HomeMy WebLinkAbout10-E2-21BOPEN TO
BELOW
DN
DN
PANEL
T21E1
PANEL
T21E2
PANEL
T21E3
E1
REFER TO TYPICAL
APARTMENT 21.1
REFER TO TYPICAL
APARTMENT 21.2REFER TO TYPICAL
APARTMENT 21.3
REFER TO TYPICAL
APARTMENT 21.4
PANEL
T21E4
TYPE B1
TYPE D
TYPE B
TYPE B
E1
7
7
K
2
2
2
2 2
2
2
2
2
2
2
3
3
3
2
2
2
1
2
2
2
2
2
1/4"=1'0"
BUILDING 2.1 - LEVEL F2 1/4"=1'0"
BUILDING 2.1 - LEVEL E1
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
PROJECT TITLE:
COLLEGETOWN
TERRACE APARTMENTS
ITHACA, NY
NOVARR MACKESEY
DEVELOPMENTPROFESSIONAL LICENSE
NUMBER:
NEW YORK STATE SEAL:
a r c h i t e c t s
ikon.5 PROJECT NO.:P58.00
VERSIONS
NO. DATE DESCRIPTION
CIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL
ENGINEER:
LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:
12923
NORTH
PROJECTJULY 1, 2011
1 07.01.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
KEY PLAN
2 08.10.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
ADDENDUM - 1
GENERAL NOTES:
A. CIRCUIT EXIT SIGNS ON LEVELS C, D, AND E TOGETHER WITH #10
AWG CONDUCTORS FROM A 20A-1P CIRCUIT BREAKER IN PANEL
H21. PROVIDE CIRCUIT BREAKER HANDLE LOCK.
B. CIRCUIT DESIGNATION ON THIS PLAN REFER TO PANEL H21,
UNLESS NOTED OTHERWISE.
BUILDING 2.1 FLOOR PLAN - LEVEL E, LEVEL F
KSO
E2.21B
KEYED NOTES:
PROVIDE SMOKE DETECTOR INSIDE STAIRWAY.
PROVIDE PHOTOCELL ON ROOF FOR CONTROL OF BUILDING
MOUNTED EXTERIOR LIGHTING AND POLE MOUNTED SITE
LIGHTING. CIRCUIT THROUGH TIME CLOCK AND CONTACTORS
LOCATED IN A-LEVEL MEP ROOM.
THE CORRIDOR IS CONSIDERED PART OF THE STAIRWAY
ENCLOSURE. ONLY DEVICES AND ASSOCIATED CONDUIT AND
CABLING SERVING THE STAIRWAY ENCLOSURE ARE PERMITTED
TO BE IN THE STAIRWAY. NON-STAIRWAY CONDUITS AND CABLING
SHALL CROSS THE STAIRWAY CORRIDOR IN RATED ENCLOSURES
INDICATED ON THE ARCHITECTURAL DOCUMENTS.
1
2
3
2