Loading...
HomeMy WebLinkAboutOld Navy - 744 S Meadow Ste 350 - FA Specs Fire Lite MMF301 Monitor Module.pdf Mounting and Wiring NOTE: This module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. 1. Connect the red (+) and black (-) wires to the positive and negative loop power leads of the Signaling Line Circuit (SLC). 2. Connect the violet (+) and yellow (-) wires to a two-wire, normally open initiating loop. 3. Install the specified EOL resistor value to terminate the initiating loop. 4. Set the address on the module per job drawings. 5. Install the module in the desired mounting location. Figure 2. typical 2-Wire style B initiating device circuit (idc) conFiguration: 0 78 6 5 4 3 21 910 11 12 13 1415 (+) (–) TO NEXT DEVICE BLACK RED (+) (–)(+)(–) VIOLET YELLOW 01 2 3 4 5 6789 SIGNAL LINE CIRCUIT (SLC) 47k EOL INCLUDED (ELR-47k) UL LISTED COMPATIBLE CONTROL PANEL ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED TENS ONES C0614-02 BeFore installing This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. general description The MMF-301 monitor module can be installed in a single gang junction box directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting (see Figure 1). The MMF-301 is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiating circuit for normally open contact fire alarm and security devices. This module can be used to replace an M301 module in existing systems. coMpatiBility requireMents To ensure proper operation, this module should only be connected to listed compatible system control panels only. Figure 1: C1063-00 speciFications Nominal Operating Voltage: 15-32 VDC Average Operating Current: 375 µA (group poll); 350 µA (direct poll); 600 µA Maximum (Communicating, IDC Shorted) EOL resistance: 47K ohms Maximum IDC Resistance: 1,500 Ohms Maximum IDC Voltage: 11 Volts Maximum IDC Current: 450 µA Temperature Range: 32˚F to 120˚ F (0˚C to 49˚ C) Humidity: 10% to 93% Non-condensing Dimensions: 1.3˝ H x 2.75˝ W x 0.65˝ D Wire length: 6˝ minimum MMF-301 Monitor Module FL-460-004 1 I56-3654-002 ©2008 FireLite Alarms Inc. I56-3654-002 installation and Maintenance instructions One FireLite Place Northford, CT 06472 Phone: 203.484.7161 Fire Lite CRF 300 Relay Module.pdfuntitled df-60379:A1 • 08/04/09 — Page 1 of 2 CRF-300(A) Relay Module Addressable Devices df-60379:A1 • E-400 General The CRF-300(A) Addressable Relay Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, door holders, dampers, control equipment, etc. Addressability allows the dry contact to be activated through panel programming, on a select basis. LiteSpeed™ is a communication protocol developed by Fire•Lite Engineering that greatly enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. Features • Built-in type identification automatically identifies these devices to the control panel. • Internal circuitry and relay powered directly by two-wire SLC loop. • Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated. • High noise immunity (EMF/RFI). • Wide viewing angle of LED. • SEMS screws with clamping plates for wiring ease. • Direct-dial entry of address: 01– 159 for MS-9600(A) series panels, 01 – 99 on MS-9200UDLS(A) and MS-9050UD(A). Applications The CRF-300(A) may be programmed to operate dry contacts for door holders, Air Handling Unit shutdown, etc., and to reset four-wire smoke detector power. Construction • The face plate is made of off-white heat-resistant plastic. • Controls include two rotary switches for direct-dial entry of address setting. • The CRF-300(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. • The CRF-300(A) provides two Form-C dry contacts that switch together. Operation Each CRF-300(A) uses one of the addresses on a SLC loop. It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. NOTE: Open/short supervision is suspended with the CRF-300. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the control panel, so as to differentiate between a control module and a relay module. Specifications Normal operating voltage: 15 to 32 VDC. Maximum SLC current draw: 6.5 mA (LED on). Average operating current: 230 μA direct poll (CLIP mode), 255 μA group poll (LiteSpeed mode) with LED flashing. EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 mm) deep box. Relay Contact Ratings Load Description Application Maximum Voltage Current Rating Resistive Non-Coded 30 VDC 3.0 A Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9 A Resistive Non-Coded 125 VAC 0.9 A Inductive (L/R=5ms) Coded 30 VDC 0.5 A Inductive (L/R=2ms) Coded 30 VDC 1.0 A Inductive (PF=0.35) Non-Coded 125 VAC 0.5 A CRF-300(A) 60379cov.jpg Page 2 of 2 — df-60379:A1 • 08/04/09 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com LiteSpeed™ is a trademark and Fire•Lite® Alarms is a registered trademark of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Made in the U.S. A. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL: S2424 • ULC: S2424 • FM approved • CSFM: 7300-0075:185 • MEA: 72-01-E Product Line Information CRF-300(A): Intelligent addressable relay module. : Intelligent addressable relay module, ULC listed model. SMB500: Optional surface-mount backbox. NOTE: For installation instructions, see document I56-1190-005 and refer to the SLC Wiring Manual, document 51309. Fire Lite D355PL Duct Detector.pdfDF_60430-c2.fm DF-60430:C2 • 12/18/2012 — Page 1 of 2 D355PL(A)/DNRW InnovairFlex Intelligent Non-Relay Photoelectric Duct Smoke Detector Intelligent Addressable Devices DF-60430:C2 • E-650 General The Fire•Lite InnovairFlex® D355PL(A) intelligent non-relay photoelectric duct smoke detector and DNRW watertight nonrelay photoelectric duct smoke detector feature a pivoting housing that fits both square and rectangular footprints capable of mounting to a round or rectangular duct. DNRW duct smoke detector, with its NEMA-4 rating, is listed as a watertight, UV resistant enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water, allowing operators to use the detector in the most extreme environments. These units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute (0.5 to 20.32 m/s), temperatures of -4°F to 158°F (-20°C to 70°C), and a humidity range of 0 to 95 percent (non-condensing.) An improved cover design isolates the sensor head, which allows for ease of maintenance. A cover tamper feature indicates a trouble signal for a removed or improperly installed sensor cover. The Fire•Lite InnovairFlex housing provides a 3/ 4-inch conduit knockout and ample space to facilitate easy wiring and mounting of a relay module. The Fire•Lite InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories. Features • Photoelectric, integrated low-flow technology. • Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/s). • Versatile mounting options: square or rectangular configuration. • Broad ranges for operating temperature (-4°F to 158°F, 20°C to 70°C) and humidity (0% to 95% non-condensing). • Patented sampling tube installs from front or back of the detector with no tools required. • Cover tamper signal. • Increased wiring space with a newly added 3/4” conduit knockout. • Available space within housing to accommodate mounting of a relay module. • Easily accessible code wheels on sensor head (sold separately). • Clear cover for convenient visual inspection. • Remote testing capability. • Requires com line power only. • Accommodates the installation of an addressable relay module, sold separately, (CRF-300) for applications requiring a Form-C relay. Specifications Size: (Rectangle) 14.38 in (37 cm) Length; 5 in (12.7 cm) Width, 2.5 in (6.6 cm) Depth. Size: (Square) 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth. Weight: 1.6 lb (0.73 kg). Operating Temperature Range: -4°F to 158°F (-20°C to 70°C). Storage Temperature Range: -22°F to 158°F (-30°C to 70°C). Operating Humidity Range: 0% to 95% relative humidity (non-condensing). Air Duct Velocity: 100 to 4,000 ft/min (0.5 to 20.32 m/s). Accessories Fire•Lite provides system flexibility with a variety of accessories, including two remote test stations and different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detectors accessories are UL listed. D355PLs and DNRWs with a date code of 0013 or higher do not require external 24VDC for remote test applications when used with a remote-test-capable detector. ACCESSORY CURRENT LOADS AT 24 VDC Agency Listings and Approvals Consult product manual for lists of compatible UL-Listed devices. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL: S1059. • ULC: S1059 Device Standby Alarm RA100Z 0mA 12 mA Max RTS151/ RTS151KEY 0mA 12mA Max intelligent innovair Page 2 of 2 — DF-60430:C2 • 12/18/2012 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Fire•Lite® Alarms is a registered trademark of Honeywell International Inc.  ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Made in the U.S. A. • CSFM: 3242-1653:0209. • FM approved. Product Line Information D355PL: Intelligent non-relay photoelectric low flow smoke detector housing. Includes SD355R Detector. DNRW: Watertight intelligent non-relay photoelectric low flow duct smoke detector housing. Does not include detector head. SD355R(A): Remote test capable addressable low-profile photoelectric smoke detector. SD355(A): Addressable low-profile photoelectric smoke detector. DCOIL: Remote test coil. Required for older DNR(W) duct detector housing. DST1: Metal sampling tube duct width up to 1 ft (0.3m). DST1.5: Metal sampling tube duct widths up to 1 ft to 2 ft (0.3 to 0.6 m). DST3: Metal sampling tube duct widths up to 2 ft to 4 ft (0.6 to 1.2 m). DST5: Metal sampling tube duct widths up to 4 ft to 8 ft (1.2 to 2.4 m). DST10: Metal sampling tube duct widths up to 8 ft to 12 ft (2.4 to 3.7 m). DH400OE-1: Weatherproof enclosure. ETX: Metal exhaust tube duct, width 1 ft (0.3 m). M02-04-00: Test magnet. P48-21-00: End cap for metal sampling tubes. RA100Z: Remote annunciator alarm LED. RTS151: Remote test station. RTS151KEY: Remote test station with key lock. Important Note • DNRW duct detector housings with a date code of 0013 or higher do not require a DCOIL or auxiliary 24 VDC for remote test applications when used with a remote test capable detector. • DNRW duct detector housings with a date code of 0012 or earlier require a DCOIL and auxiliary 24 VDC power for remote test applications. Fire Lite ES-50X.pdfuntitled DF-60953:C • 7/16/2018 — Page 1 of 4 ES-50X Intelligent Addressable FACP with Communicator Addressable Fire Alarm Control Panels DF-60953:C General The ES-50X is the latest intelligent addressable fire alarm control panel (FACP) from Fire•Lite Alarms and is a direct replacement for the MS-9050UD/LS. The ES-50X comes with a pre-installed communi-cator and supports up to 50 addressable devices in any combination of detectors or modules. With an extensive list of powerful features, the ES-50X programs just like Fire•Lite’s other addressable panels, yet fits into applications previously served only by conventional panels. The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator’s internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using the CELL-MOD or CELL-CAB-FL. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel’s USB port (and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file, walk-test data, current status and system voltages by means of a USB flash drive. The power supply and all electronics are contained on a circuit board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include local and remote upload/download software, remote annunciators, and reverse polarity/city box transmitter (4XTMF). Features • Listed to UL Standard 864, 10th edition • Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Telephone Service) Central Station Communicator • Optional CELL-MOD or CELL-CAB-FL GSM Central Station Communicator over AlarmNet® • Compatible with SWIFT® wireless devices • Auto-programming (learn mode) reduces installation time. Reports two devices set to the same address • Two independently programmable, built-in Style Z (Class A) or Style Y (Class B) NAC circuits • Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices • Notification Appliance Circuit End of Line resistor matching • Four programmable function keys for ease of maintenance • Two programmable relays and one fixed trouble relay • Built-in Programmer • Integral 80-character LCD display with backlighting • Real-time clock/calendar with automatic daylight savings control • History file with 1,000 event capacity • Addressable sounder base • Multi-criteria detector (smoke, heat, CO) with programmable response • Control module delay timer • Automatic detector sensitivity testing (NFPA 72 compliant) • Automatic device type-code verification • Point trouble identification • Waterflow selection per module point • Alarm verification selection per detector point • Maintenance alert warns when smoke detector dust accumulation is excessive • One-person audible or silent walktest with walktest log & printout • System alarm verification selection per detector point • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant) • Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus • Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator • Upload/Download of program and data via USB with optional FSTools Programming Utility SLC COMMUNICATION LOOP • Supports LiteSpeed™ and CLIP protocols • SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire • Single addressable SLC loop which meets NFPA Class B and Class A requirements • 50 addressable device capacity (any combination of addressable detectors and modules) • Compatible with Fire•Lite’s addressable devices (refer to the SLC Wiring Manual) NOTIFICATION APPLIANCE CIRCUITS (NACS) • Two independently programmable output circuits. Circuits can be configured for the following outputs: – Style Y (Class B) – Style Z (Class A) • Silence Inhibit and Autosilence timer options • Continuous, March Time, Temporal, or California code for main circuit board NACs with two-stage capability • Selectable strobe synchronization per NAC • 2.5 A special application, 250mA regulated, total power for NACs NOTE: Maximum or total 24VDC system power shared between all NAC circuits and the ANN-BUS is 2.7 A PROGRAMMING AND SOFTWARE • Autoprogramming (learn mode) reduces installation time Page 2 of 4 — DF-60953:C • 7/16/2018 • Custom English labels (per point) may be manually entered or selected from an internal library file • Two programmable Form-C relay outputs • 50 software zones • Continuous fire protection during online programming • Program Check automatically catches common errors not linked to any zone or input point • OFFLINE PROGRAMMING: Create the entire program in your office using FS-Tools, a Windows®-based software package, and upload/download system programming locally. Offline programming requires an ethernet connection. FS-Tools is available on www.firelite.com. User interface LED INDICATORS • Fire Alarm (red) • CO Alarm (red) • AC Power (green) • Supervisory (yellow) • Trouble (yellow) • Ground fault (yellow) • Battery fault (yellow) • Disabled (yellow) • Maintenance (yellow) • Communication (yellow) • Alarm Silenced (yellow) • F1-F4 Programmable Function Keys (yellow) KEYPAD • 16 key alpha-numeric pad • Acknowledge • Alarm Silence • Drill (Manual Evacuate) • Four (4) programmable function keys • Reset (lamp test) Product Line Information ES-50X: Addressable Fire Alarm Control Panel with one SLC loop. Includes main circuit board with display, pre-installed IPOTS-COM communicator, chassis with transformer, backbox with door, plastic bag containing screws, cables, key, etc. (For ES-50XC, refer to DF60954.) FS-Tools: Programming software for Windows®-based PC computer. Available for download at www.firelite.com. CELL-CAB-FL/CELL-MOD: Optional GSM communicators. IPOTS-COM: Dual technology (POTS and IP) communicator. (replacement board) DP-ES-R: Optional dress panel for the ES-50X. TR-CE: Optional trim ring for semi-flush mounting. BB-2F: Optional cabinet for one or two modules. BB-6F: Optional cabinet for up to six modules mounted on CHS-6 chassis. BB-26: Battery backbox, holds up to two 25 AH batteries & CHG-75. BB-55F: Battery box, houses two 55 AH batteries CHS-6: Chassis, mounts up to six multi-modules in a BB-6F cabinet. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75 AH. CHG-120F: Remote battery charging system for lead-acid batteries with a rating of 55 to 120 AH. Requires additional BB-55F for mounting. BAT Series: Batteries, see data sheet DF-52397. PRN Series: UL listed compatible event printer. Uses tractor-fed paper. OPTIONAL MODULES 4XTMF Reverse Polarity Transmitter Module: Provides a supervised output for local energy municipal box transmitter, alarm and trouble. Includes a disable switch and disable trouble LED. COMPATIBLE ANNUNCIATORS ANN-80: Remote, red LCD annunciator mimics the information displayed on the FACP LCD display. Recommended wire type is unshielded. ANN-100: Remote LCD annunciator mimics the information displayed on the FACP LCD display. Recommended wire type is unshielded. For use in FM applications only. ANN-I/O: LED Driver Module provides connections to a user supplied graphic annunciator. (See DF-52430.) ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF60241.) ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DF-60241.) ANN-RLY: Relay Module provides 10 programmable Form-C relays. Can be mounted inside the cabinet. (See DF-52431.) ANN-S/PG: Serial/Parallel Printer Gateway module provides a connection for a serial or parallel printer. (See DF-52429.) ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. SD365: Addressable low-profile photoelectric smoke detector. LiteSpeed only. SD365-IV: Addressable low-profile photoelectric smoke detector. Ivory. LiteSpeed and CLIP mode. SD365T: Addressable low-profile photoelectric smoke detector with thermal sensor. LiteSpeed only. SD365T-IV: Addressable low-profile photoelectric smoke detector with thermal sensor. Ivory. LiteSpeed and CLIP mode. SD365R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. LiteSpeed only. SD365R-IV: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. Ivory. LiteSpeed and CLIP mode. H365: Low-profile 135°F fixed thermal sensor. LiteSpeed only. H365-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. H365R: Low-profile, intelligent, rate-of-rise thermal sensor. LiteSpeed only. H365R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. Ivory. LiteSpeed and CLIP mode. H365HT: Low-profile intelligent 190°F/88°C fixed thermal sensor. LiteSpeed only. H365HT-IV: Low-profile intelligent 190°F/88°C fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. Legacy Devices SD355: Addressable low-profile photoelectric smoke detector. SD355T: Addressable low-profile photoelectric smoke detector with thermal sensor. SD355R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. SD355CO: Addressable, low-profile device that provides fire, heat, and carbon monoxide (CO) detection. H355: Fast-response, low-profile heat detector. H355R: Fast-response, low-profile heat detector with rate-of-rise option. H355HT: Fast-response, low-profile heat detector that activates at 190°F/88°C. DF-60953:C • 7/16/2018— Page 3 of 4 AD355: Low-profile, intelligent, “Adapt” multi-sensor detector (B350LP base included). B200S: Programmable, addressable sounder base B200SR: Addressable sounder base. BEAM355: Intelligent beam smoke detector. BEAM355S: Intelligent beam smoke detector with integral sensitivity test. D355PL: InnovairFlex low-flow non-relay duct-detector housing; includes SD355R. DNR: InnovairFlex low-flow non-relay duct-detector housing. (Order SD355R/SD365R separately.) DNRW: InnovairFlex low-flow non-relay duct-detector housing, with NEMA-4 rating. Watertight. (Order SD355R/SD365R separately.) Addressable Modules MMF-300: Addressable Monitor Module for one zone of normallyopen dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Style B (Class B) or Style D (Class A) IDC. MDF-300: Dual Monitor Module. Same as MMF-300 except it provides two Style B (Class B) only IDCs. MMF-301: Miniature version of MMF-300. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. MMF-302: Similar to MMF-300. Addressable Monitor Module for one zone of conventional two-wire detectors. Requires resettable 24 VDC power. Refer to the Device Compatibility Document for listed compatible devices and quantity limitation. CMF-300: Addressable Control Module for one Style Y/Z (Class B/ A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. NAC option requires external 24 VDC to power notification appliances. CRF-300: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500. BG-12LX: Addressable manual pull station with interface module mounted inside. I300: This module isolates the SLC loop from short circuit conditions (required for Style 6 or 7 operation). ISO-6: Six-fault isolator module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SMB500: Used to mount all modules except MMF-301 and M301. MMF-300-10: Ten-input monitor module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. MMF-302-6: Six-zone interface module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CMF-300-6: Six-circuit supervised control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CRF-300-6: Six-relay control module (Form-C relays). Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SWIFT Wi reless De vices W-GATE: LiteSpeed Wireless Gateway W-SD355: LiteSpeed intelligent, wireless photo detector. W-H355R: LiteSpeed intelligent wireless rate of rise (135°) heat detector. W-SD355T: intelligent wireless photo/heat detector. W-H355: LiteSpeed intelligent wireless fixed-temperature (135°) heat detector. W-MMF: LiteSpeed Intelligent wireless monitor module. W-CRF: LiteSpeed Intelligent wireless relay module. W-BG12LX: LiteSpeed Intelligent wireless pull station. WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: LiteSpeed Intelligent AV bases. W-USB: Wireless USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools. SWIFT Tools: Programming and diagnostic utility for the Wireless Gateway and devices. Available for download from firelite.com. NOTE: For more information on Compatible Addressable Devices for use with the ES-50X, see the following data sheets (document numbers): SD365 Series (DF-61010), H365 Series (DF-61011), AD355 (DF-52386), BG-12LX (DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-52374), CMF/CRF Series (DF-52130), CP355 (DF-52383), H355 Series (DF-52385), I300 (DF-52389), ISO-6 (DF-60485), MMF-300 Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF-52384), and SLC Wiring Manual (51309). NOTE: Legacy 300 Series detection devices such as the CP300/CP350, SD300(T)/SD350(T) and older modules such as the M300, M301, M302, C304, and BG-10LX are not compatible with LiteSpeed polling. If the SLC contains one of these devices, polling must be set for standard CLIP protocol. Please consult factory for further information on previous 300 Series devices. ADDRESSABLE DEVICE ACCESSORIES End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm assembly supervises the MMF-300, MDF-300, MMF-301, and CMF-300 module circuits. The 3.9k ohm assembly supervises the MMF-302 module circuit. These resistors are included with each module. Power Supervision Relay: Supervises the power to 4-wire smoke detectors and notification appliances. Wiring Requirements While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Refer to the panel manual for wiring details. AlarmNet®, Fire-Lite® Alarms, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Page 4 of 4 — DF-60953:C • 7/16/2018 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Country of Origin: USA SYSTEM SPECIFICATIONS System Capacity • Intelligent Signaling Line Circuits................................................1 • Addressable device capacity....................................................50 • Programmable software zones.................................................50 • Annunciators.............................................................................16 Electrical Specifications AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, auto-sensing- no switch required. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Nonpower-limited, supervised. Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger Capacity: 7-18 AH (ES-50X cabinet holds maximum of two 18 AH batteries.) Communication Loop: Supervised and power-limited. Notification Appliance Circuits: Terminal Block provides connections for two NACs, Style Y (Class B) or Style Z (Class A). Special Application power. Power-limited, supervised circuitry. Maximum signaling current per circuit: 2.5 amps special application, 250mA regulated. End-of-Line Resistor: 4.7k ohm, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC; system capable of 1.9 kΩ - 22 kΩ ELR range. Refer to the Fire•Lite Device Compatibility Document for listed compatible devices. Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays, non-power-limited, non-supervised. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. Shipping Specifications Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.) high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 – 49°C/32 –120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. NFPA Standards The ES-50X complies with the following NFPA 72 Fire Alarm Systems requirements: – LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory). – AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). – REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervisory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTMF is required.) – PROPRIETARY (Automatic, Manual and Waterflow). – CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). – OT, PSDN (Other Technologies, Packet-switched Data Network) – IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic). – CBC 2007 (Seismic) Agency Listings and Approvals The listings and approvals below apply to the basic ES-50X control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL: S624 • FM approved • CSFM: 7165-0075:0500 • FDNY: COA #6261 NOTE: See DF-60954 for ULC-listed model. Fire Lite ANN-80 Annuciator.pdfuntitled df-52417:c • 05/22/09 — Page 1 of 2 ANN-80 80-Character LCD Serial Annunciator Annunciators df-52417:c • B-90 52417cov.jpg General The ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced conditions. The ANN-80 and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply. ANN-80 is red; for white, order ANN-80-W. The ANN-80 displays English-language text of system point information including device type, zone, independent point alarm, trouble or supervisory status, as well as any custom alpha labels programmed into the control panel. It includes control switches for remote control of critical system functions. (A keyswitch prevents unauthorized operation of the control switches.) Up to eight ANN-80s may be connected to the ANN-BUS of each FACP. No programming is required, which saves time during system commissioning. Features • Listed to UL Standard 864, 9th Edition. • Backlit 80-character LCD display (20 characters x 4 lines). • Mimics all display information from the host panel. • Control switches for System Acknowledge, Signal Silence, Drill, and Reset. • Control switches can be independently enabled or disabled at the FACP. • Keyswitch enables/disables control switches and mechanically locks annunciator enclosure • Keyswitch can be enabled or disabled at the FACP. • Enclosure supervised for tamper. • System status LEDs for AC Power, Alarm, Trouble, Supervisory, and Alarm Silence. • Local sounder can be enabled or disabled at the FACP. • ANN-80 connects to the ANN-BUS terminal on the FACP and requires minimal panel programming. • Displays device type identifiers, individual point alarm, trouble, supervisory, zone, and custom alpha labels. • Time-and date display field. • Surface mount directly to wall or to single, double, or 4" square electrical box. • Semi-flush mount to single, double, or 4" square electrical box. Use ANN-SB80KIT for angled view mounting. • Can be remotely located up to 6,000 feet (1,800 m) from the panel. • Backlight turns off during AC loss to conserve battery power but will turn back on if an alarm condition occurs. • May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC). • Up to eight ANN-80s can be connected on the ANN-BUS. Controls and Indicators • AC Power • Alarm • Trouble • Supervisory • Alarm Silenced Specifications • Operating voltage range: 18 VDC to 28 VDC. • Current consumption @ 24 VDC nominal (filtered and nonresettable): 40 mA maximum. • Ambient temperature: 32°F to 120°F (0°C to 49°C). • Relative humidity: 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). • 5.375” (13.65 cm.) high x 6.875” (17.46 cm.) wide x 1.375” (3.49 cm.) deep. • For use indoors in a dry location. • All connections are power-limited and supervised. Agency Listings and Approvals The listings and approvals below apply to the ANN-80. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL: S2424 • FM approved • CSFM: 7120-0075:211 • MEA: 442-06-E The ANN-BUS POWERING THE DEVICES ON THE ANN-BUS FROM AUXILIARY POWER SUPPLY The ANN-BUS can be powered by an auxiliary power supply when the maximum number of ANN-BUS devices exceeds the ANN-BUS power requirements. See the FACP manual for more information. Page 2 of 2 — df-52417:c • 05/22/09 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com FireLite® Alarms is a registered trademark of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Made in the U.S. A. ANN-BUS DEVICE ADDRESSING Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the FACP. A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. See the FACP manual for more information. WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT The ANN-80 connects to the FACP ANN-BUS communications circuit. To determine the type of wire and the maximum wiring distance that can be used with FACP ANN-BUS accessory modules, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. NOTE: For total worst case current draw on a single ANN-BUS refer to appropriate FACP manual. After calculating the total worst case current draw, the following table specifies the maximum distance the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. See table below. WIRE REQUIREMENTS: POWER CIRCUIT • 14 to 18 AWG (0.75 - 2.08 mm2) wire for 24 VDC power circuit is acceptable. Power wire distance limitation is set by 1.2 volt maximum line drop form source to end of circuit. • All connections are power-limited and supervised. • A maximum of eight ANN-80 modules may be connected to this circuit. WIRING CONFIGURATION The following figure illustrates the wiring between the FACP and ANN-BUS devices. FACP Wiring to ANN-BUS Device ORDERING OPTIONS: ANN-80: Red 80 character LCD Annunciator. ANN-80-W: White, 80 character LCD Annunciator. ANN-SB80KIT-R: Red surface mount backbox with angled wedge. ANN-SB80KIT-W: White surface mount backbox with angled wedge. Communication Pair Wiring Distance: FACP to Last ANN-BUS Module Total Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0.100 1,852 ft. 4,688 ft. * 6,000 ft. *6,000 ft. 0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft. 0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft. 0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft. 0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft. 0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft. 0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft. 0.800 231 ft. 586 ft. 933 ft. 1,476 ft. 0.900 206 ft. 521 ft. 829 ft. 1,312 ft. 1.000 (max.) 185 ft. 469 ft. 746 ft. 1,181 ft. ANN-BUS and power wiring are supervised and power-limited. ANN-BUS Device MS-9050UD Fire Lite BG12LX Pull Station.pdfuntitled DF-52013:D • 4/13/2012 — Page 1 of 2 BG-12LX Addressable Manual Pull Station Addressable Devices DF-52013:D • E-100 FLPullStation.jpg General The Fire·Lite BG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Fire·Lite’s addressable fire alarm control panels (FACPs) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word “ACTIVATED” appears to clearly indicate the station has been operated. • Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm² wire). • Can be surface mounted (with SB-10 or SB-I/O) or semiflush mounted. Semi-flush mount to a standard singlegang, double-gang, or 4" (10.16 cm) square electrical box. • Smooth dual-action design. • Meets ADAAG controls and operating mechanisms guidelines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. • Attractive shape and textured finish. • Key reset. • Includes Braille text on station handle. • Optional trim ring (BG12TR). • Meets UL 38, Standard for Manually Actuated Signaling Boxes. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications • Shipping Weight: 9.6 oz. (272.15 g) • Normal operating voltage: 24 VDC. • Maximum SLC loop voltage: 28.0 VDC. • Maximum SLC standby current: 375 μA. • Maximum SLC alarm current: 5 mA. • Temperature Range: 32°F to 120°F (0°C to 49°C) • Relative Humidity: 10% to 93% (noncondensing) • For use indoors in a dry location Installation The BG-12LX will mount semi-flush into a single-gang, doublegang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB-10 or SB-I/O surface backbox. If the BG-12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word “ACTIVATED” (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; closing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 – 159 with Breakaway Tab removed for MS-9600 Series, 1 – 99 and MS-9200UDLS, 1 – 50 for MS-9050UD). Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non-coded, with a keyoperated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated station shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box, and shall be installed Page 2 of 2 — DF-52013:D • 4/13/2012 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com FireLite® Alarms® is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Made in the U.S. A. within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the control panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information BG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian applications.) SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17003: Keys, set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL/ULC Listed: S711 (listed for Canadian and non-Canadian applications). • MEA: 67-02-E. • CSFM: 7150-0075:0184. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. Gentex Commander3- GEC - GES Series.pdf GES3 / GEC3 Series Selectable Candela Evacuation Signals 12 VDC and 24 VDC Commander3 Strobe and Horn/Strobe 24 units per carton, 28 pounds per carton Assembled in the USA Applications The Commander3 Series is a low profile strobe and horn/strobe combination that offers dependable audible and visual alarms and the absolute lowest current available. The GE3 Series 24 VDC offers tamperproof field selectable candela options of 15, 30, 60, 75, and 110 candela. The 12 VDC offers tamperproof field selectable candela options of 15, 30, 60, and 75 candela. The GEC3 horn/strobe offers a continuous or synchable temporal 3 in 2400Hz, mechanical and chime as well as a whoop tone. All tones are easy for the professional to change in the field by the use of switches. The Commander3 Series is shipped with a standard 4” metal mounting plate which incorporates the popular Super-Slide® feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The Commander3 also features the patented Checkmate® instant voltage verification feature which allows the installer to check the voltage drop draw and match it to the blueprint. The GE3 Series appliances are ANSI/UL 464, ANSI/UL 1971, CAN/ULC S525 (24 VDC only) and/or CAN/ULC S526 (24 VDC only), is listed for use with fire protective systems and are warranted for three years from date of purchase. Standard Features • Nominal voltage 12 VDC and 24 VDC • 24 VDC field selectable candelas: 15, 30, 60, 75 & 110 • 12 VDC field selectable candelas: 15, 30, 60 & 75 • Unit Dimensions: 5” (12.7 cm) high x 4.5” (11.43 cm) wide x 2.5” (6.35 cm) deep • Super-Slide® Bracket, Ease of Supervision Testing • Checkmate® Instant Voltage Verification • Prewire entire system, install mounting bracket, then install signals • Documented lower installation and operating costs • Input terminals accept 12 to 18 AWG • Horn/strobe switch selection for high or low dBA • Horn/strobe switch for 2400 Hz, mechanical, chime and whoop tones • Horn/strobe switch for continuous or temporal 3 (not available on whoop tone) • Synchronize strobe and/or horn with Gentex AVSM Control Module • Silence audible while visual appliance will remain flashing • Tamperproof re-entrant style grill and locking screw (optional use) • Surface mount with the GSB (Gentex Surface Mount Box) • Faceplate available in red or off-white • Wall mount Product Listings • ANSI/UL 464 and ANSI/UL 1971 Listed • CAN/ULC S525 and/or CAN/ULC S526 Listed (24 VDC only) • CSFM: 7135-0569:122 (GEC3-24 & GEH-24) 7125-0569:123 (GES3-24) 7125-0569:129 (GES3-12) 7135-0569:130 (GEC3-12 & GEH-12) • MEA: 285-91-E (GEC3-24 & GES3-24) 580-06-E (GEC3-12 & GES3-12) Patents • 7,375,617 May 20, 2008 Product Compliance • NFPA 72 • Americans with Disabilities Act (ADA) • IBC/IFC/IRC • Quality Management System is certified to: ISO 9001:2008 GES3 / GEC3 - Selectable Candela Evacuation Signals GE3 12 VDC / 24 VDC Strobe Current Ratings (mA) 12 VDC (8-17.5 Volts) 24 VDC (16-33 Volts) Candela 12 VDC UL Max 24 VDC UL Max 15cd 106 mA 92 mA 30 mA 42 mA 30cd 131 mA 141 mA 42 mA 58 mA 60cd 186 mA 260 mA 66 mA 97 mA 75cd 237 mA 312 mA 80 mA 116 mA 110cd 103 mA 161 mA R = Red Faceplate, W = White Faceplate All units are available in plain (no lettering) Plain units are not returnable ALERT and AGENT bezels available for order GE3 12 VDC / 24 VDC Horn Decibel (dBA) and Current Ratings (mA) 12 VDC (8-17.5 Volts) 24 VDC (16-33 Volts) Horn Decibel Levels (dBA) Horn Current Ratings (mA Horn Decibel Levels (dBA) Horn Current Ratings (mA) Horn Mode Minimum SPL at 10ft., per ANSI/UL 464 (HIGH) Minimum SPL at 10ft., per ANSI/UL 464 (LOW) UL MAX Regulated 12 VDC Operating Current (HIGH) Minimum SPL at 10ft., per ANSI/UL 464 (HIGH) Minimum SPL at 10ft., per ANSI/UL 464 (LOW) UL MAX Regulated 24 VDC Operating Current (HIGH) Temporal 3 2400 Hz 76 dBA 69 dBA* 29 mA 78 dBA 71 dBA* 28 mA Temporal 3 Mechanical 75 dBA 68 dBA* 26 mA 76 dBA 70 dBA* 25 mA Temporal 3 Chime 62 dBA* 60 dBA* 13 mA 70 dBA* 66 dBA* 15 mA Continuous 2400 Hz 79 dBA 74 dBA* 29 mA 81 dBA 74 dBA* 28 mA Continuous Mechanical 78 dBA 72 dBA* 26 mA 80 dBA 72 dBA* 25 mA Continuous Chime 63 dBA* 61 dBA* 13 mA 70 dBA* 66 dBA* 15 mA Whoop 78 dBA 71 dBA* 55 MA 82 dBA 69 dBA* 56 mA * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). GES3 12 VDC / GES 24 VDC Selectable Candela, Low Profile Evacuation Strobe Model Part Number Voltage (VDC) Candela GES3-12WR 904-1235-002 12 15, 30, 60, 75 GES3-12WW 904-1237-002 12 15, 30, 60, 75 GES3-24WR 904-1321-002 24 15, 30, 60, 75, 110 GES3-24WW 904-1319-002 24 15, 30, 60, 75, 110 GEC3 12VDC / GEC3 24VDC Selectable Candela, Low Profile Evacuation Horn/Strobe Model Part Number Voltage (VDC) Candela Reverberant dBA at 10ft. Anechoic Room dBA at 10ft. GEC3-12WR 904-1231-002 12 15, 30, 60, 75 62-82 dBA 100 dBA GEC3-12WW 904-1233-002 12 15, 30, 60, 75 62-82 dBA 100 dBA GEC3-24WR 904-1317-002 24 15, 30, 60, 75, 110 62-82 dBA 100 dBA GEC3-24WW 904-1315-002 24 15, 30, 60, 75, 110 62-82 dBA 100 dBA 4.5” 11.4 cm 2.5” 6.35 cm 5.0” 12.7 cm Gentex Super-Slide® Mounting Bracket Allows the installer to prewire the system, test for system supervision, remove the signal head until occupancy, switch out Gentex signals without changing mounting brackets and has locking edge connector for snap-in-place installation. Gentex Checkmate® Instant Voltage Verification It is often necessary to confirm the voltage drop along a line of devices. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. Notice: Care should be taken to not short the test probes. Notes • Operating temperature: 32° to 120°F (0° to 49°C) • The GES3/GEC3 Series is not listed for outdoor use • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode, its sound pressure is the same as the continuous mode. • This appliance is not recommended for use on coded or pulsing signaling circuits Fire Protection Products Group | 10985 Chicago Drive | Zeeland, MI 49464 gentex.com | Phone: 616.392.7195 | Toll-free: 800.436.8391 | Fax: 616.392.4219 551-0050-07 Important Notice: These materials have been prepared by Gentex Corporation (“Gentex”) for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person’s activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. GES3 / GEC3 Series Selectable Candela Evacuation Signals Architect & Engineering Specifications The audible and/or visible signal shall be Gentex GES3, GEC3 Series or approved equal and shall be listed by Underwriters Laboratories (ANSI/ UL) for use with fire protective signaling systems (ANSI/UL 1971 and/or ANSI/UL 464) and with CAN/ULC S526 (24 VDC only) and/or CAN/ULC S525 (24 VDC only) with intended use in fire alarm systems. The notification appliance (GEC3) shall produce a peak sound output of 100 dBA or greater at 12 VDC or 24 VDC as measured in an anechoic chamber and shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2 Hz regardless of power input voltage. The strobe appliance shall have an operating current of 42 mA or less at 24 VDC for the 15 Cd strobe circuit and 92 mA or less at 12 VDC for the 15 Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The GE3 Series shall be mounted on the wall. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power at 24 VDC or a voltage range of 8-17.5 volts at 12 VDC. The appliance shall be capable of testing supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. System Sensor CO1224T Carbon Monoxide Detector.pdf Agency Listings CO1224T and CO1224TR Carbon Monoxide Detectors with RealTest® Technology The System Sensor CO1224T and CO1224TR (round) Carbon Monoxide (CO) Detectors use a highly accurate and reliable electrochemical sensing cell to provide early warning of dangerous CO levels. Features • RealTest® enables a functional test using canned CO • Full compliance with UL 2075 • A code-required trouble relay • Wiring supervision with SEMS terminals • A six-year end-of-life timer • 12/24 VDC • A low current draw of 20 mA in standby and 40 mA in alarm • Versatile mounting f or wall and ceiling • Accurate and reliable electrochemical sensing technology • Optional CO-PLATE CO Detector Replacement Plate to upgrade previously installed competitor detectors to the CO1224T With RealTest® technology, the CO gas sensing cell used in the CO1224T and CO1224TR CO detectors can be tested using a CO gas agent, fully meeting the requirements of NFPA 720: 2009. Simply put the detector into RealTest mode, spray a small amount of CO into the detector per the installation instructions, and within seconds the detector will alarm, indicating successful gas entry. (See the reve rse page or the user manual for complete instructions.) When dangerous amounts of CO are detected, the CO1224T and CO1224TR detectors alert residents by sounding and flashing a temp 4 signal alarm. With 24/7 central station monitoring, residents are guaranteed protection whether they are away from home, sleeping, or already suffering from the effects of CO. The CO1224T and CO1224TR are designed for system operation. These detectors are fully listed to UL 2075 and offer a coderequired trouble relay to send a sensor failure or end-of-life signal to the control panel and the central station. The CO1224T and CO1224TR also use SEMS-type terminal Philips head screws for quicker and more positive wiring connections and code-required wiring supervision. With a low current draw, these detecto rs enable more devices to be connected to the panel, limiting the need to purchase extra power supplies or more expensive panels. As 12/24 VDC detectors, the CO1224T and CO1224TR will operate on most industry security and fire alarm control panels. E307195 E304075 5276-1653:0194 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2012 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. SCDS00100 • 4/12 Ordering Information Part No. Description CO1224T 12/24 volt, 4-wire system-monitored carbon monoxide detector with RealTest® Technology CO1224TR 12/24 volt, 4-wire system-monitored round carbon monoxide detector with RealTest® Technology CO-PLATE CO detector replacement plate to cover the footprint of previously installed competitive detectors as necessary CO1224T and CO1224TR Carbon Monoxide Detector Specifications Architectural/Engineering Specifications Carbon monoxide (CO) detector shall be a system-connected System Sensor model number CO1224T or CO1224TR listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and Sensors. The detector shall be equipped with a sounder and a trouble relay. The detector’s base shall be able to mount to a single-gang electrical box or direct (surface) mount to the wall or ceiling. Wiring connections shall be made by means of SEMS screws. The detector shall provide dual-color LED indication that blin ks to indicate normal standby, alarm, or end-of-life. When the sensor supervision is in a trouble condition, the detector shall send a trouble signal to the panel. When the detector gives a trouble o r end-of-life signal, the detector shall be replaced. The detector shall provide a means to test CO gas entry into the CO sensing cell. The detector shall provide this with a test mode that accepts C O gas from a test agent and alarms immediately upon sensing CO entry. The detector shall perform in the detection of CO up to 12,000 feet above sea level and alarm within the time specified by ANSI/U L 2034 for CO concentrations of 70, 150 and 400 parts per million (ppm), as verified by a Nationally Recognized Test Laboratory. Electrical Specifications Operating Voltage 12/24 VDC Audible Signal 85 dB in alarm Standby Current 20 mA Alarm Current 40 mA (75 mA test) Alarm Contact Ratings 0.5 A @ 30 VDC Trouble Contact Ratings 0.5 A @ 30 VDC Physical Specifications Size: CO1224T Length: 5.1 in, Width: 3.3 in, Height: 1.3 in CO1224TR Diameter: 6 in, Height: 1.3 in Approximate Weight CO1224T: 7 oz ; CO1224TR: 11 oz Operating Temperature Range 32°F to 104° F (0°C to 40° C) Operating Humidity Range 22 to 90% RH Input Terminals 14 to 22 AWG Mounting Single-gang back box; surface mount to wall or ceiling Operation Modes Operation Mode Green LED Red LED Sounder Normal (standby) Blink 1 per minute — — Alarm — Blink in temp 4 pattern Sound in temp 4 pattern RealTest® Feature: The System Sensor CO1224T and CO1224TR Ca rbon Monoxide Detectors with RealTest enable evaluation of the functionality of the CO sensing cell using a canned CO test agent. Hush Feature: Pushing the Test/Hush button will silence the sounder for 5 minutes (except in RealTest mode). Trouble Feature: When the detector is in a trouble condition, it will send a trouble signal to the panel. End-of-Life Timer: After the detector’s internal sensor has reached the end of its life, a trouble signal will be sent to the panel to indicate it is time to replace the detector. An electrochemical CO detector lifespan is about six years. The det ector must be replaced by the date marked on the inside of the product. CO-PLATE: System Sensor also offers the CO-PLATE CO Detector Replacement Plate to cover the footprint (when necessary) of prev iously installed competitive carbon monoxide detectors that require replacement. 3. Push and hold the Test/Hush button for two seconds to enter RealTest mode. The green LED will flash once every seco nd to indicate RealTest mode has started. Spray canned CO agent into the detector. CO-PLATE Verify CO sensing at the control panel. The detector will automatically exit RealTest alarm mode after abou t 20-60 seconds. NOTE: Check with local codes and the AHJ to determine if a functional gas test is desired for an installation. 1. 2.