HomeMy WebLinkAboutVOLUME 2LIGHT CLASSIFICATION OF HAZARD OCCUPANCIES APARTMENTS, CORRIDORS ROOMS 1,500 SQ. FT. AREA 0.1 GPM/SQ. FT. DENSITYHYDRAULIC 225 SQ. FT. COVERAGE MAXIMUM PER SPRINKLER SPRINKLER SCHEDULE TYPESYMBOL FINISHED CEILINGS LOCATION MANUFACTURER TYCO MODEL/ID No. (SIMILAR TO 1.CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB CONDITIONS AND SHALL REPORT TO ENGINEER ANY DISCREPANCIES OR OMISSIONS THAT WOULD INTERFERE WITH SATISFACTORY COMPLETION OF THE WORK. 2.THE CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING A FULL SET OF BID DOCUMENTS AND VISIT THE SITE TO MAKE HIMSELF AWARE OF THE TOTAL JOB BEFORE SUBMITTING HIS PRICE, FAILURE TO COMPLY SHALL NOT HOLD THE OWNER RESPONSIBLE FOR ANY ADDITIONAL COST. CONTRACTOR SHALL BE RESPONSIBLE FOR ARRANGING WITH FACILITY'S BUILDING MANAGEMENT FOR HANDLING MATERIALS, AS WELL AS FOR ALLOWABLE WORKING HOURS AND DELIVERIES. 3.CONTRACTOR SHALL SUBMIT ALL SHOP DRAWINGS AND MANUFACTURERS' CUTS AND SAMPLES TO ARCHITECT PRIOR TO COMMENCEMENT OF SUCH WORK. 4.THE CONTRACTOR SHALL INDICATE ON HIS SHOP DRAWING THAT ALL PIPING LAYOUTS ARE COORDINATED WITH THE MEP AND STRUCTURAL CONDITIONS. INCLUDE ON EACH WORKING DRAWING LAYOUT CERTIFICATE, THAT ALL RELATED CONDITIONS HAVE BEEN CHECKED, AND THAT NO CONFLICT EXISTS. SUBMISSION WILL NOT BE APPROVED WITHOUT SUCH CERTIFICATION. 5.CONTRACTOR SHALL SUBMIT SPRINKLER HYDRAULIC CALCULATIONS FOR THE ENGINEER'S REVIEW TO VERIFY THE ADEQUACY OF THE INDICATED PIPE SIZES. SHOP DRAWINGS MUST INDICATE ALL HYDRAULIC CALCULATION NODE AND PIPE TAGS. A.SPRINKLER PIPING SHALL BE INSTALLED AS PER APPROVED SHOP DRAWINGS. B.CONTRACTOR SHALL BASE ALL HYDRAULIC CALCULATIONS ON THE AVAILABLE PRESSURE. 6.DRAWINGS ARE NOT TO BE SCALED. 7.CONTRACTOR SHALL EXERCISE EXTREME CARE IN PROTECTING AREAS ADJACENT TO CONSTRUCTION AREAS SHALL FULLY PROTECT THEM FROM ANY DAMAGE RESULTING FROM CONTRACTOR'S WORKMEN, SUBCONTRACTORS OR AGENTS, AND SHALL BE RESPONSIBLE FOR REPAIRING, CLEANING OR REPLACING ANY SUCH DAMAGE. 8.ALL DIMENSIONS GIVEN ARE FINISH DIMENSIONS UNLESS OTHERWISE STATED. 9.UNLESS SPECIFICALLY STATED OTHERWISE, CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, APPURTENANCES, EQUIPMENT AND SERVICES TO COMPLETE ALL WORK AS INDICATED ON DRAWINGS AND/OR SPECIFIED ON NOTES. 10.UNLESS SPECIFICALLY STATED OTHERWISE, CONTRACTOR SHALL FOLLOW MANUFACTURER'S DIRECTIONS, INSTRUCTIONS AND RECOMMENDATIONS FOR ALL MATERIALS AND PROCESSES USED IN THIS CONTRACT. 11.PROVIDE SPRINKLERS UNDER DUCTS OVER 4'-0" IN WIDTH IN AREAS WITHOUT HUNG CEILING. 12.CONTRACTOR SHALL PROVIDE AND CONDUCT A FLOW TEST OF THE BUILDING'S WATER SERVICE AT THE STREET SERVICE. FLOW TEST RESULTS SHALL BE INCLUDED IN THE HYDRAULIC CALCULATIONS. 13.635,1./(56,10(&+$1,&$/52206+$//+$9($7(03(5$785(5$7,1*2)ƒ) LOCATIONS, NECESSARY FOR INSPECTION AND MAINTENANCE. 14.ALL UPRIGHT SPRINKLERS SHALL HAVE WIRE GUARDS. 15.LOCATE ALL HORIZONTAL PIPING ABOVE SUSPENDED CEILING, UNLESS THERE IS NO CEILING. 16.ACCESS DOORS ARE TO BE PROVIDED ADJACENT TO ALL VALVES. 17.CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL PENETRATIONS, CUTTING, PATCHING, SLEEVES, AND FIRESTOPPING REQUIRED TO COMPLETE THE INSTALLATION OF ALL WORK INCLUDED UNDER THEIR CONTRACT IN ACCORDANCE WITH THE FIRE EGRESS AND SECURITY PLAN DRAWINGS AND IN ACCORDANCE WITH DIVISION 16. 18.UPON COMPLETION OF THE WORK, CONTRACTOR SHALL COMPLETELY CLEAN THE CONSTRUCTION AREA SUITABLE FOR THE OWNER'S USE, INCLUDING REMOVAL OF ALL LABELS (AFTER ARCHITECT'S INSPECTION), CLEANING OF ALL THE EQUIPMENT, CONSTRUCTION WORK, WINDOWS AND OTHER WORK, NEW AND OLD, IN THAT CONSTRUCTION AREA. 19.BUILDING DEPARTMENT APPROVED PLANS SHALL BE TURNED OVER TO OWNER AT THE COMPLETION OF THE JOB. 20.AT THE FINAL COMPLETION OF THE JOB, CONTRACTOR SHALL SUBMIT TO THE FACILITY AND TO ENGINEER A NOTARIZED AFFIDAVIT STATING COMPLIANCE WITH ALL PROVISIONS OF THIS CONTRACT, INCLUDING ALL NOTES, EXCEPT FOR THOSE CHANGES SPECIFICALLY APPROVED IN WRITING BY THE ARCHITECT. 21.CONTRACTOR SHALL GUARANTEE ALL WORK PERFORMED UNDER THIS CONTRACT FOR ONE YEAR, STARTING FROM DATE OF FINAL ACCEPTANCE OF ALL WORK. 22.THE MINIMUM SPRINKLER BRANCH PIPE SIZE SHALL BE 1". SPRINKLER NOTES 1.AUTOMATIC SPRINKLER SYSTEM SHALL COMPLY WITH SEC. 903 IBC BUILDING CODE & NFPA 13-2013. 2.AUTOMATIC SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH SEC. 903.3.1 THROUGH 903.3.7 OF IBC BUILDING CODE. 3.SPRINKLERS SHALL NOT BE OMITTED FROM ANY ROOM MERELY BECAUSE IT IS DAMP, OF FIRE-RESISTANCE-RATED CONSTRUCTION OR CONTAINS ELECTRICAL EQUIPMENT AS PER SEC. 903.3.1.1.1 OF THE IBC BUILDING CODE. 4.WHERE AUTOMATIC SPRINKLER SYSTEMS ARE REQUIRED BY IBC BUILDING CODE, QUICK-RESPONSE SPRINKLERS SHALL BE INSTALLED IN THE AREAS LISTED SEC. 903.3.2 OF IBC BUILDING CODE. 5.AUTOMATIC SPRINKLERS SHALL BE INSTALLED WITH DUE REGARD TO OBSTRUCTIONS THAT WILL DELAY ACTIVATION OR OBSTRUCT THE WATER DISTRIBUTION PATTERN. AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN OR UNDER COVERED KIOSKS, DISPLAYS, BOOTH, CONCESSION STANDS, OR EQUIPMENT THAT EXCEEDS 4 FEET IN WIDTH. NOT LESS THAN 3 FOOT CLEARANCE SHALL BE MAINTAINED BETWEEN AUTOMATIC SPRINKLERS AND TOP OF PILES OF COMBUSTIBLE FIBERS SEC. 903.3.3. OF IBC BUILDING CODE. 6.WATER SUPPLIES FOR AUTOMATIC SPRINKLER SYSTEM SHALL COMPLY WITH SEC. 903.3.5 OF IBC BUILDING CODE AND SEC. 903.3.1 THE POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST BACK FLOW IN ACCORDANCE WITH THE REQUIREMENTS OF SEC. 903.3.5 THE IBC PLUMBING CODE. 7.FIRE HOSE THREADS USED IN CONNECTION WITH AUTOMATIC SPRINKLER SYSTEMS SHALL BE APPROVED AND COMPATIBLE WITH FIRE DEPARTMENT HOSE THREADS AS PER SEC 903.3.6 OF THE IBC PLUMBING CODE. 8.ALL VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC SPRINKLER SYSTEM AND WATER-FLOW SWITCHES ON ALL SPRINKLER SYSTEM SHALL BE ELECTRICALLY SUPERVISED BY THE FIRE ALARM SYSTEM AS PER SEC. 903.4 OF THE IBC BUILDING CODE. 9.THE DOCUMENTS OR PORTIONS THERE OF LISTED IN CHAPTER 2 OF NFPA 13-2013 ARE REFERENCED WITHIN NFPA-13 AND SHALL BE CONSIDERED PART OF THE REQUIREMENTS OF THIS DOCUMENT. 10.OCCUPANCY CLASSIFICATION SHALL COMPLY WITH CHAPTER 5 OF NFPA 13-2013. 11.PROTECTION REQUIREMENTS FOR MIXED COMMODITIES SHALL BE ACCORDANCE WITH SEC. 5.6.1.2 OF NFPA 13-2013. 12.REQUIREMENTS FOR CORRECT USE OF SPRINKLER SYSTEM COMPONENTS SHALL COMPLY WITH CHAPTER 6 OF NFPA 13-2013. 13. THE K-FACTOR, RELATIVE DISCHARGE, AND MARKING IDENTIFICATION FOR SPRINKLERS HAVING DIFFERENT ORIFICE SIZES SHALL BE IN ACCORDANCE WITH TABLE 6.2.3.1 OF NFPA 13-2013. 14. AUTOMATIC SPRINKLERS SHALL HAVE THEIR FRAME ARMS, DEFLECTOR,COATING MATERIAL, OR LIQUID BULB COLORED IN ACCORDANCE WITH THE REQUIREMENTS OF TABLE 6.2.5.1 OF NFPA 13-2013. 15. THE MAXIMUM FLOOR AREA OR ANY ONE FLOOR TO BE PROTECTED BY A SINGLE RISER FROM A CONTROL VALVE AND ALARM DEVICE SHALL COMPLY WITH SEC. 8.2.1 OF NFPA 13-2013. 16. WHERE CIRCUMSTANCES REQUIRE THE USE OF OTHER THAN ORDINARY TEMPERATURE-RATED SPRINKLERS, STANDARD RESPONSE SPRINKLERS SHALL BE PERMITTED TO BE USED SEC. 8.3.3. OF NFPA 13-2013. 17. SPRINKLERS SHALL BE LOCATED, SPACED AND POSITIONED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 8.5 OF NFPA 13-2013. 18. PROTECTION AREAS AND MAXIMUM SPACING FOR EACH HAZARD SHALL COMPLY WITH TABLE 8.6.2.2.1 (a) (b) (c) (d) OF NFPA 13-2013. 19. TYPES OF HANGERS SHALL BE ACCORDANCE WITH THE REQUIREMENT OF SEC. 9.1. OF NFPA 13-2013. 20. MAXIMUM DISTANCE BETWEEN HANGERS SHALL COMPLY WITH TABLE 9.2.2.1 OF NFPA 13-2013. 27. HOSE STREAM DEMAND AND WATER SUPPLY DURATION REQUIREMENT SHALL COMPLY WITH TABLE 11.2.3.1.2 OF NFPA 13-2013. 21. THE WATER SUPPLY FOR SPRINKLERS SHALL BE DETERMINED BY DENSITY/AREA CURVE, FIGURE 11.2.3.1.1 OF NFPA 13-2013. 22. HYDRAULIC DESIGN AREA REDUCTION FOR QUICK RESPONSE SPRINKLERS SHALL COMPLY WITH FIGURE 11.2.3.2.3.1 OF NFPA 13-2013. 23. MINIMUM OPERATING PRESSURE OF ANY SPRINKLER SHALL BE 7 PSI. SEC. 23.4.4.10.1 OF NFPA 13-2013. 24. A SPRINKLER SYSTEM ACCORDANCE WITH THIS STANDARD SHALL BE PROPERLY INSPECTED, TESTED AND ACCORDANCE WITH NFPA 25 AND IBC FIRE CODE. 25. SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED AT 200 PSI AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2 HOURS, PER NFPA 13-2013 SEC. 25.2.1.1. FS D SPRINKLER DRAIN PIPING WATERFLOW SWITCH CHECK VALVE (CV) SPR FLUSHING CONNECTION SPRINKLER MAIN PIPING CONCEALED PENDENT SPRINKLER HIGH VALVED CAPPED OUTLET (MANUALLY BOTTOM CONNECTION TOP CONNECTION DROP OR RISE PIPE DROP UNLESS OTHERWISE NOTED PIPE-UP UNLESS OTHERWISE NOTED FIRE DEPARTMENT CONNECTION (STORZ TYPE) WATER-PROOF PIPE SLEEVE BALL VALVE (BV) O.S.&Y. VALVE WITH TAMPER SWITCH PIPE SLEEVE ASSEMBLY LOW FIRE PROTECTION SYMBOLS DIRECTION ARROW PRESSURE GAUGE (PG) SPRINKLER FLOOR CONTROL VALVE TS TAMPER SWITCH OPENED VALVE UNLESS OTHER WISE NOTED ALARM CHECK VALVE - ELEVATION FSP FIRE STANDPIPE SUPPLY PIPING NEW SPRINKLER BRANCH PIPING GRINNELL #F950) #TYP OR #TYL CENTER LINE CEILING DOWN DRAWING DRAIN ABD CLG. BFP DN DWG DR ELEVATION FOOT, FEET EL FT AUTOMATIC BALL DRIP BACKFLOW PREVENTER INVERT ORDINARY HAZARD INV OH SQUARE FOOT, FEET SPECIFICATIONS PRESSURE GAUGE STANDARD SPRINKLER PG S.F. SPEC SPRK STD TYPICALTYP AFF ABOVE FINISHED FLOOR FCA FLOOR CONTROL ASSEMBLY FLOW SWITCHFS TAMPER SWITCHTS SP SPRINKLER PIPING FD FLOOR DRAIN FDV FIRE DEPARTMENT VALVE LH LIGHT HAZARD NOT TO SCALENTS ABBREVIATIONS NOTE: SYMBOLS LIST IS PROVIDED FOR REFERENCE ONLY. NOT ALL SYMBOLS OR ABBREVIATIONS ARE NECESSARILY USED IN THIS PROJECT. UPRIGHT EXPOSED CEILINGS TYCO OR APPROVED EQUAL #TYP OR #TYL ORDINARY GROUP 1 MISC. STORAGE ROOMS & MECHANICAL ROOM2,500 SQ. FT.0.15 GPM/SQ. FT.130 SQ. FT. HAZARD CLASSIFICATION SEMI-RECESSED PENDENT F FIRE SERVICE TYCO TYCO FINISHED CEILINGS FINISHED CEILINGS SIDEWALL CONCEALED PENDENT 2015 I.B.C. BUILDING DEPARTMENT SPRINKLER NOTES 1.THE COMPLETE STANDPIPE SYSTEM COMPLY WITH THE FULL REQUIREMENTS INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE, AND NFPA 14-2013. 2.STANDPIPE SYSTEM COMPONENTS AND HARDWARE SHALL BE IN ACCORDANCE WITH CHAPTER 4 OF NFPA 14-2013. 3.THE LOCATION OF FIRE DEPARTMENT HOSE CONNECTIONS SHALL BE APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 4.STANDPIPE SYSTEMS SHALL BE INSTALLED WHERE REQUIRED BY THE INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE AND NFPA 14 - 2013. 5.STANDPIPE SYSTEMS ARE PERMITTED TO BE COMBINED WITH AUTOMATIC SPRINKLER SYSTEMS PER NFPA 13 AND NFPA 14. 6.THE LOCATION OF CLASS I STANDPIPE HOSE CONNECTION SHALL COMPLY WITH INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE AND NFPA 14 - 2013. 7.WHERE THE MOST REMOTE PORTION OF A FLOOR OR STORY IS MORE THAN 200 FEET FROM A HOSE CONNECTION, ADDITIONAL HOSE CONNECTIONS SHALL BE PROVIDED IN APPROVED LOCATIONS BY THE AHJ. 8.CLASS I STANDPIPE HOSE CONNECTIONS SHALL BE PROVIDED IN ALL LOCATIONS PER INTERNATIONAL BUILDING CODE. 9.WHERE THE ROOF HAS A SLOPE OF LESS THAN 4" VERTICAL AND 12" HORIZONTAL, EACH STANDPIPE SHALL BE PROVIDED WITH A HOSE CONNECTION LOCATED EITHER ON THE ROOF OR AT THE HIGHEST LANDING OF STAIRWAYS WITH STAIR ACCESS TO THE ROOF. AN ADDITIONAL HOSE CONNECTION SHALL BE PROVIDED AT THE TOP OF THE MOST HYDRAULICALLY REMOTE STANDPIPE FOR TESTING PURPOSE AS PER NFPA 14 2013. 10.PROTECTION OF RISERS AND LATERALS OF CLASS I STANDPIPE SYSTEM SHALL COMPLY WITH THE INTERNATIONAL BUILDING CODE AND NFPA14 2013. 11.IN FULLY SPRINKLERED BUILDINGS HAVING A COMBINED STANDPIPE SYSTEM THAT IS HYDRAULICALLY CALCULATED, THE MINIMUM STANDPIPE SIZE IN BUILDINGS WITH FLOOR HEIGHTS LESS THAN 150 FT. ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS SHALL BE 4 IN. PER NFPA 14 7.6.3 - 2013. 12.CABINETS CONTAINING FIRE-FIGHTING EQUIPMENT SUCH AS STANDPIPES, FIRE HOSES, FIRE EXTINGUISHERS OR FIRE DEPARTMENT VALVES SHALL NOT BE BLOCKED FROM USE OR OBSCURED FROM VIEW. 13.STANDPIPE SYSTEMS ARE REQUIRED DURING CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS SHALL BE PROVIDED IN ACCORDANCE WITH IBC SECTION 3311. 14.FITTINGS SHALL BE EXTRA-HEAVY PATTERN WHERE PRESSURES EXCEED 175 PSI (12.1 BAR). SEC. 4.3.3 OF NFPA 14-2013. 15.PROTECTION OF STANDPIPE SYSTEM WHERE A STANDPIPE OR LATERAL PIPE THAT IS NORMALLY FILLED WITH WATER PASSES THROUGH AN AREA SUBJECT TO FREEZING TEMPERATURES IT SHALL BE PROTECTED TO 0$,17$,17+(7(03(5$785(2)7+(:$7(5,17+(3,3,1*%(7:((1ƒ) $1'ƒ) ƒ&$1'ƒ& 6(&2)1)3$ 16.FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN 18 IN. NOR MORE THAN 48 IN. ABOVE THE LEVEL OF THE ADJOINING GROUND, SIDEWALK OR GRADE SURFACE. SEC. 6.4.6 OF NFPA 14-2013. 17.THE MAXIMUM PRESSURE AT ANY POINT IN THE SYSTEM AT ANY TIME SHALL NOT EXCEED 350 PSI (24.1 BAR). SEC. 7.2 OF NFPA 14-2013. 18.BRANCH LINE SHALL BE SIZED BASED ON THE HYDRAULIC CRITERIA ESTABLISHED IN SEC. 7.8 & 7.10 BUT NOT LESS THAN 2-1/2" (65 mm) SEC. 7.6.4 OF NFPA 14-2013. 19.HYDRAULICALLY DESIGNED STANDPIPE SYSTEMS SHALL BE DESIGNED TO PROVIDE THE WATER FLOW RATE AT A MINIMUM RESIDUAL PRESSURE OF 100 PSI (6.9 BAR) AT THE OUTLET OF THE HYDRAULICALLY MOST REMOTE 2-1/2" (65 mm) HOSE CONNECTION & 65 PSI (4.5 BAR) AT THE OUTLET OF THE HYDRAULICALLY MOST REMOTE 1-1/2" (38 mm) HOSE CONNECTION. SEC. 7.8.1 OF NFPA 14-2013. 20.HOSE CONNECTIONS AND HOSE STATIONS SHALL BE UNOBSTRUCTED AND SHALL BE LOCATED NOT LESS THAN 3 FT. (0.9 M) OR MORE THAN 5 FT. (1.5 m) ABOVE THE FLOOR. SEC. 7.3.1.1 OF NFPA 14-2013. 21.AT THE TOP OF THE HIGHEST RISER THERE SHALL BE PROVIDED ABOVE THE MAIN ROOF LEVEL A MANIFOLD CAPABLE OF FLOWING THE FULL FLOW OF THE RISER BEING TESTED. 22.FOR CLASS I AND CLASS III SYSTEMS THE MINIMUM FLOW RATE FOR THE HYDRAULICALLY MOST REMOTE STANDPIPE SHALL BE 500 GPM (1893 L/MIN) SEC. 7.10.1.1.1 OF NFPA 14-2013. 23.THE MINIMUM FLOW RATE FOR ADDITIONAL STANDPIPES SHALL BE 250 GPM PER STANDPIPE WITH THE TOTAL NOT TO EXCEED 1250 GPM OR 1000 GPM FOR BUILDINGS SPRINKLERED THROUGHOUT. SEC. 7.10.1.1.3 OF NFPA 14-2007. 24.CLASS I AND CLASS III STANDPIPES SHALL BE AT LEAST 4" IN SIZE. STANDPIPES THAT ARE PART OF A COMBINED SYSTEM SHALL BE 6" IN SIZE. WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN APPROVED SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13 OR NFPA 13R, THE MINIMUM STANDPIPE SIZE SHALL BE 4" FOR SYSTEMS HYDRAULICALLY DESIGNED IN ACCORDANCE WITH SECTION 7.8.1 NFPA 14 - 2013. 25.VALVES CONTROLLING WATER SUPPLIES SHALL BE SUPERVISED IN THE OPEN POSITION SO THAT A CHANGE IN THE NORMAL POSITION OF THE VALVE WILL GENERATE A SUPERVISORY SIGNAL AT THE SUPERVISING STATION. WHERE A FIRE ALARM SYSTEM IS PROVIDED, A SIGNAL SHALL ALSO BE TRANSMITTED TO THE CONTROL UNIT. 26.STANDPIPES SHALL BE TESTED IN ACCORDANCE WITH NFPA 25, STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS. 2015 INTERNATIONAL BUILDING CODE STANDPIPE NOTES RESIDENTIAL UPRIGHT SPRINKLER W/ WIRE GUARD SIDEWALL SPRINKLER RESIDENTIAL DRY CONCEALED PENDENT SPRINKLER D FP. FIRE PROTECTION DRAWING LIST FP0.GENERAL P0.01 GENERAL NOTES & SYMBOL LIST FP2.BUILDING PLANS P2.00 FLOOR PLANS FP4.DIAGRAMS FP4.01 RISER DIAGRAM FP5.DETAILS FP5.01 DETAILS VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 FIRE PROTECTION: GENERAL NOTES & SYMBOL LIST FP0.01 AH REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9GWB 8'-8" GWB 7'-6" S GWB 8'-0" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 8'-8" GWB 7'-5" GWB 7'-5" APC-2 7'-6" APC-1 7'-6" GWB 7'-5" GWB 8'-8" S GWB 7'-6" GWB SLOPED GWB SLOPED GWB 8'-11 1/2" GWB SLOPED GWB SLOPED GWB 8'-10 1/2" S GWB 7'-6" S GWB 7'-6" S GWB 7'-6"SGWB 7'-6" EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1" 1" 1" 1" 1 1/2" 1"1" 3" 2 1/2" 11/2"11/4" 1" 1 1/4" 1" 1" 1 1/4" 1 1/4" 2 1/2" 11/2"11/4" 1" 11/2"11/4" 1" 2"1"1 1/2"1 1/4" 3"SPRSPRSPR 3" 3" 3" WALL MOUNTED STORZ FD CONNECTION 4"FSP UP&DN 2" DRAIN UP&DN 212"DROP TO FDV 4"FSP UP&DN 2" DRAIN UP&DN 212"DROP TO FDV 4"DN FCVA ELECTRIC ALARM BELLREF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL S GWB 8'-11" GWB 8'-0" GWB 7'-6" S GWB 8'-11" GWB 8'-0" GWB 7'-6" S GWB 8'-11" GWB 8'-0" GWB 7'-6" F1 S GWB 8'-11" GWB 8'-0" GWB 8'-11" GWB 7'-5" GWB 8'-0" APC-1 7'-6" GWB 8'-0" GWB 7'-5" GWB 8'-11" GWB SLOPED GWB 9'-2 1/2" GWB 9'-1 1/2"GWB SLOPED S GWB 7'-6" GWB 7'-6" S S GWB 7'-6" S GWB 7'-6" S GWB 7'-6" 1" 1" 1" 1 1/2" 1" 114" 3" 3" 1"11/2" 3" 11/4" 1" 11/2"11/4" 1" 11/2"11/4" 1" 1 1/4" 1"1" 1" 1" 3" 1" 1" 1" 1 1/4"1 1/2" 3"SPRSPRFSPFSPFSP 4"FSP UP & DROP 212"TO FDV 2" DRAIN DROP & UP 4"FSP UP & DROP 2" DRAIN DROP & UP 212"TO FDV 4" 4" 4" 4" 6" FIRE SERVICE 6" BACKFLOW PREVENTER W/BY-PASS METER 4" ALARM CHECK VALVE W/ TRIM 3" FSP SPR 5'-0" 4" UP TO WALL MOUNTED STORZ FD CONNECTION FCVA RCV W/TS RCV W/TS 4" TYPICAL PIPE SLEEVE W/LINK SEAL DROP IN ELEV. PIT REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9GWB 8'-8" GWB 7'-6" GWB 7'-6" S S GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 8'-8" GWB 7'-5" APC-2 7'-6" APC-1 7'-6" GWB 7'-5" GWB 8'-8" GWB 7'-6" GWB 8'-0" S GWB 7'-6" GWB SLOPED GWB SLOPED GWB 8'-11 1/2" GWB SLOPED GWB SLOPED GWB 8'-10 1/2" S GWB 7'-6" S GWB 7'-6" S GWB 7'-6"SEFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF 1" 1" 1 1/4" 1" 1"1 1/4" 2 1/2" 11/2"11/4" 1" 1" 1" 1 1/2" 1 1/2" 3" 11/2"11/4" 1" 11/2"11/4" 1" 2"1"2"1 1/4"1 1/2"2" 1" 3" 3" SPR 4"FSP UP&DN (3RD FL) 4"FSP DN (4TH FL) 212"TO FDV 2" DRAIN UP&DN (3RD FL) 2"DRAIN DN (4TH FL) 2"4"SPRSPRFSP PIPE OFFSET @ 4TH FLOOR CEILING ONLY 4"FSP UP TO ROOF MANIFOLD 4"FSP UP&DN (3RD FL) 4"FSP DN (4TH FL) 212"TO FDV 2" DRAIN UP&DN (3RD FL) 2"DRAIN DN (4TH FL) 3" PIPE OFFSET @ 4TH FLOOR CEILING ONLYFCVA 4"FSP UP TO ROOF MANIFOLD FSP 2"4" 3"REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9GWB 8'-8" GWB 7'-6" S S GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 7'-6" S GWB 8'-8" GWB 8'-0" GWB 8'-1 3/4" GWB 7'-5" APC-2 7'-6" APC-1 7'-6" GWB 7'-5" GWB 8'-8" GWB 7'-6" GWB 8'-0"SS GWB 7'-6" GWB 7'-6" GWB SLOPED GWB SLOPED GWB 8'-11 1/2" GWB SLOPED GWB SLOPED GWB 8'-10 1/2" S GWB 7'-6" S GWB 7'-6" S GWB 7'-6"SEFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF 1" 1 1/4" 1" 1"1 1/4" 2 1/2" 3" 11/2"11/4" 1" 1 1/4" 1" 1" 1 1/2" 1 1/2" 3" 3" 11/2"11/4" 1" 11/2"11/4" 1" 2"1"1 1/4"1 1/2" 1" SPR SPRSPR4"FSP UP&DN 2" DRAIN UP&DN 212"DROP TO FDV 4"FSP UP&DN 2" DRAIN UP&DN 212"DROP TO FDV FCVA 3" 1 1/2" VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 FIRE PROTECTION: FLOOR PLANS AH 0 4 8 16 FEET SCALE: 1/8"=1'-0"1 LOWER LEVEL PLAN 0 4 8 16 FEET SCALE: 1/8"=1'-0"3 SECOND FLOOR PLAN 0 4 8 16 FEET SCALE: 1/8"=1'-0"2 GROUND FLOOR PLAN 0 4 8 16 FEET SCALE: 1/8"=1'-0"4 THIRD / FOURTH FLOOR PLAN 0 4 8 16 FEET SCALE: 1/8"=1'-0"5 ROOF PLAN FIRE PROTECTION RISER DIAGRAM NTS 6" DOUBLE CHECK DETECTOR ASSEMBLY (W/ BY-PASS METER) DCDV 6" 4" CURB VALVE 6"HOUSE VALVE 4"ALARM CHECK VALVE 4" 4"FCA 2" 4" 4" 2" 4"4"FCA 4" 2" 4"4"FCA GROUND FLOOR LOWER LEVEL SECOND FLOOR 4" 4"FCA 2" 4" FD STAIR B THIRD FLOOR 4" 2-1/2" 4" 2-1/2" 4" STAIR A 4"RISER CONTROL VALVE 4"RISER CONTROL VALVE 34"ABD CHECK VALVE ROOF 5" FIRE DEPARTMENT STORZ CONNECTION ON FRONT OF BUILDING 212" FHV AT 4'-0" AFF FOURTH FLOOR 4" 2-1/2" 4" 2" 4"4"FCA 212" FHV AT 4'-0" AFF 212" FHV AT 4'-0" AFF 212" FHV AT 4'-0" AFF 212" FHV AT 4'-0" AFF 212" FHV AT 4'-0" AFF TO SPRINKLER SYSTEM TO SPRINKLER SYSTEM TO SPRINKLER SYSTEM TO SPRINKLER SYSTEM 212" FHV AT 4'-0" AFF 212" FHV AT 4'-0" AFF SPILL TO AREAWAY DRAINS SPILL TO AREAWAY DRAINS ROOF MANIFOLD (TYP) 6"6" INCOMING FIRE SERVICE ROOF MANIFOLD (TYP) TO SPRINKLER SYSTEM NORTH STAIRSOUTH STAIR VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:14pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 FIRE PROTECTION: RISER DIAGRAM FP4.01 AH NOT TO SCALE NOT TO SCALE PIPE PENETRATING THROUGH EXTERIOR WALL BELOW GRADE TERMINATE SLEEVE FLUSH WITH FINISHED WALL SURFACES STANDARD WEIGHT STEEL PIPE SLEEVE OF SIZE TO PASS PIPE ANNULAR SPACE BETWEEN PIPE AND SLEEVE TO BE PACKED WITH UL/FM APPROVED MATERIAL AND TESTED TO THE REQUIREMENTS OF ASTM E814 (UL 1476) AND ASTM 119 (UL 263) MEA # 307-92-M FINISHED ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING (TYP FOR EACH SIDE). SEAL OR CAULK SLEEVES THRU FIRE WALLS IN A SMOKE TIGHT MANNER. LINK SEAL TYPE FOUNDATION PENETRATION SEAL OS&Y VALVE AND PIPING ARE INSTALLED IN HEATED AREA DOUBLE PIPE CLAMP PIPE HANGERSLEEVE COUPLING EXTEND TO NEAREST OPEN FIXTURE OR DRAIN3/4" AUTOMATIC BALL DRIP NOT TO SCALE ROOF MANIFOLD DETAIL DETAIL OF SEMI-RECESSED PENDENT SPRINKLER NOT TO SCALE CONCEALED SPRINKLER AT HUNG CEILING NOT TO SCALE 1"x1/2" NPT FEMALE REDUCER DETAIL OF UPRIGHT SPRINKLER NOT TO SCALE ƒ(/%2::,7+7+5867%/2&.'(7$,/ NOT TO SCALE 6" AMES 3000SS DOUBLE CHECK DETECTOR BACKFLOW PREVENTER W/ BY-PASS METER. PROVIDE W/ TEST KIT ELECTRIC SPRINKLER ALARM PRESSURE SWITCH (TYP.) WIRE TO ALARM BELL & FIRE ALARM SYSTEM ALARM TEST LINE W/ VALVE SLEEVE W/LINK SEAL (TYP.) 6" FIRE SERVICE FROM STREET TO WITHIN 5'-0" BY GENERAL CONTR. O.S.& Y. GATE VALVE W/ T.S. (TYP) SPILL OVER FLOOR DRAIN ELECTRIC SPRINKLER ALARM BELL POTTER ELECTRIC SIGNAL COMPANY MODEL # PBD2410, 24 VDC PROVIDE W/ WEATHERPROOF BACKBOX MODEL BBK-1 POTTER ROEMER MODEL # 5795-02 5" STORZ x 4" NPT W/ #5799-02 BLIND CAP & CHAIN. PRESSURE GAUGE BY-PASS LINE SPRINKLER CONTRACTOR IS RESPONSIBLE FOR ALL LOW VOLTAGE WIRING INSTALLATIONS FOR PRESSURE SWITCHES, TAMPER SWITCHES, FLOW SWITCHES, ALARM BELLS. NOTE: DRIP CUP W/ 1-1/2" DRAIN (TYPICAL) SPRINKLER ALARM/CHECK VALVE W/ TRIM O.S.& Y. GATE VALVE W/ T.S. (TYP) 2" SYSTEM DRAIN VALVE (TYP.) RETARD CHAMBER (TYPICAL) PIPE SUPPORT (TYP.) FIN FLOOR TO COMBINED SPRINKLER / STANDPIPE SYSTEM DETAIL OF FIRELINE SERVICE AND ALARM VALVE ARRANGEMENT NOT TO SCALE WATER DATA DATE: HYDRANT LOCATION: RESIDUAL: FLOW: FLOW @ 20 P.S.I.: ROD HANGER CHECK VALVE BLDG. WALL VALVE FLOOR STAND WITH INDICATOR INSULATIONPIPE SLEEVE MANIFOLD UNIT ROOF FIRE STANDPIPE DRAIN LINE CONCEALED PIPING 1/2" CLEAR MAXIMUM FINISHED WALL SURFACE. PIPING EXPOSED TO VIEW GRADE WATER STOP & ANCHOR COLLAR METAL ESCUTCHEON BUILDING WALL LONG RADIUS ƒ(/%2: FIRE MAIN CONCRETE THRUST BLOCK UNDISTURBED EARTH 1" BRANCH LINE UPRIGHT SPRINKLER CROSS MAIN STATIC: 1" SPRINKLER BRANCH PIPING SPRINKLER MAIN OR LOOP 1" DROP 1" x 1/2" NPT FEMALE REDUCER SPRINKLER CUP ASSEMBLY PENDENT SPRINKLER HEAD CEILING LIGHT FIXTURE 12" MINIMUM ELBOW (TYP.) DROP NIPPLE 1" 1"x1/2" NPT FEMALE REDUCER SPRINKLER CUP ASSEMBLY COVER PLATE ASSEMBLY CEILING 1" 5'-0"2'-O" MIN.3'-O" MAX.BRANCH PIPING 2" 4"1 1/4" 2"2" 8/25/2015 LINDEN AVE @ DRYDEN RD 81 PSI 53 PSI 980 GPM 1,492 GPM VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:14pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 FIRE PROTECTION: DETAILS FP5.01 AH GENERAL NOTES NOTE: ALL SYMBOLS NOT NECESSARILY SHOWN ON DRAWINGS. 1.DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF THE WORK. REVIEW THE GENERAL NOTES, SPECIFICATIONS AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY THE ARCHITECT OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO SUBMISSION OF BID. 2.PROVIDE WORKMANSHIP OF HIGHEST GRADE: INSTALL ALL EQUIPMENT IN CONFORMANCE WITH MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS OF THE FACILITY. 3.PROVIDE ONE YEAR GUARANTEE AGAINST DEFECTIVE WORKMANSHIP AND MATERIAL. 4.COORDINATE ALL WORK TO MINIMIZE INTERFERENCES WITH OTHER TRADES. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CEILING HEIGHTS. 5.NO "DEAD ENDS" SHALL BE LEFT ON ANY DRAINAGE PIPING UPON COMPLETION OF WORK. 6.THIS CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING A FULL SET OF BID DOCUMENTS AND VISIT THE SITE TO MAKE THEM SELF AWARE OF THE TOTAL JOB BEFORE SUBMITTING THEIR PRICE. FAILURE TO COMPLY, SHALL NOT HOLD THE OWNER RESPONSIBLE FOR ANY ADDITIONAL COST. 7.PROVIDE ACCESS PANEL FOR ALL VALVES AND CLEANOUTS ON RISE OR CONCEALED IN WALL, ABOVE CEILING OR IN CHASE. 8.REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION AND MOUNTING HEIGHTS OF PLUMBING FIXTURES. 9.DO NOT SCALE FLOOR PLANS FOR EXACT HORIZONTAL LOCATION OF PIPE ROUTING. 10.INSTALL CONCEALED PIPING TIGHT TO THE STRUCTURE AND AS HIGH AS POSSIBLE. INSTALL EXPOSED PIPING TIGHT TO THE STRUCTURE, WALL OR CEILING AND AS HIGH AS POSSIBLE. COORDINATE WITH OTHER TRADES TO AVOID CONFLICTS. 11.COORDINATE ALL WORK WITH OTHER TRADES AND CONTRACTORS. 12.COORDINATE PIPING INSTALLATION WITH STRUCTURAL GRADE BEAMS, FOOTINGS, COLUMN PIERS, ETC. SLEEVE PIPING THROUGH GRADE BEAMS, FOOTING, ETC. WHERE REQUIRED AND AS NOTED ON PLANS. COORDINATE SLEEVE INSTALLATIONS WITH THE ARCHITECT, STRUCTURAL ENGINEER, STRUCTURAL CONTRACTOR AND GENERAL CONTRACTOR BEFORE CONCRETE IS INSTALLED. 13.CLEAN FAUCET AERATORS AND PIPE STRAINERS PRIOR TO TURNING BUILDING OVER TO THE OWNER. 14.PROVIDE TRAP PRIMERS WHERE REQUIRED BY LOCAL AUTHORITIES. 15.COORDINATE PIPE ROUTING TO BE AWAY FROM ELECTRICAL PANELS. DO NOT INSTALL PIPING OVER ELECTRICAL PANELS. 16.PAINT ALL EXPOSED GAS AND WATER PIPING USING RUST INHIBITOR PAINT. PAINT AND COLOR SHALL BE COORDINATED WITH THE ARCHITECT AND / OR OWNER. 17.COORDINATE ALL ROOF PENETRATIONS WITH OTHER TRADES. MAINTAIN 10' MINIMUM CLEARANCE FROM ALL AIR INTAKES. MAINTAIN 2' CLEARANCE FROM ALL OTHER EQUIPMENT. 18.INSULATE PIPING ROUTED IN EXTERIOR BUILDING WALLS WITH MINIMUM 2" BATT INSULATION TO PREVENT FREEZING. S # RPZ DCDA ST # COLD WATER PIPING (CW) HOT WATER PIPING (HW) HOT WATER RETURN PIPING (HWR) DRAINAGE PIPING ABOVE GROUND UNDERGROUND DRAINAGE/PIPING BELOW FRESH AIR INLET PIPING SANITARY (SAN) STORM PIPING VENT PIPING (V) GREASE WASTE PIPING GAS PIPING PUMP DISCHARGE PIPING DIRECTION OF FLOW PIPE-UP UNLESS OTHERWISE NOTED PIPE DROP UNLESS OTHERWISE NOTED DROP OR RISE TOP CONNECTION BOTTOM CONNECTION VALVED CAPPED OUTLET POINT OF NEW CONNECTION POINT OF DEMOLITION SANITARY/WATER RISER DESIGNATION STORM WATER LEADER DESIGNATION AREA DRAIN, FLOOR DRAIN, ROOF DRAIN (AD, FD, RD) FLOOR DRAIN W/ TRAP CLEANOUT (CO) CLEANOUT DECK PLATE (CODP) TRAP HOUSE TRAP GATE VALVE (GV) OPEN BALL VALVE (BV) BALL VALVE (BV) CHECK VALVE CHECK VALVE CHECK VALVE (CV) O.S.&Y. VALVE O.S.&Y. VALVE WITH TAMPER SWITCH GAS PRESSURE REGULATING VALVE. VENT TO EXTERIOR. GAS VALVE BUTTERFLY VALVE HOSE BIBB SOLENOID VALVE CIRCUIT SETTER FLOW CONTROL VALVE (FCV) SHOCK ABSORBER CONCENTRIC REDUCER TEMPERATURE & PRESSURE RELIEF VALVE (TP) THERMOMETER (T) PRESSURE GAUGE (PG) UNION VENT INCREASER VENT THROUGH ROOF (VTR) WATER-PROOF PIPE SLEEVE PIPE SLEEVE STRAINER FRESH AIR INLET FAI SAN ST GW G PD HIGHLOW S AD AREA DRAIN AP ACCESS PANEL BFP BACKFLOW PREVENTER CFH CUBIC FEET PER HOUR CEILINGCLG. CO CLEAN OUT CLEAN OUT DECK PLATECODP CP CIRCULATION PUMP COLD WATERCW DCW DOMESTIC COLD WATER DN DOWN DRAIN DRAWING EXISTING DWG DR (E), EX EJ EJECTOR PUMP ELEVATIONEL ET EXPANSION TANK FAI FRESH AIR INTAKE FLOOR DRAINFD FSP FIRE STAND PIPE FOOT, FEETFT GASG GPM GWH GALLONS PER MINUTE GAS WATER HEATER HOSE BIBBHB HR HOUR HEATERHTR HW HOT WATER HOT WATER RETURN HOT WATER SUPPLY HWR HWS INVERT ELEVATION INVERT INDIRECT WASTE LAVATORY LEADER METER MECHANICAL EQUIPMENT ROOMMER M LDR LAV IW INV IE MR MOP RECEPTOR MOUNTED NOT TO SCALE MTD NTS O/C ON CENTER OVERFLOW ROOF DRAIN PRESSURE GAUGE PLUMBINGPLBG PG OD RD ROOF DRAIN RECIRCULATING PUMPRP REDUCED PRESSURE ZONE BACKFLOW PREVENTERRPZ SHOCK ABSORBERSA SAN SANITARY SUMP DISCHARGESD SH, SHR SPECS. SQ.FT. SS ST SHOWER SPECIFICATIONS SQUARE FOOT (FEET) SERVICE SINK STORM STANDARD STORM WATER TRENCH DRAIN TEMPERATURE STD SW TD TEMP TMV THERMOSTATIC MIXING VALVE TRAP PRIMER TAMPER SWITCH TYPICAL UNDERWRITERS LABORATORY TP TS TYP UL UR URINAL VENTV V.I.F.VERIFY IN FIELD VENT THROUGH ROOF WASTE WATER CLOSET WALL CLEANOUT WATER-PROOF WCO WC WP W VTR REDUCED PRESSURE ZONE BACKFLOW PREVENTER (RPZ) DOUBLE CHECK DETECTOR ASSEMBLY CIRCULATOR PUMP PLUMBING SYMBOLS ABBREVIATIONS P. PLUMBING DRAWING LIST P0.GENERAL P0.01 GENERAL NOTES & SYMBOL LIST P2.BUILDING PLANS - WATER & GAS P2.00 LOWER LEVEL PLAN - WATER & GAS P2.01 GROUND FLOOR PLAN - WATER & GAS P2.02 SECOND FLOOR PLAN - WATER & GAS P2.03 THIRD FLOOR PLAN - WATER & GAS P2.04 FOURTH FLOOR PLAN - WATER & GAS P3.BUILDING PLANS - DRAINAGE P3.00A LOWER LEVEL PLAN - DRAINAGE P3.00B LOWER LEVEL PLAN - ABOVE CEILING DRAINAGE P3.01 GROUND FLOOR PLAN - DRAINAGE P3.02 SECOND FLOOR PLAN - DRAINAGE P3.03 THIRD FLOOR PLAN - DRAINAGE P3.04 FOURTH FLOOR PLAN - DRAINAGE P3.05 ROOF PLAN - DRAINAGE P4.DIAGRAMS P4.01 DOMESTIC WATER RISER DIAGRAMS P4.02 SANITARY RISER DIAGRAMS P4.03 STORM & GAS RISER DIAGRAMS P5.SCHEDULES P5.01 SCHEDULES P6.DETAIL P6.01 DETAILS SHEET 1 OF 2 P6.02 DETAILS SHEET 2 OF 2 CLEAN OUT TO GRADECOG NOTE: ALL SYMBOLS NOT NECESSARILY SHOWN ON DRAWINGS. W # NON-FREEZE WALL HYDRANTNFWH PUMP DISCHARGEPD PRESSURE REDUCING VALVEPRV VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:11pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: GENERAL NOTES & SYMBOL LIST P0.01 AH REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL 2" CW UP 112" HW UP 2" 2" CW UP 112" HW UP 2" CW UP 112" HW UP 2" 2" 2" 2" 2" 212" 212" 2" CW UP 112" HW UP 2" 3" 3/4"HWR UP ELEV 733.67 1" 114" 1" 3 4" 34" 1" 1" 34" SK LAV-1 WCSH-1 3"GAS UP TO METER RPZ1"CW FOR MECH. MAKE-UP WATER 1"CW DROP TO 34" HB & 1" MAKE-UP WATER, 12" TO TP W/DU 2"G12"CW DROP TO TP W/DU 112" GAS DROP TO BOILER (300 CFH) GAS REGULATOR VENTS UP 5'-0" INCOMING 4" DOMESTIC WATER SERVICE CONTINUATION BY SITE CONTRACTOR WATER METER & PRV STATION (SEE DETAIL ON DWG P6.01) PROVIDE SLEEVES W/LINK SEAL (TYPICAL ALL FOUNDATION PENETRATIONS) INCOMING 6" FIRE SERVICE 34"CW DROP TO NFWH 1"3 4" 1" 34"CW DROP TO NFWH 2" CW UP 112" HW UP 1" 114" 1" 34" 34" 1" 1" 34" SK LAV-1 WCSH-1 MR SEE ABOVE FOR PIPING LAYOUT SEE ABOVE FOR PIPING LAYOUT KEYED NOTES 1" H & 114" CW TO CONTROL VALVES ABOVE CEILING WITH ACCESS PANEL (AP) 1" H & CW DROP 34" H & CW TO LAV / SK / SHR 34" CW TO WC 34" HWR TO FLOW CONTROL VALVE ASSEMBLY ABOVE CEILING WITH ACCESS PANEL (AP). SEE DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT 34" H&CW DROP TO MR 1 2 3 4 5 6 112"G112"G 112"G UP 112"G 3"G 2"G112"G112" GAS DROP TO BOILER (300 CFH) GAS PRESSURE REGULATOR (SET @ 7" WC)TYP ET-1 TMV-1RP-1 GWH (199 CFH) ƒ G SEE DETAIL ON P6.01 FOR PIPING LAYOUT GAS PRESSURE REGULATOR (SET @ 7" WC)TYP 3"Gƒ+: GWH (199 CFH) 112" GAS DROP (199 CFH) 112"G 212" 2" 212" 2"34" SIMILAR TO ABOVE VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:11pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: LOWER LEVEL PLAN - WATER & GAS P2.00 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 LOWER LEVEL PLAN - WATER & GAS REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 2" CW UP & DN 112" HW UP & DN 2" CW UP & DN 112" HW UP & DN 2" CW UP & DN 112" HW UP & DN 2" CW DN 112" HW DN 2" CW UP 112" HW UP 2" CW UP 112" HW UP 2" CW DN 112" HW DN WC LAV-1 SH-1 1" 114" 1" 34" 112" 2" SK 1" 1" 1" 114" 1" 34" 34" 1" 1" 34" SK LAV-1 WCSH-1 1" 114" 1" 3 4" 34" 1" 1" 34" SK LAV-1 WCSH-1 GAS DN 7"WC SERVICE PRESSURE GAS METER AT GRADE SET ON CONCRETE PAD. COORDINATE W/ LOCAL GAS COMPANY FOR REQUIREMENTS INCOMING GAS SERVICE BY GAS COMPANY G 3" GAS DN 34"CW DROP TO NFWH 3 4" SEE ABOVE FOR PIPING LAYOUT SEE ABOVE FOR PIPING LAYOUT 3/4"HWR UP & DN 112"G UP&DN GAS REGULATOR VENTS UP&DN SIMILAR TO ABOVE VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:11pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: GROUND FLOOR PLAN - WATER & GAS P2.01 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 GROUND FLOOR PLAN - WATER & GAS REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF 112" CW UP - 2" CW DN 114" HW UP - 112" HW DN 112" CW UP - 2" CW DN 114" HW UP - 112" HW DN 112" CW UP - 2" CW DN 114" HW UP - 112" HW DN 112" CW UP - 2" CW DN 114" HW UP - 112" HW DN 112" CW UP - 2" CW DN 114" HW UP - 112" HW DN 1" 114" 34"1"34"1" 1" WC LAV-2 SH-2 SK-1 34" 1" 114" 1" 3 4" 1" 1" 3 4" SK LAV-1 WC SH-1 1" 114" 1" 3 4" 34" 1" 1" 34" SK LAV-1 WCSH-1 KEYED NOTES 1" H & 114" CW TO CONTROL VALVES ABOVE CEILING WITH ACCESS PANEL (AP) 1" H & CW DROP 34" H & CW TO LAV / SK / SHR 34" CW TO WC 34" HWR TO FLOW CONTROL VALVE ASSEMBLY ABOVE CEILING WITH ACCESS PANEL (AP). SEE DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT 34" H&CW DROP TO MR 1 2 3 4 5 6 SEE ABOVE FOR PIPING LAYOUT SEE ABOVE FOR PIPING LAYOUT 3/4"HWR UP & DN 112"G UP&DN GAS REGULATOR VENTS UP&DN SIMILAR TO ABOVE VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:11pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: SECOND FLOOR PLAN - WATER & GAS P2.02 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 SECOND FLOOR PLAN - WATER & GAS REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF 114" CW UP - 112" CW DN 1" HW UP - 114" HW DN 114" CW UP - 112" CW DN 1" HW UP - 114" HW DN 114" CW UP - 112" CW DN 1" HW UP - 114" HW DN 114" CW UP - 112" CW DN 1" HW UP - 114" HW DN 114" CW UP - 112" CW DN 1" HW UP - 114" HW DN 1" 114" 34"1"34"1" 1" WC LAV-2 SH-2 SK-1 1" 114" 1" 3 4" 34" 1" 1" 34" SK LAV-1 WCSH-1 34"HWR UP&DN 34" 1" 114" 1" 3 4" 1" 1" 3 4" SK LAV-1 WC SH-1 KEYED NOTES 1" H & 114" CW TO CONTROL VALVES ABOVE CEILING WITH ACCESS PANEL (AP) 1" H & CW DROP 34" H & CW TO LAV / SK / SHR 34" CW TO WC 34" HWR TO FLOW CONTROL VALVE ASSEMBLY ABOVE CEILING WITH ACCESS PANEL (AP). SEE DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT 34" H&CW DROP TO MR 1 2 3 4 5 6 SEE ABOVE FOR PIPING LAYOUT SEE ABOVE FOR PIPING LAYOUT 112"G UP&DN GAS REGULATOR VENTS UP&DN SIMILAR TO ABOVE VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: THIRD FLOOR PLAN - WATER & GAS P2.03 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 THIRD FLOOR PLAN - WATER & GAS REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF1" 114" 1" 3 4" 34" 1" 1" 34" SK LAV-1 WCSH-1 114" CW DN 1" HW DN 34" 114" CW DN 1" HW DN 114" CW DN 1" HW DN 114" CW DN 1" HW DN 114" CW DN 1" HW DN 34" HWR DN 34" 34" SK-1 1" 114" 34"1"34"1" 1" WC LAV-2 SH-2 1" 114" 1" 3 4" 1" 1" 3 4" SK LAV-1 WC SH-1 34" 34" 34" KEYED NOTES 1" H & 114" CW TO CONTROL VALVES ABOVE CEILING WITH ACCESS PANEL (AP) 1" H & CW DROP 34" H & CW TO LAV / SK / SHR 34" CW TO WC 34" HWR TO FLOW CONTROL VALVE ASSEMBLY ABOVE CEILING WITH ACCESS PANEL (AP). SEE DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT 34" H&CW DROP TO MR 1 2 3 4 5 6 SEE ABOVE FOR PIPING LAYOUT SEE ABOVE FOR PIPING LAYOUT 112"G DN, 112"G UP TO ROOF (SEE ROOF PLAN P3.05 FOR CONTINUATION) GAS REGULATOR VENTS UP&DN (SEE ROOF PLAN P3.05 FOR VENT TERMINATIONS) SIMILAR TO ABOVE VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: FOURTH FLOOR PLAN - WATER & GAS P2.04 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 FOURTH FLOOR PLAN - WATER & GAS REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL SK SH-1 WC LAV-1 SK SH-1 WC SK 2" SH-1 WC SK 2" SH-1 WC 4"FD DUPLEX SEWAGE EJECTOR EJ-1 4"3"4" 2" 4" 4" 4" 4" 4" 2" 4" 2" 4"3"4" 2" 4"3"4" 2" ELEV 734.0 FF ELEV 734.5 IE 732.27' IE 733.0'2"PDSP-2 IN PIT 4"FD 4"FD 2" 2" 4" 6" SLOPE @ 14"/FT 2"V DN (2)2"V DN4" 2" 4"AD 4"AD 14 GPM TD (445 SQ FT) 4"ST 4"ST8 GPM 4"ST4"STIE 731.0' IE 730.22' 3" MR 4"FD ALL SANITARY & VENT PIPING LOCATED BELOW SLAB IN MECHANICAL ROOM SHALL BE CAST IRON. 4" 2"V DNTMV-16"RD 4"FD 4"4" FROM FOOTING DRAINS. SEE CIVIL PLANS DUPLEX SUMP PUMP SP-1 LAV-1 LAV-1 LAV-1 2"V DN VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: LOWER LEVEL PLAN - DRAINAGE AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 LOWER LEVEL FLOOR PLAN - DRAINAGE NOTE: SEE DRAWING P3.00B FOR ABOVE CEILING PIPING REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL 4" SAN UP 2" W UP 4"S UP TO WC 2"V UP 2"W UP TO SHR 2"V UP 5'-0"CONTINUATION BY SITE CONTRACTOR 2" W UP 2" V UP & DN 212" V UP & DN 4" SAN UP 2" W UP 2" V UP & DN 2" W UP TO SHR 2" V UP 4"S UP TO WC 2"V UP 2" W UP 2" V UP & DN 212" V UP & DN 4" SAN UP 2" W UP 2" V UP & DN 2" W UP TO SHR 2" V UP 4"S UP TO WC 2"V UP 2" W UP 2" V UP & DN 212" V UP & DN 4" SAN UP 2" W UP 2" V UP & DN 2" W UP TO SHR 2" V UP 4"S UP TO WC 2"V UP 4"4" 4" 4" 2" W UP 2" V UP & DN 212" V UP & DN 4" SAN UP 4"S UP TO WC 2"V UP 2" W UP TO SHR 2" W UP 2" V UP & DN 3"LDR UP - RD (42 GPM) 3"LDR UP - RD (48 GPM) 3"LDR UP&DROP - OD SPILL TO GRADE (42 GPM) 3"LDR UP&DROP - OD SPILL TO GRADE (48 GPM) DUPLEX SEWAGE EJECTOR EJ-1 DUPLEX SUMP PUMP SP-1 3"RD 3"RD6"RD6"RD 6"SAN ELEV 734.0 FF ELEV 734.0 3" 3" 4" 4" 4" 4" 3" 2"V UP 4"FD TMV-14"FD (2)2" V DN 2"V UP 6" 4"FD 2" 2" 2" V DN UP TO COG KEYED NOTES WATER CLOSET - 4"S DN, 212"V RISE LAVATORY - 2"V RISE, 2"W DROP SINK - 2"V RISE, 2"W DN SHOWER - 2"V RISE, 2"W DN MOP RECEPTOR - 3"W DN, 2"V RISE 1 2 3 4 5 2"V DN 2" PUMP CONTROL PANEL GWH 2" 2" 2"V DN 6"3"RD 6"RD PUMP CONTROL PANEL 2" 2" 4"FD 2" V DN114"PD2"PD6" GWH IE 742.00' IE 740.00' TYPICAL ACCESS PANEL AP IN CEILING VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: LOWER LEVEL PLAN - ABOVE CEILING DRAINAGE AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 LOWER LEVEL FLOOR PLAN - ABOVE CEILING DRAINAGE NOTE: SEE DRAWING P3.00A FOR PIPING AT PLUMBING FIXTURES REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC LAV-1 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN SK2" SH-1 WC LAV-1 SK 3"LDR UP - RD (42 GPM) 3"LDR UP&DN - RD (48 GPM) 3"LDR DN - RD (42 GPM) 3"LDR UP&DN - OD (48 GPM) 3"LDR UP&DN - OD (42 GPM) SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC LAV-1 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC LAV-1 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN 4" 2" W DN (2)2"V DN SH-1 2" WC LAV-1 212" V UP & DN 4" SAN UP & DN 2" W UP 2" V UP 2" W DN 2" W UP 2" V UP 2" W UP TO SHR 2" V UP 2" W DN 2" V DN 2"V DN 212" V UP 4" SAN UP 2"W UP 2"W UP TO SHR 4"S UP TO WC 2"V UP 4"S DROP 4"S DN 2"V UP 2"W DN2" 2" 4"S DN 2"W DN 2"V DN COG COG VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: GROUND FLOOR PLAN - DRAINAGE P3.01 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 GROUND FLOOR PLAN - DRAINAGE REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF SK-1 SH-2WC LAV-2 3"LDR UP&DN - RD (42 GPM) 3"LDR UP&DN - RD (48 GPM) 3"LDR UP&DN - OD (48 GPM) 3"LDR UP&DN - OD (42 GPM)SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC LAV-1 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN 212" V UP & DN 4" SAN UP & DN 2" WC 212" V UP & DN 4" SAN UP & DN SH-1 SK 2" W UP & DN 2" V UP & DN 2" W UP & DN 2" V UP & DN 2"2" LAV-1 LAV-1 LAV-1 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: SECOND FLOOR PLAN - DRAINAGE P3.02 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 SECOND FLOOR PLAN - DRAINAGE REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF 3"LDR UP&DN - RD (42 GPM) 3"LDR UP&DN - RD (48 GPM) 3"LDR UP&DN - OD (48 GPM) 3"LDR UP&DN - OD (42 GPM) SH-2WC LAV-2 SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC LAV-1 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN SK 2" W UP & DN 2" V UP & DN 2" SH-1 WC 212" V UP & DN 4" SAN UP & DN 2" W UP & DN 2" V UP & DN 212" V UP & DN 4" SAN UP & DN 2"2" SK-1 2" WC 212" V UP & DN 4" SAN UP & DN SH-1 SK 2" W UP & DN 2" V UP & DN 2" W UP & DN 2" V UP & DN LAV-1 LAV-1 LAV-1 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: THIRD FLOOR PLAN - DRAINAGE P3.03 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 THIRD FLOOR PLAN - DRAINAGE REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF 3"UP TO RD 3"UP TO OD (24 GPM) 3"LDR DN - RD (42 GPM) 3"OD 3"RD 3"UP TO RD 3"UP TO OD (18 GPM) 3"RD 3"OD 3"UP TO RD 3"UP TO OD (26 GPM) 3"OD 3"RD 3"UP TO RD 3"UP TO OD (22 GPM) 3"LDR DN - RD (48 GPM) 3"LDR DN - OD (48 GPM) 3"OD 3"OD3"LDR DN - OD (42 GPM) SH-2 WC LAV-2 SK 2" W DN 2" V DN 2" SH-1 WC LAV-1 212" V DN 4" SAN DN 4" VTR 2" W DN 2" V DN SK2" SH-1 WC 212" V DN 4" SAN DN 4"VTR SK2" SH-1 WC SK-1 2" WC SH-1 SK 212" V DN 4" SAN DN 4"VTR 2" W DN 2" V DN 2" W DN 2" V DN 2"2" 2"2" 2" W DN 2" V DN 2" W DN 2" V DN 2" 2" 212" V DN 4" SAN DN 4" VTR 2" 2" 2" W DN 2" V DN 2" W DN 2" V DN 212" V DN 4" SAN DN 4"VTR 2"2" LAV-1 LAV-1 LAV-1 3"OD 3"RD COORDINATE STORM & VENT PIPE ROUTING WITH MECHANICAL UNIT ABOVE KITCHENETTE CEILING COORDINATE STORM & VENT PIPE ROUTING WITH MECHANICAL UNIT ABOVE KITCHENETTE CEILING VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:12pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: FOURTH FLOOR PLAN - DRAINAGE P3.04 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 FOURTH FLOOR PLAN - DRAINAGE REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.93"OD 3"RD 3"OD 3"RD 3"OD 3"RD 3"OD 3"RD 4"VTR 4"VTR 4"VTR 4"VTR 4"VTR 112"G DN SEE DRAWING P2.04 FOR CONTINUATION STAND-BY GENERATOR (4)GAS REGULATOR VENTS DN. SEE DRAWING P2.04 FOR CONTINUATION TERMINATE GAS REGULATOR VENTS WITH GOOSENECK VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: ROOF PLAN - DRAINAGE P3.05 AH SCALE: 1/4"=1'-0" 0 4 8 FEET 1 ROOF PLAN - DRAINAGE NO SCALE DOMESTIC WATER RISER DIAGRAM1 LOWER LEVEL