HomeMy WebLinkAboutBartels Hall FA Replacement_Signed Dwgs INDEXEDTEAGLE HALL
SCHOELLKOPF MEMORIAL HALL
2602B
CAMPUS ROAD
LYNAH RINK
2613
CAMPUS ROAD
BARTELS HALL2631
FRIEDMAN
WRESTLINGCENTER
2638
Friedman
Strength
& Conditioning2631A
6
7
8
CB122A
122A
102
10065
10045 10021
10011
103B
103A
103
10060
10061
108
10022
10066
11010047
112D
112C
112B
10067
112A
101
10043 10044
10003 1000410050
10012
10042 10041
10001 10002
112
10052
10040
1000810007
1000610005
10053
10051
10046
10062
DISPLAY CASECONCESSION STAND122
104 106
10064
10048
SEE BASEMENTPLAN
10014
112E
112F
112G
UP
UPDN
UP
UP DN
DN
DN
DN UP DNUP
UP UP
UP
DN
UP
UP
UP UPUPUP10068
115A
115B
115
10054
10015
10014
UP
UP
BARTELS HALL
2631
CAMPUS ROAD
FRIEDMAN
STRENGTH AND
CONDITIONING
2631A CORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
T-001
12675138
TITLE SHEET
FE DESIGN
JD
2631, 2631A
SEPTEMBER 18, 2020
BARTELS HALL FIRE ALARM REPLACEMENT
T-001 TITLE SHEET
ELECTRICAL
E-001 GENERAL NOTES AND SYMBOL LEGENDS
E-100 BUILDING 2631 EXISTING AND PHASE 2 BASEMENT FIRE ALARM PLAN
E-101 BUILDING 2631 AND 2631A EXISTING AND PHASE 2 FIRST FLOOR FIRE ALARM PLAN
E-102 BUILDING 2631 AND 2631A EXISTING AND PHASE 2 SECOND FLOOR FIRE ALARM PLAN
E-103 BUILDING 2631 EXISTING AND PHASE 2 THIRD FLOOR FIRE ALARM PLAN
E-200 BUILDING 2631 NEW FA SYSTEM BASEMENT PLAN AREA 1
E-201 BUILDING 2631 AND 2631A NEW FIRE ALARM SYSTEM FIRST FLOOR PLAN AREAS 2 & 3
E-202 BUILDING 2631 AND 2631A NEW FIRE ALARM SYSTEM SECOND FLOOR PLANS AREAS 3, 4 & 5
E-203 BUILDING 2631 NEW FIRE ALARM SYSTEM THIRD FLOOR PLAN AREAS 4, 5, & 6
E-301 DETAILS
E-401 RISER DIAGRAM
SITE LOCATION -BARTELS HALL & FRIEDMAN STRENGTH AND CONDITIONING
KEY PLAN -ALL FLOOR LEVELS IN 2631 & 2631A
AREA OF WORK
BUILDING CODE SUMMARY
APPLICABLE CODES
2020 (EXISTING) IBC (ADOPTED BY NEW YORK STATE)
PROJECT SUMMARY
THIS PROJECT IS TO REPLACE THE EXISTING FIRE ALARM SYSTEM. THE
WORK IS ALTERATION LEVEL 2.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:1B
CLASSIFICATION OF HAZARDS:NONE
HIGH-RISE BUILDING:NO
EXTINGUISHING REQUIREMENT:THE EXISTING BUILDING
IS SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:MIXED USE B/A-4
FIRST FLOOR 2631
AREA OF WORK
DRAWING INDEX
PROJECT SCOPE
PROVIDE NEW ADDRESSABLE VOICE FIRE ALARM SYSTEM AND ASSOCIATED RACEWAYS IN BARTELS HALL AND FRIEDMAN STRENGTH AND
CONDITIONING. REMOVE ALL OF THE EXISTING FIRE ALARM SYSTEM UPON ACCEPTANCE OF NEW FIRE ALARM SYSTEM.
GENERAL SYMBOLS LEGEND
EXTERIOR ELEVATION
1
1
1 1X-100
X-100
1
1
1 1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
#CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE#
DRAWING REVISION NOTE#
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
FIRST FLOOR 2631A
BARTELS HALL & FRIEDMAN STRENGTH AND CONDITIONING
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-001
12675138
GENERAL NOTES
AND SYMBOL
LEGENDS
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
ELECTRICAL SUBMITTAL SCHEDULE
MATERIAL
SCHEDULE/
SHOP
DWGS.
PRODUCT
DATA SAMPLES
INSPECTIONS
& TESTS O&M DATA WARRANTIES
FIRE ALARM CONTROL PANEL X X
MUX PAD X X
TRANSPONDER PANEL X X
LOCAL OPERATORS CENTER X X
GYM PAGING PANEL X X
BATTERY CABINET X X
POWER BOOSTER PANEL X X
TERMINAL CABINET X X
FIRE ALARM DEVICES (SEE E-401)X X
ELECTRICAL LEGEND
MOTOR
HARDWIRED EQUIPMENT CONNECTION
P-1A
12
HOMERUN TO PANEL P-1A, CIRCUIT #12. FED
FROM 20A -1P BREAKER IS INTENDED UNLESS
NOTED OTHERWISE. RUN GREEN WIRE GROUND
FOR ALL CIRCUITS. PROVIDE ONE GROUND PER
CIRCUIT.
EMERGENCY POWER OFF (EPO)
GROUND ROD ELECTRODE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH AFCI PROTECTION
QUAD RECEPTACLE
LINETYPES LEGEND
SPECIAL RECEPTACLE5-30R
PANELBOARD
JUNCTION BOX
B = INSTALLED IN BASEBOARD
TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT
SR = SURFACE RACEWAY
WP = WEATHERPROOF
AC = AIR CONDITIONER
X
DUPLEX RECEPTACLE:
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
J
SAFETY SWITCH (NON-FUSED)
SAFETY SWITCH (FUSED)
FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
BATTERY CABINET
WATER FLOW SWITCH
MUXPAD
REMOTE ANNUNCIATOR
D = DUCT SMOKE DETECTOR
R = RELAY BASE
BR = BEAM RECEIVER
BT = BEAM TRANSMITTER
SB = SOUNDER BASE
W = WALL MOUNTED
WP = WEATHER PROOF
SMOKE DETECTOR:
TAMPER SWITCH
AUDIBLE NOTIFICATION
APPLIANCE/VOICE/SPEAKER
FACP
BATT
MUX
FAA
NAC PANELNAC
MANUAL PULL STATIONF
S X
F = FIXED TEMPERATURE
R = RATE OF RISE
R/F = COMBINATION RISE/FIXED TEMPERATURE
HEAT DETECTOR:
H X
CARBON MONOXIDE DETECTORCO
F
XXcd
C
FS
S
XXcd
C
TS
ADDRESSABLE MONITOR MODULE
XXcd = CANDELA
C = CEILING
CLG = CEILING
WG = WIREGUARD
COMBO A/V NOTIFICATION APPLIANCE:
SPEAKER/ STROBE
XXcd = CANDELA
C = CEILING
VISUAL NOTIFICATION APPLIANCE:
SUPPRESSION SYSTEM
UNDERGROUND ELECTRICUE
UNDERGROUND LIGHTINGUL
OVERHEAD ELECTRICOE
TO BE PROVIDED
DEMOLITION / TO BE RELOCATED
EXISTING TO REMAIN
UNDERGROUND TELCOUC
GENERAL ELECTRICAL DEMOLITION NOTES
1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING
ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER
APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED.
REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED
OTHERWISE.
2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEW
WORK SHALL BE REUSED WHERE POSSIBLE.
3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTING
SYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWN
TO BE DEMOLISHED.
4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH
THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE
RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH
SURROUNDING MATERIALS, FINISHES, AND COLORS.
5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM
DEMOLITION NOT SPECIFIED TO BE INFILLED.
6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING
CONSTRUCTION.
1.0 PROVIDE NEW ADDRESSABLE FIRE ALARM CONTROL PANEL (FACP).
2.0 PROVIDE CLASS B FOR THE INITIATION CIRCUITS. CLASS A FOR THE
NOTIFICATION CIRCUITS.
3.0 PROVIDE NEW ADDRESSABLE INITIATING DEVICE IN ALL COMMON AREAS OF
BUILDING.
4.0 PROVIDE NEW NOTIFICATION APPLIANCES AS INDICATED.
5.0 PROVIDE MUXPAD INTERFACE WITH CORNELL UNIVERSITY CENTRAL
STATION.
6.0 REMOVE ALL OF THE EXISTING FIRE ALARM SYSTEM UPON ACCEPTANCE
OF NEW FIRE ALARM SYSTEM.
7.0 CHECK ALL SMOKE DETECTORS FOR LISTED SENSITIVITY AND TO
CLEAN/REPLACE THOSE DEVICES THAT DO NOT MEET THE LISTED SENSITIVITY
AT NO ADDITIONAL COST.
ELECTRICAL SCOPE OF WORK
1.0 THESE DRAWINGS ARE FOR CORNELL UNIVERSITY USE ONLY. CONTACT THE
CORNELL PROJECT MANAGER WITH ELECTRICAL QUESTIONS.
2.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT
ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY
CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS
SHALL BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION
BEFORE WORK PROCEEDS.
3.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING
AREAS FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE
OF WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS
FROM THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND
OPERABLE.
