Loading...
HomeMy WebLinkAboutOLIN HALL B40B LAB RENOVATION_100% CD SET_SIGNED 07_TP_Technical Specs_Olin B40B.docx TECHNICAL SPECIFICATIONS FOR OLIN HALL B40B LAB RENOVATION CORNELL UNIVERSITYITHACA, NEW YORK Olin Hall 2024 Rms B40-B40B Hormozi Lab Renovation Asbestos Bulk Sampling Rpt.pdf 860 Hooper Road Endwell, NY 13760 Tel: 607.231.6600 Fax: 607.231.6650 www.delta-eas.com AN ISO 9001:2015 CERTIFIED COMPANY “We are a seamless extension of our clients’ organizations” August 24, 2020 Mr. Dale Houseknecht, Facilities Coordinator Projects II Cornell University IPP-Facilities Management FM Administration 116 Humphreys Service Building Ithaca, New York 14853-3701 Re: Olin Hall (2024) Rooms B40 and B40B Hormozi Lab Renovation Project Asbestos Bulk Sampling - Bulk Sample Report Cornell Task Authorization No. TA–345, Work Order No. 12808549 Delta Project No.: 2019.003.332 Dear Mr. Houseknecht: Enclosed, please find the Asbestos Bulk Sample Report Form, the associated Laboratory Analytical Result Sheets, Material Photos, and the Sample Location Drawing for the bulk sampling performed by Delta Certified Inspector Thomas Ferro. The sampling was performed on August 8th, 2020 and addressed suspect materials with the potential to be impacted by the upcoming Olin Hall Rooms B40 and B40B Hormozi Lab Renovation Project. Based on a review of the Design Development Drawing Set dated August 4th, 2020, previous Delta sampling efforts, and a visual inspection of the renovation area, a total of eight (8) bulk samples were collected representing four (4) suspect homogenous materials. Four (4) of the samples collected were “Non-Friable Organically Bound” (NOB) representing two (2) homogenous materials. The remaining four (4) samples were friable, “non-NOB” materials, representing two (2) homogenous materials. Results for the countertop seam epoxy were reported as “Asbestos Containing”. Results for all other samples were reported as “No Asbestos Detected”. In addition to the samples collected, other suspect homogenous materials were observed to be present but not sampled as they were addressed through previous Delta sampling efforts. These materials included: • 12” x 12” White with Gray Mottled Floor Tile and its associated Mastic – Both No Asbestos Detected • 2’ x 2’ Smooth Ceiling Tile – No Asbestos Detected • Epoxy Flooring – No Asbestos Detected • Sheetrock – No Asbestos Detected • Joint Compound – No Asbestos Detected • Trespa Labtop/Countertop – Non-Suspect • Mastic from 4” Non–suspect vinyl black cove base – No Asbestos Detected Based on the above, the only asbestos containing material to be impacted as a part of the Olin Hall Rooms B40 and B40B Hormozi Lab Renovation Project is the Seam Epoxy present on the 4 seams of the Room B40 Countertop. The total quantity of the ACM Seam Epoxy is less than 1 square foot (based on 23 linear feet at an average 1/8” width for the 4 seams where present). Bulk sample analysis was performed by AmeriSci New York, Inc., an independent laboratory approved / accredited by the NYS Department of Health (ELAP), the American Industrial Hygiene Association (AIHA), and the National Voluntary Laboratory Accreditation Program (NVLAP). Analysis of all Non-Friable Organically Bound (NOB) materials was initially performed by Polarized Light Microscopy (PLM) following the NYS DOH “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 2 of 9 AN ISO 9001:2015 CERTIFIED COMPANY ELAP 198.6 Methodologies. If the PLM results were reported as “non-asbestos”, the sample was then analyzed by Transmission Electron Microscopy (TEM) following the NYS DOH ELAP 198.4 Methodology. Analysis of all Non-NOB materials were performed by Polarized Light Microscopy (PLM) following the NYS DOH ELAP 198.1 Methodology. “Positive Stop” sample analysis protocol was utilized for a given homogenous material set with multiple samples and based on this; 7 of the 8 samples collected were analyzed. Please reference the Asbestos Bulk Sample Report Form for sample particulars and details. I have also attached Delta Company, Personnel and Laboratory Licenses/ Certifications. If you have any questions, or require any other information, please feel free to contact me at your convenience. Respectfully, DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Stephen Prislupsky Director of Environmental Services Att: Project Paperwork “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 3 of 9 AN ISO 9001:2015 CERTIFIED COMPANY Attachment A Asbestos Bulk Sample Report Form Material Asbestos PLM Result TEM Result Bulk Sample Description / Details Type Type % Asbestos % Asbestos 2019.003.332 - 01A 01 Bsmt. Countertop Seam Epoxy, Room B40 Miscellaneous 3.7% NA/PS 2019.003.332 - 01B 01 Bsmt. Countertop Seam Epoxy, Room B40 Miscellaneous NA/PS NA/PS 2019.003.332 - 02A 02 Bsmt. Countertop Mastic, Tan, Room B40 Miscellaneous ND ND ND 2019.003.332 - 02B 02 Bsmt. Countertop Mastic, Tan, Room B40 Miscellaneous ND ND ND 2019.003.332 - 03A 03 Bsmt. Door Slab Core Material, Room B40 Miscellaneous ND ND NA 2019.003.332 - 03B 03 Bsmt. Door Slab Core Material, Room B40 Miscellaneous ND ND NA 2019.003.332 - 04A 04 Bsmt. Door Slab Core Material, Room B40B Miscellaneous ND ND NA 2019.003.332 - 04B 04 Bsmt. Door Slab Core Material, Room B40B Miscellaneous ND ND NA Number of Samples Collected: 8 Project: Olin Hall Rooms B40 & B40B Hormozi Lab Renovations Asbestos Bulk Sampling HA - Homogenous Area ND - No Asbestos Detected NA - Not Analyzed by Methodology NA/PS - Not Analyzed, Positive Stop TSI - Thermal System Insulation Misc - Miscellaneous Material Trace / < 1% - Non-asbestos by definition Number www.delta-eas.com Floor Dates Sampling Performed: 08/18/2020 Date of Report: 08/24/2020 Laboratory: AmeriSci Labs Task Authorization No.: TA-345 / Work Order No.: 12808549 Chrysotile Asbestos Bulk Sample Report Form Building Code: 2024 Sample 860 Hooper Road, Endwell, NY 13760 Tel: 607.231.6600 Fax 607.231.66450 Client: Cornell University Delta Proj. No.: 2018.003.332 Asbestos Inspector: Thomas Ferro HA* Number of Samples Analyzed: PLM - 7 / TEM -2 Cornell University Olin Hall Rooms B40 / B40B Hormozi Lab Renovation Asbestos Bulk Sampling Page 1 of 1 “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 4 of 9 AN ISO 9001:2015 CERTIFIED COMPANY Attachment B Laboratory Analytical Result Sheets “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 5 of 9 AN ISO 9001:2015 CERTIFIED COMPANY Attachment C Sample Location Drawing “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 6 of 9 AN ISO 9001:2015 CERTIFIED COMPANY Attachment D Photos “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 7 of 9 AN ISO 9001:2015 CERTIFIED COMPANY HA 01 – Countertop Seam Epoxy, “Asbestos Containing” HA 02 – Countertop Mastic, “No Asbestos Detected” “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 8 of 9 AN ISO 9001:2015 CERTIFIED COMPANY HA 03 – Door Slab Core Material, Room B40, “No Asbestos Detected” HA 04 – Door Slab Core Material, Room B40B, “No Asbestos Detected” “We are a seamless extension of our clients’ organizations” DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Page 9 of 9 AN ISO 9001:2015 CERTIFIED COMPANY Attachment E Licenses and Certifications New York State – Department of Labor Division of Safety and Health License and Certificate Unit State Campus, Building 12 Albany, NY 12240 ASBESTOS HANDLING LICENSE Delta Engineers, Architects & Land Surveyors, D.P.C. 860 Hooper Road Endwell, NY 13760 FILE NUMBER: 05-0851 LICENSE NUMBER: 29322 LICENSE CLASS: RESTRICTED DATE OF ISSUE: 08/28/2019 EXPIRATION DATE: 09/30/2020 Duly Authorized Representative – Stephen Prislupsky: This license has been issued in accordance with applicable provisions of Article 30 of the Labor Law of New York State and of the New York State Codes, Rules and Regulations (12 NYCRR Part 56). It is subject to suspension or revocation for a (1) serious violation of state, federal or local laws with regard to the conduct of an asbestos project, or (2) demonstrated lack of responsibility in the conduct of any job involving asbestos or asbestos material. This license is valid only for the contractor named above and this license or a photocopy must be prominently displayed at the asbestos project worksite. This license verifies that all persons employed by the licensee on an asbestos project in New York State have been issued an Asbestos Certificate, appropriate for the type of work they perform, by the New York State Department of Labor. Eileen M. Franko, Director SH 432 (8/12) For the Commissioner of Labor Olin Hall 2024 Room B40 Minor Lab-top Epoxy Abatement SOW (003).pdf Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 1 of 5 Project Location/Information: Date Prepared: September 11, 2020 Building Name / Code / Address: Olin Hall / 2024 / 113 Ho Plaza, Ithaca, NY Cornell Space ID#(s): Basement Room B40 Cornell Project Representative: Mike Swartwout (Office: 607-255-4920 / Cell: 607-327-0128) Cornell Building Coordinator: Thom Quinn (Office: 607-255-3540, Room B-14A in Olin Hall) Quantity and description of materials being removed: Abatement operations shall include the removal of non-asbestos Lab-tops / Sink-top / Backsplashes and their associated non-friable organically bound (NOB) asbestos containing joint/seam epoxy present along the west wall in Room B40. All Lab-top/sink utilities shall be disconnected prior to abatement operations. The ACM epoxy is applied at the various joints/seams on the lab-top/sink-top sections and backsplashes to be removed. The total quantity of asbestos containing joint/seam epoxy to be removed is less than 1 square foot (23 linear feet at an average 1/8” width). Reference the attached drawing for the lab-top sections and their associated backsplashes to be removed. All lab-top bases shall be cleaned and are to remain. Method of Abatement: Non-Asbestos Lab-tops and associated ACM joint/seam epoxy removal shall be performed as per the requirements of 12 NYCRR Part 56-11.1 for In-Plant operations and Part 56-11.3 for Minor Asbestos Projects. Abatement Project Schedule/Dates/Manpower: Anticipated Crew Size: 1 Supervisor 2 Worker Project Schedule: Abatement operations including work area preparation, abatement, and final cleaning shall be performed during a worst-case single shift on Wednesday, September 16th, 2020 starting at 7:30 am. Contact Building Coordinator Tom Quin upon arrival for Room Access. Special Project Conditions: Project Power: Existing Building Power to be utilized Project Water: Source to be provided by the Owner Negative Air Exhaust Location: Localized via HEPA-Vacuum. Project Documentation / Requirements: Work Order No. Reference Task Authorization for Work Order No. Prevailing Wage Rate Project: Yes No X Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 2 of 5 Building Permits: State Permit Required: Yes No X ; Contractor to Procure: Yes No Local City Permit Required: Yes X No ; Contractor to Procure: Yes X No Project Notifications: NYS DOL 10-Day Notification Required: Yes No X EPA 10-Day Notification Required: Yes No X Building Occupant Posting, Date of Posting: As necessary for 9/16/2020 project date Prepared By: DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Stephen Prislupsky Director of Environmental Services NYS DOL Asbestos Project Designer Certificate No. 90-10891 Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 3 of 5 Attachment A Drawings Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 4 of 5 Attachment B Photos Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 5 of 5 Non-Asbestos Lab-top / Sink-top / Backsplash with ACM Joint/Seam Epoxy to be removed (sections present on blue base cabinets in photos) Olin Hall 2024 Room B40 Minor Lab-top Epoxy Abatement SOW.pdf Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 1 of 5 Project Location/Information: Date Prepared: September 11, 2020 Building Name / Code / Address: Olin Hall / 2024 / 113 Ho Plaza, Ithaca, NY Cornell Space ID#(s): Basement Room B40 Cornell Project Representative: Mike Swartwout (Office: 607-255-4920 / Cell: 607-327-0128) Cornell Building Coordinator: Thom Quinn (Office: 607-255-3540, Room B-14A in Olin Hall) Quantity and description of materials being removed: Abatement operations shall include the removal of non-asbestos Lab-tops / Sink-top / Backsplashes and their associated non-friable organically bound (NOB) asbestos containing joint/seam epoxy present along the west wall in Room B40. All Lab-top/sink utilities shall be disconnected prior to abatement operations. The ACM epoxy is applied at the various joints/seams on the lab-top/sink-top sections and backsplashes to be removed. The total quantity of asbestos containing joint/seam epoxy to be removed is less than 1 square foot (23 linear feet at an average 1/8” width). Reference the attached drawing for the lab-top sections and their associated backsplashes to be removed. All lab-top bases shall be cleaned and are to remain. Method of Abatement: Non-Asbestos Lab-tops and associated ACM joint/seam epoxy removal shall be performed as per the requirements of 12 NYCRR Part 56-11.1 for In-Plant operations and Part 56-11.3 for Minor Asbestos Projects. Abatement Project Schedule/Dates/Manpower: Anticipated Crew Size: 1 Supervisor 2 Worker Project Schedule: Abatement operations including work area preparation, abatement, and final cleaning shall be performed during a worst-case single shift on Wednesday, September 16th, 2020 starting at 7:30 am. Contact Building Coordinator Tom Quin upon arrival for Room Access. Special Project Conditions: Project Power: Existing Building Power to be utilized Project Water: Source to be provided by the Owner Negative Air Exhaust Location: Localized via HEPA-Vacuum. Project Documentation / Requirements: Work Order No. Reference Task Authorization for Work Order No. Prevailing Wage Rate Project: Yes No X Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 2 of 5 Building Permits: State Permit Required: Yes No X ; Contractor to Procure: Yes No Local City Permit Required: Yes X No ; Contractor to Procure: Yes X No Project Notifications: NYS DOL 10-Day Notification Required: Yes No X EPA 10-Day Notification Required: Yes No X Building Occupant Posting, Date of Posting: As necessary for 9/16/2020 project date Prepared By: DELTA ENGINEERS, ARCHITECTS, & LAND SURVEYORS, DPC Stephen Prislupsky Director of Environmental Services NYS DOL Asbestos Project Designer Certificate No. 90-10891 Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 3 of 5 Attachment A Drawings Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 4 of 5 Attachment B Photos Cornell University – Asbestos Abatement Type 1 Project Scope of Work Page 5 of 5 Non-Asbestos Lab-top / Sink-top / Backsplash with ACM Joint/Seam Epoxy to be removed (sections present on blue base cabinets in photos) OLIN HALL B40B LAB RENOVATION_100% CD SET_SIGNED.pdf CB CB CB BC BC BC BC CB CB C B C B BC BC BC BC BC BCBC BCBC BCBC BC BC BC BC C B BC CB BC BC CB BC BC BC BC 19 19 20 20 20 21 21 21 21 20 20 20 20 19 19 19 19 20 20 20 21 21 21 21 20 20 20 20 19 19 19 19 20 20 20 21 21 21 21 20 2 0 20 20 19 19 19 19 20 20 20 21 21 21 21 20 20 20 20 19 19 19 19 20 20 20 21 21 21 21 2 0 20 20 20 19 19 19 19 21 20 20 20 20212 1 21 21 21 21 21 21 21212121212121 PAVED PARKING UNPAVED PARKING UNPAVED PARKING PAVED ROCKS PLATFORM TENNIS COURTS S S S S IG N 101 102104 103105 106108 107 110114 116120 120B 124 126 128 130 132 142 144 148 115 145 145B 155B 155 155A 165 165B 167E 167D 167C 167B 167A168169170B170A 170 160162 152 100CD 100EB 100CE 167 167F 100JA 100UA 100UB 100SA 100CJ 100CG 100UF 100CK 100CA100CF 100CL 100CN 100UC 100SB 100JC 100SC 100CC 100TC 100TA 100JB 100UD 100TB 145A 100CM 167G 100TD 142A 148A 158 158B 156 100UR 146 100CA B00SE 148B 136 OPEN TO BELOW 111 100EA 100CP UP UP DN UP UP DN UP UPDN UP DN UP DN DN B00EA B00CC B00SC B00JB B01 B02B06 B05 B08B14 B40A B40 B40B B49 B53 B55 B57 B78 B59 B00UA B56 B54 B52 B50 B48 B46 B00UC B40C B00UL B14B B14A B00UM B00CD B00UN B00US B00EB B00TA B00UH B00TB B00UG B00UP B00UF B00JA B00SB B00CA B00SA B00UB B00UE B00UD B00JC B00UR B14C B00CA B00CA B11 B00SE UP UP UP UP 2024 OLIN HALL CAMPUS ROAD EXTERIOR ELEVATION 1 X-100 X-100 1 1 INTERIOR ELEVATION 1 X-100 SECTION MARKER 1 X-100 ENLARGED DETAIL CONSTRUCTION KEYED NOTE DEMOLITION KEYED NOTE DRAWING REVISION NOTE LINETYPE: TO BE PROVIDED / NEW LINETYPE: DEMOLITION / TO BE RELOCATED LINETYPE: EXISTING TO REMAIN # # # 1 1 1 11 AREA OF WORK AREA OF WORK T-001 TITLE SHEET ARCHITECTURAL A-001 GENERAL NOTES, SYMBOLOGY, ABBREVIATIONS AND DOOR SCHEDULE A-002 CODE COMPLIANCE/ CONTROL AREA PLANS - BASEMENT & FIRST FLOOR A-101 PARTIAL BASEMENT DEMOLITION PLAN - ROOM B40 & B40B A-102 PARTIAL BASEMENT RENOVATION PLAN AND FIRST FLOOR EQUIPMENT PLAN A-103 REFLECTED CEILING PLAN MECHANICAL M-001 GENERAL NOTES AND SYMBOL LEGENDS M-101 PARTIAL BASEMENT MECHANICAL FLOOR PLANS M-401 MECHANICAL BUILDING AUTOMATION AND CONTROL SYSTEM DETAIL M-501 SCHEDULES ELECTRICAL E-001 GENERAL NOTES AND SYMBOL LEGENDS E-101 ELECTRICAL DEMOLITION & RENOVATION PLANS E-501 SCHEDULES & DETAILS PLUMBING P-001 GENERAL NOTES AND SYMBOL LEGENDS P-101 PARTIAL BASEMENT AND FIRST FLOOR PLUMBING PLANS C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 Cornell University 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION T-001 12809855 TITLE SHEET FE DESIGN JGC 2024 OCTOBER 12, 2020 OLIN HALL B40B LAB RENOVATION BUILDING CODE SUMMARY APPLICABLE CODES 2020 NYS BUILDING CODE 2020 NYS EXISTING BUILDING CODE 2020 NYS FIRE CODE 2020 NYS PLUMBING CODE 2020 NYS MECHANICAL CODE 2020 NYS ENERGY CONSERVATION CODE 2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES 2010 AMERICANS WITH DISABILITY ACT (ADA) PROJECT SUMMARY THIS PROJECT INCLUDES THE RENOVATION OF ABOUT 1,500 SF OF LABORATORY AND OFFICE SPACES. ALTERATION LEVEL 2: LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE THAN ITS EXISTING CONDITIONS. BUILDING LIMITATIONS CONSTRUCTION CLASSIFICATION: IIA CLASSIFICATION OF HAZARDS: MAQ IN PROGRESS HIGH-RISE BUILDING: NO EXTINGUISHING REQUIREMENT: THE EXISTING BUILDING IS FULLY SPRINKLERED. OCCUPANCY OF AREA OF WORK OCCUPANCY CLASSIFICATION: BUSINESS (B / HIGHER EDUCATION LABORATORY) GENERAL SYMBOLS LEGEND DRAWING INDEX PROJECT SCOPE THE PURPOSE OF THIS PROJECT IS TO RENOVATE LABORATORY SPACE B40B AND ADJACENT OFFICE SPACE ROOM B40 IN OLIN HALL. THE MAJORITY OF DEMOLITION AND NEW WORK TAKES PLACE IN ROOM B40B AND B40, WHILE SOME LAB EQUIPMENT WILL BE INSTALLED IN ROOM 108 AS IDENTIFIED IN THIS SET OF DOCUMENTS. EXISTING CONDITIONS IN ROOM 108 WILL REMAIN IN TACKED. SITE LOCATION - OLIN HALL 2024 KEY PLANS OLIN HALL - BASEMENT OLIN HALL - FIRST FLOOR 1 08/04/2020 ISSUE FOR DD REVIEW 2 09/01/2020 ISSUE FOR 90% REVIEW 3 09/29/2020 ISSUE FOR COORDINATED REVIEW 4 10/12/2020 ISSUE FOR CONSTRUCTION WALL - EXISTING WALL - METAL STUD/ GWB WALL - CONCRETE WALL - CMU WALL - BRICK ITEMS FOR DEMOLITION DOOR/ WALL - EXISTING DOOR/ WALL - NEW DOOR/ WALL - DEMOLITION TAG - DOOR TAG - WINDOW TAG - WALL TAG - ROOM # CENTER LINE PHOTO REFERENCE LEVEL MARKER COLUMN GRID MARKER ELEVATION MARKER ELEVATION CHANGE ARROWS BREAK LINE SYMBOLS 0' - 0" 101 1t X-X X 2B00UA C L 1 Name Elevation A101 1 1 1 0 DN UP 1 11 1 ABBREVIATIONS A & AND @ AT ACT ACOUSTICAL CEILING TILE ALT ALTERNATE ALUM ALUMINUM AVG AVERAGE AFF ABOVE FINISH FLOOR B BD BOARD BLDG BUILDING BOD BOTTOM OF DECK BSMT BASEMENT C CG CORNER GUARDS CJ CONTROL JOINT CLG CEILING CL CENTER LINE CLR CLEAR CMU CONCRETE MASONRY UNIT COL COLUMN CONC CONCRETE CONF CONFERENCE CONT CONTINUOUS CORR CORRIDOR CPT CARPET CRS COURSE(S) CT CERAMIC TILE D DEMO DEMOLITION DF DRINKING FOUNTAIN DIA DIAMETER DIM DIMENSION DN DOWN DO DOOR OPENING DWG DRAWING E EA EACH EJ EXPANSION JOINT ELEC ELECTRIC ELEV ELEVATION/ ELEVATOR EPDM RUBBER ROOF MEMBRANE EQ EQUAL EX'G EXISTING EXT EXTERIOR F FD FLOOR DRAIN FDN FOUNDATION FEC FIRE EXTINGUISHER CABINET FFE FINISH FLOOR ELEVATION FRP FIBER REINFORCED POLYESTER FT FOOT/FEET FTG FOOTING G GA GAGE GALV GALVANIZED GC GENERAL CONTRACTOR GEN GENERAL GL GLASS GWB GYPSUM WALL BOARD H HC HANDICAPPED HT HEIGHT HM HOLLOW METAL HR HOUR HVAC HEATING, VENTILATING & AC J JAN JANITOR L LAV LAVATORY LB/# POUND LGMF LIGHT GAGE METAL FRAMING M MFR MANUFACTURER MAT MATERIAL MAX MAXIMUM MEZZ MEZZANINE MIN MINIMUM MO MASONRY OPENING MTL METAL N NA NOT APPLICABLE NIC NOT IN CONTRACT NR NOT RATED NTS NOT TO SCALE O OC ON CENTER OD OUTSIDE DIAMETER OPNG OPENING OSB ORIENTER STRAND BOARD P +/- PLUS OR MINUS PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PT PRESSURE TREATED Q QTY QUANTITY R R RISER RD ROOF DRAIN REF REFRIGERATOR REQ REQUIRED REV REVISION RO ROUGH OPENING RTU ROOF TOP UNIT S SHTG SHEATHING SIM SIMILAR SF SQUARE FOOT/ FEET SS STAINLESS STEEL STL STEEL STD STANDARD T T TREAD T&G TONGUE & GROOVE TEL TELEPHONE TEMP TEMPERATURE TOS TOP OF STEEL TV TELEVISION TYP TYPICAL U UEV UNEVEN DOORS W/ VISION PANEL UEF UNEVEN FLUSH DOOR V VCT VINYL COMPOSITION TILE VIF VERIFY IN FIELD W W/O WITHOUT WD WOOD 7' - 0" 3' - 0" 3' - 4" 2" 3' - 0" 2" 7' - 2" 7' - 0"2" FG F-1 7' - 0" 3' - 6" FG/ F-2 ALTERNATE #1 3' - 6" 7' - 0" 7' - 0" 3' - 0" FG/ F-1 ALTERNATE #1 3' - 0" 6' - 0" 7' - 4" 2" 7' - 0" 2" 7' - 2" 7' - 0"2" F-3 ALTERNATE #1 6' - 4" 2" 6' - 0" 2" 7' - 2" 7' - 0"2" F-2 ALTERNATE #1 5 5/8" 5 5/8" 10 5/8"7 5/8" S-1 S-1 S-1 B40 B40.1 B40C VERIFY EXISTING FRAME 7' - 0" 3' - 6" F 3' - 6" VERIFY EXISTING FRAME 7' - 0" B00CD PROVIDE GRAPHIC AS REQUIRED BY PART 47 OF THE NEW YORK STATE DEPARTMENT OF LABOR. C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION A-001 12809855 GENERAL NOTES, SYMBOLOGY, ABBREVIATIONS AND DOOR SCHEDULE J. COOLBAUGH JGC 2024 OCTOBER 12, 2020 SCOPE OF WORK 1.0 REMOVE CASEWORK FROM ROOM B40. 2.0 PROVIDE NEW CASEWORK IN ROOM B40B. 3.0 PROVIDE NEW FINISHES IN ROOM B40. 4.0 PROVIDE NEW LASER CURTAIN SYSTEM IN ROOM B40B. GENERAL NOTES 1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101 LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS BEING CONSTRUCTED. 2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER PORTION OF THE DRAWINGS AND / OR NOTES. 3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING, PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE REPLACED AT NO COST TO THE OWNER. 4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING. 5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND / OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS, ROOF OR FLOOR TO BE INFILLED SOLID. 6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE SPACES OR AREAS TO ORIGINAL CONDITION. 7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES, LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT LOCATION OF ALL ITEMS. 8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND NAME OF INSTALLER. 9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A POINT THAT A CONTAINER IS NO LONGER REQUIRED. 10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER. DOOR / HARDWARE SCHEDULE DOOR DOOR FRAME FIRE RATING GLAZING TYPE HARDWARE DETAILS REMARKSDOOR LOCATION HAND PANEL SIZE ELEVATION TYPE MATERIAL FINISH ELEVATION TYPE MATERIAL FINISH HEAD DIM. HINGES MCKINNEY TA2714 4.5 X 4.5 X 26D HINGES MCKINNEY TA2714 X 4.5 X 4.5 X NRP X 26D FIELD VERIFY DIMENSIONS FLUSH BOLT DCI 780F X 26D LOCKSET SARGENT 70-8205 X WTL X LHRB X 26D LOCKSET SARGENT 70-8205 X WTL X RH X 26D LOCKSET SARGENT 70-8215 X WTL X LH X 26D LOCKSET SARGENT 70-8205 X WTL X LH X 26D BEST RESTRICTED CYLINDERS PROVIDE BY THE EN ZONE CLOSER SARGENT 351 X P X EN X 120 DEGREE WALL BUMPERS DCI 3211T X US26D SILENCERS DCI 8S SELF LATCHING FLUSH BOLTS DCI 845 METAL DOOR DOOR COORDINATORS DCI #684 MOUNTING BRACKET DCI 600D SERIES ELECTROMAGNETIC DOOR HOLDER RIXSON MODEL 997 ELECTROMAGNETIC DOOR HOLDER RIXSON MODEL 980 HEAD JAMB THRESHOLD # OF PANELS WIDTH HEIGHT THICKNESS B00CD B00CA TO B00CD LH (2) 3' - 6" 7' - 0" 1 3/4" F HM PT-3 F-3 EX PT-3 EX 45 MIN - - 6 - - - 1 - 1 2 - 2 1 1 1 1 1 5 B40 B40B TO B40 LH (1) 3' - 0" 7' - 0" 1 3/4" FG HM PT-3 F-1 HM PT-3 2 NA S-1 3 - - - - - 1 1 1 1 3 - - - - B40.1 B00CD TO B40 RH (2) 3' - 0" 7' - 0" 1 3/4" FG/ F HM PT-3 F-2 HM PT-3 2 NA S-1 - 6 2 - 1 - - 1 2 2 2 - - - - - 4 B40C B00CD FROM B40C LHRBA (2) 3' - 6" 7' - 0" 1 3/4" FG/ F HM PT-3 F-3 HM PT-3 2 NA S-1 - 6 2 1 - - - 1 2 2 2 - - - - - 1, 3, 4 NOTES: 1. VERIFY ALL HARDWARE DIMENSIONS FOR DOOR B40C. 2. PROVIDE HINGE FILLER PLATE (BY DON-JO OR APPROVED EQUAL) ON FRAME TO REMAIN. VERIFY EXISTING HINGE SIZE. SEE DEMOLITION PLAN FOR DOOR LOCATION (A-101). 3. BASE BID - REPLACE DOOR HARDWARE ON DOOR B40C ONLY. 4. ALTERNATE #1 - REMOVE AND INSTALL NEW DOORS, FRAMES, AND HARDWARE AT DOORS B40.1 AND B40C. REFER TO RENOVATION PLAN ON A-102 AND DOOR/ FRAME ELEVATIONS FOR MORE INFORMATION. 5. VERIFY ALL HARDWARE DIMENSIONS FOR DOOR B00CD. HOLLOW METAL DOORS/ FRAMES: BASIS OF DESIGN FOR STILE AND RAIL DOORS - CURRIES 767 OR APPROVED EQUAL. BASIS OF DESIGN FOR NON-RATED FLUSH DOORS - CURRIES 607 OR APPROVED EQUAL. BASIS OF DESIGN FOR RATED FLUSH DOORS - CURRIES 727 OR APPROVED EQUAL. • 18 GAUGE MIN. DOOR • 3' WIDE AND UNDER: 16 GAUGE FRAMES • OVER 3' WIDE: 14 GAUGE FRAMES GLAZING: S-1 - 1/4" FULLY TEMPERED SAFETY GLASS PAINT: PT-3 PAINT - DOORS AND FRAMES - BLACK BENJAMIN MOORE, COLOR: XXXX "XXX", SEMI-GLOSS SCALE: 3/8" = 1'-0" DOOR AND FRAME ELEVATIONS1 SUBMITTAL REGISTRY SECTION DESCRIPTION REQUIRED SUBMITTALS 03 54 00 - CAST UNDERLAYMENT FLOOR LEVELER PRODUCT DATA 05 50 00 - METAL FABRICATIONS UNISTRUT PLATFORM SYSTEM PRODUCT DATA, SHOP DRAWINGS 07 84 13 - PENETRATION FIRESTOPPING WALL AND FLOOR PENETRATION FIRESTOPPING PRODUCT DATA 07 92 00 - SEALANTS PRODUCT DATA 08 11 13 - HOLLOW METAL DOORS AND FRAMES STILE AND RAIL, FLUSH, AND FRAMES PRODUCT DATA, SHOP DRAWINGS 08 71 00 - DOOR HARDWARE LOCKSETS, HINGES, CLOSERS, AND FLUSH BOLTS PRODUCT DATA 08 80 00 - GLAZING FULLY TEMPERED GLASS PRODUCT DATA 09 65 00 - RESILIENT FLOORING SHEET VINYL AND BASE PRODUCT DATA 09 68 13 - TILE CARPETING CARPET TILE AND VINYL BASE PRODUCT DATA 09 91 23 - INTERIOR PAINTING LATEX PAINT FOR WALLS, DOORS/ FRAMES, AND CABINETS PRODUCT DATA 12 35 53 - LABORATORY CASEWORK ADA SINK CABINET, BASE CABINETS, SHELVING AND COUNTERTOP PRODUCT DATA, SHOP DRAWINGS 1 08/04/2020 ISSUE FOR DD REVIEW 2 09/01/2020 ISSUE FOR 90% REVIEW 3 09/29/2020 ISSUE FOR COORDINATED REVIEW 4 10/12/2020 ISSUE FOR CONSTRUCTION B00EA B00CC B00SC B00JB B01 B02B06 B05 B08B14 B40A B40 B40B B49 B53 B55 B57 B78 B59 B00UA B56 B54 B52 B50 B48 B46 B00UC B40C B00UL B14B B14A B00UM B00CD B00UN B00US B00EB B00TA B00UH B00TB B00UG B00UP B00UF B00JA B00SB B00CA B00SA B00UB B00UE B00UD B00JC B00UR B14C B00CA B00CA B11 B00SE UP UP UP UP 101 102104 103105 106108 107 110114 116120 120B 124 126 128 130 132 142 144 148 115 145 145B 155B 155 155A 165 165B 167E 167D 167C 167B 167A168169170B170A 170 160162 152 100CD 100EB 100CE 167 167F 100JA 100UA 100UB 100SA 100CJ 100CG 100UF 100CK 100CA100CF 100CL 100CN 100UC 100SB 100JC 100SC 100CC 100TC 100TA 100JB 100UD 100TB 145A 100CM 167G 100TD 142A 148A 158 158B 156 100UR 146 100CA B00SE 148B 136 OPEN TO BELOW 111 100EA 100CP UP UP DN UP UP DN UP UPDN UP DN UP DN DN AREA OF WORK IN ROOMS B40B AND B40 (LEVEL 2 ALTERATION) COMMON PATH OF EGRESS: 52 FEET (IBC 1006.1.2: MAX 100' WITH SPRINKLER SYSTEM) TRAVEL DISTANCE TO EXIT: 112 FEET (IBC 1017.2: MAX 300' WITH SPRINKLER SYSTEM) TRAVEL DISTANCE TO EXIT: 80 FEET (IBC 1017.2: MAX 300' WITH SPRINKLER SYSTEM) COMMON PATH OF EGRESS: 30 FEET (IBC 1006.1.2: MAX 100' WITH SPRINKLER SYSTEM) OLIN B-CA2 ESTABLISHED CONTROL AREA 2020 OLIN B-CA1 ESTABLISHED CONTROL AREA 2015 OLIN 1-CA1 2020 MODIFICATION (RENOVATIONS TO ROOM 103, 105, 107 NOT IN SCOPE OF WORK) OF ESTABLISHED CONTROL AREA 2014 OLIN 1-CA2 2020 MODIFICATION (THIS PROJECT) OF ESTABLISHED CONTROL AREA 2014 AREA OF WORK IN ROOM 108 (LEVEL 2 ALTERATION) COMMON PATH OF EGRESS: 27 FEET (IBC 1006.1.2: MAX 100' WITH SPRINKLER SYSTEM) TRAVEL DISTANCE TO EXIT: 95 FEET (IBC 1017.2: MAX 300' WITH SPRINKLER SYSTEM) 1-HOUR FIRE SEPARATION 2-HOUR FIRE SEPARATION TRAVEL DISTANCE TO EXIT COMMON PATH OF EGRESS AREA OF WORK - LEVEL 2 ALTERATION CONTROL AREA - OLIN 1-CA2 CONTROL AREA - OLIN 1-CA1 CONTROL AREA - OLIN B-CA1 CONTROL AREA - OLIN B-CA2 C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION A-002 12809855 CODE COMPLIANCE/ CONTROL AREA PLANS BASEMENT & FIRST FLOOR J. COOLBAUGH JGC 2024 OCTOBER 12, 2020 SCALE: 1/16" = 1'-0"1 CODE COMPLIANCE/ CONTROL AREA PLANS - BASEMENT SCALE: 1/16" = 1'-0"2 CODE COMPLIANCE/ CONTROL AREA PLANS - 1ST FLOOR 0' 8' 16' 32' SCALE: 1/16"=1'-0" CODE COMPLIANCE KEY 1 08/04/2020 ISSUE FOR DD REVIEW 2 09/01/2020 ISSUE FOR 90% REVIEW 3 09/29/2020 ISSUE FOR COORDINATED REVIEW 4 10/12/2020 ISSUE FOR CONSTRUCTION 2 1 3 5 4 9 B40B B40 B00JC B00CD B40C B40A B00UH B00UF 5 6 7 8 8 8 10 10 10 11 12 13 13 EXISTING FLOORING TO REMAIN PREP FLOOR FOR NEW FLOORING ALTERNATE #2 V .I.F. 7' - 5" +/14 15 A-101 2 A-101 3 A-1014 A-1015 A-1016 A-1017 A-101 8 7 9 9 4 13 13 1 3 11 2 15 3 11 2 10 C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION A-101 12809855 PARTIAL BASEMENT DEMOLITION PLAN - ROOM B40 & B40B J. COOLBAUGH JGC 2024 OCTOBER 12, 2020 A-101 KEYED DEMOLITION NOTES 1 REMOVE EXISTING DOOR AND FRAME. 2 REMOVE EXISTING VCT. PREP FLOOR FOR NEW FLOOR FINISH. 3 REMOVE EXISTING BASE CABINETS. 4 REMOVE EXISTING DOOR HARDWARE ONLY, DOOR AND FRAME TO REMAIN. BASE BID. 5 REMOVE EXISTING WALL CABINET. 6 REMOVE EXISTING TALL CABINET. 7 REMOVE EXISTING FLOOR ANCHOR BOLTS. PATCH FLOOR WITH REPAIR MORTAR TO MATCH EXISTING ADJACENT CONDITION. 8 EXISTING WALL CABINET TO REMAIN. PREP FOR PAINTING. 9 REMOVE EXISTING DOOR AND HARDWARE ONLY. FRAME TO REMAIN. TURN DOOR AND HARDWARE OVER TO OWNER. 10 REMOVE EXISTING CURTAIN TRACK TO THE LIMITS SHOWN. PREP FOR NEW LASER TRACK. 11 EXISTING COUNTERTOP TO BE ABATED UNDER A SEPERATE CONTRACT. 12 REMOVE A PORTION OF EXISTING GYPSUM WALL BOARD TO PROVIDE ACCESS FOR PLUMBING. COORDINATE LOCATION WITH PLUMBING DRAWINGS. 13 REMOVE EXISTING DOORS AND FRAME AS PART OF ALTERNATE #1. 14 REMOVE EXISTING DOORS AND HARDWARE. EXISTING FRAME TO REMAIN. 15 REMOVE EXISTING PEGBOARD. # 0' 2' 4' 8' SCALE: 1/4"=1'-0" SCALE: 1/4" = 1'-0"1 PARTIAL BASEMENT DEMOLITION PLAN - ROOM B40 & B40B A-101 GENERAL DEMOLITION NOTES 1.0 CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO THE START OF DEMOLITION. 2.0 CONTRACTOR SHALL COORDINATE REMOVALS WITH ALL ASSOCIATED CONTRACTORS PRIOR TO DEMOLITION. 