H
DIRECTION OF FLOW
PIPE CAP OR PLUG
PIPING UP
PIPING DOWN
THERMOSTAT
HUMIDISTAT
DOMESTIC COLD WATER (CW)
DOMESTIC HOT WATER (HW)
HOT WATER CIRCULATING (HWC)
WASTE
HOSE BIBB / WALL HYDRANT
BACKFLOW PREVENTER
FLOOR DRAIN
VENT THROUGH ROOF (VTR)
WATER METERM
NOT ALL SYMBOLS LISTED BELOW ARE USED ON THIS SET OF DRAWINGS
SYMBOL DESCRIPTION
PLUMBING LEGEND
CW CW
HW HW
SAN SAN
GYPSUM BOARD
PIPE THRU WALL
PROFORM QUICK-SET FS-90
COMPOUND
INSULATION PER SECTIONS
WOOD STUD
EXTERIOR SIDING
SLOPE
Ø1-1/2" FLOOR DRAIN
SHOWER VALVE
SHOWER HEAD
WASTE PIPE Ø1-1/2"
P-TRAP Ø1-1/2"
Ø3/8" CW & HW
FINISH FLOOR LEVEL
TUB VALVE
3/4" COMBINATION
HW
CW
PANELARRESTOR
HAMMER
LINE
42"
WASTE
WALL BOX
CLOTHES
WASHER
SWEAT CONNECTION
FLOOR
1/2"
1/2"
SWEAT CONNECTION
3/4" COMBINATION
WATER
ACCESS
2"
PROJECT NO.PROJECT:TITLE OF DRAWINGDRAWING NO.
FIRST ISSUE DATE:0ISSUED/REVISIONS:DATE:123456ENGINEER:OWNER/DEVELOPER:112 N. MAIN ST.HORSEHEADS, NY 14845607-377-7990 | WWW.MASER-AE.COM119 S. CAYUGA STREETITHACA, NY 14850327 W. SENECA ST.ITHACA, NEW YORK 14850327 W. SENECA STREETA
5 4 3 2 16
B
C
D
E
A
B
C
D
E
78
5 4 3 2 1678
ISSUED FOR PERMIT08/19/2019REVISED FOR MECH. RM. EQUIP.06/04/20203-STORY, 12-UNIT APARTMENT BUILDINGREVISED FOR CONSTRUCTION06/17/2020DRAWING ALTERATIONIT IS A VIOLATION OF LAW FOR ANYPERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT,ENGINEER, SURVEYOR OR LANDSCAPEARCHITECT TO ALTER ANY ITEM ONTHIS DOCUMENT IN ANY WAY.ANY LICENSEE WHO ALTERS THISDOCUMENT IS REQUIRED BY LAW TOAFFIX THEIR SEAL AND THE NOTATION,"ALTERED BY," FOLLOWED BY THEIRSIGNATURE AND SPECIFICDESCRIPTION OF THE ALTERATIONS.#VISUMDEVELOPMENT GROUPMAY 31, 2019
2019-008
A.GENERAL NOTES:
1.CONFORM TO ALL GENERAL AND SPECIAL CONDITIONS OF CONTRACT AS SPECIFIED BY SITE
ENGINEER'S AND/OR OWNER.
2.VISIT SITE, CHECK FACILITIES AND CONDITIONS AND MAKE ALL NECESSARY OBSERVATIONS AND
MEASUREMENTS. NOTE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED AND TAKE ALL
ITEMS INTO CONSIDERATION IN BID.
3.SYSTEMS ARE TO BE COMPLETE AND WORKABLE IN ALL RESPECTS, PLACED IN OPERATION AND
PROPERLY ADJUSTED.
4.CONTRACTOR SHALL PROVIDE THEIR OWN CLEAN-UP, REMOVAL AND LEGAL DISPOSAL OF ALL
RUBBISH DAILY.
5.CONTRACTOR SHALL PROTECT THEIR WORK, THEIR EXISTING AND ADJACENT PROPERTY AGAINST
WEATHER.
6.CONTRACTOR SHALL PROTECT THEIR WORK, MATERIALS, APPARATUS AND FIXTURES FROM ANY
WORK DAMAGED BY FAILURE TO PROVIDE PROTECTION REQUIRED, SHALL BE REMOVED AND
REPLACED WITH NEW MATERIAL AT THE CONTRACTOR'S EXPENSE.
7.ARRANGE FOR AND OBTAIN OWNER'S AND INSURANCE REPRESENTATIVE'S PERMISSION FOR ANY
SERVICE SHUTDOWNS.
8.THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,
SEQUENCES OF CONSTRUCTION AND THE SAFETY OR WORKMEN.
9.NO PIPING, DUCTWORK, WIRING, ETC. SHALL BE INSTALLED OR ROUTED ABOVE ELECTRICAL PANELS
AND EQUIPMENT.
B.CODES, PERMITS, STANDARDS AND REGULATIONS:
1.CONFORM TO ALL APPLICABLE CODES (LOCAL, STATE, NATIONAL CODES, NFPA, OSHA, ETC.).
GOVERNMENT REGULATIONS, UTILITY COMPANY REQUIREMENTS, AND APPLICABLE STANDARDS.
2.OBTAIN PERMITS AND PAY ALL FEES, ARRANGE FOR ALL REQUIRED INSPECTIONS AND APPROVALS.
C.DRAWINGS:
1.THE SYSTEM AS SHOWN ON PLUMBING DRAWINGS ARE DIAGRAMMATIC. CONFIRM ALL DIMENSIONS
BY FIELD MEASUREMENT.
2.THE EXACT LOCATIONS FOR FIXTURES, EQUIPMENT AND PIPING WHICH IS NOT COVERED BY
DRAWINGS, SHALL BE OBTAINED FROM THE SITE ENGINEER'S OR THEIR REPRESENTATIVE IN THE
FIELD AND THE WORK SHALL BE LAID OUT ACCORDINGLY.
D.BASE EQUIPMENT, MATERIALS AND SUBSTITUTIONS:
1.ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE OF DEFECTS AND U.L. LABELED.