GROUND FLOOR 2ND FL 3RD FL 4TH FL ROOF INCOMING 4" DOMESTIC WATER SERVICE FROM CITY WATER PRV M RPZ PRV FD FD TP WATER HEATER WATER HEATER RPZ 1" 1 WSFU HB FD GRADE SHR LAV SKWC 114" 3.7 WSFU 1" 2.5 WSFU 34" 1 WSFU 34" 1" 1" 34" BOILER MAKE-UP FEED 114" 3.7 WSFU 1" 2.5 WSFU WCLAVSHR 34"3 4"34" 1" 2.7 WSFU 1" 1.5 WSFU SHR 34" 114" 3.7 WSFU 1" 2.5 WSFU WCLAVSHR 34"3 4"34" 1" 2.7 WSFU 1" 1.5 WSFU SHR 34" 114" 3.7 WSFU 1" 2.5 WSFU WCLAVSHR 34"3 4"34" 1" 2.7 WSFU 1" 1.5 WSFU SHR 34" 1" 2.5 WSFU 114" 3.7 WSFU 114" 5 WSFU 112" 7.4 WSFU 112" 7.5 WSFU 2" 11.1 WSFU 112" 10 WSFU 2" 14.8 WSFU SHR 114" 3.7 WSFU 1" 2.5 WSFU 1"3 4" LAV SKWC 3 4" 1 WSFU 34" 1" 112" 10 WSFU 2" 14.8 WSFU 2" 18.5 WSFU 2" 12.5 WSFU 34" 34" 112" 7.5 WSFU 2" 11.1 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 114" 5 WSFU 112" 7.4 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 1" 2.5 WSFU 114" 3.7 WSFU 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 114" 3.7 WSFU 1" 2.5 WSFU 1"3 4" LAV SKWC 3 4" 1 WSFU 34" 1" 112" 10 WSFU 2" 14.8 WSFU 2" 18.5 WSFU 2" 12.5 WSFU 34" 112" 7.5 WSFU 2" 11.1 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 114" 5 WSFU 112" 7.4 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 1" 2.5 WSFU 114" 3.7 WSFU 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 114" 3.7 WSFU 1" 2.5 WSFU 1"3 4" LAV SKWC 3 4" 1 WSFU 34" 1" 112" 10 WSFU 2" 14.8 WSFU 2" 18.5 WSFU 2" 12.5 WSFU 34" 112" 7.5 WSFU 2" 11.1 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 114" 5 WSFU 112" 7.4 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 1" 2.5 WSFU 114" 3.7 WSFU 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 1"34" LAV SKWC 34" 1 WSFU 34" 1" 34" SHR 114" 3.7 WSFU 1" 2.5 WSFU 1"34" LAV SKWC 34" 1 WSFU 34" 1" 112" 10 WSFU 2" 14.8 WSFU 2" 18.5 WSFU 2" 12.5 WSFU 34" 112" 7.5 WSFU 2" 11.1 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 114" 5 WSFU 112" 7.4 WSFU 114" 3.7 WSFU 1" 2.5 WSFU 1" 2.5 WSFU 114" 3.7 WSFU 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 3 4" 1" 3 4" 114" 3.7 WSFU 1" 2.5 WSFU SHR 1"34" LAV SKWC 34" 1 WSFU 3 4" 1" 3 4" SHR 1"34" LAV SKWC 34" 1 WSFU 3 4" 1" 3 4" SHR 1"34" LAV SKWC 34" 1 WSFU 3 4" 1" 3 4" FCV FCV FCV FCV 2" 25 WSFU 2" 37 WSFU 2" 37.5 WSFU 212" 55.5 WSFU (734'-6") (744'-6") (754'-3") (764'-0") (773'-9") 9'-9" 9'-9" 9'-9" 10'-0" RPZ 34"34"3 4"34" 3 4" FCV 34" FD TP FD NFWH MR34" 2.25 WSFU 34" 212" 88.8 WSFU 212" 74 WSFU 2" 50 WSFU 2" 60 WSFU 212" 91.05 WSFU 2" 62.25 WSFU 2" 62.25 WSFU 2" 62.25 WSFU3" 153.3 WSFU 12" VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: DOMESTIC WATER RISER DIAGRAM P4.01 AH GROUND 2ND FLOOR 3RD FLOOR 4TH FLOOR LOWER LEVEL ROOF 2" 2" 2" 2" 2" 2"(2 DFU) 2"(4 DFU) 2" 2" 2" 2" 2"(6 DFU) 2" SHR SHR SHR SHR 2" 2" 4" 4"(8DFU) 4"(4 DFU) 2" 212" 212" 212" 2" 2" 2" 2" 2" 2" 2" 2" WC LAV WC LAV WC LAV WC LAV 2" 4" 212" 2" 2" 2" 2" 2" 2" SK 2" 2" 2" SK SK SK 2"(2 DFU) 2"(4 DFU) 2"(6 DFU) 2"(8 DFU) 2" 2" 4"VTR 2"2" 4"(12 DFU) 4"(13 DFU) 2"(8 DFU) 4"(3 DFU) 4"(16 DFU) 4"(24 DFU)4"(32 DFU) 2" 2" 2" 2" 2" 2"(2 DFU) 2"(4 DFU) 2" 2" 2" 2" 2"(6 DFU) 2" SHR SHR SHR SHR 2" 2" 4" 4"(8DFU) 4"(4 DFU) 2" 212" 212" 212" 2" 2" 2" 2" 2" 2" 2" 2" WC LAV WC LAV WC LAV WC LAV 2" 4" 212" 2" 2" 2" 2" 2" 2" SK 2" 2" 2" SK SK SK 2"(2 DFU) 2"(4 DFU) 2"(6 DFU) 2"(8 DFU) 2" 2" 4"VTR 2"2" 4"(12 DFU) 4"(13 DFU)2"(8 DFU) 4"(3 DFU) 4"(16 DFU) 4"(24 DFU) 4"(32 DFU) 4" 4"(8DFU) 4"(4 DFU) 2" 212" 212" 212" 2" 2" WC WC LAV WC 4" 4"VTR 2" 2" SHR 2" 2" 2" LAV 2" 2" SHR 2" 2" 2" LAV 2"(2 DFU) 2" SHR 212" 2"(2 DFU) SHR 2" WC 2" (2 DFU) 2" SK 2" 2" 2" 2" 2" 2" 2"(2 DFU) 2"(4 DFU) 2" 2" 2" 2" 2"(6 DFU) 2" SHR SHR SHR SHR 2" 2" 4" 4"(8DFU) 4"(4 DFU) 2" 212" 212" 212" 2" 2" 2" 2" 2" 2" 2" 2" WC LAV WC LAV WC LAV WC LAV 2" 4" 212" 2" 2" 2" 2" 2" 2" SK 2" 2" 2" SK SK SK 2"(2 DFU) 2"(4 DFU) 2"(6 DFU) 2"(8 DFU) 2" 2" 4"VTR 2"2" 4"(12 DFU) 4"(13 DFU)2"(8 DFU) 4"(3 DFU)4"(16 DFU) 4"(24 DFU)4"(32 DFU) 2" 2" 2" 2" 2" SK 2" 2" SK SK 2"(2 DFU) 2"(4 DFU) 2" 2" 4"(8DFU) 4" 4" 4"(4 DFU) 4"(12 DFU) 212" 212" 212" 2" 2" 2" 2" 2" 2" WC LAV WC LAV WC LAV 212" 4"VTR 2" 2" SHR 2" 2" 2" 2" 2" 2"(4 DFU) 2"(8 DFU) 2" 2" 2" SHR SHR SHR2" 2" 2" SK 2" 2" 2" SK SK 2" 2" LAV 2" WC 2" SK 2" 2" 2"2" LAV SHR 2" 2"(2 DFU) 2" 2"(1 DFU) 2" LAV 212" WC 4" 3"4"(6 DFU) 2" 4"(3 DFU) 2"(2 DFU) SK 2" 2"(2 DFU) SHR 2" 2"(1 DFU) LAV 2" 212" WC 4" 3"4"(6 DFU)4"(3 DFU) 2"(2 DFU) SK 2" 2"(2 DFU) SK 2" 2"(1 DFU) LAV 2" 212" WC 4" 212" 2"(2DFU) SHR 2"(2 DFU) SHR 2" 2"(1 DFU) LAV 2" WC 212" 4" 3"4"(6 DFU)4"(3 DFU) 2"(2 DFU) SK 2" FD FD NO SCALE SANITARY RISER DIAGRAM1 2" PD 6" 2" 2" 2" 6" 2" ELEV. SUMP PUMP 2" COPDCOPDCOPDCOPD 4"(8 DFU) 4"(8 DFU) 4"(8 DFU) 4"(40 DFU) 4"(16 DFU)4"(6 DFU) 4"(5 DFU) 2" 4"(66 DFU)4"(64 DFU)2" 2" 4"(11 DFU) 4"(12 DFU) 4"(14 DFU) 4"(15 DFU)4"(3 DFU) 4"(69 DFU) 8"(86 DFU) 4"(84 DFU) 2"(6 DFU) 4"(34 DFU) 4"(13 DFU) 4"(56 DFU) 4"(16 DFU) 4"(86 DFU) 4"(3 DFU) 2" 2" 2" 2"(10 DFU) 4"(24 DFU) 4"(8 DFU) 6" 4" 2" 1/4"/FT SLOPE 4"(156 DFU) 2"(12 DFU) 2"(14 DFU) 4"(70 DFU) 1/4"/FT SLOPE 2" BUILDING WALL DUPLEX SEWAGE EJECTORS 6" SANITARY SEWER GRADE SUMP PIT (SEE 4.03) EJ-1 FD 4" 2" 4" 4"(32 DFU) FD COPD FD 3"(3DFU) MR 2" VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: SANITARY RISER DIAGRAM P4.02 AH NO SCALE STORM RISER DIAGRAM1 ALL STORM PIPING RUN @ 18"/FT SLOPE SIZING BASED ON 3"/HR RAINFALL RATE. GROUND 2ND FLOOR 3RD FLOOR 4TH FLOOR ROOF LOWER 3" OD 3" RD (24 GPM) 3" RD 3" OD (18 GPM) 3" OD 3" OD 3" OD TERMINATE 3" OD ABOVE GRADE BUILDING WALL 3" OD 3" OD 3" RD (26 GPM) 3" RD 3" OD (22 GPM) 3" OD 3" OD 3" OD 3" OD 3" OD DUPLEX SUMP PUMPS COG 6" STORM SEWER 5'-0" CONTINUATION BY SITE CONTRACTORTO SANITARY VENT SYSTEM 114" PD 3" RD 3" RD 6" RD 6" RD 3" RD 3" RD 4" AD 4" ADTD 4"ST (8 GPM)4"ST (14 GPM) 4"ST (24 GPM) SP-1 NO SCALE GAS RISER DIAGRAM2 GROUND 2ND FLOOR ROOF LOWER BUILDING WALL GAS UP TO METER GWH 199 CFH GWH 199 CFH BOILER 300 CFH M GAS METER (COORDINATE INSTALLATION REQ'TS WITH LOCAL GAS COMPANY) INCOMING GAS SERVICE BY GAS CO. GAS PRESSURE REGULATOR VENTS. PROVIDE W/GOOSENECK TERMINATION 3RD FLOOR 4TH FLOOR G LINE SIZE VENTS (TYP) 193 CFH STAND-BY GENERATOR GGBOILER 300 CFHGG GGDEVELOPED LENGTH - 150 FEET SIZING BASED ON INCOMING 7" WC PRESSURE G G 2" 112" 112" 2" 112" 112" 112" 112" 112" 112" 3"(1,191 CFH) G 6" RD VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: STORM & GAS RISER DIAGRAM P4.03 AH DESCRIPTIONSYMBOL MAXIMUM WATER CONSUMPTION WASTE VENT D.F.U.W.S.F.U. CONNECTIONS HOT COLD FIXTURE TRIM REMARKS PLUMBING FIXTURE SCHEDULE /SAN. REFER TO ARCHITECTURAL PLANS FOR FIXTURE MOUNTING HEIGHTS. MUSTEE MOP BASIN #65M 24"X36"X10", MOLDED STONE WITH FACTORY INSTALLED STAINLESS STEEL DOME STRAINER AND SEDIMENT BASKET. CHICAGO #897-CP FAUCET W/ VACUUM BREAKER,WALL BRACE, CHROME PLATED, PAIL HOOK, AND HOSE THREAD ON SPOUT. FIAT #832AA-HOSE BRACKET COMBINATION FIAT #MSG2424 STAINLESS STEEL WALL GUARD MISCELLANEOUS EQUIPMENT SCHEDULE NO.NO. REQUIREDEQUIPMENT LOCATION MANUFACTURER REMARKSMODEL NO. TP TRAP PRIMER 1 PER FLOOR DRAIN SA AS SHOWN ON PLANS PRECISION PLUMBING PRODUCTS # PR-500 "PRIME RITE", CORROSION RESISTANT BRASS BODY, "O" RING SEALS, 1/2" INLET AND OUTLET, AND INTEGRAL VACUUM BREAKER. INSTALL THE VALVE AT A MINIMUM OF 12" ABOVE FINISHED FLOOR. PROVIDE WITH DISTRIBUTION # DU-2 FOR TWO, # DU-3 FOR THREE, OR # DU-4 FOR FOUR DRAIN CONNECTIONS. PRECISION PLUMBING PRODUCTS, HARD DRAWN COPPER BODY WITH WROUGHT COPPER FITTINGS, PISTON TYPE WITH LUBRICATED EPDM "O" RING SEALS, MEETING ASSE 1010 OR PDI WH-201. PROVIDE PDI SIZES "A" THROUGH "F" AS SHOWN ON PLANS. PROVIDE SIZE "A" UNLESS SHOWN OTHERWISE ON THE PLANS. BELL & GOSSETT # LF-CB "CIRCUIT SETTER PLUS", LEAD FREE CAST BRONZE BODY, BRASS BALL, CALIBRATED BALANCE VALVE, DIFFERENTIAL PRESSURE READOUT PORTS, DRAIN PORT, MEMORY STOP, NAMEPLATE AND 1/2" VALVE BODY SIZE UNLESS SHOWN OTHERWISE ON PLANS. SET AND BALANCE TO 0.5 GPM FLOW RATE UNLESS SHOWN OTHERWISE ON PLANS AND PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. FCV AS SHOWN ON PLANS AT HOT WATER RETURN PIPING AS SHOWN ON PLANS AS SHOWN ON PLANS AS SHOWN ON PLANS JAY R. SMITH # 1010Y (-E0X-C-R-CID), 15" DIAMETER CAST IRON BODY, FLASHING CLAMP, GRAVEL STOP, UNDERDECK CLAMP, SUMP RECEIVER, HUBLESS OUTLET, FIXED EXTENSION - HEIGHT AS REQUIRED BY INSTALLED INSULATION THICKNESS, AND CAST IRON DOME BOLTED OR LOCKED DOWN. PROVIDE OUTLET SIZE AS SHOWN ON PLANS. AS SHOWN ON PLANS JAY R. SMITH # 1080Y (-E0X-C-R-CID), 15" DIAMETER CAST IRON BODY, FLASHING CLAMP, GRAVEL STOP, UNDERDECK CLAMP, SUMP RECEIVER, HUBLESS OUTLET, FIXED EXTENSION - HEIGHT AS REQUIRED BY INSTALLED INSULATION THICKNESS, CAST IRON DOME BOLTED OR LOCKED DOWN AND 2" HIGH WATER DAM. PROVIDE OUTLET SIZE AS SHOWN ON PLANS. JAY R. SMITH # 4762 - 12" x 12" - CL, TYPE 304 STAINLESS STEEL PANEL AND FRAME WITH CONCEALED HINGE, KEY OPERATED CYLINDER LOCK. PROVIDE WITH NAILER SLOTS FOR INSTALLATION IN STUD WALLS AND ANCHOR STRAPS FOR INSTALLATION IN MASONRY CONSTRUCTION. AP AS SHOWN ON PLANS AS SHOWN ON PLANS RPZ-1 AS SHOWN ON PLANS MAKE-UP WATER TO BOILER WATTS # 009QT-S, MEETING ASSE 1013, CAST BRONZE BODY, QUARTER TURN TEST COCKS, QUARTER TURN BALL VALVES, BRONZE STRAINER, AND # 909AG AIR GAP FITTING. DCV-1 AS SHOWN ON PLANS WATER SERVICE WATTS # LF-007, MEETING ASSE 1013, LEAD FREE CAST COPPER ALLOY, QUARTER TURN TEST COCKS, RESILIENT SEATED NON-RISING STEM GATE VALVES AND WATTS #77F-DI-FDA EPOXY COATED CAST IRON STRAINER AND # 957AG AIR GAP FITTING. AS SHOWN ON PLANS NFWH AS SHOWN ON PLANS PRIER PRODUCTS # C-634NBX1, SATIN NICKEL PLATED BRASS 1" MALE INLET BY 3/4" FEMALE INLET, 3/4" THREADED HOSE CONNECTION, LOOSE KEY HANDLE, HYDRANT LENGTH AS REQUIRED FOR INSTALLED WALL THICKNESS, ADJUSTABLE WALL CLAMP, BRASS BOX WITH SATIN NICKEL PLATED FINISH AND INTEGRAL ASSE 1052 DOUBLE CHECK VACUUM BREAKER. HB AS SHOWN ON PLANS PRIER PRODUCTS # C-158NP.75, ROUGH CHROME PLATED BRASS 3/4" FEMALE FIP INLET, 3/4" THREADED HOSE CONNECTION, METAL WHEEL HANDLE, AND ASSE 1011 INTEGRAL VACUUM BREAKER. AS SHOWN ON PLANS AS SHOWN ON PLANS PRV-1 AS SHOWN ON PLANS BUILDING 2 WATER SERVICE LOCATION WATER HEATER SCHEDULE TAG GWH STORAGE GAL G.P.H. VOLTAGE 120 MANUFACTURER AND MODEL No REMARKSLOCATIONBTU/HR RECOVERY @ ƒ5,6(QUANTITY AO SMITH BTH-199 100 235199 LOWER LEVEL MECHANICAL ROOM EFFICIENCY % 95% FLUE DIA. 4" DIMENSION DIA.HEIGHT 27 3/4"75 1/2" LEAD FREE BRASS BODY WITH ROUGH BRASS FINISH, CORROSION RESISTANT INTERNAL PARTS, AND UNION CHECK STOPS WITH REMOVABLE STRAINERS, ASSE 1017 COMPLIANT, CAPABLE OF 52 GPM WITH A 10 PSI DIFFERENTIAL AND A MINIMUM FLOW RATE OF 5 GPM. SET MAXIMUM TEMPERATURE TO 120F. MIXING VALVE SCHEDULE TAG MANUFACTURER AND MODEL No LOCATION STYLE PIPE SIZES TMV-1 POWERS LFMM433 AT WATER HEATERS BUILDINGS 1, 2 & 3 ON WALL INLET OUTLET 1 1/4"1 1/4" MIN. FLOW TO ASSE 1017 5 GPM MAX FLOW @ 10PSI DROP 52 GPM REMARKSOUTLET TEMPERATURE ƒ) MAXIMUM PLUMBING PUMP SCHEDULE MOTOR VOLTSHPRPM 2800 PHASE 120 1 HEAD REMARKS 1 GPM 8 FT TAG LOCATION LEAD-FREE BRONZE BODY PUMPCPDOMESTIC HWR SERVICE SP-1 DISCHARGE - DOMESTIC EXPANSION TANK MANUFACTURER AND MODEL No TAG LOCATION STYLE TANK VOLUME (GAL) MAX ACCEPTANCE (GAL) DIMENSION (INCHES) TANK CONNECTION (INCHES) LINE PRESSURE (PSI)DIA.HEIGHT REMARKS ET AMTROL ST-30V-C FLOOR 14 11.3 15 24 3/4 70 1/2 1750 120 1 50 GPM 21 FTSP-2 WEIL 1411-538 ELEVATOR PIT 1 1/2" PROVIDE WITH ZOELLER # 30-0030 NON-CLOG, FLAPPER TYPE, CHECK VALVE. PROVIDE WITH WEIL #8245 FLOAT SWITCH WITH POWER CORD AND PIGGYBACK PLUG. COVER: FIBERBASIN #FIB24SQ 28" X 1.5" THICK SQUARE LIGHT DUTY FIBERGLASS GRID GRATE WITH FRAME. INSTALL TANK ACCORDING TO MANUFACTURER'S RECOMMENDATIONSAT WATER HEATERS AS SHOWN ON PLANS 2 PROVIDE VENTING PER MANUFACTURERS REQUIREMENTS PRV-1 WATTS 212" LF223S-HP, IRON BODY, STAINLESS STEEL SEAT, STAINLESS STEEL BOLTS, STRAINER, INLET AND OUTLET SIZE AS SHOWN ON PLANS, 50-95 PSI REDUCED PRESSURE RANGE. SET OUTLET PRESSURE TO 95 PSI WITH FLOW RATE OF 170 GPM AT A FALL OFF PRESSURE OF 20 PSI DIFFERENTIAL. PRV-3 WATTS 1" LF223S, LEAD FREE BRONZE BODY, STAINLESS STEEL SEAT, STAINLESS STEEL BOLTS, INLET AND OUTLET SIZE AS SHOWN ON PLANS, 50-95 PSI REDUCED PRESSURE RANGE. SET OUTLET PRESSURE TO 95 PSI WITH FLOW RATE OF 40 GPM AT A FALL OFF PRESSURE OF 15 PSI DIFFERENTIAL. PRV-2 WATTS 212" LF223S, IRON BODY, STAINLESS STEEL SEAT, STAINLESS STEEL BOLTS, STRAINER, INLET AND OUTLET SIZE AS SHOWN ON PLANS, 25-75 PSI REDUCED PRESSURE RANGE. SET OUTLET PRESSURE TO 70 PSI WITH FLOW RATE OF 170 GPM AT A FALL OFF PRESSURE OF 20 PSI DIFFERENTIAL. PRV-2 AS SHOWN ON PLANS BUILDING 2 WATER SERVICE LOCATION PRV-3 AS SHOWN ON PLANS BUILDING 2 WATER SERVICE LOCATION FLOW CONTROL VALVE ACCESS PANEL MECH. RM MECH. RM AS SHOWN ON PLANS ACO TRENCH DRAIN MODEL K100 WITH TYPE 410D / 412D GALVANIZED GRATE AMERICAN STANDARD # 215AA.104 "CADET PRO RIGHT HEIGHT" TANK TYPE WHITE VITREOUS CHINA FIXTURE WITH ELONGATED BOWL, 1.28 GALLONS PER FLUSH, AND SIPHON FLUSH ACTION WITH 3" OVERSIZED FLAPPER VALVE, MaP SCORE OF 1,000g AND CLOSE-COUPLED TANK WITH LEFT HAND METAL TRIP LEVER. BEMIS #1520EC WHITE ELONGATED, CLOSED-FRONT MOLDED WOOD SEAT WITH COVER WITH EASY CLEAN & CHANGE HINGES, McGUIRE # LF2166CC LEAD FREE BRASS ANGLE STOP VALVE WITH RISER AND CHROME-PLATED ESCUTCHEON. McGUIRE # LF2165CCLK LEAD FREE BRASS LOOSE KEY COMPRESSION ANGLE STOP VALVES WITH RISERS AND ESCUTCHEONS, McGUIRE # B8872CF 1-1/4" 17 GAUGE CAST CHROME PLATED BRASS ADJUSTABLE P-TRAP AND WASTE ARM WITH CLEANOUT PLUG AND ESCUTCHEON. McGUIRE # LF2165CC LEAD FREE BRASS WHEEL HANDLE ANGLE STOP VALVES WITH RISERS AND ESCUTCHEONS, McGUIRE # 151M CUP STRAINER WITH 1-1/2" 17 GAUGE TAILPIECE, McGUIRE # B8912CF 1-1/2" 17 GAUGE CAST CHROME PLATED BRASS ADJUSTABLE P-TRAP WITH BRASS CLEANOUT AND ESCUTCHEON. PROVIDE WITH INSINKERATOR BADGER 5 FOOD WASTE DISPOSER 39 WATTS EJ-1 JAY R. SMITH # 2110L (-B), CAST IRON BODY, 8" ROUND, LOOSE, MEDIUM DUTY, CAST IRON GRATE, SEDIMENT BUCKET, BOTTOM OUTLET, SEEPAGE PAN,TRAP PRIMER CONNECTION AND MEMBRANE FLASHING CLAMP. USE PUSH-ON JOINT OF OUTLET SIZE AS SHOWN ON PLANS. MANUFACTURER AND MODEL No CAPACITY EACH DUPLEX SUMP PUMP - WEIL MODEL 1408, SUBMERSIBLE WITH 1.25" DISCHARGE, CAST IRON CONSTRUCTION WITH BRONZE, SEMI-OPEN TYPE IMPELLER EXTERIOR DRAINS, FOOTING AND UNDERSLAB DRAINS 1/3 1750 120 1 30 GPM 20 FT 1 1/2"SEE DETAIL ON SHEET P6.01 FOR SPECIFICATIONS CIRCULATING PUMP BELL & GOSSETT NBF-9U/LW DUPLEX SEWAGE EJECTOR PUMPS WEIL SERIES 2436 SUBMERSIBLE GRINDER MECH. RM LOWER LEVEL SANITARY DRAINAGE 1 1750 120 1 35 GPM 19 FT 2"SEE DETAIL ON SHEET P6.01 FOR SPECIFICATIONS AS SHOWN ON PLANS JAY R SMITH 2142-U 12" ROUND TOP, HEAVY DUTY DRAIN WITH FREE STANDING SEDIMENT BUCKET WITH VANDAL PROOF GRATE KOHLER #K-2609-SU "BACHATA" - 17" X 14" OVAL UNDERMOUNT STAINLESS STEEL FIXTURE-WITH REAR OVERFLOW - LUSTER FINISH GROHE #34271ENA "CONCETTO" SINGLE LEVER, CENTERSET FAUCET. KOHLER #7127-A DRAIN WITH NON-REMOVABLE METAL STOPPER AMERICAN STANDARD #0955.001EC "MURRO" WALL HUNG WHITE VITREOUS CHINA FIXTURE - CENTER HOLE WITH OVERFLOW. PROVIDE WITH WALL HANGER AND AMERICAN STANDARD #0059.020EC VITREOUS CHINA SHROUD. GRIFFORM INNOVATIONS "BARRIER FREE SHOWER PANS" MATERIAL: CORIAN COLOR: ELEGANT GRAY STYLE: TRENCH DRAIN PAN SHAPE: T651 ENTRY: SLOPING ENTRY PAN WALL: STRAIGHT WALL 6,=(ô:,'(;'((3 IN FULLY ACCESSIBLE UNIT SPEAKMAN "NEO" BRUSHED NICKEL: #SM-1000-P-BN PRESSURE BALANCE VALVE AND TRIM #233010-BN SHOWER COMBINATION #VS-126-BN WALL MOUNT GRIFFORM INNOVATIONS "BARRIER FREE SHOWER PANS" MATERIAL: CORIAN COLOR: ELEGANT GRAY STYLE: TRENCH DRAIN PAN SHAPE: T651 ENTRY: SLOPING ENTRY PAN WALL: STRAIGHT WALL 6,=(ô:,'(;'((3 LOCATE WALL MOUNT AS PER ARCHITECTURAL '5$:,1*66(73$1,1ó 5(&(663529,'(ó RADIUS AT ENTRY EDGE IN FULLY ACCESSIBLE UNIT. LOCATE WALL MOUNT AS PER ARCHITECTURAL '5$:,1*66(73$1,1ó 5(&(663529,'(ó RADIUS AT ENTRY EDGE KOHLER #K-3325-HCF "UNDERTONE PRESERVE" - 21" ;;ò'((36,1*/(&203$570(17 UNDERMOUNT STAINLESS STEEL FIXTURE GROHE #32665DC1 "CONCETTO" SINGLE HANDLE CENTERSET FAUCET WITH PULL-OUT LAMINAR SPRAY - SUPERSTEEL INFINITY FINISH ELKAY #ELUHAD211555 - 21" X 16" X 5 3/8" DEEP, SINGLE COMPARTMENT UNDERMOUNT STAINLESS STEEL FIXTURE - LUSTERTONE PROVIDE WITH INSINKERATOR BADGER 5 FOOD WASTE DISPOSER IN FULLY ACCESSIBLE UNIT VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: SCHEDULES SHEET 1 OF 1 P5.01 AH PRV-2 SET AT 60 PSI NORMALLY CLOSED BYPASS VALVE (TYP) 4" 212" DOUBLE CHECK VALVE ASSEMBLY BACKFLOW PREVENTER - DCV-1 212" MAIN RISER CONTROL VALVE INLET STRAINER WITH BLOW OUT VALVE CAP WATER METER WITH REMOTE READOUT 4" 2"NORMALLY CLOSED BYPASS VALVE PRV-1 SET AT 95 PSIPRESSURE GAUGE (TYP) 4" DOMESTIC WATER SERVICE LEAD-IN. SIZE AS INDICATED. NOTES: 1. PROVIDE SUPPORT TO EQUIPMENT FROM WALL/FLOOR AS REQUIRED. 2. PROVIDE 30" CLEARANCE IN FRONT OF RPZ 3. PROVIDE 18" CLEARANCE ABOVE RPZ. 4. PROVIDE 12" CLEARANCE IN BACK OF RPZ TO WALL. MAXIMUM 5'-0" AFF MINIMUM 2'-6" AFF NOT TO SCALE THERMOSTATIC MIXING VALVE6 DIAL THERMOMETER IN TEE FITTING. REFER TO SPECIFICATIONS. PIPE REDUCER OR INCREASER WHERE REQUIRED TO MATCH PIPE SIZES WITH VALVE PORT SIZES THERMOSTATIC MIXING VALVE. REFER TO SPECIFICATIONS AND/OR SCHEDULE. COLD WATER SUPPLY. SHUT-OFF VALVE (TYPICAL) PIPE UNION (TYPICAL) STRAINER (TYPICAL) CHECK VALVE (TYPICAL) 30" DEEP x 12" WIDE HEAT TRAP REFER TO FLOOR PLANS FOR PIPE SIZES. PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. PIPING CONNECTIONS SHOWN ARE FOR POWERS # 430 AND # 1400 SERIES THERMOSTIC MIXING VALVES. INSTALL OTHER MANUFACTURER'S VALVES PER THEIR PUBLISHED INSTALLATION INSTRUCTIONS. MOUNT THERMOSTATIC MIXING VALVE TO WALL AT 5'-0" AFF, AT A LOCATION EASILY ACCESSIBLE FOR SERVICING. NOT TO SCALE INCOMING DOMESTIC WATER SERVICE1 NOT TO SCALE LARGE EXPANSION TANK7 PIPE HANGER TO STRUCTURE ABOVE AIR CHARGING VALVE. FILL TANK WITH AIR PRESSURE TO MATCH WATER PRESSURE. PIPE UNION: DIELECTRIC TYPE IF REQUIRED FOR DISSIMILAR METALS DRAIN VALVE FLOOR OR PLATFORM PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. MAKE PIPE SAME SIZE AS TANK FITTING. FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION PROCEDURE. VERIFY PROPER OPERATION WHEN INSTALLED. PROVIDE SEISMIC STRAP/BRACING IF/AS REQUIRED BY LOCAL CODE. ƒ)+27:$7(56833/< FROM WATER HEATER. REFER TO FLOOR PLANS. ƒ)7(03(5(':$7(5 SUPPLY TO FIXTURES SHOWN ON FLOOR PLAN NOT TO SCALE ELEVATOR SUMP PUMP4 6" MINIMUM PIPE UNION STRUCTURAL FOOTING HIGH LEVEL ALARM TETHERED FLOAT SWITCH ON-OFF TETHERED FLOAT SWITCH ARRANGEMENT SHOWN IS SCHEMATIC; ADJUST TO SUIT ACTUAL CONDITIONS. LOCATE FLOATS AT ELEVATIONS RECOMMENDED BY PUMP MANUFACTURER. INTERLOCK OF HIGH LEVEL ALARM WITH ALARM BELL (REFER TO FLOOR PLANS IF PROVIDED) IS SPECIFIED IN DIVISION 16. INTERLOCK OF HIGH LEVEL ALARM WITH BUILDING AUTOMATION SYSTEM (REFER TO SPECIFICATIONS IF PROVIDED) IS SPECIFIED IN DIVISION 15. REFER TO ARCHITECTURAL AND STRUCTURAL PLANS FOR LOCATION OF CONCRETE SUMP PIT. INSTALL PIPE AND CONTROLS TO NOT INTERFERE WITH ELEVATOR ITEMS. HIGH LEVEL ALARM PER SPECIFICATIONS AND SCHEDULES, WITH POWER WIRING SPECIFIED IN DIVISION 16 SIMPLEX RECEPTACLE AND OUTLET BOX IS SPECIFIED IN DIVISION 16. MOUNT ON WALL NEAR ELEVATOR DOORS. SUMP PUMP RECEPTACLE PLUG AND FLOAT SWITCH PIGGYBACK PLUG NON-CLOG CHECK VALVE GROMMET AROUND WIRING ELEVATOR SHAFT FLOOR STEEL GRATE IS SPECIFIED IN DIVISION 3 24"x24"x24" DEEP CONCRETE PIT PER STRUCTURAL DRAWINGS SUMP PUMP: REFER TO SCHEDULE AND SPECIFICATIONS ONE PIPE SIZE SMALLER THAN MAIN LINE SIZE. PRV-3 SET AT 70 PSI 1" 212" 4" 4" 212" 4" 212"212" 4" 4" G NO SCALE GAS FIRED WATER HEATER2 EQUAL INSTALL DRAIN VALVE FURNISHED WITH HEATER REFER TO SPECIFICATIONS, SCHEDULES AND NOTES FOR MORE INFORMATION. PIPING ARRANGEMENT SHOWN IS SCHEMATIC. VERIFY ALL CONNECTION SIZES AND LOCATIONS PER MANUFACTURER'S REQUIREMENTS. ADJUST TO SUIT FIELD CONDITIONS. REFER TO FLOOR PLANS FOR PIPE SIZES. PROVIDE SEISMIC STRAP OR BRACING IF/AS REQUIRED BY LOCAL AUTHORITIES. SEE MECHANICAL PLANS FOR WATER HEATER VENTING. G EQUAL EQUAL EQUAL PROVIDE DIELECTRIC PIPE UNION AT TANK CONNECTIONS, FOR CONNECTION OF DISSIMILAR METALS (TYPICAL) SET WATER HEATER ON CONCRETE EQUIPMENT PAD PER SPECIFICATIONS GAS-FIRED WATER HEATER; REFER TO SPECIFICATIONS AND SCHEDULE. PIPE UNION ABOVE TOP OF TANKS (TO FACILITATE REMOVAL) PROVIDE THERMOMETER IN TEE FITTING (TYPICAL) 140 DEGREE F HOT WATER TO THERMOSTATIC MIXING VALVE PROVIDE AUTOMATIC VACUUM RELIEF VALVE ABOVE TOP OF WATER HEATER PROVIDE HARD COPPER PIPING AT WATER HEATER CONNECTIONS FROM COLD WATER SUPPLY TO WATER HEATER, WITH NO CHECK VALVES INTERVENING WELDED STEEL EXPANSION TANK POLYPROYPLENE LINING AND BUTYL DIAPHRAGM, FDA AND NSF APPROVED FOR DOMESTIC WATER SERVICE INTEGRAL BASE FOR FLOOR MOUNTING 4" 5" 5" 5" 18" 12" MIN BOTTOM FINISHED FLOOR CLEANOUT TYPICAL SHUT-OFF VALVE TYPICAL UNION HIGH LEVEL ALARM SECOND PUMP ON FIRST PUMP ON PUMPS OFF CONTROL PANEL. REFER TO FLOOR PLAN FOR LOCATION. WIRING CONNECTIONS TO PANEL AND WIRING CONNECTIONS TO FLOATS AND PUMPS IS BY ELECTRICAL CONTRACTOR. GROMMET AT WIRE PENETRATION. STEEL PLATE COVER BOLTED DOWN WITH GAS-TIGHT GASKET, WITH OPENINGS FOR VENT AND OUTLETS. SEAL OPENINGS AND CRACKS WITH SILICONE. BASIN OF DIAMETER, DEPTH, AND MATERIAL PER SCHEDULE AND SPECIFICATIONS. TYPICAL TETHERED FLOAT SWITCH FOR PUMP CONTROL SEWAGE EJECTORS PER SPECIFICATIONS AND SCHEDULE. 2"VENT; REFER TO FLOOR PLAN FOR CONTINUATION. SANITARY WASTE. REFER TO FLOOR PLANS FOR INVERT ELEVATION. SEWAGE EJECTOR DISCHARGE TO SANITARY. REFER TO FLOOR PLAN FOR LOCATION. COMBINE DISCHARGES FROM BOTH PUMPS. TYPICAL FULL FLOW NON-CLOG CHECK VALVE. ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT ACTUAL INSTALLATION CONDITIONS. PIT EXCAVATION IS BY PLUMBING CONTRACTOR. LOCATE FLOATS AT ELEVATIONS RECOMMENDED BY PUMP MANUFACTURER. LOCATE PIT WITHIN 12" OF AN INTERIOR NON-BEARING PARTITION TO SUPPORT PIPES EXITING PIT AND ALLOW 36" ACCESS SPACE IN FRONT OF PIT. COORDINATE PIT INSTALLATION NEAR AN EXTERIOR WALL FOR FOOTINGS / FOUNDATIONS DEPTHS. LOCATE REMOTE CONTROL PANEL AS CLOSE AS POSSIBLE TO PIT. VERIFY EXACT ENTERING INVERT ELEVATION PRIOR TO ORDERING BASIN. NO SCALE DUPLEX SEWAGE EJECTOR3 GAS SUPPLY TO WATER HEATERS WITH GAS COCK, UNION WITH GROUND JOINT, 6" LONG DIRT LEG, AND REDUCER AT CONNECTION STUB INSTALL ASME TEMPERATURE AND PRESSURE RELIEF VALVE FURNISHED WITH WATER HEATER PROVIDE HARD COPPER RELIEF VALVE DISCHARGE PIPE, FULL SIZE OF VALVE OUTLET. TERMINATE OVER APPROVED RECEPTOR WITH AIR GAP PER CODE 3" 3" 3" 12" 6" MIN BOTTOM FINISHED FLOOR CLEANOUT TYPICAL SHUT-OFF VALVE TYPICAL UNION HIGH LEVEL ALARM SECOND PUMP ON FIRST PUMP ON PUMPS OFF CONTROL PANEL. REFER TO FLOOR PLAN FOR LOCATION. WIRING CONNECTIONS TO PANEL AND WIRING CONNECTIONS TO FLOATS AND PUMPS IS BY ELECTRICAL CONTRACTOR. GROMMET AT WIRE PENETRATION. STEEL PLATE COVER BOLTED DOWN WITH GAS-TIGHT GASKET, WITH OPENINGS FOR VENT AND OUTLETS. SEAL OPENINGS AND CRACKS WITH SILICONE. BASIN OF DIAMETER, DEPTH, AND MATERIAL PER SCHEDULE AND SPECIFICATIONS. TYPICAL TETHERED FLOAT SWITCH FOR PUMP CONTROL SUMP PUMPS PER SPECIFICATIONS AND SCHEDULE. 2"VENT; REFER TO FLOOR PLAN FOR CONTINUATION. STORM LINE. REFER TO FLOOR PLANS FOR INVERT ELEVATION. SUMP PUMP DISCHARGE TO STORM. REFER TO FLOOR PLAN FOR LOCATION. COMBINE DISCHARGES FROM BOTH PUMPS. TYPICAL FULL FLOW NON-CLOG CHECK VALVE. ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT ACTUAL INSTALLATION CONDITIONS. PIT EXCAVATION IS BY PLUMBING CONTRACTOR. LOCATE FLOATS AT ELEVATIONS RECOMMENDED BY PUMP MANUFACTURER. LOCATE PIT WITHIN 12" OF AN INTERIOR NON-BEARING PARTITION TO SUPPORT PIPES EXITING PIT AND ALLOW 36" ACCESS SPACE IN FRONT OF PIT. DO NOT INSTALL PIT NEAR AN EXTERIOR WALL BECAUSE OF INTERFERENCE WITH FOOTINGS / FOUNDATIONS. LOCATE REMOTE CONTROL PANEL AS CLOSE AS POSSIBLE TO PIT. VERIFY EXACT ENTERING INVERT ELEVATION PRIOR TO ORDERING BASIN. NO SCALE DUPLEX SUMP PUMP5 36" DIA ELEVATOR SHAFT WALL SHUT-OFF VALVE EXPOSED 2" SUMP PUMP DISCHARGE PIPE SHALL BE SCHEDULE 40 GALVANIZED STEEL WITH MALLEABLE IRON FITTINGS FIRST FLOOR SLAB COUPLING 2" SUMP PUMP DISCHARGE SHALL BE SCHEDULE 40 PVC WITH SOCKET WELD FITTINGS. DISCHARGE INTO INDIRECT WASTE RECEPTOR, WITH AIR GAP, WHERE SHOWN ON FLOOR PLAN SEAL WALL PENETRATION WATER-TIGHT DUPLEX SUMP PUMP 1. A WEIL PUMP COMPANY DUPLEX SUBMERSIBLE 1.25" DISCHARGE SUMP PUMP, MODEL 1408 SHALL BE FURNISHED AS A COMPLETE UNIT, AS SUPPLIED BY CULLEN ASSOC., INC. (732-988-9600) . 2. PUMPS SHALL BE HERMETICALLY SEALED DRY RUN TYPE WITH EPOXY ENCAPSULATION WHICH IS NON-AGING, MOISTURE, ACID AND ALKALI RESISTANT PERMITTING PUMPS TO OPERATE WITHOUT OVERHEATING AT A LOW OR NO WATER LEVEL. 3. PUMPS SHALL BE SUBMERSIBLE TYPE, CAST IRON CONSTRUCTION, BRONZE SEMI-OPEN TYPE IMPELLER, HEAVY DUTY MECHANICAL SEAL, 300 SERIES STAINLESS STEEL SHAFT, (2) DOUBLE SEALED BALL BEARINGS, STAINLESS STEEL SELF-CLEANING SUCTION STRAINER, 15' OF NEOPRENE JACKETED POWER CABLE 4. PUMPS TO HAVE A CAPACITY OF 30 GPM AT A TOTAL DYNAMIC HEAD OF 20 FEET. PUMP TO HAVE CURVE CHARACTERISTIC SO AS NOT TO OVERLOAD THE 1/3 HP MOTOR AT ANY POINT THROUGHOUT ITS ENTIRE RANGE. 5. MOTORS TO BE 1/3 HP, 1 PHASE, 60 HERTZ, 115 VOLTS, 1750 RPM, HOUSED IN AIR FILLED, WATERTIGHT CAST IRON MOTOR SHELL WITH THE WINDINGS HAVING CLASS "F" INSULATION, NEMA-6 AND PRE-LUBRICATED DOUBLE SEALED BEARINGS. OIL FILLED MOTORS OR SLEEVE TYPE BEARINGS ARE NOT ACCEPTABLE. 6. PUMP CONTROL TO BE VIA A DUPLEX WEIL PUMP CONTROL PANEL MODEL 8158 HAVING MOUNTED AND WIRED WITHIN A NEMA-1 ENCLOSURE: TWO COMBINATION MANUAL DISCONNECTS AND MOTOR CIRCUIT PROTECTORS, ADJUSTABLE AMBIENT COMPENSATED BI METALLIC THERMAL OVERLOADS WITH RESETS, TWO MAGNETIC CONTACTORS, TWO HAND-OFF AUTOMATIC SELECTOR SWITCHES WITH RUN LIGHTS, ONE CONTROL CIRCUIT TRANSFORMER, ONE ELECTRIC PUMP ALTERNATING RELAY, ONE HIGH WATER ALARM LIGHT, BELL, SILENCE PUSH-BUTTON AND AUXILIARY ALARM DRY CONTACT. A NUMBERED AND WIRED TERMINAL STRIP SHALL BE PROVIDED IN THE PANEL TO ACCEPT (4) LEVEL SENSING FLOAT SWITCHES LOCATED IN THE WET WELL TO PROVIDE LEAD-LAG AUTOMATIC PUMP OPERATION, AS WELL A HIGH WATER ALARM SIGNAL. PROVIDE A 36" DIAMETER X 78" DEEP FIBERGLASS BASIN WITH ANTIFLOATATION FLANGE AS SHOWN ON THE PLANS WITH INLET OPENING AS REQUIRED. THE BASIN SHALL BE SUPPLIED WITH MATERIALS FOR FIELD MOUNTING AN INLET OPENING, VENT OPENING AND TWO SIDE DISCHARGE OPENINGS AND CONTROLS AS REQUIRED. THE BASIN COVER SHALL BE STEEL AND HAVE A HINGED ACCESS DOOR OPENING FOR TWO PUMP REMOVALS. 8. PROVIDE CHECK AND GATE VALVES ON THE DISCHARGE OF EACH PUMP. COMPLETE THE PIPING AS SHOWN AND CLEAN THE BASIN OF ALL DEBRIS BEFORE STARTING PUMPS INTO OPERATION. CHECK VALVE (TYPICAL) SHUT-OFF VALVE (TYPICAL) COLD WATER SUPPLY TO WATER HEATER COLD WATER TO EXPANSION TANK RECIRCULATION PUMP WITH UNION CONNECTIONS, SHUT-OFF VALVE, ON / OFF SWITCH AND STRAINER UPSTREAM, CHECK VALVE AND SHUT-OFFVALVE DOWNSTREAM SUBMERSIBLE SEWAGE PUMP FURNISH AND INSTALL, WHERE SHOWN ON THE PLANS, ONE WEIL PUMP COMPANY INC. (732-988-9600) DUPLEX SUBMERSIBLE SEWAGE GRINDER PUMP FOR INSTALLATION ON A 2613 REMOVAL SYSTEM. PUMPS SHALL BE WEIL SERIES 2436 SUBMERSIBLE GRINDER TYPE, 2" DISCHARGE FOR SEWAGE SERVICE AND EACH PUMP SHALL BE RATED TO PROVIDE 35 GPM AT 19 FT. TDH. THE SUBMERSIBLE PUMP SHALL BE CONSTRUCTED OF CLOSE GRAINED HIGH DENSITY CAST IRON AND SHALL HAVE A 3" SUCTION AND 2" DISCHARGE. THE PUMP SHALL INCLUDE A GRINDER ASSEMBLY LOCATED ON THE SUCTION SIDE OF THE PUMP IMPELLER. THE CUTTER SHALL BE CAPABLE OF GRINDING ALL MATERIALS NORMALLY FOUND IN DOMESTIC SEWAGE. THE CUTTER AND SHREDDING RING ASSEMBLY MACERATES SOLIDS INTO A SLURRY AND DISCHARGES TO THE PUMP IMPELLER. THE CUTTER AND SHREDDING RING SHALL BE MADE FORM 17-4PH SUPER HARD CORROSION RESISTANT STAINLESS STEEL THIS ASSEMBLY SHALL LEAVE NO EXPOSED SHAFT TO PERMIT PACKING OF SOLIDS. THE SHREDDING RING SHALL BE FIELD REVERSIBLE TO PROVIDE NEW CUTTING EDGES TO DOUBLE THE LIFE PUMP MOTORS SHALL BE VERTICAL, NEMA-6 AND NOT MORE THAN 1 HP, 3 PHASE, 60 CYCLE, 208 VOLTS, 1750 RPM. MOTOR SHALL BE AIR FILLED, HERMETICALLY SEALED. OIL FILLED MOTOR SHELLS SHALL NOT BE CONSIDERED EQUAL. MOTOR END BELL SHALL BE DESIGNED AS A TERMINAL BOX AND SEPARATED FROM THE MOTOR SHELL BY A COMBINATION BEARING SUPPORT AND INSPECTION PLATE. MOTORS SHALL BE HOUSED IN A WATERTIGHT CAST IRON SHELL WITH CLASS F INSULATION WITH PERMANENTLY LUBRICATED UPPER AND LOWER BALL BEARINGS. MOTOR SHAFT SHALL BE 300 SERIES STAINLESS STEEL. MOTORS USING SLEEVE TYPE BEARINGS, CARBON STEEL SHAFTS OR MOTORS REQUIRING WATER COOLING JACKETS SHALL BE CONSIDERED EQUAL. CONTROLS SHALL BE WEIL SERIES 8230 SUBMERSIBLE LIQUID LEVEL CONTROLS. PROVIDE (4) LEVEL SENSING SWITCHES WITH 20' CORDS MOUNTED ON STAINLESS STEEL PIPE AND COVER BRACKET. SYSTEM SHALL PROVIDE ALL PUMPS OFF, LEAD PUMP OPERATION ALONG WITH ALTERNATION, TWO PUMP EMERGENCY PROTECTION AND HIGH WATER ALARM CONDITION. THE EQUIPMENT WILL INCLUDE A NEMA-1 INDOOR DUPLEX CONTROL PANEL MODEL BF-400 IN CABINET WITH HINGED DOOR, FOR WALL MOUNTING AS SHOWN ON PLANS. THE CONTROL PANEL WILL HAVE MOUNTED AND WIRED WITHIN TWO CIRCUIT BREAKER DISCONNECT SWITCHES, TWO STARTERS WITH OVERLOAD PROTECTION, TWO PUMP RUNNING LIGHTS, TWO HAND-OFF-AUTOMATIC SELECTOR SWITCHES, ONE ALTERNATING LEAD LAG RELAY, ONE NUMBERED AND WIRED TERMINAL STRIP, HIGH WATER ALARM LIGHT, BELL, SILENCE SWITCH AND AUXILIARY DRY CONTACT. PROVIDE A 36" DIAMETER X 72" DEEP FIBERGLASS BASIN WITH ANTIFLOATATION FLANGE AS SHOWN ON THE PLANS WITH INLET OPENING AS REQUIRED. THE BASIN COVER SHALL BE STEEL AND HAVE OPENINGS FOR TWO PUMP REMOVALS, AND CONTROLS. ALL CONNECTIONS PENETRATING THE COVER TO BE MADE GAS TIGHT. THE CONTRACTOR SHALL FURNISH AND INSTALL IN THE DISCHARGE LINE OF THE DUPLEX PUMPING SYSTEM A WEIL PUMP CO. MODEL 2616 DUPLEX PUMP CHECK/ISOLATION VALVE. THE ASSEMBLY SHALL CONSIST OF TWO BALL CHECK VALVES AND ONE PLUG VALVE. THE UNIT ASSEMBLY SHALL CONSIST OF TWO BALL CHECK VALVES AND ONE PLUG VALVE. THE UNIT ASSEMBLY SHALL HAVE FOUR CONTROL SEQUENCES CONSISTING OF: (1) NORMAL OPERATION WITH PUMP "A" AND "B" OPEN TO THE DISCHARGE LINE, (2) PUMP "A" ISOLATED AND PUMP "B" OPEN TO THE DISCHARGE LINE, (3) PUMP "B" ISOLATED AND PUMP "A" OPEN TO DISCHARGE LINE, (4) PUMP "A" & "B" ISOLATED FROM THE DISCHARGE LINE. WHEN EITHER OR BOTH PUMPS ARE ISOLATED THE DESIGN OF THE ASSEMBLY SHALL BE ALLOW THE SERVICING OF THE INDIVIDUAL CHECK VALVES OR THE PUMPS. 36" DIA 78" 72" ON / OFF SWITCH VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING: DETAILS SHEET 1 OF 2 P6.01 AH TRAP PRIMER VALVE CHECK VALVE SEAL SEWER GAS WATER TRAP VACUUM BREAKER PORT THE PRIMING VALVE MUST HAVE A MINIMUM ELEVATION OF 12" INCHES ABOVE THE FINISHED FLOOR PIPING ARRANGEMENT SHOWN IS SCHEMATIC: ADJUST TO SUIT FIELD CONDITIONS. PROVIDE TWELVE FEET OF SOFT COPPER TUBE ABOVE FLOOR FOR CONNECTION TO TRAP PRIMER TO BE LOCATED ABOVE CEILING. INSTALL TRAP PRIMER LINE(S) DOWNSTREAM OF TRAP PRIMER OR DISTRIBUTION UNIT USING 1/2" SOFT COPPER TUBING. INSTALL WITHOUT KINKS, AND SLOPE CONTINUOUSLY TOWARDS FLOOR DRAIN. IF PIPE IS BELOW FLOOR SLAB ON GRADE, PROVIDE 1/2" ELASTOMERIC INSULATION FROM PRIMER CONNECTION TO 1" ABOVE FLOOR SLAB. CONCEAL PIPE(S) IN PARTITION OR CHASE IN FINISHED AREAS. TRAP PRIMER AND PIPES MAY BE INSTALLED EXPOSED IN UNFINISHED, NON-PUBLIC AREAS. PROVIDE FLOOR DRAIN BODY OR P-TRAP WITH THREADED TRAP PRIMER CONNECTION. PROVIDE SWEAT TO THREADED ADAPTER. BRAZE JOINT BELOW FLOOR SLAB ON GRADE. 1/2"9' O.C.1-1/4" TO 2" 2-1/2" TO 4"10' O.C.1/2" ROD (SIZE AS REQUIRED) PIPE CLEVIS HANGER LINES UP TO AND INCLUDING 4" IN SIZE. HANGING DETAILS SHALL BE SUBMITTED TO HANGER SPACING SHALL BE AS FOLLOWS: THE ABOVE DETAIL SHALL BE USED ONLY FOR STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL. INCREASE CLEVIS HANGER SIZE TO ALLOW FOR INSULATION OF THOSE LINES REQUIRING INSULATION. FOR INSULATED LINES USE STEEL PIPE SHIELDS 1/2" TO 1" PIPE SIZE 5. 4. 7' O.C. MAX. HANGER SPACING NOTES: AT HANGER POINTS. 3. 2. 1. 3/8" INSULATION JOIST WOODEN BOLT THROUGH JOIST FLOOR ABOVE OR ROOF DOUBLE LOCK-NUT & WASHER (TYPICAL) WOODEN JOIST (TYPICAL) PIPE HANGER BOLT THROUGH JOIST (TYPICAL) 2"x2"x90 DEGREE ANGLE (TYPICAL) HOT WATER RECIRCULATION BRANCH UNION FLOW CONTROL VALVE (FCV); REFER TO FLOOR PLANS FOR PIPE SIZE. TYPICAL FULL-PORT BALL TYPE SHUT-OFF VALVE STRAINER CHECK VALVE PIPE INSULATION SECURE WITH ADHESIVE EXPOSED VALVES AND FITTINGS TYPICAL AT ALL JOINTS. AND OUTER HOLDING BAND OR USE SELF-SEALING LAPS SECURE WITH ADHESIVE MITERED FITTING FIRE RETARDANT JACKET REQUIRED PIPE INSULATION THICKNESS. WRAP WITH 1 INCH THICK, 1 POUND DENSITY TO VAPOR SEAL COLD WATER, CHILLED WATER BUTT STRIP AT JOINTS. AND STORM WATER PIPING. SECURE WITH WIRE OR TAPE. CONCEALED VALVES AND FITTINGS FINISH COAT OF MASTIC FIBERGLASS SECTIONAL INSULATION PREMOLDED FITTING 3" PIPE INSULATION. COAT OF MASTIC PREMOLDED FIBERGLASS OR RADIAL MITERED SKIM COAT OF INSULATION CEMENT. WRAP WITH FIBERGLASS REINFORCING CLOTH. OVERLAP 2 INCHES ON PIPE INSULATION. ALL SEALS AND LAPS AT TOP. SEALING LAP. THREADED ROD CLEVIS HANGER 1/2" CLEAR MAXIMUM CONCEALED PIPING FLUSH WITH FINISHED TERMINATE SLEEVE INSULATION WALL SURFACES HANGER, ROD & INSERT UP TO 3" 4" TO 6" WITHOUT INCOMPRESSIBLE INSULATING WITH INCOMPRESSIBLE INSULATING PIPE DIAMETER PIPE DIAMETER UP TO 3" DOUBLE LOCKNUTS NOTE: 6" 5" 4" USSG 16 16 16 18 THICKNESS SHIELD SHIELD USSG THICKNESS 18 16 SHIELD LENGTH 18" 21" 15" 12" BLOCK AT HANGER SHIELD LENGTH BLOCK AT HANGER 6" 8" ZINC CHROMATE PRIMER PRIOR TO INSTALLATIONGALVANIZED METAL SHIELD SHALL BE DIPPED IN STANDARD WEIGHT STEEL PIPE SLEEVE OF SIZE TO PASS PIPE ANNULAR SPACE BETWEEN PIPE AND SLEEVE TO BE PACKED WITH (UL 263). (TYP FOR EACH SIDE). FINISHED ESCUTCHEON PLATE FINISHED WALL SURFACE. PIPING EXPOSED TO VIEW FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING TO THE REQUIREMENTS OF ASTM E814 (UL 1479) AND ASTM 119 UL/FM APPROVED AND TESTED SEAL OR CAULK SLEEVES THRU MANNER. FIRE WALLS IN A SMOKE TIGHT FINISHED WALL LEAD SURFACE TIGHTLY PACKED OAKUM & POURED SEAL SLEEVE WITH COAT EXTERIOR SURFACES WITH CONTINUOUS WELD TAR COMPOUND NOTES: 1. PIPE SLEEVE FOR EXTERIOR WALL ABOVE OR BELOW GRADE. EXTERIOR WALLS DURING WALL CONSTRUCTION STANDARD WEIGHT STEEL PIPE SLEEVE INSTALLED CENTER PIPE IN SLEEVE SEALING AND ANCHORING COLLAR MASTIC OR ASPHALT SEAL WATERTIGHT WITH NOT TO SCALE PIPE PENETRATION THRU FIRE RATED WALL5 NOT TO SCALE PIPE, VALVE AND FITTING INSULATION DETAIL 11 NOT TO SCALE TYPICAL INSULATED PIPE SUPPORT6 NOT TO SCALE TYPICAL PIPE SLEEVES THRU WALL2 NOT TO SCALE PIPE PENETRATION THRU FOUNDATION WALL3 NOT TO SCALE TRAP PRIMER DETAIL1 NOT TO SCALE TYPICAL HANGER DETAILS4 NOT TO SCALE WOOD JOIST HANGER DETAILS7 NOT TO SCALE TRAP PRIMER INSTALLATION8 NOT TO SCALE FLOW CONTROL VALVE ASSEMBLY9 REFER TO SPECIFICATIONS, SCHEDULES, AND NOTES FOR MORE INFORMATION. MAKE CONNECTIONS AND PROVIDE INSTALLATION PER MANUFACTURER'S RECOMMENDATIONS. ARRANGEMENT SHOWN IS SCHEMATIC: PROVIDE REDUCERS AND ADAPTERS AS REQUIRED. NO SCALE EXTERIOR AREAWAY DRAIN10 GRASS AREA: EXCAVATE AS REQUIRED AND PATCH TO MATCH EXISTING PROVIDE 20"x20"x8" THICK 3000 PSI CLASS "C" CONCRETE PAD, REINFORCED WITH 6x6x1/4 WIRE MESH. TROWEL SMOOTH AND EDGE. SURROUND JOINT WITH CONCRETE HORIZONTAL STORM DRAIN, SIZE AS SHOWN ON PLAN, AND TYPE OF PIPE PER SPECIFICATIONS. DIRECTION OF FLOW AREAWAY DRAIN SET IN CONCRETE PAD RISER SHALL BE CAST IRON, SAME SIZE AS SEWER UP TO 4" MAXIMUM, OF LENGTH AS REQUIRED BY DEPTH OF SEWER. PROVIDE CAST IRON LONG SWEEP AT END OF LINE, ENTER TOP OF PIPE. TO SUMP PUMP VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:13pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 PLUMBING DETAILS SHEET 2 OF 2 P6.02 AH M. MECHANICAL DRAWING LIST M0.GENERAL M0.01 GENERAL NOTES & SYMBOL LIST M2.BUILDING PLANS M2.00 LOWER LEVEL PLAN M2.00P LOWER LEVEL PLAN - PIPING M2.01 GROUND FLOOR PLAN M2.01P GROUND FLOOR PLAN - PIPING M2.02 SECOND FLOOR PLAN M2.02P SECOND FLOOR PLAN - PIPING M2.03 THIRD FLOOR PLAN M2.03P THIRD FLOOR PLAN - PIPING M2.04 FOURTH FLOOR PLAN M2.04P FOURTH FLOOR PLAN - PIPING M2.05 ROOF PLAN M4.DIAGRAMS M4.01 RISER DIAGRAMS SHEET 1 OF 4 M4.02 RISER DIAGRAMS SHEET 2 OF 4 M4.03 RISER DIAGRAMS SHEET 3 OF 4 M4.04 RISER DIAGRAMS SHEET 4 OF 4 M5.SCHEDULES M5.01 SCHEDULES SHEET 1 OF 2 M5.02 SCHEDULES SHEET 2 OF 2 M6.DETAILS M6.01 DETAILS SHEET 1 OF 5 M6.02 DETAILS SHEET 2 OF 5 M6.03 DETAILS SHEET 3 OF 5 M6.04 DETAILS SHEET 4 OF 5 M6.05 DETAILS SHEET 5 OF 5 D DRAIN LINE PIPING STRAINER 'Y' TYPE WITH BLOWDOWN VALVE UNION PROVIDE ACCESS SPACE FOR SERVICING ALL MECHANICAL EQUIPMENT INCLUDING PROVIDE VOLUME DAMPERS AT EACH LOW PRESSURE SUPPLY, RETURN OUTDOOR AIR AND FIRST 20'-0" OF ALL LOW PRESSURE SUPPLY AND RETURN DUCTWORK FROM FCU UNITS ALL SUPPLY AIR DUCTWORK IN SPACES WHICH HAVE EXPOSED DUCTWORK SHALL HAVE PROVIDE COMPLETE PIPING SPECIALITIES, DAMPERS AND INSTRUMENTATION FOR EACH PIECE OF EQUIPMENT AS PER DRAWINGS, SPECIFICATIONS. 3. PROVIDE SIGHT-PROOF BACK-SHEET BEHIND RETURN AIR GRILLES. MOTORS FOR CEILING FANS, HEATING COILS, VALVES AND FILTERS 8. 7. EXHAUST DUCT BRANCH TAKE-OFF. 5. 6. 4. SHALL BE 1" ACOUSTICALLY LINED, UNLESS OTHERWISE NOTED. ACOUSTICAL LINING. GENERAL NOTES: 1. 2. PIPE DOWN PIPE UP DIRT POCKET CW A COLD WATER MAKE UP LINE ARROW INDICATES DIRECTION OF FLOW PIPE ANCHOR AIR LINE SUPPLY AIR OUTLET - 3, 2 & 1 WAY THROW U.H.UNIT HEATER S.F. / SF TO T.G. TR.R TYP. TD TR.G. S.P. S.A.D. TOP GRILLE TRANSFER GRILLE TRANSFER REGISTER TRANSFER OPENING TYPICAL TRANSFER DUCT SPILL AIR DAMPER STATIC PRESSURE SQUARE FEET DUCT SMOKE DETECTOR (XXXX) - INDICATES VOLUMETRIC FLOW RATE (CFM) SLOPING RISE IN DUCT IN DIRECTION OF ARROW SLOPING DROP IN DUCT IN DIRECTION OF ARROW DUCT SIZE - FIRST SIZE INDICATES PLAN SIZE SPIN-IN FITTING WITH VOLUME DAMPER DUCT SECTION UNDER NEGATIVE PRESSURE DUCT SECTION UNDER POSITIVE PRESSURE TRANSFER DUCT WITH ACOUSTIC LINING CEILING DIFFUSERC.D. N.T.S. O.A.I. O.A.D. R.A.D. M.V. MIN / MAX M.B.H. G.C. HWS / HWR RETURN AIR DAMPER OUTSIDE AIR INTAKE MANUAL AIR VENT OUTSIDE AIR DAMPER NOT TO SCALE GENERAL CONTRACTOR THOUSAND BTU'S PER HOUR MINIMUM / MAXIMUM HOT WATER SUPPLY / HOT WATER RETURN F.F. F.M.S F.C. EUH E.A.D. F.D. C.U. DEF CV C.U.H. CFM C.G. FLEXIBLE CONNECTION ELECTRIC UNIT HEATER EXHAUST AIR DISCHARGE FIRE DAMPER AND ACCESS DOOR FLOW MEASURING STATION FINISHED FLOOR CONDENSING UNIT CUBIC FEET OF AIR PER MINUTE CONSTANT VOLUME CABINET UNIT HEATER DRYER EXHAUST FAN CEILING GRILLE U UNDERCUT DOOR SUPPLY AIR OUTLET, 4 WAY SOUND LINING IN DUCTWORK RETURN AIR REGISTER A.D. L M MOTORIZED DAMPER ELBOW WITH TURNING VANES LOUVER DOOR M.D. ACCESS DOOR IN DUCT DUCT FLEXIBLE CONNECTION VOLUME DAMPER MECHANICAL SYMBOL LIST ABBREVIATIONS CONT. C.C. ATC A.L. A.F.F A.V. A.D. AC AUTOMATIC TEMPERATURE CONTROLS ABOVE FINISHED FLOOR AUTOMATIC AIR VENT ACOUSTICAL LINING CONTINUOUS COOLING COIL AIR CONDITIONING UNIT ACCESS DOOR 18 x 12 18x12 (2000) D R DUCTWORK B BOILER EF EXHAUST FAN TEF TOILET EXHAUST FAN PROVIDE CONDENSATE DRAIN LINE FROM EACH FCU UNIT. CONDENSATE DRAIN LINES SHALL DRAIN TO FLOOR DRAIN AS INDICATED. 9.DUCTWORK SIZING: DUCTWORK SHALL BE DESIGNED / SIZED AT 0.07 INCHES W.G. PRESSURE DROP PER 100 FEET OF DUCT, AND VELOCITY SHALL NOT EXCEED 800 FPM. 10.PIPE SIZES AND REQUIRED REFRIGERANT CHARGES SHALL BE VERIFIED WITH MANUFACTURER BASED ON FINAL ROUTING AND LENGTH OF PIPING.DESIGN CRITERIA: 1. OUTSIDE DESIGN CONDITIONS: LOCATION: LATITUDE: WINTER: SUMMER::%7ƒ) 2. INSIDE DESIGN CONDITIONS: DRY BULB TEMPERATURE (SUMMER):“ƒ) RELATIVE HUMIDITY (SUMMER): DRY BULB TEMPERATURE (WINTER): ƒ '%7ƒ) '%7ƒ) ƒ) 50% ƒ) RELATIVE HUMIDITY (WINTER):UNCONTROLLED “ƒ) AHU AIR HANDLING UNIT FCU FAN COIL UNIT ACCU AIR COOL CONDENSING UNIT EWH ELECTRIC WALL HEATER D DRAIN KEF KITCHEN EXHAUST FAN HC HEATING COIL BS BRANCH SELECTOR DX DIRECT EXPANSION RH REHEAT COIL OA OUTSIDE AIR ET EXPANSION TANK CFG CEILING (FILTER) GRILLE RS / RL / HG REFRIGERANT SUCTION, REFRIGERANT LIQUID, HOT GAS BG BREAK GLASS NG NATURAL GAS CO CARBON MONOXIDE PNL PANEL (SNOW MELT) VFD VARIABLE FREQUENCY DRIVE SR SUPPLY / SIDEWALL REGISTER GFP GLYCOL FEED AUTO FEED PUMP UNIT T NG CO TEMPERATURE SENSOR (THERMOSTAT) NATURAL GAS DETECTOR CARBON MONOXIDE DETECTOR SD TS TEMPERATURE SENSOR (THERMOSTAT) PV POWER VENTILATOR FIRE DAMPER WITH ACCESS DOOR FIRE SMOKE DAMPER BCU BLOWER COIL UNIT AFR ABOVE FINISHED ROOF ITHACA, NEW YORK WMS WIRE MESH SCREEN CIRCUIT SETTER WHERE ACOUSTICAL LINING IS SPECIFIED ON THE DRAWINGS OR IN THE SPECIFICATIONS, THE DUCT SIZES SHALL BE INCREASED TO ACCOMMODATE THE THICKNESS OF ACOUSTICAL LINING. BOILER BREAK GLASSBG VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:06pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: GENERAL NOTES & SYMBOL LIST M0.01 GES REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL KEYED NOTES 4" CONCRETE PAD. (TYP.) PROVIDE RETURN GRILLE IN CEILING WITH FILTERS. TYPICAL FOR ALL. PROVIDE FCU WITH OPEN RETURN AND WMS. PROVIDE 8x4 LOUVER, COORDINATE LOUVER LOCATION WITH THE ARCHITECT.MIN0.1 SQ.FT FREE AREA. PROVIDE 26 GAUGE SUB-DUCT. SUB-DUCT EXTENDS ´83,16,'((;+$8675,6(57<3,&$/)25 TOILET RISERS. ELEVATOR HOIST-WAY COOLING INLET. 