HomeMy WebLinkAboutFull MechUPEXIST.BEDROOMEXIST. CLOSEDPORCHEXIST.BEDROOMEXIST.STUDYEXIST.FOYEREXIST.BATHEXIST. LIVINGRM. (PANELED)EXIST.KITCHENEXIST.BEDROOMEXIST.BEDROOMEXIST.BEDROOMUPUPDNEXIST.BATHEXIST.STAIRBUILDING ADDITION TO BE DEMOLISHEDBY GENERAL CONTRACTOR22222222224UPUPEXIST.BEDROOMEXIST.LIVING RM.EXIST.FURNACE /UTILITY RM.EXIST.KITCHENEXIST.BEDROOMEXIST.LIVING RM.EXIST.BATHEXIST.BATHEXIST.BEDROOMEXIST.BEDROOMEXIST.BEDROOMEXIST.STAIR33CAP AT MAIN111111111532221BUILDING ADDITION TO BE DEMOLISHEDBY GENERAL CONTRACTOR666DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
08'16'32'KEY PLANBUILDING 4.4 FLOOR PLAN - LEVEL A AND BSEV/KMO1/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL A - REMOVALS11/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL B - REMOVALS212KEYED NOTES - HVAC: (NOT ALL NOTES USED ON EACH PLAN)REMOVE FINTUBE, PIPING, VALVES, CONTROLS AND ACCESSORIES.REMOVE RADIATOR, PIPING, VALVES, CONTROLS AND ACCESSORIES.REMOVE BOILER, PIPING, VALVES, VENTS, CONTROLS ANDACCESSORIES.3GENERAL NOTES - ELECTRICAL:A.COORDINATE ALL REMOVAL WORK WITH OTHER TRADES PRIOR TOCOMMENCEMENT OF ANY WORK.B.REMOVE LIGHT FIXTURES, RECEPTACLES, FIRE ALARM DEVICES,COMMUNICATION OUTLETS, PANELBOARDS AND LOAD CENTERS,MECHANICAL EQUIPMENT CONNECTIONS, AND MISCELLANEOUSDEVICES, AND ASSOCIATED CONDUIT AND WIRING BACK TOSOURCE.C.COORDINATE ALL REMOVAL WORK WITH THE OWNERSREPRESENTATIVE PRIOR TO COMMENCEMENT OF WORK.JANUARY 9, 201201.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 131KEYED NOTES - ELECTRICAL:REMOVE 200A SERVICE PANEL, METER, AND SERVICE CONDUCTORS.COORDINATE REMOVAL WORK WITH UTILITY.1KEYED NOTES - PLUMBING:REMOVE ALL GAS PIPING, SUPPORTS, VALVES, AND ACCESSORIES.REMOVE FIXTURES. REMOVE ALL ASSOCIATED PIPING ANDACCESSORIES.REMOVE WATER METER, PIPING, AND ACCESSORIES.REMOVE GAS PIPE TO RANGE, SUPPORTS, VALVES, ANDACCESSORIES.REMOVE ALL PLUMBING PIPING, SUPPORTS, VALVES, ANDACCESSORIES.REMOVE GAS PIPING, SUPPORTS, VALVES, AND ACCESSORIES BACKTO MAIN. CAP AT MAIN.GENERAL NOTES - PLUMBINGA.COORDINATE ALL REMOVAL WORK WITH OTHER TRADES PRIOR TOCOMMENCEMENT OF ANY WORK.B.REMOVE ALL PLUMBING PIPING LOCATED IN WALLS AND CEILINGS.COORDINATE ALL REMOVAL WORK WITH THE OWNERSREPRESENTATIVE PRIOR TO COMMENCEMENT OF WORK.12345208.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS6
EXIST.BEDROOMEXIST.LIVING RM.EXIST.KITCHENEXIST. BATHEXIST.BEDROOMEXIST.BEDROOMDNDNUPEXIST.BEDROOMEXIST.LIVING RM.22222111BUILDING ADDITION TO BE DEMOLISHEDBY GENERAL CONTRACTOREXIST.KITCHENFIREPLACEUPFIREPLACEEXIST.BEDROOMEXIST.BEDROOMEXIST.BATHEXIST.BEDROOMEXIST.BATHEXIST.LIVING RM.EXIST.KITCHENEXIST.BEDROOMDNUPDN2222211111BUILDING ADDITION TO BE DEMOLISHEDBY GENERAL CONTRACTORDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
08'16'32'KEY PLANBUILDING 4.4 FLOOR PLAN - LEVEL C AND D REMOVALSSEV/KMO1/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL D - REMOVALS21/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL C - REMOVALS212HVAC KEYED NOTES: (NOT ALL NOTES USED ON EACH PLAN)REMOVE FINTUBE, PIPING, VALVES, CONTROLS AND ACCESSORIES.REMOVE RADIATOR, PIPING, VALVES, CONTROLS AND ACCESSORIES.REMOVE BOILER, PIPING, VALVES, VENTS, CONTROLS ANDACCESSORIES.3JANUARY 9, 201201.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 131GENERAL NOTES - ELECTRICAL:A.COORDINATE ALL REMOVAL WORK WITH OTHER TRADES PRIOR TOCOMMENCEMENT OF ANY WORK.B.REMOVE LIGHT FIXTURES, RECEPTACLES, FIRE ALARM DEVICES,COMMUNICATION OUTLETS, PANELBOARDS AND LOAD CENTERS,MECHANICAL EQUIPMENT CONNECTIONS, AND MISCELLANEOUSDEVICES, AND ASSOCIATED CONDUIT AND WIRING BACK TOSOURCE.C.COORDINATE ALL REMOVAL WORK WITH THE OWNERSREPRESENTATIVE PRIOR TO COMMENCEMENT OF WORK.KEYED NOTES - PLUMBING:REMOVE FIXTURES. REMOVE ALL ASSOCIATED PIPING ANDACCESSORIES.GENERAL NOTES - PLUMBINGA.COORDINATE ALL REMOVAL WORK WITH OTHER TRADES PRIOR TOCOMMENCEMENT OF ANY WORK.B.REMOVE ALL PLUMBING PIPING LOCATED IN WALLS AND CEILINGS.COORDINATE ALL REMOVAL WORK WITH THE OWNERSREPRESENTATIVE PRIOR TO COMMENCEMENT OF WORK.1208.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
MECHANICAL SYMBOL LIST ANDSTANDARD NOTESTJM/KMOM0.01MECHANICAL SYMBOL LISTMECHANICAL SYMBOL LISTHWSHOT WATER SUPPLYHWRHOT WATER RETURNDIRECTION OF FLOWCAP OR PLUGELBOW DOWNELBOW UP/TOP CONNECTIONUNION (OR FLANGE)VALVE (SHUT-OFF)CONTROL VALVEFLOW BALANCERAFFDENOTES DIMENSION ABOVE FINISHED FLOORADACCESS DOORFDFIRE DAMPERAADAUTOMATIC AIR DAMPERFCFLEX CONNECTIONVOLUME DAMPERDUCT SECTION-SUPPLYDUCT SECTION - RETURN - EXHAUSTA" = DIMENSION SHOWNB" = OTHERA"B"AIR FLOWPROGRAMMABLE THERMOSTAT AND CUH CONTROLLERTSUPPLY AIRTAKE OFFS24x1412x1224x1412x12
1-1/2 TIMES BRANCH SIZEVD24x14
12x12VDEXHAUST ORRETURN AIRFITTING24x1212x121-1/2 TIMES BRANCH SIZEDUCT UP THRUROOF24x12TURN DOWNTURN UP24x24DUCT TURNINGUP OR DOWN90° ELBOWWITH TURNINGVANESCFMTYPENECK SIZEGRILLE, REGISTER, DIFFUSERCUBIC FEET/MINUTECFMNOT TO SCALENTSSTATIC PRESSURE SENSORSPSWITH GUARDGTTEMPERATURE SENSORST211.14.2011PB 020305.18.2012CONSOLIDATED SET405.25.2012PERMIT SET508.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN
AC44B3/4" HWS &HWR DNUC7"Ø TO KITCHENHOOD. HOOD BYOTHERS.10'-0" FT-A4'-0" FT-A4'-0" FT-ACUH44B1" HWS & HWRUP & DN4"Ø10x616x816x8TT10'-0" FT-A5'-0" FT-A2'-6" FT-ATTT34" HWS & HWRUP & DN7'-0" FT-A21EXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'C'34"16x10T314x10 TO KITCHENHOOD. HOOD BYOTHERS.314x10EXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'C'34" HWS &HWR UP34" HWS &HWR DN1" HWS &HWR UPEXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'C'T10x6140110x63FD38x610018x6(TYP 2)8x610x610x68x61001(TYP 2)12x30480A8" AFF34" HWS& HWRLOUVEREDACCESS PANEL10x61401UPWH-901.2FP BACKFLOWDW BACKFLOW1" HWS & HWRUP & 3/4 DN3'-0" FT-A7'-0" FT-A7'-0" FT-A7'-0" FT-A4'-0" FT-B4"Ø RIGIDWH-901.13TTAC44A34" HWS & HWRT34" HWS &HWR DN34" HWS &HWR DN8x6110110x634" HWS & HWR UP16x810x63'-0" FT-ACUH44A6"Ø TO KITCHENHOOD. HOOD BYOTHERS.TUCUCUCUCFCA1ACCU18x815014"H CONC. PAD114" HWS &HWR UP10x6150110x6150130x12600C34" HWS &HWR UP12x30480A10x6150116x88x610x61401TT42ACCU2151" HWS & HWR UP4"H CONC. PAD3T16x10ASB441ETMANUAL STARTERSP443P44416x8 AAD18x12 LOUVER18x12 FILTER WITH FRAMEF44VENT KIT16" ABOVE GRADEBOD8'-2"6x6501(TYP. OF 2)8" AFFP441P442TTHIGH CAPACITY AUTO. VENT16x8300GLYCOL12x12 LOUVER7"Ø TO KITCHENHOOD. HOOD BYOTHERS.EXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'B'10x62' FT-BAADT8" AFFLOUVEREDACCESS PANEL(TYP 2)8x610x68x61001(TYP 2)FD110x614013FD2UH13/4"6716x8VENT KIT16" ABOVE GRADE3/4"DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
08'16'32'KEY PLANBUILDING 4.4 FLOOR PLAN - LEVEL A AND BSEV/KMOM2.44A1/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL A11/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL B2512KEYED NOTES: (NOT ALL NOTES USED ON EACH PLAN)16x12 PLENUM. PROVIDE CLOSED CELL FOAM INTERIOR LINER FOR PLENUM.COORDINATE EXACT LOCATION OF HWS & HWR WITH PTAC ACCESSDOOR, COIL CONNECTIONS, CONDENSATE RISER AND ELECTRICAL.DO NOT BLOCK RETURN AIRFLOW OPENING WITH RISERS.CONNECT REFRIGERATION PIPING TO FAN COIL. PIPING SIZED PERMANUFACTURER'S RECOMMENDATIONS. PROVIDE STAINLESS STEELCHANNEL OVER EXPOSED REFRIGERANT TUBING. ANCHOR ATBUILDING AND CURB.FAN COIL CONDENSING UNIT. INSTALL ON CONCRETE PAD. TUBINGSIZE TO BE DETERMINED BY HEAT PUMP MANUFACTURER.VENTILATION FAN FOR MECHANICAL ROOM.CONCEAL CONTROL BALANCE AND SHUTOFF VALVES ABOVEFINISHED CEILING ACCESSIBLE FROM FAN COIL ACCESS OPENING.LOCATE CONTROL BALANCE AND SHUTOFF VALVES IN MECHANICALROOM.34GENERAL NOTES:A. DIFFUSERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROMEDGE OF DIFFUSER TO SPRINKLERS. COORDINATE FINALLOCATIONS OF DIFFUSER WITH SPRINKLER CONTRACTOR PRIOR TOINSTALLATION.B. HWS AND HWR PIPING TO RUN IN JOIST SPACE UNLESS SOFFITIS SHOWN ON ARCHITECTURAL DRAWINGS.C. PROVIDE CONTROL, ISOLATION, DRAIN,VENT AND BALANCE VALVES BEHIND FIN TUBE COVER.D.AC FAN MOTOR SPEED SHALL BE FIELD WIRED TO HIGH SPEED INHEATING MODE.JANUARY 9, 2012101.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13208.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS67
F-14"Ø6"Ø TO KITCHENHOOD. HOOD BYOTHERS.4"Ø34" HWS &HWR DN4'-0" FT-A4'-0" FT-A38x8950C16x6250120x8400110x6150110x6150110'-0" FT-A34" HWS &HWR DN3'-6" FT-B11'-0" FT-A34" HWS & HWR DNTFCD138x838x106"Ø4'-0" FT-B34" HWS &HWR DNTUCTUCT10x610014"Ø8'-0" FT-A8'-0" FT-A3TTDRYER BOOSTERVENT FAN10x614x8x10 BACKBOXWITH BAFFLEBETWEEN KITCHENAND LAUNDRY.DN4"Ø4"ØAC44C34" HWS & HWR314x10 TO KITCHENHOOD. HOOD BYOTHERS.7"Ø TO KITCHENHOOD. HOOD BYOTHERS.314x1034" HWS &HWR DN4'-0" FT-A4'-0" FT-A1" HWS &HWR DNEXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'D'34"34" HWS &HWR UP8'-0" FT-A5'-0" FT-A7-0" FT-A7'-0" FT-A34"12x8200110x610x612x8200116x1016x1010x88x68x68x81501(TYP. 2)4"Ø2134" HWS &HWR DNTTTTT34" HWS &HWR UP4'-0" FT-A6x65017"Ø34" HWS &HWR DNEXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'D'34"EXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'D'34" HWS UP34"EXTEND PIPING ABOVEFINISHED CEILING TOFINTUBE ON LEVEL 'D'DP34"UCTUC34" HWS &HWR UP34"4'-6" FT-A33EXTEND REFRIGERANTPIPING ABOVEFINISHED CEILING TOFCD1 ON LEVEL 'D'34" HWS UP34" HWR UPDRYER BOOSTERVENT FAN34" HWS &HWR UP34"10x12340B18x618x66x12 DN(8" AFFTYP 2)18x10680A18x1018x8DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
08'16'32'KEY PLANBUILDING 4.4 FLOOR PLAN - LEVEL C AND D SEV/KMOM2.44B1/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL C11/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL D212KEYED NOTES: (NOT ALL NOTES USED ON EACH PLAN)16x12 PLENUM. PROVIDE CLOSED CELL FOAM INTERIOR LINER FOR PLENUM.COORDINATE EXACT LOCATION OF HWS & HWR WITH UNIT ACCESSDOOR, COIL CONNECTIONS, CONDENSATE RISER AND ELECTRICAL.DO NOT BLOCK RETURN AIRFLOW OPENING WITH RISERS.CONNECT REFRIGERATION PIPING TO FAN COIL. PIPING SIZED PERMANUFACTURER'S RECOMMENDATIONS.GENERAL NOTES:A. DIFFUSERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROMEDGE OF DIFFUSER TO SPRINKLERS. COORDINATE FINALLOCATIONS OF DIFFUSER WITH SPRINKLER CONTRACTOR PRIOR TOINSTALLATION.B. HWS AND HWR PIPING TO RUN IN JOIST SPACE UNLESS SOFFITIS SHOWN ON ARCHITECTURAL DRAWINGS.C. PROVIDE CONTROL, ISOLATION, DRAIN,VENT AND BALANCE VALVES BEHIND FIN TUBE COVER.D.AC FAN MOTOR SPEED SHALL BE FIELD WIRED TO HIGH SPEED INHEATING MODE.JANUARY 9, 2012101.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 133208.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
MECHANICAL DETAILSSEVM5.01SCALE: NONE1.PIPING FOR CEILING MOUNTED UNITS IS SIMILAR.BRASS PLUG (TYP.)COILSHUT-OFF VALVE(TYP.)DOWNFEEDUNION(TYP.)COILFLOW BALANCER(TYP.)FINISHED FLOORSLEEVESRETURNSUPPLYUPFEEDMANUAL AIR VENTPIPING IN FURRED-IN SPACE,WALL CHASE, OR EXPOSED ASSHOWN ON DRAWINGS.RETURNSUPPLYGENERAL NOTE:GENERAL NOTES:1.PLACE SHUT-OFF VALVE AHEAD OF CONTROL VALVE IN UNITS WITH CONTROL VALVES.SCALE: NONEUNIONHEATERVUNIONSHUT-OFF VALVE (TYP.)SUPPLYMANUAL AIR VENTFLOW BALANCERCONTROL VALVERETURNSCALE: NONEFLOWBALANCERSHUT-OFFVALVE(TYP.)SUPPLYMANUAL AIR VENTUNION (TYP.)CEILINGUNIT HEATERCABINETRETURN1/2" THREADEDROD SUPPORTSVIBRATION ISOLATORSCONTROLVALVESCALE: NONEFILTERSUPPLYRETURNSLEEVE (TYP.)HEATING COILFLOORSHUT-OFF VALVE(TYP.)HYDRONICSUB-BASEFLOW BALANCERMANUAL