3.0 CONTRACTOR IS RESPONSIBLE TO REPAIR ANY DAMAGED SUSTAINED TO ADJACENT EXISTING CONDITIONS DURING THE REMOVAL OF EXISTING BUILDING ELEMENTS. NOT TO SCALE2 DEMO PHOTO NOT TO SCALE3 DEMO PHOTO NOT TO SCALE4 DEMO PHOTO NOT TO SCALE5 DEMO PHOTO NOT TO SCALE6 DEMO PHOTO NOT TO SCALE7 DEMO PHOTO NOT TO SCALE8 DEMO PHOTO 1 08/04/2020 ISSUE FOR DD REVIEW 2 09/01/2020 ISSUE FOR 90% REVIEW 3 09/29/2020 ISSUE FOR COORDINATED REVIEW 4 10/12/2020 ISSUE FOR CONSTRUCTION 1270 SF EXG RSV B40B VB PT-1 529 SF EXG CPT B40 VB PT-1 B40C B00CD B40A B00UH B00UF B00JC B40 1 2 6 4 5 5' - 1 1/4" 1' - 8 1/2" 3' - 0 7/8" 3' - 6" 14' - 2" 2' - 6" 2 2 2 3 3 3 3 3 7 7 10 3' - 6 1/4"9 ' - 7 1/4" 1' - 0 1/2" A-102 3 8 3 9 9 14 14 11 B40.1 B40C V.I.F. 7' - 5" +/EXISTING FLOORING TO REMAIN NEW SHEET VINYL FLOORING ALTERNATE #2 12 12 EXISTING FLOORING TO REMAIN NEW SHEET VINYL FLOORING ALTERNATE #2 E4.1 E6 E4 E5 E3 E2 B00CD 13 15 15 15 LIMIT OF CORRIDOR WORK B00CA 16 B40 34" 36" BC-1 48" BC-2 48" BC-3 36" BC-4 36" 18" DEEP OPEN SHELVING, BASIS OF DESIGN: SIGMA FLEX BY MOTT MANUFACTURING OR APPROVED EQUAL ADA STEEL BASE CABINET TRESPA TOPLAB OR APPROVED EQUAL 30" DEEP COUNTERTOPS WITH 4" BACKSPLASH RACEWAY - REFER TO ELECTRICAL DRAWINGS PEGBOARD PROVIDE HINGE FILLER PLATES AND PAINT FRAME PT-3, REFER TO A-001 FOR MORE INFORMATION NEW HOLLOW METAL STILE AND RAIL DOOR AND FRAME, PAINT PT-3. REFER TO A-001 FOR MORE INFORMATION EYE WASH AND FAUCET, REFER TO PLUMBING DRAWINGS FOR MORE INFORMATION PT-1 ROOM NUMBER CEILING FINISH WALL FINISH FLOOR FINISH WALL BASE ROOM AREA 108 E1 E1.2 E1.3 C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION A-102 12809855 PARTIAL BASEMENT RENOVATION PLAN AND FIRST FLOOR EQUIPMENT PLAN J. COOLBAUGH JGC 2024 OCTOBER 12, 2020 0' 2' 4' 8' SCALE: 1/4"=1'-0" SCALE: 1/4" = 1'-0"1 PARTIAL BASEMENT RENOVATION PLAN - ROOM B40 & B40B A-102 KEYED RENOVATION NOTES 1 PATCH EXISTING WALL WHERE CASEWORK WAS REMOVED. MATCH EXISTING ADJACENT CONDITIONS. SPACKLE, SAND, PRIME AND PAINT 2 COATS ENTIRE WALL OR TO LIMITS SHOWN. 2 OWNER PROVIDED LASER CURTAIN (SLC-250W-B) AND MOUNTING SYSTEM (SLCTA) BY KENTEK OR APPROVED EQUAL. OWNER PROVIDED LASER CURTAIN INTERLOCK SYSTEM BY LASER SAFETY SYSTEMS OR APPROVED EQUAL. CONTRACTOR TO INSTALL LASER CURTAIN AS PER MANUFACTURER'S INSTRUCTIONS. 3 NEW FURNITURE BY OWNER. 4 PROVIDE NEW CARPET TILE. SEE SPECS (THIS PAGE) FOR MORE INFORMATION. 5 PROVIDE NEW DOOR HARDWARE. REFER TO DOOR SCHEDULE A-001 FOR MORE INFORMATION. 6 PATCH APPROX 8 HOLES IN FLOOR WITH EUCLID TAMMS THIN PATCH POLYMER-MODIFIED MULTI-USE REPAIR MORTAR OR APPROVED EQUAL. MATCH EXISTING ADJACENT FLOOR CONDITIONS. 7 EXISTING WALL CABINET TO REMAIN. PREP FOR PAINTING. REFER TO SPECS (THIS PAGE) FOR PAINT INFORMTAION 8 PATCH WALL WHERE PLUMBING WAS INSTALLED. MATCH EXISTING ADJACENT CONDITIONS. SPACKLE, SAND, PRIME AND PAINT 2 COATS ENTIRE WALL OR TO LIMITS SHOWN. 9 OWNER SUPPLIED NEW EQUIPMENT AND CONTRACTOR INSTALLED. 10 EXISTING WALL CABINET TO REMAIN. 11 PATCH WALL WHERE PLUMBING WAS REMOVED. MATCH EXISTING ADJACENT CONDITIONS. SPACKLE, SAND, PRIME AND PAINT 2 COATS ENTIRE WALL OR TO LIMITS SHOWN. 12 PROVIDE NEW DOORS AND FRAMES. REFER TO DOOR SCHEDULE/ ELEVATIONS A-001 FOR MORE INFORMATION. ALTERNATE #1 13 PROVIDE NEW FIRE RATED DOORS. REFER TO DOOR SCHEDULE/ ELEVATIONS A-001 FOR MORE INFORMATION. 14 OWNER SUPPLIED EXISTING EQUIPMENT AND CONTRACTOR INSTALLED. 15 FILL ALL VOIDS AND PENETRATIONS THAT ARE NOT FIRE CAULKED ALONG ENTIRE WALL. EXISTING WALLS NEEDS TO MAINTAIN MIN 1 HOUR FIRE RATING. 16 PROVIDE UNISTRUT POLES (TOTAL OF 4) FROM FLOOR TO DECK ABOVE. PROVIDE ALL HARDWARE TO ANCHOR TO FLOOR AND DECK ABOVE. # SCALE: 1/4" = 1'-0"3 INTERIOR ELEVATION OF CASEWORK EXG EXISTING TO REMAIN PT-1 PAINT - INTERIOR WALLS: BENJAMIN MOORE, COLOR: 912 "LINEN WHITE" INTERIOR WALLS: EGGSHELL PT-2 PAINT - METAL CASEWORK: BENJAMIN MOORE, COLOR: 912 "LINEN WHITE" METAL SURFACES: SEMI-GLOSS PT-3 PAINT - DOORS AND FRAMES - BLACK BENJAMIN MOORE, COLOR: XXXX "XXX", SEMI-GLOSS CPT CARPET TILE - TBD VB VINYL BASE - TBD RSV RESILIENT SHEET VINYL FLOORING -TBD - ALTERNATE #2 FINISH LEGEND (BASIS-OF-DESIGN PRODUCTS) CABINET LEGEND (BASIS-OF-DESIGN PRODUCTS) BC-1 MOTT - STEEL ADA COMPLIANT SINK BASE CABINET (158KS22) COLOR: WHITE BC-2 MOTT - STEEL BASE CABINET WITH DRAWERS (1510022) COLOR: WHITE BC-3 MOTT - STEEL BASE CABINET WITH DRAWERS (1410041) COLOR: WHITE BC-4 MOTT - STEEL BASE CABINET WITH DRAWERS (1410014) COLOR: WHITE COUNTERTOP - TRESPA TOPLAB, 30" DEEP COUNTERTOPS WITH 4" BACKSPLASH LAB EQUIPMENT LIST TAG ROOM FURNISHED BY RIGGED & MOUNTED BY EQUIPMENT DESCRIPTION MANUFACTURER MODEL LOCATION WIDTH (IN) DEPTH (IN) HEIGHT (IN) E1 108 OWNER OWNER RHEOMETER TA INSTRUMENTS DHR BENCH 14 19 36 E1.2 108 OWNER OWNER RECIRCULATING WATER BATH POLYSCIENCE MX SERIES BENCH - - E1.3 108 OWNER OWNER AIR COMPRESSOR JUN-AIR 1770008 UNDER COUNTER 18 28 17 E2 B40B OWNER OWNER LASER COHERENT PL-501 OPTICS TABLE 2 6 3 E3 B40B OWNER OWNER SYRINGE PUMP CETONI NEMESYS OPTICS TABLE 3 12 4 E4 B40B OWNER OWNER OPTICS VIBRATION ISOLATION TABLE (PNUEMATIC) NEWPORT RPR-48-8 FLOOR 96 48 36 E4.1 B40B OWNER OWNER OPTICS VIBRATION ISOLATION TABLE (PNUEMATIC) NEWPORT RS2000-48-8 FLOOR 96 48 36 E5 B40B EXISTING OWNER OPTICS VIBRATION ISOLATION TABLE (PNUEMATIC) MELLES GRIOT - FLOOR 96 48 36 E6 B40B EXISTING OWNER OPTICS VIBRATION ISOLATION TABLE (MANUAL) - - FLOOR 96 48 36 SCALE: 1/4" = 1'-0"2 PARTIAL FIRST FLOOR EQUIPMENT PLAN 1 08/04/2020 ISSUE FOR DD REVIEW 2 09/01/2020 ISSUE FOR 90% REVIEW 3 09/29/2020 ISSUE FOR COORDINATED REVIEW 4 10/12/2020 ISSUE FOR CONSTRUCTION F F 1 1 1 1 2 A-103 2 2 3 3 MODIFY EXISTING METAL VALANCE TO ACCOMMODATE NEW TRACK SYSTEM. PROVIDE NEW BENT METAL PANEL TO MATCH RADIUS OF TRACK. RIVET TO EXISTING VALANCE. 2 2 2 2 2 2 EXISTING CEILING TILE AND GRID TO REMAIN EXISTING METAL VALANCE TO REMAIN. MODIFY VALANCE AT TRACK RADIUS. PROVIDE CURVED METAL VALANCE TO MATCH TRACK RADIUS. SEE A1/A-103 REFLECTED CEILING PLAN FOR LOCATION. OWNER PROVIDED AND CONTRACTOR INSTALLED, LASER CURTAIN (SLC-250W-B) AND MOUNTING SYSTEM (SLCTA) BY KENTEK OR APPROVED EQUAL. OWNER PROVIDED AND CONTRACTOR INSTALLED, LASER CURTAIN INTERLOCK SYSTEM BY LASER SAFETY SYSTEMS OR APPROVED EQUAL. EXISTING CEILING SUPPORTS TO REMAIN C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION A-103 12809855 REFLECTED CEILING PLAN J. COOLBAUGH JGC 2024 OCTOBER 12, 2020 0' 2' 4' 8' SCALE: 1/4"=1'-0" SCALE: 1/4" = 1'-0"1 REFLECTED CEILING PLAN A-103 KEYED RENOVATION NOTES 1 OWNER PROVIDED AND CONTRACTOR INSTALLED, NEW LASER CURTAIN (SLC-250W-B) AND MOUNTING SYSTEM (SLCTA) BY KENTEK OR APPROVED EQUAL. OWNER PROVIDED AND CONTRACTOR INSTALLED, LASER CURTAIN INTERLOCK SYSTEM BY LASER SAFETY SYSTEMS OR APPROVED EQUAL. 2 PROVIDE HORIZONTAL P1000 SERIES UNISTRUT 6’ LONG AT ROUGHLY 4’ O.C. ATTACHED TO THE FLOOR/ BEAMS ABOVE WITH (2) UNISTRUT P1049 AND (2) ½” IN. DIAMETER EXPANSION ANCHORS EACH SIDE, POWER STUD SD2+ BY POWERS/DEWALT. PROVIDE A MINIMUM 2 ½” INCH OF EMBEDMENT AND INSTALL PER MANUFACTURER REQUIREMENTS INCLUDING MINIMUM EDGE DISTANCE. COORDINATE FINAL LOCATIONS WITH OWNER. 3 REINSTALL SUSPENDED CEILING SYSTEM AFTER THE COMPLETION OF MECHANICAL, ELECTRICAL, AND PLUMBING WORK. REPLACE ANY DAMAGED PIECES WITH NEW ACOUSTICAL CEILING PANELS AND GRID TO MATCH EXISTING. # SCALE: 1 1/2" = 1'-0"2 SECTION AT CURTAIN TRACK SCALE: 1-1/2"=1'-0" 6" 1'0" 3" 1 08/04/2020 ISSUE FOR DD REVIEW 2 09/01/2020 ISSUE FOR 90% REVIEW 3 09/29/2020 ISSUE FOR COORDINATED REVIEW 4 10/12/2020 ISSUE FOR CONSTRUCTION C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION M-001 12809855 GENERAL NOTES AND SYMBOL LEGENDS S. BURKE SLB 2024 OCTOBER 12, 2020 MECHANICAL ABBREVIATIONS BCU BLOWER COIL UNIT CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CC CLEAN CONDENSATE CO CLEAN OUT CS CLEAN STEAM CD CONDENSATE DRAIN EA EXHAUST AIR EG EXHAUST AIR GRILLE FD FIRE DAMPER GWR GLYCOL HEATING RETURN GWS GLYCOL HEATING SUPPLY HPR HIGH PRESSURE STEAM RETURN HPS HIGH PRESSURE STEAM SUPPLY HWR HOT WATER HEATING RETURN HWS HOT WATER HEATING SUPPLY LPC LOW PRESSURE CONDENSATE LPS LOW PRESSURE STEAM MU MAKE UP WATER MPC MEDIUM PRESSURE CONDENSATE MPS MEDIUM PRESSURE STEAM NG NATURAL GAS PCWR PROCESS CHILLED WATER RETURN PCWS PROCESS CHILLED WATER SUPPLY HG REFRIGERANT HOT GAS RL REFRIGERANT LIQUID RS REFRIGERANT SUCTION RAG RETURN AIR GRILLE SA SUPPLY AIR SD SUPPLY AIR DIFFUSER VD VOLUME DAMPER MECHANICAL SYMBOLOGY AIRFLOW BACKFLOW PREVENTER BALANCE VALVE BALL VALVE BOTTOM PIPE CONNECTION BUTTERFLY VALVE CAP OR PLUG CHECK VALVE CIRCULATING PUMP DIRECTION OF FLOW DUCT AIRFLOW DUCT DOWN (EXHAUST OR RETURN) DUCT DOWN (SUPPLY) FIRE AND SMOKE DAMPER IN DUCT FIRE DAMPER IN DUCT FLANGE CONNECTION FLEX CONNECTOR FLEXIBLE CONNECTION FLEXIBLE DUCT FLOW METER FLOW SWITCH FUSIBLE LINK VALVE GLOBE VALVE MANUAL AIRVENT ORIFICE METER PIPE DOWN PIPE UP PIPING REDUCER (CONCENTRIC) PIPING REDUCER (ECCENTRIC) PRESSURE GAUGE PRESSURE OR TEMPERATURE PETES PLUG PRESSURE REDUCING VALVE PRESSURE SWITCH RECTANGULAR ELBOW RECTANGULAR ELBOW WITH TURNING VANES RELIEF VALVE SMOKE DAMPER IN DUCT SOLENOID VALVE STANDARD BRANCH DUCT STEAM TRAP STRAINER (DUPLEX) STRAINER WITH BLOWDOWN VALVE AND CAP SUPPLY THROUGH NEXT FLOOR OR ROOF TEMPERATURE WELL THERMOMETER THERMOMETER (DIAL) TOP PIPE CONNECTION TRIPLE DUTY VALVE UNION CONNECTION VACUUM BREAKER VOLUME DAMPER IN DUCT CONTROL SYMBOLOGY 2-WAY CONTROL VALVE, DIGITAL 2-WAY CONTROL VALVE, PNEUMATIC 3-WAY CONTROL VALVE, DIGITAL 3-WAY CONTROL VALVE, PNEUMATIC ADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE) AIRFLOW CONTROL VALVE (VENTURI OR VORTEX SHEDDING) AVERAGING SENSOR BINARY POINT BUTTERFLY CONTROL DAMPER CARBON DIOXIDE SENSOR CONDENSATE SENSOR CURRENT SENSOR DEW-POINT SENSOR DIFFERENTIAL PRESSURE SENSOR DIFFERENTIAL PRESSURE SENSOR ELECTRIC TO PNEUMATIC SWITCH ELECTRIC TO PNEUMATIC TRANSDUCER END SWITCH FLOW ELEMENT (METER) FLOW SENSOR HIGH LEVEL SWITCH HUMIDSTAT SENSOR LIQUID IMERSION TEMPERATURE SENSOR LOW LEVEL SWITCH MODULATING MOTOR MOTOR STARTER NETWORK COMMUNICATION POINT, BACnet MSTP OCCUPANCY SENSOR OPEN/CLOSE OPPOSED BLADE CONTROL DAMPER PARALLEL BLADE CONTROL DAMPER PNEUMATIC THERMOSTAT PRESSURE SENSOR PRESSURE SWITCH RELATIVE HUMIDITY SENSOR RELAY ROOM TEMPERATURE SENSOR WITH ADJUSTABLE THERMOSTAT ROOM TEMPERATURE SENSOR WITH OCCUPANCY OVERRIDE ROOM TEMPERATURE SENSOR WITH ON/OFF SWITCH ROOM TEMPERATURE SENSOR WITH VISUAL DISPLAY ROTATION DETECTOR SINGLE POINT SENSOR SMOKE DETECTOR SPEED COMMAND START/STOP STATIC PRESSURE SENSOR SWITCH TEMPERATURE SENSOR TEMPERATURE SENSOR TEMPERATURE SENSOR WITH ADJUSTABLE SETPOINT GENERAL DRAWING SYMBOLOGY DEMOLISHED WORK EXISTING PIPING TO REMAIN EXISTING TO REMAIN EXISTING WORK TO REMAIN NEW WORK POINT OF CONNECTION POINT OF DISCONNECTION CONTROL ABBREVIATIONS AI ANALOG INPUT AO ANALOG OUTPUT AV ANALOG VALUE BI BINARY INPUT BO BINARY OUTPUT BV BINARY VALUE F.L. FAIL LAST N.C. NORMALLY CLOSED N.O. NORMALLY OPEN VFD VARIABLE FREQUENCY DRIVE MECHANICAL SCOPE OF WORK 1.0 DEMO LAB AIR TRANSFER GRILLES. 2.0 MOVE SUPPLY DIFFUSER AND SUSPEND FOR NEW WORK STATIONS. 3.0 INSTALL EXHAUST GRILLE WITHIN CURTAIN AREA OF B40B TO BALANCE PRESSURIZATION. 4.0 REBALANCE EXHAUST. 5.0 -.6.0 -.7.0 -.8.0 -.9.0 -.10.0 -.11.0 -.12.0 -.13.0 -.14.0 -.15.0 -.MECHANICAL GENERAL NOTES 1.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND CLEAR DIMENSIONS. 