3 HOUR COMBINATION FIRE AND SMOKE DAMPER, 10x10, 120V ACTUATOR, AND INLET GRILLE. COORDINATE EXACT LOCATION WITH ELEVATOR EQUIPMENT INSTALLER. PROVIDE ACCESS DOOR. DENOTES RISER IDENTIFICATION NUMBER. SEE DRAWING M4.01 1 2 3 4 5 6 ‘ TEF-1 1'-3"W X 4'-2"H LOUVER NEEDED MIN 3.5 SQ.FT FREE AREA INTAKE AIR PLENUMCONG CO NATURAL GAS SENSOR NATURAL GAS SENSOR CD 18X18 (75) AS-1 16X10 UP 14X10 UP 6x6 10X10 UP UH-B CO MONITORING PANEL AHU-1 BOILER BREAK GLASS T T T T FCU-B FCU-B CFG 18X18 1 FSD 6 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 EF-3 TEF-1 CD 9x9 (50) 8X6 8X6 20X8 SR 10x6 (200) SR 10x6 (200) U OA PLENUM 40"L X 34"W X 24"H EWH-A 5" FLUE UP TO ROOF (B-1, B-2) 4" WATER HEATER FLUE UP TO ROOF (TYP 2)14X620X6 W.M.S (450) ET-1 B-2 B-1 VFD VFD 1 T MER EXH. UH-A GFP-1 14X10 16X10 P-HW-1 P-HW-2 VFD PANELS TO BE MOUNTED ON THIS WALL ET. TO BE LOCATED BELOW THE DUCTS 4 ‘ 5 1 6X6 6X6 ‘ ‘ ‘ ‘ 3 2 U SUPLEX SEWAGE EJECTOR GWHGWH ‘ BG M ‘ TEF-1 FCU-B CFG 18X18 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 4 6X6 ‘ ‘ 3 2 ‘ TEF-1 FCU-B CFG 18X18 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 4 6X6 ‘ ‘ 3 2 M MCPCP CONSTANT AIR VOLUME CONTROL PANEL VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:06pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: LOWER LEVEL PLAN M2.00 GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 LOWER LEVEL FLOOR PLAN REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL BS-1BS-1BS-1D D D D FCU-B HGRSRLHWRHWS HWS & R 1-1/2" UPBS-1RS/RL/HG ACCU 1-UP RS/RL ACCU 3-UP FCU-B FCU-B 1-1/4" 3/4" COND. 1-1/4" UP 3/4" 3/4"DD D HWS & R 2" UP 3/4" 1" 3/4" 1"CONG CO NATURAL GAS SENSOR NATURAL GAS SENSOR P-HW-1 P-HW-2 AS-1 GFP-1 UH-B CO MONITORING PANEL AHU-1 BOILER BREAK GLASS UH-A FCU-B OA PLENUM 40"L X 34"W X 24"H EWH-A ET-1 B-2 B-1 1-1/2" 1-1/2" 1" TO AHU1 3/4" 3/4" 1" T MER EXH. DIFFERENTIAL PRESSURE BYPASS CIRCUIT SETTER 1-1/2" HC-B HC-B HC-B HC-B3/4"HWRHWS3/4" 3/4" 3/4" HG RSRL RS RL VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:06pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: LOWER LEVEL PLAN - PIPING GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 LOWER LEVEL FLOOR PLAN - PIPING REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF CD 9x9 (50) SR 8x6 (130) SR 8x6 (160) CD 9x9 (25) ‘ ‘ ‘ RG 10X10 UP 16X10 DN 10X10 UP 14X10 DN ‘ 6x6 6x6 10x6 RETURN OPENING WITH WMS ABOVE CEILING 8x6 CD 18X18 (105) 8X6 1 4 3 CUH-A 1 2 3 5 4 2 10X10 UP&DN 8X6 8X6 8X6 8X6 20X8 CD 18X18 (105) T T T T T FCU-B FCU-B FCU-B FCU-B FCU-A CFG 18X18 CFG 18X18 CFG 18X18 SR 10X6 (180) SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 SR 10x6 (200) SR 10x6 (200) TEF-1 TEF-1 TEF-1 TEF-1 TEF-1 CUH-A EWH-A EWH-A 16x6 UP5 4 3 4 3 6X6 ‘ ‘ 6X6 ‘ ‘ 6X6 ‘ ‘ T AHU-1 (T) 6X6 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:06pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: GROUND FLOOR PLAN M2.01 GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 GROUND FLOOR PLAN REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF BS-1 BS-1BS-1FCU-BBS-1D D D D HGRSRLHGRS RL HWRHWS CUH-A RS/RL/HG ACCU 1-UP&DN RS/RL ACCU 3-UP&DN D BS-1HWS & R 2" UP 2" DN HWS&R 1 1 2" DN FCU-B FCU-B FCU-B CUH-A 1" 3/4" 1-1/4" 3/4" 3/4" 3/4" 1" CND. UP & DN 3/4" 3/4" 3/4" 3/4"DD D DD1" HC-B HC-B HC-B HC-A HWRHWS3/4" 3/4" 3/4" FCU-A HC-B VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:06pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: GROUND FLOOR PLAN - PIPING GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 GROUND FLOOR PLAN - PIPING REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF KEYED NOTES 5" FLUE UP TO ROOF AND DOWN TO BOILER. 4" FLUE UP TO ROOF AND DOWN TO WATER HEATER PROVIDE ALL RETURN IN CEILING WITH FILTERS. TYPICAL FOR ALL. PROVIDE FCU WITH OPEN RETURN AND WMS. DENOTES RISER IDENTIFICATION NUMBER. SEE DRAWING M4.01 1 2 3 4 T 4 3 ‘ ‘ ‘ T T T RG6x6 6x6 8x6 SR 10x6 (160) SR 12x6 (250) 10X8 UP 10X10 DN 10X8 UP 10X10 DN 1 8x6 W/WMS 16x6 UP 16x6 UP&DN 16x6 UP 16x6 UP 1 2 3 5 4 2 16x6 UP 10X10 UP&DN 30X8 10X6 8X6 8X6 T FCU-D FCU-B FCU-B FCU-B FCU-B CFG 18X18 CFG 18X18 CFG 18X18 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 8X6 CD 9x9 (50) CD 6X6 (25)20X88X6 8X6SR 10x6 (175) SR 10x6 (200) TEF-1 TEF-1 TEF-1 TEF-1 TEF-1 CD 18X18 (105) CD 18X18 (105) SR 8x6 (150) 6X6 ‘ ‘ 8X6 6X6 ‘ 8X6 6X6 ‘ 4 3 CFG 18X18 4 3 RA SR 6x6 (75) VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:06pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: SECOND FLOOR PLAN M2.02 GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 SECOND FLOOR PLAN REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF BS-1 BS-1FCU-D BS-1D D D FCU-BHGRSRLHG RSRL HWR HWS RS/RL/HG ACCU 1-UP&DN RS/RL ACCU 3-UP&DN BS-1D BS-1HWS & R 2" UP 2" DN 1-1/4" FCU-B FCU-B FCU-B 3/4" 1" 3/4" 1" CND. UP & DN 3/4" 3/4" 3/4" 3/4"DDD D 3/4" HC-B HC-B HC-B HC-B HC-D HWRHWSVERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:06pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: SECOND FLOOR PLAN - PIPING GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 SECOND FLOOR PLAN - PIPING REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF KEYED NOTES 5" FLUE UP TO ROOF AND DOWN TO BOILER. 4" FLUE UP TO ROOF AND DOWN TO WATER HEATER PROVIDE ALL RETURN IN CEILING WITH FILTERS. TYPICAL FOR ALL. PROVIDE FCU WITH OPEN RETURN AND WMS. DENOTES RISER IDENTIFICATION NUMBER. SEE DRAWING M4.01 1 2 3 4 T 4 3 ‘ ‘ ‘ T T T RG 6x6 6x6 8x6 8X6 UP 10X8 DN 8X6 UP 10X8 DN 1 8x68x6 W/WMS 16x6 UP&DN 16x6 UP&DN 16x6 UP&DN 16x6 UP&DN 1 2 3 5 16x6 UP&DN 4 2 10X10 UP&DN CD 9x9 (50) 8X6 T FCU-C FCU-B FCU-B FCU-B CFG 18X18 CFG 18X18 CFG 18X18 CFG 18X18 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 SR 8x6 (160) SR 10x6 (200) 30X8 8X6 CD 9x9 (50) CD 6X6 (25)8X6 8X6SR 10x6 (175) SR 10x6 (200) 20X8 TEF-1 TEF-1 TEF-1 TEF-1 CD 18X18 (105) CD 18X18 (105)SR 10x6 (175) SR 10x6 (200) SR 8x6 (150) 8X6 8X6 6X6 ‘ CD 6X6 (25) 8X6 6X6 ‘ 8X6 6X6 ‘ 20X8 4 3 4 3 RA TEF-1 CD 12X12 (50) ‘ ‘ FCU-B 4 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: THIRD FLOOR PLAN M2.03 GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 THIRD FLOOR PLAN REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF FCU-BBS-1D D HGRSRLHG RSRL HWR HWS BS-1 FCU-C RS/RL/HG ACCU 1-UP&DN RS/RL/HG ACCU 2-UP RS/RL ACCU 3-UP&DN BS-1BS-1D D D HWS & R 1-1/4" UP 2" DN FCU-B FCU-B FCU-B 1-1/4" 1" CND. UP & DN 3/4" 3/4" 3/4" 3/4" 1"BS-1HC-B HC-B HC-B HC-B HC-C HWRHWS3/4" 3/4" 3/4" 3/4" 3/4" VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: THIRD FLOOR PLAN - PIPING GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 THIRD FLOOR PLAN - PIPING REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF SR 10x6 (200) SR 12x6 (285) CD 9x9 (50) CD 9x9 (50) 16x6 DN ‘ 16x6 DN 16x6 DN 16x6 DN T T T T DUCT UP TO TEF-A DUCT UP TO TEF C DUCT UP TO TEF B DUCT UP TO TEF E DUCT UP TO TEF D 6x6 6x6 8x6 RG T SR 8x6 (160) SR 10x6 (200) CD 18X18 (200) 8X6 DN 8X6 DN 8x6 W/WMS 1 2 3 5 1 4 2 16x6 DN CD 6X6 (25) CD 6X6 (25) 10X10 UP&DN DUCT UP TO EF-2 30X8 30X8 8X68X6 20X88X6 8X6 KEYED NOTES 5" FLUE UP TO ROOF AND DOWN TO BOILER. 4" FLUE UP TO ROOF AND DOWN TO WATER HEATER PROVIDE ALL RETURN IN CEILING WITH FILTERS. TYPICAL FOR ALL. PROVIDE FCU WITH OPEN RETURN AND WMS. DENOTES RISER IDENTIFICATION NUMBER. SEE DRAWING M4.01 1 2 3 4 T FCU-C FCU-B FCU-B FCU-B FCU-C CFG 18X18 CFG 18X18 CFG 18X18 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 SR 10x6 (175) CD 9x9 (50) SR 10x6 (200) CD 6X6 (25) 20X8 SR 10x6 (175) SR 10x6 (200) TEF-1 TEF-1 TEF-1 TEF-1 CD 18X18 (105) CD 18X18 (105) 4 3 SR 8x6 (150) 8X6 8X6 6X6 8X8 6X6 8X6 6X6 ‘ CFG 18X18 4 3 CFG 18X18 4 3 TEF-1 ‘ ‘ RA ‘ ‘ ‘ CD 12X12 (50) ‘ M2M-204M T.O. GYPSUM-CEMENT UNDERLAYMENT - FOURTH FLOOR ELEV. + 773'-9" T.O. METAL ROOF DECK ELEV. + 783'-334" R-4.5 R-4.2 3"RD 3"OD 20X8 FC-B 8X6 7'-6" 8'-85 8" HC-B CFG EF-A 16X6 10X10 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: FOURTH FLOOR PLAN M2.04 GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 FOURTH FLOOR PLAN SCALE: 1/4"=1'-0" 0 4 8 FEET 2 SECTION A-A A REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF BS-1 BS-1BS-1BS-1FCU-C BS-1D D D HGRSRLHG RSRL 3-WAY AUTOMATIC CONTROL VALVE (SEE DETAIL) HWR HWS RS/RL/HG ACCU 1-DN RS/RL/HG ACCU 2-DN RS/RL ACCU 3-DN RS/RL/HG ACCU 1 RS/RL ACCU 3 RS/RL/HG UP TO ACCU 2 D D D D D D HWS & R 1-1/4" DN FCU-B FCU-B FCU-C 1-1/4" 1" CND. DN 3/4" 3/4" 1" A 3/4" 3/4" D HC-B HC-B HC-C HC-B HC-C HWRHWS3/4" 3/4" 3/4" 3/4" 2 M-204P FCU-B T.O. GYPSUM-CEMENT UNDERLAYMENT - FOURTH FLOOR ELEV. + 773'-9" T.O. METAL ROOF DECK ELEV. + 783'-334" HOISTWAY TOP OF CMU 1" HWS 1" HWR RS/RL/HG REF. PIPES SPRINKLER PIPE 6X6 SUPPLY DUCT 3/4" CONDENSATE RS/RL REF. PIPES RS/RL/HG REF. PIPES VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: FOURTH FLOOR PLAN - PIPING GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 FOURTH FLOOR PLAN - PIPING SCALE: 1/4"=1'-0" 0 4 8 FEET 2 SECTION A-A NOT TO SCALE EXHAUST RISER DIAGRAM REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9ACCU-1 TEF-E EF-1 TEF-D TEF-B TEF-C ACCU-2 ACCU-3 ROOF CURB ROOF CURB EF-2 KEYED NOTES 5" FLUE FROM BOILER. PROVIDE ROOF SUPPORT, FLUE PIPE EXTENDS TO 3 FEET ABOVE THE HIGHEST STRUCTURE WITHIN 10 FEET HORIZONTALLY. PROVIDE GUY WIRE SUPPORTS FOR VERTICAL FLUE SECTIONS 4" FLUE FROM WATER HEATER. PROVIDE ROOF SUPPORT, FLUE PIPE EXTENDS TO 3 FEET ABOVE THE HIGHEST STRUCTURE WITHIN 10 FEET HORIZONTALLY. PROVIDE GUY WIRE SUPPORTS FOR VERTICAL FLUE SECTIONS REFRIGERANT PIPES DOWN TO AHU IN MER SIX REFRIGERANT PIPES DOWN TO FCU'S. SIZING OF REFRIGERANT PIPES PER THE MANUFACTURER RECOMMENDATIONS. ALL EXHAUST FANS TO BE A MINIMUM OF 10 FEET OF THE ROOF EDGE. PROVIDE FLUE SUPPORTS ON ROOF FOR HORIZONTAL FLUE SECTIONS. MOUNT MINIMUM 3'-0" AFR. EXHAUST FAN WITH AUTOMATIC DAMPER, ACTUATOR AND THERMOSTAT. CONTROL WIRING AND POWER FOR EXHAUST FAN, MOTORIZED DAMPER AND THERMOSTAT BY ELECTRICAL CONTRACTOR, THERMOSTAT SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. MOUNT THERMOSTAT ON HOIST WAY WALL 4' BELOW MAIN ROOF DECK. FAN AND DAMPERS SHALL BE $&7,9$7(',)7+(7(03(5$785(5,6($%29(ƒ) 1 2 3 4 5 6 7 1 2 3 4 5 6 7 GENERATOR HG RS RL RS RL TEF-A VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: ROOF PLAN M2.05 GES SCALE: 1/4"=1'-0" 0 4 8 FEET 1 ROOF PLAN ROOF 4TH FLOOR 3RD FLOOR 2ND FLOOR TOILET EF-A 50 CFM 50 CFM 200 CFM LOWER LEVEL FLOOR FD GRD FLOOR 50 CFM 16x6 16x6 16x6 16x6 NOT TO SCALE1RISER 1 PROVIDE 26 GAUGE SUB-DUCT. SUB-DUCT EXTENDS 22" UP INSIDE EXHAUST RISER. (TYP.FOR ALL) KEYED NOTES REFER TO DETAIL1 BELOW FOR CONSTANT PRESSURE AIR FLOW DIAGRAM FOR ALL TEF EXHAUST FANS. TOILET EXHAUST DUCT FROM CEILING MOUNTED TEF-1 IN INDIVIDUAL BATHROOMS. REFER TO PLANS FOR AIR QUANTITIES. 1 2 2 TYP. 1 LOWER LEVEL FLOOR NOT TO SCALE2RISER 2 LOWER LEVEL FLOOR NOT TO SCALE3RISER 3 LOWER LEVEL FLOOR NOT TO SCALE4RISER 4 LOWER LEVEL FLOOR NOT TO SCALE5RISER 5 FD ROOF 4TH FLOOR 3RD FLOOR 2ND FLOOR 50 CFM 50 CFM 200 CFM FD GRD FLOOR 50 CFM 16x6 16x6 16x6 16x6 PROVIDE 26 GAUGE SUB-DUCT. SUB-DUCT EXTENDS 22" UP INSIDE EXHAUST RISER. (TYP.FOR ALL) 2 TYP. 1 FD ROOF 4TH FLOOR 3RD FLOOR 2ND FLOOR 50 CFM 50 CFM 200 CFM FD GRD FLOOR 50 CFM 16x6 16x6 16x6 16x6 PROVIDE 26 GAUGE SUB-DUCT. SUB-DUCT EXTENDS 22" UP INSIDE EXHAUST RISER. (TYP.FOR ALL) 2 TYP. 1 FD ROOF 4TH FLOOR 3RD FLOOR 2ND FLOOR 50 CFM 50 CFM 200 CFM FD GRD FLOOR 50 CFM 16x6 16x6 16x6 16x6 PROVIDE 26 GAUGE SUB-DUCT. SUB-DUCT EXTENDS 22" UP INSIDE EXHAUST RISER. (TYP.FOR ALL) 2 TYP. 1 FD ROOF 4TH FLOOR 3RD FLOOR 2ND FLOOR 50 CFM 50 CFM 200 CFM FD GRD FLOOR 50 CFM 16x6 16x6 16x6 16x6 PROVIDE 26 GAUGE SUB-DUCT. SUB-DUCT EXTENDS 22" UP INSIDE EXHAUST RISER. (TYP.FOR ALL) 2 TYP. 1 FD50 CFM50 CFM50 CFM EXTERIOR WALL 50 CFM 50 CFM 50 CFM 50 CFM 50 CFM TOILET EF-B TOILET EF-C TOILET EF-D TOILET EF-E EXTERIOR WALL EXTERIOR WALL 50 CFM 75 CFM VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: RISER DIAGRAMS SHEET 1 OF 4 M4.01 GPS T S ECM MOTOR DISCONNECT SWITCH TRANSFORMER TRANSDUCER IN ACCESSIBLE CEILING PRESSURE SENSOR PROBE IN DUCTWORK TEF ROOF 3W 4TH FLOOR CEILING DUCTWORK POWER BY ELEC. CONTRACTOR MER LOW VOLTAGE WIRE IN CONDUIT BY MECHANICAL CONTRACTOR 3W IN CONDUIT TO MOTORIZED DAMPER NEMA 4X CONTROL PANEL WITH CONSTANT PRESSURE AIR FLOW CONTROLLER. (MULTIPLE CONTROLLERS CAN BE MOUNTED IN CONTROL PANEL) NOT TO SCALE CONSTANT PRESSURE AIR FLOW DIAGRAM (TEF) NOT TO SCALE EXHAUST RISER DIAGRAM GROUND FLOOR 2ND FLOOR 3RD FLOOR 4TH FLOOR ROOF LOWER LEVEL TO / FROM HW CIRCULATION PUMPS 3/4" 2" 4" CONCRETE PAD (TYP.) 2-1/2" AUTOMATIC CONTROL VALVE SAFETY RELIEF VALVE ACID NEUTRALIZING PRESSURE DIFFERENTIAL BYPASS TO AHU / HC / UH / CUH FROM AHU / HC / UH / CUH P-HW-1 (DUTY) P-HW-2 (STANDBY) MAKE-UP WATER NOT TO SCALE BOILER PIPING DETAILS BALANCING VALVE (TYP)HWSHWRHWSHWRNOTE: REFER TO PLANS/FLOW DIAGRAM FOR PIPE SIZES SHUT-OFF RELIEF VALVE RELIEF VALVE PRESSURE GAUGE THERMOMETER VALVES STRAINERS PRESSURE GAUGE SHUT-OFF PRESSURE THERMOMETER VALVES STRAINERS PRESSURE GAUGE ACID NEUTRALIZER BOILER BOILER HOT WATER PIPING RISER NOTES: 1.REFER TO PLANS, DETAILS, CONTROL DIAGRAMS AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR VALVES, GAUGES, INSTRUMENTATION AND ACCESSORIES. 2.PROVIDE DRAIN VALVE AT BOTTOM OF RISERS AND AT ALL LOW POINTS OF PIPING (TYP) 3.PROVIDE AIR VENTS AT TOP OF RISERS AND AT HIGH POINTS OF PIPING. DRIP LEGDRIP LEG DRAIN (TYP) GASGAS 3/4" 3/4"3/4"3/4"3/4"3/4" HC-BCUH-A 3 GPM 3/4"3/4" 1" AHU-1 4 GPM 1" 1,1/2" 1" 2-1/2" 2" 1 1/2" UH-A 3.5 GPM UH-B 0.8 GPM HC-B1.7 GPM HC-B 1.7 GPM 3/4"1" 1.7 GPM HC-B 1.7 GPM HC-A 1.2 GPM HC-B 1.7 GPM 3/4" CUH-A 3 GPM 1-1/4" HC-D 2.7 GPM HC-B 1.7 GPM 3/4" HC-B 1.7 GPM 3/4" HC-B 1.7 GPM 2" 3/4"3/4" HC-C2.2 GPM HC-B 1.7 GPM 3/4" HC-B 1.7 GPM 3/4" HC-B 1.7 GPM 3/4"3/4" HC-C2.2 GPM HC-B 1.7 GPM 3/4" HC-B 1.7 GPM 3/4" HC-C2.2 GPM 2" 3/4" HC-B 1.7 GPM 3/4" HC-B 1.7 GPM 3/4" HC-B 1.7 GPM 1"1-1/4" 1"1-1/4" 3/4" HC-B1.7 GPM 3/4" HC-B1.7 GPM 1"1-1/4" 1"1-1/4" 1-1/2" 3/4" HC-B 1.7 GPM 2" 2-1/2" 2-1/2"2-1/2" 2-1/2" NOT TO SCALE BOILER FLOW DIAGRAM NOT TO SCALE HOT WATER SUPPLY AND RETURN PIPING RISER DIAGRAM VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: RISER DIAGRAMS SHEET 2 OF 4 M4.02 GPS 5/8x1 1/8x7/8" 39.5 ft [3] 3/8x3/4x5/8" 14.0 ft [1] 3/8x5/8x1/2" 1.5 ft [1] 1/4x1/2" 9.0 ft [3] 3/8x3/4x5/8" 2.5 ft 3/8x5/8x1/2" 6.0 ft [1] 1/4x1/2" 7.5 ft [1] 3/8x5/8x1/2" 7.5 ft [1] 3/8x5/8x1/2" 2.5 ft [2] 1/4x1/2" 7.5 ft [3] 3/8x5/8x1/2" 5.0 ft 3/8x5/8x1/2" 11.0 ft [1] 1/4x1/2" 14.5 ft [3] 3/8x5/8x1/2" 8.0 ft [2] 1/4x1/2" 9.0 ft [1] 3/8x7/8x3/4" 10.0 ft 3/8x3/4x5/8" 13.5 ft [2] 3/8x5/8x1/2" 2.5 ft [1] 1/4x1/2" 19.0 ft [3] 3/8x5/8x1/2" 2.5 ft 3/8x5/8x1/2" 6.0 ft [1] 1/4x1/2" 6.5 ft [1] 3/8x5/8x1/2" 7.0 ft [1] 3/8x5/8x1/2" 2.5 ft [2] 1/4x1/2" 8.0 ft [3] 3/8x5/8x1/2" 5.0 ft 3/8x5/8x1/2" 4.0 ft [2] 1/4x1/2" 8.0 ft [2] 3/8x5/8x1/2" 8.5 ft [2] 1/4x1/2" 8.0 ft [1] 3/8x5/8x1/2" 23.5 ft [2] 3/8x5/8x1/2" 1.0 ft [1] 1/4x1/2" 15.0 ft [2] 3/8x5/8x1/2" 2.5 ft 3/8x5/8x1/2" 6.0 ft 1/4x1/2" 7.0 ft [1] 3/8x5/8x1/2" 6.5 ft 3/8x5/8x1/2" 2.5 ft [2] 1/4x1/2" 7.5 ft [3] 3/8x5/8x1/2" 13.0 ft [2] 1/4x1/2" 9.0 ft [1] ACCU-1 REYQ168TATJU KHRP25M72TU9 KHRP25A22T9 BS 12 BSQ36TVJ A FCU-2-5 FXMQ12PBVJU KHRP25A22T9 BS 15 BSQ36TVJ A FCU-2-3 FXMQ12PBVJU KHRP25A22T9 BS 13 BSQ36TVJ A FCU-2-2 FXMQ12PBVJU KHRP25A22T9 BS 11 BSQ36TVJ A FCU-2-4 FXMQ18PBVJU BS 14 BSQ36TVJ A FCU-2-1 FXMQ12PBVJU KHRP25A33T9 KHRP25A22T9 BS 17 BSQ36TVJ A FCU-1-5 FXMQ12PBVJU KHRP25A22T9 BS 20 BSQ36TVJ A FCU-1-3 FXMQ12PBVJU KHRP25A22T9 BS 18 BSQ36TVJ A FCU-1-2 FXMQ12PBVJU KHRP25A22T9 BS 21 BSQ36TVJ A FCU-1-4 FXMQ09PBVJU BS 19 BSQ36TVJ A FCU-1-1 FXMQ12PBVJU KHRP25A22T9 BS 22 BSQ36TVJ A FCU-0-4 FXMQ12PBVJU KHRP25A22T9 BS 25 BSQ36TVJ A FCU-0-3 FXMQ12PBVJU KHRP25A22T9 BS 23 BSQ36TVJ A FCU-0-2 FXMQ12PBVJU BS 24 BSQ36TVJ A FCU-0-1 FXMQ12PBVJU ACCU-1 REYQ168TATJU REYQ168TATJU BS 12 BSQ36TVJ A FCU-2-5 FXMQ12PBVJU BRC1E73 (1) BS 15 BSQ36TVJ A FCU-2-3 FXMQ12PBVJU BRC1E73 (1) BS 13 BSQ36TVJ A FCU-2-2 FXMQ12PBVJU BRC1E73 (1) BS 11 BSQ36TVJ A FCU-2-4 FXMQ18PBVJU BRC1E73 (1) BS 14 BSQ36TVJ A FCU-2-1 FXMQ12PBVJU BRC1E73 (1) BS 17 BSQ36TVJ A FCU-1-5 FXMQ12PBVJU BRC1E73 (1) BS 20 BSQ36TVJ A FCU-1-3 FXMQ12PBVJU BRC1E73 (1) BS 18 BSQ36TVJ A FCU-1-2 FXMQ12PBVJU BRC1E73 (1) BS 21 BSQ36TVJ A FCU-1-4 FXMQ09PBVJU BRC1E73 (1) BS 19 BSQ36TVJ A FCU-1-1 FXMQ12PBVJU BRC1E73 (1) BS 22 BSQ36TVJ A FCU-0-4 FXMQ12PBVJU BRC1E73 (1) BS 25 BSQ36TVJ A FCU-0-3 FXMQ12PBVJU BRC1E73 (1) BS 23 BSQ36TVJ A FCU-0-2 FXMQ12PBVJU BRC1E73 (1) BS 24 BSQ36TVJ A FCU-0-1 FXMQ12PBVJU BRC1E73 (1) L1, L2, L3 61.9A 3ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.6A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 0.6A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph IN F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 NOT TO SCALE REFRIGERANT RISER DIAGRAM (ACCU-1) NOT TO SCALE SCHEMATIC WIRING DIAGRAM (ACCU-1) VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: RISER DIAGRAMS SHEET 3 OF 4 M4.03 GS 1/2x1 1/8x7/8" 10.0 ft [3] 3/8x5/8x1/2" 1.5 ft [1] 3/8x5/8x1/2" 2.0 ft [1] 1/4x1/2" 7.0 ft [3] 3/8x5/8x1/2" 5.0 ft 3/8x5/8x1/2" 11.0 ft 1/4x1/2" 14.5 ft [3] 3/8x5/8x1/2" 8.0 ft [2] 1/4x1/2" 8.0 ft [1] 3/8x7/8x3/4" 6.5 ft 3/8x5/8x1/2" 5.5 ft 1/4x1/2" 7.5 ft [1] 3/8x7/8x3/4" 2.5 ft [1] 3/8x5/8x1/2" 1.0 ft [1] 1/4x1/2" 8.5 ft [3] 3/8x3/4x5/8" 38.0 ft [4] 3/8x5/8x1/2" 1.0 ft [1] 1/4x1/2" 8.5 ft [3] 3/8x5/8x1/2" 2.5 ft 3/8x5/8x1/2" 6.0 ft [1] 1/4x1/2" 7.0 ft [1] 3/8x5/8x1/2" 7.5 ft [1] 3/8x5/8x1/2" 2.0 ft [2] 1/4x1/2" 7.0 ft [3] 3/8x5/8x1/2" 5.0 ft 3/8x5/8x1/2" 11.0 ft [1] 1/4x1/2" 14.5 ft [3] 3/8x5/8x1/2" 8.0 ft [2] 1/4x1/2" 8.0 ft [1] ACCU-2 REYQ144TATJU KHRP25M72TU9 KHRP25A22T9 BS 3 BSQ36TVJ A FCU-4-2 FXMQ12PBVJU KHRP25A22T9 BS 4 BSQ36TVJ A FCU-4-4 FXMQ15PBVJU BS 5 BSQ36TVJ A FCU-4-1 FXMQ12PBVJU KHRP25A33T9 BS 2 BSQ36TVJ A FCU-4-3 FXMQ15PBVJU KHRP25A33T9 BS 1 BSQ36TVJ A FCU-4-5 FXMQ12PBVJU KHRP25A22T9 BS 6 BSQ36TVJ A FCU-3-5 FXMQ12PBVJU KHRP25A22T9 BS 10 BSQ36TVJ A FCU-3-3 FXMQ12PBVJU KHRP25A22T9 BS 8 BSQ36TVJ A FCU-3-2 FXMQ12PBVJU KHRP25A22T9 BS 7 BSQ36TVJ A FCU-3-4 FXMQ15PBVJU BS 9 BSQ36TVJ A FCU-3-1 FXMQ12PBVJU ACCU-2 REYQ144TATJU REYQ144TATJU BS 3 BSQ36TVJ A FCU-4-2 FXMQ12PBVJU BRC1E73 (1) BS 4 BSQ36TVJ A FCU-4-4 FXMQ15PBVJU BRC1E73 (1) BS 5 BSQ36TVJ A FCU-4-1 FXMQ12PBVJU BRC1E73 (1) BS 2 BSQ36TVJ A FCU-4-3 FXMQ15PBVJU BRC1E73 (1) BS 1 BSQ36TVJ A FCU-4-5 FXMQ12PBVJU BRC1E73 (1) BS 6 BSQ36TVJ A FCU-3-5 FXMQ12PBVJU BRC1E73 (1) BS 10 BSQ36TVJ A FCU-3-3 FXMQ12PBVJU BRC1E73 (1) BS 8 BSQ36TVJ A FCU-3-2 FXMQ12PBVJU BRC1E73 (1) BS 7 BSQ36TVJ A FCU-3-4 FXMQ15PBVJU BRC1E73 (1) BS 9 BSQ36TVJ A FCU-3-1 FXMQ12PBVJU BRC1E73 (1) L1, L2, L3 55A 3ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.5A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.5A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph L1, L2 0.1A 1ph L1, L2 1.5A 1ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph IN F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 OUT F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 IN F1,F2 F1,F2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 P1,P2 NOT TO SCALE REFRIGERANT RISER DIAGRAM (ACCU-2) NOT TO SCALE SCHEMATIC WIRING DIAGRAM (ACCU-2) VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: RISER DIAGRAMS SHEET 4 OF 4 M4.04 GPS NOTES: 1.MOUNT UNIT FLOOR/CEILING SLAB STRUCTURE WITH SPRING VIBRATION ISOLATORS. 2.ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH. 3.FILTERS SHALL BE LOCATED AT GRILLES. CONTRACTOR TO PROVIDE EXTERIOR INSULATION ON CABINET. 4.PROVIDE INTEGRAL LIFT PUMP FOR ALL INDOOR FAN COILS. PROVIDE WITH WATER BUG DETECTION. 5.PROVIDE KPR DATA BOARD AND 24 VOLT TRANSFORMER IN CONTROL BOX TO PREVENT SIMULTANEOUS COOLING AND HEATING. 