HomeMy WebLinkAboutDrawings_Rhodes Hall 5th Flooring Renov INDEXEDRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 TRyan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationCOVER SHEETT-001TITLET-001 COVER SHEETT-002 SYMBOLS, NOTES & ABBREVIATIONST-003 ACCESSIBILITY NOTES & DETAILST-004 AREA OF WORK & CODE INFORMATIONRHODES HALL 5TH FLOOR RENOVATIONCORNELL UNIVERSITYITHACA, NEW YORKABATEMENTAR-101 ASBESTOS ABATEMENT PLANARCHITECTURALDA-101 FIFTH FLOOR DEMOLITIONDA-111 FIFTH FLOOR CEILING DEMOLITION PLANA-101 FIFTH FLOOR PLANA-101A FIFTH FLOOR PLAN - ALTERNATESA-102 SIXTH, SEVENTH AND EIGHTH FLOOR PLANSA-111 FIFTH FLOOR REFLECTED CEILING PLANA-111A FIFTH FLOOR REFLECTED CEILING PLAN - ACCOUSTIC TREATMENTA-121 POWER & COMMUNICATIONS - FIFTH FLOOR PLANA-131 FIFTH FLOOR - FLOOR FINISH PLANA-141 FURNITURE & EQUIPTMENT PLAN - FIFTH FLOORA-301 INTERIOR ELEVATIONSA-302 INTERIOR ELEVATIONSA-410 BUILDING SECTIONSA-501 DETAILS IA-502 DETAILS IIA-503 DETAILS IIIA-541 MILLWORK DETAILSA-542 MILLWORK DETAILSA-601 DOOR AND GLAZING SCHEDULEA-602 DOOR AND GLAZING DETAILSA-603 FINISH SCHEDULE & PARTITION TYPESA-700 INTERIOR 3D VIEWSFIRE PROTECTIONFP-000 GENERAL NOTES, SYMBOLS LIST AND DETAILS - FPFP-100 PARTIAL FIFTH FLOOR DEMOLITION PLAN - FPFP-200 PARTIAL FIFTH FLOOR PLAN - FIRE PROTECTIONPLUMBINGP-000 GENERAL NOTES, SYMBOLS LIST, AND SCHEDULES - PLUMBING P-100 PARTIAL FIFTH FLOOR DEMOLITION PLAN - PLUMBINGP-200 PARTIAL FIFTH FLOOR PLAN - PLUMBINGP-201 PENTHOUSE PLAN - PLUMBINGELECTRICALE-000 GENERAL NOTES & SYMBOLS LISTE-100 PARTIAL FIFTH FLOOR PLAN - POWER & SPECIAL SYSTEMSDEMOLITIONE-101 PARTIAL FIFTH FLOOR PLAN - LIGHTING DEMOLITIONE-200 PARTIAL FIFTH FLOOR PLAN - POWER NEW WORKE-201 PARTIAL FIFTH FLOOR PLAN - LIGHTING NEW WORKE-202 PARTIAL FIFTH FLOOR PLAN - SPECIAL SYSTEMS NEW WORKE-203 PARTIAL FIFTH FLOOR PLAN - FIRE ALARM NEW WORKE-204 PENTHOUSE ELECTRICAL - NEW WORKE-400 ELECTRICAL DETAILSE-500 ELECTRICAL SCHEDULESMECHANICALH-000 GENERAL NOTES & SYMBOLS LIST - HVACH-100 PARTIAL FIFTH FLOOR PLAN - DUCTWORK DEMOLITION H-101 PARTIAL FIFTH FLOOR PLAN - PIPING DEMOLITIONH-200 PARTIAL FIFTH, SIXTH & SEVENTH FLOOR PLANS - DUCT H-201 PARTIAL FIFTH, SIXTH & SEVENTH FLOOR PLANS - PIPING H-300 PARTIAL PENTHOUSE PLANS - HVACH-400 PIPING SCHEMATICS - HVACH-500 CONTROL SCHEMATICS & SYSTEM SUMMARIESH-501 CONTROL SCHEMATICS & SYSTEM SUMMARIESH-502 CONTROL SCHEMATICS & SYSTEM SUMMARIESH-600 DETAILS - HVACH-700 AIR HANDLING UNIT DIMENSIONS & DETAILS - HVACH-800 SCHEDULES - HVACSTRUCTURALS001 DESIGN DATA AND GENERAL NOTESS100 PARTIAL FRAMING PLANS
CB
CB
CB
CB
UPSON HALL2045GRUMMAN HALL2043UPSON AUTO SHOP 2045ARHODES DRIVEWARD CENTER2061SYMBOLS:KEYNOTEDETAILSECTIONELEVATIONSVERTICAL ELEVATIONPARTITION TYPE (SEE A-602 FOR DETAILS)ACCESSORY TYPEDOOR NUMBERREVISION NUMBERROOM NUMBERALIGNING SURFACES???01A-000000.00'FINISH FL.A1012431A1?1011001T-1ALIGNLEGENDEXISTING WALL TO REMAINNEW INTERIOR PARTITIONNEW 1-HR RATED PARTITIONNEW 2-HR RATED PARTITIONNEW FIXED FURNITURE/ CASEWORKEXISTING WALL PARTITION TO BE DEMOLISHEDABBREVIATIONS:&AND@ATAASSOCIATEACALTERNATING CURRENT/ACOUSTICALA/CAIR CONDITIONINGACMASBESTOS CONTAINING MATERIALACTACOUSTICAL CEILING TILEADAREA DRAINADJADJUSTABLE/ADJACENTAFACCESS FLOORAFFABOVE FINISH FLOORALTALTERNATEALUM ALUMINUMAMPAMPEREANOD ANODIZEDAPACCESS PANELAPPD APPROVEDARCH ARCHITECT/ARCHITECTURALASPH ASPHALTASYM ASYMMETRICALAVBAIR & VAPOR BARRIERAVGAVERAGEBBBUILDING BOARDBDBOARDBLDG BUILDINGBLKG BLOCKINGBMBEAM/BENCH MARKB.O.BY OTHERSBRKBRICKBSMT BASEMENTBTMBOTTOMBTWBETWEENBURBUILT UP ROOFINGBVLBEVELCABCABINETC.C.CENTER TO CENTERCERCERAMICCFMCUBIC FEET PER MINUTECJCONTROL JOINTCLCLOSERCLGCEILINGCLRCLEARCMUCONCRETE MASONRY UNITC.O.CASED OPENINGCOL(S) COLUMN(S)COMM COMMUNICATIONCONC CONCRETECOND CONDUITCONF CONFERENCECONN CONNECTION(S)CONSTR CONSTRUCTIONCONT CONTINUOUSCOORD COORDINATECORR CORRIDORCPCIRCUIT PANELCPTCARPETCRCOLD ROLLEDCRSCOURSE(S)CSOCASED OPENINGCTCERAMIC TILECTAICOOLING TOWER AIR INTAKECTRCENTERCUCUBICCWCOLD WATERCYCOPYDDEEP/DEPTHDBLDOUBLEDCDIRECT CURRENTDEMO DEMOLITIONDETDETAILDFDRINKING FOUNTAINDIADIAMETER/DIAGONALDIMDIMENSIONDISPDISPENSERDLDEAD LOADDNDOWNDODOOR OPENINGDRDOORDWGDRAWINGEEAST(E)EXISTING TO REMAINEAEACHECEMPTY CONDUITEECEXISTING EXPOSED CONSTRUCTIONEFEXHAUST FANEIFSEXTERIOR INSULATION FINISH SYSTEMELELEVATION(S)ELEC ELECTRICALELEV ELEVATOREMEMERGENCYEMTELECTRICAL METALLIC TUBINGENCL ENCLOSUREEQEQUAL(ER)EXIST. TO BE REMOVED(ERR) EXIST. TO BE REMOVED & RELOCATEDEWCELECTRICAL WATER COOLEREXHEXHAUSTEXIST,EX EXISTINGEXP BT EXPANSION BOLTEXP JT EXPANSION JOINTEXTEXTERIORFFILEFAFIRE ALARMFDFLOOR DRAINFEFIRE EXTINGUISHERFECFIRE EXTINGUISHER CABINETFHCFIRE HOSE CABINETFINFINISHFIXTFIXTUREFLRFLOORFLUOR FLUORESCENTF.O.FACE OFFPFIRE PROOFFPSC FIRE PROOF SELF CLOSINGFPBFIRE PULL BOXFRFRAMEFSPFIRE STANDPIPEFTFOOTFTGFOOTINGFWCFABRIC WALL COVERINGGAGAUGEGALV GALVANIZEDGBLK GYPSUM BLOCKGCGENERAL CONTRACTORGFIGROUND FAULT INTERRUPTERGLGLASSGR,GD GRADEGWBGYPSUM WALLBOARDGYPGYPSUMHBHOSE BIBBHCHANDICAPPEDHMHOLLOW METALHDWHARDWAREHDWD HARDWOODHORIZ HORIZONTALHPHIGH POINTHPLHIGH PRESSURE LAMINATEHRHOURHTHEIGHTHTGHEATINGHVAC HEATING, VENTILATION, AIR CONDITIONINGHVPHIGH VOLTAGE PANELHWHOT WATERIBCINSTALL BY CONTRACTORIBOINSTALL BY OWNERIDINSIDE DIAMETERINCLINCLUDE/INCLUDINGINSUL INSULATIONINTINTERIORJBOX JUNCTION BOXJSJAMB SWITCHJTJOINTKWKILOWATTLACLACQUERLAMLAMINATELAVLAVATORYLBSPOUNDSLFLINEAR FEETLHLEFT HANDLHRB LEFT HAND RETURN BEVELLLLIVE LOADLSCLOCKSET CYLINDRICALLSMLOCKSET MORTISEDLDLINEAR DIFFUSERLTLIGHTLVLOUVERLVPLOW VOLTAGE PANELMAGMAGNETICMARB MARBLEMASMASONRYMAXMAXIMUMMCMAIL CHUTEMEZZ MEZZANINEMFRMANUFACTURERMINMINIMUMMISCMISCELLANEOUSMLDG MOLDINGM.O.MASONRY OPENINGMOD-BIT MODIFIED BITUMINOUS ROOFINGMPMEASURE POINT / MASONRY PAINTMTDMOUNTEDMTLMETALMULMULLIONNNORTH/NEWNATNATURALNECNEW EXPOSED CONSTRUCTIONNICNOT IN CONTRACTNONUMBERNOMNOMINALNRNOISE REDUCTIONNRCNOISE REDUCTION COEFFICIENTNTSNOT TO SCALEOCON CENTERODOUTSIDE DIAMETEROHOPPOSITE HANDOPPOPPOSITEPART PARTITIONPCPL PORTLAND CEMENT PLASTERPGLPLATE GLASSPBOPROVIDED BY OWNERPLFPOUNDS PER LINEAR FOOTPLAM PLASTIC LAMINATEPLAS PLASTERPSIPOUNDS PER SQUARE INCHPTPAINTPTDPAINTEDPTGPAINTINGPTDR PAPER TOWEL DISPENSERPTRPAPER TOWEL RECEPTACLEPVCPOLYVINYL CHLORIDEPWDPLYWOODR/ARETURN AIRRADRADIUSRBRUBBER BASERDROOF DRAIN(RE)RELOCATED EXISTINGRCPREFLECTED CEILING PLANREFREFRIGERATORREINREINFORCING/REINFORCEDREQD REQUIREDRHRIGHT HANDRHRB RIGHT HAND REVERSE BEVELRMROOMROROUGH OPENINGRUBRUBBERSSOUTH/SUPPLYSAFB SOUND ATTENUATION FIRE BATTSBSTRAIGHT BASESCSEPARATE CIRCUIT/SELF CLOSINGSCHSCHEDULESEAL SEALANTSIMSIMILARSLCSOLID CORESNDSANITARY NAPKIN DISPOSALSNVSANITARY NAPKIN VENDORSPEC SPECIFICATIONSQSQUARESSSTAINLESS STEELSTDSTANDARDSTLSTEELSTNSTAINSTRUCT STRUCTURESUBSUBSTITUTESUSP SUSPENDEDSVCSERVICESYMSYMMETRICALSYSSYSTEMTBTOWEL BARTBDTO BE DETERMINEDTDTRENCH DRAINTELTELEPHONETGLTEMPERED GLASST>ONGUE & GROOVETHTHRESHOLDTHRU THROUGHTHKTHICK/THICKNESSTLTILET.O.TOP OFT.O.S. TOP OF SLABTPDTOILET PAPER DISPENSERTSTILE STARTTYPTYPICALU.O.N. UNLESS OTHERWISE NOTEDVVOLTVBVINYL BASEVCTVINYL COMPOSITE TILEVERT VERTICALVIFVERIFY IN FIELDVNRVENEERV. PLAS VENEER PLASTERVTVINYL TILEWWEST/WATTW/WITHWCWATER CLOSETWDWOODWFWIDE FLANGEWPWATER PROOFWRWASTE RECEPTACLEWSWET STACKWWF WELDED WIRE FABRICWWM WELDED WIRE MESHYDYARDDUMPSTER LOCATION 2COORDINATE WITH EXISTINGIN-GROUND TANKDUMPSTER LOCATION 1PARKING SPOT LIMITEDTO 10 YARDS OR LESSRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedSYMBOLS, NOTES &ABBREVIATIONST-002N.T.S1SITE PLAN1/32" = 1'-0"3STAGING PLAN
2010 ADAAG FIG. 302.32017 ICC A117.1 FIG. 302.3ELONGATED OPENINGS IN FLOOR OR GROUND SURFACES2010 ADAAG FIG. 303.22017 ICC A117.1 FIG. 303.2VERTICAL CHANGE IN LEVEL2010 ADAAG FIG. 303.32017 ICC A117.1 FIG. 303.3(A) & 303.3(B)BEVELED CHANGE IN LEVELDOMINANT DIRECTION OF TRAVELLONG DIMENSIONPERPENDICULAR TO DOMINANTDIRECTION OF TRAVEL1/2" MAX.1/4" MAX.MAX.1/4"MAX.1/4"1/2" MAX.21211/4"-1/2"(A)(B)SIZE OF TURNING SPACE2010 ADAAG FIG. 304.3.22017 ICC A117.1 FIG. 304.3.1.1, 304.3.1.2, & 304.3.2.1(A), (B) & (C)CLEAR FLOOR OR GROUND SPACE2010 ADAAG FIG. 305.32017 ICC A117.1 FIG. 305.3.1 & 305.3.236" MIN.X > 24"60" MIN.X > 15"NOTE: ALCOVES SHALL BE 36 INCHES WIDE MINIMUM WHERE THE DEPTH EXCEEDS 24 INCHES.NOTE: ALCOVES SHALL BE 60 INCHES WIDE MINIMUM WHERE THE DEPTH EXCEEDS 15 INCHES. MANEUVERING CLEARANCE IN AN ALCOVE, FORWARD APPROACH2010 ADAAG FIG. 305.7.12017 ICC A117.1 FIG. 305.7.2MANEUVERING CLEARANCE IN AN ALCOVE, PARALLEL APPROACH2010 ADAAG FIG. 305.7.22017 ICC A117.1 FIG. 305.7.1CLEAR WIDTH OF AN ACCESSIBLE ROUTE2010 ADAAG FIG. 403.5.12017 ICC A117.1 FIG. 403.5.1(A) & (C)POSITION OF CLEAR FLOOR OR GROUND SPACE2010 ADAAG FIG. 305.52017 ICC A117.1 FIG. 305.5(A) & (B)FORWARDPARALLEL67" MIN.*60" MIN.CIRCULAR52" MIN.*48" MIN.MIN.30"*REQUIREMENT FOR NEW BUILDING68" MIN.36" MIN.60" MIN.16" MIN.36" MIN.8" MIN.8" MIN.24" MIN.16" MIN.T-SHAPED NEW BUILDING -OPTION 1T-SHAPEDEXISTING BUILDING60" MIN.36" MIN.MIN.24"MIN.12"MIN.36"MIN.12"60" MIN.64" MIN.38" MIN.60" MIN.11" MIN.42" MIN.11" MIN.22" MIN.64" MIN.40" MIN.60" MIN.12" MIN.40" MIN.12" MIN.20" MIN.T-SHAPED NEW BUILDING -OPTION 2T-SHAPED NEW BUILDING -OPTION 3*REQUIREMENT FOR NEW BUILDING*REQUIREMENT FOR NEW BUILDINGMAX.24"52" MIN.*48" MIN.MAX.24"36" MIN.32" MIN.TOE CLEARANCEELEVATION2010 ADAAG FIG. 306.22017 ICC A117.1 FIG. 306.2(A) & (B)9"6" MAX.30" MIN.17"-25"PLAN*27" MIN.11" MIN.9" MIN.8" MIN.30" MIN.25" MAX.PLAN*KNEE CLEARANCE FOR CHILDREN SHALL BE 24" MIN.KNEE CLEARANCEELEVATION2010 ADAAG FIG. 306.32017 ICC A117.1 FIG. 306.3(A) & (B)X > 80"MAX.4"X > 27"27" MAX.X > 12"NOTE: WHERE AN OBSTRUCTION IS MOUNTED BETWEEN POSTS, AND THE CLEAR DISTANCE BETWEEN POSTS IS GREATER THAN 12", THE LOWEST EDGE OF SUCH OBSTRUCTION SHALL BE 27" MAX. OR 80" MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE.LIMITS OF PROTRUDING OBJECTS2010 ADAAG FIG. 307.22017 ICC A117.1 FIG. 307.2POST MOUNTED PROTRUDING OBJECTS2010 ADAAG FIG. 307.32017 ICC A117.1 FIG. 307.3(A) & (B)27" MAX.X < 80"VERTICAL CLEARANCE2010 ADAAG FIG. 307.42017 ICC A117.1 FIG. 307.4NOTE: GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED WHERE THE VERTICAL CLEARANCE IS LESS THAN 80" HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR BARRIER SHALL BE LOCATED 27" MAXIMUM ABOVE THE FINISHED FLOOR OR GROUND.> 27" AND < 80"POSTMAX.*4"MAX.*4"27"-80"4" MAX.4" MAX.X < 12"X > 12".>80"UNLIMITED20" MAX.48" MAX.MAX.>20" - 25"44" MAX.NOTE: - WHERE REACH DEPTH EXCEEDS 20", THE HIGH FORWARD REACH SHALL BE 44" MAX. IN HEIGHT, AND THE REACH DEPTH SHALL BE 25" MAXIMUM.NOTES: - WHERE REACH DEPTH EXCEEDS 10", THE HIGH SIDE REACH SHALL BE 46" MAXIMUM, FOR A REACH DEPTH OF 24" MAXIMUM.- OPERABLE PARTS SHALL COMPLY WITH SECTION 309.34" MAX.48" MAX.10" MAX.34" MAX.46" MAX.MAX.>10" - 24"OBSTRUCTED HIGH FORWARD REACH2010 ADAAG FIG. 308.2.22017 ICC A117.1 FIG. 308.2.2(A) & (B)OBSTRUCTED HIGH SIDE REACH2010 ADAAG FIG. 308.3.22017 ICC A117.1 FIG. 308.3.2ADULT15" MIN.ADULT48" MAX.AGE 5-818" MIN.*AGE 9-1216" MIN.*AGE 5-8"40" MAX.*AGE 9-1244" MAX.*UNOBSTRUCTED FORWARD REACH2010 ADAAG FIG. 308.2.12017 ICC A117.1 FIG. 308.2.1*THIS IS AN ADVISORY REQUIREMENT FOUND ONLY IN 2010 ADAAG.2010 ADAAG FIG. 308.3.12017 ICC A117.1 FIG. 308.3.110" MAX.MIN.15"48" MAX.UNOBSTRUCTED SIDE REACHMIN.22"42" MIN. **MIN.*12"*IF BOTH A CLOSER AND A LATCH ARE PROVIDED**48" MIN. IF BOTH A CLOSER AND A LATCH ARE PROVIDED***2017 ICC A117.1 REQUIRES ADDITIONAL 12" MANEUVERING CLEARANCE BEYOND LATCH SIDE (NOT REQUIRED BY 2010 ADAAG) AND THEREFORE PROVIDES GREATER ACCESSIBILITY.HINGE APPROACH, PUSH SIDE***MANEUVERING CLEARANCE (MANUAL SWING DOORS & GATES)2010 ADAAG FIG.404.2.4.12017 ICC A117.1 FIG.404.2.3.2(A), (B), (C), (D), (E), (F), (G), & (H)90.00°32" MIN.32" MIN.32" MIN.> 24"36" MIN.HINGED DOORSLIDING DOORFOLDING DOORDOORWAYS WITHOUT DOORSNOTE:- CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.- OPENINGS MORE THAN 24" IN DEPTH AT DOORS AND DOORWAYS WITHOUT DOORS SHALL PROVIDE A CLEAR OPENING WIDTH OF 36" MIN.CLEAR WIDTH OF DOORWAYS2010 ADAAG FIG.404.2.3(A), (B), & (C)2017 ICC A117.1 FIG.404.2.2(A), (B), (C), & (D)SIDE APPROACH- STRICTER 2010 ADAAG REQUIREMENTS (NOT REQUIRED BY 2017 ICC A117.1)52* MIN.*48" MIN.FRONT APPROACHMANEUVERING CLEARANCE AT DOORWAYS WITHOUT DOORS2010 ADAAG FIG.404.2.4.22017 ICC A117.1 FIG.404.2.3.4(A), (B), & (C)MIN.22"42" MIN.MIN.24"42" MIN.POCKET OR HINGE APPROACH STOP OR LATCH APPROACH18" MIN.60" MIN.FRONT APPROACH, PULL SIDEHINGE APPROACH, PULL SIDE60" MIN.36" MIN.HINGE APPROACH, PULL SIDE 54" MIN.42" MIN.*REQUIREMENT FOR NEW BUILING48" MIN.12" MIN.52" MIN.*48" MIN.FRONT APPROACH, PUSH SIDE (NO CLOSER AND LATCH)FRONT APPROACH, PUSH SIDE (WITH CLOSER AND LATCH) LATCH APPROACH, PUSH SIDE (NO CLOSER)MIN.24"42" MIN.LATCH APPROACH, PUSH SIDE(WITH CLOSER)MIN.24"48" MIN.LATCH APPROACH, PULL SIDE (NO CLOSER)LATCH APPROACH, PULL SIDE (WITH CLOSER)48" MIN.24" MIN.54" MIN.MIN.24"42" MIN.X > 8"MIN.18"60" MIN.48" MIN.*X > 8"X > 8"MIN.12"48" MIN.*MANEUVERING CLEARANCES AT RECESSED DOORS AND GATES2010 ADAAG FIG.404.2.4.32017 ICC A117.1 FIG.404.2.3.5(A), (B), & (C)PULL SIDEPUSH SIDEPUSH SIDE (WITH CLOSER AND LATCH)NOTE:- MANEUVERING CLEARANCES FOR FORWARD APPROACH SHALL BE PROVIDED WHEN ANY OBSTRUCTION WITHIN 18" OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE THAN 8" BEYOND THE FACE OF THE DOOR, MEASURED PERPENDICULAR TO THE FACE OF THE DOOR OR GATE.*52" MIN. FOR NEW BUILDINGDOOR AND GATES IN SERIES* -EXISTING BUILDING2010 ADAAG FIG.404.2.62017 ICC A117.1 FIG.404.2.5(A),(B),(C),(D),(E), & (F)*2017 ICC A117.1 REQUIRES ADDITIONAL 60" CLEAR WIDTH WHERE 2010 ADAAG DOES NOT REQUIRE MIN. WIDTH.**2010 ADAAG REQUIRES 48" MINIMUMWIDTHDOOR48" MIN.WIDTHDOOR60" MIN.*60" MIN.*60" MIN.**48" MIN.WIDTHDOOR60" MIN.*ELECT.OUTLET TELE/DATA JACKWALL MTD. T.V.MONITOR1' - 6"6' - 6"FIRE EXTINGUISHERCABINET3' - 0"NOTE: - THESE DIMENSIONS ARE TYPICAL MOUNTING HEIGHTS. REFER TO ELEVATIONS FOR SPECIFIC LOCATIONS AND HEIGHTS.- DEVICES THAT ARE NEAR ONE ANOTHER SHALL BE ALIGNED VERTICALLY AND/OR HORIZONTALLYMAX.4' - 0"FIRE WARDENFLOOR STATION4' - 0"FA PULL STATION3' - 10"CARDREADER3' - 2"LIGHT SWITCH3' - 10"FA DEVICES80"-96"EXITOF SIGNOF DOOROF LEVERLCLCLCROOM ID SIGN4' - 6" MIN.9"LCLCFIRE ALARM / STROBE80"-96"LIGHT SWITCH3' - 10"OUTLET1' - 6"THERMOSTAT5' - 0"6"LCFINISHED FLOORNOTE: - WHERE A TACTILE SIGN IS PROVIDED AT A DOOR, THE SIGN SHALL BE LOCATED ALONGSIDE THE DOOR AT THE LATCH SIDE. WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH TWO ACTIVE LEAFS, THE SIGNSHALL BE LOCATED TO THE RIGHT OF THE RIGHT HAND DOOR. WHERE THERE IS NO WALL SPACE AT THE LATCH SIDE OF A SINGLE DOOR OR AT THE RIGHT SIDE OF DOUBLE DOORS, SIGNS SHALL BE LOCATED ON THE NEAREST ADJACENT WALL.- SIGNS CONTAINING TACTILE CHARACTERS SHALL BE LOCATED SO THAT ACLEAR FLOOR SPACE OF 18" MIN. BY 18" MIN. CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE ARC OF ANY DOOR SWING BETWEEN THE CLOSED POSITION AND 45 DEG. OPEN POSITION.EXCEPTION: SIGNS WITH TACTILE CHARACTERS SHALL BE PERMITTED ON THE PUSH SIDE OF DOORS WITH CLOSERS AND WITHOUT HOLD-OPEN DEVICES.LOCATION OF TACTILE SIGNS AT DOORS2010 ADAAG FIG. 703.4.22017 ICC A117.1 FIG. 703.3.1145.00°LCMIN.18"MIN.18"CENTERED ON RAISED CHARACTERSRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedACCESSIBILITY NOTES &DETAILST-00312" = 1'-0"1OPENINGS AND CHANGES IN FLOOR OR GROUND SURFACES1/4" = 1'-0"2WHEELCHAIR TURNING RADIUS AND FLOOR CLEARANCE1/2" = 1'-0"3CLEARANCE AND ONSTRUCTIONS1/4" = 1'-0"4DOORS AND OPENINGS1/4" = 1'-0"5TYPICAL MOUNTING HEIGHTSGENERAL NOTES:- THE DETAILS ON SHEETS T-003 COMBINE THE REQUIREMENTS OF ICC A117.1 - 2017 AND THE 2010 ADAAG STANDARDS.- THE TEXT OF ICC A117.1 - 2017 AND THE 2010 ADAAG PREVAILS OVER DRAWN FIGURES.- WHERE THE NOTATIONS ON T-003 INDICATE A DIFFERENCE BETWEEN THE REQUIREMENTS OF THE 2010 ADAAG AND ICC A 117.1 - 2017, FOLLOW THE MORE RESTRICTIVE STANDARD UNLESS INDICATED OTHERWISE. 1/4" = 1'-0"6LOCATION OF TACTILE SIGNS AT DOORS
LEGEND:AREA OF WORK, UNLESS OTHERWISE NOTED1 HOUR RATED WALL2 HOUR RATED WALLCODES & STANDARDS2020 NYS EXISTING BUILDING CODE (NYSEBC)2020 NYS BUILDING CODE (NYSBC)2020 NYS MECHANICAL CODE (NYSMC)2020 NYS PLUMBING CODE (NYSPC)2020 NYS FIRE CODE (NYSFC)2020 NYS ENERGY CONSERVATION CONSTRUCTION CODE (NYSECCC)NYS UNIFORM FIRE PREVENTION CODENATIONAL FIRE PROTECTION ASSOCIATION STANDARDS (NFPA)AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR CONDITIONING ENGINEERS (ASHRAE) STANDARD CORNELL UNIVERSITY'S, DESIGN AND CONSTRUCTION STANDARDSFM GLOBAL DATA SHEETSNATIONAL ELECTRICAL CODE (NEC)OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA)AMERICAN NATIONAL STANDARDS INSTITUTE CODE (ANSI)AUTHORITY HAVING JURISDICTIONCITY OF ITHACA, NYWORK LEVELALTERATION TYPE II (WORK AREAS IS UNDER 50% OF THE FLOOR AREA)CONSTRUCTION TYPEIB (EXISTING CONSTRUCTION)FIRE-RESISTANCE RATINGS FOR BUILDING ELEMENTS:STRUCTURAL FRAME: 2 HOURSEXTERIOR BEARING WALL:2 HOURSINTERIOR BEARING WALL:2 HOURSEXTERIOR NONBEARING WALLS AND PARTITIONS:1 HOURINTERIOR NONBEARING WALLS AND PARTITIONS:0 HOURFLOOR CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:2 HOURSROOF CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:1 HOURUSE TYPEB- BUSINESS (PROJECT AREA) NO CHANGEOCCUPANCY & EGRESS NOTES: (2020 BUILDING CODE OF THE STATE OF NEW YORK)1004OCCUPANT LOADTABLE 1004.5 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANTFUNCTION OF SPACEOCCUPANT LOAD FACTORACCESSORY300 SF GROSSBUSINESS150 SF NETCONFERENCE 15 SF NETASSEMBLY (SEE SECTION 1004.6 FIXED SEATING) LOUNGE 150 SF NETSHOP 50 SF NETPROJECT AREA IS INCLUDED IN BUSINESS - 12,783 SF GROUP BELOW AREA PER DESIGN ROOM #/NAME AREA OCCUPANT OCCUPANT LOAD551 - LABORATORY 3,368 SF 150 SF23 TOTAL23FIFTH FLOOR TOTAL (EXISTING EXCPET SPACE NOTED ABOVE) AREA PER DESIGN OCCUPANT GROUPS AREA OCCUPANT OCCUPANT LOADACCESSORY 89 SF 300 SF 1ACCESSORY 168 SF 300 SF 1ACCESSORY 87 SF 300 SF 1BUSINESS 568 SF 150 SF 4BUSINESS 12,783 SF 150 SF86CONFERENCE693 SF 15 SF47CONFERENCE267 SF 15 SF18CONFERENCE218 SF 15 SF15EDUCATIONAL 2,403 SF 20 SF 121 LOUNGE451 SF 150 SF 4SHOP175 SF 50 SF 4SHOP670 SF 50 SF14SHOP454 SF 50 SF10SHOP388 SF 50 SF 8TOTAL 3341005.3.2 OTHER EGRESS COMPONENTSTHE CAPACITY, IN INCHES, OF MEANS OF EGRESS COMPONENTS OTHER THAN STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF EGRESS CAPACITY FACTOR OF 0.2 INCH PER OCCUPANT.STAIR # PROVIDED INCH PER DOOR DESIGN OCCUPANTDOOR WIDTH OCCUPANT CAPACITY LOAD5th FLOOR STAIR #1 40" 0.2 200111STAIR #2 40" 0.2 200111STAIR #3 40"0.2 2001125th FLOOR TOTAL DOOR CAPACITY = 600 > 3344th FLOOR STAIR #1 40" 0.2 200STAIR #2 40" 0.2 200STAIR #3 40"0.2 2004th FLOOR TOTAL DOOR CAPACITY = 600 > 3rd FLOOR STAIR #1 40" 0.2 200STAIR #2 40" 0.2 200STAIR #3 40"0.2 2003rd FLOOR TOTAL DOOR CAPACITY = 600 > 2nd FLOOR STAIR #1 40" 0.2 200STAIR #2 40" 0.2 200STAIR #3 40"0.2 2002nd FLOOR TOTAL DOOR CAPACITY = 600 > 1006NUMBER OF EXITS AND EXIT ACCESS DOORWAYSTABLE 1006.3.2 MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS PER STORYOCCUPANT LOAD PER STORY MIN. NUMBER OF EXITS 1 - 5002501 - 1,00033 EXITS PROVIDED (EXISTING, NO CHANGE)1009ACCESSIBLE MEANS OF EGRESS1009.3.2 STAIRWAY WIDTHSTAIRWAYS SHALL HAVE A CLEAR WIDTH OF 48 INCHES MINIMUM BETWEEN HANDRAILSEXCEPTION: 1. THE CLEAR WIDTH OF 48 INCHES BETWEEN HANDRAILS IS NOT REQUIRED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM.1010DOORS, GATES AND TURNSTILES1010.1.1 SIZE OF DOORSTHE REQUIRED CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM CLEAR OPENING WIDTH OF 32 INCHES. THE CLEAR OPENING WIDTH OF DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.1011STAIRWAYS1011.2 WIDTH AND CAPACITYTHE REQUIRED CAPACITY OF STAIRWAYS SHALL BE DETERMINED AS SPECIFIED IN SECTION 1005.1, BUT THE MINIMUM WIDTH SHALL BE NOT LESS THAN 44 INCHES.1017EXIT ACCESS TRAVEL DISTANCETABLE 1017.2 EXIT ACCESS TRAVEL DISTANCEOCCUPANCY WITHOUT SPRINKLER SYSTEM WITH SPRINKLER SYSTEM B200 FEET300 FEET5th FLOOR PRIMARY TRAVEL DISTANCE = 110'-8"SECONDARY TRAVEL DISTANCE = 182'-6"BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM.1005MEANS OF EGRESS SIZING1005.3.1 STAIRWAYSTHE CAPACITY, IN INCHES, OF MEANS OF EGRESS STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH STAIRWAYS BY A MEANS OF EGRESS CAPACITY FACTOR OF 0.3 INCH PER OCCUPANTSTAIR # EXISTING INCH PER STAIR DESIGN OCCUPANTSTAIR WIDTH OCCUPANT CAPACITY LOAD5th FLOOR STAIR #1 50"0.3 166111STAIR #2 50"0.3 166111STAIR #3 45"0.3 1501125th FLOOR TOTAL STAIR CAPACITY = 482 >3344th FLOOR STAIR #1 50"0.3 166STAIR #2 50"0.3 166STAIR #3 45"0.3 1504th FLOOR TOTAL STAIR CAPACITY = 482 >3rd FLOOR STAIR #1 50"0.3 166STAIR #2 50"0.3 166STAIR #3 45"0.3 1503rd FLOOR TOTAL STAIR CAPACITY = 482 >2nd FLOOR STAIR #1 50"0.3 166STAIR #2 50"0.3 166STAIR #3 45" 0.3 1502nd FLOOR TOTAL STAIR CAPACITY = 482 >GF8FEDCBA1234567G5H5X1K111098121314JJ17161518HY1HXYLABORATORY551551B59'-0"65'-0"52'-0"24'-6"41'-0"TOTAL DISTANCE: 182'-6"42'-0"9'-8"TOTAL DISTANCE: 110'-8"59STAIR #3STAIR #2DOOR STAIR WIDTH 40" 50"CAPACITY 200 166LOAD 111 111DOOR STAIR WIDTH 40"50"CAPACITY 200166LOAD 112112DOOR 551/1 REQUIRED PROVIDEDWIDTH 32"36"CAPACITY 160180LOAD12DOOR 551/3 REQUIRED PROVIDEDWIDTH 32"68"CAPACITY 160340LOAD11STAIR #1DOOR STAIR WIDTH 40" 50"CAPACITY 200 166LOAD 111 111111501503500502504504A522524A524525527526528529531530532533535534536537539538541520518516514B523521A521519517508512514571Department LegendACCCESORYASSEMBLYBUSINESSCONFERENCELOUNGESHOP572574576578580596594592590588586584582BUSINESS12,783 SF86 PEOPLEEDUCATIONAL2,403 SF120 PEOPLECONFERENCE218 SF15 PEOPLESHOP454 SF10 PEOPLESHOP388 SF8 PEOPLECONFERENCE267 SF18 PEOPLECONFERENCE693 SF47 PEOPLESHOP670 SF14 PEOPLESHOP175 SF4 PEOPLEBUSINESS568 SF4 PEOPLEOCCUPANCY LEGENDACCESSORY87 SF1 PEOPLEACCESSORY168 SF1 PEOPLEACCESSORY89 SF1 PEOPLELOUNGE235 SF5 PEOPLEKEY NOTES:1TEMPORARY PARTITION AND DOOR. FIRE RATED TO MATCH ADJACENT CONSTRUCTION.Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedAREA OF WORK & CODEINFORMATIONT-004ALTERNATE DESCRIPTIONALTERNATE 1ADDITIONAL FIRE RATED GLAZING IN CORRIDOR WALL 50044ALTERNATE 2PROVIDE SOFFIT ALONG COL. LINE D AND INSTALL SLIDING GLASS WHITEBOARDS ON BARN DOOR STYLE HARDWARE ACROSS THE OPENING. ALTERNATE 3PROVIDE A FOLDABLE ACOUSTICAL PANEL WALL (WITH ONE SWING DOOR) ALONG COL. LINE D. ALTERNATE 4PROVIDE A SOLID STUD AND GYPSUM BOARD WALL WITH HOLLOW METAL FRAME AND DOOR ALONG COL. LINE D. PROVIDE POWER AND DATA IN THE WALL, BOTH SIDES. 1/16" = 1'-0"1CODE INFORMATION - LEVEL 5
UPUPUPTGBCPABCDEFBFBFBFBFBFBGF8FEDCBA1234567G5H5X1K111098121314HX18' - 6 3/16"22' - 8"22' - 8"22' - 8"22' - 8"14' - 4 5/16"4' - 1 7/8"18' - 6 3/16"22' - 8"22' - 8"22' - 8"22' - 8"18' - 6 5/8"1' - 7 5/8"1' - 7 5/8"1' - 7 5/8"EQEQTERRACE517514B519518521A520523500502504504A503501512514500765007350044578576574572500635006250061508516521GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS580DATACLOSET552ELEC.CLOSET50075LOUNGE568WOMEN50021MEN50022GRAD.STUDENTS5961A-4102A-4101111223343333334433344446717588888884994877NOTE: NOISY WORK SHALL BE COORDINATED WITH THE LECTURE HALL SCHEDULE AND WILL NOT BE PERMITTED WHILE CLASS IS ON-GOING. SEE ALSO SPECIFICATIONS. 1010557A551551A55555750047559559A597DEMOLITION KEY NOTES:REMOVE EXISTING RAISED FLOOR SYSTEM SET ON 8" STEEL LEGS. LEGS ARE SET IN ADHESIVE, REMOVE ADHESIVE COMPLETELY FROM EXISTING CONCRETE SLAB. REMOVE EXISTING RAMP AND RAILINGS.REMOVE EXISTING DOOR, FRAME, AND HARDWARE AND WALL STRUCTURE TO DECK ABOVE. INDICATES EXISTING PARTITION TO BE REMOVED.EXISTING WINDOW TO BE REMOVED. REMOVE EXISTING DOOR, FRAME AND HARDWARE. SALVAGE FOR REINSTALLATION. PATCH AND REPAIR EXISTING WALL TO REMAIN. SALVAGE DOOR HOLD OPENS FOR REINSTALLATION.REMOVE EXISTING FLOOR FINISH (CARPET AND RUBBER BASE)REMOVE EXISTING SPRAY ON FIREPROOFING. PREPARE STEEL TO RECEIVE NEW INTUMESCENT COATINGREMOVE EXISTING RADIATOR COVERS.REMOVE WALL FOR INSTALLATION OF NEW ADA PUSH BUTTON.1 2 3 4 5 6 7 8 9 10 LEGENDEXISTING WALL TO REMAINDEMOLISHED ELEMENTREMOVE DOOR AND FRAMERevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/8" = 1'-0"FIFTH FLOOR DEMOLITIONDA-1011/8" = 1'-0"1DEMOLITION - LEVEL 5GENERAL DEMOLITION NOTES:1. REMOVE ALL EXISTING FLOOR FINISHES COMPLETELY (CARPET UNLESS NOTED AS RAISED FLOOR). 2. PREPARE EXISTING CONCRETE FLOOR SLAB AS REQUIRED TO RECEIVE NEW RESINOUS FLOOR FINISH. THIS INCLUDES BUT IS NOT LIMITED TO SHOT BLASTING OR OTHER MECHANICAL MEANS REQUIRED TO CREATE A LEVEL SURFACE AS DESCRIBED IN THE SPECIFICATIONS.
