HomeMy WebLinkAboutSnee 1149 - Architectural Drawings101ROOM NAME1A101SIM1A101SIMA1011SIM1'-0"B1W1F1101ROOM NAMENameElevationW1A1011SIMDETAIL ENLARGEMENTWALL SECTIONBUILDING SECTIONDETAIL SECTION1INTERIOR ELEVATIONDOOR & INTERIOR WINDOW TAGWALL TAGROOM IDENTIFICATIONEXTERIOR WINDOW & LOUVER TAGROOM FINISH KEYCONTRACT LIMIT LINEEXISTING DOORNEW DOORPARTITIONS, DOORS AND ITEMS TO BE REMOVEDFULL HEIGHT PARTITION PARTIAL HEIGHT PARTITION NOTE KEYFLOOR ELEVATION1011001REVISION CLOUD & TAGPLAN ELEVATION50'-6"SITE ELEVATIONSTRUCTURAL ELEVATIONWORKING POINTWPCEILING HEIGHTEQUIPMENT TAGA101SIMA1A2A3A411iSCOPE LINEDIMENSION TO THE FACE OF FRAMING AT NEW CONSTRUCTION, TYP.DIMENSION TO THE FACE OF FINISH AT EXISTING CONSTRUCTIONDIMENSION TO THE FACE OF FINISH50'-6"50'-6"1EXISTING PARTITIONSET NUMBERARCHITECTURAL SYMBOLS AND PATTERNSPROJECT INFORMATIONCrescent Building217 North Aurora StreetIthaca, New York 14850607.241.0244G00105/03/202111614/ COB #2013112 Hollister DriveSnee Hall 1149 Microscopy Lab RenovationCONSTRUCTION DOCUMENTSCORNELL UNIVERSITYGENERALG101 FIRST FLOOR CODE CONFORMANCE PLANHAZARDOUS MATERIALAR101 FIRST FLOOR ASBESTOS REMOVAL PLANARCHITECTURAL DEMOLITIONAD101 FIRST FLOOR DEMOLITION PLANARCHITECTURALA001 TYPICAL MOUNTING HEIGHTS & WALL TYPESA101 SNEE FIRST FLOOR PARTIAL PLAN - ROOM 1149A102 FIRST FLOOR PARTIAL FURNITURE PLAN (FOR REF ONLY)A151 PARTIAL REFLECTED CEILING PLANA251 INTERIOR ELEVATIONS & DETAILSA601 DOOR & SIGNAGE SCHEDULEPLUMBING DEMOLITIONPD101 FIRST FLOOR RM 1149 PLAN - PLUMBINGMECHANICALM001 DRAWING INDEX, SYMBOLS, & ABBREVS.M101 FIRST FLOOR RM 1149 PLANS - HVACM501 DETAILSM601 SCHEDULESM701 CONTROL SCHEMATICSELECTRICAL DEMOLITIONED101 FIRST FLOOR DEMOLITION PLANELECTRICALE001 DRAWING INDEX, SCHEDULES, SYMBOL LISTS & NOTESE101 FIRST FLOOR ELECTRICAL PLANTELECOMMUNICATIONSTA001 COVER SHEETTA101 AV INFRASTRUCTURE DESIGNTA102 AV INFRASTRUCTURE DESIGNTA501 DETAILS & SCHEDULES - AVTA701 AV SYSTEM DESIGNFOR REFERENCE ONLY - EXISTING DRAWINGSA01 LEVEL 1 FLOOR PLANA06 LEVEL 1 RCPA10 PARTITION TYPES AND DETAILSE05 LEVEL 1 LIGHTE06 LEVEL 1 POWER AND AUXP03 LEVEL 1 PLUMBING PLANT2-1. CA_CP FIRST FLOOR PATHWAYS AND CABLINGDATE:JOB NUMBER:CONSTRUCTION CLASSIFICATION:SPRINKLER PROTECTION:BUILDING USE CLASSIFICATION:TOTAL EXISTING BUILDING AREA:AREA OF RENOVATION:AREA OF ADDITION:TOTAL AREA OF PROJECT:IIB SPB OCCUPANCY74,599 SF558 SF0 SF558 SF LOCATION PLANF|S Engineering, DPC721 East Genesee Street, Syracuse, NY 13210.1505315.471.4013 Tomei AV Consulting LLC29 Janivar DriveIthaca, NY 14850607.592.5370443 Electronics PkwyLiverpool, New York 13088315.457.5200Barton & Loguidice Engineering SNEE 11491149 (1) LOCATION OF EXITS(2) EXIT ACCESS TRAVEL DISTANCE: DISTANCE TO EXITS FROM THE MOST REMOTE POINT IN THE MOST REMOTE ROOM ON THE FLOOR(3) DIRECTION OF EGRESS TRAVEL, INCLUDING DIRECTION OF SWING OF DOORS(4) COMMON PATH OF EGRESS TRAVELDIRECTION OF EGRESS TRAVEL INDICATED BYORDIRECTION OF DOOR SWING IS SHOWN GRAPHICALLY FOR EACH DOORSYMBOL ON DRAWING (IF APPLICABLE)(5) MINIMUM 1 HOUR CONSTRUCTION(6) MINIMUM 2 HOUR CONSTRUCTIONE(7) SMOKE BARRIER (1 HOUR CONSTRUCTION)(8) ALTERATION LEVEL 2 WORK AREA(9) PRESUMED 1 HOUR CONSTRUCTION(10) PRESUMED 2 HOUR CONSTRUCTION1161112911201120A1146101310251013A1012A1012103611501162A116211021102A102011241164A1164114211601035115811401010A101010111030100210011030A1038DISPLAYDISPLAYDISPLAY DISPLAY1160AUPUPUPUPDNUPEETRAVEL DISTANCE - 30'ALLOWABLE - 300'TRAVEL DISTANCE - 117'ALLOWABLE - 300'FECFEC980 SF558 SF1149MICROSCOPYCLASSROOMTRAVEL DISTANCE - 44'ALLOWABLE - 100'ALTERNATE #2WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NG101FIRST FLOORCODECONFORMANCEPLAN05/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive# Description Date 11611129114910131013A1012A101210101038DISPLAYDISPLAY DISPLAYDISPLAYATRIUMATRIUMWARNINGNew York State Law for anyperson, unless acting under thedirection of a licensed Architect,.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NAR101FIRST FLOORASBESTOSREMOVALPLAN05/03/202111614/ COB #2013ALD2CORNELL UNIVERSITY CONSTRUCTION DOCUMENTS Snee Hall 1149 Microscopy Lab Renovation 112 Hollister Drive 1/4" = 1'-0"A1FIRST FLOOR ASBESTOS REMOVAL PLAN#Description DateASBESTOS MATERIAL REMOVAL SCHEDULEAPPROXIMATE QUANTITYMATERIALLEGENDREMOVE AND DISPOSE OF FLOOR TILE.(BLACK FLOOR TILE MASTIC IS NON-ACM)600 SFGENERAL NOTES - ASBESTOS REMOVALA.CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETION OF ASBESTOS-CONTAINING MATERIAL REMOVALSDEFINED IN THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR ALL MEANS, METHODS,SUPERVISION, MANAGEMENT, AND SEQUENCING TO COMPLETE THE WORK. ADDITIONALLY, THE CONTRACTOR SHALLMAKE ALL EFFORTS TO COOPERATE AND COORDINATE WITH THE OTHER PROJECT CONTRACTORS. THE CONTRACTORSHALL COORDINATE ALL BUILDING/ELECTRICAL HVAC SHUTDOWNS AND ISOLATION WITH THE OWNER.B.CONTRACTOR SHALL HOLD A CURRENT LICENSE IN THE STATE OF NEW YORK FOR ASBESTOS REMOVAL AND SHALLEMPLOY NYS DEPARTMENT OF LABOR CERTIFIED EMPLOYEES. SUFFICIENT STAFF SHALL BE PROVIDED TO COMPLETETHE ASBESTOS REMOVAL WITHIN THE SCHEDULED CONSTRUCTION PERIODS.C.MATERIAL REMOVAL AND DISPOSAL SHALL BE IN ACCORDANCE WITH THE PROCEDURES IDENTIFIED IN THE PROJECTMANUAL AND APPLICABLE LOCAL, STATE, AND FEDERAL REGULATIONS. CONTRACTOR, AT HIS OWN EXPENSE, MAYOBTAIN A SITE VARIANCE FROM THE NYS DEPARTMENT OF LABOR.D.DRAWINGS INDICATE THE EXTENT OF ASBESTOS REMOVAL AND ARE TO BE USED AS A GUIDELINE. CONTRACTORSHALL DISPOSE OF ASBESTOS-CONTAINING MATERIALS ILLUSTRATED ON THE CONTRACT DRAWINGS AND LISTED INTHE SPECIFICATIONS.E.CONTRACTOR SHALL COORDINATE PROPOSED DECONTAMINATION UNIT LOCATIONS, STAGING AREAS, AND WORKSITE ACCESS WITH BUILDING OWNER AND/OR THEIR REPRESENTATIVE.F.CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACEMENT OR REPAIR OF ANY DAMAGES TO THE BUILDING, BUILDINGCOMPONENTS, OR SYSTEMS NOT INCLUDED IN THIS SCOPE THAT ARE CONSEQUENTLY DAMAGED AS A RESULT OF THECONTRACTOR'S WORK.REMOVE AND DISPOSE OF ASBESTOS-CONTAININGLABORATORY BENCH TOP MASTIC.2 SFNOTE: CONTRACTOR SHALL REMOVE CABINETRY TOACCESS AND REMOVE ACM FLOOR TILE UNDER UNITAS REQUIRED DURING THE WORK. 11611129114910131013A1012A101210101038DISPLAYDISPLAYDISPLAYDISPLAYATRIUMATRIUMD1D5D2D4D4D7D8D8D3DEMOLITION NOTES:D1. DEMOLISH FLOORING AND WALL BASE, ENTIRE SPACE, TYPICALCOORDINATE WITH HAZMAT DRAWINGS D2. DEMOLISH DOOR AND FRAME ASSEMBLYD3. DEMOLISH CEILING SOFFIT, SEE A151D4. REMOVE TACKBOARD AND/OR CHALKBOARD AND DELIVER TO OWNER.D5. REMOVE & ABATE EXISTING COUNTERTOP, SINK, WALL & BASE CABINETS, COMPLETE. REMOVE EXISTING SHELVING, COMPLETE D6. SEE HAZMAT DRAWINGS FOR ABATEMENTD7. DEMOLISH DOOR, KEEP FRAME ASSEMBLY D8. REMOVE ALL SHELVING, COMPLETE D9. REMOVE EXISTING CONDUIT, PIPING, WIREMOLD, ETC.SEE MEP DRAWINGS FOR MORE INFORMATION, TYP. INDICATES WORK AREAWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NAD101FIRST FLOORDEMOLITIONPLAN05/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive1/4" = 1'-0"A1FIRST FLOOR DEMOLITION PLAN1149 -WEST WALL1149 -WEST WALL1149 -SOUTH WALL1149 -SINK1149 -SOUTH WALL 1149 -PARTIAL NORTH WALL D9D4D8D9D9D9D51149 -WEST WALLD91149 -EAST WALLD4D81149 -EAST SOFFITD91149 -NORTH WALL D9D9D8D8D9D7D3# Description Date AANSI -2003FIG. 308.2.1UNOBSTRUCTED FORWARD REACHFIG. 308.2.2OBSTRUCTED HIGH FORWARD REACHFIG. 308.3.1UNOBSTRUCTED SIDE REACHFIG. 308.3.2OBSTRUCTED HIGH SIDE REACHPROTRUDING OBJECTSCLEAR FLOOR SPACEUnless otherwise specified may include kneeand toe clearancesCIRCULAR TURNING SPACEMay include knee and toe clearances'T-TURN' TURNING SPACEMay include knee and toe clearances only atthe end of either the base or one arm.GENERAL -TYPICAL CLEARANCES AND REACH RANGES 48" MAX48"15" MIN.20" MAX48" MAX25" MAX44" MAX48" MAX15" MIN.46" MAX24" MAX34" MAX.48" MAX10"34" MAX.4" MAX80"27"4'-0"2'-6"5'-0"5'-0"3'-0"1'-0"3'-0"1'-0"EXCEPTIONS:(a) HANDRAILS MAY PROTRUDE 4-1/2" MAX.(b) DOOR CLOSERS & STOPS MAY BE 78" MIN. ABOVE THE FLOORFIG. 307.2CONCRETE MASONRY UNITUNDERSIDE OF STRUCTURE• EXISTING WALL TYPE, INFILLS TO MATCH ADJACENT CONSTRUCTION7 5/8"IWS TYPE: AMETAL FURRING @ 16" O.C.GYPSUM BOARD5/8"SEALANT, BOTH SIDES, ENTIRE PERIMETER1 1/2"SEALANT, BOTH SIDES, ENTIRE PERIMETERMATCH EXISTINGVIFWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A001TYPICALMOUNTINGHEIGHTS &WALL TYPES05/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive1 1/2" = 1'-0"C9IWS # - CMU - 8"# Description Date A251F6F31161112910131013A1012A101210351038DISPLAYDISPLAYATRIUMKEEP EXISTING FRAME. PROVIDE NEW DOOR. PROVIDE WIRELESS CARD READER. COORDINATE WITH OWNER FOR WIRELESS CONNECTION1149B1P1F11149MICROSCOPYCLASSROOM1'-2"INFILL WALL WHERE DOOR AND FRAME WERE REMOVED. TOOTH IN NEW CMU TO MATCH ADJACENT EXISTING.REPLACE BASE FOR ENTIRE LENGTH OF THIS SEGMENT OF WALL FROM CORNER TO CORNER. EXISTING FLOOR TO BE PROTECTED DURING CONSTRUCTION. IF UNABLE TO PROTECT AND MAINTAIN WITHOUT DAMAGE, ALERT OWNER TO ARRANGE FOR HAZMAT TESTING PRIOR TO PROCEEDING. PATCH AND PAINT TO MATCH EXISTING ADJACENT SURFACES AS NEEDED WITH LIMITED DISRUPTION TO 1161 OCCUPANTS. GYPSUM BOARD TO BE FLUSH WITH ADJACENT SURFACES IN 1149. A601A814"ALTERNATE #1CASEWORK 6'-0"ALTERNATE #1CASEWORK 24'-0"GMBGMBAFINISH NOTES:1. ALL WALLS TO BE PAINTED P1 UNLESS OTHERWISE NOTED.2. ALL GYPSUM BOARD CEILINGSBTO BE PAINTED P3 UNLESS OTHERWISE NOTED ON REFLECTED CEILING PLAN.3. HM DOORS / FRAMES AND PAINTED WINDOW TRIM / FRAMES SHALL BE PAINTED P2 UNLESS OTHERWISE NOTED.4. ALL WALL BASE TO BE B1 UNLESS OTHERWISE NOTED.5. ALL CEILING TO BE PAINTED P3 WITH ALL EXPOSED MEP UNLESS OTHERWISE NOTED. 6. SEE INTERIOR ELEVATIONS FOR ADDITIONAL WALL AND BASE FINISHES, TYPICAL.7. SEE REFLECTED CEILING PLAN FOR ADDITIONAL FINISH INFORMATION, TYPICAL.8. ALL FLOORING MATERIAL AND TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION UNLESS OTHERWISE NOTED.9. MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, ETC. TO BE PAINTED TO MATCH ADJACENT WALL SURFACES.10. NO LUXURY VINYL TILE TO BE CUT LESS THAN 6", 11. ALL METAL UNDER-COUNTER SUPPORT BRACKETS TO BE PAINTED TO MATCH ADJACENT WALL FINISH.12. EXPOSED CMU TO BE PAINTED TO MATCH ADJACENT WALL FINISH. FINISH LEGEND & KEY:WALLP1PAINT COLOR 1P2PAINT COLOR 2P3PAINT COLOR 3FLOORF1LUXURY VINYL TILE INSTALL PLANKS ASHLAR RUNNING IN NORTH/-SOUTH DIRECTIONBASEB1RESILIENT BASE COLOR 1ROOM #WALLFLOORBASEFINISH TAGWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A101SNEE FIRSTFLOORPARTIAL PLAN -ROOM 114905/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive1/4" = 1'-0"A3FIRST FLOOR PARTIAL PLAN - 1149# Description Date A251F6F31161112910131013A1012A10121038DISPLAYDISPLAYATRIUM4'-10"3'-9"EXISTING RELOCATED STORAGE CABINETS (BLUE). FURNISHED BY OWNER. CASEWORK -ALTERNATE 1MICROSCOPE TABLES (24X41). FURNISHED BY OWNER. 1149558 SF1149MICROSCOPYCLASSROOM41"3'-0"3'-10"3'-6"5'-0"CASEWORK -ALTERNATE 1GMBGMB1161112910131013A1012A10121038DISPLAYDISPLAYATRIUM4'-0"EXISTING RELOCATED STORAGE CABINETS -WITH DRAWERS -STACKED 2 HIGH. SECURE TO WALL. FURNISHED BY OWNER. MICROSCOPE TABLES (24X41). FURNISHED BY OWNER. 1149558 SF1149MICROSCOPYCLASSROOM41"3'-10"3'-6"3'-0"2'-0"EXISTING RELOCATED STORAGE CABINETS (BLUE). FURNISHED BY OWNER. 3'-6"3'-6"4'-5 1/4"5'-0"GMBGMBFLOOR PLAN NOTES:1. SEE EXISTING PHOTOS FOR ADDITIONAL SCOPE INFORMATION, TYPICAL.2. PATCH ALL DAMAGED WALL SURFACES WITHIN ROOM 1149, TO MATCH EXISTING, TYPICAL. 3. ALL WALL INFILLS TO MATCH EXISTING CONSTRUCTION UNLESS OTHERWISE NOTED.4. PATCH ALL FLOOR PENETRATIONS TO MATCH EXISTING CONSTRUCTION. PROVIDE FINISHES AT ALL MEP REMOVAL LOCATIONS5. PATCH ALL WALL PENETRATIONS TO MATCH EXISTING ADJACENT CONSTRUCTION.6. AT LOCATIONS WHERE OPENINGS ARE MADE IN EXISTING CONSTRUCTION TO FACILITATE THE INSTALLATION OF MEP WORK, RESTORE TO PRE-CONSTRUCTION CONDITIONS AND MATCH ADJACENT CONSTRUCTION, U.O.N.7. PROVIDE BLOCKING AS REQUIRED AT ALL WALL-MOUNTED SHELVING, FURNITURE, A/V MONITORS, PROJECTION SCREENS, SPEAKERS AND ANCILLARY EQUIPMENT.8. PROVIDE LEVEL 4 FINISH WITHIN ROOM 1149. PATCH OR ALTERNATIVELY PROVIDE NEW LAYER OF GYPSUM BOARD CONSISTENTLY WITHIN 1149 UP TO STRUCTURALDECK. 9. COORDINATE ALL POWER AND DATA CONNECTIONS WITH POWER PLANS, EQUIPMENT AND FURNITURE PLANS AND ELEVATIONS, TYP. WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NA102FIRST FLOORPARTIALFURNITUREPLAN (FOR REFONLY)05/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive1/4" = 1'-0"A6FIRST FLOOR PARTIAL PLAN - 1149 FURNITURE WITH ALTERNATE 1 CASEWORK1/4" = 1'-0"A1FIRST FLOOR PARTIAL PLAN - 1149 FURNITURE WITH EXISTING CABINETS# Description Date RETURN AIR GRILLESUPPLY AIR GRILLEPROJECTION SCREENGYPSUM BOARD CEILINGREFLECTED CEILING PLAN NOTES:3. ALL GYPSUM SOFFITS AND CEILINGS TO BE REPLACED AT EXISTING LOCATIONS AND CEILING HEIGHT. 5. REPAIR CEILINGS DAMAGED OR IMPACTED BY CONCEALED SCOPE INCLUDING BUT NOT LIMITED TO MEP AND AV WORK THAT IS NOT SPECIFICALLY DETAILED ON THIS DRAWING. 7. PROVIDE PROJECTOR MOUNT FOR INSTALLATION.8. REPAIR CEILINGS AFFECTED BY AV WORK. 9. PAINT EXPOSED CONCRETE WAFFLE CEILING, GYPSUM BOARD CEILINGS, SOFFITS P3. 10. PAINT ALL EXPOSED DUCTWORK, CONDUIT, WIREMOLD, PIPES, ETC, P3 TO MATCH CEILING, TYPICAL. CEILING MATERIALS:OTHER:PROJECTOR1149MICROSCOPYCLASSROOM12'-10"13'-7"PROJECTOR MOUNT, SEE AV DRAWINGSPROJECTION SCREEN, SEE AV DRAWINGSC5A151TYPMETAL FRAMING AS REQUIREDGYPSUM WALL BOARD ON SUSPENSION SYSTEMMATCH EXISTINGCORNER BEAD, TYP.WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NA151PARTIALREFLECTEDCEILING PLAN05/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive1/4" = 1'-0"C7PARTIAL FIRST FLOOR RCP - 11493" = 1'-0"C5GYPSUM BOARD SOFFIT# Description Date D5A251TYP7'-2"3'-8"4'-4"3'-6"2'-0"3'-6"2'-0"2'-6"2'-6"D3A251TYP42"GMBGMB4'-0"8'-0"PROJECTION SCREEN -SEE AV DRAWINGSCL11'-11"11'-11"D7A251TYP3'-0" 3'-0"7'-2"ALTERNATE 16'-0"SPEAKER -SEE AV DRAWINGS8'-0"INTERIOR ELEVATION NOTES:1.REFER TO FINISH TAG FOR BASE MATERIAL2. ALL SUPPORT BRACKETS TO BE PAINTED TO MATCH ADJACENT WALL SURFACE.3. PATCH AND REPAIR, ANY DAMAGED WALL SURFACES FROM REMOVAL OF EXISTING BLACKBOARDS, MARKERBOARD, TACKBOARDS, WIREMOLD, PIPES, CONDUIT, ETC. 4. GMB: GLASS MARKER BOARD5. FWTP: FABRIC WRAPPED TACK PANEL6. ALL CABINETS ARE ALTERNATE #1 (WOOD). 1'-0"3"CONTINUOUS BASEADJUSTABLE SHELVESPULLCABINET DOORTALL CABINET4"1'-2"ADJUSTABLE SHELVESCONTINUOUS BASE7'-2"SOLID SURFACE TOP POWER & DATA FOR MICROSCOPE TABLES2'-10"FINISHED END PANELCABINET DRAWERCONTINUOUS BASEPULL4 1/2"3 EQ3"1'-2"7'-2"4"WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A251INTERIORELEVATIONS &DETAILS05/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive1/4" = 1'-0"F3MICROSCOPY CLASSROOM - SHELVING (ALTERNATE 1)1/4" = 1'-0"F6MICROSCOPY CLASSROOM - TEACHING WALL3/4" = 1'-0"D7TALL STORAGE CABINET - DOOR (ALTERNATE 1)3/4" = 1'-0"D5TALL STORAGE CABINET - BASE WITH DOOR (ALTERNATE 1)3/4" = 1'-0"D3TALL DRAWER CABINET (ALTERNATE 1)# Description Date DOOR TYPES:D16"6"6 1/2"10"NOTE: WHERE WOOD IS INDICATED FOR MATERIAL, PROVIDE STILE-AND-RAIL WOOD DOORS 1149NameTitle8"BRAILLE55" A.F.F.60" A.F.F.5"3/8"2 1/2"8"1 1/2"CL3/8"3"(4-1/4" x 5 1/2" WINDOW)SIGN TYPE A1/8" MATTE ACRYLIC SUB SURFACE SCREENED, BACKGROUND COLORS TBDCHANGEABLE INSERT: 4-1/4" X 5 1/2"TYPEFACE: HELVETICA MEDIUMNAME & TITLE: 5/8"ROOM NUMBER: 1-1/2" UC RAISEDBRAILE: GRADE II SURFACE MOUNTED CLEAR1"RAISED BAR, COLOR TO MATCH LETTERING1/2"SIGNAGE NOTES:1. ALL SIGNAGE TO COMPLY WITH THE OWNER GRAPHIC STANDARDS.2. TACTILE LETTERING HELVETICA MEDIUM TYPEFACE. 3. ALL SIGNAGE TO COMPLY WITH ADA MINIMUM CHARACTER SPACES OF 1/8".4. FABRICATOR IS RESPONSIBLE FOR ACCURATELY CREATING GRADE 2 BRAILLE IN SUPPORT OF THE TACTILE MESSAGE.5. ALL SYMBOLS AND PICTOGRAMS TO COMPLY WITH OWNER GRAPHIC STANDARDS.6. ALL COLORS WILL BE SELECTED BY OWNER AND ARCHITECT IN COMPLIANCE WITH OWNER STANDARD.ROOM SIGN TYPE AALIGN RAISED BAR TO CMU JOINT, 56" A.F.F, V.I.F.WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A601DOOR &SIGNAGESCHEDULE05/03/202111614/ COB #2013YNPCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister DriveSHEET SCHEDULE - DOOR AND FRAMEDOORNUMBERRoomNumberRoom NameFRAMEDOORFIRERATINGHARDWAREGROUPCOMMENTS DOOR NUMBERELEV MATERIAL HEAD JAMB GLAZING ELEV MATERIAL SIZE GLAZING1149 1149 MICROSCOPY CLASSROOM EXISTING -- EXISTING EXISTING -- D1 WD 3'-0" X 7'-0" FRG-2 3/4 HR 6 WIRELESS CARD READER11493" = 1'-0"D8SIGN TYPES3/4" = 1'-0"A8MICROSCOPY CLASSROOM# Description Date SAN (E)SAN (E)V (E)G (E)CA (E)CA (D)CA (E)CA (D)G (E)G (E)CA (E)CA (E)CA (E)DISCONNECT SINK, CAP PIPING IN WALLREMOVE CA OUTLET ON WALLREMOVE CA & G OUTLETS ON WALLREMOVE CA & G OUTLETS ON WALLSAN (E)SAN (E)11491.SURVEY EXISTING CONDITIONS AND CORRELATE WITH REQUIREMENTS INDICATED TO DETERMINEEXTENT OF SELECTIVE DEMOLITION REQUIRED.2.COORDINATE ALL REQUIRED SHUTDOWNS OF EXISTING SYSTEMS WITH OWNER.3.MAINTAIN SERVICES/SYSTEMS INDICATED TO REMAIN AND PROTECT THEM AGAINST DAMAGE.4.REMOVE PORTIONS OF PIPING INDICATED TO BE REMOVED AND CAP OR PLUG REMAINING PIPING WITHSAME OR COMPATIBLE PIPING MATERIAL.5.DISCONNECT AND CAP SERVICES TO EQUIPMENT/FIXTURES TO BE REMOVED. REMOVE FIXTUREROUGH-INS, SANITARY, VENT AND DOMESTIC WATER PIPING, INSULATION, HANGERS ANDACCESSORIES. CAP PIPING AT MAINS. CAP WATER PIPING AS CLOSE AS POSSIBLE TO MAINS. DO NOTLEAVE "DEADLEGS".GENERAL REMOVAL NOTESFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910PD101FIRST FLOORRM 1149 PLAN -PLUMBING05/01/202111614/ COB #2013DDDCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive3"SCALE: 1/4" = 1'-0"PD101A4PARTAIL FIRST FLOOR DEMO PLAN-1149# Description Date ISSUE:DATE:DRAWN BY:CHECKED BY:SCALE:PROJECT NO.SHEET TITLESHEETDRAWING NO.ALTERATION OF THIS DOCUMENTEXCEPT BY A LICENSED DESIGNPROFESSIONAL, IS A VIOLATION OFNEW YORK STATE EDUCATIONAL LAW.OFFS ENGINEERING,DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044Enter address hereR:\Revit MEP 2012\Templates\S&A_Mechanical.rte10/5/2011 4:16:29 PMOwnerProject NameSK-M201/01/2019AuthorCheckerProject NumberUnnamedMARK DATE DESCRIPTION14/10RECTANGULAR DUCT (SIZE IN INCHES)ROUND DUCT (DIAMETER IN INCHES)14ØAUTOMATIC AIR DAMPERVOLUME DAMPERSMOKE DAMPERFIRE DAMPERSDVDFDSYMBOLDESCRIPTIONAADDUCTWORK SYMBOLS & ABBREVIATIONSFIRE SMOKE DAMPERFSDDUCT SMOKE DETECTOR (FURNISHED & WIRED BY DIV 28, MOUNTED BY DIV 23. INSTALL PER MANUFACTURER'S INSTRUCTIONS)DSDOVAL DUCT (SIZE IN INCHES)14/10ØLOW VELOCITY DUCTWORK SYMBOLSSINGLE LINEDOUBLE LINEDESCRIPTIONDIRECTION OF FLOWDUCT SIZE, FIRST FIGURE IS SIZE SHOWN12/2012/20SUPPLY DUCT SECTION (POSITIVE) PRESSURE, FIRST FIGURE IS TOP20/1220/12RETURN / EXHAUST DUCT SECTION20/1220/12ROUND SIDE TAP WITHVOLUME DAMPER (UNLESSOTHERWISE NOTED)90° BRANCHTAKE OFF(45° ENTRY TYPE FORRECTANGULAR DUCT)1-1/4A)XB (MIN)VDVDAxB4" (MIN)45°VDVDVDDUAL 90°BRANCH TAKEOFF(45° ENTRY TYPE)FLEXIBLE DUCTFLEX CONNECTIONACCESS DOORADADGRILLE REGISTEROR DIFFUSER INBOTTOM OF DUCTDUCTELBOW UPOR DOWNTURN UPTURN DOWN12x6TURN DOWN12x6TURN UPORLONG RADIUS 90DEGREE ELBOWOR TURNINGVANESTRANSITION: LOCATION OF TRANS. IS DIAGRAMMATICAL CONTRACTOR MAY EXTEND LENGTH OF LARGER DUCT TO ACCOMMODATE STD. LENGTH DUCT SECTIONS.CONTRACTOR'S OPTIONAS SHOWN90 DEGREE BRANCHTAKEOFF FROMVERTICAL DUCT-45DEGREE ENTRY TYPEELEV.PLANPLANELEV.DUCT RISE / DROP TOAVOID OBSTRUCTIONARROW INDICATES AIRFLOW DIRECTION90° BRANCH TAKE OFF(TEE TYPEFOR ROUND DUCT)RISERDDROPRISEUPDNDROPVDVDRETURN / EXHAUST DUCT PENETRATION OF FLOOR OR ROOF ABOVE. SEE PLANS FOR DAMPER REQUIREMENTSSUPPLY DUCT PENETRATION OF FLOOR OR ROOF ABOVE. SEE PLANS FOR DAMPER REQUIREMENTSMECHANICAL PIPING SYMBOLS & ABBREVIATIONSSHUTOFF VALVE (REFER TO SPECIFICATIONS FOR SPECIFIC TYPE)CHECK VALVEBUTTERFLY VALVEBALL VALVEPETCOCKCALIBRATED BALANCING VALVEUNIONPRESSURE GAUGE (WITH VALVE)TEMPERATURE SENSORDRAIN VALVE WITH CAPPED AND CHAINED HOSE ENDPIPE UP / PIPE DOWN (ELBOW)BRANCH CONNECTION -UP / DOWNCONCENTRIC REDUCERPIPING (ARROW INDICATES DIRECTION OF FLOW)PIPE ANCHOR PIPE GUIDEGLOBE VALVEPIPE CAPPITCH OF PIPESTRAINER W/ BLOW OFFSTRAINERMVAVPRESSURE RELIEF VALVETEMPERATURE WELLTHERMOMETERTRIPLE DUTY VALVECONDENSATE "P"-TRAPDNUPPSFSPRESSURE SWITCHFLOW SWITCHEXPANSION JOINTPRESSURE REDUCING REGULATOR VALVETGATE VALVE2-WAY CONTROL VALVE3-WAY CONTROL VALVEMANUAL AIR VENT / AUTOMATIC AIR VENTSYMBOLDESCRIPTIONSPECIFIC SHUTOFF VALVE TYPES:SUPPLY DIFFUSER PLAN SYMBOL EXPLANATION:CFMSUPPLY AIR DIFFUSER (NOMINAL 2' x 2')SUPPLY DIFFUSER TYPE (SEE SCHEDULE)RETURN / EXHAUST AIR REGISTERCFMSL8REGISTER/GRILLE PLAN SYMBOL EXPLANATION:CFM (E = EXHAUST / R = RETURN)REGISTER/GRILLE TYPE (SEE SCHEDULE)CFMRE10SYMBOLDESCRIPTIONGRILLE, REGISTER & DIFFUSER SYMBOLSLINEAR SLOT DIFFUSER WITH DISTRIBUTION PLENUMREGISTER AND DIFFUSER AIR FLOW PATTERNS4-WAY BLOW3-WAY BLOW2-WAY BLOWDUCTWORK EXISTING TO REMAIN IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTDUCTWORK REMOVED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTPOINT OF CONNECTION -NEW TO EXISTINGPOINT OF REMOVAL -DEMOLITION TO EXISTINGDEDICATED ELECTRICAL AREA -NO MECHANICAL WORK ALLOWED IN OR ABOVE HIGHLIGHTED AREA UNLESS SPECIFICALLY NOTED OTHERWISEPIPE REMOVED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTPIPE EXISTING TO REMAIN IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTSYS (E)SYSTEM NAME(E) = EXIST TO REMAIN, (D) = EXIST TO BE REMOVEDDUCTWORK PROVIDED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTPIPE PROVIDED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTSYS (D)SYSSYS (D)SYS(10x6) SYS (E)(10) SYS (E)DEMOLITION KEYED NOTEKEYED NOTESYSTEM PHASING SYMBOLSM#MD#??PLAN DETAILBUILDING SECTIONDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDEXTENT OF DETAILEXTENT OF DETAILA1B1C1D1E1A2B2C2D2E2A3B3C3D3E3A4B4C4D4E4A5B5C5D5E5A6B6C6D6E6DETAIL NUMBERDETAIL SCALEDETAIL NAMEDETAIL NUMBERPLAN SETUPSHEET NUMBER WHERE DETAIL IS LOCATEDCAUTION: THESE DOCUMENTS WERE DIGITALLY PRODUCED AND/OR REPRODUCED. CONFIRM REDUCTION OR MAGNIFICATION USING DIMENSIONAL 3"-LONG LINE IN TITLE BARS. IF SCALING DRAWINGS FOR APPROXIMATE DIMENSIONS, ALTERNATE ARCHITECTURAL SCALES MAY BE USED AS FOLLOWS:DOCUMENT REDUCTION/MAGNIFICATION SCALEIF LINE MEASURES 2”(67% COPY):USE 3/16th SCALE ON 1/8”=1’-0”DWGUSE 3/8th SCALE ON 1/4”=1’-0”DWGIF LINE MEASURES 1.5”(50% COPY):USE 1/16th SCALE ON 1/8”=1’-0”DWGUSE 31/8th SCALE ON 1/4”=1’-0”DWG3"3"????XXXX" = X"FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M001DRAWINGINDEX,SYMBOLS &ABBREVS.05/01/202111614/ COB #2013TAMCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister DriveMECHANICAL DRAWING INDEXNUMBER NAMEREVISIONS# DATEM001 DRAWING INDEX, SYMBOLS & ABBREVS.M101 FIRST FLOOR RM 1149 PLANS - HVACM501 DETAILSM601 SCHEDULESM701 CONTROL SCHEMATICSHVAC DESIGN CRITERIAINTERIOR DESIGN CONDITIONSHEATING 70 deg F DBCOOLING 75 deg F DB / 63 deg F DBOUTDOOR DESIGN CONDITIONSSUMMER 88 deg F DB / 75 deg F WBWINTER-5 deg F DBCLIMATE ZONE 6HVAC DESIGN REQUIREMENTSITEM YES NODUCT SMOKE DETECTORS XFIRE DAMPERS XSMOKE DAMPERSXFIRE RATED ENCLOSURE XFIRE RATED ROOF / FLOOR / CEILING ASSEMBLY XFIRE STOPPING (REFER TO DIVISION 7) XSMOKE CONTROLXECONOMIZER CONTROL N/ADUCT SEALING XGENERAL MECHANICAL NOTESA REFER TO ARCHITECTURAL DRAWINGS FOR CEILING GRID WORKPREFORMED BY OTHERS. IF NOT SHOWN ELSEWHERE INCLUDE IN THISDIVISIONS WORK AS REQUIRED.B WHERE WORK ISN'T SHOWN BY OTHERS, HVAC CONTRACTOR SHALLREMOVE, STORE, AND REINSTALL EXISTING LAY-IN CEILING TILES & TEESAS REQUIRED FOR ALL WORK SHOWN.C HVAC CONTRACTOR SHALL COORDINATE LEFT OR RIGHT UNITCONNECTION ORIENTATION.D HVAC CONTRACTOR SHALL INSTALL UNIT TO ALLOW FOR MAINTENANCEACCESS TO FILTERS, VALVES, CONTROLS, LUBRICATION POINTS,INCLUDING MOVING EXISTING INTERERENCES SUCH AS CONDUITS,WIRINGS AND PIPING.E HVAC CONTRACTOR SHALL HIRE OWNER APPROVED ROOFINGCONTRACTOR AS TO NOT VOID ROOF WARRANTY.F CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, AND REPORTDISCREPANCIES TO THE ARCHITECT / ENGINEER AND AWAIT CLARIFICATIONPRIOR TO PROCEEDING WITH REMOVAL AND RENOVATION WORK.G THE INTENT OF THIS PROJECT IS TO PROVIDE A DDC BASED CONTROLSYSTEM TO REPLACE ALL EXISTING PNEUMATIC CONTROLS. REMOVE ALLEXISTING PNEUMATIC TUBING, THERMOSTATS, VALVES, ACTUATORS, ETC.AND REPLACE W/ DDC. CONFIRM SIZES, QUANTITIES AND LOCATIONS PRIORTO BID.LAT LEAVING AIR TEMPERATURELWT LEAVING WATERTEMPERATUREMAX. MAXIMUMMBH 1,000 BTUHMCA MINIMUM CIRCUIT AMPACITYMGAP MEDICAL GAS ALARM PANELMIN. MINIMUMMOCP MAXIMUM OVERCURRENTPROTECTIONMTD MOUNTEDNC NORMALLY CLOSEDNIC NOT IN CONTRACTNO NORMALLY OPENNOM. NOMINALNTS NOT TO SCALEOA OUTSIDE AIROAI OUTDOOR AIR INTAKEOED OPEN-END DUCTPD PRESSURE DROPPH PHASEPLBG. CONTRACTOR FOR PLUMBINGDIVISIONPRV PRESSURE REDUCING VALVEPS PRESSURE SWITCH / SENSORPSI POUNDS PER SQUARE INCHRA RETURN AIRRH RELATIVE HUMIDITYRV RELIEF VALVESA SUPPLY AIRSENS. SENSIBLESPL SOUND PRESSURE LEVELSWL SOUND POWER LEVELTA TRANSFER AIRTC TEMPERATURE CONTROLSCONTRACTORTDV TRIPLE DUTY VALVETOS TOP OF STEELTS TAMPER SWITCHUH UNIT HEATERUNO UNLESS NOTED OTHERWISEVRA VENTILATION RELIEF AIRVRS VENTILATION SUPPLY AIRWB WET BULBZVB ZONE VALVE BOXAAV AIR ADMITTANCE VALVEAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEBFF BELOW FINISHED FLOORBFG BELOW FINISHED GRADEBOS BOTTOM OF STEELBTUH BRITISH THERMAL UNIT PERHOURCFM CUBIC FEET PER MINUTECO CLEANOUTCOP COEFFICIENT OFPERFORMANCEDB DRY BULBDIA. DIAMETER°F DEGREES FARENHEITEA EXHAUST AIREAT ENTERING AIR TEMPERATUREEFF. EFFICIENCYELEC. CONTRACTOR FOR ELECTRICALDIVISIONEWT ENTERING WATERTEMPERATUREEXT EXISTINGEXT. PD EXTERNAL PRESSURE DROPFF FINISHED FLOORFL FAIL LASTFLA FULL LOAD AMPACITYFLR FLOORFP CONTRACTOR FOR FIREPROTECTIONFPM FEET PER MINUTEFS FLOW SWITCHFSD FIRE / SMOKE DAMPERFT FEETFT-HD FEET OF HEAD (PRESSURE)GC CONTRACTOR FOR GENERALCONSTRUCTION DIVISIONGPM GALLONS PER MINUTEGRD GRILLES, REGISTERS,DIFFUSERSHGT HEIGHTHP HORSEPOWERHVAC CONTRACTOR FOR HEATING,VENTILATING & AIRCONDITIONING DIVISIONIN-WC INCHES OF WATER COLUMN(PRESSURE)IN. INCHHVAC DUCT SYSTEM ABBREVIATIONSABBREV. DESCRIPTIONEA EXHAUST AIROA OUTDOOR AIRPA PRIMARY AIRRA RETURN AIRSA SUPPLY AIRHVAC PIPE SYSTEM ABBREVIATIONSABBREV. DESCRIPTIONCD CONDENSATE DRAINHWR HOT WATER RETURNHWS HOT WATER SUPPLYHVAC EQUIPMENT ABBREVIATIONSABBREV. DESCRIPTIONEF FANFCU-1 FAN-COIL UNITFTR-A FINNED TUBE RADIATIONTU VARIABLE AIR VOLUME BOXTU-R VARIABLE AIR VOLUME BOX - RETURNTU-S VARIABLE AIR VOLUME BOX - SUPPLYUH UNIT HEATERVAV VARIABLE AIR VOLUME BOXGENERAL ABBREVIATIONSTO THE BEST OF THE ENGINEER'S PROFESSIONAL JUDGEMENT, THE DESIGN OF THIS PROJECT CONFORMS TO ALL APPLICABLE PORTIONS OF THE FOLLOWING:THE 2020 NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODETHE 2020 NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, 2016 ASHRAE 90.1, AND 2007 ASHRAE 183; FOLLOWING THE COMPLIANCE PATH MARKED BELOW:ANSI / ASHRAE / IESNA 90.1, AS AMENDED BY 19 NYCRR PART 1240.IECC CHAPTER 4 [CE] PRESCRIPTIVE PROVISIONS (SECTIONS C402, C403, C404, C405, C408 AND ONE OF THE SIX OPTIONS IN SECTION C406 AS NOTED BELOW:MORE EFFICIENT HVAC PERFORMANCE IN ACCORDANCE WITH SECTION C406.2.REDUCED LIGHTING POWER DENSITY SYSTEM IN ACCORDANCE WITH SECTION C406.3.ENHANCED LIGHTING CONTROL IN ACCORDANCE WITH SECTION C406.4.ON-SITE SUPPLY OF RENEWABLE ENERGY IN ACCORDANCE WITH SECTION C406.5.PROVISION OF A DEDICATED OUTDOOR AIR SYSTEM FOR CERTAIN HVAC EQUIPMENT IN ACCORDANCE WITH SECTION C406.6.HIGH-EFFICIENCY SERVICE WATER HEATING IN ACCORDANCE WITH SECTION C406.7.ENHANCED ENVELOPE PERFORMANCE IN ACCORDANCE WITH SECTION C406.8.REDUCED AIR INFILATRATION IN ACCORDANCE WITH SECTION C406.9.TOTAL BUILDING PERFORMANCE PROVISIONS (SECTION C407)THE NEW YORK STATE EDUCATION DEPARTMENT ("SED") MANUAL OF PLANNING STANDARDSTHE 2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIESTHE 2018 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF:HOSPITALSOUTPATIENT FACILITIESRESIDENTIAL HEALTH, CARE, AND SUPPORT FACILITIESALL SYMBOLS SHOWN ARE NOT NECESSARILY USED# Description Date TTCO2TSTSTSMD2MD1MD1MD5MD6MD1MD11149MD9MD9MD9MD9MD9MD9MD9MD91149TU-S1CONNECT TO EXST. 16" DIA SA DUCTCONNECT TO EXST. 3/4" HWS/HWR PIPING12"SA-10"350SA-10"350VD TYPBALANCE EXST. RETURN TU AND ASSOCIATED GRILLE TO 700 CFM MAX AND 300 CFM MIN.1149400 CFM400 CFM820 CFM820 CFM1720 CFMFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M101FIRST FLOORRM 1149 PLANS- HVAC05/01/202111614/ COB #2013TAMCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister DriveNOTE:1. MOUNT ALL DUCTWOTK AND EQUIPMENT HIGH AS POSSIBLE. COORDINATE WITH ALL EXISTING TO REMAIN LIGHTING AND OTHER SERVICES.2. BALANCE EXISTING UNITS TO CFM INDICATED.3. ALL NEW DUCTWORK, EQUIPMENT AND PIPING IN 1149 IS EXPOSED. INSTALL AND INSULATE PER SPECIFICATIONS. REFER TO ARCHITECTURAL SPECIFICATIONS AND COORDINATE FOR PAINTING REQUIREMENTS.3"SCALE: 1/4" = 1'-0"M1011FIRST FLOOR RM 1149 DEMO - HVAC3"SCALE: 1/4" = 1'-0"M1012FIRST FLOOR RM 1149 - HVACMECHANICAL KEYED NOTESMD1 DISCONNECT AND REMOVE DUCTWORK AND ACCESSORIES INCLUDING HANGERS AND GRILLES/DIFFUSERS.MD2 DISCONNECT AND REMOVE HWS/HWR PIPING AND ACCESSORIES.MD5 DISCONNECT AND REMOVE VAV TERMINAL UNIT AND ACCESSORIES INCLUDING CONTROLS ANDWIRING.MD6 DISCONNECT AND REMOVE TEMPERATURE SENSOR AND ACCESSORIES INCLUDING WIRING.MD9 PROVIDE PRE-BALANCE REPORTS PRIOR TO DEMOLITION FOR EXISTING AIRFLOWS FOREQUIPMENT NOTED.# Description Date DAMPER SHALL BE IN NECK OF DIFFUSER, U.N.O.TAP LOCATION IS DIAGRAMMATIC ONLY. ACTUAL LOCATION MAY BE ON TOP, BOTTOM OR SIDE. SEE PLANSSECURE FLEX TO COLLAR & DUCT ELBOW W/ DRAW BAND OR SCREWS. DO NOT TAPE JOINTSRIGID DUCT TO WITHIN 4' 0" OF DIFFUSER6" SHEET METAL COLLAR EXTENSION SECURED TO DIFFUSER, AS REQUIREDSUPPLY-AIR DUCT SIZE PER PLANSSPIN-IN COLLAR W/ LOCKING VOLUME DAMPERSUPPORT DEVICES FROM ABOVE STRUCTURE, INDEPENDENT OF CEILING SYSTEM, AS REQUIREDPLENUM INLET COLLARPROVIDE HANGER SUPPORTS, AS REQUIRED, TO ALLOW FULL RADIUS ELBOW AND PREVENT KINKING (TYP)FLEXIBLE DUCTWORK MAXIMUM LENGTH = 6'-0" (TYP)SQUARE DIFFUSERLINEAR DIFFUSERKEYED NOTES:TYPICAL FOR ACCESSIBLE CEILINGSCEILING13221231" INTERNAL ACOUSTIC DUCT LINED DOUBLE WALL DUCT FOR A DISTANCE OF 10 FEET FROM UNIT OUTLET.LOCATE VALVES AND CONTROL DEVICES FOR CONVENIENT ACCESS AND REMOVAL.TRANSITION SUPPLY DUCT FROM RUN OUT DUCT SIZE SHOWN ON PLAN TO UNIT INLET SIZE.VP/T PORTFLOW BALANCERMANUAL AIR VENTUNION (TYP)TERMINAL UNITFLEXIBLE CONNECTIONSUPPLY AIR DUCT1/2" DRAIN WITH HOSE BIBB2 WAY CONTROL VALVESHUTOFF VALVEMAINSKEYED NOTES:RS123132BOTTOM FLANGE MOUNTED "C" CLAMP WITH SET SCREW, LOCKNUT & RETAINING STRAP. (FOR USE ON BEAMS ONLY, NOT ALLOWED ON JOISTS)VIBRATION ISOLATION DEVICE ASSEMBLY FOR, FANS, AIR HANDLING UNITS, FAN/COIL UNITS, ETC.TOP FLANGE MOUNTED "C" CLAMP WITH SET SCREW & LOCKNUT. (FOR USE ON BEAMS ONLY, NOT ALLOWED ON JOISTS)CONCENTRIC BEAM CLAMP WITH THREADED, WELDED EYEROD. FOR USE WITH JOISTS AND BEAMS.STEEL ALL-THREAD RODS.STEEL PLATE WASHER WITH DOUBLE NUT.A. PROVIDE LINKED EYELETS WITH STUD, AT CONNECTION TO SLOPING STRUCTURE WITH PITCH OF 1 IN 12 OR GREATER. BENDING OF HANGER RODS NOT ALLOWED.FLOOR / ROOF DECKING ASSEMBLY.BEAMKEYED NOTES:JOISTNOTES:CHANNEL SPANNING BETWEEN BEAMS AND/OR JOISTS IN DECKING "CAVITY". SET ON AND SECURE TO BEAMS AND JOISTS.1234567172653461/4" TUBING OR PIPING UP TO 2" RISER. 1/2" FOR LARGER RISERS.PETCOCK OR HOSE BIBB IN ACCESSIBLE LOCATIONHOSE END CONNECTION WITH CAPPROVIDE 8" SQUARE ACCESS DOOR WHERE ASSEMBLY IS LOCATED ABOVE INACCESSIBLECONSTRUCTIONEXTEND HOSE END TO WITHIN 12" OF CEILING ACCESS DOOR LOCATIONA. PROVIDE AIR VENT AT ALL HIGH POINTS OF PIPING AND WHERE NOTED ON DRAWINGS.6" HIGH AIR CHAMBER SAME SIZE AS PIPINGUP TO 2" DIA. MAXIMUM. 2" DIA. FOR LARGER PIPING.RISERNOTE:[ ] CURB FURNISHED BY HVAC DIVISION.[ ] CURB INSTALLED BY DIVISION 1.[ ] CURB BY BUILDING MANUFACTURER.[ ] BY HVAC DIVISION.[ ] BY DIVISION 1.[ ] BY BUILDING MANUFACTURER.[ ] GRAVITY OPERATED BACKDRAFTDAMPER.[ ] MOTOR OPERATED BACKDRAFTDAMPER.OPENING ANDANGLE FRAMECONNECT DUCT TOCURB/DAMPER FRAME AS REQ'D4"INSULATE PLENUM ANDFIRST 10FT. OF DUCT.EXHAUST-BRANCH DUCT SIZE & QTY PER PLANSEXHAUST DUCT RISER, FULL SIZE OF CURB INLET OPENINGDRIP PAN FORMED BY SOLDERING SEAMS WATER-TIGHT, 3" DEEPFANROOF CURBROOFINGJOIST OR BEAM6"KEYED NOTES:312123FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M501DETAILS05/01/202111614/ COB #2013TAMCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister DriveSCALE: NOT TO SCALEM5011Flexible Duct To DiffuserSCALE: NOT TO SCALEM5014VAV Terminal UnitSCALE: NOT TO SCALEM5015Hanger Support FasteningSCALE: NOT TO SCALEM5016Manual Air VentSCALE: NOT TO SCALEM5012UPBLAST FUME EXHAUST FAN# Description Date PIPE SIZE(IN)141 -200105 -14061 -10440 -60PIPE INSULATION SCHEDULEFLUID TEMPRANGE (°F)CONDUCTIVITYBTU*IN/(hr*FT2*°F)MEAN RATINGTEMP (°F)INSULATION THICKNESS(IN)1.52.01.0N/A1.01.50.5.051.51.0125125100100N/A75757575750.25 -0.290.25 -0.290.21 -0.280.21 -0.28N/A0.21 -0.270.21 -0.270.20 -0.260.20 -0.260.20 -0.26< 1-1/2 1-1/2 to </= 8< 1-1/2 1-1/2 to </= 8ALL < 1-1/2 1-1/2 to </= 8< 11 to </= 8> 8< 40NOTES:1. FOR EXTERIOR PIPING, PROVIDE ADDITIONAL PROTECTIVE JACKET, MATERIAL AS SPECIFIED.2. PROVIDE HEAT TRACING WHERE NOTED, AND INSULATION FOR HEAT-PUMP PIPING SERVING ROOFTOP UNITS.3. PROVIDE FACTORY APPLIED ASJ FOR ALL FIBERGLASS PIPE INSULATION.4. PROVIDE VAPOR BARRIER ON ALL SYSTEMS OPERATING BELOW AMBIENT TEMPERATURE.5. PROVIDE DOUBLE THICKNESS INSULATION FOR EXTERIOR, ABOVE-GRADE PIPING.6. PROVIDE PVC JACKET ON ALL INTERIOR, INSULATED, EXPOSED PIPING. PIPING EXPOSED IN MECHANICAL ROOM DOES NOT REQUIRE A PVC JACKET UNLESS NOTED ON PLANS. 7. PIPE INSULATION SHALL BE PAINTABLE.SERVICEUNCONDITIONEDSPACER-6WITHINBUILDINGENVELOPEDUCT INSULATION SCHEDULEMINIMUM INSTALLED "R" VALUE ( CLIMATE ZONES 5 THROUGH 8)NOTES:1. ENERGY CODE DOES NOT REQUIRE INSULATION, HOWEVER INSULATION IS REQUIRED TO PREVENT CONDENSATION ON DUCTWORK. PROVIDE A MINIMUM THICKNESS. 2. PROVIDE R-12 IF DUCTED TO AN ENERGY RECOVERY UNIT.3. PROVIDE R-6 IF DUCTED TO AN ENERGY RECOVERY UNIT.4. PROVIDE FIELD APPLIED JACKET.INSIDE BUILDING ENVELOPEINDIRECTLYCONDITIONEDSPACECONDITIONEDSPACER-12OUTSIDEBUILDINGENVELOPE(NOTE 4)R-12R-6R-6R-6NONER-6R-5R-12R-12NONE (NOTE 3)R-6R-5R-6NONEHEATING AND/OR AIR-CONDITIONING SUPPLY AIRHEATING AND/OR AIR-CONDITIONING RETURN AIRHEAT PUMP SUPPLY AIRTRANSFER AIR DUCTSOUTSIDE-AIR DUCTS, PLENUMS, MIXING BOXESLOUVER BLANK-OFFSRELIEF-AIR DUCTS AND PLENUMSEXHAUST AIR DUCTS LEAVING ENERGY RECOVERY UNITVENTILATION SUPPLY AIR BELOW 60 DEG FVENTILATION SUPPLY AIR ABOVE 60 DEG FNONER-5R-12R-5NONER-12R-12R-12R-12R-12R-12R-12R-12R-12N/AR-12R-12R-12R-12NONENONENONENONENONE (NOTE 3)R-6R-1.3R-6R-6AIR-CONDITIONING SUPPLY AND RETURN AIR THROUGH POOL AREASVENTILATION SUPPLY AIR BELOW 60 DEG F, THROUGH POOL AREASR-1.3R-6R-12R-12R-12R-6R-1.3R-6R-6VENTILATION SUPPLY AIR ABOVE 60 DEG F, THROUGH POOL AREASCONCEALED KITCHEN EXHAUST DUCTWORKR-1.3R-6R-12R-12R-12R-12R-12DEFINITIONS:1. UNCONDITIONED SPACE:INCLUDES SPACES NOT DIRECTLY HEATED OR COOLED SUCH AS VENTED AND UNVENTED ATTICS, SHAFTS AND VENTED CRAWLSPACES.2. INDIRECTLY CONDITIONED SPACE:SPACES THAT ARE NOT CONDITIONED DIRECTLY BUT HAVE UNINSULATED SURFACES SEPARATING THEM FROM CONDITIONED SPACES AND ARE INCLUDED WITHIN THE INSULATED ENVELOPE OF THE BUILDING.3. CONDITIONED SPACE:AN AREA OR ROOM WITHIN A BUILDING BEING HEATED OR COOLED, OR WITH A FIXED OPENING DIRECTLY INTO AN ADJACENT CONDITIONED SPACE.EXHAUST AIR DUCTSR-6R-5R-5R-12N/ANONE (NOTE 2)NONE (NOTE 2)N/A (NOTE 2)N/A (NOTE 2)SEE NOTE 1SEE NOTE 1SEE NOTE 1SEE NOTE 1NONENONEFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M601SCHEDULES05/01/202111614/ COB #2013TAMCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister DriveVAV TERMINAL UNIT SCHEDULEMARKINLET SIZE (IN)CFM HEATING COIL MAXDISCHARGENCREMARKSMAX MIN CFM MBH EAT (°F) LAT (°F) GPMTU S1 12 700 300 300 14.5 55 100 1.5 25 1,2NOTES:1. PROVIDE COIL & ROWS SIZED FOR 130 DEG F SUPPLY REHEAT WATER AND 100 DEG F RETURN.3. BOD PRICE DESV.GRILLE AND DIFFUSER SCHEDULEMARK MANUFACTURER MODEL FRAME FINISHEA PRICE 530 SEE PLANS WHITESA PRICE SCDA SEE PLANS WHITESB PRICE SCS SEE PLANS WHITENOTES:1. PROVIDE OPPOSED BLADE DAMPER FOR ALL DIFFUSERS ANDREGISTERS.2. COORDINATE MOUNTING FRAME FOR EACH APPLICATION.3. SUBMIT COLOR CHART TO ARCHITECT FOR REVIEW.4. MAX N.C. LEVEL OF NC-25.5. SUBMIT COMPLETE CHART FOR EACH ROOM WITH ALL INFORMATION.6. SB TYPE: LINEAR 4'-0" LENGTH, (2) 3/4" SLOTS W/ PLENUM.# Description Date AIAV: SETPOINTBIAOAOAV: FLOW FEEDBACK (CFM)AV: POSITION FEEDBACK(%)AV: FLOW SETPOINT (CFM)AOAIAV: TEMP RISE DEG FAOAV: FLOW FEEDBACK (CFM)AV: POSITION FEEDBACK(%)AV: FLOW SETPOINT (CFM)SYSTEM DESCRIPTIONVARIABLE VOLUME SUPPLY BOX (VAV-#) COOLINGBASEBOARD RADIATION HEATINGCONTROL FOR INTERIOR VAV BOXES WITHOUT ASSOCIATED BASEBOARD HEAT IS THE SAME WITH DELETION OF BASEBOARD HEAT POINTS AND SEQUENCES.GENERALSYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND CONTROL SYSTEM (BACS).ALL SETPOINTS SHALL BE ADJUSTABLE.THE BACS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR SEVEN DIFFERENT DAILY SCHEDULES PER WEEK.THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.BASIS OF DESIGN MINIMUM COOLING AND HEATING AIRFLOW SETPOINT IS TO BE 30% OF THE MAXIMUM COOLING AIRFLOW SETPOINT.SETPOINTSSPACE COOLING TEMPERATURE SETPOINTS:OCCUPIED: 75 °F +/-1.5 °FOCCUPIED SETBACK: 75 °F +3 °FUNOCCUPIED: 75 °F +6 °FSPACE HEATING TEMPERATURE SETPOINTS:OCCUPIED: 70 °F +/-1.5 °FOCCUPIED SETBACK: 70 °F -3 °FUNOCCUPIED: 70 °F -6 °FSV AIRFLOW RATE: CFM HEATING: AS SCHEDULEDCFM COOLING: AS SCHEDULEDEV AIRFLOW RATE: CFM HEATING: AS SCHEDULEDCFM COOLING: AS SCHEDULEDMINIMUM SPACE OCCUPANCY INDEX TIME: 30 MINUTESZONE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRISPACE OCCUPANCYZONE OCCUPANCY SHALL BE DETERMINED BASED ON A COMBINATION OF A TIME OF DAY SCHEDULE AND A SPACE OCCUPANCY SENSOR.DURING THE SCHEDULED OCCUPANCY PERIOD, THE ZONE SHALL BE INITIALLY INDEXED TO OCCUPIED AND OPERATE FOR A MINIMUM OF 30 MINUTES, AT WHICH TIME THE SPACE OCCUPANCY SENSOR SHALL INDEX THE SPACE BETWEEN OCCUPIED AND OCCUPIED SETBACK MODE.IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, AS DETERMINED VIA THE OCCUPANCY SENSOR, THE ZONE SHALL BE INDEXED TO OCCUPY FOR THE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO UNOCCUPIED WHEN OCCUPANCY IS NOT SENSED FOR A PERIOD OF 30 MINUTES.FOR ZONES WITH MULTIPLE SPACES, AN OCCUPANCY SENSOR SHALL BE PROVIDED IN EACH SPACE, AND ZONE OCCUPANCY SHALL BE BASED ON OCCUPANCY INPUTS FROM ANY OF THE SPACE OCCUPANCY SENSORS ASSOCIATED WITH THAT ZONE.ZONE TEMPERATURE CONTROLTEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OF PROGRAMMED SCHEDULE AND A SPACE OCCUPANCY SENSOR.FOR ZONES WITH MULTIPLE SPACES, ZONE TEMPERATURE SHALL BE DETERMINED BASED ON AN AVERAGE OF ALL SPACE TEMPERATURES ASSOCIATED WITH THE ZONE.OCCUPIED HEATING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD AND THE ZONE TEMPERATURE FALLS BELOW THE OCCUPIED SET POINT, THE VAV DAMPER SHALL MODULATE TOWARD THE MINIMUM POSITION AND ON FURTHER DEMAND FOR HEATING THE REHEAT COIL CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN THE SET POINT. WHEN THE COIL VALVE IS FULLY OPEN AND THERE IS FURTHER DEMAND FOR HEAT, THE VAV CONTROLLER SHALL REVERSE SEQUENCE TO ALLOW THE UNIT DAMPER TO OPEN AS REQUIRED TO SUPPLY MORE WARM AIR TO THE ZONE. OCCUPIED COOLING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD AND THE ZONE TEMPERATURE RISES ABOVE THE OCCUPIED SET POINT, THE REHEAT COIL VALVE SHALL BE CLOSED AND THE VAV DAMPER SHALL MODULATE TOWARD THE OPEN POSITION AS REQUIRED TO MAINTAIN THE SET POINT.UNOCCUPIED HEATING: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD AND THE ZONE TEMPERATURE FALLS BELOW THE UNOCCUPIED SET POINT, THE VAV DAMPER SHALL MODULATE TOWARD THE MINIMUM POSITION, AND ON FURTHER DEMAND THE REHEAT COIL CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN THE SET POINT. WHEN THE COIL VALVE IS FULLY OPEN AND THERE IS FURTHER DEMAND FOR HEAT, THE VAV CONTROLLER SHALL REVERSE SEQUENCE TO ALLOW THE UNIT DAMPER TO OPEN AS REQUIRED TO SUPPLY MORE WARM AIR TO THE ZONE.UNOCCUPIED COOLING: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD AND THE ZONE TEMPERATURE RISES ABOVE THE UNOCCUPIED SET POINT, THE REHEAT COIL VALVE SHALL BE CLOSED AND THE VAV DAMPER SHALL MODULATE TOWARD THE OPEN POSITION AS REQUIRED TO MAINTAIN THE SET POINT.IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY.OCCUPIED SETBACK: IF THE SPACE BECOMES UNOCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD THEN THE SPACE TEMPERATURE SETPOINT WILL CHANGE TO THE OCCUPIED SETBACK SETPOINT FOR HEATING OR COOLING.dTsaOSHWSF.L.FIN RADIATIONTO OTHER ROOMSON ZONECOMMODBACnet / ARCNETOR BACnet / MSTPREHEAT COILTTO OTHER ROOMSON ZONECOMMODBACnet / ARCNETOR BACnet / MSTPTO AHUFROM AHUWHERE EXISTING OR PROVIDED BY DIV. 26FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910M701CONTROLSCHEMATICS05/01/202111614/ COB #2013TAMCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister DriveSCALE: NOT TO SCALEM7011Baseboard Heating And Variable Air Volume Cooling Zone ControlDESCRIPTIONHARDWARE POINTS SOFTWARE POINTSSHOW ONGRAPHICNOTESBI BO AI AO AV BV SCHTRENDALARMBACS/DDC DESCRIPTIONSUPPLY VAV DAMPER POSITION COMMAND X X XRETURN VAV DAMPER POSITION COMMAND X X XSUPPLY VAV AIRFLOW FEEDBACK (CFM) X X X 10% FLOW DEVIATION FROMSETPOINTX BACnet MSTPNETWORK POINTCOIL TEMPERATURE RISE DEG F X X X 5 DEG F TEMPERATURE RISEWHEN HEATING VALVE ISCOMMANDED CLOSEDX BACnet MSTPNETWORK POINTRETURN VAV AIRFLOW FEEDBACK (CFM) X X X 10% FLOW DEVIATION FROMSETPOINTX BACnet MSTPNETWORK POINTZONE TEMPERATURE SETPOINT X X XSUPPLY VAV AIRFLOW SETPOINT (CFM) X X X BACnet MSTPNETWORK POINTRETURN VAV AIRFLOW SETPOINT (CFM) X X X BACnet MSTPNETWORK POINTZONE TEMPERATURE X X X ± 4°F FROM SETPOINT XSUPPLY VAV POSITION FEEDBACK (%) X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTPNETWORK POINTRETURN VAV POSITION FEEDBACK (%) X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTPNETWORK POINTHEATING COIL VALVE POSITION COMMAND X X X XLEAVING AIR TEMPERATURE X X XBASEBOARD RADIATION CONTROL VALVEPOSITION COMMANDX X X FAIL LASTZONE OCCUPANCY X X X# Description Date DEMOLITION KEYED NOTES:EXISTING WALL MOUNTED RECELTAPCLES, DISCONNECTS, DATA PORTS, AND ELECTRICAL FIXTURES TO BE REMOVED . REMOVE ALL ASSOCIATED CIRCUITING AND RACEWAY BACK TO SOURCE. CONTRACTOR SHALL VERIFY EXACT QUANTITIES IN THE FIELD.LIGHT FIXTURES ARE EXISTING TO REMAIN.EXISTING SECURITY SYSTEM CONTROL BOX TO BE REMOVED AND RETURNED TO OWNER.ALTERNATE #2 EXISTING SECURITY SYSTEM CONTROL BOX TO BE MOVED TO COMMUNICATIONS ROOM 105C.1234FIVE RECPETACLES IN WIREWAY1ALTERNATE #2234A. COORDINATE SCHEDULING OF REMOVAL WORK WITH OWNER OR OWNER'S REPRESENTATIVE, PHASING DRAWINGS AND REQUIREMENTS.B. VERIFY LOCATIONS AND SCHEDULE OF REMOVAL WORK IN ALL AREAS PRIOR TO STARTING WORK. REFER TO OTHER TRADES DRAWINGS AND COORDINATE REMOVAL WORK WITH OTHER TRADES DIVISION CONTRACTORS PRIOR TO STARTING.C. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES WITHIN SPACES INDICATED. D. PROVIDE ALL REQUIRED WIRING AND TEMPORARY CONNECTIONS NECESSARY TO MAINTAIN ELECTRICAL CONTINUITY OF ALL EXISTING ELECTRICAL EQUIPMENT, RECEPTACLES, DEVICES, LIGHTING FIXTURES AND DEVICES, FIRE ALARM EQUIPMENT AND DEVICES THAT ARE TO REMAIN DURING ALL STAGES OF WORK.E. PROVIDE TEMPORARY SUPPORT FOR ALL EXISTING RACEWAYS AND BRANCH CIRCUITRY TO REMAIN DURING ALL STAGES OF WORK.F. PROTECT ALL EXISTING ELECTRICAL EQUIPMENT, RECEPTACLES, DEVICES, LIGHTING FIXTURES AND DEVICES, FIRE ALARM EQUIPMENT AND DEVICES, TELECOMMUNICATIONS EQUIPMENT AND DEVICES, SECURITY (CCTV) EQUIPMENT AND DEVICES AND ALL ASSOCIATED RACEWAYS AND BRANCH CIRCUITRY TO REMAIN FROM DAMAGE AND DEBRIS DURING ALL STAGES OF WORK.G. ALL ELECTRICAL DEVICES AND EQUIPMENT SHOWN ON FLOOR PLANS ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.H. OBTAIN A LIST FROM THE OWNER, OR THE OWNER’S REPRESENTATIVE, OF ANY ITEMS THEY WISH TO RETAIN. DISCONNECT, REMOVE, INVENTORY AND DELIVER ALL ITEMS TO OWNER DESIGNATED ON-SITE LOCATION IN GOOD OPERATING ORDER. PROVIDE A TRANSMITTAL OF THE ITEMS INVENTORIED TO THE OWNER OR OWNER'S REPRESENTAIVE. ALL OTHER ITEMS SHALL BE REMOVED FROM THE PROJECT SITE COMPLETE AND DISPOSED OF IN THE APPROPRIATE MANNER.I. EXISTING CONDUIT AND BRANCH CIRCUTRY LOCATED IN NON-ACCESSIBLE WALLS/FLOORS, JUNCTION BOXES SHALL BE ABANDON IN PLACE AS FOLLOWS:• DISCONNECT BRANCH CIRCUIT AT SOURCE.• REMOVE SURFACE AND FLOOR BOX(ES).• PROVIDE PRIMED STEEL BLANK PLATE ON ANY FLUSH OUTLET BOX(ES) TO REMAIN.• CUT BACK RACEWAY SUBS SO AS TO BE RECESSED INTO FLOOR/WALL.• PATCH ALL ANCHOR HOLES FROM REMOVED EQUIPMENT. BOXES, AND RACEWAYS.J. REMOVE AND REPLACE EXISTING DOWLIGHTS AND SWITCHES IN MAP ROOM 1134.G. REMOVE ALL UNUSED IT CABLING BACK TO THE SOURCE.GENERAL DEMOLITION NOTESFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910ED101FIRST FLOORDEMOLITIONPLAN05/01/202111614/ COB #2013AuthorCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive3"SCALE: 1/4" = 1'-0"ED1011DEMO FIRST FLOOR PLAN RM 1149# Description Date ISSUE:DATE:DRAWN BY:CHECKED BY:SCALE:PROJECT NO.SHEET TITLESHEETDRAWING NO.ALTERATION OF THIS DOCUMENTEXCEPT BY A LICENSED DESIGNPROFESSIONAL, IS A VIOLATION OF NEW YORK STATE EDUCATIONAL LAW.OFFS ENGINEERING,DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044Enter address hereR:\Revit MEP 2012\Templates\S&A_Mechanical.rte10/5/2011 4:16:29 PMOwnerProject NameSK-M201/01/2019AuthorCheckerProject NumberUnnamedMARK DATE DESCRIPTION??PLAN DETAILBUILDING SECTIONDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDEXTENT OF DETAILEXTENT OF DETAILA1B1C1D1E1A2B2C2D2E2A3B3C3D3E3A4B4C4D4E4A5B5C5D5E5A6B6C6D6E6DETAIL NUMBERDETAIL SCALEDETAIL NAMEDETAIL NUMBERPLAN SETUPSHEET NUMBER WHERE DETAIL IS LOCATEDCAUTION: THESE DOCUMENTS WERE DIGITALLY PRODUCED AND/OR REPRODUCED. CONFIRM REDUCTION OR MAGNIFICATION USING DIMENSIONAL 3"-LONG LINE IN TITLE BARS. IF SCALING DRAWINGS FOR APPROXIMATE DIMENSIONS, ALTERNATE ARCHITECTURAL SCALES MAY BE USED AS FOLLOWS:DOCUMENT REDUCTION/MAGNIFICATION SCALEIF LINE MEASURES 2”(67% COPY):USE 3/16th SCALE ON 1/8”=1’-0”DWGUSE 3/8th SCALE ON 1/4”=1’-0”DWGIF LINE MEASURES 1.5”(50% COPY):USE 1/16th SCALE ON 1/8”=1’-0”DWGUSE 31/8th SCALE ON 1/4”=1’-0”DWG3"3"????XXXX" = X"NOTES:FSCFINISHED FLOOR1'-6"1'-6"1'-6"DUPLEX RECEPTACLEDESK TOPTELEPHONEDATA OUTLET2'-0"EXTERIOR DUPLEXRECEPTACLE4'-0"DUPLEX RECEPTACLEMECH RMLIGHT SWITCH4'-0"PBGYM DOOR PUSHBUTTONFSEE NOTE 3FIRE ALARMPULLSTATIONWALL MOUNTEDTELEPHONE/INTERCOM PHONESEE NOTE 3F5'-0"DISCONNECTSWITCH6'-0"PANELBOARDFIRE ALARMA/V DEVICEFIRE ALARMVISUAL DEVICESEE NOTE 4EMERGENCYLIGHTCLOCKINTERCOMSPEAKERSEE NOTE 51. IN LOCATIONS WHERE SIMILAR DEVICES ARE MOUNTED AT THE SAME HEIGHT DEVICES SHALL BE PROPERLY "GANGED" AND SHALL HAVE ASINGLE COVER PLATE.2. IN LOCATIONS WHERE DIFFERENT DEVICES ARE MOUNTED AT DIFFERENT HEIGHTS WITHIN FOUR FEET OF ONE ANOTHER. DEVICES SHALL BE MOUNTED SUCH THAT THEY HAVE A COMMON CENTER LINE. IF THERE ARE THREE OR MORE DEVICES THE CONTRACTOR SHALL REQUEST A DETAIL FROM THE ARCHITECT.3. 42" MINIMUM TO 48" MAXIMUM AND WITHIN 5FT FROM DOOR. 4. 80" OR, AT SHALLOW CEILING INSTALLATIONS, WITHIN 6" OF FINISHED CEILING. VERIFY WITH ENGINEER.5. 90" AFF, OR, AT SHALLOW CEILING INSTALLATIONS, TOP OF UNIT WITHIN 6" OF FINISHED CEILING.SEE NOTE 3A.REFER TO ARCHITECTURAL DRAWINGS FOR EXTENT OF BASE BID NEW CONSTRUCTION AND RENOVATED AREAS, PHASING REQUIREMENTS AND ALTERNATES.PROVIDE MATERIALS AND LABOR FOR COMPLETE, FUNCTIONAL SYSTEMS. COORDINATE WIRING AND CONNECTION REQUIREMENTS FOR EQUIPMENT. MATERIALS, EQUIPMENT, CONDUCTORS, WIRING DEVICES, ETC. SHALL BE NEW AND UL-LISTED, SUITABLE FOR LOCATION AND FUNCTION.COORDINATE EXACT LOCATION OF ELECTRICAL BOXES AND RACEWAY PRIOR TO ROUGH-IN. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS.PROVIDE TEMPORARY POWER AND LIGHTING. PROVIDE TEMPORARY ELECTRICAL CIRCUITRY AND CONNECTIONS AS REQUIRED TO MAINTAIN SERVICES.VERIFY SCOPE AND PHASING OF DEMOLITION WORK FOR AREAS TO BE ABATED AND RENOVATED. PROTECT EXISTING CIRCUITRY SERVING ADJACENT AREA/EQUIPMENT WHICH WILL REMAIN IN USE. PROVIDE SUPPORT AND TEMPORARY CONNECTIONS/RE-ROUTING AS REQUIRED. REFER TO ARCHITECTURAL DRAWINGS INDICATING REMOVAL SCOPE OF WORK. CONTRACTOR FOR DIVISION 26 SHALL DISCONNECT AND REMOVE BRANCH CIRCUITRY, LIGHT FIXTURES, WIRING DEVICES, CLOCKS, SPEAKERS, TELEPHONES AND RESPECTIVE SYSTEM WIRING/CABLING COMPLETE. REMOVALS SHALL INCLUDE ALL ELECTRICAL COMPONENTS IN/ON WALLS THAT ARE TO BE REMOVED. MAINTAIN CIRCUITRY TO EQUIPMENT AND DEVICES THAT ARE TO REMAIN.FIRE STOP PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS WITH FIRE STOP MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF WHICH IT IS PENETRATING. SOUND TRANSFERENCE: FLUSH WALL MOUNTED ELECTRICAL BOXES MOUNTED IN COMMON WALLS BETWEEN ADJACENT ROOMS, SHALL BE INSTALLED INDEPENDENT OF EACH OTHER; EACH WITH SEPARATE CONDUIT RISER(S). NIPPLING OF FLUSH WALL MOUNTED ELECTRICAL BOXES NOT ALLOWED. WHERE ELECTRICAL BOXES ARE MOUNTED BACK TO BACK, PROVIDE INSULATION BETWEEN BOXES. GROUNDING REQUIREMENTS1. ALL GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLES 250.2. ALL INSULATED GROUND CONDUCTORS SHALL BE GREEN. PROVIDE EQUIPMENT GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT.3. PROVIDE GROUNDING PER EQUIPMENT MANUFACTURER REQUIREMENTS.CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS:1. VARIOUS PIECES OF EQUIPMENT WILL BE FURNISHED TO THE PROJECT SITE AND INSTALLED BY OTHER DIVISIONS.2. PROVIDE ROUGHING-IN AND FINAL CONNECTIONS AS REQUIRED IN ACCORDANCE WITH EQUIPMENT INSTALLATION INSTRUCTIONS.3. BEFORE PROCEEDING WITH THE WORK, OBTAIN FULL INFORMATION REGARDING ROUGH-IN MEASUREMENTS, EQUIPMENT LAYOUTS, ELEVATIONS, TRIM BEING FURNISHED, AND OTHER NECESSARY DATA.4. UPON REQUEST, CONSTRUCTION MANAGER WILL PROVIDE THIS DIVISION WITH DIAGRAMS, PHOTOGRAPHS, DRAWINGS, AND/OR SPECIFICATIONS AND OTHER COMPLETE DESCRIPTIVE DATA. DO NOT ROUGH WITHOUT APPROVED LAYOUT FROM CONSTRUCTION MANAGER.5. PROVIDE ACCESSORIES SO THAT CONNECTIONS MAY BE MADE IN A MANNER THAT SHALL MEET ALL REGULATIONS AND CODES.6. SEE APPROPRIATE SECTIONS OF THIS DIVISION'S SPECIFICATIONS FOR MATERIALS AND METHODS.USE OF SHALLOW FLUSH MOUNT ELECTRICAL BOXES SHALL BE PERMITTED WHERE DEPTH OF WALL CAVITY/FURRING IS LESS THAN 2 1/2" AS INDICATED ON ARCHITECTURAL DRAWINGS.CONCEAL ALL ADDED CONDUITS, EXPOSED CONDUIT INSTALLATION IS UNACCEPTABLE UNLESS PRIOR APPROVAL IS GIVEN BY ARCHITECT. ANY EXPOSED CONDUIT INSTALLATION SHALL BE PAINTED TO MATCH ADJACENT WALL FINISH.REFER TO T SERIES AV DRAWINGS AND COORIDINATE ELECTRICAL REQUIREMENTS.B.GENERAL NOTESC.D.E.F.G.H.I.J.J.X1X2EXIT SIGN LIGHT FIXTURE WITH CONNECTION TO EMERGENCY POWER. COORDINATE TYPE AND MOUNTING. PROVIDE ARROWS WHERE INDICATED. DESCRIPTIONSYMBOLLIGHTING SYMBOLSDLED LIGHT FIXTURE, SUBSCRIPT D = FIXTURE TYPE, REFER TOSPECIFICATIONS AND LIGHT FIXTURE SCHEDULE.EMTVFCAFFACGNFGFGROUND FAULT INTERUPT DEVICENON-FUSEDGROUNDABOVE FINISHED FLOORVARIABLE FREQUENCY CONTROLLERABOVE COUNTER - 6"ABOVE COUNTERTOP OR BACKSPLASHELECTRIC METALLIC TUBINGEWC ELECTRIC WATER COOLERED13aSNIGHT LIGHTNLAT UNITAUFIRE SMOKE DAMPER. PROVIDE CONNECTIONS AS INDICATEDFSOS1PCPANELBOARD, 208/120V - SURFACE MOUNTEDBRANCH CIRCUIT HOMERUN: 2 #12, 1 #12G, 1/2"C TO PANELBOARD CIRCUIT NUMBER AS INDICATED UNLESS OTHERWISE NOTED.B1 / 12 = PANEL NAME / CIRCUIT NUMBERDESCRIPTIONSYMBOLABBREVIATIONSPHOTOCELL.WALL MOUNTED OCCUPANCY SENSOR, 1 = TYPE, REFER TOSPECIFICATIONS.WALL SWITCH, 3 = THREEWAY, a = FOR LIGHTING FIXTUREMARKED SAME.CEILING MOUNTED OCCUPANCY SENSOR, 3 = TYPE, REFER TOSPECIFICATIONS.SYMBOLGENERAL SYMBOLSREFERS TO KEYED DEMOLITION NOTE ON RESPECTIVE DRAWINGDESCRIPTIONDESCRIPTIONCOMBINATION MAGNETIC STARTERFUSED DISCONNECT SWITCHNON-FUSED DISCONNECT SWITCHSYMBOLSECONDARY SERVICE SYMBOLSPANELBOARD, 208/120V - RECESSED MOUNTEDMOTOR CONNECTION. EQUIPMENT AND CIRCUITRY AS INDICATED ON PLANS AND KEYED TO ELECTRICAL EQUIPMENT AND CONTROL SCHEDULE OR AS OTHERWISE NOTED.SFFFFIRE ALARM CONNECTION. SUBSCRIPT IDENTIFIES TYPE:FS - FIRE SMOKE DAMPER CONNECTIONFA - FIRE ALARM SHUTDOWN OF EQUIPMENTFIRE ALARM SYSTEM ANNUNCIATOR PANELSYMBOLFIRE ALARM SYSTEM CONTROL PANEL (FACP)FIRE ALARM SYMBOLSDESCRIPTIONFIRE ALARM SYSTEM THERMAL DETECTORFIRE ALARM SYSTEM MANUAL PULL STATIONFIRE ALARM SYSTEM SMOKE DETECTORFIRE ALARM SYSTEM SMOKE DETECTOR, DUCT MOUNTFIRE ALARM SYSTEM COMBINATION VISUAL AND AUDIBLEINDICATING DEVICE, WALL MOUNTED. STROBE INTENSITY 75CANDELAS, UNLESS INDICATED OTHERWISE. SUBSCRIPTS: WP - WEATHERPROOF, WG - WIREGUARDFIRE ALARM SYSTEM VISUAL (ONLY) INDICATING APPLIANCE, WALL MOUNTED, INTENSITY 75 CANDELA UNLESS INDICATED OTHERWISEFACPFAAFSWPFIRE ALARM SYSTEM - BEAM DETECTOR TYPE, TRANSMITTERTRBRDUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDACG.F.C.I. DUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDGF/ACGFDOUBLE DUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDACWEATHERPROOF DUPLEX RECEPTACLE OUTLETWPFLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE OUTLETISOLATED GROUND DUPLEX RECEPTACLE OUTLETIGSPECIAL PURPOSE RECEPTACLE OUTLET, NEMA CONFIGURATION TO MATCH PLUGBRANCH CIRCUITRY: 2 #12, 1 #12G, 1/2"C UNLESS OTHERWISE NOTEDB1/12FFIRE ALARM SYSTEM COMBINATION VISUAL AND AUDIBLEINDICATING DEVICE, CEILING MOUNTED. STROBE INTENSITY 75CANDELAS, UNLESS INDICATED OTHERWISE. SUBSCRIPTS: WP - WEATHERPROOF, WG - WIREGUARDFIRE ALARM SYSTEM VISUAL (ONLY) INDICATING APPLIANCE, CEILING MOUNTED, INTENSITY 75 CANDELA UNLESS INDICATED OTHERWISEFDUPLEX RECEPTACLE OUTLET, SURACE MOUNTED FIRE ALARM SYSTEM - BEAM DETECTOR TYPE, RECEIVERSSDEVICE SYMBOLSDESCRIPTIONSYMBOLFIRE ALARM SYSTEM - SPRINKLER FLOW SWITCHFSFIRE ALARM SYSTEM - SPRINKLER TAMPER SWITCHTSDSD4 PORT (QUAD) USB CHARGER OUTLET WAPDESCRIPTIONSYMBOLVOICE/DATA SYMBOLSDATA OUTLET, WALL MOUNTED(2) CAT 6 CABLES / (2) RJ-45 JACKS UNLESS NOTED OTHERWISETYPE WAP (WIRELESS ACESS POINT) DATA OUTLET, CEILING MOUNTED(1) CAT 6A CABLE / (1) RJ-45 JACKWALL PHONE - (1) CAT 6 CABLE / (1) RJ-45 JACKE1REFERS TO KEYED NOTE ON RESPECTIVE DRAWINGHP-012FIRE ALARM SYSTEM MAGNETIC DOOR HOLD OPENETR EXISTING TO REMAIN3OSSFIRE ALARM SYSTEM SMOKE DETECTOR, ELEVATOR RECALLRJJUNCTION BOXAUTOMATIC TRANSFER SWITCHATSPANELBOARD, 480/277V - SURFACE MOUNTEDPANELBOARD, 480/277V - RECESSED MOUNTEDDIMMER SWITCHJMS - CEILING MOUNTED, FLUSH, DOUBLE-GANG JUNCTION BOX FOR MOTORIZED SCREEN. COORDINATE LOCATION WITH AV CONTRACTOR AND ARCHITECT. XXDATA OUTLET FOR AV EQUIPMENT, WALL MOUNTED AT 18" AFF, UNLESS NOTED OTHERWISE(4) CAT 6 CABLES / (4) RJ-45 JACKS UNLESS NOTED OTHERWISEAV/4SS - WALL MOUNTED, FLUSH, SINGLE-GANG JUNCTION BOX FOR PROJECTOR SCREEN SWITCH. MOUNT AT 45" AFF COORDINATE LOCATION WITH AV CONTRACTOR AND ARCHITECT. DATA OUTLET FOR AV EQUIPMENT, WALL MOUNTED AT 78" AFF UNLESS NOTED OTHERWISE(2) CAT 6 CABLES / (2) RJ-45 JACKS UNLESS NOTED OTHERWISEAV/2AL -ASSISTIVE LISTENING TRANSMITTERAV -AUDIO VISUAL INTERFACEFP -FLAT PANEL DISPLAYPB -AV PANEL BOXCP -CONTROL PANELSCEILING MOUNTED SPEAKER.WIREMOLDFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E001DRAWINGINDEX,SCHEDULES,SYMBOL LISTS& NOTES05/01/202111614/ COB #2013ASC/JLRCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister DriveELECTRICAL DRAWING INDEXNUMBER NAMEREVISIONS# DATEED101 FIRST FLOOR DEMOLITION PLANE001 DRAWING INDEX, SCHEDULES, SYMBOL LISTS & NOTESE101 FIRST FLOOR ELECTRICAL PLANE102 SECOND & THIRD FLOOR ELECTRICAL PLANTO THE BEST OF THE ENGINEER'S PROFESSIONAL JUDGEMENT, THE DESIGN OF THIS PROJECT CONFORMS TO ALL APPLICABLE PORTIONS OF THE FOLLOWING:THE 2020 NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODETHE 2020 NEW YORK STATE ENERGY CONSERVATION CODE FOLLOWING THE COMPLIANCE PATH MARKED BELOW:ANSI / ASHRAE / IESNA 90.1IECC CHAPTER 4 [CE] PRESCRIPTIVE PROVISIONS (SECTIONS C402, C403, C404, C405, AND ONE OF THE SIX OPTIONS IN SECTION C406 AS NOTED BELOW:MORE EFFICIENT HVAC PERFORMANCE IN ACCORDANCE WITH SECTION C406.2.REDUCED LIGHTING POWER DENSITY SYSTEM IN ACCORDANCE WITH SECTION C406.3.ENHANCED LIGHTING CONTROL IN ACCORDANCE WITH SECTION C406.4.ON-SITE SUPPLY OF RENEWABLE ENERGY IN ACCORDANCE WITH SECTION C406.5.PROVISION OF A DEDICATED OUTDOOR AIR SYSTEM FOR CERTAIN HVAC EQUIPMENT IN ACCORDANCE WITH SECTION C406.6.HIGH-EFFICIENCY SERVICE WATER HEATING IN ACCORDANCE WITH SECTION C406.7.TOTAL BUILDING PERFORMANCE PROVISIONS (SECTION C407)THE BUILDING STANDARD OF THE NEW YORK STATE EDUCATION DEPARTMENTTHE 2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIESALL SYMBOLS SHOWN ARE NOT NECESSARILY USEDSCALE: NOT TO SCALEE001A3DEVICE MOUNTING HEIGHTS# Description Date s s OS295" AFF95" AFF95" AFFASSISTED LEARNING TRANSMITTER3L1LG/1EX. PANELL1LGMICROSCOPYCLASSROOM1149MICROSCOPE TABLE4L1LG/2L1LG/3L1LG/4L1LG/7L1LG/6L1LG/5L1LG/8567A. VERIFY EXACT LOCATION OF RECEPTACLES & DATA OUTLETS WITH ARCHITECT, ARCHITECT'S ELEVATION DRAWINGS, AV CONSULTANT AND TA-SERIES DRAWINGS PRIOR TO ROUGH-IN.B. PROVIDE SEPARATE NEUTRAL AND GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT INDICATED.C. VERIFY EXACT LOCATION OF LIGHT FIXTURES WITH ARCHITECT AND ARCHITECT'S REFLECTED CEILING PLANS AND ELEVATION DRAWINGS PRIOR TO ROUGH-IN.D. CIRCUIT LIGHT FIXTURES TOGETHER WITH 2#10, #10E.G. - 1/2" CONDUIT, UNLESS NOTED OTHERWISE.E. UNLESS OTHERWISE INDICATED, AT ROOMS/LOCATIONS WHERE DIMMING SWITCHES ARE INDICATED PROVIDE 0-10V DIMMING / LIGHTING CONTROL. COORDINATE THE 0-10V DIMMING CONTROL WITH THE 0-10V LED DRIVERS AT LIGHT FIXTURES.F. NEW CABLING WILL ROUTE TO EXISTING CIT INFRASTRUCTURE.G. EXISTING CABLE TRAYS AND PULLBOXES SHALL REMAIN ACCESSIBLE.H. WALL SPEAKER SPEAKERS AND ASSISTED LEARNING TRANSMITTER TO BE CONTROLLED FROM WALL MOUNTED DEVICE BEHIND INSTRUCTOR'S DESK. WIRING SHOULD INCASED IN RACEWAY.GENERAL NOTESKEYED NOTESREVISE EXISTING WIRING FOR EXISTING FRONT ROW LIGHT FIXTURES CLOSEST TO WESTERN WALL. ADD LIGHT SWITCH FOR SEPERATE CONTROL OF FRONT ROW LIGHT FIXTURES TO MATCH ZONES AS INDICATED. (Z#)PROVIDE WIRING AND CONNECTIONS FOR POWER AND DATA OUTLETS AT EACH DESK.PROVIDE RECEPTACLE AND DATA DROP FOR CEILING MOUNTED PROJECTOR.PROVIDE AV CABLE PATH BETWEEN INSTRUCTOR'S TABLE AND CEILING MOUNTED PROJECTOR.DESK POWER AND DATA WILL BE FED FROM WALL MOUNTED SURFACE RACEWAY.PROVIDE DATA CONNECTION FOR FUTURE DOOR SECURITY CONTROL.REMOVE AND REPLACE POWER WIRING AND DATA CABLING FOR EXISTING DISPLAY CABINETS SOUTH OF ROOM 1149. COORDINATE WITH SNEE BUILDING MANAGER.1234567MICROSCOPYCLASSROOM11491EX. PANELL1LGZ1Z1Z2 Z2 Z2 Z2Z2Z2Z2Z2Z1 Z2 Z2 Z2 Z2Z2Z2Z2Z1Z133Z1Z2FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#21022WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E101FIRST FLOORELECTRICALPLAN05/01/202111614/ COB #2013ASC/JLRCORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab Renovation112 Hollister Drive3"SCALE: 1/4" = 1'-0"E10111149 POWER & SYSTEMS PLAN3"SCALE: 1/4" = 1'-0"E10131149 LIGHTING PLAN# Description Date ELECTRICAL & TELECOM SYMBOLS WALL MOUNTED CEILING MOUNTED FLOOR MOUNTED DESCRIPTION AC DUPLEX OUTLET AC QUAD OUTLET DIRECT POWER CONNECTION TO EQUIPMENT NETWORK DATA JACK - COPPER (# OF JACKS) NETWORK DATA JACK - FIBER (# OF JACKS) TELEPHONE JACK (# OF JACKS) NETWORK DATA/TELEPHONE COMBO JACK (# OF JACKS) CABLE TELEVISION JACK JUNCTION BOX INDEX OF DRAWINGS DRAWING #DRAWING NAME TA001 COVER SHEET TA101 AV INFRASTRUCTURE DESIGN TA102 AV INFRASTRUCTURE DESIGN TA501 DETAILS & SCHEDULES TA701 AV SYSTEM DESIGN ABBREVIATIONS AFC ABOVE FINISHED CEILING LVC LOW VOLTAGE CONTROLLER AFF ABOVE FINISHED FLOOR NIC NOT IN CONTRACT AVC AUDIO VISUAL CONTRACTOR NTS NOT TO SCALE EC ELECTRICAL CONTRACTOR OFE OWNER FURNISHED EQUIPMENT EQ EQUAL RCP REFLECTED CEILING PLAN FB FLOOR BOX REV REVISION GC GENERAL CONTRACTOR SPEC SPECIFICATION HVAC HEATING & COOLING SYSTEMS SPKR SPEAKER IR INFRARED TB TABLE BOX IWE INCLUDED WITH EQUIPMENT TBD TO BE DETERMINED J JUNCTION BOX TYP TYPICAL KO KNOCK OUT VIF VERIFY IN FIELD LV LOW VOLTAGE WB WALL BOX LVC LOW VOLTAGE CONTROLLER CONNECTORS 1/4"B 1/4" TIP-RING-SLEEVE BALANCED PHNX PHOENIX (CAPTIVE SCREW) 1/4"U 1/4" TIP-SLEEVE UNBALANCED RCA RCA 3.5MM 3.5MM STEREO AUDIO RJ45 UNSHIELDED RJ45 DB9 9-PIN DSUB SERIAL SRJ45 SHIELDED RJ45 DP DISPLAY PORT TB THUNDERBOLT DVI-A DVI DIGITAL TERM TERMINAL BLOCK DVI-D DVI DIGITAL USB-A USB STANDARD TYPE A FCON F-TYPE COAX USB-B USB STANDARD TYPE B HDMI HDMI USB-C USB STANDARD TYPE C IEC IEC POWER VGA 15-PIN DSUB VGA IR INFRARED EMITTER VISCA SONY VISCA 8-PIN MINI-DIN MDP MINI DISPLAY PORT XLR XLR GENERAL NOTES & SPECIFICATIONS GENERAL NOTES 1.ALL SIZE, DIMENSION AND LOCATION INFORMATION MUST BE VERIFIED ON ARCHITECTURAL DRAWINGS. IF VALUES CONFLICT, CONTACT OWNER'S REPRESENTATIVE FOR CLARIFICATION. 2.ALL BACK BOX, OUTLET AND SWITCH MEASUREMENTS ARE SPECIFIED AND DRAWN TO VERTICAL CENTER, UNLESS OTHERWISE NOTED. 3.FLUSH MOUNTED OUTLET, PULL, AND JUNCTION BOXES SHALL BE EQUIPPED WITH COVERS WHICH OVERLAP BOX SIDES BY 3/4" TO COVER ROUGH OPENING IN FINISHED WALL. SURFACE MOUNTED BOXES SHALL BE EQUIPPED WITH COVERS OF THE SAME SIZE AS BOX. 4.CONSTRUCTION WORK SHOWN IN THESE DRAWINGS IS THE RESPONSIBILITY OF THE G.C. UNLESS OTHERWISE NOTED. 5.QUANTITIES SHOWN ON THESE DRAWINGS SHALL BE CONFIRMED BY EACH DISCIPLINE. DISCREPANCIES SHOULD BE REFERRED TO THE OWNER'S REPRESENTATIVE. 6.ALL WALL MOUNTED DEVICES SHALL HAVE 3/4" PLYWOOD WALL BLOCKING (PROVIDED BY GC) SPANNING THE WALL MOUNTING BRACKET. ELECTRICAL & TELECOM NOTES 1.ALL CABLE PATH, CIRCUIT, ROUTING AND LOCATION INFORMATION MUST BE VERIFIED ON ELECTRICAL DRAWINGS. IF VALUES CONFLICT, CONTACT OWNER'S REPRESENTATIVE FOR CLARIFICATION. 2.ALL ELECTRICAL WORK SHALL ABIDE BY NATIONAL AND LOCAL ELECTRICAL CODE. IF CODES CONFLICT, THE STRICTER OF THE TWO SHALL BE FOLLOWED. 3.G.C. SHALL PROVIDE ALL CONDUIT, PULL BOXES, JUNCTION BOXES, BOX COVERS, LOW VOLTAGE CUT-IN RINGS, J-HOOKS, BRIDLE RINGS, FLOOR BOXES, PLATES, PANELS, ENCLOSURES, POWER CIRCUITS, POWER CABLE AND POWER CONNECTIONS, UNLESS OTHERWISE NOTED. CUSTOM AV PANELS SHALL BE PROVIDED AND INSTALLED BY THE A.V.C., UNLESS OTHERWISE NOTED. 4.AC OUTLETS AND DATA/TELECOM JACKS SHOWN ON THESE DRAWINGS ARE FOR AV PURPOSES. REFER TO ELECTRICAL DRAWINGS FOR OTHER AC AND DATA/TELECOM NEEDS. 4.ALL LOW VOLTAGE AV RELATED DATA CABLES EXPOSED IN PLENUM SPACES MUST BE PLENUM RATED CABLE. 5.VERIFY FLOOR BOX LOCATION AND CONTENTS WITH ARCHITECT PRIOR TO INSTALLATION. LOCATIONS MAY CHANGE FROM ORIGINAL DRAWINGS BASED ON FINALIZED FURNITURE LAYOUTS. 6.ALL CIRCUITS POWERING AUDIO VISUAL EQUIPMENT SHALL BE DERIVED FROM THE SAME ELECTRICAL PHASE, BE DEDICATED STRICTLY TO AV DEVICES, HAVE ISOLATED GROUNDS TERMINATING AT A SINGLE POINT IN THE ASSOCIATED SUBPANEL, AND BE PROTECTED BY 20 AMP BREAKERS PER CIRCUIT, UNLESS OTHERWISE NOTED. 7.HIGH VOLTAGE CIRCUITS POWERING AUDIO VISUAL EQUIPMENT SHALL NOT BE RUN IN CLOSE PROXIMITY TO OR SHARE CIRCUITS POWERING MOTORIZED EQUIPMENT, LIGHTING SYSTEM DIMMERS OR ANY OTHER INDUCTIVE ELECTRICAL LOADS. 8.CONDUIT ROUTING TO BE COORDINATED & APPROVED ON SITE BY THE AUDIO VISUAL CONTRACTOR. 9.CONDUIT PULL BOXES SHALL BE PLACED AFTER 180 DEGREES OF BENDS AND/OR EVERY 100 FEET. 10.CONDUIT MATERIAL SHALL BE EMT STEEL CONDUIT (NOT FLEXIBLE, PVC OR ALUMINUM), ENDS SHALL BE FITTED WITH INSULATED BUSHINGS AND PULL STRING LEFT IN ALL CONDUIT. 11.CONDUIT CONTAINING AUDIO VISUAL CABLING SHALL NOT CONTAIN POWER OR DATA CABLING. AV SIGNAL CONDUIT SHALL BE SEPARATED FROM CONDUIT CONTAINING POWER CABLING BY AT LEAST 12". POWER CONDUIT MUST CROSS AV SIGNAL CONDUIT AT 90 DEGREE ANGLES. 12.BEND RADIUS FOR CONDUIT SIZED 2" OR LESS SHALL BE NO LESS THAN 6 TIMES THE INTERNAL DIAMETER. CONDUIT SIZED LARGER THAN 2" SHALL HAVE A BEND RADIUS NO LESS THAN 10 TIMES THE INTERNAL DIAMETER. 13.ALL FREE-AIR CABLES IN ACCESSIBLE CEILING SHALL BE IN J-HOOKS SECURED TO THE HARD DECK CEILING, WITH NO MORE THAN 60" SPACING BETWEEN HANGERS. HVAC NOTES 1.HVAC SUPPLY VENTS SHALL NOT BE INSTALLED IN THE CEILING BETWEEN THE PROJECTOR AND PROJECTION SCREEN TO PREVENT THERMAL ARTIFACTS IN PROJECTED IMAGE. 2.HVAC VENTS SHALL NOT BE INSTALLED NEXT TO HANGING (WALL OR CEILING MOUNTED) PROJECTION SCREENS TO PREVENT SCREEN MOVEMENT. AUDIO VISUAL INSTALLATION NOTES 1.ALL AUDIO VISUAL EQUIPMENT, CABLING, DEVICE MOUNTING AND TERMINATIONS SHOWN IN THESE DRAWINGS WILL BE PROVIDED BY THE AUDIO VISUAL CONTRACTOR, UNLESS OTHERWISE NOTED. 4.ALL LOW VOLTAGE AV CABLES EXPOSED IN PLENUM SPACES MUST BE PLENUM RATED CABLE. 5.ALL CABLES SHALL BE LABELED ON EACH END WITH WIRE ID #, AND SIGNAL SOURCE/DESTINATION. 6.ALL CONNECTION PLATE JACKS SHALL BE LABELED WITH ENGRAVING OR PRINTED LABELS. 7.RJ45 CONNECTORS SHALL BE TERMINATED USING THE T568B WIRING STANDARD. 8.VELCRO STRIPS SHALL BE USED TO SECURE CATX CABLES, NOT PLASTIC ZIP TIES. 9.POWER AND AV SIGNAL CABLES SHALL BE ROUTED ON SEPARATE SIDES OF THE EQUIPMENT RACK. RACK CABLING SHALL INCLUDE SERVICE LOOPS FOR EQUIPMENT REMOVAL AND SERVICING. 10.ALL AV DEVICES INSTALLED ON WALLS OR CEILING SHALL BE SECURED TO STRUCTURAL BLOCKING OR HARD DECK CEILING WITH SAFETY TETHERS. 11.SPEAKER GRILL PAINTING INSTRUCTIONS: FOLLOW MANUFACTURER INSTRUCTIONS, REMOVE GRILLS FROM SPEAKERS, USE ROLLERS OR BRUSHES (NOT SPRAYERS), AND CHECK THAT GRILL HOLES ARE NOT CLOGGED WITH PAINT. TVTVTV JJJ F F F DRAWING SYMBOLS DETAIL INDICATOR ELEVATION INDICATOR KEYNOTE 01 AV201 01 AV501 01 HEIGHT AFF (#)(#)(#) (#)(#)(#) (#)(#)(#) (#)(#)(#) AV EQUIPMENT SYMBOLS SYMBOL EQUIPMENT NAME EQUIPMENT MOUNTING BOX TYPE BOX MIN DEPTH BOX MOUNTING METHOD PLATE NOTES ASSISTIVE LISTENING TRANSMITTER WALL 1-GANG 2"SURFACE MOUNTED ON FINISHED WALL LISTEN LA-347 DEVICE MOUNTED TO BOX PLATE CONTROL PANEL TABLE SEE SYMBOL FOR TYPE - REFER TO TA501 CONTROL PANEL SCHEDULE PROJECTOR CEILING SEE SYMBOL FOR TYPE - REFER TO TA501 PROJECTOR SCHEDULE PROJECTION SCREEN WALL SEE SYMBOL FOR TYPE - REFER TO TA501 PROJ. SCREEN SCHEDULE SPEAKER WALL SEE SYMBOL FOR TYPE - REFER TO TA501 SPEAKER SCHEDULE XX X#18" SPEAKER ZONE NUMBER TYPE (REFER TO TA60x SCHEDULES) EQUIPMENT SYMBOL AL CPX P X S X# AV EQUIPMENT SYMBOLS KEY PSX RESPONSIBILITY CHART FURNISHED BY:INSTALLED BY:A.V.C.G.C.E.C.FURNITUREOWNEROTHEREXISTINGA.V.C.G.C.E.C.FURNITUREOWNEROTHEREXISTINGCEILING MOUNTED EQUIPMENT PROJECTOR PROJECTOR CEILING MOUNTING PLATE & PIPE PROJECTOR CEILING PIPE MOUNTED BOX PROJECTOR CEILING MOUNTING STRUCTURE (UNISTRUT) PROJECTOR MOUNTING BRACKET WALL MOUNTED EQUIPMENT PROJECTION SCREEN & MOUNTING BRACKETS PROJECTION SCREEN WALL BLOCKING WALL SPEAKERS ASSISTIVE LISTENING TRANSMITTER AV DEVICES CONTROL BUTTON PANEL HDMI EXTENDER AV NETWORK SWITCH WIRELESS MICROPHONE AUDIO DEVICES (DSP, AMPLIFIER) CABLES LOW VOLTAGE AV CABLES AV CONNECTORS ELECTRICAL & CABLE PATH AC POWER OUTLETS NETWORK DATA JACKS BACK BOXES/J-BOXES/LV CUT-IN RINGS/FACEPLATES J-HOOKS/CABLE HANGERS CONDUITS, RACEWAY, PULL STRINGS & PULL BOXES PROGRAMMING AV CONTROL SYSTEM PROGRAMMING AUDIO DSP PROGRAMMING DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 05/03/2021 11614/ COB #2013 CORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab RenovationMT THESE DRAWINGS ARE TO BE USED FOR REFERENCE ONLY 112 Hollister DriveTA001 COVER SHEET PS A99" 01 TA501 S A95" S A95" CPA 03 TA101 AL 95" PROJECTED IMAGE (SEE RCP ON TA101 DETAIL 2)(2)18"18"50"X80" (94" DIAGONAL) PROJECTION SCREEN TYPE A WITH WALL BRACKETS (BY GC) SECURED TO BUILDING STRUCTURE (CMU WALL). COORDINATE HEIGHT OF MOUNTING BRACKETS IN FIELD TO ASSURE THAT THE TOP EDGE OF SCREEN CASE IS TIGHT TO EXISTING LIGHTS. SEE TA501 DETAIL 01. WALL SPEAKER TYPE A (BY AVC) SURFACE MOUNTED. TYPICAL OF 2. 163"137" BOTTOM OF PROJECTED IMAGE AFF: 42" SPEAKER AFF: 95" SCREEN WALL BRACKETS AFF (COORDINATE IN FIELD): 99" ASSISTIVE LISTENING AFF: 95" ASSISTIVE LISTENING IR TRANSMITTER (BY AVC) SURFACE MOUNTED OVER 1-GANG J-BOX (BY EC). 10" 12" BOTTOM OF PROJECTOR AFF: 90" EXISTING HANGING LIGHT FIXTURES PROJECTOR CEILING MOUNTING METHOD TBD IN FIELD BASED ON EXISTING OBSTRUCTIONS. SEE TA501 DETAIL 02. SEE TA501 DETAIL 01 FOR SCREEN MOUNTING DETAIL 154" TABLES SHOWN AT 30" AFF FOR REFERENCE ONLY. SEE ARCHITECTURAL/ FURNITURE DRAWINGS. 100" 1149 MICROSCOPY CLASSROOM PROJECTOR LENS TO SCREEN THROW: 141" (2) 02 TA501 P A CENTER OF PROJECTOR CEILING MOUNT FROM SOUTH WALL: 163" CENTER OF PROJECTOR CEILING MOUNT FROM WEST WALL: 154" DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 05/03/2021 11614/ COB #2013 CORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab RenovationMT THESE DRAWINGS ARE TO BE USED FOR REFERENCE ONLY 112 Hollister DriveTA101 AV INFRASTRUCTURE DESIGN 01 SNEE 1149 ENLARGED FLOOR PLAN EQUIPMENT LAYOUT - AV SCALE: 1/4" = 1'-0" 03 SNEE 1149 WEST WALL ELEVATION - AV SCALE: 1/2" = 1'-0"04 SNEE 1149 SECTION - AV SCALE: 1/2" = 1'-0" 02 SNEE 1149 ENLARGED CEILING PLAN EQUIPMENT LAYOUT - AV SCALE: 1/4" = 1'-0" S WALL SPEAKER P PROJECTOR FINISHED CEILING FINISHED FLOOR SNEE HALL 11493/4" AL ASSISTIVE LISTENING TRANSMITTER 3/4" S WALL SPEAKER RACEWAY TO STUB ON CEILING NEXT TO PROJECTOR MOUNTING LOCATION RACEWAY TO STUB AT 18" AFF ADJACENT TO POWER/DATA ON SOUTH WALL NEXT TO INSTRUCTOR'S TABLE 1/2"1/2" 1" RACEWAY TO STUB AT SPEAKER LOCATIONS 95" AFF (NO J-BOX) ON WEST WALL. TYPICAL OF 2.SNEE HALL 1149DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 05/03/2021 11614/ COB #2013 CORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab RenovationMT THESE DRAWINGS ARE TO BE USED FOR REFERENCE ONLY 112 Hollister DriveTA102 AV INFRASTRUCTURE DESIGN RACEWAY RISER NOTES 1)ELECTRICAL AND NETWORK DATA CONDUIT AND PULL-BOXES TO BE SPECIFIED BY OTHERS. IF SHOWN ON THIS DRAWING, THEY ARE FOR REFERENCE ONLY. 2)THIS DRAWING DOES NOT INDICATE EXACT JUNCTION BOX LOCATIONS OR EXACT RACEWAY ROUTING. COORDINATE FINAL LOCATION, ROUTING, AND FINISH WITH OWNER'S REPRESENTATIVE AND AV CONTRACTOR IN FIELD. 3)" T " INDICATES RACEWAY STUB, RATHER THAN TERMINATION AT A J-BOX. 01 SNEE 1149 RACEWAY RISER - AV SCALE: NTS SECTION TOP HARD DECK CEILING 24" X 1 5/8" X 1 5/8" SLOTTED CHANNEL ANCHORED TO HARD DECK ABLE TO HOLD GROSS WEIGHT OF PROJECTOR AND MOUNT ASSEMBLY PER MANUFACTURER CUT SHEETS PLUS SAFETY FACTOR OF FIVE. PROVIDED BY GC. COORDINATE IN FIELD TO EXTEND THREADED ROD TO TRAPEZE AROUND EXISTING OBSTRUCTIONS. (TYP. OF 2) 24" X 1 5/8" X 1 5/8" SLOTTED CHANNEL (PROVIDED BY GC) (TYP. OF 2) CHIEF CMA115W CEILING PLATE (PROVIDED BY AVC) 1 1/2" NPT THREADED PIPE (COLOR: WHITE) LENGTH TBD IN FIELD (PROVIDED BY AVC) 120V 20A DUPLEX POWER OUTLET & (2) DATA JACKS (BY EC) NIGEL B NB-PEBPM PIPE STORAGE BOX (BY AVC) PAINTED WHITE (BY AVC). NO POWER RUN TO TO BOX. USE POWER STRIP (BY AVC) IN PIPE BOX TO CEILING MOUNTED POWER OUTLET. WIRELESS MIC RECEIVER SECURED TO TOP OF BOX (BY AVC). 120V 20A DUPLEX POWER OUTLET & (2) DATA JACKS (BY EC) WALL BRACKETS SECURED TO BUILDING STRUCTURE (CMU WALL) BY GC. ABLE TO HOLD GROSS WEIGHT OF SCREEN & MOUNTING BRACKETS PER MANUFACTURER SPECIFICATIONS, PLUS SAFETY FACTOR OF FIVE. SCREEN DROP FROM WALL CLEARANCE: 3 7/8". ADDITIONAL SURFACE MOUNTED BLOCKING (BY GC) MAY BE NEEDED TO CLEAR CHALK/MARKER TRAYS, ETC. BUILDING STRUCTURE (CMU WALL) FINISHED WALL ELEVATIONSECTION CONTROL PANEL SCHEDULE TYPE STYLE PANEL MAKE & MODEL MOUNT MAKE & MODEL BOX TYPE BOX MIN DEPTH DATA A BUTTON PANEL CRESTRON MPC3-101-B EXTRON 70-1097-01 TABLETOP KIT & 70-1160-12 TABLE CLAMP NO J-BOX NEEDED (TABLETOP KIT)NA NONE PROJECTOR SCHEDULE TYPE DESCIPTION PROJECTOR MOUNTING PROJECTOR MAKE & MODEL MOUNT MAKE & MODEL EQUIPMENT STORAGE BOX MAKE & MODEL BLOCKING / SUPPORT BOX TYPE BOX MIN DEPTH POWER DATA/VOICE A CEILING MOUNTED PROJECTOR CEILING EPSON L610U CHIEF CMA330 NIGEL B DESIGN NB-PEBPM-W PIPE MOUNTED SEE TA501 DETAIL NONE NA 120V 20A DUPLEX POWER OUTLET ATTACHED TO HARD DECK CEILING (2) DATA JACKS ATTACHED TO HARD DECK CEILING SPEAKER SCHEDULE TYPE DESCIPTION SPEAKER MOUNTING SPEAKER MAKE & MODEL MOUNT MAKE & MODEL BLOCKING / SUPPORT BOX TYPE BOX MIN DEPTH PLATE POWER A WALL SPEAKER SURFACE MOUNTED TO WALL JBL CONTROL 25-1-WH INCLUDED WITH SPEAKER NONE NONE (RACEWAY STUBS AT SPEAKER LOCATIONS)NA NA NONE PROJECTION SCREEN SCHEDULE TYPE DESCIPTION SCREEN MOUNTING SCREEN MAKE & MODEL CASE FINISH CUSTOM DROP MOUNTING BRACKET MAKE & MODEL BLOCKING / SUPPORT BOX TYPE BOX MIN DEPTH POWER LOW VOLTAGE CONTROLLER LOCATION A WALL MOUNTED MANUAL PULL-DOWN WALL DA-LITE MODEL C WITH CSR 34726 WHITE STANDARD 2" BLACK DROP DA-LITE 40932 SEE TA501 DETAIL NO J-BOX NEEDED NA NONE (MANUAL PULL-DOWN SCREEN)NA DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 05/03/2021 11614/ COB #2013 CORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab RenovationMT THESE DRAWINGS ARE TO BE USED FOR REFERENCE ONLY 112 Hollister Drive01 PROJECTION SCREEN WALL MOUNTING DETAIL SCALE: NTS 02 PROJECTOR CEILING MOUNTING DETAIL SCALE: NTS TA501 DETAILS & SCHEDULES - AV 01 SNEE 1149 CLASSROOM VIDEO/AUDIO/CONTROL SLD SCALE: NO SCALE CRESTRON HD-TX-101-C-E HDMI EXTENDER TRANSMITTER HDMI IN TO RX SRJ45 CRESTRON HD-RX-101-C-E HDMI EXTENDER RECEIVER FROM TXSRJ45 HDMI OUT HDMI EPSON L610U PROJECTOR HDMI IN 1HDMI HDMI IN 2 COMPUTER IN 1 AUDIO IN 1 HDBASET RS-232 LANRJ45 AUDIO OUT 3.5MM MONITOR OUT JBL CONTROL 25-1 WALL SPEAKER 8-OHM TAP INPHNX OUT JBL CONTROL 25-1 WALL SPEAKER 8-OHM TAP INPHNX OUT LISTEN LT-84-01 ASSISTIVE LISTENING IR EMITTER BAL LINE IN 1 UNBAL LINE IN 1RCA MIC IN 1 BAL LINE IN 2 UNBAL LINE IN 2 MIC IN 2 DC POWERPWR LINK OUT A LINK OUT B LISTEN LPT-A117 POWER EXTENDER (REMOTE) EXTRJ45 DC POWER OUT PWRFROM LISTEN POWER SUPPLY LISTEN LPT-A117 POWER EXTENDER (LOCAL) DC POWER INPWR EXT RJ45 CRESTRON CEN-SW-POE-5 POE NETWORK SWITCH PORT 1RJ45 PORT 2 PORT 3 RJ45 PORT 4 RJ45 UPLINK RJ45 INSTRUCTOR TABLE PROJECTOR PIPE BOX CEILING PROJECTOR PIPE BOX WEST WALL CRESTRON MPC3-101-B BUTTON PANEL/CTRL PROCESSOR LAN/POE RJ45 CRESNET IR EXTRON DMP 44 LC DSP INPUT 1PHNX INPUT 2PHNX INPUT 3PHNX INPUT 4 RS-232PHNX DIG CTRL IN 1 DIG CTRL IN 2 DIG CTRL IN 3 OUTPUT 1 PHNX OUTPUT 2 PHNX OUTPUT 3 PHNX OUTPUT 4 EXTRON MPA 152 PLUS AMPLIFIER L INPHNX R INPHNX REMOTE L SPKR OUT PHNX R SPKR OUT PHNX TO CAMPUS LAN WALL JACK SHURE ULXS4 WIRELESS MIC RECEIVER BALANCED OUT XLR PROJECTOR PIPE BOX (ON TOP) CAMPUS LAN CONNECTION TBD BY CORNELL IT 01 CRESTRON CEN-IO-COM-102 RS232 EXPANDER LAN POERJ45 COM 1 PHNX COM 2 01 MOUNTED IN EXTRON 70-1097-01 TABLETOP KIT (BLACK 1-GANG) & 70-1160-12 TABLE CLAMP HDMI CABLE FOR OFE LAPTOP DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 05/03/2021 11614/ COB #2013 CORNELL UNIVERSITYCONSTRUCTION DOCUMENTSSnee Hall 1149 Microscopy Lab RenovationMT THESE DRAWINGS ARE TO BE USED FOR REFERENCE ONLY 112 Hollister DriveTA701 AV SYSTEM DESIGN