6.FILTERS ARE PROVIDED IN THE RETURN GRILLES, PROVIDE UNITS WITH OPEN ENDED RETURN WITH WIRE MESH SCREEN. FCU FAN COIL UNIT SCHEDULE - (VARIABLE REFRIGERANT VOLUME UNITS)BASIS OF DESIGN: DAIKIN UNIT NO.AREA SERVED TOTAL CFM COOLING TOTAL (MBH) COOLING SENSIBLE (MBH) HEATING (MBH) ELECTRICAL DATA WEIGHT (LBS)REFRIGERANT MODEL NO.REMARKS(VOLT PH)MCA MFS FCU-A SEE PLANS 315 8.0 6.7 10.1 208 / 1 0.6 15 55 R410A FXMQ09PBVJU FCU-B SEE PLANS 450 10.2 8.4 13 208 / 1 1.4 15 62 R410A FXMQ12PBVJU FCU-C SEE PLANS 560 12.6 10.6 15.9 208 / 1 1.5 15 79 R410A FXMQ15PBVJU FCU-D SEE PLANS 635 15.2 13.7 19.2 208 / 1 1.6 15 79 R410A FXMQ18PBVJU NOTES: 1.PROVIDE INDIVIDUAL POWER CONNECTIONS. 2.MAINTAIN MANUFACTURER'S CLEARANCES ABOVE AND BELOW BOXES. 3.PROVIDE REQUIRED MOUNTS. BS BRANCH SELECTOR BOX BASIS OF DESIGN: DAIKIN TAG SERVES SELECTED MODEL ELECTRICAL DATA NET WEIGHT (LBS) DIMENSIONS L x H x WMCA AMP MOCP AMP (V/P/H) BS-1 FCU-A,B,C,D BSQ36TVJ 0.1 15 208 / 1 / 60 27 15.3" x 8.1" x 12.8" ACCU AIR COOLED CONDENSING UNIT (VRF)BASIS OF DESIGN: DAIKIN UNIT NO.SERVES LOCATION EER COP #ƒ) CAPACITY COND. DATA ELECTRICAL DATA WEIGHT (LBS)MODEL NO.COOLING TOTAL (MBH) HEATING (MBH) OUTDOOR DESIGN DB ƒ) REFRIG. TYPE MODULE # ELECT. DATA (VOLT/PH) TYPE OF COMP. MINIMUM CIRCUIT AMPACITY MAXIMUM FUSE SIZE ACCU-1 LL,1,2 FLOORS ROOF 11.6 3.7 156 176 89 R410A -208/3 SCROLL 61.9 70 780 REYQ168TATJU ACCU-2 3,4 FLOORS ROOF 12.4 3.8 134 150 89 R410A -208/3 SCROLL 55 70 780 REYQ144TATJU NOTES: 1.PROVIDE COMPRESSOR CYCLE PROTECTOR. 2.3529,'(/2:$0%,(17&21752/:,1'%$))/()25&21'(16,1*81,723(5$7,21'2:172ƒ) 3.PROVIDE REMOTE AND OUTDOOR AIR TEMPERATURE SENSORS. 4.MOUNT UNIT ON EQUIPMENT RAILS/BIG FOOT SUPPORTS ON ROOF. UNIT SHALL BE ELEVATED A MINIMUM 18" ABOVE FINISHED ROOF. TIE UNIT AND SUPPORT DOWN TO STRUCTURE. NOTES: 1.PROVIDE REFRIGERANT PIPING BETWEEN AC UNIT AND CONDENSING UNIT PER MANUFACTURER'S RECOMMENDATIONS. 2.PROVIDE INTERCONNECTING CONTROL WIRING BETWEEN ACCU AND AHU. 3.MOUNT UNIT ON 4" CONCRETE PAD. 4.UNITS ARE SELECTED BASED ON HWC, DX COOLING COIL, FILTER SECTION AND FAN SECTION. NOTES: 1.ACCU UNITS SHALL HAVE FIVE YEAR EXTENDED WARRANTY FOR COMPRESSORS. 2.PROVIDE COMPRESSOR CYCLE PROTECTOR. 3.3529,'(/2:$0%,(17&21752/)25&21'(16,1*81,723(5$7,21'2:172ƒ) 4.PROVIDE REMOTE AND OUTDOOR AIR TEMPERATURE SENSORS ACCU AIR COOLED CONDENSING UNIT (AHU)BASIS OF DESIGN: AAON UNIT NO.SERVICE LOCATION EER CAPCAITY COND DATA ELECTRICAL WEIGHT (LBS) MODEL NO.REMARKSOUTDOOR DESIGN DB ƒ) REFRIG. TYPE VOLT / PH MCA MOCPCOOLING MBH HEATING MBH ACCU-3 AHU-1 ROOF 12.1 33.1 34.6 95 R-410A 208 / 3 4 15 397 CFA-003-A-A-8 DC00H HC HEATING COIL WITH 40% PROPYLENE GLYCOL SCHEDULE BASIS OF DESIGN: USA COIL & AIR COIL NO. EQUIPMENT OR SYSTEM SERVED MODEL NUMBER AIR DATA WATER DATA COIL DATA REMARKSTOTAL CFM MAX. FACE VELOC. (FPM) '%7(03ƒ)MAX. P.D. (IN.W.G.)GPM 7(03ƒ)MAX. P.D. (IN.W.G.) HEAT CAP. (MBH)ROWS/FPI NOMINAL SIZE (IN.) F.W. X F.L. DRY WEIGHT (EACH) ENT.LVG.ENT.LVG. HC-A FCU-A F12-206-8.8x14-01A 315 370 62 101.1 0.05 1.24 180 157.6 1.91 14 2 / 6 14x8.75 8.5 HC-B FCU-B F12-206-8.8x20-01A 450 370 62 102.2 0.05 1.71 180 156.1 1.09 20 2 / 6 20x8.75 11 HC-C FCU-C F12-206-8.8x32-02A 560 288 62 105.1 0.04 2.20 180 155.2 1.42 27 2 / 6 32x8.75 16.1 HC-D FCU-D F12-206-8.8x32-02A 635 327 62 104 0.04 2.71 180 157.8 2.07 29 2 / 6 32x8.75 16.1 NOTES: 1.ELECTRIC WALL HEATER SHALL BE PROVIDED WITH FUSED DISCONNECT SWITCH. 2.ELECTRIC WALL HEATER SHALL BE PROVIDED WITH AIR FLOW SWITCH TO SHUT HEATER OFF IN THE EVENT OF FAN FAILURE. 3.PROVIDE WITH UNIT MOUNTED THERMOSTAT. EWH ELECTRIC WALL HEATER SCHEDULE BASIS OF DESIGN: BERKO SYMBOL MODEL LOCATION KW OUTPUT MBH CFM VOLT/PH MCA MOCP EAT LAT OPER WT.REMARKS EWH-A SRA1012DSAF SEE PLANS 1 3.4 65 120/1 10.5 15 60 108 30 2 STAGE HEATER NOTES: 1.CONTRACTOR TO PROVIDE DUCT TRANSITIONS AT INLET AND OUTLET TO COILS. AHU AIR HANDLING UNIT WITH 40% PROPYLENE GLYCOL SCHEDULE BASIS OF DESIGN: AAON UNIT NO.LOCATION AREA SERVED TOTAL CFM OUTSIDE AIR HP AIR DATA DX COOLING WATER DATA ELECTRICAL REF. WEIGHT (LBS) MODEL NO.REMARKSENT. DB ƒ) ENT. WB ƒ) LAT. DB ƒ) LAT. WB ƒ) ESP TOTAL (MBH) SENSIBLE (MBH) HEATING (MBH) 7(03 ƒ) GPM VOLT/PH FLA ENT LVG AHU-1 MER CORRIDOR-LOBBY 1100 130 1.1 77.3 63.3 53 51.9 1 33.1 26.4 34.6 180 161.3 4 208/3 3 R-410A 306 V3-ARB-8-0 141D-11Q VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:07pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: SCHEDULES SHEET 1 OF 2 M5.01 GES NOTES: 1.PROVIDE DISCONNECT SWITCH 2.PROVIDE SOLID STATE SPEED CONTROL FOR BALANCING. 3.PROVIDE WITH HANGERS AND SUPPORTS WITH VIBRATION ISOLATORS. 4.PROVIDE 12" HIGH ROOF CURB. 5.PROVIDE DUCT PRESSURE SENSOR, VARI-GREEN CONSTANT PRESSURE CONTROL WITH REMOTE TRANSDUCER. REMOTE TRANSDUCER SHALL BE LOCATED ABOVE ACCESSIBLE CEILING. CONSTANT PRESSURE AIR FLOW CONTROLLER SHALL BE LOCATED IN NEMA 4X PANEL ON THE ROOF.PROVIDE ALL LOW VOLTAGE WIRING AND REQUIRED TUBING FROM STATIC PRESSURE PROBE TO REMOTE TRANSDUCER. 6.PROVIDE BACK DRAFT DAMPER. 7.PROVIDE MOTORIZED DAMPER NOTES: 1.xxx ET EXPANSION TANK SCHEDULE BASIS OF DESIGN: AMTROL TANK NO.LOCATION SYSTEM SERVED TANK TYPE (OPEN OR CLOSED) TANK VOLUME (GAL.) SIZE AVG. OPER. TEMP. ƒ) INITIAL FILL PRESS. (PSIG) MAX. OPER. PRESS. (PSIG) A.S.M.E . WORK PRESS. (PSIG) MODEL REMARKS DIA. (IN.)LENGTH (IN.) ET-1 LOCATION HEATING SYSTEM CLOSED M 24 47 190 30 50 125 AX-120V NOTES: 1.PROVIDE GALVANIZED ANGLE MOUNTING FRAME SUPPORT. AS AIR SEPARATOR SCHEDULE BASIS OF DESIGN: SPIROTHERM PLAN NO LOCATION PIPE DIA INLET PIPE DIA OUTLET HEIGHT IN.DIA.GPM MAX OPER TEMP ƒ) MAX OPER. PRESSU RE PSI DRY WEIGHT LBS MODEL REMARKS AS-1 MER 3"3"23.7 9"140 180 150 95 SPIROVENT VSR300 NOTES: 1.LOCATE BOILERS ON CONCRETE PAD WITH NEOPRENE PADS SIMILAR TO MASON INDUSTRIES TYPE MSW WITH MINIMUM STATIC DEFLECTION OF 0.1 INCHES. 2.ELECTRICAL: PROVIDE ONE 115V/1 CIRCUIT FOR FAN AND ANOTHER 115V/1 FOR CONTROL. 3.PROVIDE INTEGRATED BOILER CONTROL (NURO). B BOILER SCHEDULE BASIS OF DESIGN: PATTERSON KELLEY BOILER NO.LOCATION SERVICE MAX. OPER. PRESS. (PSIG) DESIGN PRESS. RATING (PSIG) FLUE OUTLET SIZE (IN.) GROSS INPUT (MBH) GROSS OUTPUT (MBH) EFFICIENCY AT RATED LOAD (%) HOT WATER DATA W/40% PROP GLYCOL FUEL-GAS BURNER DATA BOILER TYPE OPER. WEIGHT (LB) MODEL REMARKS GPM MAX PRESS. DROP (FT.) 7(03ƒ) GAS TYPE GAS RATE (CFH) GAS INLET PRESSURE (IN. WG) MIN/MAXGASENT.LVG. B-1 MER REHEAT COILS 80 14.0 ‘300 279 93.5 %28 12 160 180 NATURAL 388 3.5 / 14 CONDENSING 290 MACH CM-300 B-1 MER REHEAT COILS 80 14.0 ‘300 279 93.5 %28 12 160 180 NATURAL 388 3.5 / 14 CONDENSING 290 MACH CM-300 GFP PACKAGE GLYCOL AUTO FILL SCHEDULE BASIS OF DESIGN: ARMSTRONG PUMP NO.LOCATION MODEL STORAGE CAPACITY HP MOTOR DATA DIMENSIONS WxDxH REMARKSFLAVOLT/PH GFP-1 MER GLA-S-HP-1 53 GAL 1/3 2.7 120 / 1 26"x24"x51"A ACTIVE / B STD. BY PUMP NOTES: 1.PROVIDE DRY CONTACTS FOR REMOTE INDICATION OF ALARM. 2.PROVIDE NEMA 4X CONTROL PANEL WITH TWO (2) HDA SWITCHES. NOTES: 1.PROVIDE VARIABLE FREQUENCY DRIVE FOR P-HW-1,2. P PUMP SCHEDULE BASIS OF DESIGN: GRUNDFOS PUMP NO.LOCATION EQUIPMENT OR SYSTEM SERVED PUMP TYPE GPM TOTAL HEAD (FT.) FLUID TEMP. ƒ) IMPELLER DIA. NPSHr (FT.) EFF. @ OPER. POINT (%) BHP MAX MOTOR DATA MODEL NO.REMARKS HP VOLT/ PH RPM P-HW-1 MER HEATING SYSTEM VERTICAL INLINE 32 53 180 6.99"6.05 54.52 0.78 1.5 208/3 1765 VL 12707 40% PROYLENE GLYCOL P-HW-1 MER HEATING SYSTEM VERTICAL INLINE 32 53 180 6.99"6.05 54.52 0.78 1.5 208/3 1765 VL 12707 40% PROYLENE GLYCOL AIR DEVICES BASIS OF DESIGN: TITUS DESIGNATION NECK SIZE NOMINAL FACE SIZE MODEL NO.REMARKS CD SEE PLANS 18" X 18"TDCA 2 SR SEE PLANS SEE PLANS 272FL 1,2 RG SEE PLANS 18" X 18"50F 2 CFG SEE PLANS SEE PLANS 50FF 2 NOTES: 1.PROVIDE WITH INTEGRAL VOLUME DAMPER. 2.COORDINATE COLOR AND BORDER TYPE WITH THE ARCHITECT. NOTES: 1.PROVIDE REMOTE MOUNTED THERMOSTAT. 2.PROVIDE MANUAL MOTOR STARTER WITH THERMAL OVER LOAD, DISCONNECT SWITCH AND AQUASTAT UH / CUH CABINET AND UNIT HEATER WITH 40% PROPYLENE GYLCOL SCHEDULE BASIS OF DESIGN: STERLING UNIT NO.LOCATION MBH AIR DATA WATER DATA MOTOR DATA MODEL NO.REMARKSCFM (HI) 7(03ƒ) GPM 7(03 ƒ) MAX P.D. (FT.) HP (WATTS) RPM (HI) NO. OF SPEEDS VOLT/ PH/HZENT.LVG.ENT LVG UH-A MER 34.8 750 60 103 3.5 180 160 0.12 1/20 HP 1000 2 120 / 1 / 60 HS-48 - UH-B HOUSE KEEPING 8 245 60 91 0.8 180 160 0.8 16W 1550 2 120 / 1 / 60 HS-108A - CUH-A STAIRS 30 420 55 120 3 180 160 0.1 1/10 HP 1050 3 120 / 1 / 60 RC-1200-04 HI CAP COIL TEF EF FAN SCHEDULE BASIS OF DESIGN: GREENHECK UNIT NO.LOCATION AREA OR SYSTEM SERVED FAN TYPE CFM ESP FAN RPM DRIVE MOTOR DATA WEIGHT (LBS) MODEL NO.REMARKSBHPHPV/C/PH MOTOR RPM TEF-A ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7 TEF-B ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7 TEF-C ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7 TEF-D ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7 TEF-E ROOF TOILET EXHAUST CENTRIFUGAL 325 0.50 1618 DD -0.1 115/60/1 1725 24 G-085-VG 1,2,4,5,7 TEF-1 CEILING SEE PLANS INLINE 50 0.25 652 DD -15W 115/60/1 -9 SP-B70 1,2,3,6 EF-1 ROOF ELEVATOR CENTRIFUGAL 300 0.50 1665 DD -0.1 115/60/1 1725 24 G-080-VG 1,2,4,7 EF-2 ROOF MER CENTRIFUGAL 450 0.50 1522 DD -0.07 115/60/1 1725 25 G-090-VG 1,2,4,7 EF-3 CEILING JANITOR INLINE 75 0.25 749 DD -80W 115/60/1 -10 SP-B110 1,2,3,6 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:08pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: SCHEDULES SHEET 2 OF 2 M5.02 GES MANUAL AIR VENT AUTOMATIC MODULATING VALVE STRAINER SUPPLY TO FLOOR DRAIN 1" DRAIN VALVE LUBRICATED PLUG VALVE RETURN WITH DIAL SETTING THERMOMETER (TYPICAL) PETE'S PLUG (TYPICAL) NOTE: FOR MULTIPLE COILS PROVIDE SEPARATE CONTROL VALVES AND ACCESSORIES 1. NOT TO SCALE HOT WATER COIL PIPING DETAIL (2-WAY VALVE) N.C. NOT TO SCALE BOILER FLUE DETAIL MINIMUM 3FT HIGH ABV ROOF WATER COIL RETURN SUPPLY BALL VALVE (TYP.) BALANCING VALVE (TYP.) BUTTERFLY VALVE (TYP.) AIR FLOW 3-WAY AUTOMATIC CONTROL VALVE (OPERATOR INSTALLED VERTICALLY) MANUAL AIR VENT (TYP.) UNION (TYP.) NOTES: 1.PROVIDE PIPE HANGERS SO THAT HOT WATER COIL DOES NOT BEAR WEIGHT OF PIPING. 2.PIPING SHALL BE INSTALLED IN SUCH A MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALVES OR EQUIPMENT. 3.LEAVE 18" MIN. CLEARANCE ABOVE TEST PLUGS TO ALLOW INSERTION OF PROBES. 4.UNIONS ARE TO BE DIELECTRIC WHEN TWO DISSIMILAR METALS ARE BEING JOINED. STRAINER 3 4" HOSE END DRAIN VALVE W/ CAP (TYP.) THERMOMETER (TYP.) HOT WATER COIL PIPING DETAIL (3-WAY VALVE) NOT TO SCALE AL29-4C STAINLESS STEEL WITH 2" ANNULAR SPACE AND MINERAL WOOL INSULATION GALVANIZED SHEET METAL 5.3-WAY VALVE USED ON HOT WATER COILS AT THE DISCHARGE OF FAN COIL UNITS AT THE END OF THE RUN ONLY (ALL OTHER HEATING COILS SHALL BE PROVIDED WITH 2-WAY VALVES). REFER TO DRAWINGS 2.14P, 2.24P AND 2.34P FOR EXACT LOCATION. LARGE DOUBLE VANE SMALL DOUBLE VANE DETAIL NOTE: RADIUS ELBOWS SHALL HAVE A THROAT RADIUS ELBOW 36" OR WIDER LARGE DOUBLE VANE SQUARE ELBOW UP TO 36" IN WIDTH (NOT TO SCALE) LOW VELOCITY DUCTWORK ELBOWS EQUAL TO 1.5 TIMES DUCT WIDTH. 2 1/4" RUNNER DETAIL LARGE DOUBLE VANE 8 1/4" SMALL DOUBLE VANE SQUARE UP TO 20" IN WIDTH SINGLE VANE ELBOW 90 90 DETAIL SMALL DOUBLE VANE 2"R SINGLE VANE 4 1/2" R 1 1/8" 1"R 2 1/2" DETAIL 90 RUNNER DETAIL 2"R 4"R 1 9/16" 2"R 1"R 4 1/2" R VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:08pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: DETAILS SHEET 1 OF 5 M6.01 GES MAX. SPACING 4'-0" 8'-0" 6'-0" LESS THAN DUCT SIZE < 2 SQ. FT. > 2 SQ. FT. 48" WIDE 1"X1/16" 1"X1/8" HANGER SIZE OVER 10 SQ. FT. DUCT SIZE UPTO 4 SQ. FT. UPTO 10 SQ. FT. HANGER DETAIL FOR DUCTS SCREWS SHEET METAL FOR DUCTS OVER HANGER DETAIL 48" WIDE 2" MIN. AUXILIARY STRUCTURAL STEEL WHERE REQUIRED DUCT SUPPORT DETAIL (NOT TO SCALE) NOTES: 1.SPECIFICATION REQUIREMENTS SHALL APPLY WHERE THEY EXCEED THOSE INDICATED IN THIS DETAIL. 2.REFER TO DETAIL (TYPICAL PIPING, DUCTWORK, EQUIPMENT SUPPORT DETAIL FOR CONCRETE SUPPORTS.) (NOT TO SCALE) TRANSFER DUCT DETAIL 1" ACCOUSTICAL LINING W W 2W W BRANCH DUCT NECK 2 = MAIN DUCT NOTE: PROVIDE VOLUME DAMPER AT EACH LOW PRESSURE SUPPLY, EXHAUST AND RETURN BRANCH DUCT. MAIN - NECK 1 SIZE NECK 2 BRANCH 2 NECK 1 BRANCH 1~(SUPPLY AND RETURN) RISE OR DROP BOX OUTLET BE SAME SIZE AS BOX TO REHEAT COIL SHALL DUCT CONN. FULL SIZE OPENING ~ TURNING VANES NECK 1 = % AIR IN CHANGE IN MAIN DUCT SIZE, TYP. BRANCH DUCT, TYP.~~~~~~~~V.D., TYP. ~~~~~~~~~~ VAV BOX XX (CFM)~~~~TYPICAL SINGLE LINE DUCT STANDARDS (NOT TO SCALE) RECT. TO ROUND TRANSITION MIN. 3X DUCT DIAMETER STRAIGHT RUN INTO BOX ~~PLAN VIEW ELEVATION VIEW DUCT OVER DIFFUSERS/GRILLES SINGLE LINE DIAGRAM DUCT DIFFUSER/ GRILLE DUCT DIFFUSER/ GRILLE SMACNA'S FIRE SMOKE AND RADIATION DAMPER INSTALLATION A. ALL FIRE DAMPERS SHALL BE RATED TO MAINTAIN THE RATING OF THE FIRE SEPARATION. THEY SHALL BE APPROVED AND LABELED BY UNDERWRITER'S LABORATORIES (U.L). THE INSTAL- LATION SHALL BE IN ACCORDANCE WITH NFPA 90A, UL 555 AND GUIDE FOURTH EDITION 1992. B. ALL DUCT-COLLAR CONNECTIONS SHALL COMPLY WITH UL 555 AND C. GAUGES FOR COLLAR AND RECTANGULAR DUCT SHALL BE AS FOLLOWS: 1. CONNECTIONS BETWEEN COLLAR AND DUCT WORK SHALL BE BREAK- AWAY TYPE SUCH AS "S" SLIP, CRIMP, OR OTHER SLIP TYPE IN ACCORDANCE WITH SMACNA FIRE DAMPER GUIDE, 1992. UNLESS OTHERWISE REQUIRED BY CODE. 2. FIRE DAMPER COLLARS SHALL BE SAME GAUGE AS DUCTWORK WITH A MINIMUM OF 16 GAUGE FOR DUCTWORK UP TO 36" WIDE. FOR DUCTWORK ABOVE 36" WIDE, THE COLLAR SHALL BE 14 GAUGE. D. PROVIDE STEEL STUD FRAMING IN THE DRY WALL OPENING TO ACCEPT THE FIRE DAMPER ASSEMBLY (INCLUDING SLEEVES, ETC.) AS SHOWN. E. AFTER THE INSTALLATION OF DAMPERS, THE CONTRACTOR SHALL SEAL AND TAPE ALL JOINTS FOR AIR TIGHTNESS. ACCESS DOOR ON SIDE AS SHOWN OR BOTTOM OF DUCT. MIN. SIZE 18"x14" IF DUCT SIZE PERMITS SMALLER DUCTS MAKE DOOR 2" SMACNA. NOTES: SMALLER THAN DUCT. WELDS, NO. 10 SHEETMETAL SCREWS, 1/4" DIA., NUTS AND BOLTS, OR 3/16" STEEL POP RIVETS, ALL 6" ON CENTER. H. RETAINING ANGLES SHALL BE SECURED TO COLLAR, SLEEVE OR PLATE WITH EITHER 1/2" TACKWELDS, NO. 10 SHEETMETEL SCREWS, 1/4" DIA., NUTS AND BOLTS, OR 3/16" STEEL POP RIVETS, ALL 6" ON CENTER. I. WHERE HUNG CEILING DOES NOT HAVE REMOVABLE TILES, AN ACCESS DOOR (FIRE RATED WHERE REQUIRED) SHALL BE IN- STALLED IN CEILING NEAR LOCATION OF FIRE DAMPER. J. ALL RETAINING ANGLES SHALL BE GALVANIZED STEEL. K. INSTALL FIRE DAMPER IN THIS FASHION SO THE LOCKING DEVICE CAN BE ACCESSED WHEN THE DAMPER IS CLOSED. F. TO ALLOW FOR EXPANSION, DAMPERS SHALL HAVE A CLEAR- ANCE EQUIVALENT TO 1/8" FOR EACH FOOT OF DAMPER HEIGHT. THE SIDE CLEARANCE SHALL BE 1/8" FOR EACH FOOT OF DAMPER WIDTH DIVIDED EQUALLY TO THE RIGHT AND TO THE LEFT OF THE COLLAR. THE MAXIMUM CLEARANCE FOR THE TOP AND THE TOTAL OF BOTH SIDES SHALL BE 1/2" EACH. THE RETAINING ANGLES SHALL BE 1-1/2 x 1-1/2 x 1/8 SO THAT THERE WILL BE A MINIMUM OF 1" OVERLAP ON THE FIRE SEPARATION. G. DAMPER SHALL BE SECURED TO COLLAR WITH EITHER 1/2" TACK FIRE DAMPER DUCT DETAIL DOUBLE "S" SLIP CONNECTION TYPE ALL SIDES 1-1/2 x 1-1/2 x 1/8 MOUNTING ANGLES CONNECTION FLANGE CLEARANCE 1/4" MIN. 14 GA. SLEEVE FIRE RESISTIVE MATERIAL AS REQUIRED BY CODE. FIBERGLASS FIRE DAMPER SLEEVE #10 GAUGE STEEL SLEEVE 1/4" THICK (NOT TO SCALE) 1. MAT-FACED FIBERGLASS ACOUSTIC LINING APPROVED TYPE BY N.F.P.A. 90. 2. DUCT LINER SHALL BE ADHERED TO THE DUCT WITH AN APPROVED FIRE 3. MECHANICAL FASTENERS WHICH DO NOT PIERCE THE SHEET METAL SHALL BE ON 16" INCH CENTERS AND WITHIN 3" OE EACH EDGE (WELD PINS WITH A THICKNESS AND DENSITY AS PER SPEC. NEOPRENE COATED STENCILED NFPA 90. A SUITABLE FOR DUCT VELOCITY 0F 4000 F.P.M. RETARDANT ADHISIVE (6" WIDE @ 12" O.C. MINIMUM). WITH PERMANENTLY ATTACHED METAL NOSING. 4. ACOUSTICAL EDGES AT TRANSVERSE CONNECTIONS OR STARTING POINTS 2" WASHERS). NOTES : A DETAIL A-A 2 1 3 1 4 AIR FLOW DUCTWORK WITH ACOUSTICAL LINING (NOT TO SCALE) FIRE SMOKE COMBINATION DAMPER BOTH SIDES 6" MAX DUCT SPRING DAMPER OPERATOR OUTSIDE THE DUCT (COORDINATE LOCATION FOR ACCESS & SERVICING) SMOKE DETECTOR GENERAL NOTES: 1. DAMPER TO BE U.L. LABELED N.F.P.A. 90A AND MEA APPROVED. DAMPER SHALL BE RUSKIN MODEL FSD37 - 1-1/2 HOUR RATING (MEA #394-93-M) OR APPROVED EQUAL. 2. ACCESS DOOR IS SHOWN IN SIDE OF DUCT. 3. THIS DETAIL IS FOR GUIDE ONLY. INSTALL DAMPER IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. 4. DETAIL FOR SMOKE DAMPER IN TRANSFER OPENING SHALL BE SIMILAR, EXCEPT FOR CONNECTING DUCT, ACCESS DOOR AND BREAKAWAY CONNECTIONS. 5. MATERIAL AND EQUIPMENT DELIVERED WITHOUT MANUFACTURERS MEA OR BMS LABELS OR CERTIFICATES MUST BE REJECTED FROM JOB SITE AS PER 27-131(c). PROVIDE CLEARANCE OF 1/8" PER LINEAL FOOT OF SLEEVE DIMENSION (1" MAX.) ON SIDES OF SLEEVE. DAMPER SLEEVE TO BE MINIMUM 14" U.S. GA. SHEETMETAL SECURE RETAINING ANGLES TO SLEEVE 8" ON CENTER WITH 1/4" BOLTS & NUTS, 1/2" LONG WELDS, #10 STEEL SCREWS, OR 3/16" STEEL RIVETS. ANGLES MUST OVERLAP OPENING 1" MIN. PROVIDE FUSIBLE LINK IN DAMPER NOT TO SCALE ACCESS DOOR CONNECTING ROD RATED PARTITION BREAK AWAY CONNECTION, SEALED WITH A NON-HARDENING SEALANT, WITH FLAME SPREAD RATING LESS THAN 25 AND SMOKE DEVELOPED RATING OF LESS THAN 50. NO FASTENERS. VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:08pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: DETAILS SHEET 2 OF 5 M6.02 GES REFRIGERANT PIPING PORTAL DETAIL ELEC. POWER CONDUIT CONTROL CONDUITREFRIGERANT PIPING NOT TO SCALE PLENUM PITCH PLENUM TOWARDS LOUVER AIR PLENUM PITCH PLENUM TOWARDS LOUVER 1/8"SLOPE INSTALLATION DRAWINGS FOR LOUVER REFER TO ARCHITECTURAL NOTES: FLASHING BY G.C. FACE EXTERIOR BY G.C. FLASHING DRAWINGS FOR LOUVER REFER TO ARCHITECTURAL INSTALLATION FACE EXTERIOR METAL PLENUM AIR TIGHT SEAL SHEET AS PER SPECS (TYP.) STAINLESS STEEL WELDED CONSTRUCTION DUCT SUPPORTS BIRDSCREEN AIR TIGHT SEAL SHEET METAL PLENUM LOUVER AIR SEAL AROUND TIGHT ALL RIGID INSULATION PLENUMS AS SPECIFIED ON AIR TIGHT ALL AROUND AS PER SPECIFICATION SHEET METAL BLANK-OFF (TYP.) STAINLESS STEEL WELDED CONSTRUCTION DUCT SUPPORTS AS PER SPECS SEAL BLANK-OFF 1/8"SLOPE BIRDSCREEN TIGHT ALL LOUVER AIR SEAL AIR AROUND AS SPECIFIED ON RIGID INSULATION PLENUMS LOUVERS-DETAIL (NOT TO SCALE) PLENUM CONNECTIONS TO 1. CONTRACTOR SHALL FILL PLENUM WITH 10 GALLONS OF WATER, AND VERIFY THAT THE WATER DRAINS THROUGH THE LOUVER TO THE EXTERIOR OF THE BUILDING. 2. PROVIDE DRAIN AT LOWEST POINT OF THE PLENUM. DRAIN SHALL HAVE A P-TRAP AND PIPED TO NEAREST FLOOR DRAIN. FOR LOW PRESSURE DUCTWORK DUCT BRANCH TAKEOFF RETURN OR EXHAUST AIR SUPPLY AIR (NOT TO SCALE) VOLUME DAMPER WITH ADJUST DIAL SETTING 1/4 W 5"MIN 45 SUPPORT DETAIL FOR VERTICAL DUCTS PLAN ELEVATION DUCT DUCT SEAM DUCT RIVETED TO DUCT 2"X2"X1/8" ANGLES (NOT TO SCALE) SUPPLEMENTAL STEEL. REFER TO STRUCTURAL DRAWINGS. SQUARE DUCT ROUND DUCT DETAIL OF FLEXIBLE DUCT CONNECTOR (NOT TO SCALE) DUCT FLEXIBLE MATERIAL IMPREGNATED WOVEN GLASS CLOTH DUCT DRAW BANDS STAINLESS STEEL DETAIL DRAW BAND FLEXIBLE MATERIAL DRAW BAND WEATHERPROOF. ALL HARDWARE SHALL BE STAINLESS STEEL IN THIS INSTANCE. ACCESS DOOR & PANEL DETAILS SECTION "B"-"B" 1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY 2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS 3. PROVIDE ACCESS DOORS ON AIR HANDLING UNITS AND DUCT WORK INSTALLED IN EQUIPMENT ROOMS. PROVIDE ACCESS PANELS ON ALL EQUIPMENT AND DUCTWORK INSTALLED ABOVE FINISHED CEILINGS WHERE SPACE 4. ACCESS DOOR INSTALLED IN THE DUCT EXPOSED TO WEATHER TO BE (NOT TO SCALE) ACCESS DOOR LIMITATIONS DO NOT ALLOW HINGED DOORS TO OPEN. "B" NOTES: "B" INSULATION OR ACOUSTIC LINING OR ACOUSTIC SECTION "A"-"A" "A" ACCESS PANEL MIN. 3 LATCHES/DOOR MIN. 3 HINGES/DOOR "A" CASING DUCT OR LINING INSULATION HANDLE INSIDE GASKET GASKET DUCT DUCTS PENETRATING NON-RATED WALLS DETAIL FOR ACOUSTICAL SEALING OF (NOT TO SCALE) WALL PIPING THERMAL INSULATION AS SPECIFIED PIPING CLAMPS WELDED TO PIPE RISER CLAMP NUTS AND BOLTS PIPE RISER SUPPORTS DETAIL (NOT TO SCALE) SUPPLEMENTAL STEEL SUPPORTS BY HVAC CONTRACTOR SUPPLEMENTAL STEEL (TYP.) NOTES: 1.CENTERLINE OF PIPE SHALL ALIGN WITH CENTERLINE OF CLAMP 2.PROVIDE CONTINUOUS VAPOR BARRIER ON CHW PIPING 3.PROVIDE SHOP DRAWING TO STRUCTURAL ENGINEER FOR REVIEW 4.APPLICABLE TO PIPE RISERS GOING THROUGH LESS THAN 3 FLOORS. SEAL, CAULK WATER TIGHT BASE FLASHING (STAINLESS STEEL) ROOF FINISH ROOFING SYSTEM GALVANIZED MALEABLE IRON (I.P.S.) FLASHING FITTING COUNTER-FLASHING (STAINLESS STEEL) 6" ALL AROUND UPPER HALF WATER PROOF CAULKING COMPOUND LOWER HALF FIREPROOF PACKING SLAB STEEL PIPE SLEEVE ESCUTCHEON OR COVER PIPE THRU ROOF SLAB (NOT TO SCALE) PENETRATION DETAIL NOTE: 1.COORDINATE ALL FLASHING REQUIREMENTS WITH ARCHITECTURAL DRAWINGS. REINSULATE ROOF STRUCTURE IF OPENING IN STRUCTURE IS IRREGULAR AND GREATER THAN 1", WRAP DUCT WITH 1" THICK FIBROUS MATERIAL AND FILL REMAINING OPENING WITH GROUT IF OPENING IS LIMITED TO '(6,5('72Ð72r63$&( PACK OPENING ALL AROUND WITH FIBERGLASS AND CAULK WITH NON-HARDENING SEALANT DUCT LOAD SHOULD NOT BE CARRIED BY THIS SEAL NON-HARDENING MASTIC CAULKING COMPOUND Ð72r0$;,080 SHEET METAL SLEEVE MINERAL WOOL INSULATION NOTE: PROVIDE QUANTITY/SIZE OF PIPE/CONDUIT OPENING AS REQUIRED, COORDINATE WITH OTHER TRADES. VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:08pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: DETAILS SHEET 3 OF 5 M6.03 GES TRAPEZE HANGER REPLACE FIREPROOFING WHERE DISTURBED NOTES: 1. SUBMIT SHOP DRAWING OF SUPPLEMENTAL STEEL SUPPORT FOR REVIEW BY THE STRUCTURAL ENGINEER. SLAB SUPPLEMENTAL STEEL STEEL ANGLE (TYP.) SUPPLEMENTAL STEEL SUPPORT FOR EQUIPMENT AND PIPING DETAIL (NOT TO SCALE) THREADED HANGER ROD WITH HEX (TYP.) SUPPORT RODS WITH LOCKING NUT NOTE INTERIOR WALL U.L. FIRESTOP SYSTEM PIPE SLEEVE OF SIZE TO PASS PIPE PIPE 1/2" to 3/4" RATED WALL OR FLOOR PIPE PENETRATION OF (TYP. FOR BOTH SIDE OF WALL) 160 161 162 ADJUSTABLE WROUGHT CLEVIS PACK WITH INSULATING MATERIAL INSULATION SADDLE (SEE SCHEDULE) PIPE 1/2" TO 1 1/2" 2" TO 10" ABOVE 10" INSULATION MATERIAL HANGER GRINNELL FIG. 260 STEEL SADDLE FOR USE WITH HOT PIPING INSULATION INSULATION SADDLE SCHEDULE PIPE SIZE GRINNEL FIG No. VAPOR BARRIER HOT WATER UNIT HEATER (NOT TO SCALE) AIR FLOW MANUAL AIR VENT CONTROL VALVE SIZE OF PIPE DIRT POCKET FULL HWS AQUASTAT CIRCUIT SETTER T HWR FULL WELD TRANSITION DETAIL FROM STEEL TO COPPER (NOT TO SCALE) SCREWED COUPLING BLACK STEEL PIPE RISER OR MAIN RISER W/THREADED FEMALE END SCHEDULE 40 WELD-O-LET NEOPRENE GASKET COPPER RUNOUT KNURLED PIPE OR LUBRICATED PLUG VALVE W/FLANGED END COPPER PIPE TEFLON OR MICARTA DIELECTRIC MATERIAL GALVANIZED UNION SCHEDULE 40 SCREWED END BALL VALVE JAMESBURY OR MCANNA TO NEAREST FLOOR DRAIN CHARGING VALVE SHUT-OFF VALVE GLOBE VALVE QUICK FILL BY-PASS FLOOR DIRECTION OF FLOW FLOOR SUPPORTS DIAPHRAGM TYPE EXPANSION TANK CONNECTIONS DETAIL (NOT TO SCALE) CLOSED LOOP AIR-SEPARATOR AND DRAIN VALVE PIPED TO NEAREST FLOOR DRAIN (TYPICAL) UNION LOCKSHIELD VALVE 10" MIN. DRAIN VALVE ARRANGEMENT (NOT TO SCALE) AT LOW POINTS OF RISERS RISER OR UP-FEED RUNOUT HORIZONTAL BRANCH OR MAIN DIRT POCKET FULL SIZE OF PIPE (3" MAX.) 3/4" HOSE VALVE. PIPE TO NEAREST FLOOR DRAIN CAP NIPPLE AUTOMATIC AIR VENT PIPE TO NEAREST FLOOR DRAIN UNLESS OTHERWISE NOTED AUTO. AIR VENT W/PETCOCK (TYP.) ISOLATION VALVE 1/2" COPPER DRAIN LINE TOP OF WATER RISER OR HIGH POINT IN PIPING (NOT TO SCALE) UNION MANUAL AIR VENT DETAIL AT HIGH POINTS OF MAINS AND RISERS (IN ACCESSIBLE LOCATION) MANUAL VENT COCK (NOT TO SCALE) OF MAIN HIGH POINT NIPPLE CAP SIZE OF PIPE (3" MAX.) AIR POCKET FULL 10" MIN. 3/4" STEEL OR DRAIN LOCATION 1/2" COPPER TO PIPE PENETRATION OF INTERIOR NON-RATED WALL NOT TO SCALE INTERIOR WALL METAL PIPE SLEEVE PIPE 1" to 1 1/2" SEAL BOTH SIDES WITH NON-HARDENING FIRE PROOF CAULK MINERAL WOOL INSULATION TIGHTLY PACKED FOR FULL DEPTH OF WALL PACK OPENING ALL AROUND SHEET METAL SLEEVE AIRTIGHT WITH NON-HARDENING SEALANT ADJUSTABLE RANGE PRESSURE REDUCING VALVE BACKFLOW PROTECTED COLD WATER MAKE-UP SHUT-OFF VALVE SUPPLY CONNECTION PRESSURE RELIEF VALVE EXPANSION TANK STRAINER REMOVAL SPACE TO PUMP SUCTION AIR SEPARATOR SARCO 13 W FLOAT TYPE AIR VENTAIR SEPARATOR FCU-C-D-E HC-C-D-EHC-BHC-A HC-F-G-H FCU-BFCU-A FCU-F-G-H 14x8 20x8 32x8 48x8 OPEN RETURN W/WMS HOT WATER HEATING COIL DUCT SIZE SAME SIZE AS HEATING COIL (TYP.) BACK FLOW PREVENTER FIRST 20'-0" OF ALL LOW PRESSURE SUPPLY AND RETURN DUCTWORK FROM FCU UNITS SHALL BE 1" ACOUSTICALLY LINED. (TYP.) FOR ALL OPEN RETURN W/WMS OPEN RETURN W/WMS VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:08pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: DETAILS SHEET 4 OF 5 M6.04 GES TYPICAL CLAMP DETAILS UFS - BEAM CLAMP ADJUSTABLE SIDE - BEAM CLAMP NOT TO SCALE ALL THREADED ROD, SIZE AS REQUIRED NUT & BOLT WITH WASHER ASSEMBLY TOP SLIDE BOTTOM HOOK STRUCTURAL STEEL CLAMP JAWS ALL THREADED ROD, SIZE AS REQUIRED JAM NUT TIE ROD WITH NUTS & WASHERS CHEMICAL POT FEEDER DETAIL NOT TO SCALE ONE HALF MAIN PIPE SIZE 3/4" DRAIN CHEMICAL POT FEEDER SEE SPECS. 3/4" FILL AND VENT VALVE 4'-0" ABOVE FLOOR MAX FUNNEL FLOW INDICATOR UNION (TYPICAL)PUMP DISCHARGE PRESSURE GAUGE PUMP SUCTION CONDENSATE DRAIN TRAP NOT TO SCALE APPROVED AIR GAP HEIGHT EACH DIMENSION IS EQUAL TO FAN NEGATIVE STATIC PRESSURE FULL SIZE OF DRAIN CONNECTION REMOVABLE CAP UNION DRAIN PAN UNION REMOVABLE CAP FULL SIZE OF DRAIN CONNECTIONDRAIN PAN MINIMUM 1.5 X FAN TOTAL STATIC PRESSURE APPROVED AIR GAP HEIGHT DRAW-THRU UNIT BLOW-THRU UNIT [[g$1*/( 7<3,&$/ WOODEN JOIST (TYPICAL) PIPE OR DUCT HANGER WOOD JOIST DETAIL PIPE/DUCT SUPPORT FROM BOLT THROUGH JOIST (TYPICAL) NOT TO SCALE DOUBLE LOCK-NUT & WASHER (TYPICAL) HOT WATER CABINET UNIT HEATER DETAIL NOT TO SCALE HWR HWS BALL VALVE (TYP.) STRAINER AUTO CONTROL VALVE PREWIRED TO RETURN THERMOSTAT UNION (TYP.) CONTROLS COIL FAN ROOF-TOP CENTRIFUGAL EXHAUST FAN 12" ROOF CURB ROOF CURB MOTORIZED DAMPER 3/4" MIN. OVERLAP ROOF DECK & BUILT UP ROOFING SEE PLAN FOR DUCT SIZE CAULKING ALL-ROUND, TYP. FLASHING & COUNTER FLASHING FAN FAN MOTOR FAN HOUSING NOT TO SCALE FIELD WIRED FROM DISCONNECT TO STARTER REFER TO MANUFACTURER'S LITERATURE FOR SIZE OF OPENING REQUIRED 10" CLEARANCE ALL-ROUND DAMPER DETAIL # 3 - TOP OF RISER AND HORIZONTAL RUNS DETAIL # 1 - BASE OF RISER DETAIL # 2 - RISER LINE LEGEND NOTE: THIS DETAIL DOES NOT DEPICT SEISMIC SUPPORT INFORMATION. PROVIDE SEISMIC EQUIPMENT SUPPORT IN ACCORDANCE WITH APPLICABLE CODES AND MANUFACTURERS RECOMMENDATIONS. 1.ACR COPPER REFRIGERATION LINES TYPE L 2.CLOSED CELL INSULATION. THICKNESS AS DESIGNATED FOR THE PARTICULAR APPLICATION. 3.PIPE SUPPORT MATERIAL. 4.HYDRAZORB CLAMP ON LIQUID LINE ONLY. CORRESPONDING SUCTION LINE TO BE TIE STRAPPED TO LIQUID LINE. 5 5.NYLON LOCKNUT (AIRCRAFT TYPE) AND CADIUM PLATED BOLT. 6.PLATE OR SHEET METAL SADDLE (8" TO 12" IN LENGTH) TO PREVENT COMPRESSION OF INSULATION. SADDLE TO BE GLUED TO INSULATION. 7.NYLON TIE WRAP. DESIGNED TO SECURE BUT NOT TO TOTALLY PREVENT NORMAL EXPANSION AND CONTRACTION MOVEMENT. REFRIGERATION PIPING SUPPORT DETAILS NOT TO SCALE (NO DAMPER FOR DRYER EXHAUST) CLG ABOVE VALVE (TYPICAL) SHUT-OFF VALVE. COMBINATION BALANCING & HWR U HWS SHUT-OFF VALVE. AUTOMATIC CONTROL (TYPICAL) NOT TO SCALE NOTES: 1.SIMILAR PIPING FOR MULTIPLE ELEMENTS IN SERIES. 2.WHEN INSTALLING TWO ELEMENTS HIGH IN SERIES, CONNECT HWS TO BOTTOM ELEMENT AND PITCH UP TOWARD HWR. 3.THREE ELBOW CONNECTIONS SHALL BE USED AT SUPPLY & RETURN CONNECTIONS TO & FROM RISERS TO SUIT PROJECT. HOT WATER (BARE ELEMENT) FIN TUBE RADIATION 1/8" AIR VENT AT TOP OF RISER HWS THE HORIZONTAL DIMENSION OF THE OIL TRAPS SHALL BE AS SHORT AS POSSIBLE. 1. NOTES: SUCTION LINE OIL TRAP EXPANSION VALVE SOLENOID VALVE MOISTURE INDICATOR FILTER DRIER LIQUID LINE STOP VALVE WITH FITTINGS AS SPECIFIED FOR REFRIGERANT PIPING. COMBINED AS PART OF THE MOISTURE INDICATOR. (DRYERS MAY BE OF COMBINATION DRYER-INDICATOR TYPE) PLUGS, AND RELIEF DISCHARGE PIPING AS RECOMMENDED BY ASHRAE 15. VENT PRESSURE TAPS: EXCEPT AS INDICATED OTHERWISE, PROVIDE RELIEF VALVE, FUSABLE DISCHARGE PIPING, WHERE REQUIRED, IN LOCATIONS THAT ARE SAFE FOR ALL VALVE TO THE CONDENSER AND THE LIQUID LINE SIGHT GLASS. VALVES SHALL BE FOR THE REFRIGERANT SYSTEM LOCATED IN THE LIQUID LINE BETWEEN THE SHUT-OFF CHARGING VALVES: EXCEPT AS INDICATED OTHERWISE , PROVIDE CHARGING VALVES 350 PSIG WITHOUT DAMAGE. SIGHT GLASS BODY SHALL BE FORGED BRASS OR BRONZE SIGHT GLASS INDICATOR SHALL CAPABLE OF WITHSTANDING A TEST PRESSURE OF TYPE WITH TWO BULLS-EYE AND COVER CAPS OF NONFERROUS MATERIALS, UNLESS LIQUID REFRIGERANT SIGHT GLASSES: PROVIDE THE DOUBLE-PORT, SEE-THROUGH THE DESICCANT IN PLACE AND DISTRIBUTING THE LIQUID REFRIGERANT EQUALLY DRYER SHALL BE CAPABLE OF WITHSTANDING A SERVICE PRESSURE OF 250 PSIG. DRYER BODY SHALL BE OF BRASS OR STEEL AND PROVIDED WITH MEANS FOR HOLDING 6. PERSONNEL IN AND AROUND THE BUILDING. CONNECTED BY A FULL-SIZE LIQUID LINE TEE. 7. a. THROUGHOUT THE DESICCANT. b. 5. a. PITCH ALL LINES DOWN IN DIRECTION OF REFRIGERANT FLOW. REFRIGERANT DIAGRAM NOTES: PROVIDE WITH EXTERNAL, REMOVABLE STRAINER. VALVES SHALL OPEN WHEN TURNED COUNTER-CLOCKWISE. ENDS OF VALVES SHALL CONFORM TO ANSI B2.1. VALVES SHALL HAVE BRAZING TYPE CONNECTIONS. STEEL OR NONCORROSIVE NONFERROUS INTERNAL PARTS. REPLACEABLE WITHOUT BREAKING VALVE CONNECTIONS. WITHOUT APPLYING HEAT OR BREAKING PIPE CONNECTIONS. THREADED INTERNAL PARTS SHALL BE REMOVED FOR INSPECTION OR REPLACEMENT VALVES SHALL HAVE BRASS, BRONZE OR STEEL ALLOY BODIES WITH STAINLESS TEST AND RATE IN ACCORDANCE WITH ASHRAE STANDARD 17 AND ARI 750 FOR PROVIDE VALVE SIZE AND SUPERHEAT ADJUSTMENT AS RECOMMENDED BY THE POWER ASSEMBLIES AND VALVE CAGE ASSEMBLIES SHALL BE REMOVABLE AND THERMOSTATIC EXPANSION VALVES (DIRECT-OPERATED): PROVIDE DIAPHRAGM AND SPRING LOADED TYPE WITH EXTERNAL EQUALIZERS, BULB AND TUBING AND EXTERNAL SPECIFICALLY FOR REFRIGERANT SERVICE AND SUITABLE FOR INSTALLATION WITH REFRIGERATION: PROVIDE ISOLATION VALVES DESIGNED, MANUFACTURED, TESTED, PROVIDED WITH A VALVED BYPASS OF THE SAME SIZE OF THE LIQUID LINE. LIQUID LINE DRYERS: DRYERS SHALL BE THE CARTRIDGE REFILLABLE TYPE, AND e. 4. f. VALVE MANUFACTURER. CAPACITIES UP TO 40 KW. d. c. SUPERHEAT ADJUSTMENT WITH SEAL CAP. a. b. 3. b. COPPER TUBING. a. 1. 2. TYPICAL REFRIGERANT FLOW DIAGRAM NOT TO SCALE AHU ACCU VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:08pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 MECHANICAL: DETAILS SHEET 5 OF 5 M6.05 GES ENCLOSED CIRCUIT BREAKER FIRE ALARM SYSTEM, REMOTE ANNUNCIATOR FLOW SWITCH TAMPER SWITCH TELECOM SCOPE NOTES: 1.ALL TELECOM (DATA AND VOICE) CABLING WORK (CABLES, PULLS & INSTALLATION,) ARE NOT PART OF THIS BID PACKAGE, AND WILL BE PERFORMED BY OTHERS. 2.THIS CONTRACTOR SHALL PROVIDE UNDER THE BASE BID TELECOM OUTLET BOXES, CONDUITS, SLEEVES. 3.COORDINATE WORK WITH TENANT'S TELECOM CONTRACTOR. ELECTRICAL SYMBOL LIST AMPERE(S) CONDUIT WASHER & DRYER CIRCUIT BREAKER ABOVE FINISHED FLOOR AIR CONDITIONING UNIT ABBREVIATIONS EXISTING EXHAUST FAN ELECTRICAL GROUND LIGHTING POLE(S) RECEPTACLE POWER PANEL HORSE POWER KILO VOLT-AMPERE GROUND FAULT INTERRUPTER EMPTY CONDUIT EMERGENCY/NIGHT LIGHT TIME CLOCK SWITCH TYPICAL VOLT(S) UNLESS OTHERWISE NOTED WEATHERPROOF WATT(S) / WIRE G, GRD WP W TYP. UON V TC SW. PP RECEP LTG P KVA GFI HP CB EF EM/NL ELEC. EX, EXIST. EC WD AFF C A, AMP AC FIRE ALARM CONTROL PANEL FIRE ALARM HORN/STROBE MANUAL FIRE ALARM PULL STATION DUCT SMOKE DETECTOR HEAT DETECTOR FIRE ALARM STROBE FIRE ALARM CONTROL MODULE FIRE ALARM MONITORING MODULE CONDENSATE PUMPCP FIRE ALARM TERMINAL CABINET CEILING MOUNTED RECEPTACLE, TYPE AS SHOWN DOUBLE DUPLEX RECEPTACLE IN 2 GANG BOX, 20A, 125V, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED), RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED), SINGLE RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED) 6-20R 2 GFI 2P, 3W (GROUNDED), NEMA CONFIG. 5-20R NEMA CONFIG. 5-20R SINGLE SPECIAL PURPOSE RECEPTACLE: NEMA CONFIG. 5-20R NEMA CONFIG. 5-20R: (APPLIANCE OR EQUIPMENT OUTLET) DENOTES CIRCUIT NUMBER-'2' 'GFI'DENOTES GROUND FAULT INTERRUPTER- DENOTES SWITCH CONTROL-'a' '6-20R' 'R'- -DENOTES NEMA CONFIGURATION DENOTES RANGE PANEL OR CABINET, TYPE AS NOTED PANELBOARD (SURFACE TRIM) PANELBOARD (FLUSH TRIM) DISTRIBUTION PANELBOARD a 2 CONTROL SWITCH: DENOTES SWITCH CONTROL-'a' DENOTES 3-WAY SWITCH-'3' DENOTES 4-WAY SWITCH-'4' DENOTES AUTOMATIC VACANCY SENSOR SWITCH-'VC' 3 a CEILING, WALL MOUNTED REMOTE EMERGENCY LIGHT WALL OUTLET BOX AND LIGHT FIXTURE CEILING, WALL MOUNTED JUNCTION BOX CEILING OUTLET BOX AND LIGHT FIXTURE: HALF SHADE INDICATES FIXTURE WITH INTEGRAL EMERGENCY CEILING, WALL OUTLET BOX AND EXIT LIGHT: - DIRECTIONAL ARROWS AS INDICATED - SHADED AREA DENOTES FACE(S) UPON WHICH EMERGENCY LIGHTING BATTERY UNIT WITH SEALED BEAM HEADS - TICK WITH 'G' INDICATES SEPARATE INSULATED GROUND WIRE - TICK MARKS INDICATE NUMBER OF WIRES CONTAINED IN CONDUIT CIRCUIT HOMERUN TO PANELBOARD AND CIRCUITS INDICATED MULTI-POLE CIRCUIT HOMERUN TO PANELBOARD AND (PROVIDE IN ALL CONDUITS WHETHER SHOWN OR NOT.) CONNECTED TO UNSWITCHED LEG OF LOCAL LIGHTING CIRCUIT. HR DP-A #2 J J BATTERY BALLAST. 'EXIT' APPEARS CONDUIT RUN CONCEALED: LP-3A #1,3,5(R) G A a a 2 2 A CIRCUITS INDICATED CONDUIT RUN CONCEALED IN CEILING DENOTES FIXTURE TYPE-'A' DENOTES CIRCUIT NUMBER-'2' DENOTES SWITCH CONTROL-'a' DENOTES EMERGENCY-'EM' DENOTES EMERGENCY BATTERY BALLAST-'EMB' DENOTES NIGHT LIGHT (UNSWITCHED)-'NL' DENOTES SWITCHED-'SW' ARROWS DENOTE NUMBER OF CIRCUITS- (R)DENOTES CIRCUIT VIA RELAY FOR CONTROL- (PC)DENOTES VIA PHOTOCELL FOR CONTROL- TAIL DENOTES CONNECTION TO EQUIPMENT - AS REQUIRED DENOTES HOMERUN JUNCTION BOX-'HR' SMOKE DETECTOR TV WALL MOUNTED CATV OUTLET WALL MOUNTED DATA OUTLET - DENOTES PUBLIC TELEPHONE`P' TELEPHONE OUTLET: `W'- DENOTES FOR WALL MOUNTED TELEPHONE U.O.N. PROVIDE BUSHINGS. WITH DEDICATED 1"C STUBBED UP TO ABOVE ACCESSIBLE CEILING 2-GANG COVER, 4-11/16" SQ. x 2-1/8"D BOX WALL MOUNTED COMBINATION DATA/TELEPHONE OUTLET: MOUNTEDMTD DENOTES FOR AUDIO VISUAL CABLING-'AV' DENOTES ABOVE COUNTER HEIGHT-'AC' WALL FIRE ALARMFA DOUBLE DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED), NEMA CONFIG. 5-20R (APPLIANCE OR EQUIPMENT OUTLET) 'MC'DENOTES MOMENTARY CONTACT SWITCH- S F H D F F VC VC W DENOTES WATER COOLER-'WC' DENOTES REFRIGERATOR-'R' DENOTES MICROWAVE-'M' DENOTES COFFEE MAKER-'C' DENOTES DISHWASHER-'D' RECESSED 4-GANG WALL BOX FOR TV SIMILAR TO LEGRAND EFSB4 SERIES. WIRELESS ACCESS POINT LOCATION DENOTES CEILING MOUNTED OCCUPANCY SENSOROC WALL MOUNTED DUAL TECHNOLOGY VACANCY SENSOR UTILIZE EXISTING SWITCH TO PROVIDE MANUAL ON/OFF OVERRIDE. CEILING MOUNTED DUAL TECHNOLOGY VACANCY SENSOR WITH 1000 SQ FT COVERAGE. PROVIDE POWER / RELAY PACK(S) AND MOMENTARY CONTACT ON/OFF SWITCH(ES) AS REQUIRED FOR SWITCHING INDICATED. W WASHER-'W' NOTIFICATION APPLIANCE CIRCUITNAC MM CM SMOKE DETECTOR WITH SOUNDER BASESSB TS FS CB RA GENERAL NOTES: 1.REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL REQUIREMENTS. 2.ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE, REVIEW ARCHITECTURAL DRAWINGS AND BE RESPONSIBLE FOR REVIEWING A FULL SET OF BID DOCUMENTS TO MAKE HIMSELF AWARE OF THE TOTAL JOB BEFORE SUBMITTING HIS PRICE. 3.VERIFY ALL EXISTING SITE CONDITIONS IN THE FIELD AND INCLUDE IN THE BID, THE PRICE OF ALL WORK REQUIRED. 4.ALL WORK SHALL BE INSTALLED CONCEALED UNLESS OTHERWISE NOTED. 5.CONTRACTOR SHALL FIELD VERIFY DIMENSIONS OF FINISHED CONSTRUCTION PRIOR TO FABRICATION AND INSTALLATION OF FIXTURES AND EQUIPMENT. 6.ELECTRICAL CONTRACTOR SHALL SUBMIT SAMPLES OF RECEPTACLES AND PLATES TO THE ARCHITECT FOR APPROVAL BEFORE MAKING HIS INSTALLATION. 7.LIGHTING FIXTURES IN ACCESSIBLE CEILINGS SHALL BE FURNISHED WITH FLEXIBLE CONDUIT CONNECTIONS TO SEPARATELY MOUNTED JUNCTION BOXES. ONE JUNCTION BOX SHALL SERVE A MAXIMUM OF FOUR (4) FIXTURES. MAXIMUM LENGTH OF FLEXIBLE CONNECTION SHALL BE 6'-0". 8.WIRING IN AIR PLENUM HUNG CEILINGS INSTALLED WITHOUT CONDUIT OR EMT SHALL BE TEFLON JACKETED AND PLENUM RATED. 9.CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF EQUIPMENT TO BE INSTALLED BY OTHER TRADES BEFORE STARTING CONDUIT WORK. 10.CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL RACEWAYS AND WIRING FROM EQUIPMENT AND DEVICES TO THEIR SOURCE OF POWER. 11.CONTRACTOR SHALL, AFTER HIS WORK IS COMPLETED, TEST THE ELECTRICAL DISTRIBUTION SYSTEM FOR SHORT CIRCUITS, LOOSE WIRING, ETC., TO THE SATISFACTION OF THE OWNER. ALL COSTS FOR THIS TEST SHALL BE BORNE BY THE CONTRACTOR. 12.FOR WIRING IN METAL PARTITIONS WHERE EMT IS IMPRACTICAL, FLEXIBLE STEEL CONDUIT GALVANIZED, MINIMUM 3/4" SHALL BE USED. 13.FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL ELECTRICAL OUTLETS, SWITCHES AND LIGHTING FIXTURES SEE ARCHITECTURAL FLOOR PLANS, DETAILS AND ELEVATIONS. 14.MOUNTING HEIGHTS OF EQUIPMENT AND DEVICES SHALL BE AS INDICATED ON THE ARCHITECTURAL DRAWINGS. WHERE MOUNTING HEIGHTS ARE NOT GIVEN ON THE ARCHITECTURAL DRAWINGS, UTILIZE THE FOLLOWING MOUNTING HEIGHTS UNLESS OTHERWISE NOTED (ALL DIMENSIONS TO CENTERLINE OF BOX): A.RECEPTACLES (WALL MOUNTED) - 15" A.F.F. B.TELEPHONE/DATA OUTLETS - SAME AS RECEPTACLES C.WALL MOUNTED TELEPHONES - 44" A.F.F. D.LIGHTING SWITCHES AND CONTROLS - 48" A.F.F. TO TOP OF HANDLE E.MANUAL FIRE ALARM STATIONS - 48" A.F.F. TO TOP F.FIRE ALARM HORN AND STROBE UNITS - 80" A.F.F. OR 6" BELOW THE G.CARD READERS - 48" A.F.F. TO TOP H.PANELBOARDS AND CABINETS - 78" TO TOP OF ENCLOSURE. 15.MINIMUM RACEWAY SIZE SHALL BE 3/4" AND SHALL BE RUN PARALLEL TO BUILDING STRUCTURAL LINES. RACEWAYS SHALL NOT BE RUN HORIZONTALLY BELOW 8'-0" IN PARTITIONS. ALL EMPTY RACEWAYS SHALL BE FURNISHED WITH A 200 LB. TEST NYLON DRAG LINE. 16.WHERE EQUIPMENT, LIGHTING FIXTURES AND WIRING DEVICES ARE SHOWN WITH CIRCUIT NUMBERS ONLY, THE MINIMUM BRANCH CIRCUITING REQUIREMENTS SHALL BE AS FOLLOWS: A.LIGHTING FIXTURES - 2#12, 1#12 GRD. - 3/4"C. B.RECEPTACLES - 2#12, 1#12 GRD. - 3/4"C. C.HOMERUNS TO PANEL BOARDS SHALL CONTAIN NO MORE THAN (3) CIRCUITS. D.WHERE LIGHTING SWITCH INDICATIONS ARE NOT SHOWN, SWITCHES SHALL BE CONNECTED TO CONTROL ALL SWITCHED FIXTURES WITHIN THE CORRESPONDING SPACE. 17.WIRE SIZES SHALL BE INCREASED TO COMPENSATE FOR VOLTAGE DROP AS FOLLOWS: A.120V CIRCUITS LONGER THAN 75' SHALL UTILIZE MIN. #10 AWG. GARBAGE DISPOSALGD 'WD'-DENOTES WASHER & DRYER S SB CO SMOKE DETECTOR / CO DETECTOR COMBINATION WITH SOUNDER BASE DISCONNECTDISC. E. ELECTRICAL DRAWING LIST E0.GENERAL E0.01 GENERAL NOTES & SYMBOL LIST E1.SITE PLAN E1.00 SITE PLAN E2.BUILDING PLANS E2.00 LOWER LEVEL PLAN E2.01 GROUND FLOOR PLAN E2.02 SECOND FLOOR PLAN E2.03 THIRD FLOOR PLAN E2.04 FOURTH FLOOR PLAN E2.05 ROOF PLAN E4.DIAGRAMS E4.01 POWER RISER DIAGRAM E4.02 AUXILIARY SYSTEM RISER DIAGRAMS E5.SCHEDULES E5.01 SCHEDULES E6.DETAILS E6.01 DETAILS DOOR HOLDERDH VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 ELECTRICAL: GENERAL NOTES & SYMBOL LIST E0.01 AJS DRYDEN SOUTH, LLC (R.O.) DRY-LIN LLC PEA FAMILY REALTY, LLC (R.O.) LINDEN AVENUE ASSOCIATES (R.O.) LAMBROU (R.O.) EXISTING JOHNSON SCHOOL OF MANAGEMENT LRP-43 LRP-33 LRP-23 LRP-13 LRP-03 LRP-41 LRP-31 LRP-21 LRP-11 LRP-01 LRP-42 LRP-32 LRP-22 LRP-12 LRP-02 LRP-44 LRP-34 LRP-24 LRP-14 LRP-04 LRP-15 LRP-45 LRP-35 LRP-25 SPP ATS LRP-1BH PP-1BH INCOMING TELECOM SERVICE (2) 3"C T UTILITY TRANSFORMER MMU MULTIPLE METERING UNIT (TYP) M M M M MM UNDERGROUND 2" CONDUITS (TYP FOR EACH APARTMENT PANEL FEEDER) 1 (2)5" EMPTY CONDUITS WITH PULL STRINGS UTILITY POLE APPROXIMATE LOCATION OF LOWER LEVEL IT/DATA ROOM 4 SETS OF 3#350KCMIL+1#3/0G-3"C KEYED NOTES TYPICAL FEEDERS TO BE ROUTED UNDER AREAWAYS AND UNDER BASEMENT FLOOR SLABS. FEEDERS TO STUB UP AT PANEL LOCATIONS. FEEDERS TO UPPER FLOOR PANELS TO BE CONCEALED IN WALLS. 1 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 0 4 8 16 FEET SCALE: 1/8"=1'-0"1 SITE PLAN ELECTRICAL: SITE PLAN E1.00 AJS REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF IT/DATA HOUSEKEEPING / BUILDING STORAGE MECHANICAL KEYED NOTES LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE THE DOOR. COORDINATE EXACT LOCATION WITH THE OWNERS REPRESENTATIVE FROM DATA CLOSET. CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT AND CONTROL DEVICE. UP TO LIGHT AND SWITCH AT TOP OF SHAFT PROVIDE 4-CHANNEL, ASTRONOMICAL TIME CLOCK WITH PHOTOSENSOR OVERRIDE SIMILAR TO TORK #DLC400BP. COORDINATE PROGRAMMING WITH OWNER. COORDINATE MACHINE ROOMLESS ELEVATOR POWER / CONTROLS LOCATION WITH MANUFACTURER'S DATA / EQUIPMENT AT TOP OF SHAFT. FOR MOTORIZED DAMPERS INSTALLED ON PLENUM. PROVIDE INTERCONNECTION TO BOILERS, HOT WATER HEATER, AIR HANDLER, AND MECHANICAL ROOM EXHAUST FAN TO OPEN DAMPERS UPON ACTIVATION OF ASSOCIATED EQUIPMENT. COORDINATE EXACT REQUIREMENTS WITH MECHANICAL CONTRACTOR. FIRE ALARM SYSTEM SHALL SHUNT TRIP POWER UPON HEAT DETECTOR ACTIVATION. PROVIDE ADDITIONAL INTERFACE RELAY AS REQUIRED FOR MONITORING OF ELEVATOR POWER. 