GF8FEDCBA1234567G5H5X1K111098121314HX1 1 1 1 1 2 3 4 LEGENDINDICATES EXISTING ACOUSTICAL CEILING TILE AND SUSPENSION SYSTEM TO BE DEMOLISHED, INCLUDES ALL CEILING MOUNTED LIGHTING AND DEVICES AND SUPPLY REGISTERS AND DIFFUSERS. EXISTING DUCTWORK AND CEILING MOUNTED EQUIPMENT TO REMAIN UNLESS OTHERWISE NOTED.DEMOLITION KEY NOTES:REMOVE EXISTING SOFFIT. EXISTING EXTERIOR WALL CONSTRUCTION, INSULATION, AND BRACING TO REMAIN.REMOVE EXISTING CEILING.REMOVE EXISTING ACCESS PANEL. REMOVE AND REINSTALL EXISTING ACT GRID AND TILE TO ACCOMMODATE THE NEW PARTITION INSTALLATION. 1 2 3 4 Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/8" = 1'-0"FIFTH FLOOR CEILINGDEMOLITION PLANDA-1111/8" = 1'-0"1DEMOLITION - LEVEL 5
UPUPUPGF8FEDCBA1234567G5H5X1K111098121314HX18' - 6 3/16"22' - 8"22' - 8"22' - 8"22' - 8"14' - 4 5/16"4' - 1 7/8"18' - 6 3/16"22' - 8"22' - 8"22' - 8"22' - 8"18' - 6 5/8"1' - 7 5/8"1' - 7 5/8"1' - 7 5/8"EQEQTERRACEGRAD.STUDENTS596GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS58057857657457250044LOUNGE568DATACLOSET552ELEC.CLOSET50075MEN50022WOMEN500215007350076512514508504A504502500503501517519521521A523520518516514B571503 SF505 SF1A-4102A-41042460 SF505 SF31503 SF51 1 1 11 11 11 11 3 4 4 11 11 11 11 44 SFSTORAGE551B551B15001LABORATORY551A14 6 7 7 A-30119 TYP.A-3013546A-5411A-5413A-5414A1A1551112 A-5011C113 13 13 B1A1D29 9 9 13 13 STORAGE551A551A1E15513B16A-502TYP.12 TYP.12 TYP.D1A-3021A-5013E1A-3017A-3018A-30122A-5022A-5022A-50210 10 A-5012A-5012SIM.TYP.2 50046STAIR# 3500035004050042STAIR# 250002500635006250061571AA-501455121' - 4"11' - 0"3' - 1"6' - 9"3' - 0"50021150022114 14 14 14 14 A11' - 4"A1EQEQTYP.TYP.TYP.1' - 1"ALIGNOF WALL AND COLUMN0' - 4"4' - 5"8' - 1"ALIGNKEY NOTES:FIXED WOOD LABORATORY CASEWORK, WOOD WITH EPOXY COUNTERTOP.PREPARE EXISTING CONCRETE FLOOR TO RECEIVE NEW FINISH, SEE ALSO A-131. WALL MOUNTED OPEN SHELVING BY LABORATORY CASEWORK MFR. SINK WITH COUNTERTOP MOUNTED EYEWASH.NOT USED.RELOCATED CORRIDOR DOOR, FRAME AND HARDWARE. NOT USED.INCLUDE PAINTED FLOOR MARKINGS, APPROXIMATELY 4" WIDE AND LOCATED ALONG THE COLUMN LINES IN THE PROJECT AREA.WIRE MESH DIVIDER CURTAIN. SUSPENDED FROM C CHANNEL TRACK WITH TROLLEY ACCESSORY. RECESSED FIRE EXTINGUISHER CABINET. 2-HOUR RATED INTUMESCENT COATING ON COLUMNS. PREPARE EXISTING STEEL TO RECEIVE COATINGREPLACE EXISTING RADIATOR COVERS. ADD END CAPS.NEW ROOM SIGNAGE. SEE .SURFACE MOUNTED STAINLESS STEEL CORNER GUARD, 8' TALL1 2 3 4 5 6 7 8 9 10 11 12 /1A-60313 14 LEGENDEXISTING WALL TO REMAINNEW INTERIOR PARTITIONNEW 1-HR RATED PARTITIONNEW 2-HR RATED PARTITIONNEW FIXED FURNITURE/ CASEWORKEXISTING WALL PARTITION TO BE DEMOLISHEDRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedFIFTH FLOOR PLANA-1011/8" = 1'-0"1LEVEL 5GENERAL NOTE:1. GRIND EXISTING CONCRETE SLAB, FILL ALL CRACKS WITH EPOXY SEALANT, AND PREPARE TO RECEIVE SPECIFIED FINISH. 2. PAINT ALL WALLS AND EXPOSED CEILING ELEMENTS IN THE PROJECT AREA. PAINT ALL WALLS IN EXISTING CORRIDOR 50044. 3. REFER TO SHEET A-141 FOR LOOSE FURNITURE PLAN
UPUPGF8FEDCBA234567G5H5X1K111098121314HX1A-4102A-41018' - 6 3/16"22' - 8"22' - 8"22' - 8"22' - 8"14' - 4 5/16"4' - 1 7/8"22' - 8"22' - 8"22' - 8"22' - 8"18' - 6 5/8"1' - 7 5/8"EQEQTERRACEGRAD.STUDENTS596GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS58057857657457250044LOUNGE568DATACLOSET552ELEC.CLOSET50075MEN50022WOMEN500215007350076512514508504A504502500503501517519521521A523520518516514B571503 SF505 SF42460 SF505 SF31503 SF5ALTERNATE 1: GLAZED WALL PARTITION.ALTERNATE 2: MOVABLE BARN-DOOR STYLE WHITE BOARDS. OPENING HEIGHT 8'-2". 3'-6" X 8'-0" PANELS BY CLARIDGE OR SIMILAR. A-3024STORAGE551BA-3023LABORATORY551LABORATORY597551150046STAIR# 3500035004050042STAIR# 250002500635006250061571ASTORAGE597A5512Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/8" = 1'-0"FIFTH FLOOR PLAN -ALTERNATESA-101A1/8" = 1'-0"1LEVEL 5 - ALTERNATE 2
DNDNDNUPDNGF8FEDCBA1234567G5H5X1K111098121314HX657B657A653653A65466860075652655627657658651REMOVE AND REINSTALL NEW 2 HOUR RATED SHAFT CONSTRUCTION TO ACCOMMODATE INSTALLATION OF NEW DUCTWORK . SEE PARTITION C1.GF8FEDCBA1234567G5H5X1K111098121314HX757757B70044757A757C75170575270075768SERVER/DATA CENTERREMOVE AND REINSTALL NEW 2 HOUR RATED SHAFT CONSTRUCTION TO ACCOMMODATE INSTALLATION OF NEW DUCTWORK . SEE PARTITION C1.GF8FEDCBA1234567G5H5X1K111098121314HX800608006480280480061801803805NEW AHU AND HOUSEKEEPING PAD, SEE ALSO MECHANICAL AND STRUCTURAL DRAWINGSACS 3 & 4REMOVE EXISTING SECURITY FENCE AND GATE AND REINSTALL IN NEW LAYOUT.NEW MECHANICAL EQUIPMENT AND HOUSEKEEPING PAD, SEE ALSO MECHANICAL AND STRUCTURAL DRAWINGSGF8FEDCBA1234567G5H5X1K1110912HNEW OPENING AND FRAME SUPPORT IN EXISTING ROOF CONSTRUCTION FOR NEW LOUVERED PENTHOUSE. SEE ALSO STRUCTURAL AND MECHANICAL DRAWINGS. LIMITS OF ROOF REPLACEMENT WORK. ALL WORK SHALL BE DONE TO MAINTAIN EXISTING ROOF WARRANTY. 10A-502A-5029Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/16" = 1'-0"SIXTH, SEVENTH AND EIGHTHFLOOR PLANSA-1021/16" = 1'-0"1SIXTH FLOOR PLAN1/16" = 1'-0"2SEVENTH FLOOR PLAN1/16" = 1'-0"3PENTHOUSE FLOOR PLAN1/16" = 1'-0"4ROOF FLOOR PLAN
GF8FEDCBA1234567G5H5X1K111098121314HX1A-4102A-410B.O. BEAM10' - 1 1/2"TYP.A2A-11121 TYP.A33 3 1A-5029A-5034 10' - 8"4 2 A4A1A1A56 6 A2A21 TYP.1 TYP.8' - 8"8' - 8"8' - 8"11' - 7"B.O. BEAM10' - 1 1/2"11' - 7"10' - 1 1/2"B.O. BEAMB.O. BEAMB.O. BEAM11' - 10 1/2"B.O. BEAM9' - 1"8' - 0"9A-503SIM.11' - 4 1/2"B.O. BEAMA-1113A-1114A7A711A-503TYP.8' - 2"4 LINE OF NEW TO EX. CEILINGLINE OF EX. TO NEW CEILING4 A8A87 TYP.ALIGNEQEQTYP.EQTYP.EQEQEQTYP.EQTYP.EQOF GRIDOF GRID2 1/4"3' - 7"3' - 3"EQEQEQEQ2' - 10"2' - 10"EQEQEQEQALIGNALIGNALIGN7A-503KEY NOTES:1DUAL ROLLER WINDOW SHADES WITH FASCIA, ONE SOLAR AND ONE BLACK OUT SHADE. BASIS OF DESIGN URBANSHADE BY MECHOSHADEFLUSH MOUNTED CEILING ACCESS PANEL, 2'X2'SUSPENDED STUD AND GYPSUM BOARD ENCLOSURE AROUND EXISTING MECHANICAL EQUIPMENT (ABOVE CEILING) FOR ACOUSTICAL PURPOSES. NEW GYPSUM BOARD CEILING FLUSH WITH ADJACENT EXISTING CEILING TO REMAIN.PATCH AND PAINT CEILING.TRANSFER DUCTS. SEE MECHANICAL.GYPSUM ENCLOSURE AROUND EXISTING BEAM. FIREPROOFING TO REMAIN. SEE DETAILS ON A-502.234567LIGHT LEGEND:A1LINEAR PENDANT, 8'-0" LONGA2LINEAR PENDANT, 4'-0" LONGA3LINEAR PENDANT, 6'-0" LONGA42X2 RECESSED DIRECT/INDIRECTA5RECESSED CAN LIGHTA6 FLAT RECESSED LET LIGHT, 8'-0" LONGA7 FLAT RECESSED LET LIGHT, 3'-0" LONGA8LINEAR PENDANT, 7'-0" LONGCEILING FINISH LEGEND:FOAM ACOUSTICAL CEILING TREATMENT ADHERED TO CEILING. PROVIDE SONEX, TECH WEDGE ACOUSTICAL FOAM BY ACOUSTICAL SOLUTIONS INC. 2" THICK, 2'X4' PANEL SIZE. PROVIDE FULL RANGE OF MFR. COLOR SAMPLES FOR SELECTIONEXISTING ACOUSTICAL CEILING TILE AND SUSPENSION SYSTEMNEW ACOUSTICAL CEILING TILE AND SUSPENSION SYSTEMNEW SUSPENDED GYPSUM BOARD CEILINGACOUSTICAL WALL TREATMENT, GROOVED AND PERFORATED ACOUSTICAL WOOD PANELLIGHT SUSPENDED ABOVE C CHANNEL SYSTEM.CEILING MOUNTED RETRACTABLE POWER RECEPTACLEUNISTRUT OR KINDORF C-CHANNEL SUSPENDED FROM THREADED ROD FASTENERS TO SLAB ABOVE. HUNG AT 8'-8" AFF.EQEQEQNOTES:1. PROVIDE 10% ADDITIONAL ATTIC STOCK OF ALL C-CHANNEL SUSPENDED SYSTEM2. ALL SYSTEM COMPONENTS TO BE PAINTED.3. DIMENSIONS ARE TYPICAL UNLESS NOTED OTHERWISE.8' - 6"8' - 6"EQEQTYP.EQTYP.EQLEGEND:SUPPLY DIFFUSERRETURN GRILLEWIRELESS WALL MOUNTED ACCESS POINTRETRACTABLE POWER CHORDWAPF2UNISTRUT OR KINDORF C-CHANNEL SUSPENDED FROM THREADED ROD FASTENERS TO SLAB ABOVE. HUNG AT 8'-8" AFF.8' - 6"ALIGNALIGN9' - 0"B.O SOFFIT9' - 6"B.O CURTAIN ROD3 8 °10A-503INDICATES BLACKOUT CURTAIN AND TRACK (BY OWNER)ALIGNALIGNDEQEQEQ8' - 6"4' - 3"UNISTRUT OR KINDORF C-CHANNEL SUSPENDED FROM THREADED ROD FASTENERS TO SLAB ABOVE. HUNG AT 8'-8" AFF.ALIGNTYP.EQTYP.EQRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedFIFTH FLOOR REFLECTEDCEILING PLANA-1111/8" = 1'-0"1LEVEL 5 REFLECTED CEILING PLAN1/4" = 1'-0"2TYPICAL SLOTTED METAL FRAMING CEILING LAYOUT1/4" = 1'-0"3SLOTTED METAL FRAMING CEILING LAYOUT1/4" = 1'-0"4SLOTTED METAL FRAMINGCEILING LAYOUTGENERAL NOTES:1. ONLY DOWNTURNED SPRINKLER HEADS ARE SHOWN. SEE PLUMBING DRAWINGS FOR UPTURNED AND DOWNTURNED SPRINKLER HEADS.2. LIGHTS ARE SHOWN FOR REFERENCE ONLY. REFER TO MEP FOR CEILING MOUNTED FIXTURES.
GF8FEDCBA1234567G5H5X1K111098121314HX1A-4102A-410ALIGNALIGNALIGNTYP.EQTYP.EQEQEQTYP.EQTYP.EQOF ACOUSTIC PANELSOF ACOUSTIC PANELSCEILING FINISH LEGEND:FOAM ACOUSTICAL CEILING TREATMENT ADHERED TO CEILING. PROVIDE SONEX, TECH WEDGE ACOUSTICAL FOAM BY ACOUSTICAL SOLUTIONS INC. 2" THICK, 2'X4' PANEL SIZE. PROVIDE FULL RANGE OF MFR. COLOR SAMPLES FOR SELECTIONEXISTING ACOUSTICAL CEILING TILE AND SUSPENSION SYSTEMNEW ACOUSTICAL CEILING TILE AND SUSPENSION SYSTEMNEW SUSPENDED GYPSUM BOARD CEILINGACOUSTICAL WALL TREATMENT, GROOVED AND PERFORATED ACOUSTICAL WOOD PANELRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/8" = 1'-0"FIFTH FLOOR REFLECTEDCEILING PLAN -ACCOUSTICTREATMENTA-111A1/8" = 1'-0"1LEVEL 5 REFLECTED CEILING PLAN - ACCOUSTICAL TREATMENT
TGBCPABCDEDHDHDCDCCR3a,bDCR3a,bD3a,bDCRGF8FEDCBA1234567G5H5X1K111098121314HXLABORATORY551STORAGE551BWAPWAPWAPA-50111 1 1 2 3 4 STORAGE551AF F F F F F F SSSEP LEGEND:WALL MOUNTED DUPLEX RECEPTACLE (SEE ELECTRICAL PLANS)WALL MOUNTED QUADRUPLEX RECEPTACLE (SEE ELECTRICAL PLANS)GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE (SEE ELECTRICAL PLANS)DATA RECEPTACLE (O.F.C.I.)CARD READERDOOR HOLD OPEN, TIED TO FIRE ALARM SYSTEMDOOR STRIKEMAG LOCKCEILING MOUNTED RETRACTABLE POWER RECEPTACLE(S)WIRELESS ACCESS POINTPUSH BUTTONLIGHT SWITCHDIMMER SWITCHALARM SIGNAL, STROBESPACE SENSOR/ TEMPERATE ADJUSTMENTEMERGENCY PHONECRDHDSMLWAPSDF SEP POWER & DATA KEY NOTES:DEDICATED POWER RECEPTACLE TO SERVE THE CONDENSATE PUMP. TO BE MOUNTED INSIDE THE BASE CABINET. INDICATES CORD REELS LOCATED ON CEILING. SEE ALSO DETAIL FOR LAYOUT OF DEVICES AT COLUMN RACEWAY. LOCATE SWITCH ON COLUMN FACE. EXPOSED CONDUIT PAINTED TO MATCH COLUMN FINISH. 1 2 3 4 /7A-502Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedPOWER & COMMUNICATIONS -FIFTH FLOOR PLANA-1211/8" = 1'-0"1POWER & COMMUNICATIONS - LEVEL 5GENERAL NOTES:1. ARCHITECTURAL POWER AND COMMUNICATIONS PLANS SHOW GENERAL LOCATION OF RECEPTACLES AND DEVICES. COORDINATE FINAL LOCATIONS WITH ARCHITECT ON SITE PRIOR TO INSTALLING BACK BOXES. SEE MEP DRAWINGS FOR COMPLETE ELECTRICAL AND COMMUNICATIONS REQUIREMENTS.2. RECEPTACLE COVER PLATES ARE VERTICAL U.O.N.3. CENTER LINE OF ELECTRICAL AND DATA RECEPTACLE COVER PLATES ARE 18" A.F.F. U.O.N.
UPUPUPGF8FEDCBA1234567G5H5X1K111098121314HX1A-4102A-41018' - 6 3/16"22' - 8"22' - 8"22' - 8"22' - 8"14' - 4 5/16"4' - 1 7/8"18' - 6 3/16"22' - 8"22' - 8"22' - 8"22' - 8"18' - 6 5/8"1' - 7 5/8"1' - 7 5/8"1' - 7 5/8"EQEQTERRACE578576574572500445007350076512514508504A504502500503501517519521521A523520518516514B571GRAD.STUDENTS596GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS580LOUNGE568DATACLOSET552ELEC.CLOSET50075MEN50022WOMEN50021LABORATORY551STORAGE551BSTORAGE551ACURTAINS ABOVE TO ALIGN WITH FLOOR MARKINGSMARKINGS TO ALIGN WITH COL. CLEQEQEQEQ2' - 11"ALIGNALIGN11A-502LINE OF NEW TO EX. CARPET TILELEGENDCARPET TILE AND 6" RUBBER BASE.EXISTING CARPET TILE TO REMAIN.EXPOSED CONCRETE. PREPARE SURFACE AS REQUIRED TO RECEIVE SPECIFIED FINISH, INCLUDING PROVIDING A LEVEL SURFACE PER THE SPECIFICATIONS, FILL CRACKS WITH EPOXY FILLER, POLISH, AND SEAL. USE SIKAFLOOR 160 (PRIMER), SIKAFLOOR 217 (CLEAR EPOXY COAT), SIKAFLOOR 315N (CHEMICAL RESISTANT CLEAR URETHANE). EPOXY FLOOR COATING SIKAFLOOR 2870 (LINE STRIPING) IN PATTERN SHOWN. APPLY BEFORE APPLICATION OF CLEAR URETHANE TOP COAT. COLOR TBD.NOTES1. INSTALL 6" BASE MOLDING IN ROOM 551, STORAGE ROOMS 551A AND 551B, AND CORRIDOR 50044Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/8" = 1'-0"FIFTH FLOOR -FLOOR FINISHPLANA-1311/8" = 1'-0"1FLOOR FINISH PLAN - LEVEL 5
KEY NOTES:MOVABLE STORAGE CABINET WITH WOOD TOP (N.I.C.)INDUSTRIAL WORKBENCH WITH BUTCHER BLOCK TOP, ON CASTERS. SIZE 60"X30". (N.I.C.) STORAGE RACK ON CASTERS, APPROX. 7' HIGH. (N.I.C.)BLACK OUT CURTAIN BOOTH, SUSPENDED FROM CEILING GRID (N.I.C.)FULL HEIGHT WIRE MESH CURTAIN. TRACK SUSPENDED FROM SLAB ABOVE.FLOOR MOUNTED SCREEN WITH METAL GRID PANEL. SEE . EXPERIMENT AREA, WOOD BOX, ROBOTIC ARM, ETC. (N.I.C.)STOOL ON WHEELS, ADJUSTABLE HEIGHT. (N.I.C.)8'-8" HIGH OPEN SHELVING1 2 3 4 5 6 7 8 /2A-1419 4' - 0"6' - 0"1' - 0"1 1/2" X 1 1/2" STEEL TUBE FRAME, PAINTED. FULLY WELD ALL JOINTSWIRE MESH INFILLBASIS OF DESIGN: CHAOS BY CAMBRIDGE ARCHITECTURAL MESH1/4" DEEP STABILIZING LEG (STEEL)1" = 1'-0"PROVIDE WEIGHT IN BASE FOR STABILITYGF8FEDCB1234G59H500442122312233888855558882123213312122331221222322688858123882186686668685555588LABORATORY551STORAGE551ASTORAGE551B999999666Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedFURNITURE & EQUIPTMENT PLAN-FIFTH FLOORA-1412DEMOUNTABLE TYPE PANEL3/16" = 1'-0"1FURNITURE & EQUIPTMENT - LEVEL 5
LEVEL 5867' -4"LEVEL 6880' -8"GF8FED1 1 1A-5027A 7A PT-3PT-3PT-35511NEW WALL CONSTRUCTIONEXISTING WALL8 8 14 NEW WALLEXISTING WALLRB, TYP.EXISTING WALLEQEQKEY NOTES:NEW FRAME AND GLAZING. SEE A-601.WIRELESS WALL MOUNTED ACCESS POINT (SEE ELECTRICAL DRAWINGS)SUSPENDED LIGHT FIXTURE (SEE RCP)UNISTRUT OR KINDORF C-CHANNEL SUSPENDED FROM THREADED ROD FASTENERS TO SLAB ABOVE. HUNG AT 8'-8" AFF.CEILING MOUNTED RETRACTABLE POWER RECEPTACLE(S)DUAL ROLLER WINDOW SHADES WITH FASCIA, ONE SOLAR AND ONE BLACK OUT SHADE. BASIS OF DESIGN URBANSHADE BY MECHOSHADE. PROVIDE AT EACH EXTERIOR WINDOW.NEW ROOM SIGNAGE. SEE .NEW ROOM SIGNAGE. PROVIDE 8.5" X 11" INSERT.WIRE MESH CURTAINS ON UNISTRUT TRACK ASSEMBLY.GLASS MARKERBOARD PANEL ON STAINLESS STEEL SLIDING TRACK HARDWARE SYSTEM.FOAM ACOUSTICAL PANELS ADHERED TO CEILING. WIREMOLD WITH POWER RECEPTACLES.TRANSFER DUCTS. SEE MECHANICAL. COORDINATE FINAL LOCATION IN FIELD WITH ARCHITECT. RECESSED FIRE CABINET.DOOR HOLDER CONNECTION.CABLE TRAY. SEE ELECTRICAL.SMOKE DETECTOR. FIN TUBE RADIATOR COVER.INDICATES NEW SHAFT WALL PARTITION, EXTEND 6" ABOVE FINISHED CEILING, DO NOT DISTURB EXISTING WALL FIRE DAMPERS.RELOCATED CONTROLSWALL STOPPIPING TO SERVICE SINK BELOW, INSTALL TIGHT TO COLUMN, PAINT.ACOUSTICAL WALL TREATMENT, GROOVED AND PERFORATED ACOUSTICAL WOOD PANELEMERGENCY PHONE.1 2 3 4 5 6 /1A-6037 8 9 10 11 12 13 14 15 16 17 18 19 20 21 7A 22 23 LEVEL 5867' -4"LEVEL 6880' -8"234CORRIDOR50044A-54126 TYP.6"2 10 PT-1PT-213 16 RB, TYP.20 WAP11 PT-4A-5026SIM.LEVEL 5867' -4"LEVEL 6880' -8"GF8FEDCCORRIDOR500443 4 TYP.TYP.A-50255 TYP.8 TYP.PT-1PT-26' - 8"15 NEW WALLEXISTING WALLEXISTING WALLNEW WALL5"3' - 10" TYP.EQEQ10 9A-5035511551210 TYP.23 SLEVEL 5867' -4"LEVEL 6880' -8"234CORRIDOR500443 4 TYP.TYP.7 6 2 10 13 551316 1/2"RB, TYP.EQEQ2 WAPWAPA-5031111 16 A-5037SSLEVEL 5867' -4"LEVEL 6880' -8"FEDCCORRIDOR500443 4 TYP.TYP.5 TYP.6 TYP.A-5416A-5415A-5022A-5022A-50228 TYP.22 TYP.6A-502PT-415 17 TYP.22 15 21 22 TYP.22 TYP.22 TYP.22 TYP.6 TYP.6 TYP.6 TYP.6 TYP.10 TYP.GENERAL NOTES:1. FOR POWER / DATA OUTLET LOCATIONS, SEE2. WHERE EXISTING WALL HATCH IS NOTED ON ELEVATIONS IT IS TO DELINEATE NEW VS EXISTING WALL LOCATIONS/ EXISTING WALLS ON OTHER ELEVATIONS ARE NOT ALL INDICATED BY THIS HATCH. 3. ALL ABOVE CEILING ITEMS, INCLUDING PIPING, DUCTS, CONDUITS, ETC. TO BE PAINTED. /1A-121LEVEL 5867' -4"LEVEL 6880' -8"FEPT-3PT-33A-50116 16 18 18 14 RB, TYP.EXISTING WALL19 3' - 10"NEW WALL CONSTRUCTIONEXISTING WALLLEVEL 5867' -4"LEVEL 6880' -8"3PT-3PT-3NEW WALL CONSTRUCTIONEXISTING WALL5513RB, TYP.1 7A LEVEL 5867' -4"LEVEL 6880' -8"GF87 PT-1PT-2A-541916 LEGENDWALL MOUNTED DUPLEX RECEPTACLE (SEE ELECTRICAL PLANS)WALL MOUNTED QUADRUPLEX RECEPTACLE (SEE ELECTRICAL PLANS)GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE (SEE ELECTRICAL PLANS)DATA RECEPTACLE (O.F.C.I.)STROBE LIGHT (SEE ELECTRICAL PLANS)LIGHT SWITCHCARD READERWIRELESS ACCESS POINTSPACE SENSORCRWAPSRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/4" = 1'-0"INTERIOR ELEVATIONSA-3011/4" = 1'-0"1WEST ELEVATION @ CORRIDOR1/4" = 1'-0"3INTERIOR ELEVATION IN ROOM 551 LOOKING NORTH1/4" = 1'-0"5INTERIOR ELEVATION IN ROOM 551 LOOKING EAST1/4" = 1'-0"4INTERIOR ELEVATION IN ROOM 551 LOOKING SOUTH1/4" = 1'-0"6INTERIOR ELEVATION IN ROOM 551 LOOKING WEST1/4" = 1'-0"7INTERIOR ELEVATION IN CORRIDOR 50044 LOOKING EAST1/4" = 1'-0"2INTERIOR ELEVATION IN CORRIDOR 50044 LOOKING NORTH1/4" = 1'-0"8INTERIOR ELEVATION IN ROOM 551LOOKING WEST
LEVEL 5867' -4"LEVEL 6880' -8"45EQEQEQEQ12 12 KEY NOTES:NEW FRAME AND GLAZING. SEE A-601.WIRELESS WALL MOUNTED ACCESS POINT (SEE ELECTRICAL DRAWINGS)SUSPENDED LIGHT FIXTURE (SEE RCP)UNISTRUT OR KINDORF C-CHANNEL SUSPENDED FROM THREADED ROD FASTENERS TO SLAB ABOVE. HUNG AT 8'-8" AFF.CEILING MOUNTED RETRACTABLE POWER RECEPTACLE(S)DUAL ROLLER WINDOW SHADES WITH FASCIA, ONE SOLAR AND ONE BLACK OUT SHADE. BASIS OF DESIGN URBANSHADE BY MECHOSHADE. PROVIDE AT EACH EXTERIOR WINDOW.NEW ROOM SIGNAGE. SEE .NEW ROOM SIGNAGE. PROVIDE 8.5" X 11" INSERT.WIRE MESH CURTAINS ON UNISTRUT TRACK ASSEMBLY.GLASS MARKERBOARD PANEL ON STAINLESS STEEL SLIDING TRACK HARDWARE SYSTEM.FOAM ACOUSTICAL PANELS ADHERED TO CEILING. WIREMOLD WITH POWER RECEPTACLES.TRANSFER DUCTS. SEE MECHANICAL. COORDINATE FINAL LOCATION IN FIELD WITH ARCHITECT. RECESSED FIRE CABINET.DOOR HOLDER CONNECTION.CABLE TRAY. SEE ELECTRICAL.SMOKE DETECTOR. FIN TUBE RADIATOR COVER.INDICATES NEW SHAFT WALL PARTITION, EXTEND 6" ABOVE FINISHED CEILING, DO NOT DISTURB EXISTING WALL FIRE DAMPERS.RELOCATED CONTROLSWALL STOPPIPING TO SERVICE SINK BELOW, INSTALL TIGHT TO COLUMN, PAINT.ACOUSTICAL WALL TREATMENT, GROOVED AND PERFORATED ACOUSTICAL WOOD PANELEMERGENCY PHONE.1 2 3 4 5 6 /1A-6037 8 9 10 11 12 13 14 15 16 17 18 19 20 21 7A 22 23 LEVEL 5867' -4"LEVEL 6880' -8"238' - 0"9 PT-1PT-2LEVEL 5867' -4"LEVEL 6880' -8"GF8FED1 1 1 1 7A 7A PT-3PT-3PT-3551114 RB, TYP.Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/4" = 1'-0"INTERIOR ELEVATIONSA-3021/4" = 1'-0"1INTERIOR ELEVATION IN ROOM 571 LOOKING SOUTH1/4" = 1'-0"3INTERIOR ELEVATION AT WHITE BOARD PARTITION - ALTERNATE 21/4" = 1'-0"4WEST ELEVATION @ CORRIDOR - ALTERNATE 1
LEVEL 5867' -4"LEVEL 6880' -8"1234567LEVEL 7894' -0"T.O. PARAPET910' -8"PENTHOUSEFLOOR T.O.S.907' -4"HIGH ROOF T.O.S.927' -4"T.O. PARAPET 3930' -8"PROJECT AREA500442A-410A-5026A-502955150042512514800648028006080060803PENTHOUSEMECHANICAL SHAFTLEVEL 5867' -4"LEVEL 6880' -8"F8FEDCBALEVEL 7894' -0"T.O. PARAPET910' -8"PENTHOUSEFLOOR T.O.S.907' -4"HIGH ROOF T.O.S.927' -4"T.O. PARAPET 3930' -8"1A-410PROJECT AREA500445518006480060A-5025PENTHOUSERevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/8" = 1'-0"BUILDING SECTIONSA-4101/8" = 1'-0"1SECTION 11/8" = 1'-0"2SECTION 2
F3EXISTING STRUCTURAL COLUMN . REMOVE EXISTING SPRAY ON FIREPROOFING AND PREPARE SURFACE TO RECEIVE NEW 2 HR RATED INTUMESCENT COATING. COLOR BY ARCHITECT. WIREMOLD/RACEWAY WITH POWER AND DATA. SEE ALSO ELECTRICAL DRAWINGS. A-5027F43' - 0 1/2"3' - 0 1/2"EXISTING WALL CONSTRUCTIONALIGNALIGNCORRIDOR50044LABORATORY551SHAFT0' - 2 1/2"0' - 2 1/2"RELOCATED DOUBLE SWING DOOR AND FRAME WITH HOLD OPENSEXISTING SHAFT CONSTRUCTION34A-502RECESSED FIRE CABINETWALL TYPE - SEE PLANE4EXISTING STRUCTURAL COLUMNWIRE MOLDALIGNBASE MOLDING BELOWA-5027STEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.1' - 0"Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedDETAILS IA-5011 1/2" = 1'-0"1TYPICAL WIREMOLD AT COLUMNS3/4" = 1'-0"3PLAN DETAIL AT CORRIDOR POCKET DOOR1 1/2" = 1'-0"2PLAN DETAIL AT RECESSED FIRE CABINET1 1/2" = 1'-0"4PLAN DETAIL AT DOOR OPENING
LEVEL 6880' -8"4EXISTING STRUCTURAL BEAM WITH FIREPROOFINGA-602H3ACOUSTICAL CEILING PANEL & SUSPENSION SYSTEM (SEE RCP FOR TYPE)EXISTING FLOOR CONSTRUCTION3 5/8" METAL STUDS @ 24" O.C. MAX 21/2" METAL STUDS DIAGONAL BRACES 48" O.C. AS REQUIRED.21/2" CONTINUOUS METAL TRACK, 18 GAUGE SECURED TO STRUCTURE6"GWB SOFFIT8' - 8"EDGE OF THE WALL BEYONDLEVEL 5867' -4"LEVEL 6880' -8"E1/2" DIA. THREADED HANGER RODPAINTED C-CHANNELNUT AND WASHER (TYP.)EXISTING STEEL FRAMING WITH FIREPROOFINGSUSPENDED LIGHT FIXTUREFINISHED FLOOR DUCT BEYONDCEILING MOUNTED RETRACTABLE POWER RECEPTACLE(S)SPRINKLER SYSTEMACOUSTICAL FOAM PANELCHANNEL BRACEWIRE MECH CURTAINC CHANNEL TRACK WITH TROLLEY ACCESSORYA-5035METAL GRID:B.O. GRID 8'-8" - 8'-10"LIGHTING:B.O. LIGHT 9'-1" - 9'-6"SPRINKLER:9'-7" - 9'-11"DUCTS:B.O. 10'-0" - 12'-10 3/4"CEILING MOUNTING HEIGHT ZONESCHANNEL AND GYPSUM BD ENCLOSURE LEVEL 5867' -4"E3A-502EXISTING WINDOW SILLNEW WINDOW SILLEXISTING WINDOW SILL NEW WINDOW SILLEXISTING WINDOW FRAMEEXISTING WINDOW SILLNEW PLASTIC LAMINATE WINDOW SILL TO MATCH EXISTINGEXISTING RADIATOR (TYP.)PROVIDE NEW END CAP AND COVER FOR PIPING EXPOSED WHEN COLUMN ENCLOSURE IS REMOVED. SEAMLESS TAPED AND SPECKLED JOINT BETWEEN NEW AND EXISTING WALLBASE MOLDINGEXISTING WINDOWEXISTING WALL CONSTRUCTIONPLASTIC LAMINATED SILL, COLOR TO MATCH EXISTINGALIGN0' - 2"METAL STUD AND GYPSUM BOARD0' - 0 1/2"WALL REVEAL TO ALIGN WITH BOTTOM OF SUSPEND METAL GRID, INSTALL IN NEW WALL PARTITION OR CUT INTO EXISTING. AT ALL PERIMETER WALLS IN LAB 551PT-1PT-28'-8"WALL TYPESEE PLANPRESSURE TREATED WOOD BLOCKINGPREFABRICATED EQUIPMENT CURBADHESIVE CEMENTSPLICING CEMENTIN-SEAM SEALANTFLASHINGLOUVER PENTHOUSE FOR EXHAUST FAN, SET ON WATER CUTOFF MASTIC4" RIGID INSULATIONNEW SLAB OPENINGEXISTING ROOF SYSTEM TO REMAINLAP MEMBRANE OVER EXISTINGNEW EPDM ROOF SYSTEM TO MATCH EXISTINGNOTE: SEE ALSO STRUCTURAL AND MECHANICAL DRAWINGSSEE STRUCTURAL DRAWINGS FOR ALL NEW STEEL FRAMING MEMBERS. APPLY SPRAY ON FIREPROOFING TO MATCH ADJACENT EXISTING CONSTRUCTIONLEVEL 5867' -4"LEVEL 6880' -8"2DUAL ROLLER WINDOW SHADES WITH FASCIA, ONE SOLAR AND ONE BLACK OUT SHADE. BASIS OF DESIGN URBANSHADE BY MECHOSHADEACOUSTIC PANELSC-CHANNELSUSPENDED LIGHT FIXTURE (SEE RCP)A-50311LEVEL 5867' -4"3± 2' - 6"EXISTING STRUCTURAL COLUMNQUAD RECEPTACLEDATA OUTLETWIRE MOLDLEVEL 5867' -4"3' - 0"5/8" GWBRECESSED FIRE CABINETFINISHED FLOOREXISTING CARPETNEW CARPETTRANSITION STRIPEXISTING FLOOR CONSTRUCTION10A-502LOUVERSEXISTING ROOF CONSTRUCTIONRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedDETAILS IIA-5021 1/2" = 1'-0"1DETAIL @ GLAZED PARTITION3/4" = 1'-0"5SECTION1 1/2" = 1'-0"2TYPICAL WINDOW ELEVATION BEHIND COLUMNS3" = 1'-0"3WINDOW SILL DETAIL12" = 1'-0"8WALL REVEAL DETAIL1 1/2" = 1'-0"10TYPICAL VENTILATION LOUVER DETAIL3/4" = 1'-0"6SECTION DETAIL AT WINDOWS1 1/2" = 1'-0"7TYPICAL ELEVATION OF WIREMOLDS AT COLUMN1 1/2" = 1'-0"4SECTION DETAIL AT RECESSED FIRE CABINET12" = 1'-0"11NEW TO EXISTING CARPET TRANSITION DETAIL1" = 1'-0"9ELEVATION @ VENTILATION LOUVER
PAINTED UNISTRUT C CHANNEL SYSTEMSUSPENDED LED LIGHTSACOUSTIC CEILING PANELSFLOOR CONSTRUCTION ABOVECORNER FITTING SEE /2A-503T-INTERSECTION FITTING SEE /3A-503INTERSECTION FITTING SEE /4A-503NOTE:PROVIDE ALL REQUIRED ACCESSORIES FOR THE METAL GRID SYSTEM, INCLUDING HANGARS, RODS, ATTACHMENT TO DECK ABOVE, NUTS, BOLTS, SLOTTED C CHANNEL, CONNECTION PIECES, BRACING, ETC. PROVIDE MOCKUP GRID AT FULL SIZE IN SINGLE LOCATION TO SERVE AS MODEL FOR THE BALANCE OF THE INSTALLATIONALL COMMENTS OF HANGING METAL GRID SYSTEM SHALL BE PAINTED.EPAINTED C CHANNELSTAINLESS STEEL MESH CURTAIN1/4" DIA. THREADED HANGER ROD. , PROVING BRACING BETWEEN HANGERSWASHER AND BOLT8' - 8"TROLLEY SYSTEM, ACCESSORY BY CHANNEL MFR.EXISTING STRUCTURAL BEAMEXISTING STRUCTURAL COLUMN BEYONDCENTER MOUNT BEAM CLAMPSREMOVE EXISTING SPRAY-ON FIREPROOFING TO INSTALL BEAM CLIP. INSTALL NEW SPRAY ON FIREPROOFING WHERE DISTURBED. INSTALL GYPSUM BOARD TIGHT TO UNDERSIDE OF SPRAY-ON FIREPROOFING. A-5038HANGING WIRE (TYP.)MAIN BEAM (TYP.)ACOUSTIC LAY-IN CEILING PANELS (REFER TO R.C.P. FOR TYPE)EXISTING FLOOR CONSTRUCTION ABOVEREFER TO R.C.P. CEILING HEIGHTCROSS TEE (TYP.)CONTINUOUS 1/2" SHADOW MOULDING PERIMETER (TYP)PARTITION - SEE PLANCEILING HEIGHTREFER TO R.C.P. ANGLE MOLDING REVEAL WIDTH TO MATCH WIDTH OF TEE GRID.ACOUSTIC LAY-IN CEILING PANEL (REFER TO R.C.P. FOR TYPE)FACE OF PARTITION OR FASCIALEVEL 6880' -8"571SEALANTTAPE & SPACKLE, TYP.1 LAYER 5/8" GWB1 LAYER 1" GWB LINER PANELSTEEL J-RUNNER2 LAYER 5/8" GWBCORNER BEADSEALANTEXISTING WALLEXISTING STRUCTURAL BEAMEXISTING FLOOR CONSTRUCTION3 1/8"2 1/2"EXISTING HVAC UNIT9' - 1"A-5028ATTACH SUSPENSION ROD TO THE SOFFITLEVEL 6880' -8"FC-CHANNEL9' - 0"9' - 6"DUCTEXISTING STRUCTURAL BEAMS WITH FIREPROOFINGMETAL STUD AND GYPSUM BOARD BEAM ENCLOSURE. FIREPROOFING TO REMAIN. INSTALL GYPSUM BOARD TIGHT TO UNDERSIDE OF FIREPROOFINGBLACKOUT CURTAIN TRACK (N.I.C.)METAL STUD AND GYPSUM BOARD SOFFIT HUNG FROM CEILING FOR FUTURE BLACKOUT CURTAIN (BLACKOUT CURTAINS AND TRACK BY OWNER)PAINTED C CHANNELTHREADED HANGER RODBRACINGPAINTED C CHANNELPAINTED C CHANNELLEVEL 6880' -8"2EXISTING WINDOWNEW ROLLER SHADESFUR OUT WALL USING 1 5/8" STUD AND 5/8" GWBACOUSTICAL PANELSA-50312A-50313± 11' - 0 1/2"EXISTING STRUCTURAL BEAM WITH FIRE PROOFING1 5/8" STUD2 1/2" STUDALIGNCONTINUOUS WALL TRACKSHIM AS REQUIREDALUMINUM "Z" CLIPALIGNDRIVE CHAINROLLER TUBE AND SHADE ASSEMBLY WITH DOUBLE SHADE1"EDGE BANDALUMINUM "Z" CLIPSHIM AS REQUIREDCONTINUOUS WALL TRACKEXISTING WALL CONSTRUCTIONMATCHING VENEER SPLINERAW SAW-CUT EDGESHIM AS REQUIREDALUMINUM "Z" CLIPCONTINUOUS TRACK1/16"1/8"LEVEL 6880' -8"4EXISTING STRUCTURAL BEAM WITH FIREPROOFINGNEW OR EXISTING CORRIDOR WALL± 10' - 9 1/2"METAL STUD AND GYPSUM BOARD BEAM ENCLOSURE. FIREPROOFING TO REMAIN. Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedDETAILS IIIA-50313D VIEW LOOKING AT THE GRID SYSTEM3" = 1'-0"5SECTION DETAIL AT CURTAIN ROD1 1/2" = 1'-0"6A.C.T. CEILING DETAIL (TYP.)12" = 1'-0"8CEILING EDGE DETAIL1 1/2" = 1'-0"9SOFFIT DETAIL1 1/2" = 1'-0"10SECTION DETAIL AT BLACKOUT BOOTH3" = 1'-0"2CORNER FITTING3" = 1'-0"3T-INTERSECTION FITTING3" = 1'-0"4INTERSECTION FITTING1 1/2" = 1'-0"11SECTION DETAIL AT ACCOUSTICAL PANELS6" = 1'-0"12ACCOUSTIC PANEL ATTACHMENT DETAIL AT BASE6" = 1'-0"13ACCOUSTIC PANEL ATTACHMENT DETAIL AT TOP6" = 1'-0"14ACCOUSTIC PANEL BUTT ATTACHMENT AND CORNER DETAIL1 1/2" = 1'-0"7BEAM ENCLOSURE AT CORRIDOR WALL
GF8A-5412ALIGNUNDERMOUNT SINK WITH DRYING PAN ADJACENTLEVEL 5867' -4"LEVEL 6880' -8"44' - 2"1' - 8"3' - 8"3' - 8"3' - 8"10A-541CABINET RESERVED FOR WATER PUMP9A-5413A-542SIM.EYE WASHERC2A-54154 1/4"UNDERMOUNT SINK WITH DRYING PAN ADJACENTE21A-410A-5416A-54113UNDERMOUNT SINK WITH DRYING PAN ADJACENTLEVEL 5867' -4"LEVEL 6880' -8"C3' - 0"3' - 6"3' - 0"3' - 0"CABINET RESERVED FOR WATER PUMP5A-5423A-542EYE WASHERCUT CASEWORK END PANEL AROUND EXISTING FIN TUB RADIATOR. 1A-542PROVIDE 12"X12" ACCESS PANEL EQEQ4A-542LEVEL 5867' -4"E3' - 6"3' - 0"3' - 0"2A-542CABINET RESERVED FOR WATER PUMP3A-542EYE WASHERCUT CASEWORK END PANEL AROUND EXISTING FIN TUB RADIATOR. 5A-542CUT CASEWORK END PANEL AROUND EXISTING FIN TUB RADIATOR. PROVIDE BRACING AND BLOCKING AS REQUIRED(3) ADJUSTABLE SHELVES; SHELF PIN HOLES INSIDE PANELS ENDWOOD CABINET(2) ADJUSTABLE SHELVES; HOLES IN END PANELS WOOD TOEKICK4' - 4"1' - 8"2' - 10"2' - 6"3/4" MARINE GRADE PLYWOODEPOXY COUNTERTOPPROVIDE METAL FRAMING OR METAL FABRICATIONS PARTITION REINFORCING AS REQUIRED TO SUPPORT WOOD ACCESS PANEL ASSEMBLY.1' - 2"UNDER CABINET LED STRIP LIGHTPOWER AND DATA RECEPTACLEWOOD CABINET WITH PULL0' - 4"1' - 11"0' - 5 1/2"0' - 1 1/2"UNDERMOUNT STAINLESS STEEL SINK BY CASEWORK MFR.WOOD ACCESS PANEL WOOD PANELMIN.0' - 8"TOE CLR.0' - 6"MIN.0' - 11"MIN.0' - 9"MIN.1' - 5"MIN.2' - 3"2' - 6"FAUCET FINISH FLOORADA CLEARANCE (SHOWN DASHED)BACKSPLASHLINE OF BASE CABINET BEYONDEPOXY COUNTERTOPPANEL ATTACHMENT CLIPSALLOWING PANEL TO BE EASILYREMOVED FOR ACCESS.METAL OR TREATEDWOOD FRAMINGPROVIDE METAL FRAMING OR METAL FABRICATIONS PARTITION REINFORCING AS REQUIRED TO SUPPORT WOOD ACCESS PANEL ASSEMBLY.PROVIDE BRACING AND BLOCKING AS REQUIRED(3) ADJUSTABLE SHELVES; SHELF PIN HOLES INSIDE PANELS ENDWOOD CABINET1' - 2"4' - 4"1' - 8"2' - 10"UNDER CABINET LED STRIP LIGHTWIRE MOLD WITH GFCI RECEPTACLESLEVEL 5867' -4"2POWER OUTLETFIN TUBE RADIATORRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedMILLWORK DETAILSA-5413/8" = 1'-0"1ENLARGED PLAN AT FIXED LABORATORY CASEWORK3/8" = 1'-0"2ELEVATION AT CASEWORK3/8" = 1'-0"3ENLARGED PLAN AT FIXEDLABORATORY CASEWORK3/8" = 1'-0"4ENLARGED PLAN AT FIXEDLABORATORY CASEWORK3/8" = 1'-0"5ELEVATION AT CASEWORK3/8" = 1'-0"6ELEVATION AT CASEWORK1 1/2" = 1'-0"9BASE AND UPPER CABINET DETAIL1 1/2" = 1'-0"10ADA SINK AND UPPER CABINET DETAIL83D VIEW LOOKING AT MILLWORK3/8" = 1'-0"13SIDE ELEVATION AT CASEWORK
(2) ADJUSTABLE SHELVES; HOLES IN END PANELS WOOD TOEKICK0' - 1 1/2"0' - 5 1/2"2' - 6"3/4" MARINE GRADE PLYWOODEPOXY COUNTERTOP0' - 3 1/2"FIN TUBE PIPING LOCATED IN CHASE BEHIND CASEWORKA-50230' - 5 1/2"WOOD CABINET WITH PULLEQEQEQ0' - 4"(2) ADJUSTABLE SHELVES; HOLES IN END PANELS WOOD TOEKICK, FLUSH, TO COVER ALL CABINET ENDS0' - 1 1/2"0' - 5 1/2"1' - 11"0' - 4"2' - 6"3/4" MARINE GRADE PLYWOODEPOXY COUNTERTOP0' - 3 1/2"POWER AND DATA RECEPTACLE RECESSED, FLUSH WITH FRONTFIN TUBE PIPING LOCATED IN CHASE BEHIND CASEWORKA-50230' - 5 1/2"WOOD CABINET WITH PULLEQEQ(2) ADJUSTABLE SHELVES; HOLES IN END PANELS WOOD CABINET WITH PULLWOOD TOEKICK, FLUSH, TO COVER ALL CABINET ENDS2' - 10"3/4" MARINE GRADE PLYWOODEPOXY COUNTERTOP0' - 3 1/2"0' - 4"1' - 10 1/2"0' - 5 1/2"DRAWER ON SELF-CLOSING BOTTOM SLIDERS W/ RECESSED PULL2' - 6"FIN TUBE PIPING LOCATED IN CHASE BEHIND CASEWORKA-50230' - 5 1/2"PROVIDE 12" X 12" ACCESS PANEL FOR ACCESS TO FIN TUBE CONTROLS BEYONDUNDERMOUNT STAINLESS STEEL SINK BY CASEWORK MFR.WOOD ACCESS PANEL ON 3/4" MARVEL GRADE PLYWOODWOOD PANELMIN.0' - 8"TOE CLR.0' - 6"MIN.0' - 11"MIN.0' - 9"MIN.1' - 5"MIN.2' - 3"FAUCET FINISH FLOORADA CLEARANCE (SHOWN DASHED)BACKSPLASHLINE OF BASE CABINET BEYONDEPOXY COUNTERTOPPANEL ATTACHMENT CLIPSALLOWING PANEL TO BE EASILYREMOVED FOR ACCESS.METAL OR TREATEDWOOD FRAMINGFIN TUBE PIPING LOCATED IN CHASE BEHIND CASEWORKA-50230' - 5 1/2"± 3 1/2"WOOD TOEKICK, FLUSH, TO COVER ALL CABINET ENDS0' - 5 1/2"1' - 11"0' - 4"FALSE DRAWERFIN TUBE PIPING LOCATED IN CHASE BEHIND CASEWORKA-50230' - 5 1/2"WOOD CABINET WITH PULLUNDERMOUNT STAINLESS STEEL DEEP SINK BY CASEWORK MFR.FAUCET BACKSPLASH± 3 1/2"Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1 1/2" = 1'-0"MILLWORK DETAILSA-5421 1/2" = 1'-0"4BASE CABINET DETAIL1 1/2" = 1'-0"5BASE CABINET DETAIL1 1/2" = 1'-0"3BASE CABINET DETAIL1 1/2" = 1'-0"1ADA SINK @ LABORATORY CASEWORK1 1/2" = 1'-0"2ADA SINK @ LABORATORY CASEWORK
-D1-INSULATED - HOLLOW METAL DOORSEE SCHEDULESEE SCHEDULEDOOR TYPESSCALE: 1/2"=1'-0"-D2-FIRE RATED METAL DOOR WITH VISION LITENOTE:GL-11 HOUR RATED GLAZING INCLUDES GLASS PRIVACY FILM, BASIS OF DESIGN: SOLYX SXJ-0561 MATTE FINE DOT GRADIENT 72". GL-2NON RATED DOUBLE GLAZED UNIT INCLUDES GLASS PRIVACY FILM, BASIS OF DESIGN: SOLYX SXJ-0561 MATTE FINE DOT GRADIENT 72". -D3-METAL DOOR WITH VISION LITESEE DOOR SCHEDULEJ4H3S4GL-1H2S1J5GRADIENT FILM6' - 2"3' - 7"2 3/4"2 3/4"2"2"2 3/4"2 3/4"SEE DOOR SCHEDULESEE DOOR SCHEDULEJ4H3S4GL-2J2H2S1PANIC BARJ4H3S3SEE DOOR SCHEDULEGL-1J5H2S12' - 4"GRADIENT FILM6' - 2"3' - 6"2 3/4"2 3/4"2 3/4"2"2"2 3/4"J4H3S3M1EQEQEQEQEQEQEQSEE DOOR SCHEDULESEE DOOR SCHEDULEGL-2GL-2J2H2S12' - 4"GRADIENT FILM6' - 2"2 3/4"2 3/4"PANIC BARSIM.2 3/4"2 3/4"2 3/4"22' - 3"9' - 10 1/2"2"2 3/4"15' - 8"-F1-FIRE RATED STEEL FRAMED ENTRANCE AND STOREFRONT SYSTEM-F2-STEEL FRAMED ENTRANCE AND STOREFRONT SYSTEMFRAME TYPESSCALE: 1/2"=1'-0"-F6-ALTERNATE BID 1 ONLYFIRE RATED STEEL FRAMED ENTRANCE AND STOREFRONT SYSTEM-F5-ALTERNATE BID 1 ONLYSTEEL FRAMED ENTRANCE AND STOREFRONT SYSTEM0' - 2"DOOR SIZESEE SCHEDULE-F4-FIRE RATED METAL FRAME SYSTEM0' - 2"DOOR SIZESEE SCHEDULE-F3-FULLY WELDED INSULATED HOLLOW METALJ3H1J2H2S10' - 2"0' - 2"SIM.GL-2GL-2REMOVABLE MULLION WHERE SPECIFIEDPANIC BARSEE SCHEDULESEE SCHEDULE10"GL-1Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation1/2" = 1'-0"DOOR AND GLAZING SCHEDULEA-601500/1 CORRIDOR 1 HR EXISTING EXISTING 26' - 0"8' - 8"0' - 2"EXISTING HMPNT SET 3 H1J1-EXISTING DOOR AND FRAME - SALAVAGE AND REINSTALL551/1 LABORATORY 1 HR D2HM / GLASS 13' - 0"8' - 6"0' - 2"F1STL PNT SET 1 H2J5S1PROVIDE ACCESS CONTROL. RATED DOORS INSTALLATION AND GAP MEASUREMENT MUST COMPLY WITH NFPA 80 STANDARD.551/2 LABORATORY NONE D3HM / GLASS 26' - 0"8' - 6"0' - 2"F2STL PNT SET 2 H2J2S1PROVIDE ACCESS CONTROL. 3/4" UNDERCUT551/3 LABORATORY NONE D3HM / GLASS 25' - 11 1/2" 8' - 4 7/8" 0' - 2"F4STL PNT SET 2 H2J2 SIM. S1PROVIDE ACCESS CONTROL. 3/4" UNDERCUT551A/1 STORAGE NONE D1HM12' - 6"7' - 0"0' - 2"F1HM PNT SET 4 H1J3-3/4" UNDERCUT551B/1 STORAGE NONE D1HM13' - 0"7' - 0"0' - 2"F1HM PNT SET 4 H1J3-3/4" UNDERCUT551/1 LABORATORY 1 HR D2HM / GLASS 13' - 0"8' - 6"0' - 2"F6STL PNT SET 1 H2J5S1ALTERNATE BID 1 ONLY. PROVIDE ACCESS CONTROL. RATED DOORS INSTALLATION AND GAP MEASUREMENT MUST COMPLY WITH NFPA 80STANDARD.551/2 LABORATORY NONE D3HM / GLASS 26' - 0"8' - 6"0' - 2"F5STL PNT SET 2 H2J2S1ALTERNATE BID 1 ONLY. PROVIDE ACCESS CONTROL. 3/4" UNDERCUTGENERAL NOTES:1. ALL INTERIOR DOOR HARDWARE LOCK SETS ARE SARGENT "STANDARD LEVER, STYLE J" MORTISE LOCKS/EXIT DEVICES OR APPROVED EQUAL.2. REFER TO FLOOR PLAN FOR DOOR SWING.3. A SOLID WALL FROM TOP OF FRAME TO UNDERSIDE OF STRUCTURE ABOVE SHALL BE CONSTRUCTED ABOVE ALL FRAMES, INCLUDE BRACING AT DOOR OPENINGS. PROVIDE HEADER AND/OR LINTEL AS REQUIRED TO SUPPORT WALL CONSTRUCTION AT HEAD OF ALL FRAMES. SEE WALL PARTITIONS A-603.4. ALL CYLINDERS/KEYING TO BE ‘BEST’. 5. SEE SPECIFICATIONS FOR GLAZING TYPES.6. PROVIDE ALL ACCESS CONTROL COMPONENTS AND ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION AND FUNCTIONING SYSTEM. INSTALLATION AND COMMISSIONING TO BE COORDINATED WITH THE OWNER.7. OPENING FORCE ON ALL DOORS SHALL NOT EXCEED 5 POUNDS.8. HARDWARE SHALL COME FROM A SINGLE SOURCE. SUBSTITUTIONS TO THE SETS BELOW IS SUBJECT TO APPROVAL BY ARCHITECT AND UNIVERSITY. 9. SEE THE POWER AND COMMUNICATIONS PLAN AND ELECTRICAL DRAWINGS FOR ADDITIONAL ACCESS CONTROL REQUIREMENTS AND DIAGRAMS. 10. DOOR CLOSERS, WHERE SCHEDULED, SHALL BE LOCATED ON THE INTERIOR (NON-CORRIDOR) SIDE. 11. POWER SUPPLY BPS-24-1 SHALL BE INCLUDED FOR EACH ELECTRIFIED MORTISE LOCKSET. READER INTERFACE MODULES TO BE FIELD LOCATED ON THE INTERIOR SIDE OF THE DOOR.12. INSTALL ALL FIRE RATED GLAZING PER MFR. INSTRUCTIONS TO MAINTAIN REQ'D RATING.13. POWER TRANSFER (WHERE SCHEDULED) SHALL BE LOCATED BETWEEN MIDDLE AND TOP HINGE. 14. SEE SPECIFICATIONS FOR DOOR HARDWARE SETS.-ALT 1-ALT 1DOOR AND FRAME SYSTEM SCHEDULEDOOR NO. ROOM NAMEFIRERATINGDOOR TYPEDOORMATERIAL# OFLEAFSDOORFRAME TYPEFRAMEMATERIALFINISHHARDWARESETHEADDETAILJAMBDETAILSILL DETAILCOMMENTSWIDTH HEIGHT THICKNESS50021/1 WOMEN 1 HR EXISTING EXISTING 13' - 0"7' - 0"0' - 2"EXISTING HM PNT SET 5 H1J3-50022/1 MEN1 HR EXISTING EXISTING 13' - 0"7' - 0"0' - 2"EXISTING HM PNT SET 5 H1J3-
STEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.GLAZINGALIGNCORRIDOR1"2 3/4"2 1/2"CORRIDORALIGNSTEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.GLAZINGEXISTING FLOOR CONSTRUCTION WITH NEW FINISH SURFACEGLAZINGSTEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.CARPETBASE MOLDING BEYONDCORRIDOR1"0' - 2 1/2"2 3/4"GLAZINGSTEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.ALIGNCORRIDOR0' - 2 1/2"2 3/4"STEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.BUTT JOINT BETWEEN GLAZING2 1/2"GLASS1"EXTEND GYP. BD. INTOFRAME 5/8" MIN.WELDED H.M. DOOR AND #16 GA.STL. FRAME. SET FRAME ANDBRACE AS REQUIRED PRIOR TOWALL CONSTR.METAL STUD BOX HEADERMETAL FRAME JAMB ANCHOR,SECURE WALL FRAMING ASREQUIREDFILL H.M. FRAME VOIDS WITHFIBERGLASS INSULATION PRIOR TO WALL CONSTR.DOOR LEAF. SEE DOORSCHEDULE FOR ADDITIONALINFORMATION.SECURE GWB SHEATHING TOHEADER FRAMING AS REQUIRED1/2"SEE PLANPARTITION TYPE1 15/16"1 15/16"5/8"2"1 3/4"FILL H.M. FRAMEVOIDS WITHFIBERGLASSINSULATION PRIORTO WALL CONSTR.SECURE GWB SHEATHING TOJAMB FRAMING AS REQUIREDWELDED H.M. DOOR AND#16 GA. STL. FRAME. SETFRAME AND BRACE ASREQUIRED PRIOR TO WALLCONSTR.EXTEND GYP. BD. INTOFRAME 5/8" MIN.METAL FRAME JAMBANCHOR, SECURE WALLFRAMING AS REQUIREDDOOR LEAF. SEE DOORSCHEDULE FOR ADDITIONALINFORMATION.1 15/16"1 15/16"2"5/8"SEE PLANPARTITION TYPE1/2"STEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.ALIGNLEVER HANDLESIDELITE GLAZINGGLAZINGSTEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.CORRIDOR6"1 3/4"HINGE VARIES, SEE HARDWARE SET0' - 4 7/8"0' - 7 3/8"SHAFTLABORATORY551CORRIDOR50044EXISTING DOOR, SALVAGE AND RE-INSTALLEXISTING FRAME, SALVAGE AND RE-INSTALLINDICATES OPEN POSITIONCORRIDORSIDELITE GLAZINGLEVER HANDLEGLAZINGSTEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.PANIC BARREMOVABLE MULLION6"1"1"ALIGNHINGE VARIES, SEE HARDWARE SET1 3/4"2 5/8"2 5/8"1A-602BASKER ROD AND SEALANT, BOTH SIDESSOLID BLOCKING (2) LAYERS 5/8" GWB TO MAINTAIN 60 MIN FIRE RATING60 MIN FIRE RATED DOOR FRAMECLOSERSTEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.GLAZINGALIGNCORRIDOR6"BACKER ROD AND SEALANT, BOTH SIDESFIN FLOOR10"1 3/4"1/4"3"BASE MOLDINGGLAZINGSTEEL DOOR FRAME SYSTEM. SEE DOOR AND FRAME TYPE.SOLID BLOCKING & CAULK(2) LAYERS 5/8" GWB TO MAINTAIN 60 MIN FIRE RATINGDOOR FRAMEDOORALIGNCORRIDORREMOVABLE MULLIONATTACHMENT ADAPTERBASE RECEIVER, ATTACHED INTO EXISTING CONCRETE SLABRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedDOOR AND GLAZING DETAILSA-6023" = 1'-0"J4PLAN DETAIL @ GLAZED PARTITION3" = 1'-0"H3SECTION DETAIL @ GLAZED PARTITION HEAD3" = 1'-0"S4SECTION DETAIL @ GLAZED PARTITION SILL3" = 1'-0"S3SECTION DETAIL @ GLAZED PARTITION SILL- ALTERNATE 13" = 1'-0"M1MULLION DETAIL3" = 1'-0"H1DOOR HEAD DETAIL3" = 1'-0"J3DOOR JAMB DETAIL6" = 1'-0"J5DOOR JAMB DETAIL3" = 1'-0"J1DOOR JAMB DETAIL6" = 1'-0"J2DOOR JAMB DETAIL6" = 1'-0"H2GLAZED DOOR HEAD DETAIL6" = 1'-0"S1GLAZED DOOR THRESHOLD DETAIL3" = 1'-0"1SECTION DETAIL AT REMOVABLE MULLION
GWBGYPSUM WALL BOARD*SECTION 092900 - GYPSUM WALL BOARD*SEE PARTITION TYPES FOR GWB TYPESGWB-IRIMPACT RESISTANT GWBSECTION 092900 - GYPSUM WALL BOARDCEILINGGWBPAINTED GYPSUM BOARDSECTION 092900 - GYPSUM DRYWALLACT-1CEILING PANEL SECTION 095113 - ACOUSTIC PANEL CEILINGSEE SPECIFICATIONSSEE SPECIFICATIONSSEE SPECIFICATIONSULTIMA TILE WITH REGULAR EDGE AND PRELUDE XL SUSPENSION SYSTEM BY ARMSTRONGCODEDEFINITIONSPECIFICATIONFLOOREXPOSED CONC. EXISTING CONCRETESECTION 096726 - RESINOUS FLOORINGCPT-1CARPET TILESECTION 096813 - TILE CARPETINGBASERB-1THERMOSET RUBBER BASE - COLOR 1SECTION 096512 - RESILIENT BASE AND ACCESSORIESWALLSPRODUCTSIKAFLOOR 160 (PRIMER), SIKAFLOOR 217 (CLEAR EPOXY COAT), SIKAFLOOR 315N (CHEMICAL RESISTANT CLEAR URETHANE), AND SIKAFLOOR 2870 (LINE STRIPING)HONOR ROLL COLLECTION BY INTERFACEJOHNSONITE 6" RUBBER BASEAPT - 1 ACOUSTICAL WALL TREATMENTSECTION 098414 - ACOUSTICAL WALL TREATMENTDECOUSTICS SOLO GROOVED WOOD PANELPAINTPT - 1PAINT - WALL GENERALSECTION 099000 - PAINTING AND FINISHESSEE SPECIFICATIONSAFP - 1ACOUSTICAL CEILING TREATMENTSECTION 098400 - ACOUSTICAL CEILING TREATMENTSONEX TEC WEDGE FOAM BY ACOUSTICAL SOLUTIONSPT - 2PAINT - UPPER WALLSECTION 099000 - PAINTING AND FINISHESSEE SPECIFICATIONSPT - 3PAINT - WALL GENERAL, CORRIDORSECTION 099000 - PAINTING AND FINISHESSEE SPECIFICATIONSPT - 4PAINT - BLACKOUT BOOTHSECTION 099000 - PAINTING AND FINISHESSEE SPECIFICATIONSPT - 5PAINT - CEILINGSECTION 099000 - PAINTING AND FINISHESSEE SPECIFICATIONSWINDOW TREATMENTSWT-1MANUAL OPERATED WINDOW SHADE WITH SINGLE ROLLERSECTION 122413 - WINDOW SHADESDUAL ROLLER URBANSHADE BY MECHOSHADEPLASTIC LAMINATEPL-1PLASTIC LAMINATE WINDOW SILL SECTION 062000 WILSONART HPL (HIGH PRESSURE LAMINATE) UNDERSIDE OF FLOOR CONSTRUCTIONSTEEL STUD(1) LAYER 5/8" WALLBOARDEACH SIDE.SCHEDULED FLOOR FINISH AND BASECONTINUOUS FIRERATED SEALANT TYPICAL BOTH SIDES AND AT VERTICAL INTERFACE AT FIRE RATED PARTITIONS. CONTINUOUS ACOUSTIC SEALANT TYPICAL BOTH SIDES AND VERTICAL INTERFACE AT NON-RATED PARTITIONS.CONTINUOUS STEEL RUNNERA: NON RATEDALL NOTES REFER TO BOTH SIDES OF PARTITION, U.O.N. GAUGE AND SPACING AS REQUIRED TO MEET SPAN AND DEFLECTION REQUIREMENTSCONTINUOUS FIRERATED SEALANT TYPICAL BOTH SIDES AND VERTICAL INTERFACE AT FIRE RATED PARTITIONS.CONTINUOUS ACOUSTIC SEALANT TYPICAL BOTH SIDES AND VERTICAL INTERFACE AT NON-RATED PARTITIONS.CONTIN. STL RUNNER DEFLECTION TRACK TYPICAL. PROVIDE MOVEMENT GAPPARTITION: NON RATED A14 7/8"(3 5/8" STUD)ASTUD DEPTHS BASED ON THE FOLLOWING: 2 1/2" STUDS MAX HEIGHT 11'-3" 3 5/8" STUDS MAX HEIGHT 16'-5" 4" STUDS MAX HEIGHT 18'-4" TOP OF EXIST. FLOOR CONSTRUCTION, U.O.N.SEE FINISH SCHEDULEFOR WALL FINISH.PLANNOTESHEADBASEBPARTITION-1 HOUR RATEDASSEMBLY TO COMPLY WITH UL U419B1B: 1 HOUR-RATEDWIDTH TO MATCH ADJACENT EXISTINGPLANNOTESHEADC: 2 HOUR RATEDSHAFT WALL -2 HOUR RATEDASSEMBLY TO COMPLY WITH UL U415C15"2 1/2" STUDC(2) LAYER 1/2" FIRECODE C GWBUNDERSIDE OF FLOOR CONSTRUCTIONCONTINUOUS FIRE RATED SEALANT BOTH SIDES AND VERTICAL INTERFACE TYPICALCONTIN. STL RUNNER DEFLECTION TRACK TYPICAL. PROVIDE MOVEMENT GAP STEEL STUDSCHEDULED FLOOR FINISH AND BASECONTINUOUS FIRE RATED SEALANT BOTH SIDES AND VERTICAL INTERFACE TYPICALCONTINUOUS STEEL RUNNERTOP OF EXIST. FLOOR CONSTRUCTION, U.O.N.1 1/2" THERMAFIBER SOUND ATTENUATION FIRE BLANKET1" SHAFT WALL LINERBASEPLANNOTESHEADSCHEDULED FLOOR FINISH AND BASEACOUSTICAL CAULKINGUNDERSIDE OF FLOOR CONSTRUCTIONCONTINUOUS ACOUSTICAL SEALANTWALL FURRING -NON RATEDNO ACOUSTIC BATTETOP OF EXIST. FLOOR CONSTRUCTION, U.O.N.RESILIENT CHANNELBASEE: INSULATEDE14 1/8"1/2" RESILIENT CHANNELSCHEDULED WALL FINISH5/8" WALLBOARD3/4" PLYWOODMINERAL WOOL AS PER FIRE RATED MASTIC MANUFACTURER'S RECOMMENDATION1/2" AIR SPACEPLANNOTESHEADFULL HEIGHT SOUND ATTENUATIONBLANKET AT PARTITION TYPE P U.O.N.D: NON-INSULATEDTYPICAL:1. WIDTH VARIES, SEE PLAN2. ANCHOR STUD TO EXISTING WALL CONSTRUCTION, SPACE CLIPS EQUALLY AS REQUIRED PER MANUFACTURERS SPECIFICATION FOR HEIGHT OF FURRED WALLUNDERSIDE OF FLOOR CONSTRUCTIONNOTE: STUD DEPTHS BASED ON BRACING BACK TO STRUCTURE AS REQUIRED CONTIN. STL RUNNER DEFLECTIONTRACK TYPICAL. PROVIDEMOVEMENT GAP AS REQUIRED BYSTRUCTURALCONTINUOUS ACOUSTICAL SEALANTWALL FURRING -NON RATEDWITH INSULATIOND15 1/4"3 5/8" STUD WITH 1/2"SPACESTUD DEPTHS BASED ON THE FOLLOWING: 1 5/8" STUDS MAX HEIGHT 11'-0" 2 1/2" STUDS MAX HEIGHT 12'-6" 3 5/8" STUDS MAX HEIGHT 18'-7" D23 5/8"2 1/2" STUD WITH 1/2"SPACEBASESCHEDULED WALL FINISH.SCHEDULED FLOOR FINISH AND BASEACOUSTICAL CAULKINGSTEEL RUNNERTOP OF EXIST. FLOOR CONSTRUCTION, U.O.N.D000RAISED CHARACTERS AND BRAILLEPLASTIC SIGN FIELD1/8" SLIDING ACRYLIC LENS INSERTED INTO C-CHANNEL SHAPE FOR PAPER INSERT INSTALLATIONSPACE FOR PAPER INSERT0.06" CLEAR ACRYLIC UNDERSIZED BACKERPROVIDE BACK PLATE (SAME SIZE AND COLOR AS SIGN) WHEN MOUNTING ON GLASSRAISED CHARACTERS AND BRAILLEPLASTIC SIGN FIELD1/8" SLIDING ACRYLIC LENS INSERTED INTO C-CHANNEL SHAPE FOR PAPER INSERT INSTALLATIONSPACE FOR PAPER INSERTPROVIDE BACK PLATE (SAME SIZE AND COLOR AS SIGN) WHEN MOUNTING ON GLASSINTERIOR ROOM IDENTIFICATION SIGNAGE:1. A ROOM SIGN, AS DETAILED HERE, SHALL BE PROVIDED AND INSTALLED FOR EACH NEW DOOR IN THE PROJECT AREA.2. WHEN MOUNTING ON GLASS, PROVIDE BACKING (SAME SIZE AS SIGN) ON OPPOSITE SIDE OF THE GLASS.3. SUBMIT SHOP DRAWINGS SHOWING SCHEDULE LAYOUT, PROFILES AND PRODUCT COMPONENTS, INCLUDING MATERIAL DETAILS, DIMENSIONS, ANCHORAGE, AND ACCESSORIES FOR ARCHITECT'S REVIEW AND APPROVAL BEFORE STARTING FABRICATION.4. ALL SIGNAGE SYSTEMS SHALL MEET REQUIREMENTS OF THE AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG) AND LOCAL AMENDMENTS AND MODIFICATIONS.5. RAISED LETTERING AND/OR NUMERALS: COMPUTER-CUT CHARACTERS WITH MATTE FINISH, COLOR AS SPECIFIED FROM MANUFACTURER'S STANDARD COLOR CHART. SHALL EXTEND A MINIMUM OF 1/32" FROM THE SIGN SURFACE. PHOTOPOLYMER TAGS SHALL NOT BE ACCEPTABLE.6. GRADE 2 BRAILLE: CLEAR RASTER BALLS COMPUTER DRILLED AND PRESSURE INSERTED INTO SIGN FACE, SHALL BE HALF-HEMISPHERE IN SHAPE AND SHALL EXTEND A MINIMUM OF 0.025" FROM THE SIGN SURFACE. OTHER METHODS OF MANUFACTURE, INCLUDING SURFACE APPLIED PHOTOPOLYMER BRAILLE TAGS SHALL NOT BE ACCEPTABLE.7. FASTENER: VERY HIGH BOND (VHB) .030 INCH THICK DOUBLE-FACE TAPE.FINISHES:1. COLORS AS SELECTED FROM THE MANUFACTURER'S STANDARD CHART.2. PATTERNS: AS SELECTED FROM THE MANUFACTURER'S STANDARD CHART.1' - 0"0' - 9 1/2"7/8" THUMBSLOT0' - 8 3/8"0' - 10 7/8"0' - 11"1/8" ACRYLIC BACKERINSERT SLOTVINYL TAPEFILLER1/16" NON-GLARE ACRYLICFILLER1/16" NON-GLARE ACRYLICRevisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs indicatedFINISH SCHEDULE & PARTITIONTYPESA-6036" = 1'-0"1ROOM SIGNAGE DETAIL6" = 1'-0"2ROOM SIGNAGE DETAILFINISH SCHEDULEROOMNUMBERROOM NAME FLOOR FINISHBASEFINISHWALL FINISHCEILING FINISHCOMMENTSNORTH EAST SOUTH WEST50044 CORRIDOR CP-1RB-1 PT-3 PT-3 PT-3 PT-3 ACT551 LABORATORY EXPOSED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED, PNT-5 INCLUDE FLOOR PAINT MARKING ON EXPOSED CONCRETE551B STORAGE EXPOSED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED, PNT-5551A STORAGE EXPOSED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED, PNT-5
Revisions:Issue for Bid December 15, 2020Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20 Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper Road Endwell, NY 13760607-231-6674 TTrophy Point4588 South Park AvenueBlasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor Renovation12" = 1'-0"INTERIOR 3D VIEWSA-700N.T.S2PRELIMINARY RENDERING LOOKINGEAST - ALTERNATE BID 1N.T.S1PRELIMINARY RENDERING LOOKINGEASTN.T.S3PRELIMINARY RENDERING LOOKINGWEST
DESIGN DATA NOTES
SEISMIC LOADS:4.
GENERAL:1.
LOADING SCHEDULE (PSF)
MISC.LIVE
LOADLEVELEXISTING
SLAB
EXISTING CEILING
AND MECHANICAL
6.STRUCTURAL MATERIAL STRENGTHS:
STRUCTURAL AND MISCELLANEOUS STEEL:
ROLLED STEEL W SHAPES
ROLLED STEEL C, S, M, MC, AND HP SHAPES
ROLLED STEEL PLATES, BARS, AND ANGLES
HOLLOW STRUCTURAL SECTIONS (HSS)
PIPE
FOR CONNECTIONS, PROVIDE HIGHER GRADE AS REQUIRED FOR CAPACITY.
- ASTM A 992
- ASTM A 36 OR ASTM A 572,
GRADE 50
- ASTM A 36 OR ASTM A 572,
GRADE 50
- ASTM A 500, GRADE C
- ASTM A 53, TYPE E OR S, GRADE B
REINFORCING STEEL FOR CONCRETE:ASTM A 615, GRADE 60
2020 BUILDING CODE OF NEW YORK STATE (BCNYS)DESIGN PROVISIONS
RISK CATEGORY
TERRAIN/EXPOSURE CATEGORY
SEE 1/S001 FOR ADDITIONAL WIND LOAD DATA FOR ROOFS, OVERHANGS, COMPONENTS, AND
CLADDING.
117 mph
91 mph
0.85
1.0
0.85
ENCLOSED
±0.18
116 feet
ULTIMATE WIND SPEED (3 SECOND GUST) (Vult):
NOMINAL WIND SPEED (3 SECOND GUST) (Vasd):
DIRECTIONALITY FACTOR (kd):
TOPOGRAPHIC FACTOR (Kzt):
GUST EFFECT FACTOR (G):
ENCLOSURE CLASSIFICATION:
INTERNAL PRESSURE COEFFICIENT (GCpi):
HEIGHT OF MAIN ROOF:
CODE COMPLIANCE FOR EXISTING STRUCTURES:2.
DESIGN PROVISIONS
COMPLIANCE METHOD (EBCNYS)
ALTERATION LEVEL 2CLASSIFICATION OF WORK (EBCNYS)
2020 EXISTING BUILDING CODE OF NEW YORK STATE (EBCNYS)
WORK AREA
THE FOLLOWING GRAVITY LOAD CARRYING ELEMENTS HAVE BEEN EVALUATED BASED ON THE LIVE
LOAD AND DEAD LOAD REQUIREMENTS DESCRIBED BELOW:
PENTHOUSE FLOOR BEAMS AT NEW MECHANICAL UNIT. ROOF BEAMS AT NEW EXHAUST FAN.
EXISTING STRUCTURAL ELEMENTS RESISTING LATERAL LOADS ARE NO LESS CONFORMING TO THE
PROVISIONS OF THE 2020 EBCNYS WITH RESPECT TO EARTHQUAKE AND WIND DESIGN THAN THEY
WERE PRIOR TO THIS WORK. THEREFORE LATERAL LOADS HAVE NOT BEEN EVALUATED FOR THIS
STRUCTURE.
SITE CLASS:
SHORT-PERIOD DESIGN ACCELERATION (Sds):
ONE-SECOND DESIGN ACCELERATION (Sd1):
SHORT PERIOD MAPPED SPECTRAL RESPONSE (Ss):
ONE-SECOND MAPPED SPECTRAL RESPONSE (S1):
SEISMIC DESIGN CATEGORY:
IMPORTANCE FACTOR (Ie):
D (ASSUMED)
0.127
0.073
0.119
0.045
B
1.25
WIND LOADS:
GROUND SNOW LOAD (Pg)
FLAT-ROOF SNOW LOAD (Pf)
SNOW EXPOSURE FACTOR (Ce)
THERMAL FACTOR (Ct)
IMPORTANCE FACTOR (Is)
40 psf
31 psf
1.0
1.0
1.1
5.
SNOW LOADS:3.
III
C
TOTAL
LOAD REMARKS
HIGH ROOF
PENTHOUSE
65
77
70
10
20
38
30
200
185
325
INCLUDES HUNG
MEP EQUIPMENT
3" TOPPING SLAB
ROOFING AND
INSULATION
****
**
*
***
**
1. DIMENSIONS TO, OF, AND IN EXISTING STRUCTURE SHALL BE VERIFIED IN FIELD BY CONTRACTOR.
2. DO NOT SCALE DRAWINGS. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY DISCREPANCIES IN
DIMENSIONS BETWEEN EXISTING CONDITIONS AND/OR ARCHITECTURAL DRAWINGS AND THE
STRUCTURAL DRAWINGS.
3. DO NOT CHANGE SIZE OR SPACING OF STRUCTURAL ELEMENTS.
4. DETAILS SHOWN ARE TYPICAL; SIMILAR DETAILS APPLY TO SIMILAR CONDITIONS UNLESS
OTHERWISE INDICATED.
5. THE NOTES ON THIS DRAWING ARE TYPICAL UNLESS OTHERWISE INDICATED.
6. CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING OF PROPOSED DEVIATIONS OR
SUBSTITUTIONS FROM DIMENSIONS, MATERIALS, OR EQUIPMENT SHOWN ON THE DRAWINGS AND
MAKE ONLY THOSE DEVIATIONS OR SUBSTITUTIONS ACCEPTED BY ENGINEER.
7. CONTRACTOR SHALL DETERMINE EXACT LOCATIONS OF EXISTING UTILITIES BEFORE COMMENCING
WORK. CONTRACTOR AGREES TO BE FULLY RESPONSIBLE FOR DAMAGES WHICH MIGHT OCCUR AS
A RESULT OF FAILING TO EXACTLY LOCATE AND PRESERVE EXISTING UTILITIES.
8. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY.
CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION SAFETY.
GENERAL NOTES
1. LOCATE MECHANICAL UNITS AS SHOWN; COORDINATE WITH MECHANICAL DRAWINGS. NOTIFY
ENGINEER IF ACTUAL UNIT WEIGHTS EXCEED THE WEIGHTS SHOWN ON DRAWINGS.
2. CONNECTION DESIGN BY FABRICATOR WILL BE SUBJECT TO REVIEW BY ENGINEER.
3. DO NOT PLACE HOLES THROUGH STRUCTURAL STEEL MEMBERS EXCEPT AS SHOWN AND DETAILED
ON STRUCTURAL DRAWINGS.
4. WHERE FILLET WELD SIZES ARE NOT SPECIFICALLY NOTED, THE FABRICATOR SHALL DETAIL A
MINIMUM SIZE FILLET WELD IN ACCORDANCE WITH AWS STANDARDS. THE ACTUAL SIZES SHALL BE
SHOWN ON THE SHOP DRAWINGS.
STRUCTURAL STEEL NOTES
1. THE OWNER WILL ENGAGE THE SERVICES OF A QUALIFIED SPECIAL INSPECTOR FOR THIS PROJECT,
WHO WILL PROVIDE AND/OR COORDINATE INSPECTION AND TESTING REQUIREMENTS AS
NECESSARY IN ACCORDANCE WITH THE PROVISIONS OF CHAPTER 17 OF THE BCNYS.
2. THE REGISTERED DESIGN PROFESSIONAL HAS PREPARED A STATEMENT OF SPECIAL INSPECTIONS,
WHICH INCLUDES SPECIFICATION 014533, AND THE SCHEDULE OF SPECIAL INSPECTIONS. THESE
DOCUMENTS WILL BE SUBMITTED WITH THE CONTRACT DOCUMENTS AND THE APPLICATION FOR
BUILDING PERMIT TO THE CODE ENFORCEMENT OFFICIAL.
3. SPECIAL INSPECTIONS AND TESTING SHALL BE CONTINUOUS OR PERIODIC DURING THE
PERFORMANCE OF THE WORK, AS NOTED.
4. THE CONTRACTOR SHALL HOLD A PRE-CONSTRUCTION MEETING WITH THE REGISTERED DESIGN
PROFESSIONAL, SPECIAL INSPECTOR, TESTING AGENCY, AND AFFECTED SUB-CONTRACTORS TO
REVIEW THE REQUIRED SPECIAL INSPECTION AND TESTING REQUIREMENTS FOR THE PROJECT. THE
CONTRACTOR SHALL DISTRIBUTE CONSTRUCTION SCHEDULES TO EACH ATTENDEE.
5. THE SPECIAL INSPECTOR SHALL SUBMIT INTERIM REPORTS AND, AT THE COMPLETION OF SPECIAL
INSPECTIONS, A FINAL STATEMENT OF SPECIAL INSPECTIONS. REPORTS SHALL BE STAMPED AND
SIGNED BY A PROFESSIONAL ENGINEER.
6. THE SPECIAL INSPECTOR SHALL NOTIFY THE CONTRACTOR IMMEDIATELY OF DISCREPANCIES.
SUBSEQUENT REPORTS SHALL NOTE WHEN AND HOW DEFICIENCIES WERE CORRECTED. THE
SPECIAL INSPECTOR SHALL NOTIFY THE REGISTERED DESIGN PROFESSIONAL AND THE CODE
ENFORCEMENT OFFICIAL OF DISCREPANCIES WHICH HAVE NOT BEEN CORRECTED.
7. THE CONTRACTOR SHALL COOPERATE WITH THE SPECIAL INSPECTOR INCLUDING ADVANCE
NOTIFICATION OF REQUIRED INSPECTION OR TEST, INCIDENTAL LABOR, AND SAFE ACCESS TO THE
WORK AREAS, AND ACCESS TO CONTRACT DOCUMENTS SO THAT INSPECTIONS AND TESTING MAY
BE PERFORMED WITHOUT HINDRANCE.
8. THE SPECIAL INSPECTION PROGRAM SHALL IN NO WAY RELIEVE THE CONTRACTOR OF THE
OBLIGATION TO PERFORM THE WORK IN ACCORDANCE WITH THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS OR FROM IMPLEMENTING AN EFFECTIVE QUALITY CONTROL PROGRAM.
9. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
SPECIAL INSPECTION NOTES
Revisions:
Issue for Bid December 15, 2020
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 13760
607-231-6674 T
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
Scale:
Fifth Floor Renovation
12" = 1'-0"
DESIGN DATA AND GENERAL
NOTES
S001
December 15, 2020
S001_ABBREVIATIONS LEGEND
ADJ ADJACENT EXT EXTERIOR PE PROFESSIONAL ENGINEER
L ANGLE EOD EDGE OF DECK PERP PERPENDICULAR
APPROX APPROXIMATE EOS EDGE OF SLAB PLF POUNDS PER LINEAL
ARCH ARCHITECT FD FLOOR DRAIN FOOT
ARCHITECTURAL FDN FOUNDATION PSF POUNDS PER SQUARE
B/ BOTTOM OF FTG FOOTING FOOT
BLDG BUILDING GA GAUGE PSI POUNDS PER SQUARE
BRG BEARING GALV GALVANIZED INCH
BP BASE PLATE HSS HOLLOW STEEL SECTION PCF POUNDS PER CUBIC
CANT CANTILEVER HORIZ HORIZONTAL FOOT
CJ CONTROL,HI HIGH PC PRECAST
CONTRACTION, HP HIGH POINT PSL PARALLEL STRAND
CONSTRUCTION JOINT HVAC HEATING/VENTILATING/LUMBER
CMU CONCRETE MASONRY INFO INFORMATION R RADIUS
UNIT(S)INT INTERIOR RD ROOF DRAIN
CONC CONCRETE INV INVERT RDP REGISTERED DESIGN
CONT CONTINUOUS K KIPS PROFESSIONAL
COL COLUMN LG LONG REQD REQUIRED
CFMF COLD-FORMED LLH LONG LEG HORIZONTAL REINF REINFORCING OR
METAL FRAMING LLV LONG LEG VERTICAL REINFORCED
COORD COORDINATE LOC LOCATION REV REVISION OR REVISED
DIA DIAMETER LW LIGHT WEIGHT RO ROUGH OPENING
DIM DIMENSION LVL LAMINATED VENEER SIM SIMILAR
DN DOWN LUMBER SPA SPACE
do DITTO LO LOW STD STANDARD
DWG DRAWING MANUF MANUFACTURER SF SQUARE FEET
EA EACH MAX MAXIMUM SS STAINLESS STEEL
EF EACH FACE MECH MECHANICAL STL STEEL
EJ EXPANSION JOINT MIN MINIMUM SQ SQUARE
ELEC ELECTRICAL MISC MISCELLANEOUS T/ TOP OF
EL ELEVATION MO MASONRY OPENING TYP TYPICAL
ELEV ELEVATOR NA NOT APPLICABLE UNO UNLESS NOTED
ENGR ENGINEER NIC NOT IN CONTRACT OTHERWISE
EMBD EMBEDDED NOM NOMINAL VERT VERTICAL
EQ EQUAL NW NORMAL WEIGHT VIF VERIFY IN FIELD
EQUIP EQUIPMENT OC ON CENTER W/ WITH
ES EACH SIDE OD OUTSIDE DIAMETER WP WORK POINT
EW EACH WAY OPNG OPENING WWR WELDED WIRE
EXIST EXISTING OPP OPPOSITE REINFORCEMENT
PAF POWDER ACTUATED WCJ WALL CONTROL OR
FASTENER CONSTRUCTION JOINT
eG
eF8
eF
eE
eD
e3 e4
eW21 X50
eW12X16eW24X55eW24X55eW16X31eW24X55eW24X55eW16X31
eW16X26
eW24X76
eW16X31
eW16X26
eW16X26
eW16X26
eW16X26
OUTLINE OF ACS-8 AHU,
MAX WT = 5,600LB
OUTLINE OF 6" CONC
HOUSEKEEPING PAD,
SEE 3/S100. SEE MECH
DWGS FOR EQUIPMENT
SIZE, HOUSE KEEPING PAD
EXTENDS 6" BEYOND
EQUIPMENT EXTENTS
EXIST 4 1/2" CONC SLAB ON 3" x18GA
GALV MTL DECK WITH 3" CONC TOPPING
(10 1/2" TOTAL THICKNESS)
eG
eF8
eF
eE
eD
e3 e4
eW 18X4 0
eW14X22eW14X22eW18X40eW18X40eW18X40eW18X40eW24X55
eW12X19
eW12X22
eW12X19
eW12X19
eW12X19
eW12X19
eW14X22
6" (TYP)
OUTLINE OF NEW OPENING
FOR INTAKE LOUVER, SEE
MECH AND ARCH DWGS FOR
SIZE AND LOCATION. SEE
4/S100 FOR FRAME DETAIL.
INSTALL FRAME PRIOR TO
SAWCUTTING OPENING.
EXIST 2 1/2" CONC SLAB ON 3" x18GA
GALV MTL DECK
(5 1/2" TOTAL THICKNESS)
DRILL AND GROUT
#4x1'-0" AT 2'-0"OC
3/4" CHAMFER
#4 AT 16"OC
3" ±6"NOTE:
COORDINATE PAD LOCATIONS WITH ACCEPTED SHOP
DRAWINGS AND SUBMITTALS.
EXIST 3" CONC
TOPPING
EXIST 3" COMPOSITE
METAL DECK7 1/2" ±<
<<
<<
SPAN MEMBER 1AAPLAN
A-A
MEMBER 1, (4) SIDES
(TYP) SEE TABLE
SEE ARCH OR MECH DWGS
FOR FRAME DIMS AND LOCS
L 4'-0"
4'-0" L 6'-0"
6'-0" L 13'-0"
L3x3x1/4
L4x4x1/4
C6x8.2
EXIST STEEL BEAM
COPE MEMBER AS REQD
WHERE DECK IS
TIGHT TO T/EXIST BEAM7'-6 5/8"± (VIF)3/16 1 1/2 (TYP)
1. T/EXISTING STEEL ELEVATION (+98'- 8 1/2") UNLESS NOTED OTHERWISE.
2. ELEVATIONS NOTED THUS ( ) ARE TO T/STEEL WITH RESPECT TO ELEVATION (+98'- 8 1/2").
3. NOTIFY ENGINEER IF ACTUAL WEIGHTS OF MEP EQUIPMENT EXCEED WEIGHTS NOTED IN
DRAWINGS. CONTRACTOR SHALL SUBMIT LOAD DATA TO ENGINEER FOR REVIEW PRIOR TO
PROCEEDING WITH INSTALLATION OF EQUIPMENT AND ANY ASSOCIATED STRUCTURAL
SUPPORTS. COORDINATE EXACT LOCATION OF EQUIPMENT (INCLUDING HOUSEKEEPING PADS,
RAILS, STRUCTURAL FRAMING, ETC.) WITH MECHANICAL DRAWINGS AND EQUIPMENT
SUPPLIERS.
NOTES:
1. T/STEEL ELEVATION (+118'-10 1/2") UNLESS NOTED OTHERWISE.
2. ELEVATIONS NOTED THUS ( ) ARE TO T/STEEL (B/DECK) WITH RESPECT
TO ELEVATION (+118'-10 1/2").
NOTES:
S100
2
S100
1
Revisions:
Issue for Bid December 15, 2020
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 13760
607-231-6674 T
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
Scale:
Fifth Floor Renovation
As indicated
PARTIAL FRAMING PLANS
S100
December 15, 2020
1/4" = 1'-0"S100
1 PARTIAL PENTHOUSE FLOOR FRAMING PLAN
1/4" = 1'-0"S100
2 PARTIAL PLAN HI ROOF FRAMING
3/4" = 1'-0"S100
3 HOUSEKEEPING PAD DETAIL
1/4" = 1'-0"S100
4 WELDED ANGLE FRAME DETAIL
GENERAL NOTES:A. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DISPOSE OF ALL DEMOLITION DEBRIS AND MATERIALS OFF SITE IN A PROPER LEGAL MANNER.B. ALL NEW PENETRATIONS THROUGH WALLS, FLOORS AND ROOFS SHALL BE PROVIDED FOR INSTALLATION OF MECHANICAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, EQUIPMENT, DUCTWORK, PIPING, ETC. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE FIRE/SMOKE STOPPED. ALL PENETRATIONS THROUGH NON RATED WALLS SHALL BE SEALED WITH A NON-HARDENING SEALANT ON BOTH SIDES OF WALL PENETRATION TO REDUCE NOISE TRANSMISSION.C. THE DUCTWORK SIZES AND TYPES (ROUND, RECTANGULAR AND FLAT OVAL)WERE SELECTED FOR SPACE LIMITATION WITHIN THE RENOVATED AREA. IN ADDITION, THE DUCTWORK SIZES AND TYPES WERE CHOSEN TO ALLOW SPACE ABOVE THE CEILINGS FOR FUTURE DUCTWORK, PIPING AND/OR CONDUIT. IT IS NOT ACCEPTABLE FOR THE CONTRACTOR TO CHANGE THE SIZE OR TYPE OF DUCTWORK FOR BIDDING OR INSTALLATION UNLESS SPECIFICALLY APPROVED BY THE ENGINEER. D. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE ALL SHUTDOWNS OF AIR HANDLING, CHILLED WATER, HOT WATER, STEAM, ETC. SYSTEMS WITH CORNELL UNIVERSITY FACILITY PERSONNEL FOR TIE-IN CONNECTIONS. ALL SHUT DOWNS WILL OCCUR DURING NIGHTS OR WEEKENDS. THE CONTRACTOR SHALL ASSIST THE UNIVERSITY PERSONNEL IN SHUTTING DOWN, DRAINING, VENTING, ETC. OF SYSTEM TO FACILITATE THE INTENDED WORK.E. A MINIMUM OF 1'-6" SHALL BE PROVIDED IN FRONT OF CONTROL ACCESS ENCLOSURES AT ALL TERMINAL UNITS. NO PIPING OR CONDUIT SHALL BE DIRECTLY INSTALLED BELOW AIR TERMINAL UNIT ACCESS ENCLOSURES THAT WILL PROHIBIT ACCESS UP TO THE CONTROL ENCLOSURE. COORDINATE THESE REQUIREMENTS WITH ALL OTHER TRADES ON THE PROJECT. IF PROPER SERVICE ACCESS IS NOT MAINTAINED BECAUSE OF POOR COORDINATION, THE CONTRACTOR SHALL RELOCATE OBSTRUCTIONS AT NO ADDITIONAL COST TO THE OWNER.F. PROVIDE A VOLUME DAMPER AT EACH DIFFUSER AND GRILLE FOR PROPER BALANCING REGARDLESS IF SHOWN ON DRAWINGS. ALL VOLUME DAMPERS SHALL BE A MINIMUM OF 6'-0" FROM DIFFUSER OR GRILLE CONNECTION.IF FLEXIBLE DUCTWORK IS UTILIZED FOR FINAL CONNECTION AT GRILLES, THE CROSS SECTIONAL AREA OF THE FLEXIBLE DUCTWORK SHALL NOT BE LESS THAN THE CROSS SECTIONAL AREA OF THE GRILLE NECK.G. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE LOCATIONS OF ALL ROOM TEMPERATURE SENSORS WITH THE ARCHITECT/ENGINEER. THE CONTRACTOR SHALL SCHEDULE A WALK THROUGH WITH THE ARCHITECT/ENGINEER TO LOCATE SENSOR LOCATIONS PRIOR TO INSTALLATION. THE TEMPERATURE SENSORS SHALL BE INSTALLED IN ALIGNMENT WITH ELECTRICAL, FIRE, AND OTHER DEVICES WHEN LOCATED ON COMMON WALLS.H. DAMAGE TO EXISTING SYSTEMS (EQUIPMENT, PIPING, DUCTWORK, CONTROLS AND ACCESSORIES) SHOWN TO REMAIN AS A RESULT OF THE CONTRACTORS WORK IS THE RESPONSIBILITY OF THE CONTRACTOR TO REPAIR AND/OR REPLACE WITH SIMILAR OR LIKE MATERIALS AT NO ADDITIONAL COST TO THE OWNER.I. COORDINATE ALL SHUT DOWNS WITH OWNER PRIOR TO CONSTRUCTION.J. THE DEMOLITION DRAWINGS SHOW IN GENERAL MAJOR EQUIPMENT, PIPING AND DUCTWORK REMOVALS. THE INTENT IS NOT TO IDENTIFY ALL MISCELLANEOUS PIPING, PIPING ACCESSORIES, DUCTWORK, DUCTWORK ACCESSORIES, SUPPORTS, CONTROLS, CONTROL ACCESSORIES, CONTROL WIRING, CONDUIT, AND CONTROL PNEUMATIC TUBING AND ACCESSORIES TO BE DISCONNECTED AND REMOVED BUT IS THE REQUIREMENTS UNDER THIS CONTRACT. NO EQUIPMENT, PIPING OR DUCTWORK SHALL BE ABANDONED IN PLACE UNLESS OTHERWISE NOTED ON THE DRAWINGS.K. THE MOUNTING HEIGHT FOR ALL ROOM THERMOSTATS OR SENSORS SHALL BE 48 IN. TO TOP OF THE COVER.L. UNLESS SHOWN ON THE ARCHITECTURAL DRAWINGS, IT IS THE RESPONSIBILITY OF THIS CONTRACT TO PATCH WITH LIKE MATERIAL AND FINISH ALL EXISTING DUCTWORK OR PIPE PENETRATIONS THROUGH FLOORS AND WALLS AFTER DEMOLITION. M. EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION DOCUMENTS AND ARE NOT GUARANTEED. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BID. NO ALLOWANCE WILL BE MADE FOR ADDITIONAL COSTS DUE TO CONTRACTORS FAILURE TO VERIFY EXISTING CONDITIONS AND DIMENSIONS.N. THE OWNER OCCUPIED AREAS INCLUDE SENSITIVE EQUIPMENT AND RESEARCH WHICH MUST NOT BE INTERRUPTED OR OTHERWISE DISTRUPTED WITHOUT PRIOR NOTICE AND APPROPRIATE PLANNING. MBHTHOUSAND BTU/HOUR(E)EXISTINGDOUBLE LINE RECTANGULARDUCT CONTINUEDFPMFEET PER MINUTEAIR FLOWAFFABOVE FINISHED FLOORPIPE ANCHORG.C.GENERAL CONTRACTORPIPE GUIDEE.C.ELECTRICAL CONTRACTOREXPANSION COMPENSATOR WITH GUIDESN.C.NORMALLY CLOSEDPRE-FAB EXPANSION LOOPTEMPERATURE SENSORSTRAINERPRESSURE GAUGETHERMOMETERUNION24x12DNUPAIR VENTV24x1214x86" BOOTTAPTT THERMOSTATIC TRAP14"18"LATERALFT FLOAT & THERMOSTATIC TRAPSUPPLY DIFFUSER, REGISTER OR GRILLETD THERMODYNAMIC TRAPFLEXIBLE DUCTWORKBT BUCKET TRAPCOMPRESSED AIRADIRECTION OF FLOWBBD BOILER BLOW DOWNCONDENSER WATER SUPPLYCSCR CONDENSER WATER RETURNCWSCHILLED WATER SUPPLYCWR CHILLED WATER RETURNDDRAINFUEL OIL FILLFOFFUEL OIL GAUGEFOGFOS FUEL OIL SUPPLYFOR FUEL OIL RETURNFOV FUEL OIL TANK VENTGGASGLYCOL SUPPLYGSGLYCOL RETURNGRHPWS HEAT PUMP WATER SUPPLYHPWR HEAT PUMP WATER RETURNHWS HOT WATER SUPPLYHWR HOT WATER RETURNHG HOT GASLPSLOW PRESSURE STEAMLPC LOW PRESSURE CONDENSATEMPS MEDIUM PRESSURE STEAMMPC MEDIUM PRESSURE CONDENSATEHPS HIGH PRESSURE STEAMHPC HIGH PRESSURE CONDENSATEPCPUMPED CONDENSATERD REFRIGERANT DISCHARGERL REFRIGERANT LIQUIDRSREFRIGERANT SUCTIONVAC VACUUMCWDOMESTIC COLD WATEREXISTING WORK TO BE REMOVEDDOUBLE LINE PIPE ORROUND DUCT CONTINUEDEPNEUMATIC THERMOSTATNTS NOT TO SCALE(DBL) DOUBLE WALL LINED DUCTCFM CUBIC FEET PER MINUTEADACCESS DOORP.C. PLUMBING CONTRACTORN.O. NORMALLY OPENHUMIDISTATROUND DUCT - IN INCHES12"24x12DNUP14"CONICALTEE18"VOLUME DAMPERCAP OR PLUGELBOW DOWNELBOW UPAAD AUTOMATIC AIR DAMPERFD FIRE DAMPERSDSMOKE DAMPERBDD BACK DRAFT DAMPERMMOTORIZED DAMPERBALL VALVEGATE VALVECHECK VALVEBALANCING VALVEBUTTERFLY VALVEPRESSURE REDUCING VALVEPRVCONTROL VALVEPRESSURE/TEMPERATURE TEST PLUG(L)(2L) ACOUSTIC THERMAL LINING - 2" THICKM.C. MECHANICAL CONTRACTORW/W WALL TO WALLGTHERMOSTAT/SENSOR WITH GUARDGDUCT SECTION - SUPPLYDUCT SECTION - RETURNWIDTH A x DEPTH BABRD24x1214"6" BOOTTAPBG BLAST GATEFIN TUBE RADIATIONVALANCEABCREGISTER, GRILLE OR DIFFUSER TAGA = TYPEB = NECK SIZEC = CFMBCDFIN TUBE RADIATION TAGFT-A = TYPEB = FIN TUBE LENGTHC = ENCLOSURE LENGTHD = GPMFT-AABCDVALANCE TAGA = TYPEB = COIL SIZEC = COOLING GPMD = HEATING GPMPOINT OF CONNECTIONPOINT OF DISCONNECTIONBOTTOM TAPTRIPLE DUTY VALVETDGLOBE VALVETHREE WAY CONTROL VALVESUCTION DIFFUSERSDDRAIN VALVE WITH HOSE CONNECTION,CAP AND CHAINFC FLEX CONNECTOR - DUCTWORKFLEXIBLE CONNECTOR - PIPINGAIR TERMINAL UNIT AND TAG (OPTION 1)ABCAIR TERMINAL UNIT TAG (OPTION 2)A = UNIT NO.B = MAXIMUM CFMC = MINIMUM CFMAxBFODUCT SECTION - FLAT OVAL (FO)VVENTREDUCERSHSACOUSTIC THERMAL LINING - 1-1/2" THICKEXHAUST GRILLERETURN REGISTERSINGLE LINE PIPE CONTINUEDTRANSITION SQUARE TO ROUNDRISE IN DUCT - IN DIRECTION OF AIRFLOWDROP IN DUCT - IN DIRECTION OF AIRFLOWSUPPLY DUCT TURNING UP OR DOWNRETURN DUCT TURNING UP OR DOWNSUPPLY/RETURN RECTANGULAR MAINRECTANGULAR BRANCHSUPPLY/RETURN RECTANGULAR MAINROUND BRANCHSUPPLY/RETURN ROUND MAINROUND BRANCHSUPPLY/RETURN ROUND MAINROUND BRANCHMITERED ELBOW WITH TURNING VANESDESCRIPTIONSYMBOLDESCRIPTIONSYMBOLTRELIEF VALVETHVAC SYMBOL LISTXXDRAWING KEYNOTEDEMOLITION KEYNOTEABCRADIANT CEILING PANEL TAGA = TYPEB = LENGTHC = GPMCARBON DIOXIDE SENSORCCARBON MONOXIDE SENSORCOGAS SENSORGSYMBOLDESCRIPTIONSYMBOLDESCRIPTIONAVERAGING SENSORSSSTART/STOPOCOPEN/CLOSEEDENABLE/DISABLETTEMPERATURE SENSOR(DUCT OR PIPE MOUNTED)HHUMIDITY SENSOR(DUCT MOUNTED)IPELECTRICAL INTERFACEAUTOMATIC AIR DAMPER(PARALLEL BLADE)AUTOMATIC AIR DAMPER(OPPOSED BLADE)EELECTRIC/ELECTRONICCONTROL VALVE (3-WAY)EES END SWITCHEA EXHAUST AIRMOISTURE SENSOROCCUPANCY SENSORFLOW METERSUPPLY FANSFBTU ENERGY METERBTUPDIFFERENTIAL STATICPRESSURE SWITCHALARMSTATUSPROBE SENSORRELAYFREEZE-STATFZEELECTRIC ACTUATORCURRENT TRANSDUCERFLOW SENSORAIR FLOW MEASURINGSTATIONHARD WIRE INTERFACESSOLENOID VALVESMMANUAL SWITCHTHERMOSTATIC EXPANSIONVALVECARBON DIOXIDE SENSOR(DUCT MOUNTED)CO2BINARY POINTANALOG POINTTHERMOWELLPDIFFERENTIAL STATICPRESSURE TRANSMITTERCONTROLS SCHEMATIC SYMBOL LISTASDADJUSTABLE SPEED DRIVER134aREFRIGERANT R134a SENSOR(WALL MOUNTED)CCCOOLING COILBASE MOUNTED PUMPFILTER BANKRETURN AIR FANRFEF EXHAUST AIR FANHCHEATING COILSMOKE CONTROL FANSCHUMIDIFIER DISPERSION GRIDEPELECTRIC/PNEUMATICSWITCH OR RELAYPEPNEUMATIC/ELECTRICSWITCH OR RELAYFFLOW TRANSMITTERPPRESSURE TRANSMITTERELECTRIC/PNEUMATICTRANSDUCERIEELECTRONIC/ELECTRICTRANSDUCERPNEUMATIC CONTROLVALVE (3-WAY)PNEUMATIC CONTROLVALVE (2-WAY)ELECTRIC/ELECTRONICCONTROL VALVE (2-WAY)PNEUMATIC ACTUATORMAIN TEMPERATURECONTROL AIR SOURCEAIN LINE PUMPHRCHEAT RECOVERY COILAIR TERMINAL UNIT WITH FACTORY ATTENUATOR (OPTION 1)VAV-X-XXVAV-X-XXLAB AIR VALVERADIANT CEILING PANELFLOW SWITCHVARIABLE FREQUENCY DRIVEGBGAS BURNERPPRESSURE SWITCHHUMIDIFIERHARSOSMFSFBUTTERFLY CONTROL DAMPERVFDOA OUTSIDE AIRRARETURN AIRSA SUPPLY AIRCARBON MONOXIDE SENSOR(DUCT MOUNTED)COF.L.FAIL LASTDEWPOINT SENSOR(DUCT MOUNTED)DPCCONDENSATE SENSORSTATIC PRESSURE SENSOR(DUCT MOUNTED)SPCTBI BINARY INPUTBO BINARY OUTPUTAI ANALOG INPUTAO ANALOG OUTPUTBV BINARY VALUEAV ANALOG VALUEHIGH LEVEL SWITCHHILOWLOW LEVEL SWITCHVENTURI AIRFLOW CONTROL VALVETRANSFORMERMOTOR STARTERMSROTATION DETECTORRDSMOKE DETECTORSDMOD MODULATINGELECTRIC TO PNEUMATIC TRANSDUCEREPSPEED COMMANDSCAOMADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE)COMNETWORK COMMUNICATION INTERFACE POINTSIGNALOUTCURRENT SENSORCSSIGNALOUTASIGNAL INAIR INASIGNAL INELECTRIC TO PNEUMATIC SWITCHLINE VOLTAGE THERMOSTATTNITROGEN DIOXIDE SENSORNMOTORSSPACE SENSOR WITH SETPOINT ADJUSTMENTSASSPACE SENSOR WITH OCCUPANCY OVERRIDESSPACE SENSOR WITH VISUAL DISPLAYSSPACE SENSOR WITH FAN ON/OFF SWITCHTROOM TEMPERATURE SENSOR WITH SETPOINT ADJUSTMENTTTTROOM TEMPERATURE SENSOR WITH OCCUPANCY OVERRIDEROOM TEMPERATURE SENSOR WITH VISUAL DISPLAYROOM TEMPERATURE SENSOR WITH FAN ON/OFF SWITCHDIGITAL INPUT (GENERAL)DIDODIGITAL OUTPUT (GENERAL)ANALOG INPUT (GENERAL)ANALOG OUTPUT (GENERAL)AIAOLIQUID IMMERSION TEMPERATURE SENSORTSINGLE POINT SENSORMMOVDFSAOVDFF.O. FAIL OPENRELATIVE HUMIDITY SENSORRHLOW LIMIT TEMPERATURE SWITCHFZPCWSPROCESS COLD WATER RETURNBUILDING COLD WATER SUPPLYBUILDING COLD WATER RETURNPCWRBCWSBCWRPROCESS COLD WATER SUPPLYDSDDUCT SMOKE DETECTORRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020GENERAL NOTES & SYMBOLSLIST -HVACH-000
GF8FEDCB234567G5H5X1K11109812X(E)75x55 UP& DOWN(E)52x14(E)14x4(E)16x6(E)8"(E)14x8(E)26x10(E)20x6(E)30x10(E)28x8(E)8x4(E)26x10(E)12" UP &DOWN(E)26x12 UP(E)FD(E)FD(E)FD(E)FD(E)75x55 UP& DOWN(E)FD(E)FD(E)8"14x4(E)8"(E)26x8(E)20x8(E)14x4(E)16x6(E)14x4(E)12"(E)30x14(E)22x6 (TYP)(E)6"(E)24x8(E)18x8(E)12x6(E)30x14(E)22x6 (TYP)(E)12x6(E)18x8(E)24x8(E)16x12(E)20x10(E)8"(E)12x6(E)12x4(E)8"(E)12"(E)10"(E)30x8(E)24x12(E)18x8(E)22x6 (TYP)(E)12x6(E)12x6(E)12"(E)18x6(E)12x6(E)12x4(E)12x4(E)14x6(E)26x10(E)24x8(E)12x6(E)18x6(E)12x6(E)12x6(E)26x10(E)20x6(E)60x14(E)60x14(E)48x12(E)75x55(E)AAD(E)AAD(E)AAD(E)AAD(E)AAD(E)AAD(E)AAD5213311111144(E)VAV(E)VAV(E)VAV(E)VAV(E)VAV(E)VAV(E)VAV(E)VAV(E)VAV2222222222222222155(E)52x14(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD11144222221116(E)24x10 UP& DOWN(E)FD77Room571DATA CLOSET552ELEC. CLOSET50075LOUNGE568CORRIDOR50044Room503SHOP501Room504Room504ARoom502Room500STAIR# 250002Room508Room512Room514Room517Room578Room576Room574Room572MEN50022Room50076Room50073WOMEN500218O.E.D.O.E.D.9111Revisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH FLOOR PLAN -DUCTWORK DEMOLITIONH-1001/8" = 1'-0"1PARTIAL FIFTH FLOOR PLAN - DUCTWORK DEMOLITIONDEMOLITION NOTES1 DISCONNECT AND REMOVE DUCTWORK ANDDUCTWORK ACCESORIES.2 DISCONNECT AND REMOVE DIFFUSER OR GRILLE.3 DISCONNECT AND REMOVE FAN COIL UNIT, ASSOCIATEDDUCTWORK AND CONTROLS.4 DISCONNECT AND REMOVE AIR TERMINAL, AIRTERMINAL ACCESSORIES, ASSOCIATED DUCTWORK ANDCONTROLS.5 CAP DUCT AT POINT OF DISCONNECT.6 DISCONNECT AIR TERMINAL AND AIR TERMINALACCESSORIES. STORE AIR TERMINAL FOR REUSE.REFER TO NEW WORK PLANS FOR FURTHER DETAILS.7 REMOVE DUCTWORK TO THE WALL PENETRATION ANDCAP. DUCTWORK CAP SHALL BE CONCEALED BY THENEW WALL FINISHES.8 DISCONNECT AND REMOVE EXISTING FIRE DAMPER.9 DISCONNECT AND REMOVE DUCTWORK. TERMINATEWITH AN O.E.D.
GF8FEDCB234567G5H5X1K11109812X(E)FCU(E)AC(E)AC(E)AC(E)AC(E)AC(E)8" PCWS/RUP & DOWN(E)8" BCWS/RUP & DOWN(E)2"(E)4"(E)3"(E)1-1/2"(E)2"(E)2"(E)2"(E)1"(E)CWS(E)FCU(E)CWR(E)2-1/2"11112332222111144(E)1-1/2" HWS UP & DOWN(E)1-1/4" HWS UP & DOWN(E)1" HWR UP & DOWN(E)3/4"(E)3/4"(E)3/4"(E)3/4"(E)1" HWR UP & DOWN(E)FINTUBE(TYP)(E)3/4"(E)3/4"4116666665555555666(E)FINTUBE(TYP)(E)FINTUBE(TYP)(E)FINTUBE(TYP)(E)FINTUBE(TYP)(E)FINTUBE(TYP)7SS8S7S7S766666667SFINTUBE RADIATION PIPING SCHEMATIC 1111111Room571Room503SHOP501Room500Room502Room504Room504ARoom508Room50073WOMEN50021Room50076MEN50022ELEC. CLOSET50075DATA CLOSET552LOUNGE568CORRIDOR50044Room578Room576Room574Room572STAIR# 250002199Revisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH FLOOR PLAN -PIPING DEMOLITIONH-1011/8" = 1'-0"1PARTIAL FIFTH FLOOR PLAN - PIPING DEMOLITIONDEMOLITION NOTES1 DISCONNECT AND REMOVE PIPING AND PIPINGACCESSORIES.2 DISCONNECT AND REMOVE AC UNIT, ASSOCIATED PIPINGAND CONTROLS.3 DISCONNECT AND REMOVE FAN COIL UNIT, ASSOCIATEDPIPING AND CONTROLS.4 DISCONNECT AND REMOVE PNEUMATIC CONTROL VALVE.5 DISCONNECT AND REMOVE EXISTING FINTUBEENCLOSURE.6 DISCONNECT AND REMOVE EXISTING FINTUBE.7 DISCONNECT AND REMOVE EXISTING SENSOR.8 DISCONNECT AND REMOVE EXISTING OCCUPANCYOVERRIDE SWITCH.9 REMOVE INSULATION ON PIPING RISER WITHIN FIFTHFLOOR RENOVATION AREA.
GF8FEDCB234567G5H5X1K11109812X(E)75x55 UP& DOWN(E)12" UP &DOWN(E)26x12 UP(E)FD(E)FD(E)FD(E)FD(E)75x55 UP& DOWN(E)FD(E)FD(E)22x6 (TYP)(E)22x6 (TYP)(E)22x6 (TYP)(E)AAD(E)AAD(E)AAD(E)AAD(E)AAD(E)AAD(E)VAVSAV-1(E)VAV(E)VAV(E)VAV(E)VAV(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)FD(E)60x14(E)60x14(E)6"(E)24x8(E)18x8(E)12x6(E)12x6(E)18x8(E)24x8(E)16x12(E)12x6(E)12x4(E)8"(E)12"(E)10"(E)30x8(E)24x12(E)18x8(E)12x6(E)12x6(E)12"(E)18x6(E)12x6(E)12x4(E)12x4(E)14x6(E)26x10(E)20x6(E)60x14(E)60x14(E)48x12(E)75x55(E)52x14LABORATORY551STORAGE551BRoom50073WOMEN50021MEN50022Room50076ELEC. CLOSET50075DATA CLOSET552CORRIDOR50044Room572Room574Room576Room578Room571SAV-3GEV-3RD30x1622x10VAV-138x1238x12 UP30x16 UP30x16DD(E)24x10(E)24x8LOUNGE568RR6"6"6""16150TYP=3x2222A-30x141FD/SD(E)24x10 UP& DOWN(E)12"52x14(E)52x14FD/SDFD/SDx3612A-FD/SDx3612A-12"46x16(E)30x1414x8DR30x1224x1016x8RHC-28"28x1616x8x2222A700x86A1008x612"GEV-122x10GEV-2x86A1008x6x2222A700TYP=214"14"26x12SAV-2DRHC-124x1016x816x812x6 12x6VAV-220x1016x814"24x108"22x1026x12x2082345TYP=4x2082350TYP=2x2082350TYP=246x1628x1632x12DRDRDRD22x10x4212A138020x1020x1012"RHC-324x10RR14"4333333324x10x2262350TYP=2x2222A-(E)36x12O.E.D.O.E.D.230x142222DSDDSDDSD18x1218x12DSD6652600216007360063F45G5H51026x16 UP &38x12 DOWN30x16 UP &DOWN(E)24x20UP &(E)24x10 DOWN(E)76x54 UP & DOWN(E)36x10(E)FD(E)50x1448x16(E)FD(E)FD56752700217006370073F45G5H51030x16 UP &DOWN(E)24x20UP &(E)24x10 DOWN(E)76x54 UP & DOWN26x16 UP &DOWN(E)36x10(E)FD(E)FD(E)FD(E)48x16(E)50x1456GF8FE23456G5H5X111109(E)GENERATOR EXHAUST(E)LOUVERED PENTHOUSEINTAKE(E)LAB EXHAUST FAN (LEF-1)(E)VENTINTAKE PENTHOUSE LP-1(E)LOUVERED PENTHOUSEINTAKE(E)LOUVERED PENTHOUSEINTAKELP-1 TO BE 25' FROM ANY EXHAUST TERMINATION(E)PLUMBING VENT(E)ROOF DRAIN(E)ROOF DRAIN(E)ROOF DRAIN(E)PLUMBING VENTRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH, SIXTH &SEVENTH FLOOR PLANS -DUCTH-200DRAWING NOTES1 RELOCATE EXISTING AIR TERMINAL UNIT. RECONNECT ANDEXTEND CONTROL WIRING. TIE NEW DUCTWORK INTOTERMINAL UNIT.2 TIE DUCTWORK INTO EXISTING. TRANSITION AS REQUIREDTO MAKE THE CONNECTION.3 PROVIDE ASJ - JACKETING OVER DUCTWORK INSULATION INPREPARATION FOR PAINTING.4 ALL EXPOSED DUCTWORK WITHIN LAB SHALL BE CLEANEDAND DEGREASED IN PREPARATION FOR PAINTING.5 MAINTAIN 18" CLEAR BETWEEN SUPPLY DUCT RISER ANDEXISTING OPEN ENDED RETURN DUCT.6 REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OFEXISTING BEAMS WITHIN THE CHASE. OFFSET DUCTWORKWITHIN CHASE AS REQUIRED TO COORIDINATE WITHEXISTING BEAMS1/8" = 1'-0"1PARTIAL FIFTH FLOOR PLAN - DUCTWORK1/8" = 1'-0"3PARTIAL SIXTH FLOOR PLAN - DUCTWORK1/8" = 1'-0"4PARTIAL SEVENTH FLOOR PLAN - DUCTWORK1/8" = 1'-0"2PARTIAL ROOF PLAN - DUCTWORK
GF8FEDCB234567G5H5X1K11109812X(E)8" PWS/RUP & DOWN(E)8" BCWS/R UP & DOWN(E)4"LABORATORY551STORAGE551BCORRIDOR50044ELEC. CLOSET50075DATA CLOSET552LOUNGE568Room50076MEN50022WOMEN50021Room50073Room571Room572Room574Room576Room578(E)1-1/2" HWS UP & DOWN(E)1-1/4" HWS UP & DOWN(1.87GPM)(E)1" HWR UP & DOWN(1.87 GPM)(E)FINTUBE(TYP)(E)3/4"(E)3/4"3/4"3/4"(E)1" HWR UP & DOWN(E)FINTUBE(TYP)(E)3/4"(E)3/4"(3.27GPM)3333RHC-12-1/2"2-1/2"31-1/2" HWS/RUPHWS(E)FINTUBE(TYP)3/4"3/4"SSSSHWR(E)2-1/2"1212CWSCWR4SFINTUBE RADIATION PIPING SCHEMATIC 1255555555STO VAV-23/4"1 1/2"RHC-2RHC-31"1"66LABORATORY551ZONE 1ZONE 2LABORATORY551ZONE 3STO VAV-17777652600216007360063F8F45G5H5101-1/2" HWS/RUP & DOWN752700217006370073F8F45G5H5101-1/2" HWS/RUP & DOWNRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH, SIXTH &SEVENTH FLOOR PLANS -PIPINGH-2011/8" = 1'-0"1PARTIAL FIFTH FLOOR PLAN - PIPINGDRAWING NOTES1 PROVIDE NEW 2-WAY CONTROL VALVE WITH ELECTRONICACTUATION, CONTROLS AND CONTROL ACCESSORIES.PROVIDE PIPING AND PIPING ACCESSORIES AS REQUIREDTO ACCOMMODATE NEW CONNECTION.2 PROVIDE NEW CONTROLS AND CONTROL ACCESSORIESFOR EXISTING FIN TUBE RADIATION. REFER TO CONTROLSCHEMATIC AND SYSTEM SUMMARY FOR FURTHERREQUIREMENTS.3 PROVIDE NEW FINTUBE ENCLOSURE. ENCLOSURE SHALLBE EQUAL TO STERLING JVA-14.4 PROVIDE NEW OCCUPANCY OVERRIDE SWITCH.5 TIE PIPING INTO EXISTING. PROVIDE ALL PIPINGMODIFICATIONS AS REQUIRED TO MAKE THECONNECTION.6 RE-INSULATE PIPING RISER. PROVIDE JACKETING ASREQUIRED FOR PAINTING7 PROVIDE NEW FINTUBE ENCLOSURE TO WRAP THECOLUMN. ENCLOSURE SHALL BE EQUAL TO STERLINGJVA-7.1/8" = 1'-0"2PARTIAL SIXTH FLOOR PLAN - PIPING1/8" = 1'-0"3PARTIAL SEVENTH FLOOR PLAN - PIPING
807801801A8028006280480060F8FED34567G5H5X1K1110912(E)94x58 DOWN(E)94x58 DOWN(E)24x20 DOWN(E)12"DOWN TO 4TH FLOOR(E)24x20 DOWN(E)P-16(E)CV-5(E)GHWR(E)GHWS(E)EFCV-7EXPANSION TANKSERVING REHEAT LOOPEXPANSION TANKSERVING GLYCOL RUN-AROUND LOOP55 GALLONPOLY BARREL1PUMP P-18 & P-19PUMP P-2026x1626x16SA DN26x1630x1630x16EA DN30x1630x16HRC-2(E)12"36x1432x32UP TOLP-1ACS-812BCWSBCWRGHWRGHWS12"24x2224x2224x22UP TO(E)LEF-13(E)PCWS(E)PCWR(E)BCWS(E)BCWR(E)LPS(E)PC(E)LPS(E)BCWS(E)BCWR(E)PCWS(E)PCWRGHWRGHWS1 1/2"HWS/RDOWNHWSHWR(E)ACS-3(E)ACS-4PUMP P-21(E)8"(E)8"(E)6"2"2"(E)2"(E)8"(E)2 1/2"3/4"1 1/2"(E)2 1/2"(E)8"(E)124x58(E)40x18(E)124x58(E)220x76(E)24x20(E)30x30(E)24x20(E)30x30(E)36x30(E)36x30(E)64x58(E)124x58 DOWN(E)220x76DOWN(E)124x58 DOWN(E)120x721 1/2"1 1/2"FD/SDFD/SD4AAD51"6F-32 D1 D7D6" CONCRETE PAD8889AADDSDDSD10108006280060E5G51012" UP TO(E)LEF-11(E)64x58(E)220x76(E)120x7212"2GENERAL NOTES:A. REFER TO PIPING SCHEMATIC ON DRAWING H-400 FOR ADDITIONAL INFORMATIONRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL PENTHOUSE PLANS -HVACH-3001/4" = 1'-0"1PARTIAL PENTHOUSE PLAN - HVAC1/4" = 1'-0"2PARTIAL PENTHOUSE PLAN - DUCTWORK DEMOLITIONDRAWING NOTES1 REFER TO PIPING SCHEMATIC ON DRAWING H-400 FOR PIPINGREQUIREMENTS.2 LOCATE AIR HANDLING UNIT ON 6" CONCRETE PAD. REFER TO AHUDETAILS FOR FURTHER INROMATION / REQUIREMENTS.3 TIE DUCTWORK INTO EXISTING EXHAUST FAN. OFFSET DUCTWORK ASREQUIRED TO TIE INTO EXISTING DUCTWORK AT ROOF PENETRATION.4 1" MAKE-UP WATER LINE. REFER TO PLUMBING DRAWINGS FORCONTINUATION OF PIPING.5 PROVIDE A DUCT MOUNTED AIRFLOW STATION.6 PROVIDE CONDENSATE DRAIN CONNECTION AND TRAP. REFER TOPLUMBING DRWAINGS FOR CONTINUATION OF PIPING. REFER TO DETAILSFOR FURTHER REQUIREMENTS.7 THE AIRFLOW STATION SHALL BE LOCATED PER THE MANUFACTURER'SREQUIREMENT. THE BASIS OF DESIGN REQUIRES 1 DUCT DIAMTER (1D) OFSTRAIGHT RUN DUCT PRIOR TO AN ELBOW AND 2 DUCT DIAMETERS (2D)OF STRAIGHT RUN DUCT AFTER AN ELBOW.8 TIE PIPING INTO EXISTING. PROVIDE ALL PIPING MODIFICATIONS ASREQUIRED TO MAKE THE CONNECTION.9 TIE PIPING INTO EXISTING. PROVIDE ALL PIPING MODIFICATIONS ASREQUIRED TO MAKE THE CONNECTION.10 6" CONCRETE PAD SHALL EXTEND 6" PAST EQUIPMENT ON ALL SIDES.DEMOLITION NOTES1 REMOVE EXHAUST DUCTWORK BACK TO THE CONNECTIONTO THE ROOF MOUNTED EXHAUST FAN LEF-1.2 DISCONNECT AND REMOVE EXISTING EXHAUSTDUCTWORK AND PREP FOR CONNECTION TO NEW.
H-400
PIPING SCHEMATICS - HVAC
1
(TYPICAL)
CAP AND CHAIN
WITH HOSE END,
ƒ" BALL VALVE
(TYPICAL)
P/T PLUG
TO SIDE OF MAIN HEADER)
SYSTEM CONNECTION (CONNECT
VALVE
LOCK-SHIELD
THERMAL TRAP
24" MIN.ƒ"ƒ"ƒ"
ƒ"
CAP & CHAIN
ƒ" BALL VALVE W/
GLYCOL SYSTEM FILL POINT
COIL HRC-1
HEAT RECOVERY
COIL HRC-2
HEAT RECOVERY
V V
•"
1 212
POLY BARREL
55 GALLON EXPANSION TANK
NOT TO SCALE
JAER-23-601 OR EQUAL
JOHN WOOD MODEL
(PRECHARGE TANK TO 12 PSI)
ACCEPTANCE VOLUME
10 GALLON
DRAWING NOTES:
1
2
P-20
TRAP
THERMAL
24" MIN.
VALVE
LOCK-SHEILDƒ"SIDE OF PIPE
CONNECT TO
ƒ"
OR EQUAL
MODEL VJS150
SEPARATOR
SPIROVENT AIR
ƒ"
REHEAT COILS
FLOOR
HWS TO 5TH
REHEAT COILS
5TH FLOOR
HWR FROM
SEPARATOR
SPIROVENT AIR
OR EQUAL
MODEL VJS150
ƒ"
EXPANSION TANK
JAER-23-601 OR EQUAL
JOHN WOOD MODEL
(PRECHARGE TANK TO 12 PSI)
ACCEPTANCE VOLUME
10 GALLON
REFER TO PLUMBING DRAWINGS
DOMESTIC WATER CONNECTION
WATER VALVE
MAKE UP
•"
•"
P-18
P-19
AIR VENT
AUTOMATIC
SITE GLASS
1"FEEDER
POT
CHEMICAL
ƒ"
ƒ"
NOT TO SCALE
REHEAT HOT WATER SYSTEM PIPING SCHEMATIC - HVAC2
GLYCOL RUN AROUND LOOP PIPING SCHEMATIC - HVAC
1•"1•"
1•"
1•"1•"1•"1•"
1•"
1•"
1•"1•"1•"CV-7
HEAT EXCHANGER
PLATE AND FRAME
1•"1•"
1•"
GHWS
GHWR 2"2"1•"
1•"
GHWS
GHWR
P-16
TO (E)PUMP
GHWSGHWRCOIL
PREHEAT
TO ASC-8
CONNECTION SHALL BE ON THE DISCHARGE AIR SIDE OF THE COIL.
PIPE COIL FOR COUNTERFLOW ARRANGEMENT. SUPPLY
ARRANGE PIPING WITH UNIONS TO ALLOW REMOVAL OF COIL.1•"1•"AIR VENT
MANUAL
CONTAINMENT SYSTEM
PIPE TO GLYCOL
RELIEF VALVE (75 PSI)
AIR VENT
MANUAL
FLOOR DRAIN
PIPE TO NEAREST
RELIEF VALVE (50 PSI)
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 13760
607-231-6674 T
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
Scale:
Fifth Floor Renovation
As Indicated
December 4, 2020
December 15, 2020Issued for Bid
H-500
CONTROL SCHEMATIC &
SYSTEM SUMMARY
BO S
S
SCAO R BI
TYPICAL VFD CONTROL/MONITORING POINTSVFDM
R AOM SYSTEM
FIRE ALARM
WIRE TO
COM BACnet / MSTP
AV: SPEED (RPM)
AV: POWER (KW)
SP
AI
SETPOINT
AV
M
BYPASS
MOD
AO
AIR
EXHAUST
REFER TO PLANS
ES
BI
HR
C
T
AI
T
AI
HR
C
T
AI
T
AI
AIR
OUTSIDE
P
AI TAI AIPBI
S
S BO
CS
BI
M MS
TM
VFD
F
AI
ES
BO
O
C
BI
P
BI
CIRCUIT
TO FAN
C
PH
T
AI
AO
N.O.
COIL
PREHEAT
M VFD
COIL VALVE
PREHEAT
SETPOINT
AV
FZ
BI
CIRCUIT
TO FAN
C
C
COIL
COOLING
AO
N.C.
COIL VALVE
COOLING
T
AI
CIRCUIT
TO FAN
P
BI
SP
REFER TO PLANS
SETPOINT
AV
AI
AIR
SUPPLY
SETPOINT
AV
T
AI
SD
BI
AOM SYSTEM
ALARM
TO FIRE
1
NOT TO SCALE
AIR HANDLING UNIT ACS-8 AND EXISTING EXHAUST FAN LEF-1 CONTROL SCHEMATIC AND SYSTEM SUMMARY
INDICATES EXISTING
RH
AI
DEWPOINT
AV
ESO
C
BIBO
SC
AO
LEF-1
ACS-8
SEQUENCE OF OPERATION
SYSTEM DESCRIPTION
100% OUTSIDE AIR HANDLING UNIT (ACS-8)
SUPPLY AIR FAN
EXISTING LAB EXHAUST FAN (LEF-1)
GYLCOL PRE-HEAT COIL
CHILLED WATER COOLING COIL
GLYCOL RUN AROUND ENERGY RECOVERY COILS (HRC-1 & HRC-2)
ARE SHOWN SOLID ON THE CONTROL DIAGRAM)
(EXISTING CONTROL POINTS ARE SHOWN DASHED AND NEW CONTROL POINTS
GENERAL
CONTROL SYSTEM (BACS).
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND
NORMAL POWER.
POWER FOR THE TEMPERATURE CONTROL PANEL SHALL BE FED FROM
CONTROLLED EQUIPMENT SHALL BE FED FROM NORMAL POWER.
ALL SETPOINTS SHALL BE ADJUSTABLE.
SEVEN DIFFERENT DAILY SCHEDULES PER WEEK.
THE BACS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR
SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME
AND SHALL REQUIRE MANUAL RESET.
ALL SAFETIES SHALL BE HARD WIRED INTO THE FAN MOTOR POWER CIRCUIT,
CONTROL WHEN THE FAN IS OFF FOR CONTINUED FREEZE PROTECTION.
DURING HEATING MODE, THE HEATING CONTROL VALVE SHALL CONTINUE TO
ACTUATOR. THE MAXIMUM STROKE TIME SHALL BE 15 SECONDS.
EXHAUST FAN ISOLATION DAMPER SHALL BE PROVIDED WITH FAST ACTING
CONTROL SEQUENCE OF OPERATION SHALL BE AS FOLLOWS:
SHALL BE VERIFIED FOR PROPER OPERATION. MODIFIED EXHAUST FAN
EXHAUST FAN SHALL BE RECOMMISSIONED AND ALL EXISTING FAN CONTROLS
EXISTING EXHAUST FAN LEF-1 SERVES THE 4TH FLOOR LAB. THE EXISTING
SETPOINTS
AHU DISCHARGE AIR TEMPERATURE (DAT): SEE RESET SCHEDULE
ERC DISCHARGE AIR TEMPERATURE: SAME AS AHU DAT SETPOINT
F
0
FREEZESTAT LOW LIMIT TEMPERATURE: 38
FILTER DIFFERENTIAL PRESSURE HIGH LIMIT: 1.XX" W.C.
SUPPLY FAN DISCHARGE HIGH STATIC PRESSURE LIMIT: -6.0" W.C.
SUPPLY FAN SUCTION LOW STATIC PRESSURE LIMIT: -6.0" W.C.
SUPPLY FAN MINIMUM START SPEED: 1400 CFM (20% OF MAX)
OWNER)
SYSTEM OCUPANCY SCHEDULE: 6 AM - 8 PM, MON-FRI (COORDINATE WITH
START/STOP
ASSOCIATED LABORATORY EXHAUST FAN.
AIR HANDLING UNIT SUPPLY FAN SHALL BE INTERLOCKED WITH THE
SYSTEM SHALL BE ENABLED AT ALL TIMES.
SHUTOFF DAMPER CONTROL
EXHAUST AIR DAMPERS SHALL BE CLOSED.
WHEN THE SYSTEM FANS ARE OFF, THE OUTSIDE AIR AND ASSOCIATED
PRIOR TO STARTING THE SYSTEM FANS.
ASSOCIATED EXHAUST AIR DAMPERS SHALL PROVE OPEN VIA END SWITCH
WHEN THE SYSTEM FANS ARE INDEXED TO START, THE OUTSIDE AIR AND
SUPPLY FAN SPEED CONTROL
MAINTAIN THE CRITICAL ZONE DAMPER POSITION AT 95% OPEN.
DOWNSTREAM STATIC PRESSURE SETPOINT SHALL BE RESET AS NEEDED TO
REQUIRED TO MAINTAIN THE DOWNSTREAM STATIC PRESSURE SETPOINT. THE
THE SUPPLY AIR FAN SHALL MODULATE VIA A VARIABLE FREQUENCY DRIVE AS
EXHAUST FAN SYSTEM CONTROL
SHALL MODULATE TO FULL OPERATING SPEED.
SHALL BE INDEXED TO OPEN. ONCE THE DAMPER IS PROVEN OPEN, THE FAN
MINIMUM START SPEED (20%), AT WHICH TIME THE FAN ISOLATION DAMPER
ON A CALL TO OPERATE, THE FAN SHALL BE INDEXED TO START AND RUN AT
MODULATE CLOSED AS NEEDED TO MAINTAIN SETPOINT.
RISES MORE POSITIVE THAN SETPOINT, THE BYPASS DAMPER SHALL
MODULATE TO MAINTAIN SETPOINT. IF THE EXHAUST DUCT STATIC PRESSURE
SETPOINT WITH THE FAN AT FULL SPEED, THE BYPASS DAMPER WILL OPEN AND
IF THE EXHAUST DUCT STATIC PRESSURE FALLS MORE NEGATIVE THAN
TO MAINTAIN THE CRITICAL ZONE DAMPER POSITION AT 95% OPEN.
THE DOWNSTREAM STATIC PRESSURE SETPOINT SHALL BE RESET AS NEEDED
FLOW.
DAMPER SHALL CLOSE, AND THE FAN SHALL INDEX TO 40% OF FULL DESIGN
EXHAUST FAN, THE SYSTEM SHALL INDEX AIRFLOW CONTROL. THE BYPASS
ON FAILURE OF AIR HANDLING UNIT ASSOCIATED WITH THE LABORATORY
GLYCOL RUN AROUND HEAT RECOVERY CONTROL
PUMP SHALL BE ENABLED AND OPERATE AT CONSTANT SPEED.
F BELOW THE SUPPLY AIR TEMPERATURE SETPOINT. THE
0
TEMPERATURE IS 7-10
WINTER MODE: WINTER MODE SHALL BE INITIATED WHEN THE OUTSIDE AIR
BE DISABLED.
F BELOW THE EXHAUST AIR TEMPERATURE. THE PUMP SHALL
0
SETPOINT AND 5
OUTSIDE AIR TEMPERATURE IS ABOVE THE SUPPLY AIR TEMPERATURE
INTERMEDIATE MODE: INTERMEDIATE MODE SHALL BE INITIATED WHEN THE
THE PUMP SHALL BE ENABLED AND OPERATE AT CONSTANT SPEED.
F ABOVE THE EXHAUST AIR TEMPERATURE SETPOINT.
0
TEMPERATURE IS 7-10
SUMMER MODE: SUMMER MODE SHALL BE INITIATED WHEN THE OUTSIDE AIR
SUPPLY AIR TEMPERATURE CONTROL
SCHEDULE:
TEMPERATURE SHALL BE ALLOWED TO RESET BASED ON THE FOLLOWING
DISCHARGE AIR TEMPERATURE RESET: THE AHU DISCHARGE AIR
DAT = 5---OAT = 75F &
DAT = 6---OAT = 55F &
CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN SETPOINT.
SHALL START AND RUN AT A CONSTANT SPEED, AND THE PREHEAT COIL
CHILLED WATER CONTROL VALVE SHALL BE CLOSED, THE PREHEAT COIL PUMP
WHEN THE AHU DISCHARGE AIR TEMPERATURE FALLS BELOW SETPOINT, THE
MODULATE AS REQUIRED TO MAINTAIN SETPOINT.
SHALL BE CLOSED, AND THE CHILLED WATER CONTROL VALVE SHALL
PREHEAT COIL PUMP SHALL BE OFF, THE PREHEAT COIL CONTROL VALVE
WHEN AHU DISCHARGE AIR TEMPERATURE RISES ABOVE SETPOINT, THE
SAFETIES
UPON ACTIVATION OF THE LOW LIMIT TEMPERATURE SWITCH.
GLYCOL COIL PUMP SHALL START AND THE CONTROL VALVES SHALL OPEN
DOWN, THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL CLOSE, THE
FREEZE PROTECTION: THE SUPPLY AND EXHAUST AIR FANS SHALL SHUT
OF THE HIGH FAN DISCHARGE STATIC PRESSURE SWITCH.
THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL CLOSE UPON ACTIVATION
HIGH FAN STATIC: THE SUPPLY AND EXHAUST AIR FANS SHALL SHUT DOWN,
OF THE LOW FAN SUCTION STATIC PRESSURE SWITCH.
THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL CLOSE UPON ACTIVATION
LOW FAN STATIC: THE SUPPLY AND EXHAUST AIR FANS SHALL SHUT DOWN,
DAMPER SHALL CLOSE UPON ACTIVATION OF A DUCT SMOKE DETECTOR.
SMOKE DETECTION: THE FAN SHALL SHUT DOWN AND THE OUTSIDE AIR
(P-21)
COIL PUMP
COIL PUMP (P-20)
HEAT RECOVERY
F
AI
AI
CSBI
POINT SCHEDULE
AIR HANDLING UNIT ACS-8 AND EXISTING EXHAUST FAN LEF-1
HARDWARE POINTS SOFTWARE POINTS
GRAPHIC
SHOWN ON NOTES
BI BO AI AO AV BV SCH TREND
ALARM
BACS EMCS DESCRIPTION
STEAM LOAD SHED X (6)BINARY NETWORK INPUTS FROM EMCS
CHILLED WATER LOAD SHED X (4)BINARY NETWORK INPUTS FROM EMCS
OUTSIDE AIR DAMPER POSITION COMMAND X X
OUTSIDE AIR DAMPER STATUS X X X
OUTSIDE AIR RELATIVE HUMIDITY X X
OUTSIDE AIR DEWPOINT X X X
OUTSIDE AIR TEMPERATURE X X X AVERAGING SENSOR
FILTER RACK DIFFERENTIAL PRESSURE X X X X HIGH LIMIT X MAGNEHELIC INDICATING TRANSMITTER
HEAT RECOVERY LOOP PUMP START/STOP X X X
HEAT RECOVERY LOOP PUMP STATUS X X X X FAILURE X VIA CONTACT ON DRIVE
HEAT RECOVERY LOOP PUMP SPEED COMMAND X X X
HEAT RECOVERY LOOP SYSTEM PRESSURE X X X X LOW PRESSURE X PRESSURE SWITCH
HEAT RECOVERY LOOP SYSTEM PRESSURE SETPOINT X
HRC SUPPLY COIL ENTERING WATER TEMPERATURE X X X
HRC SUPPLY COIL LEAVING WATER TEMPERATURE X X X
HRC SUPPLY COIL LEAVING AIR TEMPERATURE X X X AVERAGING SENSOR
HRC SUPPLY COIL LEAVING AIR TEMPERATURE SETPOINT X X X AVERAGING SENSOR
HRC EXHAUST COIL ENTERING AIR TEMPERATURE X X X AVERAGING SENSOR
HRC EXHAUST COIL LEAVING AIR TEMPERATURE X X X AVERAGING SENSOR
HRC HEAT RECOVERY EFFECTIVENESS X X X CALCULATE BASED ON TEMPERATURE
HRC RECOVERED ENERGY (BTUH)X X X CALCULATE BASED ON TEMPERATURE
HRC TOTALIZED RECOVERED ENERGY (BTU/YR)X X X CALCULATE BASED ON TEMPERATURE
SUPPLY FAN START/STOP X X X X INTERLOCK WITH FA SYSTEM
SUPPLY FAN SPEED COMMAND X X X
SUPPLY FAN STATUS X X X FAILURE X VIA CONTACT ON DRIVE
SUPPLY FAN POWER (KW)X X X BACnet MSTP NETWORK POINT
SUPPLY FAN SPEED (RPM)X X X BACnet MSTP NETWORK POINT
SUPPLY FAN DUCT SMOKE DETECTOR STATUS X X
SUPPLY FAN DISCHARGE PRESSURE SWITCH STATUS X X X HIGH LIMIT X
SUPPLY FAN SUCTION PRESSURE SWITCH STATUS X X X LOW LIMIT X
SUPPLY FAN AIRFLOW X X X INSTALL IN INLET CONE
PREHEAT COIL VALVE POSITION COMMAND X X X X F DELTA T ACROSS COIL WITH VALVE COMMANDED CLOSED
o
5 X NORMALLY OPEN
PREHEAT COIL PUMP START/STOP X X X
PREHEAT COIL PUMP STATUS X X X X FAILURE X VIA CONTACT ON DRIVE
PREHEAT COIL PUMP SPEED COMMAND X X X
PREHEAT COIL PUMP POWER (KW)X X X BACnet MSTP NETWORK POINT
PREHEAT COIL PUMP SPEED (RPM)X X X BACnet MSTP NETWORK POINT
PREHEAT COIL DISCHARGE AIR TEMPERATURE X X X AVERAGING SENSOR
LOW LIMIT TEMPERATURE STATUS X X X LOW LIMIT X
COOLING COIL VALVE POSITION COMMAND X X X X DELTA T ACROSS COIL WITH VALVE COMMANDED CLOSED
o
5 X NORMALLY CLOSED
COOLING COIL DISCHARGE AIR TEMPERATURE X X X AVERAGING SENSOR
AHU DISCHARGE AIR TEMPERATURE X X X X DEVIATION FROM SETPOINT X SINGLE POINT SENSOR
AHU DISCHARGE AIR TEMPERATURE SETPOINT X X X
EXHAUST FAN AIRFLOW X X X INSTALL IN DUCT
EXHAUST FAN ISOLATION DAMPER OPEN/CLOSED X X
EXHAUST FAN ISOLATION DAMPER STATUS X X X
EXHAUST FAN DOWNSTREAM STATIC PRESSURE X X X X 10% DEVIATION FROM SETPOINT X
EXHAUST FAN DOWNSTREAM STATIC PRESSURE SETPOINT X X X
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 13760
607-231-6674 T
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
Scale:
Fifth Floor Renovation
As Indicated
December 4, 2020
December 15, 2020Issued for Bid
H-501
1
NOT TO SCALE
STEAM LOAD SHED MATRIX
CONTROL POINT LOAD SHED-1 STEAM LOAD SHED-2 STEAM LOAD SHED-3 STEAM LOAD SHED-4 STEAM LOAD SHED-5 STEAM LOAD SHED-6 STEAM
ZONE CONTROL
NON-RESEARCH SPACES INDEX SPACE TO UNOCCUPIED MODE INDEX TEMPERATURE SET POINT TO 60 DEG F
RESEARCH SPACES INDEX SPACE TO UNOCCUPIED MODE, RESETTABLE TO OCCUPIED MODE SPACE TEMPERATURE SET POINT TO 60 DEG F
INDEX SPACE AIR CHANGE RATE TO MIN UNPCCUPIED AC/PH AND
CRITICAL SPACES (2)UNDER CONTROL
AIR HANDLING SYSTEM CONTROL
100% OUTSIDE AIR SYSTEMS - NON CRITICAL UNDER CONTROL TEMPERATURE TO 55 DEG F
INDEX DISCHARGE AIR INDEX UNIT "OFF"
100% OUTSIDE AIR SYSTEMS - CRITICAL (2)UNDER CONTROL INDEX DISCHARGE AIR TEMPERATURE TO 55 DEG F (1)
LABORATORY MAKE-UP AIR SYSTEMS UNDER CONTROL INDEX DISCHARGE AIR TEMPERATURE TO 55 DEG F (1)
LABORATORY EXHAUST SYSTEMS UNDER CONTROL
HYDRONIC SYSTEM CONTROL
REHEAT LOOP SYSTEM - NON CRITICAL UNDER CONTROL
SCHEDULE, WHICHEVER IS LOWER
DEG F OR MAINTAIN RESET
INDEX LOOP TEMPERATURE TO 140
CLOSE STEAM VALVE, PUMPS "ON"
REHEAT LOOP SYSTEMS - CRITICAL (2)UNDER CONTROL
GLYCOL HEATING LOOP SYSTEM UNDER CONTROL
NOTES:
(1)RETAIN ORIGINAL SET POINT IF LOWER THAN 55 DEG F.
(2)THE DETERMINATION OF WHETHER A SYSTEM OR ZONE IS CONSIDERED "CRITICAL" SHALL BE DETERMINED ON A CASE-BY-CASE BASIS.
GENERALLY ANIMAL ROOMS, SERVER ROOMS AND LIBRARIES ARE THE ONLY SPACES THAT ARE PREQUALIFIED AS "CRITICAL"
EACH PROJECT SHALL CONDUCT AN INDEPENDENT MEETING WITH THE PRIMARY PURPOSE OF MAKING LOAD SHED DECISIONS
CHILLED WATER LOAD SHED MATRIX
NOT TO SCALE
STEAM LOAD SHED MATRIX
CONTROL SCHEMATICS
AND SYSTEM SUMMARIES
GS
GR
AI
P
BO
M
VFDS
S
SCAO
COM
R BI
- AV: SPEED (RPM)
- AV: POWER (KW)
TYPICAL VFD CONTROL/MONITORING POINTS
T
AI
T
AI
SETPOINT
AV
SETPOINT
AV
M
VFD
M
VFD
P BI
BACnet
REFER TO PLANS FOR LOCATION
PRESSURE TRANSDUCER.
REMOTE DIFFERENTIAL STATIC
NOT TO SCALE
REHEAT HOT WATER SYSTEM CONTROL SCHEMATIC AND SYSTEM SUMMARY3
P-18
P-19
SYSTEM DESCRIPTION
REHEAT HOT WATER LOOP HEAT EXCHANGER (CV-7A & CV-7B)
REHEAT HOT WATER LOOP PUMPS (P-19, P-20)
GENERAL
CONTROL SYSTEM (BACS).
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND
ALL SETPOINTS SHALL BE ADJUSTABLE.
SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME
SETPOINTS
REHEAT HOT WATER LOOP SUPPLY TEMPERATURE: 13
DIFFERENTIAL PRESSURE: XX PSI (ADJ)
START/STOP
WITH THE SYSTEM ARE OPEN AND CALLING FOR DEMAND.
SYSTEM SHALL BE ENABLED WHEN 10% OF THE CONTROL VALVES ASSOCIATED
AND THE LEAD PUMP SHALL INDEX TO STANDBY AND BE OFF.
HOURS OF OPERATION THE STANDBY PUMP SHALL INDEX TO LEAD AND RUN,
THE LEAD PUMP SHALL START, STANDBY PUMP SHALL BE OFF. AFTER 1000
AND RUN.
ON FAILURE OF THE LEAD PUMP, THE STANDBY PUMP SHALL INDEX TO LEAD
SPEED CONTROL
CRITICAL ZONE CONTROL VALVE POSITION AT 95% OPEN.
LOOP DIFFERENTIAL SETPOINT SHALL BE RESET AS NEEDED TO MAINTAIN THE
REQUIRED TO MAINTAIN THE LOOP DIFFERENTIAL PRESSURE SETPOINT. THE
WHEN ENABLED, PUMP SHALL MODULATE VIA VARIABLE FREQUENCY DRIVE AS
REHEAT HOT WATER LOOP CONTROL
TO LEAD AND THE LEAD HEAT EXCHANGER SHALL INDEX TO LAG.
BE CLOSED. AFTER 1000 HOURS (ADJ) THE LAG HEAT EXCHANGER SHALL INDEX
EXCHANGER ISOLATION CONTROL VALVE AND STEAM CONTROL VALVE SHALL
WATER REHEAT LOOP SUPPLY WATER TEMPERATURE SETPOINT. THE LAG HEAT
STEAM CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN THE HOT
THE LEAD HEAT EXCHANGER ISOLATION CONTROL VALVE SHALL OPEN AND THE
EXCHANGER SHALL INDEX TO LEAD.
ON FAILURE OF THE LEAD EXCHANGER CONTROL VALVE(S), THE LAG HEAT
CHILLED WATER LOAD SHED MATRIX
CONTROL POINT DAYTIME (DEFCON 3)
LOAD SHED 1 - CHILLED WATER
(DEFCON 2)
LOAD SHED 2 - CHILLED WATER NIGHT
EMERGENCY (DEFCON 1)
LOAD SHED 3 - CHILLED WATER
EMERGENCY (DEFCON)
LOAD SHED 4 - CHILLED WATER LCS
ZONE CONTROL
NON-RESEARCH SPACES
INDEX SPACE TO UNOCCUPIED MODE
UNDER CONTROL
CHILLED WATER COIL CONTROL VALVE INDEX CHILLED WATER COIL CONTROL VALVE CLOSED
RESEARCH SPACES INDEX SPACE TO UNOCCUPIED MODE, RESTTABLE TO OCCUPIED MODE VALVE CLOSED
INDEX CHILLED WATER CONTROL
CRITICAL SPACES (2)UNDER CONTROL
AIR HANDLING SYSTEM CONTROL
100% OUTSIDE AIR SYSTEMS - NON CRITICAL SET POINT TO 65 DEG F (1)
INDEX DISCHARGE AIR TEMPERATURE
SET POINT TO 70 DEG F (1)
INDEX DISCHARGE AIR TEMPERATURE
SET POINT TO 75 DEG F (1)
INDEX DISCHARGE AIR TEMPERATURE
VALVE CLOSED
INDEX CHILLED WATER CONTROL
100% OUTSIDE AIR SYSTEMS - CRITICAL (2)UNDER CONTROL
LABORATORY MAKE-UP AIR SYSTEMS UNDER CONTROL SET POINT TO 65 DEG F (1)
INDEX DISCHARGE AIR TEMPERATURE
LABORATORY EXHAUST SYSTEMS UNDER CONTROL
HYDRONIC SYSTEM CONTROL
BUILDING RECIRCULATION LOOP - NON CRITICAL INDEX CHILLED WATER TEMPERATURE TO 53 DEG F INDEX PUMPS "OFF" AND OPEN RECICULATING LOOP VALVE TO 100%
BUILDING RECIRCULATION LOOP - CRITICAL (2)UNDER CONTROL
NOTES:
(1)RETAIN FREE COOLING IF REQUIRED AND AVAILABLE
(2)THE DETERMINATION OF WHETHER A SYSTEM OR ZONE IS CONSIDERED "CRITICAL" SHALL BE DETERMINED ON A CASE-BY-CASE BASIS.
GENERALLY ANIMAL ROOMS, SERVER ROOMS AND LIBRARIES ARE THE ONLY SPACES THAT ARE PREQUALIFIED AS "CRITICAL"
EACH PROJECT SHALL CONDUCT AN INDEPENDENT MEETING WITH THE PRIMARY PURPOSE OF MAKING LOAD SHED DECISIONS
SEQUENCE OF OPERATION
T
AI
T
AI
CV-7
AOE
GHWS
GHWR
2
POINT SCHEDULE
REHEAT HOT WATER LOOP HEAT EXCHANGER CV-7
HARDWARE POINTS SOFTWARE POINTS
GRAPHIC
SHOWN ON NOTES
BI BO AI AO AV BV SCH TREND
ALARM
BACS EMCS DESCRIPTION
STEAM LOAD SHED X (6)BINARY NETWORK INPUTS FROM EMCS
OUTSIDE AIR TEMPERATURE X X X IF NOT PROVIDED GLOBALLY
GLYCOL LOOP SUPPLY WATER TEMPERATURE X X X X X
GLYCOL LOOP RETURN WATER TEMPERATURE X X X X X
REHEAT HOT WATER LOOP SUPPLY WATER TEMPERATURE X X X X + / - 4 DEG F FROM SETPOINT X
REHEAT HOT WATER LOOP SUPPLY WATER TEMP SETPOINT X X X
REHEAT HOT WATER LOOP RETURN WATER TEMPERATURE X X X X X
REHEAT HOT WATER LOOP DIFFERENTIAL PRESSURE X X X X 10% DEVIATION FROM SETPOINT X REFER TO PLANS
REHEAT HOT WATER LOOP DIFFERENTIAL PRESSURE SETPOINT X X X
REHEAT HOT WATER LOOP SYSTEM PRESSURE X X X X LOW PRESSURE X REFER TO PLANS
REHEAT HOT WATER PUMP START/STOP X X X TYPICAL OF 2
REHEAT HOT WATER PUMP STATUS X X X X FAILURE X VIA CONTACT ON DRIVE - TYPICAL OF 2
REHEAT HOT WATER PUMP SPEED COMMAND X X X TYPICAL OF 2
REHEAT HOT WATER PUMP POWER (KW)X X X BACnet MSTP NETWORK POINT - TYPICAL OF 2
REHEAT HOT WATER PUMP SPEED (RPM)X X X BACnet MSTP NETWORK POINT - TYPICAL OF 2
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 13760
607-231-6674 T
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
Scale:
Fifth Floor Renovation
As Indicated
December 4, 2020
December 15, 2020Issued for Bid
H-502
CONTROL SCHEMATICS
AND SYSTEM SUMMARIES
NOT TO SCALE
1
H
C
H
C
AIR
SUPPLY
BI
OS
sa
d
AI
T
AI
T
SETPOINT
AV
EE
AO
F.L.
AIR
EXHAUST
GEV
CONTROLLER
ANALOG ELECTRIC
MOD
AO AV
SETPOINT
AI AI
FLOW ALARM
CONTROLLER
ANALOG ELECTRIC
MOD
AO
AI AI
FLOW ALARM
AV
SETPOINT
SAV
ZONE
P
CONTROLLER
ANALOG ELECTRIC
MOD
AO AV
SETPOINT
AI AI
FLOW ALARM
P
CONTROLLER
ANALOG ELECTRIC
MOD
AO AV
SETPOINT
AI AI
FLOW ALARM
GEVSAV EASA
**NOTE: FOR VENTURI STYLE VALVES THIS DETAIL SHALL REPLACE THE VALVES SHOWN WITHIN THE SYSTEM SCHEMATIC**
HWSHWR
F.L.
N.O.
AO
WHERE SHOWN
FIN TUBE RADIATION,
INDICATES EXISTING
SYSTEM DESCRIPTION
GENERAL EXHAUST AIR VALE (GEV)
SUPPLY AIR VALVE (SAV)
DUCT MOUNTED REHEAT COIL (RHC)
EXISTING BASEBOARD RADIATION HEATING
GENERAL
CONTROL SYSTEM (BACS).
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND
ALL SETPOINTS SHALL BE ADJUSTABLE.
SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME
FROM THE SPACE.
LABORATORY AIR CHANGE RATES ARE BASED ON TOTAL EXHAUST AIR FLOW
HEIGHT).
CALCULATE THE REQUIRED CFM USING THE GROSS VOLUME (AREA X CEILING
THE SPACE SHALL BE CONTROLLED TO AN AIR CHANGE RATE, THE BACS SHALL
SETPOINTS
LABORATORY AIRFLOW CONTROL
ROOM OCCUPANCY SHALL BE DETERMINED VIA ROOM OCCUPANCY SENSORS.
AIR VALVE POSITIONS SHALL BE BASED ON MODE. UNDER NORMAL CONTROL,
AIRFLOW DIFFERENTIAL.
SUPPLY AIR VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE SPECIFIED
MODULATE AS NEEDED TO MAINTAIN THE OCCUPIED AIR CHANGE RATE. THE
WHEN THE ROOM IS OCCUPIED, THE GENERAL EXHAUST AIR VALVE SHALL
AIRFLOW DIFFERENTIAL.
SUPPLY AIR VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE SPECIFIED
MODULATE AS NEEDED TO MAINTAIN THE UNOCCUPIED AIR CHANGE RATE. THE
WHEN THE ROOM IS UNOCCUPIED, THE GENERAL EXHAUST AIR VALVE SHALL
ZONE TEMPERATURE CONTROL
PROGRAMMED SCHEDULE AND SPACE OCCUPANCY SENSORS.
SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OF
AND REHEAT COIL CONTROL VALVES SHALL BE CLOSED.
WHEN THE SPACE TEMPERATURE IS AT SETPOINT, THE BASEBOARD RADIATION
VALVE SHALL MODULATE TO MAINTAIN THE SPACE TEMPERATURE SETPOINT.
BASEBOARD RADIATION CONTROL VALVE FULLY OPEN, THE REHEAT CONTROL
SETPOINT. IF THE SPACE TEMPERATURE IS NOT AT SETPOINT WITH THE
CONTROL VALVE SHALL MODULATE TO MAINTAIN THE SPACE TEMPERATURE
OCCUPIED HEATING TEMPERATURE SETPOINT, THE BASEBOARD RADIATION
OCCUPIED PERIOD AND THE SPACE TEMPERATURE FALLS BELOW THE
OCCUPIED HEATING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED
VALVE SHALL CLOSE.
OCCUPIED COOLING TEMPERATURE SETPOINT, THE REHEAT COIL CONTROL
OCCUPIED PERIOD AND THE SPACE TEMPERATURE RISES ABOVE THE
OCCUPIED COOLING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED
OCCUPIED SETBACK TEMPERATURE SETPOINT.
SEQUENCE SHALL APPLY, BUT THE SPACE SHALL BE MAINTAINED AT THE
SCHEDULED OCCUPIED PERIOD, THE ABOVE OCCUPIED HEATING/COOLING
OCCUPIED SETBACK: IF THE SPACE BECOMES UNOCCUPIED DURING THE
MAINTAINED AT THE UNOCCUPIED SETBACK TEMPERATURE SETPOINT.
OCCUPIED HEATING SEQUENCE SHALL APPLY, BUT THE SPACE SHALL BE
BELOW THE UNOCCUPIED HEATING TEMPERATURE SETPOINT, THE ABOVE
SCHEDULED UNOCCUPIED PERIOD AND THE SPACE TEMPERATURE FALLS
UNOCCUPIED HEATING: IF THE SPACE IS UNOCCUPIED DURING THE
MAINTAINED AT THE UNOCCUPIED COOLING TEMPERATURE SETPOINT.
OCCUPIED SETBACK SEQUENCE SHALL APPLY, BUT THE SPACE SHALL BE
ABOVE THE UNOCCUPIED COOLING TEMPERATURE SETPOINT, THE ABOVE
SCHEDULED UNOCCUPIED PERIOD AND THE SPACE TEMPERATURE RISES
UNOCCUPIED COOLING: IF THE SPACE IS UNOCCUPIED DURING THE
SEQUENCE OF OPERATION
POINT SCHEDULE
EQUIPMENT
HARDWARE POINTS SOFTWARE POINTS
GRAPHIC
SHOWN ON NOTES
BI BO AI AO AV BV SCH TREND
BACS EMCS DESCRIPTION
STEAM LOAD SHED X (6)BINARY NETWORK INPUTS FROM EMCS
CHILLED WATER LOAD SHED X (4)BINARY NETWORK INPUTS FROM EMCS
TOTAL EXHAUST AIRFLOW (CFM)X X X
TOTAL EXHAUST SETPOINT (CFM)X X X
LAB AIR CHANGE RATE (ACPH)X X X
FLOW OFFSET SETPOINT (CFM)X X
FLOW OFFSET ACTUAL (CFM)X X
GENERAL EXHAUST AIR VALVE AIRFLOW FEEDBACK (CFM)X X X
GENERAL EXHAUST VALVE MIN AIRFLOW SETPOINT (CFM)X X
GENERAL EXHAUST VALVE MAX AIRFLOW SETPOINT (CFM)X X
GENERAL EXHAUST VALVE FLOW FEEDBACK (CFM)X X X
GENERAL EXHAUST AIR VALVE STATUS X
X VALVE COMMAND NOT EQUAL TO FEEDBACK
X TRI-STATE ALARMX10% FLOW DEVIATION FROM SETPOINT
X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)
SUPPLY VALVE FLOW FEEDBACK (CFM)X X X
SUPPLY VALVE STATUS X
X 10% FLOW DEVIATION FROM SETPOINT
X TRI-STATE ALARMXVALVE COMMAND NOT EQUAL TO FEEDBACK
X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)
SUPPLY VALVE POSITION COMMAND (CFM)X X X
SUPPLY VALVE MIN AIRFLOW SETPOINT (CFM)X X
SUPPLY VALVE MAX AIRFLOW SETPOINT (CFM)X X
REHEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR
REHEAT COIL VALVE POSITION COMMAND (%)X X X 5 DEG DELTA ACROSS COIL WITH VALVE COMMANDED CLOSED X FAIL LAST
BASEBOARD RADIAITON CONTROL VALVE POSITION COMMAND (%)X X X FAIL LAST, REFER TO PLANS FOR QTY
SPACE TEMPERATURE SETPOINT, HEATING X X X
SPACE TEMPERATURE SETPOINT, COOLING X X X
SPACE TEMPERATURE X X SPACE TEMPERATURE +/- 4 DEG F FROM SETPOINT X REFER TO PLANS
SPACE TEMPERATURE SETPOINT ADJUSTMENT X X REFER TO PLANS
SPACE OCCUPANCY X X X X REFER TO PLANS
SPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINT X X X X REFER TO PLANS
SPACE COOLING TEMPERATURE SETPOINTS:
F
0
75OCCUPIED:
F
0
78UNOCCUPIED SETBACK:
F
0
81UNOCCUPIED:
SPACE HEATING TEMPERATURE SETPOINTS:
F
0
70OCCUPIED:
F
0
67UNOCCUPIED SETBACK:
F
0
64UNOCCUPIED:
TOTAL EXHAUST AIR CHANGE RATE (ACPH):
REFER TO LAB AIRFLOW SCHEDULES
ACPH = TOTAL EXHAUST CFM X 60 / ROOM VOLUME
TOTAL EXHAUST AIRFLOW RATE (CFM):
REFER TO LAB AIRFLOW SCHEDULE
SUPPLY AIRFLOW RATE (CFM):
REFER TO LAB AIRFLOW SCHEDULE
TYPICALLY = TOTAL EXHAUST AIRFLOW RATE + OFFSET
GENERAL EXHAUST AIRFLOW RATE (CFM):
REFER TO LAB AIRFLOW SCHEDULE
SPACE AIR DIFFERENTIAL OFFSET (CFM):
REFER TO LAB AIRFLOW SCHEDULE
30 MINUTESMINIMUM LABORATORY OCCUPANCY INDEX TIME:
ZONE OCCUPANCY SCHEDULE: COORDINATE WITH OWNER
TYPICAL LAB CONTROL SCHEMATIC AND SYSTEM SUMMARY
NOT TO SCALE
2
POINT SCHEDULE
HARDWARE POINTS SOFTWARE POINTS
GRAPHIC
SHOWN ON NOTES
BI BO AI AO AV BV SCH TREND
ALARM
BACS EMCS DESCRIPTION
VAV DAMPER POSITION X X X
VAV AIRFLOW FEEDBACK (CFM)X X X 10% DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT
VAV AIRFLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT
VAV POSITION FEEDBACK (%)X X X VALVE COMMAND DOES NOT EQUAL FEEDBACK X BACnet MSTP NETWORK POINT
ZONE TEMPERATURE X X X + / - 4 DEG F FROM SETPOINT X REFER TO PLANS
ZONE TEMPERATURE SETPOINT X X X REFER TO PLANS
AIR
SUPPLY
MOD
AO
COM
OR BACnet / MSTP:
BACnet / ARCNET
- AV: FLOW SETPOINT (CFM)
- AV: POSITION FEEDBACK (%)
- AV: FLOW FEEDBACK (CFM)
EXISTING VAV
AI
Tsa
SETPOINT
AV
TYPICAL VAV WITHOUT REHEAT CONTROL SCHEMATIC AND SYSTEM SUMMARY
SEQUENCE OF OPERATION
SYSTEM DESCRIPTION
VARIABLE AIR VOLUME SUPPLY BOX
GENERAL
SETPOINTS
SPACE COOLING TEMPERATURE SETPOINTS:
F
O
75OCCUPIED:
F
O
81UNOCCUPIED:
SPACE HEATING TEMPERATURE SETPOINTS:
F
O
70OCCUPIED:
F
O
64UNOCCUPIED:
ZONE OCCUPANCY SCHEDULE: COORDINATE WITH OWNER
CONTROL SYSTEM (BACS).
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND
ALL SETPOINTS SHALL BE ADJUSTABLE.
SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME
ALL SETPOINTS SHALL BE ADJUSTABLE.
PROGRAMMED SCHEDULED OCCUPANCY.
TEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON
AIRFLOW SETPOINT.
OCCUPIED HEATING: THE SUPPLY AIR VAV BOX SHALL INDEX TO THE HEATING
NEEDED TO MAINTAIN SETPOINT.
MODULATE BETWEEN THE MINIMUM AND MAXIMUM AIRFLOW SETPOINTS AS
COOLING TEMPERATURE SETPOINT, THE SUPPLY AIR VAV BOX SHALL
AIRFLOW SETPOINT. IF THE ZONE TEMPERATURE RISES ABOVE THE OCCUPIED
OCCUPIED COOLING: THE SUPPLY AIR VAV BOX SHALL INDEX TO THE MINIMUM
ZONE TEMPERATURE CONTROL
BI
OS
REFER TO PLANS
REFER TO PLANS
X REFER TO PLANSXXSPACE OCCUPANCY
LAB AIRFLOW SCHEDULE
ZONE NUMBER DESCRIPTION ROOM DIMENSIONS CODE MINIMUM VENTILATION EXHAUST AIR SUPPLY AIR XFER
(NOTE 1)AREA HEIGHT NYS NYS EXHAUST VALVE VALVE OCCUPIED UNOCCUPIED SUPPLY VALVE VALVE OCCUPIED UNOCCUPIED ALL
OUTDOOR EXHAUST POINT SIZE RANGE POINT SIZE RANGE MODES
AIRFLOW AIRFLOW (NOTE 4)(NOTE 4)
(NOTE 2)(NOTE 3)MAX MIN MAX MIN
(CFM)(ACH)(CFM)(ACH)(CFM)(CFM)(CFM)(ACH)(CFM)(ACH)(CFM)(CFM)(CFM)(CFM)(CFM)
1 AC/HR LAB 1245 11.0 334 1.5 1245 5.5 GEV-1 14"2750 250 1380 6.0 680 3.0 SAV-1 14"2750 250 1380 680 0
2 AC/HR LAB 1360 11.0 345 1.4 1360 5.5 GEV-2 14"2750 250 1500 6.0 750 3.0 SAV-2 14"2750 250 1400 140 -100
3 AC/HR LAB 730 11.0 241 1.8 730 5.5 GEV-3 12"1790 180 800 6.0 400 3.0 SAV-3 12"1790 180 700 300 -100
NOTES
1.THIS REPRESENTS A LABORATORY WHERE THE MINIMUM REQUIRED AIR CHANGE RATES ESTABLISHED FOR THE LABORATORY DRIVES THE EXHAUST RATE
2.
CFM/SQFT WITH A DEFAULT OCCUPANY DENSITY OF 25 PEOPLE PER 1000 SQFT.
CODE MINIMUM OUTDOOR VENTILATION AIRFLOW: NEW YORK STATE UNIFORM MECHANICAL CODE (2020 MCNYS), TABLE 403.3.1.1, OCCUPANCY CLASSIFICATION - EDUCATION SCIENCE LABORATORIES, 10 CFM/PERSON + 0.18
3.CODE MINIMUM EXHAUST AIRFLOW: NEW YORK STATE UNIFORM MECHANICAL CODE (2020 MCNYS), TABLE 403.3.1.1, OCCUPANCY CLASSIFICATION - EDUCATION SCIENCE LABORATORIES, 1.0 CFM/SQFT.
4.THE MAX / MIN POSITIONS ON THE VALVE WILL BE SET AT THE FACTORY TO THE FULL FANGE WITH ACTUAL AIRFLOW SET IN SOFTWARE.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 13760
607-231-6674 T
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
Scale:
Fifth Floor Renovation
As Indicated
December 4, 2020
December 15, 2020Issued for Bid
COILHWRHWSTEST WELLSV3/4" DRAIN VALVE W/HOSE END CONNECTION,CAP & CHAIN (TYPICAL).BALLVALVECONTROLVALVEDETAIL NOTES:A.ARRANGE PIPING FOR REMOVAL OF COIL WITHOUTDISTURBING PIPING AHEAD OF UNIONS.B.PROVIDE DUCT ACCESS DOOR UPSTREAM OF COIL.C.PIPE COIL FOR COUNTERFLOW ARRANGEMENT IFCOIL IS MORE THEN ONE ROW. HOT WATER SUPPLYCONNECTION SHALL BE ON THE DISCHARGE AIRSIDE OF THE COIL.ROOF DECKFLASHINGROOF INSULATIONINSULATE OUTSIDEOF PLENUMCROSSBREAK BOTTOMTO CREATE PITCHROOF6" WATERTIGHTDRAIN PANPLENUM FULL SIZEOF THROAT, ALLJOINTS SOLDEREDWATERTIGHTANGLE IRONSUPPORTSINTEGRAL BIRDSCREEN(TYP. ALL SIDES)DRIP LEGREMOVABLEROOF CAP1/4" MASTIC SOUNDDEADENERDUCTMATE 3/4" NPT DRAINFITTING AND CHROME PLATEDBRASS CAP.HEIGHT ASSPECIFIED[18" -24"]INTERMEDIATESUPPORT STEEL,ALL SIDESDETAIL NOTES:A.G.C. TO PROVIDE ROOF OPENING, FRAMING AND FLASHING.B.LOCATION, SETTING AND SECURING OF CURB BY HVAC.C.PROVIDE SHIMS WHERE REQUIRED TO LEVEL CURB.D.PROVIDE WIND RESTRAINT PER SPECIFICATION SECTION 230550-WINDRESTRAINT FOR HVAC SYSTEMS.DETAIL NOTES:A.AHU'S TO HAVE A 6" HOUSEKEEPING PAD AND A 6" HIGH (MIN.) FACTORYBASE RAIL.B.PROVIDE INDIVIDUAL DRAIN PAN TRAP ASSEMBLY FOR COIL SECTIONS. C.REFER TO PLUMBING DRAWINGS FOR PIPING CONTINUATION AFTER THETRAP. PUMP AND TERMINATE DRAINS AT NEAREST FLOOR DRAIN.C.SEE SPECIFICATIONS FOR PIPE TYPE.COND.DRAINPANH = FAN OUTLET PRESSURE (IN. W.C.) + 1" MIN.HFANOUTLETPRESSURE1 1/4"1" MIN.BLOW THRU UNITS (POSITIVE STATIC PRESSURE)CLEANOUT(TYP.)MIN. HEIGHTOF TRAP =H+1+1.5(PIPE DIA.)OFFSET FROM PANCONNECTION TO ALLOWFULL ACCESS TOCLEANOUT PLUGCOILCWRCWSVPRESSURE GAUGEWITH 1/4" BALL VALVE(TYPICAL)3/4" DRAIN VALVE WITH HOSE END CONNECTION,CAP & CHAIN (TYPICAL).DETAIL NOTES:A.ARRANGE PIPING TO ALLOW REMOVAL OF COIL WITHOUT REMOVALOF PIPING AHEAD OF UNIONS AND TO ALLOW ACCESS TO FILTERSAND ACCESS PANELS.B.PIPE COIL FOR COUNTERFLOW ARRANGEMENT. SUPPLYCONNECTION SHALL BE ON THE DISCHARGE AIR SIDE OF THE COIL.C.WHERE THERE IS MORE THAN ONE COIL SECTION, PROVIDE ISOLATIONVALVES, AIR VENTS, DRAIN CONNECTIONS, PRESSURE GAUGES, UNIONSAND FLOW BALANCER FOR EACH SECTION. PIPE SIZE TO EACH COILSECTION SHALL MATCH THE COIL CONNECTION SIZE.CONTROLVALVECOILGHWRGHWSV3/4" DRAIN VALVE WITH HOSE END CONNECTION,CAP & CHAIN (TYPICAL).DETAIL NOTES:A.ARRANGE PIPING TO ALLOW REMOVAL OF COIL WITHOUT REMOVALOF PIPING AHEAD OF UNIONS AND TO ALLOW ACCESS TO FILTERSAND ACCESS PANELS.B.PIPE COIL FOR COUNTERFLOW ARRANGEMENT. SUPPLYCONNECTION SHALL BE ON THE DISCHARGE AIR SIDE OF THE COIL.C.WHERE THERE IS MORE THAN ONE COIL SECTION, PROVIDE ISOLATIONVALVES, AIR VENTS, DRAIN CONNECTIONS, PRESSURE GAUGES, UNIONSAND FLOW BALANCER FOR EACH SECTION. PIPE SIZE TO EACH COILSECTION SHALL MATCH THE COIL CONNECTION SIZE.P/T TESTPLUG90
5040608070 100
020301090
5040608070 100
0203010INLINE PUMP-SEE SCHEDULEFOR CAPACITYCOMPOUND GAUGESTRAINERDRAIN VALVE W/HOSEEND CONNECTION,CAP & CHAIN.FLANGECONNECTION(TYP.)CHECKVALVEBALANCINGVALVEISOLATIONVALVE, (TYP.)PRESSUREGAUGEBALL VALVE(TYP.)DETAIL NOTES:A.PRESSURE GAUGES -SELECT GAUGE RANGE TO PLACE MAXIMUM SYSTEM OPERATINGPRESSURE IN MIDDLE THIRD OF RANGE.B.PROVIDE UNION ON PUMP INLET AND OUTLET IF PUMP IS NOT FLANGED.C.INSTALL PUMP WITH SHAFT HORIZONTAL. PIPING MAY BE INSTALLED HORIZONTAL, AS SHOWN,OR VERTICAL DEPENDING ON SITE CONDITIONS.D.INSTALL CHECK VALVE HORIZONTALLY, OR VERTICALLY WITH FLOW UPWARD. INSTALL STRAINERHORIZONTALLY.E.WHERE PIPING IS GREATER THAN 2", PROVIDE A TRIPLE DUTY VALVE IN PLACE OF CHECK VALVE,FLOW BALANCER AND SHUTOFF VALVE.F.OMIT BALANCING VALVE ON VARIABLE FLOW SYSTEMS.GHWRGHWSCOILVCOILPUMP12"3/4" DRAIN VALVE WITH HOSE END CONNECTION,CAP & CHAIN (TYPICAL).PRESSURE GAUGEWITH 1/4" BALL VALVEPRESSUREGAUGE WITH1/4" MANIFOLD& BALL VALVESDETAIL NOTES:A.ARRANGE PIPING TO ALLOW REMOVAL OF COIL WITHOUT REMOVALOF PIPING AHEAD OF UNIONS AND TO ALLOW ACCESS TO FILTERSAND ACCESS PANELS.B.PIPE COIL FOR COUNTERFLOW ARRANGEMENT. SUPPLYCONNECTION SHALL BE ON THE DISCHARGE AIR SIDE OF THE COIL.CONTROLVALVESHEETMETAL PLENUM SAME SIZE AS RETURN/EXHAUST GRILLE NECK SIZERETURN/EXHAUST DUCTWORKRETURN/EXHAUST GRILLENECKRETURN/EXHAUST GRILLE FACEDUCT SAME SIZE AS SUPPLY GRILLE NECK SIZESUPPLY DUCTWORKSUPPLY AIR GRILLEBOOT TAPINSTALLATION IS SIMILAR OF BOTH BOTTOM AND SIDE MOUNTING OF GRILLE.DETAIL NOTES:A.DECK, BEAM,OR JOISTNOTE: FLEX SHALL BE 4'-0"MAXIMUM WITH (1) 90 DEGBENDELBOW SUPPORT FOR FLEXDUCT AND DIFFUSER SIZE AND TYPE AS SHOWN ON DRAWINGS.FLEX DUCT MAXIMUM LENGTH IS 24" WITH A 6" MAXIMUM OFFSET.OMIT FLEXIBLE DUCT CONNECTION AND PROVIDE HARD CONNECTIONTO DIFFUSERS WHERE DUCTWORK/DIFFUSER CONNECTION IS LOCATEDABOVE HARD CEILINGS. DO NOT PROVIDE FLEXIBLE DUCTWORK ABOVEHARD CEILINGS.DETAIL NOTES:A.B.C.FASTENERSDAMPER (WITH BLADEPOSITION INDICATOR)OPTIONALFIRESTATDAMPER SLEEVE: SLEEVE LENGTHTO INCLUDE WALL THICKNESS PLUSADDITIONAL LENGTH REQUIRED BYDAMPER MANUFACTURER IN ROOM.INSTALL FACTORY FURNISHED 1/4"FIBER FRAX THERMAL BLANKET FOREXPOSED SLEEVE IN ROOM. WALLTHICKNESS TO BE FIELD VERIFIEDPRIOR TO ORDERING DAMPERS.14 GA.WIREMESHDAMPERACTUATORGRILLE MOUNTINGFLANGEGRILLEWALLDETAIL NOTES:A.FOR COMBINATION FIRE/SMOKE DAMPERS TO BE PROVIDED IN EXISTING ORNEW DUCTS PENETRATING EXISTING WALLS, THIS CONTRACTOR IS REQUIREDTO REFRAME AND RECONSTRUCT THE EXISTING WALL PENETRATION ANDFRAMING AS PER SMACNA FIRE DAMPER OPENING PROTOCOL DETAIL FIG. 3-1(FIRE DAMPER GUIDE) AS WELL AS MANUFACTURER AND UL LISTING INSTALLATIONDETAIL.SLIP JOINTFIRE DAMPERDETAIL NOTES:A.HORIZONTAL FREE AREA DAMPER INSTALLATION SIMILAR.B.FOR DOUBLE WALL DUCT, USE INSULATION END CAP AND INSULATE SLEEVE.C.FOR FIRE DAMPERS TO BE PROVIDED IN EXISTING OR NEW DUCTS PENETRATINGEXISTING WALLS, THIS CONTRACTOR IS REQUIRED TO REFRAME AND RECONSTRUCTTHE EXISTING WALL PENETRATION AND FRAMING AS PER SMACNA FIRE DAMPEROPENING PROTOCOL DETAIL FIG. 3-1 (FIRE DAMPER GUIDE) AS WELL AS MANUFACTURERAND UL LISTING INSTALLATION DETAIL.WALL:FIRE RATEDCONSTRUCTIONROUND/FLAT OVAL ORRECTANGULAR DUCTACCESS DOOR: SIZE ANDTYPE PER SPECIFICATIONSSLEEVE MATERIAL GAUGE,ANGLE SIZE AND GAUGE,ANGLE FASTENING, ANDOVERSIZED WALL OPENINGAS PER CURRENT SMACNASTANDARD AND UL LISTINGINSTALLATION DETAILDO NOT BOLTANGLES TO WALL6" MIN.CAULKING MATERIALDETAIL NOTES:A.HORIZONTAL DAMPER INSTALLATION SIMILAR.B.FOR DOUBLE WALL DUCT, USE INSULATION END CAP, INSULATE SLEEVE.C.FOR COMBINATION FIRE/SMOKE DAMPERS TO BE PROVIDED IN EXISTING ORNEW DUCTS PENETRATING EXISTING WALLS, THIS CONTRACTOR IS REQUIREDTO REFRAME AND RECONSTRUCT THE EXISTING WALL PENETRATION ANDFRAMING AS PER SMACNA FIRE DAMPER OPENING PROTOCOL DETAIL FIG. 3-1(FIRE DAMPER GUIDE) AS WELL AS MANUFACTURER AND UL LISTING INSTALLATIONDETAIL.DAMPER (WITH BLADEPOSITION INDICATOR)DAMPERACTUATORWALL:FIRE RATEDCONSTRUCTIONDO NOT BOLTANGLES TO WALLS-JOINT/DUCTMATE, SLEEVETO DUCTOVER CENTERLOCKAUXILIARYOPERATINGJACK SHAFTACCESS DOOR:SIZE AND TYPE PER SPECIFICATIONSS-JOINT/DUCTMATE, SLEEVETO DUCTROUND/FLAT OVAL ORRECTANGULAR DUCTDAMPERSLEEVEOPTIONALFIRESTATSLEEVE MATERIALGAUGE, ANGLE SIZEAND GAUGE, ANGLEFASTENING ANDOVERSIZED WALLOPENING AS PERSMACNA STANDARDAND UL LISTINGINSTALLATION DETAILRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020DETAILS -HVACH-600NOT TO SCALE4TERMINAL REHEAT COIL PIPING DETAIL - HOT WATERNOT TO SCALE5LOUVERED PENTHOUSE DETAILNOT TO SCALE6CONDENSATE DRAIN TRAP DETAILNOT TO SCALE3AHU COOLING COIL PIPING DETAIL - 2 WAYNOT TO SCALE2ENERGY RECOVERY COIL PIPING DETAILNOT TO SCALE7INLINE PUMP PIPING DETAILNOT TO SCALE1AHU PREHEAT COIL PIPING DETAIL - 2 WAY WITH PUMPNOT TO SCALE8EXHAUST GRILLE PLENUM INSTALLATION DETAILNOT TO SCALE12LAB SUPPLY GRILLE INSTALLATION DETAILNOT TO SCALE13TYPICAL DIFFUSER INSTALLATION DETAIL - LAY-IN CEILINGNOT TO SCALE11FIRE/SMOKE DAMPER W/ INTEGRAL GRILLE INSTALLATION DETAILNOT TO SCALE10FIRE DAMPER INSTALLATION DETAILNOT TO SCALE9COMBINATION FIRE/SMOKE DAMPER INSTALLATION DETAIL
SGFCISGFCISGFCISGFCISGFCISGFCISGFCIPLAN VIEWELEVATION VIEW5'-1"5'-1"5'-1"5'-1"5'-1"3'-10.5"23'-6.5"12222234567894'-2"34567MAKE-UP AIRSUPPLY AIR1810910910Revisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020AIR HANDLING UNITDIMENSIONS & DETAILS -HVACH-700NOT TO SCALE1AIR HANDLING UNIT ACS-8 DETAILDRAWING NOTES1 35x14 MAKE UP AIR CONNECTION.2 ACCESS DOOR.3 PRE-FILTER AND FINAL FILTERS.4 40% ETHLYENE GLYCOL HEAT RECOVERY COIL.5 SUPPLY AIR FAN.6 40% PROPLYENE GLYCOL PRE-HEAT COIL.7 CHILLED WATER COOLING COIL (DESATURATION).8 26x16 SUPPLY AIR CONNECTION.9 8" BASE FRAME.10 6" CONCRETE PAD, REFER TO STRUCTURAL PLANS.
Revisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020SCHEDULES -HVACH-800STD. 18020654310.213.61301004.63 40% EG 408 3 8.76 BUFFALO AIR HANDLING1(DEG. F)(DEG. F) VEL. (FPM) (In. WC) FLOW (GPM) TEMP. (DEG. F) TEMP. (DEG. F) (Ft. HD)(MBH) ENT. AIR TEMP. LVG. AIR TEMP. MAX. FACE AIR P.D. WATER ENT. WATER LVG. WATER WATER P.D. FLUID VOLTS PHASE FLATYPE CAPACITY AIR SIDEWATER SIDEPREHEATING COIL (HOT WATER)UNIT ELECTRICALCHARACTERISTICSMANUFACTURER & MODEL No. REMARKSAIR HANDLING UNIT SCHEDULE - CHILLED WATER /HOT WATER, CONT'D2. PROVIDE FILTER WITH 36"x36" CLARK AIR SYSTEM SIDE-LOCK FILTER HOUSING.1. PROVIDE FILTER WITH INTEGRAL 1" RECESS FOR USE WITH PRE-FILTER.REMARKS:PRE-FILTER2 24 12 414 Tri-Dim Tri-Pleat UltraF-3 DUCT MOUNTED(E)LEF-1SIDE SERVICE 4400 0.181.01 24 24 4VARIES PLEATED PANEL MERV 9 40-4529Tri-Dim Tri-Pleat Ultra21 24 12 1258 VILEDON MV85F-1ACS-8ACS-8 FINALFILTERFRONT ACCESS 3700 0.231.01 24 24 12VARIESV BANK MERV 13A 80-90131VILEDON MV8512 24 12 28F-1ACS-8ACS-8PRE-FILTERFRONT ACCESS 3700 0.31 0.751 24 24 2VARIES PLEATED PANEL MERV 8 25-3017CAMFILL FARR 30/30-(In.) (In.) (In.)(CFM)HEIGHT WIDTH LENGTHRATING (%) (Sq. Ft.)BANK NO.AIR FLOW (In. WC) (In. WC) NO. SIZEARRANGEMENT FRAME MERV EFFICIENCIES AREAFILTER LOCATION SERVICETYPE SYSTEM INITIAL P.D. FINAL P.D. CARTRIDGESHOLDING EFFICIENCYMEDIA MANUFACTURER & MODEL NO. REMARKSAIR FILTER SCHEDULELP-1 ROOF ACS-8 INTAKE ALUMINUM 7.1 5 46 19 3/4" 46 3700 525 0.055GREENHECK WIH - 32x32-(CFM) (FPM)(Sq. Ft.)(In.) (In.) (In.) FLOW VEL. (In. WC)AREA TIERS WIDTH HEIGHT DEPTH AIR THROAT MAX P.D.UNIT NO. LOCATION SERVICE TYPE MATERIAL THROAT NO. OF DIMENSIONS (APPROX.) AIR PERFORMANCEMANUFACTURER & MODEL NO. REMARKSLOUVERED PENTHOUSE SCHEDULERHC-3 LABORATORY 551 EQUIPMENT 551 FLANGED 30.2 700 5595 0.15 414.8 2.01301000.4 WATER 6 5 13.5 18 AEROFIN W-5.0CF-13.5X18.0-6-0.333 -RHC-2 LABORATORY 551 EQUIPMENT 551 FLANGED 56.2 1300 5595 0.22 436.4 4.01301000.2 WATER 8 5 16.5 26 AEROFIN W-5.0CF-16.5X26.0-8-0.666 -RHC-1 LABORATORY 551 EQUIPMENT 551 FLANGED 59.6 1380 5595 0.18 463.2 4.01301000.9 WATER 6 5 16.5 26 AEROFIN W-5.0CF-16.5X26.0-6-0.333 -(CFM) (DEG. F) (DEG. F) (In. W.C.) (FPM) (GPM) (DEG. F) (DEG. F) (Ft. HD)(In.) (In.)FLOW TEMP. TEMP. P.D. VELOCITY FLOW TEMP.TEMP.P.D.INCH LENGTH WIDTH(MBH) AIR ENT. AIR LVG. AIR AIR MAX. FACE WATER ENT. WATER LVG. WATER WATER FLUID DEEP PERUNIT NO. LOCATIONSERVICE MOUNTING CAPACITY AIR SIDEWATER SIDEROWS FINSCOIL FACEDIMENSIONSMANUFACTURER & MODEL No. REMARKSHEATING COIL SCHEDULE - HOT WATER1. BOTTOM OF DRAIN CONNECTION SHALL BE A MINIMUM OF 3" ABOVE THE BOTTOM OF THE EQUIPMENT RAIL.REMARKS:ACS-8 PENTHOUSE MER 5TH FLR LAB 3700 3700 2.5 7.25 PLENUM 1 - 15" 6.3 3485 DIRECT 7.5 ASD 147.9 20.47 1.2 91 74 55.5 54 4493812.247628 8(CFM) (CFM) (In. WC) (In. WC)& MIN DIA. BHP RPM(MBH) (TONS) (In. WC) DB WB DB WB VEL. (FPM) FLOW (GPM) (Ft. HD) TEMP. (DEG. F) TEMP. (DEG. F)INCHFLOW O.A. STATIC STATIC TYPE FAN NO. MAX FAN DRIVE HP STARTER SENSIBLE TOTAL AIR P.D. EAT (DEG. F) LAT (DEG. F) MAX. FACE WATER WATER P.D. ENT. WATER LVG. WATERPERAIR MIN EXT. TOTAL FAN CHARACTERISTICSMOTORCAPACITYAIR SIDEWATER SIDEROWS FINSUNIT NO. LOCATION SERVICE SUPPLY FANCOOLING COIL (CHILLED WATER - DESATURATION)AIR HANDLING UNIT SCHEDULE - CHILLED WATER /HOT WATERCV-7 PENTHOUSE MER REHEAT LOOP PLATE EXCHANGER 9.5 140 105 1500.63 40% EG 10 100 130 1500.55514 WATER 61.03 BELL AND GOSSETT GPX-AP20(GPM) (DEG. F) (DEG. F)(GPM) (DEG. F) (DEG. F)(FPS)RATE ENT. LVG. (MBH) (Ft. HD)RATE ENT. LVG. (MBH) (Ft. HD) TUBE VEL. PASSES(Sq. Ft.)FLOW WATER TEMP.CAPACITY PRESS. DROP FLUID FLOW WATER TEMP.CAPACITY PRESS. DROP MAXIMUM NO. OF FLUID SURFACE AREAUNIT NO. LOCATION SERVICETYPE HIGH TEMP. SIDELOW TEMP. SIDEHEAT TRANSFER MANUFACTURER & MODEL NO. REMARKSHEAT EXCHANGER SCHEDULE - WATER TO GLYCOL3. STAND-BY2. GLYCOL - PROPYLENE, 40%.1. GLYCOL - ETHLYLENE, 40%.REMARKS:P-21 PENTHOUSE MER ACS-8 PREHEAT COIL INLINE1430 175 3995 1/2 208 1 INTEGRAL ASD -180 34.8 0.45 1-1/4 BELL & GOSSETT ECOCIRC XL 55-451P-20 PENTHOUSE MER HEAT RECOVERYINLINE1270 95 3450 3 208 3ASD4.875 60 28 0.998 1BELL & GOSSETT E-90 1AAB2P-19 PENTHOUSE MER REHEAT LOOPINLINE1040 175 3995 1/2 208 1 INTEGRAL ASD -180 28.9 0.45 1-1/4 BELL & GOSSETT ECOCIRC XL 55-453P-18 PENTHOUSE MER REHEAT LOOPINLINE1040 175 3995 1/2 208 1 INTEGRAL ASD -180 28.9 0.45 1-1/4 BELL & GOSSETT ECOCIRC XL 55-45-(%)(In.)(GPM) IN FEET(DIA. In.) (DEG. F) EFF.SIZES& DESCRIPTION FLOW TOTAL HEAD WWP RPM HP VOLTS PHASE STARTER SIZE TEMP. PUMP BHP DISCHARGEPUMP NO. LOCATIONSERVICEUNIT TYPE PUMP CAPACITYMAX MOTOR CHARACTERISTICSIMPELLER FLUID MIN. MAX. SUCTION & MANUFACTURER & MODEL NO. REMARKSPUMP SCHEDULEARETURNSTEEL WHITETITUS MODEL 355-RL-2SUPPLYSTEEL WHITETITUS MODEL 272-RL-1SUPPLYSTEEL WHITETITUS MODEL TMS-TYPE APPLICATION MATERIAL FINISH MANUFACTURER & MODEL NO. REMARKSREGISTER GRILLE AND DIFFUSER SCHEDULE2. INTEGRAL SOUND ATTENUATOR.1. FIBER FREE LINER.REMARKS:VAV-2 LOUNGE 568 520 270 0.01 82227TITUS DESV1,2VAV-1 CORRIDOR 50044 450 300 0.01 81925TITUS DESV1,2(CFM) (CFM) (In. WC)FLOW FLOW MAX CFM (In.)AIR AIR PRESS AT SIZE AT 1" S.P. AT 1" S.P.UNIT NO. SERVICE MAX MIN MIN INLET INLET RAD N.C. DISCH N.C. MANUFACTURER & MODEL NO. REMARKSVAV - SINGLE DUCT - AIR TERMINAL UNIT SCHEDULE1. COIL PERFORMANCE BASED ON TURBULATORS INSIDE OF THE TUBES.REMARKS:HRC-2 PENTHOUSE MER EXHAUST AIR STANDARD FLANGED 150 4400 70450.554891245.767038.6 40% PG 8 12 36 36AEROFIN W1, 2HRC-1 PENTHOUSE MER OUTSIDE AIR STANDARD FLANGED 150 3700 -5250.74431P-201242.43-532.8 40% PG 8 10 37.5 33AEROFIN W1(CFM) (DEG. F) (DEG. F) (In. W.C.) (FPM)(GPM) (Ft. HD) (DEG. F) (DEG. F)(In.) (In.)FLOW TEMP. TEMP. P.D. VELOCITY NO. FLOW P.D.TEMP.TEMP.INCH LENGTH WIDTH(MBH) AIR ENT. AIR LVG. AIR AIR MAX. FACE PUMP WATER WATER ENT. WATER LVG. WATER FLUID DEEP PERUNIT NO. LOCATION SERVICE TYPE MOUNTING CAPACITY AIR SIDEWATER SIDEROWS FINSCOIL FACEDIMENSIONSMANUFACTURER & MODEL No. REMARKSENERGY RECOVERY "RUN-AROUND" COIL SCHEDULE6. PROVIDE WITH TIGHT SHUT-OFF5. PROVIDE WITH FACTORY DRAW BAND CLAMPS IF VENTURI STYLE VALVE IS PROVIDED.4. PROVIDE WITH FAN STATIC RESET IF VENTURI STYLE VALVE IS PROVIDED.3. PROVIDE WITH FACTORY SOUND NEUTRALIZER IF VENTURI STYLE VALVE IS PROVIDED.2. THE MAX / MIN POSITIONS ON THE VALVE WILL BE SET AT THE FACTORY TO THE FULL RANGE WITH ACTUAL AIRFLOW SETPOINTS IN SOFTWARE.1. REFER TO THE LAB AIRFLOW SCHEDULES FOR FURTHER REQUIREMENTS.REMARKS:GEV-3 LABORATORY 551 ZONE 312" 1790 180 800400 HORIZONTAL 0.2 ACCUTROL ACCUVALVE AVC6000 1,2,3,4,5,6GEV-2 LABORATORY 551 ZONE 214" 2750 250 1500750 HORIZONTAL 0.2 ACCUTROL ACCUVALVE AVC6000 1,2,3,4,5,6GEV-1 LABORATORY 551 ZONE 114" 2750 250 1380680 HORIZONTAL 0.2 ACCUTROL ACCUVALVE AVC6000 1,2,3,4,5,6SAV-3 LABORATORY 551 ZONE 312" 1790 180 700300 HORIZONTAL 0.2 ACCUTROL ACCUVALVE AVC6000 1,2,3,4,5,6SAV-2 LABORATORY 551 ZONE 214" 2750 250 1400140 HORIZONTAL 0.2 ACCUTROL ACCUVALVE AVC6000 1,2,3,4,5,6SAV-1 LABORATORY 551 ZONE 114" 2750 250 1380680 HORIZONTAL 0.2 ACCUTROL ACCUVALVE AVC6000 1,2,3,4,5,6(CFM) (CFM) (CFM) (CFM)(In. WC)FLOW FLOW FLOW FLOWPRESSURE(In.) MAX AIR MIN AIR MAX AIR MIN AIR POSITION OPERATINGUNIT NO. LOCATIONSERVICE SIZE FACTORY RANGE OPERATIONAL RANGE MOUNTING MINIMUM MANUFACTURER & MODEL NO. REMARKSLAB AIR VALVE SCHEDULE
SPRINKLERBRANCH LINEIF OFFSET LENGTHEXCEEDS 2', PROVIDEPIPE HANGERDROP NIPPLECLOSE NIPPLEREDUCERSUSPENDEDCEILINGSPRINKLER PER SPEC(RECESSED PENDENTSPRINKLER SHOWN)(CONCEALED PENDENT)(PENEDENT WITH GUARD)(PENDENT)THREADED 90°ELBOW (TYPICAL)SPRINKLER PER SPECIFICATION (CONCEALED PENDENT SPRINKLER SHOWN)REDUCERSUSPENDED CEILINGSPRINKLER PER SPECIFICATION (PENDENT SPRINKLER WITH GUARD SHOWN)REDUCERSUSPENDED CEILINGSPRINKLER PER SPECIFICATION(PENDENT SPRINKLER SHOWN)SUSPENDED CEILINGREDUCERDESCRIPTIONSYMBOLFIRE PROTECTION SYMBOL LISTQUICK RESPONSE UPRIGHT SPRINKLERPOINT OF CONNECTIONSIDEWALL SPRINKLERNTS NOT TO SCALE(ETR) EXISTING TO REMAINGC GENERAL CONTRACTORPCPLUMBING CONTRACTORFCFLUSHING CONNECTIONNEW PIPINGSSPRINKLER MAIN/BRANCH PIPING (S)ELBOW DOWNDRAIN VALVEELBOW UPCHECK VALVETOP TEE CONNECTIONFLUSHING CONNECTIONCONCEALED PENDENT SPRINKLERSHUT-OFF VALVE WITH TAMPER SWITCH (TS)EXISTING WORK TO BE REMOVEDAFF ABOVE FINISHED FLOORMC MECHANICAL CONTRACTORECELECTRICAL CONTRACTOR(E)EXISTING PIPINGFP FIRE PROTECTION SERVICE (FP)DSPRINKLER DRAIN PIPING (D)45°OFFSETBOTTOM/TEE CONNECTIONPIPE CONTINUATIONQUICK RESPONSE PENDENT SPRINKLERPOINT OF DISCONNECTIONFSFLOW SWITCH (FS)FIRE DEPARTMENT VALVE (FDV)INSPECTOR'S TEST CONNECTION (ITC)(E)EXISTINGORDRAWING KEYNOTEDEMOLITION/REMOVAL KEYNOTEXXFULL SIZE FLUSHING VALVEFULL PIPE CAPFINAL SPRINKLER HEADSPRINKLER CROSS MAIN, REFER TO PLAN FOR SIZEFLUSHING DETAIL NOTES:A.B.C.CONTRACTOR TO PROVIDE SUPPORTING CALCULATIONS FOR THE FLUSHING VALVES,AS PART OF THE SPRINKLER SHOP DRAWINGS.THE FLUSHING VALVES HAVE TO BE SIZED, PER NFPA 20, FOR A MINIMUM VELOCITYMAND THE SPRINKLER CONTRACTOR TO PROVIDE CALCULATIONS, WITH SUBMITTEDSHOW DRAWINGS THAT THE FLUSH VALVE WILL FLOW AT THE MINIMUM VELOCITY,PER NFPA 20.REFER TO FP-000 FOR ADDITIONAL NOTES.05/22/20208:21 AMJARED HOYT135 HOY ROAD, CITY OF ITHACA, NY 14850160 PSI1000 GPMPRESSURE(PSI)10FLOW(GPM)FIRE PUMP FLOW TEST DATADATE:ADDRESS:TIME:STATIC PRESS: FLOW AT 125 PSI:FLOW TEST PERFORMED BY:51520253035404550556065707580859095100105110115120125200 400 600 800100012001400160018002000SCALE: B125 PSI @ 1000 GPM91 PSI @ 1500 GPMFLOW TEST NOTES:A. FLOW TEST RESULTS ARE BASED ON FIRE PUMP TEST:• 160 PSI @ 0 GPM• 125 PSI @ 1000 GPM• 91 PSI @ 1500 GPMRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020GENERAL NOTES, SYMBOLS LISTAND DETAILS -FPFP-000NOT TO SCALE1RETURN BEND DETAILTHESE NOTES ARE APPLICABLE TO THE FULL SET OF CONTRACT DRAWINGS.PROVIDE A COMPLETE FIRE PROTECTION SPRINKLER SYSTEM FOR THE SPACES INDICATED IN COMPLIANCE WITH THE NYS FIRE CODE, STATE CODE REFERENCED EDITION OF NFPA 13 AND THE AUTHORITY HAVING JURISDICTION.THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED. THE CONTRACTOR SHALL CONFIRM ALL PIPE SIZES BY HYDRAULIC CALCULATIONS.THERE SHALL BE NO DECREASE IN PIPE SIZES UNLESS DIRECTED BY ENGINEER.THE PLANS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL ARRANGEMENT OF PIPING, SPRINKLER HEADS AND EQUIPMENT. ALL MAINS, BRANCH LINES, SPRINKLER HEADS, EQUIPMENT AND SYSTEM COMPONENTS SHALL BE PROVIDED. THE PLANS ARE NOT INTENDED TO SHOW EVERY ITEM OF WORK OR EQUIPMENT. THE CONTRACTOR SHALL FURNISH AND INSTALL ANY COMPONENT NECESSARY TO COMPLETE THE SYSTEM IN ACCORDANCE WITH THE BEST PRACTICE OF THE TRADE, NFPA AND THE AHJ WITHOUT ADDITIONAL COST. DRAWINGS DO NOT INDICATE ALL OFFSETS, CHANGES IN ELEVATION, ETC. WHICH MAY BE REQUIRED. THE CONTRACTOR SHALL MAKE SUCH CHANGES IN PIPING AND LOCATION OF EQUIPMENT, ETC. TO ACCOMMODATE WORK, OBSTACLES, AND WORK OF OTHER CONTRACTORS.INSTALL EQUIPMENT AND PIPING TO AVOID INTERFERENCE WITH THE OPERATION, SERVICE, AND MAINTENANCE OF EQUIPMENT. ADVISE OTHER TRADES OF REQUIRED SERVICE CLEARANCES.ALL NEW PENETRATIONS THROUGH WALLS, FLOORS AND ROOFS SHALL BE PROVIDED BY THIS CONTRACTOR FOR INSTALLATION OF FP SYSTEMS INCLUDING, BUT NOT LIMITED TO, EQUIPMENT, PIPING, ETC.. THIS CONTRACTOR SHALL PROVIDE SLEEVES FOR ALL PIPING PENETRATING THROUGH RATED WALLS AND FLOORS. SLEEVES SHALL BE INSTALLED AND BE FIRESTOPPED. ALL PENETRATIONS THROUGH NON RATED WALLS SHALL BE SLEEVED AND SEALED WITH A NON-HARDENING SEALANT ON BOTH SIDES OF THE WALL.DISPOSE OF ALL WASTE MATERIALS CAUSED BY WORK OF THIS CONTRACTOR. LEGALLY DISPOSE ALL MATERIALS TO A LOCATION OFF SITE.COORDINATE AND SCHEDULE WORK AND SHUTDOWNS WITH THE OWNER AND OTHER TRADES PRIOR TO CONSTRUCTION. ARRANGE PIPING TO DRAIN BACK TO LOW POINTS. WHERE NOT POSSIBLE PROVIDE AUXILIARY DRAINS ON SPRINKLER MAIN.PROVIDE SPRINKLER GUARDS FOR ALL SPRINKLERS, LOCATED BELOW DUCTWORK IN MECHANICAL ROOMS, AND FOR SPRINKLERS IN MECHANICAL AND STORAGE SPACES LESS THAN 8 FT. ABOVE FLOOR.DO NOT DRILL, CORE, OR CUT ANY PORTION OF COLUMNS, BEAMS, JOISTS, OR BRIDGING RIBS WITHOUT PRIOR APPROVAL.CONFIRM ALL ELEVATIONS SHOWN ON THESE DRAWINGS.PIPING SHALL BE INSTALLED AND CONCEALED ABOVE FINISHED CEILINGS WITH SPRINKLER HEADS LOCATED IN CENTER OF CEILING TILES. IN AREAS WITH NO CEILINGS PIPING SHALL BE EXPOSED.FIRE PROTECTION GENERAL NOTES:A.B.C.D.E.F.G.H.I.J.K.L.M.N.O.NO WORK SHALL BE DONE ON FP SYSTEM UNTIL HEAT DETECTORS ARE UP AND OPERATIONAL. REFER TO 'E' DRAWINGS.NOTE:1.NOT TO SCALE2CORNELL UNIVERSITY TYPICAL FLUSH ASSEMBLY FOR ALL MAINS, CROSS MAINS,BRANCHES AND RUN OUTSFOR HYDRAULIC REFERENCEONLY3FIRE HYDRANT FLOW TEST DATA CHARTHYDRAULIC CALCULATIONS AND SHOP DRAWINGS:-SYSTEM TO BE DESIGNED TO FM GLOBAL DATA SHEETS AND HAZARD CLASSES AS WELL AS NFPA 13.-CONTRACTOR IS RESPONSIBLE TO DOWNLOAD, REVIEW, AND PROVIDE SHOP DRAWINGS AND CALCULATIONS TO MEET FM GLOBAL DATA SHEETS.-PROVIDE SUBMISSION OF DRAWINGS AND CALCULATIONS WITH EXTRA TIME BUILT IN FOR FM GLOBAL REVIEW COMMENTS.-PROVIDE COMMENTS TO REPLY BACK TO FM GLOBAL REVIEW AND REVISE CALCULATIONS AND DRAWINGS AS REQUIRED.
GF8FEDCBA1234567G5H5X1K111098121314XLOUNGE568DATA CLOSET552ELEC. CLOSET50075CORRIDOR50044Room571Room572Room574Room576Room578STAIR# 350003GRAD.STUDENTS596GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS580STAIR# 250002SHOP501Room503Room500Room502Room504Room504ARoom50073WOMEN50021Room50063Room50062Room50061MEN50022Room50076Room508Room512Room514Room514BRoom516Room518Room520Room517Room519Room521Room521ARoom523CORRIDOR50044(E) 6" FP, (E) 2" DRAIN UP AND DN 1"(E)FP(E)S(E)FP1"1"2"1"1"1"1 1/4"1 1/2"1"1 1/4"1 1/4"1"1"1"1"IE = ?(E) FLOW CONTROL VALVE IN CABINET(E)S(E)S(E)S(E)S(E)S(E)S(E)SCAP AT THIS LOCATION SO REST OF THE SYSTEM REMAINS OPERATIONAL. TIE BACK IN WHEN SYSTEM HAS BEEN REVISEDCAP AT THIS LOCATION SO REST OF THE SYSTEM REMAINS OPERATIONAL. TIE BACK IN WHEN SYSTEM HAS BEEN REVISEDRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH FLOORDEMOLITION PLAN -FPFP-1001/8" = 1'-0"1PARTIAL FIFTH FLOOR DEMOLITION PLAN
GF8FEDCBA1234567G5H5X1K111098121314XRoom571GRAD.STUDENTS596GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS580Room578Room576Room574Room572LABORATORY551STAIR# 350003LABORATORY551Room50073WOMEN50021Room50063Room50062Room50061DATA CLOSET552LOUNGE568ELEC. CLOSET50075MEN50022Room50076CORRIDOR50044CORRIDOR50044Room523Room521ARoom520Room521Room519Room517Room518Room516Room512Room514Room514BRoom504ARoom508STAIR# 250002Room500SHOP501Room503Room502Room5041"1"1"2"1"1"(E) 6" FP, (E) 2" DRAIN UP AND DN (E) FLOW CONTROL VALVESS1"(E)S(E)S(E)S(E)S(E)S(E)SS(E)S(E)S(E)FP(E)FP(E)S2"2"1 1/4"1 1/4"1"1"2"1"2"1 1/2"1 1/4"1"1"1"1 1/2"1 1/2"2"2"1 1/2"1 1/2"2"1"1 1/4"1 1/2"2"2"1 1/4"1"1 1/4"1"1 1/4"1"1 1/4"1"1 1/4"1"2"1 1/4"1"1 1/4"1"1"1 1/4"1"1 1/2" RISER1 1/4"1"PENDENT SPRINKLER IN CEILING. REFER TO ARCH. PLANS FOR HEIGHTPENDENT SPRINKLER IN CEILING. REFER TO ARCH. PLANS FOR HEIGHTPENDENT SPRINKLER IN CEILING. REFER TO ARCH. PLANS FOR HEIGHTPENDENT SPRINKLER IN CEILING. REFER TO ARCH. PLANS FOR HEIGHTCONCEALED SPRINKLER IN CEILING. REFER TO ARCH. PLANS FOR HEIGHTPENDENT SPRINKLER HEAD. REFER TO DETAIL 2 ON THIS DRAWING. (TYP)QR UPRIGHT SPRINKLER HEAD. REFER TO DETAIL 2 ON THIS DRAWING. (TYP)PENDENT SPRINKLER HEAD. REFER TO DETAIL 2 ON THIS DRAWING. (TYP)QR UPRIGHT SPRINKLER HEAD. REFER TO DETAIL 2 ON THIS DRAWING. (TYP)PENDENT SPRINKLER HEAD. REFER TO DETAIL 2 ON THIS DRAWING. (TYP)QR UPRIGHT SPRINKLER HEAD. REFER TO DETAIL 2 ON THIS DRAWING. (TYP)11111111125TH FLOOR6TH FLOOR2" S MAINPENDENT SPRINKLER HEAD. INSTALL DEFLECTOR BELOW ARCHITECTURAL ELEMENTS.QR UPRIGHT SPRINKLER HEAD.Revisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH FLOOR PLAN -FIRE PROTECTIONFP-2001/8" = 1'-0"1PARTIAL FIFTH FLOOR PLANNONE2TYPICAL SPRINKLER HEAD ELEVATIONDRAWING NOTES1 RELOCATE SPRINKLER HEAD TO CENTER IN NEWCEILING GRID. REVISE PIPING AS NECESSARY.
VENT PIPINGSHOCK ABSORBER (SA)BACKFLOW PREVENTER (BFP)UNIONPIPE GUIDECHECK VALVEBALANCING VALVESHUT OFF VALVEINDIRECT WASTE PIPING (IW)IWCLEANOUT (CO)WALL PLATE CLEANOUT (WPCO)DECK PLATE CLEANOUT (DPCO)CAP OR PLUGPIPE CONTINUATION"P" TRAPTOP TEE CONNECTIONBOTTOM/TEE CONNECTIONELBOW UP45°OFFSETELBOW DOWNDESCRIPTIONPLUMBING SYMBOL LISTSYMBOLSTSTORM WATER SEWER PIPING (ST)ACID VENT PIPING (AV)AVACID WASTE PIPING (AW)AWSANITARY SEWER PIPINGSANHOT WATER RECIRCULATING PIPING (HWR)HOT WATER PIPING (HW)COLD WATER PIPING (CW)NEW PIPING LOCATED BELOW FLOOR/SLABNEW PIPING LOCATED ABOVE FLOOR/SLAB(E)EXISTING PIPINGECELECTRICAL CONTRACTORPC PLUMBING CONTRACTORMC MECHANICAL CONTRACTORGC GENERAL CONTRACTORVTR VENT THRU ROOFBFF BELOW FINISHED FLOORAFF ABOVE FINISHED FLOOR(ETR) EXISTING TO REMAIN(E) EXISTINGNTSNOT TO SCALEPOINT OF DISCONNECTIONPOINT OF CONNECTIONEXISTING WORK TO BE REMOVEDPD PUMP DISCHARGE PIPING (PD)DRAWING KEYNOTEDEMOLITION/REMOVAL KEYNOTEXXST(S) SECONDARY STORM WATER SEWER PIPING (ST(S)DETAIL NOTES:DOMESTIC COLD WATERFLOW DIRECTION LABEL. PROVIDE 360 DEGREE WRAP OVERLAPPING BOTH ENDS OF THE PIPE FUNCTION LABEL AND MATCHING THE FLOW DIRECTION OF THE PIPE CONTENTS.PIPE FUNCTION LABELA.B.C.D.E.F.PROVIDE A PIPE LABEL FOR EACH PIPE FUNCTION.PROVIDE AT LEAST ONE LABEL ON EACH PIPE FOR EVERY ROOM THEPIPE PASSES THROUGH.PROVIDE LABELS IN LARGE SPACES ON MAXIMUM 20' CENTERS FOREVERY PIPE UNLESS OTHERWISE NOTED IN THE SPECIFICATIONS.LABELS TO BE LOCATED IN AN EASILY VISIBLE LOCATION AS THEYWOULD NORMALLY BE SEEN. IE. ON THE BOTTOM HALF OF PIPESIN THE AIR AND ON THE TOP HALF OR SIDES OF PIPES MOUNTED LOW.LABELS SHALL BE, COLOR CODED, PRE-PRINTED, SELF ADHESIVE VINYL.SEE SPECIFICATION FOR OTHER REQUIREMENTS AND LIST OF PIPE FUNCTIONS.DETAIL NOTES:A. ELECTRICAL EQUIPMENT INCLUDES PANELS, TRANSFORMERS, DISCONNECTS,STARTERS, MOTOR CONTROL CENTERS, SWITCHGEAR, ADJUSTABLE SPEEDDRIVES, AND FUSED SWITCHES (THIS ALSO APPLIES TO ELECTRICAL GEARMOUNTED DIRECTLY ON MECHANICAL EQUIPMENT).B. DEDICATED ELECTRICAL SPACE IS DEFINED BY NEC 110.C. NO PIPING OR DUCTWORK MAY BE INSTALLED IN DEDICATED ELECTRICALSPACE OR WORKING SPACE.STRUCTURAL CEILINGSTRUCTURAL CEILING6'-6"SPRINKLER ALLOWEDDEDICATEDELECTRICALSPACEWORKINGSPACE3'-0" TO 9'-0"PER NEC 1106'-0"DUCTWORKINGSPACESIDEVIEWLUMINAIREPERMITTED6'-6"MIN.SIDEVIEWDEDICATEDELECTRICALSPACE6'-0"ORLESSSUSPENDEDCEILINGSUSPENDEDCEILINGFRONTVIEW6'-6"MIN.LUMINAIREPERMITTEDFRONTVIEW30"MIN.PIPINGPERMITTEDLUMINAIREPERMITTEDPIPINGPERMITTEDTYPICALELECTRICALEQUIPMENTPIPINGPERMITTEDMAINONOFFMAINONOFFMAINONOFFMAINONOFFMAINONOFFMAINONOFF6'-0"WORKINGSPACE36"MIN.PUMP SCHEDULENO. LOCATIONSERVICEGPMHEAD FTWATERMOTORTYPEDESIGN MAKEHP VOLTAGE PHASERPMFIXTURE AND EQUIPMENT CONNECTION SCHEDULEDESIGNATION DESCRIPTIONCOLDWATERHOTWATERWASTE ORSANITARYVENTREMARKSSHOCK ABSORBER SCHEDULENO.FIXTURE UNITRATINGSIZE ININCHESPDI SYMBOLSA-A1 - 111/2"ASA-B12 - 323/4"BSA-C33 - 601"CUCP-1AT SINKSANITARY301/2 115345010LIBERTY MODEL 405 SK-A SINK 1/2" 1/2"1 1/2" 1 1/2"DRAIN1EW-A EMER. EYEWASH 1/2" TEPID----CP-1PENTHOUSE MER INDIRECT WASTE1/30 115LIBERTY MODEL LC-20 DRAIN1(E)CW MAINIWA.DETAIL NOTES:B.FINISHED FLOORC.D.E.BY DIVISION 22BY DIVISION 232'-6" MINIMUM5' MAXIMUMTO HVACEQUIPMENTMAKEUPWATERINDIRECT WASTE. RUN TONEAREST FLOOR DRAIN WITH1" MINIMUM AIR GAP.FLOORDRAIN3" AIR GAP3" FUNNEL DRAINFINAL CONNECTIONBY DIVISION 233/4" RPZ BACKFLOWPREVENTERBACKFLOW PREVENTER SHALL BE LOCATED UPSTREAM OF ALLCONNECTIONS TO HVAC EQUIPMENT.PROVIDE PROPER SUPPORTS FOR BACKFLOW PREVENTER ANDPIPING.PROVIDE 8" CLEARANCE BEHIND BACKFLOW PREVENTER, 1'ABOVE AND 2'-6" CLEARANCE IN FRONT OF DEVICE.THE INSTALLATION OF A FIXED AIR GAP FITTING IS NOT ACCEPTABLEFOR USE ON DRAIN LINE. PROVIDE FUNNEL DRAIN AS INDICATED.PAINT SUPPORTS WITH ONE (1) PRIMER AND TWO (2) FINISH COATSOF COLOR AS SPECIFIED.3/4" DRAIN VALVE2" IWREDUCERINCREASER1"1"1/2" HW, 1/2" CW, 1 1/2" V, & 2" FORCE MAIN UP. REFER TO FLOOR PLAN FOR ROUTING1 1/2" DRAIN LINEUCP-1TMV-ASINKEYEWASHRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020GENERAL NOTES, SYMBOLS LIST,AND SCHEDULES -PLUMBINGP-000NOT TO SCALE1PIPING IDENTIFICATION LABEL DETAILNOT TO SCALE2PIPING OVER ELECTRICAL EQUIPMENT DETAILTHESE NOTES ARE APPLICABLE TO ALL PLUMBING CONTRACT DRAWINGS.DISPOSE OF ALL DEMOLITION AND/OR OTHER WASTE MATERIALS CAUSED BY WORK OF THIS CONTRACT. LEGALLY DISPOSE OF ALL MATERIALS TO A LOCATION OFF SITE.COORDINATE AND SCHEDULE WORK AND SHUTDOWNS WITH THE OWNER AND OTHER TRADES PRIOR TO DEMOLITION.PATCH HOLES IN EXISTING CONSTRUCTION LEFT BY THE REMOVAL OF PIPING AND EQUIPMENT. MAINTAIN THE FIRE/SMOKE RATING OF EXISTING CONSTRUCTION. DEMOLITION SHALL INCLUDE, BUT NOT BE LIMITED TO: PIPING, VALVES, FIXTURES, EQUIPMENT, HANGERS, SUPPORTS, AND INSULATION EXCEPT ASBESTOS.SLEEVE AND SEAL ALL WALL AND FLOOR PENETRATIONS. PROVIDE FIRESTOPPING FOR ALL PENETRATIONS. ALL PENETRATIONS THROUGH FIRE WALLS AND FLOORS SHALL BE SLEEVED AND FIRE/SMOKE STOPPED. REFER TO CONTRACT DOCUMENTS FOR FIRE WALL AND FLOOR LOCATIONS. ALL PENETRATIONS THROUGH NON RATED WALLS SHALL BE SLEEVED AND SEALED. SEAL WITH A NON-HARDENING SEALANT ON BOTH SIDES OF WALL PENETRATION TO REDUCE NOISE TRANSMISSION.MAINTAIN SERVICE CLEARANCES OF ALL EQUIPMENT. ADVISE OTHER TRADES OF ALL REQUIRED SERVICE CLEARANCES.PROVIDE CLEANOUTS AT THE BASE OF ALL STORM, SANITARY AND WASTE STACKS.PITCH 4" AND LARGER SANITARY, STORM, AND WASTE PIPING AT 1/8" PER FOOT UNLESS OTHERWISE NOTED. FOR SANITARY, STORM, AND WASTE PIPING 3" AND SMALLER PITCH AT 1/4" PER FOOT UNLESS OTHERWISE NOTED.THE PLANS ARE DIAGRAMMATIC AND INDICATE THE GENERAL PIPING AND EQUIPMENT ARRANGEMENT. ALL PIPING MAINS, EQUIPMENT, BRANCH LINES, AND SYSTEM COMPONENTS SHALL BE PROVIDED. THE PLANS ARE NOT INTENDED TO SHOW EVERY ITEM OF WORK OR EQUIPMENT. THE CONTRACTOR SHALL PROVIDE ALL COMPONENTS NECESSARY TO COMPLETE THE SYSTEM IN ACCORDANCE WITH THE BEST PRACTICE OF THE TRADE WITHOUT ADDITIONAL COST.ITEMS OF WORK OR EQUIPMENT SHOWN ON THE DRAWINGS ONLY, OR CALLED FOR IN THE SPECIFICATIONS ONLY, SHALL BE PROVIDED IN THE SAME MATTER AS IF THEY APPEARED ON BOTH THE DRAWINGS AND THE SPECIFICATIONS.DRAWINGS DO NOT INDICATE ALL OFFSETS, CHANGES IN ELEVATION, ETC. WHICH MAY BE REQUIRED. THE CONTRACTOR SHALL MAKE ALL SUCH CHANGES IN PIPING AND LOCATIONS OF EQUIPMENT, ETC. TO ACCOMODATE WORK, OBSTACLES, AND WORK OF OTHER CONTRACTORS. INSTALL EQUIPMENT AND PIPING TO AVOID INTERFERENCE WITH THE OPERATION, SERVICE AND MAINTENANCE OF EQUIPMENT. ADVISE OTHER TRADES OF REQUIRED SERVICE CLEARANCES. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PATCHING OF EXISTING OR NEW FIREPROOFING WHICH IS DISTURBED OR REMOVED DURING THE COURSE OF ANY DEMOLITION OR NEW WORK THAT IS PART OF THIS CONTRACT.FIELD VERIFY ALL FLOOR ELEVATIONS INDICATED ON THE PLANS.REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL PLUMBING FIXTURES, LOCATIONS OF GRAB BARS AND CONTROLS, ETC.PROVIDE SHUTOFF VALVES ON ALL CW AND HW BRANCHES SERVING INDIVIDUAL PLUMBING FIXTURES.UNLESS OTHERWISE INDICATED, PLUMBING CONTRACTOR SHALL PROVIDE CUTTING AND PATCHING AND ALL CORING OF SLABS, WALLS AND OTHER ITEMS REQUIRED FOR PLUMBING WORK.GENERAL NOTES:A.B.C.D.E.F.G.H.I.J.K.L.M.N.O.P.NOT TO SCALE4MAKE-UP WATER BACKFLOW PREVENTER DETAILNOT TO SCALE3SINK AND EYEWASH SCHEMATICNOTE: ALL LOCATIONS ARE SIMILAR
LOUNGE568DATA CLOSET552ELEC. CLOSET50075CORRIDOR50044Room571Room572Room574Room576Room578STAIR# 350003GRAD.STUDENTS596GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS580STAIR# 250002SHOP501Room503Room500Room502Room504Room504ARoom50073WOMEN50021Room50063Room50062Room50061MEN50022Room50076Room508Room512Room514Room514BRoom516Room518Room520Room517Room519Room521Room521ARoom523CORRIDOR50044GF8FEDCBA1234567G5H5X1K111098121314X(E) 3" IW UP(E) 3" IW UP(E)IW3"3"(E)IW(E) 3" IW UP3"(E)IW(E)IW3"(E)IW3"(R) 3" IW DOWN TO SERVICE SINK W/ AIR GAP3"(E) 4" SAN, (E) 3" V, (E) 2" CW, (E) 1" HW UP AND DN(E) 4" S.P.O., (E) 3" V.P.O, (E)CW C.O., (E)HW C.O. REMOVE HW BACK INTO CHASE I.E. = 107" 1111111Revisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH FLOORDEMOLITION PLAN -PLUMBINGP-1001/8" = 1'-0"1PARTIAL FIFTH FLOOR DEMOLITION PLANDEMOLITION NOTES1 DISCONNECT AND REMOVE CONDENSATE ASSOCIATED WITH HVAC EQUIPMENT BACK TOMAIN & CAP. VERIFY ROUTING AND EXTENT OF REMOVALS IN FIELD.
(E) HW RISER(E) HW RISERREMOVE SECTION1" HW1" HWBYPASS VALVE IN CLOSED POSITION, LABEL "NORMALLY CLOSED"GF8FEDCBA1234567G5H5X1K111098121314XRoom571GRAD.STUDENTS596GRAD.STUDENTS594STAFF592STAFF590ASSOC.DIRECTOR588LIBRARY586CLERICAL584DIRECTOR582GRAD.STUDENTS580Room578Room576Room574Room572LABORATORY551STAIR# 350003LABORATORY551Room50073WOMEN50021Room50063Room50062Room50061DATA CLOSET552LOUNGE568ELEC. CLOSET50075MEN50022Room50076CORRIDOR50044CORRIDOR50044Room523Room521ARoom520Room521Room519Room517Room518Room516Room512Room514Room514BRoom504ARoom508STAIR# 250002Room500SHOP501Room503Room502Room504(E) 3" IW UP(E) 3" IW UP(E) 3" IW UP3" IW DOWN TO SERVICE SINK W/ AIR GAP(E) 4" SAN, (E) 3" V, (E) 2" CW, (E) 1" HW UP AND DN(E)IW3"3"3"(E)IW(E)IW(E)IW3"3"SK-A1/2" CW, HW, 1 1/2" V, AND 1 1/2" FM DN1/2" CW, HW, 1 1/2" V DN1/2" CW, HW, 1 1/2" V DNSK-ASK-A●●3/4"●●●●PD1 1/2"1/2"1 1/2"●●●●1"1"2" V2" SAN(E)1 1/2" CW TAP CUT AND PATCH WALL TO CONNECT TO 1" HW RISER, REFER TO DETAIL 1/P201PUMP UCP-1 TO BE UNDER COUNTER AT SINK, REFER TO DETAIL 3/P-000PUMP UCP-1 TO BE UNDER COUNTER AT SINK, REFER TO DETAIL 3/P-000PUMP UCP-1 TO BE UNDER COUNTER AT SINK, REFER TO DETAIL 3/P-000PD●●●(E)IW(E)IWEW-AEW-AEW-A●●●1/2"1"●●1"●●1"1"1/2"PD1 1/2"3/4"1 1/2"ROUTE PIPING UP IN CHASE SPACEROUTE PIPING DOWN COLUMN EXPOSEDRACK PIPING ON WALL IN CHASEPD●●●●1 1/2"●●●ROUTE 3" IW AROUND DOOR HEADER & THRU SHAFT.IWRevisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PARTIAL FIFTH FLOOR PLAN -PLUMBINGP-200NOT TO SCALE1RISER CONNECTION DETAIL1/8" = 1'-0"2PARTIAL FIFTH FLOOR PLAN
8006480061809807801801A803803A80580046800478028118006280480060GF8FEDCBA1234567G5H5X1K111098121314X(E)FDAHU -NEW(E)FD(E)FD(E)FD(E)FD(E)FD●LABEL "NON-POTABLE"PROVIDE 3/4" RPZ DESIGN BASIS WATTS LF009 AND ROUTE DISCHARGE TO FD. REFER TO DETAIL 4/P-000CONNECT TO HVAC MAKE-UP WATER, CONT'D ON HVAC DRAWINGS1"●TERMINATE PIPING ABOVE FLOOR DRAIN W/ AIR GAPPUMP CP-1. CONNECT TO HVAC CONDENSATE, CONT'D ON HVAC DRAWINGSIW1 1/4"(E)4" CW(E)3/4"1"●Revisions:Richard McElhiney Architects LLC347 West 36 Street Suite 1501New York, NY 10018212-245-5195 T212-239-7130 FJacobs303 South Broadway, Suite G20Tarrytown NY 10591914-841-1069 TM/E Engineering, P.C.300 Trolley BoulevardRochester, NY 14606585-288-5590 T Ryan Biggs Clark Davis257 Ushers Rd Clifton Park, NY 12065518-406-5506 TDelta860 Hooper RoadEndwell, NY 12065518-406-5506Trophy Point4588 South Park Avenue Blasdell, New York 14219716-823-0006 TKey Plan:Notes:Rhodes HallCornell UniversityIthaca, NY 14850December 15, 2020Scale:Fifth Floor RenovationAs IndicatedIssue for Bid December 15, 2020PENTHOUSE PLAN -PLUMBINGP-2011/8" = 1'-0"1PENTHOUSE PLAN
OPEN FULL ARROW(S) INDICATES 480 VOLT CIRCUIT
TO MULTI-POLE CIRCUIT BREAKER, UNLESS NOTED
OTHERWISE.
OPEN HALF ARROW(S) INDICATES 277 VOLT CIRCUIT
TO SINGLE POLE CIRCUIT BREAKER(S), UNLESS
NOTED
OTHERWISE.
SOLID FULL ARROW(S) INDICATES 208 VOLT CIRCUIT
TO MULTI-POLE CIRCUIT BREAKER, UNLESS NOTED
OTHERWISE.
SOLID HALF ARROW(S) INDICATES 120 VOLT CIRCUIT
TO SINGLE POLE CIRCUIT BREAKER(S), UNLESS
NOTED
OTHERWISE.
LP-404
HOME RUN TO PANELBOARD. LETTERS/NUMBERS
INDICATE PANEL. NUMBERS INDICATE CIRCUITS.
NUMBER OF ARROWS EQUALS NUMBER OF CIRCUITS.
CIRCUIT SHALL BE 20 AMP, 120 VOLT, 2 #12, 1 #12
EG., IN " C, UNLESS NOTED OTHERWISE. BRANCH
CIRCUIT WIRING SIZE AND NUMBER TO MATCH
HOMERUN. REFER TO SPEC'S FOR RACEWAY TYPE.
BASIC MATERIALS
AND METHODS
3
HEAVY SOLID IS NEW,
EXISTING ELECTRICAL WIRING, EQUIPMENT OR
DEVICE,
SOLID LIGHT IS EXISTING TO REMAIN
,
EXISTING ELECTRICAL WIRING, EQUIPMENT OR
DEVICE,
DASED LIGHT IS EXISTING TO BE REMOVED OR
RELOCATED
,
REFERENCE TO DRAWING NOTE
DH
OS
D
J
DOOR HOLD
CORD DROPCD
DIMMER - SHALL BE COMPATIBLE WITH FIXTURES
PROVIDED.
TOGGLE SWITCH, VOLTAGE AS INDICATED ON FIXTURE
SCHEDULE, SUBSCRIPTS INDICATE TYPE:
2 - TWO POLE SWITCH
3 - THREE WAY SWITCH
4 - FOUR WAY SWITCH
M - MONENTARY CONTACT
K - KEY OPERATED
a,b,c - SWITCHING DESIGNATIONS NUMBER OF
LETTERS EQUALS NO. OF GANGED SWITCHES
V - VACANCY SENSOR
VD - VACANCY SENSOR, DIMMER SWITCH
VDS - VACANCY SENSOR, DUAL SWITCHED
WP - WEATHERPROOF
QUAD RECEPTACLE 20 AMP, 125 VOLT
DUPLEX RECEPTACLE, 20 AMP, 125 VOLT
SUBSCRIPTS INDICATE TYPE:
G - GROUND FAULT INTERUPT
OC - OVER COUNTER
UC - UNDER THE COUNTER
WP - WEATHER PROOF
TP - TAMPER PROOF
P - CEILING PROJECTOR, MOUNT IN PROJECTOR
MOUNTING PLATE
USB - INTEGRAL USB CHARGER
H - MOUNT IN HORIZONTAL DIRECTION
SPECIAL PURPOSE RECEPTACLE. PROVIDE PROPER
VOLTAGE, CLASS, CURRENT RATING AND NEMA
CONFIGURATION AS REQUIRED BY BRANCH CIRCUIT
AND/OR MATCH CAP ON EQUIPMENT BEING
FURNISHED
BY OTHERS. PROVIDE CORD AND CAP. SUBSCRIPTS
INDICATE TYPE:
J
CEILING MOUNTED OCCUPANCY SENSOR
JUNCTION BOX
3a,b,c
3 REFERENCE TO DEMOLITION NOTE
EXISTING TO REMAIN - INDICATES EXISTING ITEM
SHALL REMAIN. MAINTAIN EXISTING ELECTRICAL
CONNECTIONS UNLESS OTHERWISE NOTED.
(E)
EXISTING TO BE RELOCATED - INDICATES EXISTING
ITEM SHALL BE RELOCATED. DISCONNECT AND
REMOVE, REINSTALL AT NEW LOCATION AND
RECONNECT ITEM AS REQUIRED.
(ER)
CORD REELCR
PUSH BUTTON
LAB BENCH RECEPTACLES. VARIOUS CONFIGURATIONS.
FB FLOOR BOX. SHALL BE WIREMOLD RFB4E_OG, UNLESS
OTHERWISE INDICATED. PROVIDE (1) 3/4" CONDUIT
FOR POWER TO TWO DUPLEX RECEPTACLES, (1) 1"
CONDUIT FOR FUTURE DATA DROP AND (2) 1" CONDUIT
FOR AV TO ACCESSIBLE CEILING. COVER
PER ARCHITECT.
COMMUNICATIONS
DIDF DATA INTERMEDIATE DISTRIBUTION FRAME
DMDF DATA MAIN DISTRIBUTION FRAME
EXISTING COMMUNICATIONS OUTLET
TEL/DATA DROP:
4"x4"x2.50" BOX WITH A 1-GANG MUD RING &
FACEPLATE WITH DUPLEX DESIGN. 1" CONDUIT
EXTENDED TO NEAREST CABLE TRAY IN CORRIDOR
( UNLESS OTHERWISE NOTED) FOR DATA/VOICE.
TERMINATE CONDUIT AT J HOOK IN CORRIDOR WITH
CONDUIT BUSHING. PULL (2) CAT 6 CABLE, TERMINATE
AT PATCH PANEL IN BDF.
W - SINGLE GANG BACK BOX WITH MUD RING AND 1"
CONDUIT EXTENDED TO NEAREST CABLE TRAY IN
CORRIDOR (UNLESS OTHERWISE NOTED) FOR
DATA/VOICE. WALL MOUNT AT 46"AFF. PROVIDE (1)
CAT 6 CABLE TO BDF.
DDC - SINGLE GANG BOX WITH BLANK COVER PLATE.
PROVIDE 3/4"C STUBBED TO ACCESSIBLE
CEILING SPACE ABOVE. DDC ALARM WIRING BY
DIV 23.
C - CAMERA, COORDINATE MOUNTING HEIGHT WITH
ARCHITECTURAL DRAWINGS.
TV - COORDINATE MOUNTING HEIGHT WITH
ARCHITECTURAL DRAWINGS.
DSD
FSD
FS
TS
FAAP
FACP
WAP
H
F
F
F
SD
S
FIRE ALARM
SMOKE DAMPER CONNECTION
DUCT SMOKE DETECTOR
FIRE ALARM SHUT DOWN RELAY
SMOKE DETECTOR, BEAM TYPE RECEIVERSRX
SMOKE DETECTOR, BEAM TYPE TRANSMITTERSTX
FLOW SWITCH CONNECTION
TAMPER SWITCH CONNECTION
FIRE ALARM ANNUNCIATION PANEL
FIRE ALARM CONTROL PANEL
REMOTE DUCT SMOKE DETECTOR TEST INDICATOR
RATE-OF-RISE HEAT DETECTOR
ALARM SIGNAL, STROBE, SHALL BE WHITE DEVICE
ALARM SIGNAL, SPEAKER AND STROBE, SHALL BE
WHITE DEVICE
MANUAL PULL STATION
SMOKE DETECTOR
M
D
CB
T
CONTACTOR
ENCLOSED CIRCUIT BREAKER
COMBINATION FUSED DISCONNECT SWITCH
AND MAGNETIC STARTER
208Y/120 VOLT PANELBOARD.
TRANSFORMER
COMPLETE ELECTRICAL CONNECTION
TO EQUIPMENT
A d
A d
CEILING MOUNTED EXIT LUMINAIRE
WALL MOUNTED EXIT LUMINAIRE
STRIP LUMINAIRE
CEILING MOUNTED AREA-OF-RESCUE LUMINAIRE
WALL MOUNTED AREA-OF-RESCUE LUMINAIRE
CEILING MOUNTED LUMINARIE. UPPERCASE LETTERS
INDICATE FIXTURE TYPE ON LUMINAIRE SCHEDULE,
LOWER CASE LETTER INDICATE LIGHTING ZONE
WALL MOUNTED LUMINARIE. UPPERCASE LETTERS
INDICATE FIXTURE TYPE ON LUMINAIRE SCHEDULE,
LOWER CASE LETTER INDICATE LIGHTING ZONE
LUMINAIRE CONNECTED TO LIFE SAFETY
EMERGENCY
POWER
WALL MOUNTED EMERGENCY LUMINAIRE
WITH BATTERY PACK
MOTOR CONNECTION. REFER TO ELECTRICAL
EQUIPMENT AND CONTROL SCHEDULE FOR SIZE
POWER DISTRIBUTION
AND CONTROL
480Y/277 VOLT PANELBOARD.
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
DISTRIBUTION PANELBOARD.
MOTORIZED DAMPER CONNECTION
LUMINAIRES
TRACK LIGHTING
DOUBLE HEAD POLE MOUNTED LUMINAIRE
SINGLE HEAD POLE MOUNTED LUMINAIRE
A
E N
LA
G
EGAP
RTSA
TVSS
ONE LINE
DIAGRAM SYMBOLS
GROUND CONNECTION
AUTOMATIC TRANSFER SWITCH
GENERATOR
EMERGENCY GENERATOR ANNUNCIATOR PANEL
REMOTE TRANSFER SWITCH ANNUNCIATOR PANEL
TRANSFORMER, REFER TO SCHEDULE FOR SIZE
AND TYPE
POTENTIAL TRANSFORMER
LIGHTNING ARRESTOR
TRANSIENT VOLTAGE SURGE SUPPRESSOR
PT
CT
A
E N
LA
G
EGAP
RTSA
TVSS
ONE LINE
DIAGRAM SYMBOLS
FUSED DISCONNECT SWITCH
THERMAL MAGNETIC MOLDED CASE CIRCUIT
BREAKER
AUTOMATIC TRANSFER SWITCH
GENERATOR
EMERGENCY GENERATOR ANNUNCIATOR PANEL
REMOTE TRANSFER SWITCH ANNUNCIATOR PANEL
FEEDER DESIGNATION. REFER TO FEEDER
SCHEDULE
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
TRANSIENT VOLTAGE SURGE SUPPRESSOR
PT
CT
CEILING
RECEPTACLE
4'-0"
EXIT
LIGHT
SWITCH
2.
MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY CONSTRUCTION
THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST BLOCK OR BRICK
COURSING.
THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED
OTHERWISE ON THE DRAWINGS.
1.
DETAIL NOTES:
1'-6"
DIVIDED
SURFACE
RACEWAY
HORN/LIGHT
LENS ON
TOP
FINISHED
FLOOR
PULLSTATION
COORDINATE EXACT
MOUNTING
HEIGHT WITH ARCHITECT.
ENTIRE LENS SHALL BE MINIMUM 80" AFF AND NOT
GREATER THAN 96" AFF.
WHERE NOT PERMITTED BY CEILING HEIGHT
DEVICE
SHALL BE MOUNTED
WITHIN 6" OF THE CEILING.
4'-0"
EXIT SIGNS
CENTERED ABOVE DOOR
CR CARD READER, REFER TO DETAIL
DC DOOR CONTACT
COMBINATION POWER/COMMUNICATION SURFACE
RACEWAY WITH DEVICES AS INDICATED. WIREMOLD G4000.
RACEWAY SHALL BE MOUNTED "OVER COUNTER" UNLESS
OTHERWISE NOTED.
ML MAG LOCK
WAP - WIRELESS ACCESS POINT WALL MOUNT AT 90"AFF
4"x4"x2.25" BOX WITH DOUBLE GANG PLASTER RING. 1"
EMT CONDUIT EXTENDED TO NEAREST CABLE TRAY IN
CORRIDOR (UNLESS OTHERWISE NOTED). PROVIDE TWO
(2) CAT 6A CABLES. TERMINATE IN BDF AND 6-8" PIGTAIL
WITHOUT FACEPLATE.
EM TYPICAL EMERGENCY PHONE OUTLET LOCATION.
PROVIDE 4"x4" BACKBOX WITH A SINGLE GANG
MUD RING AND (1) 3/4" CONDUIT TO ACCESSIBLE CEILING
SPACE. PROVIDE (1) CAT 6 CABLE TO BDF. COORDINATE
FINAL LOCATION WITH THE OWNER PRIOR TO
INSTALLATION.
DAS ANTENNAANT
DS DAYLIGHT SENSOR
EM EMERGENCY PHONE: INTERIOR LOCATIONS
EMERGENCY PHONES PROVIDED BY ELECTRICAL
CONTRACTOR. REFER TO DETAIL SHEETS FOR
INSTALLATION DETAILS.
PT POKE THROUGH - WIREMOLD 8AT SERIES. PROVIDE
(1) 3/4" CONDUIT FOR POWER TO TWO DUPLEX
RECEPTACLES, (1) 1" CONDUIT FOR FUTURE DATA
DROP AND (1) 1-1/2" CONDUIT FOR AV TO
ACCESSIBLE CEILING. COVER PER ARCHITECT.
P PROJECTOR - (1) DUPLEX AND (1) TEL/DATA DROP.
RTS
ENCLOSED CABLE TRAY SIZE PER QUANTITY OF
CABLES AND 50% FUTURE CAPACITY AT A MINIMUM.
AV
PT STEELCASE TWO DOOR LOW PROFILE CONNECTOR
COVER MODEL #16-0011519. PROVIDE ALL
REQUIRED
ACCESSORIES FOR A COMPLETE SYSTEM
INCLUDING
BUT NOT LIMITED TO WALL POWER IN FEED,
POWER
TRACK, CONNECTORS, ETC.
FIRE ALARM HORN/SPEAKERF
DC DOOR CONTACT
G.
H.
I.
WHEN EXISTING CONSTRUCTION, WHICH IS TO REMAIN, IS DAMAGED DURING THE COURSE OF
DEMOLITION AS A RESULT OF THE CONTRACTOR'S WORK, IT SHALL BE REPAIRED AND/OR
REPLACED WITH SIMILAR OR LIKE MATERIALS, AS MUCH AS POSSIBLE, SUBJECT TO THE
OWNERS APPROVAL.
THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND REPLACEMENT OF EXISTING
CONSTRUCTION IN THE WAY OF NEW WORK. PROTECT BUILDING AND FURNISHINGS FROM DAMAGE.
COORDINATE PHASING OF WORK WITH OWNER'S REPRESENTATIVE.
COORDINATE ALL SHUTDOWNS WITH UNIVERSITY PRIOR TO DEMOLITION. ALL FIRE ALARM
SHUTDOWNS SHALL BE SCHEDULED THROUGH CUSTOMER SERVICE WITH AT LEAST 24 HOURS
NOTICE BEFORE WORK IS TO BE STARTED.
EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION
DOCUMENTS WHEN AVAILABLE AND ARE NOT GARAUNTEED. PRIOR TO SUBMITTING BID, VISIT
SITE AND IDENTIFY EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE DEMOLITION
WORK. NO COMPENSATION WILL BE GRANTED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY
WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY EXPERIENCED OBSERVERS.
THIS CONTRACTOR SHALL PARTICIPATE IN SURVEY OF THE EXISTING ELECTRICAL SYSTEMS. THE
CONTRACTOR SHALL DISCONNECT AND CAP ALL SERVICE LINES TO BE DISCONNECTED FOR THOSE
SERVICES WHICH NORMALLY ARE INCLUDED IN HIS FIELD OF WORK. PARTICULAR CARE SHALL BE
TAKEN TO AVOID CREATING HAZARD OR CAUSING DISRUPTION IN ADJOINING AREAS. NOT ALL
DEVICES TERMINATIONS, JUNCTION BOXES AND WIRING HAVE BEEN SHOWN.
REFER TO PLUMBING CONTRACT DRAWINGS AND SPECIFICATIONS FOR EXACT QUANTITIES AND
LOCATIONS OF ALL PLUMBING EQUIPMENT BEING ABANDONED OR REMOVED, WHICH WILL REQUIRE
DE-ENERGIZATION, REMOVAL AND BLANK-OFF BY THE CONTRACTOR.
EXISTING FIRE ALARM SYSTEM SHALL BE KEPT OPERATIONAL DURING THE CONSTRUCTION PERIOD
THE BUILDING UNDER RENOVATION MAY BE DISCONNECTED FROM SERVICE DURING THE HOURS THE
CONTRACTOR IS WORKING, AT THE DISCRETION OF THE FIRE DEPARTMENT AND THE OWNER'S
REPRESENTATIVE, BUT MUST BE OKACED BACK ON LINE DURING OTHER PERIODS. APPROVAL TO BE
IN WRITING.
THE EXISTING ELECTRICAL EQUIPMENT AND DEVICES WITHIN DEMOLITION AREA SHALL BE DEMOLISHED
ALONG WITH ALL FEEDERS AND CONDUITS BACK TO POINT OF SOURCE UNLESS OTHERWISE NOTED.
ALL ITEMS SHOWN ON THE DEMOLITION DRAWINGS SHALL BE DISCONNECTED AND REMOVED UNLESS
NOTED OTHERWISE. WALLBOXES, BACKBOXES AND CONDUIT SHALL BE REUSED AS DETERMINED BY
CONTRACTOR. ALL UNUSED CONDUITS SHALL BE REMOVED. DISCONNECT AND MAKE SAFE ANY
EQUIPMENT TO BE REMOVED BY OTHERS. COORDINATE REMOVAL OF EQUIPMENT WITH OTHER TRADES
PRIOR TO DEMOLITION.
MAINTAIN AND RESTORE, IF INTERRUPTED BY REMOVALS OR IN PATH OF NEW CONSTRUCTION, ALL
CIRCUITS, CONDUITS AND FEEDERS PASSING THROUGH AND SERVING UNDISTURBED AREAS (SHOWN
OR NOT SHOWN).
ALL EXISTING CONDUITS STUBBED THROUGH FLOOR SERVING ITEMS TO BE REMOVED AND NOT SHOWN
OR REQUIRED TO BE REUSED, SHALL BE CUT OFF FLUSH WITH SLAB LEVEL WITH CONCRETE.
IN ANY AREA REQUIRING THE PERFORMANCE OF ANY TRADE'S WORK WORK, THIS CONTRACTOR SHALL
CAREFULLY REMOVE AND STORE ANY OR ALL ELECTRICAL ITEMS IN PATH OF WORK, REINSTALLING AND
RECONNECTING SAME AS REQUIRED, IN ACCORDANCE WITH THE PLANS AND/OR AS DIRECTED AFTER
COMPLETION OF OTHER TRADE'S WORK IN THAT AREA.
DISCONNECT, MAKE SAFE AND REMOVE ALL TEMPORARY AND ABANDONED WIRE WITHIN THE SPACE.
BRANCH CIRCUIT WIRING TO DEVICES IN AREAS OF DEMOLITION SHALL BE DISCONNECTED, MADE SAFE
AND REMOVED COMPLETELY BACK TO THE PANELBOARD. THE CONTRATOR SHALL NOT ABANDON
BRANCH CIRCUIT WIRING TO ANY AREAS WICH ARE TO REMAIN BUT ARE AFFECTED BY THE DEMOLITION
OR NEW CONSTRUCTION.
DISCONNECT AND REMOVE PANEL, FEEDERS AND BRANCH CIRCUITS BACK TO POINT OF SOURCE
PRIOR TO THE START OF DEMOLITION, CONTRACTOR SHALL FIELD VERIFY ALL BRANCH CIRCUITS AND
MAINTAIN THOSE CIRCUITS THAT EXTEND OUTSIDE OF THE SCOPE OF WORK.
AFTER RENOVATING EXISTING ELECTRICAL WORK, THE CONTRACTOR SHALL INSURE THAT ALL
REMAINING AND NEW EQUIPMENT WILL OPERATE PROPERLY.
PROVIDE TEMPORARY HEAT DETECTORS IN AREAS WHERE SPRINKLERS ARE REMOVED FROM SERVICE
DURING CONSTRUCTION. COORDINATE WITH FIRE PROTECTION CONTRACTOR.
GENERAL DEMOLITION NOTES:(APPLY TO ALL DRAWINGS):
A.
B.
C.
D.
E.
F.
G.
H.
I.
SLEEVE AND SEAL ALL WALL AND FLOOR PENETRATIONS. PROVIDE FIRESTOPPING FOR ALL
FIRE-RATED PENETRATIONS. UTILIZE REMOVABLE FIRESTOPPING MATERIAL AT CABLE TRAY
PENETRATIONS. PROVIDE ACOUSTICAL SEALANT FOR ALL NON RATED PENETRATIONS.
ALL FIRE RATINGS SHALL BE MAINTAINED.
MAINTAIN SERVICE CLEARANCES OF ALL EQUIPMENT.
COORDINATE EXACT LOCATION OF ALL CONDUIT ROUTES, EQUIPMENT AND DEVICES WITH
EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
MINIMUM CONDUIT SIZE SHALL BE 3/4" FOR POWER CIRCUITS UOI.
PROVIDE NYLON PULLSTRING IN ALL EMPTY CONDUITS.
FIRE ALARM SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS
NOT LESS THAN 80 INCHES AND NOT GREATER THAN 96 INCHES ABOVE THE FINISHED FLOOR.
CIRCUITING TO DEVICES/EQUIPMENT SHALL BE 2-#12AWG & 1-#12EG (MULTIPLE HOME RUNS
IN SAME CONDUIT MAY SHARE SAME EQUIPMENT GROUND) FOR EACH 20 AMPERE CIRCUIT
UNLESS OTHERWISE NOTED. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRALS (CIRCUITS
SHALL NOT SHARE NEUTRALS).
PROVIDE CONDUIT/WIRING (CIRCUITING) AND REQUIRED EQUIPMENT CONNECTIONS TO ALL
DEVICES/EQUIPMENT. CONNECT TO CIRCUIT(S) AS INDICATED.
ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE REFERENCE STANDARD
EDITION OF NFPA CODES, AS CITED BY THE FIRE CODE OF NEW YORK STATE, BUILDING
CODE OF NEW YORK STATE AND CORNELL UNIVERSITY DESIGN STANDARDS.
ALL CONDUITS AND SUPPORTS SHALL BE AS TIGHT TO DECK AS POSSIBLE.
PROVIDE PULLBOX FOR EVERY 180 DEGREE OF BENDS FOR TEL/DATA AND 360 DEGREES
OF BENDS FOR POWER CONDUITS.
ALL ELECTRICAL DEVICES (RECEPTACLES, SWITCHES, FIRE ALARM, ETC.) SHALL BE
ALIGNED HORIZONTALLY AND VERTICALLY. CONTRACTOR TO SCHEDULE AND COORDINATE
PROJJECT WALKTHROUGH WITH ARCHITECT AND ENGINEER PRIOR TO COMMENCEMENT OF
ANY DEVICE ROUGH-IN FOR FINALIZATION OF ALIGNMENTS.
ALL EXISTING DEVICES CIRCUITED TO PANELS BEING RENAMED SHALL BE PROVIDED WITH
UPDATED LABELS.
PROVIDE ALL PATHWAYS AND BACK BOXES AS CALLED FOR ON AV DRAWINGS PROVIDED BY
ANOTHER CONSULTANT.
COORDINATE IT SERVICE CHANGES OR DISRUPTIONS IN SERVICE WITH CIT OPERATIONS AT
(607)255-5500.
GENERAL NOTES:(APPLY TO ALL DRAWINGS):
A.
B.
C.
D.
E.
F.
J.
K.
L.
M.
N.
J.
K.
L.
M.
N.
FCU FAN COIL UNIT
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
CONT.CONTACTOR
F.A.T.C.
F.A.C.P.
ELECTRIC WATER COOLER
DISTRIBUTION PANEL
GROUND FAULT CIRCUIT INTERRUPTER
GENERAL CONTRACTOR
ELECTRICAL CONTRACTOR
HEATING, VENTILATING AND AIR CONDITIONING
F.A.FIRE ALARM
H.V.A.C.
G.C.
E.C.
BSMT.BASEMENT
CLG.
EA.
CONTR.
GEN.
CEILING
EACH
GENERATOR
A.AMPERE
DN.
EXIST.
AUTO.
DOWN
EXISTING
AUTOMATIC
DP
EMERG.
ELEC.
G.F.C.I.
ELECTRIC
EMERGENCY
HORSEPOWER
GALVANIZED RIGID STEEL
GND.GROUND
GRS.
ABBREV.
ABBREVIATIONS
C
BKR.
HP.
CAMERA
BREAKER
DESCRIPTION
FZ (3)FIRE ZONE (3)
ABOVE FINISHED FLOORA.F.F.
EM.EMERGENCY
CONTRACTOR
A.F.G. ABOVE FINISHED GRADE
EWC
MOUNTED UNDER COUNTER HEIGHT
TV TELEVISION
WEATHERPROOF
REFRIGERATOR
SPECIFICATION
MOUNTED OVER COUNTER HEIGHT
PLUMBING CONTRACTOR
TELEPHONE BACKBOARD
TELEPHONE TERMINAL CABINET
T.B.B.
MICRO
T.T.C.
MICROWAVE
P.C.
REFRIG.
TYP.TYPICAL
SPEC.
P.
SP.SPACE
POLE
NL NIGHT LIGHT
V.VOLT
SW. SWITCH
MAIN CIRCUIT BREAKER
MAIN LUG ONLY
P = POLE A = AMPERE
UNDERWRITER'S LABORATORY
LTG.
U.L.
4 W.
KW.
LIGHTING
KILOWATT
WIRE
M.L.O.
3P.15A.
PH.
M.C.B.
PHASE
PNL.PANEL
PV POWER VENTILATOR
WP
OC
UC
UV
WG
VP
EF
EHP
CUH
UNIT VENTILATOR
WIRE GUARD
FRACTIONAL HORSEPOWER
EXHAUST FAN
CABINET UNIT HEATER
VANDAL PROOF POLYCARBONATE GUARD
ABBREVIATIONS
ABBREV. DESCRIPTION
WAP WIRELESS ACCESS POINT
O.
UH UNIT HEATER
P.
O.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
GENERAL NOTES & SYMBOLS
LIST
E-000
TGBCPABCDEFBFBFB FB
FBFB
F
F
F F
F
F
F
F
F
F
J DHDHG
F8
F
E
D
C
B
A
1 2 4 5 6 7
G5
H5 X1 K
11
10
9
8
12
13
14
X
LOUNGE
568
DATA CLOSET
552
ELEC. CLOSET
50075
CORRIDOR
50044
Room
571
Room
572
Room
574
Room
576
Room
578
STAIR# 3
50003
GRAD.
STUDENTS
596
GRAD.
STUDENTS
594
STAFF
592
STAFF
590
ASSOC.
DIRECTOR
588
LIBRARY
586
CLERICAL
584
DIRECTOR
582
GRAD.
STUDENTS
580
STAIR# 2
50002
SHOP
501
Room
503
Room
500
Room
502
Room
504
Room
504A
Room
50073
WOMEN
50021
Room
50063
Room
50062
Room
50061
MEN
50022
Room
50076
Room
508
Room
512
Room
514
Room
514B
Room
516
Room
518
Room
520
Room
517
Room
519
Room
521
Room
521A
Room
523
CORRIDOR
50044
(E)LP-5(1)
(E)LP-5(2)
(E)UP-5A
(E)UP-5B
(E)DP-5AC1
(E)DP-CC1
(E)UP-5E
(E) DATA
RACKS
(E) (E)T TT(E)
(E)
(E)
(E)(E)
(E)
(E)
1
1 1
1
1
1
1 1
1 1
(E)
(E)
(E)
(E)
(E)
VAV
2
3
E-202 GENERAL NOTES:
A. EXISTING CABLE TRAY IN LABORATORY MAY NEED TO BE REMOVED AND RELOCATED DEPENDING ON EXISTING
HEIGHT. CABLE TRAY SHALL BE LOCATED BETWEEN 9'-0" & 9'6". THIS SHALL BE ASSESSED IN FIELD BETWEEN
CONTRACTOR AND ARCHITECT IF CAN BE RELOCATED OR PROVIDE NEW.
B. ANY EXISTING CABLE TRAY NOT SHOWN IN LABORATORY SHALL BE DISCONNECTED AND REMOVED.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
PARTIAL FIFTH FLOOR PLAN -
POWER & SPECIAL SYSTEMS
DEMOLITION
E-100
1/8" = 1'-0"
1 PARTIAL FIFTH FLOOR PLAN - POWER & SPECIAL SYSTEMS DEMOLITION
E-100 DEMOLITION NOTES
1 DEMOLISH AND REMOVE ALL EXISTING ELECTRICAL, FIRE ALARM, AND SPECIAL SYSTEMS
DEVICES IN THIS AREA. ALL DEVICES MAY NOT BE SHOWN ON PLANS. ALL CIRCUITS IN
THESE SPACES SHALL BE DEMOLISHED BACK TO SOURCE AND BE PREPARED TO BE
REUSED IN THE NEW PHASE OF THIS PROJECT.
2 REMOVE AND SALVAGE DOOR HOLDS FOR REUSE IN PROJECT. SALVAGE WIRE FOR
REUSE IN NEW WORK PHASE.
3 DEMOLISH AND REMOVE ALL EXISTING CABLING UNDERNEATH RAISED FLOOR IN THIS
ROOM.
.
G
F8
F
E
D
C
B
A
1 2 4 5 6 7
G5
H5
X1
K
11
10
9
8
12
13
14
X
LOUNGE
568
DATA CLOSET
552
ELEC. CLOSET
50075
CORRIDOR
50044
Room
571
Room
572
Room
574
Room
576
Room
578
STAIR# 3
50003
GRAD.
STUDENTS
596
GRAD.
STUDENTS
594
STAFF
592
STAFF
590
ASSOC.
DIRECTOR
588
LIBRARY
586
CLERICAL
584
DIRECTOR
582
GRAD.
STUDENTS
580
STAIR# 2
50002
SHOP
501
Room
503
Room
500
Room
502
Room
504
Room
504A
Room
50073
WOMEN
50021
Room
50063
Room
50062
Room
50061
MEN
50022
Room
50076
Room
508
Room
512
Room
514
Room
514B
Room
516
Room
518
Room
520
Room
517
Room
519
Room
521
Room
521A
Room
523
CORRIDOR
50044
(E) (E)(E)(E)(E)(E)(E)(E)(E)(E)(E)
(E)
(E)
(E)
(E)
(E)
(E)
E-101 GENERAL NOTES:
A. DISCONNECT AND REMOVE ALL EXISTING LIGHTING BACK TO SOURCE OR NEAREST EXISTING TO REMAIN JUNCTION
BOX. SALVAGE CIRCUIT FOR REUSE AND EXTENSION.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
PARTIAL FIFTH FLOOR PLAN -
LIGHTING DEMOLITION
E-101
1/8" = 1'-0"
1
PARTIAL FIFTH FLOOR PLAN - LIGHTING DEMOLITION
CR CR CR
CR CR CR CR
CRCRCRCR
CR CR CR CR
CRCRCRCR
CRCR
CRCR
J
J
J
J
J
M
M
G
F8
F
E
D
C
B
A
1 2 4 5 6 7
G5
H5
X1 K
11
10
9
8
12
13
14
X
Room
571
GRAD.
STUDENTS
596
GRAD.
STUDENTS
594
STAFF
592
STAFF
590
ASSOC.
DIRECTOR
588
LIBRARY
586
CLERICAL
584
DIRECTOR
582
GRAD.
STUDENTS
580
Room
578
Room
576
Room
574
Room
572
LABORATORY
551
STAIR# 3
50003
LABORATORY
551
Room
50073
WOMEN
50021
Room
50063
Room
50062
Room
50061
DATA CLOSET
552
LOUNGE
568
ELEC. CLOSET
50075
MEN
50022
Room
50076
CORRIDOR
50044
CORRIDOR
50044
Room
523
Room
521A
Room
520
Room
521
Room
519
Room
517
Room
518
Room
516
Room
512
Room
514
Room
514B
Room
504A
Room
508
STAIR# 2
50002
Room
500
SHOP
501
Room
503
Room
502
Room
504
(E)LP-5(1)
(E)LP-5(2)
(E)DP-5AC1
(E)DP-CC1
(E)UP-5A
(E)UP-5B
(E)UP-5ET TT(E)
(E)
(E)
(E)(E)
(E)
1
1
1
(E)
GFI
OC
GFI
1
351
2
3
3
3
4
4 4
28
5
50 47 6
7
8
910
11
12
35
12
12
39
14
16 17
15 30
18 19 32 34
20 21 36 38
22 23 40 42
24 25 44 46
27 26 48
VAV
VAV
29
29
GFI12
2 TUP-5LAB
NTX-45-5
GFIGFI
5
5
3133 41
43
45
49
54
3
37
41
45
47
67
54
51
3
4
4
4
4
4
4
4
4
(E)
VAV
55
57
5
5
12
OC
GFI
69
67
65
63
71 71
OC
GFI
OC
GFI
DOOR OPERATOR
DOOR OPERATOR
6
6
UP-5LAB
66
UP-5LAB
66
13
53
E-200 GENERAL NOTES:
A. ALL CIRCUITING SHOWN IN THIS LAB SPACE SHALL BE FED FROM PANEL UP-5LAB.
B. CORD REEL SHALL BE FED FROM A JUNCTION BOX BY 15' OF SO CABLE. POWER CONNECTION TO JUNCTION BOX
SHALL BE FED BY EMT FROM SOURCE PANEL.
C. ALL GFI RECEPTACLES NEAR SINKS SHALL BE GASKETED GFI RATED FOR WASHDOWN APPLICATIONS.
D. CONTRACTOR SHALL COORDINATE WITH END USER FOR CEILING HOOK LOCATIONS TO MOUNT CORD REEL.
E. CONTRACTOR SHALL PROVIDE KINDORF WITH RACK FOR CORD REEL PERMANENT LOCATION WHEN NOT IN USE
ABOVE CEILING. THIS LOCATION SHALL BE COORDINATED IN FIELD AROUND OTHER CONTRACTORS SCOPE AND BE
COORDINATED WITH END USER AND ARCHITECT SO THAT IT IS IN AN EASILY ACCESSIBLE LOCATION.
F. DISCONNECT AND RECONNECT VAV AS NECESSARY. CONFIRM WITH MECHANICAL CONTRACTOR FOR EXACT
LOCATIONS.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
PARTIAL FIFTH FLOOR PLAN -
POWER NEW WORK
E-200
1/8" = 1'-0"
1 PARTIAL FIFTH FLOOR PLAN - POWER NEW WORK
E-200 DRAWING NOTES
1 DEDICATED RECEPTACLE SHALL BE MOUNTED UNDERCOUNTER ON A DEDICATED CIRCUIT TO SERVE THE DRAIN
PUMP THAT WILL BE INSTALLED UNDERNEATH SINK.
2 RECEPTACLE SHALL BE MOUNTED IN ABOVE COUNTER CABINETS THAT WILL FEED UNDERCABINET LIGHTING.
RECEPTACLE SHALL BE TIED INTO RECEPTACLE CIRCUIT #12.
3 WIREMOLD THAT SHALL FEED THESE (2) RECEPTACLES SHALL RUN ALONG WALL INTO AND BEHIND THE CABINET.
RECEPTACLES SHALL BE FLUSH MOUNTED TO SIDE OF CABINET.
4 RECEPTACLES SHALL BE FED FROM 2 CHANNEL ANODIZED CLEAR FINISH WIREMOLD. RECEPTACLES SHALL BE
MOUNTED AT 36" AFF.
5 JUNCTION BOX SHALL FEED (3) LAB VALVE BOXES. 20A-1P CIRCUIT SHALL FEED THEM, CIRCUIT NUMBER AS
INDICATED. FINAL JUNCTION BOX LOCATION SHALL BE DETERMINED IN FIELD. FIELD COORDINATE WITH
MECHANICAL CONTRACTOR.
6 PROVIDE WIRING IN 3/4" CONDUIT PER MANUFACTURER REQUIREMENTS.
3a,b,cD3a,bD4
c,dD
OS
OS
OSOS
OS OS
OS OS
OS OS
OS
OS
OS
OS
DS
DS
DS
DS
M
M
OS
G
F8
F
E
D
C
B
A
1 2 4 5 6 7
G5
H5
X1
K
11
10
9
8
12
13
14
X
Room
571
GRAD.
STUDENTS
596
GRAD.
STUDENTS
594
STAFF
592
STAFF
590
ASSOC.
DIRECTOR
588
LIBRARY
586
CLERICAL
584
DIRECTOR
582
GRAD.
STUDENTS
580
Room
578
Room
576
Room
574
Room
572
LABORATORY
551
STAIR# 3
50003
LABORATORY
551
Room
50073
WOMEN
50021
Room
50063
Room
50062
Room
50061
DATA CLOSET
552
LOUNGE
568
ELEC. CLOSET
50075
MEN
50022
Room
50076
CORRIDOR
50044
CORRIDOR
50044
Room
523
Room
521A
Room
520
Room
521
Room
519
Room
517
Room
518
Room
516
Room
512
Room
514
Room
514B
Room
504A
Room
508
STAIR# 2
50002
Room
500
SHOP
501
Room
503
Room
502
Room
504
A2 A1
A1A1A1
A3 A1 A1 A1
A1A1A1A1
A1 A1 A1 A1
A1A1A1A1
A1 A1 A1 A1
A1A1A1A1
A1 A1 A1 A1
A1
A6A6
A1A1
A1A1
A1
A1 A1
A2A1
A2A1
A1A1
A1
A1
A1
A1
(E) (E) (E) (E) (E) (E) (E) (E) (E) (E) (E)
(E)
(E)
(E)
(E)
(E)
(E)
aaa
a a
aaaa
a a
b b b b
bb
c c c c
cc
c c c c
ccc
d
d
d
dd
d
d d
X1
X1
X1
X1EM EM EM
EM
EM
A4
A4
A4
A4
A4
A4 A4 A4 A4 A4
A4
X1
X1
X1
EM/NL
EM/NL
EM/NL
EM/NL
EM/NL
EM/NL
EM/NL
EM/NL
(E)UP-5E
(E)LP-5(1)
(E)LP-5(2)
(E)UP-5A
(E)UP-5B
(E)DP-5AC1
(E)DP-CC1
(E)
(E)
(E)
A5
A4
a
b
c
d
X1
X1
X1
DAYLIGHT SENSOR
ZONE a
DAYLIGHT SENSOR
ZONE b
DAYLIGHT SENSOR
ZONE c
DAYLIGHT SENSOR
ZONE d
UP-5LAB
A7
A7
d
d
a
a
b
c
d
E-201 GENERAL NOTES:
A. CONNECT ALL NEW EXIT SIGNS IN EXISTING EXIT SIGN CIRCUITS. REWORK AND EXTEND CIRCUITING AS REQUIRED.
CONNECT ALL NEW LIGHTING IN EXISTING CIRCUITS MADE SPARE DURING DEMOLITION. REWORK AND EXTEND
CIRCUITING AS REQUIRED.
B. ALL EM/NL LIGHT FIXTURES SHALL HAVE UL924 RELAY INSTALLED TO CONTROL THE LIFE SAFETY LIGHTING.
C. ALL LIGHT FIXTURE STEM MOUNTING SHALL BE FIELD COORDINATED. ELECTRICAL CONTRACTOR MAY HAVE TO
CROSS-BRACE FIXTURES AROUND DUCT WORK AND OTHER UTILITIES.
D. OCCUPANCY SENSOR IN LOUNGE SHALL CONTROL THE VAV SYSTEM. REFER TO ARCHITECT AND OWNER IF THEY
SHALL ALSO LIKE IT TIED INTO THE EXISTING LIGHTS.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
PARTIAL FIFTH FLOOR PLAN -
LIGHTING NEW WORK
E-201
1/8" = 1'-0"
1 PARTIAL FIFTH FLOOR PLAN - LIGHTING NEW WORK
TGBCPABCDEWAP
WAP
WAP
CR CRCRDC
DC
DC
G
F8
F
E
D
C
B
A
1 2 4 5 6 7
G5
H5
X1
K
11
10
9
8
12
13
14
X
Room
571
GRAD.
STUDENTS
596
GRAD.
STUDENTS
594
STAFF
592
STAFF
590
ASSOC.
DIRECTOR
588
LIBRARY
586
CLERICAL
584
DIRECTOR
582
GRAD.
STUDENTS
580
Room
578
Room
576
Room
574
Room
572
LABORATORY
551
STAIR# 3
50003
LABORATORY
551
Room
50073
WOMEN
50021
Room
50063
Room
50062
Room
50061
DATA CLOSET
552
LOUNGE
568
ELEC. CLOSET
50075
MEN
50022
Room
50076
CORRIDOR
50044
CORRIDOR
50044
Room
523
Room
521A
Room
520
Room
521
Room
519
Room
517
Room
518
Room
516
Room
512
Room
514
Room
514B
Room
504A
Room
508
STAIR# 2
50002
Room
500
SHOP
501
Room
503
Room
502
Room
504
(E)
(E)
(E)
1
1 1
1
1
1
1
1
2
E-202 GENERAL NOTES:
A. TIE CARD READER INTO NEAREST EXISTING RECEPTACLE CIRCUIT.
B. NEW CABLE TRAY SHALL BE 12" WIDE.
C. PROVIDE (3)20A-1P CIRCUIT FOR DOOR HARDWARE CONTROLS FROM PANEL UP-5LAB.
D. EXISTING CABLE TRAY IN LABORATORY MAY NEED TO BE REMOVED AND RELOCATED DEPENDING ON EXISTING
HEIGHT. CABLE TRAY SHALL BE LOCATED BETWEEN 9'-0" & 9'6".
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
PARTIAL FIFTH FLOOR PLAN -
SPECIAL SYSTEMS NEW WORK
E-202
1/8" = 1'-0"
1 PARTIAL 5TH FLOOR PLAN - SPECIAL SYSTEMS
E-202 DRAWING NOTES
1 THE 2 CHANNEL WIREMOLD SHALL HAVE 6 DATA PORTS ABOVE THE RECEPTACLES.
2 (1) TELEPHONE CONNECTION FOR AN EMERGENCY PHONE. REFER TO ARCHITECT
DRAWINGS FOR FINAL EM PHONE LOCATION.
S
S
S
S
S S
S
F
F
F
F
F
F
F
S DHDHF
S
S
S S
S
SD SDDSD DSD
RTS RTS
SD
SD
DSD
DSD
RTS
RTS
G
F8
F
E
D
C
B
A
1 2 4 5 6 7
G5
H5
X1
K
11
10
9
8
12
13
14
X
Room
571
GRAD.
STUDENTS
596
GRAD.
STUDENTS
594
STAFF
592
STAFF
590
ASSOC.
DIRECTOR
588
LIBRARY
586
CLERICAL
584
DIRECTOR
582
GRAD.
STUDENTS
580
Room
578
Room
576
Room
574
Room
572
LABORATORY
551
STAIR# 3
50003
LABORATORY
551
Room
50073
WOMEN
50021
Room
50063
Room
50062
Room
50061
DATA CLOSET
552
LOUNGE
568
ELEC. CLOSET
50075
MEN
50022
Room
50076
CORRIDOR
50044
CORRIDOR
50044
Room
523
Room
521A
Room
520
Room
521
Room
519
Room
517
Room
518
Room
516
Room
512
Room
514
Room
514B
Room
504A
Room
508
STAIR# 2
50002
Room
500
SHOP
501
Room
503
Room
502
Room
504
(E)
1
UP-5LAB
62
UP-5LAB
62
UP-5LAB
64
UP-5LAB
64
E-203 GENERAL NOTES:
A.PROVIDE TEMPORARY HEAT DETECTORS IN AREAS WHERE SPRINKLERS ARE REMOVED FROM SERVICE
DURING CONSTRUCTION. COORDINATE WITH FIRE PROTECTION CONTRACTOR.
B.CONTRACTOR SHALL VERIFY WITH FA DISTRIBUTER THAT INITIATING ZONES AND NOTIFICATION ZONES HAVE
ENOUGH CAPACITY TO ADD THE PROPOSED SMOKE AND NOTIFICATION DEVICES.
C.PROVIDE 20A/1P CIRCUIT THAT SHALL FEED SMOKE DAMPERS.
D.ALL FIRE ALARM SPEAKERS AND STROBES SHALL BE IN SYNC.
E.ALL SMOKE DETECTORS WITHIN THE CORRIDORS SHALL BE ADDED TO ZONE 65 WHICH IS "SMOKE DETECTORS
CORRIDOR SMOKE DOORS".
F.FOR THE SMOKE DETECTORS IN RM 551, THESE SHALL BE ADDED TO ZONE 66 WHICH IS "SMOKE DETECTOR ROOM
586". THE DIRECTORY SHALL BE UPDATED TO SHOW ZONE 66 AS ROOM 586 AND 551.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
PARTIAL FIFTH FLOOR PLAN -
FIRE ALARM NEW WORK
E-203
1/8" = 1'-0"
1 PARTIAL 5TH FLOOR PLAN - FIRE ALARM
E-203 DRAWING NOTES
1 DOOR HOLD OPEN SHALL BE TIED INTO THE FIRE ALARM SYSTEM. CONTRACTOR SHALL REUSE EXISTING DOOR
HOLDERS AT THIS LOCATION THAT WERE REMOVED IN DEMOLITION PHASE.
M M
M
M
M
ASDASDSD
SD
DSD
DSD
RTS
RTS
80064
80061809
807
801
801A
803
803A
805
80046 80047
802
811
80062
804
80060
G
F8
F
E
D
C
B
A
1 2 4 5 6 7
G5
H5
X1
K
11
10
9
8
12
13
14
X
(E)UP-P
(E)LP-P
(E)EUP-P(1)
(E)ELP-P
(E)EUP-P(2)T
UP-P2
NEW 30 CKT 60A PANEL
P-18 P-19
ACS-8
P-20
P-21
P-20
ACS-8
1
NTX-15-P
2
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
PENTHOUSE ELECTRICAL -NEW
WORK
E-204
1/8" = 1'-0"
1 PENTHOUSE - ELECTRICAL NEW WORK
E-204 DRAWING NOTES
1 RECEPTACLE SHALL BE FED FROM PANEL UP-P2 NEXT AVAILABLE 20A/1P CIRCUIT. RECEPTACLE SHALL BE MOUNTED ON
UNIT OR CLOSE ENOUGH THAT PUMP CAN BE CONNECTED. CONTRACTOR SHALL DETERMINE FINAL LOCATION IN FIELD.
2 SMOKE DAMPER SHALL BE FED FROM PANEL UP-P2 NEXT AVAILABLE 20A/1P CIRCUIT
PANEL NUMBER
BRANCH BREAKER
NUMBER
4LN3B-17 DYMO LABEL, VERIFY
COLOR WITH OWNER,
ADHERE TO COVERPLATE
USING CONTACT CEMENT.
FACTORY ADHESIVE
WILL NOT BE
SUFFICIENT. ACTUAL
CIRCUIT INFORMATION
SHALL BE AS INSTALLED
AND NOT NECESSARILY
THE SAME CIRCUIT
NUMBER AS SHOWH ON
THE PLANS.
GROUNDING PIN ON TOP
OR TO LEFT OF OUTLET ON
HORIZONTALLY MOUNTED
RECEPTACLES
4LN3B-17
PROVIDE GREEN GROUND WIRE IN ALL RECEPTACLE CIRCUITS.
CONNECT TO GROUND BUS IN PANEL.
DO NOT INSTALL RECEPTACLES, COMPUTER OR TELEPHONE
OUTLETS BACK TO BACK. INSTALL IN ADJACENT STUD CAVITIES,
TO REDUCE SOUND TRANSMISSION.
TYPICAL
DETAIL NOTES:
A.
B.
EQUIPMENT: "INSERT DESIGNATION"
POWER SOURCE: "INSERT SOURCE"
TYPE SUPPLY: INSERT-NORMAL, OR
CRITICAL OPERATION POWER, OR OPTIONAL
STANDBY, OR LEGALLY REQUIRED, OR LIFE
SAFETY EMERGENCY AS APPLICABLE"
VOLTAGE: "INSERT APPLICABLE
VOLTAGE-208/120V OR 480/277V, ETC."
CONDUCTOR COLOR CODING:
PHASE A - "BLACK OR BROWN"
PHASE B - "RED OR ORANGE"
PHASE C - "BLUE OR YELLOW"
NEUTRAL - "WHITE OR GRAY"
GROUND - GREEN
AVAILABLE SHORT CIRCUIT CURRENT:
"INSERT AMPS RMS"
PROVIDE CUSTOM NAMEPLATE AS INDICATED FOR ALL PANELBOARDS, MCC'S,
SWITCHBOARDS, SWITCHGEAR, TRANSFER SWITCHES, GENERATORS ETC.
NAMEPLATE SHALL BE ENGRAVED (WHITE LETTERING, BLACK BACKGROUND) AND
ATTACHED TO THE EQUIPMENT WITH SCREWS. LETTERING SHALL BE 1/4" HIGH
WITH SPACE BETWEEN LINES 1/8" MINIMUM. MINIMUM SHALL BE 8"H x 8"W.
PROVIDE SAMPLE NAMEPLATE FOR REVIEW.
THE AVAILABLE SHORT CIRCUIT SHOULD BE PROVIDED AT THE SERVICE ENTRANCE.
2.
1.
DETAIL NOTES:
3.
4.
LOAD
CEILING
SENSOR
120/277V SWITCH
DETAIL NOTES:
PROVIDE ADDITIONAL SENSORS AS INDICATED ON THE PLANS AND AS RECOMMENDED BY THE
MANUFACTURERS.
PROVIDE INDICATED SWITCHING.
CONTROL
OUTPUT
COMMON
+24 VDC
SWITCH PACKNEUTRAL
LINE
2
1
2
1
SEQUENCE OF OPERATION
ROOM UNOCCUPIED: LIGHTING TO BE OFF AFTER TIME DELAY FROM LAST MOTION SENSING.
ROOM OCCUPIED: UPON SENSING OF MOTION IN THE SPACE, THE SENSOR SHALL ENABLE THE SWITCH PACK TO
ENERGIZE THE LIGHTING (LOAD). LIGHTING SHALL REMAIN ENERGIZED UNTIL MOTION IS NOT SENSED (INITIATE
TIME DELAY, SET FOR 30 MINUTES).
1.
2.
POWER PANEL
(SUPPLY)
CONTROL
TRANSFORMER
HC
MOTOR
CONNECTION
(EQUIPMENT)
COMBINATION MAGNETIC
STARTER/DISCONNECT
SWITCH (CONTROL UNIT)
FIRE ALARM
SYSTEM
WIRING
CONTROL WIRING
PROVIDED UNDER
MECHANICAL WORK
OL
OL
OL
HC
H
O
A
OL
POWER WIRING AND CONNECTIONS PROVIDED UNDER ELECTRICAL WORK.
MOTOR STARTER FURNISHED AND INSTALLED UNDER ELECTRICAL WORK
CONTROL DEVICES FURNISHED AND INSTALLED UNDER ELECTRICAL WORK.
DISCONNECT SWITCH PROVIDED UNDER ELECTRICAL WORK.
BOND EQUIPMENT GROUND CONDUCTOR TO ENCLOSURE.
BOND EQUIPMENT GROUND CONDUCTOR TO MOTOR FRAME.
LOCAL DISCONNECT
SWITCH (WHERE
INDICATED)3
4
5
111
M
DETAIL NOTES:
2
1
3
4
5
6
3/4" BOLT THRU
WALL (TYP)
4" X 1/2" FLAT
STOCK (TYP)ANGLE BRACE
(TYP)
ALL CHANNEL
FRAME PLATFORM
TOP VIEW
SIDE VIEW
WELD ENTIRE ASSEMBLY TO MATCH TRANSFORMER BASE.
PROVIDE VIBRATION ISOLATORS BETWEEN TRANSFORMER BASE AND SUPPORT.
MAXIMUM 30 KVA SIZE TRANSFORMER.
DETAIL NOTES:
A.
B.
C.
20' CORD REEL
#12/3 CORD
WIRE MESH CORD GRIP,
HUBBELL 074010 TYPE
UTILITY BOX
AND COVER.
HARDWIRED CONNECTION
TO CORD REEL.
15' SO CABLE
PROVIDE CHANNEL OR
ANGLE SUPPORT STEEL
MOUNTED TO BUILDING
STRUCTURE
BOX WITH 20A
DOUBLE DUPLEX RECEPTACLE
LOCATED 8'-0" FROM
FLOOR
HARD MOUNTED. REFER TO
OWNER/ARCH FOR FINAL
REEL LOCATION.
DETAIL NOTES:
ACCESS CONTROL SYSTEM COMPOSITE CABLE ROUTED TO LOCAL DATA ROOM VIA CABLE TRAY
SYSTEM.
8"x8"x4" ACCESS CONTROL SYSTEM JUNCTION BOX MOUNTED ABOVE ACCESSIBLE CEILING
SYSTEM ON SECURE SIDE OF DOOR.
LEAVE 20FT. OF ACCESS CONTROL SYSTEM COMPOSITE CABLE COILED AT BOX LOCATION FOR
CONNECTION TO DOOR DEVICES.
NOT USED.
3/4" RACEWAY FROM JUNCTION BOX TO DOOR FRAME FOR DOOR CONTACT, REQUEST-TO-EXIT
DEVICE WIRING.
DOOR CONTACT.
ELECTRIC LATCH, LOCKING HARDWARE.
3/4" RACEWAY FROM JUNCTION BOX TO CARD READER.
CARD READER - MOUNTED ON DOOR SILE.
120 VOLT POWER SOURCE FROM LOCAL EMERGENCY POWER PANELBOARD.
ACCESS CONTROL SYSTEM COMPOSITE CABLE SHALL BE: PAIGE ELECTRONIC WIRE AND CABLE
#454932AYW OR APPROVED EQUAL.
1 11
10
3 2
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
10
11
DETAIL NOTES:
ACCESS CONTROL SYSTEM COMPOSITE CABLE ROUTED TO LOCAL DATA ROOM
VIA CABLE TRAY SYSTEM.
8"x8"x4" ACCESS CONTROL SYSTEM JUNCTION BOX MOUNTED ABOVE ACCESSIBLE
CEILING SYSTEM ON SECURE SIDE OF DOOR.
LEAVE 20FT. OF ACCESS CONTROL SYSTEM COMPOSITE CABLE COILED AT BOX
LOCATION FOR CONNECTION TO DOOR DEVICES.
NOT USED.
3/4" RACEWAY FROM JUNCTION BOX TO DOOR FRAME FOR DOOR CONTACT,
REQUEST-TO-EXIT DEVICE WIRING.
DOOR CONTACT.
ELECTRIC LATCH, LOCKING HARDWARE. ELECTRIC STRIKES SHALL AND NOT PART
OF THE HARDWARE.
3/4" RACEWAY FROM JUNCTION BOX TO CARD READER.
CARD READER - MOUNTED ON DOOR SILE.
120 VOLT POWER SOURCE FROM LOCAL EMERGENCY POWER PANELBOARD.
ACCESS CONTROL SYSTEM COMPOSITE CABLE SHALL BE: PAIGE ELECTRONIC
WIRE AND CABLE #454932AYW OR APPROVED EQUAL.
1
2
3
4
5
6
7
8
9
10
11
3
10
1 11
2
8
9
4
5
6
7
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
ELECTRICAL DETAILS
E-400
NTS
1
TYPICAL RECEPTACLE IDENTIFICATION
NTS
2
EQUIPMENT NAMEPLATE DETAIL
NTS
3
CEILING MOUNTED OCCUPANCY SENSOR
NTS
4 TYPICAL THREE PHASE MOTOR CONNECTIION
NTS
5 TRANSFORMER MOUNTING DETAIL - WALL MOUNTED
NTS
6 CORD REEL DETAIL
1/8" = 1'-0"
7 ACCESS CONTROL SYSTEM WIRING - SINGLE DOOR - TYPICAL DETAIL
1/8" = 1'-0"
8 ACCESS CONTROL SYSTEM WIRING - DOUBLE DOOR - TYPICAL DETAIL
EXISTING PANEL LP-P SHALL HAVE 30A-3P BREAKER INSTALLED THAT
WILL FEED NEW PANEL UP-P2. A 15KVA WALL MOUNTED
TRANSFORMER SHALL BE INSTALLED. SEE DRAWING E-202 FOR
LOCATIONS.
DETAIL NOTES:
A.
UP-P2
60A
208/120V
MCB
(E)LP-P
100A
480/277V
MCB
30A
15kVA
60A
B1 DEXISTING
INCOMING
BOTH 30A & 60A BREAKERS, TRANSFORMER, PANEL UP-P2, AND ALL
ASSOCIATED WIRING IS NEW.
REFER TO DRAWING E-204 FOR TRANSFORMER AND PANEL
LOCATION.
B.
NTX-15-P
REFERENCE NOTES:
1.COORDINATE WITH ARCHITECT FOR FIXTURE COLOR.
2.COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR
EXACT CEILING TYPES FOR MOUNTING TYPE AND TRIM REQUIRED.
EXISTING PANEL DP-CC51 SHALL HAVE 70A-3P BREAKER INSTALLED
THAT WILL FEED NEW PANEL UP-5LAB. A 45KVA FLOOR MOUNTED
TRANSFORMER SHALL BE INSTALLED. SEE DRAWING E-200 FOR
LOCATIONS.
DETAIL NOTES:
A.
UP-5LAB
175A
208/120V
MCB
(E)DP-CC51
400A
480/277V
MLO
70A
45kVA
175A
E1 IEXISTING
INCOMING
BOTH 70A & 175A BREAKERS, TRANSFORMER, PANEL UP-5LAB, AND
ALL ASSOCIATED WIRING IS NEW.
REFER TO DRAWING E-200 FOR TRANSFORMER AND PANEL
LOCATION.
B.
NTX-45-5
C.
Revisions:
Richard McElhiney Architects LLC
347 West 36 Street Suite 1501
New York, NY 10018
212-245-5195 T
212-239-7130 F
Jacobs
303 South Broadway, Suite G20
Tarrytown NY 10591
914-841-1069 T
M/E Engineering, P.C.
300 Trolley Boulevard
Rochester, NY 14606
585-288-5590 T
Ryan Biggs Clark Davis
257 Ushers Rd
Clifton Park, NY 12065
518-406-5506 T
Delta
860 Hooper Road
Endwell, NY 12065
518-406-5506
Trophy Point
4588 South Park Avenue
Blasdell, New York 14219
716-823-0006 T
Key Plan:
Notes:
Rhodes Hall
Cornell University
Ithaca, NY 14850
December 15, 2020
Scale:
Fifth Floor Renovation
As Indicated
Issue for Bid December 15, 2020
ELECTRICAL SCHEDULES
E-500
NTS
1 ONE LINE DIAGRAM - POWER PENTHOUSE
3. IF IDENTIFICATION ON ONE-LINE DIAGRAM SHOWS CONDUCTORS WELL ABOVE OVER-CURRENT PROTECTION,
VOLTAGE DROP HAS BEEN ACCOUNTED FOR.
2. WHERE MULTIPLE SETS ARE SPECIFIED, PROVIDE THREE (3) PHASE, NEAUTRAL AND GROUND IN EACH
CONDUCTOR. CONDUCTORS AND CONDUITS SHALL BE EQUAL IN LENGTH AND OF SAME MANUFACTURER.
1. CONDUIT SZIES ARE BASED ON TYPE THHN, THWN, THWN-2 CONDUCTORS, AS SHOWN IN TABLE C1 IN
NATIONAL ELECTRICAL CODE
GENERAL NOTES
6000 16 500 (2) 500 CC 3 1/2"CC1 3 1/2"
5000 12 600 (2) 500 BB 3 1/2"BB1 3 1/2"
4000 10 600 500 AA 3 1/2"AA1 3 1/2"
3000 8 500 500 Z 3 1/2"Z1 3 1/2"
2500 6 600 350 Y 3 1/2"Y1 3 1/2"
2000 5 600 250 X 3 1/2"X1 3 1/2"
1600 4 600 4/0 W 3 1/2"W1 3 1/2"
1200 3 600 3/0 V 3 1/2"V1 3 1/2"
1000 2 500 2/0 U 3"U1 3"
800 2 500 1/0 T 3"T1 3"
700 2 500 1/0 S 3"S1 3"
600 2 350 1 R 3"R1 3"
500 2 250 2 Q 2 1/2"Q1 2 1/2"
450 2 4/0 2 P 2 1/2"P1 2 1/2"
400 1 500 2 O 3"O1 3"
350 1 500 2 N 3"N1 3"
300 1 350 4 M 3"M1 3"
250 1 250 4 L 2 1/2"L1 2 1/2"
225 1 4/0 4 K 2 1/2"K1 2 1/2"
200 1 30/6 J 2"J1 2"
175 1 2/0 6 I 2"I1 2"
150 1 1/0 6 H 2"H1 2"
110 1 1 6 G 1 1/2"G1 1 1/2"
100 1 2 8 F 1 1/4"F1 1 1/4"
70 1 4 10 E 1 1/4"E1 1 1/4"
60 1 6 10 D 1"D1 1"
40 1 8 10 C 3/4"C1 3/4"
30 1 10 10 B 3/4"B1 3/4"
20 1 12 12 A 3/4"A1 3/4"
PHASE & NEUT GROUND IDENTIFIER CONDUIT SIZE IDENTIFIER CONDUIT SIZE
OVERCURRENT DEVICE
RATING # SETS WIRE SIZE (PER SET)4 WIRE FEEDERS WITH GROUNDING
CONDUCTOR
3 WIRE FEEDERS WITH GROUNDING
CONDUCTOR
CONDUIT AND COPPER CABLE SCHEDULE
NTS
2 ONE LINE DIAGRAM - POWER 5TH LAB
Notes:
Total Est. Demand:53 A
Total Conn.:65 A
Spare 2500 VA 100.00%2500 VA Total Est. Demand:18950 VA
Receptacle 18900 VA 76.46%14450 VA Total Conn. Load:23400 VA
Power 2000 VA 100.00%2000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:56 A 68 A 74 A
Total Load:6720 VA 7980 VA 8700 VA
83 84
81 82
79 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 80
77 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 78
75 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 76
73 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 74
71 Receptacle 20 A 1 720 VA 0 VA 1 20 A Spare 72
69 Receptacle 20 A 1 360 VA 0 VA 1 20 A Spare 70
67 Receptacle 20 A 1 360 VA 0 VA 1 20 A Spare 68
65 Receptacle 20 A 1 360 VA 0 VA 1 20 A Bathroom Door Power 66
63 Receptacle 20 A 1 360 VA 500 VA 1 20 A Duct Smoke Connection 64
61 Spare 20 A 1 0 VA 500 VA 1 20 A Duct Smoke Connection 62
59 Spare 20 A 1 0 VA 500 VA 1 20 A Door Hardware Controls 60
57 Lab Valve Boxes 20 A 1 500 VA 500 VA 1 20 A Door Hardware Controls 58
55 Lab Valve Boxes 20 A 1 500 VA 500 VA 1 20 A Door Hardware Controls 56
53 Receptacle 20 A 1 360 VA 540 VA 1 20 A Receptacle 54
51 Receptacle 20 A 1 540 VA 0 VA 1 20 A Spare 52
49 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle 50
47 Receptacle 20 A 1 540 VA 180 VA 1 20 A Receptacle 48
45 Receptacle 20 A 1 540 VA 180 VA 1 20 A Receptacle 46
43 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 44
41 Receptacle 20 A 1 540 VA 180 VA 1 20 A Receptacle 42
39 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 40
37 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 38
35 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 36
33 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 34
31 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 32
29 VAV 20 A 1 1000...180 VA 1 20 A Receptacle 30
27 Receptacle 20 A 1 180 VA 360 VA 1 20 A Receptacle 28
25 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 26
23 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 24
21 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 22
19 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 20
17 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 18
15 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 16
13 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 14
11 Receptacle 20 A 1 180 VA 1080... 1 20 A Receptacle 12
9 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle 10
7 Receptacle 20 A 1 540 VA 360 VA 1 20 A Receptacle 8
5 Receptacle 20 A 1 540 VA 540 VA 1 20 A Receptacle 6
3 Receptacle 20 A 1 900 VA 540 VA 1 20 A Receptacle 4
1 Receptacle 20 A 1 180 VA 360 VA 1 20 A Receptacle 2
CKT Circuit Description Trip Poles
A B C A B C
Poles Trip Circuit Description CKT
Notes:
Enclosure:Type 1 MCB Rating:175 A
Mounting:Surface Wires:4 Mains Rating:225 A
Supply From:Phases:3 Mains Type:MCB
Location:Volts:120/208 Wye A.I.C. Rating:22K
Branch Panel: UP-5LAB
ELEC CLOSET 50075
P-21 PUMP PENTHOUSE 1/2 1 208 5.4 UP-P2 15/2 2#12 1#12 3/4"C 2#12 1#12 3/4"C X AU 30A NF AU P-21
P-20 PUMP PENTHOUSE 3 3 208 10.6 UP-P2 30/3 3#12 1#12 EG 3/4"C 3#12 1#12 EG 3/4"C X AU 30A NF AU P-20
P-19 PUMP PENTHOUSE 1/2 1 208 5.4 UP-P2 15/2 2#12 1#12 3/4"C 2#12 1#12 3/4"C X AU 30A NF AU P-19
P-18 PUMP PENTHOUSE 1/2 1 208 5.4 UP-P2 15/2 2#12 1#12 3/4"C 2#12 1#12 3/4"C X AU 30A NF AU P-18
ACS-8 AIR HANDLING UNIT PENTHOUSE 7 1/2 3 480 11.0 ELP-P 30/3 3#12 1#12 3/4"C 3#12 1#12 3/4"C X AU 30A NF AU ACS-8
PHASE GROUND CONDUIT PHASE GROUND CONDUIT
SWITCH
AMPS FUSE SIZE LOC.WEATHER
PROOF
REF.
NOTES
ITEM
ID NAME ROOM LOCATION HP KW PHASE SYSTEM
VOLTS
MCA or
SYSTEM
AMPS
PANEL or
CONTROL
CENTER
CIRCUIT
BREAKER
or "FU" FOR
FUSE
POWER WIRING FROM PANEL TO
CONTROL UNIT
POWER WIRING FROM CONTROL
UNIT TO EQUIPMENT
NEMA SIZE STARTERNEMA TYPEMANUAL MOTOR STARTERMANUAL MOTOR STARTERWITH RELAYMAGNETIC STARTERCOMBINATION MAGNETICSTARTERCOMBINATION REDUCEDVOLTAGE STARTERCOMBINATION STARTERMP/FUSE (F) SIZEADJUSTABLE SPEEDDRIVEADJUSTABLE SPEEDDRIVEWITH BYPASSADJUSTABLE SPEEDDRIVEWITH REDUNDANT ASDPACKAGED CONTROLUNIT FURNISHED BYOTHERSDUPLEX PUMPCONTROLLER BY OTHERSFIRE ALARM FANSHUTDOWN REQUIREDSUPPLY DUCT SMOKEDETECTOR W/ REMOTETEST STATIONRETURN DUCT SMOKEDETECTOR W/ REMOTETEST STATIONEXHAUST DUCT SMOKEDETECTOR W/ REMOTETEST STATIONTHERMOSTATCONNECTIONAQUASTAT CONNECTIONMOTORIZED DAMPERCONNECTIONSTART/STOPPUSHBUTTONSHAND/OFF/AUTOSELECTOR SWITCHCONTROL DEVICELOCATIONSAFETY SWITCH
ITEM
ID
EQUIPMENT POWER SOURCE, PROTECTION & WIRING CONTROL DEVICES AS SHOWN ON THE PLANS BY ITEM DESIGNATION
G. "IU" INDICATES INTEGRAL WITH UNIT.
F. "NF" INDICATES NON-FUSED.
E. "AU" INDICATES CONTROL DEVICES IS LOCATED AT THE UNIT.
D. PROVIDE OVERLOADS, SIZE AS REQUIRED, BY THE DIVISION 22/23 CONTRACTOR.
C. ALL DEVICES SHALL BE SURFACE MOUNTED UNLESS OTHERWISE NOTED.
B. ITEM NUMBER INDICATES EQUIPMENT NUMBER
A. ALL DEVICES PROVIDED BY THE DIVISION 26 CONTRACTOR.
ELECTRIC EQUIPMENT AND CONTROL SCHEDULE
GENERAL NOTES:
X1 EXIT SIGN SIMKAR SLEDARW LED 120/277V 1
A7 2' LINEAR FLUSH MOUNTED FIXTURE COOPER: 2-FSN6-750-L9SCT3 LED 120/277V 1,2
A6 8' LINEAR FLUSH MOUNTED FIXTURE COOPER: 8-FSN6-750-L9SCT3 LED 120/277V 1,2
A5 4" RECESSED DOWNLIGHT GOTHAM LIGHITNG MODEL:
EVO4-35-15-4AR-WD-LSS-MVOLT-TRW-CRI90
LED 120/277V 1,2
A4 2'x2' RECESSED FIXTURE METALUX 22FP LED - 3500K LED 120/277V 1,2
A3 6' LINEAR PENDANT NEO-RAY: S124DP-C795D-9-40-S4-6FO-1-U-DD-A-S LED 120/277V 1,2
A2 4' LINEAR PENDANT NEO-RAY: S124DP-C795D-9-40-S4-4FO-1-U-DD-A-S LED 120/277V 1,2
A1 8' LINEAR PENDANT NEO-RAY: S124DP-C795D-9-40-S4-8FO-1-U-DD-A-S LED 120/277V 1,2
TYPE DESCRIPTION MFR. & CATALOG No.LAMP VOLTAGE/BALLAST REFERENCE NOTES
LUMINAIRE SCHEDULE
DP-CC51
1 30A 3
UP-P2 PENTHOUSE X 208/120 3 4 60A.10k X 1 1 25A 2
2 9 20A 1
3 3 15A 2
30
VOLT PHASE WIRE F S ACTIVE SPARE SPACE
NAME ROOM LOCATION
DIST.BRANCH
CIR.MLO MCB MFS QUANTITY TRIP / FUSE
SIZE-FU POLES
PANEL INFORMATION
TYPE
VOLTAGE RATING BUS
RATING
MAIN AMPERE RATING
KAIC
(RMS
SYM)
MOUNT
BRANCH CIRCUIT DEVICES
TOTAL NO.
OF
CIRCUITS
NOTES
PANELBOARD SCHEDULE