Mechanical Compliance Certificate
Project Title:
90.1 (2016) Standard
Project Type:Alteration
Location:Ithaca, New York
Climate Zone:5a
Construction Site:
744 South Meadow Street
Suite 400
Ithaca, NY
Owner/Agent:
RGLA
5100 River Road
Suite 125
Schiller Park, IL 60176
Designer/Contractor:
HNY Consulting Engineers
New York, NY 10018
212-413-8770
Project Information
Energy Code:
ULTA #1503
Mechanical Systems List
Quantity System Type & Description
Gas Storage Water Heater, Capacity: 100 gallons, Input Rating: 199 kBtu/h w/ Circulation Pump
Proposed Efficiency: 80.00 % Et, Required Efficiency: 80.00 % Et
SWH COMPLIANCE REQUIRED.
1 Water Heater 1
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 90.1 (2016) Standard requirements in COMcheck Version 4.1.5.1 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
ULTA #1503
J:\Lenexa\Programs\U-Z\ULTA\2050004606 1503 Ithaca, NY\000\Energy\(ASHRAE 2016)
COMCheck.cck
04/27/21Report date:
71 ofPage
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.5.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2016) Standard
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
4.2.2,
7.7.1,
10.4.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
4.2.2,
8.4.1.1,
8.4.1.2,
8.7
[PR6]2
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
ULTA #1503
J:\Lenexa\Programs\U-Z\ULTA\2050004606 1503 Ithaca, NY\000\Energy\(ASHRAE 2016)
COMCheck.cck
04/27/21Report date:
72 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
7.4.4.1
[PL2]3
Temperature controls installed on
service water heating systems
(<=120ºF to maximum temperature
for intended use).
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
7.4.4.2
[PL3]1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
ULTA #1503
J:\Lenexa\Programs\U-Z\ULTA\2050004606 1503 Ithaca, NY\000\Energy\(ASHRAE 2016)
COMCheck.cck
04/27/21Report date:
73 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
6.4.3.4.5
[ME39]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
6.5.3.2.1
[ME40]2
DX cooling systems >= 75 kBtu/h (>=
65 kBtu/h effective 1/2016) and
chilled-water and evaporative cooling
fan motor hp >= ¼ designed to vary
supply fan airflow as a function of load
and comply with operational
requirements.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
7.5.3
[ME78]2
Gas-fired water-heating equipment
installed in new buildings: where a
singular piece of water-heating
equipment >= 1,000 kBtu/h serves
the entire building, thermal efficiency
must be >= 90 Et. Where multiple
pieces of water-heating equipment
serve the building with combined
rating is >= 1,000 kBtu/h, the
combined input-capacity-weighted-
average thermal efficiency , thermal
efficiency must be >= 90 Et. Exclude
input rating of equipment in individual
dwelling units and equipment <= 100
kBtu/h.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
6.5.7.2.4
[ME49]3
Approved field test used to evaluate
design air flow rates and demonstrate
proper capture and containment of
kitchen exhaust systems.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
7.4.2
[ME36]2
Service water heating equipment
meets efficiency requirements.
Complies
Does Not
Not Observable
Not Applicable
6.4.3.9
[ME63]2
Heating for vestibules and air curtains
with integral heating include
automatic controls that shut off the
heating system when outdoor air
temperatures > 45F. Vestibule
heating and cooling systems
controlled by a thermostat in the
vestibule with heating setpoint <=
60F and cooling setpoint >= 80F.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.5.10
[ME73]3
Doors separating conditioned space
from the outdoors have controls that
disable/reset heating and cooling
system when open.
Complies
Does Not
Not Observable
Not Applicable
Exception: Alteration project to existing building.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
ULTA #1503
J:\Lenexa\Programs\U-Z\ULTA\2050004606 1503 Ithaca, NY\000\Energy\(ASHRAE 2016)
COMCheck.cck
04/27/21Report date:
74 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
8.4.2
[EL10]2
At least 50% of all 125 volt 15- and
20-Amp receptacles are controlled by
an automatic control device.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
8.4.3
[EL11]2
New buildings have electrical energy
use measurement devices installed.
Where tenant spaces exist, each
tenant is monitored separately. In
buildings with a digital control system
the energy use is transmitted to to
control system and displayed
graphically.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
10.4.1
[EL9]2
Electric motors meet requirements
where applicable.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
ULTA #1503
J:\Lenexa\Programs\U-Z\ULTA\2050004606 1503 Ithaca, NY\000\Energy\(ASHRAE 2016)
COMCheck.cck
04/27/21Report date:
75 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
7.4.4.3
[FI11]3
Public lavatory faucet water
temperature <=110°F.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
7.4.4.4
[FI12]3
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
10.4.3
[FI24]2
Elevators are designed with the
proper lighting, ventilation power, and
standby mode.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
ULTA #1503
J:\Lenexa\Programs\U-Z\ULTA\2050004606 1503 Ithaca, NY\000\Energy\(ASHRAE 2016)
COMCheck.cck
04/27/21Report date: