HomeMy WebLinkAbout09-M4-40UP
UPUP
PIPING ABOVE SUSPENDED
CEILING (TYP.)
114"
112"
114" HWS & HWR UP
114"
114" HWS & HWR UP
114" HWS & HWR UP
114" HWS & HWR UP
2"
114"
114" HWS & HWR UP
114"
114"
112"
114" HWS & HWR UP
PIPING ABOVE SUSPENDED
CEILING (TYP.)
2"
114" HWS & HWR UP
114" HWS & HWR UP
REFER TO DRAWING
M4-40/8 FOR WORK
IN THIS AREA
REFER TO DRAWING
M4-40/5 FOR WORK
IN THIS AREA
REFER TO DRAWING
M4-40/2 FOR WORK
IN THIS AREA
1" HWS & HWR UP
112"
__"
1" HWS & HWR UP
2" HWS
& HWR
114"
114" HWS & HWR UP
114"
PIPING ABOVE SUSPENDED
CEILING (TYP.)
2"
114" HWS & HWR UP
114" HWS & HWR UP
114" HWS & HWR UP
BOILER
ROOMBIKE
STORAGE
BOILER
ROOM
BOILER
ROOM
IT
CLOSET
IT
CLOSET
IT CLOSET
BIKE
STORAGE
BIKE
STORAGE
1-1/2"1-1/2"
2" HWS
& HWR
2" HWS
& HWR
1-1/2"
4"Ø BOILER INTAKE &
4"Ø BOILER EXHAUST
6"Ø CONCENTRIC TERMINATION
KIT
4"Ø BOILER INTAKE &
4"Ø BOILER EXHAUST
6"Ø CONCENTRIC TERMINATION
KIT
4"Ø BOILER INTAKE &
4"Ø BOILER EXHAUST
6"Ø CONCENTRIC TERMINATION
KIT
114"
112"
TS1TS2
TS1TS2TS1TS2
2
22
2
2
1" HWS & HWR UP
2
AS
2"
B-4.1-1
HWH
R 8
4
EXT
5
F-4.0-1
AAD
16"x16"
LOUVER
13x12
GRILLE
7 3
2
3
7
7
1
5
6
VSD 4.1-1 &
VSD 4.1-2
FD
P 4.1-3
P-4.1-4 16"x16"
LOUVERFD
P-4.1-1
P-4.1-2
7
16x16
FILTER HOUSING
& FILTER
HWHB-4.1-1
FP
SERVICE
ACID
NUETRALIZING/TRAP
P 4.1-3
P-4.1-4
2"
2"
2"
2"
AS-12"
P-4.1-1P-4.1-2
EXT
GLYCOL
FULL
SIZE
2"2"
3/4"
16 x 16 TRANSFER
DUCT WITH AND FILTER RACK
3/4"
VSD 4.1-1
VSD 4.1-2
2"
2"
AS-12"
P-4.2-1P-4.2-2
EXT
GLYCOL
FULL
SIZE
2"2"
3/4"
16 x 16 TRANSFER
DUCT WITH AD & FILTER RACK
3/4"
VSD 4.2-1
VSD 4.2-2
HWHB-4.2-1
FP
SERVICE
ACID
NUETRALIZING/TRAP
P 4.2-3
P-4.2-4
2"
2"
AS
2"
B-4.1-1
HWH
R
7
8
4
EXT
5
F-4.0-2
AAD
16"x16"
LOUVER
13x12
GRILLE
73
2
3
7
7
1
5
6
VSD 4.2-1 &
VSD 4.2-2
FD
P 4.2-3
P-4.2-416"x16"
LOUVER FDP-4.2-1
P-4.2-2
16x16
FILTER HOUSING &
FILTER
AS
2"
B-4.3-1
HWH
R
7
8
4
EXT
5
F-4.0-3
AAD
16"x16"
LOUVER
13x12
GRILLE
73
2
3
7
7
1
5
6
VSD 4.3-1
VSD 4.3-2
FD
P 4.3-3
P-4.3-416"x16"
LOUVER FDP-4.3-1
P-4.3-2
16x16
FILTER HOUSING
& FILTER
2"
2"
AS-1"
P-4.3-1P-4.3-2
EXT
GLYCOL
FULL
SIZE
2"2"
3/4"
16 x 16 TRANSFER
DUCT WITH AD & FILTER RACK
3/4"
VSD 4.3-1
VSD 4.3-2
HWHB-4.3-1
FP
SERVICE
ACID
P 4.3-3
P-4.3-4
2"
2"
1/8"=1'0"
BUILDING 4.0 - LEVEL A1
DRAWING NO.:
DRAWN BY:
DATE:
SHEET TITLE:
PROJECT TITLE:
COLLEGETOWN
TERRACE APARTMENTS
ITHACA, NY
NOVARR MACKESEY
DEVELOPMENTPROFESSIONAL LICENSE
NUMBER:
NEW YORK STATE SEAL:
a r c h i t e c t s
ikon.5 PROJECT NO.:P58.00
VERSIONS
NO. DATE DESCRIPTION
CIVIL ENGINEER:STRUCTURAL ENGINEER:MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL
ENGINEER:
LANDSCAPE ARCHITECT:HAZARDOUS MATERIAL ENGINEER:
12923
NORTH
PROJECTJULY 1, 2011
1 07.01.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
KEY PLAN
2 08.10.2011 SEQUENCE 1 - CONSTRUCTION DOCUMENTS
ADDENDUM - 1
BUILDING 4.0 FLOOR PLAN - LEVEL A
PR
M2.40
1/4"=1'0"
BUILDING 4.1 MECHANICAL ROOM PLAN2
1/4"=1'0"
BUILDING 4.1 MECHANICAL ROOM ELEVATION3
1/4"=1'0"
BUILDING 4.1 - MECHANICAL ROOM ELEVATION4
1
2
KEYED NOTES:
2" HWS & HWR.
CONDENSING BOILER.
3
4
BOILER LOOP PUMPS PIPED IN
PARALLEL.
HEATING SYSTEM LOOP PUMP, TYPICAL
OF 2.
5
6
EXTEND 4" VENT AND COMBUSTION AIR
TO EXTERIOR WALL. TERMINATE WITH 4"
TERMINATION KIT.
EXTEND PIPING FROM ACID
NEUTRALIZING TRAP TO FLOOR DRAIN.
COORDINATE FLOOR DRAIN LOCATION
WITH BOILER DRAIN AND PLUMBING
INSTALLER.
7
8
PLUMBING AND FIRE PROTECTION
EQUIPMENT SHOWN FOR REFERENCE
ONLY.
MECHANICAL ROOM EXHAUST FAN.
GENERAL NOTES:
A SEE M7-01 FOR PIPING SCHEMATIC
DIAGRAM.
ALL ISOLATION VALVES IN BOILER LOOP
SHALL BE FULL PORT.
PAINT PUMP SUPPORT STEEL ONE COAT
CHEROKEE RED OVER PRIMER.
PROVIDE PVC JACKETING FOR PIPING
INSULATION IN MECHANICAL ROOM
BELOW 7' AFF.
B
C
D
1/4"=1'0"
BUILDING 4.2 MECHANICAL ROOM PLAN5
1/4"=1'0"
BUILDING 4.2 MECHANICAL ROOM ELEVATION6
1
2
KEYED NOTES:
2" HWS & HWR.
CONDENSING BOILER.
3
4
BOILER LOOP PUMPS PIPED IN
PARALLEL.
HEATING SYSTEM LOOP PUMP, TYPICAL
OF 2.
5
6
EXTEND 4" VENT AND COMBUSTION AIR
TO EXTERIOR WALL. TERMINATE WITH 4"
TERMINATION KIT.
EXTEND PIPING FROM ACID
NEUTRALIZING TRAP TO FLOOR DRAIN.
COORDINATE FLOOR DRAIN LOCATION
WITH BOILER DRAIN AND PLUMBING
INSTALLER.
7
8
PLUMBING AND FIRE PROTECTION
EQUIPMENT SHOWN FOR REFERENCE
ONLY.
MECHANICAL ROOM EXHAUST FAN.
GENERAL NOTES:
A SEE M7-01 FOR PIPING SCHEMATIC
DIAGRAM.
ALL ISOLATION VALVES IN BOILER LOOP
SHALL BE FULL PORT.
PAINT PUMP SUPPORT STEEL ONE COAT
CHEROKEE RED OVER PRIMER.
PROVIDE PVC JACKETING FOR PIPING
INSULATION IN MECHANICAL ROOM
BELOW 7' AFF.
B
C
D
1/4"=1'0"
BUILDING 4.2 - MECHANICAL ROOM ELEVATION7
1/4"=1'0"
BUILDING 4.3 MECHANICAL ROOM PLAN8
1
2
KEYED NOTES:
2" HWS & HWR.
CONDENSING BOILER.
3
4
BOILER LOOP PUMPS PIPED IN
PARALLEL.
HEATING SYSTEM LOOP PUMP, TYPICAL
OF 2.
5
6
EXTEND 4" VENT AND COMBUSTION AIR
TO EXTERIOR WALL. TERMINATE WITH 4"
TERMINATION KIT.
EXTEND PIPING FROM ACID
NEUTRALIZING TRAP TO FLOOR DRAIN.
COORDINATE FLOOR DRAIN LOCATION
WITH BOILER DRAIN AND PLUMBING
INSTALLER.
7
8
PLUMBING AND FIRE PROTECTION
EQUIPMENT SHOWN FOR REFERENCE
ONLY.
MECHANICAL ROOM EXHAUST FAN.
GENERAL NOTES:
A SEE M7-01 FOR PIPING SCHEMATIC
DIAGRAM.
ALL ISOLATION VALVES IN BOILER LOOP
SHALL BE FULL PORT.
PAINT PUMP SUPPORT STEEL ONE COAT
CHEROKEE RED OVER PRIMER.
PROVIDE PVC JACKETING FOR PIPING
INSULATION IN MECHANICAL ROOM
BELOW 7' AFF.
B
C
D
1/4"=1'0"
BUILDING 4.3 MECHANICAL ROOM ELEVATION9
1/4"=1'0"
BUILDING 4.3 - MECHANICAL ROOM ELEVATION10
2 2
2
GENERAL NOTES:
ALL PIPING IN GARAGE SPACE IS ABOVE SUSPENDED CEILING.
SEE STRUCTURAL PLAN SHOWING BEAM PENETRATIONS FOR THE
PASSAGE OF PIPING AND CONDUIT. COORDINATE MECHANICAL PIPING
WITH PLUMBING, ELECTRICAL AND FIRE PROTECTION INSTALLERS.
IN GENERAL, STRUCTURAL BEAM SIZES IN THE GARAGE LEVEL
PROHIBIT PASSING CONDUITS, CONDUCTORS, PIPING, ETC., BETWEEN
THE BOTTOM OF BEAM AND CEILING/CEILING INSULATION SYSTEM.
DO NOT RUN CONDUITS, CONDUCTORS, PIPING, ETC. WITHIN THE
INSULATION SYSTEM. THERE ARE SPACES WHERE BEAMS HAVE
OPENINGS TO PASS UTILITIES THROUGH THE BEAM; REFER TO
STRUCTURAL DOCUMENTS. COORDINATE ALL UTILITY PENETRATIONS
THROUGH BEAMS WITH OTHER TRADES PRIOR TO COMMENCEMENT
OF ANY WORK.
A
2
B
22
2
2
2
2222
KEYED NOTES
1 CEILING PLENUM TEMPERATURE SENSOR NETWORK. SUSPEND SENSOR
VERTICALLY IN CENTER OF PLENUM SPACE. NETWORK SENSORS
TOGETHER AND CONNECT TO FIRE ALARM PANEL
C