HomeMy WebLinkAbout10-E5-02DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
PROJECT TITLE:
COLLEGETOWN
TERRACE APARTMENTS
ITHACA, NY
NOVARR MACKESEY
DEVELOPMENTPROFESSIONAL LICENSE
NUMBER:
NEW YORK STATE SEAL:
a r c h i t e c t s
ikon.5 PROJECT NO.:P58.00
VERSIONS
NO. DATE DESCRIPTION
CIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL
ENGINEER:
LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:
12923
JULY 1, 2011
1 07.01.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
KEY PLAN
2 08.10.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
ADDENDUM - 1
ELECTRICAL DETAILS
KSO
E5.02
GENERAL NOTES:
A. REPAIR ALL SETTLEMENT.
B. MINIMUM TOP SOIL - 6".
C. PROVIDE DIRECT BURIED INSTALLATION FOR COMMUNICATION DUCTBANKS AND POWER BRANCH CIRCUITS.
D. WHERE ADDITIONAL CABLES ARE CALLED FOR, INCREASE TRENCH WIDTH AND INSTALL CABLES WITH 3"
MINIMUM SPACING.
E. EXCAVATED MATERIAL MEETING SPECIFICATIONS MAY BE USED FOR BACKFILL IN TRENCHES. IN THE EVENT
EXCAVATED MATERIAL DOES NOT MEET SPECIFICATIONS, PROVIDE GRANULAR BACKFILL AS SPECIFIED FOR
BACKFILL. REMOVE UNSUITABLE MATERIAL FROM SITE.
30" MINIMUM
3" MINIMUM SPACING
FINISH GRADE
3" SAND BED
AROUND CONDUIT
COMPACT BACKFILL TO
MATCH SURROUNDING
CONDITIONS
NO ROCKS, DEBRIS IN
BACKFILL
SCHEDULE 80 PVC
CONDUIT UNLESS
OTHERWISE SHOWN
SKID RESISTANT
SURFACE
HANDHOLE
TYPE
12" CRUSHED STONE
BELOW HANDHOLE.
EXTEND 6" (MIN.)
AROUND OUTSIDE EDGE
ON HANDHOLE
HHL
SLOPE FINISH GRADE
AWAY FROM COVER.
E
18"
D
DIMENSION
CB
12"10"20"
A
12"
DIMENSION SCHEDULE
B
C
A
E
D
STAINLESS STEEL HEX
HEAD BOLT WITH
WASHER AND GROMMET
PULL SLOT
CUSTOM COVER
DESIGNATION: POWER,
COMMUNICATIONS, CATV,
ETC.
GENERAL NOTE:
A. DO NOT LOCATE IN VEHICULAR TRAFFIC OR SIDEWALK AREAS.
CAST POLYMER
CONCRETE COVER
CAST POLYMER
CONCRETE BOX
CAST POLYMER
CONCRETE HANDHOLE
SERVICE
ENTRANCE
EQUIPMENT
STRUCTURAL
STEEL
#4/0 CU
SERVICE ENTRANCE
GROUND BUS
#4/0 CU
CONCRETE
ENCASED
ELECTRODE IN
FLOOR SLAB
TYPICAL 3/4"x10'
COPPERCLAD
GROUND ROD
GROUND
GRID
TYPICAL - EACH
BUILDING
WATER SERVICE
EXOTHERMIC
WELD
LISTED PIPE CLAMP
(WITHIN 5' OF POINT OF
ENTRANCE INTO
BUILDING)
LISTED CLAMP
TYPICAL - TWO
HOLE
COMPRESSION
FITTING BOLTED
TO BUS
TYPICAL -
EXOTHERMIC WELD
GENERAL NOTES:
A. TYPICAL FOR ALL SERVICE ENTRANCE EQUIPMENT.
B. PROVIDE SCHEDULE 80 PVC SLEEVES FOR GROUND CONDUCTORS.
GROUND CLAMP HUB
AND CABLE CLAMP.
GROUNDING METER JUMPER
AROUND WATER METER AND
INSULATING JOINTS.
#2 CU
#4/0 CU
NO SCALE
HANDHOLE DETAIL1
NO SCALE
ELECTRODE SYSTEM DETAIL
SERVICE ENTRANCE GROUNDING
3
NO SACLE
MULTIPLE CONDUIT DETAIL
TYPICAL DIRECT BURIED IN SANDBED
2
PAVING OR TOPSOIL TO
MATCH SITE CONDITIONS
MARKING TAPE
INSULATED
MOUNTING
BRACKET
1/4" COPPER GROUND BAR
NO SCALE
GROUND BAR DETAIL
GENERAL NOTES:
A. PROVIDE #4 GREEN INSULATED GROUND WIRE TO MAIN SERVICE
GROUND.
B. PROVIDE GROUND BAR IN EACH COMMUNICATION ROOM/CLOSET.
REFER TO FLOOR PLANS FOR LOCATIONS AND QUANTITIES.
C. PROVIDE LONG BARREL, INDENT TYPE LUGS FOR GROUND CONNECTION.
4
#4 CU
COMM ROOM
GROUND BAR
2
HH 34"26"23"38"40"
NOTE
1
NOTES:
1. LIGHTING HANDHOLES
HHL ARE NOT SHOWN ON
SITE PLANS.
2
FIRE ALARM RISER GENERAL NOTES:
A. THE FIRE ALARM RISER DIAGRAM IS DIAGRAMMATIC ONLY AND IS NOT
INTENDED TO SHOW EACH DEVICE OR EXACT CONNECTIONS. OBTAIN
WIRING DIAGRAM FROM SYSTEM VENDOR FOR ALL DEVICES AND
COMPONENTS REQUIRED TO MEET SPECIFICATIONS. THE ACTUAL
FIELD INSTALLATION WILL REQUIRE PULL BOXES, OFFSETS, OUTLET
BOXES & OTHER RELATED ELECTRIC WORK TO PROVIDE THE PROPER
INSTALLATION.
B. ALL CONDUCTOR WIRING SHALL BE PERMANENTLY IDENTIFIED AND
LABELED IN ACCORDANCE WITH THE SPECIFICATIONS.
C. SLC CIRCUITS: #18 TP (SHIELDED) FPL CABLE
STROBE CIRCUITS (NAC): 2-#12 FPL CABLE
24VDC AUX. POWER: 2-#12 FPL CABLE
D. NOT ALL FIRE ALARM DEVICES ARE SHOWN OR INDICATED. DEVICES
ARE REPRESENTATIVE ONLY. REFER TO APPLICABLE FLOOR PLANS
FOR DEVICE LOCATIONS, TYPES AND QUANTITIES.
E. MAIN FIRE ALARM CIRCUIT WILL RUN IN HALLWAY AND IS PERMISSIBLE
TO T-TAP BRANCH CIRCUITS TO EACH APARTMENT FROM MAIN CIRCUIT.
F. PROVIDE NAC PANELS AND TERMINAL EQUIPMENT CABINETS AS
REQUIRED.
M. PROVIDE FIRE ALARM SYSTEM CONNECTION TO ELEVATOR SHUNT TRIP
DISCONNECT SWITCHES.
FACP
120V
20A-1P
1
FPHP TS
2
KEYED NOTES:
PROVIDE TWO 4-PR CAT5E TELEPHONE LINES FROM BUILDING
TELEPHONE SYSTEM BACKBOARD TO FIRE ALARM CONTROL PANEL.
PROVIDE SUPERVISORY CONNECTION TO FIRE PROTECTION HEAT
TRACE CONTROL PANEL.
TERMINAL EQUIPMENT CABINET.
ADDRESSABLE MONITOR MODULE.
1
2
24VDC AUX POWER
24VDC AUX POWER
24VDC AUX POWER
TEC
120V
20A-1P
FPHP TS
2
24VDC AUX POWER
24VDC AUX POWER
24VDC AUX POWER
TEC
120V
20A-1P
FPHP TS
2
24VDC AUX POWER
24VDC AUX POWER
24VDC AUX POWER
FACP
120V
20A-1P
1
FPHP TS
2
24VDC AUX POWER
24VDC AUX POWER
24VDC AUX POWER
NO SCALE
BUILDINGS 1, 2.4, 4.1, 4.2 & 4.3
FIRE ALARM SYSTEM RISER DIAGRAM
6
NO SCALE
BUILDING 2.0, 2.1, 2.2 & 2.3
FIRE ALARM SYSTEM RISER DIAGRAM
5
3
4
33
4
TYPICAL
4
TYPICAL
4
TYPICAL