2.0 PNEUMATIC TERMINATIONS: IF COPPER: DEMO BACK TO MAIN AND PROVIDED SOLDERED END CAP IF POLY: DEMO BACK TO MAIN AND PROVIDE BRASS PLUG DO NOT USE SHEETMETAL SCREW OR BEND OVER END OF COPPER TUBE. 3.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR. EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE CORRECTED. 4.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION, FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK REQUIRED AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER TO ACCESS SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE UNIVERSITY. 5.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED AREAS. 6.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING. 7.0 TESTING AND BALANCING: THE CONTRACTOR SHALL BALANCE ALL AIR SYSTEMS AS INDICATED. SUBMIT RESULTS OF TESTING AND BALANCING ON STANDARD TAB CONTRACTOR'S FORMS TO THE ENGINEER FOR REVIEW. SYSTEMS SHALL BE BALANCED TO WITHIN +/- 10% OF DESIGN VALUES. FINAL BALANCING SHALL OCCUR AFTER ALL LEAKS IN THE BUILDING ENVELOPE HAVE BEEN IDENTIFIED AND SEALED. 8.0 SEAL ALL PIPE, GRILLE, DIFFUSER, DUCT, CONDUIT PENETRATIONS WITH APPROPRIATE MATERIALS (CAULK, FOAM, ETC,) THAT ARE IMPENETRABLE TO THE CONTAINED ORGANISMS AND WITHSTAND REPEATED DECONTAMINATIONS WITH CLEANING AGENTS. MECHANICAL SUBMITTAL SCHEDULE SECTION TITLE REQUIRED 230000 HEATING, VENTILATING & AIR-CONDITIONING 230517 SLEEVES AND SLEEVE SEALS FOR HVAC PIPING PRODUCT DATA 230518 ESCUTCHEON FOR HVAC PIPING PRODUCT DATA 230519 METERS AND GAGES FOR HVAC EQUIPMENT PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 230523 GENERAL DUTY VALVES FOR HVAC PIPING PRODUCT DATA 230529 HANGERS & SUPPORTS FOR HVAC PRODUCT DATA 230543 MECHANICAL VIBRATION AND MOVEMENT CONTROL PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 230553 IDENTIFICATION FOR HVAC COMPONENTS PRODUCT DATA 230593 TESTING, ADJUSTING & BALANCING FOR HVAC QUALIFICATIONS, INSPECTION AND TEST REPORTS 230700 HVAC INSULATION PRODUCT DATA 230719 HVAC PIPING & EQUIPMENT INSULATION PRODUCT DATA 230900 INSTRUMENTATION & CONTROL FOR HVAC PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 230920 ANALOG LABORATORY CONTROL PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 230923 DIRECT DIGITAL CONTROL SYSTEM FOR HVAC PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 230924 AUTOMATION & CONTROL SYSTEM PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 231000 FACILITY FUEL SYSTEMS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 232000 HVAC PIPING AND PUMPS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 232113 HYDRONIC PIPING PRODUCT DATA 232123 HYDRONIC PUMPS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 233100 DUCTWORK PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 233113 METAL DUCTS PRODUCT DATA 233116 NONMETAL DUCTS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 233300 AIR DUCT ACCESSORIES PRODUCT DATA 233400 HVAC FANS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 233600 AIR TERMINAL UNITS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 233700 AIR OUTLETS AND INLETS PRODUCT DATA 234000 HVAC AIR CLEANING DEVICES PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 235000 CENTRAL HEATING EQUIPMENT PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 236000 CENTRAL COOLING EQUIPMENT PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 237000 CENTRAL HVAC EQUIPMENT PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 238200 TERMINAL HEATING AND COOLING UNITS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 238210 FAN COIL COOLING UNITS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 239000 UNASSIGNED 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% CD REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION 24x14 RA(E) 35x16 SA(E) 44x16 RA(E) 20x10 EA(E) 20x10 EA(E) 35x16 SA(E) 32x16 SA(E) 29x16 SA(E) 27x14 SA(E) 23x14 SA(E) 10x10 EA(E) 40x12 RA(E) 10x8 RA(E) 6ø RA(E) 44x12 RA(E) 24x12 EA(E) 20x14 RA(E) EG-1 1045 CFM EG-1 1400 CFM VSV-B40BVEV-B40B SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM SD-1 122 CFM 3 SD-1 100 CFM 2 20x10 EA(E) EG-2 244 CFM EG-3 244 CFM 3 UP TO ABOVE CEILING 4 SD-1 122 CFM OS OS UP TO ABOVE CEILING 1 1 1 1 24x14 RA(E) 35x16 SA(E) 44x16 RA(E) 20x10 EA(E) 20x10 EA(E) 35x16 SA(E) 32x16 SA(E) 29x16 SA(E) 27x14 SA(E) 23x14 SA(E) 10x10 EA(E) 40x12 RA(E) 10x8 RA(E) 6ø RA(E) 44x12 RA(E) 24x12 EA(E) 20x14 RA(E) 2 3 B40B Room B40 Room B40A Room B00CD Room B00UH Room B00UM Room 3 C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION M-101 12809855 PARTIAL BASEMENT MECHANICAL FLOOR PLANS S. BURKE SLB 2024 OCTOBER 12, 2020 # 0' 4' 8' 16' SCALE: 1/8"=1'-0" M-101 KEYED DEMOLITION NOTES 1 REMOVE TRANSITION GRILLS AND DEMO EXISTING TRANSFER DUCTWORK. 2 REMOVE EXISTING LINEAR SLOT SUPPLY DIFFUER AND FLEX DUCT AND SAVE FOR REUSE. PREPARE FOR NEW CONSTRUCTION. 3 DEMO SECTION ON 20"X10" EXHAUST DUCTWORK. PREPARE FOR NEW CONSTRUCTION. # M-101 KEYED RENOVATION NOTES 1 INSTALL NEW CEILING MOUNTED OCCUPANCY SENSOR SIMILAR TO ACUITY CM-10 PDT IN CENTER OF CEILING TILE AND LOCATE PER MANUFACTURERS RECCOMENDATIONS. CONNECT TO POWER PACK SIMILAR TO ACUITY SP20. USE ALL OCCUPANCY SENSORS TO DETERMINE IF ROOM IS OCCUPIED PER CONTROLS DRAWINGS ON M-401. 2 REUSE EXISTING LINEAR SLOT DIFFUSER AND SUSPEND FROM CEILING BETWEEN WALL AND 35"X16" DUCTWORK. SUPPORT WITH HANGERS FROM ABOVE. SUPPLY AIR TO SERVE WORK SPACES BELOW. BALANCE AIRFLOW TO 103 CFM. 3 CONNECT NEW 8" DIAMETER EXHAUST DUCT TO EXISTING 20"X10" EXHAUST DUCT. INSTALL BALANCING DAMPERS ON EXISTING 20"X10" EXHAUST DUCT AND NEW 8"DIA. EXHAUST DUCT. RUN 8" DIAMETER DUCT BELOW CEILING UNTIL IT CLEARS STRUCTURAL CEMENT MEMBER. TRANSITION DUCT TO RUN ABOVE CEILING OVER CURTAIN WALL. INSTALL LINEAR SLOT EXHAUST DIFFUSER IN CEILING TO MATCH EXISTING LINEAR SLOT SUPPLY DIFFUSER. 4 CONNECT NEW B40B OCCUPANCY SENSORS TO VEV-B40B (EXISTING). SCALE: 1/8" = 1'-0"1 PARITAL BASEMENT CONSTRUCTION PLAN SCALE: 1/8" = 1'-0"2 PARTIAL BASEMENT DEMOLITION PLAN 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% CD REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION BACnet / ARCNET OR BACnet / MSTP AV: FLOW FEEDBACK (CFM) AV: POSITION FEEBACK (%) AV: FLOW SETPOINT (CFM) BACnet / ARCNET OR BACnet / MSTP AV: FLOW FEEDBACK (CFM) AV: POSITION FEEBACK (%) AV: FLOW SETPOINT (CFM) OS MOD MOD BI T AI sa d COM COM EVAVSVAV AI T AV SETPOINT AO REHEAT COIL AO AO ANI T ANI H AV: HEATING STPT AV: COOLING STPT C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION M-401 12809855 MECHANICAL BUILDING AUTOMATION AND CONTROL SYSTEM DETAIL S. BURKE SLB 2024 OCTOBER 12, 2020 SYSTEM DESCRIPTION GENERAL EXHAUST AIR VAV (EXISTING) SUPPLY AIR VAV (EXISTING) REHEAT COIL (EXISTING) GENERAL THE ZONE IS CONTROLLED THROUGH THE BUILDING AUTOMATION AND CONTROL SYSTEM (BACS). ALL SETPOINTS SHALL BE ADJUSTABLE. THE BACS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR SEVEN DIFFERENT DAILY SCHEDULES PER WEEK. THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS. SETPOINTS SPACE COOLING TEMPERATURE SETPOINTS: OCCUPIED: 75 °F ± 1.5 °F OCCUPIED SETBACK: 75 °F + 3 °F UNOCCUPIED: 75 °F + 6 °F SPACE HEATING TEMPERATURE SETPOINTS: OCCUPIED: 70 °F ± 1.5 °F OCCUPIED SETBACK: 70 °F - 3 °F UNOCCUPIED: 70 °F - 6 °F AIRFLOW SETPOINTS: REFER TO AIRFLOW SCHEDULE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRI AIRFLOW CONTROL VAV POSITIONS SHALL BE BASED ON MODE. UNDER NORMAL CONTROL, ROOM OCCUPANCY SHALL BE DETERMINED VIA ROOM OCCUPANCY SENSORS. WHEN THE ROOM IS OCCUPIED, THE GENERAL EXHAUST AIR VAV SHALL MODULATE TO MAINTAIN THE OCCUPIED AIR CHANGE RATE. THE SUPPLY AIR VAV SHALL MODULATE TO MAINTAIN THE INDICATED AIRFLOW DIFFERENTIAL. WHEN THE ROOM IS UNOCCUPIED, THE GENERAL EXHAUST AIR VAV SHALL MODULATE TO MAINTAIN THE UNOCCUPIED AIR CHANGE RATE. THE SUPPLY AIR VAV SHALL MODULATE TO MAINTAIN THE INDICATED AIRFLOW DIFFERENTIAL. RM B40B IS A LAB AND IS DESIGNATED TO MAINTAIN NEGATIVE TO ADJACENT PUBLIC CORRDOR. SPACE TEMPERATURE CONTROL, HEATING OCCUPIED HEATING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, AND THE TEMPERATURE FALLS BELOW THE OCCUPIED SPACE HEATING TEMPERATURE SETPOINT, THE REHEAT COIL CONTROL VALVE SHALL MODULATE AS NEEDED TO MAI NTAIN THE SPACE AT THE OCCUPIED HEATING TEMPERATURE SETPOINT. OCCUPIED HEATING SETBACK: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, AND THE TEMPERATURE FALLS BELOW THE OCCUPIED SETBACK HEATING TEMPERATURE SETPOINT, THE REHEAT COIL CONTROL VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE SPACE AT THE OCCUPIED SETBACK HEATING TEMPERATURE SETPOINT. UNOCCUPIED HEATING: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, AND THE TEMPERATURE FALLS BELOW THE UNOCCUPIED SPACE HEATING TEMPERATURE SETPOINT, THE REHEAT COIL CONTROL VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE SPACE AT THE UNOCCUPIED HEATING TEMPERATURE SETPOINT. WHEN THE SPACE TEMPERATURE IS AT SETPOINT, THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED. SPACE TEMPERATURE CONTROL, COOLING OCCUPIED COOLING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, AND THE SPACE TEMPERATURE RISES ABOVE THE OCCUPIED COOLING TEMPERATURE SETPOINT, COOLING CONTROL SHALL OVERRIDE AIR CHANGE RATE CONTROL. THE GENERAL EXHAUST AIR VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN THE SPACE AT THE OCCUPIED COOLING TEMPERATURE SETPOINT. THE SUPPLY AIR VALVE SHALL MODULATE TO MAINTAIN THE INDICATED AIRFLOW DIFFERENTIAL. OCCUPIED COOLING SETBACK: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, AND THE SPACE TEMPERATURE RISES ABOVE THE OCCUPIED SETBACK COOLING TEMPERATURE SETPOINT, COOLING CONTROL SHALL OVERRIDE AIR CHANGE RATE CONTROL. THE GENERAL EXHAUST AIR VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN THE SPACE AT THE OCCUPIED SETBACK COOLING TEMPERATURE SETPOINT. THE SUPPLY AIR VALVE SHALL MODULATE TO MAINTAIN THE INDICATED AIRFLOW DIFFERENTIAL. UNOCCUPIED COOLING: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, AND THE SPACE TEMPERATURE RISES ABOVE THE UNOCCUPIED COOLING TEMPERATURE SETPOINT, COOLING CONTROL SHALL OVERRIDE AIR CHANGE RATE CONTROL. THE GENERAL EXHAUST AIR VALVE SHALL MODULATE OPEN AS NEEDED TO MAINTAIN THE SPACE AST THE UNOCCUPIED COOLING TEMPERATURE SETPOINT. THE SUPPLY AIR VALVE SHALL MODULATE TO MAINTAIN THE INDICATED AIRFLOW DIFFERENTIAL. SEQUENCE OF OPERATIONS SCALE: 1" = 1'-0"1 BUILDING AUTOMATION AND CONTROL SYSTEM DETAIL (B40B) CONTROL AND ALARM POINTS SCHEDULE LAB B40B HARDWARE POINTS SOFTWARE POINTS SHOW ON GRAPHIC NOTESBI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION CV-105-RH, COIL VALVE POSITION COMMAND (%) X 5 DEG F DELTA T ACROSS COIL WITH VALVE COMMANDED CLOSED USE EXISTING POINT EAV-B40B, AIRFLOW (CFM) X X X USE EXISTING POINT EAV-B40B, AIRFLOW SETPOINT (CFM) USE EXISTING POINT EAV-B40B, VALVE POSITION COMMAND (CFM) X X USE EXISTING POINT SAV-B40B, AIRFLOW (CFM) X X X USE EXISTING POINT SAV-B40B, AIRFLOW SETPOINT (CFM) X X USE EXISTING POINT SAV-B40B, VALVE POSITION COMMAND (CFM) X X USE EXISTING POINT 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% CD REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION M-501 12809855 SCHEDULES S. BURKE SLB 2024 OCTOBER 12, 2020 DUCT SPECIFICATIONS SERVICE LOCATION PRESSURE CLASS SEAL CLASS LEAKAGE CLASS RECT LEAKAGE CLASS ROUND MATERIAL LINING INSULATION MIN R-VALUE INSULATION MATERIAL INSULATION FIELD JACKET INSULATION VAPOR RETARDER FINISH SUPPLY: RECTANGULAR, EXPOSED, AHU - VAV 4" POS A 6 3 G90 GALVANIZED NONE R-6 B NONE YES PAINT SUPPLY: RECTANGULAR, CONCEALED, AHU - VAV 4" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE SUPPLY, RECTANGULAR, EXPOSED, TERMINAL UNIT - OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 B NONE YES PAINT SUPPLY, ROUND, EXPOSED, TERMINAL UNIT - OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 D NONE YES PAINT SUPPLY, RECTANGULAR, CONCEALED, TERMINAL UNIT - OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE SUPPLY, ROUND, CONCEALED, TERMINAL UNIT - OUTLET 2" POS A 6 3 G90 GALVANIZED NONE R-6 A NONE YES NONE EXHAUST: LABORATORY HORIZONTAL MAINS 4" NEG A 6 3 G90 GALVANIZED NONE N/A N/A N/A N/A PAINT EXHAUST: LABORATORY - ACCESSIBLE LOCATIONS AND RISERS 4" NEG A 6 3 G90 GALVANIZED NONE N/A N/A N/A N/A PAINT SPECS: 1 ALL DUCTWORK AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN COMPLIANCE WITH THE LATEST ISSUE OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE. 2 CONSTRUCT TEES, BENDS, AND ELBOWS WITH RADIUS OF NOT LESS THAN 1.0 TIMES THE WIDTH OF DUCT ON CENTER LINES. 3 WHERE RECTANGULAR ELBOWS ARE USED, PROVIDE AIR FOIL TYPE TURNING VANES. 4 INCREASE DUCT SIZES GRADUALLY, AND IN COMPLIANCE WITH FIGURE 4-7 OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE. 5 BRANCH CONNECTIONS SHALL BE MADE WITH A 45 DEGREE ENTRY. STRAIGHT TEES ARE NOT ACCEPTABLE. 6 SEALANTS AND GASKETS: SURFACE BURNING CHARACTERISTICS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25, AND MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED TO UL 723. 7 ALL MANUAL BALANCING DAMPERS SHALL BE PROVIDED WITH LOCKING HAND QUADRANT. 8 CONNECT DIFFUSERS TO SUPPLY DUCTS WITH MAXIMUM OF 36-INCHES OF FLEXIBLE DUCT CLAMPED OR STRAPPED IN PLACE. 9 PROVIDE FLEXIBLE CONNECTORS TO CONNECT DUCTS TO EQUIPMENT. 10 INSTALL VOLUME DAMPERS AT POINTS ON SUPPLY, RETURN, AND EXHAUST SYSTEMS WHERE BRANCHES EXTEND FROM LARGER DUCTS. 11 USE BLO-R-VAC PVC HOSE (McMASTER-CARR PART NO 5666K46) MEETING UL 94VO FOR FLAME RETARDANCE TO CONNECT ADA FUME HOODS WITH ADJUSTABLE BASES TO THE EXHAUST SYSTEM. 12 PAINT ALL DUCTWORK EXPOSED TO VIEW IN OCCUPIED AREAS TO MATCH SURROUNDING FINISH. 13 REMOVE SURFACE CONTAMINANTS AND DEPOSITS FROM DUCTWORK AND EQUIPMENT PRIOR TO TESTING AND BALANCING. 14 ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84. TYPE A INSULATION: MINERAL FIBERGLASS BLANKET, ASTM C553 TYPE I, ASTM C1136 TYPE I FACTORY APPLIED FSK JACKET, K-VALUE BETWEEN 0.22 - 0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 0.75 PCF TYPE B INSULATION: MINERAL FIBERGLASS BOARD, ASTM C612 TYPE IA OR IB, ASTM C1136 TYPE I FACTORY APPLIED ASJ JACKET, K-VALUE BETWEEN 0.22 - 0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 3.0 PCF TYPE D INSULATION: MINERAL FIBERGLASS, PREFORMED PIPE INSULATION, ASTM C 547, TYPE I, GRADE A, ASTM C1136 TYPE I FACTORY APPLIED ASJ JACKET, K-VALUE BETWEEN 0.22 - 0.27 BTU-IN/HR-FT²-˚F @ 75 ˚F AIRFLOW SCHEDULE - ROOMS WITHOUT FUME HOODS ROOM # DESCRIPTION ROOM AREA (SF) ROOM HEIGHT (FT) VALVE VALVE SIZE FACTORY RANGE MAX (CFM) FACTORY RANGE MIN (CFM) BACS SETPOINT, MAX HEATING (CFM) BACS SETPOINT, MAX HEATING (ACH) BACS SETPOINT, OCCUPIED (CFM) BACS SETPOINT, OCCUPIED (ACH) BACS SETPOINT, UNOCCUPIED (CFM) BACS SETPOINT, UNOCCUPIED (ACH) SUPPLY AIR VALVE SUPPLY AIR VALVE SIZE SUPPLY AIR, BACS SETPOINT, OCCUPIED (CFM) SUPPLY AIR, BACS SETPOINT, UNOCCUPIED (CFM) 108 RESEACH LAB 380 9' TB-35 (EXISTING TO REMAIN) 10 - - - - 794 13.9 - TB-34 (EXISTING TO REMAIN) 12 1150 72 B40 OFFICE 520 9' B40 6 - - 140 1.8 140 1.8 50 0.6 VSV-B40 (EXISTING TO REMAIN) 4 140 60 B40B RESEACH LAB 1905 9' 8" VEV-B40B (EXISTING TO REMAIN) 14 - - 2295 6.7 2295 6.7 1300 3.8 VSV-B40B EXISTING TO REMAIN - 2050 1050 SPECS: 1ACCEPTABLE MANUFACTURERS: ANEMOSTAT, CARNES, KRUEGER, PRICE, TITUS EG-2 B40B PRICE SDR-75-5 206 8 LINEAR SLOT... ALUMINU M LAY-IN LINEAR SLOT... WHITE SD-1 B40B YORK (REUSE... VARIABLE VOLUME... 103 LINEAR SLOT... ALUMINU M DUCT MOUNT WHITE MANF MODEL TAG# LOCATION SERVED BOD AIRFLOW (CFM) NECK SIZE (IN) TYPE MATERIA L MOUNTING PATTER N FINISH NOTES REGISTER, GRILLE AND DIFFUSER SCHEDULE 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% CD REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION E-001 12715689 GENERAL NOTES AND SYMBOL LEGENDS E. REICHARD ETR 2024 OCTOBER 12, 2020 LUMINAIRE SCHEDULE TYPE DESCRIPTION MOUNTING SIZE MANUFACTURER CATALOG NO. VOLTAGE LAMPS WATTAGE FINISH A-1 RECESSED VOLUMETRIC RECESSED 2X2 LITHONIA 2BLT2-RB-33LHE-ADP-MVOLT-EZ1-LP930 MVOLT LED 26.67 WHITE GENERAL ELECTRICAL NOTES 1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALL BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORK PROCEEDS. 2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREAS FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OF WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROM THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND OPERABLE. 3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE MATERIAL PENETRATED. 4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK. 5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED WITH ASSOCIATED PHASE CONDUCTORS. 6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABEL ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE AND INVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667. 7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL CONDUCTORS. 8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90 DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WET AREAS. 9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTED OTHERWISE. 10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE PANELBOARD. SIZE AS INDICATED. 11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT HANGERS FOR CONDUIT AS NEEDED. 12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE CORRECTED. ELECTRICAL SCOPE OF WORK 1.0 PROVIDE POWER AND LIGHTING DESIGN FOR OLIN B40, B40B AND 108 LAB RENOVATION. ELECTRICAL LEGEND LIGHTING LEGEND MOTOR 1'x4' LUMINAIRE HARDWIRED EQUIPMENT CONNECTION P-1A 12 HOMERUN TO PANEL P-1A, CIRCUIT #12. FED FROM 20A - 1P BREAKER IS INTENDED UNLESS NOTED OTHERWISE. RUN GREEN WIRE GROUND FOR ALL CIRCUITS. PROVIDE ONE GROUND PER CIRCUIT. EMERGENCY POWER OFF (EPO) GROUND ROD ELECTRODE DUPLEX RECEPTACLE WITH GFCI PROTECTION DUPLEX RECEPTACLE WITH AFCI PROTECTION QUAD RECEPTACLE LINETYPES LEGEND SPECIAL RECEPTACLE 5-30R PANELBOARD JUNCTION BOX B = INSTALLED IN BASEBOARD TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT SR = SURFACE RACEWAY WP = WEATHERPROOF AC = AIR CONDITIONER DUPLEX RECEPTACLE: DOUBLE DUPLEX RECEPTACLE MOTOR STARTER J 2'x4' LUMINAIRE CEILING MOUNTED LUMINAIRE EM LIGHTING BATTERY UNIT COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT SINGLE FACE, WALL MOUNT EXIT SIGN DOUBLE FACE, WALL MOUNT EXIT SIGN SINGLE FACE, CEILING MOUNT EXIT SIGN DOUBLE FACE, CEILING MOUNT EXIT SIGN LIGHT SWITCH: SAFETY SWITCH (NON-FUSED) SAFETY SWITCH (FUSED) 3 = 3-WAY SWITCH 4 = 4-WAY SWITCH D = DIMMER SWITCH O = WALL SWITCH OCCUPANCY SENSOR V = WALL SWITCH VACANCY SENSOR W = WIRELESS SWITCH S = WIRELESS SCENE SWITCH WIRELESS OCCUPANCY SENSOR WIRELESS DAYLIGHT SENSOR OS DS 1'x2' LUMINAIRE FIRE ALARM LEGEND FIRE ALARM CONTROL PANEL BATTERY CABINET WATER FLOW SWITCH MUXPAD REMOTE ANNUNCIATOR D = DUCT SMOKE DETECTOR R = RELAY BASE BR = BEAM RECEIVER BT = BEAM TRANSMITTER SB = SOUNDER BASE SMOKE DETECTOR: TAMPER SWITCH AUDIBLE NOTIFICATION APPLIANCE FACP BATT MUX FAA NAC PANELNAC MANUAL PULL STATIONF S X F = FIXED TEMPERATURE R = RATE OF RISE R/F = COMBINATION RISE/FIXED TEMPERATURE HEAT DETECTOR: H X CARBON MONOXIDE DETECTOR CO AM F XXcd C FS F S XXcd C TS ADDRESSABLE MODULE XXcd = CANDELA C = CEILING COMBO A/V NOTIFICATION APPLIANCE: XXcd = CANDELA C = CEILING VISUAL NOTIFICATION APPLIANCE: SUPPRESSION SYSTEM ELECTRICAL ABBREVIATIONS AC AIR CONDITIONER AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AFI ARC FAULT INTERRUPTER AMM ADDRESSABLE MONITOR MODULE AOM ADDRESSABLE OUTPUT MODULE ARB AUXILIARY RELAY BOARD ATS AUTOMATIC TRANSFER SWITCH B BASEBOARD BKR BREAKER C CONDUIT CD CANDELA CKT CIRCUIT CR CONTROL RELAY EC ELECTRICAL CONTRACTOR EMT ELECTRICAL METALLIC TUBING EPO EMERGENCY POWER OFF STATION FAA FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FSD FIRE SMOKE DAMPER GAA GENERATOR ALARM ANNUNCIATOR GFI GROUND FAULT INTERRUPTER GND GROUND HP HORSEPOWER KW KILOWATT LC LIGHTING CONTACTOR LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT LTG LIGHTING MCB MAIN CIRCUIT BREAKER MLO MAIN LUG ONLY MTS MANUAL TRANSFER SWITCH NAC NOTIFICATION APPLIANCE CIRCUIT NIC NOT IN CONTRACT OE OVERHEAD ELECTRIC PC PHOTOCELL PM PLUGMOLD PP POWER PANEL PVC POLYVINYL CHLORIDE CONDUIT RGS RIGID GALVANIZED STEEL CONDUIT SR SURFACE RACEWAY ST SHUNT TRIP TM THERMAL MAGNETIC TR TRIM/CASEWORK/WAINSCOTT TSP TWISTED SHIELDED PAIR TYP TYPICAL UE UNDERGROUND ELECTRIC UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY V VOLTS VA VOLT AMPS WP WATERPROOF UNDERGROUND ELECTRICU E UNDERGROUND LIGHTINGUL OVERHEAD ELECTRICO E TO BE PROVIDED DEMOLITION / TO BE RELOCATED EXISTING TO REMAIN UNDERGROUND TELCOU C MOUNTING HEIGHTS CARD READER 48" TOP OF BOX LIGHT SWITCH 48" TOP OF BOX RECEPTACLE 18" TOP OF BOX DATA OUTLET 18" TOP OF BOX TV OUTLET 84" TOP OF BOX PHONE OUTLET 48" TOP OF BOX SAFETY SWITCH 60" CENTERLINE OF HANDLE MOTOR STARTER 60" CENTERLINE OF HANDLE PANELBOARD 72" TOP OF PANELBOARD MANUAL PULL STATION 48" OPERABLE HANDLE NOTIFICATION APPLIANCE 80" BOTTOM OF LENS DOOR HOLD OPEN COORDINATE IN FIELD EM BATTERY UNIT 96" BOTTOM OF UNIT EM REMOTE UNIT 102" BOTTOM OF UNIT EXIT SIGN 96" BOTTOM OF UNIT LIGHT POLE WITH LED LUMINAIRES, REFER TO PLANS FOR NUMBER AND CONFIGURATION OF HEADS GENERAL ELECTRICAL DEMOLITION NOTES 1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED. REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED OTHERWISE. 2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEW WORK SHALL BE REUSED WHERE POSSIBLE. 3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTING SYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWN TO BE DEMOLISHED. 4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH SURROUNDING MATERIALS, FINISHES, AND COLORS. 5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM DEMOLITION NOT SPECIFIED TO BE INFILLED. 6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING CONSTRUCTION. 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION F F F F PANEL SP4 PANEL SP3 PANEL SP2 PANEL SP1 EM EM SP3/6 SP2/2,4 LEPPB/4,8 SP2/1 SP1/26 B40B B40 B40C B00CD B40A B00UH B00JC 1 2 34 4 4 5 PP2/22 PP2/24 PP2 10 11 DH AM DH PANEL LAB-BC 13 PANEL SP-4 PANEL SP-3 PANEL SP-2 PANEL SP-1 B40B B40 B40C B00CD B40A B00UH B00JC 1 2 3 EM RECEPTACLES 5 EM EM 30A208V 20A 208V EXISTING RECEPTACLE FOR NEW COMPRESSOR 3 3 3 33 33 3 3 3 B40B B40 B40C B00CD B40A B00UH B00JC 4 4 4 4 4 4 4 4 33 DD B40B B40 B40C B00CD B40A B00UH B00JC A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1A -1 A-1 A-1 A-1 A-1A -1A -1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 A-1 7 6 6 7 7 6 6 6 6 DD OS OS OSOS A-1 A-1 8 8 8 8 8 9 12 12 12 C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION E-101 12715689 ELECTRICAL DEMOLITION & RENOVATION PLANS E. REICHARD ETR 2024 OCTOBER 12, 2020 # 0' 4' 8' 16' SCALE: 1/8"=1'-0" E-101 KEYED DEMOLITION NOTES 1 DISCONNECT AND REMOVE THE 250V, NEMA L6-20R TWIST LOCK RECEPTACLE. REMOVE CONDUIT AND CONDUCTORS BACK TO SOURCE. 2 PROVIDE KNOCKOUT COVERS FOR PANEL SP-2 TO COVER EXISTING KNOCKOUTS AND KNOCKOUTS FROM REMOVALS. 3 DISCONNECT AND REMOVE RECEPTACLES ALONG THE EAST WALL BETWEEN THE DOORS. REMOVE CONDUCTORS BACK TO SOURCE AND LABEL SPARE. 4 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVE CONDUIT AND CONDUCTORS BETWEEN FIXTURES. CONDUIT AND CONDUCTORS FOR EXISTING SWITCHES TO REMAIN FOR REUSE WITH NEW LIGHT FIXTURES. 5 DISCONNECT AND REMOVE THE EXISTING EMERGENCY RECEPTACLES ON EAST WALL. REMOVE CONDUIT TO TOP OF ROOM. INSTALL JUNCTION BOX AND SAVE CONDUCTORS FOR REUSE. # E-101 KEYED RENOVATION NOTES 1 PROVIDE SQUARE D, QO, 120V, SINGLE POLE, 10KA, 20A BREAKER IN PANEL SP-1 FOR RECEPTACLE CIRCUIT. 2 PROVIDE THREE SQUARE D, QO, 120V, SINGLE POLE, 10KA, 20A BREAKERS IN PANEL SP-2 FOR RECEPTACLE CIRCUITS. 3 PROVIDE SQUARE D, QO, 120V, SINGLE POLE, 10KA, 20A BREAKER IN PANEL SP-3 FOR RECEPTACLE CIRCUIT. 4 PROVIDE TWO NEMA 5-20R RECEPTACLES ON OVERHEAD UTILITY POST ABOVE TABLE. PROVIDE 2-#12 AND 1-#12 GND IN ¾” EMT FROM PANEL TO SOLID CHANNEL 1-5/8” TYPE STRUT WITH CHANNEL COVER FOR USE AS RACEWAY. MOUNT STRUT VERTICALLY AND PROVIDE RECEPTACLES ALONG FACE OF STRUT RACEWAY, ONE ON EACH SIDE. 5 PROVIDE RECEPTACLES 6” ABOVE COUNTERTOP IN ALUMINUM DIVIDED 3300 RACEWAY TO SPLIT NORMAL AND BACKUP/EM CONDUCTORS. PROVIDE 2-#12 AND 1-#12 GND IN ¾” EMT FROM PANEL TO LOCATION ABOVE CEILING NEAR COUNTERTOP AND TRANSITION TO THE SURFACE RACEWAY. PROVIDE 2-#12 AND 1-#12 GND ¾” EMT (SEPARATE FROM NORMAL POWER CONDUCTORS) FROM JUNCTION BOX WITH SAVED CONDUCTORS FOR EMERGENCY CIRCUITS (LEPPB 4,8) TO LOCATION ABOVE CEILING NEAR COUNTERTOP AND TRANSITION TO THE SURFACE RACEWAY. 6 PROVIDE NEW LIGHT FIXTURE IN LOCATION INDICATED. PROVIDE 2-#12 AND 1-#12 GND IN MC CABLE BETWEEN FIXTURES AND TO POWER PACK FOR CONTROL. RECONNECT TO LINE SIDE CONDUCTORS SAVED FROM REMOVALS FOR POWER. PROVIDE SENSOR SWITCH CM9 OCCUPANCY SENSORS (OR EQUAL) IN LOCATIONS INDICATED WITH A SENSOR SWITCH PP20 (OR EQUAL) POWER PACK MOUNTED IN JUNCTION BOX ABOVE CEILING. PROVIDE SENSOR SWITCH SPODMDSAWH DIMMER SWITCH (OR EQUAL) IN EXISTING 4 GANG BOX AT DOOR SAVED FROM REMOVALS. PROVIDE LOW VOLTAGE WIRING FROM OCCUPANCY SENSOR TO SWITCH, FROM POWER PACK TO SWITCH AND FROM LED DRIVER TO SWITCH. REFER TO WIRING DIAGRAM DETAIL 2 ON DWG E-501 FOR ADDITIONAL INFORMATION. 7 PROVIDE NEW LIGHT FIXTURE IN LOCATION INDICATED. PROVIDE 2-#12 AND 1-#12 GND IN MC CABLE BETWEEN FIXTURES AND TO POWER PACK FOR CONTROL. RECONNECT TO LINE SIDE CONDUCTORS SAVED FROM REMOVALS FOR POWER. PROVIDE A SENSOR SWITCH PP20 (OR EQUAL) POWER PACK MOUNTED IN JUNCTION BOX ABOVE CEILING. PROVIDE SENSOR SWITCH SPODMDSAWH DIMMER SWITCH (OR EQUAL) IN EXISTING SINGLE GANG BOX SAVED FROM REMOVALS. PROVIDE LOW VOLTAGE WIRING FROM POWER PACK TO SWITCH AND FROM LED DRIVER TO SWITCH. REFER TO WIRING DIAGRAM DETAIL 1 ON DWG E-501 FOR ADDITIONAL INFORMATION. 8 PROVIDE BLANK COVER PLATE ON EXISTING SWITCH BOX. 9 PROVIDE 4 GANG WALL PLATE WITH 2 BLANKS FOR NEW DIMMER SWITCHES AT DOOR. PROVIDE 4 GANG ALL PLATE WITH 4 BLANKS FOR BOTTOM BOX AT DOOR. 10 PROVIDE RECEPTACLES IN EXISTING SURFACE RACEWAY. PROVIDE 2-#12 AND 1-#12 GND IN EXISTING RACEWAY AND CONNECT TO EXISTING CIRCUITS AS NOTED. 11 PROVIDE 60W, 120VAC INPUT, 24VDC OUTPUT POWER SUPPLY FOR SYRINGE PUMP. COORDINATE FINAL LOCATION WITH LAB USERS. 12 PROVIDE NEW EMERGENCY LIGHT FIXTURE IN LOCATION INDICATED. FIXUTRE IS TO BE WIRED DIRECTLTY TO EMERGENCY CIRCUIT AND ALWAYS ON. PROVIDE 2-#12 AND 1-#12 GND IN MC CABLE FROM NEW EMERGENCY FIXTURES TO EXISTING EMERGENCY LIGHT IN HALLWAY. 13 PROVIDE 2-#12 AND 1-#12 IN MC FROM PANEL LAB-BC CIRCUIT #2, 20 AMP SPARE BREAKER TO MAGNETIC DOOR HOLDERS VIA FIRE ALARM RELAY MODULE NORMALLY CLOSED CONTACTS. DOOR HOLDERS PROVIDED BY GC. SOUTH DOOR HOLDER IS MOUNTED TO WALL, NORTH DOOR HOLDER IS ON FLOOR. PROVIDE JUNCTION BOX AND SURFACE RACEWAY FROM WALL TO NORTH DOOR HOLDER ON FLOOR. SOUTH DOOR HOLDER IS MOUNTED TO WALL. PAINT BOX AND SURFACE RACEWAY TO MATCH WALL AND FLOOR. PROVIDE AOM-2RF FIRE ALARM RELAY CONTROL MODULE ABOVE CEILING IN 4”X4” JUNCTION BOX AND CONNECT TO SLC WITH 2-#14 IN ½” EMT. SCALE: 1/8" = 1'-0"2 BASEMENT POWER, DATA & FIRE ALARM RENOVATION SCALE: 1/8" = 1'-0"1 BASEMENT POWER, DATA & FIRE ALARM DEMOLITION SCALE: 3/16" = 1'-0"5 1ST FLOOR EXISTING PLAN SCALE: 1/8" = 1'-0"3 BASEMENT LIGHTING DEMOLITION SCALE: 1/8" = 1'-0"4 BASEMENT LIGHTING RENOVATION 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION ON/OFF WH GRY VIO REDBLK WH/BLU RED BLK VIO LINE N WH BLK/OR BLU BLU PP20 POWERPACK DIMMER SWITCH LED DRIVER 2-#18 IN MC3 -#18 IN MC ON/OFF WH GRY VIO REDBLK WH/BLU RED BLK WH VIO WH RED BLK LINE N WH BLK/OR BLU BLU PP20 POWERPACK OCCUPANCY SENSOR DIMMER SWITCH LED DRIVER 2-#18 IN MC3 -#18 IN MC 3-#18 IN MC C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION E-501 12715689 SCHEDULES & DETAILS E. REICHARD JD 2024 OCTOBER 12, 2020 TOTAL AMPS: 0 A 0 A 0 A TOTAL LOAD: 0 VA 0 VA 0 VA 29 30 27 28 25 AIR COND. RM 128 20 1 0 0 1 20 REC EX OPTICS TABLE 26 23 -- -- -- 0 0 1 20 DEDICATED LSR REC W. WALL 24 21 -- -- -- 0 0 -- -- -- 22 19 BAKEOUT OVENS ZASTAR 20 3 0 0 2 20 EXISTING LOAD 20 17 H AREA 6 20 1 0 0 -- -- -- 18 15 F AREA 5 20 1 0 0 2 20 208 REC AREA 1 16 13 E AREA 5 20 1 0 0 1 20 I AREA 7 14 11 L AREA 8 20 1 0 0 1 20 J AREA 7 12 9 K AREA 8 20 1 0 0 1 20 G AREA 6 10 7 M AREA 8 20 1 0 0 1 20 D AREA 1 8 5 D AREA 4 20 1 0 0 1 20 C AREA A 6 3 P AREA 4 20 1 0 0 1 20 B AREA 1-2 4 1 N AREA 2 20 1 0 0 1 20 A AREA 1-2 2 CKT DESCRIPTION TRIP POLES A B C POLES TRIP DESCRIPTION CKT ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 100 A FED FROM: PHASE: 3 MAINS TYPE: MLO LOCATION: VOLTS: 208Y/120V AIC RATING: 10,000 AMPS PANEL SP-1 TOTAL AMPS: 0 A 0 A 0 A TOTAL LOAD: 0 VA 0 VA 0 VA 11 -- -- -- 0 0 -- -- -- 12 9 -- -- -- 0 0 -- -- -- 10 7 NO. 2 50 3 0 0 3 50 NO. 1 8 5 -- -- -- 0 0 1 15 EXISTING LOAD 6 3 LASER POWER 208V 15 2 0 0 1 20 REC NEWPORT TABLE 4 1 REC EAST COUNTER TOP 20 1 0 0 1 20 REC NEWPORT TABLE 2 CKT DESCRIPTION TRIP POLES A B C POLES TRIP DESCRIPTION CKT ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 100 A FED FROM: PHASE: 3 MAINS TYPE: MLO LOCATION: VOLTS: 208Y/120V AIC RATING: 10,000 AMPS PANEL SP-2 TOTAL AMPS: 0 A 0 A 0 A TOTAL LOAD: 0 VA 0 VA 0 VA 11 EXISTING LOAD 20 1 0 0 -- -- -- 12 9 EXISTING LOAD 20 1 0 0 -- -- -- 10 7 -- -- -- 0 0 3 20 EXISTING LOAD 8 5 EXISTING LOAD 30 2 0 6 3 EX OPTICS TABLE 20 1 0 4 1 2 CKT DESCRIPTION TRIP POLES A B C POLES TRIP DESCRIPTION CKT ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 100 A FED FROM: PHASE: 3 MAINS TYPE: MLO LOCATION: VOLTS: 208Y/120V AIC RATING: 10,000 AMPS PANEL SP-3 TOTAL AMPS: 0 A 0 A 0 A TOTAL LOAD: 0 VA 0 VA 0 VA 11 -- -- -- 0 0 1 30 EXISTING LOAD 12 9 220V REC SOUTH EAST WALL 15 2 0 0 -- -- -- 10 7 -- -- -- 0 0 2 15 208V REC SOUTH WALL 8 5 220V REC SOUTH WEST WALL 20 2 0 0 -- -- -- 6 3 -- -- -- 0 0 2 30 220V REC SOUTH EAST WALL 4 1 220V REC WEST WALL 20 2 0 2 CKT DESCRIPTION TRIP POLES A B C POLES TRIP DESCRIPTION CKT ENCLOSURE: Type 1 MOUNTING: Surface WIRES: 4 MAINS RATING: 100 A FED FROM: PHASE: 3 MAINS TYPE: MLO LOCATION: VOLTS: 208Y/120V AIC RATING: 10,000 AMPS PANEL SP-4 NOTES: NEW BREAKERS AND DESIGNATIONS SHOWN IN BOLD. NOTES: NEW BREAKERS AND DESIGNATIONS SHOWN IN BOLD. NOTES: NEW BREAKERS AND DESIGNATIONS SHOWN IN BOLD. NOTES: NEW BREAKERS AND DESIGNATIONS SHOWN IN BOLD. NOT TO SCALE1 LIGHTING CONTOROL WIRING DIAGRAM NOT TO SCALE2 LIGHTING CONTROL WIRING DIAGRAM WITH OCCUPANCY SENSOR NOTES: ADDITIONAL POWERPACK AND WIRING FOR HVAC CONTROL TO BE PROVIDED AND CONNECTED BY OTHERS. COORDINATE WITH HVAC CONTRACTOR. 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION P-001 12809855 GENERAL NOTES AND SYMBOL LEGENDS T. FISHER TRF 2024 OCTOBER 12, 2020 PLUMBING SUBMITTAL SCHEDULE SECTION REQUIRED TITLE 220523 GENERAL DUTY VALVES FOR PLUMBING PIPING PRODUCT DATA 220529 HANGERS & SUPPORTS FOR PLUMBING PRODUCT DATA 220553 ID FOR PIPING AND EQUIPMENT PRODUCT DATA 220719 PLUMBING PIPING INSULATION PRODUCT DATA 221116 DOMESTIC WATER PIPING PRODUCT DATA,TESTING 224500 LABORATORY PLUMBING FIXTURES AND TRIM PRODUCT DATA 224500 EMERGENCY PLUMBING FIXTURES PRODUCT DATA 226113 LABORATORY COMPRESSED AIR PIPING PRODUCT DATA,TESTING 226653 LAB WASTE & LAB VENT PIPING PRODUCT DATA,TESTING PLUMBING SCOPE OF WORK 1.0 B40 - PROVIDE COMPRESSED AIR SERVICE CONNECTIONS AT GENERAL POINTS OF USE AND SUPPLY FOR OPTICS TABLE ISOLATORS. 2.0 B40 - PROVIDE ADA COMPLIANT FAUCET, EYEWASH, PIPING AND ACCESSORIES FOR CASEWORK LAB SINK. 3.0 SELECTIVE DEMOLITION OF EXISTING ABANDONED PIPING. 4.0 EXISTING FIRE PROTECTION SYSTEMS ARE EXISTING TO REMAIN. EXISTING SPACE CONSTRAINTS AND OBSTRUCTIONS ARE TO BE SIMILAR TO EXISTING CONDITIONS. PLUMBING FIXTURE SCHEDULE & SPEC TAG COMPONENTS MANUFACTURER MODEL DESCRIPTION MATERIAL FINISH / COLOR COLD WATER HOT WATER TEPID WATER WASTE / SANITARY VENT STANDARDS F1-B40B LAB SINK FAUCET WATER SAVER L412VB-BH MIXING, GOOSENECK BRASS CHROME PLATED 1/2" 1/2" ADA COMPLIANT DRAIN AND TRAP ORION BLUELINE FRPP NH DRUM TRAP POLYPROPYLENE STANDARD 1-1/2" 1-1/2" NO HUB MECHANICAL JOINT FITTINGS SUPPLY/STOPS T&S BRASS B-1310 ANGLE KEY STOP BRASS STANDARD 1/2" 1/2" 1/2" INLET, OUTLET SHALL MATCH FAUCET CONNECTION SIZE EW-B40 EMERGENCY EYEWASH BRADLEY S19274HDB DECK MOUNTED , SWING DOWN BRASS CHROME PLATED 1/2" 1/2" ADA COMPLIANT PLUMBING PIPING SCHEDULE AND SPECIFICATIONS PIPE SERVICE ABBREVIATION MATERIAL FITTINGS JOINT INSULATION THICKNESS (IN) CONDUCTIVITY (BTU-IN/HR-FT^2-DEGF) MEAN TEMP (DEG F) MATERIAL DOMESTIC COLD WATER DCW ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER, LEAD FREE 1 0.22-0.27 75 TYPE A DOMESTIC HOT WATER DHW ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER, LEAD FREE 1 0.22-0.27 75 TYPE A LAB WASTE & VENT LW/LV ASTM D4101 ASTM D635 POLYPROPYLENE, SCH 40 ASTM D4101 POLYPROPYLENE MECHANICAL N/A N/A N/A N/A COMPRESSED AIR CA ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER, LEAD FREE N/A N/A N/A N/A PIPING ACCESSORIES SCHEDULE AND SPECIFICATIONS TAG DEVICE BOD MANUFACTURER MODEL CAPACITY SPECIFICATIONS MV-B40B MIXING VALVE BRADLEY S19-2000 1.5 GPM MINIMUM FLOW ROUGH BRASS, ANSI Z358.1 COMPLIANT, ASSE 1071 CERTIFIED, FACTORY SETPOINT 85 DEG F. PRV1-B40B PRESSURE REGULATING ASSEMBLY WATERSAVER L2873-366V-758WS 300 PSIG WOG VERTICAL ASSEMBLY, BRASS BODY WITH NEOPRENE DIAPHRAGM, 0-125 PSIG OUTLET RANGE, REMOVABLE QUICK CONNECT FITTING. V-1 SHUT-OFF BALL VALVE(WATER/AIR SERVICE) WATTS B6000-SS 300 PSIG WOG MSS SP-110, 2-PIECE, STANDARD PORT, BRONZE BODY, 316 SS BALL & STEM, PTFE OR TFE SEAT PLUMBING GENERAL NOTES 1.0 DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS. IF DIMENSIONS OR CONDITIONS ARE FOUND TO BE IN CONFLICT WITH THE DRAWINGS, THE CONTRACTOR SHALL IMMEDIATELY REFER THE CONFLICT TO THE ENGINEER. 2.0 UTILITY SHUTDOWNS: SHUTDOWN OF ANY BUILDING UTILITY SYSTEM SHALL BE COORDINATED WITH CUSTOMER SERVICE AT PH: 607-255-5322. THE CONTRACTOR SHALL BEAR THE COST OF THE UTILITY SHUTDOWN. SCHEDULE WORK TEN DAYS IN ADVANCE AND NOTIFY THE OWNER'S REPRESENTATIVE TO COORDINATE BUILDING FUNCTIONS WITH THE BUILDING COORDINATOR. 3.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF OTHER TRADES (EG ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE SPACES OR AREAS TO ORIGINAL CONDITION. 4.0 ALL PENETRATIONS THROUGH FULL HEIGHT WALLS ARE TO BE FIRESTOPPED IN ACCORDANCE WITH UL STANDARDS. ALL GAPS AND JOINTS AT RATED FLOORS, ROOFS AND WALLS ARE TO BE FIRE AND SMOKE STOPPED. CAPS AND JOINTS INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRESTOPPING INCLUDES BOTH FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. 5.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR. EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE CORRECTED. 6.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION, FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK REQUIRED AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER TO ACCESS SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE UNIVERSITY. 7.0 VERIFY FINAL EQUIPMENT/FIXTURE LOCATIONS FOR ROUGHING-IN. 8.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING. 9.0 THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO FORM A COMPLETE, FUNCTIONING SYSTEM. ITEMS NOT SPECIFICALLY MENTIONED, BUT WHICH ARE INHERENTLY NECESSARY TO MAKE A COMPLETE WORKING INSTALLATION SHALL BE PROVIDED. 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% CD REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION SPECIFICATIONS: 1. SOLDER FILLER METALS: ASTM B32, LEAD-FREE ALLOYS. INCLUDE WATER FLUSHABLE FLUX ACCORDING TO ASTM B813. 2. INSTALL PLUMBING SYSTEMS TO FACILITATE SERVICE, MAINTENANCE AND REPAIR OR REPLACEMENT OF COMPONENTS. 3. ALL WASTE PIPING SHALL BE PITCHED AT 1/8" PER FOOT. ALL SUPPLY PIPING SHALL BE PITCHED BACK TOWARDS CONNECTION TO THE ROOM ENTRANCE. 4. PROVIDE VAPOR RETARDER ON PIPING INSULATION SYSTEMS CARRYING FLUIDS WITH AN OPERATING TEMPERATURE LOWER THAN 60 DEGREES F. 5. POLYPROPYLENE PIPING SHALL BE FLAME RETARDANT. 6. ALL PIPING AND INSULATION SYSTEM EXPOSED TO VIEW SHALL BE PAINTED TO MATCH SURROUNDING SURFACES. 7. MAINTAIN INDICATED FIRE RATING OF WALLS, PARITIONS, CEILINGS, AND FLOORS AT PIPE PENETRATIONS. SEAL PIPE PENETRATIONS WITH FIRESTOP MATERIALS. 8. DO NOT ENCLOSE, COVER OR PUT PLUMBING PIPING SYSTEMS INTO OPERATION UNTIL IT HAS BEEN INSPECTED AND APPROVED BY THE AUTHORITIES HAVING JURISDICTION. 9. LEAVE NEW, ALTERED, EXTENDED, OR REPLACED DOMESTIC WATER PIPING UNCOVERED AND UNCONCEALED UNTIL IT HAS BEEN TESTED. EXPOSE WORK THAT WAS COVERED OR CONCEALED BEFORE IT WAS TESTED. 10. PROVIDE PIPE LABLES AND DIRECTIONAL ARROWS ON ALL NEW PIPING SYSTEMS. LABELS SHALL BE PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT ADHESIVE BACKING. LETTERS SHALL BE 1/4-INCH IF VIEWING DISTANCE IS LESS THAN 24 INCHES, 1/2INCH FOR VIEWING DISTANCES UP TO 72 INCHES, AND PROPORTIONATELY LARGER LETTERING FOR GREATER VIEWING DISTANCES. 11. ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84. 12. TESTING OF DOMESTIC WATER PIPING: CAP AND SUBJECT DOMESTIC WATER PIPING TO STATIC WATER PRESSURE OF 50 PSIG ABOVE OPERATING PRESSURE, WITHOUT EXCEEDING PRESSURE RATING OF PIPING SYSTEM MATERIALS ISOLATE TEST SOURCE AND ALLOW TO STAND FOR FOUR HOURS. LEAKS AND LOSS IN TEST PRESSURE CONSTITUTE DEFECTS THAT MUST BE REPAIRED REPAIR LEAKS AND DEFECTS WITH NEW MATERIALS AND RETEST PIPING UNTIL SATISFACTORY RESULTS ARE OBTAINED. 13. TESTING OF LAB WASTE AND VENT PIPING: CAP AND SUBJECT DOMESTIC WASTE AND VENT PIPING TO STATIC WATER PRESSURE OF 10 FEET HEAD PRESSURE ABOVE HIGHEST POINT OF SYSTEM UNDERGOING TEST ISOLATE TEST SOURCE AND ALLOW TO STAND UNTIL SYSTEM CAN BE VISUALLY INSPECTED BY AUTHORITY HAVING JURISDICTION. LEAKS CONSTITUTE DEFECTS THAT MUST BE REPAIRED REPAIR LEAKS AND DEFECTS WITH NEW MATERIALS AND RETEST PIPING UNTIL SATISFACTORY RESULTS ARE OBTAINED. SPECIFICATIONS: 1. PROVIDE PRESSURE GAUGES AT DISCHARGE OF EACH PRESSURE REDUCING VALVE AND WHERE INDICATED. 1 3/4" CA 1 1/2" CA 1 1/2" CA CA DRYER (E) FD (E) 1 B40B Room B40 Room B00CD RoomB40C Room B40A Room B00UH Room B00UM Room B00JC Room B00UF Room 2 3 1-1/2" CAPPED PIPE STUB ABOVE FLOOR (E) CA DRYER AND FILTERS (E) 1 1/2" CA 1 1/2" CA 3/4" CA 1 3/4" CA 1/2" CA 2 7 3 CA B40B Room B40A Room B00UH Room B00CD Room B40 Room B00JC Room B00UF Room B00UM RoomP-101 4 PRV1-B40 PRV1-B40 CA CA 5 P-101 3/4" CA 5 3/4" CA 1/2" CA 1/2" CA E5 E4.1 E4 OPTICS TABLE OPTICS TABLE OPTICS TABLE 9 F1-B40B EW-B40B MV-B40B EYEWASH LAB SINK FAUCET MIXING VALVE 1-1/2" LW 1-1/2" LV 1/2" CW 1/2" HW WITHIN BASE CABINET CHASE 6 PRV1-B40B 8 CA 1/2" CA 4 RHEOMETER (OWNER PROVIDED) E1 E1.2 E1.3 1ST FLOOR 0' - 0" PLATFORM -4' - 6" 1ST FLOOR 0' - 0" OPTICAL TABLE (E) V-1 PRV1-B402 1/2" CA MOUNT PIPING TO UNISTRUT POLE DROP CEILING (E) PROVIDE SPLIT-RING ESCUTCHEON AT PIPING PENETRATIONS THROUGH CEILING TERMINATE PIPING SERVICE WITH SWAGELOCK 1/4" FITTING FOR CONNECTION BY OTHERS V-1 C O R N E L L U N I V E R S I T Y F O U N D E D 5 6 8 1 A D FACILITIES ENGINEERING ARCHIVE BAR CODE ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 113 HO PLAZA ITHACA, NEW YORK 14850 OLIN HALL B40B LAB RENOVATION P-101 12809855 PARTIAL BASEMENT AND FIRST FLOOR PLUMBING PLANS T. FISHER TRF 2024 OCTOBER 12, 2020 SCALE: 1/8" = 1'-0"1 PARTIAL BASEMENT PLUMBING DEMOLITION PLAN SCALE: 1/8" = 1'-0"2 PARTIAL BASEMENT PLUMBING CONSTRUCTION PLAN P-101 KEYED DEMOLITION NOTES 1 DISCONNECT AND REMOVE PORTION OF EXPOSED COMPRESSED AIR PIPING, ACCESSORIES AND VALVES BACK TO ABOVE CEILING. REFER TO 2/P-101 FOR RECONNECTION. 2 DISCONNECT DOMESTIC COLD WATER AND HOT WATER SERVING EXISTING LAB SINK. PREPARE PIPING TO SERVE ADA LAB SINK IN LAB B40. CUT AND PATCH WALL AS REQUIRED TO ACCESS PIPING. PATCH WALL TO MATCH EXISTING. 3 DISCONNECT AND REMOVE 1-1/2" LAB WASTE AND TRAP BACK TO EXISTING RISER IN WALL. PREPARE FOR CONNECTION OF ADA SINK IN LAB B40. CUT AND PATCH WALL AS REQUIRED TO ACCESS PIPING. PATCH WALL TO MATCH EXISTING. P-101 KEYED RENOVATION NOTES 1 CONNECT TO EXISTING COMPRESSED AIR SUPPLY ABOVE CEILING AS REQUIRED TO PROVIDE COMPRESSED AIR CONNECTIONS AT LAB TABLES. 2 PROVIDE COMPRESSED AIR DROP TO BELOW CEILING. MOUNT PIPING TO UTILITY RACK/PLATFORM AND TERMINATE WITH PRESSURE REGULATOR ASSEMBLY AND ONE (1) 1/4" SWAGELOK CONNECTION. AIR SUPPLY TO SERVE OPTICS TABLE PNEUMATIC ISOLATORS. REFER TO 5/P-101. 3 REMOVE EXISITNG FLOOR DRAIN GRATE AND REPLACE WITH GASKETED CLEANOUT TOP. COORDINATE WITH FLOOR FINISH. 4 OWNER PROVIDED POINT OF USE OIL-LESS AIR COMPRESSOR TO SERVE RHEOMETER. NOTED AND SHOWN FOR REFERENCE ONLY. 5 CUT AND PATCH WALL AS REQUIRED TO CONNECT TO EXISTING LAB WASTE, LAB VENT, DOMESTIC COLD, AND DOMESTIC HOT WATER SERVICES WITHIN WALL FOR LAB SINK IN B40. ROUTE PIPING WITHIN BASE CABINET CHASEWAY. 6 INSTALL MIXING VALVE WITHIN SINK BASE CABINET. PROVIDE 1/2" COLD AND 1/2" HOT WATER SUPPLY TO MIXING VALVE. PROVIDE 1/2" TEMPERED WATER SUPPLY FROM MIXING VALVE TO EYEWASH. 7 PROVIDE COMPRESSED AIR DROP TO BELOW CEILING. MOUNT PIPING TO UTILITY RACK/PLATFORM AND TERMINATE WITH PRESSURE REGULATOR ASSEMBLY AND TWO (2) 1/4" SWAGELOK CONNECTIONS. AIR SUPPLY TO SERVE OPTICS TABLE PNEUMATIC ISOLATORS. REFER TO 5/P-101. 8 PROVIDE COMPRESSED AIR DROP TO BELOW CEILING. MOUNT PIPING TO EXISTING WALL AND TERMINATE 6" ABOVE SINK BACKSPLASH WITH PRESSURE REGULATOR ASSEMBLY AND ONE (1) 1/4" SWAGELOK CONNECTION. AIR SUPPLY TO SERVE GENERAL LAB USE/TOOL CONNECTIONS. 9 CUT AND CAP EXISTING 1-1/2" PIPE STUB AT FINISH FLOOR LEVEL AS REQUIRED TO ACCOMODATE FLOOR FINISH. COORDINATE WITH FLOOR FINISH. SCALE: 1/2" = 1'-0"4 ADA LAB SINK CALLOUT DETAIL # # SCALE: 1/4" = 1'-0"3 PARTIAL FIRST FLOOR CONSTRUCTION PLAN SCALE: 1/2" = 1'-0"5 LAB SERVICE CONNECTION ELEVATION 1 08/04/20 ISSUE FOR DD REVIEW 2 09/01/20 ISSUE FOR 90% CD REVIEW 3 09/29/20 ISSUE FOR COORDINATED REVIEW 4 10/12/20 ISSUE FOR CONSTRUCTION 0' 4' 8' 16' SCALE: 1/8"=1'-0" 0' 2' 4' 8' SCALE: 1/4"=1'-0" 0' 1' 2' 4' SCALE: 1/2"=1'-0"