2.BASE BID MANUFACTURERS ARE INCLUDED IN THE SPECIFICATIONS OR LISTED IN THE NAME OR
MAKE OF ANY ARTICLE, DEVICE, MATERIAL, FORM OF CONSTRUCTION, FIXTURE, ETC. STATED IN
THIS SPECIFICATIONS, WHETHER OR NOT THE WORDS "OR APPROVED EQUAL" ARE USED, SHALL BE
KNOWN AS A "STANDARD".
3.ALL PROPOSALS SHALL BE BASED ON "STANDARDS" SPECIFIED.
4.THE EQUIPMENT SCHEDULES ON THE DRAWINGS INDICATE MANUFACTURERS EQUIPMENT MODEL
NUMBERS THAT THIS DESIGN HAS BEEN BASED ON. THE USE OF OTHER MANUFACTURERS
EQUIPMENT THAT IS LISTED AS ACCEPTABLE ALTERNATES AND REFLECTS ANY ADDITIONAL COST
OF SUCH CHANGES SHALL BE PAID BY THE CONTRACTOR.
5.SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL OF THE OWNER. IF A SUBSTITUTION IS SUBMITTED,
IT IS THE CONTRACTOR'S RESPONSIBILITY TO EVALUATE IT AND CERTIFY THAT THE SUBSTITUTION IS
EQUIVALENT IN ALL RESPECTS TO THE BASE SPECIFICATIONS.
6.COORDINATE ALL APPROVED SUBSTITUTIONS. ANY COSTS RESULTING FROM SUBSTITUTION SHALL
BE THE RESPONSIBILITY OF ANY PAID FOR BY THE CONTRACTOR. APPROVED SHOP DRAWINGS DO
NOT ABSOLVE THIS CONTRACTOR FROM THIS RESPONSIBILITY.
E.WARRANTY:
1.FULLY WARRANT ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR (1) YEAR FROM DATE OF
ACCEPTANCE.
2.EXTEND ALL MANUFACTURERS' WARRANTIES TO OWNER.
3.REPAIR OR REPLACE WITHOUT CHARGE TO THE OWNER ALL ITEMS FOUND DEFECTIVE DURING THE
WARRANTY PERIOD. IN THE CASE OF REPLACEMENT OR REPAIR DUE TO FAILURE WITHIN THE
WARRANTY PERIOD, THE WARRANTY ON THAT PORTION OF THE WORK SHALL BE EXTENDED FOR A
MINIMUM PERIOD OF ONE (1) YEAR FROM THE DATE OF SUCH REPLACEMENT OR REPAIR.
F.INSULATION:
1.PLUMBING INSULATION (AS MANUFACTURED BY OWENS CORNING, KNAUF, SCHULLER OR
CERTAINTEED)
2.INSULATE ALL ABOVE GRADE HOT AND COLD WATER PIPING WITH MOLDED FIBER GLASS HAVING AN
ALL SERVICE JACKET.
3.INSULATION THICKNESS SCHEDULE: 1) LESS THAN 2" DIAMETER PIPE: 1" THICK-HW AND 1/2" THICK
CW; 2) 2"-8" DIAMETER PIPE: 1-1/2" THICK.
G.PIPING AND VALVES:
1.LABEL ALL PIPING AND SHOW DIRECTION OF FLOW EVERY 20 FEET ON CENTER.
2.CONNECTIONS TO EQUIPMENT:
2.1.PROVIDE VALVED WATER AND/OR GAS CONNECTION FOR EQUIPMENT.
2.2.INCLUDE ACCESSORIES REQUIRED BY CODE, DRAWING OR MANUFACTURER'S INSTRUCTIONS.
3.FLUSH, VENT AND SANITIZE ALL WATER PIPING WITH CHLORINE AS REQUIRED PER AWWA, LOCAL
BUILDING DEPARTMENT AND HEALTH DEPARTMENT CODES.
4.DOMESTIC HOT AND COLD WATER PIPING UNDER CONCRETE FLOOR TO BE COVERED WITH SAND SO
THAT PIPING WILL NOT BECOME EMBEDDED IN THE FLOOR SLAB.
5.ALL PIPING UNDER CONCRETE FLOOR SHALL BE PEX, CONTINUOUS. NO SPLICES OR FITTINGS WILL
BE ALLOWED. PROVIDE CPVC CONDUITS FOR ALL UNDERSLAB PIPING.
6.EXTREME CAUTION MUST BE TAKEN SO THAT NO COPPER PIPING AND INSULATION UNDER
CONCRETE FLOORS BECOMES CRUSHED, CUT, SPLIT OR DEFORMED DURING THE POURING OF THE
FLOOR SLAB.
7.ALL PIPING UNDER CONCRETE FLOORS SHALL BE COVERED INSIDE A PVC PIPE.
G.PLUMBING INSTRUMENTS AND CONTROLS:
1.AFTER INSTALLATION, CHECK ALL EQUIPMENT AND PERFORM START UP IN ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS.
2.ALL PIPING SHALL BE TESTED AND FREE OF LEAKS AS REQUIRED BY THE LOCAL AUTHORITY HAVING
JURISDICTION.
3.WORK THAT IS SCHEDULED TO BE CONCEALED OR INSULATED SHALL REMAIN UNCOVERED UNTIL
REQUIRED TESTS HAVE BEEN COMPLETED. IF THE CONSTRUCTION SCHEDULE REQUIRES, ARRANGE
FOR TESTS ON SECTIONS AT A TIME.
4.BALANCE ALL SYSTEMS, CALIBRATE CONTROLS, CHECK FOR PROPER OPERATION AND SEQUENCE
UNDER ALL CONDITIONS AND MAKE ALL NECESSARY ADJUSTMENTS.
5.INSTRUCT OWNER IN OPERATION OF SYSTEMS AND SUBMIT OPERATING AND MAINTENANCE
MANUAL FOR ALL EQUIPMENT AND SYSTEMS.
TYP. THRU WALL PIPING DETAIL
SCALE: 3" = 1'-0"1
TYP. SHOWER/TUB PLUMBING DETAIL
SCALE: 1" = 1'-0"2
TYP. WASHER WALL BOX PLUMBING DETAIL
SCALE: 3/4" = 1'-0"3
TYP. UNIT PLUMBING FIXTURE SCHEDULE:
1.DW = DISHWASHER
1.1.1/2" Ø HW
1.2.1-1/2" Ø WASTE
2.SINKS
2.1.3/8" Ø CW
2.2.3/8" Ø HW
2.3.1-1/2" Ø WASTE
3.WH = WATER HEATER
3.1.3/4" Ø CW
3.2.3/4" Ø HW
4.TOILET
4.1.3/8" Ø CW
4.2.3" Ø WASTE
5.TUB = BATH TUB
5.1.3/8" Ø CW
5.2.3/8" Ø HW
5.3.1-1/2" Ø WASTE
6.WD = WASHER/DRYER
6.1.1/2" Ø CW
6.2.1/2" Ø HW
6.3.2" WASTE
PLUMBING - NOTES, LEGEND & DETAILSP001
&
ABBREV
AC
ANSI
ASTM
ATM
BL
BLDG.
B.O.P
°C
Cm
DC
DN
D.O.L
DR
DWGS
°F
FD
FM
FP
FPM
FS
FT
GPM
HP
Hz
JP
kG
kW
LB
m
MAX
MIN
mm
NC
NFPA
NO
NO.
N.P.T
NRS
PIV
PS
RN
TYP
AND
ABBREVIATION
ALTERNATING CURRENT
AMERICAN NATIONAL STANDARD INSTITUTE
AMERICAN SOCIETY FOR TESTING METERIAL
ATMOSPHERE
BRANCH LINE
BUILDING
BOTTOM OF PIPE
DEGREE CELSIUS
CENTIMETRE
DIRECT CURRENT
DROP NIPPLE
DIRECT ON-LINE STARTER
DRAIN
DRAWINGS
DEGREE FAHRENHEIT
FLOOR DRAIN
FACTORY MUTUAL
FIRE PUMP
FEET PER MINUTE
FLOW SWITCH
FEET
GALLON PER MINUTE
HORSE POWER
HERTZ
JOCKEY PUMP
KILOGRAM
KILOWATT
POUND
METRE
MAXIMUM
MINIMUM
MILIMETRE
NORMALLY CLOSED
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY OPEN
NUMBER
NATIONAL PIPE TREAD
NON RISING STEM VALVE
POST INDICATOR VALVE
PRESSURE SWITCH
RISER NIPPLE
TYPICAL
GENERAL VALVE
GATE VALVE (NON-RISING STEM)
OS & Y GATE VALVE
ANGLE VALVE
CHECK VALVE
BUTTERFLY VALVE
SOLENOID VALVE
HYDRAULIC CONTROL VALVE
S
HCV
PRV PRESSURE REGULATING VALVE (PILOT OPERATED)
PRESSURE RELIEF VALVE (PILOT OPERATED)
SIGHT FLOW INDICATOR
EQUIPMENT DRAIN
OPEN WASTE CONE
CLOSED WASTE CONE
FOOT VALVE
AUTOMATIC AIR VENT WITH VALVE
POST INDICATOR VALVE
SELF OPERATED PRESSURE REGULATING VALVE
SELF OPERATED BACK PRESSURE REGULATING VALVE
PILOT OPERATED PRESSURE REGULATING VALVE
PILOT OPERATED BACK PRESSURE REGULATING VALVE
DR DRAIN VALVE
KEY OPERATED VALVE
VALVE IN PIT
FLOW METERING ELEMENT
FS FS - FLOW SWITCH, PS - PRESSURE SWITCH
PRESSURE GAUGE WITH COCK AND SNUBBER
AIR ELEMINATOR, AUTOMATIC WITH VALVE
FLOOR DRAINFD
ALIGNMENT GUIDE SLEEVE
EXPANSION JOINT
PUMP
PITCH OF DRAINPD
FLOW IN DIRECTION OF ARROW
M
D
F
DRAIN PIPE
FIRE PROTECTION PIPE
ELBOW 90°
ELBOW LOOKING UP
ELBOW LOOKING DOWN
TEE
TEE LOOKING UP
TEE LOOKING DOWN
FLANGE
UNION
REDUCER
REDUCER CONCENTRIC
REDUCER ECCENTRIC STRAIGHT INVERT
REDUCER ECCENTRIC STRAIGHT CROWN
ELBOW 45°
ELBOW REDUCER
ELBOW LONG RADIUS
LATERAL
REMOVABLE CAP END
BLIND FLANGED END
FIRE HYDRANT
ROOF MANIFOLD
HOSE REEL CABINET, SURFACE MOUNT
HOSE REEL CABINET, SEMI-RECESSED MOUNT
HOSE REEL CABINET, RECESSED MOUNT
ALARM VALVE (LOOKING DOWN)
WATER MOTOR GONG
SIDE WALL PENDENT SPRINKLER HEAD
CO PORTABLE EXTINGUISHER
AUTOMATIC BCF (HALON 1211) EXTINGUISHER
FIRE PROTECTION SYSTEM LEGEND
LETTER SYMBOLS VALVE & PIPING SYMBOLS FITTING SYMBOLS
SYMBOLS DESCRIPTIONSYMBOLSDESCRIPTIONSYMBOLSDESCRIPTION
SYMBOLS DESCRIPTION
FH
FHC
FHC
FHC
FIRE DEPARTMENT CONNECTION
ALARM VALVE WITH WATER MOTOR GONG
PENDENT SPRINKLER HEAD, RECESSED TYPE
DRY CHEMICAL EXTINGUISHER
HYDRANT HOSE CABINET
UP-RIGHT SPRINKLER HEAD
HHC
FDC
FIRE PROTECTION SYMBOLS
PROJECT NO.PROJECT:TITLE OF DRAWINGDRAWING NO.
FIRST ISSUE DATE:0ISSUED/REVISIONS:DATE:123456ENGINEER:OWNER/DEVELOPER:112 N. MAIN ST.HORSEHEADS, NY 14845607-377-7990 | WWW.MASER-AE.COM119 S. CAYUGA STREETITHACA, NY 14850327 W. SENECA ST.ITHACA, NEW YORK 14850327 W. SENECA STREETA
5 4 3 2 16
B
C
D
E
A
B
C
D
E
78
5 4 3 2 1678
ISSUED FOR PERMIT08/19/2019REVISED FOR MECH. RM. EQUIP.06/04/20203-STORY, 12-UNIT APARTMENT BUILDINGREVISED FOR CONSTRUCTION06/17/2020DRAWING ALTERATIONIT IS A VIOLATION OF LAW FOR ANYPERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT,ENGINEER, SURVEYOR OR LANDSCAPEARCHITECT TO ALTER ANY ITEM ONTHIS DOCUMENT IN ANY WAY.ANY LICENSEE WHO ALTERS THISDOCUMENT IS REQUIRED BY LAW TOAFFIX THEIR SEAL AND THE NOTATION,"ALTERED BY," FOLLOWED BY THEIRSIGNATURE AND SPECIFICDESCRIPTION OF THE ALTERATIONS.#VISUMDEVELOPMENT GROUPMAY 31, 2019
2019-008
A.FIRE PROTECTION NOTES:
1.THE FIRE PROTECTION SYSTEM ENGINEERING DRAWINGS,
SPECIFICATIONS, PRESCRIPTIVE AND PERFORMANCE CRITERIA, WATER
SUPPLY ANALYSIS AND OTHER MATERIALS OR REPRESENTATIONS,
WHICH ARE SUBMITTED WITH THE GENERAL CONSTRUCTION
DOCUMENTS THAT SET FORTH THE OVERALL DESIGN REQUIREMENTS
AND PROVIDE SUFFICIENT DIRECTION FOR THE CONTRACTOR TO LAY
OUT THE CONSTRUCTION, ALTERATION, DEMOLITION, RENOVATION,
REPAIR, MODIFICATION, PERMITTING AND SUCH, FOR ANY PUBLIC OR
PRIVATE FIRE PROTECTION SYSTEM(S), WHICH ARE PREPARED, SIGNED,
DATED AND SEALED BY THE ENGINEER OF RECORD FOR THE FIRE
PROTECTION SYSTEM(S).
2.THE CONTRACTOR SHALL PROVIDE: LAYOUT DRAWINGS, HYDRAULIC
CALCULATIONS, CATALOG INFORMATION ON STANDARD PRODUCTS,
AND OTHER CONSTRUCTION DATA PREPARED BY THE LICENSED
CONTRACTOR THAT PROVIDES DETAIL ON THE LOCATION OF RISERS,
CROSS MAINS, BRANCH LINES, SPRINKLER HEADS, SIZING OF PIPE,
HANGER LOCATIONS, AND HYDRAULIC CALCULATIONS AND ALSO
SERVES AS A GUIDE FOR FABRICATION AND INSTALLATION OF A FIRE
PROTECTION SYSTEM. FIRE PROTECTION SYSTEM LAYOUT DOCUMENTS
ARE BASED UPON ENGINEERING DIRECTION PROVIDED IN THE FIRE
PROTECTION SYSTEM ENGINEERING DOCUMENTS AND REQUIRE NO
ADDITIONAL ENGINEERING INPUT. THESE SHOP DRAWINGS SHALL BE
SUBMITTED TO THE ENGINEER OF RECORD FOR REVIEW. SHOP
DRAWINGS STAMPED APPROVED OR FURNISH AS CORRECTED SHALL
THEN BE SUBMITTED BY THE CONTRACTOR TO THE BUILDING
DEPARTMENT AHJ FOR APPROVAL.
3.HANGER LOCATIONS SHALL BE COORDINATED WITH THE BUILDING
STRUCTURE. SUPPORT PIPING IN ACCORDANCE WITH NFPA-13,
PROVIDE ALL MISCELLANEOUS STEEL FRAMING AS REQUIRED TO
SUPPORT PIPING FROM STRUCTURE. HANGERS AND ROD SHALL HAVE
A GALVANIZED OR PLATED FINISH.
4.PROVIDE CHROME ESCUTCHEONS WHERE PIPING PENETRATES WALLS
IN EXPOSED AREAS.
5.SPRINKLER HEADS SHALL BE AS FOLLOWS:
5.1.HEADS MOUNTED IN CEILINGS SHALL BE SEMI-RECESSED TYPE,
QUICK RESPONSE, FACTORY CHROME PLATED.
5.2.HEADS IN AREAS WITHOUT CEILINGS SHALL BE UPRIGHT, BRASS
FINISH, QUICK RESPONSE TYPE.
5.3.HEAD MOUNTED IN ELECTRICAL ROOM SHALL BE SIDEWALL HEAD
TYPE, QUICK RESPONSE TYPE.
6.TIE-IN OF FLOW SWITCH AND TAMPER SWITCHES TO FIRE ALARM
SYSTEM, AND WIRING SHALL BE PERFORMED UNDER DIVISION 26.
7.ALL SPRINKLER PIPING SHALL BE PAINTED WHERE INSTALLED BELOW
CEILINGS, AND SIMILAR LOCATIONS WHERE EXPOSED. COLOR AS
DIRECTED BY THE ARCHITECT IN PUBLIC SPACES, RED WHERE EXPOSED
IN UNOCCUPIED SPACES SUCH AS EQUIPMENT ROOMS. PROVIDE HEAD
GUARDS IN EQUIPMENT ROOMS AND SIMILAR LOCATIONS WHERE THE
HEADS ARE SUBJECT TO DAMAGE.
8.TEST SYSTEMS AT 200 PSI FOR TWO HOURS IN ACCORDANCE WITH
NFPA-13 AND 24 AND REQUIREMENTS OF AHJ AND PREPARE
"CONTRACTORS MATERIAL AND TEST CERTIFICATE" AS PRESCRIBED BY
NFPA STANDARDS.
9.PROVIDE A SPRINKLER HEAD CABINET AND PROVIDE SPARE SPRINKLER
HEADS FOR EACH TYPE OF SPRINKLER HEADS IN ACCORDANCE WITH
NFPA-13.
10.SIAMESE FIRE DEPARTMENT CONNECTION SHALL HAVE (2) - 2 1/2 INCH
POLISHED BRASS INLET HOSE CONNECTIONS, 4" OUTLET PIPE, RED
ENAMEL FINISH, CAST IRON EASE OFF CAPS, AUTOMATIC BRASS BALL
DRIP CONNECTION, YARD MOUNT TYPE.
11.LABEL DRAIN PIPING, INSPECTOR'S TEST, MAIN DRAIN, SHUT-OFF
VALVES, AND SIMILAR COMPONENTS.
12.SUBMIT FITTINGS PRODUCT DATA FOR ALL MATERIALS, INCLUDING
PIPING FITTINGS, VALVES, HEADS, AND SIGNS.
13.SEE CIVIL DRAWINGS FOR UNDERGROUND PIPING MATERIALS.
14.PROVIDE AUXILIARY DRAINS FOR TRAPPED SECTIONS OF PIPING.
15.HAZARD CLASSIFICATION OF OCCUPANCIES, DENSITY AREA (GMP/SQ FT)
AND HOSE DEMAND (GPM) DESIGN REQUIREMENTS ARE IN
ACCORDANCE WITH NFPA-13.
16.THE FIRE PROTECTION CONTRACTOR SHALL LIMIT THE SPRINKLER
PIPING MAINS SO AS TO BE LOCATED IN A 6" HORIZONTAL SPACE
ABOVE THE CEILINGS, USING EITHER THE 6" OF SPACE DIRECTLY ABOVE
THE CEILINGS, OR THE 6" OF SPACE DIRECTLY BELOW THE STRUCTURE.
COORDINATION WITH MECHANICAL AND PLUMBING CONTRACTORS IS
REQUIRED PRIOR TO SUBMISSION OF SPRINKLER SHOP DRAWINGS.
17.THE FIRE PROTECTION CONTRACTOR SHALL COORDINATE ALL MAIN
PIPING RUNS THROUGH THE BUILDING WITH ALL TRADES. ANY EXPOSED
PIPING ROUTING SHALL BE APPROVED BY ARCHITECT PRIOR TO
FABRICATION AND INSTALLATION.
18.TO THE BEST OF THE ENGINEERS KNOWLEDGE, MICROBIAL INDUCED
CORROSION (MIC) IS NOT OF CONCERN. SCHEDULE 40 BRANCH PIPING
IS SPECIFIED, IN PART FOR CORROSION RESISTANCE.
19.THE WATER SUPPLY TO THE FIRE PROTECTION SYSTEM SHALL BE
TESTED FOR CONTAMINANTS THAT MAY LEAD TO MICROBIAL
CORROSION. IF POSSIBLE CONTAMINANTS ARE FOUND, PROTECTIVE
MEASURES SHALL BE DESIGNED INTO THE SYSTEM. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR PROCUREMENT OF THE TEST, AND
EVALUATION OF THE RESULTS. PROVIDE TEST RESULTS AND
RECOMMENDATIONS TO THE DESIGN TEAM AND OWNER.
20.AT THE CONTRACTOR OPTION, FLEXIBLE HEADS MAY BE USED.
HOWEVER, NO EXCESS FLEXIBLE PIPE MAY BE RESTING ON CEILING
TILES. RESTRICT USE TO 3'-0" SECTIONS.
21.APPLICABLE CODES AND STANDARDS TO BE APPLIED:
21.1.2020 INTERNATIONAL BUILDING CODE AS ADOPTED BY NEW YORK
STATE
21.2.2020 INTERNATIONAL FIRE PREVENTION CODE AS ADOPTED BY
NEW YORK STATE
21.3.NFPA-13-2019 EDITION
21.4.CITY OF ITHACA MUNICIPAL CODE
MECHANICAL ROOM ELEVATION
SCALE: 1" = 1'-0"1 MECHANICAL ROOM PLAN & ELEVATIONP002
*BYPASS- CAN GO ABOVE OR BELOW WITHOUT
INTERFERENCE WITH METER
℄
IN
METER
*BYPASS WILK
INSZURNA
CO
M
PA
NY
U350AOUT
SPRINKLER RISER
WATER METER,
BACKFLOW
PREVENTION
ASSEMBLY
2'-8"PIPE TO OUTSIDE
PIPE TAP
BALL DRIP VALVE
ELECTRICAL PANELS
MOUNTED ON BACK WALL,
SEE E-SERIES PLANS
6" X 2 12" X 2 12" WALL
MOUNTED, SIAMESE F.D.C.2'-6"PAVER, SEE
SITE PLAN
CEILING
8'-3"2'-8"
HOUSE PANEL MOUNTED ON SIDE
WALL, SEE E-SERIES PLANS
2" DOMESTIC WATER
SERVICE TO BLDG. UNITS
2" ZURN-WILKINS
2-350XL RPZ ASSEMBLY
4" MIN. AIR GAP; AIR GAP
FITTINGS NOT PERMITTED
4 12" FUNNEL
3 12" PVC DRAIN
SLOPED AT 14"/FT.1-HR. RATED WALL2'-6"PIPE SUPPORTS PER
MANUF. REQ.
COMBINED WATER FROM MAIN, 6" DIA.,
AWWA SPEC #C151 CLASS 350, CEMENT
LINED DUCTILE IRON
SEE P003/7 FOR THE
THRU SLAB DETAIL
6" Ø ZURN-WILKINS, MODEL 350A DCVA
W/BG VALVES, MOUNTED VERTICAL UP,℄
OF DEVICE 30" - 60" FROM F.F.E.
1'-1"
(1'-0" MIN.)
(2'-6" MIN.)(2'-6"MIN.)6" Ø RISER TO BLDG.
SPRINKLERS
2" Ø BALL VALVE (TYP.)
2" X 1 12" REDUCER (TYP. OF 2)
1 12" WATER METER
STRAINER
ZURN FD2360 FLOOR DRAIN
W/4" Ø SCH. 40 DWV DRAIN
PIPE, SLOPE @ 14"/FT.,
CONNECT TO BLDG. WASTE
SHUT
114" SQ.
BODY
6" DIAMETER
518"
12"
DIAMETER
STANDPIPE
(PAINTED BLACK)
STANDPIPE
(PAINTED RED)
STANDPIPE GROUND LINE MARK
FINISHED GRADE
TAMPER SWITCH
PADLOCK
CONCRETE THRUST BLOCK; CONCRETE
SHALL NOT CONTACT BOLTS OR ENDS OF
MECHANICAL FITTINGS.
WEDGE ACTION RESTRAINTS, (TYP.)
EXCESS PRESSURE
RELIEF VALVE
WATER FLOW SWITCH
(MUST TIE INTO A
CENTRAL STATION)
FDC CHECK VALVE;
UL/FM APPROVED
WATER MOTOR
ALARM
ALARM VALVE
W/GAUGES AND RETARD
SEE P003/6 FOR THE
THRU SLAB DETAIL
1-HR. RATED WALL12'-3"
T.S. 396.62'
4'-0"
T.F. 393.12'
T.P. ~391.62'4'-8"1'-0"2'-6"POST INDICATOR VALVE
(MIN. 32-FT. FROM BLDG.)1'-014"3'-41
4"
1'-0"12'-314"5'-63
4"
3 12" PVC DRAIN
SLOPED AT 14"/FT.
6" X 2 12" X 2 12" WALL
MOUNTED, SIAMESE F.D.C.
MECHANICAL ROOM PLAN
SCALE: 1" = 1'-0"2
TO BLDG.
SPRINKLERS
ZURN FD2360 FLOOR DRAIN &
4" Ø SDR35 PVC UNDER
SLAB, CONNECT TO BLDG. 6"
WASTE ON OPPOSITE SIDE
COMBINED WATER FROM MAIN, 6" DIA.,
AWWA SPEC #C151 CLASS 350, CEMENT
LINED DUCTILE IRON
2" DOMESTIC WATER
SERVICE TO BLDG.
UNITS
OUTLET TO WALKWAY
DOMESTIC WATER DISTRIBUTION
MANIFOLD; (1) 2" Ø IN;
MIN. (12) 34" Ø CW LINES OUT;
ALSO UNIT MASTER VALVES &
RADIO METERS
EIGHT (8), 34" DIA. SERVICE LINES UP
TO 2ND & 3RD FLOORS
FOUR (4), 34" DIA.
SERVICE LINES OUT
TO 1ST FLOOR UNITS
PROJECT NO.PROJECT:TITLE OF DRAWINGDRAWING NO.
FIRST ISSUE DATE:0ISSUED/REVISIONS:DATE:123456ENGINEER:OWNER/DEVELOPER:112 N. MAIN ST.HORSEHEADS, NY 14845607-377-7990 | WWW.MASER-AE.COM119 S. CAYUGA STREETITHACA, NY 14850327 W. SENECA ST.ITHACA, NEW YORK 14850327 W. SENECA STREETA
5 4 3 2 16
B
C
D
E
A
B
C
D
E
78
5 4 3 2 1678
ISSUED FOR PERMIT08/19/2019REVISED FOR MECH. RM. EQUIP.06/04/20203-STORY, 12-UNIT APARTMENT BUILDINGREVISED FOR CONSTRUCTION06/17/2020DRAWING ALTERATIONIT IS A VIOLATION OF LAW FOR ANYPERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT,ENGINEER, SURVEYOR OR LANDSCAPEARCHITECT TO ALTER ANY ITEM ONTHIS DOCUMENT IN ANY WAY.ANY LICENSEE WHO ALTERS THISDOCUMENT IS REQUIRED BY LAW TOAFFIX THEIR SEAL AND THE NOTATION,"ALTERED BY," FOLLOWED BY THEIRSIGNATURE AND SPECIFICDESCRIPTION OF THE ALTERATIONS.#VISUMDEVELOPMENT GROUPMAY 31, 2019
2019-008MIN. 1"MAX. 12"MIN. 1"MAX. 12"VARIESPIPE PROTECTION STEEL
SADDLE (TOP & BOTTOM)
STRAP
HARD, NON-HEAT
CONDUCTING MATERIAL
PER NFPA 13
SPRINKLER PIPE
INSULATION
FIXING NUT
STEEL ANGLE
NUT W/PLATE
WASHER
NOTE:
1.ALL FABRICATED STEEL SHALL BE GALVANIZED OR
PAINTED WITH TWO COATS OF ZINC CHROMATE
WOOD JOIST
MULTIPLE PIPE HANGER
SCALE: N.T.S.5
CONTINUOUS WELD
SEAL WATERTIGHT
WITH MASTIC
FACE OF WALL
ESCUTCHEON PLATE COVER
(ESCUTCHEON SHOULD BE ON BOTH
SIDES) INSIDE FACE OF WALL
18" THICK CIRCULAR
STEEL PLATE
PIPE SLEEVE THROUGH WALL
SCALE: N.T.S.6
CONTINUOUS WELD
ESCUTCHEON PLATE COVER
(ESCUTCHEON SHOULD BE ON BOTH
SIDES) INSIDE FACE OF WALL
18" THICK CIRCULAR
STEEL PLATE
SEAL WATERTIGHT
WITH MASTIC
PIPE SLEEVE THROUGH SLAB
SCALE: N.T.S.7
1
2" ANCHOR BOLT
W/EXPANSION SHIELD
RISER NIPPLE
SPRINKLER MAIN
WOOD JOIST
WOOD JOIST
SPRINKLER INSTALLED
DIRECTLY TO TEE
BRANCH PIPE
SPRINKLER HEAD (UPRIGHT)
SCALE: N.T.S.8
TEE
1" Ø GALV. PIPE
CEILING
SPRINKLER HEAD
(PENDANT TYPE)
SPRINKLER HEAD
(UPRIGHT TYPE)
LATERAL PIPE
MAIN LINE
REDUCER
LATERAL PIPE
1" Ø GALV. PIPE
CEILING
SPRINKLER HEAD
(PENDANT TYPE)
SPRINKLER HEAD
(UPRIGHT TYPE)
LATERAL PIPE
MAIN LINE
REDUCER
TEE
ARRANGEMENT OF BRANCH LINES SUPPLYING SPRINKLER ABOVE & BELOW CEILING
SCALE: N.T.S.3
PENDANT AND UPRIGHT SPRINKLER BRANCH
SCALE: N.T.S.4
BEND
1" Ø GALV. PIPE
CEILING
SPRINKLER HEAD
LATERAL PIPE
REDUCER
LATERAL PIPE
1" Ø GALV. PIPE
CEILING
SPRINKLER
HEAD
LATERAL PIPE
REDUCER
MAIN LINE
DEFLECTOR PLATE
1" X 58" REDUCER
LATERAL PIPE
1" Ø GALV. PIPE
CEILING
SPRINKLER
HEAD
LATERAL PIPE
REDUCER
TEE
POST INDICATOR VALVE
SCALE: N.T.S.2
SHUT
9"
1" SQUARE
EXTENSION
114" SQ.
BODY
6" DIAMETER
30" TO 42"
4'-0"
MINIMUM
518"
12"
DIAMETER
STANDPIPE
(PAINTED BLACK)
STANDPIPE
(PAINTED RED)
TO RISER ROOM
FIELD ADJUSTMENT NOTES:
1.REMOVE THE BODY FROM THE TOP OF THE INDICATOR POST ASSEMBLY.
2.CUT THE REQUIRED LENGTH OFF THE BOTTOM OF THE STANDPIPE FOR
THE GROUND LINE TO MATCH UP WITH STANDPIPE GROUND LINE MARK.
3.CUT THE 1 INCH SQ. EXTENSION AT A DISTANCE OF 9 INCHES ABOVE THE
TOP OF THE STANDPIPE.
4.SET THE "OPEN" AND "SHUT" TARGETS FOR THE APPROPRIATE VALVE
SIZE.
5.RE-ATTACH THE BODY TO THE TOP OF THE INDICATOR POST ASSEMBLY.
6.ALL POST INDICATOR VALVES SHALL BE INSTALLED WITH AN
ELECTRONIC UL LISTED TAMPER SWITCH.
7.THERE SHALL BE 36 INCHES OF UNOBSTRUCTED CLEARANCE AROUND
THE PERIMETER OF ALL POST INDICATOR VALVES.
8.POST INDICATOR VALVE SHALL BE LOCATED AT A MINIMUM 32 FEET
FROM BUILDING.
STANDPIPE GROUND LINE MARK
STANDPIPE
POST INDICATOR ASSEMBLY WITH
BODY REMOVED
CL
(7" MIN.)
(10" MAX.)
GROUND LINE OR FINISHED
GRADE
GROUND LINE OR FINISHED
GRADE
TAMPER SWITCH (SEE
INSET)
PADLOCK
SHUT
PADLOCK
TAMPER
SWITCH
INSET
ALL JOINTS TO THE MAIN SHALL BE
RESTRAINED
12.375"
8.125"
1.82"
6.86"
SCH. 40
DWV PIPE
4"
ZURN FD2360 FLOOR DRAIN
SCALE: N.T.S.1
FIRE PROTECTION DETAILSP003
DW
DW
DW DW
REF.REF.
REF.REF.
W/DW/D
W/D W/D
WH WH
RANGE
RANGERANGE
RANGE WH
WH
6-IN. WASTE LINE
TO STREET, SEE
CIVIL PLANS
6" X 3" X 3" TEE6" X 6" X 3" TEE
6" X 6" X 6" TEE;
CONNECT MECH. RM.
DRAIN UNDER SLAB
6" X 6" X 3" TEE
6-IN. COMBINED
DOMESTIC/FIRE SERVICE
FROM MAIN, SEE CIVIL PLANS
FROM 2ND FL.
FROM 3RD FL.
FROM 2ND FL.
FROM 3RD FL.
FROM 2ND FL.
FROM 3RD FL.
FROM 2ND FL.
FROM 3RD FL.
PROJECT NO.PROJECT:TITLE OF DRAWINGDRAWING NO.
FIRST ISSUE DATE:0ISSUED/REVISIONS:DATE:123456ENGINEER:OWNER/DEVELOPER:112 N. MAIN ST.HORSEHEADS, NY 14845607-377-7990 | WWW.MASER-AE.COM119 S. CAYUGA STREETITHACA, NY 14850327 W. SENECA ST.ITHACA, NEW YORK 14850327 W. SENECA STREETA
5 4 3 2 16
B
C
D
E
A
B
C
D
E
78
5 4 3 2 1678
ISSUED FOR PERMIT08/19/2019REVISED FOR MECH. RM. EQUIP.06/04/20203-STORY, 12-UNIT APARTMENT BUILDINGREVISED FOR CONSTRUCTION06/17/2020DRAWING ALTERATIONIT IS A VIOLATION OF LAW FOR ANYPERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT,ENGINEER, SURVEYOR OR LANDSCAPEARCHITECT TO ALTER ANY ITEM ONTHIS DOCUMENT IN ANY WAY.ANY LICENSEE WHO ALTERS THISDOCUMENT IS REQUIRED BY LAW TOAFFIX THEIR SEAL AND THE NOTATION,"ALTERED BY," FOLLOWED BY THEIRSIGNATURE AND SPECIFICDESCRIPTION OF THE ALTERATIONS.#VISUMDEVELOPMENT GROUPMAY 31, 2019
2019-008
FIRST FLOOR UNITS 101 - 104
SCALE: 3/8" = 1'-0"1 FIRST FLOOR PLUMBING PLANP101
UNIT 101
UNIT 102 UNIT 103
UNIT 104
DOMESTIC WATER DISTRIBUTION
MANIFOLD; 2" Ø SERVICE IN;
MIN. 12 CW OUTLETS @ 34" Ø OUT
MECH.
EIGHT (8), 34" DIA. SERVICE LINES
UP TO 2ND & 3RD FLOORS
FOUR (4), 3 4" DIA. SERVICE LINES
OUT TO 1ST FLOOR UNITS
TYP. UNIT PLUMBING FIXTURE SCHEDULE:
1.DISHWASHER
1.1.1/2" Ø HW
1.2.1-1/2" Ø WASTE
2.SINK
2.1.3/8" Ø CW
2.2.3/8" Ø HW
2.3.1-1/2" Ø WASTE
3.WATER HEATER
3.1.3/4" Ø CW
3.2.3/4" Ø HW
4.TOILET
4.1.3/8" Ø CW
4.2.3" Ø WASTE
5.BATH TUB
5.1.3/8" Ø CW
5.2.3/8" Ø HW
5.3.1-1/2" Ø WASTE
6.WASHER/DRYER
6.1.1/2" Ø CW
6.2.1/2" Ø HW
6.3.2" WASTE
NOTE:
1.ALL WASTE CONNECTIONS FROM UNIT
TO MAIN SHALL BE UNDER THE SLAB
AND CLEANOUTS TO TOP OF SLAB.
SEE P002 FOR ELEVATION AND
LARGE SCALE PLAN
DW
DW
DW
DW
UP
REF.
REF.REF.
REF.
W/DW/D
W/D W/D
WH
WHWH
WH
RANGE
RANGERANGE
RANGE
3" Ø WASTE TO 1ST FLOOR
AND TEE INTO BLDG.