1 2 3 4 5 6 7 DRAWING NOTES: 1.ALL CIRCUITS SHOWN SHALL BE FED FROM 'PP-1BH', U.O.N. 2.EMERGENCY BALLASTS OF ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF UNSWITCHED CIRCUIT SERVING THE AREA. 3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE WIRED THRU TIME CLOCK LOCATED IN LOWER LEVEL MECHANICAL ROOM. F1 F3 F1 F1 F1 F1 F1 F3 F1 F3 F5 F4 F5 R b aab TV+ 2 BS JSM ALL CIRCUITS SHALL BE FED FROM 'LRP-03', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-01', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-02', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-04', U.O.N. JSM P-HW-1 P-HW-2 CO MONITORING PANEL FOR ELEVATOR S GFI H 5 GFI3 H H H S S S S S SPPATS LRP-1BH PP-1BH 1 FOR RANGE HOOD / MICROWAVE (TYP.) LRP-03 LRP-01 LRP-02 FCU-B VFD AHU-1 VFD VFD D 11 17 1FSD 6 4 B-2 B-1 35 EM/NL EM/NL GFI FACP 3 EM EM EM EM F F FF F F TS TS TS FS TS TS TS TS TS GWH-1 GWH-2 CONSTANT AIR VOLUME CONTROL PANEL PUMP CONTROL PANEL (TYP FOR 2) GFP-1 UH-B SP-1 EJ-1 MM JSM3 33 5 7 79 11 13 4 44 4 M 2 1 1 8 8 8 1 1 6 4 F1 F1 F1 F1 F4 R b aab TV+ 2 JSM 1 FCU-B 3 5 7 79 11 13 4 44 4 M 2 1 1 8 8 8 1 1 6 4 F1 F1 F1 F1 F4 R b aab TV+ 2 JSM 1 FCU-B 3 5 7 79 11 13 4 44 4 M 2 1 1 8 8 8 1 1 6 4 F1 F1 F1 F1 F4 R b ab TV+ 2 JSM 1 FCU-B 3 5 7 79 11 13 4 44 4 M 2 1 1 8 8 8 1 1 6 4 10 10 10 10 1 1 1 1 1 1 1 1 1 FF OC OC BS JSM BS JSM BS JSM M UH-A 16 SPP SPP G G G G JSM CP-1 11 14 10 10 SPP 7 9 2 SPP SPP SPP#8 SPP#8 SPP#8 SPP#8 SPP#8 SPP#8 2 2 2 1 8 10 12 14 ALL CIRCUITS SHALL BE FED FROM 'LRP-1BH', U.O.N. 11 1 TC FOR ELEVATOR4 13 15 15 FS TS 30 F2X F2X EF-3 LRP-04 EWH-A 14 11 11 11 13 LRP-1BH 13 LRP-1BH 10 10 J FOR DOOR HOLD OPEN 16 ANN GENERATOR ANNUNCIATOR 7 SPP 7 28 TO ELEV DISC. IN MECH. ROOM 7 NL NL a EM a EM a EM F3 1a EM a a a a 35SCO SB S CO SB S CO SB S CO SB 8 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 SCALE: 1/4"=1'-0" 0 4 8 FEET 1 LOWER LEVEL PLAN ELECTRICAL: LOWER LEVEL PLAN E2.00 AJS 1 1 1 1 1 2 REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF ENTRY LOBBY EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF KEYED NOTES LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE THE DOOR. COORDINATE EXACT LOCATION WITH THE OWNERS REPRESENTATIVE FROM DATA CLOSET. CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT AND CONTROL DEVICE. 1 2 DRAWING NOTES: 1.ALL CIRCUITS SHOWN SHALL BE FED FROM 'PP-1BH', U.O.N. 2.EMERGENCY BALLASTS OF ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF UNSWITCHED CIRCUIT SERVING THE AREA. 3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE WIRED THRU TIME CLOCK LOCATED IN LOWER LEVEL MECHANICAL ROOM.F1 F1 F1F1 F1 F1 F1 F1 F1 F1 F3 F1 F1 F1F1F1 F1 F1F1 F1 F1 F1 F1 F1 F5F6 F5 F4 F2 F2 F4 F4 F4 F4 R R R R R b aab b aab b aab b aab b aab TV + TV+ ALL CIRCUITS SHALL BE FED FROM 'LRP-13', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-11', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-12', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-14', U.O.N. 2 BS JSM BS JSM BS JSM BS JSM JSM JSM JSM J SM JSM ALL CIRCUITS SHALL BE FED FROM 'LRP-15', U.O.N. FCU-E JSM S 1 1 1 1 1 FCU-B FCU-B FCU-B FCU-B FCU-A EM/NL EM/NL EM EM EM EMEM EM FF F F TS FS OC OC OC OC 1 1 1 1 1 1 1 11 1 1 FF 1 LRP-13 LRP-11 LRP-12 13 77539 11 4 44 2 4 M 6 4 1 1 8 8 8 1 44 M 4 44 7539 10 11 7 6 TV+ 1 1 8 1 1 8 8 TV+ 1 1 8 1 1 8 8 TV+ 1 1 8 1 1 8 8 1 188 8 1 1 4 4 4 4 7539 13 M 13 7539 13 M 4 4 4 4 4 13 9 11 3 5 7 7 10 M 4 4 4 4 4 11 6 6 7 7 1 11 11 1 BS JSM CUH-A 2 2 2 M 17 M 17 LRP-15 LRP-14 FX5 FX5 2 2 2 2 EWH-A 14 EWH-A 14 11 11 11 11 11 13 LRP-1BH 13 LRP-1BH 10 10 10 10 10 J FOR DOOR HOLD OPEN 16 J16 FOR ENTRY DOOR POWER SUPPLY F3 1a EM F3 1a EM NL F3 1a EM NL F3 1a EM a a a a EM/NL F6 1EM/NL S CO SB S CO SB S CO SB S CO SB S CO SB S S S 8 8 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 SCALE: 1/4"=1'-0" 0 4 8 FEET 1 GROUND FLOOR PLAN ELECTRICAL: GROUND FLOOR PLAN E2.01 AJS 1 1 1 1 1 1 1 1 1 2 REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF KEYED NOTES LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE THE DOOR. COORDINATE EXACT LOCATION WITH THE OWNERS REPRESENTATIVE FROM DATA CLOSET. CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT AND CONTROL DEVICE. PROVIDE ROOF SNOW & ICE MELTING CABLE ON CANOPY SIMILAR TO RAYCHEM GM-1XT. PROVIDE WITH DIGITAL ELECTRONIC CONTROLLER WITH GROUND FAULT (RAYCHEM #ECW-GF) AND ALL REQUIRED POWER CONNECTION KITS, END SEALS, MOUNTING ACCESSORIES AND OTHER ASSOCIATED APPURTENANCES FOR A COMPLETE AND FULLY OPERATIONAL SYSTEM. ELECTRONIC CONTROLLER SHALL BE MOUNTED UNDERNEATH CANOPY. WIRE TO PANEL LRP-1BH CIRCUIT #7. 1 2 3 DRAWING NOTES: 1.ALL CIRCUITS SHOWN SHALL BE FED FROM 'PP-1BH', U.O.N. 2.ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF UNSWITCHED CIRCUIT SERVING THE AREA. 3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE WIRED THRU TIME CLOCK LOCATED IN LOWER LEVEL MECHANICAL ROOM. F1 F1 F1F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1F1 F1 F1 F4 F4 F5 F4 F4 F4 F5 F2 aR R R R b ab ab aab ab ab b baab b a c TV+ TV+ TV+ ALL CIRCUITS SHALL BE FED FROM 'LRP-23', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-21', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-22', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-24', U.O.N. BS JSM BS JSM BS JSM BS JSM JSM JSM J SM JSM ALL CIRCUITS SHALL BE FED FROM 'LRP-25', U.O.N. S FCU-D JSM 1 1 1 1 1 4 4 4 4 4 4 6 2 10 FOR RANGE HOOD / MICROWAVE (TYP.) FCU-B FCU-B FCU-B FCU-B EM/NL EM/NL EM EMF F FF TS FS R TV+ 13 8 4a c 1 1 1 8 8 LRP-23 LRP-21 LRP-22 LRP-24 3 3 3 TV+ 1 1 8 8 1 1 8 13 77539 13 77539 13 77539 7 7 5 3 9 M M M M 9 11 3 5 7 7 11 2 4 4 44 4 1 1 6 11 1 1 8 8 8 6 4 4 44 4 11 1 1 8 8 8 4 4 4 4 462 11 1 1 4 4 44 4 13 1 1 8 8 1 1 8 26 1 1 10 10 10 10 3 F BS JSM 4 4 4 4 4 FX6 2 2 2 2 2 LRP-25 11 11 11 11 13 LRP-1BH 10 10 10 10 10 J FOR DOOR HOLD OPEN 16 F F F1 F1 F1 F6 OC OC OC 3 3 3 3 F3 3a EM F3 3a EM NL F3 3a EM NL 3a EM a a a a EM/NL F6 3EM/NL F3 S CO SB S CO SB S CO SB S CO SB S CO SB S CO SB S S VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 SCALE: 1/4"=1'-0" 0 4 8 FEET 1 SECOND FLOOR PLAN ELECTRICAL: SECOND FLOOR PLAN E2.02 AJS 1 1 1 1 1 1 1 1 1 REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF KEYED NOTES LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE THE DOOR. COORDINATE EXACT LOCATION WITH THE OWNERS REPRESENTATIVE FROM DATA CLOSET. CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT AND CONTROL DEVICE. PROVIDE ROOF SNOW & ICE MELTING CABLE ON CANOPY SIMILAR TO RAYCHEM GM-1XT. PROVIDE WITH DIGITAL ELECTRONIC CONTROLLER WITH GROUND FAULT (RAYCHEM #ECW-GF) AND ALL REQUIRED POWER CONNECTION KITS, END SEALS, MOUNTING ACCESSORIES AND OTHER ASSOCIATED APPURTENANCES FOR A COMPLETE AND FULLY OPERATIONAL SYSTEM. ELECTRONIC CONTROLLER SHALL BE MOUNTED UNDERNEATH CANOPY. WIRE TO PANEL LRP-1BH CIRCUIT #9. 1 2 3 DRAWING NOTES: 1.ALL CIRCUITS SHOWN SHALL BE FED FROM 'PP-1BH', U.O.N. 2.EMERGENCY BALLASTS OF ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF UNSWITCHED CIRCUIT SERVING THE AREA. 3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE WIRED THRU TIME CLOCK LOCATED IN LOWER LEVEL MECHANICAL ROOM. R R R R R b aab b aab b aab b aba TV+ TV+ TV+ TV+ ALL CIRCUITS SHALL BE FED FROM 'LRP-33', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-31', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-32', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-34', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-35', U.O.N. JSM JSM JSM JSM 2 2 2 FCU-C JSM S 3 1 1 1 1 1 FCU-B FCU-B FCU-B FCU-B EM/NL EM/NL EM EM FF F F TS FS LRP-34 LRP-33 LRP-31 LRP-32 3 3 3 3 13 77539 11 13 77539 11 13 4 4 44 2 6 1 1 M M M M M 4 4 4 4 4 6 1 1 2 2 6 4 4 4 4 1 1 1 1 6 11 13 44 2 4 44 4 2 4 44 4 4 6 13 7 11 9 3 5 7 1 1 8 8 8 1 1 8 8 8 1 1 8 8 8 8 1 1 1 8 8 8 1 1 8 7 7 5 3 9 77539 11 10 10 10 10 10 OC BS JSM BS JSM BS JSM BS JSM 3 BS J SM 4 4 4 TV+ 1 1 LRP-35 2 2 4 b b aa a c 11 11 11 11 11 10 10 10 10 10 J FOR DOOR HOLD OPEN 16 F F F1 F1 F1 F6 OC OC OC 3 3 3 F3 3a EM F3 3a EM NL F3 3a EM NL 3a EM a a a a EM/NL F6 3EM/NL S CO SB S CO SB S CO SB S CO SB S CO SB S CO SB S S VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 SCALE: 1/4"=1'-0" 0 4 8 FEET 1 THIRD FLOOR PLAN ELECTRICAL: THIRD FLOOR PLAN E2.03 AJS 1 1 1 1 1 1 1 1 1 REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF EFFICIENCY 330 SF 1-BED 430 SF KEYED NOTES LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE THE DOOR. COORDINATE EXACT LOCATION WITH THE OWNERS REPRESENTATIVE FROM DATA CLOSET. CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT AND CONTROL DEVICE. DOWN TO LIGHT AND SWITCH AT BOTTOM OF SHAFT 1 2 3 DRAWING NOTES: 1.ALL CIRCUITS SHOWN SHALL BE FED FROM 'PP-1BH', U.O.N. 2.EMERGENCY BALLASTS OF ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF UNSWITCHED CIRCUIT SERVING THE AREA. 3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE WIRED THRU TIME CLOCK LOCATED IN LOWER LEVEL MECHANICAL ROOM. F1F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F2 F1 F1 F1 F1 F1 F1 F1F1 F5 F5 F4 F4 F4 F4 F4 R R R R b aab b aab b aab b aba R ALL CIRCUITS SHALL BE FED FROM 'LRP-43, U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-41', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-42', U.O.N. ALL CIRCUITS SHALL BE FED FROM 'LRP-44', U.O.N. JSM JSM JSM JSM 2 2 2 2 FCU-C JSM 3 S H S 1 1 1 1 1 ALL CIRCUITS SHALL BE FED FROM 'LRP-45', U.O.N. EM/NL EM/NLEM EM FF F F TS FS LRP-43 LRP-41 LRP-42 LRP-45 LRP-44 5 5 5 5 13 77539 11 13 77539 11 13 77539 11 1 1 8 8 8 1 1 8 8 8 1 1 8 8 8 8 1 1 1 8 8 8 1 1 8 13 7 11 9 3 5 7 2 2 2 2 2 M M M M M FCU-B FCU-C FCU-B 7 7 5 3 9 11 10 10 10 10 10 FCU-B TV+ 1 1 TV+ 1 1 TV+ 1 1 TV+ 1 1 TV+ 1 1 6 6 6 6 6 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 44 4 4 4 4 4 4 44 4 4 13 BS JSM BS J SM BS JSM BS J SM BS J SM 6 6 6 2 b ab a a c 11 11 11 11 11 10 10 10 10 10 J FOR DOOR HOLD OPEN 16 F F F1 F1 F1 F6 OC OC OC 5 5 5 5 F3 5a EM F3 5a EM NL F3 5a EM NL 5a EM a a a a EM/NL F6 5EM/NL F3 TS a a GFI 15 3 S CO SB S CO SB S CO SB S CO SB S CO SB S CO SB S S VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 SCALE: 1/4"=1'-0" 0 4 8 FEET 1 FOURTH FLOOR PLAN ELECTRICAL: FOURTH FLOOR PLAN E2.04 AJS 1 1 1 1 1 1 1 1 1 REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F REF-F REF-A REF-A REF-C REF-C REF-D REF-D REF-E REF-B REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9JST EF-2 JST EF-1 JST TEF-E JST TEF-C J ST TEF-B JST TEF-A ACCU-1 WP WP WP WP WP WP ACCU-2 12KW / 15kVA, 208/120V, 3-PHASE, 4-WIRE, NATURAL GAS GENERATOR WITH 60A OUTPUT CIRCUIT BREAKER IN WEATHERPROOF, LEVEL 1, SOUND ATTENUATED ENCLOSURE (APPROX. 500 LBS) ACCU-3 JST TEF-D WP 23 2GFI WP a GFI WP a PC aGFI WP a a DRAWING NOTES: 1.ALL CIRCUITS SHOWN SHALL BE FED FROM 'PP-2BH', U.O.N. 2.ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF UNSWITCHED CIRCUIT SERVING THE AREA. KEYED NOTES MOTORIZED DAMPERS FOR EXHAUST FANS SHALL BE CONNECTED TO 120V CIRCUIT OF ASSOCIATED FAN. PROVIDE ALL REQUIRED 120V POWER TO THERMOSTAT AND MOTORIZED DAMPER. COORDINATE LOCATION OF EQUIPMENT WITH MECHANICAL CONTRACTOR. 1 2 29 GFI WP 12 a GFI WP a 8 8 8 8 10 10 10 12 12 12 12 12 12 12 12 12 1 2 2 2 2 2 JST TEF-A WP10 2 J ST TEF-E WP8 2 a 12a 12 a12 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY PROJECT NORTH 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 SCALE: 1/4"=1'-0" 0 4 8 FEET 1 ROOF PLAN ELECTRICAL: ROOF PLAN E2.05 AJS LOWER LEVEL GROUND FLOOR SECOND FLR THIRD FLR FOURTH FLR ROOF GRADE KEYED NOTES 3#1/0+1#6G-2"C1 MECH LRP-01 LRP-02 LRP-04 LRP-03 LRP-13LRP-14LRP-15LRP-11 LRP-12 LRP-22 LRP-32 LRP-42 LRP-25 LRP-35 LRP-45 LRP-24 LRP-34 LRP-44 LRP-23 LRP-33 LRP-43 LRP-21 LRP-31 LRP-41 G 12kW / 15kVA, 208/120V 3-PHASE, 4-WIRE, NATURAL GAS GENERATOR WITH 60A OUTPUT CIRCUIT BREAKER IN WEATHERPROOF, LEVEL 1, SOUND ATTENUATED ENCLOSURE 125A 125A 125A 125A 125A 125A 125A 125A 125A 125A 125A 125A 125A 125A MMU M M M M M M M M M M M M M M HOUSE M 125A 125A125A125A M M M M 400A 4#500KCMIL+1#2G-3-1/2"C 24"MIN 125A M 125A 125A 125A 125A M M M M 125A M LRP-1BH PP-1BHEN L ATS 60A, 208/120V, 3-PHASE, 4-WIRE (3-POLE) SPP 11 1 1 1 1 1111 1 1 1 11 1 111 111 11 125A, 208/120V, 1-PHASE, 3-WIRE (TYP) UTILITY TRANSFORMER 208/120V, 3-PHASE, 4-WIRE SECONDARY UTILITY SERVICE 4 SETS OF 3#350KCMIL+1#3/0G-3"C (2)5"C EMPTY CONDUIT 60A J ANN GENERATOR ANNUNCIATOR MAIN SERVICE SWITCH 4#4+1#8G-1-1/2"C PP-1BH#36 4#4+1#8G-1-1/2"C 4#4+1#8G-1-1/2"C CONTROL WIRING IN 1"C (TYP) SEE E1.00 FOR ADDITIONAL INFORMATION PP-1BH#37 4#4+1#8G-1-1/2"C ELECTRICAL: POWER RISER DIAGRAM E4.01 AJS NOT TO SCALE1ONE LINE DIAGRAM VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 LOWER LEVEL GROUND FLOOR SECOND FLOOR THIRD FLOOR FOURTH FLOOR ROOF KEYED NOTES PROVIDE (2) 3" CONDUITS FOR TV AND TELE/DATA INCOMING SERVICE. PLYWOOD BACKBOARD IN MECHANICAL ROOM FOR TV AND TELE/DATA EQUIPMENT. PROVIDE (1) 2-1/2"C FROM MECHANICAL ROOM TO ABOVE CEILING OF COMMON CORRIDOR. SERVICE LOCATION FOR INDIVIDUAL APARTMENT. REFER TO FLOOR PLANS FOR EXACT LOCATIONS AND QUANTITIES. 1 2 3 4 2 GENERAL NOTES A.PROVIDE GROUNDING PER SPECIFICATIONS AND DETAILS B.COORDINATE ENTIRE INSTALLATION WITH TIME WARNER C.INSTALL COAX CABLE FURNISHED BY TIME WARNER CABLE TIME WARNER CABLE SHALL PROVIDE TERMINATIONS AND TESTING INSTALL OUTLET IN COVER PLATE AND PROVIDE COVER PLATE MECHANICAL ROOM GROUND BAR #6 GROUND TO GROUNDING ELECTRODE SYSTEM RG-6U COAX FURNISHED BY TWC, INSTALLED BY ELECTRICAL CONTRACTOR CATV SERVICE ENTRANCE EQUIPMENT BY TIME WARNER TIME WARNER BACKBOARD CATV SERVICE ENTRANCE CABLE PROVIDED BY SERVICE PROVIDER TV REFER TO FLOOR PLANS FOR QUANTITY / LOCATIONS FACP RA FATC F EOL F F F F S H F CM TS CM FS FFEOL FFEOL FATC FFEOL FATC FFEOL FATC FFEOL F 120V 20A-1P S H F CM TS CM FS ELEVATOR PRIMARY RECALL ELEVATOR SECONDARY RECALL ELEVATOR SHUNT TRIP ELEVATOR FIREMAN'S HAT CMCMCMCMMM ELEVATOR MONITORING 1 GROUND FLR FIRST FLR SECOND FLR THIRD FLR FOURTH FLR LOWER LEVEL 1 2 TV TV TV TV TV TV 3 3 3 3 3 3 4 4 4 4 4 4 CM S H F CM TS CM FS CM S H F CM TS CM FS CM S H F CM TS CM FS CM MMMMCM GENERATOR RUN GENERATOR TROUBLE DOOR HOLD OPEN NOT TO SCALE TYPICAL CABLE TV SERVICE DIAGRAMS NOT TO SCALE FIRE ALARM RISER DIAGRAM CATV WIRING DIAGRAM CONDUIT DISTRIBUTION ELECTRICAL: AUXILIARY SYSTEMS RISER DIAGRAMS E4.02 AJS VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 LIGHTING FIXTURE SCHEDULE FIXTURE TYPE DESCRIPTION MANUFACTURER CAT NO.BALLAST VOLTAGE LAMPS REMARKS(#) WATTS, TYPE F1 10" LED, CEILING MOUNTED FLUSH FIXTURE WAC LIGHTING FM-4610-30-WT DRIVER 120 12.5W, LED F2 LED WALL MOUNTED SCONCE WAC LIGHTING WS-7318-BN DRIVER UNV 20.5W, LED F3 10" LED, CEILING MOUNTED FLUSH FIXTURE WAC LIGHTING FM-4610-30-WT DRIVER 120 12.5W, LED WITH MINI INVERTER - PW SERIES BY EVEN LITE F4 LED BATH VANITY FIXTURE WAC LIGHTING WS-7334-BN DRIVER 120V 48W, LED F5 WALL MOUNTED, LED STAIR FIXTURE WITH INTEGRAL OCCUPANCY SENSOR LUMINAIRE LED TSL94-100W-3500K-MV-120-277-OP-W HT-DAMP-EMB722 DRIVER UNV 100W, LED F6 WALL MOUNTED, LED STAIR FIXTURE WITH INTEGRAL OCCUPANCY SENSOR LUMINAIRE LED TSL92-50W-3500K-MV-120-277-OP-WH T-DAMP-EMB722 DRIVER UNV 50W, LED FX2 LED OUTDOOR WALL SCONCE MODERN FORMS WS-W1408-GH DRIVER 120 11.5W, LED FX5 LED STRIPLIGHT INTERLUX 98407-XX DRIVER 120V 3.7W/FT, LED LENGTH AS INDICATED ON DRAWINGS. PROVIDE ALL REQUIRED MOUNTING HARDWARE AND ACCESSORIES FOR A COMPLETE INSTALLATION FX6 LED OUTDOOR LINEAR LIGHT INTERLUX E97687-W-20 DRIVER 120V 25W, LED PROVIDE ALL REQUIRED MOUNTING HARDWARE AND ACCESSORIES FOR A COMPLETE INSTALLATION FE1 REMOTE BATTERY PACK WITH SELF-DIAGNOSTICS EVENLITE TCL2WSD NICKEL CADMIUM UNV (2) 2W LED FE2 EXIT LIGHT WITH INTEGRAL BATTERY EVENLITE SOVEMNR2MBARCXXSD LED UNV 2.5W, LED FE3 EXIT LIGHT EVENLITE TLXEMRUWSD LED UNV 2.5W, LED NOTES: 1.LIGHTING FIXTURE SCHEDULE SHOWN ON ENGINEER'S DRAWINGS ARE FOR INFORMATION PURPOSES ONLY. LIGHTING FIXTURES SHOWN ARE THOSE SELECTED BY ARCHITECT. ENGINEER SHALL NOT BE RESPONSIBLE FOR INFORMATION SHOWN RELATED TO FIXTURE SELECTION AND OVERALL LIGHTING DESIGN. ARCHITECT SHALL CONFIRM EXACT STYLES, COLORS, FINISHES AND MODEL NUMBERS OF ALL LIGHT FIXTURES. 2.COORDINATE LOCATION OF REMOTE DRIVERS IN FIELD. LOCATE DRIVERS WITHIN ACCESSIBLE CEILINGS. NOTES: 1.TYPICAL FOR ALL APARTMENT PANELS. REFER TO E1.00 AND FLOOR PLANS. ELECTRICAL: SCHEDULES E5.01 AJS 1 1 VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4 2 1 ABBREVIATION LIST JH =MAIN ELEVATOR SERVICE DISCONNECT SWITCH VIA SHUNT TRIP CIRCUIT BREAKER. PROVIDED BY ELECTRICAL CONTRACTOR JH1=HOISTWAY AUXILIARY DISCONNECT SWITCH PROVIDED BY ELECTRICAL CONTRACTOR JHL=ELEVATOR CAB LIGHTS AND POWER DISCONNECT SWITCH. PROVIDED BY ELECTRICAL CONTRACTOR. LDU=INSPECTION AND TEST PANEL PROVIDED BY ELEVATOR CONTRACOTOR TA=3-PHASE AUTOTRANSFORMER (208V, 480V) PROVIDED BY ELEVATOR CONTRACTOR TSU=MOTOR CONTROLLER PROVIDED BY ELEVATOR CONTRACTOR TAS=TEST AND INSPECTION PANEL AUTOTRANSFORMER PROVIDED BY ELEVATOR CONTRACTOR VFD=VARIABLE FREQUENCY DRIVE PROVIDED BY ELEVATOR CONTRACTOR PDB=POWER DISTRIBUTION BLOCK PROVIDED BY ELEVATOR CONTRACTOR M=MOTOR PROVIDED BY ELEVATOR CONTRACTOR NOT TO SCALE TYPICAL MRL ELEVATOR EQUIPMENT TOP OF HOISTWAY SAFETY COMPONENTS TAS JH1 VFD TSUFUSE BOX TA JH JHL LDU SEE NOTE 2 2" SEE NOTE 1 SEE NOTE 4 2" 1" 1. 2. 1/2" SEE NOTE 3 COPPER GROUND BAR. 1/4" x 4" x 1". HOLE CENTERS MATCH NEMA DOUBLE LUG CONFIGURATION. INSULATORS. 3. 4. LOCKWASHERS. WALL MOUNTING BRACKET. NOT TO SCALE GROUND BAR DETAIL (TYP) 2001A TO 3000A GROUNDING ELECTRODE CONDUCTORS (TO WATER SERVICE, SUPPLEMENTAL ELECTRODE, BLDG. STEEL AND SERVICE SWITCH) SHALL BE SIZED AS FOLLOWS: GROUND BUS SHALL BE 1/4"x 4"x 2'-6"(MIN.), DRILLED FOR TWO-HOLE HYDRAULIC COMPRESSION LUGS. TERMINATION OF GROUNDING ELECTRODE CONDUCTORS SHALL BE WITH TWO-HOLE COMPRESSION LUGS OR EXOTHERMIC WELD. PROVIDE TWO COPPER ALLOY MECHANICAL LUGS FOR FIRE ALARM GROUNDS, EQUAL TO FCI BURNDY TYPE "KA4C", SECURED TO BUS WITH 1/4" -20 SILICON BRONZE BOLTS. MAIN SERVICE SWITCH BUS LINK FOR BONDING FIRE PROTECTION. SEE FIRE PROTECTION SERVICE GROUNDING DETAIL. SEE NOTE No. 1 SEE GROUNDING ELECTRODE SIZING TABLE FOR CONDUIT AND CONDUCTOR SIZE. (TYPICAL FOR EACH SERVICE SWITCH). GH-100B GH-50B GH-75B GH-125-B CONDUIT GROUNDING FITTINGS SHALL BE O-Z/GEDNEY TYPE GH-B AS FOLLOWS: GROUND RODS SHALL BE SPACED A MINIMUM OF 10'-0" APART, AND SHALL BE BURIED A MINIMUM OF 2'-6" BELOW FINISH GRADE. ALL CONDUCTOR TO GROUND ROD AND CONDUCTOR TO CONDUCTOR CONNECTIONS SHALL BE EXOTHERMIC WELD TYPE. MANY BUILDINGS HAVE MORE THAN ONE DOMESTIC WATER OR FIRE PROTECTION SERVICE. A GROUND CONDUCTOR, IN CONDUIT, SHALL BE INSTALLED FROM THE MAIN BLDG GROUND BUS TO EACH DOMESTIC WATER AND FIRE PROTECTION SERVICE. SEE DOMESTIC WATER OR FIRE PROTECTION SERVICE GROUNDING DETAILS. FITTING 3. 2. NOTES: 1. UP TO 800AGND AWG/KCMILCONDUIT 4/0 TO 500KCMIL1-1/4" 1" 3/4" 1/2"8 TO 2 4 TO 2/0 1 TO 250KCMIL GENERATORS ABOVE 3000A 801A TO 2000A CONDUIT GROUNDING FITTING. SEE NOTE No. 3 MDP GROUND BUS 5. 4. SERVICE SIZE 3/4" x 10' COPPER-CLAD STEEL OR STAINLESS STEEL GROUNDING ROD (TYP. OF 3.) SEE NOTE No. 2 DOMESTIC WATER SERVICE. SEE WATER SERVICE GROUNDING DETAIL. SEE NOTE NO. 1 1#2-3/4"C EXOTHERMIC WELD MAIN TELECOMMUNICATION GROUND BUS AT TELEPHONE SERVICE ENTRANCE BUILDING COLUMN G N 3/0 PER NFPA 70, TABLE 250.66 500KCMIL 350KCMIL 250KCMIL GROUND ELECTRODE CONDUCTOR SUPPLEMENTAL GROUNDING ELECTRODE NOT TO SCALE ELECTRIC SERVICE GROUNDING SCHEMATIC NOTE: PROVIDE AUX CONTACTS W/ 2#14 TO ELEVATOR EQUIPMENT FOR ALL ELEVATOR DISCONNECT SWITCHES. ELECTRICAL: DETAILS E6.01 AJS VERSIONS NO.DATE DESCRIPTION ARCHITECT: 864 Mapleton Road Princeton, NJ 08540 609.919.0099 fax 609.919.0088 a r c h i t e c t s ikon.5 www.ikon5architects.com CIVIL ENGINEER: FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL ENGINEER: STRUCTURAL ENGINEER: LANDSCAPE ARCHITECT: PROJECT TITLE: PROFESSIONAL LICENSE NUMBER DRAWING NO.: DRAWN BY: DATE: SHEET TITLE: Jun 14, 2018 - 2:04pm 01.17.2018 238 LINDEN AVENUE ITHACA, NY 1 01.17.2018 CONSTRUCTION DOCUMENTS 2 02.21.2018 ADDENDUM 1 3 02.22.2018 ADDENDUM 2 4 03.02.2018 ADDENDUM 4