AIR VENTUNION (TYP.)ROOM CABINETSCALE: NONEFINISHED FLOORRETURN AIR GRILLE(BY HVAC)FINISHED CEILINGTERMINATE RETURN AIR DUCTABOVE CEILING W/ OPEN ENDCOLUMN CENTER LINEOPPOSED BLADE KEYOPERATED DAMPERSECTIONRUBBER GASKETALL AROUNDSCALE: NONEAIR SUPPLY REGISTERREAR BARSFACE BARS45°AIR SUPPLY DUCT6" LONG EXTENSIONDUCT COLLARGYPSUM BOARDWALL CAVITYRETURN AIR DUCTP&TP&TCOMBUSTIONAIR INLETRELIEF VALVE (TYP.)BALANCING VALVE(TYP.)SHUT OFF VALVE(TYP.)112" NPTDRAIN CONN.CONDENSATEDRAIN TRAPVENTMANDATORY GASPRESSURE REGULATORPRESSURE &TEMPERATUREGAUGEUNION (TYP.)DIRT TRAPMANUAL SHUT OFF VALVEHEAT SYSTEMRETURN TOADDITIONAL UNITSGAS SUPPLYMAINTAIN AREGULATED 7" W.C.PRESSURE ATMAXIMUM BTU/HRINPUTHEATINGSYSTEMSUPPLYGENERAL NOTES:1. FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THEBOILER, SEE MANUFACTURER'S DRAWING.2. SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TOPERMIT THE FLUIDS TO DRAIN FREELY, BY GRAVITY, TO A CONVENIENT FLOORDRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT 18" ABOVEFLOOR.3. LOCATE WATER INLET AND OUTLET FITTINGS (I.E. UNIONS, ELBOWS, ETC.) A MINIMUMOF 6" FROM BOILER FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OFBOILER PANELS AND COVERS. ALL PIPING AND ELECTRIC CONNECTIONS (SERVICESWITCHES, CONDUIT BOXES) SHOULD LIKEWISE BE 6" AWAY FROM SIDE PANELS.SCALE: NONE4"H CONC. PADINLINE PUMP(TYP.)STRAINER(TYP.)GENERAL NOTES:1.FOR DUCTS THROUGH MECHANICAL ROOM FLOORS, INSTALL EXTENDED SLEEVEFOR MOUNTING ANGLE FRAME ON FLOOR CURB.SCALE: NONEACCESS DOOR:MINIMUM SIZE 16"x12"IF DUCT IS LESS THAN 14" WIDE,PROVIDE 24" LONG REMOVABLEDUCT SECTION FLANGED ANDGASKETED, SECURED WITHWING NUT IN LIEU OF DOOR.LOCATE ON LINK SIDE OF DAMPER14 GAUGE SLEEVETHROUGH FLOOR,6" LONGER THANFLOOR THICKNESSFLOORFIRE DAMPERDO NOT BOLTTO FLOORSPRING NEGATORCONTINUOUS 112"x112"x12GAUGE(UP TO 48" DUCT)2x2x12 GAUGE(49" TO 72" DUCT)FASTEN TO SLEEVE ONLYSLIP JOINT (TYPICAL)RECTANGULAR DUCT12345678211.14.2011PB 020305.18.2012CONSOLIDATED SET405.25.2012PERMIT SET508.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN
45 DEGREEDUCT ENTRYFITTING,TYPICALMECHANICAL DETAILSSEVM5.02RUNNER MIN.24 GAUGESCALE: NONEMIN.3"MIN.3"'W'EQUAL45°45°EQUAL'W'VANE RUNNERASSEMBLYEVANES MIN.24 GAUGE45°BACDDMIN. 24 GAUGEVANE RUNNERBOLT VANE ASSEMBLYTO ELBOW CHEEKVANES WELDEDTO RUNNER2" R1" R638"214" REDCBADIM.'W'20" &OVER'W'19" &UNDER414" R214"314"218"118"278"SCALE: NONE1.NEW CONSTRUCTION: G.C. TO PROVIDE ROOF OPENING, FRAMING ANGLE ANDFLASHING. LOCATION SETTING AND SECURING OF CURB BY MECHANICALCONTRACTOR.2.SHIM CURB LEVEL.GENERAL NOTES:SCRIBE END OFDAMPER SHAFT TOINDICATE DAMPERPOSITIONROOF DECKSCREW EQUIPMENTTO CURB 8" C.C.TREATED WOOD BLOCKWATERTIGHT PLENUMINSULATE OUTSIDEOF PLENUM34" COUPLING WITHNIPPLE AND CAPANGLE FRAMINGSECURELY BOLT CURBTO ANGLE FRAMINGFAN POWER