4.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR
FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE
MATERIAL PENETRATED.
5.0 PERFORM WORK IN ACCORDANCE WITH THE REQUIREMENT OF THE LATEST
PUBLICATIONS OF THE NEC, NEW YORK STATE UNIFORM FIRE PREVENTION AND
BUILDING CODE, NEW YORK STATE ENERGY CODE, AND LOCAL CODES
APPLICABLE TO THE PARTICULAR WORK.
6.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT
DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF
INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL
PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF THE
WORK.
7.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE
EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON
CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED
WITH ASSOCIATED PHASE CONDUCTORS.
8.0 PROVIDE A NEW TYPE WRITTEN DIRECTORY FOR EACH PANELBOARD. LABEL ALL
NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE
PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE
AND INVENTORY NUMBER. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH
CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-S667.
9.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
10.0 CONDUCTORS SHALL BE A MINIMUM 12AWG, STRANDED COPPER, 600VAC, 90
DEGREE C, TYPE THHN/THWN FOR DRY AREAS AND XHHW/THWN FOR WET
AREAS.
11.0 CONDUIT EXPANSION JOINTS SHALL BE INSTALLED AS PER NEC AND WHERE
BUILDING VIBRATION JOINTS EXIST.
12.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE
ELECTRICAL METALLIC TUBING (EMT) FOR THIS INSTALLATION, SURFACE
MOUNTED UNLESS NOTED OTHERWISE.
13.0 WIREMOLD RACEWAY SHALL BE A MINIMUM OF 700 WIREMOLD FOR INDIVIDUAL
DEVICES AND 2400 WIREMOLD OR LARGER FOR MULTIPLE CIRCUITS. WIREMOLD
SHALL BE COLOR "IVORY" .
14.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE
PANELBOARD. SIZE AS INDICATED.
15.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT
HANGERS FOR CONDUIT AS NEEDED.
16.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND
DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE
AND REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN
MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL
DEFICIENCIES ARE CORRECTED.
17.0 DISCREPANCIES BETWEEN THESE DRAWINGS AND ASSOCIATED SPECIFICATIONS
ARE TO BE BROUGHT TO THE ATTENTION OF FACILITIES ENGINEERING FOR
RESOLUTION.
GENERAL NOTES
3.0 SUBMITTALS:
A. GENERAL SUBMITTAL REQUIREMENTS:
1. SUBMITTALS SHALL BE APPROVED BY CORNELL UNIVERSITY'S
FACILITIES ENGINEERING AND ENVIRONMENTAL HEALTH AND SAFETY.
2. SHOP DRAWINGS SHALL BE PREPARED BY PERSONS WITH THE
FOLLOWING QUALIFICATIONS:
a. TRAINED AND CERTIFIED BY MANUFACTURER IN FIRE-ALARM
SYSTEM DESIGN.
b. NICET-CERTIFIED FIRE-ALARM TECHNICIAN, LEVEL Ill MINIMUM
OR LICENSED PROFESSIONAL
B. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED.
C. SHOP DRAWINGS: FOR FIRE-ALARM SYSTEM. INCLUDE PLANS, ELEVATIONS,
SECTIONS, DETAILS, AND ATTACHMENTS TO OTHER WORK.
1. SYSTEM RISER DIAGRAM WITH TYPICAL EQUIPMENT AND DEVICE
CONNECTION.
2. INCLUDE VOLTAGE DROP CALCULATIONS FOR NOTIFICATION
APPLIANCE CIRCUITS.
3. INCLUDE BATTERY-SIZE CALCULATIONS.
4. INCLUDE FLOOR PLANS TO INDICATE FINAL OUTLET LOCATIONS
SHOWING ADDRESS OF EACH ADDRESSABLE DEVICE. SHOW SIZE AND
ROUTE OF CABLE AND CONDUITS.
5. INCLUDE WIRE COLOR-CODING SCHEDULE.
4.0 SOFTWARE SERVICE AGREEMENT
A. COMPLY WITH UL 864.
B. TECHNICAL SUPPORT: BEGINNING WITH SUBSTANTIAL COMPLETION, PROVIDE
SOFTWARE SUPPORT FOR TWO YEARS. FREE RE-PROGRAMMINGS (2) OF
SYSTEM TO ENSURE ALL POINTS ARE ADDRESSED AS NEEDED PER CORNELL
ENVIRONMENTAL HEALTH & SAFETY (EH&S).
C. UPGRADE SERVICE: UPDATE SOFTWARE TO LATEST VERSION AT PROJECT
COMPLETION. INSTALL AND PROGRAM SOFTWARE UPGRADES THAT BECOME
AVAILABLE WITHIN TWO YEARS FROM DATE OF SUBSTANTIAL COMPLETION.
UPGRADING SOFTWARE SHALL INCLUDE OPERATING SYSTEM. UPGRADE
SHALL INCLUDE NEW OR REVISED LICENSES FOR USE OF SOFTWARE.
5.0 MANUFACTURERS
A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
PRODUCTS BY ONE OF THE FOLLOWING:
1.GAMEWELL FIRE CONTROL INSTRUMENTS, INC.; A HONEYWELL
COMPANY.
2. HONEYWELL/NOTIFIER
3.EDWARD SYSTEM TECHNOLOGIES (EST).
6.0 FIRE-ALARM CONTROL PANEL
A. GENERAL REQUIREMENTS FOR FIRE-ALARM CONTROL UNIT:
1. FIELD-PROGRAMMABLE, MICROPROCESSOR-BASED, MODULAR,
POWER-LIMITED DESIGN WITH ELECTRONIC MODULES, COMPLYING
WITH UL 864 AND LISTED AND LABELED BY AN NRTL.
2. ADDRESSABLE CONTROL CIRCUITS FOR OPERATION OF MECHANICAL
EQUIPMENT.
B. ALPHANUMERIC DISPLAY AND SYSTEM CONTROLS: ARRANGED FOR
INTERFACE BETWEEN HUMAN OPERATOR AT FIRE ALARM CONTROL
UNIT AND ADDRESSABLE SYSTEM COMPONENTS INCLUDING ANNUNCIATION
AND SUPERVISION. DISPLAY ALARM, SUPERVISORY, AND COMPONENT STATUS
MESSAGES AND THE PROGRAMMING AND CONTROL MENU.
1. ANNUNCIATOR AND DISPLAY: LIQUID CRYSTAL TYPE (1), (2), (3) LINE(S}
OF (40) (80) CHARACTERS TRUMMUM.
2. KEYPAD: ARRANGED TO PERMIT ENTRY AND EXECUTION OF
PROGRAMMING, DISPLAY, AND CONTROL COMMANDS AND TO INDICATE
CONTROL COMMANDS TO BE ENTERED INTO THE SYSTEM FOR
CONTROL OF SMOKE DETECTOR SENSITIVITY AND OTHER
PARAMETERS.
a. DESIGNATE KEY/ BUTTON FOR MONTHLY ALARM TESTING (ONLY
SENDS ALARM CONDITION TO CENTRAL CONSOLE).
3. INMATING DEVICE, NOTIFICATION APPLIANCE, AND SIGNALING LINE
CIRCUITS: NFPA 72.
a. INITIATING DEVICE CIRCUITS: STYLE D (CLASS A).
b. NOTIFICATION APPLIANCE CIRCUITS: STYLE Z (CLASS A).
ALTERNATING NOTIFICATION CIRCUITS ON SLEEPING LEVELS.
c. SIGNALING LINE CIRCUITS: STYLE D.
d. INSTALL NO MORE THAN 50 ADDRESSABLE DEVICES ON EACH
SIGNALING LINE CIRCUIT.
C. NOTIFICATION APPLIANCE CIRCUIT: OPERATION SHALL SOUND IN A TEMPORAL
3 PATTERN (FIRE) AND TEMPORAL 4 PATTERN FOR CO DETECTION.
D. TRANSMISSION TO REMOTE ALARM RECEIVING STATION: AUTOMATICALLY
TRANSMIT ALARM, SUPERVISORY, AND TROUBLE SIGNALS TO A REMOTE
ALARM STATION.
E. PRIMARY POWER: 24--VDC OBTAINED FROM 120-VAC SERVICE AND A POWER-
SUPPLY MODULE. INITIATING DEVICES, NOTIFICATION APPLIANCES, SIGNALING
LINES, TROUBLE SIGNALS, SHALL BE POWERED BY 24-VDC SOURCE.
1. ALARM CURRENT DRAW OF ENTIRE FIRE-ALARM SYSTEM SHALL NOT
EXCEED 80 PERCENT OF THE POWER SUPPLY MODULE RATING.
F. SECONDARY POWER: 24-VDC SUPPLY SYSTEM WITH BATTERIES, AUTOMATIC
BATTERY CHARGER, AND AUTOMATIC TRANSFER SWITCH.
1. BATTERIES: SEALED LEAD ACID.
G. INSTRUCTIONS: COMPUTER PRINTOUT OR TYPEWRITTEN INSTRUCTION CARD
MOUNTED BEHIND A PLASTIC OR GLASS OVER IN A STAINLESS-STEEL OR
ALUMINUM FRAME. INCLUDE INTERPRETATION AND DESCRIBE APPROPRIATE
RESPONSE FOR DISPLAYS AND SIGNALS. BRIEFLY DESCRIBE THE FUNCTIONAL
OPERATION OF THE SYSTEM UNDER NORMAL, ALARM, AND TROUBLE
CONDITIONS.
7.0 MANUAL FIRE-ALARM BOXES
A. GENERAL REQUIREMENTS FOR MANUAL FIRE-ALARM BOXES: COMPLY WITH UL
38. BOXES SHALL BE FINISHED IN RED WITH MOLDED, RAISED-LETTER
OPERATING INSTRUCTIONS IN CONTRASTING COLOR; SHOW VISIBLE
INDICATION OF OPERATION; AND SHALL BE MOUNTED ON RECESSED OUTLET
BOX. IF INDICATED AS SURFACE MOUNTED, PROVIDE MANUFACTURER'S
SURFACE BACK BOX.
1. DOUBLE-ACTION MECHANISM REQUIRING TWO ACTIONS TO INITIATE AN
ALARM, PULL-LEVER TYPE WITH INTEGRAL ADDRESSABLE MODULE
ARRANGED TO COMMUNICATE MANUAL-STATION STATUS (NORMAL,
ALARM, OR TROUBLE) TO FIRE-ALARM CONTROL UNIT.
2. STATION RESET: KEY OPERATED SWITCH.
8.0 SYSTEM SMOKE DETECTORS
A. GENERAL REQUIREMENTS FOR SYSTEM SMOKE DETECTORS:
1. COMPLY WITH UL 268; OPERATING AT 24--VDC, NOMINAL.
2. DETECTORS SHALL BE TWO-WIRE TYPE.
3. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE
DETECTOR STATUS (NORMAL, ALARM, OR TROUBLE) TO FIRE-ALARM
CONTROL UNIT.
4. BASE MOUNTING: DETECTOR AND ASSOCIATED ELECTRONIC
COMPONENTS SHALL BE MOUNTED IN A TWIST-LOCK MODULE THAT
CONNECTS TO A FIXED BASE. PROVIDE TERMINALS IN THE FIXED BASE
FOR CONNECTION TO BUILDING WIRING.
5. DETECTOR SHALL NOT BE MOUNTED WITHIN 3 FEET OF CEILING FAN
BLADE TIP, 3' AWAY FROM AIR DIFFUSER OR OUT OF DIRECT LINE OF
AIR FLOW.
B. PHOTOELECTRIC SMOKE DETECTORS:
1. DETECTOR ADDRESS SHALL BE ACCESSIBLE FROM FIRE-ALARM
CONTROL UNIT AND SHALL BE ABLE TO IDENTIFY THE DETECTOR'S
LOCATION WITHIN THE SYSTEM AND ITS SENSITIVITY SETTING.
2. AN OPERATOR AT FIRE-ALARM CONTROL UNIT, HAVING THE
DESIGNATED ACCESS LEVEL, SHALL BE ABLE TO MANUALLY ACCESS
THE FOLLOWING FOR EACH DETECTOR:
a. PRIMARY STATUS.
b. DEVICE TYPE.
c. PRESENT AVERAGE VALUE.
d. PRESENT SENSmVITY SELECTED.
e. SENSOR RANGE (NORMAL, DIRTY, ETC.).
SPECIFICATIONS CONT. FROM LOWER RIGHT
C. BEAM DETECTORS:
1. FIRERAY FFE M/N 5000-031 SERIES REFLECTIVE BEAM SMOKE
DETECTOR ADD-ON HEAD.
2. FIRERAY FFE M/N 5000-103 SERIES REFLECTIVE BEAM SMOKE
DETECTORS WITH GROUND LEVEL TEST STATION.
9.0 HEAT DETECTORS
A. GENERAL REQUIREMENTS FOR HEAT DETECTORS: COMPLY WITH UL 521.
B. HEAT DETECTOR, COMBINATION TYPE: ACTUATED BY EITHER A FIXED
TEMPERATURE OF 135 DEG F (57 DEG C) OR A RATE OF RISE THAT EXCEEDS 15
DEG F (8 DEG C) PER MINUTE UNLESS OTHERWISE INDICATED.
1. MOUNTING: ADAPTER PLATE FOR OUTLET BOX MOUNTING.
2. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE
DETECTOR STATUS (NORMAL, ALARM, OR TROUBLE) TO FIRE-ALARM
CONTROL UNIT.
C. HEAT DETECTOR, FIXED-TEMPERATURE TYPE: ACTUATED BY TEMPERATURE
THAT EXCEEDS A FIXED TEMPERATURE OF 190 DEG F (88 DEG C).
1. MOUNTING: ADAPTER PLATE FOR OUTLET BOX MOUNTING.
2. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE
DETECTOR STATUS (NORMAL, ALARM, OR TROUBLE) TO FIRE-ALARM
CONTROL UNIT.
10.0 NOTIFICATION APPLIANCES
A. GENERAL REQUIREMENTS FOR NOTIFICATION APPLIANCES: CONNECTED TO
NOTIFICATION APPLIANCE SIGNAL CIRCUITS, ZONED AS INDICATED, EQUIPPED
FOR MOUNTING AS INDICATED AND WITH SCREW TERMINALS FOR SYSTEM
CONNECTIONS.
1. COMBINATION DEVICES: FACTORY-INTEGRATED AUDIBLE AND VISIBLE
DEVICES IN A SINGLE-MOUNTING ASSEMBLY, EQUIPPED FOR MOUNTING
AS INDICATED AND WITH SCREW TERMINALS FOR SYSTEM
CONNECTIONS.
B. SPEAKER: ELECTRIC-VIBRATING-POLARIZED TYPE, 24-VDC; WITH PROVISION
FOR HOUSING THE OPERATING MECHANISM BEHIND A GRILLE. COMPLY WITH
UL 464. SPEAKER SHALL PRODUCE A SOUND-PRESSURE LEVEL OF 90 OBA,
MEASURED 10 FEET (3M) FROM THE SPEAKER, USING THE CODED SIGNAL
PRESCRIBED IN UL 464 TEST PROTOCOL.
C. VISIBLE NOTIFICATION APPLIANCES: XENON STROBE LIGHTS COMPLY WITH UL
1971, WITH CLEAR OR NOMINAL WHITE POLYCARBONATE LENS MOUNTED ON
AN ALUMINUM FACEPLATE. THE WORD "FIRE" IS ENGRAVED IN MINIMUM 1-INCH-
(25--MM--) HIGH LETTERS ON THE LENS.
1. RATED LIGHT OUTPUT:
a. 15/30/75/110 CD, SELECTABLE IN THE FIELD.
2. MOUNTING: WALL MOUNTED UNLESS OTHERWISE INDICATED.
3. FOR UNITS WITH GUARDS TO PREVENT PHYSICAL DAMAGE, LIGHT
OUTPUT RATINGS SHALL BE DETERMINED WITH GUARDS IN PLACE.
4. FLASHING SHALL BE IN A TEMPORAL PATTERN, SYNCHRONIZED WITH
OTHER UNITS.
5. STROBE LEADS: FACTORY CONNECTED TO SCREW TERMINALS.
6. MOUNTING FACEPLATE: FACTORY FINISHED RED.
7. STROBES SHOULD BE SYNCHRONIZED.
11.0 ADDRESSABLE INTERFACE DEVICE
A. DESCRIPTION: MICROELECTRONIC MONITOR MODULE, NRTL LISTED FOR USE
IN PROVIDING A SYSTEM ADDRESS FOR ALARM-INITIATING DEVICES FOR WIRED
APPLICATIONS WITH NORMALLY OPEN CONTACTS.
12.0 COMMUNICATION
A. TRANSMISSION OF ALARM, SUPERVISORY AND TROUBLE SIGNAL BY MUXPAD.
13.0 EQUIPMENT INSTALLATION
A. COMPLY WITH NFPA 72 AND CUDCS 283100 FOR INSTALLATION OF FIRE-ALARM
EQUIPMENT.
B. EQUIPMENT MOUNTING: INSTALL FIRE-ALARM CONTROL UNIT ON FINISHED
FLOOR WITH TOPS OF CABINETS NOT MORE THAN 72 INCHES (1830 MM) ABOVE
THE FINISHED FLOOR.
C. SMOKE-OR HEAT-DETECTOR SPACING:
1. COMPLY WITH NFPA 72, "SMOKE-SENSING FIRE DETECTORS" SECTION
IN THE "INITIATING DEVICES" CHAPTER, FOR SMOKE-DETECTOR
SPACING.
2. COMPLY WITH NFPA 72, "HEAT-SENSING FIRE DETECTORS" SECTION IN
THE "INITIATING DEVICES" CHAPTER, FOR HEAT-DETECTOR SPACING.
3. SMOOTH CEILING SPACING SHALL NOT EXCEED 30 FEET (9 M).
4. SPACING OF DETECTORS FOR IRREGULAR AREAS, FOR IRREGULAR
CEILING CONSTRUCTION, AND FOR HIGH CEILING AREAS SHALL BE
DETERMINED ACCORDING TO APPENDIX A IN NFPA 72.
D. COMBINATION NOTIFICATION DEVICES: FACTORY-INTEGRATED AUDIBLE AND
VISIBLE DEVICE: INSTALL NOT LESS THAN 6 INCHES (150 MM) BELOW THE
CEILING, AS REQUIRED PER NFPA 72, AND AS SPECIFIED ON THE DRAWINGS.
F. COMBINATION NOTIFICATION DEVICES NEED TO FOLLOW MOUNTING
REQUIREMENTS FOR VISUAL PORTION OF THE DEVICE.
14.0 IDENTIFICATION
A. PROVIDE LETTERED PLATES FOR THE FOLLOWING EQUIPMENT, COMPONENTS,
AND ACCESSORIES. THE PLATE SHALL CONTAIN THE EQUIPMENT
IDENTIFICATION (CUSTOM PANEL NUMBER, AREA SERVED) AS WELL AS POWER
CIRCUIT SOURCE AND BREAKER NUMBER. LABEL SHALL BE PLASTIC LAMICOID
ENGRAVED PLATED OR APPROVED EQUAL. (NOTE: ALL LETTERED PLATES
SHALL BE REVIEWED AND APPROVED BY CORNELL UNIVERSITY'S
ENVIRONMENTAL HEALTH AND SAFETY PRIOR TO INSTALLATION.)
1. FIRE ALARM CONTROL PANELS, REMOTE POWER SUPPLIES.
2. JUNCTION BOX COVER SHALL BE IN RED COLOR.
B. PROVIDE COMPUTER-GENERATED ADHESIVE LABELS AND INSTALL ON THE
BASES OF ALL INITIATING DEVICE AND NOTIFICATION APPLIANCES, AS WELL AS
ANY REMOTE TEST AND MONITORING STATIONS. THE LABEL SHALL INDICATE
THE ADDRESS AND MUST BE LEGIBLE FROM A STANDING POSITION BELOW.
1. LABELING GUIDELINE FOR SIGNALING LINE CIRCUIT (SLC):
FACPIBOARD -LOOPICCT # -DEVICE #.
2. LABELING GUIDELINE FOR NOTIFICATION APPLIANCE CIRCUIT (NAC):
FACPIBOARD -LOOP/CCR# -DEVICE# (WHERE ADDRESSABLE).
15.0 FIELD QUALITY CONTROL
A. A FIRE ALARM PROGRAM LIST TO BE PROVIDED TO EH&S FOR REVIEW AND
APPROVAL PRIOR TO RELEASE TO THE FIRE ALARM VENDOR. THIS EFFORT IS
TO ALLOW FOR THE FIRE ALARM DEVICE DESCRIPTORS AND ROOM NUMBERS
TO BE COORDINATED PRIOR TO ENTERING INTO THE FIRE ALARM PANEL, AS
WELL AS TO VERIFY THE PROGRAMMING AND OPERATIONAL SEQUENCE.
B. ACCEPTANCE TESTING:
1. PROVIDE MINIMUM (72) HOURS PRIOR NOTICE TO EH&S AND AHJ.
2. COMPLETE AND SUBMIT PROGRAM SHEETS TO EH&S.
3. ENSURE THAT THE SYSTEM IS PRE-TESTED.
4. CONTRACTOR TO PROVIDE ALL TESTING EQUIPMENT.
5. SMOKE DETECTORS SHALL BE TESTED BY SMOKE.
6. HEAT DETECTORS SHALL BE TESTED BY HEAT.
7. CO DETECTORS SHALL BE TESTED PER MANUFACTURES
RECOMMENDATIONS.
C. AS-BUILT DOCUMENTATION: REVISE RISER DIAGRAM, BASED ON ACTUAL
CONDITIONS, TO INDICATE ALL DEVICE CONNECTIONS AND LABELING AND
SETTINGS, EQUIPMENT LOCATIONS, COMMUNICATION CONNECTION, AND
POWER SOURCES.
1. COPIES OF AS BUILT DOCUMENTATION SHALL BE PROVIDED TO
PROJECT MANAGER, EH&S AND CORNELL UNIVERSITY FACILITIES
ENGINEERING.
SPECIFICATIONS CONT. FROM LOWER RIGHT
1.0 FIRE ALARM SYSTEM SHALL BE INSTALLED PER ALL APPLICABLE CODES (NYSBC,
FIRE CODE, NFPA 72 AND NEC) AND STANDARDS (CUDCS).
2.0 SYSTEM DESCRIPTION:
A. NON-CODED, ADDRESSABLE SYSTEM, WITH MULTIPLEXED SIGNAL
TRANSMISSION, DEDICATED TO FIRE-ALARM SERVICE ONLY.
SPECIFICATIONS
V
J XX SC = DOOR SELF-CLOSER/HOLDER
FS = FIRE SHUTTER
WG
WG = WIREGUARD
BEAM DETECTORBD
MOUNTING HEIGHTS
CARD READER 48" TOP OF BOX
LIGHT SWITCH 48" TOP OF BOX
RECEPTACLE 18" TOP OF BOX
DATA OUTLET 18" TOP OF BOX
TV OUTLET 84" TOP OF BOX
PHONE OUTLET 48" TOP OF BOX
SAFETY SWITCH 60" CENTERLINE OF HANDLE
MOTOR STARTER 60" CENTERLINE OF HANDLE
PANELBOARD 72" TOP OF PANELBOARD
MANUAL PULL STATION 48" OPERABLE HANDLE
NOTIFICATION APPLIANCE 80" BOTTOM OF LENS
DOOR HOLD OPEN COORDINATE IN FIELD
EM BATTERY UNIT 96" BOTTOM OF UNIT
EM REMOTE UNIT 102" BOTTOM OF UNIT
EXIT SIGN 96" BOTTOM OF UNIT
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
AMM
ADDRESSABLE OUTPUT MONITORAOM
TANDEM RELAY MODULEMR
UP
UPUP
UPUP
B16
B18
B20
B22
B24
B26
B28
B30
B32
B34
B36
B38
B0027
B0026
B0042
B17
B21
B23
B0028
B31
B33
B39
B0046
B0001B0066
B0063
B0053
B0065
B0040
B07
B07A
B0068
B0069
B0062
B0061
B06
B06A
B0052
B01
B01A
B0003 B0004
B0002
B0060
B46A
B46
B46C B46D
B51
B42
B47B
B47A
B49
B44
B40
B0055
B40A
B0056 B45
B41 B43
B46B
B47C
B47
B0064
B0054
B0031
B0030
B0051
B07B
B07C
B0021
B0022
B0023
B0025
B0024
B0020
B0067
B0029
B0020A
B0024A
B0063
B0053
B0065 B0062
B0061
B0052
B0002
B0060
B0064
B0054 B0051FS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
S
S
S
FFFFFFS
FF
F FFROLLING
DOOR
S S S H
H
ELEV.FF
E-100
1
F
WP
S
ELEV.
MECH.
F
S S
S
S S
FF
F
F
F
S
MAIN
ELECTRIC
ROOM
INDICATES EXISTING SPRINKLER
HEAD (TYPICAL ON DRAWING)
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWING)
ALL COMBO NOTIFICATION
APPLIANCES ARE
SPEAKER/STROBE DEVICES
TS TS
TS
TS
FS
FS
FS
FS
TS
EXISTING FIRE ALARM
CONTROL PANEL.
SEE PHOTO.
EXISTING VOICE EVACUATION
ALARM BOX. SEE PHOTO CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-100
12675138
BUILDING 2631
EXISTING AND
PHASE 2
BASEMENT FIRE
ALARM PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
0' 4' 8'16'
SCALE: 1/8"=1'-0"
SCALE:1/16" = 1'-0"2 FULL BASEMENT PLAN 0' 8' 16' 32'
SCALE: 1/16"=1'-0"
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
SCALE:1/8" = 1'-0"1 PARTIAL BASEMENT PLAN
ROOM B0064 -FIRE ALARM PANEL &
VOICE EVACUATION ALARM BOX
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
122A
122A
102
10065
10045 10021
10011
103B
103A
103
10060
10061
108
10022
10066
110
10047
112D
112C
112B
10067
112A
101
10043 10044
10003 1000410050
10012
10042 10041
10001 10002
112
10052
10040
1000810007
1000610005
10053
10051
10046
10062
DISPLAY CASECONCESSION STAND122
104 106
10064
10048
SEE BASEMENT
PLAN
10014
112E
112F
112G
UP
UPDN
UP
UP DN
DN
DN
DN UP DNUP
UP UP
UP
DN
UP
UP
UP UPUPUP10068
115A
115B
115
10054
10015
10014
UP
UP
1M12
DN
BUILDING 2631A FIRST FLOOR
LOCATION OF MEZZANINE
FF
S
S
S
F FFF
S
S
J
FS
J
FS
J
FS
J
FS
S
FIRE SHUTTER
TYPICAL
J
FIRE
SHUTTER
S
S
S
S
J
FIRE
SHUTTERFF
H
S
FSTS
H
FA TERMINAL BOX
S S S
S ELEV.
F F
S SFAA
EXISTING FA ANNUNCIATION
PANEL. SEE PHOTO.
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S S S
F
FF
F FF
F
F
SSSS
D
D
F
F
FJ
FIRE
SHUTTER FF
S
S
S
S FF
S
S
F FF
F F
WG
WG
F
WG
S
H
FS
TS
H
S
S
EXISTING SPRINKLER HEAD
(TYPICAL ON DRAWING)
WG
INDICATES EXISTING SPRINKLER
HEAD (TYPICAL ON DRAWING)
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWING)WG
WG
ALL COMBO NOTIFICATION
APPLIANCES ARE HORNS/STROBES
EXISTING VOICE EVACUATION
ALARM BOX
EXISTING VOICE EVACUATION
ALARM BOX
EXISTING VOICE EVACUATION
ALARM BOX
EXISTING FIRE DEPARTMENT
VOICE EVACUATION ALARM
BOX. TO BE REMOVED
(PHASE 2)
EXISTING KNOCK BOX
LYNAH RINK
1
ALL COMBO NOTIFICATION
APPLIANCES IN BARTELS ARE
SPEAKER/STROBE DEVICES CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-101
12675138
BUILDING 2631
AND 2631A
EXISTING AND
PHASE 2 FIRST
FLOOR FIRE
ALARM PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1/16" = 1'-0"1 1ST FLOOR
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
SCALE:1/8" = 1'-0"2 BUILDING 2631 MEZZANINE
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
0' 4' 8' 16'
SCALE: 1/8"=1'-0"
FA ANNUNCIATION PANEL
E-101 KEYED DEMOLITION NOTES
1 REMOVE EXISTING VOICE EVACUATION ALARM BOX AND ASSOCIATED DEVICES AND
WIRING COMPLETELY. PROVIDE A WHITE BLANK PLATE OVER EXISTING BACK BOX.
#
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
20011 20012
2001520016
20045 20047
20062 20067
20065 20066
20068
202 204 206 208 210 212
214
215
218
222 224 226
227
228 230 232
240
241
242244
213 217 219 221 223
20040
225 20060
20049 20048
243
2000620005
OPEN TO BELOW OPEN TO BELOW
10013
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
DN
DN DN
DN DN
DN
UPUP
DN
DN
DN
DN
UP
1M115A
1M115DN
DN
V V40'40'
40'40'
V V
40'
40'
40'
BD
BD
BD40'
40'BD
BD
BD
40'
FF
BEAM DETECTOR
TYPICAL
SSSSS
FS
FS
FSTS
TS
TS S
S
S
S
S
S
S
S
S
D
S
D
S D S
D
S
D
S
S
S S
S
S
S
S D S
D
S
S
D S D
S
H H
FFF FFF
FS TS
FS TSFF
FFFF
F
F
S D
S SHAFT
S ELEV.
S
F
SSS
F
CLG.F
CLG.
S
EXISTING SPRINKLER HEAD
(TYPICAL ON DRAWNG)
WALL
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWNG)
ALL COMBO NOTIFICATION
APPLIANCES ARE HORNS/STROBES
SPEAKER (TYPICAL)
ALL COMBO NOTIFICATION
IN BARTELS APPLIANCES ARE
SPEAKER/STROBE DEVICES
0' 8' 16' 32'
SCALE: 1/16"=1'-0"CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-102
12675138
BUILDING 2631
AND 2631A
EXISTING AND
PHASE 2
SECOND FLOOR
FIRE ALARM
PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1/16" = 1'-0"1 2ND FLOOR BUILDING 2631A MEZZANINE
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
3P0063
3P0062
3P0017
3P00153P0016
DN DN
UP
DN
ROOFFF
BD
BD
BD
BD
BD
BD
BEAM DETECTOR
TYPICAL
VVVV
VVVV
S WP
S WP
STAIR VENT
SHAFT VENT
SMOKE HATCH
TYPICAL
S WP
S WP
STAIR VENT
SHAFT VENT
S WP
S WP
HOISTWAY
SHAFT VENT
S
D S
D
S
D
S
D
S
D
H H FS
TSFF
S
D
S
D
S
D
S
D
H
H
FS TS
F
FBDBD
H H
INDICATES EXISTING SPRINKLER
HEAD (TYPICAL ON DRAWING)
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWNG)
SPEAKER (TYPICAL)
1
1
1
1 1
1
ALL COMBO NOTIFICATION
IN BARTELS APPLIANCES ARE
SPEAKER/STROBE DEVICES CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-103
12675138
BUILDING 2631
EXISTING AND
PHASE 2 THIRD
FLOOR FIRE
ALARM PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1/16" = 1'-0"1 3RD FLOOR
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
E-103 KEYED DEMOLITION NOTES
1 REMOVE EXISTING DETECTOR AND ASSOCIATED WIRING COMPLETELY BACK TO
SOURCE. MODIFY VENT TO BE OPERATED MANUALLY.
#
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
UP
UPUP
UPUP
B16
B18
B20
B22
B24
B26
B28
B30
B32
B34
B36
B38
B0027
B0026
B0042
B17
B21
B23
B0028
B31
B33
B39
B0046
B0001B0066
B0063
B0053
B0065
B0040
B07
B07A
B0068
B0069
B0062
B0061
B06
B06A
B0052
B01
B01A
B0003 B0004
B0002
B0060
B46A
B46
B46C B46D
B51
B42
B47B
B47A
B49
B44
B40
B0055
B40A
B0056 B45
B41 B43
B46B
B47C
B47
B0064
B0054
B0031
B0030
B0051
B07B
B07C
B0021
B0022
B0023
B0025
B0024
B0020
B0067
B0029
B0020A
B0024A
B0001
B0063
B0053
B0065 B0062
B0061
B0052
B0002
B0060
B0064
B0054 B0051FS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
S
S
S
FFFFFFS
FF
F FFROLLING
DOOR
S S S H
H
ELEV.FF
F
WP
S
ELEV.
MECH.
F
S S
S
S S
FF
F
F
F
S
MAIN
ELECTRIC
ROOM
INDICATES NEW FIRE ALARM
DEVICE (TYPICAL ON DRAWING)
E-200
1SSSSSSSSSSSSSSSSS
S
S
SS
S
S SS
S
SSSSS
PROGRAM THE ELEV. SMOKE DETECTOR TO OPERATE THE SMOKE
VENT IN THE SHAFT
S
S HHFF
S
ELEV.
MECH.B0065 -MAIN
ELECTRIC ROOM
TS TS
TS
TS
FS
FS
FS
FS
TS
PROPOSED LOCATION OF
NEW FA CONTROL PANEL
AND ASSOCIATED DEVICES.
SEE DRAWING E-301
SEE E-100 FOR EXISTING
FA CONTROL PANEL
1
MAIN SPRINKLER ROOM
22 CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-200
12675138
BUILDING 2631
NEW FA SYSTEM
BASEMENT PLAN
AREA 1
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. IN UTILITY SPACES, THE USE OF EMT AS SURFACE RACEWAY IS ACCEPTABLE. IN
FINISHED SPACES, PROVIDE IVORY WIREMOLD SURFACE RACEWAY. REFER TO
KEYED NOTES FOR DETAILS.
3. THIS DRAWING DOES NOT SHOW THE EXISTING SPRINKLER SYSTEM.
4. PROVIDE NEW FIRE ALARM DEVICES AS INDICATED ON DRAWING. NEW DEVICES
SHALL BE INSTALLED APPROXIMATELY CLOSE TO THE EXISTING FIRE ALARM
DEVICES (SEE EXISTING FA SYSTEM FLOOR PLAN FOR THE EXISTING FA DEVICES
LOCATIONS).
SCALE:1/16" = 1'-0"2 FULL BASEMENT PLAN NEW WORK AREA 1
SCALE:1/8" = 1'-0"1 PARTIAL BASEMENT PLAN NEW WORK
E-200 KEYED CONSTRUCTION NOTES
1 CIRCUIT TEMPER AND FLOW SWITCHES TO THE NEW VELOCITI SERIES MMI-10F
PANEL. SEE DRAWING E-301.
2 EXISTING FIRE PUMP SHALL BE MONITORED BY THE NEW FIRE ALARM CONTROL
PANEL. SEE E-301 FOR ADDITIONAL INFORMATION.
0' 4' 8' 16'
SCALE: 1/8"=1'-0"
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
#
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
122A
122A
102
10065
10045 10021
10011
103B
103A
103
10060
10061
108
10022
10066
110
10047
112D
112C
112B
10067
112A
101
10043 10044
10003 1000410050
10012
10042 10041
10001 10002
112
10052
10040
1000810007
1000610005
10053
10051
10046
10062
DISPLAY CASECONCESSION STAND122
104 106
10064
10048
SEE BASEMENT
PLAN
10014
112E
112F
112G
UP
UPDN
UP
UP DN
DN
DN
DN UP DNUP
UP UP
UP
DN
UP
UP
UP UPUPUP10068
115A
115B
115
10054
10015
10014
UP
UP
1M12
DN
BUILDING 2631A FIRST FLOOR
LOCATION OF MEZZANINE
FF
S
S
S
F FFF
S
S
J
FS
J
FS
J
FS
J
FS
S
FIRE SHUTTER
TYPICAL
J
FIRE
SHUTTER
S
S
S
S
J
FIRE
SHUTTERFF
S
S
FSTS
S
FA TERMINAL BOX
S S S
S ELEV.
F F
S SFAA
REPLACE FA ANNUNCIATION PANEL
S
S
S
S
S
S
S
S
S
S
S AC1(R)
S
S
S
S
S S S
F
FF
F FF
F
F
SSSS
D
D
F
F
FJ
FIRE
SHUTTER
F
S
S
S
S
F
S
S
F FF
F F
WG
WG
FWG
S
H
FS
TS
H
S AC1(S)
S
WG
INDICATES NEW FIRE ALARM
DEVICE (TYPICAL ON DRAWING)
WG
WG
ALL NEW COMBO NOTIFICATION
APPLIANCES ARE SPEAKER/STROBES
WGWG
WG
WG
ELECTRICAL ROOM ADD NEW FCI M/N
HPPFF12 NAC APPLIANCE POWER
BOOSTER PANEL & TERMINAL CABINET
M/N SSU00645, TC-2, 32 POINT CABINET
WG
WG
SSSS
EXISTING FIRE DEPARTMENT
VOICE EVACUATION ALARM
BOX. TO BE REMOVED
(PHASE 2)
EXISTING KNOCK BOX
ELECTRICAL ROOM ADD NEW FCI M/N
HPPFF12 NAC APPLIANCE POWER
BOOSTER PANEL & TERMINAL CABINET
M/N SSU00645, TC-2, 32 POINT CABINET
WG
WG
AREA 3AREA 2
AREA 3AREA 2
LYNAH RINK
1
1
1
1
CO
7
6
EXISTING VOICE EVACUATION
ALARM BOX TO BE REPLACED EXISTING VOICE EVACUATION
ALARM BOX TO BE REPLACED
2
2
1
6
3
4
1
EXISTING VOICE EVACUATION
ALARM BOX TO BE REPLACED
2
5
8
9
S S
SS SSSS CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-201
12675138
BUILDING 2631
AND 2631A NEW
FIRE ALARM
SYSTEM FIRST
FLOOR PLAN
AREAS 2 & 3
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
E-201 KEYED CONSTRUCTION NOTES
1 NOT IN CONTRACT. FIRE SHUTTER WORK SHALL NOT BE REQUIRED BY THIS
PROJECT.
2 SEE RISER DIAGRAM FOR WORK REQUIREMENT.
3 REPLACE EXISTING FIRE ALARM ANNUNCIATOR WITH A NEW LOCAL OPERATORS
CENTER. PROVIDE A CUSTOM BLANK PLATE OVER EXISTING BACK BOX. PAINT TO
MATCH EXISTING WALL COLOR. SEE DRAWING E-401 FOR ADDITIONAL
INFORMATION. CONTACT TIM MCGEE AT WFS FOR BLANK PLATE.
4 PROVIDE A CUSTOM MADE BLANK PLATE OVER EXISTING BOX. COLOR TO MATCH
EXISTING WALL.
5 PROVIDE NEW DUCT SMOKE DETECTOR WITH REMOTE TEST SWITCH. DETECTOR
TO REPORT TO FACP AS SUPERVISORY CONDITION ONLY. TYPICAL ON DRAWING,
SEE RISER DIAGRAM FOR TYPICAL WIRING REQUIREMENTS.
6 TAMPER SWITCH TO REPORT TO FACP AS SUPERVISORY CONDITION. FLOW SWITCH
TO REPORT AS ALARM CONDITION. SEE E-401 FOR ADDITIONAL INFORMATION.
7 CARBON MONOXIDE DETECTOR. REFER TO E-401 FOR ADDITIONAL INFORMATION.
8 FANS IN THIS ROOM WITH DUCT SMOKE DETECTORS ARE ABOVE 2000 CFM AND
SHALL REQUIRE FIRE ALARM SHUTDOWN.
9 PROGRAM ELEVATOR SMOKE DETECTOR TO OPERATE SMOKE VENT IN THE SHAFT.
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
SCALE:1/16" = 1'-0"1 1ST FLOOR NEW WORK
SCALE:1/8" = 1'-0"2 BUILDING 2631 MEZZANINE NEW WORK
0' 4' 8' 16'
SCALE: 1/8"=1'-0"
#
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. IN UTILITY SPACES, THE USE OF EMT AS SURFACE RACEWAY IS ACCEPTABLE. IN
FINISHED SPACES, PROVIDE IVORY WIREMOLD SURFACE RACEWAY. REFER TO
KEYED NOTES FOR DETAILS.
3. THIS DRAWING DOES NOT SHOW THE EXISTING SPRINKLER SYSTEM.
4. PROVIDE NEW FIRE ALARM DEVICES AS INDICATED ON DRAWING. NEW DEVICES
SHALL BE INSTALLED APPROXIMATELY CLOSE TO THE EXISTING FIRE ALARM
DEVICES (SEE EXISTING FA SYSTEM FLOOR PLAN FOR THE EXISTING FA DEVICES
LOCATIONS).
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
20011 20012
2001520016
20045 20047
20062 20067
20065 20066
20068
202 204 206 208 210 212
214
215
218
222 224 226
227
228 230 232
240
241
242244
213 217 219 221 223
20040
225 20060
20049 20048
243
2000620005
OPEN TO BELOW OPEN TO BELOW
10013
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
DN
DN DN
DN DN
DN
UPUP
DN
DN
DN
DN
UP
1M115A
1M115DN
DN
25'
40'
40'
40'
BD
40'
40'
40'
FF
BEAM DETECTOR
TYPICAL
SSSSS
FS
FS
FSTS
TS
TS S
S
S
S
S
S
S
S
S RF-2A
D
S HV-3
D
S D
HV-2
S RF-2
D
S RF-3
D
S
S
S S
S
S
S
S D
FC-1
S D
FC-2
S
S FC-3
D S D
FC-1
S
H H
FFF FFF
FS TS
FS TSFF
FFFF
F
F
S D
FC-4
S ELEV.
S
F
SSS
F
CLG.F
CLG.
S
WALL
INDICATES NEW FIRE ALARM
DEVICE (TYPICAL ON DRAWNG)
1
BD
BDBD
BD
BD
ALL NEW COMBO NOTIFICATION APPLIANCES
SHALL BE SPEAKER/STROBES
AREA 3AREA 4
AREA 3AREA 4
S
ELECTRICAL ROOM ADD NEW FCI M/N
HPPFF12 NAC APPLIANCE POWER
BOOSTER PANEL & TERMINAL CABINET
M/N SSU00645, TC-2, 32 POINT CABINET
ADD NEW FCI M/N HPPFF12 NAC
APPLIANCE POWER BOOSTER PANEL
& TERMINAL CABINET M/N SSU00645,
TC-2, 32 POINT CABINET
AREA 5
2
2 1
2 2
2 33
3
3
2
3
4
S SHAFT
5 VV25'
SPEAKER A
SPEAKER B CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-202
12675138
BUILDING 2631
AND 2631A NEW
FIRE ALARM
SYSTEM SECOND
FLOOR PLANS
AREAS 3, 4 & 5
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
E-202 KEYED CONSTRUCTION NOTES
1 TAMPER SWITCH TO REPORT TO FACP AS SUPERVISORY CONDITION. FLOW SWITCH
TO REPORT AS ALARM CONDITION. SEE E-401 FOR ADDITIONAL INFORMATION.
2 PROVIDE NEW DUCT SMOKE DETECTOR WITH REMOTE TEST SWITCH. DETECTOR
TO REPORT TO FACP AS SUPERVISORY CONDITION ONLY. TYPICAL ON DRAWING.
SEE RISER DIAGRAM FOR TYPICAL WIRING REQUIREMENTS.
3 FAN IS BELOW 2000 CFM AND SHALL NOT REQUIRED FIRE ALARM SHUTDOWN.
4 FANS IN THIS ROOM WITH DUCT SMOKE DETECTORS ARE ABOVE 2000 CFM AND
SHALL REQUIRE FIRE ALARM SHUTDOWN.
5 PROGRAM ELEVATOR SMOKE DETECTOR TO ALSO TO OPERATE THE SMOKE VENT
IN THE SHAFT.
SCALE:1/16" = 1'-0"1 2ND FLOOR NEW WORK
#
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
BUILDING 2631A MEZZANINE
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. IN UTILITY SPACES, THE USE OF EMT AS SURFACE RACEWAY IS ACCEPTABLE. IN
FINISHED SPACES, PROVIDE IVORY WIREMOLD SURFACE RACEWAY. REFER TO
KEYED NOTES FOR DETAILS.
3. THIS DRAWING DOES NOT SHOW THE EXISTING SPRINKLER SYSTEM.
4. PROVIDE NEW FIRE ALARM DEVICES AS INDICATED ON DRAWING. NEW DEVICES
SHALL BE INSTALLED APPROXIMATELY CLOSE TO THE EXISTING FIRE ALARM
DEVICES (SEE EXISTING FA SYSTEM FLOOR PLAN FOR THE EXISTING FA DEVICES
LOCATIONS).
S
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
F
3P0063
3P0062
3P0017
3P00153P0016
DN DN
UP
DN
ROOFFF
BEAM DETECTOR
TYPICAL
S HV-6(S)
D
S
HV-7(R)
S HV-3(S)
D
S HV-5(R)
D S HV-7(S)
D
H H FS
TSFF
S HV-1(R)
D
S D
HV-4(R)
S D
HV-1(S)
S HV-4(S)
D
H
H
FS TS
F
FH H
BD
BD
BD
BD
BD
BD
BD
BD
INDICATES NEW FIRE ALARM
DEVICE (TYPICAL ON DRAWING)
ADD NEW FCI M/N HPPFF12 NAC
APPLIANCE POWER BOOSTER PANEL
& TERMINAL CABINET M/N SSU00645,
TC-2, 32 POINT CABINET
AREA 5
AREA 6
AREA 4
1
2
D
1
2
3
3
V
SPEAKE A, MOUNT AT 30'
V
SPEAKE B, MOUNT AT 30'CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-203
12675138
BUILDING 2631
NEW FIRE ALARM
SYSTEM THIRD
FLOOR PLAN
AREAS 4, 5, & 6
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
E-203 KEYED CONSTRUCTION NOTES
1 TAMPER SWITCH TO REPORT TO FACP AS SUPERVISORY CONDITION. FLOW SWITCH
TO REPORT AS ALARM CONDITION. SEE E-401 FOR ADDITIONAL INFORMATION.
2 PROVIDE NEW DUCT SMOKE DETECTOR WITH REMOTE TEST SWITCH. DETECTOR
TO REPORT TO FACP AS SUPERVISORY CONDITION ONLY. TYPICAL ON DRAWING.
SEE RISER DIAGRAM FOR TYPICAL WIRING REQUIREMENTS.
3 FANS IN THIS ROOM WITH DUCT SMOKE DETECTORS ARE ABOVE 2000 CFM AND
SHALL REQUIRE FIRE ALARM SHUTDOWN.
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
SCALE:1/16" = 1'-0"1 3RD FLOOR NEW WORK
#
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. IN UTILITY SPACES, THE USE OF EMT AS SURFACE RACEWAY IS ACCEPTABLE. IN
FINISHED SPACES, PROVIDE IVORY WIREMOLD SURFACE RACEWAY. REFER TO
KEYED NOTES FOR DETAILS.
3. THIS DRAWING DOES NOT SHOW THE EXISTING SPRINKLER SYSTEM.
4. PROVIDE NEW FIRE ALARM DEVICES AS INDICATED ON DRAWING. NEW DEVICES
SHALL BE INSTALLED APPROXIMATELY CLOSE TO THE EXISTING FIRE ALARM
DEVICES (SEE EXISTING FA SYSTEM FLOOR PLAN FOR THE EXISTING FA DEVICES
LOCATIONS).
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
FIRE ALARM
CONTROL PANEL
BATTERY CABINET
GFCI E3 SERIES
AMPLIFICATION
TRANSPONDER PANEL
BATTERY CABINET
FCI M/N HPPFF12
NAC APPLIANCE
POWER BOOSTER
PANEL
5' - 8"
CIT EQUIPMENT
CIT PLYWOOD BOARD
6' - 0"7
7
5
4
9
4
2
1 10
11
3
7
6
PHONE CABLE BY CIT
1" EMT BY CONTRACTOR
SEE RISER
DIAGRAM
3' - 0"
AREA OF WORK
DOOR
CEILING
FLOOR
7
8
BATTERY CABINET
4
GFCI E3 SERIES
AMPLIFICATION
TRANSPONDER PANEL
7
7
5
TO SPEAKER A IN 101
TO SPEAKER B IN 101
TO COMMON SPEAKERS
TO COMMON SPEAKERS
SERVING
ADDITIONAL
COMMON
SPEAKERSVELOCITY
PANELTYPICAL TS & FS LOCATED IN RM. B0063
(1) PAIR OF 16 AWG TWISTED, NOT SHIELDED IN
3/4" EMT
(1) PAIR OF 16 AWG TWISTED, NOT SHIELDED IN
3/4" EMT
TSFS
(2) PAIRS OF 14 AWG TWISTED,
SHIELDED IN 3/4" EMT, TYPICAL
12
THE FIRE ALARM ARCHNET NETWORK CABLING RUNNING BETWEEN THE FIRE ALARM CONTROL PANEL,
TRANSPONDER, LOCAL OPERATORS CENTER, AND GYM PAGING PANELS, MUST BE INSTALLED AS NOTED IN A
DEDICATED RACEWAY AND MAY NOT BE INTERMINGLED WITH SLC INITIATION CIRCUITS OR SPEAKER CIRCUITS.
SPEAKER CIRCUIT CABLING MAY NOT BE INSTALLED IN THE SAME RACEWAY AS SLC INITIATING CIRCUIT WIRING.
MUXPAD
EXISTING
FIRE
PUMP
PANEL
13
7
7
14
TO SPEAKER B IN 112
TO SPEAKER A IN 112 CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-301
12675138
DETAILS
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1" = 1'-0"1 NEW FIRE ALARM EQUIPMENT ELEVATION VIEW RM B0065
E-301 KEYED CONSTRUCTION NOTES
1 NEW GFCI E3 SERIES FIRE ALARM CONTROL PANEL. "C" SIZE ENCLOSURE, 19-3/8" W
X 30"H X 4-1/2" D.
2 DIGITIZE M/N 425126-0031 MUXPAD II CONTROL PANEL. 13.25"W X 9.25'H X 3.5"D.
3 CIRCUIT TO THE EXISTING CIRCUIT BREAKER FEEDING THE EXISTING FIRE ALARM
CONTROL PANEL.
4 SSU00501 BATTERY CABINET, (2) FCI B-31R STANDBY BATTERIES. 22"W X 10"H X
8.81" D.
5 GFCI E3 SERIES AMPLIFICATION TRANSPONDER PANEL WITH GFCI M/N 1100-0460
ENCLOSURE. "B" SIZE ENCLOSURE, 19-3/8"W X 19-3/8"H X 4-1/2"D.
6 VELOCITI SERIES MMI-10F, MULTI-MOD TEN INPUT MONITOR MODULE IN MBB-2
ENCLOSURE. 12.25" X 9.25"W X 3.32"D (SERVING BASEMENT FLOW AND TAMPER
SWITCHES).
7 1" CONDUIT & CABLES BY CONTRACTOR. TERMINATION BY WEST FIRE SYSTEMS,
INC.
8 ADJACENT TO THE NEW FACP, PROVIDE A SURFACE MOUNT RECEPTACLE. CIRCUIT
THE RECEPTACLE TO THE SAME CIRCUIT FEEDING THE NEW FACP.
9 FCI M/N HPPFF12 NAC APPLIANCE POWER BOOSTER PANEL. 16.7"W X 19"H X 5.2"D.
PROVIDE 120V POWER CONNECTION. CIRCUIT TO THE SAME CIRCUIT FEEDING THE
NEW FACP.
10 INSIDE THE FACP, PROVIDE 120VAC SURGE SUPPRESSOR, SPACE AGE
ELECTRONICS INC. MODEL GFCI M/NE 120V-GT.
11 (1) 12 AWG (EARTH GROUND) IN 1" EMT TO NEAREST BUILDING STEEL.
12 THE PROJECT MANAGER TO HIRE CORNELL INFORMATION & TECHNOLOGIES (CIT)
TO PROVIDE A NEW TELEPHONE CABLE.
13 PROVIDE (3) AMM-2F TO MONITOR EXISTING FIRE PUMP. ONE TO MONITOR THE
PHASE REVERSAL, THE SECOND TO MONITOR RUNNING, THE THIRD TO MONITOR
POWER FAILURE. PROVIDE (1) PAIR OF 16 AWG TWISTED, NOT SHIELDED IN 3/4"
EMT RUNNING FROM THE THREE ADDRESSABLE MONITOR MODULES TO THE
EXISTING FIRE ALARM CONTROL PANEL.
14 TAMPER SWITCH TO REPORT TO FACP AS SUPERVISORY CONDITION. FLOW SWITCH
TO REPORT AS ALARM CONDITION.
#
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
FIRE ALARM
CONTROL PANEL
B0065
AREA 1
S FHSF
J J
GENERATOR
CONTROLLER
13 13
AREA 2
TERMINAL CABINET
10065
AREA 2
BOOSTER PANEL
10065 AREA 3
TERMINAL CABINET
10067
AREA 3
BOOSTER PANEL
10067
(1) PAIR OF 16 AWG. TWISTED, NOT
SHIELDED INITIATION CIRCUT, CLASS
B. TYP. FOR ALL INITIATION DEVICES
(2) PAIRS OF 14 AWG THHN
NOTIFICATION CIRCUIT,
CLASS A. TYP. FOR ALL
STROBE DEVICES
12
4
LOCAL OPERATORS
CENTER
10042
S F H F S
6 2
3 8 9
2
3 8 9
1414
BASEMENT
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
7
10
5 5
AREA 4
TERMINAL CABINET
20065
AREA 4
BOOSTER PANEL
20065
2
3 8 9
14
5
AREA 5
TERMINAL CABINET
200682
10
AREA 5
BOOSTER PANEL
20068
3 8 9
14
AREA 6
TERMINAL CABINET
3P0062
AREA 6
BOOSTER PANEL
3P0062
2
3 8 9
14
5
11
1
12
12
12
12
12
5
12
12
GYM PAGING
PANEL
101 WEST
GYM PAGING
PANEL
112
(1) PAIR 14 TWISTED FOR
CLASS A NETWORK IN 1" EMT
(1) PAIR 14 THHN FOR 24 VDC
POWER IN 1" EMT
(1) PAIR 14 TWISTED FOR
CLASS A NETWORK IN 1" EMT
(1) PAIR 14 THHN FOR 24 VDC
POWER IN 1" EMT
(1) PAIR 14 TWISTED FOR
CLASS A NETWORK RETURN
IN 1" EMT
COAMM-2F
(1) PAIRS OF 14 AWG THHN 24
VDC FOR DETECTION POWER
(1) PAIR OF 16 AWG. THHN
INITIATION CIRCUT, CLASS B
COMMON PATH WAY W/ (2)
PAIRS OF 14 AWG TWISTED,
SHIELDED SPEAKERS
CIRCUIT, CLASS A. IN 3/4" EMT
(2) PAIRS OF 14 AWG THHN
NOTIFICATION CIRCUIT,
CLASS A. TYP. FOR STROBE
DEVICE
S FHSF
(1) 14 AWG THHN GROUND IN 3/4" EMT
GYM PAGING
PANEL
101 EAST
(1) PAIR 14 TWISTED FOR
CLASS A NETWORK IN 1" EMT
(1) PAIR 14 THHN FOR 24 VDC
POWER IN 1" EMT
COMMON PATH WAY W/ (12)
PAIRS OF 14 AWG TWISTED,
SHIELDED SPEAKERS
CIRCUIT, CLASS A. IN 3/4" EMT
COMMON PATH WAY W/ (8)
PAIRS OF 14 AWG TWISTED,
SHIELDED SPEAKERS
CIRCUIT, CLASS A. IN 3/4" EMT
COMMON PATH WAY W/ (4) PAIRS OF 14
AWG TWISTED, SHIELDED SPEAKERS
CIRCUIT, CLASS A. IN 3/4" EMT
S FHSF
S FHSF
S FHSF
S F H F S
S F H F S
15JJ
TS
FS
10066
10066
15JJ
TS
FS
10065
10065
VELOCITI
PANEL
5
TSFSFSFS TS TS
20066
(1) PAIR OF 16 AWG. TWISTED, NOT
SHIELDED INITIATION CIRCUT, CLASS
B.
15
J J
TS
FS 3P0062
3P0062
VELOCITI
PANELFSFSTSTS
20048
(1) PAIR OF 16 AWG. TWISTED, NOT
SHIELDED INITIATION CIRCUT, CLASS B.
5
10
FS TS
3P0063
(1) PAIR OF 16 AWG.
TWISTED, NOT SHIELDED
INITIATION CIRCUT, CLASS B.
COMMON PATH WAY W/ (2)
PAIRS OF 14 AWG TWISTED,
SHIELDED SPEAKERS
CIRCUIT, CLASS A. IN 3/4" EMT
COMMON PATH WAY W/ (2)
PAIRS OF 14 AWG TWISTED,
SHIELDED SPEAKERS
CIRCUIT, CLASS A. IN 3/4" EMT
BD
BD
TYP. IN
GYM 101 (1) PAIR OF 16 AWG. TWISTED, NOT
SHIELDED INITIATION CIRCUT, CLASS
B.
S D
AOM MR
FAN
(1) PAIR OF 16 AWG. TWISTED, NOT
SHIELDED INITIATION CIRCUT, CLASS
B. TYPICAL
(1) PAIRS OF 16 AWG
TWISTED UNSHIELDED SLC
CIRCUIT. TYPICAL
(2) PAIRS OF 14 AWG THHN
FOR SUPERVISED
CONNECTION/SAFETY
CONNECTION. TYPICAL
S D
AOM MR
FAN
S D
AOM MR
FAN
S D
AOM MR
FAN
S D
AOM MR
FAN
(1) 14 AWG THHN GROUND
IN 3/4" EMT
(1) 14 AWG THHN GROUND
IN 3/4" EMT
(1) PAIRS OF 14 AWG THHN 24
VDC FOR POWER
16
17
17 17
17
17
18 CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-401
12675138
RISER DIAGRAM
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1" = 1'-0"1 RISER DIAGRAM
E-401 KEYED CONSTRUCTION NOTES
1 REFER TO DRAWING E-301 FOR ADDITIONAL INFORMATION.
2 FIRE ALARM TERMINAL CABINET. M/N SSU00645, TC-2, 32 POINT CABINET. 14”W X
14”H X 3.5”D.
3 FCI M/N HPPFF12, NAC APPLIANCE POWER BOOSTER PANEL. 16.7W X 19”H X 5.2D.
4 (5) PAIRS OF 16 AWG TWISTED, NOT SHIELED ADDRESSABLE CIRCUITS. (1) PAIR OF
14 AWG THHN, FOR ANNUNCIATOR POWER. (2) PAIRS OF 14 TWISTED, NOT
SHIELDED FOR ANNUNCIATOR DATA. 1 1/2” EMT.
5 1” EMT & CABLES BY THE CONTRACTOR. TERMINATION BY WEST FIRE SYSTEMS,
INC.
6 ENTRY LOBBY LOCAL OPERATORS CENTER (LOC.) GAMEWELL FCI E3 SERIES LOC.
FCI E3BB-BAA CABINET WITH FCI E3ID3-A INNER DOOR ASSEMBLY. 19.25”W X 10”H X
3.D.
7 (1) PAIR OF 14 AWG THHN FOR 24 VDC POWER AND (2) SEPERATE PAIRS OF 14
TWISTED FOR NETWORK IN/OUT & (1) 14 AWG THHN GROUNG IN 1” EMT. SURFACE
RACEWAY ON WALL SHALL BE WM2400.
8 CIRCUIT POWER BOOSTER PANEL TO NEAREST 120V RECEPTACLE CIRCUITRY.
9 INSIDE OF PANEL, PROVIDE 120V AC SURGE SUPPRESSOR, SPACE AGE
ELECTRONICS INC. MODEL GFCI M/N E120V-GT.
10 (1) PAIR OF 16 AWG TWISTED, NOT SHIELDED, ADDRESSABLE CIRCUITS.
11 (3) PAIRS OF 16 AWG TWISTED, NOT SHIELDED, ADDRESSABLE CIRCUITS.
12 1” EMT COMMON PATHWAY WITH (1) PAIR OF 16 AWG TWISTED, NOT SHIELDED
(INITIATION CIRCUIT, CLASS B). (2) PAIRS OF 14 AWG THHN (STROBE CIRCUITS,
CLASS A). SURFACE RACEWAY TO A TYPICAL FA DEVICE SHALL BE WM700.
13 IN THE VICINITY OF THE CONTROLLER, PROVIDE A 4” X 4” J-BOX. INSIDE OF BOX,
PROVIDE (1) FCI AMM-2IF MODULE TO MONITOR THE GENERATOR.
14 (1) 12 AWG (EARTH GROUND) IN 1” EMT TO NEAREST BUILDING STEEL.
15 AMM-2F IN A 4"x4" J-BOX SERVING TS OR FS. PROVIDE (1) PAIR OF 16 AWG TWISTED,
NOT SHIELDED INITIATION CIRCUIT TO THE DEVICE.
16 ALSO TO PROVIDE (1) PAIR 14 AWG THHN FOR 24 VDC POWER TO THE GROUND
LEVEL TEST STATION & (1) PAIR 16 AWG TWISTED UNSHIELDED INITIATING CIRCUIT
TO AN AMM-2IF MODULE WHICH WILL BE INSTALLED ADJACENT TO THE GROUND
LEVEL TEST STATION.
17 TAMPER SWITCH TO REPORT TO FACP AS SUPERVISORY CONDITION. FLOW SWITCH
TO REPORT AS ALARM CONDITION.
18 CARBON MONOXIDE DETECTOR TO REPORT AS SUPERVISORY CONDITION WITH
LOCAL SOUNDER AND DOES NOT REQUIRE THE FIRE ALARM SYSTEM TO
ANNUNCIATE THE TEMPORAL 4 CODE.
#
MATERIAL LIST
• GFCI M/N ASD-PL3 ANALOG SMOKE SENSOR HEAD WITH M/N B300-6 FLANGED
BASE
• GFCI M/N ATD-L3 ANALOG 135-DEGREE FT HEAT SENSOR HEAD WITH M/N B300-6
FLANGED BASE
• GFCI M/N MS-7AF ANALOG DOUBLE ACTION MANUAL PULL STATION
• GFCI M/N DNR ANALOG DUCT SMOKE DETECTOR COMPLETE WITH REMOTE
TEST STATION, SENSOR HEAD, AND AIR SAMPLING TUBE
• GFCI M/N AOM-2RF/MR-101C ANALOG OUTPUT CONTROL & TANDEM RELAY
MODULE
• GFCI M/N AMM-2F ANALOG SINGLE INPUT SUPERVISION MODULE
• GFCI M/N SPSRL WALL MOUNTED 70VRMS COMBINATION SPEAKER/STROBE
APPLIANCE
• GFCI M/N SPRL WALL MOUNTED 70VRMS STAND ALONE SPEAKER APPLIANCE
• GFCI M/N SPSCRL CEILING MOUNTED 70VRMS COMBINATION SPEAKER/STROBE
APPLIANCE
• GFCI M/N SRL WALL MOUNTED STANDALONE STROBE APPLIANCE
• GFCI M/N SPSRK WALL MOUNTED WEATHERPROOF 70VRMS COMBINATION
SPEAKER/STROBE APPLIANCE W/BACK BOX
• FFE M/N 5000-103 SERIES REFLECTIVE BEAM SMOKE DETECTOR WITH GROUND
LEVEL TEST STATION
• FFE M/N 5000-031 SERIES REFLECTIVE BEAM SMOKE DETECTOR ADD-ON HEAD.
• GFCI M/N CO1224 CARBON MONOXIDE DETECTOR.
• GFCI GYMNASIUM PAGING PANEL (VOICE EVACUATION ALARM BOX)
• FOR GYM 101 & 112, PROVIDE HYPERSPIKE TCPA-10 SPEAKERS.
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION