIZE OR WEIGHT OF ITEM, PROVIDE SURFACE-APPLIED PROTECTION BEFORE SURFACE PREPARATION AND PAINTING.a. AFTER COMPLETING PAINTING OPERATIONS, USE WORKERS SKILLED IN THE TRADES INVOLVED TO REINSTALL ITEMS THAT WERE REMOVED. REMOVE SURFACE-APPLIED PROTECTION IF ANY.C. CLEAN SUBSTRATES OF SUBSTANCES THAT COULD IMPAIR BOND OF PAINTS, INCLUDING DUST, DIRT, OIL, GREASE AND INCOMPATIBLE PAINTS AND ENCAPSULANTS.a. REMOVE INCOMPATIBLE PRIMERS AND REPRIME SUBSTRATE WITH COMPATIBLE PRIMERS OR APPLY TIE COAT AS REQUIRED TO PRODUCE PAINT SYSTEMS INDICATED.D. CONCRETE SUBSTRATES: REMOVE RELEASE AGENTS, CURING COMPOUNDS, EFFLORESCENCE AND CHALK. DO NOT PAINT SURFACES IF MOISTURE CONTENT OR ALKALINITY OF SURFACES TO BE PAINTED EXCEEDS THAT PERMITTED IN MANUFACTURER'S WRITTEN INSTRUCTIONS.5. APPLICATION:A. APPLY PAINTS ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS AND TO RECOMMENDATIONS IN "MPI MANUAL"a. USE APPLICATORS AND TECHNIQUES SUITED FOR PAINT AND SUBSTRATE INDICATED.b. PAINT SURFACES BEHIND MOVABLE EQUIPMENT AND FURNITURE SAME AS EXPOSED SURFACESc. PAINT FRONT AND BACKSIDES OF ACCESS PANELS, REMOVABLE OR HINGED COVERS, AND SIMILAR HINGED ITEMS TO MATCH EXPOSED SURFACESd. DO NOT PAINT OVER LABELS OF INDEPENDENT TESTING AGENCIES OR EQUIPMENT NAME, IDENTIFICATION, PERFORMANCE RATING OR NOMENCLATURE PLATES.B. TINT EACH UNDERCOAT A LIGHTER SHADE TO FACILITATE IDENTIFICATION OF EACH COAT IF MULTIPLE COATS OF SAME MATERIAL ARE TO BE APPLIED. TINT UNDERCOATS TO MATCH COLOR OF TOPCOAT, BUT PROVIDE SUFFICIENT DIFFERENCE IN SHADE OF UNDERCOATS TO DISTINGUISH EACH SEPARATE COAT.C. IF UNDERCOATS OR OTHER CONDITIONS SHOW THROUGH TOPCOAT, APPLY ADDITIONAL COATS UNTIL CURED FILM HAS A UNIFORM PAINT FINISH, COLOR AND APPEARANCE.D. APPLY PAINTS TO PRODUCE SURFACE FILMS WITHOUT CLOUDINESS, SPOTTING, HOLIDAYS, LAPS, BRUSH MARKS, ROLLER TRACKING, RUNS, SAGS, ROPINESS OR OTHER SURFACE IMPERFECTIONS. CUT IN SHARP LINES AND COLOR BREAKS.E. PAINTING FIRE SUPPRESSION, PLUMBING, HVAC, ELECTRICAL, COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY WORK:a. PAINT THE FOLLOWING WORK WHERE EXPOSED IN OCCUPIED SPACES:• EQUIPMENT, INCLUDING PANELBOARDS• UNINSULATED METAL PIPING• UNINSULATED PLASTIC PIPING• PIPE HANGERS AND SUPPORTS• METAL CONDUIT• PLASTIC CONDUIT• DUCT, EQUIPMENT AND PIPE INSULATION HAVING COTTON OR CANVAS INSULATION COVERING OR OTHER PAINTABLE JACKET MATERIAL• OTHER ITEMS AS DIRECTED BY ARCHITECTb. PAINT PORTIONS OF INTERNAL SURFACES OF METAL DUCTS, WITHOUT LINER, BEHIND AIR INLETS AND OUTLETS THAT ARE VISIBLE FROM OCCUPIED SPACES.6. CLEANING AND PROTECTIONA. AT END OF EACH WORKDAY, REMOVE RUBBISH, EMPTY CANS, RAGS AND OTHER DISCARDED MATERIALS FROM PROJECT SITE.B. AFTER COMPLETING PAINTING APPLICATION, CLEAN SPATTERED SURFACES. REMOVE SPATTER PAINTS BY WASHING, SCRAPING OR OTHER METHODS. DO NOT SCRATCH OR DAMAGE ADJACENT FINISHED SURFACES.C. PROTECT WORK OF OTHER TRADES AGAINST DAMAGE FROM PAINT APPLICATION. CORRECT DAMAGE TO WORK OF OTHER TRADES BY CLEANING, REPAIRING, REPLACING AND REFINISHING, AS APPROVED BY ARCHITECT, AND LEAVE IN AN UNDAMAGED CONDITION.D. AT COMPLETION OF CONSTRUCTION ACTIVITIES OR OTHER TRADES, TOUCH UP AND RESTORE DAMAGED OR DEFACED PAINTED SURFACES.7. INTERIOR PAINTING SCHEDULEA. GYPSUM BOARD: PROVIDE THE FOLLOWING FINISH SYSTEMS OVER INTERIOR GYPSUM BOARD SURFACES:a. SEMIGLOSS ACRYLIC ENAMEL FINISH: TWO FINISH COATS OVER A PRIMER• PRIMER: INTERIOR GYPSUM BOARD PRIMER• FINISH COATS: WATERBORNE ACRYLIC EPOXY.B. FERROUS METAL: PROVIDE THE FOLLOWING FINISH SYSTEMS OVER FERROUS METAL:a. SEMIGLOSS ACRYLIC-ENAMEL FINISH: TWO FINISH COATS OVER A PRIMER• PRIMER: INTERIOR FERROUS-METAL PRIMERFINISH COATS: INTERIOR SEMIGLOSS ACRYLIC ENAMELSECTION 06 10 53 MISCELLANEOUS ROUGH CARPENTRY1. PRODUCT: WOOD GROUNDS, NAILERS, BLOCKING & BACKING PANELSA. LUMBER STANDARDS AND GRADE STAMPS: PS 20, AMERICAN SOFTWOOD LUMBER STANDARD AND INSPECTION AGENCY GRADE STAMPS.B. FIRE-RETARDANT TREATMENT: AWPA C20 FOR LUMBER AND AWPA C27 FOR PLYWOOD; NONCORROSIVE TYPEC. DIMENSION LUMBER: HEM-FIR, SELECT STRUCTURAL NO. 2SECTION 08 12 13 HOLLOW METAL FRAMES1. HEAVY DUTY INTERIOR FRAMES PER SDI 250.8A. PHYSICAL PERFORMANCE: LEVEL B PER SDI A250.4B. MATERIALS: UNCOATED STEEL SHEET, MINIMUM 0.053 INCHC. CONSTRUCTION: FULLY-WELDEDD. EXPOSED FINISH: PRIMESECTION 08 14 16 FLUSH WOOD DOORS1. INTERIOR FLUSH WOOD DOORSA. CORE: a. NON-RATED: PARTICLEBOARD COREb. FIRE-RATED: MINERAL CORE, POSITIVE PRESSURE AB. FACE: MDO, FACTORY PRIMEDC. GRADE: WDMA EXTRA HEAVY DUTYSECTION 08 80 00 GLAZING1. GLASS PRODUCTSA. FULLY TEMPERED FLOAT GLASS: ASTM C 1048, KIND FT (FULLY TEMPERED), CONDITION A (UNCOATED) UNLESS OTHERWISE INDICATED, TYPE 1, CLASS 1 (CLEAR), QUALITY Q3.2. GLASS SCHEDULE:A. MONOLITHIC-GLASS (TYPE S-1)a. CLEAR FULLY TEMPERED FLOAT GLASSb. THICKNESS: 6.0 MM (0.25 INCH)c. PROVIDE SAFETY LABELING, 16 CFR 1201, CATEGORY IISECTION 08 31 13 ACCESS DOORS AND FRAMES1. ACCESS DOORS FOR WALLS & CEILINGSA. FRAMES: 16 GA (.0598 INCH) SHEET STEEL WITH FLANGE SUITABLE FOR ADJACENT MATERIALB. DOORS: 14 GA (.0625 INCH) SHEET STEELC. DOOR TYPE: FLUSH PANELD. FIRE RATING: NFPA 80SECTION 08 71 00 DOOR HARDWARE1. SUBMITTALS:A. PRODUCT DATA: MANUFACTURER'S PRODUCT DATA SHEETS INCLUDING INSTALLATION DETAILS, MATERIAL DESCRIPTIONS, DIMENSIONS OF INDIVIDUAL COMPONENTS AND PROFILES, OPERATIONAL DESCRIPTIONS AND FINISHES.B. DOOR HARDWARE SCHEDULE: PREPARED BY OR UNDER THE SUPERVISION OF SUPPLIER, DETAILING FABRICATION AND ASSEMBLY OF DOOR HARDWARE, AS WELL AS PROCEDURES AND DIAGRAMS. COORDINATE THE FINAL DOOR HARDWARE SCHEDULE WITH DOORS, FRAMES, AND RELATED WORK TO ENSURE PROPER SIZE, THICKNESS, HAND, FUNCTION, AND FINISH OF DOOR HARDWARE.2. WARRANTY:A. SPECIAL WARRANTY PERIODS:1.TEN YEARS FOR MORTISE LOCKS AND LATCHES.2.FIVE YEARS FOR EXIT HARDWARE.3.TEN YEARS FOR MANUAL SURFACE DOOR CLOSERS.4.TWO YEARS FOR ELECTROMECHANICAL DOOR HARDWARE3. MAINTENANCE SERVICE:A. CONTINUING SERVICE: BEGINNING AT SUBSTANTIAL COMPLETION, AND RUNNING CONCURRENT WITH THE SPECIFIED WARRANTY PERIOD, PROVIDE CONTINUOUS (6) MONTHS FULL MAINTENANCE INCLUDING REPAIR AND REPLACEMENT OF WORN OR DEFECTIVE COMPONENTS, LUBRICATION, CLEANING, AND ADJUSTING AS REQUIRED FOR PROPER DOOR OPENING OPERATION. PROVIDE PARTS AND SUPPLIES AS USED IN THE MANUFACTURE AND INSTALLATION OF ORIGINAL PRODUCTS.4. PRODUCTS: PROVIDE PRODUCTS INDICATED IN HARDWARE SCHEDULE. NO SUBSTITUTIONS PERMITTED.SECTION 09 51 13 ACOUSTICAL PANEL CEILINGSSECTION 09 65 13 RESILIENT BASE AND ACCESSORIESSECTION 10 14 00 SIGNS1. SUBMITTALSA. PRODUCT DATA: FOR EACH TYPE OF PRODUCT.B. SHOP DRAWINGS: FOR PANEL SIGNS.C. SAMPLES FOR INITIAL SELECTION: FOR EACH TYPE OF SIGN ASSEMBLY, EXPOSED COMPONENT, AND EXPOSED FINISH.a. INCLUDE REPRESENTATIVE SAMPLES OF AVAILABLE TYPESTYLES AND GRAPHIC SYMBOLS.D. SAMPLES FOR VERIFICATION: FULL-SIZE SAMPLE SHOWING ALL COMPONENTS AND WITH THE REQUIRED FINISH(ES)2. PANEL SIGNSA. PANEL SIGN: SIGN WITH SMOOTH, UNIFORM SURFACES; WITH MESSAGE AND CHARACTERS HAVING UNIFORM FACES, SHARP CORNERS, AND PRECISELY FORMED LINES AND PROFILES; AND AS FOLLOWS:B. SOLID-SHEET SIGN:ACRYLIC SHEET WITH FINISH SPECIFIED IN "SURFACE FINISH AND APPLIED GRAPHICS" SUBPARAGRAPH AND AS FOLLOWS:a. THICKNESS:MANUFACTURER'S STANDARD FOR SIZE OF SIGN.b. SURFACE-APPLIED, RAISED GRAPHICS: APPLIED POLYMER CHARACTERS AND BRAILLE.c. SIGN-PANEL PERIMETER: FINISH EDGES SMOOTH.d. CORNER CONDITION IN ELEVATION:SQUARE.e. MOUNTING:SURFACE MOUNTED TO WALL WITH ADHESIVE AND TWO-FACE TAPE.f. SURFACE FINISH AND APPLIED GRAPHICS:• INTEGRAL ACRYLIC SHEET COLOR:AS SELECTED BY ARCHITECT FROM FULL RANGE OF INDUSTRY COLORS.• TEXT AND TYPEFACE:ACCESSIBLE RAISED CHARACTERS AND BRAILLE AND VARIABLE CONTENT AS SCHEDULED.FINISH RAISED CHARACTERS TO CONTRAST WITH BACKGROUND COLOR, AND FINISH BRAILLE TO MATCH BACKGROUND COLOR. AS SELECTED BY ARCHITECT FROM FULL RANGE OF INDUSTRY COLORS.C. MATERIALSa. ACRYLIC SHEET: ASTM D 4802, CATEGORY AS STANDARD WITH MANUFACTURER FOR EACH SIGN, TYPE UVF (UV FILTERING).b. TWO-FACE TAPE: MANUFACTURER'S STANDARD HIGH-BOND, FOAM-CORE TAPE, 0.045 INCH THICK, WITH ADHESIVE ON BOTH SIDES.D. INSTALLATIONa. INSTALL SIGNS LEVEL, PLUMB, TRUE TO LINE, AND AT LOCATIONS AND HEIGHTS INDICATED, WITH SIGN SURFACES FREE OF DISTORTION AND OTHER DEFECTS IN APPEARANCE.E. SCHEDULEa. PROVIDE (1) SIGN FOR EACH DOOR NUMBERINDICATED ON PLANS.1. PRODUCTS:AS INDICATED IN FINISH SCHEDULE.2. INSTALLATION:INSTALL ACOUSTICAL PANEL CEILINGS ACCORDING TO ASTM C636/C636M AND MANUFACTURER'S WRITTEN INSTRUCTIONS.3. CLEANING: CLEAN EXPOSED SURFACES OF ACOUSTICAL PANEL CEILINGS, INCLUDING TRIM, EDGE MOLDINGS, AND SUSPENSION-SYSTEM MEMBERS. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR CLEANING AND TOUCHUP OF MINOR FINISH DAMAGE.REMOVE AND REPLACE CEILING COMPONENTS THAT CANNOT BE SUCCESSFULLY CLEANED AND REPAIRED TO PERMANENTLY ELIMINATE EVIDENCE OF DAMAGE.1. PRODUCTS:AS INDICATED IN FINISH SCHEDULE.2. ADHESIVES: WATER-RESISTANT TYPE RECOMMENDED BY RESILIENT-PRODUCT MANUFACTURER FOR RESILIENT PRODUCTS AND SUBSTRATE CONDITIONS INDICATED.3. RESILIENT BASE INSTALLATIONA. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLING RESILIENT BASE.B. APPLY RESILIENT BASE TO WALLS, COLUMNS, PILASTERS, CASEWORK AND CABINETS IN TOE SPACES, AND OTHER PERMANENT FIXTURES IN ROOMS AND AREAS WHERE BASE IS REQUIRED.C. INSTALL RESILIENT BASE IN LENGTHS AS LONG AS PRACTICAL WITHOUT GAPS AT SEAMS AND WITH TOPS OF ADJACENT PIECES ALIGNED.D. TIGHTLY ADHERE RESILIENT BASE TO SUBSTRATE THROUGHOUT LENGTH OF EACH PIECE, WITH BASE IN CONTINUOUS CONTACT WITH HORIZONTAL AND VERTICAL SUBSTRATES.E. ON MASONRY SURFACES OR OTHER SIMILAR IRREGULAR SUBSTRATES, FILL VOIDS ALONG TOP EDGE OF RESILIENT BASE WITH MANUFACTURER'S RECOMMENDED ADHESIVE FILLER MATERIAL.F. JOB-FORMED CORNERS:USE STRAIGHT PIECES OF MAXIMUM LENGTHS POSSIBLE AND FORM WITH RETURNS NOT LESS THAN 3 INCHES IN LENGTH.MITER OR COPE CORNERS TO MINIMIZE OPEN JOINTS.4. RESILIENT ACCESSORY INSTALLATIONA. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLING RESILIENT ACCESSORIES.B. RESILIENT MOLDING ACCESSORIES: BUTT TO ADJACENT MATERIALS AND TIGHTLY ADHERE TO SUBSTRATES THROUGHOUT LENGTH OF EACH PIECE. INSTALL REDUCER STRIPS AT EDGES OF FLOOR COVERING THAT WOULD OTHERWISE BE EXPOSED.5. CLEANING AND PROTECTIONA. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR CLEANING AND PROTECTING RESILIENT PRODUCTS.B. REMOVE ADHESIVE AND OTHER BLEMISHES FROM SURFACES OPERATIONS IMMEDIATELY AFTER COMPLETING RESILIENT-PRODUCT INSTALLATION.C. PROTECT RESILIENT PRODUCTS FROM MARS, MARKS, INDENTATIONS, AND OTHER DAMAGE FROM CONSTRUCTION OPERATIONS AND PLACEMENT OF EQUIPMENT AND FIXTURES DURING REMAINDER OF CONSTRUCTION PERIOD.D. COVER RESILIENT PRODUCTS SUBJECT TO WEAR AND FOOT TRAFFIC UNTIL SUBSTANTIAL COMPLETION.SECTION 07 84 13 PENETRATION FIRESTOPPINGA. FOR PENETRATIONS IN FIRE-RESISTANCE-RATED WALLS: PENETRATION FIRESTOPPING SYSTEMS WITH RATINGS DETERMINED PER ASTME814 OR UL1479, BASED ON TESTING AT A POSITIVE PRESSURE DIFFERENTIAL OF 0.01-INCH WG.1. F-RATING: NOT LESS THAN THE FIRE-RESISTANCE RATING OF CONSTRUCTIONS PENETRATED.B. ACCESSORIES: PROVIDE COMPONENTS FOR EACH PENETRATION FIRESTOPPING SYSTEM THAT ARE NEEDED TO INSTALL FILL MATERIALS AND TO MAINTAINRATINGS REQUIRED. USE ONLY THOSE COMPONENTS SPECIFIED BY PENETRATION FIRESTOPPING SYSTEM MANUFACTURER AND APPROVED BY QUALIFIED TESTING AND INSPECTING AGENCY FOR CONDITIONS INDICATED.1. PERMANENT FORMING/DAMMING/BACKING MATERIALS.2. SUBSTRATE PRIMERS.3. COLLARS.4. STEEL SLEEVES.C. INSTALL PENETRATION FIRESTOPPING SYSTEMS TO COMPLY WITH MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND PUBLISHED DRAWINGS FOR PRODUCTS AND APPLICATIONS.D. INSTALL FILL MATERIALS BY PROVEN TECHNIQUES TO PRODUCE THE FOLLOWING RESULTS:1. FILL VOIDS AND CAVITIES FORMED BY OPENINGS, FORMING MATERIALS, ACCESSORIES AND PENETRATING ITEMS TO ACHIEVE REQUIRED FIRE-RESISTANCE RATINGS.2. APPLY MATERIALS SO THEY CONTACT AND ADHERE TO SUBSTRATES FORMED BY OPENINGS AND PENETRATING ITEMS.3. FOR FILL MATERIALS THAT WILL REMAIN EXPOSED AFTER COMPLETING THEWORK, FINISH TO PRODUCE SMOOTH, UNIFORM SURFACES THAT ARE FLUSH WITH ADJOINING FINISHES.SECTION 12 36 53 LABORATORY WORK SURFACES1. PRODUCT: EPOXY RESIN WORK SURFACEA. BASIS OF DESIGN MANUFACTURER: DURCON, INC2. MATERIAL: SOLID EPOXY RESINA. SHEETS CAST FROM MODIFIED EPOXY RESIN AND NON-ASBESTOS INERT FILLERB. SHEET MONOLITHIC THROUGHOUT WITHOUT SURFACE COATING APPLICATION3. COLOR: BLACK ONYX4. FABRICATION: EPOXY RESIN WORK SURFACEA. THICKNESS: 1"B. EDGE TREATMENT: 1/8" BEVEL W/ DRIP GROOVEC. CORNER TREATMENT: EXPOSED CORNERS SHALL BE EASED SLIGHTLY FOR SAFETYD. BACK AND END SPLASHES:1. SUPPLIED LOOSE FOR FIELD INSTALLATION2. SAME MATERIAL AND THICKNESS AS WORK SURFACE3. 4" HIGH UNLESS OTHERWISE NOTED4. TOP-MOUNTED END SPLASH WHERE WORK SURFACES ABUT ADJACENT CONSTRUCTION AND AT LOCATIONS INDICATED ON DRAWINGSE. JOINTS: AS INDICATED ON DRAWINGS, MAXIMUM 1/8" BONDED WITH EPOXY GROUTF. SINK CUTOUTS: AS INDICATED ON DRAWINGS, ROUTED FOR DROP-IN SINKG. ALLOWABLE TOLERANCES:a. SQUARE: PLUS OR MINUS 1/64" FOR EACH 12" OF LENGTHb. LOCATION OF CUTOUTS AND DRILLED OPENINGS: PLUS OR MINUS 1/8" OF DESIGN DIMENSIONc. SIZE OF CUTOUTS OR DRILLED OPENINGS: PLUS 1/8" OR MUNS 0"5. FABRICATION: EPOXY RESIN SINKA. MOLD SINKS FROM THERMOSETTING EPOXY RESINB. MOLD INTERIOR CORNERS TO RADIUS. SLOPE SINK BASE TO DRAIN OUTLET.C. PROVIDE 1-1/2" OUTLET WITH OPEN ENDED STANDPIPE; STANDPIPE OVERFLOW 2" SHORTER THAN DEPTH OF SINKD. UNLESS OTHERWISE INDICATED, FABRICATE SINKS OF DROP-IN SUPPORT BY UPPER FLANGE FROM WORK SURFACE.E. COLOR: TO MATCH ADJACENT WORK SURFACES.F. SINK TYPES:a. SK-A: D-25 (18" X 15" X 7.9")b. SK-B: A-25 (18" X 15" X 5")SECTION 12 35 51 LABORATORY CASEWORK1. PRODUCT: CABINETSA. MANUFACTURER: MOTT MANUFACTURINGB. PERFORMANCE REQUIREMENTS: COMPLY WITH SEFA 8 RECOMMENDED PRACTICESC. PRODUCT: STEEL CABINETSa. CABINETS:• CONSTRUCTION: INSET• CABINET SIDES: 18 GA• TOP RAILS: 14 GA• DOOR FRONTS: 18GA• RUBBER BUMPERS/SILENCERS• ADJUSTABLE SHELVES: 20GA• PULLS: 4" STAINLESS STEEL WIRE PULL• HINGES: STAINLESS STEEL OVERLAY HINGES• STEEL FINISH: POWDER COATEDb. BASE CABINET• REMOVABLE BACK: 20 GA• REAR RAIL: 16 GA• DRAWER RUNNER SUPPORT: 14 GA GALVANIZED• DRAWER LINER: 20 GA• ROLLER CATCHES• 3/8" THREADED LEVELER PLATE: 11 GA• DRAWER WITH INTEGRAL SIDES & BACK: 18 GA OR 20 GA• ENCLOSED TOE SPACE: 18 GAc. UPPER CABINET• GLAZED DOORS: HOLLOW-METAL STILES AND RAILS. GLASS HELD IN RESILIENT CHANNELS OR GASKET MATERIALD. PRODUCT: REAGENT SHELVING SYSTEME. PRODUCT: PEG BOARDSa. POLYPROPYLENE, EPOXY OR PHENOLIC-COMPOSITE PEGBOARDS WITH REMOVABLE POLYPROPYLENE PEGS AND STAINLESS-STEEL DRIP TROUGHS WITH DRAIN OUTLET.F. PRODUCT: GAS / AIR FITTINGSSECTION 08 88 13 FIRE-RESISTANT GLAZING1. GLASS PRODUCTSA. LAMINATED CERAMIC GLAZING: LAMINATED GLASS MADE FROM TWO PLIES OF CLEAR, CERAMIC GLASS2. GLASS SCHEDULE:A. LAMINATED CERAMIC GLAZING (TYPE S-2)a. 45 MINUTE FIRE-PROTECTION RATED LAMINATED CERAMIC GLASSb. THICKNESS: 8.0 MMc. PROVIDE SAFETY LABELING, 16 CFR 1201, CATEGORY IId. PRODUCTS: SUBJECT TO COMPLIANCE WITH THE REQUIREMENTS;• SAFTI FIRST RATED GLAZING SOLUTIONS; PRYAN PLATINUM L• TECHNICAL GLASS PRODUCTS; FIRELITE PLUS• VETROTECH SAINT-GOBAIN; SGG KERALITE FR-LSECTION 22 40 00 PLUMBING FIXTURES1. PRODUCT: SCULLERY SINK WITH TWO DRAINBOARDS (SK-C)A. SIMILAR TO SS8124LR2 AS MANUFACTURERED BY ELKAY WITH DIMENSIONS AS FOLLOWS:a. 27" DEEP X 74" WIDE X 36" HIGH WITH AN 8" REAR SPLASHb. 24" X 24" BOWL CENTEREDc. CONTRACTOR TO VERIFY OVERALL WIDTH PRIOR TO ORDER2. MATERIAL: STAINLESS STEELSECTION 12 24 13 ROLLER WINDOW SHADES1. MANUAL, SPRING-ROLLER OPERATING MECHANISM A. ROLLER MOUNTING CONFIGURATION: SINGLE ROLLERB. INSTALLATION ACCESSORIES: HEMBAR HOLD DOWNS AND FRONT FASCIA2. SHADEBAND MATERIALS: COMPLYING W/ NFPA 701A. ROOM-DARKENING FABRIC: WOVEN FIBERGLASS AND PVC-COATED FIBERGLASS3. PRODUCT SAFETY STANDARD: WCMA A100.1These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/11/2021 9:30:55 AMBIM 360://20625.01 Cornell PreQual Corson Hall Rm 136-142A/20625.01 Cornell PreQual Corson Hall Rm 136-142A.rvt20625.01CWJ/SDFSpecificationsCWJCREA-603100% ConstructionDocumentsCornell UniversityCorson Hall Rm E136-E142A LabRenovationIthaca, NYMay 7, 2021 WALL HYDRANT (WH) / HOSE BIBB (HB) SHOCK ABSORBER (SA) BACKFLOW PREVENTER (BFP) UNION PRESSURE REDUCING VALVE CHECK VALVE BALANCING VALVE SHUT OFF VALVE INDIRECT WASTE PIPING (IW)IW FLOOR DRAIN (FD) / FLOOR SINK (FS) CLEANOUT (CO) WALL PLATE CLEANOUT (WPCO) DECK PLATE CLEANOUT (DPCO) CAP OR PLUG PIPE CONTINUATION "P" TRAP TOP TEE CONNECTION BOTTOM/TEE CONNECTION ELBOW UP 45°OFFSET ELBOW DOWN DESCRIPTION PLUMBING SYMBOL LIST SYMBOL VACUUM PIPING (V)V COMPRESSED AIR PIPING (CA)CA NATURAL GAS PIPING (G)G LAB VENT PIPING (LV)LV STRAINER LAB WASTE PIPING (LW)LW DIR DEIONIZED WATER RETURN PIPING (DIR) DEIONIZED WATER PIPING (DI)DI TEMPERED HOT WATER RETURN PIPING (TWR)TWR TEMPERED HOT WATER PIPING (TW)TW HOT WATER RECIRCULATING PIPING (HWR) HOT WATER PIPING (HW) COLD WATER PIPING (CW) NEW PIPING LOCATED BELOW FLOOR/SLAB NEW PIPING LOCATED ABOVE FLOOR/SLAB (E)EXISTING PIPING EC ELECTRICAL CONTRACTOR PC PLUMBING CONTRACTOR MC MECHANICAL CONTRACTOR GC GENERAL CONTRACTOR VTR VENT THRU ROOF BFF BELOW FINISHED FLOOR AFF ABOVE FINISHED FLOOR (ETR)EXISTING TO REMAIN (E)EXISTING NTS NOT TO SCALE POINT OF DISCONNECTION POINT OF CONNECTION EXISTING WORK TO BE REMOVED DRAWING KEYNOTE DEMOLITION/REMOVAL KEYNOTE X X DETAIL NOTES: DOMESTIC COLD WATER FLOW DIRECTION LABEL. PROVIDE 360 DEGREE WRAP OVERLAPPING BOTH ENDS OF THE PIPE FUNCTION LABEL AND MATCHING THE FLOW DIRECTION OF THE PIPE CONTENTS. PIPE FUNCTION LABEL A. B. C. D. E. F. PROVIDE A PIPE LABEL FOR EACH PIPE FUNCTION. PROVIDE AT LEAST ONE LABEL ON EACH PIPE FOR EVERY ROOM THE PIPE PASSES THROUGH. PROVIDE LABELS IN LARGE SPACES ON MAXIMUM 20' CENTERS FOR EVERY PIPE UNLESS OTHERWISE NOTED IN THE SPECIFICATIONS. LABELS TO BE LOCATED IN AN EASILY VISIBLE LOCATION AS THEY WOULD NORMALLY BE SEEN. IE. ON THE BOTTOM HALF OF PIPES IN THE AIR AND ON THE TOP HALF OR SIDES OF PIPES MOUNTED LOW. LABELS SHALL BE, COLOR CODED, PRE-PRINTED, SELF ADHESIVE VINYL. SEE SPECIFICATION FOR OTHER REQUIREMENTS AND LIST OF PIPE FUNCTIONS. DETAIL NOTES: (E)FUME HOOD WORK SURFACE AT NON ADA HEIGHT, 36 INCHES ABOVE FINISHED FLOOR. (E)FUME HOOD WORK SURFACE AT ADA HEIGHT, 30 INCHES ABOVE FINISHED FLOOR. PROVIDE 2" DRUM TRAP. PROVIDE SUFFICIENT PIPE ON INLET TO ALLOW 6" OF WORK SURFACE ADJUSTMENT. PROVIDE 1 1/2" DRAIN FROM CUP SINK. PROVIDE SUFFICIENT TAILPIECE ON OUTLET TO ALLOW FOR 6" OF WORK SURFACE ADJUSTMENT. DRAIN IS TO BE SLEEVED WITHIN THE 2" INLET PIPE PROVIDED ON THE DRUM TRAP. 2" DRAIN, ROUTE BEHIND UNIT IN CHASE SPACE AND CONNECT TO SINK DRAIN PROVIDE 1 1/2" ACID VENT SERVING CUP SINK DRAIN. CONNECT TO NEAREST VENT SERVICE AS INDICATED ON PLANS. COORDINATE WITH VENT FROM ADJACENT LABORATORY FIXTURES. DOMESTIC COLD WATER CONNECTION: PROVIDE BRASS/ STAINLESS STEEL FLEXIBLE CONNECTION TO PRE-PIPED LABORATORY DOMESTIC WATER SERVICE AT FT FUME HOOD. GAS CONNECTION: PROVIDE BRASS/ STAINLESS STEEL FLEXIBLE CONNECTION TO PRE-PIPED LABORATORY DOMESTIC WATER SERVICE AT FT FUME HOOD. 1 2 3 4 5 6 7 LAB EXHAUST DUCT (TYP.) DUCT COLLAR (TYP.) FUME HOOD FUME HOOD 1 7 2 7 4 3 5 6 4 3 5 6 8 8 8 GAS SOLENOID VALVESTRAINER GAS SHUTOFF VALVE S MASTER GAS SHUTOFF VALVE SWITCH RELAY CONTROL PANEL BRANCH LINE SIZE AS INDICATED ON DRAWING. A. DETAIL NOTES: DIVISION 22 SHALL PROVIDE ALL CONTROL WIRING BETWEEN SWITCH, RELAY PANEL AND GAS SHUTOFF VALVE(S). POWER WIRING TO THE RELAY PANEL WILL BE BY DIVISION 26. VALVES ARE SHOWN FOR CLARITY ONLY. REFER TO PLANS FOR LOCATIONS. B. POWER WIRING TO PANEL BY DIVISION 26. COORDINATE INSTALLATION WITH DIVISION 26. (E)3/4"(E)3/4" EMERGANCY EYEWASH. LOCATE SO WHEN IN USE IT IS OVER THE SINK. 2" LAB WASTE. PIPING IN WALL. SINK TMV. REFER TO ASSOCIATED EYEWASH SPECIFICATION FOR TYPE.1/2" COLD WATER SUPPLY 1/2" HOT WATER SUPPLY 1/2" RODI WATER SUPPLY LAB VENT. REFER TO PLANS TO SEE IF INDIVIDUAL VENT IS REQUIRED. DI FAUCET PIPING IN WALL (TYP) NOTE: IF IN ADA CABINET, ALL PIPING SHALL MEET ANSI & ADA REQUIREMENTS FINISHED FLOOR CASEWORK These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions5/7/2021 9:51:36 AMC:\Users\cmdoktor\Documents\200311_CorsonFirstFloor_P_Central_R20_cmdoktor.rvt20625.01 THK General Notes, Symbols List, Details & Schedules - Plumbing GDD CMD P-000 100% Construction Documents Submission Cornell University Corson Hall Rm 136-142A Lab Renovation Ithaca, NY May 7, 2021 NOT TO SCALE1PIPING IDENTIFICATION LABEL DETAIL NOT TO SCALE3ADJUSTABLE FUME HOOD INSTALLATION DETAIL THESE NOTES ARE APPLICABLE TO THE FULL SET OF CONTRACT DOCUMENTS. EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION DOCUMENTS WHEN AVAILABLE. THE LOCATIONS SHOWN MUST BE CONSIDERED APPROXIMATE. OTHER SUCH WORK MAY EXIST, HOWEVER, LOCATION AND SIZE ARE NOT PRESENTLY KNOWN. IT IS STRONGLY ENCOURAGED TO VISIT SITE PRIOR TO BID TO REVIEW EXISTING CONDITIONS AND CONFIRM SCOPE OF WORK. WHEN EXISTING CONSTRUCTION IS DAMAGED DURING WORK BY THIS CONTRACTOR, REPAIR AND/OR REPLACE WITH SIMILAR MATERIALS AS MUCH AS POSSIBLE, SUBJECT TO ARCHITECTS APPROVAL. DISPOSE OF ALL DEMOLITION AND/OR OTHER WASTE MATERIALS CAUSED BY WORK OF THIS CONTRACTOR. LEGALLY DISPOSE ALL MATERIALS TO A LOCATION OFF SITE. COORDINATE AND SCHEDULE WORK AND SHUTDOWNS WITH THE OWNER AND OTHER TRADES PRIOR TO DEMOLITION. ALL EXISTING PIPING TO REMAIN SHALL BE RECONNECTED TO ACTIVE SERVICE PIPING. ALL PIPING TO BE REMOVED, SHALL BE REMOVED BACK TO ACTIVE PIPING AND CAPPED. VALVE AND CAP ALL WATER PIPING. REMOVE ALL INACTIVE PIPING UNLESS NOTED. ALL PIPING TO BE REMOVED AND LOCATED WITHIN A WALL TO REMAIN MAY BE ABANDONED IN PLACE UNLESS NOTED. REMOVE PIPING BACK TO BEHIND THE FINISHED WALL SURFACE AND CAP. PATCH HOLES IN EXISTING CONSTRUCTION LEFT BY THE REMOVAL OF PIPING OR EQUIPMENT WITH MATERIALS TO MATCH EXISTING CONSTRUCTION. MAINTAIN FIRE/SMOKE RATING. DEMOLITION SHALL INCLUDE, BUT NOT BE LIMITED TO: PIPING, VALVES, FIXTURES, EQUIPMENT, HANGERS, SUPPORTS, AND INSULATION EXCEPT ASBESTOS. REMOVE EXISTING CONSTRUCTION IN THE WAY OF NEW WORK. PROTECT BUILDING AND FURNISHINGS FROM DAMAGE. WHERE NEW WORK IS TO BE INSTALLED ABOVE AN EXISTING CEILING, PROVIDE FOR THE REMOVAL OF THE CEILING. UPON COMPLETION OF WORK, REPAIR ALL DAMAGED CEILING SURFACES, REPLACE ALL DAMAGED TILES. SLEEVE AND SEAL ALL WALL AND FLOOR PENETRATIONS. PROVIDE FIRESTOPPING FOR ALL PENETRATIONS. MAINTAIN SERVICE CLEARANCES OF ALL EQUIPMENT. ADVISE OTHER TRADES OF THE REQUIRED SERVICE CLEARANCES. PROVIDE FOR THE DRAINING AND REFILLING OF PIPING SYSTEMS, INCLUDING AIR REMOVAL, RESETTING OF FLUSH VALVES, FLUSHING SYSTEMS OF DIRT AND SCALE CAUSED BY SHUTDOWNS AND STARTUPS. REFER TO EQUIPMENT/ FIXTURE SCHEDULE FOR FINAL CONNECTION SIZES. PROVIDE CLEANOUTS AT THE BASE OF ALL STORM, SANITARY AND WASTE STACKS. PITCH 4" AND LARGER LAB WASTE PIPING AT 1/8" PER FOOT UNLESS OTHERWISE NOTED. FOR SANITARY AND WASTE PIPING 3" AND SMALLER PITCH AT 1/4" PER FOOT UNLESS OTHERWISE NOTED. A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. P. Q. R. GENERAL NOTES: NOT TO SCALE4GAS PIPING SHUT-OFF DETAIL NOT TO SCALE 2 SINK WITH EYEWASH DETAIL 1 REFER TO DETAIL 2 ON P-000. REMARKS: EW-A EYE WASH 1/2" TEPID --- 1 SK-C SINK 1/2" 1/2" 1/2"1/2"2" 1 1/2" - SK-B SINK-ADA 1/2" 1/2" 1/2"2" 1 1/2" - SK-A SINK 1/2" 1/2" 1/2"2" 1 1/2" - DESIGNATION DESCRIPTION COLD WATER HOT WATER DI WATER DECHLORINATED WATER LAB WASTE LAB VENT REMARKS FIXTURE AND EQUIPMENT CONNECTION SCHEDULE 1 F H 14 15 16 SK-A SK-B LW 2"LW LW ●●● ●●●  (E)DI(E)G ●●●(E)DI(E)G●●● ●●●  (E)DI (E)G ●●(E)DC●(E)DI(E)2" BUBBLER AIR & (E)3/4" CO2(E)BUBBLER AIR (E)2" (E)DC (E)3/4" (E)3/4" CW, (E)3/4" HW, (E)3/4" DI & (E)3/4" DC (E)G(E)DI ●● ● (E)3/4" CW, (E)3/4" HW, (E)3/4" DI & (E)3/4" G (E)4" LW (BURIED) (E)SINK TO REMAIN (E)FD TO REMAIN (E)4" LW UP & DN (E)LW LW 1 1/2" ● 1/2" 1/2" CW, 1/2" HW & 1/2" DI IN CASEWORK TO SINK. 1/2" CW, 1/2" HW & 1/2" DI IN CASEWORK TO SINK. 2" LW DN. REFER TO DETAIL 4 ON P-000. 1/2" CW & G DN IN WALL. CUT & PATCH WALL AS REQUIRED.●●●DIEW-A SK-A SK-C 1/2" CW, 1/2" HW, 1/2" DI & 2" LW TO SINK. DROP PIPING IN CASEWORK CHASE. COORDINATE LOCATION WITH G.C. (E)4" LW UP & DN (E)EMER. SHOWER (E)1/2" CW, (E)1/2" HW, (E)1/2" DI & (E)1 1/2" LW DN TO SINK ROUTE LW TO AVOID SINK LEGS. COORDINATE WITH G.C. RECONNECT SINK WITH (E) SUPPLY PIPING, MODIFY AS REQUIRED FOR NEW CONNECTION. PROVIDE NEW LAB WASTE AND ROUTE AROUND SINK TABLE LEGS. 1/2" CW, 1/2" HW, 1/2" DI & 1/2" G DN. ROUTED TO SINK IN CASEWORK CHASE. G 1/2" RECONNECT 1/2" CW & 1/2" G TO FUME HOOD. 1/2" 1/2" 1/2" 1/2" WET LAB E142 MICROSCOPY/ MICROINJECTION E138 PREP E142A ANIMAL ROOM E136 GO-A ROUTE 1/2" G UNDER CASEWORK TO GO-A. 1 1/2" LW RACKED ON WALL UNDER CASEWORK. LV 1 1/2" (E)4" LV UP & DN EW-A GAS SHUT-OFF. SUPPLY RELAY CONTROL PANEL AND SWITCH. ELECTRICAL CONNECTION BY EC. REFER TO DETAILS FOR FURTHER REQUIREMENTS. PROVIDE SIGNAGE. GAS SOLENOID VALVE. REFER TO DETAILS FOR FURTHER REQUIREMENTS. 1 1 1 1 1 1 1 1 1/2" GAS DN IN WALL. ROUTE PIPING IN CASEWORK CHASE TO OUTLET. GO-A. INSTALL TO MEET ADA. (E)DC 1 1/2" V UP. CONNECT TO VENT STACK IN CHASE. 1 1/2" LV IN CASEWORK CHASE 3 3 3 2" 2" 2" LW TO SINK 2" LW TO SINK G 1/2" EW-A F H 14 15 16 ●●● ●●●  (E)DI(E)G ●●●(E)DI(E)G●●●(E)DI●●● ●●●  (E)DI (E)G ●●(E)DC●(E)DI(E)2" BUBBLER AIR & (E)3/4" CO2(E)BUBBLER AIR (E)2" (E)DC (E)3/4" (E)3/4" CW, (E)3/4" HW, (E)3/4" DI & (E)3/4" DC (E)G(E)DI ●●● (E)3/4" CW, (E)3/4" HW, (E)3/4" DI & (E)3/4" G (E)4" LW (BURIED) (E)SINK TO REMAIN CUT & PATCH FLOOR AS REQUIRED TO CAP PIPING BELOW FLOOR. CUT & PATCH WALL AS REQUIRED TO CAP PIPING BELOW FLOOR. CUT & PATCH WALL AS REQUIRED TO REMOVE PIPING BEHIND WALL. 1 1 REMOVE (E)1/2" CW, (E)1/2" HW, (E)1/2" DI & (E)2" LW TO SINK (E)FD TO REMAIN 1 REMOVE (E)1/2" CW, (E)1/2" HW & (E)2" LW TO SINK (E)1/2" CW, (E)1/2" HW& (E)1 1/2" LW DN TO SINK (E)4" LW UP & DN (E)1 1/2" (E)1/2" (E)1/2" (E)LW ●● ●(E)LW(E)1 1/2"(E)LW (E)1 1/2" (E)LW (E)1/2" CW, (E)1/2" HW, (E)1/2" DI & (E)1 1/2" LW DN TO SINK REMOVE HOSE BIBS AND 1'-0" OF PIPE AND REINSTALL HOSE BIBS. 2 2 (E)DI 2 (E)4" LW UP & DN (E)EMER. SHOWER DISCONNECT (E)1 1/2" LW, (E)1/2" CW & (E)1/2" G TO FUME HOOD TO ALLOW FUME HOOD TO BE MOVED. 1 1 REMOVE PIPING BACK TO WALL AND CAP. CUT & PATCH WALL AS REQUIRED TO CAP PIPING. REMOVE PIPING UNDER CASEWORK REMOVE PIPING UNDER CASEWORK (E)4" LV UP & DN WET LAB E142 MICROSCOPY/ MICROINJECTION E138 PREP E142A ANIMAL ROOM E136 3 2 REMOVE EXPOSED PIPING AND CAP ABOVE CEILING (E)G ●●● (E)LW 2 (E)DC 4" LV UP REMOVE EXISTING VENT PIPING. GENERAL NOTES: A. REMOVE, PROTECT AND REINSTALL CEILING AS REQUIRED. These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions5/7/2021 11:12:03 AMC:\Users\cmdoktor\Documents\200311_CorsonFirstFloor_P_Central_R20_cmdoktor.rvt20625.01 THK Partial First Floor Plans - Plumbing GDD CMD P-100 100% Construction Documents Submission Cornell University Corson Hall Rm 136-142A Lab Renovation Ithaca, NY May 7, 2021 1/4" = 1'-0"2 1st Floor - Plumbing New Work 1/4" = 1'-0"1 1st Floor - Plumbing Demolition DEMOLITION NOTES 1 REMOVE SINK, FAUCET, AND ASSOCIATED PIPING. 2 DISCONNECT AND REMOVE PIPING BACK TO POINT OF DISCONNECT AND CAP. 3 REMOVE SINK AND FAUCET. MODIFY PIPING AS REQUIRED FOR NEW SINK. N DRAWING NOTES 1 CO2 OUTLETS ARE NOT USED. PROVIDE CAP ON NOZZLE. 3 COORDINATE WITH G.C. FOR SAWCUTTING OF BURIED PIPING. EACH LINE MUST BE RUN SEPARATE TO MAIN TO MAINTAIN VENTING. F H 14 15 16 (E)FP(E)FP(E)FP(E)FP(E)FP(E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN LOCATE SPRINKLER HEAD IN CENTER OF TILE (TYP) F H 14 15 16 (E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN (E)SPRINKLER HEAD TO REMAIN REMOVE SPRINKLER HEAD AND HARD PIPED SECTION(TYP) REMOVE SPRINKLER HEAD AND HARD PIPED SECTION(TYP) REMOVE SPRINKLER HEAD AND HARD PIPED SECTION(TYP)(E)FP(E)FP(E)FP(E)FP(E)FPUPRIGHT SPRINKLER DESCRIPTIONSYMBOL FIRE PROTECTION SYMBOL LIST QUICK RESPONSE UPRIGHT SPRINKLER POINT OF CONNECTION SIDEWALL SPRINKLER NTS NOT TO SCALE (ETR)EXISTING TO REMAIN GC GENERAL CONTRACTOR PC PLUMBING CONTRACTOR FC FLUSHING CONNECTION NEW PIPING S SPRINKLER MAIN/BRANCH PIPING (S) ELBOW DOWN DRAIN VALVE ELBOW UP CHECK VALVE TOP TEE CONNECTION FLUSHING CONNECTION DRY PENDENT SPRINKLER SHUT-OFF VALVE WITH TAMPER SWITCH (TS) EXISTING WORK TO BE REMOVED AFF ABOVE FINISHED FLOOR MC MECHANICAL CONTRACTOR EC ELECTRICAL CONTRACTOR (E)EXISTING PIPING FP FIRE PROTECTION SERVICE (FP) D SPRINKLER DRAIN PIPING (D) 45°OFFSET BOTTOM/TEE CONNECTION PIPE CONTINUATION PENDENT SPRINKLER QUICK RESPONSE PENDENT SPRINKLER POINT OF DISCONNECTION FIRE DEPARTMENT VALVE (FDV) INSPECTOR'S TEST CONNECTION (ITC) (E)EXISTING OR DRAWING KEYNOTE DEMOLITION/REMOVAL KEYNOTE X X GENERAL NOTES: A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION DOCUMENTS WHEN AVAILABLE. THE LOCATIONS SHOWN MUST BE CONSIDERED APPROXIMATE. OTHER SUCH WORK MAY EXIST, HOWEVER, LOCATION AND SIZE ARE NOT PRESENTLY KNOWN. VISIT SITE PRIOR TO BID TO REVIEW EXISTING CONDITIONS AND DETERMINE SCOPE OF WORK. WHEN EXISTING CONSTRUCTION IS DAMAGED DURING WORK BY THIS CONTRACTOR, REPAIR AND/OR REPLACE WITH SIMILAR OR LIKE MATERIALS AS MUCH AS POSSIBLE, SUBJECT TO ARCHITECTS APPROVAL. DISPOSE OF ALL DEMOLITION AND/OR OTHER WASTE MATERIALS CAUSED BY WORK OF THIS CONTRACTOR. LEGALLY DISPOSE ALL MATERIALS TO A LOCATION OFF SITE. COORDINATE AND SCHEDULE WORK AND SHUTDOWNS WITH THE OWNER AND OTHER TRADES PRIOR TO DEMOLITION. ALL EXISTING PIPING TO REMAIN SHALL BE RECONNECTED TO ACTIVE SERVICE PIPING. ALL PIPING TO BE REMOVED, SHALL BE REMOVED BACK TO ACTIVE PIPING AND CAPPED. VALVE AND CAP ALL WATER PIPING. REMOVE ALL INACTIVE PIPING UNLESS NOTED. ALL PIPING TO BE REMOVED AND LOCATED WITHIN A WALL TO REMAIN MAY BE ABANDONED IN PLACE UNLESS NOTED. REMOVE PIPING BACK TO BEHIND THE FINISHED WALL SURFACE AND CAP. PLUG HOLES IN EXISTING CONSTRUCTION LEFT BY THE REMOVAL OF PIPING OR EQUIPMENT. MAINTAIN FIRE/SMOKE RATING. DEMOLITION SHALL INCLUDE, BUT NOT BE LIMITED TO: PIPING, VALVES, FIXTURES, EQUIPMENT, HANGERS, SUPPORTS, AND INSULATION EXCEPT ASBESTOS. All SECURING AND ATTACHMENT POINTS TO EXISTING BUILDING STRUCTURE INCLUDING WALLS, CEILINGS, FLOORS, SLABS, DECKS, ETC. SHALL BE REVIEWED WITH CORNELL UNIVERSITY AND THE PROJECT ENVIRONMENTAL CONSULTANT PRIOR TO SECURING AND ATTACHING DEVICES AND EQUIPMENT. SOME BUILDING ELEMENTS MAY CONTAIN ASBESTOS AND ABATEMENT MAY BE REQUIRED. ABATEMENT SHALL BE PERFORMED BY SEPARATE CONTRACTOR WITH THE ASSISTANCE OF THIS CONTRACTOR FOR IDENTIFYING ATTACHMENT POINT LOCATIONS. MIXING OF DEMOLITION AND CONSTRUCTION DEBRIS IN COMMON DUMPSTERS IS NOT ALLOWED. ALL DEMOLITION AND CONSTRUCTION DEBRIS SHALL BE SEPARATED AND SORTED THEN PLACED IN THE DESIGNATED DUMPSTER FOR THAT SPECIFIC MATERIAL IN COMPLIANCE WITH PROJECT LEED CONSTRUCTION WASTE MANAGEMENT REQUIREMENTS. ABANDONING EXISTING SYSTEMS, EQUIPMENT AND APPURTENANCES IN PLACE IS NOT ALLOWED. ALL SYSTEMS, EQUIPMENT AND APPURTENANCES DEEMED FOR REMOVAL SHALL BE REMOVED. THE CONTRACTOR SHALL NOTIFY CORNELL UNIVERSITY IF EXISTING SYSTEMS, EQUIPMENT AND APPURTENANCES ARE FOUND THAT HAD NOT BEEN INDICATED ON THE PROJECT PLANS TO EITHER BE REMOVED OR TO REMAIN IN PLACE. PIPE ROUTING DOES NOT SHOW PIPE FITTINGS THAT WILL BE REQUIRED. MOST LOCATIONS WILL REQUIRE PIPING TO RISE INTO STRUCTURAL CAVITY AND THEN BACK DOWN. (TYPICAL ALL LOCATIONS). PROVIDE WIRE GAGES ON ALL SPRINKLERS IN ELECTRICAL AND TR ROOMS. NO WORK TO BE DONE ON FIRE PROTECTION SYSTEM UNTIL HEAT DETECTORS ARE INSTALLED & OPERATIONAL. REFER TO ELECTRICAL DRAWINGS. These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions5/7/2021 9:51:36 AMC:\Users\cmdoktor\Documents\200311_CorsonFirstFloor_P_Central_R20_cmdoktor.rvt20625.01 THK General Notes , Symbols List & Details & Floor Plans - Fire Protection GDD CMD FP-100 100% Construction Documents Submission Cornell University Corson Hall Rm 136-142A Lab Renovation Ithaca, NY May 7, 2021 1/4" = 1'-0" 1 1st Floor - Fire Protection 1/4" = 1'-0" 2 1st Floor - Fire Protection Demolition GENERAL NOTES:A. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DISPOSE OF ALL DEMOLITION DEBRIS AND MATERIALS OFF SITE IN A PROPER LEGAL MANNER.B. ALL NEW PENETRATIONS THROUGH WALLS, FLOORS AND ROOFS SHALL BE PROVIDED FOR INSTALLATION OF MECHANICAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, EQUIPMENT, DUCTWORK, PIPING, ETC. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE FIRE/SMOKE STOPPED. ALL PENETRATIONS THROUGH NON RATED WALLS SHALL BE SEALED WITH A NON-HARDENING SEALANT ON BOTH SIDES OF WALL PENETRATION TO REDUCE NOISE TRANSMISSION.C. THE DUCTWORK SIZES AND TYPES (ROUND, RECTANGULAR AND FLAT OVAL)WERE SELECTED FOR SPACE LIMITATION WITHIN THE RENOVATED AREA. IN ADDITION, THE DUCTWORK SIZES AND TYPES WERE CHOSEN TO ALLOW SPACE ABOVE THE CEILINGS FOR FUTURE DUCTWORK, PIPING AND/OR CONDUIT. IT IS NOT ACCEPTABLE FOR THE CONTRACTOR TO CHANGE THE SIZE OR TYPE OF DUCTWORK FOR BIDDING OR INSTALLATION UNLESS SPECIFICALLY APPROVED BY THE ENGINEER. D. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE ALL SHUTDOWNS OF AIR HANDLING, CHILLED WATER, HOT WATER, STEAM, ETC. SYSTEMS WITH CORNELL UNIVERSITY FACILITY PERSONNEL FOR TIE-IN CONNECTIONS. ALL SHUT DOWNS WILL OCCUR DURING NIGHTS OR WEEKENDS. THE CONTRACTOR SHALL ASSIST THE UNIVERSITY PERSONNEL IN SHUTTING DOWN, DRAINING, VENTING, ETC. OF SYSTEM TO FACILITATE THE INTENDED WORK.E. A MINIMUM OF 1'-6" SHALL BE PROVIDED IN FRONT OF CONTROL ACCESS ENCLOSURES AT ALL TERMINAL UNITS. NO PIPING OR CONDUIT SHALL BE DIRECTLY INSTALLED BELOW AIR TERMINAL UNIT ACCESS ENCLOSURES THAT WILL PROHIBIT ACCESS UP TO THE CONTROL ENCLOSURE. COORDINATE THESE REQUIREMENTS WITH ALL OTHER TRADES ON THE PROJECT. IF PROPER SERVICE ACCESS IS NOT MAINTAINED BECAUSE OF POOR COORDINATION, THE CONTRACTOR SHALL RELOCATE OBSTRUCTIONS AT NO ADDITIONAL COST TO THE OWNER.F. PROVIDE A VOLUME DAMPER AT EACH DIFFUSER AND GRILLE FOR PROPER BALANCING REGARDLESS IF SHOWN ON DRAWINGS. ALL VOLUME DAMPERS SHALL BE A MINIMUM OF 6'-0" FROM DIFFUSER OR GRILLE CONNECTION.IF FLEXIBLE DUCTWORK IS UTILIZED FOR FINAL CONNECTION AT GRILLES, THE CROSS SECTIONAL AREA OF THE FLEXIBLE DUCTWORK SHALL NOT BE LESS THAN THE CROSS SECTIONAL AREA OF THE GRILLE NECK.G. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE LOCATIONS OF ALL ROOM TEMPERATURE SENSORS WITH THE ARCHITECT/ENGINEER. THE CONTRACTOR SHALL SCHEDULE A WALK THROUGH WITH THE ARCHITECT/ENGINEER TO LOCATE SENSOR LOCATIONS PRIOR TO INSTALLATION. THE TEMPERATURE SENSORS SHALL BE INSTALLED IN ALIGNMENT WITH ELECTRICAL, FIRE, AND OTHER DEVICES WHEN LOCATED ON COMMON WALLS.H. DAMAGE TO EXISTING SYSTEMS (EQUIPMENT, PIPING, DUCTWORK, CONTROLS AND ACCESSORIES) SHOWN TO REMAIN AS A RESULT OF THE CONTRACTORS WORK IS THE RESPONSIBILITY OF THE CONTRACTOR TO REPAIR AND/OR REPLACE WITH SIMILAR OR LIKE MATERIALS AT NO ADDITIONAL COST TO THE OWNER.I. COORDINATE ALL SHUT DOWNS WITH OWNER PRIOR TO CONSTRUCTION.J. THE DEMOLITION DRAWINGS SHOW IN GENERAL MAJOR EQUIPMENT, PIPING AND DUCTWORK REMOVALS. THE INTENT IS NOT TO IDENTIFY ALL MISCELLANEOUS PIPING, PIPING ACCESSORIES, DUCTWORK, DUCTWORK ACCESSORIES, SUPPORTS, CONTROLS, CONTROL ACCESSORIES, CONTROL WIRING, CONDUIT, AND CONTROL PNEUMATIC TUBING AND ACCESSORIES TO BE DISCONNECTED AND REMOVED BUT IS THE REQUIREMENTS UNDER THIS CONTRACT. NO EQUIPMENT, PIPING OR DUCTWORK SHALL BE ABANDONED IN PLACE UNLESS OTHERWISE NOTED ON THE DRAWINGS.K. THE MOUNTING HEIGHT FOR ALL ROOM THERMOSTATS OR SENSORS SHALL BE 48 IN. TO TOP OF THE COVER.L. UNLESS SHOWN ON THE ARCHITECTURAL DRAWINGS, IT IS THE RESPONSIBILITY OF THIS CONTRACT TO PATCH WITH LIKE MATERIAL AND FINISH ALL EXISTING DUCTWORK OR PIPE PENETRATIONS THROUGH FLOORS AND WALLS AFTER DEMOLITION. M. EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION DOCUMENTS AND ARE NOT GUARANTEED. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BID. NO ALLOWANCE WILL BE MADE FOR ADDITIONAL COSTS DUE TO CONTRACTORS FAILURE TO VERIFY EXISTING CONDITIONS AND DIMENSIONS.N. THE OWNER OCCUPIED AREAS INCLUDE SENSITIVE EQUIPMENT AND RESEARCH WHICH MUST NOT BE INTERRUPTED OR OTHERWISE DISTRUPTED WITHOUT PRIOR NOTICE AND APPROPRIATE PLANNING. DSDMBHTHOUSAND BTU/HOUR(E)EXISTINGDOUBLE LINE RECTANGULARDUCT CONTINUEDFPMFEET PER MINUTEAIR FLOWAFF ABOVE FINISHED FLOORPIPE ANCHORG.C.GENERAL CONTRACTORPIPE GUIDEE.C.ELECTRICAL CONTRACTOREXPANSION COMPENSATOR WITH GUIDESN.C.NORMALLY CLOSEDPRE-FAB EXPANSION LOOPTEMPERATURE SENSORSTRAINERPRESSURE GAUGETHERMOMETERUNION24x12DNUPAIR VENTV24x1214x86" BOOTTAPTTTHERMOSTATIC TRAP14"18"LATERALFT FLOAT & THERMOSTATIC TRAPSUPPLY DIFFUSER, REGISTER OR GRILLETDTHERMODYNAMIC TRAPFLEXIBLE DUCTWORKBT BUCKET TRAPCOMPRESSED AIRADIRECTION OF FLOWBBD BOILER BLOW DOWNCONDENSER WATER SUPPLYCSCR CONDENSER WATER RETURNCWS CHILLED WATER SUPPLYCWR CHILLED WATER RETURNDDRAINFUEL OIL FILLFOFFUEL OIL GAUGEFOGFOS FUEL OIL SUPPLYFOR FUEL OIL RETURNFOV FUEL OIL TANK VENTGGASGLYCOL SUPPLYGSGLYCOL RETURNGRHPWS HEAT PUMP WATER SUPPLYHPWR HEAT PUMP WATER RETURNHWS HOT WATER SUPPLYHWR HOT WATER RETURNHG HOT GASLPS LOW PRESSURE STEAMLPC LOW PRESSURE CONDENSATEMPS MEDIUM PRESSURE STEAMMPC MEDIUM PRESSURE CONDENSATEHPS HIGH PRESSURE STEAMHPC HIGH PRESSURE CONDENSATEPC PUMPED CONDENSATERD REFRIGERANT DISCHARGERL REFRIGERANT LIQUIDRS REFRIGERANT SUCTIONVACVACUUMCW DOMESTIC COLD WATEREXISTING WORK TO BE REMOVEDDOUBLE LINE PIPE ORROUND DUCT CONTINUEDEPNEUMATIC THERMOSTATNTS NOT TO SCALE(DBL) DOUBLE WALL LINED DUCTCFM CUBIC FEET PER MINUTEAD ACCESS DOORP.C. PLUMBING CONTRACTORN.O. NORMALLY OPENDUCT SMOKE DETECTORHUMIDISTATROUND DUCT - IN INCHES12"24x12DNUP14"CONICALTEE18"VOLUME DAMPERCAP OR PLUGELBOW DOWNELBOW UPAAD AUTOMATIC AIR DAMPERFD FIRE DAMPERSD SMOKE DAMPERBDD BACK DRAFT DAMPERM MOTORIZED DAMPERBALL VALVEGATE VALVECHECK VALVEBALANCING VALVEBUTTERFLY VALVEPRESSURE REDUCING VALVEPRVCONTROL VALVEPRESSURE/TEMPERATURE TEST PLUG(L)(2L) ACOUSTIC THERMAL LINING - 2" THICKM.C. MECHANICAL CONTRACTORW/W WALL TO WALLGTHERMOSTAT/SENSOR WITH GUARDGDUCT SECTION - SUPPLYDUCT SECTION - RETURNWIDTH A x DEPTH BABRD24x1214"6" BOOTTAPBG BLAST GATEFIN TUBE RADIATIONVALANCEABCREGISTER, GRILLE OR DIFFUSER TAGA = TYPEB = NECK SIZEC = CFMBCDFIN TUBE RADIATION TAGFT-A = TYPEB = FIN TUBE LENGTHC = ENCLOSURE LENGTHD = GPMFT-AABCDVALANCE TAGA = TYPEB = COIL SIZEC = COOLING GPMD = HEATING GPMPOINT OF CONNECTIONPOINT OF DISCONNECTIONBOTTOM TAPTRIPLE DUTY VALVETDGLOBE VALVETHREE WAY CONTROL VALVESUCTION DIFFUSERSDDRAIN VALVE WITH HOSE CONNECTION,CAP AND CHAINFC FLEX CONNECTOR - DUCTWORKFLEXIBLE CONNECTOR - PIPINGAIR TERMINAL UNIT AND TAG (OPTION 1)ABCAIR TERMINAL UNIT TAG (OPTION 2)A = UNIT NO.B = MAXIMUM CFMC = MINIMUM CFMAxBFODUCT SECTION - FLAT OVAL (FO)VVENTREDUCERSHSACOUSTIC THERMAL LINING - 1-1/2" THICKEXHAUST GRILLERETURN REGISTERSINGLE LINE PIPE CONTINUEDTRANSITION SQUARE TO ROUNDRISE IN DUCT - IN DIRECTION OF AIRFLOWDROP IN DUCT - IN DIRECTION OF AIRFLOWSUPPLY DUCT TURNING UP OR DOWNRETURN DUCT TURNING UP OR DOWNSUPPLY/RETURN RECTANGULAR MAINRECTANGULAR BRANCHSUPPLY/RETURN RECTANGULAR MAINROUND BRANCHSUPPLY/RETURN ROUND MAINROUND BRANCHSUPPLY/RETURN ROUND MAINROUND BRANCHMITERED ELBOW WITH TURNING VANESDESCRIPTIONSYMBOLDESCRIPTIONSYMBOLTRELIEF VALVETHVAC SYMBOL LISTXXDRAWING KEYNOTEDEMOLITION KEYNOTEABCRADIANT CEILING PANEL TAGA = TYPEB = LENGTHC = GPMCARBON DIOXIDE SENSORCCARBON MONOXIDE SENSORCOGAS SENSORGSYMBOLDESCRIPTIONSYMBOLDESCRIPTIONAVERAGING SENSORSSSTART/STOPOCOPEN/CLOSEEDENABLE/DISABLETTEMPERATURE SENSOR(DUCT OR PIPE MOUNTED)HHUMIDITY SENSOR(DUCT MOUNTED)IPELECTRICAL INTERFACEAUTOMATIC AIR DAMPER(PARALLEL BLADE)AUTOMATIC AIR DAMPER(OPPOSED BLADE)EELECTRIC/ELECTRONICCONTROL VALVE (3-WAY)EES END SWITCHEA EXHAUST AIRMOISTURE SENSOROCCUPANCY SENSORFLOW METERSUPPLY FANSFBTU ENERGY METERBTUPDIFFERENTIAL STATICPRESSURE SWITCHALARMSTATUSPROBE SENSORRELAYFREEZE-STATFZEELECTRIC ACTUATORCURRENT TRANSDUCERFLOW SENSORAIR FLOW MEASURINGSTATIONHARD WIRE INTERFACESSOLENOID VALVESMMANUAL SWITCHTHERMOSTATIC EXPANSIONVALVECARBON DIOXIDE SENSOR(DUCT MOUNTED)CO2BINARY POINTANALOG POINTTHERMOWELLPDIFFERENTIAL STATICPRESSURE TRANSMITTERASDADJUSTABLE SPEED DRIVER134aREFRIGERANT R134a SENSOR(WALL MOUNTED)CCCOOLING COILBASE MOUNTED PUMPFILTER BANKRETURN AIR FANRFEF EXHAUST AIR FANHCHEATING COILSMOKE CONTROL FANSCHUMIDIFIER DISPERSION GRIDEPELECTRIC/PNEUMATICSWITCH OR RELAYPEPNEUMATIC/ELECTRICSWITCH OR RELAYFFLOW TRANSMITTERPPRESSURE TRANSMITTERELECTRIC/PNEUMATICTRANSDUCERIEELECTRONIC/ELECTRICTRANSDUCERPNEUMATIC CONTROLVALVE (3-WAY)PNEUMATIC CONTROLVALVE (2-WAY)ELECTRIC/ELECTRONICCONTROL VALVE (2-WAY)PNEUMATIC ACTUATORMAIN TEMPERATURECONTROL AIR SOURCEAIN LINE PUMPHRCHEAT RECOVERY COILAIR TERMINAL UNIT WITH FACTORY ATTENUATOR (OPTION 1)VAV-X-XXVAV-X-XXLAB AIR VALVERADIANT CEILING PANELFLOW SWITCHVARIABLE FREQUENCY DRIVEGBGAS BURNERPPRESSURE SWITCHHUMIDIFIERHARSOSMFSFBUTTERFLY CONTROL DAMPERVFDOA OUTSIDE AIRRA RETURN AIRSA SUPPLY AIRCARBON MONOXIDE SENSOR(DUCT MOUNTED)COF.L. FAIL LASTDEWPOINT SENSOR(DUCT MOUNTED)DPCCONDENSATE SENSORSTATIC PRESSURE SENSOR(DUCT MOUNTED)SPCTBI BINARY INPUTBO BINARY OUTPUTAI ANALOG INPUTAO ANALOG OUTPUTBV BINARY VALUEAV ANALOG VALUEHIGH LEVEL SWITCHHILOWLOW LEVEL SWITCHVENTURI AIRFLOW CONTROL VALVETRANSFORMERMOTOR STARTERMSROTATION DETECTORRDSMOKE DETECTORSDMOD MODULATINGELECTRIC TO PNEUMATIC TRANSDUCEREPSPEED COMMANDSCAOMADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE)COMNETWORK COMMUNICATION INTERFACE POINTSIGNALOUTCURRENT SENSORCSSIGNALOUTASIGNAL INAIR INASIGNAL INELECTRIC TO PNEUMATIC SWITCHLINE VOLTAGE THERMOSTATTNITROGEN DIOXIDE SENSORNMOTORSSPACE SENSOR WITH SETPOINT ADJUSTMENTSASSPACE SENSOR WITH OCCUPANCY OVERRIDESSPACE SENSOR WITH VISUAL DISPLAYSSPACE SENSOR WITH FAN ON/OFF SWITCHTROOM TEMPERATURE SENSOR WITH SETPOINT ADJUSTMENTTTTROOM TEMPERATURE SENSOR WITH OCCUPANCY OVERRIDEROOM TEMPERATURE SENSOR WITH VISUAL DISPLAYROOM TEMPERATURE SENSOR WITH FAN ON/OFF SWITCHBINARY INPUT (GENERAL)BIBOBINARY OUTPUT (GENERAL)ANALOG INPUT (GENERAL)ANALOG OUTPUT (GENERAL)AIAOLIQUID IMMERSION TEMPERATURE SENSORTSINGLE POINT SENSORMMOVDFSAOVDFF.O. FAIL OPENRELATIVE HUMIDITY SENSORRHLOW LIMIT TEMPERATURE SWITCHFZCONTROLS SCHEMATIC SYMBOL LISTThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/7/2021 9:29:49 AMC:\Users\nmjacobson\Documents\200311_CorsonFirstFloor_M_Central_R20_nmjacobson.rvt20625.01NMJGeneral Notes,Symbols List &Schedules - HVACGDDSJGM-000100% ConstructionDocumentsCornell UniversityCorson Hall Rm 136-142A LabRenovationIthaca, NYMay 7, 20211. PANEL SIZE = 24 IN X 24 INREMARKS:1SUPPLYSTEEL WHITETITUS MODEL TRITEC1TYPE APPLICATION MATERIAL FINISH MANUFACTURER & MODEL NO. REMARKSREGISTER GRILLE AND DIFFUSER SCHEDULE FH141516MICROSCOPY/MICROINJECTIONE138(E)12x10(E)24x12(E)12x10(E)12x6(E)8"(E)12x12(E)14x6(E)10"(E)10x10(E)10"(E)7"(E)7"(E)12x10(E)12x10(E)8"(E)8x8(E)12x12(E)8"(E)12x10(E)5"(E)12x8(E)10"(E)14x12(E)12x8(E)6"(E)12"(E)8x8(E)8"(E)8"(E)12x10(E)4"(E)6x6(E)8"(E)HWR(E)3/4"(E)3/4"(E)3/4"(E)3/4"(E)SAV-E142(E)SAV-E138(E)SAV-E136(E)EAV-E142-2(E)EAV-E142-1(E)EAV-E138RDDDRDDR(E)GWS(E)GWR(E)CWS(E)CWR(E)8"(E)8"(E)34x16(E)36x16(E)14x12DDR(E)HWSDR(E)12x6(E)12x8(E)3/4"(E)EAV-E142A(E)EAV-E136ANIMAL ROOME136PREPE142AWET LABE142E100CA(E)8"(E)12"(E)5"333331212"8"(E)SAV-E142"(E)32512"117510"117510"118010"132510"(E)1908"(E)1958"(E)1958"(E)38012"11358"(E)32512"(E)18584444444x22 10(E)115TYP=3x22 10(E)1154455x22 10(E)1104x22 10(E)1104666677FH141516(E)12x6(E)12x10(E)12"(E)24x12(E)12x10(E)12x6(E)8"(E)12x12(E)14x6(E)10"(E)10x10(E)10"(E)2"(E)2"(E)7"(E)5"(E)7"(E)12x10(E)12x10(E)12x8(E)8"(E)8x8(E)12x12(E)8"(E)12x10(E)5"(E)12x8(E)8"(E)10"(E)14x12(E)12x8(E)6"(E)12"(E)8x8(E)8"(E)8"(E)12x10(E)4"(E)6x6(E)8"(E)HWR(E)3/4"(E)3/4"(E)3/4"(E)3/4"(E)3/4"(E)SAV-E142(E)SAV-E138(E)SAV-E136(E)SAV-E142(E)EAV-E142-2(E)EAV-E142-1(E)EAV-E142A(E)EAV-E136(E)EAV-E138RDDDRDDR(E)GWS(E)GWR(E)CWS(E)CWR(E)8"(E)8"(E)34x16(E)36x16(E)14x12DDR(E)HWSDR444441132MICROSCOPY/MICROINJECTIONE138PREPE142AWET LABE142E100CAANIMAL ROOME13655These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/7/2021 9:29:50 AMC:\Users\nmjacobson\Documents\200311_CorsonFirstFloor_M_Central_R20_nmjacobson.rvt20625.01NMJFirst Floor Plans -HVACGDDSJGM-101100% ConstructionDocumentsCornell UniversityCorson Hall Rm 136-142A LabRenovationIthaca, NYMay 7, 20211/4" = 1'-0"2First Floor Plan - HVAC1/4" = 1'-0"1First Floor Plan - HVAC - DemolitionDEMOLITION NOTES1 DISCONNECT AND REMOVE EXISTING DUCTWORK AND ACCESSORIES.2 DISCONNECT AND REMOVE EXISTING STAINLESS DUCTWORK FROM FUME HOOD.FLEXIBLE DUCTWORK TIED INTO FUME HOOD SHALL REMAIN.3 DISCONNECT AND REMOVE EXISTING DUCTWORK AND ACCESSORIES FROM CHEMICALCABINET.4 DISCONNECT AND REMOVE EXISTING DIFFUSER. PREP FOR CONNECTION TO NEW.REMOVE DUCTWORK AS REQUIRED.5 TEMPORARILY SUPPORT GRILLE AS REQUIRED FOR CEILING REPLACEMENT.DRAWING NOTES1 TIE DUCTWORK INTO EXISTING. PROVIDE ALL DUCTWORK MODIFICATIONS AS REQUIREDTO MAKE THE CONNECTION.2 AFTER RELOCATION OF THE FUME HOOD, TIE NEW STAINLESS STEEL DUCTWORK INTOTHE EXISTING FLEXIBLE DUCTWORK CONNECTED TO THE FUME HOOD.3 TIE EXISTING DUCTWORK INTO NEW DIFFUSER. TRANSITION AS REQUIRED TO MAKE THECONNECTION. ALIGN DIFFUSER WITH NEW CEILING GRID.4 REBALANCE DIFFUSER TO AIRFLOW NOTED.5 PROVIDE ALARM FOR FREEZER AND TIE INTO BMS.6 RECOMMISSION AND RE-CALIBRATE EXISTING CONTROLS FOR THIS SPACE. REFER TOCONTROL SCHEMATIC AND SYSTEM SUMMARIES FOR FUTHER INFORMATION.7 ALIGN EXISTING GRILLE WITH NEW CEILING GRID.N FUME HOODFUME HOODFUME HOOD WITH WORK SURFACEAT NON-ADA HEIGHT, 36" A.F.F.FUME HOOD WITH WORK SURFACEAT ADA HEIGHT, 30" A.F.F.DETAIL NOTES:1 ROUND FLEXIBLE EXHAUST DUCT CONNECTION, SHOWING FULLY COMPRESSEDTO ACCOMMODATE 36" WORK SURFACE HEIGHT.2 ROUND FLEXIBLE EXHAUST DUCT CONNECTION, SHOWING FULLY EXTENDEDTO ACCOMMODATE 30" WORK SURFACE HEIGHT.3 FLEXIBLE EXHAUST DUCT SHALL BE BLO-R-VAC, 12-IN ROUND NOMINALDIMENSION, HOSE IS COMPRESSIBLE TO 60% OF ITS LENGTH, COLOR IS BLUE, SUITABLE FOR CHEMICAL FUME EXTRACTION.DUCT COLLAR (TYP.)LAB EXHAUST DUCT (TYP.)2 31 3FLEX DUCTDETAIL NOTES:A.DUCT AND DIFFUSER SIZE AS SHOWN ON DRAWINGS.B.FLEX DUCT MAXIMUM LENGTH IS 24" WITH A 6" MAXIMUM OFFSET.C.LOCATE VOLUME DAMPER AT BRANCH TAKE-OFF, MIN 6'-0" FROM DIFFUSER.DIFFUSER WITH MANUFACTURERSSTANDARD PLENUMSUPPLY AIRDUCTMINIMUM 6'-0"FROM DIFFUSERDIFFUSER WITH MANUFACTURERSSTANDARD PLENUMSHEETMETAL ELBOW, SUPPORTFROM BUILDING STRUCTUREINLET SIZE AS INDICATED ON DRAWINGSMINIMUM 6'-0"FROM DIFFUSERThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/7/2021 9:29:50 AMC:\Users\nmjacobson\Documents\200311_CorsonFirstFloor_M_Central_R20_nmjacobson.rvt20625.01NMJDetails - HVACGDDSJGM-200100% ConstructionDocumentsCornell UniversityCorson Hall Rm 136-142A LabRenovationIthaca, NYMay 7, 2021NOT TO SCALE1ADA Fume Hood Installation DetailNOT TO SCALE2Typical High Volume, Low Velocity Diffuser Installation Detail POINT SCHEDULEMISCELLANEOUS ELECTRICALHARDWARE POINTSSOFTWARE POINTSSHOWN ON GRAPHICNOTESBIBO AI AOAV BVSCH TRENDALARMBACSEMCSDESCRIPTIONFREEZER STATUSXXHIGH TEMPERATUREX(REFER TO PLANS FOR QTY.)LAB AIRFLOW SCHEDULEROOM NUMBER DESCRIPTIONROOM DIMENSIONSCODE MINIMUM VENTILATIONEXHAUST AIRSUPPLY AIRXFER(NOTE 1) AREAHEIGHTNYS NYS EXHAUST VALVEMAX COOLINGOCCUPIED UNOCCUPIEDSUPPLY VALVEMAX OCCUPIED UNOCCUPIEDALLOUTDOOR EXHAUSTPOINTSIZEPOINT SIZECOOLINGMODESAIRFLOW AIRFLOW(SF)(FT) (CFM)(ACH) (CFM) (ACH)(CFM) (ACH) (CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (CFM)E136 COOLING LAB1898.6 64 2.4 189 7.0(E)EAV-E1368" 680 25 1957 195 7 (E)SAV-E136 7" 5809595-100E138 COOLING LAB 1328.5 54 2.9 132 7.1 (E)EAV-E138 6" 380 20 120 6 60 3 (E)SAV-E138 5" 320600-60E142A COOLING LAB 688.5 42 4.4 68 7.1 (E)EAV-E142A 5" 185 19 100 10 50 5 (E)SAV-E142A 4" 135500-50NOTES1.THIS REPRESENTS A LABORATORY WHERE THE TEMPERATURE REQUIREMENTS (COOLING) OF THE LAB OVERRIDE THE REQUIRED AIR CHANGES.LAB AIRFLOW SCHEDULEROOM NUMBER DESCRIPTION ROOM DIMENSIONS CODE MINIMUM VENTILATIONEXHAUST AIRSUPPLY AIRXFER(NOTE 1) AREA HEIGHTNYS NYS EXHAUST VALVEOCCUPIEDOCCUPIED UNOCCUPIED UNOCCUPIED UNOCCUPIED SUPPLY VALVE OCCUPIEDOCC UNOCC UNOCC UNOCC ALLOUTDOOR EXHAUSTPOINT SIZESASH OPENSASH CLOSED SASH FULL SASH OPEN SASH CLOSED POINT SIZE SASH OPEN SASH SASH SASH SASH MODESAIRFLOW AIRFLOW(NOTE 2)(NOTE 3) (NOTE 4)CLOSED(NOTE 2) CLOSEDFULL OPEN CLOSED100 FPM80 FPM100 FPM65 FPM100 FPM 80 FPM(SF)(FT) (CFM) (ACH) (CFM) (ACH)(CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM)E142VAV LAB5978.5 157 1.9 597 7.1(E)EAV-E142-1 8" 630850571806630741052805 (E)SAV-E142 10" 530 405 355 480 260 240-150(E)EAV-E142-2 7" 505032500110TOTAL680555505630410390NOTES1.THIS REPRESENTS A LABORATORY WHERE THE REQUIREMENTS OF THE FUME HOODS EXCEEDS THE MINIMUM REQUIRED AIR CHANGE RATES ESTABLISHED FOR THE LABORATORY.2.OCCUPIED SASH OPEN MODE: FUME HOOD EXHAUST AIR FLOW REPRESENTS A 80-100 FPM FACE VELOCITY AT 18-INCH SASH HEIGHT. FUME HOOD AIR VALVE BASIS OF DESIGN WILL BE 100 FPM @ 18-INCHES SASH HEIGHT. FINAL AIRFLOW SETPOINT ESTABLISHED DURING HOOD CERTIFICATION.3.UNOCCUPIED SASH FULL MODE: FUME HOOD EXHAUST AIRFLOW REPRESENTS A 100 FPM FACE VELOCITY AT 18-INCH SASH HEIGHT, SASH IS ABOVE 18-INCHES. FUME HOOD EXHAUST SHALL NOT INDEX TO UNOCCUPIED MODE.4.UNOCCUPIED SASH OPEN MODE: FUME HOOD EXHAUST REPRESENTS AT 65 FPM FACE VELOCITY, SASH IS AT OR BELOW 18-INCHES. FUME HOOD EXHAUST SHALL INDEX TO UNOCCUPIED MODE. These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©387 East Main Street Rochester NY 14604585 232 8300 | rochester@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions5/7/2021 9:29:51 AMC:\Users\nmjacobson\Documents\200311_CorsonFirstFloor_M_Central_R20_nmjacobson.rvt20625.01GDDControl Schematics &System SummariesGDDNMJM-300100% ConstructionDocumentsCornell UniversityCorson Hall Rm 136-142A LabRenovationIthaca, NYMay 7, 2021NOT TO SCALE3Miscellaneous Electrical Control Schematic and System SummaryNOT TO SCALE2Typical Lab with Supply Air VAV & General Exhaust VAV Control Schematic and System SummaryNOT TO SCALE1LAB E142 with Supply Air VAV, Fume Hood Exhaust Air VAV & General Exhaust Air VAV Control Schematic and System Summary BASIC MATERIALS AND METHODS 3 HEAVY SOLID IS NEW, EXISTING ELECTRICAL WIRING, EQUIPMENT OR DEVICE, SOLID LIGHT IS EXISTING TO REMAIN , EXISTING ELECTRICAL WIRING, EQUIPMENT OR DEVICE, DASED LIGHT IS EXISTING TO BE REMOVED OR RELOCATED , REFERENCE TO DRAWING NOTE OS J TOGGLE SWITCH, VOLTAGE AS INDICATED ON FIXTURE SCHEDULE, SUBSCRIPTS INDICATE TYPE: 2 - TWO POLE SWITCH 3 - THREE WAY SWITCH 4 - FOUR WAY SWITCH M - MONENTARY CONTACT K - KEY OPERATED a,b,c - SWITCHING DESIGNATIONS NUMBER OF LETTERS EQUALS NO. OF GANGED SWITCHES V - VACANCY SENSOR VD - VACANCY SENSOR, DIMMER SWITCH VDS - VACANCY SENSOR, DUAL SWITCHED WP - WEATHERPROOF QUAD RECEPTACLE 20 AMP, 125 VOLT DUPLEX RECEPTACLE, 20 AMP, 125 VOLT SUBSCRIPTS INDICATE TYPE: GFI - GROUND FAULT INTERUPT OC - OVER COUNTER UC - UNDER THE COUNTER WP - WEATHER PROOF TP - TAMPER PROOF USB - INTEGRAL USB CHARGER 'X' - SPECIFIC LETTER DENOTES SPECIFIC PIECE OF EQUIPMENT ON ARCHITECT PLANS. SPECIAL PURPOSE RECEPTACLE. PROVIDE PROPER VOLTAGE, CLASS, CURRENT RATING AND NEMA CONFIGURATION AS REQUIRED BY BRANCH CIRCUIT AND/OR MATCH CAP ON EQUIPMENT BEING FURNISHED BY OTHERS. PROVIDE CORD AND CAP. SUBSCRIPTS INDICATE TYPE: J CEILING MOUNTED OCCUPANCY SENSOR JUNCTION BOX 3a,b,c 3 REFERENCE TO DEMOLITION NOTE EXISTING TO REMAIN - INDICATES EXISTING ITEM SHALL REMAIN. MAINTAIN EXISTING ELECTRICAL CONNECTIONS UNLESS OTHERWISE NOTED. (E) EXISTING TO BE RELOCATED - INDICATES EXISTING ITEM SHALL BE RELOCATED. DISCONNECT AND REMOVE, REINSTALL AT NEW LOCATION AND RECONNECT ITEM AS REQUIRED. (ER) COMMUNICATIONS EXISTING COMMUNICATIONS OUTLET TEL/DATA DROP: 4"x4"x2.50" BOX WITH A 1-GANG MUD RING & FACEPLATE WITH DUPLEX DESIGN. 1" CONDUIT EXTENDED TO NEAREST CABLE TRAY IN CORRIDOR ( UNLESS OTHERWISE NOTED) FOR DATA/VOICE. TERMINATE CONDUIT AT J HOOK IN CORRIDOR WITH CONDUIT BUSHING. PULL (2 OR 4) CAT 6 CABLE, TERMINATE AT PATCH PANEL IN BDF. REFER TO DRAWINGS FOR QUANTITY. W - SINGLE GANG BACK BOX WITH MUD RING AND 1" CONDUIT EXTENDED TO NEAREST CABLE TRAY IN CORRIDOR (UNLESS OTHERWISE NOTED) FOR DATA/VOICE. WALL MOUNT AT 46"AFF. PROVIDE (1) CAT 6 CABLE TO BDF. DDC - SINGLE GANG BOX WITH BLANK COVER PLATE. PROVIDE 3/4"C STUBBED TO ACCESSIBLE CEILING SPACE ABOVE. DDC ALARM WIRING BY DIV 23. C - CAMERA, COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS. TV - COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS. WAP H F F F S FIRE ALARM RATE-OF-RISE HEAT DETECTOR ALARM SIGNAL, STROBE ALARM SIGNAL, SPEAKER AND STROBE MANUAL PULL STATION SMOKE DETECTOR 208Y/120 VOLT PANELBOARD. COMPLETE ELECTRICAL CONNECTION TO EQUIPMENT A d A d CEILING MOUNTED EXIT LUMINAIRE WALL MOUNTED EXIT LUMINAIRE CEILING MOUNTED LUMINARIE. UPPERCASE LETTERS INDICATE FIXTURE TYPE ON LUMINAIRE SCHEDULE, LOWER CASE LETTER INDICATE LIGHTING ZONE WALL MOUNTED LUMINARIE. UPPERCASE LETTERS INDICATE FIXTURE TYPE ON LUMINAIRE SCHEDULE, LOWER CASE LETTER INDICATE LIGHTING ZONE LUMINAIRE CONNECTED TO LIFE SAFETY EMERGENCY POWER WALL MOUNTED EMERGENCY LUMINAIRE WITH BATTERY PACK POWER DISTRIBUTION AND CONTROL 480Y/277 VOLT PANELBOARD. LUMINAIRES CEILING RECEPTACLE 4'-0" EXIT LIGHT SWITCH 2. MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST BLOCK OR BRICK COURSING. THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGS. 1. DETAIL NOTES: 1'-6" DIVIDED SURFACE RACEWA Y HORN/LIGHT LENS ON TOP FINISHED FLOOR PULLSTATION COORDINATE EXACT MOUNTING HEIGHT WITH ARCHITECT. ENTIRE LENS SHALL BE MINIMUM 80" AFF AND NOT GREATER THAN 96" AFF. WHERE NOT PERMITTED BY CEILING HEIGHT DEVICE SHALL BE MOUNTED WITHIN 6" OF THE CEILING. 4'-0" EXIT SIGNS CENTERED ABOVE DOOR COMBINATION POWER/COMMUNICATION SURFACE RACEWAY WITH DEVICES AS INDICATED. WIREMOLD G4000. RACEWAY SHALL BE MOUNTED "OVER COUNTER" UNLESS OTHERWISE NOTED. WAP - WIRELESS ACCESS POINT WALL MOUNT AT 90"AFF 4"x4"x2.25" BOX WITH DOUBLE GANG PLASTER RING. 1" EMT CONDUIT EXTENDED TO NEAREST CABLE TRAY IN CORRIDOR (UNLESS OTHERWISE NOTED). PROVIDE TWO (2) CAT 6A CABLES. TERMINATE IN BDF AND 6-8" PIGTAIL WITHOUT FACEPLATE. G. H. I. WHEN EXISTING CONSTRUCTION, WHICH IS TO REMAIN, IS DAMAGED DURING THE COURSE OF DEMOLITION AS A RESULT OF THE CONTRACTOR'S WORK, IT SHALL BE REPAIRED AND/OR REPLACED WITH SIMILAR OR LIKE MATERIALS, AS MUCH AS POSSIBLE, SUBJECT TO THE OWNERS APPROVAL. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND REPLACEMENT OF EXISTING CONSTRUCTION IN THE WAY OF NEW WORK. PROTECT BUILDING AND FURNISHINGS FROM DAMAGE. COORDINATE PHASING OF WORK WITH OWNER'S REPRESENTATIVE. COORDINATE ALL SHUTDOWNS WITH UNIVERSITY PRIOR TO DEMOLITION. ALL FIRE ALARM SHUTDOWNS SHALL BE SCHEDULED THROUGH CUSTOMER SERVICE WITH AT LEAST 24 HOURS NOTICE BEFORE WORK IS TO BE STARTED. EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION DOCUMENTS WHEN AVAILABLE AND ARE NOT GARAUNTEED. PRIOR TO SUBMITTING BID, VISIT SITE AND IDENTIFY EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE DEMOLITION WORK. NO COMPENSATION WILL BE GRANTED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY EXPERIENCED OBSERVERS. THIS CONTRACTOR SHALL PARTICIPATE IN SURVEY OF THE EXISTING ELECTRICAL SYSTEMS. THE CONTRACTOR SHALL DISCONNECT AND CAP ALL SERVICE LINES TO BE DISCONNECTED FOR THOSE SERVICES WHICH NORMALLY ARE INCLUDED IN HIS FIELD OF WORK. PARTICULAR CARE SHALL BE TAKEN TO AVOID CREATING HAZARD OR CAUSING DISRUPTION IN ADJOINING AREAS. NOT ALL DEVICES TERMINATIONS, JUNCTION BOXES AND WIRING HAVE BEEN SHOWN. REFER TO PLUMBING CONTRACT DRAWINGS AND SPECIFICATIONS FOR EXACT QUANTITIES AND LOCATIONS OF ALL PLUMBING EQUIPMENT BEING ABANDONED OR REMOVED, WHICH WILL REQUIRE DE-ENERGIZATION, REMOVAL AND BLANK-OFF BY THE CONTRACTOR. EXISTING FIRE ALARM SYSTEM SHALL BE KEPT OPERATIONAL DURING THE CONSTRUCTION PERIOD THE BUILDING UNDER RENOVATION MAY BE DISCONNECTED FROM SERVICE DURING THE HOURS THE CONTRACTOR IS WORKING, AT THE DISCRETION OF THE FIRE DEPARTMENT AND THE OWNER'S REPRESENTATIVE, BUT MUST BE OKACED BACK ON LINE DURING OTHER PERIODS. APPROVAL TO BE IN WRITING. THE EXISTING ELECTRICAL EQUIPMENT AND DEVICES WITHIN DEMOLITION AREA SHALL BE DEMOLISHED ALONG WITH ALL FEEDERS AND CONDUITS BACK TO POINT OF SOURCE UNLESS OTHERWISE NOTED. ALL ITEMS SHOWN ON THE DEMOLITION DRAWINGS SHALL BE DISCONNECTED AND REMOVED UNLESS NOTED OTHERWISE. WALLBOXES, BACKBOXES AND CONDUIT SHALL BE REUSED AS DETERMINED BY CONTRACTOR. ALL UNUSED CONDUITS SHALL BE REMOVED. DISCONNECT AND MAKE SAFE ANY EQUIPMENT TO BE REMOVED BY OTHERS. COORDINATE REMOVAL OF EQUIPMENT WITH OTHER TRADES PRIOR TO DEMOLITION. MAINTAIN AND RESTORE, IF INTERRUPTED BY REMOVALS OR IN PATH OF NEW CONSTRUCTION, ALL CIRCUITS, CONDUITS AND FEEDERS PASSING THROUGH AND SERVING UNDISTURBED AREAS (SHOWN OR NOT SHOWN). ALL EXISTING CONDUITS STUBBED THROUGH FLOOR SERVING ITEMS TO BE REMOVED AND NOT SHOWN OR REQUIRED TO BE REUSED, SHALL BE CUT OFF FLUSH WITH SLAB LEVEL WITH CONCRETE. IN ANY AREA REQUIRING THE PERFORMANCE OF ANY TRADE'S WORK WORK, THIS CONTRACTOR SHALL CAREFULLY REMOVE AND STORE ANY OR ALL ELECTRICAL ITEMS IN PATH OF WORK, REINSTALLING AND RECONNECTING SAME AS REQUIRED, IN ACCORDANCE WITH THE PLANS AND/OR AS DIRECTED AFTER COMPLETION OF OTHER TRADE'S WORK IN THAT AREA. DISCONNECT, MAKE SAFE AND REMOVE ALL TEMPORARY AND ABANDONED WIRE WITHIN THE SPACE. BRANCH CIRCUIT WIRING TO DEVICES IN AREAS OF DEMOLITION SHALL BE DISCONNECTED, MADE SAFE AND REMOVED COMPLETELY BACK TO THE PANELBOARD. THE CONTRATOR SHALL NOT ABANDON BRANCH CIRCUIT WIRING TO ANY AREAS WICH ARE TO REMAIN BUT ARE AFFECTED BY THE DEMOLITION OR NEW CONSTRUCTION. DISCONNECT AND REMOVE PANEL, FEEDERS AND BRANCH CIRCUITS BACK TO POINT OF SOURCE PRIOR TO THE START OF DEMOLITION, CONTRACTOR SHALL FIELD VERIFY ALL BRANCH CIRCUITS AND MAINTAIN THOSE CIRCUITS THAT EXTEND OUTSIDE OF THE SCOPE OF WORK. AFTER RENOVATING EXISTING ELECTRICAL WORK, THE CONTRACTOR SHALL INSURE THAT ALL REMAINING AND NEW EQUIPMENT WILL OPERATE PROPERLY. PROVIDE TEMPORARY HEAT DETECTORS IN AREAS WHERE SPRINKLERS ARE REMOVED FROM SERVICE DURING CONSTRUCTION. COORDINATE WITH FIRE PROTECTION CONTRACTOR. REFER TO MECHANICAL CONTRACT DRAWINGS AND SPECIFICATIONS FOR EXACT QUANTITIES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT BEING ABANDONED OR REMOVED, WHICH WILL REQUIRE DE-ENERGIZATION, REMOVAL AND BLANK-OFF BY THE CONTRACTOR. GENERAL DEMOLITION NOTES:(APPLY TO ALL DRAWINGS): A. B. C. D. E. F. G. H. I. SLEEVE AND SEAL ALL WALL AND FLOOR PENETRATIONS. PROVIDE FIRESTOPPING FOR ALL FIRE-RATED PENETRATIONS. UTILIZE REMOVABLE FIRESTOPPING MATERIAL AT CABLE TRAY PENETRATIONS. PROVIDE ACOUSTICAL SEALANT FOR ALL NON RATED PENETRATIONS. ALL FIRE RATINGS SHALL BE MAINTAINED. MAINTAIN SERVICE CLEARANCES OF ALL EQUIPMENT. COORDINATE EXACT LOCATION OF ALL CONDUIT ROUTES, EQUIPMENT AND DEVICES WITH EXISTING CONDITIONS PRIOR TO CONSTRUCTION. MINIMUM CONDUIT SIZE SHALL BE 3/4" FOR POWER CIRCUITS UOI. PROVIDE NYLON PULLSTRING IN ALL EMPTY CONDUITS. FIRE ALARM SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80 INCHES AND NOT GREATER THAN 96 INCHES ABOVE THE FINISHED FLOOR. CIRCUITING TO DEVICES/EQUIPMENT SHALL BE 2-#12AWG & 1-#12EG (MULTIPLE HOME RUNS IN SAME CONDUIT MAY SHARE SAME EQUIPMENT GROUND) FOR EACH 20 AMPERE CIRCUIT UNLESS OTHERWISE NOTED. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRALS (CIRCUITS SHALL NOT SHARE NEUTRALS). PROVIDE CONDUIT/WIRING (CIRCUITING) AND REQUIRED EQUIPMENT CONNECTIONS TO ALL DEVICES/EQUIPMENT. CONNECT TO CIRCUIT(S) AS INDICATED. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE REFERENCE STANDARD EDITION OF NFPA CODES, AS CITED BY THE FIRE CODE OF NEW YORK STATE, BUILDING CODE OF NEW YORK STATE AND CORNELL UNIVERSITY DESIGN STANDARDS. ALL CONDUITS AND SUPPORTS SHALL BE AS TIGHT TO DECK AS POSSIBLE. PROVIDE PULLBOX FOR EVERY 180 DEGREE OF BENDS FOR TEL/DATA AND 360 DEGREES OF BENDS FOR POWER CONDUITS. ALL ELECTRICAL DEVICES (RECEPTACLES, SWITCHES, FIRE ALARM, ETC.) SHALL BE ALIGNED HORIZONTALLY AND VERTICALLY. CONTRACTOR TO SCHEDULE AND COORDINATE PROJJECT WALKTHROUGH WITH ARCHITECT AND ENGINEER PRIOR TO COMMENCEMENT OF ANY DEVICE ROUGH-IN FOR FINALIZATION OF ALIGNMENTS. REFER TO EAV SERIES DRAWINGS FOR ADDITIONAL ELECTRICAL WORK. ALL EXISTING DEVICES CIRCUITED TO PANELS BEING RENAMED SHALL BE PROVIDED WITH UPDATED LABELS. PROVIDE ALL PATHWAYS AND BACK BOXES AS CALLED FOR ON AV DRAWINGS PROVIDED BY ANOTHER CONSULTANT. COORDINATE IT SERVICE CHANGES OR DISRUPTIONS IN SERVICE WITH CIT OPERATIONS AT 255-5500. GENERAL NOTES:(APPLY TO ALL DRAWINGS): A. B. C. D. E. F. J. K. L. M. N. J. K. L. M. N. FCU FAN COIL UNIT FIRE ALARM CONTROL PANEL FIRE ALARM TERMINAL CABINET CONT.CONTACTOR F.A.T.C. F.A.C.P. ELECTRIC WATER COOLER DISTRIBUTION PANEL GROUND FAULT CIRCUIT INTERRUPTER GENERAL CONTRACTOR ELECTRICAL CONTRACTOR HEATING, VENTILATING AND AIR CONDITIONING F.A.FIRE ALARM H.V.A.C. G.C. E.C. BSMT.BASEMENT CLG. EA. CONTR. GEN. CEILING EACH GENERATOR A.AMPERE DN. EXIST. AUTO. DOWN EXISTING AUTOMATIC DP EMERG. ELEC. G.F.C.I. ELECTRIC EMERGENCY HORSEPOWER GALVANIZED RIGID STEEL GND.GROUND GRS. ABBREV. ABBREVIATIONS C BKR. HP. CAMERA BREAKER DESCRIPTION FZ (3)FIRE ZONE (3) ABOVE FINISHED FLOORA.F.F. EM.EMERGENCY CONTRACTOR A.F.G.ABOVE FINISHED GRADE EWC MOUNTED UNDER COUNTER HEIGHT TV TELEVISION WEATHERPROOF REFRIGERATOR SPECIFICATION MOUNTED OVER COUNTER HEIGHT PLUMBING CONTRACTOR TELEPHONE BACKBOARD TELEPHONE TERMINAL CABINET T.B.B. MICRO T.T.C. MICROWAVE P.C. REFRIG. TYP.TYPICAL SPEC. P. SP.SPACE POLE NL NIGHT LIGHT V.VOLT SW. SWITCH MAIN CIRCUIT BREAKER MAIN LUG ONLY P = POLE A = AMPERE UNDERWRITER'S LABORATORY LTG. U.L. 4 W. KW. LIGHTING KILOWATT WIRE M.L.O. 3P.15A. PH. M.C.B. PHASE PNL.PANEL PV POWER VENTILATOR WP OC UC UV WG VP EF EHP CUH UNIT VENTILATOR WIRE GUARD FRACTIONAL HORSEPOWER EXHAUST FAN CABINET UNIT HEATER VANDAL PROOF POLYCARBONATE GUARD ABBREVIATIONS ABBREV. DESCRIPTION WAP WIRELESS ACCESS POINT O. UH UNIT HEATER P. O. P. Q. AAD AUTOMATIC AIR DAMPER These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions5/7/2021 11:27:13 AMC:\Users\crspall\Documents\200311_CorsonFirstFloor_E_Central_R20_crspall.rvt20625.01 MRG Electrical Symbols List & General Notes GDD CRS E-000 100% Construction Documents Cornell University Corson Hall Rm 136-142A Lab Renovation Ithaca, NY May 7, 2021 E131A J JJJ F F F J J F F FWAPWAP S S S S S F F H 14 15 16 17 CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) LCE1-3 EPLE1-2 DPLE1-2(E) PLE1-2A(E) (E) (ER)(ER)(ER) (E) (E) E100CA (E) (E) F H 14 15 16 17 WET LAB E142 PREP E142A ANIMAL ROOM E136 MICROSCOPY/ MICROINJECTION E138 EPLE1-2 DPLE1-2(E) PLE1-2A(E) LCE1-3 (E) CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) CLG (E) (E) (E) E E E(ER) (ER) (ER)GFI GFI DDC 1 1 E100CA GFI 2 A EM LCE1-3, 2 LCE1-3, 6 (E) LCE1-3, 8 LCE1-3, 10 LCE1-3, 1 LCE1-3, 3 LCE1-3, 5 LCE1-3, 7,9 4 4 15 15 11 7 2 13 13 13 EPLE1-2, 6,8 (E) (E) 4 4 5 5 5 5 5 5 5 5 5 5 5 4 B EM (E) EPLE1-3 EPLE1-3, 1 LCE1-3, 11 6 NEMA 6-15 13 5 5 5 GENERAL NOTES: A. DISCONNECT AND SALVAGE FUME HOOD CONNECTIONS TO ACCOMODATE MINOR RELOCATION. B. ALL DEMOLISHED CIRCUITING SHOWN SHALL BE BROUGHT BACK TO SOURCE AND MAKE EXISTING BREAKER SPARE. C. ALL DEMOLISHED DATA CABLING IN THE CONSTRUCTION AREA SHALL BE REMOVED BACK TO SOURCE. D. PRIOR TO CONSTRUCTION THE PROJECT MANAGER AND/OR THE TELECOM COORDINATOR FOR THE BUILDING NEEDS TO SEND A TICKET IN TO NCS-OS@CORNELL.EDU TO HAVE ALL ACTIVE CIRCUITS WITHIN THE CONSTRUCTION AREA DISCONNECTED. ELECTRICAL CONTRACTOR SHALL COORDINATE THIS WITH PROJECT MANAGER. GENERAL NOTES: A. ALL EM RECEPTACLE CIRCUITS SHALL BE FED FROM EXISTING PANEL EPLE1-2, CIRCUIT NUMBER AS INDICATED. B. ALL NEW NORMAL POWER CONNECTIONS SHALL COME FROM PANEL PLE1-2A, CIRCUIT NUMBER AS INDICATED. UNLESS OTHERWISE NOTED. C. REFER TO ARCHITECT EQUIPMENT SCHEDULE FOR ALL POWER CONNECTIONS WITH ASSOCIATED 'X' ON PLANS. D. CONTRACTOR SHALL CONNECT THE NEW FIRE ALARM DEVICES INTO THE EXISTING FIRE ALARM SYSTEM. E. PROVIDE DUAL CHANNEL RACEWAY AS SHOWN. SHALL BE INSTALLED OVER COUNTER. ALL RECEPTACLES WITHIN 6' OF SINK SHALL BE GFI TYPE. F. DATA DROP DDC -CONTRACTOR SHALL ONLY PROVIDE PATHWAY TO ABOVE FINISHED CEILING FOR LOW VOLTAGE WIRING INTO BUILDING MANAGEMENT SYSTEM. G. TEL/DATA CLOSET IS LOCATED APPROXIMATELY 125' WEST FROM COLUMN NUMBER 14 IN ROOM A202. CONTRACTOR SHALL PROVIDE 1" CONDUIT FOR NEW TEL/DATA CABLE FROM TEL/DATA CLOSET IF EXISTING ABOVE CEILING CONDUIT CANNOT FIT NEW CABLING . ROUTE CONDUIT ABOVE CEILING IN LINE WITH EXISTING TEL/DATA CONDUIT. H. FACP IS LOCATED IN ROOM A102. EXISTING FACP IS HONEYWELL E3 SERIES. I. NEW FEED FOR SMOKE DETECTORS SHALL BE REQUIRED FROM FACP FOR ZONE SYSTEM. DRAWING NOTES: 1. POWER AND DATA SHALL BE FED FROM THE CEILING THROUGH THE CHASE NEAR THE SINK AND DOWN INTO THE DUAL CHANNEL RACEWAY ON THE CASEWORK. 2. EQUIPMENT CONNECTION FOR GAS SHUTOFF CONTROL PANEL 120V POWER SHALL COME FROM PANEL LCE1-3, CIRCUIT # 3. 20A-1P BREAKER AND (3)#12AWG & (1)#12 EG IN 3/4" C. FINAL LOCATION TO BE DETERMINED IN FIELD WITH PLUMBING CONTRACTOR. 3. RECONNECT FUME HOOD AND EXTEND FEEDERS AS NECESSARY TO MAKE PROPER CONNECTION. 4. QUAD DATA PORT SHALL BE UTILIZED. 5. DUPLEX DATA PORT SHALL BE UTILIZED. 6. CONTRACTOR SHALL STAGGER CIRCUITS EVERY OTHER RECEPTACLE IN THIS WIREMOLD. These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions5/7/2021 3:30:08 PMC:\Users\cmdoktor\Documents\200311_CorsonFirstFloor_E_Central_R20_cmdoktor.rvt20625.01 MRG Partial First Floor Plan - Power GDD CRS E-100 100% Construction Documents Cornell University Corson Hall Rm 136-142A Lab Renovation Ithaca, NY May 7, 2021 1/4" = 1'-0"1 Partial First Floor Plan - Power Demo 1/4" = 1'-0"2 Partial First Floor Plan - Power N E131A E146 OS OS OS OS OS OS OS OS E141 OS OS 334 3333 OS OS OS OS F H 14 15 16 17 (E) (E) (E) (E)(E) (E) (E) (E) (E) (E) (E) (E) (ER) (ER)(E) 1 E100CA 2 2 2 F H 14 15 16 17 WET LAB E142 PREP E142A ANIMAL ROOM E136 MICROSCOPY/ MICROINJECTION E138 (E) (E) (E) (E) (E) (E) (E) (E) (E) (E) (E) (E) (E) (ER) 1 E100CA (ER) X1EM EM EM 2 2 2 2 2 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 GENERAL NOTES: A. CONTRACTOR SHALL REUSE AND EXTEND SALVAGED CIRCUITING TO LIGHTING FIXTURES AS REQUIRED FOR RECONNECTION. B. CONTRACTOR SHALL TIE IN NEW EXIT SIGN CIRCUIT IN ROOM E136 INTO EXISTING EXIT SIGN LIGHTING CIRCUIT IN ROOM E142. PROVIDE (2)#12AWG & (1)#12EG IN 3/4" C. C. EM BATTERY PACKS SHALL BE CONNECTED TO EXISTING LIGHTING CIRCUIT AHEAD OF ANY CONTROLS. D. NEW AUXILLARY CONTACTS SHALL BE PROVIDED IN ALL EXISTING TO REMAIN OCCUPANCY SENSORS FOR HVAC CONTROLS AS REQUIRED. COORDINATE WITH HVAC CONTRACTOR. DEMOLITION NOTES: 1. LIGHT SWITCHING DEVICES SHALL BE REMOVED. LIGHTING FIXTURE AND OCCUPANCY SENSOR CONFIGURATION SHALL BE DISCONNECTED FOR CHANGES IN ZONES IN NEW WORK PHASE. CONTRACTOR SHALL SALVAGE ALL LIGHTING CIRCUITS FOR REUSE IN NEW WORK PHASE. 2. RELOCATE EXISTING LIGHT SWITCHING CONTROLS TO NEW LOCATIONS AS REQUIRED. REUSE, REWORK AND EXTEND EXISTING WIRE AS REQUIRED. DRAWING NOTES: 1. ALL LIGHTS IN E142 SHALL BE ON A SINGLE SWITCH LEG ZONE A. LIGHTS SHALL BE CONTROLLED VIA THE (3) SWITCHES IN THE ROOM AND ALL BE OPERABLE VIA EITHER SWITCH. 2. NEW SWITCH CONTROLS SHALL CONTROL EXISTING LIGHTS IN THIS ROOM. These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions5/7/2021 11:27:14 AMC:\Users\crspall\Documents\200311_CorsonFirstFloor_E_Central_R20_crspall.rvt20625.01 MRG Partial First Floor Plan - Lighting GDD CRS E-101 100% Construction Documents Cornell University Corson Hall Rm 136-142A Lab Renovation Ithaca, NY May 7, 2021 1/4" = 1'-0"1 Partial First Floor Plan - Lighting Demo 1/4" = 1'-0"2 Partial First Floor Plan - Lighting N BRANCH BREAKER NUMBER TYPICAL BLNL5-17 GENERAL DETAIL NOTES: PANEL NAME HL-T106-17 HL-T106-17 RECEPTACLE (EMERGENCY CIRCUIT RECEPTACLE SHALL BE "RED") B. PROVIDE GREEN GROUND WIRE IN ALL RECEPTACLE CIRCUITS. CONNECT TO GROUND BUS IN PANEL. DO NOT INSTALL RECEPTACLES, COMPUTER OR TELEPHONE OUTLETS BACK TO BACK. INSTALL IN ADJACENT STUD CAVITIES, TO REDUCE SOUND TRANSMISSION. A. 1/2" CONDUIT TO ABOVE LAY-IN CEILING WITH BUSHED END GROUNDING PIN ON TOP OR TO LEFT OF OUTLET ON HORIZONTALLY MOUNTED RECEPTACLES 1/2" CONDUIT TO ABOVE LAY- IN CEILING WITH BUSHED END TAPE LABEL, VERIFY COLOR WITH OWNER, ADHERE TO COVERPLATE. (ACTUAL CIRCUIT INFORMATION SHALL BE AS INSTALLED AND NOT NECESSARILY THE SAME CIRCUIT NUMBER AS SHOWN ON THE PLANS.) EQUIPMENT: "INSERT DESIGNATION" POWER SOURCE: "INSERT SOURCE" TYPE SUPPLY: INSERT-NORMAL, OR CRITICAL OPERATION POWER, OR OPTIONAL STANDBY, OR LEGALLY REQUIRED, OR LIFE SAFETY EMERGENCY AS APPLICABLE" VOLTAGE: "INSERT APPLICABLE VOLTAGE-208/120V OR 480/277V, ETC." CONDUCTOR COLOR CODING: PHASE A - "BLACK OR BROWN" PHASE B - "RED OR ORANGE" PHASE C - "BLUE OR YELLOW" NEUTRAL - "WHITE OR GRAY" GROUND - GREEN AVAILABLE SHORT CIRCUIT CURRENT: "INSERT AMPS RMS" PROVIDE CUSTOM NAMEPLATE AS INDICATED FOR ALL PANELBOARDS, MCC'S, SWITCHBOARDS, SWITCHGEAR, TRANSFER SWITCHES, GENERATORS ETC. NAMEPLATE SHALL BE ENGRAVED (WHITE LETTERING, BLACK BACKGROUND) AND ATTACHED TO THE EQUIPMENT WITH SCREWS. LETTERING SHALL BE 1/4" HIGH WITH SPACE BETWEEN LINES 1/8" MINIMUM. MINIMUM SHALL BE 8"H x 8"W. PROVIDE SAMPLE NAMEPLATE FOR REVIEW. THE AVAILABLE SHORT CIRCUIT SHOULD BE PROVIDED AT THE SERVICE ENTRANCE. 2. 1. DETAIL NOTES: 3. 4. 3/4" FLEXIBLE CONDUIT OR MC CABLE MAXIMUM 6' LENGTH 3/4" FLEXIBLE CONDUIT OR MC CABLE MAXIMUM 6' LENGTH TYPICAL 2'x4' LUMINAIRE 3/4" EMT 3/4" EMT LINE NEUTRAL BLK LOAD WHITE / NEUTRAL RED (LINE) POWER/RELAY PACKWHT. BLK. OFF SWITCH RED (LOAD)BLUBLKREDCONTROL OUTPUTBLU COMMON +24VDCRED BLU CONTROL OUTPUT COMMONBLK +24VDC CEILING SENSOR CEILING SENSOR RED ROOM UNOCCUPIED: LIGHTING TO BE OFF AFTER TIME DELAY FROM LAST MOTION SENSING. ROOM UCCUPIED: UPON SENSING OF MOTION IN THE SPACE, THE SENSOR SHALL ENABLE THE SWITCH PACK TO ENERGIZE THE LIGHTING (LOAD). LIGHTING SHALL REMAIN ENERGIZED UNTIL MOTION IS NOT SENSED (INITIATE TIME DELAY, SET FOR 30 MINUTES) 2. 1. SEQUENCE OF OPERATION: PROVIDE ADDITIONAL SENSORS AS INDICATED ON THE PLANS AS RECOMMENDED BY THE MANUFACTURERS. PROVIDE INDICATED SWITCHING.2. 1. DETAIL NOTES: PROVIDE CONNECTIONS TO BUILDING MANAGEMENT SYSTEM AS REQUIRED ALONG WITH ALL ADDITIONAL ACCESSORIES REQUIRED. A. GENERAL NOTES: 2 1 REFERENCE NOTES: 1. FIXTURE FINISH COLOR SHALL BE COORDINATE WITH ARCHITECT AND OWNER. F F FACP 120V, 20A CIRCUIT(S) CONNECTED TO EMERGENCY LIFE SAFETY INITIATING AUXILLIARY CIRCUIT FAN SHUT DOWN ACCESS CONTROL SYSTEM NOTIFICATION - VISUAL NOTIFICATION - AUDIBLE (SPEAKER) SPEAKER ZONE #1: XXXX 3 4 5 5 5 5 F F NOTIFICATION - VISUAL NOTIFICATION - AUDIBLE (SPEAKER) SPEAKER ZONE #2: XXXX 5 5 F F NOTIFICATION - VISUAL NOTIFICATION - AUDIBLE (SPEAKER) SPEAKER ZONE #3: XXXX 5 5 CONNECTION TO THE BUILDING MANAGEMENT SYSTEM CONNECTION TO THE CAMPUS FIRE ALARM NETWORK 6 CONNECTION TO EXISTING HONEYWELL MONITORING PANEL 7 F F NOTIFICATION - VISUAL NOTIFICATION - AUDIBLE (SPEAKER) SPEAKER ZONE #4: XXXX 5 5 BATTERIES (LOCATED IN A102) NOTIFICATION - AUDIBLE (SPEAKER) SPEAKER ZONE #5: XXXX F 5F NOT USED. NOT USED. ALL CABLING SHALL BE AS REQUIRED BY THE SYSTEM MANUFACTURER AND SUCF FIRE ALARM GUIDELINES. ROUTE 24VDC POWER WITH ALL INITIATION CIRCUITING. TYPICAL UNLESS OTHERWISE INDICATED. PROVIDE LINE ISOLATORS ON INITIATING DEVICE CIRCUITS ALLOWING NO MORE THAN 30 DEVICES TO BE EFFECTED IN THE EVENT OF A WIRING FAULT (TYPICAL). FIRE ALARM CIRCUIT WIRING EXTENDING BACK TO THE MAIN FIRE ALARM CONTROL PANEL. ALL WIRING SHALL BE CLASS "A" UOI. CONNECTION FROM THE CAMPUS NETWORK. PROVIDE NETWORK CARD AND ALL REQUIRED COMPONENTS FOR COMMUNICATION WITH THE EXISTING CAMPUS NETWORK. PROVIDE CABLING AS REQUIRED BY THE SYSTEM MANUFACTURER BACK TO THE SECOND FLOOR SERVER ROOM IN 3/4" CONDUIT. CONNECTION FROM THE EXISTING HONEYWELL MONITORING SYSTEM. PROVIDE CABLING AS REQUIRED BY THE SYSTEM MANUFACTURER. DETAIL NOTES: 1 2 3 4 5 6 7 ALL FIRE ALARM WORK SHALL BE PER THE SUCF & SUNY BINGHAMTON FIRE ALARM GUIDELINES. DEVICES SHOWN ARE DIAGRAMMATIC ONLY. FOR EXACT LOCATIONS AND QUANTITIES SEE FLOOR PLANS. ALL FIRE ALARM SYSTEM RACEWAY SIZES AND CIRCUITRY REQUIREMENTS SHALL BE IN ACCORDANCE WITH EQUIPMENT MANUFACTURERS RECOMMENDATIONS AND ALL CODES THAT MAY APPLY. CABLING MUST BE UNIQUELY IDENTIFIED AND LABELED, AND A PERMANENT, ACCURATE RECORD OF THE IDENTIFICATION AND USE OF EACH CABLE MUST BE MADE AT THE TIME OF INSTALLATION. LABELING IS TO BE DONE WITH PERMANENT MARKERS ON CLEAR MYLAR TAPE. THE TAPE SHALL BE LONG ENOUGH SO WHEN WRAPPED AROUND THE CABLE IT WILL WRAP OVER ITSELF, PROTECTING THE WRITING. FACP AND OTHER PANELS SHALL BE MOUNTED WITH CLEARANCES FOR OBSERVATION AND TESTING. THE FACP SHALL BE MOUNTED SO THAT THE LCD DISPLAY IS BETWEEN 60" AND 68" (EYE LEVEL). SPACE DETECTORS IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDED DISTANCE. PROVIDE ADDITIONAL DETECTORS WHERE REQUIRED. ALL LOW VOLTAGE FIRE ALARM CIRCUITS MAY OCCUPY A COMMON CONDUIT. RUN AC POWER AND CONTROL WIRING (FAN SHUTDOWN, ETC.) IN SEPARATE CONDUIT. DO NOT RUN WITH ANY OTHER FIRE ALARM SYSTEM WIRING IN A COMMON CONDUIT. ALL CONDUIT, MOUNTING BOXES AND PANELS SHALL BE HUNG AND FASTENED WITH FITTINGS TO ENSURE POSITIVE GROUNDING THROUGHOUT THE ENTIRE SYSTEM. THE FACP SHALL BE MOUNTED USING VERTICAL STEEL CHANNEL SUPPORTS AS A STAND OFF. TRANSPOSING OR CHANGING COLOR CODING OF WIRES IS NOT PERMITTED. ALL CONDUCTORS IN CONDUIT CONTAINING MORE THAN ONE WIRE SHALL BE LABELED ON EACH END AND IN JUNCTION BOXES WITH "E-Z MARKERS". CONDUCTORS IN CABINETS SHALL BE FORMED AND HARNESSED SO THAT EACH DROPS OFF DIRECTLY OPPOSITE ITS TERMINAL. ALL WIRING SHALL BE CHECKED AND TESTED TO ENSURE THAT THERE ARE NO GROUNDS, OPENS, OR SHORTS. FIRE ALARM GENERAL NOTES:WIRING COLOR CODES SHALL BE CONSISTENT THROUGHOUT THE SYSTEM AND SHALL ALLOW FOR EASY IDENTIFICATION OF INITIATING, INDICATING AND AUXILIARY CONTROL CIRCUITS. THE FIRE ALARM RISER DENOTES THE GENERAL ARRANGEMENT OF THE SYSTEM WITH TYPICAL DEVICES AND MINIMUM QUANTITIES OF TERMINAL CABINETS & POWER BOOSTERS. PROVIDE ADDITIONAL TERMINAL CABINETS, BOOSTERS, ETC. AS REQUIRED TO PROVIDE A COMPLETE AND OPERATIONAL SYSTEM. ALL FIRE ALARM SYSTEM JUNCTION BOXES SHALL BE PAINTED RED WITH STENCIL LETTERING INDICATING "FIRE ALARM SYSTEM". WIRING INDICATED ON THE RISER DIAGRAM IS DIAGRAMMATIC ONLY. IT IS NOT INTENDED TO INDICATE ROUTING OR QUANTITY OF WIRES REQUIRED. PROVIDE WIRING FOR A COMPLETE SYSTEM AS REQUIRED BY SYSTEM MANUFACTURER. PROVIDE CONTROL RELAY MODULES FOR HEAT DETECTORS LOCATED IN ELEVATOR MACHINE ROOMS AND ELEVATOR HOIST WAYS FOR SHUNT TRIP CONTROL OF THE DISCONNECT SWITCHES SERVING THE ELEVATORS. PROVIDE ALL INTERCONNECTING WIRING, ADDRESSABLE MODULES, ETC. A MINIMUM OF (4) FOUR PROGRAMMABLE FUNCTION SWITCHES SHALL BE LOCATED AT THE MAIN FACP AND ANNUNCIATOR(S). THE FOLLOWING SHALL BE CAPABLE OF BEING DISABLED FROM THE FACP: ALL HORNS, STROBES, DOOR HOLDERS, ELEVATORS, AND FAN SHUTDOWN. THE FACP SHALL BE PROVIDED WITH A MINUMUM OF TWO FREE EXPANSION CARD BAYS FOR FUTURE EXPANSION. ALL ADDRESSABLE INITIATING CIRCUITS SHALL HAVE A MINIMUM OF AT LEAST 30% SPARE CAPACITY PER LOOP AND FLOOR. ALL FACP OR AUXILLARY NAC OUTPUT CIRCUITS SHALL HAVE AT LEAST 30% SPARE OUTPUT POWER FOR FUTURE EXPANSION. ALL NOTIFICATION APPLIANCES SHALL BE ADRESSABLE. ALL DEVICES LOCATED ABOVE CEILINGS SHALL HAVE A REMOTE LED INDICATOR MOUNTED ON THE WALL AT EYE LEVEL AS NEAR AS POSSIBLE BELOW THE DEVICE AND LABELED ACCORDINGLY. AUDIO AND VISUAL SIGNAL DEVICES TO BE ON SEPERATE CIRCUITS TO ALLOW AUDIO DEVICES TO BE SILENCED WHILE VISUAL DEVICES (STROBES) CONTINUE TO FLASH. PROVIDE SYNCRHONIZATION OF ALL NEW STROBES. A. B. C. D. E. F. G. H. I. J. K. M. L. N. O. P. Q. R. S. T. U. V. W. X. F F F F F F F F F F F F F F F F F F F F FSDFSD CM CM CM CM IM IM IM CM TS WF F S H S HF These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions5/7/2021 11:27:14 AMC:\Users\crspall\Documents\200311_CorsonFirstFloor_E_Central_R20_crspall.rvt20625.01 MRG Electrical Details & Schedule GDD CRS E-200 100% Construction Documents Cornell University Corson Hall Rm 136-142A Lab Renovation Ithaca, NY May 7, 2021 1/8" = 1'-0"1 TYPICAL RECEPTACLE IDENTIFICATION REQUIREMENTS NTS2EQUIPMENT NAMEPLATE DETAIL NTS3TYPICAL BRANCH CIRCUIT WIRING FOR CEILING NTS4CEILING MOUNTED OCCUPANCY SENSOR (MULTIPLE SENSORS) EM EM BATTERY PACK SIGNIFY: CHLORIDE CLU-N-W LED 120/277V 1 X1 LED EXIT SIGN REFER TO PLANS FOR MOUNTING SIGNIFY: CHLORIDE CLX-N-RW LED 120/277V 1 L1 1'x4' LED LAB SPACE RECESSED FIXTURE METALUX: 14EN-LD2-43-UNV-L840-CD1 LED 120/277V 1 TYPE DESCRIPTION MFR. & CATALOG No.LAMP VOLTAGE/BALLAST REFERENCE NOTES LUMINAIRE SCHEDULE 1/8" = 1'-0"5 Fire Alarm Riser