WIRINGWHEN REQUIREDPLENUM2"ROOFFLASHINGDOUBLE-WALLCURB15'-0"INSULATED DUCTCROSSBREAKBOTTOM TOCREATE PITCHDAMPER MOTORDAMPERASSEMBLYNEOPRENEGASKET12" MIN.INSIDE DIMENSIONSTO SUIT EQUIPMENTREQUIREMENTSCHANNEL SPANNING BETWEEN BEAMS AND /OR JOISTS IN DECKING "CAVITY". CONCENTRIC BEAM CLAMP WITH THREADED, WELDED EYEROD. FOR USE WITH JOISTS AND BEAMS. VIBRATION ISOLATION DEVICE ASSEMBLY.NO SCALESET ON AND SECURE TO BEAMS AND JOISTS.CADMIUM PLATED STEEL PLATE WASHER WITH DOUBLE NUT.CADMIUM PLATED STEEL ALL-THREAD RODS.KEYED NOTES:GENERAL NOTE:BEAMJOISTFLOOR/ROOF DECKING ASSEMBLY276346511234567A.PROVIDE LINKED EYELETS WITH STUD, AT CONNECTION TO SLOPING STRUCTURE WITHPITCH OF 1 IN 12 OR GREATER. BENDING OF HANGER RODS NOT ALLOWED.STRAINER WITH VALVEDBLOWDOWN CONNECTION(TYP.)SHUT-OFF VALVE(TYP.)SCALE: NONEGENERAL NOTE:1.PROVIDE CHECK VALVE, SHUTOFF VALVE, AND FLOW BALANCER IN PLACE OFTRIPLE DUTY VALVE WHERE PIPE SIZE IS LESS THAN 2".STANDBYPUMPTD14" MANIFOLDWITH GAUGECOCKSUNION(TYP.)TDPRESSURE GAUGE(TYP.)INLINE PUMPTRIPLE DUTY VALVE(TYP.)INLINE PUMPSCALE: NONEGENERAL NOTE:1.PROVIDE CHECK VALVE, SHUTOFF VALVE, AND FLOW BALANCER IN PLACE OFTRIPLE DUTY VALVE WHERE PIPE SIZE IS LESS THAN 2".STRAINER WITHVALVED BLOWDOWNCONNECTIONSHUT-OFF VALVE(TYP.)TDUNION(TYP.)TRIPLE DUTY VALVEPRESSURE GAUGE14" MANIFOLDWITH GAUGECOCKSSYMBOL INDICATED ON DRAWINGSCALE: NONEPIPE: SIZE AS NOTED ON PLANSEXTEND 14" COPPER TUBINGAND LOCATE VENT INACCESSIBLE LOCATIONWHEN REQUIRED6" LONG AIR COLLECTION CHAMBER:114" PIPE ON GREATER THAN 4" LINES34" PIPE ON 4" AND SMALLER LINESMANUAL AIR VENTLOCATION FOREXPOSED PIPING14" COPPER TUBINGEXPANSION TANK(BLADDER TYPE)GLYCOL WATERSTORAGE TANKAIR SEPARATORASSEMBLYUNION(TYP.)TO PUMP4" HIGH CONCRETE PADSHUT-OFF VALVE(TYP.)MAIN AUTOMATIC VALVERETURNSCALE: NONESCALE: NONEW/ INTEGRAL PUMPBOTTOM FLANGE MOUNTED "C" CLAMP WITH SET SCREW & LOCKNUT.(FOR USE ON BEAMS ONLY, NOT ALLOWED ON JOISTS)TOP FLANGE MOUNTED "C" CLAMP WITH SET SCREW & LOCKNUT.(FOR USE ON BEAMS ONLY, NOT ALLOWED ON JOISTS)12468753MAKE-UP WATER 211.14.2011PB 020305.18.2012CONSOLIDATED SET405.25.2012PERMIT SET508.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN
VERTICALAC UNIT16x1216x1816x6300 CFM200 CFM200 CFM8'-11"8'10'V951231491015121346781178951234616x1216x18300 CFM200 CFM341625AIR COOLEDCONDENSERTWO REFRIGERANT CIRCUITS,PROVIDE FLEXIBLE CONNECTORS8" SDR SEALED WATER TIGHT5" CONCRETE SLAB,#4 STEELREINFORCEDPACK WITH NON-SHRINK GROUTTO BUILDING48"MINIMUMCLEARANCE42"MINIMUMCLEARANCEBOILERPUMPBOILER PUMP56745123EXTFSASGLYCOL212318917651011413159PARKING GARAGECEILINGPRE-CASTPLANK1" HWS & HWR7" MINIMUMSTEEL BEAMPENETRATIONPIPE HANGER(TYP.)358"x414" BARE ELEMENTFIN-TUBE, 34" TUBE, 40 FPF.(TYP.)CONCRETE BEAMPENETRATIONMECHANICAL DETAILSSEVM5.03RELIEF VALVE(TYPICAL)BOILER(TYPICAL)CLEANOUTFLOOR DRAINSLOPESLOPE1-1/4"2FLUE(TYP.)DRAIN VALVE(TYPICAL)CONDENSATE TRAP ANDACID NEUTRALIZER(TYPICAL)1KEYED NOTES:TYPICAL PTAC UNIT.SCALE: 1/2" = 1'-0"PTAC PLENUM AND DUCTWORK ELEVATION (TYPICAL TWO BEDROOM APARTMENT)12FLEXIBLE DUCT CONNECTOR.316x12 DUCT EXTENSION.4TRANSITION TO 16x18. 16x20 FOR 3 BEDROOM APARTMENTS.516x18 PLENUM. LINE INTERIOR WITH CLOSED CELL FOAMINSULATION.6ROOM CEILING.7112" BLANKET INSULATION.8TYPICAL SUPPLY AIR REGISTER W/ OBP.9SAFE OFF 16x6 DUCT FOR 12x6 DIFFUSER.1KEYED NOTES:TYPICAL PTAC UNIT.SCALE: 1/2" = 1'-0"PTAC AND DUCTWORK ELEVATION (TYPICAL)22FLEXIBLE DUCT CONNECTOR.316x12 DUCT EXTENSION.4TRANSITION TO 16x18. 16x20 FOR 3 BEDROOM APARTMENTS.516x18 PLENUM. LINE INTERIOR WITH CLOSED CELLFOAM INSULATION. SEE DETAIL 4 / M2-33D-1.616x6 DUCT BRANCH.7HOT WATER/GLYCOL SUPPLY PIPING.834" RUNOUT TO HOT WATER COIL.9ACCESS PANEL TO PTAC CLOSET.1KEYED NOTES:SCALE: 1" = 1'-0"PTAC TOP PLENUM DETAIL3212 GA. SHEET METAL ANGLE CLIPS. ANCHOR BRANCHDUCTS TO PLENUM.316x6 INSULATED BRANCH DUCT.16x18 PLENUM. LINE INTERIOR WITH 1" CLOSED CELL FOAM.4FLOOR STRUCTURE.5112" HAT CHANNEL612x6 DIFFUSER DUCT.10HOT WATER/GLYCOL SUPPLY.11PROVIDE UL CLASSIFIED FIRE STOP SYSTEM FOR PIPINGFLOOR PENETRATIONS.12EXTEND 34" SUPPLY TO HOT WATER COIL.13EXTEND 34" RETURN TO HOT WATER COIL.14TYPICAL VENT AT HIGH POINT OF COIL BRANCH CIRCUIT.GENERAL NOTES:VENT TOP OF EACH RISER PAIR WITH 3#4" BALL VALVE,5#8" HOSE ADAPTOR, CAP & CHAIN.ASCALE: NONE(TYPICAL FOR ALL BOILERS)BOILER DRAIN PIPING DETAIL81KEYED NOTES: OVERSIZE DRAIN PIPE FROM RELIEF VALVE FOR LOOSE FIT. OFFSET DRAIN PIPE AS NECESSARY TO AVOID HWR PIPING AND CONDENSATE TRAP.21/4"=1'0"BOILER AND BOILER PUMP ELEVATION (TYPICAL)41/4"=1'0"HEATING SYSTEM PUMP MODULE (TYPICAL)512KEYED NOTES:HIGH EFFICIENCY BOILER, TYPICAL.4" HOUSE KEEPING PAD.34BOILER PRIMARY LOOP FROM COMMON PIPE.56BOILER INLET AND OUTLET PIPE & VALVES.7 PVC COMBUSTION AIR INLET DUCT.PVC VENT OUTLET DUCT.GENERAL NOTES:SEE M7-01 FOR PIPING SCHEMATIC DIAGRAM.ALL ISOLATION VALVES IN BOILER LOOP ANDDHW HEATER LOOP SHALL BE FULL PORT.ABGENERAL NOTES:SEE M7-01 FOR PIPING SCHEMATIC DIAGRAM.PAINT PUMP SUPPORT STEEL ONE COAT CHEROKEE REDOVER PRIMER.ABEXTEND PIPING FROM ACID NEUTRALIZING TRAP TO FLOOR DRAIN. COORDINATE FLOOR DRAIN LOCATION WITH BOILERDRAIN AND PLUMBING INSTALLER.KEYED NOTES:DUPLEX HEATING SYSTEM PUMPS.EXTEND MAV FULL SIZE TO GLYCOL STORAGE TANK.TRIPLE DUTY VALVE, TYPICAL.3" X 3" X 1/4" WELDED TUBE STEEL PIPE SUPPORTANCHORED TO CONCRETE WALL.AIR SEPARATOR.EXPANSION TANK.MAKE-UP WATER.DRAIN, 3/4" BALL VALVE 5/8"HOSEADAPTOR, CAP & CHAIN, TYPICAL.EXTEND 2" TO DHW PLATE TO PLATE INLET.1234567891/8"=1'0"BARE ELEMENT FIN-TUBE PIPING SCHEMATIC DETAIL FOR PARKING GARAGE CEILING PLENUM (TYPICAL)698 TRIPLE DUTY VALVE. INSTALL PER MANUFACTURESUNRESTRICTED PIPE LENGTH UPSTREAM & DOWN.SCALE: NO SCALEAHU HOT WATER / GLYCOL HEATING COIL PIPING DETAIL7SCALE: NO SCALEAHU-1 DX PARTIAL PIPING DETAIL1015CONTROL VALVE. EXTEND CONTROL CONDUCTORS FROMTHERMOSTAT TO UNIT TERMINAL STRIP AND CONTROL VALVE.211.14.2011PB 020305.18.2012CONSOLIDATED SET405.25.2012PERMIT SET508.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN
4"ØFLOORSTRUCTUREDRYER FANMANUALSTARTERLINT TRAP BY FANMANUFACTURERFLOORMOUNT FAN AMINIMUM 84"INCHES FROMDRYER OUTLETDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923KEY PLANMECHANICAL DETAILSSEVM5.04SCALE: NONEFAN COIL UNIT DETAIL1SCALE: NONEHW FIN RADIATION PIPING DETAIL3FAN COIL UNITFLEX CONNECTORFILTER ACCESSSUPPLY AIRTO SPACEDUCT LOCATIONS OFF OF FAN COIL PLENUM VARIES.HOSE KIT SHALL FORM TRAP WITH 24" LONG CONDENSATE DRAIN HOSE. CONNECT TOCONDENSATE DRAIN PIPING CONNECTION LEFT BY DIV 22. CLAMP ON BOTH ENDS.HANG UNIT FROM STRUCTURE. PROVIDE RODS, SUPPORTS, AND VIBRATION ISOLATORS.PROVIDE ACCESSIBILITY FROM BELOW UNIT. MECHANICAL/ELECTRICAL WORK SHALL NOTBE LOCATED BELOW UNIT. ARRANGEMENT SHALL PERMIT REMOVAL OF FAN COIL FORMAJOR SERVICING.PROVIDE PROPER SPACE CLEARANCE AT CONTROL PANEL FOR SERVICING.GENERAL NOTES:1.RLRS12RETURN AIR PLENUMFULL SIZE OF RETURNAIR OPENING ON FANCOIL UNIT.PROVIDE FILTER RACK.ROUTE RS & RL TO OUTDOOR CONDENSER.INSULATE RETURN AIR PLENUM.KEYED NOTES:12FLEX CONNECTORRETURN AIRFROM SPACE2.3.4.5.SUPPLYBRASS PLUGSHUT-OFF VALVE(TYP.)CONTROL VALVEUNION(TYP.)FINISHED FLOORALTERNATERETURN AND SLEEVERETURNSLEEVE(TYP.)MANUAL AIR VENTFLOW BALANCERDOOR ACCESS(TYP.)JANUARY 9, 2012101.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13208.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSā GENERAL NOTES:1.USE 80% FREE AREA FIRE DAMPER FOR TRANSFER AIR REGISTERS.2.USE "THINLINE" FIRE DAMPER IN WALLS 4 INCHES DEPTH AND LESS.1.FOR DOUBLE WALL HIGH VELOCITY DUCT USE INSULATION END CAP BETWEENDOUBLE WALL AND SINGLE COLLAR. INSULATE COLLAR.GENERAL NOTES:SCALE: NONEREGISTER ON BOTH SIDESFIRE DAMPER INSTALLATION DETAIL -72 HOUR SINGLE WALL - LOW VELOCITY -FIRE DAMPER INSTALLATION DETAIL - SCALE: NONE100% OUT OF AIRSTREAM5SCALE: 1/4" - 1'DRYER BOOSTER FAN DETAIL22
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923KEY PLANMECHANICAL SCHEDULESSEVM6.07JANUARY 9, 2012101.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13BOILER SCHEDULE - GAS FIREDUNIT NO.LOCATIONSERVICEMOTORTYPEFUELRELEIFSYSTEMMIN.MAX.MIN. GASGASFLUEDESIGNREMARKSVOLTSPHASEVALVEMEDIAOUTPUTOUTPUTPRESSUREFIRINGCONN.PRODUCTPRESSURE(MBH)(MBH)BEFORERATESIZE &(PSIG)REG.FULLNUMBER(IN. WC)(CFH)B441BLDG 4.4HEATING1151CONDGAS30HW572604"2854"LOCHINVAR KBN286Note 1Note 1:Provide the following :Condensate Neutralization Kit201.12.2012SEQUENCE 1 - ASI17308.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS