HomeMy WebLinkAboutFull ElectDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSELECTRICAL SYMBOL LIST ANDSTANDARD NOTESKSOE0.01ELECTRICAL SYMBOL LISTEXISTING EQUIPMENT/WORK.NEW EQUIPMENT/WORK.3REFERENCE TO DRAWING NOTEEWCELECTRIC WATER COOLERACABOVE COUNTERAFFABOVE FINISHED FLOORGFI GFCIGROUND FAULT CIRCUIT INTERRUPTER TYPE RECEPTACLEWGWIRE GUARDWPWATERPROOF (OR) WEATHERPROOFCCONDUITBRANCH CIRCUIT TO PANELBOARD, WHEN SHOWN,LETTERING INDICATES PANELBOARD DESIGNATIONS.QUANTITY OF ARROWHEADS INDICATE QUANTITY OFBRANCH CIRCUITS. PROTECT EACH BRANCH CIRCUIT WITHA 20 AMPERE, 1-POLE OVERCURRENT DEVICE UNLESSOTHER SIZE INDICATED. TYPICAL DESIGNATION,(2#12,1#12G-1/2"C,20A-1P.)3LLPB5ON BRANCH CIRCUITRY WHERE ONLY THE CIRCUIT NUMBERIS SHOWN, CIRCUIT RECEPTACLES WITH THE SAMENUMBER TO THE CIRCUIT INDICATED WITH A HOMERUN TOEACH NUMBERED GROUP. CONNECT TO A 20A-1P CIRCUITBREAKER, OR AS NOTED FOR SPECIAL PURPOSERECEPTACLES.32B8114 ON BRANCH CIRCUITRY WHERE ONLY THE CIRCUIT NUMBERIS SHOWN, CIRCUIT LUMINAIRES WITH THE SAME NUMBERTO THE CIRCUIT INDICATED WITH A HOMERUN TO EACHNUMBERED GROUP. CONNECT TO A 20A-1P CIRCUITBREAKER, OR AS NOTED.11422DIAGRAM CIRCUIT DESIGNATION. REFER TO SCHEDULE ONDIAGRAM.2BRANCH CIRCUIT PANELBOARD. REFER TO PANEL BOARDSCHEDULE.JJUNCTION BOX3LIGHTING CONTROL SWITCH. LIGHTING WALL SWITCHES,1 POLE IF NO NOTATION. 3=3 WAY, 4=4 WAY, K=KEY TYPELOWER CASE LETTER INDICATES CONTROL DESIGNATION.OSOCCUPANCY SENSOR, CEILING MOUNTED.OSOCCUPANCY SENSOR, WALL MOUNTED.DUPLEX RECEPTACLEQUAD RECEPTACLESPECIAL PURPOSE RECEPTACLE.3INDICATION OF GANGED DEVICESLIGHTING FIXTURELIGHTING FIXTURE, WALLxxEMLIGHTING FIXTURE WITH DESIGNATION ENDING "EM "CONTAINS INTEGRAL FLUORESCENT EMERGENCY POWERUNITLIGHTING FIXTURE, FLUORESCENT STRIPEMERGENCY LIGHTING FIXTURE, INTEGRAL BATTERYEXIT LIGHT FIXTUREEXIT LIGHT FIXTURE, WALL MOUNTEDMF1EQUIPMENT CONNECTION, WITH DESIGNATION FROMELECTRIC EQUIPMENT AND CONTROL SCHEDULEF1LOCATION OF ONE OR MORE EQUIPMENT CONTROLDEVICES AS SCHEDULED ON ELECTRIC EQUIPMENT ANDCONTROL SCHEDULE. DESIGNATION REFERS TOEQUIPMENT CONTROLLEDDISCONNECT SWITCH, VOLTAGE AND AMPERE RATING TOMATCH EQUIPMENT SERVED. REFER TO ELECTRICEQUIPMENT AND CONTROL SCHEDULE FOR FUSINGREQUIREMENTS.DDOOR BUZZERFFIRE ALARM SYSTEM, MANUAL PULL STATIONFIRE ALARM SYSTEM, NOTIFICATION APPLIANCE, HORNSTROBE. V=VISUAL ONLY. NUMBER = CANDELLA RATINGV, 75FFIRE ALARM SYSTEM, THERMODETECTOR, COMBINATIONFIXED TEMPERATURE/RATE-OF-RISE, FIXED TEMPERATURERATING 135°F, UNLESS INDICATED OTHERWISE.HFIRE ALARM SYSTEM SMOKE DETECTOR. "DT" INDICATESDUCT MOUNTED TYPE WITH REMOTE TEST STATION.DTSELECTRICAL SYMBOL LISTFFFIRE ALARM SYSTEM, MAGNETIC DOOR HOLDER,INDIVIDUAL,WALL MOUNTED. SUBSCRIPT "F" INDICATESFLOOR MOUNTED.SHFIRE ALARM SYSTEM, CONNECTION TO SMOKE HATCHFSFIRE ALARM SYSTEM, CONNECTION TO SPRINKLER FLOWSWITCH. NUMBER INDICATES QUANTITYTS1-FIRE ALARM SYSTEM, CONNECTION TO SPRINKLER SYSTEMTAMPER SWITCH. NUMBER INDICATES QUANTITYPIVFIRE ALARM SYSTEM, CONNECTION TO SPRINKLER/STANDPIPE SYSTEM PIV VALVE TAMPER SWITCHWALL MOUNTED TELEPHONE OUTLET. LETTERINDICATES TYPE. REFER TO SCHEDULES.WORKSTATION OUTLET LAYOUT. LETTER INDICATES TYPE,NUMBER INDICATES BRANCH CIRCUIT NUMBER. REFER TODETAIL.a1TELEVISION OUTLET. LETTER INDICATES TYPEaTVFUSED DISCONNECT SWITCH, RATINGS AS INDICATEDSTANDARD THERMAL MAGNETIC MOLDED CASE CIRCUITBREAKER, RATINGS AS INDICATEDCTCURRENT TRANSFORMER, RATING AS INDICATEDLIGHTNING ARRESTOR, RATINGS AS INDICATEDGENERAL NOTES - ALL DRAWINGS:A.BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS,LIVING ROOMS, BEDROOMS, CLOSETS, AND HALLWAYS SHALL BE PROTECTED BY ALISTED ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION TYPE CIRCUIT BREAKERSDESIGNED TO PROTECT THE BRANCH CIRCUIT PER NEC ARTICLE 210.12.B.RECEPTACLES SHALL BE GFCI TYPE WHERE INSTALLED IN BATHROOMS, KITCHENS,OUTDOORS, ROOFTOPS, AND WHERE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OFTHE OUTSIDE EDGE OF A SINK.C.UNLESS NOTED OTHERWISE, PROVIDE 15 AND 20 AMP SINGLE PHASE 120 VOLT CIRCUITCONDUCTORS AS FOLLOWS: #12 AWG FOR CIRCUITS UP TO 100 FEET LONG, #10 AWGFOR CIRCUITS 101 TO 150 FEET LONG, #8 AWG FOR CIRCUITS 151 TO 250 FEET LONG.D.PROVIDE BRANCH CIRCUITS AS FOLLOWS:* BRANCH CIRCUITS IN DWELLING UNITS OF BUILDINGS 1.1, 2.1, 2.2, 2.3, 2.4, 4.1, 4.2, AND 4.3 SHALL BE NM CABLE.* BRANCH CIRCUITS FOR INTERIOR HOUSE LOADS ON RESIDENTIAL LEVELS (NOT PARKING GARAGE LEVELS) SHALL BE NM CABLE.* BRANCH CIRCUITS ON PARKING GARAGE LEVELS SHALL BE MC CABLE.* NM CABLE IS NOT PERMITTED IN TYPE II CONSTRUCTION.E.CIRCUIT EXIT SIGNS TOGETHER FROM 20A-1P CIRCUIT BREAKER IN PANELBOARD THATSERVES AREA LIGHTING. PROVIDE CIRCUIT BREAKER HANDLE LOCK.F.DUPLEX RECEPTACLES SHOWN IN DWELLING UNITS REPRESENT CODE REQUIREDQUANTITIES AND GENERAL SPACING PER NEC ARTICLE 210. DO NOT SCALE PLANS.VERIFY RECEPTACLE SPACING AND ADJUST LOCATIONS AS NECESSARY TO MEET NECARTICLE 210. WHERE STUD SPACING DOES NOT PERMIT NEC SPACING REQUIREMENTS,PROVIDE BRACKETS, STUDS, OR ADDITIONAL RECEPTACLES AS NECESSARY TOACHIEVE NEC ARTICLE 210 REQUIREMENTS.G.PROVIDE TAMPERPROOF RECEPTACLES FOR ALL 15 AND 20 AMP RECEPTACLES INDWELLING UNITS PER NEC ARTICLE 406.11. LOCATIONS INCLUDE ALL RECEPTACLESSPECIFIED IN NEC ARTICLE 210.52 (KITCHENS, DINING ROOMS, LIVING ROOMS,BEDROOMS, BATHROOMS, LAUNDRY AREA, CLOSETS, AND HALLWAYS).H.CIRCUIT EMERGENCY LIGHTING BALLASTS TO LOCAL AREA LIGHTING BRANCH CIRCUIT,AHEAD OF CONTROL DEVICES.I.PROVIDE NEMA 14-30R RECEPTACLE FOR EACH ELECTRIC CLOTHES DRYER ORCOMBINATION WASHER/DRYER. PROVIDE 2#10, #10N, #10G CONDUCTORS.J.PROVIDE NEMA 14-50R RECEPTACLE FOR EACH ELECTRIC RANGE. PROVIDE 2#8, #8N,#8G CONDUCTORS.K.PROVIDE 15A RECEPTACLES AND #14 AWG CONDUCTORS FOR CIRCUITS SERVED FROM15A CIRCUIT BREAKERS IN DWELLING UNITS.L.PROVIDE CONTROL FOR SITE LIGHTING AND BUILDING MOUNTED EXTERIOR LIGHTFIXTURES THROUGH MULTI-P0LE LIGHTING CONTACTORS, ASTRONOMICAL TIMESWITCH, AND ROOF MOUNTED PHOTOCELL FOR PHOTOCELL "ON" AND TIMER "OFF"CONTROL. COORDINATE TIME SWITCH SCHEDULE WITH OWNERS REPRESENTATIVE.M.PROVIDE FIRE ALARM SYSTEM WIRING COILED IN A JUNCTION BOX BEHIND A BLANKCOVER PLATE FOR DWELLING UNIT NOTIFICATION APPLIANCES NOTED AS FUTUREDEVICE.FIRE ALARM SYSTEM COMBINATION SMOKE DETECTOR ANDCO DETECTOR WITH SOUNDER BASESaDATA OUTLET. LETTER INDICATES TYPE. REFER TOSCHEDULES.SBGFCI, AC, DUPLEX RECEPTACLEFIRE ALARM SYSTEM SMOKE DETECTOR WITH SOUNDERBASESFIRE ALARM SYSTEM, FIRE ALARM CONTROL PANEL(S)FIRE ALARM SYSTEM, REMOTE ANNUNCIATORFIRE ALARM SYSTEM, ADDRESSABLE SMOKE DETECTORCOMMUNICATION ROOM/CLOSET GROUND BARTWCTIME WARNER CABLEFIRE ALARM SYSTEM, NOTIFICATION APPLIANCE, V=VISUALONLY, NUMBER = CANDELLA RATING, F = FUTURE DEVICE.V,15,FFA, 15,FFFIRE ALARM SYSTEM, NOTIFICATION APPLIANCE, HORNA=AUDIBLE ONLY, NUMBER = CANDELLA RATING FORFUTURE DEVICE.LAPFIRE ALARM SYSTEM, CONNECTION TO SPRINKLER LOW AIRPRESSURE SWITCHPSFIRE ALARM SYSTEM, CONNECTION TO SPRINKLERPRESSURE SWITCHFIRE ALARM SYSTEM, CONNECTION TO SPRINKLER ELECTRICWATER FLOW BELLFCO1-SBROOF MOUNTED PHOTOCELL CIRCUITED TO EXTERIORLIGHTING CONTACTOR AND TIME SWITCH.FIRE ALARM SYSTEM CONNECTION TO GARAGE LEVELTEMPERATURE SENSORFIRE ALARM SYSTEM CONNECTION TO ADDRESSABLECARBON MONOXIDE DETECTORAB311.21.2011CONSTRUCTION CHANGE DIRECTIVE 5408.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
HAHAHBHBHBHBHBHBEXISTINGEXISTINGH422,1;3H4221;3H422,1;3H422,5;7H422,5;7H1A2,1;31TYPICAL1TYPICALHBHBHBH22,27;29H2227;29H22,27;29H22,27;29H22,27;29BUILDING 2.4BUILDING 2.3BUILDING 2.2BUILDING 2.1BUILDING 1BUILDING 4.1BUILDING 4.2BUILDING 4.3HAHAHAHAH901M,34;36H901M,34;36H901M,34;36H901M,34;36HAH1A2,1;32DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSELECTRICAL SITE PLANKSOE2.01GENERAL NOTES:A.UNLESS NOTED OTHERWISE, BRANCH CIRCUIT DUCTBANKCONSTRUCTION SHALL BE DIRECT BURIED IN SAND BED.B.PROVIDE CONCRETE DUCTBANK UNDER ROADS, DRIVE LANES, PAVEDSURFACES AND CONCRETE WALKS.C.EXISTING SITE UTILITIES ARE NOT SHOWN ON THIS PLAN. REFER TOCIVIL PLANS FOR ALL SITE UTILITIES. OTHER UTILITIES MAY BEPRESENT OR PLACED IN DIFFERENT LOCATIONS. VERIFY EXACTLOCATIONS OF EXISTING UTILITIES BY TEST HOLES OR SITEINVESTIGATION BEFORE EXCAVATING. NOTIFY THE UNDERGROUNDFACILITIES PROTECTION ORGANIZATION (UFPO) TO LOCATE UTILITIESBEFORE WORK COMMENCES. COORDINATE WITH CIVIL DRAWINGS.D.HAND EXCAVATE WHERE CROSSING EXISTING UTILITIES.E.PROVIDE GALVANIZED RIGID STEEL CONDUIT STUB-UPS FROM ALL PVCCONDUIT.F.PROVIDE HAND HOLES FOR SITE BRANCH CIRCUITS AT BUILDINGENTRANCES AND AS REQUIRED TO FACILITATE CIRCUITRYINSTALLATION. PITCH CONDUIT AWAY FROM BUILDINGS, TOWARDHAND HOLES.G.LOCATIONS OF HAND HOLES ARE NOT SHOWN, FIELD VERIFY WITHCONSTRUCTION MANAGER BEFORE WORK COMMENCES. COORDINATEWITH SITE LANDSCAPE WORK AND OTHER UTILITY WORK.H.PROVIDE #10 AWG CONDUCTORS FOR ALL SITE LIGHTING UNLESSNOTED OTHERWISE.GENERAL NOTES:PROVIDE FIRE ALARM CONNECTION TO PIV VALVE TAMPER SWITCH.PROVIDE CABLE IN 1 INCH RIGID STEEL CONDUIT, DIRECT BURIED INSAND BED, 24 INCHES BELOW GRADE WITH MARKER TAPE.COORDINATE SITE LIGHTING BRANCH CIRCUIT ROUTING IN FRONT OFBUILDING 1 WITH THE LANDSCAPING CONTRACTOR PRIOR TOTRENCHING.1311.21.2011CONSTRUCTION CHANGE DIRECTIVE 5401.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13504.27.2012CCD #342608.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
120113115531'533'531'1T1T3T2CPB-2HH-1HH-2FRONTFRONTFRONTTRANSFORMERPAD, TYPICALCPB-3COMMINICATIONPULLBOX,TYPICALCOMMUNICATIONHAND HOLE,TYPICALCPB-1CPB-2HH-4CPB-3CPB-5HH-6HH-7CPB-4T5T6FRONTFR
O
NTAPPROXIMATE LOCATION OF ITCLOSET ON LEVEL ABOVEGARAGE, FIELD VERIFY EXACTLOACTIONHHL-1HHL-2ELECTRICAL UTILITY PLANKSOE2.021GENERAL NOTES:A.UNLESS NOTED OTHERWISE, COMMUNICATION DUCTBANKCONSTRUCTION SHALL BE DIRECT BURIED IN SAND BED.B.ELECTRIC SERVICE DUCTBANKS FROM TRANSFORMERSECONDARIES TO SERVICE ENTRANCE EQUIPMENT SHALL BEREINFORCED CONCRETE ENCASED.C.FOR COMMUNICATION DUCTBANKS, PROVIDE REINFORCEDCONCRETE DUCTBANK UNDER ROADS, DRIVE LANES, PAVEDSURFACES AND CONCRETE WALKS.D.EXISTING SITE UTILITIES ARE NOT SHOWN ON THIS PLAN. REFERTO CIVIL PLANS FOR ALL SITE UTILITIES. OTHER UTILITIES MAY BEPRESENT OR PLACED IN DIFFERENT LOCATIONS. VERIFY EXACTLOCATIONS OF EXISTING UTILITIES BY TEST HOLES OR SITEINVESTIGATION BEFORE EXCAVATING. NOTIFY THEUNDERGROUND FACILITIES PROTECTION ORGANIZATION (UFPO)TO LOCATE UTILITIES BEFORE WORK COMMENCES. COORDINATEWITH CIVIL DRAWINGS.E.HAND EXCAVATE WHERE CROSSING EXISTING UTILITIES.F.PROVIDE GALVANIZED RIGID STEEL CONDUIT STUB-UPS FROM ALLPVC CONDUIT.G.CONDUIT AND DUCTBANK ROUTING IS DIAGRAMMATIC. ACTUALROUTING SHALL BE DETERMINED IN THE FIELD. PITCHDUCTBANKS AND CONDUIT AWAY FROM BUILDINGS, TOWARD PULLBOXES AND HAND HOLES.H.LOCATIONS OF PULLBOXES AND HAND HOLES ARE APPROXIMATE,FIELD VERIFY WITH CONSTRUCTION MANAGER BEFORE WORKCOMMENCES. COORDINATE WITH SITE LANDSCAPE WORK ANDOTHER UTILITY WORK.KEYED NOTES:EXTEND 4" CONDUIT DIRECT BURIED IN SAND BED FROM SPAREVERIZON CONDUIT TO COMMUNICATION MANHOLE. COORDINATELOCATION OF SPARE CONDUIT WITH VERIZON.COORDINATE LOCATION OF PAD MOUNTED TRANSFORMERS WITHCONSTRUCTION MANAGER. TRANSFORMERS ALSO SERVEBUILDING 3.TIME WARNERS SERVICE DUCTBANK IS PROVIDED BY TIMEWARNER AND IS CO-LOCATED IN THE NYSEG PRIMARY DUCTBANK.THE ELECTRICAL CONTRACTOR SHALL EXTEND THE TIMEWARNER DUCTS FROM APPROXIMATELY 5 FEET AHEAD OF THETRANSFORMER PRIMARY TO THE INTERIOR OF THE BUILDING,TERMINATING ADJACENT TO THE METER CENTER. MAINTAIN 48INCH CLEARANCE ABOUT THE TRANSFORMER PAD AND 12 INCHESFROM ELECTRICAL SERVICE DUCTS. TIME WARNER USES 4" PVCBUT ALSO USES 2" PVC. PROVIDE DUCT SIZE AND TYPE TO MATCHTIME WARNER DUCTS. COORDINATE ENTIRE INSTALLATION WITHTIME WARNER PRIOR TO COMMENCEMENT OF WORK. PROVIDEPULL ROPE IN ALL CONDUITS. REFER TO CIVIL PLANS FORPROPOSED NYSEG PRIMARY ROUTING.APPROXIMATE LOCATION OF EXISTING UTILITY POLE WITH TIMEWARNER SERVICES. THE ELECTRICAL CONTRACTOR SHALLPROVIDE A DUCTBANK FOR TIME WARNER SERVICE CABLE TO THEINTERIOR OF THE BUILDING, TERMINATING ADJACENT TO THEMETER CENTER. MAINTAIN 12 INCHES FROM ELECTRICALSERVICE DUCTS. PROVIDE 4 INCH SCHEDULE 80 PVC.COORDINATE ENTIRE INSTALLATION WITH TIME WARNER PRIORTO COMMENCEMENT OF WORK. PROVIDE PULL ROPE IN ALLCONDUITS.NOT USED.PROVIDE A 34"H X 34"W X 7"D (MINIMUM SIZE) WEATHERPROOFPULLBOX WITH CORROSION RESISTANT HARDWARE BELOW THEBRIDGE BETWEEN THE HORIZONTAL AND VERTICAL CONDUIT RUN.SEE DETAIL 6 WALL ELEVATION ON THIS PLAN.PROVIDE 1" CONDUIT WITH PULL ROPE FROM HHL-1 TO BUILDING 1COMMUNICATION ROOM TO SERVE FUTURE BLUE LIGHT PHONECOMM LINE. PROVIDE 1" CONDUIT WITH PULL ROPE FROM HHL-2TO PANEL H1A1 TO SERVE FUTURE BLUE LIGHT PHONE POWER.PROVIDE 1"C (MINIMUM) WITH CAT6 4-PR UTP OUTDOOR RATEDCABLE FROM BUILDING 1, LEVEL A DATA ROOM TO THE ELECTRICCAR CHARGING STATION. PROVIDE ALL TERMINATIONS FOR ACOMPLETE SYSTEM. COORDINATE TERMINATION LOCATION INLEVEL A DATA ROOM WITH OWNER REPRESENTATIVE.PROVIDE 2#6,#8G FROM 40A-2P CIRCUIT BREAKER IN PANEL H1A1TO ELECTRIC CAR CHARGING STATION. TYPICAL FOR TWOCIRCUITS TERMINATING TO A SINGLE CHARGING STATION.COMBINE BRANCH CIRCUITS IN A SINGLE 1-1/4"C. COORDINATEENTIRE INSTALLATION WITH CHARGING STATION SUPPLIER.E2.011SPNO SCALEDUCTBANK SECTIONPE2.012SPNO SCALEDUCTBANK SECTIONE2.013PPP = 4" ACTIVE POWER CONDUITS = 4" SPARE CONDUITNO SCALEDUCTBANK SECTIONPPP = 4" ACTIVE POWER CONDUITS = 4" SPARE CONDUITP = 4" ACTIVE POWER CONDUITS = 4" SPARE CONDUITE2.014NO SCALEDUCTBANK SECTIONE2.015NO SCALEDUCTBANK SECTIONSCCSCC = 4" ACTIVE COMMUNICATION CONDUITS = 4" SPARE CONDUITC = 4" ACTIVE COMMUNICATION CONDUITS = 4" SPARE CONDUITNOTE:A.REFER TO DUCTBANK NOTES ON THIS PLAN AND DETAILS FORDUCTBANK CONSTRUCTION REQUIREMENTS.NOTE:A.REFER TO DUCTBANK NOTES ON THIS PLAN AND DETAILS FORDUCTBANK CONSTRUCTION REQUIREMENTS.NOTE:A.REFER TO DUCTBANK NOTES ON THIS PLAN AND DETAILS FORDUCTBANK CONSTRUCTION REQUIREMENTS.NOTE:A.REFER TO DUCTBANK NOTES ON THIS PLAN AND DETAILS FORDUCTBANK CONSTRUCTION REQUIREMENTS.NOTE:A.REFER TO DUCTBANK NOTES ON THIS PLAN AND DETAILS FORDUCTBANK CONSTRUCTION REQUIREMENTS.SCALE: 1" = 40'ELECTRICAL SITE PLANDRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
08'16'32'KEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSAugust 10, 2011SS2311.02.2011SEQUENCE 1 - CCD#234412.02.2011SEQUENCE 1 - CCD#856PP501.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13602.24.2012CONSTRUCTION CHANGE DIRECTIVE 197704.03.2012CONSTRUCTION CHANGE DIRECTIVE 2989806.11.2012PR03906.18.2012CCD #441008.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
PUBLIC RM.202PORCHPUBLIC RM.201BATH206BATH205BEDROOM204LIVING RM.203HALL207STAIR "B"2-BED UNITLOAD CENTERT44BWASHER/DRYER27733BBBB991111DISPOSALDISHWASHERAA1RANGE7RANGE117911X1bbaabbAAAA1LOAD CENTERT901B11AAD287181876788687DISPOSALcee3daaa44444444444UPBEDROOM108BATH109BEDROOM110DINING107106105LIVING RM.102KITCHEN1012-BED UNITSTAIR "B"CLOS.104FURNACE RM.BATH103BEDROOMLOAD CENTERT44ADISPOSALDISHWASHERAABB91WASHER/DRYER92RANGE313BB7711117FACP21,23LOAD CENTERT901APANELH901RMETERCENTERMC9011711aaWASHER/DRYER1RANGEDISPOSALDISHWASHER181818abcbAAAAAAAAVSD-1VSD-224854910111243549CONCRETE PADBELOW METERCENTERababPANELH901MELECTRODE GROUNDGRID. FIELDCOORDINATE LOCATION.83TIME CLOCK444444444444DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
08'16'32'KEY PLANBUILDING 4.4 FLOOR PLAN - LEVEL A AND BKSOE2.44A1/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL A11/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL B21GENERAL NOTES:A.PROVIDE TAMPERPROOF RECEPTACLES FORALL 15 AND 20 AMP RECEPTACLES INDWELLING UNITS PER NEC ARTICLE 406.11.LOCATIONS INCLUDE ALL RECEPTACLESSPECIFIED IN NEC ARTICLE 210.52 (KITCHENS,DINING ROOMS, LIVING ROOMS, BEDROOMS,BATHROOMS, LAUNDRY AREA, CLOSETS, ANDHALLWAYS).B.CIRCUIT EXTERIOR LIGHTING FIXTURESTHROUGH TIME SWITCH LOCATED IN FURNACEROOM 105. PROVIDE SEPARATE TIMESCHEDULE FOR POLE MOUNTED FIXTURESAND BUILDING MOUNTED FIXTURES. PROVIDETIME SWITCH AND COORDINATE SCHEDULEWITH OWNER.C.CIRCUIT EXIT SIGNS TOGETHER WITH LOCALAREA LIGHTING, AHEAD OF CONTROL DEVICESD.INSTALL GARBAGE DISPOSAL CORD SETFURNISHED BY MECHANICAL CONTRACTOR.KEYED NOTES:RECEPTACLE SERVES COMBINATIONMICROWAVE AND EXHAUST HOOD.COORDINATE RECEPTACLE LOCATION WITHCONSTRUCTION MANAGER.PROVIDE AUDIBLE ONLY FIRE ALARM SYSTEMNOTIFICATION APPLIANCE. DEVICE LOCATIONSHALL ACCOMMODATE FUTUREAUDIBLE/VISUAL DEVICE.UNLESS OTHERWISE NOTED, CIRCUITDESIGNATIONS REFER TO LOAD CENTER T44A.UNLESS OTHERWISE NOTED, CIRCUITDESIGNATIONS REFER TO LOAD CENTERT901A.UNLESS OTHERWISE NOTED, CIRCUITDESIGNATIONS REFER TO PANELBOARDH901M.UNLESS OTHERWISE NOTED, CIRCUITDESIGNATIONS REFER TO LOAD CENTER T44B.UNLESS OTHERWISE NOTED, CIRCUITDESIGNATIONS REFER TO LOAD CENTERT901B.UNLESS OTHERWISE NOTED, CIRCUITDESIGNATIONS REFER TO LOAD CENTERH901R.PROVIDE POWER CONNECTION TOMECHANICAL TEMPERATURE CONTROL PANELUSING 2#12+G MC CABLE FROM 20A-1P CIRCUITBREAKER IN PANEL H901M.TIME WARNER CABLE BACKBOARD. TIMEWARNER CABLE EQUIPMENT CABINET(S)PROVIDED BY TIME WARNER.VERIZON BACKBOARD.DATA RACK MDF-9013-WAY SWITCH TO CONTROL STAIRWAYLIGHTS. SEE LEVEL C FOR OTHER 3-WAYSWITCH LOCATION.KEYED SWITCH SHALL CONTROL LIGHTS ONALL LEVELS OF STAIRWAY.23456789101112JANUARY 9, 201201.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 1313141203.30.2012CCD #28304.13.2012CCD #30408.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS4
BEDROOM401BEDROOM402KITCHEN405BATH406BEDROOM404ROOF DECKLIVING /DINING403STAIR "A"AA120207991WASHER/DRYERDISPOSALRANGE1111AAAA7AADISHWASHER2LOADCENTERT901D6673520333333333BEDROOM301BEDROOM302303ROOF DECKKITCHEN304BATH305EXIST.STAIRSTAIR "A"HALL306BEDROOMSTAIR "B"LOAD CENTERT44CAAAAWASHER/DRYER21AA99DISPOSALDISHWASHER1RANGE737RANGE1DISPOSALDISHWASHERWASHER/DRYER2277153202018189AAAAAA97777793545477X2333333333333DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923NORTHPROJECT
08'16'32'KEY PLANBUILDING 4.4 FLOOR PLAN - LEVEL C AND D KSOE2.44B1/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL C11/4"=1'0"BUILDING 4.4 FLOOR PLAN - LEVEL D21GENERAL NOTES:A.PROVIDE TAMPERPROOF RECEPTACLES FORALL 15 AND 20 AMP RECEPTACLES INDWELLING UNITS PER NEC ARTICLE 406.11.LOCATIONS INCLUDE ALL RECEPTACLESSPECIFIED IN NEC ARTICLE 210.52 (KITCHENS,DINING ROOMS, LIVING ROOMS, BEDROOMS,BATHROOMS, LAUNDRY AREA, CLOSETS, ANDHALLWAYS).B.CIRCUIT EXIT SIGNS TOGETHER WITH LOCALAREA LIGHTING, AHEAD OF CONTROL DEVICES.C.INSTALL GARBAGE DISPOSAL CORD SETFURNISHED BY MECHANICAL CONTRACTOR.KEYED NOTES:RECEPTACLE SERVES COMBINATIONMICROWAVE AND EXHAUST HOOD.COORDINATE RECEPTACLE LOCATION WITHCONSTRUCTION MANAGER.PROVIDE AUDIBLE ONLY FIRE ALARM SYSTEMNOTIFICATION APPLIANCE. DEVICE LOCATIONSHALL ACCOMMODATE FUTUREAUDIBLE/VISUAL DEVICE.CIRCUIT NUMBERS IN THIS STAIRWAY REFERTO LOAD CENTER T901D.UNLESS NOTED OTHERWISE, CIRCUITDESIGNATIONS REFER TO LOAD CENTER T44C.UNLESS NOTED OTHERWISE, CIRCUITDESIGNATIONS REFER TO PANEL H901R.UNLESS NOTED OTHERWISE, CIRCUITDESIGNATIONS REFER TO LOAD CENTER T901DPROVIDE REVERSE PHASE ELV-TYPE DIMMERFOR CONTROL OF LED FIXTURES.23456JANUARY 9, 201201.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 131704.13.2012CCD#302308.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS3
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSNO SACLEELEVATOR SHUTDOWN DETAIL1ELECTRICAL DETAILSKSOE5.01GENERAL NOTES:A. SHUNT TRIP WITH COIL CLEARING CONTACT RATED 24V DC.B. PROVIDE SEPARATE 20A FUSED CIRCUIT FROM FIRE ALARM PANEL FOR EACHSHUNT TRIP.C. BREAKER SIZE PER DRAWINGS - PROVIDE ACCORDING TO QUANTITY AND SIZE ORELEVATOR CIRCUITS.HOUSE PANELTO ELEVATOR HOISTWAY EQUIPMENT.REFER TO ELEVATOR DETAIL.TYPICAL FOR HEATDETECTORS LOCATED INTHE ELEVATOR PIT ANDHOISTWAY, EACHELEVATOR. WIRECONTACTS IN PARALLEL.TO MAIN FIRE ALARMPANEL (INITIATING)TO MAIN FIRE ALARMPANEL (24VDC)2#12, 1/2"COUTLET/SUPPORT BRACKET- ERICO/CADDY FASTENERSTANDARD 1 GANG, RAISEDOUTLET BOX COVERS - FORDUPLEX RECEPTACLE.GENERAL NOTES:A.FOR BACK-TO-BACK OUTLET LOCATIONS IN ADJOINING ROOMS, STAGGER BOXES LOCATION TOADJACENT CAVITIES IN WALL TO MINIMIZE SOUND TRANSMISSION.B.FROM EACH VOICE, DATA, AND TV OUTLET LOCATION, PROVIDE 3/4" MIN. SIZE EMT RACEWAY,LARGER IF REQUIRED FOR CABLE/CONNECTOR, CONCEALED IN WALL CONSTRUCTION, TO NEARESTACCESSIBLE CEILING SPACE.C.PROVIDE ALL PROVISIONS AS REQUIRED FOR A COMPLETE SYSTEM.STANDARD 1 GANG, RAISED OUTLET BOXCOVERS - FOR VOICE/DATA/TV OUTLETS.BEHIND BRACKET.STANDARD 4''SQ. x1-1\2"D. ELECTRICALBOX. TYPICAL FORVOICE, DATA, TV ANDDUPLEX RECEPTACLES.METAL STUDS-TYPICALLY 16'' o.c.LCNOMINAL 8 FOOTCEILING PLANEFA SYSTEMA/V DEVICEILLUMINATEDEXIT SIGNTOP OFPANELBOARDBACKBOXFA SYSTEMPULLSTATIONDOOR OPENINGWALL MOUNTEDINTERCOMLIGHTINGCONTROLWITHIN 6"FINISHEDFLOORELEVATIONSTANDARD
COUNTER
POWER,DATA, TVOR VOICE72"EQUALEQUALCOUNTERTOP80" TO BOTTOM
48"STRIKESIDE45" FOR
POWER,DATA ORVOICE60"DISCONNECTSWITCH ORSTARTER1FO911AT TOP OFHOISTWAYH3548TO PANELSIMPLEX RECEPTACLEFOR SUMP PUMPGFCI1KEYED NOTES:COMPACT FLUORESCENT FIXTURE WITH LAMP SHIELD. DO NOT WIRE ON LOADSIDEOF RECEPTACLE.CIRCUITRY PROVIDED BY ELEVATOR CONTRACTORHEAVY-DUTY, FUSED DISCONNECT SWITCH, COORDINATE VOLTAGE, PHASE, AND FUSESIZE WITH ELEVATOR SUPPLIER. WIRE COMPLETE TO ELEVATOR CONTROLLER.DISCONNECT SWITCH SHALL BE SHUNT TRIP TYPE. UPON ACTIVATION OF HEATDETECTOR IN HOISTWAY, SHUNT TRIP DISCONNECT SHALL OPERATE/OPEN IN ORDERTO SHUT DOWN ELEVATOR BEFORE SPRINKLERS ACTIVATE. 24V SHUNT TRIP COIL.HEAVY-DUTY, FUSED DISCONNECT SWITCH, 240 VOLT, 30 AMP (WITH 20 AMP FUSE,VERIFY WITH ELEVATOR SUPPLIER), SINGLE PHASE WITH SOLID NEUTRAL FORELEVATOR CAR LIGHTS AND VENTILATION FAN. WIRE COMPLETE TO ELEVATORCONTROLLER.HEAVY DUTY, FUSED DISCONNECT SWITCH, 240 VOLTS, 30 AMPS (WITH 20 AMP FUSE,VERIFY WITH ELEVATOR SUPPLIER), SINGLE PHASE WITH SOLID NEUTRAL FOR CARHEATING AND AIR CONDITIONING. WIRE COMPLETE TO ELEVATOR CONTROLLER.PROVIDE A 3/4" CONDUIT WITH CAT5E CABLE FROM THE MAIN TELEPHONE TERMINALBOARD TO ELEVATOR CONTROLLER.ELEVATOR FEEDER. REFER TO ELECTRIC EQUIPMENT AND CONTROL SCHEDULE.SMOKE DETECTOR LOCATED IN ELEVATOR LOBBY, ON EACH FLOOR. CONNECT TOFIRE ALARM SYSTEM AND ELEVATOR RECALL SYSTEM.SMOKE DETECTOR LOCATED AT TOP OF ELEVATOR HOISTWAY. CONNECT TO SMOKEHATCH (IF PRESENT), FIRE ALARM SYSTEM AND ELEVATOR RECALL SYSTEM.NOT USEDFIXED TEMPERATURE HEAT DETECTOR, 135°F, AT TOP OF ELEVATOR HOISTWAY.LOCATE WITHIN TWO FEET OF SPRINKLER HEAD. CONNECT TO FIRE ALARM SYSTEMAND ELEVATOR SHUTDOWN. PROVIDE CONTROL MODULES FOR SHUTDOWN.PROVIDE CONTROL MODULE, PROGRAMMING AND CONNECTION TO ELEVATOR TOFACILITATE ILLUMINATION OF ELEVATOR CAB HIGH HAT ALARM WHEN ANY FIREDETECTION DEVICE IN MACHINE ROOM OR HOISTWAY GOES INTO ALARM.PROVIDE MONITOR MODULE TO MONITOR PRESENCE OF SHUNT TRIP CONTROLPOWER. CONNECT TO FIRE ALARM SYSTEM.PROVIDE NEMA 1 CABINET WITH RELAYS FOR DESIGNATED LEVEL RECALL,ALTERNATE LEVEL RECALL, VISUAL WARNING (HIGH HAT ALARM) AND ELEVATORSHUTDOWN. LOCATE WITHIN 3 FEET OF ELEVATOR CONTROLLER. PROVIDE WIRINGCOMPLETE TO ELEVATOR CONTROLLER.1023456789GENERAL NOTES:A.LAYOUT IS GENERAL AND IS INTENDED TO SHOW ITEMS OF WORK AND NOTLOCATIONS OR SPACE CONFIGURATION. ACTUAL LOCATION OF ITEMS TO BECOORDINATED WITH ACTUAL LAYOUT OF ELEVATOR EQUIPMENT, SPACES, ANDWITH CODE ENFORCEMENT AUTHORITY HAVING JURISDICTION.B.ELEVATOR MACHINE IS LOCATED IN HOISTWAY. THERE IS NO ELEVATORMACHINE ROOM.111212TO PANEL1361314ELEVATORCONTROLLER14NO SCALERECEPTACLE & VOICE/DATA/TV OUTLETSINSTALLATION @ SIDE-BY-SIDE2NO SACLEELEVATOR DETAIL (WITH BUILDING SPRINKLER SYSTEM)6NO SCALEPIT PLANCNO SCALELOBBY PLANBNO SCALESHAFT PLANANO SACLETYPICAL ROUGHING HEIGHTS FOR ELECTRIC WORK5CONDUITS TO STUB UPWITHIN LUMINAIRE BASED12" PEA GRAVEL WELLCOMPACTED. ADJUST TOALLOW PROPER BASEELEVATIONDIMENSION SCHEDULELUMINAIRETYPEDESIGNATIONUNDISTURBED EARTHABCDPER MANUFACTURERHOT DIPPED GALVANIZEDRIGID STEEL CONDUITWITH THREADEDCOUPLING. SIZE ASSHOWN ON PLANSTIE REBARS TOGETHERPROVIDE VERTICAL 4-#4REBARS AND #3HORIZONTAL REBARS 6"ON CENTERSBA1" X 45° CHAMFER ALLAROUNDCOORDINATE LUMINAIREPLATE SIZE. PROVIDE LARGERBASE IF REQUIREDWEEP SLOTREBARSC3/4" PVC GROUNDCONDUCTOR SLEEVEGROUNDING BUSHINGFINISH GRADEANCHOR BOLT CIRCLE,ORIENTATION AND PROJECTIONINSTALLED ACCORDING TOMANUFACTURER'S TEMPLATECOMPACTBACKFILL3/4" X 10'-0"GROUND RODCOMPACTBACKFILL18"COMPACTBACKFILL#2 BARECOPPERGROUNDWIRENO SCALEROUND BASEFOUNDATION DETAIL - SITE LUMINAIRES51"30"3"18"45"30"3"16"HAHBHOISTWAYBUILDINGTAJHLDUTOPOFHOISTWAYSAFETYCOMPONENTSTASJH1VFDFUSEBOXTSUABBREVIATION LIST:JH = MAIN ELEVATOR SERVICE DISCONNECT SWITCH WITH SHUNT TRIP PROVIDED BY ELECTRICALCONTRACTOR.JH1 = HOISTWAY AUXILIARY DISCONNECT SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.JHS = INSPECTION AND TEST PANEL SWITCH PROVIDED BY ELEVATOR CONTRACTOR.LDU = INSPECTION AND TEST PANEL PROVIDED BY ELEVATOR CONTRACTOR.TA = 3-PHASE AUTOTRANSFORMER (208V:480V) PROVIDED BY ELEVATOR CONTRACTOR.TSU = MOTOR CONTROLLER PROVIDED BY ELEVATOR CONTRACTOR.TAS = TEST AND INSPECTION PANEL AUTOTRANSFORMER PROVIDED BY ELEVATOR CONTRACTOR.VFD = VARIABLE FREQUENCY DRIVE PROVIDED BY ELEVATOR CONTRACTOR.PDB = POWER DISTRIBUTION BLOCK PROVIDED BY ELEVATOR CONTRACTOR.M = MOTOR PROVIDED BY ELEVATOR CONTRACTOR.FUSE BOX PROVIDED BY ELEVATOR CONTRACTOR.MTOELECTRICALPANEL32227777JHJH17TOTRANSFORMERTAELEVATORFEEDERMAIN SHUNT TRIPCAR FANCAR LIGHTSSUMP PUMP RECEPTELEV1H1A1; 3,5,7H1A1, 45H1A1, 43H1A1ELEVATOR FEEDER SOURCE SCHEDULE70A3PTAJHWALL MOUNTEDSMOKE/CODETECTOR10"311.21.2011CONSTRUCTION CHANGE DIRECTIVE 5408.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSELECTRICAL DETAILSKSOE5.02GENERAL NOTES:A.REPAIR ALL SETTLEMENT.B.MINIMUM TOP SOIL - 6".C.PROVIDE DIRECT BURIED INSTALLATION FOR COMMUNICATION DUCTBANKS AND POWER BRANCH CIRCUITS.D.WHERE ADDITIONAL CABLES ARE CALLED FOR, INCREASE TRENCH WIDTH AND INSTALL CABLES WITH 3"MINIMUM SPACING.E. EXCAVATED MATERIAL MEETING SPECIFICATIONS MAY BE USED FOR BACKFILL IN TRENCHES. IN THE EVENTEXCAVATED MATERIAL DOES NOT MEET SPECIFICATIONS, PROVIDE GRANULAR BACKFILL AS SPECIFIED FORBACKFILL. REMOVE UNSUITABLE MATERIAL FROM SITE.30" MINIMUM3" MINIMUM SPACINGFINISH GRADE3" SAND BEDAROUND CONDUITCOMPACT BACKFILL TOMATCH SURROUNDINGCONDITIONSNO ROCKS, DEBRIS INBACKFILLSCHEDULE 80 PVCCONDUIT UNLESSOTHERWISE SHOWNSKID RESISTANTSURFACEHANDHOLETYPE12" CRUSHED STONEBELOW HANDHOLE.EXTEND 6" (MIN.)AROUND OUTSIDE EDGEON HANDHOLEHHLSLOPE FINISH GRADEAWAY FROM COVER.E18"DDIMENSIONCB12"10"20"A12"DIMENSION SCHEDULEBCAEDSTAINLESS STEEL HEXHEAD BOLT WITHWASHER AND GROMMETPULL SLOTCUSTOM COVERDESIGNATION: POWER,COMMUNICATIONS, CATV,ETC.GENERAL NOTE:A.DO NOT LOCATE IN VEHICULAR TRAFFIC OR SIDEWALK AREAS.CAST POLYMERCONCRETE COVERCAST POLYMERCONCRETE BOXCAST POLYMERCONCRETE HANDHOLESERVICEENTRANCEEQUIPMENTSTRUCTURALSTEEL#2/0 CUSERVICE ENTRANCEGROUND BUS#2/0 CUCONCRETEENCASEDELECTRODE INFLOOR SLABTYPICAL 3/4"x10'COPPERCLADGROUND RODGROUNDGRIDTYPICAL - EACHBUILDINGWATER SERVICEEXOTHERMICWELDLISTED PIPE CLAMP(WITHIN 5' OF POINT OFENTRANCE INTOBUILDING)LISTED CLAMPTYPICAL - TWOHOLECOMPRESSIONFITTING BOLTEDTO BUSTYPICAL -EXOTHERMIC WELDGENERAL NOTES:A.TYPICAL FOR ALL SERVICE ENTRANCE EQUIPMENT.B.PROVIDE SCHEDULE 80 PVC SLEEVES FOR GROUND CONDUCTORS.GROUND CLAMP HUBAND CABLE CLAMP.GROUNDING METER JUMPERAROUND WATER METER ANDINSULATING JOINTS.#4 CU#2/0 CUNO SCALEHANDHOLE DETAIL1NO SACLEMULTIPLE CONDUIT DETAILTYPICAL DIRECT BURIED IN SANDBED 2PAVING OR TOPSOIL TOMATCH SITE CONDITIONSMARKING TAPEINSULATEDMOUNTINGBRACKET1/4" COPPER GROUND BARNO SCALEGROUND BAR DETAILGENERAL NOTES:A.PROVIDE #4 GREEN INSULATED GROUND WIRE TO MAIN SERVICEGROUND.B.PROVIDE GROUND BAR IN EACH COMMUNICATION ROOM/CLOSET.REFER TO FLOOR PLANS FOR LOCATIONS AND QUANTITIES.C.PROVIDE LONG BARREL, INDENT TYPE LUGS FOR GROUND CONNECTION.4#4 CUCOMM ROOMGROUND BARHH34"26"23"38"40"NOTE1NOTES:1.LIGHTING HANDHOLESHHL ARE NOT SHOWN ONSITE PLANS.FIRE ALARM RISER GENERAL NOTES:A.THE FIRE ALARM RISER DIAGRAM IS DIAGRAMMATIC ONLY AND IS NOTINTENDED TO SHOW EACH DEVICE OR EXACT CONNECTIONS. OBTAINWIRING DIAGRAM FROM SYSTEM VENDOR FOR ALL DEVICES ANDCOMPONENTS REQUIRED TO MEET SPECIFICATIONS. THE ACTUALFIELD INSTALLATION WILL REQUIRE PULL BOXES, OFFSETS, OUTLETBOXES & OTHER RELATED ELECTRIC WORK TO PROVIDE THE PROPERINSTALLATION.B.ALL CONDUCTOR WIRING SHALL BE PERMANENTLY IDENTIFIED ANDLABELED IN ACCORDANCE WITH THE SPECIFICATIONS.C.SLC CIRCUITS: #18 TP (SHIELDED) FPL CABLE STROBE CIRCUITS (NAC): 2-#12 FPL CABLE 24VDC AUX. POWER: 2-#12 FPL CABLED.NOT ALL FIRE ALARM DEVICES ARE SHOWN OR INDICATED. DEVICESARE REPRESENTATIVE ONLY. REFER TO APPLICABLE FLOOR PLANSFOR DEVICE LOCATIONS, TYPES AND QUANTITIES.E.MAIN FIRE ALARM CIRCUIT WILL RUN IN HALLWAY AND IS PERMISSIBLETO T-TAP BRANCH CIRCUITS TO EACH APARTMENT FROM MAIN CIRCUIT.F.PROVIDE NAC PANELS AND TERMINAL EQUIPMENT CABINETS ASREQUIRED.M. PROVIDE FIRE ALARM SYSTEM CONNECTION TO ELEVATOR SHUNT TRIPDISCONNECT SWITCHES.FACP120V20A-1P1FPHPTS2KEYED NOTES:PROVIDE TWO 4-PR CAT5E TELEPHONE LINES FROM BUILDINGTELEPHONE SYSTEM BACKBOARD TO FIRE ALARM CONTROL PANEL.PROVIDE SUPERVISORY CONNECTION TO FIRE PROTECTION HEATTRACE CONTROL PANEL.TERMINAL EQUIPMENT CABINET.ADDRESSABLE MONITOR MODULE.1224VDC AUX POWER24VDC AUX POWER24VDC AUX POWERTEC120V20A-1PFPHPTS224VDC AUX POWER24VDC AUX POWER24VDC AUX POWERTEC120V20A-1PFPHPTS224VDC AUX POWER24VDC AUX POWER24VDC AUX POWERFACP120V20A-1P1FPHPTS224VDC AUX POWER24VDC AUX POWER24VDC AUX POWERNO SCALEBUILDINGS 1, 2.4, 4.1, 4.2 & 4.3FIRE ALARM SYSTEM RISER DIAGRAM6NO SCALEBUILDING 2.0, 2.1, 2.2 & 2.3FIRE ALARM SYSTEM RISER DIAGRAM534334TYPICAL4TYPICAL4TYPICALSERVICEENTRANCEEQUIPMENTSTRUCTURALSTEEL#3/0 CUSERVICE ENTRANCEGROUND BUS#3/0 CUCONCRETEENCASEDELECTRODE INFLOOR SLABTYPICAL 3/4"x10'COPPERCLADGROUND RODGROUNDGRIDTYPICAL - EACHBUILDINGWATER SERVICEEXOTHERMICWELDLISTED PIPE CLAMP(WITHIN 5' OF POINT OFENTRANCE INTOBUILDING)LISTED CLAMPTYPICAL - TWOHOLECOMPRESSIONFITTING BOLTEDTO BUSTYPICAL -EXOTHERMIC WELDGENERAL NOTES:A.TYPICAL FOR ALL SERVICE ENTRANCE EQUIPMENT.B.PROVIDE SCHEDULE 80 PVC SLEEVES FOR GROUND CONDUCTORS.GROUND CLAMP HUBAND CABLE CLAMP.GROUNDING METER JUMPERAROUND WATER METER ANDINSULATING JOINTS.#4 CU#3/0 CUNO SCALEELECTRODE SYSTEM DETAIL - BUILDING 2.0SERVICE ENTRANCE GROUNDING6#4 CUCOMM ROOMGROUND BARNO SCALE BUILDINGS 1, 2.4, 4.1, 4.2, 4.3, 901/4.4ELECTRODE SYSTEM DETAIL -3311.21.2011CONSTRUCTION CHANGE DIRECTIVE 5SERVICE ENTRANCE GROUNDING401.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13508.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSFIRE ALARM INPUT/OUTPUT MATRIXOUTPUT ALARMFIRE ALARM3 CODE 3 CODE DOORS HOLD-TEMPORALTEMPORAL OPEN RELEASE, SUPERVISORY BUILDING WIDE SOUNDER OFF PREMISE OFF PREMISE ELEVATOR ALARM A/V'S AND ALL BASES SUPERVISORY FIRE ALARM RECALL, FANS SOUNDER WITHIN SAME ALARM SHUT DOWN, BASES DWELLING UNIT ETC.INITIATINGDEVICESMANUAL PULLXXXXSTATIONSMOKE DETECTOR/ XXXX SENSORONE (1) SOUNDER BASE MULTI-SENSOR XXX SMOKE ALGORITHMTWO (2) OR MORE SOUNDER BASE MULTI-XXXXSENSOR SMOKE ALGORITHMHEAT DETECTOR/ XXXXSENSORTAMPER SWITCHXXFLOW SWITCHXXXXLOW AIR PRESSURE XXSWITCHCARBON MONOXIDE XX (STEADY X SENSOR SOUNDER5
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923KEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSAugust 10, 2011ELECTRICAL DETAILSKSOE5.03TRENCH WIDTHCOMPACT BACKFILL TOMATCH SURROUNDINGCONDITIONSNO ROCKS, DEBRIS INBACKFILLUNLESS OTHERWISE NOTED RESTORESURFACE TO MATCH SITE CONDITIONSPROVIDE MIN. 3"CONCRETE ON ALLSIDES OF CONDUITCONDUIT: SIZE, MATERIALAND IDENTIFICATION, ASSPECIFIEDMIN. 3" BETWEEN CONDUITS#4 REBARS, 6" O. C. TIEDTO CONDUIT SUPPORTSTYPICAL CONDUITSPACER MAXIMUM10'-0" O.C.PROVIDE PRECAST BASEAT CONDUIT SPACERBASE, WHERE BOTTOM OFTRENCH IS NOT LEVELAND UNIFORM#4 REBARS SPIKES FORHOLD DOWN BAR. MINIMUM24" GROUND PENETRATION,DRIVEN AT AN APPROXIMATE25° ANGLE TO CONDUIT RUNHOLD DOWN BAR.PROVIDE QUANTITY TOPREVENT FLOUT-OUT,MAXIMUM 15'-0" O.C.MIN. 3" BETWEENCONDUITSCONTINUOUSMARKER TAPEGENERAL NOTES:A.REFER TO DUCTBANK SECTION AND/OR ONE-LINE DIAGRAM FOR ACTUAL QUANTITY AND SIZE OF CONDUITSREQUIRED.B.LEAVE PULL ROPE IN ALL SPARES.C.EXCAVATED MATERIAL MEETING SPECIFICATIONS MAY BE USED FOR BACKFILL IN TRENCHES. IN THE EVENTEXCAVATED MATERIAL DOES NOT MEET SPECIFICATIONS, PROVIDE GRANULAR BACKFILL AS SPECIFIED FORBACKFILL. REMOVE UNSUITABLE MATERIAL FROM SITE.D.UNLESS OTHERWISE NOTED, TOP OF CONDUIT SHALL BE 30" BELOW FINISHED GRADE.FINISH GRADEGENERAL NOTES:A.REINFORCE WITH GRADE 60, #4 BARS @ 6" O. C. E. W.B.3/4" CHAMFER STRIP, ALL TOP EDGES INCLUDING OPENING.C.TOP AND BOTTOM TO BE SMOOTH FINISH.D.4000 PSI CONCRETE AT 28 DAYS.E.VERIFY ACTUAL REQUIRED ANCHOR BOLTS, CABLE OPENING AND OVERALL DIMENSIONSAND CONFIGURE ACCORDINGLY. COORDINATE WITH NYSEG.F.PROVIDE PAD AND INSTALLATION PER NYSEG REQUIREMENTS. SUBMIT TO NYSEG FORAPPROVAL PRIOR TO ORDERING.DIMENSIONS IN INCHES10DIMENSIONS OF POURED OR PRECAST CONCRETE PADS75-500kVA15KV3PH78A487218CBDEMIN. 1/2" COVER FORREINFORCING BARSX-FORMER RATINGFFRONTACGELIFTING LOOP,TYP.DB6"6"3"2700WEIGHTS(lbs)F1713G4 BARS @ 18" TOPONLY(TYP)TYPTYP3"NO SCALEPRECAST CONCRETE FLAT PAD4NO SACLECONCRETE ENCASED DUCTBANK DETAILTYPICAL REINFORCED7NO SACLETYPICAL SAND BED DUCTBANK DETAIL9TRENCH WIDTHCOMPACT BACKFILL TOMATCH SURROUNDINGCONDITIONSNO ROCKS, DEBRIS INBACKFILLUNLESS OTHERWISE NOTED RESTORESURFACE TO MATCH SITE CONDITIONSPROVIDE MIN. 3"CONCRETE ON ALLSIDES OF CONDUITCONDUIT: SIZE, MATERIALAND IDENTIFICATION, ASSPECIFIEDMIN. 3" BETWEEN CONDUITSTYPICAL CONDUITSPACER MAXIMUM10'-0" O.C.PROVIDE PRECAST BASEAT CONDUIT SPACERBASE, WHERE BOTTOM OFTRENCH IS NOT LEVELAND UNIFORM#4 REBARS SPIKES FORHOLD DOWN BAR. MINIMUM24" GROUND PENETRATION,DRIVEN AT AN APPROXIMATE25° ANGLE TO CONDUIT RUNHOLD DOWN BAR.PROVIDE QUANTITY TOPREVENT FLOUT-OUT,MAXIMUM 15'-0" O.C.MIN. 3" BETWEENCONDUITSCONTINUOUSMARKER TAPEGENERAL NOTES:A.REFER TO DUCTBANK SECTION AND/OR ONE-LINE DIAGRAM FOR ACTUAL QUANTITY AND SIZE OF CONDUITSREQUIRED.B.LEAVE PULL ROPE IN ALL SPARES.C.EXCAVATED MATERIAL MEETING SPECIFICATIONS MAY BE USED FOR BACKFILL IN TRENCHES. IN THE EVENTEXCAVATED MATERIAL DOES NOT MEET SPECIFICATIONS, PROVIDE GRANULAR BACKFILL AS SPECIFIED FORBACKFILL. REMOVE UNSUITABLE MATERIAL FROM SITE.D.UNLESS OTHERWISE NOTED, TOP OF CONDUIT SHALL BE 30" BELOW FINISHED GRADE.FINISH GRADENO SACLECONCRETE ENCASED DUCTBANK DETAILTYPICAL5GENERAL NOTES:A.ALLOW SUFFICIENT SLACK CABLE SO SPLICES CAN BE MADE ABOVE GRADE, OUTSIDE OFHANDHOLE. COIL SPLICE AND SLACK CABLE NEATLY INTO HANDHOLE.B.DO NOT LOCATE HANDHOLES IN VEHICULAR TRAFFIC AREAS.C.INSIDE DIMENSIONS: HT. 48 IN., WIDTH 48 IN., LENGTH 48 IN.12" OF #2 CRUSHEDSTONE; EXTENDMINIMUM OF 6" BEYONDOUTSIDE EDGE.MIN. TWO (2) COURSES BRICK.PLACE ADDITIONAL BRICK ASREQUIRED TO BRING FRAME UPTO FINISHED GRADEGROUT FRAME4" X 10" KNOCKOUTS,TWO (2) ON EACHSIDESLOPE FINISHED GRADEAWAY FROM COVERFRAME AND COVERUNDISTURBEDEARTHGRAVELREPAIR PAVING ORPLANTING TO MATCHSURROUNDINGCONDITIONSHANDHOLEFRAMEPOWERMANHOLE/PULLBOXTYPE ATYPECBBASEA33-1/2"ROUND43"32"FEG6-1/2"32"COVERXEFDCCOVERDESIGNATIONGBD30"NO SCALEPULLBOX FRAME AND COVER6NO SCALEPULL BOX DETAIL8TRENCH WIDTHCOMPACT BACKFILL TOMATCH SURROUNDINGCONDITIONSNO ROCKS, DEBRIS INBACKFILLCONDUIT: SIZE, MATERIALAND IDENTIFICATION, ASSPECIFIEDMIN. 3" BETWEEN CONDUITSTYPICAL CONDUITSPACER MAXIMUM10'-0" O.C.PROVIDE PRECAST BASEAT CONDUIT SPACERBASE, WHERE BOTTOM OFTRENCH IS NOT LEVELAND UNIFORMMIN. 3" BETWEENCONDUITSCONTINUOUSMARKER TAPEGENERAL NOTES:A.REFER TO DUCTBANK SECTION AND/OR ONE-LINE DIAGRAM FOR ACTUAL QUANTITY AND SIZE OF CONDUITSREQUIRED.B.LEAVE PULL ROPE IN ALL SPARES.C.EXCAVATED MATERIAL MEETING SPECIFICATIONS MAY BE USED FOR BACKFILL IN TRENCHES. IN THE EVENTEXCAVATED MATERIAL DOES NOT MEET SPECIFICATIONS, PROVIDE GRANULAR BACKFILL AS SPECIFIED FORBACKFILL. REMOVE UNSUITABLE MATERIAL FROM SITE.D.UNLESS OTHERWISE NOTED, TOP OF CONDUIT SHALL BE 30" BELOW FINISHED GRADE.E.SPACERS AND PRECAST BASE MAY BE DELETED FOR SINGLE TIER DUCTBANK SECTIONS.FINISH GRADEPROVIDE MIN. 3"SAND BED ON ALLSIDES OF CONDUITUNLESS OTHERWISE NOTED RESTORESURFACE TO MATCH SITE CONDITIONSTO TELCO. GROUND(IF AVAILABLE)DETAIL AGROUND GRID 2/0 CuBARE SOFT DRAWN - 19STRANDCONCRETEFOUNDATIONPRIMARYSECONDARY36"18"18"18"2/0 Cu BARE SOFTDRAWN - 19STRAND'C' TYPECOMPRESSIONCONNECTORGROUNDCLAMP8' GROUND ROD2/0 Cu BARE SOFTDRAWN - 19 STRANDGRADE12"GROUNDCLAMP8' GROUND RODPLAN VIEWSECTION VIEWDETAIL ADETAIL BNO SACLETHREE PHASE PADMOUNTED TRANSFORMERNYSEG - GROUNDING PLAN10DETAIL BGROUND RODDETAIL BDETAIL BDETAIL B18"GROUND RODGROUND RODGROUND ROD18"AX1-1/2"14750-25001538950751731002118311.21.2011CONSTRUCTION CHANGE DIRECTIVE 518" MINIMUM COMPACTED #2CRUSHED STONEGENERAL NOTES:A.COORDINATE ANCHOR LOCATION WITH METER CENTER BASE.B.VERIFY DIMENSIONS OF METER CENTER BASE PRIOR TO FABRICATION.C.PAD SHALL EXTEND 3" BEYOND METER CENTER BASE.D.VERIFY AND COORDINATE STUB UP AREAS IN METER CENTER PAD WITH METERCENTER.NO SCALEEXTERIOR METER CENTER PAD DETAIL3PATCH PAVEMENT TO MATCHEXISTING CONDITIONSSECTION 18"3"12"3"TYPICAL #4 @ 18" ON CENTEREACH DIRECTIONPLAN4"401.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13508.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSELECTRICAL SCHEDULESKSOE6.02P A N E L B O A R D T Y P E F S C H E D U L EA.I.C. RATING:10000VOLTS:208/120MAINS:125ALOCATION:VARIESBRKR SPACE:20PHASE:1MCB:SOURCE:METER CENTERMTG./NEMA #:1WIRE:3MLO:125AFEEDER:REFER TO ONE-LINE DIAGRAM#LOADBREAKERBREAKERLOAD#TYPEDESCRIPTIONAMPPOLEPOLEAMPDESCRIPTIONTYPE1BEDROOM 1 POWER AND LIGHTING15A1120AKITCHEN POWER23BEDROOM 2 POWER AND LIGHTING15A1120AKITCHEN POWER 45LIVING ROOM LIGHTING15A1120ADISHWASHER67LIVING ROOM POWER 15A1120ADISPOSAL89BATHROOM 1 POWER AND LIGHTING20A1120ARANGE HOOD1011BATHROOM 2 POWER AND LIGHTING20A1240ARANGE1213APARTMENT PTAC UNIT20A21415SPACE1617SPACESPACE1819SPACESPACE20NOTE:P A N E L B O A R D T Y P E D1 S C H E D U L EA.I.C. RATING:10000VOLTS:208/120MAINS:125ALOCATION:VARIESBRKR SPACE:20PHASE:1MCB:SOURCE:METER CENTERMTG./NEMA #:1WIRE:3MLO:125AFEEDER:REFER TO ONE-LINE DIAGRAM#LOADBREAKERBREAKERLOAD#TYPEDESCRIPTIONAMPPOLEPOLEAMPDESCRIPTIONTYPE1BEDROOM 1 POWER AND LIGHTING15A1120AKITCHEN POWER23BEDROOM 2 POWER AND LIGHTING15A1120AKITCHEN POWER 45LIVING ROOM LIGHTING 15A1120ADISHWASHER67LIVING ROOM POWER 15A1120ADISPOSAL89BATHROOM 1 POWER AND LIGHTING20A1120ARANGE HOOD1011BATHROOM 2 POWER AND LIGHTING20A1240ARANGE1213APARTMENT PTAC UNIT20A21415SPACE1617WASHER/DRYER30A2SPACE1819SPACE20NOTE:P A N E L B O A R D T Y P E F1 S C H E D U L EA.I.C. RATING:10000VOLTS:208/120MAINS:125ALOCATION:VARIESBRKR SPACE:20PHASE:1MCB:SOURCE:METER CENTERMTG./NEMA #:1WIRE:3MLO:125AFEEDER:REFER TO ONE-LINE DIAGRAM#LOADBREAKERBREAKERLOAD#TYPEDESCRIPTIONAMPPOLEPOLEAMPDESCRIPTIONTYPE1BEDROOM 1 POWER AND LIGHTING15A1120AKITCHEN POWER23BEDROOM 2 POWER AND LIGHTING15A1120AKITCHEN POWER 45LIVING ROOM LIGHTING15A1120ADISHWASHER67LIVING ROOM POWER 15A1120ADISPOSAL89BATHROOM 1 POWER AND LIGHTING20A1120ARANGE HOOD1011BATHROOM 2 POWER AND LIGHTING20A1240ARANGE1213APARTMENT PTAC UNIT30A21415SPACE1617SPACESPACE1819SPACESPACE20NOTE:P A N E L B O A R D T Y P E F2 S C H E D U L EA.I.C. RATING:10000VOLTS:208/120MAINS:125ALOCATION:VARIESBRKR SPACE:20PHASE:1MCB:SOURCE:METER CENTERMTG./NEMA #:1WIRE:3MLO:125AFEEDER:REFER TO ONE-LINE DIAGRAM#LOADBREAKERBREAKERLOAD#TYPEDESCRIPTIONAMPPOLEPOLEAMPDESCRIPTIONTYPE1BEDROOM 1 POWER AND LIGHTING15A1120AKITCHEN POWER23BEDROOM 2 POWER AND LIGHTING15A1120AKITCHEN POWER 45LIVING ROOM LIGHTING15A1120ADISHWASHER67LIVING ROOM POWER 15A1120ADISPOSAL89BATHROOM 1 POWER AND LIGHTING20A1120ARANGE HOOD1011BATHROOM 2 POWER AND LIGHTING20A1240ARANGE1213APARTMENT PTAC UNIT15A21415SPACE1617SPACESPACE1819SPACESPACE20NOTE:311.21.2011CONSTRUCTION CHANGE DIRECTIVE 5405.11.2012CCD #35BUILDINGS 2.1, 2.2, 2.3 - ELECTRIC EQUIPMENT AND CONTROL SCHEDULEF-1---INDICATES EQUIPMENT DESIGNATION FROM SCHEDULE101---INDICATES ROOM LOCATION FOR CONTROL DEVICEAU---INDICATES CONTROL DEVICE LOCATED AT UNITX---INDICATES FIRE ALARM FAN SHUTDOWN IS REQUIREDEQUIPMENTITEMS FURNISHED AND INSTALLED BY ELECTRICAL DIVISIONITEMS FURNISHED BY OTHER DIVISIONS AND INSTALLED BY ELECTRICAL DIVISIONEQUIP.NAMEROOMHPKWVPHPANEL ORCIRCUITPOWER WIRINGPOWER WIRINGGNDREF.FUSEDNONFIREMANUALCOMB.2-SPEEDVARIABLEISOLATIONSINGLEPKG.DESIGNLOCATIONCONTROLBREAKERFROM PANEL TOFROM CONTROLWIRENOTESDISC.FUSEDALARMMOTORMAGNETICCOMB.SPEEDTRANS. (IT)POINTCTRL.CENTERCONTROL UNITUNIT TO SWITCHDISC.FANSTARTERSTARTERMAGNETICDRIVESOR LINECONNECTUNITEQUIPMENTSWITCHSHUTDOWNSTARTERREACTOR (LR)AC-2.1AIR COMPRESSORMEP ROOM1-1/12003H21M-115A-3P3#12+G MC3#12+G MC#12MEP RMB-2.1-1BOILERMEP ROOM0.51151H21M-115A-1P2#12+G MC2#12+G MC#12MEP RMB-2.1-2BOILERMEP ROOM0.51151H21M1-115A-1P2#12+G MC2#12+G MC#12MEP RMCUH-2.0B-1CABINET UNIT HEATERSTAIR0.11151H21M-115A-1P2#12+G MC#12AUCUH-2.0B-2CABINET UNIT HEATERSTAIR0.11151H2215A-1P2#12+G MC#12AUCUH-2.0B-3CABINET UNIT HEATERSTAIR0.11151H2315A-1P2#12+G MC#12AUCUH-2.1C-1CABINET UNIT HEATERNORTH ENTRY0.11151H21M-115A-1P2#12+G MC#12AUCUH-2.2C-1CABINET UNIT HEATERNORTH ENTRY0.11151H2215A-1P2#12+G MC#12AUCUH-2.3C-1CABINET UNIT HEATERNORTH ENTRY0.11151H2315A-1P2#12+G MC#12AUEFK-2.1-1EXHAUST FAN (KITCHEN)ROOF (2.1)1/51151H21M-120A-1P2#12+G MC2#12+G MC#121ROOFMEP ROOMEFK-2.1-2EXHAUST FAN (KITCHEN)ROOF (2.1)1/51151H21M-120A-1P2#12+G MC2#12+G MC#121ROOFMEP ROOMEFK-2.1-3EXHAUST FAN (KITCHEN)ROOF (2.1)1/51151H21M-120A-1P2#12+G MC2#12+G MC#121ROOFMEP ROOMEFK-2.2-1EXHAUST FAN (KITCHEN)ROOF (2.2)1/51151H2220A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFK-2.2-2EXHAUST FAN (KITCHEN)ROOF (2.2)1/51151H2220A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFK-2.2-3EXHAUST FAN (KITCHEN)ROOF (2.2)1/51151H2220A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFK-2.2-4EXHAUST FAN (KITCHEN)ROOF (2.2)1/51151H2220A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFK-2.3-1EXHAUST FAN (KITCHEN)ROOF (2.3)1/51151H2320A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFK-2.3-2EXHAUST FAN (KITCHEN)ROOF (2.3)1/51151H2320A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFK-2.3-3EXHAUST FAN (KITCHEN)ROOF (2.3)1/51151H2320A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFK-2.3-4EXHAUST FAN (KITCHEN)ROOF (2.3)1/51151H2320A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFT-2.1-1EXHAUST FAN (BATHROOM)ROOF (2.1)1/71151H21M-120A-1P2#12+G MC2#12+G MC#121ROOFMEP ROOMEFT-2.1-2EXHAUST FAN (BATHROOM)ROOF (2.1)1/71151H21M-120A-1P2#12+G MC2#12+G MC#121ROOFMEP ROOMEFT-2.1-3EXHAUST FAN (BATHROOM)ROOF (2.1)1/71151H21M-120A-1P2#12+G MC2#12+G MC#121ROOFMEP ROOMEFT-2.2-1EXHAUST FAN (BATHROOM)ROOF (2.2)1/51151H2220A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFT-2.2-2EXHAUST FAN (BATHROOM)ROOF (2.2)1/51151H2220A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFT-2.3-1EXHAUST FAN (BATHROOM)ROOF (2.3)1/51151H2320A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EEFT-2.3-2EXHAUST FAN (BATHROOM)ROOF (2.3)1/51151H2320A-1P2#12+G MC2#12+G MC#121ROOFLEVEL EF-2.0-1FANMEP ROOM1/41151H21M-115A-1P2#12+G MC2#12+G MC#12MEP ROOMF-2.1-1FANROOF1/41151H21M-115A-1P2#12+G MC2#12+G MC#12ROOFMEP ROOMF-2.2-1FANROOF1/4115115A-1P2#12+G MC2#12+G MC#12ROOFMEP ROOMF-2.2C-1FANCORR CLOSET0.41151H2215A-1P2#12+G MC2#12+G MC#12AUF-2.2D-1FANCORR CLOSET0.41151H2215A-1P2#12+G MC2#12+G MC#12AUF-2.2E-1FANCORR CLOSET0.41151H2215A-1P2#12+G MC2#12+G MC#12AUF-2.3C-1FANCORR CLOSET0.41151H2315A-1P2#12+G MC2#12+G MC#12AUF-2.3D-1FANCORR CLOSET0.41151H2315A-1P2#12+G MC2#12+G MC#12AUF-2.3E-1FANCORR CLOSET0.41151H2315A-1P2#12+G MC2#12+G MC#12AUF-TFAN - TENANT BATHROOMSVARIES0.11151VARIES20A-1P2#12 + G NM2#12 + G NM#122HE-2.0HEAT EXCHANGERMEP ROOM1151H21M-115A-1P2#12, 1/2"C2#12, 1/2"C#12AUP-2.1-1PUMP - HEATINGMEP ROOM32003H21M-120A-3P3#12+G MC3#12+G MC#12MEP RM (VSD-2.1-1)P-2.1-2PUMP - HEATINGMEP ROOM32003H21M-120A-3P3#12+G MC3#12+G MC#12MEP RM (VSD-2.1-2)P-2.1-3PUMP - BOILERMEP ROOM0.371151H21M-115A-1P2#12+G MC2#12+G MC#12MEP RMP-2.1-3APUMP - BOILERMEP ROOM0.371151H21M-115A-1P2#12+G MC2#12+G MC#12MEP RMP-2.1-4PUMP - BOILERMEP ROOM0.371151H21M-115A-1P2#12+G MC2#12+G MC#12MEP RMP-2.1-4APUMP - BOILERMEP ROOM0.371151H21M-115A-1P2#12+G MC2#12+G MC#12MEP RMP-2.1-5PUMP - HWHMEP ROOM2/51151H21M-120A-1P2#12, 1/2"C2#12, 1/2"C#12MEP RMP-2.1-6PUMP - HWHMEP ROOM2/51151H21M-120A-1P2#12, 1/2"C2#12, 1/2"C#12MEP RMPP-2.1-1DOMESTIC CIRC PUMPMEP ROOM1/121151H21M-115A-1P2#12, 1/2"C2#12, 1/2"C#12MEP RMPTAC-2.1C1PTAC UNITLEVEL C APT2.22001T21C120A-2P2#12 + G NM-#12AUPTAC-2.1C2PTAC UNITLEVEL C APT2.22001T21C220A-2P2#12 + G NM-#12AUPTAC-2.1C3PTAC UNITLEVEL C APT1.52001T21C415A-2P2#12 + G NM-#12AUPTAC-2.1C4PTAC UNITLEVEL C APT3.22001T21C330A-2P2#10 + G NM-#10AUPTAC-2.1D1PTAC UNITLEVEL D APT2.22001T21D120A-2P2#12 + G NM-#12AUPTAC-2.1D2PTAC UNITLEVEL D APT2.22001T21D220A-2P2#12 + G NM-#12AUPTAC-2.1D3PTAC UNITLEVEL D APT1.52001T21D415A-2P2#12 + G NM-#12AUPTAC-2.1D4PTAC UNITLEVEL D APT3.22001T21D330A-2P2#10 + G NM-#10AUPTAC-2.1E1PTAC UNITLEVEL E APT2.22001T21E120A-2P2#12 + G NM-#12AUPTAC-2.1E2PTAC UNITLEVEL E APT2.22001T21E220A-2P2#12 + G NM-#12AUPTAC-2.1E3PTAC UNITLEVEL E APT1.52001T21E415A-2P2#12 + G NM-#12AUPTAC-2.1E4PTAC UNITLEVEL E APT3.22001T21E330A-2P2#10 + G NM-#10AUF-2.3-1FANROOF1/41151H2315A-1P2#12, 1/2"C2#12, 1/2"C#12ROOFF-2.3-2FANROOF1/41151H2315A-1P2#12, 1/2"C2#12, 1/2"C#12ROOFF-2.3-3FANROOF1/41151H2315A-1P2#12, 1/2"C2#12, 1/2"C#12ROOFPP-2-02CIRC PUMPLEVEL A1/121151H1A115A-1P2#12, 1/2"C2#12, 1/2"C#12MEP RMNOTES:1. CIRCUIT FAN THROUGH EXHAUSTO VARIABLE SPEED CONTROLLER PROVIDED BY MECHANICAL CONTRACTOR.2. TENANT BATHROOM EXHAUST FANS SHALL BE CIRCUITED TOGETHER WITH THE ASSOCIATED BATHROOM LIGHTING CIRCUIT. INSTALL FAN CONTROLLER FURNISHED BY MECHANICAL CONTRACTOR. COORDINATE JUNCTION BOX SIZE WITH MECHANICAL CONTRACTOR.DATA OUTLET SCHEDULETYPEMOUNTING HEIGHTNOTEA18" AFF1B18" AFF2CABOVE COUNTER3DABOVE CEILING41TIME WARNER CABLE DATA SYSTEM. 2TIME WARNER CABLE DATA SYSTEM. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATION.3NOT USED.4TIME WARNER CABLE DATA SYSTEM WIRELESS ACCESS POINT. TV OUTLET SCHEDULETV TYPEMOUNTING HEIGHTNOTEA18" AFF1BAC2NOTES:1TIME WARNER TV SYSTEM. PROVIDE OUTLET UNDER BASE BID.2TIME WARNER TV SYSTEM. PROVIDE OUTLET UNDER BASE BID. COORDINATE OUTLET LOCATION WITH ARCHITECTURAL ELEVATIONS.506.18.2012CCD #44608.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTS
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSELECTRICAL SCHEDULESKSOE6.13411.21.2011CONSTRUCTION CHANGE DIRECTIVE 5501.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13603.12.2012CCD #21708.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSLIGHTING FIXTURE SCHEDULETYPE LAMPS VOLTAGENOMINALDESCRIPTIONLENS / FINISHDESIGN FIXTURE SERIESNOTESWATTAGESHIELDINGHA150W MH208200POLE MOUNTED SINGLE ARM (4" POST), TYPE 3 OPTICSSELECTED BY ARCHITECT FROM PHILIPS GARDCO MA22-1-1. UNITED18 FT HIGH, 4 IN ROUND STRAIGHT SMOOTH POLE, 7 GAUGE STEEL, CAST ALUMINUMSTANDARD FINISHESLIGHTING STANDARDS RSP-18-4-4 POLEBASE COVER, 2" X 4" OVAL HAND HOLEHB70W MH208120POLE MOUNTED SINGLE ARM (4" POST), TYPE 2 OPTICSSELECTED BY ARCHITECT FROM 12 FT HIGH, 4 IN ROUND STRAIGHT SMOOTH POLE, 0.188" WALL STEEL, CAST ALUMINUMSTANDARD FINISHESBASE COVER, 2" X 4" OVAL HAND HOLEFA2-13W CF12030FLUSHMOUNT CEILING FIXTUREFROSTED GLASSPOLISHED STEELLIGHT SOURCELS-5337 SERIESFA12-13W CF1203012-INCHDIAMETER SHALLOW ROUND DOMEFROSTED GLASSPOLISHED STEELLIGHT SOURCELS-5337 SERIESFB3-13W CF1204517-INCHDIAMETER SHALLOW ROUND DOMEFROSTED GLASSPOLISHED STEELLIGHT SOURCELS-5338 SERIESFC2-25W T81205037-INCH WALL MOUNTED VANITY FIXTURESMOOTH WHITE ACRYLIC LENSMARBLE END CAPSINCON LIGHTING 59818-50Z-ESENERGY STARFC12-17W T81204025-INCH WALL MOUNTED VANITY FIXTURESMOOTH WHITE ACRYLIC LENSMARBLE END CAPSINCON LIGHTING 59818-34Z-ESFD1-26W QUAD120306 INCH DOWNLIGHTOPEN SPECULAR CLEAR REFLECTORPHILIPS CAPRI CFR6V26QFE3-13W CF1204517-INCH DIAMETER SHALLOW ROUND DOMEFROSTED GLASSPOLISHED STEELLIGHT SOURCELS-5338 SERIESFEEM3-13W CF1204517-INCH DIAMETER SHALLOW ROUND DOMEFROSTED GLASSPOLISHED STEELLIGHT SOURCEREMOTE EMERGENCY BALLAST WITH TEST SWITCH AND INDICATORLS-5338 SERIESFF1-26W QUAD1203013 INCH DIAMETER SHALLOW ROUND DOMEOPAL STANDARD DIFFUSERWHITELUMINAIRE LIGHTINGARV13-1PLC26FFEM1-26W QUAD1203013 INCH DIAMETER SHALLOW ROUND DOMEOPAL STANDARD DIFFUSERWHITELUMINAIRE LIGHTINGINTEGRAL EMERGENCY BALLASTARV13-1PLC26FGEM2-32W-T812070WALL MOUNTED, INTEGRAL EMERGENCY BATTERY PACK, UL LISTED FOR DAMP LOCATIONCLEAR PRISMATIC WHITEDAY-BRITE STWINTEGRAL OCCUPANCY SENSOR DIMS FIXTURE TO 5%FL1-32W T812035VANDAL RESISTANT,SURFACE MOUNTED AT GRID CEILING, FIBERGLASS BODYACRYLICDAY-BRITE DWAEUL LISTED FOR WET LOCATION, COLD WEATHER BALLAST.FLEM1-32W T812035VANDAL RESISTANT,SURFACE MOUNTED AT GRID CEILING, FIBERGLASS BODYACRYLICDAY-BRITE DWAEUL LISTED FOR WET LOCATION, COLD WEATHER BALLAST. COLD WEATHER EM BALLASTFO1-100W INC120100WALL MOUNTED VANDALPROOF DIE CAST ALUMINIM, UL WET LOCATION LISTEDCLEAR GLASS WITH GUARDSILVER GREYDAY-BRITE VIN-100FR2-32W T8120704 FT INDUSTRIALWIRE GUARDWHITEDAY-BRITE IAFREM2-32W T8120704 FT INDUSTRIALWIRE GUARDWHITEDAY-BRITE IAINTEGRAL EMERGENCY BATTERYFS2-26W PLC12060WALL MOUNTED, ALUMINIM, UL WET LOCATION LISTEDTRANSLUCENT WHITE ACRYLICSELECTED BY ARCHITECT FROM VISA OW 1044COLD WEATHER BALLASTSTANDARD FINISHESFSEM2-26W PLC12060WALL MOUNTED, ALUMINIM, UL WET LOCATION LISTED, COLD WEATHER BALLASTTRANSLUCENT WHITE ACRYLICSELECTED BY ARCHITECT FROM VISA OW 1044INTEGRAL EMERGENCY COLD WEATHER BALLASTSTANDARD FINISHESFSI2-26W PLC12060WALL MOUNTED, ALUMINIM, UL WET LOCATION LISTEDTRANSLUCENT WHITE ACRYLICSELECTED BY ARCHITECT FROM VISA OW 1044STANDARD FINISHESFSIEM2-26W PLC12060WALL MOUNTED, ALUMINIM, UL WET LOCATION LISTED, COLD WEATHER BALLASTTRANSLUCENT WHITE ACRYLICSELECTED BY ARCHITECT FROM VISA OW 1044INTEGRAL EMERGENCY BALLASTSTANDARD FINISHESFT1-26W QUAD120306 INCH LENSED DOWNLIGHTFRESNELSPLAY WHITE REFLECTORPHILIPS OMEGA S6 SRDUL LISTED FOR WET LOCATIONFX1-35W-T5120405 FT SURFACE MOUNTED LINEAR FLUORESCENT, CONCAVE SOCKET COVER, SATIN CLEARBIRCHWOOD LIGHTING TORI SMFXEM1-35W-T5120404 INCH DOWNLIGHTOPENCLEAR REFLECTORBIRCHWOOD LIGHTING TORI SMFY2-13W CFL120605 FT SURFACE MOUNTED LINEAR FLUORESCENT, CONCAVE SOCKET COVER, SATIN CLEARPHILIPS CAPRIINTEGRAL EMEREGECNY BALLASTCFR1C4V13 NEINB P4RCLF4 FT LED12060LINEAR LED SURFACE MOUNTED, DIMMABLE, 4 FT LENGTHBLACKCOLOR KINETICS eW GRAZE POWERCORE2700 DEG K, 10 X 60 BEAM SPREADEM2-8W MR16120EMERGENCY LIGHTING UNIT, 6 VOLT, LEAD ACID BATTERY WHITEPHILIPS MCPHILBEN CAX6HEMC2-9W MR16120EMERGENCY LIGHTING UNIT, UL LISTED WET LOCATION, 6 VOLT, LEAD ACID BATTERY WHITEPHILIPS MCPHILBEN 65XWITH HEATER, SELF TESTING AND DIAGNOSTICSE1RED LED120THERMOPLASTIC EXIT SIGN, NICAD BATTERY, SINGLE SIDED, MOUNTING AND WHITEPHILIPS MCPHILBEN VEARROWS AS SHOWN ON PLANSE2RED LED120THERMOPLASTIC EXIT SIGN, NICAD BATTERY, DOUBLE SIDED, MOUNTING AND WHITEPHILIPS MCPHILBEN VEARROWS AS SHOWN ON PLANSX1RED LED120THERMOPLASTIC EXIT SIGN, NICAD BATTERY, SINGLE SIDED, MOUNTING AND WHITEPHILIPS MCPHILBEN VEARROWSAS SHOWN ON PLANSX2RED LED120THERMOPLASTIC EXIT SIGN, NICAD BATTERY, DOUBLE SIDED, MOUNTING AND WHITEPHILIPS MCPHILBEN VEARROWS AS SHOWN ON PLANSX3RED LED120THERMOPLASTIC EXIT SIGN, NICAD BATTERY, SINGLE SIDED, MOUNTING AND WHITEPHILIPS MCPHILBEN VEARROWS AS SHOWN ON PLANS, DAMP LOCATION RATEDX4RED LED120THERMOPLASTIC EXIT SIGN, NICAD BATTERY, DOUBLE SIDED, MOUNTING AND WHITEPHILIPS MCPHILBEN VEARROWS AS SHOWN ON PLANS, DAMP LOCATION RATEDNOTES: PHILIPS GARDCO MA22-1-1. UNITEDLIGHTING STANDARDS RSP-18-11 POLE11111. PROVIDE SCREW-IN COMPACT FLUORESCENT LAMP777308.23.2011REVISION
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923KEY PLANELECTRICAL SCHEDULESKSOE6.142JANUARY 9, 201201.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 131REMARKS:1. PROVIDE LOAD CENTER TYPE CONSTRUCTION.208.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSPANELBOARD SCHEDULE - BUILDING 901/4.4PANELBOARD RATINGSMAINSUB-FEEDBRANCH BREAKERSREMARKBREAKERRATINGSRATINGSBREAKERSPANEL LOCATIONVOLTSPHMAINPANELFRAMETRIPINTER'PTLUGSBKR.1 POLE2 POLE3 POLESIZE POLESPACESNO.INTERUPTDESIG-BUSMOUNTINGSIZEAMPSRMS SYMTRIPSIZE ANDSIZE ANDSIZE ANDQUANTITYOFRMS SYM.NATIONAMPSAMPSAMPSQUANTITYQUANTITYQUANTITYSPARESPOLESAMPSH901MFURNACE ROOM 1052083100SURFACE15A-815A-320A-1P-35421800020A-920A-120A-3P-1H901RFURNACE ROOM 1052083400SURFACE15A-7, 20A-1030A-1, 40A-160A-3P20A-1P-411422500020A-3P-1T44ABUILDING 4.4, LEVEL A2081125RECESSED15A-4, 20A-520A-232010000130A-1, 40A-1T44BBUILDING 4.4, LEVEL B2081125RECESSED15A-4, 20A-520A-232010000130A-1, 40A-1T44CBUILDING 4.4, LEVEL C2081125RECESSED15A-4, 20A-420A-242010000130A-1, 40A-1T901ABUILDING 901, LEVEL A2081100RECESSED15A-6, 20A-520A-212010000130A-1, 40A-1T901BBUILDING 901, LEVEL B2081100RECESSED15A-2, 20A-540A-11120100001T901DBUILDING 901, LEVEL D2081100RECESSED15A-5, 20A-515A-1, 20A-1103010000130A-2, 40A-1BUILDING 4.4 - ELECTRIC EQUIPMENT AND CONTROL SCHEDULEF-1---INDICATES EQUIPMENT DESIGNATION FROM SCHEDULE101---INDICATES ROOM LOCATION FOR CONTROL DEVICEAU---INDICATES CONTROL DEVICE LOCATED AT UNITX---INDICATES FIRE ALARM FAN SHUTDOWN IS REQUIREDEQUIPMENTITEMS FURNISHED AND INSTALLED BY ELECTRICAL DIVISIONITEMS FURNISHED BY OTHER DIVISIONS AND INSTALLED BY ELECTRICAL DIVISIONEQUIP.NAMEROOMHPKWVPHPANEL ORCIRCUITPOWER WIRINGPOWER WIRINGGNDREF.FUSEDNONFIREMANUALCOMB.2-SPEEDVARIABLEISOLATIONSINGLEPKG.DESIGNLOCATIONCONTROLBREAKERFROM PANEL TOFROM CONTROLWIRENOTESDISC.FUSEDALARMMOTORMAGNETICCOMB.SPEEDTRANS. (IT)POINTCTRL.CENTERCONTROL UNITUNIT TO SWITCHDISC.FANSTARTERSTARTERMAGNETICDRIVESOR LINECONNECTUNITEQUIPMENTSWITCHSHUTDOWNSTARTERREACTOR (LR)AC-4.4AIR COMPRESSORFURNACE ROOM 10512003H901M15A-3P3#12+G NM3#12+G NM#12105ACCU-1AIR COOLED COND UNIT 1EXTERIOR - EAST5.51T901D30A-2P2#10, 1/2"C2#10, 1/2"C#10AUACCU-2AIR COOLED COND UNIT 2EXTERIOR - EAST21T901A20A-2P2#12, 1/2"C2#12, 1/2"C#12AUAC44APACKAGED AC UNIT WITH HEATBLDG 4.42.22001T44A20A-2P2#12+G NM-#12AUAC44BPACKAGED AC UNIT WITH HEATBLDG 4.42.22001T44B20A-2P2#12+G NM-#12AUAC44CPACKAGED AC UNIT WITH HEATBLDG 4.42.22001T44C20A-2P2#12+G NM-#12AUB44-1BOILERFURNACE ROOM 1050.21151H901M15A-1P2#12+G NM2#12+G NM#12105CUH-A1CABINET UNIT HEATER A1BLDG 4.4 - LEVEL A0.11151H901M15A-1P2#12+G NM-#12AUCUH-B1CABINET UNIT HEATER B1HALL 2070.11151H901M15A-1P2#12+G NM-#12AUFC-A1FAN COIL UNIT A1DINING 1070.31151T901A15A-1P2#12+G NM-#12AUFC-D1FAN COIL UNIT D1DINING 4030.32001T901D15A-2P2#12+G NM-#12AUF-44EXHAUST FANFURNACE ROOM 1051/201151H901M15A-1P2#12+G NM2#12+G NM#122105F-TFAN - TENANT BATHROOMSVARIES0.11151VARIES20A-1P2#12 + G NM2#12 + G NM#121P44-1PUMP - HEATINGFURNACE ROOM 10512003H901M15A-3P3#12+G NM3#12, 1/2"C#12105 (VSD-1)P44-2PUMP - HEATINGFURNACE ROOM 10512003H901M15A-3P3#12+G NM3#12, 1/2"C#12105 (VSD-2)P44-3PUMP - BOILERFURNACE ROOM 1052/51151H901M20A-1P2#12+G NM2#12, 1/2"C#12105P44-4PUMP - BOILERFURNACE ROOM 1052/51151H901M20A-1P2#12+G NM2#12, 1/2"C#12105PP-901DOMESTIC CIRC PUMPFURNACE ROOM 1051/121151H901M15A-1P2#12+G NM2#12+G NM#12105WH-901.1WATER HEATER 1FURNACE ROOM 1050.11151H901M15A-1P2#12+G NM2#12+G NM#12105WH-901.2WATER HEATER 2FURNACE ROOM 1050.11151H901M15A-1P2#12+G NM2#12+G NM#12105NOTES:1. TENANT BATHROOM EXHAUST FANS SHALL BE CIRCUITED TOGETHER WITH THE ASSOCIATED BATHROOM LIGHTING CIRCUIT. INSTALL FAN CONTROLLER FURNISHED BY MECHANICAL CONTRACTOR. COORDINATE JUNCTION BOX SIZE WITH MECHANICAL CONTRACTOR.2 INSTALL ADJUSTABLE SPEED CONTROLLER FURNISHED BY MECHANICAL CONTRACTOR.FD1FAN - DRYER BOOSTERAPARTMENT 0.11151T44A15A-1P2#12+G NM#12AUFD2FAN - DRYER BOOSTERAPARTMENT 0.11151T901A15A-1P2#12+G NM#12AUFD3FAN - DRYER BOOSTERAPARTMENT 0.11151T44B15A-1P2#12+G NM#12AUFD4FAN - DRYER BOOSTERAPARTMENT 0.11151T44C15A-1P2#12+G NM#12AUFD5FAN - DRYER BOOSTERAPARTMENT 0.11151T901D15A-1P2#12+G NM#12AU200200UH1UNIT HEATERFURNACE ROOM 1051151H901M15A-1P2#12+G NM2#12+G NM#121/3105222
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSNO SCALEBUILDING 4.3 - POWER ONE-LINE DIAGRAM1ELECTRICAL ONE-LINE DIAGRAMKSOE7.07PAD-MOUNT TRANSFORMER T5BY UTILITY COMPANY.TRANSFORMER PAD BYELECTRICAL CONTRACTOR.REFER TO PAD-MOUNTTRANSFORMER DETAILS.REFER TO CIVILDRAWINGS FOR PRIMARYSERVICE REQUIREMENTS.BUILDING STEELINCOMING WATER MAINGROUND BUSCONCRETE ENCASEDELECTRODETO ELECTRODE GROUNDGRID. SEE ELECTRODEGROUND GRID DETAIL.50A 3PMC43 - 600A, 208/120V, 3 PHASE, 4 WIRE, 35K AICGENERAL NOTES:A.PHASE BALANCE TENANT BREAKERS SO PHASES AB, BC, ANDCA ARE EQUALLY LOADED.B.VERIFY EXACT METER SOCKET TYPE WITH UTILITY BEFOREPROCURING EQUIPMENT.C.FEEDERS ARE COPPER CONDUCTORS UNLESS NOTEDOTHERWISE. REFER TO SPECIFICATIONS FOR PERMITTEDSUBSTITUTIONS WITH ALUMINUM CONDUCTORS.D.FEEDER NOTED WITH "AL" INDICATE ALUMINUM CONDUCTORS.3P100A3P3P2P125A2P125A2P125A2P125A2P125A2P125A2P125A2P125A2P125A2P125A2P125A2P125A2P311.21.2011CONSTRUCTION CHANGE DIRECTIVE 5EXTEND DUCTBANK FROM TRANSFORMER TOA POINT WHERE DUCTBANK MAY BEEXTENDED TO BUILDING 3 (METER CENTERM311) IN A FUTURE CONSTRUCTION PHASE.EXTEND DUCTBANK FROM TRANSFORMER TOA POINT WHERE DUCTBANK MAY BEEXTENDED TO BUILDING 3 (METER CENTERM312) IN A FUTURE CONSTRUCTION PHASE.NO SCALEBUILDING 901/4.4 - POWER ONE-LINE DIAGRAM2125A2P100A2P125A2PGROUND BUS424300A3PMC901 - 600A, 208/120V, 3 PHASE, 4 WIRE, 65K AIC125A2P444-3P-3PSPARESPAREREFER TO SERVICE ENTRANCE GROUNDINGELECTRODE SYSTEM DETAIL ON DRAWINGE5.02401.09.2012SEQUENCE 1 - CONSTRUCTION CHANGEDIRECTIVE 13100A 3P125A2P125A2PKEYED NOTES:EXTERIOR FEEDERS SHALL BE SINGLE CONDUCTORS INCONDUIT FROM METER CENTER TO INTERIOR OF BUILDING. MCCABLE IS FOR CONCEALED INTERIOR USE ONLY EXCEPT INUNFINISHED SPACES WHERE EXPOSED MC CABLE ISACCEPTABLE.1111508.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSFEEDER SCHEDULECIRCUITCONDUCTOR AND CONDUIT NOTESDESIGNATIONSIZE AND QUANTITY14#2, #8G, 1-1/4"C23#1/0, #4G, MC AL33#2/0, #4G, MC AL43#3/0, #4G, MC AL53#4/0, #2G, MC AL64#8, #10G, 3/4"C72 SETS (4#500, 4"C)84#1/0, #6G, 2"C94 SETS (4#350, 3"C)102 SETS (4"C WITH PULL ROPE)114#500, #2G, 4"C124 #3/0, #6G, 2"C136 SETS (4"C WITH PULL ROPE)143 SETS (4#350, 4"C)153#350, #4G, MC AL163#750, #1/0G, MC AL1718192055
DRAWING NO.:DRAWN BY:DATE:SHEET TITLE:PROJECT TITLE:COLLEGETOWNTERRACE APARTMENTSITHACA, NYNOVARR MACKESEYDEVELOPMENTPROFESSIONAL LICENSENUMBER:NEW YORK STATE SEAL:a r c h i t e c t sikon.5PROJECT NO.:P58.00VERSIONSNO.DATEDESCRIPTIONCIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICALENGINEER:LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:12923JULY 1, 2011107.01.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSKEY PLAN208.10.2011SEQUENCE 1 - CONSTRUCTION DOCUMENTSELECTRICAL DIAGRAMSKSOE7.08NO SCALETYPICAL TIME WARNER SERVICE DISTRIBUTION DIAGRAM3311.21.2011CONSTRUCTION CHANGE DIRECTIVE 5402.24.2012CONSTRUCTION CHANGE DIRECTIVE 19506.18.2012CCD #44608.17.2012SEQUENCE 2C - CONSTRUCTION DOCUMENTSCATV SERVICEENTRANCE CABLE BYSERVICE PROVIDERTVTIMEWARNERBACKBOARDCATV SERVICEENTRANCEEQUIPMENT BYTIME WARNERTELECOMMUNICATIONS BACKBOARDGENERAL NOTES:A.PROVIDE GROUNDING PER SPECIFICATIONS AND DETAILS.B.COORDINATE ENTIRE INSTALLATION WITH TIME WARNER.C.PROVIDE ALL CABLING FROM END USER OUTLET TO TIME WARNER SERVICEEQUIPMENT. PROVIDE ALL TERMINATIONS.REFER TO FLOOR PLANSFOR QUANTITY/LOCATIONS4-PR CAT6 UTPRG6U COAX6