MAIN; VENT UP TO ROOF
3" Ø WASTE TO 1ST FLOOR
AND TEE INTO BLDG.
MAIN; VENT UP TO ROOF
3" Ø WASTE TO 1ST FLOOR
AND TEE INTO BLDG.
MAIN; VENT UP TO ROOF
PROJECT NO.PROJECT:TITLE OF DRAWINGDRAWING NO.
FIRST ISSUE DATE:0ISSUED/REVISIONS:DATE:123456ENGINEER:OWNER/DEVELOPER:112 N. MAIN ST.HORSEHEADS, NY 14845607-377-7990 | WWW.MASER-AE.COM119 S. CAYUGA STREETITHACA, NY 14850327 W. SENECA ST.ITHACA, NEW YORK 14850327 W. SENECA STREETA
5 4 3 2 16
B
C
D
E
A
B
C
D
E
78
5 4 3 2 1678
ISSUED FOR PERMIT08/19/2019REVISED FOR MECH. RM. EQUIP.06/04/20203-STORY, 12-UNIT APARTMENT BUILDINGREVISED FOR CONSTRUCTION06/17/2020DRAWING ALTERATIONIT IS A VIOLATION OF LAW FOR ANYPERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT,ENGINEER, SURVEYOR OR LANDSCAPEARCHITECT TO ALTER ANY ITEM ONTHIS DOCUMENT IN ANY WAY.ANY LICENSEE WHO ALTERS THISDOCUMENT IS REQUIRED BY LAW TOAFFIX THEIR SEAL AND THE NOTATION,"ALTERED BY," FOLLOWED BY THEIRSIGNATURE AND SPECIFICDESCRIPTION OF THE ALTERATIONS.#VISUMDEVELOPMENT GROUPMAY 31, 2019
2019-008
SECOND FLOOR UNITS 201 - 204
SCALE: 3/8" = 1'-0"1 SECOND FLOOR PLUMBING PLANP102
TYP. UNIT PLUMBING FIXTURE SCHEDULE:
1.DISHWASHER
1.1.1/2" Ø HW
1.2.1-1/2" Ø WASTE
2.SINK
2.1.3/8" Ø CW
2.2.3/8" Ø HW
2.3.1-1/2" Ø WASTE
3.WATER HEATER
3.1.3/4" Ø CW
3.2.3/4" Ø HW
4.TOILET
4.1.3/8" Ø CW
4.2.3" Ø WASTE
5.BATH TUB
5.1.3/8" Ø CW
5.2.3/8" Ø HW
5.3.1-1/2" Ø WASTE
6.WASHER/DRYER
6.1.1/2" Ø CW
6.2.1/2" Ø HW
6.3.2" WASTE
UNIT 201
UNIT 202 UNIT 203
UNIT 204
FOUR (4), 3 4" DIA. SERVICE LINES
UP TO THE 3RD FLOOR
FOUR (4), 34" DIA. SERVICE LINES
OUT TO 2ND FLOOR UNITS
FROM 3RD FLOOR FROM 3RD FLOOR
FROM 3RD FLOOR
DW
DW
DW
DW
UP
REF.
REF.
REF.
REF.
W/DW/D
W/D W/D
WH
WHWH
WH
RANGE
RANGERANGE
RANGE
3" Ø WASTE TO 1ST FLOOR
AND TEE INTO BLDG.
MAIN; VENT UP TO ROOF 3" Ø WASTE TO 1ST FLOOR
AND TEE INTO BLDG.
MAIN; VENT UP TO ROOF
3" Ø WASTE TO 1ST FLOOR
AND TEE INTO BLDG.
MAIN; VENT UP TO ROOF
PROJECT NO.PROJECT:TITLE OF DRAWINGDRAWING NO.
FIRST ISSUE DATE:0ISSUED/REVISIONS:DATE:123456ENGINEER:OWNER/DEVELOPER:112 N. MAIN ST.HORSEHEADS, NY 14845607-377-7990 | WWW.MASER-AE.COM119 S. CAYUGA STREETITHACA, NY 14850327 W. SENECA ST.ITHACA, NEW YORK 14850327 W. SENECA STREETA
5 4 3 2 16
B
C
D
E
A
B
C
D
E
78
5 4 3 2 1678
ISSUED FOR PERMIT08/19/2019REVISED FOR MECH. RM. EQUIP.06/04/20203-STORY, 12-UNIT APARTMENT BUILDINGREVISED FOR CONSTRUCTION06/17/2020DRAWING ALTERATIONIT IS A VIOLATION OF LAW FOR ANYPERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT,ENGINEER, SURVEYOR OR LANDSCAPEARCHITECT TO ALTER ANY ITEM ONTHIS DOCUMENT IN ANY WAY.ANY LICENSEE WHO ALTERS THISDOCUMENT IS REQUIRED BY LAW TOAFFIX THEIR SEAL AND THE NOTATION,"ALTERED BY," FOLLOWED BY THEIRSIGNATURE AND SPECIFICDESCRIPTION OF THE ALTERATIONS.#VISUMDEVELOPMENT GROUPMAY 31, 2019
2019-008
THIRD FLOOR UNITS 301 - 304
SCALE: 3/8" = 1'-0"1 THIRD FLOOR PLUMBING PLANP103
TYP. UNIT PLUMBING FIXTURE SCHEDULE:
1.DISHWASHER
1.1.1/2" Ø HW
1.2.1-1/2" Ø WASTE
2.SINK
2.1.3/8" Ø CW
2.2.3/8" Ø HW
2.3.1-1/2" Ø WASTE
3.WATER HEATER
3.1.3/4" Ø CW
3.2.3/4" Ø HW
4.TOILET
4.1.3/8" Ø CW
4.2.3" Ø WASTE
5.BATH TUB
5.1.3/8" Ø CW
5.2.3/8" Ø HW
5.3.1-1/2" Ø WASTE
6.WASHER/DRYER
6.1.1/2" Ø CW
6.2.1/2" Ø HW
6.3.2" WASTE
UNIT 301
UNIT 302 UNIT 303
UNIT 304
FOUR (4), 34" DIA. SERVICE LINES
OUT TO 3RD FLOOR UNITS