HomeMy WebLinkAbout10-E7-01DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
PROJECT TITLE:
COLLEGETOWN
TERRACE APARTMENTS
ITHACA, NY
NOVARR MACKESEY
DEVELOPMENTPROFESSIONAL LICENSE
NUMBER:
NEW YORK STATE SEAL:
a r c h i t e c t s
ikon.5 PROJECT NO.:P58.00
VERSIONS
NO. DATE DESCRIPTION
CIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL
ENGINEER:
LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:
12923
JULY 1, 2011
1 07.01.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
KEY PLAN
2 08.10.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
ADDENDUM - 1
NO SCALE
BUILDING 2.4 - POWER ONE-LINE DIAGRAM2
ELECTRICAL ONE-LINE DIAGRAM
KSO
E7.01
PAD-MOUNT TRANSFORMER
BY UTILITY COMPANY.
TRANSFORMER PAD BY
ELECTRICAL CONTRACTOR.
REFER TO PAD-MOUNT
TRANSFORMER DETAILS.
REFER TO CIVIL
DRAWINGS FOR PRIMARY
SERVICE REQUIREMENTS.
BUILDING STEEL
INCOMING WATER MAIN
GROUND BUS
CONCRETE ENCASED
ELECTRODE
#4/0 COPPER PER NEC
TABLE 250.66
TO ELECTRODE GROUND
GRID. SEE ELECTRODE
GROUND GRID DETAIL.
NO SCALE
BUILDING 1 - POWER ONE-LINE DIAGRAM1
PAD-MOUNT TRANSFORMER
BY UTILITY COMPANY.
TRANSFORMER PAD BY
ELECTRICAL CONTRACTOR.
REFER TO PAD-MOUNT
TRANSFORMER DETAILS.
REFER TO CIVIL
DRAWINGS FOR PRIMARY
SERVICE REQUIREMENTS.
BUILDING STEEL
INCOMING WATER MAIN
GROUND BUS
CONCRETE ENCASED
ELECTRODE
#4/0 COPPER PER NEC
TABLE 250.66
TO ELECTRODE GROUND
GRID. SEE ELECTRODE
GROUND GRID DETAIL.
FEEDER SCHEDULE
CIRCUIT CONDUCTOR AND CONDUIT NOTES
DESIGNATION SIZE AND QUANTITY
1 4#2, #8G, 1-1/4"C
2 3#1/0, #4G, MC AL
3 3#2/0, #4G, MC AL
4 3#3/0, #4G, MC AL
5 3#4/0, #2G, MC AL
6 4#8, #10G, 3/4"C
7 2 SETS (4#500, 4"C)
8 4#1/0, #6G, 2"C
9 4 SETS (4#350, 3"C)
10 2 SETS (4"C WITH PULL ROPE)
11 4#500, #2G, 4"C
12 4 #3/0, #6G, 2"C
13
14
15
16
17
18
19
20
50A
3P
50A
3P
50A
3P
MC10 - 800A, 208/120V, 3 PHASE, 4 WIRE, 18K AIC
MC24 - 600A, 208/120V, 3 PHASE, 4 WIRE, 25K AIC
GENERAL NOTES:
A. PHASE BALANCE TENANT BREAKERS SO PHASES AB, BC, AND
CA ARE EQUALLY LOADED.
B. VERIFY EXACT METER SOCKET TYPE WITH UTILITY BEFORE
PROCURING EQUIPMENT.
C. FEEDERS ARE COPPER CONDUCTORS UNLESS NOTED
OTHERWISE. REFER TO SPECIFICATIONS FOR PERMITTED
SUBSTITUTIONS WITH ALUMINUM CONDUCTORS.
D. FEEDER NOTED WITH "AL" INDICATE ALUMINUM CONDUCTORS.
2
100A
2P
100A
2P
100A
2P
125A
2P
125A
2P
125A
2P
125A
2P
100A
2P
100A
2P
100A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
100A
2P
100A
2P
100A
2P
150A
2P
3P
3P
3P
3P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
125A
2P
2
2
2
2
150A
2P