HomeMy WebLinkAboutVOLUME 2LIGHT
CLASSIFICATION OF HAZARD OCCUPANCIES
APARTMENTS, CORRIDORS
ROOMS
1,500 SQ. FT.
AREA
0.1 GPM/SQ. FT.
DENSITYHYDRAULIC
225 SQ. FT.
COVERAGE
MAXIMUM
PER SPRINKLER
SPRINKLER SCHEDULE
TYPESYMBOL
FINISHED CEILINGS
LOCATION MANUFACTURER
TYCO
MODEL/ID No.
(SIMILAR TO
1.CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB CONDITIONS AND SHALL REPORT TO
ENGINEER ANY DISCREPANCIES OR OMISSIONS THAT WOULD INTERFERE WITH SATISFACTORY
COMPLETION OF THE WORK.
2.THE CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING A FULL SET OF BID DOCUMENTS
AND VISIT THE SITE TO MAKE HIMSELF AWARE OF THE TOTAL JOB BEFORE SUBMITTING HIS
PRICE, FAILURE TO COMPLY SHALL NOT HOLD THE OWNER RESPONSIBLE FOR ANY
ADDITIONAL COST. CONTRACTOR SHALL BE RESPONSIBLE FOR ARRANGING WITH FACILITY'S
BUILDING MANAGEMENT FOR HANDLING MATERIALS, AS WELL AS FOR ALLOWABLE WORKING
HOURS AND DELIVERIES.
3.CONTRACTOR SHALL SUBMIT ALL SHOP DRAWINGS AND MANUFACTURERS' CUTS AND
SAMPLES TO ARCHITECT PRIOR TO COMMENCEMENT OF SUCH WORK.
4.THE CONTRACTOR SHALL INDICATE ON HIS SHOP DRAWING THAT ALL PIPING LAYOUTS ARE
COORDINATED WITH THE MEP AND STRUCTURAL CONDITIONS. INCLUDE ON EACH WORKING
DRAWING LAYOUT CERTIFICATE, THAT ALL RELATED CONDITIONS HAVE BEEN CHECKED, AND
THAT NO CONFLICT EXISTS. SUBMISSION WILL NOT BE APPROVED WITHOUT SUCH
CERTIFICATION.
5.CONTRACTOR SHALL SUBMIT SPRINKLER HYDRAULIC CALCULATIONS FOR THE ENGINEER'S
REVIEW TO VERIFY THE ADEQUACY OF THE INDICATED PIPE SIZES. SHOP DRAWINGS MUST
INDICATE ALL HYDRAULIC CALCULATION NODE AND PIPE TAGS.
A.SPRINKLER PIPING SHALL BE INSTALLED AS PER APPROVED SHOP DRAWINGS.
B.CONTRACTOR SHALL BASE ALL HYDRAULIC CALCULATIONS ON THE AVAILABLE
PRESSURE.
6.DRAWINGS ARE NOT TO BE SCALED.
7.CONTRACTOR SHALL EXERCISE EXTREME CARE IN PROTECTING AREAS ADJACENT TO
CONSTRUCTION AREAS SHALL FULLY PROTECT THEM FROM ANY DAMAGE RESULTING FROM
CONTRACTOR'S WORKMEN, SUBCONTRACTORS OR AGENTS, AND SHALL BE RESPONSIBLE
FOR REPAIRING, CLEANING OR REPLACING ANY SUCH DAMAGE.
8.ALL DIMENSIONS GIVEN ARE FINISH DIMENSIONS UNLESS OTHERWISE STATED.
9.UNLESS SPECIFICALLY STATED OTHERWISE, CONTRACTOR SHALL FURNISH ALL LABOR,
MATERIALS, APPURTENANCES, EQUIPMENT AND SERVICES TO COMPLETE ALL WORK AS
INDICATED ON DRAWINGS AND/OR SPECIFIED ON NOTES.
10.UNLESS SPECIFICALLY STATED OTHERWISE, CONTRACTOR SHALL FOLLOW MANUFACTURER'S
DIRECTIONS, INSTRUCTIONS AND RECOMMENDATIONS FOR ALL MATERIALS AND PROCESSES
USED IN THIS CONTRACT.
11.PROVIDE SPRINKLERS UNDER DUCTS OVER 4'-0" IN WIDTH IN AREAS WITHOUT HUNG CEILING.
12.CONTRACTOR SHALL PROVIDE AND CONDUCT A FLOW TEST OF THE BUILDING'S WATER
SERVICE AT THE STREET SERVICE. FLOW TEST RESULTS SHALL BE INCLUDED IN THE
HYDRAULIC CALCULATIONS.
13.635,1./(56,10(&+$1,&$/52206+$//+$9($7(03(5$785(5$7,1*2))
LOCATIONS, NECESSARY FOR INSPECTION AND MAINTENANCE.
14.ALL UPRIGHT SPRINKLERS SHALL HAVE WIRE GUARDS.
15.LOCATE ALL HORIZONTAL PIPING ABOVE SUSPENDED CEILING, UNLESS THERE IS NO CEILING.
16.ACCESS DOORS ARE TO BE PROVIDED ADJACENT TO ALL VALVES.
17.CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL PENETRATIONS, CUTTING, PATCHING,
SLEEVES, AND FIRESTOPPING REQUIRED TO COMPLETE THE INSTALLATION OF ALL WORK
INCLUDED UNDER THEIR CONTRACT IN ACCORDANCE WITH THE FIRE EGRESS AND SECURITY
PLAN DRAWINGS AND IN ACCORDANCE WITH DIVISION 16.
18.UPON COMPLETION OF THE WORK, CONTRACTOR SHALL COMPLETELY CLEAN THE
CONSTRUCTION AREA SUITABLE FOR THE OWNER'S USE, INCLUDING REMOVAL OF ALL LABELS
(AFTER ARCHITECT'S INSPECTION), CLEANING OF ALL THE EQUIPMENT, CONSTRUCTION WORK,
WINDOWS AND OTHER WORK, NEW AND OLD, IN THAT CONSTRUCTION AREA.
19.BUILDING DEPARTMENT APPROVED PLANS SHALL BE TURNED OVER TO OWNER AT THE
COMPLETION OF THE JOB.
20.AT THE FINAL COMPLETION OF THE JOB, CONTRACTOR SHALL SUBMIT TO THE FACILITY AND
TO ENGINEER A NOTARIZED AFFIDAVIT STATING COMPLIANCE WITH ALL PROVISIONS OF THIS
CONTRACT, INCLUDING ALL NOTES, EXCEPT FOR THOSE CHANGES SPECIFICALLY APPROVED
IN WRITING BY THE ARCHITECT.
21.CONTRACTOR SHALL GUARANTEE ALL WORK PERFORMED UNDER THIS CONTRACT FOR ONE
YEAR, STARTING FROM DATE OF FINAL ACCEPTANCE OF ALL WORK.
22.THE MINIMUM SPRINKLER BRANCH PIPE SIZE SHALL BE 1".
SPRINKLER NOTES
1.AUTOMATIC SPRINKLER SYSTEM SHALL COMPLY WITH SEC. 903 IBC
BUILDING CODE & NFPA 13-2013.
2.AUTOMATIC SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH SEC. 903.3.1 THROUGH 903.3.7 OF IBC BUILDING CODE.
3.SPRINKLERS SHALL NOT BE OMITTED FROM ANY ROOM MERELY BECAUSE
IT IS DAMP, OF FIRE-RESISTANCE-RATED CONSTRUCTION OR CONTAINS
ELECTRICAL EQUIPMENT AS PER SEC. 903.3.1.1.1 OF THE IBC BUILDING
CODE.
4.WHERE AUTOMATIC SPRINKLER SYSTEMS ARE REQUIRED BY IBC BUILDING
CODE, QUICK-RESPONSE SPRINKLERS SHALL BE INSTALLED IN THE AREAS
LISTED SEC. 903.3.2 OF IBC BUILDING CODE.
5.AUTOMATIC SPRINKLERS SHALL BE INSTALLED WITH DUE REGARD TO
OBSTRUCTIONS THAT WILL DELAY ACTIVATION OR OBSTRUCT THE WATER
DISTRIBUTION PATTERN. AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN
OR UNDER COVERED KIOSKS, DISPLAYS, BOOTH, CONCESSION STANDS,
OR EQUIPMENT THAT EXCEEDS 4 FEET IN WIDTH. NOT LESS THAN 3 FOOT
CLEARANCE SHALL BE MAINTAINED BETWEEN AUTOMATIC SPRINKLERS
AND TOP OF PILES OF COMBUSTIBLE FIBERS SEC. 903.3.3. OF IBC BUILDING
CODE.
6.WATER SUPPLIES FOR AUTOMATIC SPRINKLER SYSTEM SHALL COMPLY
WITH SEC. 903.3.5 OF IBC BUILDING CODE AND SEC. 903.3.1 THE POTABLE
WATER SUPPLY SHALL BE PROTECTED AGAINST BACK FLOW IN
ACCORDANCE WITH THE REQUIREMENTS OF SEC. 903.3.5 THE IBC
PLUMBING CODE.
7.FIRE HOSE THREADS USED IN CONNECTION WITH AUTOMATIC SPRINKLER
SYSTEMS SHALL BE APPROVED AND COMPATIBLE WITH FIRE DEPARTMENT
HOSE THREADS AS PER SEC 903.3.6 OF THE IBC PLUMBING CODE.
8.ALL VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC
SPRINKLER SYSTEM AND WATER-FLOW SWITCHES ON ALL SPRINKLER
SYSTEM SHALL BE ELECTRICALLY SUPERVISED BY THE FIRE ALARM
SYSTEM AS PER SEC. 903.4 OF THE IBC BUILDING CODE.
9.THE DOCUMENTS OR PORTIONS THERE OF LISTED IN CHAPTER 2 OF NFPA
13-2013 ARE REFERENCED WITHIN NFPA-13 AND SHALL BE CONSIDERED
PART OF THE REQUIREMENTS OF THIS DOCUMENT.
10.OCCUPANCY CLASSIFICATION SHALL COMPLY WITH CHAPTER 5 OF NFPA
13-2013.
11.PROTECTION REQUIREMENTS FOR MIXED COMMODITIES SHALL BE
ACCORDANCE WITH SEC. 5.6.1.2 OF NFPA 13-2013.
12.REQUIREMENTS FOR CORRECT USE OF SPRINKLER SYSTEM COMPONENTS
SHALL COMPLY WITH CHAPTER 6 OF NFPA 13-2013.
13. THE K-FACTOR, RELATIVE DISCHARGE, AND MARKING IDENTIFICATION
FOR SPRINKLERS HAVING DIFFERENT ORIFICE SIZES SHALL BE IN
ACCORDANCE WITH TABLE 6.2.3.1 OF NFPA 13-2013.
14. AUTOMATIC SPRINKLERS SHALL HAVE THEIR FRAME ARMS,
DEFLECTOR,COATING MATERIAL, OR LIQUID BULB COLORED IN
ACCORDANCE WITH THE REQUIREMENTS OF TABLE 6.2.5.1 OF NFPA
13-2013.
15. THE MAXIMUM FLOOR AREA OR ANY ONE FLOOR TO BE PROTECTED BY
A SINGLE RISER FROM A CONTROL VALVE AND ALARM DEVICE SHALL
COMPLY WITH SEC. 8.2.1 OF NFPA 13-2013.
16. WHERE CIRCUMSTANCES REQUIRE THE USE OF OTHER THAN
ORDINARY TEMPERATURE-RATED SPRINKLERS, STANDARD RESPONSE
SPRINKLERS SHALL BE PERMITTED TO BE USED SEC. 8.3.3. OF NFPA
13-2013.
17. SPRINKLERS SHALL BE LOCATED, SPACED AND POSITIONED IN
ACCORDANCE WITH THE REQUIREMENTS OF SECTION 8.5 OF NFPA
13-2013.
18. PROTECTION AREAS AND MAXIMUM SPACING FOR EACH HAZARD
SHALL COMPLY WITH TABLE 8.6.2.2.1 (a) (b) (c) (d) OF NFPA 13-2013.
19. TYPES OF HANGERS SHALL BE ACCORDANCE WITH THE REQUIREMENT
OF SEC. 9.1. OF NFPA 13-2013.
20. MAXIMUM DISTANCE BETWEEN HANGERS SHALL COMPLY WITH TABLE
9.2.2.1 OF NFPA 13-2013.
27. HOSE STREAM DEMAND AND WATER SUPPLY DURATION
REQUIREMENT SHALL COMPLY WITH TABLE 11.2.3.1.2 OF NFPA 13-2013.
21. THE WATER SUPPLY FOR SPRINKLERS SHALL BE DETERMINED BY
DENSITY/AREA CURVE, FIGURE 11.2.3.1.1 OF NFPA 13-2013.
22. HYDRAULIC DESIGN AREA REDUCTION FOR QUICK RESPONSE
SPRINKLERS SHALL COMPLY WITH FIGURE 11.2.3.2.3.1 OF NFPA 13-2013.
23. MINIMUM OPERATING PRESSURE OF ANY SPRINKLER SHALL BE 7 PSI.
SEC. 23.4.4.10.1 OF NFPA 13-2013.
24. A SPRINKLER SYSTEM ACCORDANCE WITH THIS STANDARD SHALL BE
PROPERLY INSPECTED, TESTED AND ACCORDANCE WITH NFPA 25 AND
IBC FIRE CODE.
25. SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
AT 200 PSI AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR
2 HOURS, PER NFPA 13-2013 SEC. 25.2.1.1.
FS
D SPRINKLER DRAIN PIPING
WATERFLOW SWITCH
CHECK VALVE (CV)
SPR
FLUSHING CONNECTION
SPRINKLER MAIN PIPING
CONCEALED PENDENT SPRINKLER
HIGH
VALVED CAPPED OUTLET (MANUALLY
BOTTOM CONNECTION
TOP CONNECTION
DROP OR RISE
PIPE DROP UNLESS OTHERWISE NOTED
PIPE-UP UNLESS OTHERWISE NOTED
FIRE DEPARTMENT CONNECTION (STORZ TYPE)
WATER-PROOF PIPE SLEEVE
BALL VALVE (BV)
O.S.&Y. VALVE WITH TAMPER SWITCH
PIPE SLEEVE
ASSEMBLY
LOW
FIRE PROTECTION SYMBOLS
DIRECTION ARROW
PRESSURE GAUGE (PG)
SPRINKLER FLOOR CONTROL VALVE
TS TAMPER SWITCH
OPENED VALVE UNLESS OTHER WISE NOTED
ALARM CHECK VALVE - ELEVATION
FSP FIRE STANDPIPE SUPPLY PIPING
NEW SPRINKLER BRANCH PIPING
GRINNELL #F950)
#TYP OR #TYL
CENTER LINE
CEILING
DOWN
DRAWING
DRAIN
ABD
CLG.
BFP
DN
DWG
DR
ELEVATION
FOOT, FEET
EL
FT
AUTOMATIC BALL DRIP
BACKFLOW PREVENTER
INVERT
ORDINARY HAZARD
INV
OH
SQUARE FOOT, FEET
SPECIFICATIONS
PRESSURE GAUGE
STANDARD
SPRINKLER
PG
S.F.
SPEC
SPRK
STD
TYPICALTYP
AFF ABOVE FINISHED FLOOR
FCA FLOOR CONTROL ASSEMBLY
FLOW SWITCHFS
TAMPER SWITCHTS
SP SPRINKLER PIPING
FD FLOOR DRAIN
FDV FIRE DEPARTMENT VALVE
LH LIGHT HAZARD
NOT TO SCALENTS
ABBREVIATIONS
NOTE:
SYMBOLS LIST IS PROVIDED FOR REFERENCE ONLY. NOT ALL SYMBOLS
OR ABBREVIATIONS ARE NECESSARILY USED IN THIS PROJECT.
UPRIGHT EXPOSED CEILINGS TYCO OR APPROVED
EQUAL
#TYP OR #TYL
ORDINARY GROUP 1 MISC. STORAGE ROOMS & MECHANICAL ROOM2,500 SQ. FT.0.15 GPM/SQ. FT.130 SQ. FT.
HAZARD
CLASSIFICATION
SEMI-RECESSED
PENDENT
F FIRE SERVICE
TYCO
TYCO
FINISHED CEILINGS
FINISHED CEILINGS
SIDEWALL
CONCEALED
PENDENT
2015 I.B.C. BUILDING DEPARTMENT
SPRINKLER NOTES
1.THE COMPLETE STANDPIPE SYSTEM COMPLY WITH THE FULL
REQUIREMENTS INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE
CODE, AND NFPA 14-2013.
2.STANDPIPE SYSTEM COMPONENTS AND HARDWARE SHALL BE IN
ACCORDANCE WITH CHAPTER 4 OF NFPA 14-2013.
3.THE LOCATION OF FIRE DEPARTMENT HOSE CONNECTIONS SHALL BE
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
4.STANDPIPE SYSTEMS SHALL BE INSTALLED WHERE REQUIRED BY THE
INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE AND NFPA 14 -
2013.
5.STANDPIPE SYSTEMS ARE PERMITTED TO BE COMBINED WITH AUTOMATIC
SPRINKLER SYSTEMS PER NFPA 13 AND NFPA 14.
6.THE LOCATION OF CLASS I STANDPIPE HOSE CONNECTION SHALL COMPLY
WITH INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE AND NFPA
14 - 2013.
7.WHERE THE MOST REMOTE PORTION OF A FLOOR OR STORY IS MORE THAN
200 FEET FROM A HOSE CONNECTION, ADDITIONAL HOSE CONNECTIONS
SHALL BE PROVIDED IN APPROVED LOCATIONS BY THE AHJ.
8.CLASS I STANDPIPE HOSE CONNECTIONS SHALL BE PROVIDED IN ALL
LOCATIONS PER INTERNATIONAL BUILDING CODE.
9.WHERE THE ROOF HAS A SLOPE OF LESS THAN 4" VERTICAL AND 12"
HORIZONTAL, EACH STANDPIPE SHALL BE PROVIDED WITH A HOSE
CONNECTION LOCATED EITHER ON THE ROOF OR AT THE HIGHEST LANDING
OF STAIRWAYS WITH STAIR ACCESS TO THE ROOF. AN ADDITIONAL HOSE
CONNECTION SHALL BE PROVIDED AT THE TOP OF THE MOST
HYDRAULICALLY REMOTE STANDPIPE FOR TESTING PURPOSE AS PER NFPA
14 2013.
10.PROTECTION OF RISERS AND LATERALS OF CLASS I STANDPIPE SYSTEM
SHALL COMPLY WITH THE INTERNATIONAL BUILDING CODE AND NFPA14 2013.
11.IN FULLY SPRINKLERED BUILDINGS HAVING A COMBINED STANDPIPE SYSTEM
THAT IS HYDRAULICALLY CALCULATED, THE MINIMUM STANDPIPE SIZE IN
BUILDINGS WITH FLOOR HEIGHTS LESS THAN 150 FT. ABOVE THE LOWEST
LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS SHALL BE 4 IN. PER NFPA 14
7.6.3 - 2013.
12.CABINETS CONTAINING FIRE-FIGHTING EQUIPMENT SUCH AS STANDPIPES,
FIRE HOSES, FIRE EXTINGUISHERS OR FIRE DEPARTMENT VALVES SHALL
NOT BE BLOCKED FROM USE OR OBSCURED FROM VIEW.
13.STANDPIPE SYSTEMS ARE REQUIRED DURING CONSTRUCTION, ALTERATION
AND DEMOLITION OPERATIONS SHALL BE PROVIDED IN ACCORDANCE WITH
IBC SECTION 3311.
14.FITTINGS SHALL BE EXTRA-HEAVY PATTERN WHERE PRESSURES EXCEED 175
PSI (12.1 BAR). SEC. 4.3.3 OF NFPA 14-2013.
15.PROTECTION OF STANDPIPE SYSTEM WHERE A STANDPIPE OR LATERAL PIPE
THAT IS NORMALLY FILLED WITH WATER PASSES THROUGH AN AREA
SUBJECT TO FREEZING TEMPERATURES IT SHALL BE PROTECTED TO
0$,17$,17+(7(03(5$785(2)7+(:$7(5,17+(3,3,1*%(7:((1)
$1')&$1'&6(&2)1)3$
16.FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN 18 IN.
NOR MORE THAN 48 IN. ABOVE THE LEVEL OF THE ADJOINING GROUND,
SIDEWALK OR GRADE SURFACE. SEC. 6.4.6 OF NFPA 14-2013.
17.THE MAXIMUM PRESSURE AT ANY POINT IN THE SYSTEM AT ANY TIME SHALL
NOT EXCEED 350 PSI (24.1 BAR). SEC. 7.2 OF NFPA 14-2013.
18.BRANCH LINE SHALL BE SIZED BASED ON THE HYDRAULIC CRITERIA
ESTABLISHED IN SEC. 7.8 & 7.10 BUT NOT LESS THAN 2-1/2" (65 mm) SEC. 7.6.4
OF NFPA 14-2013.
19.HYDRAULICALLY DESIGNED STANDPIPE SYSTEMS SHALL BE DESIGNED TO
PROVIDE THE WATER FLOW RATE AT A MINIMUM RESIDUAL PRESSURE OF 100
PSI (6.9 BAR) AT THE OUTLET OF THE HYDRAULICALLY MOST REMOTE 2-1/2"
(65 mm) HOSE CONNECTION & 65 PSI (4.5 BAR) AT THE OUTLET OF THE
HYDRAULICALLY MOST REMOTE 1-1/2" (38 mm) HOSE CONNECTION. SEC. 7.8.1
OF NFPA 14-2013.
20.HOSE CONNECTIONS AND HOSE STATIONS SHALL BE UNOBSTRUCTED AND
SHALL BE LOCATED NOT LESS THAN 3 FT. (0.9 M) OR MORE THAN 5 FT. (1.5 m)
ABOVE THE FLOOR. SEC. 7.3.1.1 OF NFPA 14-2013.
21.AT THE TOP OF THE HIGHEST RISER THERE SHALL BE PROVIDED ABOVE THE
MAIN ROOF LEVEL A MANIFOLD CAPABLE OF FLOWING THE FULL FLOW OF
THE RISER BEING TESTED.
22.FOR CLASS I AND CLASS III SYSTEMS THE MINIMUM FLOW RATE FOR THE
HYDRAULICALLY MOST REMOTE STANDPIPE SHALL BE 500 GPM (1893 L/MIN)
SEC. 7.10.1.1.1 OF NFPA 14-2013.
23.THE MINIMUM FLOW RATE FOR ADDITIONAL STANDPIPES SHALL BE 250 GPM
PER STANDPIPE WITH THE TOTAL NOT TO EXCEED 1250 GPM OR 1000 GPM
FOR BUILDINGS SPRINKLERED THROUGHOUT. SEC. 7.10.1.1.3 OF NFPA
14-2007.
24.CLASS I AND CLASS III STANDPIPES SHALL BE AT LEAST 4" IN SIZE.
STANDPIPES THAT ARE PART OF A COMBINED SYSTEM SHALL BE 6" IN SIZE.
WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN APPROVED
SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13 OR NFPA 13R, THE
MINIMUM STANDPIPE SIZE SHALL BE 4" FOR SYSTEMS HYDRAULICALLY
DESIGNED IN ACCORDANCE WITH SECTION 7.8.1 NFPA 14 - 2013.
25.VALVES CONTROLLING WATER SUPPLIES SHALL BE SUPERVISED IN THE
OPEN POSITION SO THAT A CHANGE IN THE NORMAL POSITION OF THE VALVE
WILL GENERATE A SUPERVISORY SIGNAL AT THE SUPERVISING STATION.
WHERE A FIRE ALARM SYSTEM IS PROVIDED, A SIGNAL SHALL ALSO BE
TRANSMITTED TO THE CONTROL UNIT.
26.STANDPIPES SHALL BE TESTED IN ACCORDANCE WITH NFPA 25, STANDARD
FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED FIRE
PROTECTION SYSTEMS.
2015 INTERNATIONAL BUILDING
CODE STANDPIPE NOTES
RESIDENTIAL
UPRIGHT SPRINKLER W/ WIRE GUARD
SIDEWALL SPRINKLER
RESIDENTIAL
DRY CONCEALED PENDENT SPRINKLER D
FP. FIRE PROTECTION DRAWING LIST
FP0.GENERAL
P0.01 GENERAL NOTES & SYMBOL LIST
FP2.BUILDING PLANS
P2.00 FLOOR PLANS
FP4.DIAGRAMS
FP4.01 RISER DIAGRAM
FP5.DETAILS
FP5.01 DETAILS
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
FIRE PROTECTION:
GENERAL NOTES
& SYMBOL LIST
FP0.01
AH
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9GWB
8'-8"
GWB
7'-6"
S
GWB
8'-0"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
8'-8"
GWB
7'-5"
GWB
7'-5"
APC-2
7'-6"
APC-1
7'-6"
GWB
7'-5"
GWB
8'-8"
S
GWB
7'-6"
GWB
SLOPED
GWB
SLOPED
GWB
8'-11 1/2"
GWB
SLOPED
GWB
SLOPED
GWB
8'-10 1/2"
S
GWB
7'-6"
S
GWB
7'-6"
S
GWB
7'-6"SGWB
7'-6"
EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1"
1"
1"
1"
1 1/2"
1"1"
3"
2 1/2"
11/2"11/4"
1"
1 1/4"
1"
1"
1 1/4"
1 1/4"
2 1/2"
11/2"11/4"
1"
11/2"11/4"
1"
2"1"1 1/2"1 1/4"
3"SPRSPRSPR
3"
3"
3"
WALL MOUNTED STORZ
FD CONNECTION
4"FSP UP&DN
2" DRAIN UP&DN
212"DROP TO FDV
4"FSP UP&DN
2" DRAIN UP&DN
212"DROP TO FDV
4"DN
FCVA
ELECTRIC ALARM BELLREF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL
S
GWB
8'-11"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-11"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-11"
GWB
8'-0"
GWB
7'-6"
F1
S
GWB
8'-11"
GWB
8'-0"
GWB
8'-11"
GWB
7'-5"
GWB
8'-0"
APC-1
7'-6"
GWB
8'-0"
GWB
7'-5"
GWB
8'-11"
GWB
SLOPED
GWB
9'-2 1/2"
GWB
9'-1 1/2"GWB
SLOPED
S
GWB
7'-6"
GWB
7'-6"
S
S
GWB
7'-6"
S
GWB
7'-6"
S
GWB
7'-6"
1"
1"
1"
1 1/2"
1"
114"
3"
3"
1"11/2"
3"
11/4"
1"
11/2"11/4"
1"
11/2"11/4"
1"
1 1/4"
1"1"
1"
1"
3"
1"
1"
1"
1 1/4"1 1/2"
3"SPRSPRFSPFSPFSP
4"FSP UP & DROP
212"TO FDV
2" DRAIN DROP & UP
4"FSP UP & DROP
2" DRAIN DROP & UP
212"TO FDV
4"
4"
4"
4"
6" FIRE
SERVICE
6" BACKFLOW
PREVENTER
W/BY-PASS METER
4" ALARM CHECK
VALVE W/ TRIM
3"
FSP
SPR
5'-0"
4" UP TO WALL
MOUNTED STORZ FD
CONNECTION
FCVA
RCV W/TS
RCV W/TS
4"
TYPICAL PIPE SLEEVE
W/LINK SEAL
DROP IN
ELEV. PIT
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9GWB
8'-8"
GWB
7'-6"
GWB
7'-6"
S S
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
8'-8"
GWB
7'-5"
APC-2
7'-6"
APC-1
7'-6"
GWB
7'-5"
GWB
8'-8"
GWB
7'-6"
GWB
8'-0"
S
GWB
7'-6"
GWB
SLOPED
GWB
SLOPED
GWB
8'-11 1/2"
GWB
SLOPED
GWB
SLOPED
GWB
8'-10 1/2"
S
GWB
7'-6"
S
GWB
7'-6"
S
GWB
7'-6"SEFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
1"
1"
1 1/4"
1"
1"1 1/4"
2 1/2"
11/2"11/4"
1"
1"
1"
1 1/2"
1 1/2"
3"
11/2"11/4"
1"
11/2"11/4"
1"
2"1"2"1 1/4"1 1/2"2"
1"
3"
3"
SPR
4"FSP UP&DN (3RD FL)
4"FSP DN (4TH FL)
212"TO FDV
2" DRAIN UP&DN (3RD FL)
2"DRAIN DN (4TH FL)
2"4"SPRSPRFSP
PIPE OFFSET @
4TH FLOOR
CEILING ONLY
4"FSP UP TO
ROOF MANIFOLD
4"FSP UP&DN (3RD FL)
4"FSP DN (4TH FL)
212"TO FDV
2" DRAIN UP&DN (3RD FL)
2"DRAIN DN (4TH FL)
3"
PIPE OFFSET @
4TH FLOOR
CEILING ONLYFCVA
4"FSP UP TO
ROOF MANIFOLD
FSP
2"4"
3"REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9GWB
8'-8"
GWB
7'-6"
S S
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
7'-6"
S
GWB
8'-8"
GWB
8'-0"
GWB
8'-1 3/4"
GWB
7'-5"
APC-2
7'-6"
APC-1
7'-6"
GWB
7'-5"
GWB
8'-8"
GWB
7'-6"
GWB
8'-0"SS
GWB
7'-6"
GWB
7'-6"
GWB
SLOPED
GWB
SLOPED
GWB
8'-11 1/2"
GWB
SLOPED
GWB
SLOPED
GWB
8'-10 1/2"
S
GWB
7'-6"
S
GWB
7'-6"
S
GWB
7'-6"SEFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
1"
1 1/4"
1"
1"1 1/4"
2 1/2"
3"
11/2"11/4"
1"
1 1/4"
1"
1"
1 1/2"
1 1/2"
3"
3"
11/2"11/4"
1"
11/2"11/4"
1"
2"1"1 1/4"1 1/2"
1"
SPR
SPRSPR4"FSP UP&DN
2" DRAIN UP&DN
212"DROP TO FDV
4"FSP UP&DN
2" DRAIN UP&DN
212"DROP TO FDV
FCVA
3"
1 1/2"
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
FIRE PROTECTION:
FLOOR PLANS
AH
0 4 8 16 FEET
SCALE: 1/8"=1'-0"1 LOWER LEVEL PLAN
0 4 8 16 FEET
SCALE: 1/8"=1'-0"3 SECOND FLOOR PLAN
0 4 8 16 FEET
SCALE: 1/8"=1'-0"2 GROUND FLOOR PLAN
0 4 8 16 FEET
SCALE: 1/8"=1'-0"4 THIRD / FOURTH FLOOR PLAN
0 4 8 16 FEET
SCALE: 1/8"=1'-0"5 ROOF PLAN
FIRE PROTECTION RISER DIAGRAM
NTS
6" DOUBLE CHECK
DETECTOR ASSEMBLY (W/
BY-PASS METER)
DCDV 6"
4"
CURB VALVE
6"HOUSE
VALVE
4"ALARM
CHECK VALVE
4"
4"FCA
2"
4"
4"
2"
4"4"FCA
4"
2"
4"4"FCA
GROUND FLOOR
LOWER LEVEL
SECOND FLOOR
4"
4"FCA
2"
4"
FD
STAIR B
THIRD FLOOR
4"
2-1/2"
4"
2-1/2"
4"
STAIR A
4"RISER
CONTROL VALVE
4"RISER CONTROL VALVE
34"ABD
CHECK VALVE
ROOF
5" FIRE DEPARTMENT
STORZ CONNECTION ON
FRONT OF BUILDING
212" FHV AT
4'-0" AFF
FOURTH FLOOR
4"
2-1/2"
4"
2"
4"4"FCA
212" FHV AT
4'-0" AFF
212" FHV AT
4'-0" AFF
212" FHV AT
4'-0" AFF
212" FHV AT
4'-0" AFF
212" FHV AT
4'-0" AFF
TO SPRINKLER
SYSTEM
TO SPRINKLER
SYSTEM
TO SPRINKLER
SYSTEM
TO SPRINKLER
SYSTEM
212" FHV AT
4'-0" AFF
212" FHV AT
4'-0" AFF
SPILL TO
AREAWAY
DRAINS
SPILL TO
AREAWAY
DRAINS
ROOF
MANIFOLD
(TYP)
6"6" INCOMING FIRE
SERVICE
ROOF
MANIFOLD
(TYP)
TO SPRINKLER
SYSTEM
NORTH STAIRSOUTH STAIR
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:14pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
FIRE PROTECTION:
RISER DIAGRAM
FP4.01
AH
NOT TO SCALE
NOT TO SCALE
PIPE PENETRATING THROUGH EXTERIOR WALL
BELOW GRADE
TERMINATE SLEEVE
FLUSH WITH FINISHED
WALL SURFACES
STANDARD WEIGHT STEEL PIPE
SLEEVE OF SIZE TO PASS PIPE
ANNULAR SPACE BETWEEN PIPE
AND SLEEVE TO BE PACKED WITH
UL/FM APPROVED MATERIAL AND
TESTED TO THE REQUIREMENTS OF
ASTM E814 (UL 1476) AND
ASTM 119 (UL 263)
MEA # 307-92-M
FINISHED ESCUTCHEON PLATE
FLUSH AGAINST WALL AND OF SIZE
TO COMPLETELY COVER OPENING
(TYP FOR EACH SIDE).
SEAL OR CAULK SLEEVES THRU
FIRE WALLS IN A SMOKE TIGHT
MANNER.
LINK SEAL TYPE
FOUNDATION PENETRATION SEAL
OS&Y VALVE
AND PIPING
ARE
INSTALLED
IN HEATED
AREA
DOUBLE
PIPE
CLAMP
PIPE
HANGERSLEEVE
COUPLING
EXTEND TO NEAREST
OPEN FIXTURE OR
DRAIN3/4" AUTOMATIC BALL DRIP
NOT TO SCALE
ROOF MANIFOLD DETAIL
DETAIL OF SEMI-RECESSED PENDENT SPRINKLER
NOT TO SCALE
CONCEALED SPRINKLER AT HUNG CEILING
NOT TO SCALE
1"x1/2" NPT
FEMALE REDUCER
DETAIL OF UPRIGHT SPRINKLER
NOT TO SCALE
(/%2::,7+7+5867%/2&.'(7$,/
NOT TO SCALE
6" AMES 3000SS DOUBLE
CHECK DETECTOR BACKFLOW
PREVENTER W/ BY-PASS
METER. PROVIDE W/ TEST KIT
ELECTRIC SPRINKLER ALARM
PRESSURE SWITCH (TYP.)
WIRE TO ALARM BELL & FIRE
ALARM SYSTEM
ALARM TEST LINE W/ VALVE
SLEEVE W/LINK SEAL (TYP.)
6" FIRE SERVICE FROM
STREET TO WITHIN 5'-0"
BY GENERAL CONTR.
O.S.& Y. GATE
VALVE W/ T.S.
(TYP)
SPILL OVER FLOOR
DRAIN
ELECTRIC SPRINKLER ALARM
BELL POTTER ELECTRIC
SIGNAL COMPANY MODEL #
PBD2410, 24 VDC PROVIDE W/
WEATHERPROOF BACKBOX
MODEL BBK-1
POTTER ROEMER MODEL #
5795-02 5" STORZ x 4" NPT W/
#5799-02 BLIND CAP & CHAIN.
PRESSURE GAUGE
BY-PASS LINE
SPRINKLER CONTRACTOR IS RESPONSIBLE FOR ALL LOW VOLTAGE WIRING
INSTALLATIONS FOR PRESSURE SWITCHES, TAMPER SWITCHES, FLOW
SWITCHES, ALARM BELLS.
NOTE:
DRIP CUP W/ 1-1/2" DRAIN
(TYPICAL)
SPRINKLER ALARM/CHECK
VALVE W/ TRIM
O.S.& Y. GATE VALVE W/
T.S. (TYP)
2" SYSTEM
DRAIN VALVE
(TYP.)
RETARD CHAMBER
(TYPICAL)
PIPE SUPPORT (TYP.)
FIN FLOOR
TO COMBINED
SPRINKLER / STANDPIPE
SYSTEM
DETAIL OF FIRELINE SERVICE AND ALARM VALVE ARRANGEMENT
NOT TO SCALE
WATER DATA
DATE:
HYDRANT LOCATION:
RESIDUAL:
FLOW:
FLOW @ 20 P.S.I.:
ROD HANGER
CHECK VALVE
BLDG. WALL
VALVE FLOOR STAND
WITH INDICATOR
INSULATIONPIPE SLEEVE
MANIFOLD UNIT
ROOF
FIRE STANDPIPE
DRAIN LINE
CONCEALED PIPING
1/2" CLEAR MAXIMUM
FINISHED WALL SURFACE.
PIPING EXPOSED TO VIEW
GRADE
WATER STOP & ANCHOR COLLAR
METAL ESCUTCHEON
BUILDING WALL
LONG RADIUS
(/%2:
FIRE
MAIN
CONCRETE
THRUST BLOCK
UNDISTURBED
EARTH
1" BRANCH LINE
UPRIGHT SPRINKLER
CROSS MAIN
STATIC:
1" SPRINKLER BRANCH PIPING
SPRINKLER
MAIN OR
LOOP
1" DROP
1" x 1/2" NPT FEMALE
REDUCER
SPRINKLER CUP ASSEMBLY
PENDENT SPRINKLER HEAD
CEILING LIGHT FIXTURE
12" MINIMUM
ELBOW (TYP.)
DROP NIPPLE
1"
1"x1/2" NPT FEMALE
REDUCER
SPRINKLER CUP ASSEMBLY
COVER PLATE ASSEMBLY
CEILING
1"
5'-0"2'-O" MIN.3'-O" MAX.BRANCH PIPING
2"
4"1 1/4"
2"2"
8/25/2015
LINDEN AVE @ DRYDEN RD
81 PSI
53 PSI
980 GPM
1,492 GPM
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:14pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
FIRE PROTECTION:
DETAILS
FP5.01
AH
GENERAL NOTES
NOTE:
ALL SYMBOLS NOT NECESSARILY SHOWN ON DRAWINGS.
1.DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF THE
WORK. REVIEW THE GENERAL NOTES, SPECIFICATIONS AND PLANS FOR ADDITIONAL
REQUIREMENTS THAT MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF
THE CONSTRUCTION DOCUMENTS. NOTIFY THE ARCHITECT OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
2.PROVIDE WORKMANSHIP OF HIGHEST GRADE: INSTALL ALL EQUIPMENT IN
CONFORMANCE WITH MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS OF
THE FACILITY.
3.PROVIDE ONE YEAR GUARANTEE AGAINST DEFECTIVE WORKMANSHIP AND
MATERIAL.
4.COORDINATE ALL WORK TO MINIMIZE INTERFERENCES WITH OTHER TRADES. REFER
TO ARCHITECTURAL DRAWINGS FOR ALL CEILING HEIGHTS.
5.NO "DEAD ENDS" SHALL BE LEFT ON ANY DRAINAGE PIPING UPON COMPLETION OF
WORK.
6.THIS CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING A FULL SET OF BID
DOCUMENTS AND VISIT THE SITE TO MAKE THEM SELF AWARE OF THE TOTAL JOB
BEFORE SUBMITTING THEIR PRICE. FAILURE TO COMPLY, SHALL NOT HOLD THE OWNER
RESPONSIBLE FOR ANY ADDITIONAL COST.
7.PROVIDE ACCESS PANEL FOR ALL VALVES AND CLEANOUTS ON RISE OR CONCEALED IN
WALL, ABOVE CEILING OR IN CHASE.
8.REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION AND MOUNTING HEIGHTS OF
PLUMBING FIXTURES.
9.DO NOT SCALE FLOOR PLANS FOR EXACT HORIZONTAL LOCATION OF PIPE ROUTING.
10.INSTALL CONCEALED PIPING TIGHT TO THE STRUCTURE AND AS HIGH AS POSSIBLE.
INSTALL EXPOSED PIPING TIGHT TO THE STRUCTURE, WALL OR CEILING AND AS HIGH
AS POSSIBLE. COORDINATE WITH OTHER TRADES TO AVOID CONFLICTS.
11.COORDINATE ALL WORK WITH OTHER TRADES AND CONTRACTORS.
12.COORDINATE PIPING INSTALLATION WITH STRUCTURAL GRADE BEAMS, FOOTINGS,
COLUMN PIERS, ETC. SLEEVE PIPING THROUGH GRADE BEAMS, FOOTING, ETC. WHERE
REQUIRED AND AS NOTED ON PLANS. COORDINATE SLEEVE INSTALLATIONS WITH THE
ARCHITECT, STRUCTURAL ENGINEER, STRUCTURAL CONTRACTOR AND GENERAL
CONTRACTOR BEFORE CONCRETE IS INSTALLED.
13.CLEAN FAUCET AERATORS AND PIPE STRAINERS PRIOR TO TURNING BUILDING OVER
TO THE OWNER.
14.PROVIDE TRAP PRIMERS WHERE REQUIRED BY LOCAL AUTHORITIES.
15.COORDINATE PIPE ROUTING TO BE AWAY FROM ELECTRICAL PANELS. DO NOT INSTALL
PIPING OVER ELECTRICAL PANELS.
16.PAINT ALL EXPOSED GAS AND WATER PIPING USING RUST INHIBITOR PAINT. PAINT AND
COLOR SHALL BE COORDINATED WITH THE ARCHITECT AND / OR OWNER.
17.COORDINATE ALL ROOF PENETRATIONS WITH OTHER TRADES. MAINTAIN 10' MINIMUM
CLEARANCE FROM ALL AIR INTAKES. MAINTAIN 2' CLEARANCE FROM ALL OTHER
EQUIPMENT.
18.INSULATE PIPING ROUTED IN EXTERIOR BUILDING WALLS WITH MINIMUM 2" BATT
INSULATION TO PREVENT FREEZING.
S
#
RPZ
DCDA
ST
#
COLD WATER PIPING (CW)
HOT WATER PIPING (HW)
HOT WATER RETURN PIPING (HWR)
DRAINAGE PIPING ABOVE GROUND
UNDERGROUND DRAINAGE/PIPING BELOW
FRESH AIR INLET PIPING
SANITARY (SAN)
STORM PIPING
VENT PIPING (V)
GREASE WASTE PIPING
GAS PIPING
PUMP DISCHARGE PIPING
DIRECTION OF FLOW
PIPE-UP UNLESS OTHERWISE NOTED
PIPE DROP UNLESS OTHERWISE NOTED
DROP OR RISE
TOP CONNECTION
BOTTOM CONNECTION
VALVED CAPPED OUTLET
POINT OF NEW CONNECTION
POINT OF DEMOLITION
SANITARY/WATER RISER DESIGNATION
STORM WATER LEADER DESIGNATION
AREA DRAIN, FLOOR DRAIN, ROOF DRAIN (AD, FD, RD)
FLOOR DRAIN W/ TRAP
CLEANOUT (CO)
CLEANOUT DECK PLATE (CODP)
TRAP
HOUSE TRAP
GATE VALVE (GV)
OPEN BALL VALVE (BV)
BALL VALVE (BV)
CHECK VALVE
CHECK VALVE
CHECK VALVE (CV)
O.S.&Y. VALVE
O.S.&Y. VALVE WITH TAMPER SWITCH
GAS PRESSURE REGULATING VALVE. VENT TO EXTERIOR.
GAS VALVE
BUTTERFLY VALVE
HOSE BIBB
SOLENOID VALVE
CIRCUIT SETTER FLOW CONTROL VALVE (FCV)
SHOCK ABSORBER
CONCENTRIC REDUCER
TEMPERATURE & PRESSURE RELIEF VALVE (TP)
THERMOMETER (T)
PRESSURE GAUGE (PG)
UNION
VENT INCREASER
VENT THROUGH ROOF (VTR)
WATER-PROOF PIPE SLEEVE
PIPE SLEEVE
STRAINER
FRESH AIR INLET
FAI
SAN
ST
GW
G
PD
HIGHLOW
S
AD AREA DRAIN
AP ACCESS PANEL
BFP BACKFLOW PREVENTER
CFH CUBIC FEET PER HOUR
CEILINGCLG.
CO CLEAN OUT
CLEAN OUT DECK PLATECODP
CP CIRCULATION PUMP
COLD WATERCW
DCW DOMESTIC COLD WATER
DN DOWN
DRAIN
DRAWING
EXISTING
DWG
DR
(E), EX
EJ EJECTOR PUMP
ELEVATIONEL
ET EXPANSION TANK
FAI FRESH AIR INTAKE
FLOOR DRAINFD
FSP FIRE STAND PIPE
FOOT, FEETFT
GASG
GPM
GWH
GALLONS PER MINUTE
GAS WATER HEATER
HOSE BIBBHB
HR HOUR
HEATERHTR
HW HOT WATER
HOT WATER RETURN
HOT WATER SUPPLY
HWR
HWS
INVERT ELEVATION
INVERT
INDIRECT WASTE
LAVATORY
LEADER
METER
MECHANICAL EQUIPMENT ROOMMER
M
LDR
LAV
IW
INV
IE
MR MOP RECEPTOR
MOUNTED
NOT TO SCALE
MTD
NTS
O/C ON CENTER
OVERFLOW ROOF DRAIN
PRESSURE GAUGE
PLUMBINGPLBG
PG
OD
RD ROOF DRAIN
RECIRCULATING PUMPRP
REDUCED PRESSURE ZONE BACKFLOW PREVENTERRPZ
SHOCK ABSORBERSA
SAN SANITARY
SUMP DISCHARGESD
SH, SHR
SPECS.
SQ.FT.
SS
ST
SHOWER
SPECIFICATIONS
SQUARE FOOT (FEET)
SERVICE SINK
STORM
STANDARD
STORM WATER
TRENCH DRAIN
TEMPERATURE
STD
SW
TD
TEMP
TMV THERMOSTATIC MIXING VALVE
TRAP PRIMER
TAMPER SWITCH
TYPICAL
UNDERWRITERS LABORATORY
TP
TS
TYP
UL
UR URINAL
VENTV
V.I.F.VERIFY IN FIELD
VENT THROUGH ROOF
WASTE
WATER CLOSET
WALL CLEANOUT
WATER-PROOF
WCO
WC
WP
W
VTR
REDUCED PRESSURE ZONE BACKFLOW PREVENTER (RPZ)
DOUBLE CHECK DETECTOR ASSEMBLY
CIRCULATOR PUMP
PLUMBING SYMBOLS ABBREVIATIONS
P. PLUMBING DRAWING LIST
P0.GENERAL
P0.01 GENERAL NOTES & SYMBOL LIST
P2.BUILDING PLANS - WATER & GAS
P2.00 LOWER LEVEL PLAN - WATER & GAS
P2.01 GROUND FLOOR PLAN - WATER & GAS
P2.02 SECOND FLOOR PLAN - WATER & GAS
P2.03 THIRD FLOOR PLAN - WATER & GAS
P2.04 FOURTH FLOOR PLAN - WATER & GAS
P3.BUILDING PLANS - DRAINAGE
P3.00A LOWER LEVEL PLAN - DRAINAGE
P3.00B LOWER LEVEL PLAN - ABOVE CEILING DRAINAGE
P3.01 GROUND FLOOR PLAN - DRAINAGE
P3.02 SECOND FLOOR PLAN - DRAINAGE
P3.03 THIRD FLOOR PLAN - DRAINAGE
P3.04 FOURTH FLOOR PLAN - DRAINAGE
P3.05 ROOF PLAN - DRAINAGE
P4.DIAGRAMS
P4.01 DOMESTIC WATER RISER DIAGRAMS
P4.02 SANITARY RISER DIAGRAMS
P4.03 STORM & GAS RISER DIAGRAMS
P5.SCHEDULES
P5.01 SCHEDULES
P6.DETAIL
P6.01 DETAILS SHEET 1 OF 2
P6.02 DETAILS SHEET 2 OF 2
CLEAN OUT TO GRADECOG
NOTE:
ALL SYMBOLS NOT NECESSARILY SHOWN ON DRAWINGS.
W
#
NON-FREEZE WALL HYDRANTNFWH
PUMP DISCHARGEPD
PRESSURE REDUCING VALVEPRV
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:11pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
GENERAL NOTES
& SYMBOL LIST
P0.01
AH
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL
2" CW UP
112" HW UP
2"
2" CW UP
112" HW UP
2" CW UP
112" HW UP
2"
2"
2"
2"
2"
212"
212"
2" CW UP
112" HW UP
2"
3"
3/4"HWR UP
ELEV 733.67
1"
114"
1"
3 4"
34"
1"
1"
34"
SK
LAV-1
WCSH-1
3"GAS UP
TO METER
RPZ1"CW FOR
MECH.
MAKE-UP
WATER
1"CW DROP TO 34" HB
& 1" MAKE-UP
WATER, 12" TO TP
W/DU 2"G12"CW DROP
TO TP W/DU
112" GAS DROP
TO BOILER
(300 CFH)
GAS REGULATOR
VENTS UP
5'-0"
INCOMING 4" DOMESTIC
WATER SERVICE
CONTINUATION BY
SITE CONTRACTOR
WATER METER & PRV
STATION (SEE DETAIL
ON DWG P6.01)
PROVIDE SLEEVES
W/LINK SEAL (TYPICAL
ALL FOUNDATION
PENETRATIONS)
INCOMING 6" FIRE SERVICE
34"CW DROP
TO NFWH
1"3 4"
1"
34"CW DROP
TO NFWH
2" CW UP
112" HW UP
1"
114"
1"
34"
34"
1"
1"
34"
SK
LAV-1
WCSH-1
MR
SEE ABOVE FOR
PIPING LAYOUT
SEE ABOVE FOR
PIPING LAYOUT
KEYED NOTES
1" H & 114" CW TO CONTROL VALVES ABOVE CEILING
WITH ACCESS PANEL (AP)
1" H & CW DROP
34" H & CW TO LAV / SK / SHR
34" CW TO WC
34" HWR TO FLOW CONTROL VALVE ASSEMBLY
ABOVE CEILING WITH ACCESS PANEL (AP). SEE
DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT
34" H&CW DROP TO MR
1
2
3
4
5
6
112"G112"G
112"G UP
112"G
3"G
2"G112"G112" GAS DROP
TO BOILER
(300 CFH)
GAS PRESSURE
REGULATOR
(SET @ 7" WC)TYP
ET-1
TMV-1RP-1
GWH
(199 CFH)
G
SEE DETAIL ON P6.01
FOR PIPING LAYOUT
GAS PRESSURE
REGULATOR
(SET @ 7" WC)TYP 3"G+:
GWH
(199 CFH)
112" GAS DROP
(199 CFH)
112"G
212"
2"
212"
2"34"
SIMILAR TO ABOVE
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:11pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
LOWER LEVEL
PLAN - WATER
& GAS
P2.00
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 LOWER LEVEL PLAN - WATER & GAS
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
2" CW UP & DN
112" HW UP & DN
2" CW UP & DN
112" HW UP & DN
2" CW UP & DN
112" HW UP & DN
2" CW DN
112" HW DN
2" CW UP
112" HW UP
2" CW UP
112" HW UP
2" CW DN
112" HW DN
WC
LAV-1
SH-1
1"
114"
1"
34"
112"
2"
SK
1"
1"
1"
114"
1"
34"
34"
1"
1"
34"
SK
LAV-1
WCSH-1
1"
114"
1"
3 4"
34"
1"
1"
34"
SK
LAV-1
WCSH-1
GAS DN
7"WC
SERVICE
PRESSURE
GAS METER AT GRADE
SET ON CONCRETE PAD.
COORDINATE W/ LOCAL
GAS COMPANY FOR
REQUIREMENTS
INCOMING GAS
SERVICE BY
GAS COMPANY
G
3" GAS DN
34"CW DROP
TO NFWH
3 4"
SEE ABOVE FOR
PIPING LAYOUT
SEE ABOVE FOR
PIPING LAYOUT
3/4"HWR UP & DN
112"G UP&DN
GAS REGULATOR
VENTS UP&DN
SIMILAR TO ABOVE
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:11pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
GROUND FLOOR
PLAN - WATER
& GAS
P2.01
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 GROUND FLOOR PLAN - WATER & GAS
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
112" CW UP - 2" CW DN
114" HW UP - 112" HW DN
112" CW UP - 2" CW DN
114" HW UP - 112" HW DN
112" CW UP - 2" CW DN
114" HW UP - 112" HW DN
112" CW UP - 2" CW DN
114" HW UP - 112" HW DN
112" CW UP - 2" CW DN
114" HW UP - 112" HW DN
1"
114"
34"1"34"1"
1"
WC LAV-2
SH-2
SK-1
34"
1"
114"
1"
3 4"
1"
1"
3 4"
SK
LAV-1
WC SH-1
1"
114"
1"
3 4"
34"
1"
1"
34"
SK
LAV-1
WCSH-1
KEYED NOTES
1" H & 114" CW TO CONTROL VALVES ABOVE CEILING
WITH ACCESS PANEL (AP)
1" H & CW DROP
34" H & CW TO LAV / SK / SHR
34" CW TO WC
34" HWR TO FLOW CONTROL VALVE ASSEMBLY
ABOVE CEILING WITH ACCESS PANEL (AP). SEE
DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT
34" H&CW DROP TO MR
1
2
3
4
5
6
SEE ABOVE FOR
PIPING LAYOUT
SEE ABOVE FOR
PIPING LAYOUT
3/4"HWR UP & DN
112"G UP&DN
GAS REGULATOR
VENTS UP&DN
SIMILAR TO ABOVE
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:11pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
SECOND FLOOR
PLAN - WATER
& GAS
P2.02
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 SECOND FLOOR PLAN - WATER & GAS
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
114" CW UP - 112" CW DN
1" HW UP - 114" HW DN
114" CW UP - 112" CW DN
1" HW UP - 114" HW DN
114" CW UP - 112" CW DN
1" HW UP - 114" HW DN
114" CW UP - 112" CW DN
1" HW UP - 114" HW DN
114" CW UP - 112" CW DN
1" HW UP - 114" HW DN
1"
114"
34"1"34"1"
1"
WC LAV-2
SH-2
SK-1
1"
114"
1"
3 4"
34"
1"
1"
34"
SK
LAV-1
WCSH-1
34"HWR UP&DN
34"
1"
114"
1"
3 4"
1"
1"
3 4"
SK
LAV-1
WC SH-1
KEYED NOTES
1" H & 114" CW TO CONTROL VALVES ABOVE CEILING
WITH ACCESS PANEL (AP)
1" H & CW DROP
34" H & CW TO LAV / SK / SHR
34" CW TO WC
34" HWR TO FLOW CONTROL VALVE ASSEMBLY
ABOVE CEILING WITH ACCESS PANEL (AP). SEE
DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT
34" H&CW DROP TO MR
1
2
3
4
5
6
SEE ABOVE FOR
PIPING LAYOUT
SEE ABOVE FOR
PIPING LAYOUT
112"G UP&DN
GAS REGULATOR
VENTS UP&DN
SIMILAR TO ABOVE
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
THIRD FLOOR
PLAN - WATER
& GAS
P2.03
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 THIRD FLOOR PLAN - WATER & GAS
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF1"
114"
1"
3 4"
34"
1"
1"
34"
SK
LAV-1
WCSH-1
114" CW DN
1" HW DN
34"
114" CW DN
1" HW DN
114" CW DN
1" HW DN
114" CW DN
1" HW DN
114" CW DN
1" HW DN
34" HWR DN
34"
34"
SK-1
1"
114"
34"1"34"1"
1"
WC LAV-2
SH-2
1"
114"
1"
3 4"
1"
1"
3 4"
SK
LAV-1
WC SH-1
34"
34"
34"
KEYED NOTES
1" H & 114" CW TO CONTROL VALVES ABOVE CEILING
WITH ACCESS PANEL (AP)
1" H & CW DROP
34" H & CW TO LAV / SK / SHR
34" CW TO WC
34" HWR TO FLOW CONTROL VALVE ASSEMBLY
ABOVE CEILING WITH ACCESS PANEL (AP). SEE
DETAIL ON DWG P6.02 FOR VALVE ARRANGEMENT
34" H&CW DROP TO MR
1
2
3
4
5
6
SEE ABOVE FOR
PIPING LAYOUT
SEE ABOVE FOR
PIPING LAYOUT
112"G DN, 112"G UP TO ROOF
(SEE ROOF PLAN P3.05
FOR CONTINUATION)
GAS REGULATOR
VENTS UP&DN
(SEE ROOF PLAN P3.05
FOR VENT
TERMINATIONS)
SIMILAR TO ABOVE
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
FOURTH FLOOR
PLAN - WATER
& GAS
P2.04
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 FOURTH FLOOR PLAN - WATER & GAS
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL
SK
SH-1 WC
LAV-1
SK
SH-1 WC
SK
2"
SH-1 WC
SK
2"
SH-1 WC
4"FD
DUPLEX SEWAGE
EJECTOR EJ-1
4"3"4"
2"
4"
4"
4"
4"
4"
2"
4"
2"
4"3"4"
2"
4"3"4"
2"
ELEV 734.0
FF ELEV 734.5
IE 732.27'
IE 733.0'2"PDSP-2 IN PIT
4"FD
4"FD
2"
2"
4"
6"
SLOPE
@ 14"/FT
2"V DN
(2)2"V DN4"
2"
4"AD
4"AD
14 GPM
TD (445 SQ FT)
4"ST
4"ST8 GPM
4"ST4"STIE 731.0'
IE 730.22'
3"
MR
4"FD
ALL SANITARY & VENT PIPING LOCATED
BELOW SLAB IN MECHANICAL ROOM
SHALL BE CAST IRON.
4"
2"V DNTMV-16"RD
4"FD
4"4"
FROM FOOTING
DRAINS. SEE CIVIL
PLANS
DUPLEX SUMP
PUMP SP-1
LAV-1
LAV-1
LAV-1
2"V DN
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
LOWER LEVEL
PLAN -
DRAINAGE
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 LOWER LEVEL FLOOR PLAN - DRAINAGE
NOTE:
SEE DRAWING P3.00B FOR ABOVE CEILING PIPING
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL
4" SAN UP
2" W UP
4"S UP TO WC
2"V UP
2"W UP TO SHR
2"V UP
5'-0"CONTINUATION
BY SITE
CONTRACTOR
2" W UP
2" V UP & DN
212" V UP & DN
4" SAN UP
2" W UP
2" V UP & DN
2" W UP TO SHR
2" V UP
4"S UP TO WC
2"V UP
2" W UP
2" V UP & DN
212" V UP & DN
4" SAN UP
2" W UP
2" V UP & DN 2" W UP TO SHR
2" V UP
4"S UP TO WC
2"V UP
2" W UP
2" V UP & DN
212" V UP & DN
4" SAN UP
2" W UP
2" V UP & DN 2" W UP TO SHR
2" V UP
4"S UP TO WC
2"V UP
4"4"
4"
4"
2" W UP
2" V UP & DN
212" V UP & DN
4" SAN UP
4"S UP TO WC
2"V UP
2" W UP TO SHR
2" W UP
2" V UP & DN
3"LDR UP - RD
(42 GPM)
3"LDR UP - RD
(48 GPM)
3"LDR UP&DROP - OD
SPILL TO GRADE
(42 GPM)
3"LDR UP&DROP - OD
SPILL TO GRADE
(48 GPM)
DUPLEX SEWAGE
EJECTOR EJ-1
DUPLEX SUMP
PUMP SP-1
3"RD 3"RD6"RD6"RD
6"SAN
ELEV 734.0
FF ELEV 734.0
3"
3"
4"
4"
4"
4"
3"
2"V UP
4"FD
TMV-14"FD
(2)2" V DN
2"V UP
6"
4"FD
2"
2"
2" V DN
UP TO COG
KEYED NOTES
WATER CLOSET - 4"S DN, 212"V RISE
LAVATORY - 2"V RISE, 2"W DROP
SINK - 2"V RISE, 2"W DN
SHOWER - 2"V RISE, 2"W DN
MOP RECEPTOR - 3"W DN, 2"V RISE
1
2
3
4
5
2"V DN 2"
PUMP CONTROL PANEL
GWH
2"
2"
2"V DN
6"3"RD 6"RD
PUMP CONTROL
PANEL
2"
2"
4"FD
2" V DN114"PD2"PD6"
GWH IE 742.00'
IE 740.00'
TYPICAL ACCESS
PANEL AP IN
CEILING
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
LOWER LEVEL
PLAN - ABOVE
CEILING
DRAINAGE
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 LOWER LEVEL FLOOR PLAN - ABOVE CEILING DRAINAGE
NOTE:
SEE DRAWING P3.00A FOR PIPING AT PLUMBING FIXTURES
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
LAV-1
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
SK2"
SH-1 WC
LAV-1
SK
3"LDR UP - RD
(42 GPM)
3"LDR UP&DN - RD
(48 GPM)
3"LDR DN - RD
(42 GPM)
3"LDR UP&DN - OD
(48 GPM)
3"LDR UP&DN - OD
(42 GPM)
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
LAV-1
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
LAV-1
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
4"
2" W DN
(2)2"V DN SH-1
2"
WC
LAV-1
212" V UP & DN
4" SAN UP & DN
2" W UP
2" V UP
2" W DN 2" W UP
2" V UP
2" W UP TO SHR
2" V UP
2" W DN
2" V DN
2"V DN
212" V UP
4" SAN UP
2"W UP
2"W UP TO SHR
4"S UP TO WC
2"V UP
4"S DROP
4"S DN
2"V UP
2"W DN2"
2"
4"S DN
2"W DN
2"V DN
COG
COG
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
GROUND FLOOR
PLAN -
DRAINAGE
P3.01
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 GROUND FLOOR PLAN - DRAINAGE
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
SK-1
SH-2WC
LAV-2
3"LDR UP&DN - RD
(42 GPM)
3"LDR UP&DN - RD
(48 GPM)
3"LDR UP&DN - OD
(48 GPM)
3"LDR UP&DN - OD
(42 GPM)SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
LAV-1
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
212" V UP & DN
4" SAN UP & DN
2"
WC
212" V UP & DN
4" SAN UP & DN
SH-1
SK
2" W UP & DN
2" V UP & DN
2" W UP & DN
2" V UP & DN
2"2"
LAV-1
LAV-1
LAV-1
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
SECOND FLOOR
PLAN - DRAINAGE
P3.02
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 SECOND FLOOR PLAN - DRAINAGE
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
3"LDR UP&DN - RD
(42 GPM)
3"LDR UP&DN - RD
(48 GPM)
3"LDR UP&DN - OD
(48 GPM)
3"LDR UP&DN - OD
(42 GPM)
SH-2WC
LAV-2
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
LAV-1
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
SK
2" W UP & DN
2" V UP & DN
2"
SH-1 WC
212" V UP & DN
4" SAN UP & DN
2" W UP & DN
2" V UP & DN
212" V UP & DN
4" SAN UP & DN
2"2"
SK-1
2"
WC
212" V UP & DN
4" SAN UP & DN
SH-1
SK
2" W UP & DN
2" V UP & DN
2" W UP & DN
2" V UP & DN
LAV-1
LAV-1
LAV-1
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
THIRD FLOOR
PLAN -
DRAINAGE
P3.03
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 THIRD FLOOR PLAN - DRAINAGE
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
3"UP TO RD
3"UP TO OD
(24 GPM)
3"LDR DN - RD
(42 GPM)
3"OD
3"RD
3"UP TO RD
3"UP TO OD
(18 GPM)
3"RD
3"OD
3"UP TO RD
3"UP TO OD
(26 GPM)
3"OD
3"RD
3"UP TO RD
3"UP TO OD
(22 GPM)
3"LDR DN - RD
(48 GPM)
3"LDR DN - OD
(48 GPM)
3"OD
3"OD3"LDR DN - OD
(42 GPM)
SH-2
WC
LAV-2
SK
2" W DN
2" V DN
2"
SH-1 WC
LAV-1
212" V DN
4" SAN DN
4" VTR
2" W DN
2" V DN
SK2"
SH-1
WC
212" V DN
4" SAN DN
4"VTR
SK2"
SH-1 WC
SK-1
2"
WC SH-1
SK
212" V DN
4" SAN DN
4"VTR
2" W DN
2" V DN
2" W DN
2" V DN
2"2"
2"2"
2" W DN
2" V DN
2" W DN
2" V DN
2"
2"
212" V DN
4" SAN DN
4" VTR
2"
2"
2" W DN
2" V DN
2" W DN
2" V DN
212" V DN
4" SAN DN
4"VTR
2"2"
LAV-1
LAV-1
LAV-1
3"OD
3"RD
COORDINATE STORM & VENT PIPE
ROUTING WITH MECHANICAL UNIT
ABOVE KITCHENETTE CEILING
COORDINATE STORM & VENT PIPE
ROUTING WITH MECHANICAL UNIT
ABOVE KITCHENETTE CEILING
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:12pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
FOURTH FLOOR
PLAN -
DRAINAGE
P3.04
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 FOURTH FLOOR PLAN - DRAINAGE
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.93"OD
3"RD
3"OD
3"RD
3"OD
3"RD
3"OD
3"RD
4"VTR
4"VTR
4"VTR
4"VTR
4"VTR
112"G DN
SEE DRAWING P2.04
FOR CONTINUATION
STAND-BY
GENERATOR
(4)GAS REGULATOR
VENTS DN.
SEE DRAWING P2.04
FOR CONTINUATION
TERMINATE GAS
REGULATOR VENTS WITH
GOOSENECK
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
ROOF
PLAN -
DRAINAGE
P3.05
AH
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 ROOF PLAN - DRAINAGE
NO SCALE
DOMESTIC WATER RISER DIAGRAM1
LOWER LEVEL
GROUND
FLOOR
2ND FL
3RD FL
4TH FL
ROOF
INCOMING 4"
DOMESTIC
WATER SERVICE
FROM CITY
WATER
PRV M
RPZ
PRV
FD FD
TP
WATER
HEATER
WATER
HEATER RPZ
1" 1
WSFU
HB
FD
GRADE
SHR
LAV SKWC
114" 3.7 WSFU
1" 2.5 WSFU
34" 1 WSFU
34"
1"
1"
34"
BOILER
MAKE-UP
FEED
114" 3.7 WSFU
1" 2.5 WSFU
WCLAVSHR
34"3 4"34"
1" 2.7 WSFU
1" 1.5 WSFU
SHR
34"
114" 3.7 WSFU
1" 2.5 WSFU
WCLAVSHR
34"3 4"34"
1" 2.7 WSFU
1" 1.5 WSFU
SHR
34"
114" 3.7 WSFU
1" 2.5 WSFU
WCLAVSHR
34"3 4"34"
1" 2.7 WSFU
1" 1.5 WSFU
SHR
34"
1" 2.5 WSFU
114" 3.7 WSFU
114" 5 WSFU
112" 7.4 WSFU
112" 7.5 WSFU
2" 11.1 WSFU
112" 10 WSFU
2" 14.8 WSFU
SHR
114" 3.7 WSFU
1" 2.5 WSFU
1"3 4"
LAV SKWC
3 4" 1 WSFU
34"
1"
112" 10 WSFU
2" 14.8 WSFU
2" 18.5 WSFU
2" 12.5 WSFU
34"
34"
112" 7.5 WSFU
2" 11.1 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
114" 5 WSFU
112" 7.4 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
1" 2.5 WSFU
114" 3.7 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
114" 3.7 WSFU
1" 2.5 WSFU
1"3 4"
LAV SKWC
3 4" 1 WSFU
34"
1"
112" 10 WSFU
2" 14.8 WSFU
2" 18.5 WSFU
2" 12.5 WSFU
34"
112" 7.5 WSFU
2" 11.1 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
114" 5 WSFU
112" 7.4 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
1" 2.5 WSFU
114" 3.7 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
114" 3.7 WSFU
1" 2.5 WSFU
1"3 4"
LAV SKWC
3 4" 1 WSFU
34"
1"
112" 10 WSFU
2" 14.8 WSFU
2" 18.5 WSFU
2" 12.5 WSFU
34"
112" 7.5 WSFU
2" 11.1 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
114" 5 WSFU
112" 7.4 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
1" 2.5 WSFU
114" 3.7 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
34"
SHR
114" 3.7 WSFU
1" 2.5 WSFU
1"34"
LAV SKWC
34" 1 WSFU
34"
1"
112" 10 WSFU
2" 14.8 WSFU
2" 18.5 WSFU
2" 12.5 WSFU
34"
112" 7.5 WSFU
2" 11.1 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
114" 5 WSFU
112" 7.4 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
1" 2.5 WSFU
114" 3.7 WSFU
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
3 4"
1"
3 4"
114" 3.7 WSFU
1" 2.5 WSFU
SHR
1"34"
LAV SKWC
34" 1 WSFU
3 4"
1"
3 4"
SHR
1"34"
LAV SKWC
34" 1 WSFU
3 4"
1"
3 4"
SHR
1"34"
LAV SKWC
34" 1 WSFU
3 4"
1"
3 4"
FCV FCV FCV FCV
2" 25 WSFU
2" 37 WSFU
2" 37.5 WSFU
212" 55.5 WSFU
(734'-6")
(744'-6")
(754'-3")
(764'-0")
(773'-9")
9'-9"
9'-9"
9'-9"
10'-0"
RPZ
34"34"3 4"34"
3 4"
FCV
34"
FD
TP
FD
NFWH
MR34" 2.25
WSFU
34"
212" 88.8 WSFU
212" 74 WSFU
2" 50 WSFU
2" 60 WSFU
212" 91.05 WSFU
2" 62.25 WSFU
2" 62.25 WSFU
2" 62.25 WSFU3" 153.3 WSFU
12"
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
DOMESTIC WATER
RISER DIAGRAM
P4.01
AH
GROUND
2ND FLOOR
3RD FLOOR
4TH FLOOR
LOWER LEVEL
ROOF
2"
2"
2"
2"
2"
2"(2 DFU)
2"(4 DFU)
2"
2"
2"
2"
2"(6 DFU)
2"
SHR
SHR
SHR
SHR
2"
2"
4"
4"(8DFU)
4"(4 DFU)
2"
212"
212"
212"
2"
2"
2"
2"
2"
2"
2"
2"
WC
LAV
WC
LAV
WC
LAV
WC
LAV
2"
4"
212"
2"
2"
2"
2"
2"
2"
SK
2"
2"
2"
SK
SK
SK
2"(2 DFU)
2"(4 DFU)
2"(6 DFU)
2"(8 DFU)
2"
2"
4"VTR
2"2"
4"(12 DFU)
4"(13 DFU)
2"(8 DFU)
4"(3 DFU)
4"(16 DFU)
4"(24 DFU)4"(32 DFU)
2"
2"
2"
2"
2"
2"(2 DFU)
2"(4 DFU)
2"
2"
2"
2"
2"(6 DFU)
2"
SHR
SHR
SHR
SHR
2"
2"
4"
4"(8DFU)
4"(4 DFU)
2"
212"
212"
212"
2"
2"
2"
2"
2"
2"
2"
2"
WC
LAV
WC
LAV
WC
LAV
WC
LAV
2"
4"
212"
2"
2"
2"
2"
2"
2"
SK
2"
2"
2"
SK
SK
SK
2"(2 DFU)
2"(4 DFU)
2"(6 DFU)
2"(8 DFU)
2"
2"
4"VTR
2"2"
4"(12 DFU)
4"(13 DFU)2"(8 DFU)
4"(3 DFU)
4"(16 DFU)
4"(24 DFU)
4"(32 DFU)
4"
4"(8DFU)
4"(4 DFU)
2"
212"
212"
212"
2"
2"
WC
WC
LAV
WC
4"
4"VTR
2"
2"
SHR
2"
2"
2"
LAV
2"
2"
SHR
2"
2"
2"
LAV
2"(2 DFU)
2"
SHR
212"
2"(2 DFU)
SHR
2"
WC
2"
(2 DFU)
2"
SK
2"
2"
2"
2"
2"
2"
2"(2 DFU)
2"(4 DFU)
2"
2"
2"
2"
2"(6 DFU)
2"
SHR
SHR
SHR
SHR
2"
2"
4"
4"(8DFU)
4"(4 DFU)
2"
212"
212"
212"
2"
2"
2"
2"
2"
2"
2"
2"
WC
LAV
WC
LAV
WC
LAV
WC
LAV
2"
4"
212"
2"
2"
2"
2"
2"
2"
SK
2"
2"
2"
SK
SK
SK
2"(2 DFU)
2"(4 DFU)
2"(6 DFU)
2"(8 DFU)
2"
2"
4"VTR
2"2"
4"(12 DFU)
4"(13 DFU)2"(8 DFU)
4"(3 DFU)4"(16 DFU)
4"(24 DFU)4"(32 DFU)
2"
2"
2"
2"
2"
SK
2"
2"
SK
SK
2"(2 DFU)
2"(4 DFU)
2"
2"
4"(8DFU)
4"
4"
4"(4 DFU)
4"(12 DFU)
212"
212"
212"
2"
2"
2"
2"
2"
2"
WC
LAV
WC
LAV
WC
LAV
212"
4"VTR
2"
2"
SHR
2"
2"
2"
2"
2"
2"(4 DFU)
2"(8 DFU)
2"
2"
2"
SHR
SHR
SHR2"
2"
2"
SK
2"
2"
2"
SK
SK
2"
2"
LAV
2"
WC
2"
SK
2"
2"
2"2"
LAV
SHR
2"
2"(2 DFU)
2"
2"(1 DFU)
2"
LAV
212"
WC
4"
3"4"(6 DFU)
2"
4"(3 DFU)
2"(2 DFU)
SK
2"
2"(2 DFU)
SHR
2"
2"(1 DFU)
LAV
2"
212"
WC
4"
3"4"(6 DFU)4"(3 DFU)
2"(2 DFU)
SK
2"
2"(2 DFU)
SK 2"
2"(1 DFU)
LAV
2"
212"
WC
4"
212"
2"(2DFU)
SHR
2"(2 DFU)
SHR
2"
2"(1 DFU)
LAV
2"
WC
212"
4"
3"4"(6 DFU)4"(3 DFU)
2"(2 DFU)
SK
2"
FD FD
NO SCALE
SANITARY RISER DIAGRAM1
2" PD
6"
2"
2"
2"
6"
2"
ELEV.
SUMP
PUMP
2"
COPDCOPDCOPDCOPD
4"(8 DFU)
4"(8 DFU)
4"(8 DFU)
4"(40 DFU)
4"(16 DFU)4"(6 DFU)
4"(5 DFU)
2"
4"(66 DFU)4"(64 DFU)2"
2"
4"(11 DFU)
4"(12 DFU)
4"(14 DFU)
4"(15 DFU)4"(3 DFU)
4"(69 DFU)
8"(86 DFU)
4"(84 DFU)
2"(6 DFU)
4"(34 DFU)
4"(13 DFU)
4"(56 DFU)
4"(16 DFU)
4"(86 DFU)
4"(3 DFU)
2"
2"
2"
2"(10 DFU)
4"(24 DFU)
4"(8 DFU)
6"
4"
2"
1/4"/FT SLOPE
4"(156 DFU)
2"(12 DFU)
2"(14 DFU)
4"(70 DFU)
1/4"/FT SLOPE
2"
BUILDING WALL
DUPLEX
SEWAGE
EJECTORS
6" SANITARY
SEWER
GRADE
SUMP PIT
(SEE 4.03)
EJ-1
FD
4"
2"
4"
4"(32 DFU)
FD
COPD
FD
3"(3DFU)
MR
2"
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
SANITARY
RISER DIAGRAM
P4.02
AH
NO SCALE
STORM RISER DIAGRAM1
ALL STORM PIPING RUN @ 18"/FT SLOPE
SIZING BASED ON 3"/HR RAINFALL RATE.
GROUND
2ND FLOOR
3RD FLOOR
4TH FLOOR
ROOF
LOWER
3" OD 3" RD
(24 GPM)
3" RD 3" OD
(18 GPM)
3" OD
3" OD
3" OD
TERMINATE 3" OD
ABOVE GRADE
BUILDING WALL 3" OD
3" OD 3" RD
(26 GPM)
3" RD 3" OD
(22 GPM)
3" OD
3" OD
3" OD
3" OD
3" OD
DUPLEX
SUMP PUMPS
COG
6" STORM SEWER
5'-0"
CONTINUATION BY
SITE CONTRACTORTO SANITARY VENT SYSTEM
114" PD
3" RD
3" RD
6" RD
6" RD
3" RD
3" RD
4" AD 4" ADTD
4"ST
(8 GPM)4"ST
(14 GPM)
4"ST
(24 GPM)
SP-1
NO SCALE
GAS RISER DIAGRAM2
GROUND
2ND FLOOR
ROOF
LOWER
BUILDING WALL
GAS UP TO METER
GWH
199
CFH
GWH
199
CFH BOILER
300 CFH
M
GAS METER
(COORDINATE
INSTALLATION
REQ'TS WITH LOCAL
GAS COMPANY)
INCOMING GAS
SERVICE BY GAS CO.
GAS PRESSURE
REGULATOR VENTS.
PROVIDE
W/GOOSENECK
TERMINATION
3RD FLOOR
4TH FLOOR
G
LINE SIZE VENTS (TYP)
193 CFH
STAND-BY
GENERATOR
GGBOILER
300 CFHGG GGDEVELOPED LENGTH - 150 FEET
SIZING BASED ON INCOMING 7" WC PRESSURE
G
G
2"
112"
112"
2"
112"
112"
112"
112"
112"
112"
3"(1,191 CFH)
G
6" RD
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
STORM & GAS
RISER DIAGRAM
P4.03
AH
DESCRIPTIONSYMBOL
MAXIMUM
WATER
CONSUMPTION
WASTE VENT D.F.U.W.S.F.U.
CONNECTIONS
HOT COLD
FIXTURE TRIM REMARKS
PLUMBING FIXTURE SCHEDULE
/SAN.
REFER TO ARCHITECTURAL
PLANS FOR FIXTURE
MOUNTING HEIGHTS.
MUSTEE MOP BASIN #65M 24"X36"X10", MOLDED
STONE WITH FACTORY INSTALLED STAINLESS STEEL
DOME STRAINER AND SEDIMENT BASKET.
CHICAGO #897-CP FAUCET W/ VACUUM
BREAKER,WALL BRACE, CHROME PLATED, PAIL
HOOK, AND HOSE THREAD ON SPOUT.
FIAT #832AA-HOSE BRACKET COMBINATION
FIAT #MSG2424 STAINLESS STEEL WALL GUARD
MISCELLANEOUS EQUIPMENT SCHEDULE
NO.NO.
REQUIREDEQUIPMENT LOCATION MANUFACTURER REMARKSMODEL NO.
TP TRAP PRIMER
1 PER
FLOOR
DRAIN
SA
AS SHOWN ON
PLANS
PRECISION PLUMBING PRODUCTS # PR-500 "PRIME RITE",
CORROSION RESISTANT BRASS BODY, "O" RING SEALS, 1/2"
INLET AND OUTLET, AND INTEGRAL VACUUM BREAKER.
INSTALL THE VALVE AT A MINIMUM OF 12" ABOVE FINISHED
FLOOR. PROVIDE WITH DISTRIBUTION # DU-2 FOR TWO, #
DU-3 FOR THREE, OR # DU-4 FOR FOUR DRAIN
CONNECTIONS.
PRECISION PLUMBING PRODUCTS, HARD DRAWN COPPER
BODY WITH WROUGHT COPPER FITTINGS, PISTON TYPE
WITH LUBRICATED EPDM "O" RING SEALS, MEETING ASSE
1010 OR PDI WH-201. PROVIDE PDI SIZES "A" THROUGH "F"
AS SHOWN ON PLANS. PROVIDE SIZE "A" UNLESS SHOWN
OTHERWISE ON THE PLANS.
BELL & GOSSETT # LF-CB "CIRCUIT SETTER PLUS", LEAD
FREE CAST BRONZE BODY, BRASS BALL, CALIBRATED
BALANCE VALVE, DIFFERENTIAL PRESSURE READOUT
PORTS, DRAIN PORT, MEMORY STOP, NAMEPLATE AND 1/2"
VALVE BODY SIZE UNLESS SHOWN OTHERWISE ON PLANS.
SET AND BALANCE TO 0.5 GPM FLOW RATE UNLESS SHOWN
OTHERWISE ON PLANS AND PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
FCV
AS SHOWN ON
PLANS
AT HOT
WATER
RETURN
PIPING
AS
SHOWN
ON
PLANS
AS SHOWN
ON PLANS
AS
SHOWN
ON
PLANS
JAY R. SMITH # 1010Y (-E0X-C-R-CID), 15" DIAMETER
CAST IRON BODY, FLASHING CLAMP, GRAVEL STOP,
UNDERDECK CLAMP, SUMP RECEIVER, HUBLESS
OUTLET, FIXED EXTENSION - HEIGHT AS REQUIRED
BY INSTALLED INSULATION THICKNESS, AND CAST
IRON DOME BOLTED OR LOCKED DOWN. PROVIDE
OUTLET SIZE AS SHOWN ON PLANS.
AS
SHOWN
ON
PLANS
JAY R. SMITH # 1080Y (-E0X-C-R-CID), 15" DIAMETER
CAST IRON BODY, FLASHING CLAMP, GRAVEL STOP,
UNDERDECK CLAMP, SUMP RECEIVER, HUBLESS
OUTLET, FIXED EXTENSION - HEIGHT AS REQUIRED BY
INSTALLED INSULATION THICKNESS, CAST IRON DOME
BOLTED OR LOCKED DOWN AND 2" HIGH WATER DAM.
PROVIDE OUTLET SIZE AS SHOWN ON PLANS.
JAY R. SMITH # 4762 - 12" x 12" - CL, TYPE 304 STAINLESS
STEEL PANEL AND FRAME WITH CONCEALED HINGE, KEY
OPERATED CYLINDER LOCK. PROVIDE WITH NAILER SLOTS
FOR INSTALLATION IN STUD WALLS AND ANCHOR STRAPS
FOR INSTALLATION IN MASONRY CONSTRUCTION.
AP
AS SHOWN ON
PLANS
AS SHOWN ON
PLANS
RPZ-1
AS SHOWN ON
PLANS
MAKE-UP
WATER TO
BOILER
WATTS # 009QT-S, MEETING ASSE 1013, CAST BRONZE
BODY, QUARTER TURN TEST COCKS, QUARTER TURN BALL
VALVES, BRONZE STRAINER, AND # 909AG AIR GAP FITTING.
DCV-1 AS SHOWN ON
PLANS
WATER
SERVICE
WATTS # LF-007, MEETING ASSE 1013, LEAD FREE CAST
COPPER ALLOY, QUARTER TURN TEST COCKS, RESILIENT
SEATED NON-RISING STEM GATE VALVES AND WATTS
#77F-DI-FDA EPOXY COATED CAST IRON STRAINER AND #
957AG AIR GAP FITTING.
AS SHOWN
ON PLANS
NFWH
AS SHOWN ON
PLANS
PRIER PRODUCTS # C-634NBX1, SATIN NICKEL PLATED
BRASS 1" MALE INLET BY 3/4" FEMALE INLET, 3/4"
THREADED HOSE CONNECTION, LOOSE KEY HANDLE,
HYDRANT LENGTH AS REQUIRED FOR INSTALLED WALL
THICKNESS, ADJUSTABLE WALL CLAMP, BRASS BOX WITH
SATIN NICKEL PLATED FINISH AND INTEGRAL ASSE 1052
DOUBLE CHECK VACUUM BREAKER.
HB
AS SHOWN ON
PLANS
PRIER PRODUCTS # C-158NP.75, ROUGH CHROME PLATED
BRASS 3/4" FEMALE FIP INLET, 3/4" THREADED HOSE
CONNECTION, METAL WHEEL HANDLE, AND ASSE 1011
INTEGRAL VACUUM BREAKER.
AS SHOWN ON
PLANS
AS SHOWN ON
PLANS
PRV-1 AS SHOWN ON
PLANS
BUILDING 2
WATER SERVICE
LOCATION
WATER HEATER SCHEDULE
TAG
GWH
STORAGE
GAL G.P.H.
VOLTAGE
120
MANUFACTURER
AND MODEL No REMARKSLOCATIONBTU/HR
RECOVERY @
5,6(QUANTITY
AO SMITH BTH-199
100 235199
LOWER LEVEL
MECHANICAL ROOM
EFFICIENCY
%
95%
FLUE
DIA.
4"
DIMENSION
DIA.HEIGHT
27 3/4"75 1/2"
LEAD FREE BRASS BODY WITH ROUGH BRASS FINISH, CORROSION RESISTANT
INTERNAL PARTS, AND UNION CHECK STOPS WITH REMOVABLE STRAINERS, ASSE
1017 COMPLIANT, CAPABLE OF 52 GPM WITH A 10 PSI DIFFERENTIAL AND A
MINIMUM FLOW RATE OF 5 GPM. SET MAXIMUM TEMPERATURE TO 120F.
MIXING VALVE SCHEDULE
TAG MANUFACTURER
AND MODEL No LOCATION STYLE
PIPE SIZES
TMV-1 POWERS
LFMM433
AT WATER HEATERS
BUILDINGS 1, 2 & 3
ON WALL
INLET OUTLET
1 1/4"1 1/4"
MIN. FLOW TO
ASSE 1017
5 GPM
MAX FLOW
@ 10PSI DROP
52 GPM
REMARKSOUTLET
TEMPERATURE
)
MAXIMUM
PLUMBING PUMP SCHEDULE
MOTOR
VOLTSHPRPM
2800
PHASE
120 1
HEAD REMARKS
1 GPM 8 FT
TAG LOCATION
LEAD-FREE BRONZE BODY PUMPCPDOMESTIC HWR
SERVICE
SP-1
DISCHARGE
-
DOMESTIC EXPANSION TANK
MANUFACTURER
AND MODEL No
TAG LOCATION STYLE
TANK
VOLUME
(GAL)
MAX
ACCEPTANCE
(GAL)
DIMENSION
(INCHES)
TANK
CONNECTION
(INCHES)
LINE
PRESSURE
(PSI)DIA.HEIGHT
REMARKS
ET AMTROL ST-30V-C FLOOR 14 11.3 15 24 3/4 70
1/2 1750 120 1 50 GPM 21 FTSP-2 WEIL 1411-538 ELEVATOR PIT 1 1/2"
PROVIDE WITH ZOELLER # 30-0030
NON-CLOG, FLAPPER TYPE,
CHECK VALVE. PROVIDE WITH
WEIL #8245 FLOAT SWITCH WITH
POWER CORD AND PIGGYBACK
PLUG. COVER: FIBERBASIN
#FIB24SQ 28" X 1.5" THICK
SQUARE LIGHT DUTY FIBERGLASS
GRID GRATE WITH FRAME.
INSTALL TANK ACCORDING TO
MANUFACTURER'S
RECOMMENDATIONSAT WATER HEATERS
AS SHOWN ON
PLANS
2 PROVIDE VENTING PER
MANUFACTURERS REQUIREMENTS
PRV-1 WATTS 212" LF223S-HP, IRON BODY, STAINLESS STEEL
SEAT, STAINLESS STEEL BOLTS, STRAINER, INLET AND
OUTLET SIZE AS SHOWN ON PLANS, 50-95 PSI REDUCED
PRESSURE RANGE. SET OUTLET PRESSURE TO 95 PSI WITH
FLOW RATE OF 170 GPM AT A FALL OFF PRESSURE OF 20 PSI
DIFFERENTIAL.
PRV-3 WATTS 1" LF223S, LEAD FREE BRONZE BODY,
STAINLESS STEEL SEAT, STAINLESS STEEL BOLTS, INLET
AND OUTLET SIZE AS SHOWN ON PLANS, 50-95 PSI
REDUCED PRESSURE RANGE. SET OUTLET PRESSURE TO
95 PSI WITH FLOW RATE OF 40 GPM AT A FALL OFF
PRESSURE OF 15 PSI DIFFERENTIAL.
PRV-2 WATTS 212" LF223S, IRON BODY, STAINLESS STEEL
SEAT, STAINLESS STEEL BOLTS, STRAINER, INLET AND
OUTLET SIZE AS SHOWN ON PLANS, 25-75 PSI REDUCED
PRESSURE RANGE. SET OUTLET PRESSURE TO 70 PSI WITH
FLOW RATE OF 170 GPM AT A FALL OFF PRESSURE OF 20 PSI
DIFFERENTIAL.
PRV-2 AS SHOWN ON
PLANS
BUILDING 2
WATER SERVICE
LOCATION
PRV-3 AS SHOWN ON
PLANS
BUILDING 2
WATER SERVICE
LOCATION
FLOW CONTROL VALVE
ACCESS PANEL
MECH. RM
MECH. RM
AS SHOWN
ON PLANS
ACO TRENCH DRAIN MODEL K100 WITH TYPE 410D /
412D GALVANIZED GRATE
AMERICAN STANDARD # 215AA.104 "CADET PRO RIGHT
HEIGHT" TANK TYPE WHITE VITREOUS CHINA FIXTURE
WITH ELONGATED BOWL, 1.28 GALLONS PER FLUSH,
AND SIPHON FLUSH ACTION WITH 3" OVERSIZED
FLAPPER VALVE, MaP SCORE OF 1,000g AND
CLOSE-COUPLED TANK WITH LEFT HAND METAL TRIP
LEVER.
BEMIS #1520EC WHITE ELONGATED,
CLOSED-FRONT MOLDED WOOD SEAT WITH
COVER WITH EASY CLEAN & CHANGE HINGES,
McGUIRE # LF2166CC LEAD FREE BRASS
ANGLE STOP VALVE WITH RISER AND
CHROME-PLATED ESCUTCHEON.
McGUIRE # LF2165CCLK LEAD FREE BRASS
LOOSE KEY COMPRESSION ANGLE STOP VALVES
WITH RISERS AND ESCUTCHEONS, McGUIRE #
B8872CF 1-1/4" 17 GAUGE CAST CHROME PLATED
BRASS ADJUSTABLE P-TRAP AND WASTE ARM
WITH CLEANOUT PLUG AND ESCUTCHEON.
McGUIRE # LF2165CC LEAD FREE BRASS WHEEL
HANDLE ANGLE STOP VALVES WITH RISERS AND
ESCUTCHEONS, McGUIRE # 151M CUP STRAINER
WITH 1-1/2" 17 GAUGE TAILPIECE, McGUIRE #
B8912CF 1-1/2" 17 GAUGE CAST CHROME PLATED
BRASS ADJUSTABLE P-TRAP WITH BRASS
CLEANOUT AND ESCUTCHEON.
PROVIDE WITH
INSINKERATOR BADGER 5
FOOD WASTE DISPOSER
39
WATTS
EJ-1
JAY R. SMITH # 2110L (-B), CAST IRON BODY, 8" ROUND,
LOOSE, MEDIUM DUTY, CAST IRON GRATE, SEDIMENT
BUCKET, BOTTOM OUTLET, SEEPAGE PAN,TRAP
PRIMER CONNECTION AND MEMBRANE FLASHING
CLAMP. USE PUSH-ON JOINT OF OUTLET SIZE AS
SHOWN ON PLANS.
MANUFACTURER
AND MODEL No
CAPACITY
EACH
DUPLEX SUMP PUMP - WEIL
MODEL 1408, SUBMERSIBLE
WITH 1.25" DISCHARGE, CAST
IRON CONSTRUCTION WITH
BRONZE, SEMI-OPEN TYPE
IMPELLER
EXTERIOR DRAINS,
FOOTING AND
UNDERSLAB
DRAINS
1/3 1750 120 1 30 GPM 20 FT 1 1/2"SEE DETAIL ON SHEET P6.01 FOR
SPECIFICATIONS
CIRCULATING PUMP BELL &
GOSSETT NBF-9U/LW
DUPLEX SEWAGE EJECTOR
PUMPS WEIL SERIES 2436
SUBMERSIBLE GRINDER
MECH. RM LOWER LEVEL
SANITARY
DRAINAGE
1 1750 120 1 35 GPM 19 FT 2"SEE DETAIL ON SHEET P6.01 FOR
SPECIFICATIONS
AS SHOWN
ON PLANS
JAY R SMITH 2142-U 12" ROUND TOP, HEAVY DUTY
DRAIN WITH FREE STANDING SEDIMENT BUCKET WITH
VANDAL PROOF GRATE
KOHLER #K-2609-SU "BACHATA" - 17" X 14" OVAL
UNDERMOUNT STAINLESS STEEL FIXTURE-WITH REAR
OVERFLOW - LUSTER FINISH
GROHE #34271ENA "CONCETTO" SINGLE LEVER,
CENTERSET FAUCET. KOHLER #7127-A DRAIN
WITH NON-REMOVABLE METAL STOPPER
AMERICAN STANDARD #0955.001EC "MURRO" WALL
HUNG WHITE VITREOUS CHINA FIXTURE - CENTER
HOLE WITH OVERFLOW. PROVIDE WITH WALL
HANGER AND AMERICAN STANDARD #0059.020EC
VITREOUS CHINA SHROUD.
GRIFFORM INNOVATIONS "BARRIER FREE
SHOWER PANS"
MATERIAL: CORIAN
COLOR: ELEGANT GRAY
STYLE: TRENCH DRAIN
PAN SHAPE: T651
ENTRY: SLOPING ENTRY
PAN WALL: STRAIGHT WALL
6,=(ô:,'(;'((3
IN FULLY ACCESSIBLE UNIT
SPEAKMAN "NEO" BRUSHED NICKEL:
#SM-1000-P-BN PRESSURE BALANCE VALVE AND
TRIM
#233010-BN SHOWER COMBINATION
#VS-126-BN WALL MOUNT
GRIFFORM INNOVATIONS "BARRIER FREE
SHOWER PANS"
MATERIAL: CORIAN
COLOR: ELEGANT GRAY
STYLE: TRENCH DRAIN
PAN SHAPE: T651
ENTRY: SLOPING ENTRY
PAN WALL: STRAIGHT WALL
6,=(ô:,'(;'((3
LOCATE WALL MOUNT AS
PER ARCHITECTURAL
'5$:,1*66(73$1,1ó
5(&(663529,'(ó
RADIUS AT ENTRY EDGE
IN FULLY ACCESSIBLE UNIT.
LOCATE WALL MOUNT AS
PER ARCHITECTURAL
'5$:,1*66(73$1,1ó
5(&(663529,'(ó
RADIUS AT ENTRY EDGE
KOHLER #K-3325-HCF "UNDERTONE PRESERVE" - 21"
;;ò'((36,1*/(&203$570(17
UNDERMOUNT STAINLESS STEEL FIXTURE
GROHE #32665DC1 "CONCETTO" SINGLE HANDLE
CENTERSET FAUCET WITH PULL-OUT LAMINAR
SPRAY - SUPERSTEEL INFINITY FINISH
ELKAY #ELUHAD211555 - 21" X 16" X 5 3/8" DEEP,
SINGLE COMPARTMENT UNDERMOUNT STAINLESS
STEEL FIXTURE - LUSTERTONE
PROVIDE WITH
INSINKERATOR BADGER 5
FOOD WASTE DISPOSER
IN FULLY ACCESSIBLE UNIT
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
SCHEDULES
SHEET 1 OF 1
P5.01
AH
PRV-2 SET
AT 60 PSI
NORMALLY CLOSED
BYPASS VALVE (TYP)
4"
212" DOUBLE CHECK VALVE
ASSEMBLY BACKFLOW
PREVENTER - DCV-1
212"
MAIN RISER
CONTROL VALVE
INLET STRAINER WITH
BLOW OUT VALVE CAP
WATER METER
WITH REMOTE
READOUT
4"
2"NORMALLY CLOSED
BYPASS VALVE
PRV-1 SET
AT 95 PSIPRESSURE
GAUGE (TYP)
4"
DOMESTIC WATER
SERVICE LEAD-IN.
SIZE AS INDICATED.
NOTES:
1. PROVIDE SUPPORT TO EQUIPMENT
FROM WALL/FLOOR AS REQUIRED.
2. PROVIDE 30" CLEARANCE IN FRONT OF RPZ
3. PROVIDE 18" CLEARANCE ABOVE RPZ.
4. PROVIDE 12" CLEARANCE IN BACK OF RPZ TO WALL.
MAXIMUM
5'-0" AFF
MINIMUM
2'-6" AFF
NOT TO SCALE
THERMOSTATIC MIXING VALVE6
DIAL THERMOMETER IN TEE
FITTING. REFER TO
SPECIFICATIONS.
PIPE REDUCER OR INCREASER
WHERE REQUIRED TO MATCH
PIPE SIZES WITH VALVE PORT
SIZES
THERMOSTATIC MIXING VALVE.
REFER TO SPECIFICATIONS
AND/OR SCHEDULE.
COLD WATER SUPPLY.
SHUT-OFF VALVE
(TYPICAL)
PIPE UNION (TYPICAL)
STRAINER (TYPICAL)
CHECK VALVE (TYPICAL)
30" DEEP x 12" WIDE HEAT
TRAP
REFER TO FLOOR PLANS FOR PIPE SIZES. PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST
TO SUIT FIELD CONDITIONS. PIPING CONNECTIONS SHOWN ARE FOR POWERS # 430 AND # 1400
SERIES THERMOSTIC MIXING VALVES. INSTALL OTHER MANUFACTURER'S VALVES PER THEIR
PUBLISHED INSTALLATION INSTRUCTIONS. MOUNT THERMOSTATIC MIXING VALVE TO WALL AT 5'-0"
AFF, AT A LOCATION EASILY ACCESSIBLE FOR SERVICING.
NOT TO SCALE
INCOMING DOMESTIC WATER SERVICE1
NOT TO SCALE
LARGE EXPANSION TANK7
PIPE HANGER TO
STRUCTURE ABOVE
AIR CHARGING
VALVE. FILL TANK
WITH AIR PRESSURE
TO MATCH WATER
PRESSURE.
PIPE UNION:
DIELECTRIC TYPE IF
REQUIRED FOR
DISSIMILAR METALS
DRAIN VALVE
FLOOR OR PLATFORM
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD
CONDITIONS. MAKE PIPE SAME SIZE AS TANK FITTING. FOLLOW
MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION PROCEDURE.
VERIFY PROPER OPERATION WHEN INSTALLED. PROVIDE SEISMIC
STRAP/BRACING IF/AS REQUIRED BY LOCAL CODE.
)+27:$7(56833/<
FROM WATER HEATER.
REFER TO FLOOR PLANS.
)7(03(5(':$7(5
SUPPLY TO FIXTURES
SHOWN ON FLOOR PLAN
NOT TO SCALE
ELEVATOR SUMP PUMP4
6" MINIMUM
PIPE UNION
STRUCTURAL FOOTING
HIGH LEVEL ALARM TETHERED
FLOAT SWITCH
ON-OFF TETHERED FLOAT SWITCH
ARRANGEMENT SHOWN IS SCHEMATIC; ADJUST TO SUIT ACTUAL CONDITIONS. LOCATE FLOATS
AT ELEVATIONS RECOMMENDED BY PUMP MANUFACTURER. INTERLOCK OF HIGH LEVEL ALARM
WITH ALARM BELL (REFER TO FLOOR PLANS IF PROVIDED) IS SPECIFIED IN DIVISION 16.
INTERLOCK OF HIGH LEVEL ALARM WITH BUILDING AUTOMATION SYSTEM (REFER TO
SPECIFICATIONS IF PROVIDED) IS SPECIFIED IN DIVISION 15. REFER TO ARCHITECTURAL AND
STRUCTURAL PLANS FOR LOCATION OF CONCRETE SUMP PIT. INSTALL PIPE AND CONTROLS TO
NOT INTERFERE WITH ELEVATOR ITEMS.
HIGH LEVEL ALARM PER
SPECIFICATIONS AND
SCHEDULES, WITH POWER
WIRING SPECIFIED IN
DIVISION 16
SIMPLEX RECEPTACLE AND
OUTLET BOX IS SPECIFIED IN
DIVISION 16. MOUNT ON
WALL NEAR ELEVATOR
DOORS.
SUMP PUMP RECEPTACLE
PLUG AND FLOAT SWITCH
PIGGYBACK PLUG
NON-CLOG CHECK VALVE
GROMMET AROUND WIRING
ELEVATOR SHAFT FLOOR
STEEL GRATE IS SPECIFIED
IN DIVISION 3
24"x24"x24" DEEP CONCRETE
PIT PER STRUCTURAL
DRAWINGS
SUMP PUMP: REFER TO
SCHEDULE AND
SPECIFICATIONS
ONE PIPE SIZE SMALLER
THAN MAIN LINE SIZE.
PRV-3 SET
AT 70 PSI 1"
212"
4"
4"
212"
4"
212"212"
4"
4"
G
NO SCALE
GAS FIRED WATER HEATER2
EQUAL
INSTALL DRAIN VALVE
FURNISHED WITH HEATER
REFER TO SPECIFICATIONS, SCHEDULES AND NOTES FOR MORE INFORMATION. PIPING
ARRANGEMENT SHOWN IS SCHEMATIC. VERIFY ALL CONNECTION SIZES AND LOCATIONS PER
MANUFACTURER'S REQUIREMENTS. ADJUST TO SUIT FIELD CONDITIONS. REFER TO FLOOR
PLANS FOR PIPE SIZES. PROVIDE SEISMIC STRAP OR BRACING IF/AS REQUIRED BY LOCAL
AUTHORITIES. SEE MECHANICAL PLANS FOR WATER HEATER VENTING.
G
EQUAL
EQUAL EQUAL
PROVIDE DIELECTRIC PIPE
UNION AT TANK
CONNECTIONS, FOR
CONNECTION OF
DISSIMILAR METALS
(TYPICAL)
SET WATER HEATER ON
CONCRETE EQUIPMENT
PAD PER SPECIFICATIONS
GAS-FIRED WATER
HEATER; REFER TO
SPECIFICATIONS AND
SCHEDULE.
PIPE UNION ABOVE TOP OF
TANKS (TO FACILITATE
REMOVAL)
PROVIDE THERMOMETER
IN TEE FITTING (TYPICAL)
140 DEGREE F HOT WATER
TO THERMOSTATIC MIXING
VALVE
PROVIDE AUTOMATIC
VACUUM RELIEF VALVE
ABOVE TOP OF WATER
HEATER
PROVIDE HARD COPPER PIPING AT WATER HEATER CONNECTIONS
FROM COLD WATER
SUPPLY TO WATER
HEATER, WITH NO
CHECK VALVES
INTERVENING
WELDED STEEL
EXPANSION TANK
POLYPROYPLENE
LINING AND BUTYL
DIAPHRAGM, FDA
AND NSF APPROVED
FOR DOMESTIC
WATER SERVICE
INTEGRAL BASE FOR
FLOOR MOUNTING
4"
5"
5"
5"
18"
12" MIN
BOTTOM
FINISHED FLOOR
CLEANOUT
TYPICAL SHUT-OFF VALVE
TYPICAL UNION
HIGH LEVEL ALARM
SECOND PUMP ON
FIRST PUMP ON
PUMPS OFF
CONTROL PANEL. REFER TO
FLOOR PLAN FOR LOCATION.
WIRING CONNECTIONS TO
PANEL AND WIRING
CONNECTIONS TO FLOATS
AND PUMPS IS BY ELECTRICAL
CONTRACTOR.
GROMMET AT WIRE
PENETRATION.
STEEL PLATE COVER
BOLTED DOWN WITH
GAS-TIGHT GASKET, WITH
OPENINGS FOR VENT AND
OUTLETS. SEAL OPENINGS
AND CRACKS WITH SILICONE.
BASIN OF DIAMETER,
DEPTH, AND MATERIAL PER
SCHEDULE AND
SPECIFICATIONS.
TYPICAL TETHERED FLOAT
SWITCH FOR PUMP
CONTROL
SEWAGE EJECTORS PER
SPECIFICATIONS AND
SCHEDULE.
2"VENT; REFER TO FLOOR
PLAN FOR CONTINUATION.
SANITARY WASTE. REFER TO
FLOOR PLANS FOR INVERT
ELEVATION.
SEWAGE EJECTOR DISCHARGE
TO SANITARY. REFER TO
FLOOR PLAN FOR LOCATION.
COMBINE DISCHARGES FROM
BOTH PUMPS.
TYPICAL FULL FLOW
NON-CLOG CHECK VALVE.
ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT ACTUAL INSTALLATION
CONDITIONS. PIT EXCAVATION IS BY PLUMBING CONTRACTOR. LOCATE FLOATS AT ELEVATIONS
RECOMMENDED BY PUMP MANUFACTURER. LOCATE PIT WITHIN 12" OF AN INTERIOR NON-BEARING
PARTITION TO SUPPORT PIPES EXITING PIT AND ALLOW 36" ACCESS SPACE IN FRONT OF PIT.
COORDINATE PIT INSTALLATION NEAR AN EXTERIOR WALL FOR FOOTINGS / FOUNDATIONS DEPTHS.
LOCATE REMOTE CONTROL PANEL AS CLOSE AS POSSIBLE TO PIT. VERIFY EXACT ENTERING INVERT
ELEVATION PRIOR TO ORDERING BASIN.
NO SCALE
DUPLEX SEWAGE EJECTOR3
GAS SUPPLY TO WATER HEATERS
WITH GAS COCK, UNION WITH
GROUND JOINT, 6" LONG DIRT LEG,
AND REDUCER AT CONNECTION STUB
INSTALL ASME TEMPERATURE AND
PRESSURE RELIEF VALVE FURNISHED
WITH WATER HEATER
PROVIDE HARD COPPER RELIEF VALVE
DISCHARGE PIPE, FULL SIZE OF VALVE
OUTLET. TERMINATE OVER
APPROVED RECEPTOR WITH AIR GAP
PER CODE
3"
3"
3"
12"
6" MIN
BOTTOM
FINISHED FLOOR
CLEANOUT
TYPICAL SHUT-OFF VALVE
TYPICAL UNION
HIGH LEVEL ALARM
SECOND PUMP ON
FIRST PUMP ON
PUMPS OFF
CONTROL PANEL. REFER TO
FLOOR PLAN FOR LOCATION.
WIRING CONNECTIONS TO
PANEL AND WIRING
CONNECTIONS TO FLOATS
AND PUMPS IS BY ELECTRICAL
CONTRACTOR.
GROMMET AT WIRE
PENETRATION.
STEEL PLATE COVER
BOLTED DOWN WITH
GAS-TIGHT GASKET, WITH
OPENINGS FOR VENT AND
OUTLETS. SEAL OPENINGS
AND CRACKS WITH SILICONE.
BASIN OF DIAMETER,
DEPTH, AND MATERIAL PER
SCHEDULE AND
SPECIFICATIONS.
TYPICAL TETHERED FLOAT
SWITCH FOR PUMP
CONTROL
SUMP PUMPS PER
SPECIFICATIONS AND
SCHEDULE.
2"VENT; REFER TO FLOOR
PLAN FOR CONTINUATION.
STORM LINE. REFER TO
FLOOR PLANS FOR INVERT
ELEVATION.
SUMP PUMP DISCHARGE TO
STORM. REFER TO FLOOR
PLAN FOR LOCATION.
COMBINE DISCHARGES FROM
BOTH PUMPS.
TYPICAL FULL FLOW
NON-CLOG CHECK VALVE.
ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT ACTUAL INSTALLATION
CONDITIONS. PIT EXCAVATION IS BY PLUMBING CONTRACTOR. LOCATE FLOATS AT ELEVATIONS
RECOMMENDED BY PUMP MANUFACTURER. LOCATE PIT WITHIN 12" OF AN INTERIOR NON-BEARING
PARTITION TO SUPPORT PIPES EXITING PIT AND ALLOW 36" ACCESS SPACE IN FRONT OF PIT. DO NOT
INSTALL PIT NEAR AN EXTERIOR WALL BECAUSE OF INTERFERENCE WITH FOOTINGS / FOUNDATIONS.
LOCATE REMOTE CONTROL PANEL AS CLOSE AS POSSIBLE TO PIT. VERIFY EXACT ENTERING INVERT
ELEVATION PRIOR TO ORDERING BASIN.
NO SCALE
DUPLEX SUMP PUMP5
36" DIA
ELEVATOR SHAFT WALL
SHUT-OFF VALVE
EXPOSED 2" SUMP PUMP
DISCHARGE PIPE SHALL BE
SCHEDULE 40 GALVANIZED
STEEL WITH MALLEABLE IRON
FITTINGS
FIRST FLOOR SLAB
COUPLING
2" SUMP PUMP DISCHARGE
SHALL BE SCHEDULE 40 PVC
WITH SOCKET WELD FITTINGS.
DISCHARGE INTO INDIRECT
WASTE RECEPTOR, WITH AIR
GAP, WHERE SHOWN ON
FLOOR PLAN
SEAL WALL PENETRATION
WATER-TIGHT
DUPLEX SUMP PUMP
1. A WEIL PUMP COMPANY DUPLEX SUBMERSIBLE 1.25" DISCHARGE SUMP PUMP, MODEL
1408 SHALL BE FURNISHED AS A COMPLETE UNIT, AS SUPPLIED BY CULLEN ASSOC., INC.
(732-988-9600) .
2. PUMPS SHALL BE HERMETICALLY SEALED DRY RUN TYPE WITH EPOXY ENCAPSULATION
WHICH IS NON-AGING, MOISTURE, ACID AND ALKALI RESISTANT PERMITTING PUMPS TO
OPERATE WITHOUT OVERHEATING AT A LOW OR NO WATER LEVEL.
3. PUMPS SHALL BE SUBMERSIBLE TYPE, CAST IRON CONSTRUCTION, BRONZE SEMI-OPEN
TYPE IMPELLER, HEAVY DUTY MECHANICAL SEAL, 300 SERIES STAINLESS STEEL SHAFT,
(2) DOUBLE SEALED BALL BEARINGS, STAINLESS STEEL SELF-CLEANING SUCTION
STRAINER, 15' OF NEOPRENE JACKETED POWER CABLE
4. PUMPS TO HAVE A CAPACITY OF 30 GPM AT A TOTAL DYNAMIC HEAD OF 20 FEET. PUMP
TO HAVE CURVE CHARACTERISTIC SO AS NOT TO OVERLOAD THE 1/3 HP MOTOR AT ANY
POINT THROUGHOUT ITS ENTIRE RANGE.
5. MOTORS TO BE 1/3 HP, 1 PHASE, 60 HERTZ, 115 VOLTS, 1750 RPM, HOUSED IN AIR FILLED,
WATERTIGHT CAST IRON MOTOR SHELL WITH THE WINDINGS HAVING CLASS "F"
INSULATION, NEMA-6 AND PRE-LUBRICATED DOUBLE SEALED BEARINGS. OIL FILLED
MOTORS OR SLEEVE TYPE BEARINGS ARE NOT ACCEPTABLE.
6. PUMP CONTROL TO BE VIA A DUPLEX WEIL PUMP CONTROL PANEL MODEL 8158 HAVING
MOUNTED AND WIRED WITHIN A NEMA-1 ENCLOSURE: TWO COMBINATION MANUAL
DISCONNECTS AND MOTOR CIRCUIT PROTECTORS, ADJUSTABLE AMBIENT COMPENSATED
BI METALLIC THERMAL OVERLOADS WITH RESETS, TWO MAGNETIC CONTACTORS, TWO
HAND-OFF AUTOMATIC SELECTOR SWITCHES WITH RUN LIGHTS, ONE CONTROL CIRCUIT
TRANSFORMER, ONE ELECTRIC PUMP ALTERNATING RELAY, ONE HIGH WATER ALARM
LIGHT, BELL, SILENCE PUSH-BUTTON AND AUXILIARY ALARM DRY CONTACT. A NUMBERED
AND WIRED TERMINAL STRIP SHALL BE PROVIDED IN THE PANEL TO ACCEPT (4) LEVEL
SENSING FLOAT SWITCHES LOCATED IN THE WET WELL TO PROVIDE LEAD-LAG
AUTOMATIC PUMP OPERATION, AS WELL A HIGH WATER ALARM SIGNAL.
PROVIDE A 36" DIAMETER X 78" DEEP FIBERGLASS BASIN WITH ANTIFLOATATION FLANGE
AS SHOWN ON THE PLANS WITH INLET OPENING AS REQUIRED. THE BASIN SHALL BE
SUPPLIED WITH MATERIALS FOR FIELD MOUNTING AN INLET OPENING, VENT OPENING AND
TWO SIDE DISCHARGE OPENINGS AND CONTROLS AS REQUIRED. THE BASIN COVER
SHALL BE STEEL AND HAVE A HINGED ACCESS DOOR OPENING FOR TWO PUMP
REMOVALS.
8. PROVIDE CHECK AND GATE VALVES ON THE DISCHARGE OF EACH PUMP. COMPLETE
THE PIPING AS SHOWN AND CLEAN THE BASIN OF ALL DEBRIS BEFORE STARTING PUMPS
INTO OPERATION.
CHECK VALVE (TYPICAL)
SHUT-OFF VALVE (TYPICAL)
COLD WATER SUPPLY TO WATER HEATER
COLD WATER TO EXPANSION TANK
RECIRCULATION PUMP WITH
UNION CONNECTIONS, SHUT-OFF
VALVE, ON / OFF SWITCH AND
STRAINER UPSTREAM, CHECK VALVE
AND SHUT-OFFVALVE DOWNSTREAM
SUBMERSIBLE SEWAGE PUMP
FURNISH AND INSTALL, WHERE SHOWN ON THE PLANS, ONE WEIL PUMP COMPANY INC.
(732-988-9600) DUPLEX SUBMERSIBLE SEWAGE GRINDER PUMP FOR INSTALLATION ON A
2613 REMOVAL SYSTEM.
PUMPS SHALL BE WEIL SERIES 2436 SUBMERSIBLE GRINDER TYPE, 2" DISCHARGE FOR
SEWAGE SERVICE AND EACH PUMP SHALL BE RATED TO PROVIDE 35 GPM AT 19 FT. TDH.
THE SUBMERSIBLE PUMP SHALL BE CONSTRUCTED OF CLOSE GRAINED HIGH DENSITY
CAST IRON AND SHALL HAVE A 3" SUCTION AND 2" DISCHARGE.
THE PUMP SHALL INCLUDE A GRINDER ASSEMBLY LOCATED ON THE SUCTION SIDE OF
THE PUMP IMPELLER. THE CUTTER SHALL BE CAPABLE OF GRINDING ALL MATERIALS
NORMALLY FOUND IN DOMESTIC SEWAGE. THE CUTTER AND SHREDDING RING
ASSEMBLY MACERATES SOLIDS INTO A SLURRY AND DISCHARGES TO THE PUMP
IMPELLER. THE CUTTER AND SHREDDING RING SHALL BE MADE FORM 17-4PH SUPER
HARD CORROSION RESISTANT STAINLESS STEEL THIS ASSEMBLY SHALL LEAVE NO
EXPOSED SHAFT TO PERMIT PACKING OF SOLIDS. THE SHREDDING RING SHALL BE FIELD
REVERSIBLE TO PROVIDE NEW CUTTING EDGES TO DOUBLE THE LIFE
PUMP MOTORS SHALL BE VERTICAL, NEMA-6 AND NOT MORE THAN 1 HP, 3 PHASE, 60
CYCLE, 208 VOLTS, 1750 RPM. MOTOR SHALL BE AIR FILLED, HERMETICALLY SEALED. OIL
FILLED MOTOR SHELLS SHALL NOT BE CONSIDERED EQUAL. MOTOR END BELL SHALL BE
DESIGNED AS A TERMINAL BOX AND SEPARATED FROM THE MOTOR SHELL BY A
COMBINATION BEARING SUPPORT AND INSPECTION PLATE. MOTORS SHALL BE HOUSED
IN A WATERTIGHT CAST IRON SHELL WITH CLASS F INSULATION WITH PERMANENTLY
LUBRICATED UPPER AND LOWER BALL BEARINGS. MOTOR SHAFT SHALL BE 300 SERIES
STAINLESS STEEL. MOTORS USING SLEEVE TYPE BEARINGS, CARBON STEEL SHAFTS OR
MOTORS REQUIRING WATER COOLING JACKETS SHALL BE CONSIDERED EQUAL.
CONTROLS SHALL BE WEIL SERIES 8230 SUBMERSIBLE LIQUID LEVEL CONTROLS.
PROVIDE (4) LEVEL SENSING SWITCHES WITH 20' CORDS MOUNTED ON STAINLESS STEEL
PIPE AND COVER BRACKET. SYSTEM SHALL PROVIDE ALL PUMPS OFF, LEAD PUMP
OPERATION ALONG WITH ALTERNATION, TWO PUMP EMERGENCY PROTECTION AND HIGH
WATER ALARM CONDITION.
THE EQUIPMENT WILL INCLUDE A NEMA-1 INDOOR DUPLEX CONTROL PANEL MODEL
BF-400 IN CABINET WITH HINGED DOOR, FOR WALL MOUNTING AS SHOWN ON PLANS. THE
CONTROL PANEL WILL HAVE MOUNTED AND WIRED WITHIN TWO CIRCUIT BREAKER
DISCONNECT SWITCHES, TWO STARTERS WITH OVERLOAD PROTECTION, TWO PUMP
RUNNING LIGHTS, TWO HAND-OFF-AUTOMATIC SELECTOR SWITCHES, ONE ALTERNATING
LEAD LAG RELAY, ONE NUMBERED AND WIRED TERMINAL STRIP, HIGH WATER ALARM
LIGHT, BELL, SILENCE SWITCH AND AUXILIARY DRY CONTACT.
PROVIDE A 36" DIAMETER X 72" DEEP FIBERGLASS BASIN WITH ANTIFLOATATION FLANGE
AS SHOWN ON THE PLANS WITH INLET OPENING AS REQUIRED. THE BASIN COVER SHALL
BE STEEL AND HAVE OPENINGS FOR TWO PUMP REMOVALS, AND CONTROLS. ALL
CONNECTIONS PENETRATING THE COVER TO BE MADE GAS TIGHT.
THE CONTRACTOR SHALL FURNISH AND INSTALL IN THE DISCHARGE LINE OF THE DUPLEX
PUMPING SYSTEM A WEIL PUMP CO. MODEL 2616 DUPLEX PUMP CHECK/ISOLATION
VALVE. THE ASSEMBLY SHALL CONSIST OF TWO BALL CHECK VALVES AND ONE PLUG
VALVE. THE UNIT ASSEMBLY SHALL CONSIST OF TWO BALL CHECK VALVES AND ONE
PLUG VALVE. THE UNIT ASSEMBLY SHALL HAVE FOUR CONTROL SEQUENCES
CONSISTING OF: (1) NORMAL OPERATION WITH PUMP "A" AND "B" OPEN TO THE
DISCHARGE LINE, (2) PUMP "A" ISOLATED AND PUMP "B" OPEN TO THE DISCHARGE LINE,
(3) PUMP "B" ISOLATED AND PUMP "A" OPEN TO DISCHARGE LINE, (4) PUMP "A" & "B"
ISOLATED FROM THE DISCHARGE LINE. WHEN EITHER OR BOTH PUMPS ARE ISOLATED
THE DESIGN OF THE ASSEMBLY SHALL BE ALLOW THE SERVICING OF THE INDIVIDUAL
CHECK VALVES OR THE PUMPS.
36"
DIA
78"
72"
ON / OFF
SWITCH
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING:
DETAILS
SHEET 1 OF 2
P6.01
AH
TRAP PRIMER
VALVE
CHECK
VALVE
SEAL
SEWER GAS
WATER
TRAP
VACUUM
BREAKER
PORT
THE PRIMING VALVE MUST
HAVE A MINIMUM
ELEVATION OF 12" INCHES
ABOVE
THE FINISHED FLOOR
PIPING ARRANGEMENT SHOWN IS SCHEMATIC: ADJUST TO SUIT FIELD
CONDITIONS. PROVIDE TWELVE FEET OF SOFT COPPER TUBE ABOVE FLOOR FOR
CONNECTION TO TRAP PRIMER TO BE LOCATED ABOVE CEILING.
INSTALL TRAP PRIMER
LINE(S) DOWNSTREAM OF
TRAP PRIMER OR
DISTRIBUTION UNIT USING
1/2" SOFT COPPER TUBING.
INSTALL WITHOUT KINKS,
AND SLOPE CONTINUOUSLY
TOWARDS FLOOR DRAIN.
IF PIPE IS BELOW FLOOR
SLAB ON GRADE, PROVIDE
1/2" ELASTOMERIC
INSULATION FROM PRIMER
CONNECTION TO 1" ABOVE
FLOOR SLAB.
CONCEAL PIPE(S) IN
PARTITION OR CHASE IN
FINISHED AREAS. TRAP
PRIMER AND PIPES MAY BE
INSTALLED EXPOSED IN
UNFINISHED, NON-PUBLIC
AREAS.
PROVIDE FLOOR DRAIN
BODY OR P-TRAP WITH
THREADED TRAP PRIMER
CONNECTION. PROVIDE
SWEAT TO THREADED
ADAPTER. BRAZE JOINT
BELOW FLOOR SLAB ON
GRADE.
1/2"9' O.C.1-1/4" TO 2"
2-1/2" TO 4"10' O.C.1/2"
ROD (SIZE AS REQUIRED)
PIPE
CLEVIS HANGER
LINES UP TO AND INCLUDING 4" IN SIZE.
HANGING DETAILS SHALL BE SUBMITTED TO
HANGER SPACING SHALL BE AS FOLLOWS:
THE ABOVE DETAIL SHALL BE USED ONLY FOR
STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL.
INCREASE CLEVIS HANGER SIZE TO ALLOW FOR
INSULATION OF THOSE LINES REQUIRING INSULATION.
FOR INSULATED LINES USE STEEL PIPE SHIELDS
1/2" TO 1"
PIPE SIZE
5.
4.
7' O.C.
MAX. HANGER SPACING
NOTES:
AT HANGER POINTS.
3.
2.
1.
3/8"
INSULATION
JOIST
WOODEN
BOLT THROUGH
JOIST FLOOR ABOVE OR ROOF
DOUBLE LOCK-NUT &
WASHER (TYPICAL)
WOODEN JOIST (TYPICAL)
PIPE HANGER
BOLT THROUGH JOIST (TYPICAL)
2"x2"x90 DEGREE
ANGLE (TYPICAL)
HOT WATER RECIRCULATION BRANCH UNION
FLOW CONTROL VALVE (FCV); REFER TO FLOOR
PLANS FOR PIPE SIZE.
TYPICAL FULL-PORT BALL
TYPE SHUT-OFF VALVE
STRAINER
CHECK VALVE
PIPE INSULATION
SECURE WITH ADHESIVE
EXPOSED VALVES AND FITTINGS
TYPICAL AT ALL JOINTS.
AND OUTER HOLDING BAND
OR USE SELF-SEALING LAPS
SECURE WITH ADHESIVE
MITERED FITTING
FIRE RETARDANT JACKET
REQUIRED PIPE INSULATION THICKNESS.
WRAP WITH 1 INCH THICK, 1 POUND DENSITY TO
VAPOR SEAL COLD WATER, CHILLED WATER
BUTT STRIP AT JOINTS.
AND STORM WATER PIPING.
SECURE WITH WIRE OR TAPE.
CONCEALED VALVES AND FITTINGS
FINISH COAT OF MASTIC
FIBERGLASS
SECTIONAL
INSULATION
PREMOLDED FITTING
3"
PIPE INSULATION.
COAT OF MASTIC
PREMOLDED FIBERGLASS OR RADIAL MITERED
SKIM COAT OF INSULATION CEMENT.
WRAP WITH FIBERGLASS REINFORCING CLOTH.
OVERLAP 2 INCHES ON PIPE INSULATION.
ALL SEALS AND LAPS
AT TOP.
SEALING LAP.
THREADED ROD
CLEVIS HANGER
1/2" CLEAR MAXIMUM
CONCEALED PIPING
FLUSH WITH FINISHED
TERMINATE SLEEVE
INSULATION
WALL SURFACES
HANGER, ROD & INSERT
UP TO 3"
4" TO 6"
WITHOUT INCOMPRESSIBLE INSULATING
WITH INCOMPRESSIBLE INSULATING
PIPE
DIAMETER
PIPE
DIAMETER
UP TO 3"
DOUBLE LOCKNUTS
NOTE:
6"
5"
4"
USSG
16
16
16
18
THICKNESS
SHIELD
SHIELD
USSG
THICKNESS
18
16
SHIELD
LENGTH
18"
21"
15"
12"
BLOCK AT HANGER
SHIELD
LENGTH
BLOCK AT HANGER
6"
8"
ZINC CHROMATE PRIMER
PRIOR TO INSTALLATIONGALVANIZED
METAL SHIELD
SHALL BE DIPPED IN
STANDARD WEIGHT STEEL PIPE
SLEEVE OF SIZE TO PASS PIPE
ANNULAR SPACE BETWEEN PIPE
AND SLEEVE TO BE PACKED WITH
(UL 263).
(TYP FOR EACH SIDE).
FINISHED ESCUTCHEON PLATE
FINISHED WALL SURFACE.
PIPING EXPOSED TO VIEW
FLUSH AGAINST WALL AND OF SIZE
TO COMPLETELY COVER OPENING
TO THE REQUIREMENTS OF ASTM
E814 (UL 1479) AND ASTM 119
UL/FM APPROVED AND TESTED
SEAL OR CAULK SLEEVES THRU
MANNER.
FIRE WALLS IN A SMOKE TIGHT
FINISHED WALL
LEAD
SURFACE
TIGHTLY PACKED
OAKUM & POURED
SEAL SLEEVE WITH
COAT EXTERIOR
SURFACES WITH
CONTINUOUS WELD
TAR COMPOUND
NOTES:
1. PIPE SLEEVE FOR EXTERIOR WALL ABOVE OR BELOW GRADE.
EXTERIOR WALLS
DURING WALL CONSTRUCTION
STANDARD WEIGHT STEEL
PIPE SLEEVE INSTALLED
CENTER PIPE IN SLEEVE
SEALING AND ANCHORING COLLAR
MASTIC OR ASPHALT
SEAL WATERTIGHT WITH
NOT TO SCALE
PIPE PENETRATION THRU FIRE RATED WALL5
NOT TO SCALE
PIPE, VALVE AND FITTING INSULATION DETAIL 11
NOT TO SCALE
TYPICAL INSULATED PIPE SUPPORT6
NOT TO SCALE
TYPICAL PIPE SLEEVES THRU WALL2 NOT TO SCALE
PIPE PENETRATION THRU FOUNDATION WALL3
NOT TO SCALE
TRAP PRIMER DETAIL1
NOT TO SCALE
TYPICAL HANGER DETAILS4
NOT TO SCALE
WOOD JOIST HANGER DETAILS7
NOT TO SCALE
TRAP PRIMER INSTALLATION8
NOT TO SCALE
FLOW CONTROL VALVE ASSEMBLY9
REFER TO SPECIFICATIONS, SCHEDULES, AND NOTES FOR MORE INFORMATION. MAKE
CONNECTIONS AND PROVIDE INSTALLATION PER MANUFACTURER'S RECOMMENDATIONS.
ARRANGEMENT SHOWN IS SCHEMATIC: PROVIDE REDUCERS AND ADAPTERS AS REQUIRED.
NO SCALE
EXTERIOR AREAWAY DRAIN10
GRASS AREA: EXCAVATE AS
REQUIRED AND PATCH TO MATCH
EXISTING
PROVIDE 20"x20"x8" THICK 3000 PSI
CLASS "C" CONCRETE PAD, REINFORCED
WITH 6x6x1/4 WIRE MESH. TROWEL
SMOOTH AND EDGE.
SURROUND JOINT WITH CONCRETE
HORIZONTAL STORM DRAIN, SIZE AS
SHOWN ON PLAN, AND TYPE OF PIPE PER
SPECIFICATIONS.
DIRECTION OF FLOW
AREAWAY DRAIN SET IN
CONCRETE PAD
RISER SHALL BE CAST IRON,
SAME SIZE AS SEWER UP TO
4" MAXIMUM, OF LENGTH AS
REQUIRED BY DEPTH OF
SEWER.
PROVIDE CAST IRON LONG
SWEEP AT END OF LINE, ENTER
TOP OF PIPE.
TO SUMP PUMP
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:13pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
PLUMBING
DETAILS
SHEET 2 OF 2
P6.02
AH
M. MECHANICAL DRAWING LIST
M0.GENERAL
M0.01 GENERAL NOTES & SYMBOL LIST
M2.BUILDING PLANS
M2.00 LOWER LEVEL PLAN
M2.00P LOWER LEVEL PLAN - PIPING
M2.01 GROUND FLOOR PLAN
M2.01P GROUND FLOOR PLAN - PIPING
M2.02 SECOND FLOOR PLAN
M2.02P SECOND FLOOR PLAN - PIPING
M2.03 THIRD FLOOR PLAN
M2.03P THIRD FLOOR PLAN - PIPING
M2.04 FOURTH FLOOR PLAN
M2.04P FOURTH FLOOR PLAN - PIPING
M2.05 ROOF PLAN
M4.DIAGRAMS
M4.01 RISER DIAGRAMS SHEET 1 OF 4
M4.02 RISER DIAGRAMS SHEET 2 OF 4
M4.03 RISER DIAGRAMS SHEET 3 OF 4
M4.04 RISER DIAGRAMS SHEET 4 OF 4
M5.SCHEDULES
M5.01 SCHEDULES SHEET 1 OF 2
M5.02 SCHEDULES SHEET 2 OF 2
M6.DETAILS
M6.01 DETAILS SHEET 1 OF 5
M6.02 DETAILS SHEET 2 OF 5
M6.03 DETAILS SHEET 3 OF 5
M6.04 DETAILS SHEET 4 OF 5
M6.05 DETAILS SHEET 5 OF 5
D DRAIN LINE
PIPING
STRAINER 'Y' TYPE WITH BLOWDOWN VALVE
UNION
PROVIDE ACCESS SPACE FOR SERVICING ALL MECHANICAL EQUIPMENT INCLUDING
PROVIDE VOLUME DAMPERS AT EACH LOW PRESSURE SUPPLY, RETURN OUTDOOR AIR AND
FIRST 20'-0" OF ALL LOW PRESSURE SUPPLY AND RETURN DUCTWORK FROM FCU UNITS
ALL SUPPLY AIR DUCTWORK IN SPACES WHICH HAVE EXPOSED DUCTWORK SHALL HAVE
PROVIDE COMPLETE PIPING SPECIALITIES, DAMPERS AND INSTRUMENTATION FOR EACH PIECE
OF EQUIPMENT AS PER DRAWINGS, SPECIFICATIONS.
3.
PROVIDE SIGHT-PROOF BACK-SHEET BEHIND RETURN AIR GRILLES.
MOTORS FOR CEILING FANS, HEATING COILS, VALVES AND FILTERS
8.
7.
EXHAUST DUCT BRANCH TAKE-OFF.
5.
6.
4.
SHALL BE 1" ACOUSTICALLY LINED, UNLESS OTHERWISE NOTED.
ACOUSTICAL LINING.
GENERAL NOTES:
1.
2.
PIPE DOWN
PIPE UP
DIRT POCKET
CW
A
COLD WATER MAKE UP LINE
ARROW INDICATES DIRECTION OF FLOW
PIPE ANCHOR
AIR LINE
SUPPLY AIR OUTLET - 3, 2 & 1 WAY THROW
U.H.UNIT HEATER
S.F. / SF
TO
T.G.
TR.R
TYP.
TD
TR.G.
S.P.
S.A.D.
TOP GRILLE
TRANSFER GRILLE
TRANSFER REGISTER
TRANSFER OPENING
TYPICAL
TRANSFER DUCT
SPILL AIR DAMPER
STATIC PRESSURE
SQUARE FEET
DUCT SMOKE DETECTOR
(XXXX) - INDICATES VOLUMETRIC FLOW RATE (CFM)
SLOPING RISE IN DUCT IN DIRECTION OF ARROW
SLOPING DROP IN DUCT IN DIRECTION OF ARROW
DUCT SIZE - FIRST SIZE INDICATES PLAN SIZE
SPIN-IN FITTING WITH VOLUME DAMPER
DUCT SECTION UNDER NEGATIVE PRESSURE
DUCT SECTION UNDER POSITIVE PRESSURE
TRANSFER DUCT WITH ACOUSTIC LINING
CEILING DIFFUSERC.D.
N.T.S.
O.A.I.
O.A.D.
R.A.D.
M.V.
MIN / MAX
M.B.H.
G.C.
HWS / HWR
RETURN AIR DAMPER
OUTSIDE AIR INTAKE
MANUAL AIR VENT
OUTSIDE AIR DAMPER
NOT TO SCALE
GENERAL CONTRACTOR
THOUSAND BTU'S PER HOUR
MINIMUM / MAXIMUM
HOT WATER SUPPLY / HOT WATER RETURN
F.F.
F.M.S
F.C.
EUH
E.A.D.
F.D.
C.U.
DEF
CV
C.U.H.
CFM
C.G.
FLEXIBLE CONNECTION
ELECTRIC UNIT HEATER
EXHAUST AIR DISCHARGE
FIRE DAMPER AND ACCESS DOOR
FLOW MEASURING STATION
FINISHED FLOOR
CONDENSING UNIT
CUBIC FEET OF AIR PER MINUTE
CONSTANT VOLUME
CABINET UNIT HEATER
DRYER EXHAUST FAN
CEILING GRILLE
U UNDERCUT DOOR
SUPPLY AIR OUTLET, 4 WAY
SOUND LINING IN DUCTWORK
RETURN AIR REGISTER
A.D.
L
M
MOTORIZED DAMPER
ELBOW WITH TURNING VANES
LOUVER DOOR
M.D.
ACCESS DOOR IN DUCT
DUCT FLEXIBLE CONNECTION
VOLUME DAMPER
MECHANICAL SYMBOL LIST
ABBREVIATIONS
CONT.
C.C.
ATC
A.L.
A.F.F
A.V.
A.D.
AC
AUTOMATIC TEMPERATURE CONTROLS
ABOVE FINISHED FLOOR
AUTOMATIC AIR VENT
ACOUSTICAL LINING
CONTINUOUS
COOLING COIL
AIR CONDITIONING UNIT
ACCESS DOOR
18 x 12
18x12 (2000)
D
R
DUCTWORK
B BOILER
EF EXHAUST FAN
TEF TOILET EXHAUST FAN
PROVIDE CONDENSATE DRAIN LINE FROM EACH FCU UNIT. CONDENSATE DRAIN LINES
SHALL DRAIN TO FLOOR DRAIN AS INDICATED.
9.DUCTWORK SIZING:
DUCTWORK SHALL BE DESIGNED / SIZED AT 0.07 INCHES W.G. PRESSURE DROP PER 100
FEET OF DUCT, AND VELOCITY SHALL NOT EXCEED 800 FPM.
10.PIPE SIZES AND REQUIRED REFRIGERANT CHARGES SHALL BE VERIFIED WITH MANUFACTURER BASED
ON FINAL ROUTING AND LENGTH OF PIPING.DESIGN CRITERIA:
1. OUTSIDE DESIGN CONDITIONS:
LOCATION:
LATITUDE:
WINTER:
SUMMER::%7)
2. INSIDE DESIGN CONDITIONS:
DRY BULB TEMPERATURE (SUMMER):)
RELATIVE HUMIDITY (SUMMER):
DRY BULB TEMPERATURE (WINTER):
'%7)
'%7)
)
50%
)
RELATIVE HUMIDITY (WINTER):UNCONTROLLED
)
AHU AIR HANDLING UNIT
FCU FAN COIL UNIT
ACCU AIR COOL CONDENSING UNIT
EWH ELECTRIC WALL HEATER
D DRAIN
KEF KITCHEN EXHAUST FAN
HC HEATING COIL
BS BRANCH SELECTOR
DX DIRECT EXPANSION
RH REHEAT COIL
OA OUTSIDE AIR
ET EXPANSION TANK
CFG CEILING (FILTER) GRILLE
RS / RL / HG REFRIGERANT SUCTION, REFRIGERANT LIQUID, HOT GAS
BG BREAK GLASS
NG NATURAL GAS
CO CARBON MONOXIDE
PNL PANEL (SNOW MELT)
VFD VARIABLE FREQUENCY DRIVE
SR SUPPLY / SIDEWALL REGISTER
GFP GLYCOL FEED AUTO FEED PUMP UNIT
T
NG
CO
TEMPERATURE SENSOR (THERMOSTAT)
NATURAL GAS DETECTOR
CARBON MONOXIDE DETECTOR
SD
TS TEMPERATURE SENSOR (THERMOSTAT)
PV POWER VENTILATOR
FIRE DAMPER WITH ACCESS DOOR
FIRE SMOKE DAMPER
BCU BLOWER COIL UNIT
AFR ABOVE FINISHED ROOF
ITHACA, NEW YORK
WMS WIRE MESH SCREEN
CIRCUIT SETTER
WHERE ACOUSTICAL LINING IS SPECIFIED ON THE DRAWINGS OR IN THE SPECIFICATIONS,
THE DUCT SIZES SHALL BE INCREASED TO ACCOMMODATE THE THICKNESS OF
ACOUSTICAL LINING.
BOILER BREAK GLASSBG
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:06pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
GENERAL NOTES
& SYMBOL LIST
M0.01
GES
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL
KEYED NOTES
4" CONCRETE PAD. (TYP.)
PROVIDE RETURN GRILLE IN CEILING WITH FILTERS.
TYPICAL FOR ALL.
PROVIDE FCU WITH OPEN RETURN AND WMS.
PROVIDE 8x4 LOUVER, COORDINATE LOUVER
LOCATION WITH THE ARCHITECT.MIN0.1 SQ.FT FREE
AREA.
PROVIDE 26 GAUGE SUB-DUCT. SUB-DUCT EXTENDS
´83,16,'((;+$8675,6(57<3,&$/)25
TOILET RISERS.
ELEVATOR HOIST-WAY COOLING INLET. 3 HOUR
COMBINATION FIRE AND SMOKE DAMPER, 10x10,
120V ACTUATOR, AND INLET GRILLE. COORDINATE
EXACT LOCATION WITH ELEVATOR EQUIPMENT
INSTALLER. PROVIDE ACCESS DOOR.
DENOTES RISER IDENTIFICATION NUMBER. SEE
DRAWING M4.01
1
2
3
4
5
6
TEF-1
1'-3"W X 4'-2"H
LOUVER
NEEDED MIN
3.5 SQ.FT
FREE AREA
INTAKE AIR
PLENUMCONG
CO
NATURAL
GAS
SENSOR
NATURAL
GAS
SENSOR
CD
18X18
(75)
AS-1
16X10 UP
14X10 UP
6x6
10X10 UP
UH-B
CO
MONITORING
PANEL
AHU-1
BOILER BREAK GLASS
T
T
T
T
FCU-B
FCU-B
CFG
18X18
1
FSD
6
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
EF-3
TEF-1
CD
9x9
(50)
8X6
8X6
20X8
SR
10x6
(200)
SR
10x6
(200)
U
OA PLENUM
40"L X 34"W X 24"H
EWH-A
5" FLUE UP
TO ROOF
(B-1, B-2)
4" WATER
HEATER FLUE
UP TO ROOF
(TYP 2)14X620X6
W.M.S
(450)
ET-1
B-2
B-1
VFD VFD
1
T
MER
EXH.
UH-A
GFP-1
14X10
16X10
P-HW-1
P-HW-2
VFD PANELS TO
BE MOUNTED
ON THIS WALL
ET. TO BE
LOCATED
BELOW THE
DUCTS
4
5
1
6X6
6X6
3
2
U
SUPLEX
SEWAGE
EJECTOR
GWHGWH
BG
M
TEF-1
FCU-B
CFG
18X18
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
4
6X6
3
2
TEF-1
FCU-B
CFG
18X18
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
4
6X6
3
2
M
MCPCP CONSTANT AIR
VOLUME
CONTROL
PANEL
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:06pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
LOWER LEVEL
PLAN
M2.00
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 LOWER LEVEL FLOOR PLAN
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL
BS-1BS-1BS-1D
D
D
D
FCU-B HGRSRLHWRHWS
HWS & R
1-1/2" UPBS-1RS/RL/HG
ACCU 1-UP
RS/RL
ACCU 3-UP
FCU-B
FCU-B
1-1/4"
3/4"
COND.
1-1/4" UP
3/4"
3/4"DD
D
HWS & R
2" UP
3/4"
1"
3/4"
1"CONG
CO
NATURAL
GAS
SENSOR
NATURAL
GAS
SENSOR
P-HW-1
P-HW-2
AS-1
GFP-1
UH-B CO
MONITORING
PANEL
AHU-1
BOILER BREAK GLASS
UH-A
FCU-B
OA PLENUM
40"L X 34"W X 24"H
EWH-A
ET-1
B-2
B-1
1-1/2"
1-1/2"
1" TO
AHU1
3/4"
3/4"
1"
T
MER
EXH.
DIFFERENTIAL
PRESSURE
BYPASS
CIRCUIT
SETTER
1-1/2"
HC-B
HC-B
HC-B
HC-B3/4"HWRHWS3/4"
3/4"
3/4"
HG
RSRL
RS
RL
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:06pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
LOWER LEVEL
PLAN - PIPING
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 LOWER LEVEL FLOOR PLAN - PIPING
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
CD
9x9
(50)
SR
8x6
(130)
SR
8x6
(160)
CD
9x9
(25)
RG
10X10 UP
16X10 DN
10X10 UP
14X10 DN
6x6
6x6
10x6 RETURN
OPENING WITH
WMS ABOVE
CEILING
8x6
CD
18X18
(105)
8X6
1
4
3
CUH-A
1
2
3
5
4
2
10X10 UP&DN
8X6
8X6
8X6
8X6
20X8
CD
18X18
(105)
T
T
T
T
T
FCU-B
FCU-B
FCU-B
FCU-B
FCU-A
CFG
18X18
CFG
18X18
CFG
18X18
SR
10X6
(180)
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
SR
10x6
(200)
SR
10x6
(200)
TEF-1
TEF-1
TEF-1
TEF-1
TEF-1
CUH-A
EWH-A
EWH-A
16x6
UP5
4
3
4
3
6X6
6X6
6X6
T
AHU-1
(T)
6X6
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:06pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
GROUND FLOOR
PLAN
M2.01
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 GROUND FLOOR PLAN
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
BS-1
BS-1BS-1FCU-BBS-1D
D
D
D
HGRSRLHGRS
RL
HWRHWS
CUH-A
RS/RL/HG
ACCU 1-UP&DN
RS/RL
ACCU 3-UP&DN
D
BS-1HWS & R
2" UP
2" DN
HWS&R
1 1
2" DN
FCU-B
FCU-B
FCU-B
CUH-A
1"
3/4"
1-1/4"
3/4"
3/4"
3/4"
1" CND.
UP & DN
3/4"
3/4"
3/4"
3/4"DD
D
DD1"
HC-B
HC-B
HC-B
HC-A
HWRHWS3/4"
3/4"
3/4"
FCU-A
HC-B
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:06pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
GROUND FLOOR
PLAN - PIPING
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 GROUND FLOOR PLAN - PIPING
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
KEYED NOTES
5" FLUE UP TO ROOF AND DOWN TO BOILER.
4" FLUE UP TO ROOF AND DOWN TO WATER
HEATER
PROVIDE ALL RETURN IN CEILING WITH FILTERS.
TYPICAL FOR ALL.
PROVIDE FCU WITH OPEN RETURN AND WMS.
DENOTES RISER IDENTIFICATION NUMBER. SEE
DRAWING M4.01
1
2
3
4
T
4
3
T
T
T
RG6x6
6x6
8x6
SR
10x6
(160)
SR
12x6
(250)
10X8 UP
10X10 DN
10X8 UP
10X10 DN
1
8x6
W/WMS
16x6
UP
16x6
UP&DN
16x6
UP
16x6
UP
1
2
3
5
4
2
16x6
UP
10X10 UP&DN
30X8
10X6
8X6
8X6
T
FCU-D
FCU-B
FCU-B
FCU-B
FCU-B
CFG
18X18
CFG
18X18
CFG
18X18
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
8X6
CD
9x9
(50)
CD
6X6
(25)20X88X6
8X6SR
10x6
(175)
SR
10x6
(200)
TEF-1
TEF-1
TEF-1
TEF-1
TEF-1
CD
18X18
(105)
CD
18X18
(105)
SR
8x6
(150)
6X6
8X6 6X6
8X6 6X6
4
3 CFG
18X18
4
3
RA
SR
6x6
(75)
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:06pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
SECOND FLOOR
PLAN
M2.02
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 SECOND FLOOR PLAN
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
BS-1
BS-1FCU-D
BS-1D
D
D
FCU-BHGRSRLHG
RSRL
HWR
HWS
RS/RL/HG
ACCU 1-UP&DN
RS/RL
ACCU 3-UP&DN
BS-1D
BS-1HWS & R
2" UP
2" DN
1-1/4"
FCU-B
FCU-B
FCU-B
3/4"
1"
3/4"
1" CND.
UP & DN
3/4"
3/4"
3/4"
3/4"DDD
D
3/4"
HC-B
HC-B
HC-B
HC-B
HC-D
HWRHWSVERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:06pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
SECOND FLOOR
PLAN - PIPING
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 SECOND FLOOR PLAN - PIPING
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
KEYED NOTES
5" FLUE UP TO ROOF AND DOWN TO BOILER.
4" FLUE UP TO ROOF AND DOWN TO WATER
HEATER
PROVIDE ALL RETURN IN CEILING WITH FILTERS.
TYPICAL FOR ALL.
PROVIDE FCU WITH OPEN RETURN AND WMS.
DENOTES RISER IDENTIFICATION NUMBER. SEE
DRAWING M4.01
1
2
3
4
T
4
3
T
T
T
RG
6x6
6x6
8x6
8X6 UP
10X8 DN
8X6 UP
10X8 DN
1
8x68x6
W/WMS
16x6
UP&DN
16x6
UP&DN
16x6
UP&DN
16x6
UP&DN
1
2
3
5
16x6
UP&DN
4
2
10X10 UP&DN
CD
9x9
(50)
8X6
T
FCU-C
FCU-B
FCU-B
FCU-B
CFG
18X18
CFG
18X18
CFG
18X18
CFG
18X18
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
SR
8x6
(160)
SR
10x6
(200)
30X8
8X6
CD
9x9
(50)
CD
6X6
(25)8X6
8X6SR
10x6
(175)
SR
10x6
(200)
20X8
TEF-1
TEF-1
TEF-1
TEF-1
CD
18X18
(105)
CD
18X18
(105)SR
10x6
(175)
SR
10x6
(200)
SR
8x6
(150)
8X6
8X6 6X6
CD
6X6
(25)
8X6 6X6
8X6 6X6
20X8
4
3
4
3
RA
TEF-1
CD
12X12
(50)
FCU-B
4
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
THIRD FLOOR
PLAN
M2.03
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 THIRD FLOOR PLAN
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
FCU-BBS-1D
D
HGRSRLHG
RSRL
HWR
HWS
BS-1
FCU-C
RS/RL/HG
ACCU 1-UP&DN
RS/RL/HG
ACCU 2-UP
RS/RL
ACCU 3-UP&DN
BS-1BS-1D
D
D
HWS & R
1-1/4" UP
2" DN
FCU-B
FCU-B
FCU-B
1-1/4"
1" CND.
UP & DN
3/4"
3/4"
3/4"
3/4"
1"BS-1HC-B
HC-B
HC-B
HC-B
HC-C
HWRHWS3/4"
3/4"
3/4"
3/4"
3/4"
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
THIRD FLOOR
PLAN - PIPING
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 THIRD FLOOR PLAN - PIPING
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
SR
10x6
(200)
SR
12x6
(285)
CD
9x9
(50)
CD
9x9
(50)
16x6
DN
16x6
DN
16x6
DN
16x6
DN
T
T
T
T
DUCT UP
TO TEF-A
DUCT UP
TO TEF C
DUCT UP
TO TEF B
DUCT UP
TO TEF E
DUCT UP
TO TEF D
6x6
6x6
8x6
RG
T
SR
8x6
(160)
SR
10x6
(200)
CD
18X18
(200)
8X6 DN
8X6 DN
8x6
W/WMS
1
2
3
5
1
4
2
16x6
DN
CD
6X6
(25)
CD
6X6
(25)
10X10 UP&DN
DUCT UP
TO EF-2
30X8
30X8
8X68X6
20X88X6
8X6
KEYED NOTES
5" FLUE UP TO ROOF AND DOWN TO BOILER.
4" FLUE UP TO ROOF AND DOWN TO WATER
HEATER
PROVIDE ALL RETURN IN CEILING WITH FILTERS.
TYPICAL FOR ALL.
PROVIDE FCU WITH OPEN RETURN AND WMS.
DENOTES RISER IDENTIFICATION NUMBER. SEE
DRAWING M4.01
1
2
3
4
T
FCU-C
FCU-B
FCU-B
FCU-B
FCU-C
CFG
18X18
CFG
18X18
CFG
18X18
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
SR
10x6
(175)
CD
9x9
(50)
SR
10x6
(200)
CD
6X6
(25)
20X8
SR
10x6
(175)
SR
10x6
(200)
TEF-1
TEF-1
TEF-1
TEF-1
CD
18X18
(105)
CD
18X18
(105)
4
3
SR
8x6
(150)
8X6
8X6 6X6
8X8 6X6
8X6 6X6
CFG
18X18
4
3
CFG
18X18
4
3
TEF-1
RA
CD
12X12
(50)
M2M-204M
T.O. GYPSUM-CEMENT
UNDERLAYMENT - FOURTH
FLOOR
ELEV. + 773'-9"
T.O. METAL ROOF DECK
ELEV. + 783'-334"
R-4.5 R-4.2
3"RD
3"OD
20X8
FC-B
8X6
7'-6"
8'-85
8"
HC-B
CFG
EF-A
16X6
10X10
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
FOURTH FLOOR
PLAN
M2.04
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 FOURTH FLOOR PLAN
SCALE: 1/4"=1'-0"
0 4 8 FEET
2 SECTION A-A A
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
BS-1
BS-1BS-1BS-1FCU-C
BS-1D
D
D
HGRSRLHG
RSRL
3-WAY
AUTOMATIC
CONTROL
VALVE
(SEE DETAIL)
HWR
HWS
RS/RL/HG
ACCU 1-DN
RS/RL/HG
ACCU 2-DN
RS/RL
ACCU 3-DN
RS/RL/HG
ACCU 1
RS/RL
ACCU 3
RS/RL/HG
UP TO ACCU 2
D
D
D
D
D
D
HWS & R
1-1/4" DN
FCU-B
FCU-B
FCU-C
1-1/4"
1" CND.
DN
3/4"
3/4"
1"
A
3/4"
3/4"
D
HC-B
HC-B
HC-C
HC-B
HC-C
HWRHWS3/4"
3/4"
3/4"
3/4"
2
M-204P
FCU-B
T.O. GYPSUM-CEMENT
UNDERLAYMENT - FOURTH
FLOOR
ELEV. + 773'-9"
T.O. METAL ROOF DECK
ELEV. + 783'-334"
HOISTWAY
TOP OF CMU
1" HWS
1" HWR
RS/RL/HG
REF. PIPES
SPRINKLER
PIPE
6X6 SUPPLY
DUCT
3/4" CONDENSATE
RS/RL REF. PIPES
RS/RL/HG REF. PIPES
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
FOURTH FLOOR
PLAN - PIPING
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 FOURTH FLOOR PLAN - PIPING
SCALE: 1/4"=1'-0"
0 4 8 FEET
2 SECTION A-A
NOT TO SCALE
EXHAUST RISER DIAGRAM
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9ACCU-1
TEF-E
EF-1
TEF-D
TEF-B
TEF-C
ACCU-2
ACCU-3
ROOF
CURB
ROOF
CURB
EF-2
KEYED NOTES
5" FLUE FROM BOILER. PROVIDE ROOF SUPPORT,
FLUE PIPE EXTENDS TO 3 FEET ABOVE THE
HIGHEST STRUCTURE WITHIN 10 FEET
HORIZONTALLY. PROVIDE GUY WIRE SUPPORTS
FOR VERTICAL FLUE SECTIONS
4" FLUE FROM WATER HEATER. PROVIDE ROOF
SUPPORT, FLUE PIPE EXTENDS TO 3 FEET ABOVE
THE HIGHEST STRUCTURE WITHIN 10 FEET
HORIZONTALLY. PROVIDE GUY WIRE SUPPORTS
FOR VERTICAL FLUE SECTIONS
REFRIGERANT PIPES DOWN TO AHU IN MER
SIX REFRIGERANT PIPES DOWN TO FCU'S. SIZING
OF REFRIGERANT PIPES PER THE MANUFACTURER
RECOMMENDATIONS.
ALL EXHAUST FANS TO BE A MINIMUM OF 10 FEET
OF THE ROOF EDGE.
PROVIDE FLUE SUPPORTS ON ROOF FOR
HORIZONTAL FLUE SECTIONS. MOUNT MINIMUM 3'-0"
AFR.
EXHAUST FAN WITH AUTOMATIC DAMPER,
ACTUATOR AND THERMOSTAT. CONTROL WIRING
AND POWER FOR EXHAUST FAN, MOTORIZED
DAMPER AND THERMOSTAT BY ELECTRICAL
CONTRACTOR, THERMOSTAT SHALL BE PROVIDED
BY MECHANICAL CONTRACTOR. MOUNT
THERMOSTAT ON HOIST WAY WALL 4' BELOW MAIN
ROOF DECK. FAN AND DAMPERS SHALL BE
$&7,9$7(',)7+(7(03(5$785(5,6($%29()
1
2
3
4
5
6
7
1
2
3
4
5
6
7
GENERATOR
HG
RS
RL
RS
RL
TEF-A
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
ROOF PLAN
M2.05
GES
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 ROOF PLAN
ROOF
4TH FLOOR
3RD FLOOR
2ND FLOOR
TOILET
EF-A
50 CFM
50 CFM
200
CFM
LOWER
LEVEL FLOOR
FD
GRD FLOOR
50 CFM
16x6
16x6
16x6 16x6
NOT TO SCALE1RISER 1
PROVIDE 26 GAUGE
SUB-DUCT. SUB-DUCT
EXTENDS 22" UP
INSIDE EXHAUST RISER.
(TYP.FOR ALL)
KEYED NOTES
REFER TO DETAIL1 BELOW FOR CONSTANT PRESSURE AIR FLOW DIAGRAM FOR ALL
TEF EXHAUST FANS.
TOILET EXHAUST DUCT FROM CEILING MOUNTED TEF-1 IN INDIVIDUAL BATHROOMS.
REFER TO PLANS FOR AIR QUANTITIES.
1
2
2
TYP.
1
LOWER
LEVEL FLOOR
NOT TO SCALE2RISER 2
LOWER
LEVEL FLOOR
NOT TO SCALE3RISER 3
LOWER
LEVEL FLOOR
NOT TO SCALE4RISER 4
LOWER
LEVEL FLOOR
NOT TO SCALE5RISER 5
FD
ROOF
4TH FLOOR
3RD FLOOR
2ND FLOOR
50 CFM
50 CFM
200
CFM FD
GRD FLOOR
50 CFM
16x6
16x6
16x6 16x6
PROVIDE 26 GAUGE
SUB-DUCT. SUB-DUCT
EXTENDS 22" UP
INSIDE EXHAUST RISER.
(TYP.FOR ALL)
2
TYP.
1
FD
ROOF
4TH FLOOR
3RD FLOOR
2ND FLOOR
50 CFM
50 CFM
200
CFM FD
GRD FLOOR
50 CFM
16x6
16x6
16x6 16x6
PROVIDE 26 GAUGE
SUB-DUCT. SUB-DUCT
EXTENDS 22" UP
INSIDE EXHAUST RISER.
(TYP.FOR ALL)
2
TYP.
1
FD
ROOF
4TH FLOOR
3RD FLOOR
2ND FLOOR
50 CFM
50 CFM
200
CFM FD
GRD FLOOR
50 CFM
16x6
16x6
16x6 16x6
PROVIDE 26 GAUGE
SUB-DUCT. SUB-DUCT
EXTENDS 22" UP
INSIDE EXHAUST RISER.
(TYP.FOR ALL)
2
TYP.
1
FD
ROOF
4TH FLOOR
3RD FLOOR
2ND FLOOR
50 CFM
50 CFM
200
CFM FD
GRD FLOOR
50 CFM
16x6
16x6
16x6 16x6
PROVIDE 26 GAUGE
SUB-DUCT. SUB-DUCT
EXTENDS 22" UP
INSIDE EXHAUST RISER.
(TYP.FOR ALL)
2
TYP.
1
FD50 CFM50 CFM50 CFM
EXTERIOR
WALL
50 CFM 50 CFM 50 CFM 50 CFM 50 CFM
TOILET
EF-B
TOILET
EF-C
TOILET
EF-D
TOILET
EF-E
EXTERIOR
WALL
EXTERIOR
WALL
50 CFM 75 CFM
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
RISER
DIAGRAMS
SHEET 1 OF 4
M4.01
GPS
T S
ECM MOTOR
DISCONNECT SWITCH
TRANSFORMER
TRANSDUCER IN
ACCESSIBLE CEILING
PRESSURE SENSOR PROBE
IN DUCTWORK
TEF
ROOF
3W
4TH FLOOR CEILING
DUCTWORK
POWER BY ELEC. CONTRACTOR
MER
LOW VOLTAGE
WIRE IN CONDUIT
BY MECHANICAL
CONTRACTOR
3W IN CONDUIT
TO MOTORIZED
DAMPER
NEMA 4X CONTROL PANEL WITH
CONSTANT PRESSURE AIR FLOW
CONTROLLER. (MULTIPLE
CONTROLLERS CAN BE MOUNTED
IN CONTROL PANEL)
NOT TO SCALE
CONSTANT PRESSURE AIR FLOW DIAGRAM (TEF)
NOT TO SCALE
EXHAUST RISER DIAGRAM
GROUND FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
ROOF
LOWER LEVEL
TO / FROM HW
CIRCULATION
PUMPS
3/4"
2"
4" CONCRETE
PAD (TYP.)
2-1/2"
AUTOMATIC
CONTROL
VALVE
SAFETY
RELIEF
VALVE
ACID
NEUTRALIZING
PRESSURE
DIFFERENTIAL
BYPASS
TO AHU / HC
/ UH / CUH
FROM AHU /
HC / UH / CUH
P-HW-1
(DUTY)
P-HW-2
(STANDBY)
MAKE-UP
WATER
NOT TO SCALE
BOILER PIPING DETAILS
BALANCING VALVE (TYP)HWSHWRHWSHWRNOTE: REFER TO PLANS/FLOW
DIAGRAM FOR PIPE SIZES
SHUT-OFF
RELIEF
VALVE
RELIEF
VALVE
PRESSURE
GAUGE
THERMOMETER
VALVES
STRAINERS
PRESSURE
GAUGE
SHUT-OFF
PRESSURE
THERMOMETER VALVES
STRAINERS
PRESSURE
GAUGE
ACID
NEUTRALIZER
BOILER BOILER HOT WATER PIPING RISER NOTES:
1.REFER TO PLANS, DETAILS, CONTROL DIAGRAMS AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR
VALVES, GAUGES, INSTRUMENTATION AND ACCESSORIES.
2.PROVIDE DRAIN VALVE AT BOTTOM OF RISERS AND AT ALL LOW POINTS OF PIPING (TYP)
3.PROVIDE AIR VENTS AT TOP OF RISERS AND AT HIGH POINTS OF PIPING.
DRIP LEGDRIP LEG
DRAIN (TYP)
GASGAS
3/4"
3/4"3/4"3/4"3/4"3/4"
HC-BCUH-A
3 GPM
3/4"3/4"
1"
AHU-1
4 GPM
1"
1,1/2"
1"
2-1/2"
2"
1 1/2"
UH-A
3.5 GPM
UH-B
0.8 GPM HC-B1.7 GPM
HC-B
1.7 GPM
3/4"1"
1.7 GPM
HC-B
1.7 GPM
HC-A
1.2 GPM
HC-B
1.7 GPM
3/4"
CUH-A
3 GPM
1-1/4"
HC-D
2.7 GPM
HC-B
1.7 GPM
3/4"
HC-B
1.7 GPM
3/4"
HC-B
1.7 GPM
2"
3/4"3/4"
HC-C2.2 GPM
HC-B
1.7 GPM
3/4"
HC-B
1.7 GPM
3/4"
HC-B
1.7 GPM
3/4"3/4"
HC-C2.2 GPM
HC-B
1.7 GPM
3/4"
HC-B
1.7 GPM
3/4"
HC-C2.2 GPM
2"
3/4"
HC-B
1.7 GPM
3/4"
HC-B
1.7 GPM
3/4"
HC-B
1.7 GPM
1"1-1/4"
1"1-1/4"
3/4"
HC-B1.7 GPM
3/4"
HC-B1.7 GPM
1"1-1/4"
1"1-1/4"
1-1/2"
3/4"
HC-B
1.7 GPM
2"
2-1/2"
2-1/2"2-1/2"
2-1/2"
NOT TO SCALE
BOILER FLOW DIAGRAM
NOT TO SCALE
HOT WATER SUPPLY AND RETURN PIPING RISER DIAGRAM
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
RISER
DIAGRAMS
SHEET 2 OF 4
M4.02
GPS
5/8x1 1/8x7/8"
39.5 ft [3]
3/8x3/4x5/8"
14.0 ft [1]
3/8x5/8x1/2"
1.5 ft [1]
1/4x1/2"
9.0 ft [3]
3/8x3/4x5/8"
2.5 ft
3/8x5/8x1/2"
6.0 ft [1]
1/4x1/2"
7.5 ft [1]
3/8x5/8x1/2"
7.5 ft [1]
3/8x5/8x1/2"
2.5 ft [2]
1/4x1/2"
7.5 ft [3]
3/8x5/8x1/2"
5.0 ft
3/8x5/8x1/2"
11.0 ft [1]
1/4x1/2"
14.5 ft [3]
3/8x5/8x1/2"
8.0 ft [2]
1/4x1/2"
9.0 ft [1]
3/8x7/8x3/4"
10.0 ft
3/8x3/4x5/8"
13.5 ft [2]
3/8x5/8x1/2"
2.5 ft [1]
1/4x1/2"
19.0 ft [3]
3/8x5/8x1/2"
2.5 ft
3/8x5/8x1/2"
6.0 ft [1]
1/4x1/2"
6.5 ft [1]
3/8x5/8x1/2"
7.0 ft [1]
3/8x5/8x1/2"
2.5 ft [2]
1/4x1/2"
8.0 ft [3]
3/8x5/8x1/2"
5.0 ft
3/8x5/8x1/2"
4.0 ft [2]
1/4x1/2"
8.0 ft [2]
3/8x5/8x1/2"
8.5 ft [2]
1/4x1/2"
8.0 ft [1]
3/8x5/8x1/2"
23.5 ft [2]
3/8x5/8x1/2"
1.0 ft [1]
1/4x1/2"
15.0 ft [2]
3/8x5/8x1/2"
2.5 ft
3/8x5/8x1/2"
6.0 ft
1/4x1/2"
7.0 ft [1]
3/8x5/8x1/2"
6.5 ft
3/8x5/8x1/2"
2.5 ft [2]
1/4x1/2"
7.5 ft [3]
3/8x5/8x1/2"
13.0 ft [2]
1/4x1/2"
9.0 ft [1]
ACCU-1
REYQ168TATJU
KHRP25M72TU9 KHRP25A22T9
BS 12
BSQ36TVJ
A
FCU-2-5
FXMQ12PBVJU
KHRP25A22T9
BS 15
BSQ36TVJ
A
FCU-2-3
FXMQ12PBVJU
KHRP25A22T9
BS 13
BSQ36TVJ
A
FCU-2-2
FXMQ12PBVJU
KHRP25A22T9
BS 11
BSQ36TVJ
A
FCU-2-4
FXMQ18PBVJU
BS 14
BSQ36TVJ
A
FCU-2-1
FXMQ12PBVJU
KHRP25A33T9 KHRP25A22T9
BS 17
BSQ36TVJ
A
FCU-1-5
FXMQ12PBVJU
KHRP25A22T9
BS 20
BSQ36TVJ
A
FCU-1-3
FXMQ12PBVJU
KHRP25A22T9
BS 18
BSQ36TVJ
A
FCU-1-2
FXMQ12PBVJU
KHRP25A22T9
BS 21
BSQ36TVJ
A
FCU-1-4
FXMQ09PBVJU
BS 19
BSQ36TVJ
A
FCU-1-1
FXMQ12PBVJU
KHRP25A22T9
BS 22
BSQ36TVJ
A
FCU-0-4
FXMQ12PBVJU
KHRP25A22T9
BS 25
BSQ36TVJ
A
FCU-0-3
FXMQ12PBVJU
KHRP25A22T9
BS 23
BSQ36TVJ
A
FCU-0-2
FXMQ12PBVJU
BS 24
BSQ36TVJ
A
FCU-0-1
FXMQ12PBVJU
ACCU-1
REYQ168TATJU
REYQ168TATJU BS 12
BSQ36TVJ
A
FCU-2-5
FXMQ12PBVJU BRC1E73 (1)
BS 15
BSQ36TVJ
A
FCU-2-3
FXMQ12PBVJU BRC1E73 (1)
BS 13
BSQ36TVJ
A
FCU-2-2
FXMQ12PBVJU BRC1E73 (1)
BS 11
BSQ36TVJ
A
FCU-2-4
FXMQ18PBVJU BRC1E73 (1)
BS 14
BSQ36TVJ
A
FCU-2-1
FXMQ12PBVJU BRC1E73 (1)
BS 17
BSQ36TVJ
A
FCU-1-5
FXMQ12PBVJU BRC1E73 (1)
BS 20
BSQ36TVJ
A
FCU-1-3
FXMQ12PBVJU BRC1E73 (1)
BS 18
BSQ36TVJ
A
FCU-1-2
FXMQ12PBVJU BRC1E73 (1)
BS 21
BSQ36TVJ
A
FCU-1-4
FXMQ09PBVJU BRC1E73 (1)
BS 19
BSQ36TVJ
A
FCU-1-1
FXMQ12PBVJU BRC1E73 (1)
BS 22
BSQ36TVJ
A
FCU-0-4
FXMQ12PBVJU BRC1E73 (1)
BS 25
BSQ36TVJ
A
FCU-0-3
FXMQ12PBVJU BRC1E73 (1)
BS 23
BSQ36TVJ
A
FCU-0-2
FXMQ12PBVJU BRC1E73 (1)
BS 24
BSQ36TVJ
A
FCU-0-1
FXMQ12PBVJU BRC1E73 (1)
L1, L2, L3 61.9A 3ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.6A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 0.6A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
IN F1,F2 OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
NOT TO SCALE
REFRIGERANT RISER DIAGRAM (ACCU-1)
NOT TO SCALE
SCHEMATIC WIRING DIAGRAM (ACCU-1)
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
RISER
DIAGRAMS
SHEET 3 OF 4
M4.03
GS
1/2x1 1/8x7/8"
10.0 ft [3]
3/8x5/8x1/2"
1.5 ft [1]
3/8x5/8x1/2"
2.0 ft [1]
1/4x1/2"
7.0 ft [3]
3/8x5/8x1/2"
5.0 ft
3/8x5/8x1/2"
11.0 ft
1/4x1/2"
14.5 ft [3]
3/8x5/8x1/2"
8.0 ft [2]
1/4x1/2"
8.0 ft [1]
3/8x7/8x3/4"
6.5 ft
3/8x5/8x1/2"
5.5 ft
1/4x1/2"
7.5 ft [1]
3/8x7/8x3/4"
2.5 ft [1]
3/8x5/8x1/2"
1.0 ft [1]
1/4x1/2"
8.5 ft [3]
3/8x3/4x5/8"
38.0 ft [4]
3/8x5/8x1/2"
1.0 ft [1]
1/4x1/2"
8.5 ft [3]
3/8x5/8x1/2"
2.5 ft
3/8x5/8x1/2"
6.0 ft [1]
1/4x1/2"
7.0 ft [1]
3/8x5/8x1/2"
7.5 ft [1]
3/8x5/8x1/2"
2.0 ft [2]
1/4x1/2"
7.0 ft [3]
3/8x5/8x1/2"
5.0 ft
3/8x5/8x1/2"
11.0 ft [1]
1/4x1/2"
14.5 ft [3]
3/8x5/8x1/2"
8.0 ft [2]
1/4x1/2"
8.0 ft [1]
ACCU-2
REYQ144TATJU
KHRP25M72TU9 KHRP25A22T9
BS 3
BSQ36TVJ
A
FCU-4-2
FXMQ12PBVJU
KHRP25A22T9
BS 4
BSQ36TVJ
A
FCU-4-4
FXMQ15PBVJU
BS 5
BSQ36TVJ
A
FCU-4-1
FXMQ12PBVJU
KHRP25A33T9
BS 2
BSQ36TVJ
A
FCU-4-3
FXMQ15PBVJU
KHRP25A33T9
BS 1
BSQ36TVJ
A
FCU-4-5
FXMQ12PBVJU
KHRP25A22T9
BS 6
BSQ36TVJ
A
FCU-3-5
FXMQ12PBVJU
KHRP25A22T9
BS 10
BSQ36TVJ
A
FCU-3-3
FXMQ12PBVJU
KHRP25A22T9
BS 8
BSQ36TVJ
A
FCU-3-2
FXMQ12PBVJU
KHRP25A22T9
BS 7
BSQ36TVJ
A
FCU-3-4
FXMQ15PBVJU
BS 9
BSQ36TVJ
A
FCU-3-1
FXMQ12PBVJU
ACCU-2
REYQ144TATJU
REYQ144TATJU BS 3
BSQ36TVJ
A
FCU-4-2
FXMQ12PBVJU BRC1E73 (1)
BS 4
BSQ36TVJ
A
FCU-4-4
FXMQ15PBVJU BRC1E73 (1)
BS 5
BSQ36TVJ
A
FCU-4-1
FXMQ12PBVJU BRC1E73 (1)
BS 2
BSQ36TVJ
A
FCU-4-3
FXMQ15PBVJU BRC1E73 (1)
BS 1
BSQ36TVJ
A
FCU-4-5
FXMQ12PBVJU BRC1E73 (1)
BS 6
BSQ36TVJ
A
FCU-3-5
FXMQ12PBVJU BRC1E73 (1)
BS 10
BSQ36TVJ
A
FCU-3-3
FXMQ12PBVJU BRC1E73 (1)
BS 8
BSQ36TVJ
A
FCU-3-2
FXMQ12PBVJU BRC1E73 (1)
BS 7
BSQ36TVJ
A
FCU-3-4
FXMQ15PBVJU BRC1E73 (1)
BS 9
BSQ36TVJ
A
FCU-3-1
FXMQ12PBVJU BRC1E73 (1)
L1, L2, L3 55A 3ph L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.5A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.5A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
L1, L2 0.1A 1ph L1, L2 1.5A 1ph
L1, L2 0.1A 1ph L1, L2 1.4A 1ph
IN F1,F2 OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
IN F1,F2 F1,F2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
P1,P2
NOT TO SCALE
REFRIGERANT RISER DIAGRAM (ACCU-2)
NOT TO SCALE
SCHEMATIC WIRING DIAGRAM (ACCU-2)
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
RISER
DIAGRAMS
SHEET 4 OF 4
M4.04
GPS
NOTES:
1.MOUNT UNIT FLOOR/CEILING SLAB STRUCTURE WITH SPRING VIBRATION ISOLATORS.
2.ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH.
3.FILTERS SHALL BE LOCATED AT GRILLES. CONTRACTOR TO PROVIDE EXTERIOR INSULATION ON CABINET.
4.PROVIDE INTEGRAL LIFT PUMP FOR ALL INDOOR FAN COILS. PROVIDE WITH WATER BUG DETECTION.
5.PROVIDE KPR DATA BOARD AND 24 VOLT TRANSFORMER IN CONTROL BOX TO PREVENT SIMULTANEOUS COOLING AND HEATING.
6.FILTERS ARE PROVIDED IN THE RETURN GRILLES, PROVIDE UNITS WITH OPEN ENDED RETURN WITH WIRE MESH SCREEN.
FCU FAN COIL UNIT SCHEDULE - (VARIABLE REFRIGERANT VOLUME UNITS)BASIS OF DESIGN:
DAIKIN
UNIT
NO.AREA SERVED TOTAL
CFM
COOLING
TOTAL
(MBH)
COOLING
SENSIBLE
(MBH)
HEATING
(MBH)
ELECTRICAL DATA WEIGHT
(LBS)REFRIGERANT MODEL NO.REMARKS(VOLT
PH)MCA MFS
FCU-A SEE PLANS 315 8.0 6.7 10.1 208 / 1 0.6 15 55 R410A FXMQ09PBVJU
FCU-B SEE PLANS 450 10.2 8.4 13 208 / 1 1.4 15 62 R410A FXMQ12PBVJU
FCU-C SEE PLANS 560 12.6 10.6 15.9 208 / 1 1.5 15 79 R410A FXMQ15PBVJU
FCU-D SEE PLANS 635 15.2 13.7 19.2 208 / 1 1.6 15 79 R410A FXMQ18PBVJU
NOTES:
1.PROVIDE INDIVIDUAL POWER CONNECTIONS.
2.MAINTAIN MANUFACTURER'S CLEARANCES ABOVE AND BELOW BOXES.
3.PROVIDE REQUIRED MOUNTS.
BS BRANCH SELECTOR BOX BASIS OF DESIGN:
DAIKIN
TAG SERVES SELECTED
MODEL
ELECTRICAL DATA NET
WEIGHT
(LBS)
DIMENSIONS
L x H x WMCA
AMP
MOCP
AMP (V/P/H)
BS-1 FCU-A,B,C,D BSQ36TVJ 0.1 15 208 / 1 / 60 27 15.3" x 8.1" x 12.8"
ACCU AIR COOLED CONDENSING UNIT (VRF)BASIS OF DESIGN: DAIKIN
UNIT NO.SERVES LOCATION EER COP
#)
CAPACITY COND. DATA ELECTRICAL DATA
WEIGHT
(LBS)MODEL NO.COOLING
TOTAL
(MBH)
HEATING
(MBH)
OUTDOOR
DESIGN DB
)
REFRIG.
TYPE MODULE #
ELECT.
DATA
(VOLT/PH)
TYPE OF
COMP.
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
FUSE SIZE
ACCU-1 LL,1,2 FLOORS ROOF 11.6 3.7 156 176 89 R410A -208/3 SCROLL 61.9 70 780 REYQ168TATJU
ACCU-2 3,4 FLOORS ROOF 12.4 3.8 134 150 89 R410A -208/3 SCROLL 55 70 780 REYQ144TATJU
NOTES:
1.PROVIDE COMPRESSOR CYCLE PROTECTOR.
2.3529,'(/2:$0%,(17&21752/:,1'%$))/()25&21'(16,1*81,723(5$7,21'2:172)
3.PROVIDE REMOTE AND OUTDOOR AIR TEMPERATURE SENSORS.
4.MOUNT UNIT ON EQUIPMENT RAILS/BIG FOOT SUPPORTS ON ROOF. UNIT SHALL BE ELEVATED A MINIMUM 18" ABOVE FINISHED ROOF. TIE UNIT AND SUPPORT DOWN TO STRUCTURE.
NOTES:
1.PROVIDE REFRIGERANT PIPING BETWEEN AC UNIT AND CONDENSING UNIT PER MANUFACTURER'S RECOMMENDATIONS.
2.PROVIDE INTERCONNECTING CONTROL WIRING BETWEEN ACCU AND AHU.
3.MOUNT UNIT ON 4" CONCRETE PAD.
4.UNITS ARE SELECTED BASED ON HWC, DX COOLING COIL, FILTER SECTION AND FAN SECTION.
NOTES:
1.ACCU UNITS SHALL HAVE FIVE YEAR EXTENDED WARRANTY FOR COMPRESSORS.
2.PROVIDE COMPRESSOR CYCLE PROTECTOR.
3.3529,'(/2:$0%,(17&21752/)25&21'(16,1*81,723(5$7,21'2:172)
4.PROVIDE REMOTE AND OUTDOOR AIR TEMPERATURE SENSORS
ACCU AIR COOLED CONDENSING UNIT (AHU)BASIS OF DESIGN: AAON
UNIT NO.SERVICE LOCATION EER
CAPCAITY COND DATA ELECTRICAL
WEIGHT
(LBS)
MODEL
NO.REMARKSOUTDOOR
DESIGN DB
)
REFRIG.
TYPE
VOLT /
PH MCA MOCPCOOLING
MBH
HEATING
MBH
ACCU-3 AHU-1 ROOF 12.1 33.1 34.6 95 R-410A 208 / 3 4 15 397 CFA-003-A-A-8
DC00H
HC HEATING COIL WITH 40% PROPYLENE GLYCOL SCHEDULE BASIS OF DESIGN: USA COIL & AIR
COIL
NO.
EQUIPMENT OR
SYSTEM
SERVED
MODEL NUMBER
AIR DATA WATER DATA COIL DATA
REMARKSTOTAL
CFM
MAX.
FACE
VELOC.
(FPM)
'%7(03)MAX. P.D.
(IN.W.G.)GPM
7(03)MAX. P.D.
(IN.W.G.)
HEAT CAP.
(MBH)ROWS/FPI NOMINAL SIZE (IN.)
F.W. X F.L.
DRY WEIGHT
(EACH)
ENT.LVG.ENT.LVG.
HC-A FCU-A F12-206-8.8x14-01A 315 370 62 101.1 0.05 1.24 180 157.6 1.91 14 2 / 6 14x8.75 8.5
HC-B FCU-B F12-206-8.8x20-01A 450 370 62 102.2 0.05 1.71 180 156.1 1.09 20 2 / 6 20x8.75 11
HC-C FCU-C F12-206-8.8x32-02A 560 288 62 105.1 0.04 2.20 180 155.2 1.42 27 2 / 6 32x8.75 16.1
HC-D FCU-D F12-206-8.8x32-02A 635 327 62 104 0.04 2.71 180 157.8 2.07 29 2 / 6 32x8.75 16.1
NOTES:
1.ELECTRIC WALL HEATER SHALL BE PROVIDED WITH FUSED DISCONNECT SWITCH.
2.ELECTRIC WALL HEATER SHALL BE PROVIDED WITH AIR FLOW SWITCH TO SHUT HEATER OFF IN THE EVENT OF FAN FAILURE.
3.PROVIDE WITH UNIT MOUNTED THERMOSTAT.
EWH ELECTRIC WALL HEATER SCHEDULE BASIS OF DESIGN: BERKO
SYMBOL MODEL LOCATION KW OUTPUT
MBH CFM VOLT/PH MCA MOCP EAT LAT OPER
WT.REMARKS
EWH-A SRA1012DSAF SEE PLANS 1 3.4 65 120/1 10.5 15 60 108 30 2 STAGE HEATER
NOTES:
1.CONTRACTOR TO PROVIDE DUCT TRANSITIONS AT INLET AND OUTLET TO COILS.
AHU AIR HANDLING UNIT WITH 40% PROPYLENE GLYCOL SCHEDULE BASIS OF DESIGN: AAON
UNIT NO.LOCATION AREA SERVED TOTAL CFM OUTSIDE AIR HP
AIR DATA DX COOLING WATER DATA ELECTRICAL
REF.
WEIGHT
(LBS)
MODEL
NO.REMARKSENT. DB
)
ENT. WB
)
LAT. DB
)
LAT. WB
)ESP TOTAL
(MBH)
SENSIBLE
(MBH)
HEATING
(MBH)
7(03)
GPM VOLT/PH FLA
ENT LVG
AHU-1 MER CORRIDOR-LOBBY 1100 130 1.1 77.3 63.3 53 51.9 1 33.1 26.4 34.6 180 161.3 4 208/3 3 R-410A 306 V3-ARB-8-0
141D-11Q
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:07pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
SCHEDULES
SHEET 1 OF 2
M5.01
GES
NOTES:
1.PROVIDE DISCONNECT SWITCH
2.PROVIDE SOLID STATE SPEED CONTROL FOR BALANCING.
3.PROVIDE WITH HANGERS AND SUPPORTS WITH VIBRATION ISOLATORS.
4.PROVIDE 12" HIGH ROOF CURB.
5.PROVIDE DUCT PRESSURE SENSOR, VARI-GREEN CONSTANT PRESSURE CONTROL WITH REMOTE TRANSDUCER. REMOTE TRANSDUCER SHALL BE LOCATED ABOVE ACCESSIBLE CEILING. CONSTANT PRESSURE
AIR FLOW CONTROLLER SHALL BE LOCATED IN NEMA 4X PANEL ON THE ROOF.PROVIDE ALL LOW VOLTAGE WIRING AND REQUIRED TUBING FROM STATIC PRESSURE PROBE TO REMOTE TRANSDUCER.
6.PROVIDE BACK DRAFT DAMPER.
7.PROVIDE MOTORIZED DAMPER
NOTES:
1.xxx
ET EXPANSION TANK SCHEDULE BASIS OF DESIGN: AMTROL
TANK
NO.LOCATION SYSTEM SERVED
TANK
TYPE
(OPEN OR
CLOSED)
TANK
VOLUME
(GAL.)
SIZE AVG.
OPER.
TEMP.
)
INITIAL
FILL
PRESS.
(PSIG)
MAX.
OPER.
PRESS.
(PSIG)
A.S.M.E
. WORK
PRESS.
(PSIG)
MODEL REMARKS
DIA. (IN.)LENGTH
(IN.)
ET-1 LOCATION HEATING SYSTEM CLOSED M 24 47 190 30 50 125 AX-120V
NOTES:
1.PROVIDE GALVANIZED ANGLE MOUNTING FRAME SUPPORT.
AS AIR SEPARATOR SCHEDULE BASIS OF DESIGN: SPIROTHERM
PLAN
NO LOCATION
PIPE
DIA
INLET
PIPE
DIA
OUTLET
HEIGHT
IN.DIA.GPM
MAX
OPER
TEMP
)
MAX
OPER.
PRESSU
RE PSI
DRY
WEIGHT
LBS
MODEL REMARKS
AS-1 MER 3"3"23.7 9"140 180 150 95 SPIROVENT VSR300
NOTES:
1.LOCATE BOILERS ON CONCRETE PAD WITH NEOPRENE PADS SIMILAR TO MASON INDUSTRIES TYPE MSW WITH
MINIMUM STATIC DEFLECTION OF 0.1 INCHES.
2.ELECTRICAL: PROVIDE ONE 115V/1 CIRCUIT FOR FAN AND ANOTHER 115V/1 FOR CONTROL.
3.PROVIDE INTEGRATED BOILER CONTROL (NURO).
B BOILER SCHEDULE BASIS OF DESIGN: PATTERSON KELLEY
BOILER
NO.LOCATION SERVICE
MAX.
OPER.
PRESS.
(PSIG)
DESIGN
PRESS.
RATING
(PSIG)
FLUE
OUTLET
SIZE
(IN.)
GROSS
INPUT
(MBH)
GROSS
OUTPUT
(MBH)
EFFICIENCY
AT RATED
LOAD (%)
HOT WATER DATA W/40% PROP
GLYCOL FUEL-GAS BURNER DATA
BOILER
TYPE
OPER.
WEIGHT
(LB)
MODEL REMARKS
GPM
MAX
PRESS.
DROP
(FT.)
7(03)
GAS
TYPE
GAS
RATE
(CFH)
GAS INLET
PRESSURE
(IN. WG)
MIN/MAXGASENT.LVG.
B-1 MER REHEAT
COILS 80 14.0 300 279 93.5 %28 12 160 180 NATURAL 388 3.5 / 14 CONDENSING 290 MACH CM-300
B-1 MER REHEAT
COILS 80 14.0 300 279 93.5 %28 12 160 180 NATURAL 388 3.5 / 14 CONDENSING 290 MACH CM-300
GFP PACKAGE GLYCOL AUTO FILL SCHEDULE BASIS OF DESIGN: ARMSTRONG
PUMP
NO.LOCATION MODEL STORAGE
CAPACITY HP MOTOR DATA DIMENSIONS
WxDxH REMARKSFLAVOLT/PH
GFP-1 MER GLA-S-HP-1 53 GAL 1/3 2.7 120 / 1 26"x24"x51"A ACTIVE / B STD. BY PUMP
NOTES:
1.PROVIDE DRY CONTACTS FOR REMOTE INDICATION OF ALARM.
2.PROVIDE NEMA 4X CONTROL PANEL WITH TWO (2) HDA SWITCHES.
NOTES:
1.PROVIDE VARIABLE FREQUENCY DRIVE FOR P-HW-1,2.
P PUMP SCHEDULE BASIS OF DESIGN: GRUNDFOS
PUMP
NO.LOCATION
EQUIPMENT
OR SYSTEM
SERVED
PUMP
TYPE GPM
TOTAL
HEAD
(FT.)
FLUID
TEMP.
)
IMPELLER
DIA.
NPSHr
(FT.)
EFF. @
OPER.
POINT
(%)
BHP
MAX
MOTOR DATA
MODEL
NO.REMARKS
HP VOLT/
PH RPM
P-HW-1 MER HEATING SYSTEM VERTICAL INLINE 32 53 180 6.99"6.05 54.52 0.78 1.5 208/3 1765 VL 12707 40% PROYLENE GLYCOL
P-HW-1 MER HEATING SYSTEM VERTICAL INLINE 32 53 180 6.99"6.05 54.52 0.78 1.5 208/3 1765 VL 12707 40% PROYLENE GLYCOL
AIR DEVICES BASIS OF DESIGN: TITUS
DESIGNATION NECK SIZE NOMINAL
FACE SIZE MODEL NO.REMARKS
CD SEE PLANS 18" X 18"TDCA 2
SR SEE PLANS SEE PLANS 272FL 1,2
RG SEE PLANS 18" X 18"50F 2
CFG SEE PLANS SEE PLANS 50FF 2
NOTES:
1.PROVIDE WITH INTEGRAL VOLUME DAMPER.
2.COORDINATE COLOR AND BORDER TYPE WITH THE ARCHITECT.
NOTES:
1.PROVIDE REMOTE MOUNTED THERMOSTAT.
2.PROVIDE MANUAL MOTOR STARTER WITH THERMAL OVER LOAD, DISCONNECT SWITCH AND AQUASTAT
UH /
CUH CABINET AND UNIT HEATER WITH 40% PROPYLENE GYLCOL SCHEDULE BASIS OF DESIGN: STERLING
UNIT
NO.LOCATION MBH
AIR DATA WATER DATA MOTOR DATA
MODEL
NO.REMARKSCFM
(HI)
7(03)
GPM
7(03)MAX
P.D.
(FT.)
HP
(WATTS)
RPM
(HI)
NO. OF
SPEEDS
VOLT/
PH/HZENT.LVG.ENT LVG
UH-A MER 34.8 750 60 103 3.5 180 160 0.12 1/20 HP 1000 2 120 / 1 / 60 HS-48 -
UH-B HOUSE KEEPING 8 245 60 91 0.8 180 160 0.8 16W 1550 2 120 / 1 / 60 HS-108A -
CUH-A STAIRS 30 420 55 120 3 180 160 0.1 1/10 HP 1050 3 120 / 1 / 60 RC-1200-04 HI CAP COIL
TEF
EF FAN SCHEDULE BASIS OF DESIGN: GREENHECK
UNIT
NO.LOCATION AREA OR SYSTEM
SERVED
FAN
TYPE CFM ESP FAN
RPM DRIVE
MOTOR DATA WEIGHT
(LBS)
MODEL
NO.REMARKSBHPHPV/C/PH MOTOR
RPM
TEF-A ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7
TEF-B ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7
TEF-C ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7
TEF-D ROOF TOILET EXHAUST CENTRIFUGAL 200 0.50 1501 DD -0.05 115/60/1 1725 24 G-080-VG 1,2,4,5,7
TEF-E ROOF TOILET EXHAUST CENTRIFUGAL 325 0.50 1618 DD -0.1 115/60/1 1725 24 G-085-VG 1,2,4,5,7
TEF-1 CEILING SEE PLANS INLINE 50 0.25 652 DD -15W 115/60/1 -9 SP-B70 1,2,3,6
EF-1 ROOF ELEVATOR CENTRIFUGAL 300 0.50 1665 DD -0.1 115/60/1 1725 24 G-080-VG 1,2,4,7
EF-2 ROOF MER CENTRIFUGAL 450 0.50 1522 DD -0.07 115/60/1 1725 25 G-090-VG 1,2,4,7
EF-3 CEILING JANITOR INLINE 75 0.25 749 DD -80W 115/60/1 -10 SP-B110 1,2,3,6
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:08pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
SCHEDULES
SHEET 2 OF 2
M5.02
GES
MANUAL
AIR VENT
AUTOMATIC MODULATING VALVE
STRAINER
SUPPLY
TO FLOOR
DRAIN
1" DRAIN VALVE
LUBRICATED PLUG VALVE
RETURN
WITH DIAL SETTING
THERMOMETER
(TYPICAL)
PETE'S PLUG (TYPICAL)
NOTE:
FOR MULTIPLE COILS PROVIDE SEPARATE
CONTROL VALVES AND ACCESSORIES
1.
NOT TO SCALE
HOT WATER COIL PIPING DETAIL (2-WAY VALVE)
N.C.
NOT TO SCALE
BOILER FLUE DETAIL
MINIMUM 3FT
HIGH ABV ROOF
WATER COIL
RETURN
SUPPLY
BALL
VALVE (TYP.)
BALANCING
VALVE (TYP.)
BUTTERFLY
VALVE (TYP.)
AIR
FLOW
3-WAY AUTOMATIC
CONTROL VALVE
(OPERATOR INSTALLED
VERTICALLY)
MANUAL AIR VENT
(TYP.)
UNION (TYP.)
NOTES:
1.PROVIDE PIPE HANGERS SO THAT HOT WATER COIL DOES NOT BEAR
WEIGHT OF PIPING.
2.PIPING SHALL BE INSTALLED IN SUCH A MANNER THAT IT WILL NOT BLOCK THE
SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE
SERVICING OF FILTERS, VALVES OR EQUIPMENT.
3.LEAVE 18" MIN. CLEARANCE ABOVE TEST PLUGS TO ALLOW INSERTION OF
PROBES.
4.UNIONS ARE TO BE DIELECTRIC WHEN TWO DISSIMILAR METALS ARE BEING
JOINED.
STRAINER
3 4" HOSE END
DRAIN VALVE
W/ CAP (TYP.)
THERMOMETER
(TYP.)
HOT WATER COIL PIPING DETAIL (3-WAY VALVE)
NOT TO SCALE
AL29-4C STAINLESS STEEL
WITH 2" ANNULAR SPACE
AND MINERAL WOOL
INSULATION
GALVANIZED SHEET METAL
5.3-WAY VALVE USED ON HOT WATER COILS AT THE DISCHARGE OF FAN COIL UNITS AT THE END
OF THE RUN ONLY (ALL OTHER HEATING COILS SHALL BE PROVIDED WITH 2-WAY VALVES).
REFER TO DRAWINGS 2.14P, 2.24P AND 2.34P FOR EXACT LOCATION.
LARGE DOUBLE VANE
SMALL DOUBLE VANE
DETAIL
NOTE: RADIUS ELBOWS SHALL HAVE A THROAT RADIUS
ELBOW 36" OR WIDER
LARGE DOUBLE VANE SQUARE
ELBOW UP TO 36" IN WIDTH
(NOT TO SCALE)
LOW VELOCITY DUCTWORK ELBOWS
EQUAL TO 1.5 TIMES DUCT WIDTH.
2 1/4"
RUNNER DETAIL
LARGE DOUBLE VANE
8 1/4"
SMALL DOUBLE VANE SQUARE
UP TO 20" IN WIDTH
SINGLE VANE ELBOW
90
90
DETAIL
SMALL DOUBLE VANE
2"R
SINGLE VANE
4 1/2" R
1 1/8"
1"R
2 1/2"
DETAIL
90
RUNNER DETAIL
2"R 4"R
1 9/16"
2"R
1"R
4 1/2" R
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:08pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
DETAILS
SHEET 1 OF 5
M6.01
GES
MAX. SPACING
4'-0"
8'-0"
6'-0"
LESS THAN
DUCT SIZE
< 2 SQ. FT.
> 2 SQ. FT.
48" WIDE
1"X1/16"
1"X1/8"
HANGER SIZE
OVER 10 SQ. FT.
DUCT SIZE
UPTO 4 SQ. FT.
UPTO 10 SQ. FT.
HANGER DETAIL
FOR DUCTS
SCREWS
SHEET METAL
FOR DUCTS OVER
HANGER DETAIL
48" WIDE
2" MIN.
AUXILIARY
STRUCTURAL STEEL
WHERE REQUIRED
DUCT SUPPORT DETAIL
(NOT TO SCALE)
NOTES:
1.SPECIFICATION REQUIREMENTS SHALL APPLY WHERE THEY
EXCEED THOSE INDICATED IN THIS DETAIL.
2.REFER TO DETAIL (TYPICAL PIPING, DUCTWORK, EQUIPMENT
SUPPORT DETAIL FOR CONCRETE SUPPORTS.)
(NOT TO SCALE)
TRANSFER DUCT DETAIL
1" ACCOUSTICAL LINING
W
W 2W W
BRANCH DUCT
NECK 2 = MAIN DUCT
NOTE: PROVIDE VOLUME DAMPER AT EACH LOW PRESSURE SUPPLY,
EXHAUST AND RETURN BRANCH DUCT.
MAIN
- NECK 1
SIZE
NECK 2
BRANCH 2
NECK 1
BRANCH 1~(SUPPLY AND RETURN)
RISE OR DROP
BOX OUTLET
BE SAME SIZE AS BOX
TO REHEAT COIL SHALL
DUCT CONN.
FULL SIZE
OPENING
~
TURNING
VANES
NECK 1 = % AIR IN
CHANGE IN MAIN
DUCT SIZE, TYP.
BRANCH DUCT, TYP.~~~~~~~~V.D., TYP.
~~~~~~~~~~
VAV BOX
XX
(CFM)~~~~TYPICAL SINGLE LINE DUCT STANDARDS
(NOT TO SCALE)
RECT. TO
ROUND
TRANSITION
MIN. 3X DUCT DIAMETER
STRAIGHT RUN INTO BOX
~~PLAN VIEW ELEVATION VIEW
DUCT OVER DIFFUSERS/GRILLES SINGLE LINE DIAGRAM
DUCT DIFFUSER/
GRILLE DUCT DIFFUSER/
GRILLE
SMACNA'S FIRE SMOKE AND RADIATION DAMPER INSTALLATION
A. ALL FIRE DAMPERS SHALL BE RATED TO MAINTAIN THE RATING
OF THE FIRE SEPARATION. THEY SHALL BE APPROVED AND
LABELED BY UNDERWRITER'S LABORATORIES (U.L). THE INSTAL-
LATION SHALL BE IN ACCORDANCE WITH NFPA 90A, UL 555 AND
GUIDE FOURTH EDITION 1992.
B. ALL DUCT-COLLAR CONNECTIONS SHALL COMPLY WITH UL 555 AND
C. GAUGES FOR COLLAR AND RECTANGULAR DUCT SHALL BE AS FOLLOWS:
1. CONNECTIONS BETWEEN COLLAR AND DUCT WORK SHALL BE BREAK-
AWAY TYPE SUCH AS "S" SLIP, CRIMP, OR OTHER SLIP TYPE IN
ACCORDANCE WITH SMACNA FIRE DAMPER GUIDE, 1992. UNLESS
OTHERWISE REQUIRED BY CODE.
2. FIRE DAMPER COLLARS SHALL BE SAME GAUGE AS DUCTWORK WITH
A MINIMUM OF 16 GAUGE FOR DUCTWORK UP TO 36" WIDE. FOR
DUCTWORK ABOVE 36" WIDE, THE COLLAR SHALL BE 14 GAUGE.
D. PROVIDE STEEL STUD FRAMING IN THE DRY WALL OPENING TO ACCEPT
THE FIRE DAMPER ASSEMBLY (INCLUDING SLEEVES, ETC.) AS SHOWN.
E. AFTER THE INSTALLATION OF DAMPERS, THE CONTRACTOR SHALL
SEAL AND TAPE ALL JOINTS FOR AIR TIGHTNESS.
ACCESS DOOR ON SIDE AS SHOWN
OR BOTTOM OF DUCT. MIN. SIZE
18"x14" IF DUCT SIZE PERMITS
SMALLER DUCTS MAKE DOOR 2"
SMACNA.
NOTES:
SMALLER THAN DUCT.
WELDS, NO. 10 SHEETMETAL SCREWS, 1/4" DIA., NUTS AND
BOLTS, OR 3/16" STEEL POP RIVETS, ALL 6" ON CENTER.
H. RETAINING ANGLES SHALL BE SECURED TO COLLAR, SLEEVE OR
PLATE WITH EITHER 1/2" TACKWELDS, NO. 10 SHEETMETEL
SCREWS, 1/4" DIA., NUTS AND BOLTS, OR 3/16" STEEL POP
RIVETS, ALL 6" ON CENTER.
I. WHERE HUNG CEILING DOES NOT HAVE REMOVABLE TILES, AN
ACCESS DOOR (FIRE RATED WHERE REQUIRED) SHALL BE IN-
STALLED IN CEILING NEAR LOCATION OF FIRE DAMPER.
J. ALL RETAINING ANGLES SHALL BE GALVANIZED STEEL.
K. INSTALL FIRE DAMPER IN THIS FASHION SO THE LOCKING
DEVICE CAN BE ACCESSED WHEN THE DAMPER IS CLOSED.
F. TO ALLOW FOR EXPANSION, DAMPERS SHALL HAVE A CLEAR-
ANCE EQUIVALENT TO 1/8" FOR EACH FOOT OF DAMPER HEIGHT.
THE SIDE CLEARANCE SHALL BE 1/8" FOR EACH FOOT OF DAMPER
WIDTH DIVIDED EQUALLY TO THE RIGHT AND TO THE LEFT OF
THE COLLAR. THE MAXIMUM CLEARANCE FOR THE TOP AND THE
TOTAL OF BOTH SIDES SHALL BE 1/2" EACH. THE RETAINING
ANGLES SHALL BE 1-1/2 x 1-1/2 x 1/8 SO THAT THERE WILL
BE A MINIMUM OF 1" OVERLAP ON THE FIRE SEPARATION.
G. DAMPER SHALL BE SECURED TO COLLAR WITH EITHER 1/2" TACK
FIRE DAMPER DUCT DETAIL
DOUBLE "S" SLIP
CONNECTION TYPE
ALL SIDES
1-1/2 x 1-1/2 x 1/8
MOUNTING ANGLES
CONNECTION
FLANGE
CLEARANCE
1/4" MIN.
14 GA.
SLEEVE
FIRE RESISTIVE
MATERIAL AS
REQUIRED BY
CODE.
FIBERGLASS
FIRE DAMPER
SLEEVE
#10 GAUGE
STEEL SLEEVE
1/4" THICK
(NOT TO SCALE)
1. MAT-FACED FIBERGLASS ACOUSTIC LINING APPROVED TYPE BY N.F.P.A. 90.
2. DUCT LINER SHALL BE ADHERED TO THE DUCT WITH AN APPROVED FIRE
3. MECHANICAL FASTENERS WHICH DO NOT PIERCE THE SHEET METAL SHALL
BE ON 16" INCH CENTERS AND WITHIN 3" OE EACH EDGE (WELD PINS WITH
A
THICKNESS AND DENSITY AS PER SPEC.
NEOPRENE COATED STENCILED NFPA 90. A
SUITABLE FOR DUCT VELOCITY 0F 4000 F.P.M.
RETARDANT ADHISIVE (6" WIDE @ 12" O.C. MINIMUM).
WITH PERMANENTLY ATTACHED METAL NOSING.
4. ACOUSTICAL EDGES AT TRANSVERSE CONNECTIONS OR STARTING POINTS
2" WASHERS).
NOTES :
A
DETAIL A-A
2
1
3
1
4
AIR FLOW
DUCTWORK WITH ACOUSTICAL LINING
(NOT TO SCALE)
FIRE SMOKE COMBINATION DAMPER
BOTH SIDES
6" MAX
DUCT
SPRING
DAMPER OPERATOR OUTSIDE THE
DUCT (COORDINATE LOCATION FOR
ACCESS & SERVICING)
SMOKE DETECTOR
GENERAL NOTES:
1. DAMPER TO BE U.L. LABELED N.F.P.A. 90A AND MEA APPROVED. DAMPER SHALL BE RUSKIN MODEL FSD37 - 1-1/2 HOUR RATING
(MEA #394-93-M) OR APPROVED EQUAL.
2. ACCESS DOOR IS SHOWN IN SIDE OF DUCT.
3. THIS DETAIL IS FOR GUIDE ONLY. INSTALL DAMPER IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
4. DETAIL FOR SMOKE DAMPER IN TRANSFER OPENING SHALL BE SIMILAR, EXCEPT FOR CONNECTING DUCT, ACCESS DOOR AND
BREAKAWAY CONNECTIONS.
5. MATERIAL AND EQUIPMENT DELIVERED WITHOUT MANUFACTURERS MEA OR BMS LABELS OR CERTIFICATES MUST BE
REJECTED FROM JOB SITE AS PER 27-131(c).
PROVIDE CLEARANCE OF 1/8" PER LINEAL
FOOT OF SLEEVE DIMENSION (1" MAX.) ON
SIDES OF SLEEVE.
DAMPER SLEEVE TO BE MINIMUM
14" U.S. GA. SHEETMETAL
SECURE RETAINING ANGLES TO SLEEVE 8"
ON CENTER WITH 1/4" BOLTS & NUTS, 1/2"
LONG WELDS, #10 STEEL SCREWS, OR
3/16" STEEL RIVETS. ANGLES MUST
OVERLAP OPENING 1" MIN.
PROVIDE
FUSIBLE
LINK IN
DAMPER
NOT TO SCALE
ACCESS
DOOR
CONNECTING
ROD
RATED
PARTITION
BREAK AWAY CONNECTION,
SEALED WITH A NON-HARDENING
SEALANT, WITH FLAME SPREAD
RATING LESS THAN 25 AND
SMOKE DEVELOPED RATING OF
LESS THAN 50. NO FASTENERS.
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:08pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
DETAILS
SHEET 2 OF 5
M6.02
GES
REFRIGERANT PIPING PORTAL DETAIL
ELEC. POWER CONDUIT
CONTROL CONDUITREFRIGERANT PIPING
NOT TO SCALE
PLENUM
PITCH PLENUM
TOWARDS LOUVER
AIR
PLENUM
PITCH PLENUM
TOWARDS LOUVER
1/8"SLOPE
INSTALLATION
DRAWINGS FOR LOUVER
REFER TO ARCHITECTURAL
NOTES:
FLASHING
BY G.C.
FACE
EXTERIOR
BY G.C.
FLASHING
DRAWINGS FOR LOUVER
REFER TO ARCHITECTURAL
INSTALLATION
FACE
EXTERIOR
METAL PLENUM
AIR TIGHT
SEAL SHEET
AS PER SPECS
(TYP.)
STAINLESS STEEL
WELDED CONSTRUCTION
DUCT SUPPORTS
BIRDSCREEN
AIR TIGHT
SEAL SHEET
METAL PLENUM
LOUVER AIR
SEAL
AROUND
TIGHT ALL
RIGID INSULATION
PLENUMS
AS SPECIFIED ON
AIR TIGHT ALL AROUND
AS PER SPECIFICATION
SHEET METAL BLANK-OFF
(TYP.)
STAINLESS STEEL
WELDED CONSTRUCTION
DUCT SUPPORTS
AS PER SPECS
SEAL BLANK-OFF
1/8"SLOPE
BIRDSCREEN
TIGHT ALL
LOUVER AIR
SEAL
AIR
AROUND
AS SPECIFIED ON
RIGID INSULATION
PLENUMS
LOUVERS-DETAIL
(NOT TO SCALE)
PLENUM CONNECTIONS TO
1. CONTRACTOR SHALL FILL PLENUM WITH 10 GALLONS OF WATER,
AND VERIFY THAT THE WATER DRAINS THROUGH THE LOUVER TO
THE EXTERIOR OF THE BUILDING.
2. PROVIDE DRAIN AT LOWEST POINT OF THE PLENUM. DRAIN SHALL
HAVE A P-TRAP AND PIPED TO NEAREST FLOOR DRAIN.
FOR LOW PRESSURE DUCTWORK
DUCT BRANCH TAKEOFF
RETURN OR EXHAUST AIR
SUPPLY AIR
(NOT TO SCALE)
VOLUME DAMPER
WITH ADJUST
DIAL SETTING
1/4 W
5"MIN
45
SUPPORT DETAIL FOR VERTICAL DUCTS
PLAN
ELEVATION
DUCT
DUCT SEAM
DUCT
RIVETED TO DUCT
2"X2"X1/8" ANGLES
(NOT TO SCALE)
SUPPLEMENTAL
STEEL. REFER TO
STRUCTURAL
DRAWINGS.
SQUARE DUCT
ROUND DUCT
DETAIL OF FLEXIBLE DUCT CONNECTOR
(NOT TO SCALE)
DUCT
FLEXIBLE MATERIAL IMPREGNATED
WOVEN GLASS CLOTH
DUCT
DRAW BANDS
STAINLESS STEEL
DETAIL
DRAW BAND
FLEXIBLE MATERIAL DRAW BAND
WEATHERPROOF. ALL HARDWARE SHALL BE STAINLESS STEEL IN THIS INSTANCE.
ACCESS DOOR & PANEL DETAILS
SECTION "B"-"B"
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS
3. PROVIDE ACCESS DOORS ON AIR HANDLING UNITS AND DUCT WORK INSTALLED
IN EQUIPMENT ROOMS. PROVIDE ACCESS PANELS ON ALL EQUIPMENT
AND DUCTWORK INSTALLED ABOVE FINISHED CEILINGS WHERE SPACE
4. ACCESS DOOR INSTALLED IN THE DUCT EXPOSED TO WEATHER TO BE
(NOT TO SCALE)
ACCESS DOOR
LIMITATIONS DO NOT ALLOW HINGED DOORS TO OPEN.
"B"
NOTES:
"B"
INSULATION
OR ACOUSTIC
LINING
OR ACOUSTIC
SECTION "A"-"A"
"A"
ACCESS PANEL
MIN. 3 LATCHES/DOOR
MIN. 3 HINGES/DOOR
"A"
CASING
DUCT OR
LINING
INSULATION
HANDLE INSIDE
GASKET
GASKET
DUCT
DUCTS PENETRATING NON-RATED WALLS
DETAIL FOR ACOUSTICAL SEALING OF
(NOT TO SCALE)
WALL
PIPING
THERMAL INSULATION AS
SPECIFIED
PIPING CLAMPS WELDED
TO PIPE
RISER CLAMP
NUTS AND BOLTS
PIPE RISER SUPPORTS DETAIL
(NOT TO SCALE)
SUPPLEMENTAL STEEL SUPPORTS BY
HVAC CONTRACTOR
SUPPLEMENTAL
STEEL (TYP.)
NOTES:
1.CENTERLINE OF PIPE SHALL ALIGN WITH CENTERLINE OF CLAMP
2.PROVIDE CONTINUOUS VAPOR BARRIER ON CHW PIPING
3.PROVIDE SHOP DRAWING TO STRUCTURAL ENGINEER FOR REVIEW
4.APPLICABLE TO PIPE RISERS GOING THROUGH LESS THAN 3 FLOORS.
SEAL, CAULK
WATER TIGHT
BASE FLASHING
(STAINLESS STEEL)
ROOF FINISH
ROOFING
SYSTEM
GALVANIZED MALEABLE IRON
(I.P.S.) FLASHING FITTING
COUNTER-FLASHING
(STAINLESS STEEL)
6" ALL AROUND
UPPER HALF WATER PROOF
CAULKING COMPOUND
LOWER HALF FIREPROOF
PACKING
SLAB
STEEL PIPE SLEEVE
ESCUTCHEON OR COVER
PIPE THRU ROOF SLAB
(NOT TO SCALE)
PENETRATION DETAIL
NOTE:
1.COORDINATE ALL FLASHING REQUIREMENTS WITH
ARCHITECTURAL DRAWINGS.
REINSULATE
ROOF
STRUCTURE
IF OPENING IN STRUCTURE IS
IRREGULAR AND GREATER
THAN 1", WRAP DUCT WITH 1"
THICK FIBROUS MATERIAL
AND FILL REMAINING OPENING
WITH GROUT
IF OPENING IS LIMITED TO
'(6,5('72Ð72r63$&(
PACK OPENING ALL AROUND
WITH FIBERGLASS AND CAULK
WITH NON-HARDENING SEALANT
DUCT LOAD SHOULD
NOT BE CARRIED BY
THIS SEAL
NON-HARDENING
MASTIC CAULKING
COMPOUND
Ð72r0$;,080
SHEET METAL SLEEVE
MINERAL WOOL
INSULATION
NOTE: PROVIDE QUANTITY/SIZE
OF PIPE/CONDUIT OPENING AS
REQUIRED, COORDINATE WITH
OTHER TRADES.
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:08pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
DETAILS
SHEET 3 OF 5
M6.03
GES
TRAPEZE HANGER
REPLACE FIREPROOFING
WHERE DISTURBED
NOTES:
1. SUBMIT SHOP DRAWING OF SUPPLEMENTAL STEEL SUPPORT FOR
REVIEW BY THE STRUCTURAL ENGINEER.
SLAB SUPPLEMENTAL STEEL
STEEL ANGLE (TYP.)
SUPPLEMENTAL STEEL SUPPORT FOR EQUIPMENT
AND PIPING DETAIL
(NOT TO SCALE)
THREADED HANGER ROD
WITH HEX (TYP.)
SUPPORT RODS WITH
LOCKING NUT
NOTE
INTERIOR WALL
U.L. FIRESTOP SYSTEM
PIPE SLEEVE OF SIZE
TO PASS PIPE
PIPE
1/2" to 3/4"
RATED WALL OR FLOOR
PIPE PENETRATION OF
(TYP. FOR BOTH SIDE OF WALL)
160
161
162
ADJUSTABLE WROUGHT CLEVIS
PACK WITH
INSULATING MATERIAL
INSULATION SADDLE
(SEE SCHEDULE)
PIPE
1/2" TO 1 1/2"
2" TO 10"
ABOVE 10"
INSULATION MATERIAL
HANGER GRINNELL FIG. 260
STEEL SADDLE FOR USE WITH
HOT PIPING INSULATION
INSULATION SADDLE SCHEDULE
PIPE SIZE GRINNEL FIG No.
VAPOR BARRIER
HOT WATER UNIT HEATER
(NOT TO SCALE)
AIR FLOW
MANUAL AIR VENT
CONTROL VALVE
SIZE OF PIPE
DIRT POCKET FULL
HWS
AQUASTAT
CIRCUIT SETTER
T
HWR
FULL WELD
TRANSITION DETAIL FROM STEEL TO COPPER
(NOT TO SCALE)
SCREWED COUPLING
BLACK STEEL PIPE RISER OR MAIN
RISER W/THREADED FEMALE END
SCHEDULE 40 WELD-O-LET
NEOPRENE GASKET
COPPER RUNOUT
KNURLED PIPE
OR LUBRICATED PLUG VALVE
W/FLANGED END
COPPER PIPE
TEFLON OR MICARTA
DIELECTRIC MATERIAL
GALVANIZED UNION SCHEDULE 40
SCREWED END BALL VALVE
JAMESBURY OR MCANNA
TO NEAREST FLOOR DRAIN
CHARGING VALVE
SHUT-OFF VALVE
GLOBE VALVE
QUICK FILL BY-PASS
FLOOR
DIRECTION
OF FLOW
FLOOR SUPPORTS
DIAPHRAGM TYPE EXPANSION TANK CONNECTIONS DETAIL
(NOT TO SCALE)
CLOSED LOOP AIR-SEPARATOR AND
DRAIN VALVE PIPED TO
NEAREST FLOOR DRAIN
(TYPICAL)
UNION
LOCKSHIELD VALVE
10" MIN.
DRAIN VALVE ARRANGEMENT
(NOT TO SCALE)
AT LOW POINTS OF RISERS
RISER OR UP-FEED
RUNOUT
HORIZONTAL BRANCH
OR MAIN
DIRT POCKET FULL
SIZE OF PIPE
(3" MAX.)
3/4" HOSE VALVE. PIPE TO NEAREST
FLOOR DRAIN
CAP
NIPPLE
AUTOMATIC AIR VENT
PIPE TO NEAREST
FLOOR DRAIN UNLESS
OTHERWISE NOTED
AUTO. AIR VENT W/PETCOCK
(TYP.)
ISOLATION VALVE
1/2" COPPER DRAIN LINE
TOP OF WATER
RISER OR HIGH
POINT IN PIPING
(NOT TO SCALE)
UNION
MANUAL AIR VENT DETAIL AT
HIGH POINTS OF MAINS AND RISERS
(IN ACCESSIBLE LOCATION)
MANUAL VENT COCK
(NOT TO SCALE)
OF MAIN
HIGH POINT
NIPPLE
CAP
SIZE OF PIPE
(3" MAX.)
AIR POCKET FULL
10" MIN.
3/4" STEEL OR
DRAIN LOCATION
1/2" COPPER TO
PIPE PENETRATION OF
INTERIOR NON-RATED WALL
NOT TO SCALE
INTERIOR
WALL
METAL PIPE
SLEEVE
PIPE
1" to 1 1/2"
SEAL BOTH SIDES WITH
NON-HARDENING FIRE
PROOF CAULK
MINERAL WOOL INSULATION
TIGHTLY PACKED FOR FULL
DEPTH OF WALL
PACK OPENING ALL
AROUND SHEET METAL
SLEEVE AIRTIGHT WITH
NON-HARDENING SEALANT
ADJUSTABLE RANGE
PRESSURE REDUCING VALVE
BACKFLOW PROTECTED
COLD WATER MAKE-UP
SHUT-OFF VALVE
SUPPLY CONNECTION
PRESSURE RELIEF VALVE
EXPANSION
TANK
STRAINER REMOVAL
SPACE
TO PUMP
SUCTION
AIR SEPARATOR
SARCO 13 W
FLOAT TYPE
AIR VENTAIR SEPARATOR
FCU-C-D-E
HC-C-D-EHC-BHC-A
HC-F-G-H
FCU-BFCU-A
FCU-F-G-H
14x8 20x8 32x8
48x8
OPEN RETURN
W/WMS
HOT WATER HEATING COIL
DUCT SIZE SAME SIZE AS
HEATING COIL (TYP.)
BACK FLOW
PREVENTER
FIRST 20'-0" OF ALL LOW
PRESSURE SUPPLY AND
RETURN DUCTWORK FROM
FCU UNITS SHALL BE 1"
ACOUSTICALLY LINED.
(TYP.) FOR ALL
OPEN RETURN
W/WMS
OPEN RETURN
W/WMS
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:08pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
DETAILS
SHEET 4 OF 5
M6.04
GES
TYPICAL CLAMP DETAILS
UFS - BEAM CLAMP ADJUSTABLE SIDE - BEAM CLAMP
NOT TO SCALE
ALL THREADED ROD,
SIZE AS REQUIRED
NUT & BOLT WITH
WASHER ASSEMBLY
TOP SLIDE
BOTTOM HOOK
STRUCTURAL STEEL
CLAMP JAWS
ALL THREADED ROD,
SIZE AS REQUIRED
JAM NUT
TIE ROD WITH
NUTS & WASHERS
CHEMICAL POT FEEDER DETAIL
NOT TO SCALE
ONE HALF
MAIN PIPE SIZE
3/4" DRAIN
CHEMICAL POT FEEDER
SEE SPECS.
3/4" FILL AND VENT VALVE
4'-0" ABOVE FLOOR MAX
FUNNEL
FLOW INDICATOR
UNION
(TYPICAL)PUMP DISCHARGE
PRESSURE GAUGE
PUMP SUCTION
CONDENSATE DRAIN TRAP
NOT TO SCALE
APPROVED AIR
GAP HEIGHT
EACH DIMENSION IS EQUAL
TO FAN NEGATIVE STATIC
PRESSURE
FULL SIZE OF DRAIN
CONNECTION
REMOVABLE CAP
UNION
DRAIN PAN
UNION
REMOVABLE CAP
FULL SIZE OF DRAIN
CONNECTIONDRAIN PAN
MINIMUM 1.5 X FAN
TOTAL STATIC
PRESSURE
APPROVED AIR
GAP HEIGHT
DRAW-THRU UNIT
BLOW-THRU UNIT
[[g$1*/(7<3,&$/
WOODEN JOIST (TYPICAL)
PIPE OR DUCT HANGER
WOOD JOIST DETAIL
PIPE/DUCT SUPPORT FROM
BOLT THROUGH JOIST (TYPICAL)
NOT TO SCALE
DOUBLE LOCK-NUT &
WASHER (TYPICAL)
HOT WATER CABINET UNIT HEATER DETAIL
NOT TO SCALE
HWR
HWS
BALL
VALVE
(TYP.)
STRAINER
AUTO CONTROL
VALVE PREWIRED
TO RETURN
THERMOSTAT
UNION
(TYP.)
CONTROLS
COIL
FAN
ROOF-TOP CENTRIFUGAL EXHAUST FAN
12" ROOF CURB
ROOF CURB
MOTORIZED DAMPER
3/4" MIN. OVERLAP
ROOF DECK & BUILT UP ROOFING
SEE PLAN FOR DUCT SIZE
CAULKING ALL-ROUND, TYP.
FLASHING & COUNTER FLASHING
FAN
FAN MOTOR
FAN HOUSING
NOT TO SCALE
FIELD WIRED FROM
DISCONNECT TO
STARTER
REFER TO MANUFACTURER'S
LITERATURE FOR SIZE OF
OPENING REQUIRED
10" CLEARANCE
ALL-ROUND
DAMPER
DETAIL # 3 - TOP OF RISER AND HORIZONTAL RUNS
DETAIL # 1 - BASE OF RISER DETAIL # 2 - RISER LINE
LEGEND
NOTE:
THIS DETAIL DOES NOT DEPICT SEISMIC SUPPORT INFORMATION. PROVIDE SEISMIC EQUIPMENT SUPPORT
IN ACCORDANCE WITH APPLICABLE CODES AND MANUFACTURERS RECOMMENDATIONS.
1.ACR COPPER REFRIGERATION LINES TYPE L
2.CLOSED CELL INSULATION. THICKNESS AS DESIGNATED FOR THE
PARTICULAR APPLICATION.
3.PIPE SUPPORT MATERIAL.
4.HYDRAZORB CLAMP ON LIQUID LINE ONLY. CORRESPONDING
SUCTION LINE TO BE TIE STRAPPED TO LIQUID LINE. 5
5.NYLON LOCKNUT (AIRCRAFT TYPE) AND CADIUM PLATED BOLT.
6.PLATE OR SHEET METAL SADDLE (8" TO 12" IN LENGTH) TO PREVENT
COMPRESSION OF INSULATION. SADDLE TO BE GLUED TO
INSULATION.
7.NYLON TIE WRAP. DESIGNED TO SECURE BUT NOT TO TOTALLY
PREVENT NORMAL EXPANSION AND CONTRACTION MOVEMENT.
REFRIGERATION PIPING SUPPORT DETAILS
NOT TO SCALE
(NO DAMPER FOR
DRYER EXHAUST)
CLG
ABOVE
VALVE (TYPICAL)
SHUT-OFF VALVE.
COMBINATION BALANCING &
HWR
U
HWS
SHUT-OFF VALVE.
AUTOMATIC CONTROL
(TYPICAL)
NOT TO SCALE
NOTES:
1.SIMILAR PIPING FOR MULTIPLE ELEMENTS IN SERIES.
2.WHEN INSTALLING TWO ELEMENTS HIGH IN SERIES, CONNECT HWS TO
BOTTOM ELEMENT AND PITCH UP TOWARD HWR.
3.THREE ELBOW CONNECTIONS SHALL BE USED AT SUPPLY & RETURN
CONNECTIONS TO & FROM RISERS TO SUIT PROJECT.
HOT WATER (BARE ELEMENT) FIN TUBE RADIATION
1/8" AIR VENT AT
TOP OF RISER
HWS
THE HORIZONTAL DIMENSION OF THE OIL TRAPS SHALL BE
AS SHORT AS POSSIBLE.
1.
NOTES:
SUCTION LINE
OIL TRAP
EXPANSION VALVE
SOLENOID VALVE
MOISTURE INDICATOR
FILTER DRIER
LIQUID LINE
STOP VALVE
WITH FITTINGS AS SPECIFIED FOR REFRIGERANT PIPING.
COMBINED AS PART OF THE MOISTURE INDICATOR.
(DRYERS MAY BE OF COMBINATION DRYER-INDICATOR TYPE)
PLUGS, AND RELIEF DISCHARGE PIPING AS RECOMMENDED BY ASHRAE 15. VENT
PRESSURE TAPS: EXCEPT AS INDICATED OTHERWISE, PROVIDE RELIEF VALVE, FUSABLE
DISCHARGE PIPING, WHERE REQUIRED, IN LOCATIONS THAT ARE SAFE FOR ALL
VALVE TO THE CONDENSER AND THE LIQUID LINE SIGHT GLASS. VALVES SHALL BE
FOR THE REFRIGERANT SYSTEM LOCATED IN THE LIQUID LINE BETWEEN THE SHUT-OFF
CHARGING VALVES: EXCEPT AS INDICATED OTHERWISE , PROVIDE CHARGING VALVES
350 PSIG WITHOUT DAMAGE. SIGHT GLASS BODY SHALL BE FORGED BRASS OR BRONZE
SIGHT GLASS INDICATOR SHALL CAPABLE OF WITHSTANDING A TEST PRESSURE OF
TYPE WITH TWO BULLS-EYE AND COVER CAPS OF NONFERROUS MATERIALS, UNLESS
LIQUID REFRIGERANT SIGHT GLASSES: PROVIDE THE DOUBLE-PORT, SEE-THROUGH
THE DESICCANT IN PLACE AND DISTRIBUTING THE LIQUID REFRIGERANT EQUALLY
DRYER SHALL BE CAPABLE OF WITHSTANDING A SERVICE PRESSURE OF 250 PSIG.
DRYER BODY SHALL BE OF BRASS OR STEEL AND PROVIDED WITH MEANS FOR HOLDING
6.
PERSONNEL IN AND AROUND THE BUILDING.
CONNECTED BY A FULL-SIZE LIQUID LINE TEE.
7.
a.
THROUGHOUT THE DESICCANT.
b.
5.
a.
PITCH ALL LINES DOWN IN DIRECTION OF REFRIGERANT FLOW.
REFRIGERANT DIAGRAM NOTES:
PROVIDE WITH EXTERNAL, REMOVABLE STRAINER.
VALVES SHALL OPEN WHEN TURNED COUNTER-CLOCKWISE.
ENDS OF VALVES SHALL CONFORM TO ANSI B2.1.
VALVES SHALL HAVE BRAZING TYPE CONNECTIONS.
STEEL OR NONCORROSIVE NONFERROUS INTERNAL PARTS.
REPLACEABLE WITHOUT BREAKING VALVE CONNECTIONS.
WITHOUT APPLYING HEAT OR BREAKING PIPE CONNECTIONS. THREADED
INTERNAL PARTS SHALL BE REMOVED FOR INSPECTION OR REPLACEMENT
VALVES SHALL HAVE BRASS, BRONZE OR STEEL ALLOY BODIES WITH STAINLESS
TEST AND RATE IN ACCORDANCE WITH ASHRAE STANDARD 17 AND ARI 750 FOR
PROVIDE VALVE SIZE AND SUPERHEAT ADJUSTMENT AS RECOMMENDED BY THE
POWER ASSEMBLIES AND VALVE CAGE ASSEMBLIES SHALL BE REMOVABLE AND
THERMOSTATIC EXPANSION VALVES (DIRECT-OPERATED): PROVIDE DIAPHRAGM AND
SPRING LOADED TYPE WITH EXTERNAL EQUALIZERS, BULB AND TUBING AND EXTERNAL
SPECIFICALLY FOR REFRIGERANT SERVICE AND SUITABLE FOR INSTALLATION WITH
REFRIGERATION: PROVIDE ISOLATION VALVES DESIGNED, MANUFACTURED, TESTED,
PROVIDED WITH A VALVED BYPASS OF THE SAME SIZE OF THE LIQUID LINE.
LIQUID LINE DRYERS: DRYERS SHALL BE THE CARTRIDGE REFILLABLE TYPE, AND
e.
4.
f.
VALVE MANUFACTURER.
CAPACITIES UP TO 40 KW.
d.
c.
SUPERHEAT ADJUSTMENT WITH SEAL CAP.
a.
b.
3.
b.
COPPER TUBING.
a.
1.
2.
TYPICAL REFRIGERANT FLOW DIAGRAM
NOT TO SCALE
AHU
ACCU
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:08pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
MECHANICAL:
DETAILS
SHEET 5 OF 5
M6.05
GES
ENCLOSED CIRCUIT BREAKER
FIRE ALARM SYSTEM, REMOTE ANNUNCIATOR
FLOW SWITCH
TAMPER SWITCH
TELECOM SCOPE NOTES:
1.ALL TELECOM (DATA AND VOICE) CABLING WORK (CABLES, PULLS &
INSTALLATION,) ARE NOT PART OF THIS BID PACKAGE, AND WILL BE
PERFORMED BY OTHERS.
2.THIS CONTRACTOR SHALL PROVIDE UNDER THE BASE BID TELECOM OUTLET
BOXES, CONDUITS, SLEEVES.
3.COORDINATE WORK WITH TENANT'S TELECOM CONTRACTOR.
ELECTRICAL SYMBOL LIST
AMPERE(S)
CONDUIT
WASHER & DRYER
CIRCUIT BREAKER
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
ABBREVIATIONS
EXISTING
EXHAUST FAN
ELECTRICAL
GROUND
LIGHTING
POLE(S)
RECEPTACLE
POWER PANEL
HORSE POWER
KILO VOLT-AMPERE
GROUND FAULT INTERRUPTER
EMPTY CONDUIT
EMERGENCY/NIGHT LIGHT
TIME CLOCK
SWITCH
TYPICAL
VOLT(S)
UNLESS OTHERWISE NOTED
WEATHERPROOF
WATT(S) / WIRE
G, GRD
WP
W
TYP.
UON
V
TC
SW.
PP
RECEP
LTG
P
KVA
GFI
HP
CB
EF
EM/NL
ELEC.
EX, EXIST.
EC
WD
AFF
C
A, AMP
AC
FIRE ALARM CONTROL PANEL
FIRE ALARM HORN/STROBE
MANUAL FIRE ALARM PULL STATION
DUCT SMOKE DETECTOR
HEAT DETECTOR
FIRE ALARM STROBE
FIRE ALARM CONTROL MODULE
FIRE ALARM MONITORING MODULE
CONDENSATE PUMPCP
FIRE ALARM TERMINAL CABINET
CEILING MOUNTED RECEPTACLE, TYPE AS SHOWN
DOUBLE DUPLEX RECEPTACLE IN 2 GANG BOX, 20A, 125V,
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED),
RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED),
SINGLE RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED)
6-20R
2
GFI
2P, 3W (GROUNDED), NEMA CONFIG. 5-20R
NEMA CONFIG. 5-20R
SINGLE SPECIAL PURPOSE RECEPTACLE:
NEMA CONFIG. 5-20R
NEMA CONFIG. 5-20R:
(APPLIANCE OR EQUIPMENT OUTLET)
DENOTES CIRCUIT NUMBER-'2'
'GFI'DENOTES GROUND FAULT INTERRUPTER-
DENOTES SWITCH CONTROL-'a'
'6-20R'
'R'-
-DENOTES NEMA CONFIGURATION
DENOTES RANGE
PANEL OR CABINET, TYPE AS NOTED
PANELBOARD (SURFACE TRIM)
PANELBOARD (FLUSH TRIM)
DISTRIBUTION PANELBOARD
a
2
CONTROL SWITCH:
DENOTES SWITCH CONTROL-'a'
DENOTES 3-WAY SWITCH-'3'
DENOTES 4-WAY SWITCH-'4'
DENOTES AUTOMATIC VACANCY SENSOR SWITCH-'VC'
3
a
CEILING, WALL MOUNTED REMOTE EMERGENCY LIGHT
WALL OUTLET BOX AND LIGHT FIXTURE
CEILING, WALL MOUNTED JUNCTION BOX
CEILING OUTLET BOX AND LIGHT FIXTURE:
HALF SHADE INDICATES FIXTURE WITH INTEGRAL EMERGENCY
CEILING, WALL OUTLET BOX AND EXIT LIGHT:
- DIRECTIONAL ARROWS AS INDICATED
- SHADED AREA DENOTES FACE(S) UPON WHICH
EMERGENCY LIGHTING BATTERY UNIT WITH SEALED BEAM HEADS
- TICK WITH 'G' INDICATES SEPARATE INSULATED GROUND WIRE
- TICK MARKS INDICATE NUMBER OF WIRES CONTAINED
IN CONDUIT
CIRCUIT HOMERUN TO PANELBOARD AND CIRCUITS INDICATED
MULTI-POLE CIRCUIT HOMERUN TO PANELBOARD AND
(PROVIDE IN ALL CONDUITS WHETHER SHOWN OR NOT.)
CONNECTED TO UNSWITCHED LEG OF LOCAL LIGHTING CIRCUIT.
HR
DP-A #2
J J
BATTERY BALLAST.
'EXIT' APPEARS
CONDUIT RUN CONCEALED:
LP-3A
#1,3,5(R)
G
A
a
a
2
2
A
CIRCUITS INDICATED
CONDUIT RUN CONCEALED IN CEILING
DENOTES FIXTURE TYPE-'A'
DENOTES CIRCUIT NUMBER-'2'
DENOTES SWITCH CONTROL-'a'
DENOTES EMERGENCY-'EM'
DENOTES EMERGENCY BATTERY BALLAST-'EMB'
DENOTES NIGHT LIGHT (UNSWITCHED)-'NL'
DENOTES SWITCHED-'SW'
ARROWS DENOTE NUMBER OF CIRCUITS-
(R)DENOTES CIRCUIT VIA RELAY FOR CONTROL-
(PC)DENOTES VIA PHOTOCELL FOR CONTROL-
TAIL DENOTES CONNECTION TO EQUIPMENT -
AS REQUIRED
DENOTES HOMERUN JUNCTION BOX-'HR'
SMOKE DETECTOR
TV WALL MOUNTED CATV OUTLET
WALL MOUNTED DATA OUTLET
- DENOTES PUBLIC TELEPHONE`P'
TELEPHONE OUTLET:
`W'- DENOTES FOR WALL MOUNTED TELEPHONE
U.O.N. PROVIDE BUSHINGS.
WITH DEDICATED 1"C STUBBED UP TO ABOVE ACCESSIBLE CEILING
2-GANG COVER, 4-11/16" SQ. x 2-1/8"D BOX
WALL MOUNTED COMBINATION DATA/TELEPHONE OUTLET:
MOUNTEDMTD
DENOTES FOR AUDIO VISUAL CABLING-'AV'
DENOTES ABOVE COUNTER HEIGHT-'AC'
WALL
FIRE ALARMFA
DOUBLE DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W (GROUNDED),
NEMA CONFIG. 5-20R
(APPLIANCE OR EQUIPMENT OUTLET)
'MC'DENOTES MOMENTARY CONTACT SWITCH-
S
F
H
D
F
F
VC
VC
W
DENOTES WATER COOLER-'WC'
DENOTES REFRIGERATOR-'R'
DENOTES MICROWAVE-'M'
DENOTES COFFEE MAKER-'C'
DENOTES DISHWASHER-'D'
RECESSED 4-GANG WALL BOX FOR TV SIMILAR TO LEGRAND
EFSB4 SERIES.
WIRELESS ACCESS POINT LOCATION
DENOTES CEILING MOUNTED OCCUPANCY SENSOROC
WALL MOUNTED DUAL TECHNOLOGY VACANCY SENSOR
UTILIZE EXISTING SWITCH TO PROVIDE MANUAL ON/OFF
OVERRIDE.
CEILING MOUNTED DUAL TECHNOLOGY VACANCY SENSOR WITH 1000 SQ
FT COVERAGE. PROVIDE POWER / RELAY PACK(S) AND MOMENTARY
CONTACT ON/OFF SWITCH(ES) AS REQUIRED FOR SWITCHING INDICATED.
W
WASHER-'W'
NOTIFICATION APPLIANCE CIRCUITNAC
MM
CM
SMOKE DETECTOR WITH SOUNDER BASESSB
TS
FS
CB
RA
GENERAL NOTES:
1.REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL
REQUIREMENTS.
2.ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE, REVIEW
ARCHITECTURAL DRAWINGS AND BE RESPONSIBLE FOR REVIEWING A FULL
SET OF BID DOCUMENTS TO MAKE HIMSELF AWARE OF THE TOTAL JOB
BEFORE SUBMITTING HIS PRICE.
3.VERIFY ALL EXISTING SITE CONDITIONS IN THE FIELD AND INCLUDE IN THE
BID, THE PRICE OF ALL WORK REQUIRED.
4.ALL WORK SHALL BE INSTALLED CONCEALED UNLESS OTHERWISE NOTED.
5.CONTRACTOR SHALL FIELD VERIFY DIMENSIONS OF FINISHED
CONSTRUCTION PRIOR TO FABRICATION AND INSTALLATION OF FIXTURES
AND EQUIPMENT.
6.ELECTRICAL CONTRACTOR SHALL SUBMIT SAMPLES OF RECEPTACLES AND
PLATES TO THE ARCHITECT FOR APPROVAL BEFORE MAKING HIS
INSTALLATION.
7.LIGHTING FIXTURES IN ACCESSIBLE CEILINGS SHALL BE FURNISHED WITH
FLEXIBLE CONDUIT CONNECTIONS TO SEPARATELY MOUNTED JUNCTION
BOXES. ONE JUNCTION BOX SHALL SERVE A MAXIMUM OF FOUR (4)
FIXTURES. MAXIMUM LENGTH OF FLEXIBLE CONNECTION SHALL BE 6'-0".
8.WIRING IN AIR PLENUM HUNG CEILINGS INSTALLED WITHOUT CONDUIT OR
EMT SHALL BE TEFLON JACKETED AND PLENUM RATED.
9.CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF EQUIPMENT TO
BE INSTALLED BY OTHER TRADES BEFORE STARTING CONDUIT WORK.
10.CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL RACEWAYS AND
WIRING FROM EQUIPMENT AND DEVICES TO THEIR SOURCE OF POWER.
11.CONTRACTOR SHALL, AFTER HIS WORK IS COMPLETED, TEST THE
ELECTRICAL DISTRIBUTION SYSTEM FOR SHORT CIRCUITS, LOOSE WIRING,
ETC., TO THE SATISFACTION OF THE OWNER. ALL COSTS FOR THIS TEST
SHALL BE BORNE BY THE CONTRACTOR.
12.FOR WIRING IN METAL PARTITIONS WHERE EMT IS IMPRACTICAL, FLEXIBLE
STEEL CONDUIT GALVANIZED, MINIMUM 3/4" SHALL BE USED.
13.FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL ELECTRICAL
OUTLETS, SWITCHES AND LIGHTING FIXTURES SEE ARCHITECTURAL FLOOR
PLANS, DETAILS AND ELEVATIONS.
14.MOUNTING HEIGHTS OF EQUIPMENT AND DEVICES SHALL BE AS INDICATED
ON THE ARCHITECTURAL DRAWINGS. WHERE MOUNTING HEIGHTS ARE NOT
GIVEN ON THE ARCHITECTURAL DRAWINGS, UTILIZE THE FOLLOWING
MOUNTING HEIGHTS UNLESS OTHERWISE NOTED (ALL DIMENSIONS TO
CENTERLINE OF BOX):
A.RECEPTACLES (WALL MOUNTED) - 15" A.F.F.
B.TELEPHONE/DATA OUTLETS - SAME AS RECEPTACLES
C.WALL MOUNTED TELEPHONES - 44" A.F.F.
D.LIGHTING SWITCHES AND CONTROLS - 48" A.F.F. TO TOP OF HANDLE
E.MANUAL FIRE ALARM STATIONS - 48" A.F.F. TO TOP
F.FIRE ALARM HORN AND STROBE UNITS - 80" A.F.F. OR 6" BELOW THE
G.CARD READERS - 48" A.F.F. TO TOP
H.PANELBOARDS AND CABINETS - 78" TO TOP OF ENCLOSURE.
15.MINIMUM RACEWAY SIZE SHALL BE 3/4" AND SHALL BE RUN PARALLEL TO
BUILDING STRUCTURAL LINES. RACEWAYS SHALL NOT BE RUN
HORIZONTALLY BELOW 8'-0" IN PARTITIONS. ALL EMPTY RACEWAYS SHALL
BE FURNISHED WITH A 200 LB. TEST NYLON DRAG LINE.
16.WHERE EQUIPMENT, LIGHTING FIXTURES AND WIRING DEVICES ARE SHOWN
WITH CIRCUIT NUMBERS ONLY, THE MINIMUM BRANCH CIRCUITING
REQUIREMENTS SHALL BE AS FOLLOWS:
A.LIGHTING FIXTURES - 2#12, 1#12 GRD. - 3/4"C.
B.RECEPTACLES - 2#12, 1#12 GRD. - 3/4"C.
C.HOMERUNS TO PANEL BOARDS SHALL CONTAIN NO MORE THAN (3)
CIRCUITS.
D.WHERE LIGHTING SWITCH INDICATIONS ARE NOT SHOWN, SWITCHES
SHALL BE CONNECTED TO CONTROL ALL SWITCHED FIXTURES WITHIN
THE CORRESPONDING SPACE.
17.WIRE SIZES SHALL BE INCREASED TO COMPENSATE FOR VOLTAGE DROP
AS FOLLOWS:
A.120V CIRCUITS LONGER THAN 75' SHALL UTILIZE MIN. #10 AWG.
GARBAGE DISPOSALGD
'WD'-DENOTES WASHER & DRYER
S SB
CO SMOKE DETECTOR / CO DETECTOR COMBINATION WITH SOUNDER BASE
DISCONNECTDISC.
E. ELECTRICAL DRAWING LIST
E0.GENERAL
E0.01 GENERAL NOTES & SYMBOL LIST
E1.SITE PLAN
E1.00 SITE PLAN
E2.BUILDING PLANS
E2.00 LOWER LEVEL PLAN
E2.01 GROUND FLOOR PLAN
E2.02 SECOND FLOOR PLAN
E2.03 THIRD FLOOR PLAN
E2.04 FOURTH FLOOR PLAN
E2.05 ROOF PLAN
E4.DIAGRAMS
E4.01 POWER RISER DIAGRAM
E4.02 AUXILIARY SYSTEM RISER DIAGRAMS
E5.SCHEDULES
E5.01 SCHEDULES
E6.DETAILS
E6.01 DETAILS
DOOR HOLDERDH
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
ELECTRICAL:
GENERAL NOTES
& SYMBOL LIST
E0.01
AJS
DRYDEN SOUTH, LLC (R.O.)
DRY-LIN LLC
PEA FAMILY REALTY, LLC (R.O.)
LINDEN AVENUE ASSOCIATES (R.O.)
LAMBROU (R.O.)
EXISTING JOHNSON SCHOOL
OF MANAGEMENT
LRP-43
LRP-33
LRP-23
LRP-13
LRP-03
LRP-41
LRP-31
LRP-21
LRP-11
LRP-01
LRP-42
LRP-32
LRP-22
LRP-12
LRP-02
LRP-44
LRP-34
LRP-24
LRP-14
LRP-04
LRP-15
LRP-45
LRP-35
LRP-25
SPP
ATS
LRP-1BH
PP-1BH
INCOMING
TELECOM
SERVICE (2) 3"C
T
UTILITY
TRANSFORMER
MMU
MULTIPLE
METERING UNIT
(TYP)
M M M M MM
UNDERGROUND 2" CONDUITS
(TYP FOR EACH APARTMENT
PANEL FEEDER)
1
(2)5" EMPTY CONDUITS
WITH PULL STRINGS
UTILITY POLE
APPROXIMATE
LOCATION OF LOWER
LEVEL IT/DATA ROOM
4 SETS OF
3#350KCMIL+1#3/0G-3"C
KEYED NOTES
TYPICAL FEEDERS TO BE ROUTED UNDER AREAWAYS AND
UNDER BASEMENT FLOOR SLABS. FEEDERS TO STUB UP AT
PANEL LOCATIONS. FEEDERS TO UPPER FLOOR PANELS TO BE
CONCEALED IN WALLS.
1
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
0 4 8 16 FEET
SCALE: 1/8"=1'-0"1 SITE PLAN
ELECTRICAL:
SITE PLAN
E1.00
AJS
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
IT/DATA
HOUSEKEEPING /
BUILDING STORAGE
MECHANICAL
KEYED NOTES
LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE
THE DOOR. COORDINATE EXACT LOCATION WITH
THE OWNERS REPRESENTATIVE FROM DATA
CLOSET.
CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT
AND CONTROL DEVICE.
UP TO LIGHT AND SWITCH AT TOP OF SHAFT
PROVIDE 4-CHANNEL, ASTRONOMICAL TIME CLOCK
WITH PHOTOSENSOR OVERRIDE SIMILAR TO TORK
#DLC400BP. COORDINATE PROGRAMMING WITH
OWNER.
COORDINATE MACHINE ROOMLESS ELEVATOR
POWER / CONTROLS LOCATION WITH
MANUFACTURER'S DATA / EQUIPMENT AT TOP OF
SHAFT.
FOR MOTORIZED DAMPERS INSTALLED ON PLENUM.
PROVIDE INTERCONNECTION TO BOILERS, HOT
WATER HEATER, AIR HANDLER, AND MECHANICAL
ROOM EXHAUST FAN TO OPEN DAMPERS UPON
ACTIVATION OF ASSOCIATED EQUIPMENT.
COORDINATE EXACT REQUIREMENTS WITH
MECHANICAL CONTRACTOR.
FIRE ALARM SYSTEM SHALL SHUNT TRIP POWER
UPON HEAT DETECTOR ACTIVATION. PROVIDE
ADDITIONAL INTERFACE RELAY AS REQUIRED FOR
MONITORING OF ELEVATOR POWER.
1
2
3
4
5
6
7
DRAWING NOTES:
1.ALL CIRCUITS SHOWN SHALL BE FED FROM
'PP-1BH', U.O.N.
2.EMERGENCY BALLASTS OF ALL FIXTURES
LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF
UNSWITCHED CIRCUIT SERVING THE AREA.
3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE
WIRED THRU TIME CLOCK LOCATED IN LOWER
LEVEL MECHANICAL ROOM.
F1
F3
F1
F1
F1 F1
F1
F3
F1
F3
F5
F4
F5
R
b
aab
TV+
2
BS
JSM
ALL CIRCUITS SHALL BE FED
FROM 'LRP-03', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-01', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-02', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-04', U.O.N.
JSM
P-HW-1
P-HW-2
CO MONITORING
PANEL
FOR
ELEVATOR
S
GFI
H
5
GFI3
H
H
H
S
S
S
S
S
SPPATS
LRP-1BH
PP-1BH
1
FOR RANGE HOOD
/ MICROWAVE
(TYP.)
LRP-03
LRP-01
LRP-02
FCU-B
VFD
AHU-1
VFD
VFD
D
11 17
1FSD
6
4
B-2
B-1
35
EM/NL
EM/NL
GFI
FACP
3
EM
EM
EM
EM
F F
FF
F
F
TS
TS
TS
FS
TS
TS
TS
TS
TS
GWH-1 GWH-2
CONSTANT AIR VOLUME
CONTROL PANEL
PUMP CONTROL PANEL
(TYP FOR 2)
GFP-1
UH-B
SP-1
EJ-1
MM
JSM3 33 5 7 79
11
13
4
44
4
M
2
1
1 8 8
8
1
1
6
4
F1
F1
F1 F1
F4
R
b
aab
TV+
2
JSM
1
FCU-B
3 5 7 79
11
13
4
44
4
M
2
1
1 8 8
8
1
1
6
4
F1
F1
F1 F1
F4
R
b
aab
TV+
2
JSM
1
FCU-B
3 5 7 79
11
13
4
44
4
M
2
1
1 8 8
8
1
1
6
4
F1
F1
F1 F1
F4
R
b
ab
TV+
2
JSM
1
FCU-B
3 5 7 79
11
13
4
44
4
M
2
1
1 8 8
8
1
1
6
4
10
10
10
10
1
1
1
1
1
1
1 1
1
FF
OC
OC
BS
JSM
BS
JSM
BS
JSM
M
UH-A
16
SPP
SPP
G
G
G
G
JSM
CP-1
11
14
10
10
SPP
7
9
2
SPP
SPP
SPP#8 SPP#8
SPP#8
SPP#8
SPP#8
SPP#8
2
2
2
1
8
10
12
14
ALL CIRCUITS SHALL BE FED
FROM 'LRP-1BH', U.O.N.
11
1
TC
FOR ELEVATOR4
13
15
15
FS
TS
30
F2X
F2X
EF-3
LRP-04 EWH-A
14
11
11
11
13
LRP-1BH
13
LRP-1BH
10
10
J
FOR DOOR HOLD OPEN
16
ANN
GENERATOR
ANNUNCIATOR
7
SPP
7
28
TO ELEV
DISC. IN
MECH.
ROOM
7
NL
NL
a
EM
a
EM
a
EM
F3
1a
EM
a
a
a
a
35SCO
SB
S CO
SB
S CO
SB
S CO
SB
8
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 LOWER LEVEL PLAN
ELECTRICAL:
LOWER LEVEL
PLAN
E2.00
AJS
1
1
1
1
1
2
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
ENTRY LOBBY
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
KEYED NOTES
LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE
THE DOOR. COORDINATE EXACT LOCATION WITH
THE OWNERS REPRESENTATIVE FROM DATA
CLOSET.
CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT
AND CONTROL DEVICE.
1
2
DRAWING NOTES:
1.ALL CIRCUITS SHOWN SHALL BE FED FROM
'PP-1BH', U.O.N.
2.EMERGENCY BALLASTS OF ALL FIXTURES
LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF
UNSWITCHED CIRCUIT SERVING THE AREA.
3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE
WIRED THRU TIME CLOCK LOCATED IN LOWER
LEVEL MECHANICAL ROOM.F1
F1
F1F1
F1
F1
F1
F1
F1
F1
F3
F1
F1
F1F1F1
F1
F1F1
F1
F1
F1 F1
F1
F5F6
F5
F4
F2 F2
F4
F4
F4
F4
R
R
R
R
R
b
aab
b
aab
b aab
b
aab
b
aab
TV +
TV+
ALL CIRCUITS SHALL BE FED
FROM 'LRP-13', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-11', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-12', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-14', U.O.N.
2
BS
JSM
BS
JSM
BS
JSM
BS
JSM
JSM
JSM
JSM
J
SM
JSM
ALL CIRCUITS SHALL BE FED
FROM 'LRP-15', U.O.N.
FCU-E
JSM
S
1
1
1
1
1
FCU-B
FCU-B
FCU-B
FCU-B
FCU-A
EM/NL
EM/NL
EM
EM
EM
EMEM
EM
FF
F F
TS
FS
OC
OC
OC
OC
1
1
1
1 1
1 1
11
1
1
FF
1
LRP-13
LRP-11
LRP-12
13
77539
11
4
44
2
4
M
6 4
1
1 8 8
8
1
44
M
4
44
7539
10
11
7
6
TV+
1
1 8
1
1
8
8
TV+
1
1 8
1
1
8
8
TV+
1
1 8
1
1
8
8
1
188
8
1
1
4
4
4 4
7539
13
M
13
7539
13
M
4
4
4 4
4
13
9
11
3 5 7 7
10
M 4
4
4
4 4
11
6
6
7
7
1
11
11
1
BS
JSM
CUH-A
2
2
2
M
17
M
17
LRP-15
LRP-14
FX5
FX5
2
2
2
2
EWH-A
14
EWH-A
14
11
11
11
11
11
13
LRP-1BH
13
LRP-1BH
10
10
10
10
10
J
FOR DOOR HOLD OPEN
16
J16
FOR ENTRY DOOR
POWER SUPPLY
F3
1a
EM
F3
1a
EM
NL
F3
1a
EM
NL
F3
1a
EM
a
a a
a
EM/NL
F6 1EM/NL
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S
S
S
8
8
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 GROUND FLOOR PLAN
ELECTRICAL:
GROUND FLOOR
PLAN
E2.01
AJS
1
1
1
1
1
1
1
1
1
2
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
KEYED NOTES
LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE
THE DOOR. COORDINATE EXACT LOCATION WITH
THE OWNERS REPRESENTATIVE FROM DATA
CLOSET.
CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT
AND CONTROL DEVICE.
PROVIDE ROOF SNOW & ICE MELTING CABLE ON
CANOPY SIMILAR TO RAYCHEM GM-1XT. PROVIDE
WITH DIGITAL ELECTRONIC CONTROLLER WITH
GROUND FAULT (RAYCHEM #ECW-GF) AND ALL
REQUIRED POWER CONNECTION KITS, END SEALS,
MOUNTING ACCESSORIES AND OTHER ASSOCIATED
APPURTENANCES FOR A COMPLETE AND FULLY
OPERATIONAL SYSTEM. ELECTRONIC CONTROLLER
SHALL BE MOUNTED UNDERNEATH CANOPY. WIRE
TO PANEL LRP-1BH CIRCUIT #7.
1
2
3
DRAWING NOTES:
1.ALL CIRCUITS SHOWN SHALL BE FED FROM
'PP-1BH', U.O.N.
2.ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO
HOT LEG OF UNSWITCHED CIRCUIT SERVING THE
AREA.
3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE
WIRED THRU TIME CLOCK LOCATED IN LOWER
LEVEL MECHANICAL ROOM.
F1 F1
F1F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1F1
F1 F1
F4
F4
F5
F4
F4
F4
F5
F2
aR
R
R
R
b
ab
ab
aab
ab
ab
b
baab
b
a
c
TV+
TV+
TV+
ALL CIRCUITS SHALL BE FED
FROM 'LRP-23', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-21', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-22', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-24', U.O.N.
BS
JSM
BS
JSM
BS
JSM
BS
JSM
JSM
JSM
J
SM
JSM
ALL CIRCUITS SHALL BE FED
FROM 'LRP-25', U.O.N.
S
FCU-D
JSM
1
1
1
1
1
4
4
4
4
4
4 6
2
10
FOR RANGE HOOD
/ MICROWAVE
(TYP.)
FCU-B
FCU-B
FCU-B
FCU-B
EM/NL
EM/NL
EM
EMF
F
FF
TS
FS
R
TV+
13
8
4a
c
1
1 1
8
8
LRP-23
LRP-21
LRP-22
LRP-24
3
3 3
TV+
1
1 8
8
1
1
8
13
77539
13
77539
13
77539
7 7 5 3 9
M
M
M
M
9
11
3 5 7 7
11
2
4
4
44
4
1
1
6
11
1
1 8
8
8
6
4
4
44
4
11
1
1 8
8
8
4 4
4
4
462
11
1
1
4
4
44
4
13
1
1
8
8 1
1
8
26
1
1
10
10
10
10
3
F
BS
JSM
4
4
4
4
4
FX6
2
2
2
2
2
LRP-25
11
11
11
11
13
LRP-1BH
10
10
10
10
10
J
FOR DOOR HOLD OPEN
16
F
F
F1
F1
F1
F6
OC
OC
OC
3
3
3
3
F3
3a
EM
F3
3a
EM
NL
F3
3a
EM
NL
3a
EM
a
a a
a
EM/NL
F6 3EM/NL
F3
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S
S
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 SECOND FLOOR PLAN
ELECTRICAL:
SECOND FLOOR
PLAN
E2.02
AJS
1
1
1
1
1
1
1
1
1
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF KEYED NOTES
LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE
THE DOOR. COORDINATE EXACT LOCATION WITH
THE OWNERS REPRESENTATIVE FROM DATA
CLOSET.
CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT
AND CONTROL DEVICE.
PROVIDE ROOF SNOW & ICE MELTING CABLE ON
CANOPY SIMILAR TO RAYCHEM GM-1XT. PROVIDE
WITH DIGITAL ELECTRONIC CONTROLLER WITH
GROUND FAULT (RAYCHEM #ECW-GF) AND ALL
REQUIRED POWER CONNECTION KITS, END SEALS,
MOUNTING ACCESSORIES AND OTHER ASSOCIATED
APPURTENANCES FOR A COMPLETE AND FULLY
OPERATIONAL SYSTEM. ELECTRONIC CONTROLLER
SHALL BE MOUNTED UNDERNEATH CANOPY. WIRE
TO PANEL LRP-1BH CIRCUIT #9.
1
2
3
DRAWING NOTES:
1.ALL CIRCUITS SHOWN SHALL BE FED FROM
'PP-1BH', U.O.N.
2.EMERGENCY BALLASTS OF ALL FIXTURES
LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF
UNSWITCHED CIRCUIT SERVING THE AREA.
3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE
WIRED THRU TIME CLOCK LOCATED IN LOWER
LEVEL MECHANICAL ROOM.
R
R
R
R
R
b
aab
b
aab
b
aab
b
aba
TV+
TV+
TV+
TV+
ALL CIRCUITS SHALL BE FED
FROM 'LRP-33', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-31', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-32', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-34', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-35', U.O.N.
JSM
JSM
JSM
JSM
2
2
2 FCU-C
JSM
S
3
1
1
1
1
1
FCU-B
FCU-B
FCU-B
FCU-B
EM/NL
EM/NL
EM
EM
FF
F
F
TS
FS
LRP-34
LRP-33
LRP-31
LRP-32
3
3
3
3
13
77539
11
13
77539
11
13
4
4
44
2 6
1
1
M
M
M
M
M
4 4
4
4
4
6
1
1
2
2 6
4
4
4 4
1
1
1
1
6
11
13
44
2
4
44
4
2
4
44
4
4 6
13
7
11
9 3 5 7
1
1 8
8
8
1
1 8
8
8
1
1 8
8
8
8
1
1 1
8
8
8 1
1
8
7 7 5 3 9
77539
11
10
10
10
10
10
OC
BS
JSM
BS
JSM
BS
JSM
BS
JSM
3
BS
J
SM
4
4
4
TV+
1
1
LRP-35
2
2
4
b
b
aa
a
c
11
11
11
11
11
10
10
10
10
10
J
FOR DOOR HOLD OPEN
16
F
F
F1
F1
F1
F6
OC
OC
OC
3
3
3
F3
3a
EM
F3
3a
EM
NL
F3
3a
EM
NL
3a
EM
a
a a
a
EM/NL
F6 3EM/NL
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S
S
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 THIRD FLOOR PLAN
ELECTRICAL:
THIRD FLOOR
PLAN
E2.03
AJS
1
1
1
1
1
1
1
1
1
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
EFFICIENCY
330 SF
1-BED
430 SF
KEYED NOTES
LOCATE DATA OUTLET INSIDE THE CLOSET ABOVE
THE DOOR. COORDINATE EXACT LOCATION WITH
THE OWNERS REPRESENTATIVE FROM DATA
CLOSET.
CONNECT TEF-# TO BATHROOM LIGHTING CIRCUIT
AND CONTROL DEVICE.
DOWN TO LIGHT AND SWITCH AT BOTTOM OF
SHAFT
1
2
3
DRAWING NOTES:
1.ALL CIRCUITS SHOWN SHALL BE FED FROM
'PP-1BH', U.O.N.
2.EMERGENCY BALLASTS OF ALL FIXTURES
LABELLED 'EM' SHALL BE WIRED TO HOT LEG OF
UNSWITCHED CIRCUIT SERVING THE AREA.
3.ALL EXTERIOR LIGHT FIXTURES (TYP FX#) SHALL BE
WIRED THRU TIME CLOCK LOCATED IN LOWER
LEVEL MECHANICAL ROOM.
F1F1
F1
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F2
F1
F1
F1 F1
F1
F1
F1F1
F5
F5
F4
F4
F4
F4
F4
R
R
R
R
b
aab
b
aab
b
aab
b
aba
R
ALL CIRCUITS SHALL BE FED
FROM 'LRP-43, U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-41', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-42', U.O.N.
ALL CIRCUITS SHALL BE FED
FROM 'LRP-44', U.O.N.
JSM
JSM
JSM
JSM
2
2
2
2
FCU-C
JSM
3
S H
S
1
1
1
1
1
ALL CIRCUITS SHALL BE FED
FROM 'LRP-45', U.O.N.
EM/NL
EM/NLEM
EM
FF
F
F
TS
FS
LRP-43
LRP-41
LRP-42
LRP-45
LRP-44
5
5
5 5
13
77539
11
13
77539
11
13
77539
11
1
1 8
8
8
1
1 8
8
8
1
1 8
8
8
8
1
1 1
8
8
8 1
1
8
13
7
11
9 3 5 7
2
2
2
2
2
M
M
M
M
M
FCU-B
FCU-C
FCU-B
7 7 5 3 9
11
10
10
10
10
10
FCU-B TV+
1
1
TV+
1
1
TV+
1
1
TV+
1
1
TV+
1
1
6
6
6
6
6
4
4
4
4
4
4
4
4 4
4
4
4
4
4 4
44
4
4
4
4
4
4
44
4
4
13
BS
JSM
BS
J
SM
BS
JSM
BS
J
SM
BS
J
SM
6
6
6
2
b
ab
a
a
c
11
11
11
11
11
10
10
10
10
10
J
FOR DOOR HOLD OPEN
16
F
F
F1
F1
F1
F6
OC
OC
OC
5
5
5
5
F3
5a
EM
F3
5a
EM
NL
F3
5a
EM
NL
5a
EM
a
a a
a
EM/NL
F6 5EM/NL
F3
TS
a
a GFI
15
3
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S CO
SB
S
S
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 FOURTH FLOOR PLAN
ELECTRICAL:
FOURTH FLOOR
PLAN
E2.04
AJS
1
1
1
1
1
1
1
1
1
REF-1R-2.2R-2.5R-3.2R-3.5R-4.2R-4.5REF-5REF-F
REF-F
REF-A
REF-A
REF-C
REF-C
REF-D
REF-D REF-E
REF-B
REF-5REF-1REF-4R-2.6R-4.3REF-3REF-2R-4.9JST
EF-2
JST
EF-1
JST
TEF-E
JST
TEF-C
J
ST
TEF-B
JST
TEF-A
ACCU-1
WP
WP
WP
WP
WP
WP
ACCU-2
12KW / 15kVA, 208/120V,
3-PHASE, 4-WIRE, NATURAL GAS
GENERATOR WITH 60A OUTPUT
CIRCUIT BREAKER IN
WEATHERPROOF, LEVEL 1,
SOUND ATTENUATED
ENCLOSURE (APPROX. 500 LBS)
ACCU-3
JST
TEF-D
WP
23 2GFI
WP
a
GFI
WP
a
PC
aGFI
WP
a
a
DRAWING NOTES:
1.ALL CIRCUITS SHOWN SHALL BE FED FROM
'PP-2BH', U.O.N.
2.ALL FIXTURES LABELLED 'EM' SHALL BE WIRED TO
HOT LEG OF UNSWITCHED CIRCUIT SERVING THE
AREA.
KEYED NOTES
MOTORIZED DAMPERS FOR EXHAUST FANS SHALL BE
CONNECTED TO 120V CIRCUIT OF ASSOCIATED FAN.
PROVIDE ALL REQUIRED 120V POWER TO
THERMOSTAT AND MOTORIZED DAMPER.
COORDINATE LOCATION OF EQUIPMENT WITH
MECHANICAL CONTRACTOR.
1
2
29
GFI
WP 12
a
GFI
WP
a
8
8
8
8
10
10
10
12
12
12
12
12
12
12
12
12
1
2
2
2
2
2
JST
TEF-A
WP10
2
J
ST
TEF-E
WP8
2
a
12a
12
a12
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
PROJECT
NORTH
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
SCALE: 1/4"=1'-0"
0 4 8 FEET
1 ROOF PLAN
ELECTRICAL:
ROOF PLAN
E2.05
AJS
LOWER LEVEL
GROUND FLOOR
SECOND FLR
THIRD FLR
FOURTH FLR
ROOF
GRADE
KEYED NOTES
3#1/0+1#6G-2"C1
MECH
LRP-01 LRP-02 LRP-04 LRP-03
LRP-13LRP-14LRP-15LRP-11 LRP-12
LRP-22
LRP-32
LRP-42
LRP-25
LRP-35
LRP-45
LRP-24
LRP-34
LRP-44
LRP-23
LRP-33
LRP-43
LRP-21
LRP-31
LRP-41
G
12kW / 15kVA, 208/120V
3-PHASE, 4-WIRE, NATURAL GAS GENERATOR
WITH 60A OUTPUT CIRCUIT BREAKER IN
WEATHERPROOF, LEVEL 1, SOUND
ATTENUATED ENCLOSURE
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
MMU
M
M
M
M
M
M
M
M
M
M
M
M
M
M
HOUSE
M
125A 125A125A125A
M M M M
400A
4#500KCMIL+1#2G-3-1/2"C
24"MIN
125A
M
125A
125A
125A
125A
M
M
M
M
125A
M
LRP-1BH PP-1BHEN
L
ATS
60A, 208/120V, 3-PHASE,
4-WIRE (3-POLE)
SPP
11
1
1
1 1
1111
1 1 1 11
1
111
111
11
125A, 208/120V,
1-PHASE, 3-WIRE
(TYP)
UTILITY TRANSFORMER
208/120V, 3-PHASE, 4-WIRE
SECONDARY
UTILITY
SERVICE
4 SETS OF 3#350KCMIL+1#3/0G-3"C
(2)5"C
EMPTY
CONDUIT
60A
J
ANN
GENERATOR
ANNUNCIATOR
MAIN SERVICE
SWITCH
4#4+1#8G-1-1/2"C
PP-1BH#36
4#4+1#8G-1-1/2"C
4#4+1#8G-1-1/2"C
CONTROL WIRING IN 1"C (TYP)
SEE E1.00 FOR
ADDITIONAL
INFORMATION
PP-1BH#37
4#4+1#8G-1-1/2"C
ELECTRICAL:
POWER RISER
DIAGRAM
E4.01
AJS
NOT TO SCALE1ONE LINE DIAGRAM
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
LOWER LEVEL
GROUND FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
ROOF
KEYED NOTES
PROVIDE (2) 3" CONDUITS FOR TV AND TELE/DATA INCOMING
SERVICE.
PLYWOOD BACKBOARD IN MECHANICAL ROOM FOR TV AND
TELE/DATA EQUIPMENT.
PROVIDE (1) 2-1/2"C FROM MECHANICAL ROOM TO ABOVE
CEILING OF COMMON CORRIDOR.
SERVICE LOCATION FOR INDIVIDUAL APARTMENT. REFER TO
FLOOR PLANS FOR EXACT LOCATIONS AND QUANTITIES.
1
2
3
4
2
GENERAL NOTES
A.PROVIDE GROUNDING PER SPECIFICATIONS AND DETAILS
B.COORDINATE ENTIRE INSTALLATION WITH TIME WARNER
C.INSTALL COAX CABLE FURNISHED BY TIME WARNER CABLE TIME WARNER CABLE
SHALL PROVIDE TERMINATIONS AND TESTING INSTALL OUTLET IN COVER PLATE AND
PROVIDE COVER PLATE
MECHANICAL ROOM
GROUND BAR
#6 GROUND TO
GROUNDING
ELECTRODE SYSTEM
RG-6U COAX
FURNISHED BY
TWC, INSTALLED
BY ELECTRICAL
CONTRACTOR
CATV SERVICE
ENTRANCE
EQUIPMENT BY
TIME WARNER
TIME
WARNER
BACKBOARD
CATV SERVICE
ENTRANCE CABLE
PROVIDED BY
SERVICE PROVIDER
TV
REFER TO FLOOR
PLANS FOR QUANTITY
/ LOCATIONS
FACP
RA
FATC
F
EOL
F
F
F
F
S H F CM
TS
CM
FS
FFEOL
FFEOL
FATC
FFEOL
FATC
FFEOL
FATC
FFEOL
F
120V
20A-1P
S H F CM
TS
CM
FS
ELEVATOR PRIMARY RECALL
ELEVATOR SECONDARY RECALL
ELEVATOR SHUNT TRIP
ELEVATOR FIREMAN'S HAT
CMCMCMCMMM
ELEVATOR MONITORING
1
GROUND FLR
FIRST FLR
SECOND FLR
THIRD FLR
FOURTH FLR
LOWER LEVEL
1
2
TV
TV
TV
TV
TV
TV
3
3
3
3
3
3
4
4
4
4
4
4
CM
S H F CM
TS
CM
FS
CM
S H F CM
TS
CM
FS
CM
S H F CM
TS
CM
FS
CM
MMMMCM
GENERATOR RUN
GENERATOR TROUBLE
DOOR HOLD OPEN
NOT TO SCALE
TYPICAL CABLE TV SERVICE DIAGRAMS
NOT TO SCALE
FIRE ALARM RISER DIAGRAM
CATV WIRING DIAGRAM
CONDUIT DISTRIBUTION
ELECTRICAL:
AUXILIARY
SYSTEMS RISER
DIAGRAMS
E4.02
AJS
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4
LIGHTING FIXTURE SCHEDULE
FIXTURE
TYPE DESCRIPTION MANUFACTURER
CAT NO.BALLAST VOLTAGE
LAMPS
REMARKS(#) WATTS, TYPE
F1 10" LED, CEILING MOUNTED
FLUSH FIXTURE
WAC LIGHTING
FM-4610-30-WT DRIVER 120 12.5W, LED
F2 LED WALL MOUNTED
SCONCE
WAC LIGHTING
WS-7318-BN DRIVER UNV 20.5W, LED
F3 10" LED, CEILING MOUNTED
FLUSH FIXTURE
WAC LIGHTING
FM-4610-30-WT DRIVER 120 12.5W, LED WITH MINI INVERTER - PW SERIES
BY EVEN LITE
F4 LED BATH VANITY FIXTURE WAC LIGHTING
WS-7334-BN DRIVER 120V 48W, LED
F5
WALL MOUNTED, LED STAIR
FIXTURE WITH INTEGRAL
OCCUPANCY SENSOR
LUMINAIRE LED
TSL94-100W-3500K-MV-120-277-OP-W
HT-DAMP-EMB722
DRIVER UNV 100W, LED
F6
WALL MOUNTED, LED STAIR
FIXTURE WITH INTEGRAL
OCCUPANCY SENSOR
LUMINAIRE LED
TSL92-50W-3500K-MV-120-277-OP-WH
T-DAMP-EMB722
DRIVER UNV 50W, LED
FX2 LED OUTDOOR WALL
SCONCE
MODERN FORMS
WS-W1408-GH DRIVER 120 11.5W, LED
FX5 LED STRIPLIGHT INTERLUX
98407-XX DRIVER 120V 3.7W/FT, LED
LENGTH AS INDICATED ON
DRAWINGS. PROVIDE ALL REQUIRED
MOUNTING HARDWARE AND
ACCESSORIES FOR A COMPLETE
INSTALLATION
FX6 LED OUTDOOR LINEAR
LIGHT
INTERLUX
E97687-W-20 DRIVER 120V 25W, LED
PROVIDE ALL REQUIRED MOUNTING
HARDWARE AND ACCESSORIES FOR
A COMPLETE INSTALLATION
FE1 REMOTE BATTERY PACK
WITH SELF-DIAGNOSTICS
EVENLITE
TCL2WSD
NICKEL
CADMIUM UNV (2) 2W LED
FE2 EXIT LIGHT WITH INTEGRAL
BATTERY
EVENLITE
SOVEMNR2MBARCXXSD LED UNV 2.5W, LED
FE3 EXIT LIGHT EVENLITE
TLXEMRUWSD LED UNV 2.5W, LED
NOTES:
1.LIGHTING FIXTURE SCHEDULE SHOWN ON ENGINEER'S DRAWINGS ARE FOR INFORMATION PURPOSES ONLY. LIGHTING FIXTURES SHOWN ARE THOSE SELECTED BY
ARCHITECT. ENGINEER SHALL NOT BE RESPONSIBLE FOR INFORMATION SHOWN RELATED TO FIXTURE SELECTION AND OVERALL LIGHTING DESIGN. ARCHITECT SHALL
CONFIRM EXACT STYLES, COLORS, FINISHES AND MODEL NUMBERS OF ALL LIGHT FIXTURES.
2.COORDINATE LOCATION OF REMOTE DRIVERS IN FIELD. LOCATE DRIVERS WITHIN ACCESSIBLE CEILINGS.
NOTES:
1.TYPICAL FOR ALL APARTMENT PANELS. REFER TO E1.00 AND FLOOR PLANS.
ELECTRICAL:
SCHEDULES
E5.01
AJS
1
1
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4 2
1
ABBREVIATION LIST
JH =MAIN ELEVATOR SERVICE DISCONNECT SWITCH VIA SHUNT TRIP CIRCUIT
BREAKER. PROVIDED BY ELECTRICAL CONTRACTOR
JH1=HOISTWAY AUXILIARY DISCONNECT SWITCH PROVIDED BY ELECTRICAL
CONTRACTOR
JHL=ELEVATOR CAB LIGHTS AND POWER DISCONNECT SWITCH. PROVIDED BY
ELECTRICAL CONTRACTOR.
LDU=INSPECTION AND TEST PANEL PROVIDED BY ELEVATOR CONTRACOTOR
TA=3-PHASE AUTOTRANSFORMER (208V, 480V) PROVIDED BY ELEVATOR
CONTRACTOR
TSU=MOTOR CONTROLLER PROVIDED BY ELEVATOR CONTRACTOR
TAS=TEST AND INSPECTION PANEL AUTOTRANSFORMER PROVIDED BY
ELEVATOR CONTRACTOR
VFD=VARIABLE FREQUENCY DRIVE PROVIDED BY ELEVATOR CONTRACTOR
PDB=POWER DISTRIBUTION BLOCK PROVIDED BY ELEVATOR CONTRACTOR
M=MOTOR PROVIDED BY ELEVATOR CONTRACTOR
NOT TO SCALE
TYPICAL MRL ELEVATOR EQUIPMENT
TOP OF
HOISTWAY
SAFETY
COMPONENTS
TAS
JH1 VFD
TSUFUSE
BOX
TA
JH
JHL
LDU
SEE NOTE 2
2"
SEE NOTE 1
SEE NOTE 4
2"
1"
1.
2.
1/2"
SEE NOTE 3
COPPER GROUND BAR. 1/4" x 4" x 1". HOLE CENTERS
MATCH NEMA DOUBLE LUG CONFIGURATION.
INSULATORS.
3.
4.
LOCKWASHERS.
WALL MOUNTING BRACKET.
NOT TO SCALE
GROUND BAR DETAIL (TYP)
2001A TO 3000A
GROUNDING ELECTRODE CONDUCTORS (TO WATER SERVICE,
SUPPLEMENTAL ELECTRODE, BLDG. STEEL AND SERVICE SWITCH)
SHALL BE SIZED AS FOLLOWS:
GROUND BUS SHALL BE 1/4"x 4"x 2'-6"(MIN.), DRILLED FOR
TWO-HOLE HYDRAULIC COMPRESSION LUGS. TERMINATION OF
GROUNDING ELECTRODE CONDUCTORS SHALL BE WITH TWO-HOLE
COMPRESSION LUGS OR EXOTHERMIC WELD. PROVIDE TWO
COPPER ALLOY MECHANICAL LUGS FOR FIRE ALARM GROUNDS,
EQUAL TO FCI BURNDY TYPE "KA4C", SECURED TO BUS WITH 1/4"
-20 SILICON BRONZE BOLTS.
MAIN SERVICE
SWITCH
BUS LINK
FOR BONDING
FIRE PROTECTION. SEE FIRE
PROTECTION SERVICE
GROUNDING DETAIL. SEE NOTE
No. 1
SEE GROUNDING ELECTRODE
SIZING TABLE FOR CONDUIT AND
CONDUCTOR SIZE. (TYPICAL FOR EACH
SERVICE SWITCH).
GH-100B
GH-50B
GH-75B
GH-125-B
CONDUIT GROUNDING FITTINGS SHALL BE O-Z/GEDNEY TYPE GH-B
AS FOLLOWS:
GROUND RODS SHALL BE SPACED A MINIMUM OF 10'-0" APART,
AND SHALL BE BURIED A MINIMUM OF 2'-6" BELOW FINISH GRADE.
ALL CONDUCTOR TO GROUND ROD AND CONDUCTOR TO
CONDUCTOR CONNECTIONS SHALL BE EXOTHERMIC WELD TYPE.
MANY BUILDINGS HAVE MORE THAN ONE DOMESTIC WATER OR
FIRE PROTECTION SERVICE. A GROUND CONDUCTOR, IN CONDUIT,
SHALL BE INSTALLED FROM THE MAIN BLDG GROUND BUS TO EACH
DOMESTIC WATER AND FIRE PROTECTION SERVICE. SEE DOMESTIC
WATER OR FIRE PROTECTION SERVICE GROUNDING DETAILS.
FITTING
3.
2.
NOTES:
1.
UP TO 800AGND AWG/KCMILCONDUIT
4/0 TO 500KCMIL1-1/4"
1"
3/4"
1/2"8 TO 2
4 TO 2/0
1 TO 250KCMIL
GENERATORS
ABOVE 3000A
801A TO 2000A
CONDUIT GROUNDING
FITTING. SEE NOTE No. 3
MDP GROUND BUS
5.
4.
SERVICE
SIZE
3/4" x 10' COPPER-CLAD STEEL
OR STAINLESS STEEL
GROUNDING ROD (TYP. OF 3.)
SEE NOTE No. 2
DOMESTIC WATER
SERVICE. SEE
WATER SERVICE
GROUNDING DETAIL.
SEE NOTE NO. 1
1#2-3/4"C
EXOTHERMIC
WELD
MAIN TELECOMMUNICATION
GROUND BUS AT
TELEPHONE SERVICE
ENTRANCE
BUILDING
COLUMN
G
N
3/0
PER NFPA 70, TABLE 250.66
500KCMIL
350KCMIL
250KCMIL
GROUND ELECTRODE
CONDUCTOR
SUPPLEMENTAL
GROUNDING
ELECTRODE
NOT TO SCALE
ELECTRIC SERVICE GROUNDING SCHEMATIC
NOTE: PROVIDE AUX CONTACTS W/ 2#14 TO ELEVATOR EQUIPMENT
FOR ALL ELEVATOR DISCONNECT SWITCHES.
ELECTRICAL:
DETAILS
E6.01
AJS
VERSIONS
NO.DATE DESCRIPTION
ARCHITECT:
864 Mapleton Road
Princeton, NJ 08540
609.919.0099
fax 609.919.0088
a r c h i t e c t s
ikon.5
www.ikon5architects.com
CIVIL ENGINEER:
FIRE PROTECTION, PLUMBING,
MECHANICAL, ELECTRICAL ENGINEER:
STRUCTURAL ENGINEER:
LANDSCAPE ARCHITECT:
PROJECT TITLE:
PROFESSIONAL LICENSE NUMBER
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
Jun 14, 2018 - 2:04pm
01.17.2018
238 LINDEN
AVENUE
ITHACA, NY
1 01.17.2018 CONSTRUCTION
DOCUMENTS
2 02.21.2018 ADDENDUM 1
3 02.22.2018 ADDENDUM 2
4 03.02.2018 ADDENDUM 4