1 07.01.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
KEY PLAN
2 08.10.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
ADDENDUM - 1
ELECTRICAL DIAGRAMS
KSO
E7.08
GENERAL NOTES:
A. REFER TO DATA RACK DIAGRAMS FOR RACK REQUIREMENTS.
NO SCALE
TYPICAL DATA RACK DIAGRAMS1
TYPICAL DATA RACK LAYOUT
BLANK FILLER
FIBER PATCH PANELS
BLANK FILLER
48-PORT PATCH PANEL
24-PORT PATCH PANEL
COMMUNICATIONS ROOM
GENERAL NOTES:
A. PROVIDE 10% SPARE RACK CAPACITY BASED ON THE AMOUNT OF RACK CAPACITY
UTILIZED BY THE PATCH PANELS PROVIDED.
B. PROVIDE A MINIMUM SPARE CAPACITY OF 10 PERCENT IN THE INSTALLED PATCH
PANELS.
C. PROVIDE QUANTITY OF PATCH PANELS TO ACCOMMODATE ALL BUILDING OUTLETS.
D. PROVIDE CABLE MANAGEMENT AND GROUNDING.
E. COORDINATE WORK WITH OWNERS DATA SYSTEM SERVICE PROVIDER (LIGHTLINK
DATA SYSTEMS) PRIOR TO COMMENCEMENT OF WORK.
TO GROUNDING
ELECTRODE SYSTEM
GROUND BAR
20' SERVICE
LOOP
FIBER OPTIC
CABLE
MULTIPLE CAT 5E CABLES
TO DATA OUTLETS
REFER TO FLOOR PLANS FOR
QUANTITY/LOCATIONS OF DATA
OUTLETS
MINIMUM #6 CU
GROUND
WALL MOUNTED
DATA RACK
120V TVSS DUPLEX
RECEPTACLE ON
DEDICATED CIRCUIT,
TYPICAL
WALL MOUNTED, 48"
HIGH AND 19" WIDE
EQUIPMENT RACK
FIBER OPTIC AND CAT5E
PATCH PANELS, TYPICAL
1
KEYED NOTES:
CAT5E TO RJ-45 OUTLET, TYPICAL. PROVIDE ONE 4-PR CAT5E TO
EACH DATA SYSTEM OUTLET. REFER TO PLANS FOR QUANTITY
AND LOCATIONS.
REFER TO DATA SYSTEM DIAGRAMS FOR GENERAL LAYOUT
REQUIREMENTS.
DUCTBANK AND HAND HOLES SHOWN FOR REFERENCE AND NOT
USED FOR ACTIVE DATA SERVICE.
2
3
NO SCALE
DATA SYSTEM CABLING DIAGRAM2
CPB-5
HH-1
HH-6
1
1
1
111
CPB-1
HH-5
HH-7HH-6
CPB-2CPB-3
CPB-4
HH-2
222
2
2
2
BUILDING 2.0
MDF-21
BUILDING 1
MDF-1
BUILDING 4.2
MDF-42
BUILDING 4.1
MDF-41
BUILDING 2.4
MDF-24
BUILDING 4.3
MDF-43
CASA ROMA
MAIN IT ROOM
HH-3
BLANK FILLER
KEYED NOTES:
RACK LAYOUT IS GENERIC AND INTENDED TO SHOW GENERAL POSITIONING OF
RACK MOUNTED EQUIPMENT. PROVIDE QUANTITY AND CAPACITY OF FIBER OPTIC
AND CAT5E PATCH PANELS REQUIRED FOR EACH BUILDINGS NEEDS FOR A
COMPLETE SYSTEM.
1 RACK UNIT EMPTY SPACE FOR OWNERS SWITCHING EQUIPMENT.
TO FLOOR ABOVE, IF
PRESENT
NO SCALE
TYPICAL TIME WARNER SERVICE DISTRIBUTION DIAGRAM
CATV SERVICE
ENTRANCE CABLE BY
SERVICE PROVIDER
TV
TIME
WARNER
BACKBOARD
CATV SERVICE
ENTRANCE
EQUIPMENT BY
TIME WARNER
TELECOMMUNICATIONS BACKBOARD
RG6 COAX
GENERAL NOTES:
A. PROVIDE GROUNDING PER SPECIFICATIONS AND DETAILS.
B. COORDINATE ENTIRE INSTALLATION WITH TIME WARNER.
C. PROVIDE ALL CABLING FROM END USER OUTLET TO TIME WARNER SERVICE
EQUIPMENT. PROVIDE ALL TERMINATIONS AT END USER OUTLET.
REFER TO FLOOR PLANS
FOR QUANTITY/LOCATIONS
3
2
2
2 RACK UNIT WIRE
MANAGEMENT
EMPTY SPACE
48-PORT PATCH PANEL
BLANK FILLER
2 RACK UNIT WIRE
MANAGEMENT
EMPTY SPACE
2 RACK UNIT WIRE
MANAGEMENT
EMPTY SPACE
2
2
2
QUARRY ARMS
MAIN IT ROOM
DATA CABLE SCHEDULE NOTES:
1. 4 SETS (12 ST MM CABLE) TO SERVE BUILDING 4 GROUP.
PROVIDE EACH BUILDING WITH 1 SET.
2. 6 SETS (12 ST MM CABLE) TO SERVE BUILDINGS AS FOLLOWS:
* 4 SETS TO BUILDING 4 GROUP PER CABLE SCHEDULE NOTE 1.
* 1 SET TO SERVE CASA ROMA.
* 1 SET TO SERVE QUARRY ARMS.
3. 2 SETS (12 ST MM CABLE) TO SERVE BUILDINGS AS FOLLOWS:
* 1 SET TO SERVE CASA ROMA.
* 1 SET TO SERVE QUARRY ARMS.
4. ROUTE 1 SET (12 ST MM CABLE) FROM CASA ROMA TO QUARRY
ARMS VIA AN EXISTING DUCT BETWEEN BUILDING
COMMUNICATION ROOMS.
DATA CABLE SCHEDULE
CIRCUIT
DESIGNATION CABLE TYPE NOTES
CAT5E 4-PR UTP
12 ST MM FIBER OPTIC CABLE
4 SETS (12 ST MM FIRBER OPTIC CABLE) 1
6 SETS (12 ST MM FIRBER OPTIC CABLE) 2
2 SETS (12 ST MM FIRBER OPTIC CABLE) 3
12 ST MM FIBER OPTIC CABLE 4
2
2
2
2
2
2
2
2
2